FSS2022-0088ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT NIELSEN'S FIRE PROTECTION, INC.5022 W AVENUE N,
SUITE 102-Box E
PALMDALE CA 93551 (661)285-3473 JUSTIN@NIELSENSFIRE.
COM
CONTRACTOR NIELSEN'S FIRE PROTECTION, INC.5022 W AVENUE N,
SUITE 102-Box E
PALMDALE CA 93551 (661)285-3473 JUSTIN@NIELSENSFIRE.
COM
OWNER KOHLS DEPARTMENT STORES INC N56 W17000
RIDGEWOOD DR
MENOMONEE
FALLS
WI 92253 (661)285-3473
CONDITIONS
Description: ADJUSTING FIRE SPRINKLER FOR TENANT IMPROVEMENTS
Type: FIRE SPRINKLER (WEB)Subtype: TENANT IMPROVEMENT Status: FINALED Applied: 3/11/2022 ECON
Parcel No: 643080004 Site Address: 78950 HIGHWAY 111 LA QUINTA,CA 92253 Approved: 3/31/2022 KHET
Subdivision: PM 25865 Block: Lot: 6 Issued: ONLINE
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 4/6/2022 KHET
Valuation: $5,500.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Wednesday, April 05, 2023 1:49:52 PM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0088
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING
KHET 4/6/2022 4/6/2022 APPROVED
OVERHEAD HYRO KHET 4/6/2022 4/6/2022 APPROVED
FIRE FINAL**KHET 4/6/2022 4/6/2022 APPROVED
Tiles in place. Final okay, BCOM TI final still
needed. *5-Year Sprinkler Maintenance is
required for the building.
REVIEWS
RETURNED
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - TENANT
IMPROVEMENT OVER
10 HEADS
101-0000-42420 0 $167.00 $167.00 4/1/22 WEB11225 636324857
70 CREDIT 936026 ECON
FIRE SPRINKLER
SYSTEMS - TENANT
IMPROVEMENT OVER
10 HEADS PC
101-0000-42420 0 $333.00 $333.00 4/1/22 WEB11225 636324857
70 CREDIT 936026 ECON
Total Paid for FIRE FEES: $500.00 $500.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $11.00 $11.00 4/1/22 WEB11225 636324857
70 CREDIT 936026 ECON
Total Paid for RECORDS MANAGEMENT FEE: $11.00 $11.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 4/1/22 WEB11225 636324857
70 CREDIT 936026 ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$516.00 $516.00
Printed: Wednesday, April 05, 2023 1:49:52 PM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0088
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 3/11/2022 Etrakit Contractor 1ST SUBMITTAL CUT
SHEETS 014.pdf 1
DOC 3/11/2022 Etrakit Contractor 1ST SUBMITTAL PLAN KHOLSLAQUINTA.pdf 1
DOC 3/31/2022 KOHL HETRICK FSS2022-0088 -
APPROVED PLANS.pdf
FSS2022-0088 -
APPROVED PLANS.pdf 1
DOC 3/31/2022 KOHL HETRICK FSS2022-0088 - COA
AND JOB CARD.pdf
FSS2022-0088 - COA
AND JOB CARD.pdf 1
BOND INFORMATION
REVIEW TYPE REVIEWER SENT DATE DUE DATE DATE STATUS REMARKS NOTES
1ST FIRE - ETRAKIT
(2 WK)
KOHL
HETRICK 3/11/2022 3/25/2022 3/31/2022 APPROVED SEE ATTACHMENTS
1ST PERMIT TECH –
ETRAKIT (1 DAY)
PERMIT TECH
BUCKET 3/11/2022 3/14/2022 3/14/2022 COMPLETE
Printed: Wednesday, April 05, 2023 1:49:52 PM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0088
