FSS2022-0182ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT Frank Capirchio 2445 West 237 place Torrance Ca
90501
CA 90501 (310)953-5597 cap777_3@msn.com
CONTRACTOR CITYCO FIRE PROTECTION 2445 WEST 237 PLACE TORRANCE CA 90501 (310)953-5597 1CITYCO@GMAIL.COM
OWNER bella trust 633 via linda thousand oaks ca 91320 (310)953-5597
CONDITIONS
Description: BELLA / FIRE SPRINKLER
Type: FIRE SPRINKLER (WEB)Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: ISSUED Applied: 4/22/2022 EPRS
Parcel No: 776330007 Site Address: 50690 BREVA ST LA QUINTA,CA 92253 Approved: 7/12/2022 KHET
Subdivision: TR 32068 Block: Lot: 7 Issued:
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled:
Valuation: $1,200.00 Occupancy Type: Construction Type: Expired: 5/14/2023 KHET
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE PLAN REVISION
SUBMITTALS 101-0000-42420 0 $167.00 $0.00
Printed: Friday, April 07, 2023 8:50:57 AM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0182
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD HYRO KHET 10/26/2022 10/26/2022 APPROVED
OVERHEAD ROUGH
PIPING KHET 10/26/2022 10/26/2022 DISAPPROVE
D SEE ATTACHMENTS
Reinspection required to observe corrections
affected by clearance from HVAC, Smokies
and Ceiling Fixtures - as well as appropriate
insulation protection of CPVC from contact
with jacketed electrical wiring.
**Revised plans and calcs will also be
required prior to final.
OVERHEAD ROUGH
PIPING
KHET 11/15/2022 11/15/2022 APPROVED
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $250.00 $250.00 7/27/22 R71427 2000 CHECK CITYCO FIRE
PROTECTION AHI
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $250.00 $250.00 7/27/22 R71427 2000 CHECK CITYCO FIRE
PROTECTION AHI
Total Paid for FIRE FEES: $667.00 $500.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $11.00 $11.00 7/27/22 R71427 2000 CHECK CITYCO FIRE
PROTECTION AHI
Total Paid for RECORDS MANAGEMENT FEE: $11.00 $11.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 7/27/22 R71427 2000 CHECK CITYCO FIRE
PROTECTION AHI
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$683.00 $516.00
Printed: Friday, April 07, 2023 8:50:57 AM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0182
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 8/8/2022 Etrakit Contractor 50-690 BrevaASBlt.pdf 1
DOC 8/8/2022 Etrakit Contractor CALCS 690 CASITA.pdf 1
DOC 4/22/2022 Etrakit Public
Registration new fire sprinklers 50-690 Breva.pdf 1
DOC 4/22/2022 Etrakit Public
Registration calcs CALCS (15).pdf 1
DOC 7/12/2022 KOHL HETRICK
FSS2022-0182 -
APPROVED PLANS AND
CALCS.pdf
FSS2022-0182 -
APPROVED PLANS AND
CALCS.pdf
1
DOC 7/12/2022 KOHL HETRICK FSS2022-0182 - COA
AND JOB CARD.pdf
FSS2022-0182 - COA
AND JOB CARD.pdf 1
DOC 9/7/2022 KOHL HETRICK
FSS2022-0182 - REV 1 -
APPROVED PLANS AND
CALCS.pdf
FSS2022-0182 - REV 1 -
APPROVED PLANS AND
CALCS.pdf
1
DOC 10/26/2022 KOHL HETRICK FSS2022-0182 - 10-26-
2022 - INSP NOTES.pdf
FSS2022-0182 - 10-26-
2022 - INSP NOTES.pdf 1
BOND INFORMATION
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST PERMIT TECH –
ETRAKIT (1 DAY)
AARON
HICKSON
4/22/2022 4/25/2022 4/26/2022 PENDING DOCUMENTS
1ST FIRE - ETRAKIT
(2 WK)
KOHL
HETRICK 6/17/2022 6/20/2022 7/12/2022 APPROVED SEE ATTACHMENTS
Review voided by AHI.
REVIEW HAS BEEN REINSTATED
2ND FIRE (1 WK)KOHL
HETRICK 8/8/2022 8/15/2022 9/7/2022 APPROVED REVISED PLANS/CALCS
removing waterflow switch and casita is now
supplied by tie-in to main house and not a
separate riser at casita.
