FSS2022-0231ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT J D MECHANICAL FIRE INC 82579 FLEMING WAY
SUITE D
INDIO CA 92201 (760)775-6220 AMANDA@JDMECHAN
ICAL.CO
CONTRACTOR J D MECHANICAL FIRE INC 82579 FLEMING WAY
SUITE D
INDIO CA 92201 (760)775-6220 AMANDA@JDMECHAN
ICAL.CO
OWNER GALA ASHER 53060 ROSS AVE LA QUINTA CA 92253 (760)775-6220
CONDITIONS
Description: CLOUD NINE RESOTR / FIRE SPRINKLERS / BRES2021-0074
Type: FIRE SPRINKLER (WEB)Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 6/7/2022 ECON
Parcel No: 767680016 Site Address: 53060 ROSS AVE LA QUINTA,CA 92253 Approved: 7/13/2022 KHET
Subdivision: TR 33076-1 Block: Lot: 54 Issued: ONLINE
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 2/22/2023 LRO
Valuation: $10,000.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Thursday, April 13, 2023 2:53:51 PM 1 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0231
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD HYRO KHET 9/6/2022 9/6/2022 APPROVED No leaks
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE FAILED OR
ADDITIONAL FIELD
INSPECTIONS
(EXCESSIVE) EACH
101-0000-42421 0 $175.00 $175.00 2/22/23 WEB14430 819829694 CREDIT 1020141 ECON
FIRE FAILED OR
ADDITIONAL RE-
INSPECTION
101-0000-42421 0 $167.00 $167.00 9/22/22 WEB13124 729252645 CREDIT 1020141 ECON
FIRE PLAN REVISION
SUBMITTALS 101-0000-42420 0 $167.00 $167.00 9/22/22 WEB13124 729252645 CREDIT 1020141 ECON
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $250.00 $250.00 8/22/22 WEB12833 711202122 CREDIT 1020141 ECON
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $250.00 $250.00 8/22/22 WEB12833 711202122 CREDIT 1020141 ECON
Total Paid for FIRE FEES: $1,009.00 $1,009.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $11.00 $11.00 8/22/22 WEB12833 711202122 CREDIT 1020141 ECON
Total Paid for RECORDS MANAGEMENT FEE: $11.00 $11.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 8/22/22 WEB12833 711202122 CREDIT 1020141 ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$1,025.00 $1,025.00
Printed: Thursday, April 13, 2023 2:53:51 PM 2 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0231
BOND INFORMATION
OVERHEAD ROUGH
PIPING KHET 9/6/2022 9/6/2022 DISAPPROVE
D SEE NOTES
Observed significant as-built changes that
require revised plans and calculations to
justify prior to giving clearance of overhead
rough.
Reinspection required as well for contact
hazards.
Provided revised plans and calcs prior to
OVERHEAD ROUGH
PIPING LRO 9/28/2022 9/28/2022 APPROVED
Confirm Water meter at final inspection.
Confirm clearance from fire place heat
source, ordinary versus intermediate
temperature throughout home.
FIRE FINAL**LRO 2/21/2023 2/21/2023 DISAPPROVE
D See Notes
Several Sprinkler head caps still attached,
need to be presented with cap and with
cover plate. (2nd and 1st story Mechanical
rooms)
FIRE FINAL**LRO 2/22/2023 2/22/2023 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST FIRE - ETRAKIT
(2 WK)
KOHL
HETRICK
6/7/2022 6/21/2022 7/13/2022 APPROVED SEE ATTACHMENTS
1ST PERMIT TECH –
ETRAKIT (1 DAY)
PERMIT TECH
BUCKET
6/7/2022 6/8/2022 6/8/2022 COMPLETE
2ND FIRE (1 WK)KOHL
HETRICK
9/19/2022 9/26/2022 9/19/2022 APPROVED REVISED PLANS/CALCS SEE ATTACHMENTS
PARENT PROJECTS
Printed: Thursday, April 13, 2023 2:53:51 PM 3 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0231
