FSS2022-0220ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT SYMONS FIRE PROTECTION INC 9475 Chesapeake Drive san diego CA 92123 (619)588-6364 angela@symonsfp.com
CONTRACTOR SYMONS FIRE PROTECTION INC 9475 Chesapeake Drive san diego CA 92123 (619)588-6364 angela@symonsfp.com
OWNER National Mortgage & Land Co.81570 Carboneras LA QUINTA CA 92253 (619)588-6364 jlopez@andalusiacc.co
m
CONDITIONS
Description: ANDALUSIA / FIRE SPRINKLER / BRES2021-0691 / PLAN 202
Type: FIRE SPRINKLER (WEB)Subtype: RESIDENTIAL - TRACT
HOMES
Status: ISSUED Applied: 6/6/2022 ECON
Parcel No: 764200071 Site Address: 58995 MARBELLA LA QUINTA,CA 92253 Approved: 6/7/2022 AHI
Subdivision: 37790 Block: Lot: Issued: 6/8/2022 ONLINE
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled:
Valuation: $4,000.00 Occupancy Type: Construction Type: Expired: 3/25/2023 KHET
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details: fire sprinklers for lot 50019
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE FAILED OR
ADDITIONAL RE-
INSPECTION
101-0000-42421 0 $167.00 $167.00 9/23/22 WEB13143 730178910 CREDIT 682025 ECON
Printed: Thursday, April 13, 2023 2:33:37 PM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0220
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD HYRO KHET 8/16/2022 8/16/2022 APPROVED No leaks
OVERHEAD ROUGH
PIPING KHET 8/16/2022 8/16/2022 DISAPPROVE
D SEE NOTES
System was installed to "Old" plans and not
the Revised Approved plans, as required.
Several noted locations where too close to
HVAC diffuser and Pendant-Light/Ceiling-
fans
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE FAILED OR
ADDITIONAL RE-
INSPECTION
101-0000-42421 0 $167.00 $167.00 9/23/22 WEB13143 730178910 CREDIT 682025 ECON
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $167.00 $167.00 6/8/22 WEB12060 637566355
20 CREDIT 682025 ECON
Total Paid for FIRE FEES: $501.00 $501.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $11.00 $11.00 6/8/22 WEB12060 637566355
20 CREDIT 682025 ECON
Total Paid for RECORDS MANAGEMENT FEE: $11.00 $11.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 6/8/22 WEB12060 637566355
20 CREDIT 682025 ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$517.00 $517.00
Printed: Thursday, April 13, 2023 2:33:37 PM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0220
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 6/6/2022 Etrakit Contractor fire application FIREAPPLICATION LOT
50019.pdf 1
DOC 8/16/2022 KOHL HETRICK Lot 19 - 8-16-2022 Insp
Notes.pdf
Lot 19 - 8-16-2022 Insp
Notes.pdf 1
BOND INFORMATION
OVERHEAD ROUGH
PIPING LRO 9/7/2022 9/7/2022 DISAPPROVE
D See Notes
System was installed to "Old" plans and not
the Revised Approved plans, as required.
Sprinkler head K-factor number on the plans
do not match on what was found in person.
Replace high-temp head to match K-factor
per the plans, move hot air diffuser
accordingly to temperature of Sprinkler
head.
OVERHEAD ROUGH
PIPING KHET 9/26/2022 9/26/2022 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST PERMIT TECH –
ETRAKIT (1 DAY)
PERMIT TECH
BUCKET
6/6/2022 6/7/2022 6/7/2022 COMPLETE
PARENT PROJECTS
Printed: Thursday, April 13, 2023 2:33:37 PM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0220
A 10% REDUCTION WAS TAKEN OFF FOR CALC
PURPOSES. STATIC PRESSURE IS CALCULATED AT
86.4 PSI PER COACHELLA VALLEY
WATER DISTRICT. RESIDUAL SYSTEM WAS
CALCULATED AT 77.7 PSI.
ALL ROOMS ARE BASED ON 15x15 FT SPACING.
CALCULATIONS ARE BASED ON THE WORST
CASE SCENARIO TWO HEAD
CALC ON 15 FT SPACING
4
FS1
A
FS1
A
18 sq.ft.
16 sq.ft.
18 sq.ft.
7 sq.ft.
18 sq.ft.
23 sq.ft.