CONTINUED TOSYSTEMCONTINUED TOSYSTEMCONTINUED TOSYSTEMCONTINUED TOSYSTEMCONTINUED TOSYSTEMCONTINUED TOSYSTEM(E) (E)(E)(E) (E) (E) (E) (E) (E) (E)(E)(E)(E)(E)(E)(E)(E)(E)(E)(E)(E)(E)(E)(E)(E)(E)(E)(E)(E)(E)(E)(E)(R)(R)(R)(R)(R)(R)(R)(R)(R)(R)(R)(R)(R)(R)(R)(R)(R)(R)(R)(R)(R)(R)KOHL'S - LA QUINTA - STORE #10677VICINITY MAPHANGER RING3/8" ALL THREAD RODJAM ATR AGAINSTTOP OF PIPEEND OF LINE RESTRAINT (ATR)PIPE- SYMBOL DENOTES END OF LINE RESTRAINT excess of 150 psi. shall not exceed 24 in.* On the end hanger use either "Tolco Surge Clip" Fig.#2 in excess of the maximum pressure, when the maximum bars) pressure for two hours, or at 50 psi (3.4 bars) or tighten down ATR to the top of pipe when rods and* The length of an unsupported armover to a sprinkler pressure to be maintained in the system is in* All new systems including yard piping shall be hydrostatically tested at not less than 200 psi (13.8* Install tamper switches on all control valves and rings are used.* All wiring to be provided by others. provided by others.* Riser nipples/outlets on schedule 10 steel* All armovers to be 1" x 0'-4" unless noted otherwise.* Propriety and central station monitoring to be All welding shall conform to NFPA Standards. piping to be mechanical tees or weld-o-lets, typical.* All pipe 2½" - 4" to be schedule 10 black steel (ASTM-A135) with grooved couplings, Victaulic Fig.#005 grooved rigid couplings, and Fig.#77 flexible couplings (or equal). GENERAL OVERHEAD NOTES* All design and installation shall be in accordance with NFPA 13, 2016 Ed., all relevant building and fire codes, coordinated with fire alarm system. & Local Authority* The existing main floor system is designed @ .20/1500 sq.ft. minimum, with the use of QR-Standard spray sprinkler pendents.* All pipe 1"- 2" to be schedule 40 black steel (ASTM-A135) with cast iron threaded fittings.SCOPE OF WORK:NIELSEN'S FIRE PROTECTION SHALL MODIFY EXISTING SPRINKLERSYSTEM IN AREA OF WORK AS NECESSARY TO PROVIDE NEW LAYOUT ASSHOWN ON THIS DRAWING. REMOVE ALL PIPING, HANGERS ANDSPRINKLERS NOT INTENDED FOR REUSE. ADD SPRINKLERS AND PIPINGAS NECESSARY TO INSTALL SPRINKLER LAYOUT AS SHOWN ON THISDRAWING. COORDINATE WITH OTHER TRADES AND FIELD CONDITIONSTO PREVENT OBSTRUCTIONS AND CONFLICTS WITH SPRINKLER SYSTEM.xDEMO EXISTING PENDENT SPRINKLERS NO LONGER NEEDED INREMODELED AREA. ALL SPRINKLERS REMOVED FROM THE SYSTEMSHALL HAVE EXISTING DROPS REMOVED OR PLUGGED.xRELOCATE SPRINKLERS TO CENTERLINE OF TILE WHERE REQUIRED(3 TOTAL).xRELOCATE SPRINKLERS IN REMODELED ARE FROM THE EXISTINGELEVATION OF 9'-6" TO THE NEW ELEVATION OF 11'-2".xALL RELOCATED SPRINKLERS SHALL BE REPLACED LIKE FOR LIKE.SEE SPRINKLER LEGEND FOR MORE INFORMATION.TENANT IMPROVEMENT - SYMBOL LEGEND- EXISTING SSP- RELOCATED SSP Sprinkler heads in this area to be spaced at a maximum of 130 sq.ft.(E)(R)HEAD CAB'T & WRENCH(ES) PROVIDEDTOTAL COUNT THIS SHEET = FINISHTEMP.ORIFICEMFG.SYMBOLSPRINKLER SCHEDULE & LEGENDK-FACTORSIN#MODEL22QUANTITYHEAD TYPE(6)RELIABLE22CHRM.155°½"5.6RA1414F1FR56NEW QR SEMI-REC. SSPFIRE SPRINKLER PIPING PLAN02' 4' 8'SCALE: IN FEET1/4" = 1'-0"KOHL'S - LA QUINTA - STORE #: 10677KEY MAPKOHL'S - LA QUINTA - STORE #: 10677N.T.S.SAMMY SWG 200 PIPE HANGERSWG 200ALL THREAD RODADJUSTABLE RING HANGERWOOD NAILERAPPROVEDRiverside County Fire DepartmentLa Quinta Office of the Fire MarshalBy:FIRE SAFETY SPECIALIST03/31/2022 8:24:06 AMThe approval of plans and specifications does notpermit the violation, deletion, omission or faultyinstallation of any requirements of Title 24 or anyLocal Ordinances. Construction shall remainaccessible and exposed for inspection purposesuntil approved by the Fire Department.PERMIT # -FSS2022-0088Kohl HetrickReason: I am approving this documentContact Info: 760-409-5109