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 6/7/2022 Etrakit Contractor
1ST SUBMITTAL
HYDRAULIC
CALCULATIONS 1
AREA 1.pdf 1
DOC 6/7/2022 Etrakit Contractor
1ST SUBMITTAL
HYDRAULIC
CALCULATIONS 2
AREA 2.pdf 1
DOC 6/7/2022 Etrakit Contractor
1ST SUBMITTAL
HYDRAULIC
CALCULATIONS 3
AREA 3.pdf 1
DOC 6/7/2022 Etrakit Contractor
1ST SUBMITTAL
HYDRAULIC
CALCULATIONS 4
AREA 4.pdf 1
DOC 6/7/2022 Etrakit Contractor 1ST SUBMITTAL
SPRINKLER PLAN MAD 54 FS PLAN.pdf 1
DOC 6/7/2022 Etrakit Contractor 1ST SUBMITTAL CVWD 54 water
CONNECTION.pdf 1
DOC 6/7/2022 Etrakit Contractor 1ST SUBMITTAL SENJU 8464 Senju Concealed
4.9.pdf 1
DOC 9/19/2022 Etrakit Contractor AREA 1 corrections lot
54.pdf 1
DOC 9/19/2022 Etrakit Contractor AREA 2 corrections lot
54.pdf 1
DOC 9/19/2022 Etrakit Contractor AREA 3 corrections lot
54.pdf 1
DOC 9/19/2022 Etrakit Contractor MAD 54 AS BUILT
corrections lot 54.pdf 1
DOC 9/22/2022 Etrakit Contractor AREA 1 54 corrections X
2.pdf 1
DOC 9/22/2022 Etrakit Contractor AREA 2 lot 54
corrections X2.pdf 1
Printed: Thursday, April 13, 2023 2:53:51 PM 4 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0231
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 9/22/2022 Etrakit Contractor AREA 3 lot 54
corrections X2.pdf 1
DOC 9/22/2022 Etrakit Contractor MAD 54 AS BUILT lot 54
corrections X2.pdf 1
DOC 7/13/2022 KOHL HETRICK
FSS2022-0231 -
APPROVED PLANS AND
CALCS.pdf
FSS2022-0231 -
APPROVED PLANS AND
CALCS_1.pdf
1
DOC 7/13/2022 KOHL HETRICK FSS2022-0231 - COA
AND JOB CARD.pdf
FSS2022-0231 - COA
AND JOB CARD.pdf 1
DOC 9/6/2022 KOHL HETRICK
Pages from FSS2022-
0231 - 9-6-2022 insp
notes.pdf
Pages from FSS2022-
0231 - 9-6-2022 insp
notes.pdf
0
DOC 9/19/2022 KOHL HETRICK
FSS2022-0231 - REV 1 -
APPROVED PLANS AND
CALCS.pdf
FSS2022-0231 - REV 1 -
APPROVED PLANS AND
CALCS.pdf
1
Printed: Thursday, April 13, 2023 2:53:51 PM 5 of 5
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0231
APPROVEDRiverside County Fire DepartmentLa Quinta Office of the Fire MarshalBy:FIRE SAFETY SPECIALIST09/19/2022 2:36:07 PMThe approval of plans and specifications does notpermit the violation, deletion, omission or faultyinstallation of any requirements of Title 24 or anyLocal Ordinances. Construction shall remainaccessible and exposed for inspection purposesuntil approved by the Fire Department.PERMIT # -FSS2022-0231 REV1Kohl HetrickReason: I have reviewed this documentContact Info: 760-409-5109
16'7'
7'-8"7'-5"7'-1"7'-10"
8'15'-10"= HYDRAULIC NODE POINT( IN FEET )GRAPHIC SCALE0203/16 inch = 1'-0"0105JD MECHANICAL FIRE INC
6'-8"8'9'
8'-6"
1"1"1"
1"1"1"
1"1"
1"1"1"1"1"1"1"1"1"1"1"1"1"1"1"1"1"1"
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Living Water Designs Mad 54
Prescott, AZ 86301 Page 1
General Project Data Report
General Data
Project Title: Mad 54 Project File Name: Mad 54..fiw
Designed By: Marissa Ryan Date: 9/19/22
Code Reference:Approving Agency:
Client Name:Phone:
Address:City, State Zip Code:
Company Name: JD Mechanical Representative: Kathy Sloan
Company Address: 82579 Fleming Way Ste D City And State: Indio, CA 92201
Phone: 760-775-6220
Building Name: AREA 1 Building Owner:
Contact at Building:Phone at Building:
Address Of Building: 53060 Ross Ave City, State Zip Code:
Project Data
