FSS2021-0289ADDITIONAL SITES CHRONOLOGY CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES EMAIL TO CONTRACTOR: World Fire Protection, While at the location of the above mentioned project for a scheduled Fire Alarm function test, an employee (Eddie) for World Fire was observed installing thread-rod and Sammy Express hangers to the fire sprinkler system. Upon casual questioning it was made clear that Eddie was by himself and does not have a valid Office of the State Fire Marshal Sprinkler Fitter Certification at any classification level. This alone is a violation of state law requiring that anyone performing work on a NFPA 13 or NFPA 13R system to have appropriate certification. Previous conversations with Blake of World Fire Protection showed that the company was familiar with this requirement. Therefore, this email is your only warning. Description: EXTRA SPACE STORAGE / FIRE SPRINKLER Type: FIRE SPRINKLER (WEB)Subtype: COMMERCIAL/INDUSTRIAL Status: FINALED Applied: 12/20/2021 ECON Parcel No: 600390011 Site Address: 79120 CORPORATE CENTER DR LA QUINTA,CA 92253 Approved: 2/20/2022 KHET Subdivision: PM 29351 Block: Lot: 1 Issued: 3/11/2022 AHI Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 4/14/2022 KHET Valuation: $38,000.00 Occupancy Type: Construction Type: Expired: No. Buildings: 0 No. Stories: 0 No. Unites: 0 Details: NFPA 13 SYSTEM IN EXTRA SPACE STORAGE Printed: Friday, March 03, 2023 1:30:19 PM 1 of 5 Permit Details City of La Quinta PERMIT NUMBER FSS2021-0289 E-MAIL KOHL HETRICK 4/4/2022 4/4/2022 Continued non-compliance with the requirements outlined in CCR Title 19, Chapter 5.5 will result in reporting of such directly to CSLB and the OSFM as well as Administrative Citations. This observation during the Fire Alarm inspection caused me to take a closer look at the fire sprinkler installation and I soon began to develop additional concerns. I understand that the installation Overhead Rough/Hydro was approved on 3/24/2022 by FSI Lucero with the following notes: “032422 - Approved OH Rough/2 HR Hydro - items to check at final: Unit L330 - Sprinkler head at rear leaking. Unit L283 all the way West were missing a sammy express hanger. Unit L120 - check deflector for paint.” Unfortunately, there were some additional details that were not observed and are required to be addressed. Please review the attached document for a marked plan set identifying missing details that require correction. As-builts should also be provided as cross-main alignment changes were observed. In addition to these notes, it was observed that NONE of the cutout coupons were affixed to the mechanical fittings as a common and preferred practice for showing that they were safely retrieved. There is no way of knowing that all cutouts were retrieved at this point. This is of great concern as these cutouts, if not all are retrieved, could cause a system restriction or blockage. In similar situations in the past, it had been required for the fire sprinkler contractor to make arrangements to flush out the entire system at reasonable velocities so as to collect in gunny sacks at discharge points, any un-retrieved cutout. NFPA 13 Contractor Material and Test Certificate only requires that “you certify that you have a control feature to ensure that all cutouts (discs) are retrieved.” Please let me know if you have any further questions. Printed: Friday, March 03, 2023 1:30:19 PM 2 of 5 Permit Details City of La Quinta PERMIT NUMBER FSS2021-0289 CONTACTS NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL APPLICANT WORLD FIRE PROTECTION INC 41-905 BOARDWALK STE B PALM DESERT CA 92211 (760)565-6030 bchapman@worldfirep rotection.com CONTRACTOR WORLD FIRE PROTECTION INC 41-905 BOARDWALK STE B PALM DESERT CA 92211 (760)565-6030 bchapman@worldfirep rotection.com OWNER EXTRA SPACE PROP 126 PO BOX 800729 DALLAS TX 75380 (760)565-6030 KOHL HETRICK CONDITIONS FINANCIAL INFORMATION DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD BY FIRE SPRINKLER SYSTEMS COMMERCIAL/INDUSTR IAL 101-0000-42421 0 $240.00 $240.00 3/11/22 R69462 INVOICE 1630 CREDIT WORLD FIRE PROTECTION INC AHI FIRE SPRINKLER SYSTEMS COMMERCIAL/INDUSTR IAL PC 101-0000-42420 0 $667.00 $667.00 3/11/22 R69462 INVOICE 1630 CREDIT WORLD FIRE PROTECTION INC AHI Total Paid for FIRE FEES: $907.00 $907.00 RECORDS MANAGEMENT FEE 101-0000-42416 0 $11.00 $11.00 3/11/22 R69462 INVOICE 1630 CREDIT WORLD FIRE PROTECTION INC AHI Total Paid for RECORDS MANAGEMENT FEE: $11.00 $11.00 TECHNOLOGY ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 3/11/22 R69462 INVOICE 1630 CREDIT WORLD FIRE PROTECTION INC AHI Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00 TOTALS:$923.00 $923.00 Printed: Friday, March 03, 2023 1:30:19 PM 3 of 5 Permit Details City of La Quinta PERMIT NUMBER FSS2021-0289 ATTACHMENTS Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED DOC 12/20/2021 Etrakit Contractor 1ST SUBMITTAL - PLAN SET EXTRA SPACE UG SITE FS-1-merged (1).pdf 1 BOND INFORMATION INSPECTIONS SEQID INSPECTION TYPE INSPECTOR SCHEDULED DATE COMPLETED DATE RESULT REMARKS NOTES OVERHEAD ROUGH PIPING LIN 3/24/2022 3/24/2022 APPROVED W/EXCEPTIO N SEE NOTES 032422 - Approved OH Rough/2 HR Hydro - items to check at final: Unit L330 - Sprinkler head at rear leaking. Unit L283 all the way West were missing a sammy express hanger. Unit L120 - check deflector for paint. OVERHEAD HYRO LIN 3/24/2022 3/24/2022 APPROVED FIRE FINAL**KHET 4/6/2022 4/6/2022 CANCELED DAVID ALFORD REQUESTED TO CANCEL AS WORLD FIRE PROTECTION IS NOT READY. FIRE FINAL**KHET 4/7/2022 4/14/2022 APPROVED RECEIVED CERT OF COMP REVIEWS REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED DATE STATUS REMARKS NOTES 1ST FIRE - ETRAKIT (2 WK) KOHL HETRICK 12/20/2021 1/7/2022 1/7/2022 REVISIONS REQUIRED SEE ATTACHMENTS SEE PLAN COMMENTS - NO LETTER PROVIDED 1ST PERMIT TECH – ETRAKIT (1 DAY) ARMANDO MAGALLON 12/20/2021 12/21/2021 12/20/2021 COMPLETE 2ND FIRE (1 WK)KOHL HETRICK 2/2/2022 2/9/2022 2/18/2022 REVISIONS REQUIRED SEE ATTACHMENTS EMAILED APPLICANT. WILL TRY TO RUSH 3RD REVIEW UPON RECEIPT. 3RD FIRE (1 WK)KOHL HETRICK 2/18/2022 2/25/2022 2/20/2022 APPROVED SEE ATTACHMENTS PARENT PROJECTS Printed: Friday, March 03, 2023 1:30:19 PM 4 of 5 Permit Details City of La Quinta PERMIT NUMBER FSS2021-0289 ATTACHMENTS Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED DOC 12/20/2021 Etrakit Contractor 1ST SUBMITTAL - FIRE FLOW FIRE FLOW ESS LA QUINTA.pdf 1 DOC 12/20/2021 Etrakit Contractor 1ST SUBMITTAL - CALCS HASS88_EXTRASS1.pdf 1 DOC 12/20/2021 Etrakit Contractor 1ST SUBMITTAL - CUT SHEETS Material Cut Sheets- merged.pdf 1 DOC 2/2/2022 Etrakit Contractor ESS CORRECTION LETTER REV1.pdf 1 DOC 2/2/2022 Etrakit Contractor EXTRA SPACE REV1 merged.pdf 1 DOC 2/2/2022 Etrakit Contractor HASS88_EXTRASS1R 2-2 -22.pdf 1 DOC 2/18/2022 Etrakit Contractor Rev 2 Plans EXTRA SPACE REV2 - merged (1).pdf 1 DOC 1/7/2022 KOHL HETRICK FSS2021-0289 - 1ST REVIEW - PLAN CORRECTIONS.pdf FSS2021-0289 - 1ST REVIEW - PLAN CORRECTIONS.pdf 1 DOC 2/18/2022 KOHL HETRICK FSS2021-0289 - 2ND PC - CORRECTIONS.pdf FSS2021-0289 - 2ND PC - CORRECTIONS.pdf 1 DOC 2/20/2022 KOHL HETRICK FSS2021-0289 - COA AND JOB CARD.pdf FSS2021-0289 - COA AND JOB CARD.pdf 1 DOC 2/20/2022 KOHL HETRICK FSS2021-0289 - APPROVED PLANS AND CALCS.pdf FSS2021-0289 - APPROVED PLANS AND CALCS.pdf 1 DOC 4/4/2022 KOHL HETRICK 4-4-2022 - OFM EMAIL TO WORLD FIRE.pdf 4-4-2022 - OFM EMAIL TO WORLD FIRE.pdf 1 DOC 4/4/2022 KOHL HETRICK FSS2021-0289 - KH Inspection Notes.pdf FSS2021-0289 - KH Inspection Notes.pdf 1 DOC 4/21/2022 KOHL HETRICK FSS2021-0289 - CERT OF COMPLETION.pdf FSS2021-0289 - CERT OF COMPLETION.pdf 1 Printed: Friday, March 03, 2023 1:30:19 PM 5 of 5 Permit Details City of La Quinta PERMIT NUMBER FSS2021-0289 WORLD FIRE PROTECTION INC. 41905 BOARDWALK, SUITE B PALM DESERT, CA. 92211 760/ 800-3182 EXTRA SPACE STORAGE - BLDG L 79120 CORPORATE CENTER DR. LA QUINTA, CA. 92253 DRAWING NUMBER: FS-2 DATE: 2-2-22 -DESIGN DATA- REMOTE AREA NUMBER: 1 REMOTE AREA LOCATION: MOST REMOTE OCCUPANCY CLASSIFICATION: ORDINARY HAZARD 2 DENSITY: .20 gpm/sq. ft. AREA OF APPLICATION: 1578 sq. ft. COVERAGE PER SPRINKLER: 130 sq. ft. TYPE OF SPRINKLERS CALCULATED: VIKING K=5.6 NUMBER OF SPRINKLERS CALCULATED: 24 SPRINKLERS HOSE-STREAM DEMAND: 250 gpm TOTAL WATER REQUIRED (INCLUDING HOSE): 953.4 gpm FLOW AND PRESSURE (AT BASE OF RISER): 703.4 gpm @ 60.9 psi TYPE OF SYSTEM: LOOPED WATER SUPPLY Source: FIRE HYDRANT Test Date: 9-25-20 Test By: CVWD Location: ADAMS ST. / CORPORATE CENTER DR. Static: 89.2 psi Residual: 73.46 psi Flow: 3600 gpm Source Elevation Relative to Finished Flow Level: 0-0 ft. INSTALLING CONTRACTOR Name: WORLD FIRE PROTECTION INC. Address: 41905 BOARDWALK, SUITE B, PALM DESERT, CA. 92211 Phone: 760/ 800-3182 Certification number: C-16# 1049720 NAME OF DESIGNER: ED / LUIS AUTHORITY HAVING JURISDICTION: CITY OF LA QUINTA / S.B. CO. COMMENTS: WATERFLOW WAS REDUCED BY 10% BEFORE CALCULATIONS PERFORMED. AVAIL. @ SRC = 79.07 PSI @ 953.4 GPM 69.67 PSI REQUIRED @ SOURCE SYSTEM IS 21% BELOW CURVE (-19.53 PSI) Calculations performed by HASS under license granted by HRS SYST., INC. SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 6/1/2020 C:\PROGRAM FILES\HRS SYSTEMS\HASS88\EXTRASS1R.SDF JOB TITLE: ESS 79120 CORPORATE CENTER DR. BLDG L - .20/1578 REV1 WATER SUPPLY ANALYSIS Static: 80.28 psi Resid: 66.11 psi Flow: 3600.0 gpm -14.7 0.0 20.0 40.0 60.0 80.0 100.0 80012001600 2000 2400 2800 3200 3600 4000 FLOW (GPM) Note: (1) Dashed Lines indicate extrapolated values from Test Results G A U G E P R E S S U R E ( p s i ) A 1 2 B LEGEND 1 Available pressure 79.07 psi @ 953.3 gpm 2 Required pressure 69.67 psi @ 953.3 gpm A. Source Supply Curve B. System Demand Curve SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 6/1/2020 C:\PROGRAM FILES\HRS SYSTEMS\HASS88\EXTRASS1R.SDF JOB TITLE: ESS 79120 CORPORATE CENTER DR. BLDG L - .20/1578 REV1 NFPA WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) SRC 80.3 66.1 3600.0 79.1 953.3 69.7 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 953.3 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM OTHER HOSE STREAM ALLOWANCES 250.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 703.3 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES (FT) (PSI) (GPM) 1 12.8 K= 5.60 30.9 31.1 2 12.8 K= 5.60 26.2 28.7 3 12.8 K= 5.60 26.5 28.8 4 12.8 K= 5.60 27.6 29.4 5 11.5 K= 5.60 36.9 34.0 6 12.8 K= 5.60 22.7 26.7 7 12.8 K= 5.60 24.6 27.8 8 11.5 K= 5.60 36.8 34.0 9 12.8 K= 5.60 23.0 26.9 10 12.8 K= 5.60 25.0 28.0 11 11.5 K= 5.60 36.7 33.9 12 12.8 K= 5.60 23.0 26.9 13 12.8 K= 5.60 25.0 28.0 14 12.8 K= 5.60 22.3 26.4 15 12.8 K= 5.60 21.6 26.0 15A 12.8 - - - - 22.8 - - - 16 12.8 K= 5.60 25.5 28.3 17 12.8 K= 5.60 26.1 28.6 17A 12.8 - - - - 27.1 - - - 18 11.5 K= 5.60 36.8 34.0 19 12.8 K= 5.60 27.8 29.5 20 12.8 K= 5.60 28.3 29.8 21 12.8 K= 5.60 27.4 29.3 21A 12.8 - - - - 29.4 - - - 22 12.8 K= 5.60 26.4 28.8 23 12.8 K= 5.60 26.7 29.0 24 12.8 K= 5.60 27.8 29.5 25 11.5 - - - - 36.8 - - - 26 11.5 - - - - 36.8 - - - 27 11.5 - - - - 36.6 - - - 28 11.5 - - - - 36.7 - - - 29 11.5 - - - - 36.7 - - - 30 11.5 - - - - 36.7 - - - 31 11.5 - - - - 36.8 - - - 32 11.5 - - - - 37.3 - - - 33 11.5 - - - - 36.9 - - - SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 6/1/2020 C:\PROGRAM FILES\HRS SYSTEMS\HASS88\EXTRASS1R.SDF JOB TITLE: ESS 79120 CORPORATE CENTER DR. BLDG L - .20/1578 REV1 NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES (FT) (PSI) (GPM) 34 11.5 - - - - 37.8 - - - 35 11.5 - - - - 45.4 - - - 36 11.5 - - - - 45.9 - - - 37 11.5 - - - - 47.2 - - - TR 11.5 - - - - 50.7 - - - BR 1.0 - - - - 60.9 - - - U1 -3.0 HOSE STREAM 64.0 250.0 U2 -3.0 - - - - 63.5 - - - U3 -3.0 - - - - 62.9 - - - U -3.0 - - - - 69.2 - - - C1 -3.0 - - - - 68.8 - - - C2 -3.0 - - - - 64.8 - - - SRC -3.0 SOURCE 69.7 953.3 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 6/1/2020 C:\PROGRAM FILES\HRS SYSTEMS\HASS88\EXTRASS1R.SDF JOB TITLE: ESS 79120 CORPORATE CENTER DR. BLDG L - .20/1578 REV1 NFPA3 PIPE DATA Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) To Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes Frm Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 1 5.60 31.1 Disch 8.75 120 30.9 1 12.8 30.9 0.0 1.000 3E: 7.0 12.85 0.5 33 11.5 36.9 31.1 1.083 T: 5.8 21.60 0.253 5.5 Pipe: 2 5.60 28.7 Disch 5.00 120 26.2 2 12.8 26.2 0.0 1.250 ---- 0.00 0.0 3 12.8 26.5 28.7 1.418 5.00 0.058 0.3 Pipe: 3 5.60 28.8 Disch 5.00 120 26.5 3 12.8 26.5 28.7 2 1.250 ---- 0.00 0.0 4 12.8 27.6 57.5 1.418 5.00 0.211 1.1 Pipe: 4 5.60 29.4 Disch 4.25 120 27.6 4 12.8 27.6 57.5 3 1.250 3E:10.3 17.12 0.5 34 11.5 37.8 86.9 1.418 T: 6.8 21.37 0.454 9.7 Pipe: 5 0.0 217.5 5 1.00 120 36.9 33 11.5 36.9 31.1 1 4.000 T:27.9 27.87 0.0 32 11.5 37.3 248.6 4.310 28.87 0.014 0.4 Pipe: 6 0.0 0.0 5.42 120 37.3 32 11.5 37.3 248.6 33 4.000 T:27.9 27.87 0.0 34 11.5 37.8 248.6 4.310 33.29 0.014 0.5 Pipe: 7 5.60 34.0 Disch 5.50 120 36.9 5 11.5 36.9 183.5 31 4.000 ---- 0.00 0.0 33 11.5 36.9 217.5 4.310 5.50 0.011 0.1 Pipe: 8 0.0 129.0 8 4.00 120 36.8 31 11.5 36.8 54.5 7 4.000 ---- 0.00 0.0 5 11.5 36.9 183.5 4.310 4.00 0.008 0.0 Pipe: 9 5.60 26.7 Disch 10.00 120 22.7 6 12.8 22.7 0.0 1.000 ---- 0.00 0.0 7 12.8 24.6 26.7 1.083 10.00 0.190 1.9 Pipe: 10 5.60 27.8 Disch 8.25 120 24.6 7 12.8 24.6 26.7 6 1.000 E: 2.3 8.18 0.5 31 11.5 36.8 54.5 1.083 T: 5.8 16.43 0.711 11.7 5.60 34.0 Disch Pipe: 11 0.0 5.00 120 36.8 8 11.5 36.8 95.0 30 4.000 ---- 0.00 0.0 31 11.5 36.8 129.0 4.310 5.00 0.004 0.0 Pipe: 12 0.0 40.2 11 5.83 120 36.7 30 11.5 36.7 54.8 10 4.000 2E:27.9 27.87 0.0 8 11.5 36.8 95.0 4.310 33.70 0.002 0.1 Pipe: 13 5.60 26.9 Disch 10.00 120 23.0 9 12.8 23.0 0.0 1.000 ---- 0.00 0.0 10 12.8 25.0 26.9 1.083 10.00 0.192 1.9 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 6/1/2020 C:\PROGRAM FILES\HRS SYSTEMS\HASS88\EXTRASS1R.SDF JOB TITLE: ESS 79120 CORPORATE CENTER DR. BLDG L - .20/1578 REV1 Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) To Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes Frm Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 14 5.60 28.0 Disch 7.42 120 25.0 10 12.8 25.0 26.9 9 1.000 E: 2.3 8.18 0.5 30 11.5 36.7 54.8 1.083 T: 5.8 15.60 0.720 11.2 Pipe: 15 5.60 33.9 Disch 6.00 120 36.7 11 11.5 36.7 6.2 29 4.000 ---- 0.00 0.0 30 11.5 36.7 40.2 4.310 6.00 0.000 0.0 Pipe: 16 0.0 54.8 13 4.00 120 36.7 29 11.5 36.7 -48.6 28 4.000 ---- 0.00 0.0 11 11.5 36.7 6.2 4.310 4.00 0.000 0.0 Pipe: 17 5.60 26.9 Disch 10.00 120 23.0 12 12.8 23.0 0.0 1.000 ---- 0.00 0.0 13 12.8 25.0 26.9 1.083 10.00 0.192 1.9 Pipe: 18 5.60 28.0 Disch 7.42 120 25.0 13 12.8 25.0 26.9 1.000 E: 2.3 8.18 0.5 29 11.5 36.7 54.8 1.083 T: 5.8 15.60 0.720 11.2 Pipe: 19 0.0 54.8 13 5.50 120 36.7 29 11.5 36.7 -6.2 11 4.000 T:27.9 27.87 0.0 28 11.5 36.7 48.6 4.310 33.37 0.001 0.0 Pipe: 20 0.0 0.0 4.50 120 36.6 27 11.5 36.6 109.3 17A 4.000 T:27.9 27.87 0.0 28 11.5 36.7 109.3 4.310 32.37 0.003 0.1 Pipe: 21 5.60 26.4 Disch 10.00 120 22.3 14 12.8 22.3 0.0 1.250 ---- 0.00 0.0 15A 12.8 22.8 26.4 1.418 10.00 0.050 0.5 Pipe: 22 5.60 26.0 Disch 1.00 120 21.6 15 12.8 21.6 0.0 1.000 T: 5.8 5.84 0.0 15A 12.8 22.8 26.0 1.083 6.84 0.181 1.2 Pipe: 23 0.0 0.0 13.67 120 22.8 15A 12.8 22.8 52.4 1.250 E: 3.4 10.27 0.0 17A 12.8 27.1 52.4 1.418 T: 6.8 23.94 0.178 4.3 Pipe: 24 5.60 28.3 Disch 10.00 120 25.5 16 12.8 25.5 0.0 1.250 ---- 0.00 0.0 17 12.8 26.1 28.3 1.418 10.00 0.057 0.6 Pipe: 25 5.60 28.6 Disch 4.67 120 26.1 17 12.8 26.1 28.3 16 1.250 ---- 0.00 0.0 17A 12.8 27.1 56.9 1.418 4.67 0.207 1.0 Pipe: 26 0.0 56.9 17 2.75 120 27.1 17A 12.8 27.1 52.4 15A 1.250 E: 3.4 10.27 0.5 27 11.5 36.6 109.3 1.418 T: 6.8 13.02 0.694 9.0 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 6/1/2020 C:\PROGRAM FILES\HRS SYSTEMS\HASS88\EXTRASS1R.SDF JOB TITLE: ESS 79120 CORPORATE CENTER DR. BLDG L - .20/1578 REV1 Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) To Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes Frm Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 27 0.0 109.3 27 2.29 120 36.7 28 11.5 36.7 48.6 29 4.000 ---- 0.00 0.0 18 11.5 36.8 157.9 4.310 2.29 0.006 0.0 Pipe: 28 5.60 34.0 Disch 1.50 120 36.8 18 11.5 36.8 157.9 28 4.000 ---- 0.00 0.0 26 11.5 36.8 191.9 4.310 1.50 0.009 0.0 Pipe: 29 5.60 29.5 Disch 7.50 120 27.8 19 12.8 27.8 0.0 1.250 ---- 0.00 0.0 20 12.8 28.3 29.5 1.418 7.50 0.062 0.5 Pipe: 30 5.60 29.8 Disch 5.00 120 28.3 20 12.8 28.3 29.5 19 1.250 ---- 0.00 0.0 21A 12.8 29.4 59.3 1.418 5.00 0.224 1.1 Pipe: 31 5.60 29.3 Disch 3.00 120 27.4 21 12.8 27.4 0.0 1.000 T: 5.8 5.84 0.0 21A 12.8 29.4 29.3 1.083 8.84 0.226 2.0 Pipe: 32 0.0 59.3 20 4.25 120 29.4 21A 12.8 29.4 29.3 21 1.250 E: 3.4 10.27 0.5 26 11.5 36.8 88.6 1.418 T: 6.8 14.52 0.471 6.8 Pipe: 33 0.0 88.6 21A 3.00 120 36.8 26 11.5 36.8 191.9 18 4.000 ---- 0.00 0.0 25 11.5 36.8 280.5 4.310 3.00 0.018 0.1 Pipe: 34 5.60 28.8 Disch 5.00 120 26.4 22 12.8 26.4 0.0 1.250 ---- 0.00 0.0 23 12.8 26.7 28.8 1.418 5.00 0.059 0.3 Pipe: 35 5.60 29.0 Disch 5.00 120 26.7 23 12.8 26.7 28.8 22 1.250 ---- 0.00 0.0 24 12.8 27.8 57.8 1.418 5.00 0.213 1.1 5.60 29.5 Disch Pipe: 36 0.0 8.25 120 27.8 24 12.8 27.8 57.8 23 1.250 E: 3.4 10.27 0.5 25 11.5 36.8 87.3 1.418 T: 6.8 18.52 0.458 8.5 Pipe: 37 0.0 87.3 24 281.67 120 36.8 25 11.5 36.8 280.5 26 4.000 T:27.9 27.87 0.0 36 11.5 45.9 367.8 4.310 309.54 0.029 9.0 Pipe: 38 0.0 0.0 18.50 120 45.9 36 11.5 45.9 367.8 25 4.000 T:27.9 27.87 0.0 37 11.5 47.2 367.8 4.310 46.37 0.029 1.4 Pipe: 39 0.0 248.6 32 281.42 120 37.8 34 11.5 37.8 86.9 4 4.000 T:27.9 27.87 0.0 35 11.5 45.4 335.5 4.310 309.29 0.025 7.6 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 DATE: 6/1/2020 C:\PROGRAM FILES\HRS SYSTEMS\HASS88\EXTRASS1R.SDF JOB TITLE: ESS 79120 CORPORATE CENTER DR. BLDG L - .20/1578 REV1 Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) To Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes Frm Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 40 0.0 0.0 17.33 120 45.4 35 11.5 45.4 335.5 34 4.000 2E:27.9 55.75 0.0 37 11.5 47.2 335.5 4.310 T:27.9 73.08 0.025 1.8 Pipe: 41 0.0 335.5 35 22.50 120 47.2 37 11.5 47.2 367.8 36 4.000 E:13.9 13.94 0.0 TR 11.5 50.7 703.3 4.310 36.44 0.097 3.5 Pipe: 42 0.0 0.0 10.50 120 50.7 TR 11.5 50.7 703.3 37 4.000 C:30.7 47.39 4.5 BR 1.0 60.9 703.3 4.310 B:16.7 57.89 0.097 5.6 Pipe: 43 0.0 0.0 4.00 140 60.9 BR 1.0 60.9 703.3 TR D6.000 E:22.0 22.00 1.7 U3 -3.0 62.9 703.3 6.280 26.00 0.012 0.3 Pipe: 44 0.0 0.0 4.50 150 62.9 U3 -3.0 62.9 703.3 BR E6.000 T:46.0 46.00 0.0 U2 -3.0 63.5 703.3 6.080 50.50 0.012 0.6 Pipe: 45 0.0 0.0 77.00 150 63.5 U2 -3.0 63.5 703.3 U3 E8.000 2E:54.0 54.00 0.0 U1 -3.0 64.0 703.3 7.980 131.00 0.003 0.4 Pipe: 46 H.S. 250.0 Disch 156.00 150 64.0 U1 -3.0 64.0 703.3 U2 E8.000 ---- 0.00 0.0 C2 -3.0 64.8 953.3 7.980 156.00 0.006 0.9 Pipe: 47 0.0 Fixed Pressure Loss Device C2 -3.0 64.8 953.3 U1 4.0 psi, 953.3 gpm C1 -3.0 68.8 953.3 Pipe: 48 0.0 0.0 20.00 150 68.8 C1 -3.0 68.8 953.3 C2 E8.000 T:53.0 53.00 0.0 U -3.0 69.2 953.3 7.980 73.00 0.006 0.4 Pipe: 49 0.0 0.0 415.00 150 69.2 U -3.0 69.2 953.3 C1 E12.00 T:81.0 81.00 0.0 SRC -3.0 69.7 953.3 11.650 496.00 0.001 0.4 NOTES (HASS): (1) Calculations were performed by the HASS 8.8 D computer program in accordance with NFPA13 (2019) under license no. 27030354 granted by HRS Systems, Inc. 208 Southside Square Petersburg, TN 37144 (931) 659-9760 (2) The system has been calculated to provide an average imbalance at each node of 0.003 gpm and a maximum imbalance at any node of 0.125 gpm. SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9 DATE: 6/1/2020 C:\PROGRAM FILES\HRS SYSTEMS\HASS88\EXTRASS1R.SDF JOB TITLE: ESS 79120 CORPORATE CENTER DR. BLDG L - .20/1578 REV1 (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 22.2 ft/sec at pipe 26. (4) Items listed in bold print on the cover sheet are automatically transferred from the calculation report. (5) Available pressure at source node SRC under full flow conditions is 78.93 psi with a flow of 1009.21 gpm. (6) PIPE FITTINGS TABLE HASS Pipe Table Name: standard.pip PAGE: * MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee -------------------------------------------------------- F F45Ell 1.083 2.34 5.84 2.34 5.84 7.01 1.17 11.68 2.34 5.84 1.17 1.418 3.42 6.85 2.28 7.99 6.85 1.14 11.41 11.41 6.85 1.71 4.310 13.94 27.87 8.36 30.66 16.72 2.79 27.87 27.87 27.87 6.97 PAGE: D MATERIAL: DIRON HWC: 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G N F Ell Tee LngEll ChkVlv BfyVlv GatVlv NPTee F45Ell 6.280 22.00 47.00 14.00 51.00 16.00 5.00 47.00 11.00 PAGE: E MATERIAL: PVC150 HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G N F Ell Tee LngEll ChkVlv BfyVlv GatVlv NPTee F45Ell 6.080 22.00 46.00 14.00 49.00 15.00 5.00 46.00 11.00 7.980 27.00 53.00 20.00 68.00 18.00 6.00 53.00 13.50 11.650 36.00 81.00 24.00 87.00 28.00 8.00 81.00 18.00 Approvals Rod Size Part Number Model Screw Descriptions Ultimate Pullout (lbs) UL Test Load (lbs) FM Test Load (lbs) Min Thick Max Thick Box Qty Case Qty 1/4" 8024957 DSTR 100 * 1/4-20 x 1" TEKS 3 1510 (20 ga.) .036"-20 ga 3/16" 25 125 1/4" 8025957 DST 100 1/4-14 x 1" TEKS 3 446 (20 ga.) .036"-20 ga 3/16" 25 125 1/4" 8026957 DST 150 1/4-14 x 1-1/2" TEKS 3 970 (16 ga.) .036"-20 ga 3/16" 25 125 1/4" 8027957 DST 200 1/4-14 x 2" TEKS 3 446 (20 ga.) .036”-20 ga 3/16” 25 125 1/4" 8030957 TEK 500 12-24 x 1-1/2" TEKS 5 3125 (3/16") .187”-3/16” 1/2" 25 125 3/8" 8038957 DSTR 1 * 1/4-20 x 1" TEKS 3 1510 (20 ga.) 1500 1475 .036"-20 ga 3/16" 25 125 3/8" 8037957 DSTR 1-1/2 * 12-24 x 1-1/2" TEKS 5 1510 (3/16") 1500 1475 .060”-16 ga. 1/2" 25 125 3/8" 8039957 DSTR 516 * 5/16-18 x 1-1/4" TEKS 3 2200 (20 ga.) 1500 1475 .036"-20 ga 1/8" 25 125 3/8" 8040957 DST 10 1/4-14 x 1" TEKS 3 446 (20 ga.) 970 (16 ga.).036"-20 ga 3/16" 25 125 3/8" 8077925 DST 10-SS 1/4-14 x 1" TEKS 3 446 (20 ga.) 970 (16 ga.).036"-20 ga 3/16" 25 125 3/8" 8041957 DST 15 1/4-14 x 1-1/2" TEKS 3 446 (20 ga.) 970 (16 ga.).036"-20 ga 3/16" 25 125 3/8" 8078925 DST 15-SS 1/4-14 x 1-1/2" TEKS 3 446 (20 ga.) 970 (16 ga.).036"-20 ga 3/16" 25 125 3/8" 8042957 DST 20 1/4-14 x 2 TEKS" 3 446 (20 ga.) 970 (16 ga.).036"-20 ga 3/16" 25 125 3/8" 8043957 DST 25 1/4-14 x 2-1/2" TEKS 3 446 (20 ga.) 970 (16 ga.).036"-20 ga 3/16" 25 125 3/8" 8044957 DST 30 1/4-14 x 3" TEKS 3 446 (20 ga.) 970 (16 ga.).036"-20 ga 3/16" 25 125 3/8" 8045957 DST 516 5/16-18 x 1-1/4" TEKS 3 1500 (3/16") 1500 1475 .125"-1/8" 1/8" 25 125 3/8" 8046957 TEK 50 12-24 x 1-1/2" TEKS 5 3125 (3/16") 1500 1475 .187”-3/16” 1/2" 25 125 1/2" 8031925 DST 2.0 1/4-14 x 2" TEKS 3 446 (20 ga.) 970 (16 ga.).188"-3/16" 1/4" 25 125 1/2" 8033925 DSTR 1.0 * 1/4-20 x 1" TEKS 3 1510 (20 ga.) .036"-20 ga 3/16" 25 125 1/2" 8034925 DSTR 5.16 * 5/16-18 x 1-1/4" TEKS 3 2220 (20 ga.) .036"-20 ga 1/8" 25 125 1/2" 8035925 DST 5.16 5/16-18 x 1-1/4" TEKS 3 1500 (3/16") .125"-1/8" 1/8” 25 125 1/2" 8036925 TEK 5.0 12-24 x 1-1/2" TEKS 5 3125 (3/16") .187"-3/16" 1/2" 25 125 #14 Black Nut Driver Part # 8113910 #14 SW Red Nut Driver Part # 8114910*Includes retaining nut Approvals Rod Size Part Number Model Screw Descriptions Ultimate Pullout (lbs) UL Test Load (lbs) FM Test Load (lbs) Min Thick Max Thick Box Qty Case Qty 3/8" 8137957 SH-DSTR 1 * 1/4-20 x 1" 3220 (3/16") 1500 1475 .035" 3/16” 25 125 #14 Black Nut Driver Part # 8113910 SAMMY Swivel Head® for Steel 6 For the most up to date information, visit www.sammysuperscrew.com SAMMYS® for Steel Installs VERTICALLY into the bottom of steel structures easily and quickly! VERTICAL MOUNT STEEL STEEL STEEL STEEL STEELSPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes into contact with the material you are installing into, continue drilling until nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for installations. pre -drillingno required Product Features • Made with Teks® self-drilling fasteners - no pre-drilling required. • Install into steel range from 22 gauge – 1/2” thicknesses. • Saves time from traditional methods. • Reduces installation cost. • Quick to install using the Sammy Nut Driver with an 18V cordless drill/driver. Product Features • Eliminates distortion of threaded rod in sloped roof applications. • Accommodates 3-1/2 over 12 pitch. • Installs into angled Z-Purlin; Allows threaded rod to hang plumb. • Allows 17° deflection from vertical. (Does not comply with ROHS requirements) Installs VERTICALLY and swivels up to 17° in