HEAT ZONE
HEAT ZONE
PLAN TYPE 202 FLOOR PIPING PLAN
1" RISER IN WALL
W/ INT. LABELED
ACCESS PANEL
9 sq.ft.
17 sq.ft.
DN 2'-6
UP 2'-6
DN
UP 6'-6"6'-8"5'-6"2'-6"7'11'-3"2'-10"7'-6"10'-1"5'-6"11'-1"5'-6"4'-6"7'5'-4"
7'-6"8'-6"2'-6"3'7'-3"14'-6"7'-6"5'-6"13'-7"13'-6"7'-3"
12'-4"15'4'
6'-8"
L
L
L
L
L
J
L L L
L
L
L
L
L
L
L
L
L
L
L L
L
L
L
L
L
L
L
L
L
J
LL
L
L
L
L
L
L
L
L
L
L
L
L L LL
L
L
L
L
L
L
L
L
L
L
L
L
L L L
L L
L
J
L AL
L
LL
LACAF
J
S/C
S/C S/C
TAG
J
L
LL
L
L
L
VGFI
L
L
L
L
L
L
L
L
J J J
L
L COURTYARD
PATIO
12'-1" CLG.
GREAT ROOM
12'-1" CLG.
BATH
10'-1" CLG.
MASTER
KITCHEN
12'-1" CLG.
PORTICO
PWDR
BATH 3
10'-1" CLG.CASITA
10'-1" CLG.
PORCHENTRY
12'-1" CLG.
GARAGEGOLF CART
LAUN.
10'-1" CLG.
SITTING
12'-1" CLG.
BEDROOM
10'-1" CLG.
MASTER
BEDROOM 2
10'-1" CLG.
HALL
BATH 2
10'-1" CLG.
CLOSET10'-1" CLG.
WALK-IN
COVERED
10'-1" CLG.
16'-1" CLG.
DW
GARAGE2-CAR
WH
A/C A/CA/C
10'-1" CLG.KITCHENETTE\A1;\A1;
PWDR10'-1" CLG.
\A1;\A1;
Residential AREA 1 ?0.05gpm/ft² for 253ft²
5
B.O.R.
6
212 213
39
Hydraulic Information
OCCUPANCY CLASSIFICATION Residential AREA 1
DENSITY (gpm/ft²)0.05 for 800ft² (Actual 253ft²)
TOTAL HOSE STREAMS 5.00
TOTAL HEADS FLOWING 2
K-FACTOR 4.3
TOTAL WATER REQUIRED 29.22
TOTAL PRESSURE REQUIRED 53.249
BASE of RISER (gpm)24.22
BASE of RISER (psi)30.034
SAFETY MARGIN (psi)+33.145 (38.4%)
NVICINITY MAP N.T.S.
2-CAR GARAGEBATH2GREAT ROOM OFFICESITTING
12
4
SPRINKLER SHUT OFF
(ABOVE GROUND)
3/4" WATER METER
EL= -3'
TRANSITION FROM
COPPER TO CPVC
50' OF 2" PVC PIPE
1
5' OF 1" COPPER
(SWEEP)
B.O.R. EL= 1'
EL= -6'
4
1" COP
LATERAL
8" MAIN UNDERGROUND DETAIL
N.T.S.