Description Of Hazard: Residential Sprinkler System Type: Wet
Design Area Of Water Application: 512 ft² Maximum Area Per Sprinkler: 256 ft²
Default Sprinkler K-Factor: 4.90 K Default Pipe Material: CPVC
Inside Hose Stream Allowance: 0.00 gpm Outside Hose Stream Allowance: 0.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm
Sprinkler Specifications
Make: SENJU Model:8464
Size:7/16 Temperature Rating: 162 F
F = T RUN / B = ANGLE VALVE
Water Supply Test Data
Source Of Information:
Test Hydrant ID:Date Of Test:
Hydrant Elevation: 0 ft Static Pressure: 58.00 psi
Test Flow Rate: 1000.00 gpm Test Residual Pressure: 52.20 psi
Calculated System Flow Rate: 31.13 gpm Calculated Inflow Residual Pressure: 51.19 psi
Available Residual Pressure At
System Flow:57.99 psi
Calculation Project Data
Calculation Mode: Demand
HMD Minimum Residual Pressure: 7.05 psi Minimum Desired Flow Density: 0.05 gpm/ft²
Number Of Active Nodes: 34
Number Of Active Pipes: 36 Number Of Inactive Pipes: 161
Number Of Active Sprinklers: 2 Number Of Inactive Sprinklers: 0
C:\ ...\Mad 54.fiw Monday, September 19, 2022, 11:07 AM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Living Water Designs Mad 54
Prescott, AZ 86301 Page 2
Fire Sprinkler Output Data
Overall Pipe Output Data
Beg.
End.
Node
Nodal
KFactor
(K)
Elevation
(feet)
Spk/Hose
Discharge
(gpm)
Residual
Pressure
(psi)
Nom. Dia.
Inside Dia.
C-Value
q (gpm)
Q (gpm)
Velocity
(fps)
F. L./ft
(psi/ft)
Fittings
Type-Grp
Pipe-Len.
Fit-Len.
Tot-Len.
(ft)
PF-(psi)
PE-(psi)
PT-(psi)
1 4.90 13.00 13.01 7.05 0.75 13.01 0.09454 0.50 0.331
2 0.00 13.50 0.00 7.16 0.874 13.01 T 3.00 -0.217
CPVC 150 6.96 0 3.50 0.114
3 4.90 13.00 13.12 7.17 0.75 13.12 0.09609 0.50 0.721
4 0.00 13.50 0.00 7.68 0.874 13.12 E 7.00 -0.217
CPVC 150 7.02 0 7.50 0.504
2 0.00 13.50 0.00 7.16 0.75 0.00 0.09454 7.50 0.993
22 0.00 13.50 0.00 8.16 0.874 13.01 T 3.00 0.000
CPVC 150 6.96 0 10.50 0.993
4 0.00 13.50 0.00 7.68 0.75 0.00 0.09610 2.00 0.481
22 0.00 13.50 0.00 8.16 0.874 13.12 T 3.00 0.000
CPVC 150 7.02 0 5.00 0.481
22 0.00 13.50 0.00 8.16 0.75 0.00 0.34364 2.50 1.890
24 0.00 13.50 0.00 10.05 0.874 26.13 T 3.00 0.000
CPVC 150 13.97 0 5.50 1.890
24 0.00 13.50 0.00 10.05 1.00 13.73 0.03395 13.00 0.611
26 0.00 13.50 0.00 10.66 1.101 13.73 T 5.00 0.000
CPVC 150 4.63 0 18.00 0.611
27 0.00 13.50 0.00 36.87 0.75 0.00 0.00000 5.00 0.000
28 0.00 13.50 0.00 36.87 0.874 0.00 T 3.00 0.000
CPVC 150 0.00 0 8.00 0.000
28 0.00 13.50 0.00 36.87 0.75 0.00 0.00000 11.50 0.000
32 0.00 22.00 0.00 33.19 0.874 0.00 T 3.00 3.681
CPVC 150 0.00 0 14.50 3.681
6 0.00 22.00 0.00 33.19 0.75 0.00 0.00000 12.50 0.000
30 0.00 22.00 0.00 33.19 0.874 0.00 E 7.00 0.000
CPVC 150 0.00 0 19.50 0.000
8 0.00 22.00 0.00 33.19 0.75 0.00 0.00000 3.00 0.000
30 0.00 22.00 0.00 33.19 0.874 0.00 F 1.00 0.000
CPVC 150 0.00 0 4.00 0.000
30 0.00 22.00 0.00 33.19 0.75 0.00 0.00000 13.00 0.000
32 0.00 22.00 0.00 33.19 0.874 0.00 FT 4.00 0.000
CPVC 150 0.00 0 17.00 0.000
32 0.00 22.00 0.00 33.19 0.75 0.00 0.00000 1.00 0.000
33 0.00 22.00 0.00 33.19 0.874 0.00 T 3.00 0.000
CPVC 150 0.00 0 4.00 0.000
C:\ ...\Mad 54.fiw Monday, September 19, 2022, 11:07 AM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Living Water Designs Mad 54
Prescott, AZ 86301 Page 3
Fire Sprinkler Output Data
Overall Pipe Output Data (cont'd)
Beg.