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model F1FR Series
Quick Response
Glass Bulb Sprinklers Bulletin 014 December 2021Bulletin 014 December 2021
Model F1FR56 Sprinkler Types
Standard Spray Upright
Standard Spray Pendent
Conventional Upright/Pendent
Vertical Sidewall
Horizontal Sidewall
Model F1FR56 Recessed Sprinkler Types
Standard Spray Pendent
Horizontal Sidewall
Model F1FR56 Concealed Sprinkler Types
Standard Spray Pendent
Model F1FR42, F1FRXLH & F1FR28 Sprinkler
Types
Standard Spray Upright
Standard Spray Pendent
Model F1FR40 Sprinkler Types
Standard Spray Pendent
Model F1FR42, F1FR40, F1FRXLH & F1FR28
Recessed Sprinkler Types
Standard Spray Pendent
Model F1FR56LL & F1FR42LL Low Lead Sprinkler
Types
Standard Spray Pendent with less than 0.25% Lead Con-
tent
Listing & Approvals
The following organizations provide Listings or Approvals for
various Model F1FR series sprinklers. See the Design and
Installation table in this Bulletin for information on specific
listings and approvals applicable to each sprinkler.
1. Underwriters Laboratories Inc. and Certified for Cana-
da (cULus) in accordance with ANSI/UL199.
2. FM Approvals (FM)
3. Loss Prevention Certification Board (LPCB)
4. VdS Schadenverhütung GmbH (VdS)
5. Underwriters Laboratories Inc. and Underwriters Lab-
oratories of Canada Certified for Health Effects to NSF/
ANSI Standard 61 Annex G (ULH)
6. EC Certificate: 0786-CPD-40239 (RA1414), 0786-
CPD-40251 (RA1425), 0786-CPD-40252 (RA1475)
(EC)
7. WaterMark certified. Certificate Number 23347. (WM)
UL Listing Category
Sprinklers, Automatic & Open (VNIV)
Quick Response Sprinkler
Pendent Conventional
Recessed
Pendent/F1/F2
Upright
Vertical Sidewall Horizontal Sidewall
Recessed
Horizontal Sidewall
Recessed
Pendent/FP
Concealed
Pendent
XLH Upright XLH Pendent XLH Recessed
Pendent F1/F2
XLH Recessed
Pendent FP
Product Description
Reliable Model F1FR series sprinklers
are quick-response automatic sprinklers
with a glass bulb thermal element. Model
F1FR series sprinklers are Standard Spray
sprinklers, with the exception of the Model
F1FR56 Conventional sprinkler which is
an Old-style/Conventional sprinkler.
The Model F1FR Series automatic sprinklers utilize a 3.0
mm frangible glass bulb. These sprinklers have demonstrated
response times in laboratory tests which are five to ten times
faster than standard response sprinklers. This quick response
enables the Model F1FR Series sprinklers to apply water to a
fire faster than standard-response sprinklers of the same tem-
perature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely manufac-
tured glass capsule. This glass bulb is specially constructed to
provide fast thermal response.Jan 2022 NOTE: Please see website for updated versions of K2.8, K4.0, K4.2, and XLH Sprinklers
2.
At normal temperatures, the glass bulb contains the fluid in
both the liquid and vapor phases. The vapor phase can be seen
as a small bubble. As heat is applied, the liquid expands, forcing
the bubble smaller and smaller as the liquid pressure increases.
Continued heating forces the liquid to push out against the bulb,
causing the glass to shatter, opening the waterway and allowing
the deflector to distribute the discharging water.