steel structure *Includes retaining nut 7 To find a distributor near you, call 800-BUILDEX HORIZONTAL MOUNT STEEL STEEL STEEL STEEL STEELSIDEWINDERS® for Steel Installs HORIZONTALLY into the side of steel structures easily and quickly! Approvals Rod Size Part Number Model Screw Descriptions Ultimate Pullout (lbs) UL Test Load (lbs) FM Test Load (lbs) Min Thickness Max Thickness Box Qty Case Qty 1/4" 8047957 SWD 100 1/4-14 x 1" TEKS 3 1477 (16 ga.) .060"-16 ga 3/16" 25 125 1/4" 8049957 SWDR 100 * 1/4-20 x 1" TEKS 3 1900 (20 ga.) .036"-20 ga 3/16" 25 125 3/8" 8050957 SWD 10 1/4-14 x 1" TEKS 3 1477 (16 ga.) .060"-16 ga 3/16" 25 125 3/8" 8080925 SWD 10-SS 1/4-14 x 1" TEKS 3 1477 (16 ga.) .060"-16 ga 3/16" 25 125 3/8" 8051957 SWD 15 1/4-14 x 1-1/2" TEKS 3 1477 (16 ga.) .060"-16 ga 3/16” 25 125 3/8" 8081925 SWD 15-SS 1/4-14 x 1-1/2" TEKS 3 1477 (16 ga.) .060"-16 ga 3/16” 25 125 3/8" 8052957 SWD 20 1/4-14 x 2" TEKS 3 1477 (16 ga.) .060"-16 ga 3/16” 25 125 3/8" 8053957 SWD 516 5/16-18 x 1-1/4" TEKS 3 2480 (20 ga.) .036”-20 ga 1/8” 25 125 3/8" 8055957 SWDR 1 * 1/4-20 x 1" TEKS 3 1900 (20 ga.) 1500 1475 .036"-20 ga 3/16" 25 125 3/8" 8054957 SWDR 1-1/2 * 12-24 x 1-1/2" TEKS 5 2375 (3/16") 1500 1475 .187"-3/16" 1/2" 25 125 3/8" 8056957 SWDR 516 * 5/16-18 x 1-1/4" TEKS 3 2480 (20 ga.) 1500 1475 .036"-20 ga 1/8" 25 125 3/8" 8057957 SWT 15 12-24 x 1-1/2" TEKS 5 237 (3/16") .187"-3/16" 1/2" 25 125 SPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes into contact with the material you are installing into, continue drilling until nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for installations. #14 SW Red Nut Driver Part # 8114910 pre -drillingno required Ultimate Pullout Values (avg. lbs. ultimate) - SAMMYS Fastener Steel Gauge (lbs.) Model Dia. Pt. 20 18 16 14 12 3/16 1/4 DST 1/4 #3 446 613 970 1145 1544 3190 DST 516 5/16 #3 457 568 1209 1712 2422 TEK 50 #12 #5 487 699 913 1527 3270 3593 DSTR 1-1/2”#12 #5 3270 3593 DSTR 1”1/4 #3 1510 DSTR 516 5/16 #3 2200 Ultimate Pullout Values (avg. lbs. ultimate) - SIDEWINDERS Fastener Steel Gauge (lbs.) Model Dia. Pt. 20 18 16 14 12 3/16 1/4 SWD 1/4 #3 1477 SWDR 1-1/2”#12 #5 2375 SWDR 1”1/4 #3 1900 1900 SWDR 516 5/16 #3 2480 2480 Performance Data - Steel Sheet Steel Gauges Gauge No. 26 24 22 20 18 16 14 12 3/16” 1/4” Nominal Decimal Equivalent .018 .024 .030 .036 .048 .060 .075 .105 .188 .250 *Includes retaining nut Product Features • Made with Teks® self-drilling fasteners - no pre-drilling required. • Install into steel range from 22 gauge – 1/2” thicknesses. • Saves time from traditional methods. • Reduces installation cost. • Quick to install using the Sammy Nut Driver with an 18V cordless drill/driver. Aluminum Curtain Wall Extrusion Ultimate Pullout Values (average lbs. ultimate) Fastener Thickness Model Dia. Pt. .114 .092 .365 .132 DST 10 1/4 #3 1265 2750 SWD 10 1/4 #3 1120 1420 Agency Listings SSM/SSV Series Alarm Bells System Sensor’s SSM and SSV series alarm bells are low current, high decibel notification appliances for use in fire and burglary systems or other signaling applications. Features t"QQSPWFEGPSJOEPPSBOEPVUEPPSVTF t-PXDVSSFOUESBX t)JHIE#PVUQVU t"WBJMBCMFJOTJYJODI FJHIUJODI BOEUFOJODITJ[FT t"$BOE%$NPEFMT t%$NPEFMTQPMBSJ[FEGPSVTFXJUITVQFSWJTJPODJSDVJUSZ t.PVOUEJSFDUMZUPTUBOEBSEGPVSJODITRVBSFFMFDUSJDBMCPYJOEPPST t44.BOE447TFSJFTDPNFQSFXJSFE Reliable Performance.5IF44.BOE447TFSJFTQSPWJEFMPVE SFTPOBOUUPOFT5IF44.TFSJFTPQFSBUFTPO7%$BOEBSFNPUPS ESJWFO XIJMFUIF447TFSJFTPQFSBUFTPO7"$VUJMJ[JOHBWJCSBUJOH NFDIBOJTN Simplified Installation.'PSJOEPPSVTF UIF44.BOE447TFSJFT NPVOUUPBTUBOEBSEGPVSJODITRVBSFFMFDUSJDBMCPY'PSPVUEPPS BQQMJDBUJPOT XFBUIFSQSPPGCBDLCPY NPEFMOVNCFS8## JTVTFE 5IF44.BOE447TFSJFTDPNFQSFXJSFE UPSFEVDFJOTUBMMBUJPOUJNF 5IF44.TFSJFTJODPSQPSBUFTBQPMBSJ[FEFMFDUSJDBMEFTJHOGPSVTFXJUI TVQFSWJTJPODJSDVJUSZ 4&$4 0IJP"WFOVFt4U$IBSMFT *- 1IPOF4&/403t'BY ª4ZTUFN4FOTPS 1SPEVDUTQFDJmDBUJPOTTVCKFDUUPDIBOHFXJUIPVUOPUJDF7JTJUTZTUFNTFOTPSDPNGPS DVSSFOUQSPEVDUJOGPSNBUJPO JODMVEJOHUIFMBUFTUWFSTJPOPGUIJTEBUBTIFFU "tt Ordering Information UL/FM Model No. ULC/Canadian Model No. Description 44. 44." #FMM † 7%$ 1PMBSJ[FE E#" 44. 44." #FMM † 7%$ 1PMBSJ[FE E#" 44. 44." #FMM † 7%$ 1PMBSJ[FE E#" 447 447" #FMM † 7"$ E#" 447 447" #FMM † 7"$ E#" 447 447" #FMM † 7"$ E#" 8## 8FBUIFSQSPPGCBDLCPYGPS44.BOE447TFSJFT XIFOJOTUBMMFEPVUEPPST SSM/SSV Specifications Architectural/Engineering Specifications .PEFMTIBMMCFB44.PS4474FSJFTBMBSNCFMM#FMMTTIBMMIBWFVOEFSEPNFTUSJLFSTBOEPQFSBUJOHNFDIBOJTNT(POHTPOTBJECFMMTTIBMMCFOPTNBMMFSUIBO OPNJOBM††† TQFDJGZTJ[F XJUIBOPQFSBUJOHWPMUBHFPG7%$PS7"$ TQFDJGZCZQBSUOVNCFS #FMMTTIBMMCFTVJUBCMFGPSTVSGBDFPSTFNJnVTI NPVOUJOH0VUEPPSTVSGBDFNPVOUFEJOTUBMMBUJPOTTIBMMCFXFBUIFSQSPPG VTJOHPQUJPOBM8##XFBUIFSQSPPGFMFDUSJDBMCPY 0UIFSXJTFCFMMTTIBMMNPVOUUP BTUBOEBSE†TRVBSFFMFDUSJDBMCPYIBWJOHBNBYJNVNQSPKFDUJPOPG›†#FMMTTIBMMCFMPDBUFEBTTIPXOPOUIFESBXJOHTPSBTEFUFSNJOFECZUIF"VUIPSJUZ )BWJOH+VSJTEJDUJPO#FMMTTIBMMCFMJTUFEGPSJOEPPSPVUEPPSVTFCZ6OEFSXSJUFST-BCPSBUPSJFTBOEUIF$BMJGPSOJB4UBUF'JSF.BSTIBM BOEBQQSPWFECZ'BDUPSZ .VUVBMBOE.&" Physical/Operating Specifications Operating Temperature Range o¡'UP¡' Operating Voltage 44.TFSJFT7%$ 447TFSJFT7"$ Termination 1SPWJEFEXJUITFUTPGMFBETGPSJOPVUXJSJOH Service Use 'JSF"MBSN (FOFSBM4JHOBMJOH #VSHMBS"MBSN Warranty ZFBST Electrical Specifications Model Gong Diameter (inches) Nominal Voltage Operating Voltage Limit Maximum Current Sound Output (dBA) 44.  3FHVMBUFE7%$ UP7%$ %$N"'83N"  44.8 3FHVMBUFE7%$ UP7%$ %$N"'83N"  44.  3FHVMBUFE7%$ UP7%$ %$N"'83N"  447  3FHVMBUFE7"$ UP7"$ N"  4478 3FHVMBUFE7"$ UP7"$ N"  447  3FHVMBUFE7"$ UP7"$ N"  4PVOEPVUQVUNFBTVSFEBU6OEFSXSJUFS-BCPSBUPSJFT BTTQFDJmFEJO6- SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS The Style 177 QuickVic flexible coupling is installation-ready, and joins 2-6"/50-150 mm standard roll grooved and cut grooved steel pipe.* The coupling's unique design eliminates loose parts, insures consistent installation and provides substantial gains in productivity. * Sizes 2-4"/50-100 mm may be used to join 304/304L and 316/316L Schedule 10 stainless steel pipe with a maximum rated working pressure of 300 psi/2065 kPa. MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12. Housing Coating: Orange enamel. Gasket: • Grade “EHP” EHP (Red stripe color code) Temperature range –30°F to +250°F/–34°C to +121°C. Recommended for hot water service within the specified temperature range plus a variety of dilute acids, oil-free air and many chemical services.* UL classified in accordance with ANSI/NSF 61 for cold +86°F/+30°C and hot +180°F/+82°C potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade “T” nitrile Nitrile (Orange color code). Temperature range –20°F to +180°F/–29°C to +82°C. Recommended for petroleum products, air with oil vapors, vegetable and mineral oils within the specified temperature range. Not recommended for hot water services over +150°F/+66°C or for hot dry air over +140°F/+60°C. * Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a l isting of services which are not recommended. Bolts/Nuts: Heat-treated plated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. 06.20_1 QuickVic® Flexible Coupling for Steel STYLE 177 06.20CARBON STEEL PIPE – GROOVED COUPLINGS JOB/OWNER CONTRACTOR ENGINEER System No. __________________________Submitted By ________________________Spec Sect ____________ Para __________ Location ____________________________Date ________________________________Approved ___________________________ Date ________________________________ www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_D DIMENSIONS STYLE 177 JOINT ASSEMBLED STYLE 177 PRE-ASSEMBLED (INSTALLATION-READY CONDITION) Size Pipe End Sep. Inches mm Bolt/Nut No. – Size Dimensions – Inches/mm Aprx. Wgt. Ea. Nominal Size Inches mm Actual Outside Diameter Inches mm (1) Min (2) Max (3) Max Inches mm Pre-assembled (Installation-ready condi- tion)Joint Assembled Lbs. kgXYXYZ 2 2.375 0.13 0.19 0.25 2 – ³⁄₈ x 2 ½3.87 5.59 3.56 5.39 2.05 2.0 50 60.3 3.2 4.8 6.4 98 142 90 1.37 52 0.9 2½2.875 0.13 0.19 0.25 2 – ³⁄₈ x 2 ½4.36 6.13 4.05 5.89 2.05 2.4 65 73.0 3.2 4.8 6.4 111 156 103 150 52 1.1 3 3.500 0.13 0.19 0.25 2 – ½ x 3 5.00 7.05 4.68 6.81 2.04 3.1 80 88.9 3.2 4.8 6.4 127 179 119 173 52 1.4 4 4.500 0.13 0.25 0.38 2 – ½ x 3 5.98 8.24 5.61 7.92 2.15 3.7 100 114.3 3.2 6.4 9.5 152 209 142 201 54 1.7 6 6.625 0.13 0.25 0.38 2 – ⁵⁄₈ x 3 ¼8.23 11.18 7.95 10.92 2.09 6.3 150 168.3 3.2 6.4 9.5 209 284 202 277 53 2.9 (1) The minimum pipe end separation as required by the gasket center leg for roll or cut grooved pipe. See illustrations below. (2 & 3) Maximum pipe end separation to be used for determining overall piping system movement for roll (2) or cut (3) groove pipe. For design and installation purposes, the minimum and maximum pipe end separations should be reduced to the values shown in the table below. These design and installation considerations include thermal growth, settlement, installation misalignment and offsets. See illustrations below. Minimum Pipe Separation (1) Roll and Cut Groove Maximum Pipe Separation (2) Roll Groove The amount of linear movement and angular deflection to be used for design and installation consideration for each coupling is shown in the table below. † Victaulic recommends for design and installation purposes, these values should be reduced by 50% for ¾-3 ½"/20-90 mm sizes; 25% for 4"/100 mm and larger sizes. Exaggerated for clarity DESIGN AND INSTALLATION Size Range Design and Installation Values Roll Groove Pipe Cut Groove Pipe Inches/mm Linear Movement # Angular Deflection † Linear Movement # Angular Deflection † Per Cplg. Deg. Pipe In/Ft mm/m Per Cplg. Deg. Pipe In/Ft mm/m 2 0.06 0.32 0.13 0.64 50 1.6 1.52°26 3.2 3.04°52 2½0.06 0.26 0.13 0.52 65 1.6 1.25°22 3.2 2.50°44 3 0.06 0.22 0.13 0.44 80 1.6 1.03°18 3.2 2.06°36 4 0.13 0.34 0.25 0.68 100 3.2 1.60°28 6.4 3.20°56 6 0.13 0.23 0.25 0.46 150 3.2 1.08°18 6.4 2.16°36 Maximum Pipe Separation (3) Cut Groove 06.20_2 QuickVic® Flexible Coupling for Steel STYLE 177 06.20CARBON STEEL PIPE – GROOVED COUPLINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_D X Y Z X Y Z X Y Z X Y Z PERFORMANCE Size Schedule 10 (Steel Pipe)Schedule 40 (Steel Pipe) Nominal Inches Actual mm Actual Outside Diameter Inches mm Wall Thick. Inches mm Max. * Joint Work. Press. psi/kPa Max. * Permis. End Load Lbs./N Wall Thick. Inches mm Max. * Joint Work. Press. psi/kPa Max. * Permis. End Load Lbs./N 2 2.375 0.109 750 3322 0.154 1000 4430 50 60.3 2.77 5170 14896 3.91 6900 19714 2½2.875 0.120 600 3899 0.230 1000 6492 60 73.0 3.05 4135 17483 5.84 6900 28889 3 3.500 0.120 600 5772 0.216 1000 9621 75 88.9 3.05 4135 25882 5.49 6900 42813 4 4.500 0.120 600 9542 0.237 1000 15905 100 114.3 3.05 4135 42786 6.02 6900 71318 6 6.625 0.134 500 19263 0.28 700 24130 150 168.3 3.40 3445 86375 7.11 4825 108199 WARNING: Depressurize and drain the piping system before attempting to install, remove or adjust any Victaulic piping products. * Working Pressure and End Load are total, from all internal and external loads, based on (ANSI) steel pipe, grooved in accordance with Victaulic specifications. Contact Victaulic for performance on other pipe. WARNING: FOR ONE TIME FIELD TEST ONLY, the Maximum Joint Working Pressure may be increased to 1 ½ times the figures shown. 06.20_3 QuickVic® Flexible Coupling for Steel STYLE 177 06.20CARBON STEEL PIPE – GROOVED COUPLINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_D WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. NOTE Reference should always be made to the I-177 Victaulic Field Installation Instructions for the product you are installing. Instructions are included with each shipment of Victaulic products for complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. INSTALLATION GENERAL NOTES NOTE: When assembling Style 177 QuickVic flexible couplings onto end caps, take additional care to make certain the end cap is fully seat against the gasket center leg. For Style 177 QuickVic flexible couplings, use Victaulic No. 60 end caps containing "QV" or "QV/EZ" markings on the inside of the face. Non-Victaulic fittings shall not be used with Style 177 QuickVic flexible couplings. 