End.
Node
Nodal
KFactor
(K)
Elevation
(feet)
Spk/Hose
Discharge
(gpm)
Residual
Pressure
(psi)
Nom. Dia.
Inside Dia.
C-Value
q (gpm)
Q (gpm)
Velocity
(fps)
F. L./ft
(psi/ft)
Fittings
Type-Grp
Pipe-Len.
Fit-Len.
Tot-Len.
(ft)
PF-(psi)
PE-(psi)
PT-(psi)
10 0.00 22.00 0.00 33.19 0.75 0.00 0.00000 1.50 0.000
34 0.00 22.00 0.00 33.19 0.874 0.00 F 1.00 0.000
CPVC 150 0.00 0 2.50 0.000
33 0.00 22.00 0.00 33.19 0.75 0.00 0.00000 16.00 0.000
34 0.00 22.00 0.00 33.19 0.874 0.00 T 3.00 0.000
CPVC 150 0.00 0 19.00 0.000
33 0.00 22.00 0.00 33.19 0.75 0.00 0.00000 52.50 0.000
36 0.00 22.00 0.00 33.19 0.874 0.00 6FT 9.00 0.000
CPVC 150 0.00 0 61.50 0.000
34 0.00 22.00 0.00 33.19 0.75 0.00 0.00000 30.00 0.000
38 0.00 22.00 0.00 33.19 0.874 0.00 2F2T 8.00 0.000
CPVC 150 0.00 0 38.00 0.000
36 0.00 22.00 0.00 33.19 0.75 0.00 0.00000 33.00 0.000
40 0.00 22.00 0.00 33.19 0.874 0.00 2FT 5.00 0.000
CPVC 150 0.00 0 38.00 0.000
38 0.00 22.00 0.00 33.19 0.75 0.00 0.00000 39.00 0.000
40 0.00 22.00 0.00 33.19 0.874 0.00 5FE 12.00 0.000
CPVC 150 0.00 0 51.00 0.000
40 0.00 22.00 0.00 33.19 1.00 0.00 0.00000 13.00 0.000
42 0.00 22.00 0.00 33.19 1.101 0.00 F2E 15.00 0.000
CPVC 150 0.00 0 28.00 0.000
24 0.00 13.50 0.00 10.05 1.00 12.40 0.02809 36.50 1.194
44 0.00 22.00 0.00 7.56 1.101 12.40 6F 6.00 -3.681
CPVC 150 4.18 0 42.50 -2.486
26 0.00 13.50 0.00 10.66 1.00 0.00 0.03395 57.50 2.156
46 0.00 13.50 0.00 12.81 1.101 13.73 6F 6.00 0.000
CPVC 150 4.63 0 63.50 2.156
44 0.00 22.00 0.00 7.56 1.00 0.00 0.02809 43.00 1.573
46 0.00 13.50 0.00 12.81 1.101 12.40 6FE 13.00 3.681
CPVC 150 4.18 0 56.00 5.254
27 0.00 13.50 0.00 36.87 1.00 0.00 0.00000 30.50 0.000
48 0.00 13.50 0.00 36.87 1.101 0.00 4F2ET 23.00 0.000
CPVC 150 0.00 0 53.50 0.000
46 0.00 13.50 0.00 12.81 1.00 0.00 0.11162 50.00 10.158
50 0.00 12.50 0.00 23.41 1.101 26.13 8F4ET 41.00 0.433
CPVC 150 8.81 0 91.00 10.591
C:\ ...\Mad 54.fiw Monday, September 19, 2022, 11:07 AM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Living Water Designs Mad 54
Prescott, AZ 86301 Page 4
Fire Sprinkler Output Data
Overall Pipe Output Data (cont'd)
Beg.