Model F1FR Series sprinklers provide a wide range of options
where quick-response, glass bulb sprinklers are used:• Pendent, recessed pendent, upright, horizontal side -
wall, and vertical sidewall deflectors• K-factors of 2.8 (40 metric), 4.0 (57 metric), 4.2 (60
metric), and 5.6 (80 metric)• Flush, recessed, and concealed installations
See the Design and Installation Information table in this Bul-
letin for information on the approvals and availability of specific
Model F1FR series sprinkler configurations.
Model F1FR Recessed Pendent and Recessed Horizontal
Sidewall sprinklers are required to be used with Reliable Model
F1, F2, or FP recessed escutcheons. See the Recessed Es -
cutcheon Data table in this Bulletin for listing and approval infor-
mation with each specific Model F1FR series sprinkler. Model
F1 and F2 recessed escutcheons, shown in Fig. 1 and 3, are
a friction fit assembly allowing for 3/4-inch (19mm) and 1/2-
inch (12.7mm) of adjustment, respectively. Model FP recessed
escutcheons, shown in Fig. 2, provide a 1/2-inch (12.7mm)
threaded adjustment.
Model F1FR56 Concealed Pendent and Model F1FR56LL
Concealed Pendent sprinklers are required to be used with
Model CCP cover plates. A standard profile Model CCP cover
plate is available that provides up to 1/2-inch (12.7mm) of cover
plate adjustment. In addition, a low profile Model CCP cover
plate is also available that provides up to 5/16-inch (8.0mm) of
cover plate adjustment. See the Design and Installation Infor-
mation and Listed and Approved Temperature Ratings tables
in this Bulletin for further information on approved cover plate
options.
Application
Model F1FR Series sprinklers are intended for use in ac-
cordance with NFPA 13, FM Property Loss Prevention Data
Sheets, and the requirements of the Authority Having Juris-
diction. Care must be exercised that the k-factor, tempera-
ture rating, deflector style, and sprinkler type are in accor-
dance with the requirements of the applicable design and
installation standards. In addition, Model F1FR Series sprin-
klers must be used in accordance with their listings and ap-
provals, as well as the information provided in this Bulletin.
Installation
Glass bulb sprinklers have orange bulb protectors or protec-
tive caps to minimize bulb damage during shipping, handling
and installation. Reliable sprinkler installation wrenches are
designed to install sprinklers with bulb protectors in place. Re -
move the bulb protector at the time when the sprinkler system is
placed in service for fire protection. Removal of the bulb protec-
tor before this time may leave the bulb vulnerable to damage.
Remove bulb protectors by undoing the clasp by hand. Do not
use tools to remove bulb protectors.
Model F1FR Series sprinklers must be installed with the Reli-
able sprinkler installation wrench identified in the Design and
Installation Information table in this Bulletin. Any other wrench
may damage the sprinkler. A leak tight sprinkler joint can be
obtained with a torque of 8 to 18 lb-ft (11 to 24 N-m). Do not
tighten sprinklers over the maximum recommended installation
torque. Exceeding the maximum recommended installation
torque may cause leakage or impairment of the sprinkler.
Recessed Sprinklers
Model F1FR Series Recessed sprinklers are to be installed
as shown in Fig. 1, Fig. 2, or Fig. 3, as applicable to the specific
model being installed. The Recessed Escutcheon Data table in
the Bulletin identifies the only recessed escutcheons that are
permitted to be used with each Model F1FR Series Recessed
sprinkler. The use of any other recessed escutcheon will void all
approvals and negate all warranties.
Concealed Sprinklers
Model F1FR Series Concealed Pendent sprinklers are to
be installed as shown in Fig. 4 or Fig. 5, as applicable to the
selected cover plate. Model F1FR56 Concealed Pendent and
Model F1FR56LL Concealed Pendent sprinklers have a facto-
ry-installed Model CCP cup. A protective cap is installed at the
factory that should remain on the sprinkler until the sprinkler is
installed and should then be reinstalled on the sprinkler until the
cover plate is installed. The concealed sprinkler assemblies are
completed by the installation of a Model CCP push-on/thread-
off cover plate assembly. The cover plate and sprinkler cup as -
semblies are joined using a cover plate skirt with flexible tabs
for threaded engagement. A choice of two Model CCP cover
plate assemblies provides either 1/2-inch (13mm) or 5/8-inch
(8mm) of cover adjustment. Do not install Model F1FR Series
Concealed Pendent sprinklers in ceilings which have positive
pressure in the space above.