Printed: Friday, April 07, 2023 8:50:57 AM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0182
COATW/HSEAT w.i.c.bath 3SEAT
LINEN JJJJJJFFFFFJFJFFFFFJFFJFFFFFFFFFFFFFFFJFJ1-car / golf cartgaragekitchendiningroomgreat roommasterbedroommasterbathbedroom 2entry / foyerw.i.c.w.i.c.courtyard2-car garagelaundrybath 2next genbathnext gensuitenext genloungebedroom 4bath 4pwdrw.i.c.mech.Cgallery hallhallbedroom 3covered patiocovered patioJdiningroomcasitasbathclo.barpizzaovencovered patiocovered patioDATE
REVISIONS
DESCRIPTION
AS NOTEDFS-201-12-228/8/22AS BUILT
DATEREVISIONSDESCRIPTIONAS NOTEDFS-101-12-228/8/22AS BUILTAPPROVEDRiverside County Fire DepartmentLa Quinta Office of the Fire MarshalBy:FIRE SAFETY SPECIALIST09/07/2022 4:42:53 PMThe approval of plans and specifications does notpermit the violation, deletion, omission or faultyinstallation of any requirements of Title 24 or anyLocal Ordinances. Construction shall remainaccessible and exposed for inspection purposesuntil approved by the Fire Department.PERMIT # -FSS2022-0182 - REV 1Kohl HetrickReason: I am approving this documentContact Info: 760-409-5109
COATW/HSEAT w.i.c.bath 3SEAT
LINEN JJJJJJFFFFFJFJFFFFFJFFJFFFFFFFFFFFFFFFJFJ1-car / golf cartgaragekitchendiningroomgreat roommasterbedroommasterbathbedroom 2entry / foyerw.i.c.w.i.c.courtyard2-car garagelaundrybath 2next genbathnext gensuitenext genloungebedroom 4bath 4pwdrw.i.c.mech.Cgallery hallhallbedroom 3covered patiocovered patioJdiningroomcasitasbathclo.barpizzaovencovered patiocovered patioDATE
REVISIONS
DESCRIPTION
AS NOTEDFS-201-12-228/8/22AS BUILT
DATE
REVISIONS
DESCRIPTION
AS NOTEDFS-301-12-228/8/22AS BUILT
Job Name :SINGLE FAMILY RESIDENCE
Building :CASITA
Location :50-690 BREVA ST.
System :
Contract :
Data File :50-690 Breva CASITAASB.WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Page 1
SINGLE FAMILY RESIDENCE Date 08/08/22
HYDRAULIC DESIGN INFORMATION SHEET
Name - Date -
Location - 50-690 BREVA ST.
Building - CASITA System No. -
Contractor - Contract No. -
Calculated By - Drawing No. -
Construction: ( ) Combustible ( ) Non-Combustible Ceiling Height
OCCUPANCY -
S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D
Y Number of Sprinklers Flowing: ( )1 (X)2 ( )4 ( )
S ( )Other
T ( )Specific Ruling Made by Date
E
M Listed Flow at Start Point - 13 Gpm System Type
Listed Pres. at Start Point - 7 Psi (X) Wet ( ) Dry
D MAXIMUM LISTED SPACING 16 x 16 ( ) Deluge ( ) PreAction
E Domestic Flow Added - 5 Gpm Sprinkler or Nozzle
S Additional Flow Added - Gpm Make Model
I Elevation at Highest Outlet - Feet Size K-Factor 4.9
G Note: Temperature Rating
N
Calculation Gpm Required 31.6 Psi Required 48.7 At Test
Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test: Pump Data: Tank or Reservoir:
A Date of Test - Rated Cap. Cap.
T Time of Test - @ Psi Elev.
E Static (Psi) - 90.6 Elev.
R Residual (Psi) - 70.2 Other Well
Flow (Gpm) - 2900 Proof Flow Gpm
S Elevation - -3
P Location:
P
L Source of Information:
Y
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Page 2
SINGLE FAMILY RESIDENCE Date 08/08/22
10
20
30
40
E 50
R 60
U 70
S 80
S 90
E 100
R 110
P 120
130
140
150
300600 900 1200 1500 1800 2100 2400 2700
FLOW ( N ^ 1.85 )
City Water Supply:Demand:
C1
C2
C1 - Static Pressure :90.6 C2 - Residual Pressure:70.2 C2 - Residual Flow :2900
D1 - Elevation : 6.063 D2 - System Flow :31.584 D2 - System Pressure : 78.724 Hose ( Demand ):_______D3 - System Demand :31.584 Safety Margin : 11.871
D1
D2
Water Supply Curve C
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Page 3
SINGLE FAMILY RESIDENCE Date 08/08/22
Fitting Legend
Abbrev.Name ½¾1 1¼1½2 2½3 3½4 5 6 8 10 12 14 16 18 20 24
E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
G NFPA 13 Gate Valve 0 0 1 1 1 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
N *CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0
O *CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0
R *CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0
S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65
T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with *. The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Fittings Used Summary
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Page 4
SINGLE FAMILY RESIDENCE Date 08/08/22
Node Elevation K-Fact Pt Pn Flow Density Area Press
No.Actual Actual Req.
