FSS2022-0200ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT RESIDENTIAL FIRE PROTECTION DBA
ON GUARD
6438 ARVILLE ST LAS VEGAS NV 89118 (702)966-8021 VanesaH@ONGUARDF
P.COM
CONTRACTOR RESIDENTIAL FIRE PROTECTION DBA
ON GUARD
6438 ARVILLE ST LAS VEGAS NV 89118 (702)966-8021 VanesaH@ONGUARDF
P.COM
OWNER THOMAS J GREGORY PO BOX 1248 SUNSET BEACH CA 90742 (702)966-8021
CONDITIONS
Description: STONE CREEK RANCH / FIRE SPRINKLERS / BRES2022-0047 / PLAN 1
Type: FIRE SPRINKLER (WEB)Subtype: RESIDENTIAL - TRACT
HOMES
Status: FINALED Applied: 5/6/2022 ECON
Parcel No: 762430041 Site Address: 80332 PALO VERDE PL LA QUINTA,CA 92253 Approved: 5/9/2022 AHI
Subdivision: TR 30834 Block: Lot: 59 Issued: ONLINE
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 1/11/2023 KHET
Valuation: $0.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Thursday, April 13, 2023 1:46:42 PM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0200
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD HYRO KHET 7/26/2022 7/26/2022 APPROVED
OVERHEAD ROUGH
PIPING KHET 7/26/2022 7/26/2022 DISAPPROVE
D
Fire Sprinklers need 3 feet of clearance from
Pendant lights.
Fire Sprinklers need 18 inches of clearance
from Smoke detectors.
Re-inspection required after all electrical
wiring is completed.
Confirm at final RSV valve installed.
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE FAILED OR
ADDITIONAL FIELD
INSPECTIONS
(EXCESSIVE) EACH
101-0000-42421 0 $175.00 $175.00 1/6/23 WEB13984 783661905 CREDIT 950378 ECON
FIRE FAILED OR
ADDITIONAL RE-
INSPECTION
101-0000-42421 0 $167.00 $167.00 8/31/22 WEB12934 716677483 CREDIT 950378 ECON
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $167.00 $167.00 5/10/22 WEB11693 637088739
21 CREDIT 950378 ECON
Total Paid for FIRE FEES: $509.00 $509.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $11.00 $11.00 5/10/22 WEB11693 637088739
21 CREDIT 950378 ECON
Total Paid for RECORDS MANAGEMENT FEE: $11.00 $11.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 5/10/22 WEB11693 637088739
21 CREDIT 950378 ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$525.00 $525.00
Printed: Thursday, April 13, 2023 1:46:42 PM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0200
ATTACHMENTS
BOND INFORMATION
OVERHEAD ROUGH
PIPING KHET 8/31/2022 8/31/2022 APPROVED
FIRE FINAL**LRO 12/29/2022 12/29/2022 CANCELED See Notes Contractor called to cancel Fire Inspection,
no fee's.
FIRE FINAL**LRO 1/6/2023 1/6/2023 DISAPPROVE
D See Notes
Water pressure too low possibly due to
check valve not functioning correctly.
Please replace Ordinary temperature
Sprinkler head to an Intermediate
temperature sprinkler head for proper
spacing and clearance issues in the master
bedroom. Please also verify that Sprinkler
head matches the K-factor and Serial
number per the plans.
FIRE FINAL**KHET 1/11/2023 1/11/2023 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST PERMIT TECH –
ETRAKIT (1 DAY)
PERMIT TECH
BUCKET
5/6/2022 5/9/2022 5/9/2022 COMPLETE
PARENT PROJECTS
Printed: Thursday, April 13, 2023 1:46:42 PM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0200