Model F1FR Series Concealed Pendent sprinklers require
a 2-5/8-inch (67mm) diameter hole to be cut in the ceiling. The
Model W4 wrench is used to engage the sprinkler wrenching sur-
faces and to install the sprinkler in the fitting. Remove the protective
cap to install the sprinkler, then reinstall the protective cap until the
cover plate is installed. When inserting or removing the wrench from
the sprinkler/cup assembly, care should be taken to prevent dam-
age to the sprinkler. Do not wrench any other part of the sprinkler/
cup assembly. Installation is completed by removing the protective
cap from the sprinkler and pushing the cover plate onto the cup.
Final adjustment is made by hand turning the cover plate until the
skirt flange makes full contact with the ceiling. Cover plate removal
requires turning the cover plate in the counter clockwise direction.
After installation, inspect all sprinklers to ensure that there is a gap
between the cover plate and ceiling and that the four cup slots are
open and free from any air flow impediment to the space above.
Concealed cover plate/cup assemblies are listed only for use
with specific sprinklers. The use of any concealed cover plate/
cup assembly other than the Reliable Model CCP with Model
F1FR56 Concealed Pendent and Model F1FR56LL Concealed
Pendent sprinklers or the use of the Model CCP Concealed
cover plate assembly on any sprinkler with which it is not spe -
cifically listed my prevent good fire protection and will void all
guarantees, warranties, listings and approvals.Jan 2022 NOTE: Please see website for updated versions of K2.8, K4.0, K4.2, and XLH Sprinklers
3.
Design and Installation Information
Model
Nominal
K-factor
Nominal
Orifice
Diameter Deflector/
Orientation
Nominal
Sprinkler
Height Installation
Wrench SIN
Listings
and
Approvals
Approval
Notes
US Metric inches mm inches mm
F1FR28 2.8 40 3/8 10
Pendent 2.25 57 W2 RA1411 cULus 2
Recessed Pendent 2.25 57 W4 RA1411 cULus 2
Upright 2.25 57 W2 RA1421 cULus 1,2
F1FR40 4.0 57 3/8 10 Pendent 2.25 57 W2 RA1418 VdS
Recessed Pendent 2.25 57 W4 RA1418 VdS
F1FR42 4.2 60 7/16 10
Pendent 2.25 57 W2 RA1413 cULus 2
Recessed Pendent 2.25 57 W4 RA1413 cULus 2
Upright 2.25 57 W2 RA1423 cULus 1,2
F1FR42LL 4.2 60 7/16 10 Pendent 2.25 57 W2 RA1410 cULus, ULH
Recessed Pendent 2.25 57 W4 RA1410 cULus, ULH
F1FRXLH
(F1FR42
with Pintle)
4.2 60 7/16 10
Pendent 2.25 57 W2 RA1413 cULus 2
Recessed Pendent 2.25 57 W4 RA1413 cULus 2
Upright 2.25 57 W2 RA1423 cULus 1,2
F1FR56 5.6 80 1/2 15
Pendent 2.25 57 W2 RA1414
cULus, FM,
LPCB, VdS, EC,
WM
1,2,3,4
Recessed Pendent 2.25 57 W4 RA1414
cULus, FM,
LPCB, VdS, EC,
WM
1,2,3,4
Concealed Pendent 2.25 57 W4 RA1414 cULus,VdS,EC,
WM 5,6
Upright 2.25 57 W2 RA1425
cULus, FM,
LPCB, VdS, EC,
WM
1,2,3,4
"Conventional
(Pendent or Upright)"2.25 57 W2 RA1475 LPCB, VdS, EC,
WM 4
F1FR56LL 5.6 80 1/2 15
Pendent 2.25 57 W2 RA1415 cULus, ULH 1
Recessed Pendent 2.25 57 W4 RA1415 cULus, ULH
Concealed Pendent 2.25 57 W4 RA1415 cULus, ULH 6
F1FR56 5.6 80 1/2 15
Horizontal Sidewall 2.63 67 W2 RA1435 cULus, FM 1,2,3,7
Recessed Horizontal
Sidewall 2.63 67 W4 RA1435 cULus, FM 8
F1FR56 5.6 80 1/2 15 Vertical Sidewall (Pen-
dent or Upright)2.25 57 W2 RA1485 cULus, FM,
LPCB 1,2,3,9
(1) cULus Listed Corrosion Resistant sprinkler when ordered with available Polyester coating.