06.20 QuickVic® Flexible Coupling for Steel STYLE 177 06.20CARBON STEEL PIPE – GROOVED COUPLINGS For complete contact information, visit www.victaulic.com 06.20 5147 REV D UPDATED 6/2009 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. FireLock® Style 005 rigid coupling has a unique, patented angle-pad design which allows the housings to offset while clamping the grooves. By permitting the housings to slide on the angled bolt pads, rigidity is obtained. Support and hanging requirements correspond to NFPA 13 Sprinkler Systems. Angle-pad design permits assembly by removing one nut/bolt and swinging the housing over the gasket. This reduces components to handle during assembly. Style 005 FireLock coupling are designed and recommended for use ONLY on fire protection systems. Vic-Plus™ Gasket System: In North America, Victaulic® offers a gasket system which requires no field lubrication on wet pipe systems that are hydrostatically tested. The Vic-Plus™ System (patented) is dry, clean, and non-toxic. It reduces assembly time substantially and eliminates the mess and chance of over- lubrication. Please refer to the latest copy of the Victaulic Field Installation Handbook (I-100) for supplemental lubrication requirements and dry pipe fire protection system notes. LISTING/APPROVALS The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Related Working Pressure – psi Related Working Pressure – psi Related Working Pressure – psi Pipe Sch. Size Inches UL ULC FM Pipe Sch. Size Inches UL ULC FM Pipe Sch. Size Inches UL ULC FM 51 ¼ – 3 175 175 175 EL 1 ¼ – 2 300 N/A N/A MT 1 ¼ – 2 300 N/A N/A 10, 40 1 ¼ – 4 350 350 350 ET 1 ¼ – 2 300 N/A N/A STF 1 ¼ – 4 N/A N/A 300 5 – 8 300 300 300 EZ 4 – 6 300# N/A 300 Steady Thd.1 ¼ – 2 N/A N/A 300 BLT 1 ¼ – 2 300 300 N/A FF 1 ¼ – 4 N/A N/A 300 TF 3 – 8 N/A N/A 300 DF 1 ¼ – 4 300 300 300 GAL - 7 1 ¼ – 2 300 N/A N/A WLS 1 ¼ – 2 300 300 N/A DT 1 ¼ – 2 300 300 N/A MLT 1 ¼ – 2 300 N/A N/A XL 1 ¼ – 3 300 300 300 EF 1 1⁄ – 4 175@ N/A 175 MF 1 ¼ – 4 300 N/A 300* * FM approved for service in 1 ½ – 4" pipe. # UL Listed for service up to 4" pipe only. @ UL Listed for service up to 3" only. 10.02_1 FireLock® Rigid Coupling STYLE 005 WITH VIC-PLUS™ GASKET SYSTEM (NORTH AMERICA ONLY) 10.02IPS CARBON STEEL PIPE - FIRE PROTECTION PRODUCTS JOB/OWNER CONTRACTOR ENGINEER System No. __________________________ Submitted By ________________________ Spec Sect ____________ Para __________ Location ____________________________ Date ________________________________ Approved ___________________________ Date ________________________________ www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2006 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV_I SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS § LPC and VdS Approved, see notes on page 4 PATENTED Exaggerated for clarity DIMENSIONS Size Max. Work Pressure § * Max. End Load * Allow. Pipe End Sep. † Bolt/Nut@ No – Size Dimensions – Inches/mm Approx. Wgt. Each Nominal Size Inches/mm Actual Outside Diameter Inches/mm PSI kPa Lbs. N Inches mm Inches mm XYZ Lbs. kg 1 ¼ 1.660 350 755 0.05 2 – 3⁄8 x 2 ¼ 2.75 4.50 1.88 1.2 32 42.4 2413 3370 1.2 70 114 148 0.5 1 ½ 1.900 350 990 0.05 2 – 3⁄8 x 2 ¼ 3.00 4.75 1.88 1.2 40 48.3 2413 4415 1.2 76 121 148 0.5 22.37535015500.072 – 3⁄8 x 2 ½ 3.50 5.25 1.88 1.6 50 60.3 2413 6900 1.7 89 133 148 0.7 2 ½ 2.875 350 2270 0.07 2 – 3⁄8 x 2 ½ 4.00 5.75 1.88 1.9 65 73.0 2413 10110 1.7 102 146 148 .09 76.1 mm 3.000 350 2475 0.07 2 – 3⁄8 x 2 ½ 4.13 5.75 1.88 1.9 76.1 2413 11010 1.7 105 146 148 0.9 33.50035033650.072 – 3⁄8 x 2 ½ 4.63 6.13 1.88 2.1 80 88.9 2413 14985 1.7 118 156 148 1.0 44.50035055650.162 – 3⁄8 x 2 ½ 5.75 7.25 2.13 3.1 100 114.3 2413 24770 4.1 146 184 54 1.4 108.0 mm 4.250 300 4255 0.16 2 – 3⁄8 x 2 ½ 5.63 7.25 2.13 3.1 108.0 2068 18940 4.1 143 184 54 1.4 55.56330072900.162 – ½ x 3 6.88 9.00 2.13 4.5 125 141.3 2068 32445 4.1 175 229 54 2.0 133.0 mm 5.250 300 6495 0.16 2 – ½ x 2 ¾ 6.63 9.00 2.13 4.5 133.0 2068 28900 4.1 168 229 54 2.0 139.7 mm 5.500 300 7125 0.16 2 – ½ x 2 ¾ 6.88 9.00 2.13 4.8 139.7 2068 31715 4.1 175 229 54 2.2 66.625300103400.162 – ½ x 3 8.00 10.00 2.13 5.0 150 168.3 2068 46020 4.1 203 254 53 2.3 159.0 mm 6.250 300 9200 0.16 2 – ½ x 2 ¾ 7.63 10.00 2.13 5.5 159.0 2068 40955 4.1 194 254 54 2.5 165.1 mm 6.500 300 9955 0.16 2 – ½ x 3 8.15 10.00 2.13 5.5 165.1 2068 44295 4.1 207 254 54 2.5 8 8.625 300 17525 0.19 2 – 5⁄8 x 4 ¼ 10.50 13.14 2.63 11.3 200 219.1 2068 78000 4.8 267 334 67 5.1 * Working Pressure and End Load are total, from all internal and external loads, based on standard weight (ANSI) steel pipe, standard roll or cut grooved in accordance with Victaulic specifications. Contact Victaulic for perfor- mance on other pipe. WARNING: FOR ONE TIME FIELD TEST ONLY, the Maximum Joint Working Pressure may be increased to 1 1/2 times the figures shown. † The allowable pipe separation dimension shown is for system layout purposes only. Style 005 couplings are con- sidered rigid connections and will not accommodate expansion or contraction of the piping system. @ Number of bolts required equals number of housing segments. Metric thread size bolts are available (color coded gold) for all coupling sizes upon request. Contact Victaulic for details. § Style 005 couplings are VdS and LPC Approved to 12 Bar/175 psi. Rated for wet and dry sprinkler systems at 350 psi/2413 kPa for 1 ¼ – 4"/32 – 100 mm sizes and 300 psi /2068 kPa for 4 ¼ – 8"/108 – 200 mm sizes; Schedule 10 roll grooved or Schedule 40 cut or roll grooved steel pipe. Style 005 is rigid and does not accommodate expansion, contraction or angular deflection. X ZY 10.02_2 FireLock ® Rigid Coupling STYLE 005 WITH VIC-PLUS™ GASKET SYSTEM (NORTH AMERICA ONLY) 10.02IPS CARBON STEEL PIPE - FIRE PROTECTION PRODUCTS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2006 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV_I MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. Housing Coating: Orange enamel (North America); red enamel (Europe) • Optional: Hot dipped galvanized Gasket: • Grade “E” EPDM – Type A Vic-Plus™ Gasket System Δ (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc. and Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services up to the rated working pressure using the Grade “E” Type A Vic-Plus™ Gasket System, requiring no field lubrication for most installation conditions. • Grade “L” Silicone Recommended for dry heat, air without hydrocarbons to +350°F and certain chemical services. For dry services, Victaulic continues to recommend the use of Grade “E” Type A FlushSeal® Gasket. Contact Victaulic for details. Bolts/Nuts: Heat-treated plated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. Δ Standard gasket and FlushSeal gasket approved for dry pipe systems to –40°F/–40°C. Based on “typical” pipe surface conditions, supplemental lubricant is recommended for services installed below 0°F/–18°C and for all dry pipe systems or systems to be subjected to air tests prior to being filled with water. Supplemental lubrication may also be required on pipe with raised or undercut weld seams or pipe that has voids and/or cracks at the weld seams. Victaulic continues to recommend the use of FlushSeal gaskets for dry services. 10.60_3 FireLock® Rigid Coupling STYLE 005 WITH VIC-PLUS™ GASKET SYSTEM (NORTH AMERICA ONLY) 10.02IPS CARBON STEEL PIPE - FIRE PROTECTION PRODUCTS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2006 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV_I WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. NOTE WARNING: Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products. GENERAL NOTES INSTALLATION Reference should always be made to the I-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. 10.02 FireLock ® Rigid Coupling STYLE 005 WITH VIC-PLUS™ GASKET SYSTEM (NORTH AMERICA ONLY) 10.02IPS CARBON STEEL PIPE - FIRE PROTECTION PRODUCTS For complete contact information, visit www.victaulic.com 10.02 1538 REV I UPDATED 9/2006 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2006 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. WCAS-697KR4 FireLock® products comprise a unique system specifically designed for fire protection services. FireLock full-flow elbows and tees are a CAD-developed, hydrodynamic design that has a shorter center-to-end dimension than standard fittings. A noticeable bulge allows the water to make a smoother turn to maintain similar flow characteristics as standard full flow fittings. FireLock fittings are designed for use exclusively with Style 005 and Style 009 FireLock couplings. Use of other couplings or flange adapters may result in bolt pad interference. Victaulic FireLock fittings pressure ratings conform to the ratings of Victaulic FireLock Style 005 couplings. Fitting: Ductile iron conforming to ASTM A-536, grade 65-45-12. Fitting Coating: Orange enamel. • Optional: Hot dipped galvanized. MATERIAL SPECIFICATIONS 10.03_1 FireLock ® Fittings 10.03IPS CARBON STEEL PIPE – FIRE PROTECTION PRODUCTS JOB/OWNER CONTRACTOR ENGINEER System No. __________________________Submitted By ________________________Spec Sect ____________ Para __________ Location ____________________________Date ________________________________Approved ___________________________ Date ________________________________ www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_H See Victaulic publication 10.01 for details VNIIPO DIMENSIONS C to E C to E NO. 001 C to E NO. 003 Cto E C to E NO. 002 T NO. 006 Size No. 001 90° Elbow No. 003 45° Elbow No. 002 Straight Tee No. 006 Cap Nominal Size Inches mm Actual Outside Diameter Inches mm C to E Inches mm Approx. Weight Each Lbs. kg C to E Inches mm Approx. Weight Each Lbs. kg C to E Inches mm Approx. Weight Each Lbs. kg Thickness “T” Inches mm Approx. Weight Each Lbs. kg 1 1/4 1.660 ——————0.8 0.3 32 42.4 21 0.1 1 1/2 1.900 ——————0.82 0.4 40 48.3 ——————21 0.2 2 2.375 2.75 1.7 2.00 1.8 2.75 2.4 0.88 0.6 50 60.3 70 0.8 51 0.8 70 1.1 22 0.3 2 1/2 2.875 3.00 3.1 2.25 2.2 3.00 3.6 0.88 1.0 65 73.0 76 1.4 57 1.0 76 1.6 22 0.5 76.1 mm 3.000 3.00 3.30 2.25 2.4 ————76.1 76 1.5 57 1.1 3 3.500 3.38 4.0 2.50 3.1 3.38 5.3 0.88 1.2 80 88.9 86 1.8 64 1.4 86 2.4 22 0.5 108 mm 4.250 4.00 5.7 3.00 5.1 4.00 7.5 ——108.0 102 2.6 76 2.3 102 3.4 4 4.500 4.00 6.7 3.00 5.6 4.00 8.7 1.00 2.4 100 114.3 102 3.0 76 2.5 102 3.9 25 1.1 5 5.563 4.88 12.6 3.25 8.3 4.88 15.7 1.00 4.1 125 141.3 124 5.7 83 3.8 124 7.1 25 1.9 159 mm 6.250 5.50 12.6 3.50 9.2 5.50 17.9 ——158.8 140 5.7 89 4.2 140 8.0 6 6.625 5.50 18.3 3.50 11.7 5.50 22.7 1.00 5.9 150 168.3 140 8.3 89 5.3 140 10.3 25 2.7 8 8.625 6.81 25.5 4.25 20.4 6.94 38.7 1.13 12.7 200 219.1 173 11.6 108 9.3 176 17.6 29 5.8 10.03_2 FireLock ® Fittings 10.03IPS CARBON STEEL PIPE – FIRE PROTECTION PRODUCTS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_H FLOW DATA Size Frictional Resistance Equivalent Feet/meters of Straight Pipe † Nominal Size Inches mm Actual Outside Diameter Inches mm Elbows No. 002 Straight Tee No. 001 90° Elbow No. 003 45° Elbow Branch Run 1 1/4 1.660 1.5 0.8 3.7 1.5 32 42.4 0.5 0.2 1.1 0.5 1 1/2 1.900 2.2 1.1 5.5 2.2 40 48.3 0.7 0.3 1.7 0.7 2 2.375 3.5 1.8 8.5 3.5 50 60.3 1.1 0.5 2.6 1.1 2 1/2 2.875 4.3 2.2 10.8 4.3 65 73.0 1.3 0.7 3.3 1.3 76.1 mm 3.000 4.5 2.3 11.0 4.5 76.1 1.4 0.7 3.4 1.4 3 3.500 5.0 2.6 13.0 5.0 80 88.9 1.5 0.8 4.0 1.5 108 mm 4.250 6.4 3.2 15.3 6.4 108.0 2.0 0.9 4.7 2.0 4 4.500 6.8 3.4 16.0 6.8 100 114.3 2.1 1.0 4.9 2.1 5 5.563 8.5 4.2 21.0 8.5 125 141.3 2.6 1.3 6.4 2.6 159 mm 6.250 9.4 4.9 25.0 9.6 158.8 2.9 1.5 7.6 2.9 6 6.625 10.0 5.0 25.0 10.0 150 168.3 3.0 1.5 7.6 3.0 8 8.625 13.0 5.0 33.0 13.0 200 219.1 4.0 1.5 10.1 4.0 † The flow data listed is based upon the pressure drop of Schedule 40 pipe. 10.03_3 FireLock ® Fittings 10.03IPS CARBON STEEL PIPE – FIRE PROTECTION PRODUCTS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_H WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. NOTE NOTE: When assembling FireLock EZ couplings onto end caps, take additional care to make certain the end cap is fully seated against the gasket end stop. For FireLock EZ Style 009 and Style 009V couplings, use FireLock No. 006 end caps containing the “EZ” marking on the inside face or No. 60 end caps containing the “QV EZ” marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009/009V couplings. GENERAL NOTES WCAS-7MX2JY 10.03 FireLock ® Fittings IPS CARBON STEEL PIPE – FIRE PROTECTION PRODUCTS For complete contact information, visit www.victaulic.com 10.03 1539 REV H UPDATED 1/2009 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. 