End.
Node
Nodal
KFactor
(K)
Elevation
(feet)
Spk/Hose
Discharge
(gpm)
Residual
Pressure
(psi)
Nom. Dia.
Inside Dia.
C-Value
q (gpm)
Q (gpm)
Velocity
(fps)
F. L./ft
(psi/ft)
Fittings
Type-Grp
Pipe-Len.
Fit-Len.
Tot-Len.
(ft)
PF-(psi)
PE-(psi)
PT-(psi)
48 0.00 13.50 0.00 36.87 1.00 0.00 0.00000 49.50 0.000
52 0.00 13.50 0.00 36.87 1.101 0.00 7F4ET 40.00 0.000
CPVC 150 0.00 0 89.50 0.000
42 0.00 22.00 0.00 33.19 1.00 0.00 0.00000 11.50 0.000
53 0.00 13.50 0.00 36.87 1.101 0.00 E 7.00 3.681
CPVC 150 0.00 0 18.50 3.681
52 0.00 13.50 0.00 36.87 1.00 0.00 0.00000 31.00 0.000
54 0.00 14.50 0.00 36.44 1.101 0.00 F2E2T 25.00 -0.433
CPVC 150 0.00 0 56.00 -0.433
53 0.00 13.50 0.00 36.87 1.00 0.00 0.00000 13.00 0.000
54 0.00 14.50 0.00 36.44 1.101 0.00 2F 2.00 -0.433
CPVC 150 0.00 0 15.00 -0.433
50 0.00 12.50 0.00 23.41 1.00 0.00 0.11162 34.50 4.856
56 0.00 12.50 0.00 28.26 1.101 26.13 9F 9.00 0.000
CPVC 150 8.81 0 43.50 4.856
54 0.00 14.50 0.00 36.44 1.00 0.00 0.00000 63.50 0.000
58 0.00 10.50 0.00 38.17 1.101 0.00 10F4E2T 48.00 1.732
CPVC 150 0.00 0 111.50 1.732
56 0.00 12.50 0.00 28.26 1.00 0.00 0.11162 49.00 9.041
58 0.00 10.50 0.00 38.17 1.101 26.13 8F2E2T 32.00 0.866
CPVC 150 8.81 0 81.00 9.907
58 0.00 10.50 0.00 38.17 1.00 0.00 0.11164 3.00 1.116
100 0.00 10.50 0.00 39.28 1.101 26.13 E 7.00 0.000
CPVC 150 8.81 0 10.00 1.116
100 0.00 10.50 0.00 39.28 1.00 0.00 0.11164 11.00 2.858
125 0.00 0.00 0.00 46.69 1.101 26.13 2FEC 14.60 4.547
CPVC 150 8.81 0 25.60 7.405
125 0.00 0.00 0.00 46.69 1.00 0.00 0.15816 1.00 1.265
140 0.00 0.00 5.00 47.95 1.025 26.13 T 7.00 0.000
TYPE L COPPER TUBE 150 10.16 0 8.00 1.265
140 0.00 0.00 5.00 47.95 1.25 5.00 0.07849 4.00 1.036
160 0.00 -3.00 0.00 50.29 1.265 31.13 3EG 9.20 1.299
TYPE L COPPER TUBE 150 7.95 0 13.20 2.335
160 0.00 -3.00 0.00 50.29 2.00 0.00 0.01349 60.00 0.904
180 0.00 -3.00 0.00 51.19 1.816 31.13 F 7.00 0.000
HDPE SDR-9 150 3.86 0 67.00 0.904
C:\ ...\Mad 54.fiw Monday, September 19, 2022, 11:07 AM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Living Water Designs Mad 54
Prescott, AZ 86301 Page 5
Fire Sprinkler Output Summary
Hydraulically Most Demanding Sprinkler Node
HMD Sprinkler Node Number:1
HMD Actual Residual Pressure:7.05 psi
HMD Actual Flow:13.01 gpm
Sprinkler Summary
Sprinkler System Type:Wet
Specified Area Of Application: 512.00 ft²
Minimum Desired Density:0.050 gpm/ft²
Application Average Density:0.051 gpm/ft²
Application Average Area Per Sprinkler: 256.00 ft²
Sprinkler Flow:26.13 gpm
Average Sprinkler Flow:13.07 gpm
Flow Velocity And Imbalance Summary
Maximum Flow Velocity ( In Pipe 22 - 24 ) 13.97 ft/sec
Maximum Velocity Pressure ( In Pipe 22 - 24 ) 1.31 psi
Allowable Maximum Nodal Pressure Imbalance: 0.0100 psi
Actual Maximum Nodal Pressure Imbalance: 0.0091 psi
Actual Average Nodal Pressure Imbalance: 0.0063 psi
Actual Maximum Nodal Flow Imbalance: -0.0026 gpm
Actual Average Nodal Flow Imbalance: 0.0004 gpm
Overall Network Summary
Number Of Unique Pipe Sections: 36