6
5
½" DRAIN
FLOW SWITCH
1" CHECK VALVE
TRANSITION FROM PVC
TO COPPER
PLUMBING
SHUT OFF
DOMESTIC PLUMBING
REGULATOR
1" CPVC
300 PSI GAUGE
2 3 1" CPVC 1" CPVC EL= -9'5 GPM TO DOMESTIC PLUMBINGSprinkler Legend
Symbol Manufacturer SIN Model Quantity K-Factor Type Size Response Finish Temperature
Reliable R3511 F1RES30 5 3 Pendent ½Fast White 175°F
Total = 5
Hydraulic Information
OCCUPANCY CLASSIFICATION Residential AREA 1
DENSITY (gpm/ft²)0.05 for 800ft² (Actual 253ft²)
TOTAL HOSE STREAMS 5.00
TOTAL HEADS FLOWING 2
K-FACTOR 4.3
TOTAL WATER REQUIRED 29.22
TOTAL PRESSURE REQUIRED 53.249
BASE of RISER (gpm)24.22
BASE of RISER (psi)30.034
SAFETY MARGIN (psi)+33.145 (38.4%)
Hydraulic Information
OCCUPANCY CLASSIFICATION Residential AREA 1
DENSITY (gpm/ft²)0.05 for 800ft² (Actual 253ft²)
TOTAL HOSE STREAMS 5.00
TOTAL HEADS FLOWING 2
K-FACTOR 4.3
TOTAL WATER REQUIRED 29.22
TOTAL PRESSURE REQUIRED 53.249
BASE of RISER (gpm)24.22
BASE of RISER (psi)30.034
SAFETY MARGIN (psi)+33.145 (38.4%)
Hydraulic Information
OCCUPANCY CLASSIFICATION Residential AREA 1
DENSITY (gpm/ft²)0.05 for 800ft² (Actual 253ft²)
TOTAL HOSE STREAMS 5.00
TOTAL HEADS FLOWING 2
K-FACTOR 4.3
TOTAL WATER REQUIRED 29.22
TOTAL PRESSURE REQUIRED 53.249
BASE of RISER (gpm)24.22
BASE of RISER (psi)30.034
SAFETY MARGIN (psi)+33.145 (38.4%)
Hydraulic Information
OCCUPANCY CLASSIFICATION Residential AREA 1
DENSITY (gpm/ft²)0.05 for 800ft² (Actual 253ft²)
TOTAL HOSE STREAMS 5.00
TOTAL HEADS FLOWING 2
K-FACTOR 4.3
TOTAL WATER REQUIRED 29.22
TOTAL PRESSURE REQUIRED 53.249
BASE of RISER (gpm)24.22
BASE of RISER (psi)30.034
SAFETY MARGIN (psi)+33.145 (38.4%)
7'-0"
1 ¼"6'-6"
1 ½"
SPACING
6'-0"1"
MAX. HANGER
CPVC PIPING APPLICATION
5'-6"
SIZES
2"8'-0"
HANGER LOCATIONS
ARE TO BE PLACED PER
MFRS. SPECIFICATIONS
¾"
PIPE
FIGURE 23 - CPVC HANGER
CPVC DOUBLE FASTENER STRAP TYPE HANGER
HARDENED HEX HEAD SELF THREADING SCREW
IS FURNISHED WITH THE HANGER AND IS THE
MINIMUM FASTENER SIZE ACCEPTABLE
FIGURE 22 - CPVC HANGERCPVC SINGLE FASTENER STRAP TYPE HANGER
MINIMUM FASTENER SIZE ACCEPTABLE
IS FURNISHED WITH THE HANGER AND IS THE
HARDENED HEX HEAD SELF THREADING SCREW
FIGURE 24 - CPVC HANGERCPVC DOUBLE FASTENER STRAP TYPE HANGER
MINIMUM FASTENER SIZE ACCEPTABLE
IS FURNISHED WITH THE HANGER AND IS THE
HARDENED HEX HEAD SELF THREADING SCREW
PIPING PLAN
¼"=1'-0"
ALL 1" CPVC PIPING
SCALE: 1/4"=1'-0"FIRE SPRINKLER & PIPING PLAN
THE RECIPIENT OF THESE PLANS HEREBY ACKNOWLEDGES THAT ALL PLANS, DETAILS, SPECIFICATIONS AND/OR METHODS OF INSTALLATION CONTAINED IN THIS SET OF DRAWINGS IS THE SOLE PROPERTY OF SYMONS FIRE PROTECTION, INC., AND THAT ANY USE OF THIS SET OF DRAWINGS IS PROHIBITED AND IS A VIOLATION OF COPYRIGHT LAWS WITHOUT FIRST RECEIVING PERMISSION FROM SYMONS FIRE PROTECTION, INC.MARBELLALA QUINTA, CA 92253LA QUINTA FIRE DEPTDRAWING TITLEIRDATE12. 31. 22AFIRE SPRINKLER SYSTEMCSN
PPROJECT:EAOCTC
05-10-2022DATE :PHONE.NT
OCONTRACT WITH:RIFS1 LO
OSNATIONAL MORTGAGE ANDLAND CO.IDRAWN BY: DEREK POWELLAUTHORITY HAVING JURISDICTIONREVISIONS-N
R
BYIT
O
FSL-IC
OCT(760) 777-7125N
MSCALE :OO
MARKFIC16/C10RT
Y-TEF-NEEEF20-0577TJOB NO.