10.03 Specifications Material: Injection Molded Polystyrene Size: 21/2” swivel Type: Pin lug Included per set: (2) caps (4) eyelets (4) finished hexnuts Available in sets only 3198 LIONSHEAD AVE CARLSBAD, CA 92010 TEL + 1 760 599-1168 + 1 800 344-1822 FAX + 1 800 344-3775 © 2012 Fire Protection Products, Inc. Description The Plastic Breakable Caps for Fire department Connections are injection molded polystyrene. Each set includes two caps and 4 eyelets with nuts for 21/2” swivels. The caps have been molded with “scored” tabs for easy removal with a hydrant wrench or other similar tool. Plastic Breakable caps provide protection against the introduction of foreign material into the swivels but allow for quick access when a hose connection is necessary. Installation Remove the caps from their packaging. Hold the breakable cap to the opening of swivel. Align the breakable tans with the pin lugs on the swivel. Once aligned, insert the threaded end of one eyelet through the hole in the tab of the cap then slide the eyelet over the pin lug. Once the eyelet is in place, carefully thread the included 1/4-20 finished hexnut on to the threaded end of the eyelet until snug. Caution: Do not overtighten. The tabs of the break caps are designed to break with minimal force. WWW.FPPI.COM Fire Department Connection Breakable Caps, Plastic Installation Installation of the Fire Department Connection is achieved with readily available jobsite tools. Prior to installation make sure the proper identification sign has been installed on the nipple. Coat male threads of 4” IPS nipple liberally with a suitable pipe thread sealant such as Pipefit®. Tighten FDC one full turn past hand tight. Make sure FDC is aligned according to requirements. DO NOT OVER TIGHTEN. OVERTIGHTENING MAY CAUSE SEVERE STRETCHING AND POSSIBLE CRACKING OF THE OF THE FDC BODY. Specifications Size: 4” IPS Outlet (2) 21/2” Swivel Inlets Type: Straight Pattern Material: B16 Brass* Swivels*: NST 3.0686 x 71/2 T BCT 3.0000 x 8 TP CF 2.9900 x 71/2 T CIN-new 3.0580 x 6 TP CIN-old 3.0930 x 6 TP CLV 3.0780 x 8 TP Dayton 3.2340 x 6 TP DET 3.1250 x 71/2 T NovaSco 3.2300 x 5 TP NYFD 3.0300 x 8 TP ONT 3.1250 x 5 TP PHX 3.0620 x 6 TP QST 3.0310 x 7 TP Raleigh 3.3400 x 6 TP Richmon 3.3120 x 8 TP TEM 3.0750 x 6 TP Approvals: UL Listed 300psi FM Approved 300psi *Contains lead. Not for use in water systems intended for human consumption. 3198 LIONSHEAD AVE CARLSBAD, CA 92010 TEL + 1 760 599-1168 + 1 800 344-1822 FAX + 1 800 344-3775 © 2012 Fire Protection Products, Inc. Description The Straight Pattern Fire Department Connection is Underwriters’ Laboratories listed and Factory Mutual Approved. Manufactured from solid brass* components to increase service life. The single clapper design features brass clapper and brass seats within a cast brass* body. The 21/2” swivels are pin lug design for ease of use and compatibility with local fire service districts. Swivel gaskets are included. Breakable caps or plugs should be installed to protect swivels and prevent debris from being accidently introduced into the water way. WWW.FPPI.COM Fire Department Connection Straight Pattern Size Range:One size fits bracing pipe 1"(25mm)thru 2"(50mm), Cooper B-Line 12 gauge (2.6mm)channel, and all structural steel up to 1/4"(31.7mm)thick. Material:Steel Function:Multi-functional attachment to structure or braced pipe fitting. Features:This product’s design incorporates a concentric attachment opening which is critical to the performance of structural seismic connections. NFPA 13 (2010) 9.3.5.8.4 indicates clearly that fastener table load values are based only on concentric loading. Mounts to any surface angle. Break off bolt head assures verification of proper installation. Installation:Fig.980 is the structural or transitional attachment component of a longitudinal or lateral sway brace assembly. It is intended to be combined with the "bracing pipe" and TOLCO "braced pipe" attachment, Fig. 1000, 1001, 2002, 4L, 4A or 4B to form a complete bracing assembly. NFPA 13 and/or OSHPD guidelines should be followed. To Install:Place the Fig. 980 onto the "bracing pipe". Tighten the set screw until the head breaks off. Attachment can pivot for adjustment to proper brace angle. Approvals:—Underwriters Laboratories Listed in the USA (UL)and Canada (cUL). Approved by Factory Mutual Engineering (FM). Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Note:Fig. 980 Swivel Attachment and Fig. 1001, Fig. 1000, Fig. 2002, Fig. 4A, Fig. 4B or Fig. 4L pipe clamps make up a sway brace system of UL Listed attachments and bracing materials which satisfies the requirements of Underwriters Laboratories and the National Fire Protection Association (NFPA) Finish:Plain, Electro-Galvanized or Stainless Steel. Contact B-Line for alternative finishes. Order By:Figure number and finish. US Patent Numbers Pat. #6,273,372, Pat. #6,517,030, Pat. #6,953,174, Pat. #6,708,930, Pat. #7,191,987, Pat. #7,441,730, Pat. #7,669,806 Eaton’s B-Line Business seismic bracing components are designed to be compatible only with other B-Line bracing components, resulting in a listed seismic bracing assembly. B-Line’s warranty for seismic bracing components will be the warranty provided in B-Line’s standard terms and conditions of sale made available by B-Line, except that, in addition to the other exclusions from B-Line’s warranty, Eaton’s B-line Business makes no warranty relating to B-Line’s seismic bracing components that are combined with products not provided by Eaton’s B-Line Business. Fig. 980 - Universal Swivel Sway Brace Attachment - 3/8”-16 to 3/4”-10 rods Fig. 980H - Universal Swivel Sway Brace Attachment - 7/8”-9 to 11/4”-7 rods Component of State of California OSHPD Approved Seismic Restraints System Seismic BracingPart Max. Design Max. Design Load** (FM)Approx. Number A B D* Load (cULus) 30°-44° 45°-59° 60°-74° 75°-90° Wt./100 in. (mm) in. (mm) in. (mm) lbs./(kN) lbs./(kN) lbs./(kN) lbs./(kN) lbs./(kN) lbs. (kg) 980-3/8 51/4”(133.3)17/8”(47.6)13/32”(10.3)149 (67.6) 980-1/2 51/4”(133.3)17/8”(47.6)17/32”(13.5)148 (67.1) 980-5/8 51/4”(133.3)17/8”(47.6)11/16”(17.5)147 (66.7) 980-3/4 51/4”(133.3)17/8”(47.6)13/16”(20.5)2015 1320 1970 2310 2550 146 (66.2) 980H-7/8 63/4”(171.4)31/2”(88.9)15/16”(23.8)(8.96) (5.87) (8.76) (10.27) (11.34) 402 (182.3) 980H-1 63/4”(171.4)31/2”(88.9)11/16”(27.0)400 (181.4) 980H-11/8 63/4”(171.4)31/2”(88.9)13/16”(30.2)397 (180.1) 980H-11/4 63/4”(171.4)31/2”(88.9)15/16”(33.3)390 (176.9) * Mounting attachment hole size. ** Installed with 1” or 11/4” Schedule 40 brace pipe. B B D D A A 980 980H Mounting Hardware Is Not Included Set Screw Included All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. Seismic Bracing 182Pipe Hangers & Supports Seismic BracingSize Range:Pipe size to be braced: 1"(25mm)thru 8"(200mm)IPS. * Pipe size used for bracing: 1"(25mm)and 11⁄4"(32mm)Schedule 40 IPS. Material:Steel Function:For bracing pipe against sway and seismic disturbance. The pipe attachment component of a sway brace system: Fig. 1001 is used in conjunction with a Fig. 900 Series fitting and joined together with bracing pipe per NFPA 13, forming a complete sway brace assembly. Features:Can be used to brace schedules 7 through 40 IPS. Field adjustable, making critical pre-engineering of bracing pipe length unnecessary. Unique design requires no threading of bracing pipe. Can be used as a component of a four-way riser brace. Comes assembled and ready for installation. Fig. 1001 has built-in visual verification of correct installation. See installation note below. Installation Note:Position Fig. 1001 over the pipe to be braced and tighten two hex head cone point set screws until heads bottom out. A minimum of 1"(25mm)pipe extension is recommended. Brace pipe can be installed on top or bottom of pipe to be braced. Approvals:Underwriters Laboratories Listed in the USA (UL) and Canada (cUL). Approved by Factory Mutual Engineering (FM). Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines, OPA-0300-10. Finish:Plain or Electro-Galvanized. Contact B-Line for alternative finishes and materials. Order By:Indicate pipe size to be braced followed by pipe size used for bracing, figure number and finish. Important Note:Fig. 1001 is precision manufactured to perform its function as a critical component of a complete bracing assembly. To ensure performance, the UL Listing requires that Fig. 1001 must be used only with other TOLCO bracing products. Fig. 1001 - Sway Brace Attachment Component of State of California OSHPD Approved Seismic Restraints System FM Design Load - For Sch. 7, Sch. 10, & Sch. 40 Pipe Pipe Part Number & Approx. Wt./100 Allowable Horizontal Capacity (lbf) Per Installation 1, 2, 3 Size 1” (24mm)Brace Pipe 1 1/4” (32mm)Brace Pipe 30°-44° 45°-59° 60°-74° 75°-90° in. (mm) Lbs. (kg) Lbs. (kg) Lbs. (kN) Lbs. (kN) Lbs. (kN) Lbs. (kN) 1”(25)1001-1 X 1 100.0 (45.3)1001-1 X 11/4 118.0 (53.5)1800 (8.00)2550 (11.34)3120 (13.88)3490 (25.52) 11/4”(32)1001-11/4 X 1 100.0 (45.3)1001-11/4 X 11/4 114.0 (51.7)1230 (5.47)1740 (7.74)2140 (9.52)2380 (10.58) 11/2”(40)1001-11/2 X 1 100.0 (45.3)1001-11/2 X 11/4 115.0 (52.1)1230 (5.47)1740 (7.74)2140 (9.52)2380 (10.58) 2”(50)1001-2 X 1 108.0 (49.0)1001-2 X 11/4 121.0 (54.9)1230 (5.47)1740 (7.74)2140 (9.52)2380 (10.58) 21/2”(65)1001-21/2 X 1 138.6 (62.8)1001-21/2 X 11/4 160.4 (72.7)800 (3.56)1130 (5.02)1380 (6.14)1540 (6.85) 3”(80)1001-3 X 1 147.2 (66.7)1001-3 X 11/4 168.7 (76,5)850 (3.78)1200 (5.34)1470 (6.54)1640 (7.29) 4”(100)1001-4 X 1 160.9 (73.0)1001-4 X 11/4 182.4 (82.7)850 (3.78)1200 (5.34)1470 (6.54)1640 (7.29) 6”(150)1001-6 X 1 190.0 (86.2)1001-6 X 11/4 211.4 (95.9)510 (2.27)730 (3.25)890 (3.96)990 (4.40) 8”(200)1001-8 X 1 217.4 (98.6)1001-8 X 11/4 238.8 (108.3)510 (2.27)730 (3.25)890 (3.96)990 (4.40) Set Screws Included 1 FM Approved when used with 1 or 11/4 inch NPS Schedule 40 GB/T 3091,EN 10255H, or JIS G3451 steel pipe as the brace member. 