(2) cULus Listed Corrosion Resistant sprinkler when ordered with available Electroless Nickel PTFE plating.
(3) Available with FM approved Polyester coating in black or white.
(4) Available with LPCB and VdS approved Polyester coating.
(5) VdS and EC approvals of the F1FR56 Concealed Pendent sprinkler are for 155°F (68°C) temperature rated sprinklers only. VdS approved sprinklers must
use Norbulb brand glass bulbs with the 1/2-inch (12.7mm) adjustment Model CCP cover plate only.
(6) Model F1FR56 Concealed Pendent and Model F1FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates, available
as either standard depth with 1/2-inch (12.7mm) of adjustment or low profile with 5/16-inch (8.0 mm) of adjustment.
(7) cULus Listing of the F1FR56 Horizontal Sidewall sprinkler is for Light and Ordinary Hazard occupancies only. Minimum to maximum deflector to ceiling
distance shall be 4 inches to 12 inches (102mm to 305mm). FM Approval of the F1FR56 Horizontal Sidewall sprinkler is for Light Hazard occupancies
only.
(8) cULus Listing and FM Approval of the F1FR56 Recessed Horizontal Sidewall sprinkler is for Light Hazard occupancies only.
(9) The F1FR56 Vertical Sidewall sprinkler is listed and approved for use only in Light Hazard occupancies. LPCB approval of the F1FR56 Vertical Sidewall
sprinkler is for installation in the Pendent position only.
Technical Data:
Sensitivity: Quick-response
Thread Size: 1/2-inch NPT standard; ISO 7-R1/2 optional
Maximum Working Pressure: 175 psi (12 bar) - 100% Factory tested hydrostatically to 500 psi (34.5 bar)
SIN RA1425, RA1414 & RA1435 cULus listed for 250 psi (17 bar)Jan 2022 NOTE: Please see website for updated versions of K2.8, K4.0, K4.2, and XLH Sprinklers
4.
Listed and Approved Temperature Ratings
Model Deflector/
Orientation
Ordinary Temp.
Classification
100°F (38°C) Max. Ambient
Temp.
Intermediate Temp.
Classification
150°F (65°C) Max. Ambient
Temp.
High Temp.
Classification
225°F (107°C) Max.
Ambient Temp.
135°F (57°C)
Temp. Rating
155°F (68°C)
Temp. Rating
175°F (79°C)
Temp. Rating
200°F (93°C)
Temp. Rating
286°F (141°C) Temp.
Rating
Orange Bulb Red Bulb Yellow Bulb Green Bulb Blue Bulb
F1FR28
Pendent cULus
Recessed Pendent cULus
Upright cULus
F1FR40 Pendent VdS
Recessed Pendent VdS
F1FR42
Pendent cULus
Recessed Pendent cULus
Upright cULus
F1FR42LL Pendent cULus, ULH
Recessed Pendent cULus, ULH
F1FRXLH
Pendent cULus
Recessed Pendent cULus
Upright cULus
F1FR56
Pendent cULus, FM, LPCB, VdS, EC, WM
Recessed Pendent cULus, FM, LPCB, VdS, EC, WM
Concealed Pendent*cULus, WM cULus,VdS,EC,
WM cULus, WM
Upright cULus, FM, LPCB, VdS, EC, WM
“Conventional
(Pendent or Upright)”LPCB, VdS, EC, WM
F1FR56LL
Pendent cULus, ULH
Recessed Pendent cULus, ULH
Concealed Pendent*cULus, ULH
F1FR56
Horizontal Sidewall cULus, FM
Recessed Horizontal
Sidewall cULus, FM
F1FR56 Vertical Sidewall (Pen-
dent or Upright)cULus, FM, LPCB
* Model F1FR56 Concealed Pendent and F1FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP
cover plates. For Ordinary Temperature Classification sprinklers use a 135°F (57°C) temperature rated cover plate. For In-
termediate Temperature Classification sprinklers use a 165°F (74°C) temperature rated cover plate.