A
ANDALUSIA PLAN 202EERR
DESCRIPTIONASHEET NO.
I
682025AS NOTEDI9475 CHESAPEAKE DR, SAN DIEGO, CA 92123 (619) 588-6364 WWW.SYMONSFP.COM CA. C10 & C16 LIC. #682025 RS,CCOPDEXP. DATETNN
-
1. THIS IS A WET PIPE SPRINKLER SYSTEM DESIGNED & INSTALLED PER CRC 313.3, CFC
2019, AND/OR NFPA 13D (2016 EDITION) AND THE LA QUINTA FIRE DEPT.
2. ALL PIPE AND FITTINGS ARE NEW, UL LISTED, AND CONFORM
TO THE STANDARDS OF NFPA 13D 2016 EDITION.
3. PROVIDE ELECTRICAL BELL FOR LOCAL ALARM. WIRING BY OTHERS.
SIZE AND LOCATION ON PLANS. WATERFLOW ALARM REQUIRED TO BE CLEARLY
AUDIBLE IN ALL LIVING SPACES OVER BACKGROUND NOISE WITH ALL INTERVENING
DOORS CLOSED.
4. STORAGE IN ATTIC & CRAWL SPACES NOT ALLOWED WHERE NOT PROTECTED.
5. GARAGE & MECHANICAL ROOMS TO BE SPRINKLERED W/175* HEADS
6. SPRINKLER HEADS OMITTED FROM BATHROOMS AND CLOSETS THAT MEET THE
CONDITIONS OF 8.3.2 & 8.3.3 NFPA 13D 2016 EDITION.
7. - INDICATES HYD. CALC. REFERENCE POINT.
8. DRILLING OR NOTCHING OF STRUCTURAL MEMBERS SHALL BE IN STRICT
ACCORDANCE WITH CBC & CRC - (2016)
9. ALL PENETRATIONS THROUGH FIREWALLS & CEILINGS BETWEEN ATTACHED GARAGE
& RESIDENCE WILL BE SEALED IN AN APPROVED MANNER TO MAINTAIN INTEGRITY
OF THE FIREWALL.
10. MAINTENANCE BOOK & 1 HEAD (UP TO 3 OF EACH IF REQUIRED) OF EACH TYPE USED
PLUS HEAD WRENCH SHALL BE PROVIDED IN SPARE HEAD CABINET LOCATED
NEXT TO RISER.
11. PIPE HANGERS SHALL BE IN ACCORDANCE WITH NFPA 13D & THE WRITTEN
INSTRUCTIONS OF THE PIPE MANUFACTURER.
12. ANY SPRINKLERS THAT HAVE BEEN PAINTED OUTSIDE OF THE FACTORY SHALL BE
REPLACED WITH A NEW LISTED SPRINKLER PER NFPA 13D STANDARDS.
13. EXTERIOR EXPOSED STEEL PIPING PAINTED.(BY OTHERS)
14. CONTRACTOR/OWNER IS RESPONSIBLE FOR INSTALLATION OF UNDERGROUND.
(CHECK WITH SYMONS FIRE PROTECTION FOR PROPER SIZING.)
15. SMOKE DETECTORS ARE TO BE INSTALLED IN ACCORDANCE WITH NFPA 72,
NATIONAL FIRE CODE (AND TO BE INSTALLED BY OTHERS.)
GENERAL NOTES
RESIDUAL PSI AT SOURCE
STATIC PSI:
SYSTEM FLOW REQUIREMENTS: REMOTE AREA 1
GPM FLOWING W/
4.3 K-FACTOR
FLOWS PER HEAD =
SPRINKLER FLOW REQ. @
1HD =
SPRINKLER SYSTEM DESIGN CRITERIA & FLOW REQUIREMENTS
COCHELLA VALLEY
1HD =
PHONE NUMBER:
CONTACT:
15' SPACING
REL. RFC43 CONCL. FLAT
7'-6 MAX OFF WALL
96.0 PSIDATE OBTAINED:
GPM FLOWING W/
R. MONTEL
RESIDUAL PSI AT BASE OF RISER
(SIN) # RA0612
WATER FLOW INFO BY:
DESIGN SPRINKLER =
12.0 GPM @ 7.8 PSI
7-28-21
760 398 2661
SECTION 'A'SCALE 1/4" = 1'-0"SITE PLAN SCALE 1" = 240'-0"AS BUILT