2 Load rating for LW above refers to FM Approved Lightwall Pipe commonly referred to as “Schedule 7”. These ratings may also be applied when EN 10220 and GB/T 8163 steel pipe. 3 Load rating for Schedule 10 above may be applied to GB/T 3092,EN 10255M and H, or JIS G3454, FM Approved Thinwall, or Schedule 40 steel pipes. Note: See UL load ratings in UL Listed Design Load chart shown under drawing. All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. Seismic Bracing Pipe Hangers & Supports189 Pipe UL Listed Design Load - Lbs. Size For Brace Pipe Size 1” / 11/4” Sch. 7 Sch. 10 Sch. 40 in. (mm)1” / 11/4” 1” / 1 1/4” 1” / 1 1/4” 1”(25)-- / -- 1000 / 1000 1000 / 1000 11/4”(32)1000 / 1000 1000 / 1000 1000 / 1000 11/2”(40)1000 / 1000 1500 / 1500 1500 / 1500 2”(50)1000 / 1000 2015 / 2015 2015 / 2015 21/2”(65)1600 / 1600 2015 / 2765 2015 / 2765 3”(80)1600 / 1600 2015 / 2765 2015 / 2765 4”(100)1600 / 1600 2015 / 2765 2015 / 2765 6”(150)1600 / 1600 2015 / 2765 2015 / 2765 8”(200)1600 / 1600 2015 / 2765 2015 / 2765 Revised 5/9/2014 PICTORIAL TABLE OF CONTENTS www.anvilintl.com8 Cast Iron CAST IRON THREADED FITTINGS – CLASS 125 (STANDARD) Fig. 351 90˚ Elbow Size Range: 1/4" thru 8" Page 37 Fig. 371 90˚ Elbow - Flange & Screw Size Range: 21/2" thru 6" Page 37 Fig. 356 & 356R 45˚ Elbow (Straight & Reducing) Size Range: 1/4" thru 8" (Straight) 1" x 1/2" (Reducing) Page 38 Fig. 356A 221/2˚ Elbow Size Range: 3/4" thru 21/2" Page 38 Fig. 352 90˚ Reducing Elbow Size Range: 1/2" x 1/4" thru 6" x 5" Page 39 Fig. 358 Tee Size Range: 1/4" thru 8" Page 40 Fig. 359 Reducing Tee Size Range: 1/2" x 1/2" x 1/4" thru 6" x 6" x 5" Page 40 - 44 Fig. 360 Cross Size Range: 1/2" thru 6" Page 45 Fig. 361 Cross Reducing Size Range: 1" x 1" x 3/4" x 3/4" thru 4" x 4" x 2" x 2" Page 45 Fig. 366 Screwed Hex Coupling Size: 1" Page 46 Fig. 487 Flanged Union Gasket Type Size Range: 1/2" thru 8" Page 46 Fig. 367 Concentric Reducer Size Range: 3/4" x 1/2" thru 8" x 6" Page 47 Fig. 368 Eccentric Reducer Size Range: 3/4" x 1/2" thru 6" x 4" Page 48 Fig. 383 Hex Bushing Size Range: 11/2" x 1/4" thru 10" x 8" Page 49 - 50 Fig. 385 Face Bushing Size Range: 3" x 2" thru 4" x 3" Page 50 Fig. 387 Square Head Plugs, Cored Size Range: 3/4" thru 4" Page 51 Fig. 388 Square Head Plugs, Solid Size Range: 1/2" thru 31/2" Page 51 Fig. 389 Bar Plugs, Cored Size Range: 4" thru 8" Page 51 Fig. 380 Bar Plugs, Solid Size Range: 4" thru 8" Page 51 Fig. 390 Countersunk Plugs Size Range: 1" thru 4" Page 51 Fig. 381 Cap Size Range: 21/2" thru 8" Page 51 Fig. 370 Locknut Size Range: 21/2" thru 4" Page 52 CAST IRON THREADED FITTINGS – CLASS 250 (EXTRA HEAVY) Fig. 421 90˚ Elbow Size Range: 1/4" thru 3" Page 52 Fig. 424 45˚ Elbow Size Range: 1/2" thru 21/2" Page 52 Fig. 425 Tee Size Range: 1/4" thru 4" Page 53 Fig. 426 Reducing Tee Size Range: 3/4" x 3/4" x 1/2" thru 2" x 2" x 11/2" Page 53 PF-11.13 Bull Moose Tube’s®%DDY&LOW® is a specially engineered REPLACEMENTFOR3CHEDULE offering better flow characteristics WHILEPROVIDINGDESIGNmEXIBILITY4HISPRODUCTIS&-APPROVED ASWELLAS5,,ISTEDFOR53AND#ANADA for roll grooving and welding. !SANADDEDBENElT ITISMORE ECONOMICALTOUSETHAN3CHEDULE DUETOREDUCEDDELIVERYCOSTSANDEASEOFHANDLING&URTHERMORE %DDY&LOWS®LARGER)$PROVIDES ANOPPORTUNITYFORDOWNSIZING and further cost savings.EDDY FLOW® THE COST EFFECTIVE REPLACEMENT FOR SCHEDULE 10#LARKSON2OAD#HESTERlELD -/'ERALD -/ +ENT 7! #ASA'RANDE !: $ALLAS 48Masury, OH&OR!DDITIONAL)NFORMATION#ONTACT   /R&ROM#ANADA#ALL  www.bullmoosetube.comsales@bullmoosetube.comPIPE PREPARATION&ORPROPEROPERATION ALLPIPESURFACESSHOULDBECLEANEDPRIORTOINSTALLATION)NORDERTOPROVIDEALEAK TIGHTSEATFORTHEGASKET PIPESURFACESSHOULDBEFREEFROMINDENTATIONSANDPROJECTIONSFROMTHEENDOFTHEPIPETOTHEGROOVE!LLLOOSEPAINT SCALE DIRT CHIPS GREASE ANDRUSTMUSTBEREMOVEDPRIORTOINSTALLATION&AILURETOTAKETHESEIMPORTANTSTEPSMAYRESULTINIMPROPERCOUPLINGASSEMBLY CAUSINGLEAKAGE!LSO CHECKTHEMANUFACTURERSINSTRUCTIONSFORTHESPECIlClTTINGUSED 1-1/4 1.660 1.530 1.98 1.222 2.019 61 1-1/2 1.900 1.728 3.44 1.844 2.860 61 2 2.375 2.203 2.78 2.330 3.982 37 2-1/2 2.875 2.705 1.66 2.809 5.299 30 3 3.500 3.334 1.00 3.361 7.144 19 4 4.500 4.310 1.00 4.968 11.290 19ADVANTAGES OF BULL MOOSE TUBE® EDDY FLOW® s#ERTIlEDTO!34-!AND!4YPE% 'RADE!s&-APPROVEDFORROLLGROOVINGANDWELDINGFORUSEINWETSYSTEMSs5,,ISTEDFOR53AND#ANADA FORJOININGBYWELDINGORBYLISTEDRUBBERGASKETEDlTTINGSFORUSEINWET DRY PREACTION ANDDELUGETYPE sprinkler systems.s,IGHTWEIGHTnSAVESSHIPPINGCOSTSANDOFFERSEASIERHANDLINGs#ANBEUSEDWITHROLLGROOVEDCOUPLINGSORWELDEDOUTLETSFORPRESSURESUPTOPSIs#ANBESUPPLIEDROLLGROOVEDORPLAINENDs#ANBEHOTDIPPEDGALVANIZEDTOMEET&-S5,REQUIREMENTFORDRYSYSTEMSs3UPPLIEDWITH%$$9'5!2$))®-)#PREVENTATIVECOATING%$$9&,/7®)$ 7%)'(4 0%2&4.033):%). /$). %$$9&,/7® CRR*"5.$,% 3):%7!4%2&),,%$WT. #ORROSION2ESISTANCE2ATIOPERLATEST5,$IRECTORY,ISTING7 Bull Moose Tube® is a customer focused, growth oriented manufacturer and marketer of tubular products, where success is based on a commitment to meeting the customer’s perception of quality.Our strength resides in our people working together to satisfy customers and to promote business growth by achieving superior financial performance. www.BullMooseTube.com sales@bullmoosetube.com 800.325.4467ull Moogrowth marketer osuccess isto meetiof qualOur woanaSCHEDULE 10 SCHEDULE 40 EDDYTHREAD 40 EDDYLITE EDDY FLOWULTRA EDDY2 Bull Moose Tube’s® “Eddy Pipe®” brand sprinkler pipe is produced to meet sprinkler pipe standards and applications.EDDY PIPE® THE SUPERIOR SPRINKLER PIPEADVANTAGES OF BULL MOOSE TUBE® EDDY PIPE® FAMILYs!LLPIPEPRODUCTSARE5,,ISTEDFOR53AND#ANADA ANDHAVEBEENAPPROVEDBY&ACTORY-UTUALs%XCELLENTPRODUCTIONANDCOATINGCAPABILITIES TIGHTERTOLERANCES ANDOURUNIQUESTEELPROPERTIESMAKEOURPIPEEXCELLENTFOR roll grooving, welding, threading, and plain end fittings.s!LLPRODUCTSARECERTIlEDTO!34-!AND!4YPE% 'RADE!s!VAILABLEINSPECIlCCUTTOORDERLENGTHSFROMREGULARMILLROLLINGSs-OREPOPULARSIZESAVAILABLEWITHCOATINGORBAREs5LTRA%DDY® %DDY&LOW®, Eddylite®, and Eddythread 40® offer cost savings along with superior hydraulics without compromising service life.s3PRINKLERPIPEINVENTORYSTOCKEDIN-ASURY /HIO'ERALD -ISSOURI #ASA'RANDE !RIZONA+ENT 7ASHINGTONAND$ALLAS 4EXASs!LL"ULL-OOSEBLACK SPRINKLERPIPEINCLUDESOUREXCLUSIVE%$$9'5!2$II®-)#PREVENTATIVECOATINGs"ULL-OOSE4UBE®SPRINKLERPIPEIS&"#TM compatible. PRODUCTS s3CHEDULEAND3CHEDULE&-APPROVEDAND5,LISTED sprinkler pipe.s%DDYTHREAD®,IGHTTHREADABLE3CHEDULEREPLACEMENT WITHCORROSIONRESISTANCERATIOOFs%DDYLITE®,IGHTWALLTHREADABLEWITHSTANDARDOUTSIDEDIAMETERs%DDY&LOW®#OSTEFFECTIVEREPLACEMENTFOR3CHEDULEs5LTRA%DDY®,IGHTWALLROLLGROOVABLEPIPE s"ULL-OOSEGALVANIZEDSTEELSPRINKLERPIPEISHOTDIPPED GALVANIZEDTOMEET!34-!STANDARDS!LLPRODUCTSARE STENCILLEDTOMEET&-5,SPECIlCATIONS PROTECTIONs%DDY'UARD))®Bull Moose Tube® is producing product that can resist BACTERIOLOGICALGROWTHEVENAFTERMULTIPLERINSE OUTS9OUKNOW -)#CORROSIONCANIMPACTYOURINSTALLATIONANDYOURPROPERTY3PECIFY Bull Moose Tube®h%DDY'UARD))®” and feel comfortable knowing that you are getting Eddy Pipe® product you trust with the bacteria RESISTANCEYOUNEED%DDY'UARD))®IS.&0!AND.&0!2SYSTEM COMPATIBLEFORUSEINHYBRIDSYSTEMSASWELLAS&-APPROVED!LLINFORMATIONCONTAINEDHEREINISACCURATEASKNOWNATTHETIMEOFPUBLICATION Bull Moose Tube® reserves the right to change product specifications without notice and without incurring obligation.e.$3 Bull Moose Tube’s®3CHEDULE AND3CHEDULEARE&-!PPROVEDAND5,,ISTEDFOR53AND#ANADA EVENTHOUGHTHESEproducts do not require separate approvals and listings. Bull Moose Tube® made the decision to have them approved and listed. /UR3CHEDULEAND3CHEDULEHAVEAPRESSURERATINGOF03)and have been through the same rigorous testing as our other fine PIPEPRODUCTS3CHEDULECANBEsupplied roll grooved or plain end. Bull Moose Tube’s®3CHEDULE AND3CHEDULEPIPESAREHOTDIPPEDGALVANIZEDTOMEET!34-!STANDARDS!LLPRODUCTSARESTENCILLEDTOMEET&-5, specifications.SCHEDULE 10 & SCHEDULE 40 FM APPROVED AND UL LISTED SPRINKLER PIPE)$). 7%)'(4&4"5.$,%3):%./-).!,0)0%3):%). /$). CRR**7!4%2&),,%$7%)'(4#LARKSON2OAD#HESTERlELD -/'ERALD -/ +ENT 7! #ASA'RANDE !: $ALLAS 48Masury, OH&OR!DDITIONAL)NFORMATION#ONTACT   /R&ROM#ANADA#ALL  www.bullmoosetube.comsales@bullmoosetube.com)$). 7%)'(4&4"5.$,%3):%./-).!,0)0%3):%). /$). 1 1.315 1.097 15.27 1.41 lbs/ft 1.820 91 1-1/4 1.660 1.442 9.91 1.81 lbs/ft 2.518 61 1-1/2 1.900 1.682 7.76 2.09 lbs/ft 3.053 61 2 2.375 2.157 6.27 2.64 lbs/ft 4.223 37 2-1/2 2.875 2.635 4.92 3.53 lbs/ft 5.893 30 3 3.500 3.260 3.54 4.34 lbs/ft 7.957 19 4 4.500 4.260 2.50 5.62 lbs/ft 11.796 19 1 1.315 1.049 1.00 1.68 lbs/ft 2.055 70 1-1/4 1.660 1.380 1.00 2.27 lbs/ft 2.918 51 1-1/2 1.900 1.610 1.00 2.72 lbs/ft 3.602 44 2 2.375 2.067 1.00 3.66 lbs/ft 5.114 30 2-1/2* 2.875 2.468 1.00 5.80 lbs/ft 7.875 30 3* 3.500 3.068 1.00 7.58 lbs/ft 10.783 19 4* 4.500 4.026 1.00 10.80 lbs/ft 16.316 19SCHEDULE 10 PIPE SPECIFICATIONSSCHEDULE 40 PIPE SPECIFICATIONSPIPE PREPARATION&ORPROPEROPERATION ALLPIPESURFACESSHOULDBECLEANEDPRIORTOINSTALLATION)NORDERTOPROVIDEALEAK TIGHTSEATFORTHEGASKET PIPESURFACESSHOULDBEFREEFROMINDENTATIONSANDPROJECTIONSFROMTHEENDOFTHEPIPETOTHEGROOVE!LLLOOSEPAINT SCALE DIRT CHIPS GREASE ANDRUSTMUSTBEREMOVEDPRIORTOINSTALLATION&AILURETOTAKETHESEIMPORTANTSTEPSMAYRESULTINIMPROPERCOUPLINGASSEMBLY CAUSINGLEAKAGE!LSO CHECKTHEMANUFACTURERSINSTRUCTIONSFORTHESPECIlClTTINGUSED CRR**7!4%2&),,%$7%)'(4 /NLYAVAILABLEIN#ASA'RANDE !: #ORROSION2ESISTANCE2ATIOPERLATEST5,$IRECTORY,ISTING4 Bull Moose Tube’s® Eddythread 40® is a lightweight replacement for 3CHEDULETHATHASA#ORROSION2ESISTANCE2ATIOOFEDDYTHREAD 40® A LIGHTWEIGHT SCHEDULE 40 REPLACEMENT PIPEADVANTAGES OF BULL MOOSE TUBE® EDDYTHREAD 40®s(ASA#ORROSION2ESISTANCE2ATIOOFs(ASAPRESSURERATINGOFPSIs)SLIGHTERWEIGHTTHAN3CHEDULEs)SAPPROVEDBY&ACTORY-UTUALANDLISTEDBY5NDERWRITERS,ABORATORIESs)SPRODUCEDINACCORDANCETO!34-!AND!4YPE% 'RADE!s#ANBEUSEDWITHSTANDARD3CHEDULETHREADEDlTTINGS COUPLINGS ANDVALVESs)SPRODUCEDFROMSTEELWITHEXCELLENTPROPERTIESOFSTRENGTHANDTHREADABILITYs#ANBEUSEDINWET PREACTION ANDDELUGETYPESPRINKLERSYSTEMSs#ANBEHOTDIPPEDGALVANIZEDTOMEET&-SREQUIREMENTFORDRYSYSTEMSs/FFERSLOWERFREIGHTCOSTSs3UPPLIEDWITH%$$9'5!2$))®-)#PREVENTATIVECOATING#LARKSON2OAD#HESTERlELD -/'ERALD -/ +ENT 7! #ASA'RANDE !: $ALLAS 48Masury, OH&OR!DDITIONAL)NFORMATION#ONTACT   /R&ROM#ANADA#ALL  www.bullmoosetube.comsales@bullmoosetube.com)$). 7%)'(4,"&4"5.$,%3):%./-).!,0)0%3):%). /$). CRR*7!4%2&),,%$7%)'(4 1 1.295 1.083 1.00 1.461 1.860 70 1-1/4 1.650 1.418 1.00 2.070 2.754 51 1-1/2 1.900 1.654 1.00 2.547 3.468 44 2 2.375 2.123 1.00 3.308 4.842 30EDDYTHREAD 40® SPECIFICATIONSPIPE PREPARATION&ORPROPEROPERATION ALLPIPESURFACESSHOULDBECLEANEDPRIORTOINSTALLATION)NORDERTOPROVIDEALEAK TIGHTSEATFORTHEGASKET PIPESURFACESSHOULDBEFREEFROMINDENTATIONSANDPROJECTIONSFROMTHEENDOFTHEPIPETOTHEGROOVE!LLLOOSEPAINT SCALE DIRT CHIPS GREASE ANDRUSTMUSTBEREMOVEDPRIORTOINSTALLATION&AILURETOTAKETHESEIMPORTANTSTEPSMAYRESULTINIMPROPERCOUPLINGASSEMBLY CAUSINGLEAKAGE!LSO CHECKTHEMANUFACTURERSINSTRUCTIONSFORTHESPECIlClTTINGUSED #ORROSION2ESISTANCE2ATIOPERLATEST5,$IRECTORY,ISTING5 Replacement Parts A3008-00 Retard Mechanism A77-01-02 Terminal Block 546-7000 Cover Tamper Switch Kit WFDW Cover Wrench WFDN4 Replacement gasket kit New WFD30-2 models install in 2″ hole sizes UL models are NEMA 4 rated Sealed retard mechanism assures that the retard is not contaminated by dust and dirt when the cover is removed Visual switch activation permits installer to accurately set retard under noisy conditions Rugged, dual SPDT switches are enclosed in a durable terminal block Accommodates up to 12 AWG wire 100% synchronization activates both alarm panel and local bell simultaneously System Sensor’s WFD series is compatible with schedule 10 through 40 steel pipe, sizes 2″through 8″, and can be mounted in a vertical or horizontal position. Robust Construction.The WFD series consists of a rugged, NEMA 4 rated enclosure. Designed for both indoor and outdoor use, the WFD series operates across a wide temperature range, from 32°F to 120°F. Reliable Performance.UL listed models are equipped with tamper resistant cover screws to prevent unauthorized entry. Inside, two sets of SPDT (Form C) synchronized switches are enclosed in a durable terminal block to assure reliable performance. False Alarm Immunity.The WFD series incorporates a mechanical retard fea- ture, which minimizes the risk of false alarm due to pressure surges or air trapped in the sprinkler system. In addition, the mechanical retard’s unique sealed design is immune to dust and other contaminants. Simplified Operation.The WFD series is designed to simplify installation. Two conduit openings permit easy attachment to the local alarm system. The retard mechanism and dual SPDT switches are field-replaceable. UL ULC/Canadian Models Models WFD20 WFD20A WFD25 WFD25A WFD30-2 WFD30-2A WFD35 WFD35A WFD40 WFD40A WFD50 WFD50A WFD60 WFD60A WFD80 WFD80A Product Overview APPROVED WFD40 WFD Series Waterflow Detector SPRINKLER SYSTEMS MONITORING Part Number Description A3008-00 Retard mechanism A77-01-02 Terminal block 546-7000 Tamper proof switch kit WFDW Tamper proof wrench for cover WFDN4 Gasket kit Engineering Specifications Vane-type waterflow detectors shall be installed on system piping as designated on the drawing and/or as specified herein. Detectors shall mount on any clear pipe span of the appropriate nominal size, either a vertical upflow or horizontal run, at least 6″from any fittings which may change water direction, flow rate, or pipe diameter or no closer than 24″from a valve or drain. Detectors shall have a sensitivity in the range of 4 to 10 gallons per minute and a static pressure rating of 450 psi* for 2″- 8″ pipes. The detector shall respond to waterflow in the specified direction after a preset time delay which is field adjustable. The delay mechanism shall be a sealed mechanical pneumatic unit with visual indication of actuation. The actuation mechanism shall include a polyethylene vane inserted through a hole in