Number Of Flowing Sprinklers:2
Pipe System Water Volume:31.62 gal
Sprinkler Flow:26.13 gpm
Non-Sprinkler Flow:5.00 gpm
Minimum Required Residual Pressure At System Inflow
Node:51.19 psi
Demand Flow At System Inflow Node: 31.13 gpm
C:\ ...\Mad 54.fiw Monday, September 19, 2022, 11:07 AM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Living Water Designs Mad 54
Prescott, AZ 86301 Page 6
Fire Sprinkler Output Data
Hydraulic Supply/Demand Graph
Pressure psiFlowrate(x100) gpm
58
5252
0
10
20
30
40
50
60
70
80
90
100
1 2 3 4 5 6 7 8 9 10
Supply Curve Data
Static Pressure: 58 psi
Test Residual Pressure: 52.2 psi
Test Flow Rate: 1000 gpm
Demand Curve Data
Calculated Residual Pressure: 51.19 psi
Calculated Flow Rate: 31.13 gpm
Excess Available Residual Pressure At Calculated Flow: 6.8 psi
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 0.00 psi
C:\ ...\Mad 54.fiw Monday, September 19, 2022, 11:07 AM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Living Water Designs Mad 54
Prescott, AZ 86301 Page 1
General Project Data Report
General Data
Project Title: Mad 54 Project File Name: Mad 54..fiw
Designed By: Marissa Ryan Date: 9/19/22
Code Reference:Approving Agency:
Client Name:Phone:
Address:City, State Zip Code:
Company Name: JD Mechanical Representative: Kathy Sloan
Company Address: 82579 Fleming Way Ste D City And State: Indio, CA 92201
Phone: 760-775-6220
Building Name: AREA 2 Building Owner:
Contact at Building:Phone at Building:
Address Of Building: 53060 Ross Ave City, State Zip Code:
Project Data
Description Of Hazard: Residential Sprinkler System Type: Wet
Design Area Of Water Application: 512 ft² Maximum Area Per Sprinkler: 256 ft²
Default Sprinkler K-Factor: 4.90 K Default Pipe Material: CPVC
Inside Hose Stream Allowance: 0.00 gpm Outside Hose Stream Allowance: 0.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm
Sprinkler Specifications
Make: SENJU Model:8464
Size:7/16 Temperature Rating: 162 F
F = T RUN / B = ANGLE VALVE
Water Supply Test Data
Source Of Information:
Test Hydrant ID:Date Of Test:
Hydrant Elevation: 0 ft Static Pressure: 58.00 psi
Test Flow Rate: 1000.00 gpm Test Residual Pressure: 52.20 psi
Calculated System Flow Rate: 32.15 gpm Calculated Inflow Residual Pressure: 48.35 psi
Available Residual Pressure At
System Flow:57.99 psi
Calculation Project Data
Calculation Mode: Demand
HMD Minimum Residual Pressure: 7.05 psi Minimum Desired Flow Density: 0.05 gpm/ft²
Number Of Active Nodes: 34
Number Of Active Pipes: 36 Number Of Inactive Pipes: 161
Number Of Active Sprinklers: 2 Number Of Inactive Sprinklers: 0
C:\ ...\Mad 54.fiw Monday, September 19, 2022, 11:46 AM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Living Water Designs Mad 54
Prescott, AZ 86301 Page 2
Fire Sprinkler Output Data
Overall Pipe Output Data
Beg.
End.
Node
Nodal
KFactor
(K)
Elevation
(feet)
Spk/Hose
Discharge
(gpm)
Residual
Pressure
(psi)
Nom. Dia.
Inside Dia.
C-Value
q (gpm)
Q (gpm)
Velocity
(fps)
F. L./ft
(psi/ft)
Fittings
Type-Grp
Pipe-Len.