1 11.0 4.9 7.1 na 13.06 0.051 256 7.0
2 11.0 4.9 7.62 na 13.53 0.051 256 7.0
10 11.0 9.26 na
11 11.0 11.54 na
12 11.0 15.25 na
13 11.0 17.53 na
14 11.0 24.46 na
3 11.0 35.29 na
4 11.0 43.35 na
TR 11.0 45.89 na
BR -2.0 56.01 na 5.0
M -2.0 63.74 na
TEST -3.0 78.72 na
The maximum velocity is 12.28 and it occurs in the pipe between nodes BR and M
Pressure / Flow Summary - STANDARD
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Page 5
SINGLE FAMILY RESIDENCE Date 08/08/22
Hyd.Qa Dia.Fitting Pipe Pt Pt
Ref."C"or Ftng's Pe Pv *******Notes ******
Point Qt Pf/Ft Eqv.Ln.Total Pf Pn
1 13.06 1.101 N 7.0 9.900 7.100 K Factor = 4.90
to 150.0 0.0 7.000 0.0
2 13.06 0.0309 0.0 16.900 0.522 Vel = 4.40
2 13.52 1.101 R 1.0 6.200 7.622 K Factor = 4.90
to 150.0 N 7.0 8.000 0.0
10 26.58 0.1152 0.0 14.200 1.636 Vel = 8.96
10 0.0 1.055 E 3.107 13.000 9.258
to 150.0 0.0 3.107 0.0
11 26.58 0.1418 0.0 16.107 2.284 Vel = 9.76
11 0.0 1.025 E 2.7 20.000 11.542
to 150.0 0.0 2.700 0.0
12 26.58 0.1632 0.0 22.700 3.704 Vel = 10.33
12 0.0 1.055 E 3.107 13.000 15.246
to 150.0 0.0 3.107 0.0
13 26.58 0.1418 0.0 16.107 2.284 Vel = 9.76
13 0.0 1.101 N 7.0 37.200 17.530
to 150.0 3O 15.0 23.000 0.0
14 26.58 0.1152 R 1.0 60.200 6.934 Vel = 8.96
14 0.0 1.101 2O 10.0 70.000 24.464
to 150.0 14R 14.0 24.000 0.0
3 26.58 0.1152 0.0 94.000 10.828 Vel = 8.96
3 0.0 1.101 N 7.0 50.000 35.292
to 150.0 O 5.0 20.000 0.0
4 26.58 0.1152 8R 8.0 70.000 8.062 Vel = 8.96
4 0.0 1.101 N 7.0 14.000 43.354
to 150.0 R 1.0 8.000 0.0
TR 26.58 0.1152 0.0 22.000 2.535 Vel = 8.96
TR 0.0 1.055 E 3.107 13.000 45.889
to 150.0 S 7.768 18.643 5.630
BR 26.58 0.1418 T 7.768 31.643 4.487 Vel = 9.76
BR 5.00 1.025 T 6.75 25.000 56.006 Qa = 5.00
to 150.0 E 2.7 9.450 0.0
M 31.58 0.2245 0.0 34.450 7.733 Vel = 12.28
M 0.0 1.025 G 1.35 30.000 63.739
to 150.0 T 6.75 8.100 6.433 * * Fixed Loss = 6
TEST 31.58 0.2245 0.0 38.100 8.552 Vel = 12.28
0.0
31.58 78.724 K Factor = 3.56
Final Calculations - Hazen-Williams
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
July 12, 2022
CityCo Fire Protection
2445 West 237 Place
Torrance, CA 90501
Re: Residential Fire Sprinkler Plan Review – BELLA TRUST – LOT 7
FSS2022-0182 / 50690 BREVA, LA QUINTA, CA 92253
The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
Permanently marked identification signs shall be attached to all control valves.
The following inspections/tests are required to be witnessed by Office of the Fire Marshal Staff:
(a) Overhead Rough and Hydro static test: All piping shall be visible and pumped at normal
operating pressure. *No jacketed electrical and data wiring shall be in contact with, nor have the
potential to contact CPVC piping once insulation is installed.
(b) Final inspection
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 50690 BREVA PERMIT#: FSS2022-0182 DATE
ISSUED: 7/12/2022
DESCRIPTION: BREVA TRUST – LOT 7 CONTRACTOR: CITYCO FIRE PROTECTION
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible dur ing the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.