the pipe and connected by a mechanical linkage to the delay mech- anism. Outputs shall consist of dual SPDT switches (Form C contacts). Two conduit entrances for standard fittings of commonly used electrical conduit shall be provided on the detectors. A grounding provision is provided. Unless noted, enclosures shall be NEMA 4 listed by Underwriters Laboratories Inc. All detectors shall be listed by Underwriters Laboratories Inc. for indoor or out- door use. Static Pressure Rating 450 PSI* Triggering Threshold Bandwidth (Flow Rate) 4-10 GPM Maximum Surge 18 Feet Per Second (FPS) Compatible Pipe: Steel water pipe, schedule 10 through 40 Contact Ratings Two sets of SPDT (Form C) 10.0 A, 1/2 HP @ 125/250 VAC 2.5 A @ 6/12/24 VDC Overall Dimensions Installed: ©2002 System Sensor. The company reserves the right to change product specifications without notice. A05-0180-008•04/02•#947 Ordering Information UL Model Numbers ULC/Canadian Model Numbers Pipe Size Hole Size WFD20 WFD20A 2 ″11⁄4″ WFD25 WFD25A 2 1⁄2″11⁄4″ WFD30-2 WFD30-2A 3″2″ WFD35 WFD35A 31⁄2″11⁄4″ WFD40 WFD40A 4″2″ WFD50 WFD50A 5″2″ WFD60* WFD60A 6″2″ WFD80* WFD80A 8″2″ *Maximum pressure rating 400 psi as approved by Factory Mutual. Conduit Entrances Two openings for 1⁄2″conduit. One open, one knock-out type Operating Temperature Range 32ºF to 120ºF (0ºC to 49ºC) Enclosure Rating* NEMA 4 - suitable for indoor/outdoor use Cover Tamper Switch Standard with ULC models Optional for UL models, part no. 546-7000 Shipping Weight WFD20: 4.2 lbs. WFD40: 5.2 lbs. WFD25: 4.3 lbs. WFD50: 6.3 lbs. WFD30-2: 4.5 lbs. WFD60: 6.8 lbs. WFD35: 4.7 lbs. WFD80: 7.5 lbs. Service Use Automatic Sprinkler: NFPA-13 One or Two Family Dwelling: NFPA 13D Residential Occupancies up to 4 Stories: NFPA 13R National Fire Alarm Code: NFPA-72 Warranty 3 Years U.S. Patent Numbers 3,845,259 4,782,333 5,213,205 Standard Specifications 3.0″ 3.75″ Pipe saddle U bolt nut Width: See Table Plastic vane Pipe U bolt 1.6″ Model WFD20 WFD25 WFD30-2 WFD35 Width 4.6″ 4.6″ 5.2″ 5.7″ Model WFD40 WFD50 WFD60 WFD80 Width 6.8″ 7.8″ 9.0″ 10.8″ System Sensor Sales and Service System Sensor Headquarters 3825 Ohio Avenue St. Charles, IL 60174 Ph: 800/SENSOR2 Fx: 630/377-6495 Documents-on-Demand 800/736-7672 x3 www.systemsensor.com System Sensor Canada Ph: 905.812.0767 Fx: 905.812.0771 System Sensor Europe Ph: 44.1403.276500 Fx: 44.1403.276501 System Sensor in China Ph: 86.29.524.6253 Fx: 86.29.524.6259 System Sensor in Singapore Ph: 65.6273.2230 Fx: 65.6273.2610 System Sensor – Far East Ph: 85.22.191.9003 Fx: 85.22.736.6580 System Sensor – Australia Ph: 613.54.281.142 Fx: 613.54.281.172 System Sensor – India Ph: 91.124.637.1770 x.2700 Fx: 91.124.637.3118 Material Specifications: Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. Housing Coating: Orange enamel (North America, Asia Pacific) Red enamel (Europe) Optional: Hot dipped galvanized Gasket: Grade “E” EPDM (Type A) FireLock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories of Canada Limited, and Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services within the rated working pressure. Bolts/Nuts: Zinc electroplated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. Approvals/Listings: See Victaulic Publication 10.01 for more details. Product Description: The FireLock EZ Style 009N Installation-ReadyTM Rigid Coupling is for use in the fire protection market. The coupling’s unique design eliminates loose parts, promotes consistent installation and provides substantial gains in productivity. IMPORTANT FireLock EZ Style 009N couplings are recommended for use ONLY on fire protection systems. PATENTED FireLock EZ® Rigid Coupling Style 009N 10.64 1 victaulic.com | Couplings | Rigid | Style 009N | Publication 10.64 10.64 7072 Rev F Updated 03/2014 © 2014 Victaulic Company. All rights reserved. Job/Owner System No. Location Contractor Submitted By Date Engineer Spec Section Paragraph Approved Date Listings/Approvals 1 Nominal Size cULus FM Vds LPCB inches mm Sch. 5 psi kPa Sch. 10 psi kPa Sch. 40 psi kPa Sch. 5 psi kPa Sch. 10 psi kPa Sch. 40 psi kPa psi kPa psi kPa 1 1/4 232 365 365 175 363 363 365 365 32 1600 2517 2517 1205 2502 2502 2517 2517 1 1/2 232 365 365 175 363 363 365 365 40 1600 2517 2517 1205 2502 2502 2517 2517 2 363 365 365 175 363 363 365 365 50 2502 2517 2517 1205 2502 2502 2517 2517 2 1/2 N/A 365 365 175 363 363 365 365 65 2517 2517 1205 2502 2502 2517 2517 76.1 mm N/A 3652 N/A N/A 3633 N/A 365 365 2517 2502 2517 2517 3 N/A 365 365 175 363 363 365 365 80 2517 2517 1205 2502 2502 2517 2517 4 N/A 365 365 175 363 363 365 365 100 2517 2517 1205 2502 2502 2517 2517 108.0 mm N/A N/A N/A N/A 363 363 N/A N/A25022502 5 N/A 290 365 N/A 363 363 N/A N/A1252000251725022502 133.0 mm Refer to Submittal 10.61 139.7 mm Refer to Submittal 10.61 165.1 mm Refer to Submittal 10.61 6 N/A 290 365 N/A 363 363 N/A N/A1502000251725022502 8 N/A 290 365 N/A 363 363 N/A N/A2002000251725022502 1 Listed/Approved for wet and dry pipe systems (> –40°F/–40°C) for continuous use in freezing conditions, use of silicone gaskets is recommended. Please refer to the Victaulic Installation Manual (I-009N/009H) for details concerning when supplemental lubrication is required. 2 cULus listed for DIN 2458 2.6 mmm pipe wall. 3 FM approved for BS 1387 Medium 3.6 mm pipe wall. The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Pipe Size Pressure Rating Pipe Size Pressure Rating Pipe Size Pressure Rating Sch. inches cULus psi kPa FM psi kPa Sch. inches cULus psi kPa FM psi kPa Sch. inches cULus psi kPa FM psi kPa BLT 1 1/4 – 2 300 365 EZT 1 1/4 – 2 300 365 MT 1 1/4 – 2 300 365 2068 2517 2068 2517 2068 2517 DF 1 1/4 – 4 300 365 FF 1 1/4 – 4 300 365 MLT 1 1/4 – 2 N/A 365 2068 2517 2068 2517 2517 DT 1 1/4 – 2 300 365 FLF 1 1/4 – 4 N/A 365 ST 1 1/4 – 2 N/A 365 2068 2517 2517 2517 EF 1 1/4 – 4 175 175 FLT 1 1/4 – 2 N/A 365 STF 1 1/4 – 4 N/A 365 1206 1206 2517 2517 EL 1 1/4 – 2 300 365 FLTL 1 1/4 – 2 N/A 365 TF 2 1/4 – 4 N/A 365 2068 2517 2517 2517 ET40 1 1/4 – 2 300 365 GL 1 1/4 – 2 300 365 WLS 1 1/4 – 2 300 365 2068 2517 2068 2517 2068 2517 EZF 3 – 4 300 365 MF 1 1/4 – 4 300 365 WST 1 1/4 – 2 N/A 365 2068 2517 2068 2517 2517 XL 1 1/4 – 2 300 365 2068 2517 Speciality Pipe victaulic.com | Couplings | Rigid | Style 009N | Publication 10.64 2 10.64 7072 Rev F Updated 03/2014 © 2014 Victaulic Company. All rights reserved. victaulic.com Installation Reference should always be made to the I-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. Warranty Refer to the Warranty section of the current Price List or contact Victaulic for details. Note This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. Trademarks Victaulic, FireLock EZ, and Installation-Ready are registered trademarks of Victaulic Company. Style 009N Pre-Assembled (Push On Condition) Style 009N Dimensions: Nominal Size Actual Outside Diameter Maximum Working Pressure 1 Maximum End Load 1 Allow. Pipe End Separation 2 Bolt/Nut 3 Dimensions Approx. Weight Each Pre-assebled (Push On Condition)Joint Assembled X Y X Y Z inches mm inches mm psi kPa lbs. N inches mm (No.) size inches inches mm inches mm inches mm inches mm inches mm lbs. kg 1 1/4 1.660 365 790 0.10 2 – 3/8 × 2 M – 10 x 2 3.10 4.90 2.70 4.90 1.92 1.4 32 42.4 2517 3514 2.54 79 124 69 124 49 0.7 1 1/2 1.900 365 1035 0.10 2 – 3/8 × 2 M – 10 x 2 3.30 5.10 3.00 5.10 1.92 1.5 40 48.3 2517 4604 2.54 84 129 76 129 49 0.7 2 2.375 365 1616 0.12 2 – 3/8 × 2 M – 10 x 2 3.90 5.60 3.50 5.60 1.95 1.9 50 60.3 2517 7193 3.05 99 142 89 142 50 0.9 2 1/2 2.875 365 2370 0.12 2 – 3/8 × 2 1/2 M – 10 x 2 1/2 4.50 6.10 4.00 6.10 1.95 2.1 65 73.0 2517 10542 3.05 114 155 102 155 50 1.0 76.1 mm 3.000 365 2580 0.12 2 – 3/8 × 2 1/2 M – 10 x 2 1/2 4.56 6.00 4.05 6.06 1.94 2.1 76.1 2517 11476 3.05 115.7 152.5 102.8 153.9 49.2 1.0 3 3.500 365 3512 0.12 2 – 3/8 × 2 1/2 M – 10 x 2 1/2 5.10 6.70 4.60 6.70 1.95 2.3 80 88.9 2517 15622 3.05 129 170 117 170 50 1.0 4 4.500 365 5805 0.17 2 – 3/8 × 2 1/2 M – 10 x 2 1/2 5.95 7.80 5.54 7.47 2.14 2.9 100 114.3 2517 25822 4.32 151 199 141 190 55 1.3 108.0 mm 4.250 365 5175 0.17 2 – 3/8 × 2 1/2 5.56 7.39 5.28 7.36 2.14 3.1 108.0 2517 23020 4.318 141 1.88 134 187 54 1.4 5 5.563 365 5178 0.17 2 – 1/2 × 3 7.19 9.25 6.7 9.11 2.19 5.0 125 141.3 2000 23033 4.318 183 235 170 231 56 2.3 133.0 mm Refer to Submittal 10.61 139.7 mm Refer to Submittal 10.61 165.1 mm Refer to Submittal 10.61 6 6.625 365 9997 0.17 2 – 1/2 × 3 1/4 8.32 10.29 7.82 10.13 2.17 6.0 150 168.3 2000 44469 4.318 211 261 199 257 55 2.7 8 8.625 365 13730 0.17 2 – 5/8 × 4 10.89 13.31 10.22 13.1 2.5 11.4 200 219.1 1620 61074 4.318 277 338 260 333 64 5.2 1 Working Pressure and End Load are total, from all internal and external loads, based on standard weight (ANSI) steel pipe, standard roll or cut grooved in accordance with Victaulic specifications. See page 1 of this document for Listed/Approved ratings on other pipe. WARNING: FOR ONE TIME FIELD TEST ONLY, the Maximum Joint Working Pressure may be increased to 1 ½ times the figures shown in the chart on page 1, specific to pipe schedule and size. 2 The allowable pipe separation dimension shown is for system layout purposes only. FireLock EZ couplings are considered rigid connections and will not accommodate expansion or contraction of the piping system. 3 Number of bolts required equals number of housing segments. General Notes: NOTE: When assembling FireLock EZ couplings onto end caps, take additional care to make certain the end cap is fully seated against the gasket end stop. For FireLock EZ Style 009N couplings, use FireLock No. 006 end caps containing the “EZ” marking on the inside face or No. 60 end caps containing the “QV EZ” marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009N couplings. IMPORTANT: Gaskets intended for the Style 009 or Style 009V couplings cannot be used with the Style 009N coupling. There is no interchanging of gaskets or housings between coupling styles. Use Of Flushseal Gaskets For Dry Pipe Systems NOTE: FireLock EZ couplings are supplied with FireLock EZ Grade “E” Type A gaskets. These gaskets include an integral pipe stop, that once installed provides the similiar benefits as a FlushSeal gasket for dry pipe systems. It should be noted that standard Victaulic FlushSeal gaskets are not compatible and cannot be used with the FireLock EZ couplings. X ZY Style 009N Joint Assembled X ZY 10.64 7072 Rev F Updated 03/2014 © 2014 Victaulic Company. All rights reserved. victaulic.com 3 victaulic.com | Couplings | Rigid | Style 009N | Publication 10.64 Size Range:— 3/8"-16 Rod Attachment Material:Steel Function:Three recommended applications for this product: • May be used as a Branch Line Restraint for structural attachment to anchor bolt, beam clamp, etc. • May be used as an upper attachment with short hanger rod to omit seismic bracing. • May be used in a pitched or sloped roof application, to meet requirements of NFPA 13 (2010) 9.1.2.6. Approvals:Underwriters Laboratories Listed in the USA (UL)and Canada (cUL)to support up to 4" (100mm)pipe. Finish:Electro-Galvanized Weight: Approx. Wt./100 - 13.3 Lbs. (6.0kg) Order By:Part number Patent: #7,887,248 Fig. 75 - Swivel Attachment Fig. 78 All Steel Ceiling Plate Fig. 75 Swivel Attachment Fig. 75 Swivel Attachment Fig. 75 Swivel Attachment All Threaded Rod All Threaded Rod All Threaded Rod W-Beam Pitch e d R o of Fig. 25 Surge Restrainer Fig. 200 “Trimline” Adjustable Band Hanger May be used as a structural attachment component of a branch line restraint May be used as a upper attachment with short hanger rod to omit seismic bracing May be used with a pitched roof appli- cation, to meet requirements of NFPA 13 (2010) Sec. 9.1.2.5. B3100 Clevis Hanger Fig. 65 Reversible Beam ClampUpper AttachmentsAll dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. Upper Attachments Pipe Hangers & Supports219 Pipe HangersFig. 