Recessed Escutcheon Data
Model Deflector/
Orientation
Listed and Approved Recessed Escutcheons
SIN
Model F1
(Fig. 1 & 3)
3/4-inch (19mm)
adjustment
Model F2
(Fig. 1 & 3)
1/2-inch (12.7mm)
adjustment
Model FP
(Fig. 2)
1/2-inch (12.7mm)
adjustment
F1FR28 Recessed Pendent cULus cULus cULus RA1411
F1FR40 Recessed Pendent VdS VdS VdS RA1418
F1FR42 Recessed Pendent cULus cULus cULus RA1413
F1FR42LL Recessed Pendent cULus, ULH cULus, ULH cULus, ULH RA1410
F1FR42XLH Recessed Pendent cULus cULus cULus RA1413
F1FR56 Recessed Pendent cULus, LPCB, VdS,
EC, WM
cULus, FM, LPCB,
VdS, EC, WM cULus, VdS, EC, WM RA1414
F1FR56LL Recessed Pendent cULus, ULH cULus, ULH cULus, ULH RA1415
F1FR56 Recessed Horizontal Sidewall cULus cULus, FM cULus RA1435Jan 2022 NOTE: Please see website for updated versions of K2.8, K4.0, K4.2, and XLH Sprinklers
5.
Fig. 1
Model F1FR56, F1FR56LL, F1FR42, F1FR40, F1FR42LL, F1FRXLH &
F1FR28 Recessed Pendent sprinkler with Model F1 or F2 escutcheon
Fig. 2
Model F1FR56, F1FR56LL, F1FR42, F1FR40, F1FR42LL, F1FRXLH &
F1FR28 Recessed Pendent sprinkler with Model FP escutcheonJan 2022 NOTE: Please see website for updated versions of K2.8, K4.0, K4.2, and XLH Sprinklers
6.
Fig. 3
Model F1FR56 Recessed Horizontal Sidewall sprinkler with Model F1 or F2 escutcheon
Fig. 4
Model F1FR56/F1FR56LL Concealed Pendent sprinkler with standard depth
1/2-inch (12.7mm) adjustment - Model CCP cover plateJan 2022 NOTE: Please see website for updated versions of K2.8, K4.0, K4.2, and XLH Sprinklers
7.
Fig. 5 - Model F1FR56/F1FR56LL Concealed Pendent sprinkler with low profile 5/16-
inch (8.0mm) adjustment - Model CCP cover plate
Maintenance
The Model F1FR Series sprinklers should be inspected and
the sprinkler system maintained in accordance with NFPA 25.
Do not clean sprinklers with soap and water, ammonia or any
other cleaning fluids. Remove dust by using a soft brush or gen-
tle vacuuming. Replace any sprinkler which has been painted
(other than factory applied) or damaged in any way. A stock of
spare sprinklers should be maintained to allow quick replace-
ment of damaged or operated sprinklers.
Finishes (1) (2)
Standard Finishes
Sprinkler Escutcheon Cover plate
Bronze Brass Chrome
Chrome Chrome White
White Polyester (3)(6)(7)White
Special Application Finishes
Sprinkler Escutcheon Cover plate
Electroless Nickel
PTFE(3)(4)
Electroless Nickel
PTFE Bright Brass
Black Polyester (3)(6)(7)Bright Brass Black
Bright Brass (5)Black Off White
Off White(6)(7) Off White Satin Chrome
Satin Chrome Satin Chrome
(1) Other finishes and colors may be available on special order. Consult the
factory for details.
(2) Paint or any other coating applied over the factory finish will void all approvals
and warranties.
(3) cULus Listed as Corrosion Resistant.
(4) FM Approved as Corrosion Resistant for SIN RA1414, RA1425, RA1435,
and RA1485.
(5) 200*F (93*C) maximum temperature rated sprinkler only.