200 - “Trimline” Adjustable Band Hanger (B-Line B3170NF) Fig. 200F - “Trimline” Adjustable Band Hanger with Felt Lining for Copper Tubing (B-Line B3170NFF) Fig. 200C - “Trimline” Adjustable Band Hanger with Plastic Coated (B-Line B3170NFC) Size Range: Fig. 200 - 1/2” (15mm)thru 8” (200mm)pipe Material:Steel, Pre-Galvanized to G90 specifications Function:For fire sprinkler and other general piping purposes. Knurled swivel nut design permits hanger adjustment after installation. Features: •(1/2” (15mm)thru 2” (50mm)) Flared edges ease installation for all pipe types and protect CPVC plastic pipe from abrasion. Captured design keeps adjusting nut from separating with hanger. Hanger is easily installed around pipe. •(21/2” (65mm)thru 8” (200mm)) Spring tension on nut holds it securely in hanger before installation. Adjusting nut is easily removed. Approvals:Underwriters Laboratories listed (1/2” (15mm)thru 8” (200mm)) in the USA (UL)and Canada (cUL)for steel and CPVC plastic pipe and Factory Mutual Engineering Approved (3/4” (20mm)thru 8” (200mm)). Conforms to Federal Specifications WW-H-171E & A-A-1192A, Type 10 and Manufacturers Standardization Society ANSI/MSS SP-69 & SP-58, Type 10. Maximum Temperature:650°F (343°C) Finish:Pre-Galvanized. Stainless Steel materials will be supplied with (2) hex nuts in place of a knurl nut. Order By:Part number and pipe size ** Note:For metric hanger rod sizes add the metric rod size to the figure number. Example: 200M8-11/2 or 200M10-1 1/2 A B Fig. 200-1/2 to 200-2 Fig. 200-21/2 to 200-8 Pipe Size Rod Size A B Max. Rec. Load Approx. Wt./100 Part No.in. (mm) in. mm** in. (mm) in. (mm) lbs. (kN) lbs. (kg) 200-1/2 1/2"(15)3/8"-16 M8 or M10 3 1/8"(79.4)25/8"(66.7)400 (1.78)11 (5.0) 200-3/4 3/4"(20)3/8"-16 M8 or M10 3 1/8"(79.4)21/2"(63.5)400 (1.78)11 (5.0) 200-1 1"(25)3/8"-16 M8 or M10 3 3/8"(85.7)25/8"(66.7)400 (1.78)12 (5.5) 200-11/4 11/4"(32)3/8"-16 M8 or M10 3 3/4"(94.0)27/8"(73.0)400 (1.78)13 (5.9) 200-11/2 11/2"(40)3/8"-16 M8 or M10 3 7/8"(98.4)27/8"(73.0)400 (1.78)14 (6.4) 200-2 2"(50)3/8"-16 M8 or M10 4 1/2"(114.3)3"(76.3)400 (1.78)15 (6.9) 200-21/2 21/2"(65)3/8"-16 M10 5 5/8"(142.9)41/8"(104.7)600 (2.67)27 (12.3) 200-3 3"(75)3/8"-16 M10 5 7/8"(149.1)4"(101.6)600 (2.67)29 (13.3) 200-31/2 31/2"(90)3/8"-16 M10 7 3/8"(187.3)51/4"(133.3)600 (2.67)34 (15.6) 200-4 4"(100)3/8"-16 M10 7 3/8"(187.3)5"(127.0)1000 (4.45)35 (16.0) 200-5 5"(125)1/2"-13 M12 9 1/8"(231.8)61/4"(158.7)1250 (5.56)66 (30.2) 200-6 6"(150)1/2"-13 M12 10 1/8"(257.2)63/4"(171.4)1250 (5.56)73 (33.4) 200-8 8"(200)1/2"-13 M12 13 1/8"(333.4)83/4"(222.2)1250 (5.56)136 (62.3) Fig. 200C Fig. 200F Fig. 200 All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. Pipe Hangers Pipe Hangers & Supports61 OFFICE OF THE FIRE MARSHAL – LA QUINTA 78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074 • www.rvcfire.org February 20, 2022 World Fire Protection INC 41905 Boardwalk #B Palm Desert, CA 92211 Re: New Fire Sprinkler System Plan Review – EXTRA SPACE STORAGE FSS2021-0289 / 79120 CORPORATE CENTER DRIVE, LA QUINTA, CA 92253 The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions. 1) Approval of these plans does not include the piping of the underground system. Installing contractor shall provide separate underground plans for review and approval prior to installation. 2) All persons performing work on the automatic fire sprinkler system shall be Certified Sprinkler Fi tters or Registered with the State Fire Marshal for Apprentice or Trainee classification. 3) The completed Contractor’s Material and Test Certificate for Aboveground Piping shall be provided to the fire inspector prior to a final inspection. 4) Permanently marked identification signs shall be attached to all control valves. 5) A sign shall be located adjacent to the alarm bell worded as follows: a) SPRINKLER FIRE ALARM - WHEN BELL RINGS CALL 911 6) The fire sprinkler system shall be monitored and supervised by an approved Dedicated Function - Fire Sprinkler Monitoring System. 7) Each system shall have an Air-Relief valve in compliance with NFPA 13 installed in a remote, most elevated location. 8) CA compliant Hydraulic Calculation Placards shall be installed on the riser or other approved location. Risers shall have signage indicating the location of remotely located placards. 9) Single head sprinkler drops located in suspended ceilings shall be provided with seismic escutcheons or other approved devices for restraint or seismic bonding. 10) The following inspections/tests are required to be witnessed by Office of the Fire Marshal staff: a) Overhead Rough: All installed/relocated piping must be visible. b) Overhead Hydro: Entire system shall be hydrostatically tested at a minimum of 200 psi for 2 hours. c) Underground Supply Flush: Flush of the underground supply line until clear of all debris and to the satisfaction of the inspector. d) Final inspection: Water-flow signal test as performed from the inspector test valve. As-Built plans required to be maintained on site as approved by the inspector. General Information sign and Hydraulic Calculation plate(s) provided. Title 19 “New” system tag affixed to riser. NOTE: The underground flush shall be done through a pipe or hose equal in size to the sprinkler underground supply pipe, prior to connection to the above ground sprinkler piping. The Fire Department approved plans and conditions letter must be at the job site. Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131. All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal staff at (760)777-7074. Kohl Hetrick - Fire Safety Specialist 78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131 RIVERSIDE COUNTY FIRE PROTECTION PLANNING RECORD OF INSPECTIONS / PERMIT CARD THIS CARD IS TO REMAIN ON SITE AT ALL TIMES. INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE. JOB ADDRESS: 79120 CORPORATE CENTER DRIVE PERMIT#: FSS2021-0289 DATE ISSUED: 2/20/2022 DESCRIPTION: EXTRA SPACE STORAGE CONTRACTOR: WORLD FIRE PROTECTION INC HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS Thrust block pre-pour Door fan test UG rough piping Abort test UG hydro Mechanical shutdown Flush Detector test Final E F Deluge/pre-action SPRINKLER U.G. Final E F Thrust block pre-pour UST/AST TANK UG rough piping Installation UG hydro Removal Flush Emergency shut off Final E F Primary piping FIRE SPRINKLER Secondary piping Weld inspection Dispensers & shear valves Overhead rough piping Final E F Overhead hydro MISC. INSPECTIONS UG flush / OK to connect Spray booths Main drain/inspectors’ test Hood/duct extinguishing High pile storage High pile rack storage In-rack sprinklers H.P. vents/access/corridors Hose racks Tract access/hydrant verification Final E F Access & Address verification HOOD EXTINGUISHING OTHER CONST. PERMIT Detection system Function test Gas/electrical shut-off Nozzle model/placement Fire alarm connection Final E F SPRAY BOOTHS FIRE CODE PERMIT(S) Installation Air flow test Mechanical interlock Extinguishing system Fire alarm connection Final E F FIRE ALARM KNOX SYSTEM Rough-wire inspection Building Knox box Function test Gate access Knox box/padlock Duct detectors/velocity BUILDING INSPECTIONS 24 hr. battery test T/I final Sprinkler monitoring Shell final Final E F Final for occupancy FINAL INSPECTION DATE: INSPECTORS SIGNATURE: **WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE** 78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131 INSPECTION NOTES 1. Sway bracing and hangers will be inspected at the time of rough piping inspection. 2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler Systems) 3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required. 4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test. 5. Contractor shall supply all testing equipment, access and operating instructions at time of test. 6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the affected system to be covered or hidden. POLICIES ON FIELD INSPECTIONS A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when scheduling inspections. For City of La Quinta inspections call: (760) 777-7131. B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence without approved plans. C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required to schedule the necessary inspections and be present on site for inspections. D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not on site or where previously noted corrections have not been completed. E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into the structure until clearance has been granted by the Fire Dept and Building Official. F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official. INSPECTION NOTES: THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS. THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180 DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE. THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY. 1 Hetrick, Kohl@CALFIRE From:Hetrick, Kohl@CALFIRE Sent:Monday, April 4, 2022 2:24 PM To:Blake Chapman; Gina Paz Cc:Iniguez, Lucero@CALFIRE; Cooley, Sonia@CALFIRE Subject:FSS2021-0289 - EXTRA SPACE STORAGE - CORRECTIONS Attachments:CALFIRE - Sprinkler Fitter Certification 2019 (IB 18-014).pdf; CCR Title 19 Ch 5.5 Fire Sprinkler Fitter Certification.pdf; sprinkler-fitter-information-bulletin.pdf; FSS2021-0289 - KH Inspection Notes.pdf World Fire Protection, While at the location of the above mentioned project for a scheduled Fire Alarm function test, an employee (Eddie) for World Fire was observed installing thread-rod and Sammy Express hangers to the fire sprinkler system. Upon casual questioning it was made clear that Eddie was by himself and does not have a valid Office of the State Fire Marshal Sprinkler Fitter Certification at any classification level. This alone is a violation of state law requiring that anyone performing work on a NFPA 13 or NFPA 13R system to have appropriate certification. Previous conversations with Blake of World Fire Protection showed that the company was familiar with this requirement. Therefore, this email is your only warning. Continued non-compliance with the requirements outlined in CCR Title 19, Chapter 5.5 will result in reporting of such directly to CSLB and the OSFM as well as Administrative Citations. This observation during the Fire Alarm inspection caused me to take a closer look at the fire sprinkler installation and I soon began to develop additional concerns. I understand that the installation Overhead Rough/Hydro was approved on 3/24/2022 by FSI Lucero with the following notes: “032422 - Approved OH Rough/2 HR Hydro - items to check at final: Unit L330 - Sprinkler head at rear leaking. Unit L283 all the way West were missing a sammy express hanger. Unit L120 - check deflector for paint.” Unfortunately, there were some additional details that were not observed and are required to be addressed. Please review the attached document for a marked plan set identifying missing details that require correction. As-builts should also be provided as cross-main alignment changes were observed. In addition to these notes, it was observed that NONE of the cutout coupons were affixed to the mechanical fittings as a common and preferred practice for showing that they were safely retrieved. There is no way of knowing that all cutouts were retrieved at this point. This is of great concern as these cutouts, if not all are retrieved, could cause a system restriction or blockage. In similar situations in the past, it had been required for the fire sprinkler contractor to make arrangements to flush out the entire system at reasonable velocities so as to collect in gunny sacks at discharge points, any un-retrieved cutout. NFPA 13 Contractor Material and Test Certificate only requires that “you certify that you have a control feature to ensure that all cutouts (discs) are retrieved.” Please let me know if you have any further questions. KOHL HETRICK Fire Safety Specialist / Office of the Fire Marshal Cal Fire/Riverside County Fire Department City of La Quinta Desk: 760-777-7074 | Mobile: 760-409-5109 2 Inspection Hotline: 760-777-7131 78495 Calle Tampico, La Quinta, CA 92253 kohl.hetrick@fire.ca.gov | www.rvcfire.org Sch: Mon-Thurs Leadership, Competence, Integrity, Safety, Customer Service The Office of the County Fire Marshal is committed to facilitating fire and life safety solutions by empowering its employees to serve our community through innovation and partnership.