(6) VdS Approved for RA1425, RA1414, RA1418, and RA1475.
(7) LPCB Approved for RA1425, RA1414, and RA1475.
Material Data
Frame: DZR Brass, QM Brass, or Low Lead Brass
Deflector:CDA Alloy 220, 260, or 510
Load Screw\Pintle: CDA Alloy 360 or 544
Cup:CDA Alloy 651 or 693
Washer:Nickel Alloy 440 or 360, coated with PTFE
Adhesive Tape
Bulb:Glass
Ordering Information
Specify:
1. Sprinkler Model: [F1FR28][F1FR40][F1FR42]
[F1FR42LL][F1FRXLH][F1FR56][F1FR56LL]
2. Sprinkler Deflector/Orientation: [Pendent][Recessed
Pendent][Upright][Conventional][Horizontal Sidewall]
[Recessed Horizontal Sidewall][Vertical Sidewall]
3. Sprinkler threads: [1/2-inch NPT][ISO 7-R1/2]
4. Sprinkler Temperature Rating: [135°F (57°C)][155°F
(68°C)][175°F (79°C)][200°F (93°C)][286°F (141°C)]
5. Sprinkler Finish
6. Escutcheon Model: [F1][F2][FP]
7. Escutcheon Finish (where applicable)
8. Cover plate Model: [standard profile CCP 1/2-inch
(12.7mm) adjustment][low profile CCP 5/16-inch
(8.0mm) adjustment]
9. Cover plate Temperature Rating: [135°F (57°C) for use
with Ordinary Temperature sprinklers][165°F (74°C) for
use with Intermediate Temperature sprinklers]
10. Cover plate Finish
Note: When Model F1FR Series Recessed sprinklers are ordered, the sprin-
klers and escutcheons are packaged separately. Jan 2022 NOTE: Please see website for updated versions of K2.8, K4.0, K4.2, and XLH Sprinklers
Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 12/21 P/N 9999970300
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual
Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 100 years.
• Automatic sprinklers
• Flush automatic sprinklers
• Recessed automatic sprinklers
• Concealed automatic sprinklers
• Adjustable automatic sprinklers
• Dry automatic sprinklers
• Intermediate level sprinklers
• Open sprinklers
• Spray nozzles
• Alarm valves
• Retarding chambers
• Dry pipe valves
• Accelerators for dry pipe valves
• Mechanical sprinkler alarms
• Electrical sprinkler alarm switches
• Water flow detectors
• Deluge valves
• Detector check valves
• Check valves
• Electrical system
• Sprinkler emergency cabinets
• Sprinkler wrenches
• Sprinkler escutcheons and guards
• Inspectors test connections
• Sight drains
• Ball drips and drum drips
• Control valve seals
• Air maintenance devices
• Air compressors
• Pressure gauges
• Identification signs
• Fire department connection
Reliable offers a wide selection of sprinkler components. Following are some of the many pre -
cision-made Reliable products that guard life and property from fire around the clock.
Reliable...For Complete Protection
Jan 2022 NOTE: Please see website for updated versions of K2.8, K4.0, K4.2, and XLH Sprinklers
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
March 31, 2022
Nielsen’s Fire Protection, INC
5022 W Avenue N #102-E
Palmdale, CA 93551
Re: TI Fire Sprinkler Plan Review – KOHL’S - SEPHORA
78950 HIGHWAY 111, LA QUINTA, CA 92253
The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
The following inspections/tests are required to be witnessed by the Office of the Fire Marshal staff:
1) Overhead Rough: All installed/relocated piping must be visible.
2) Final inspection: All trim is in place, 5-Year certification is current. New/added heads shall be
included in the spare head box compliment.
*Water-flow signal test may be performed during the Final Inspection.
All persons performing work on the automatic fire sprinkler system shall be Certified Sprinkler Fitters or
Registered with the State Fire Marshal for Apprentice or Trainee classification.
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 78950 HIGHWAY 111 PERMIT#: FSS2022-0088 DATE
ISSUED: 3/31/2022
DESCRIPTION: KOHL’S - SEPHORA CONTRACTOR: NIELSEN’S FIRE PROTECTION INC.
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.