Fit-Len.
Tot-Len.
(ft)
PF-(psi)
PE-(psi)
PT-(psi)
5 4.90 21.50 13.01 7.05 0.75 13.01 0.09454 0.50 0.709
6 0.00 22.00 0.00 7.54 0.874 13.01 E 7.00 -0.217
CPVC 150 6.96 0 7.50 0.493
7 4.90 21.50 14.14 8.33 0.75 14.14 0.11038 0.50 0.828
8 0.00 22.00 0.00 8.94 0.874 14.14 E 7.00 -0.217
CPVC 150 7.56 0 7.50 0.611
2 0.00 13.50 0.00 33.52 0.75 0.00 0.00000 7.50 0.000
22 0.00 13.50 0.00 33.52 0.874 0.00 T 3.00 0.000
CPVC 150 0.00 0 10.50 0.000
4 0.00 13.50 0.00 33.52 0.75 0.00 0.00000 2.00 0.000
22 0.00 13.50 0.00 33.52 0.874 0.00 T 3.00 0.000
CPVC 150 0.00 0 5.00 0.000
22 0.00 13.50 0.00 33.52 0.75 0.00 0.00000 2.50 0.000
24 0.00 13.50 0.00 33.52 0.874 0.00 T 3.00 0.000
CPVC 150 0.00 0 5.50 0.000
24 0.00 13.50 0.00 33.52 1.00 0.00 0.00000 13.00 0.000
26 0.00 13.50 0.00 33.52 1.101 0.00 T 5.00 0.000
CPVC 150 0.00 0 18.00 0.000
27 0.00 13.50 0.00 16.17 0.75 0.00 0.06179 5.00 0.494
28 0.00 13.50 0.00 15.67 0.874 10.34 T 3.00 0.000
CPVC 150 5.53 0 8.00 0.494
28 0.00 13.50 0.00 15.67 1.00 10.34 0.02007 11.50 0.331
32 0.00 22.00 0.00 11.66 1.101 10.34 T 5.00 3.681
CPVC 150 3.48 0 16.50 4.012
6 0.00 22.00 0.00 7.54 0.75 0.00 0.09453 12.50 1.843
30 0.00 22.00 0.00 9.39 0.874 13.01 E 7.00 0.000
CPVC 150 6.96 0 19.50 1.843
8 0.00 22.00 0.00 8.94 0.75 0.00 0.11036 3.00 0.441
30 0.00 22.00 0.00 9.39 0.874 14.14 F 1.00 0.000
CPVC 150 7.56 0 4.00 0.441
30 0.00 22.00 0.00 9.39 1.00 0.00 0.11981 13.00 2.276
32 0.00 22.00 0.00 11.66 1.101 27.15 FT 6.00 0.000
CPVC 150 9.15 0 19.00 2.276
32 0.00 22.00 0.00 11.66 1.00 16.81 0.04937 1.00 0.296
33 0.00 22.00 0.00 11.96 1.101 16.81 T 5.00 0.000
CPVC 150 5.67 0 6.00 0.296
C:\ ...\Mad 54.fiw Monday, September 19, 2022, 11:46 AM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Living Water Designs Mad 54
Prescott, AZ 86301 Page 3
Fire Sprinkler Output Data
Overall Pipe Output Data (cont'd)
Beg.
End.
Node
Nodal
KFactor
(K)
Elevation
(feet)
Spk/Hose
Discharge
(gpm)
Residual
Pressure
(psi)
Nom. Dia.
Inside Dia.
C-Value
q (gpm)
Q (gpm)
Velocity
(fps)
F. L./ft
(psi/ft)
Fittings
Type-Grp
Pipe-Len.
Fit-Len.
Tot-Len.
(ft)
PF-(psi)
PE-(psi)
PT-(psi)
10 0.00 22.00 0.00 12.23 0.75 0.00 0.00000 1.50 0.000
34 0.00 22.00 0.00 12.23 0.874 0.00 F 1.00 0.000
CPVC 150 0.00 0 2.50 0.000
33 0.00 22.00 0.00 11.96 1.00 8.19 0.01304 16.00 0.274
34 0.00 22.00 0.00 12.23 1.101 8.19 T 5.00 0.000
CPVC 150 2.76 0 21.00 0.274
33 0.00 22.00 0.00 11.96 1.00 8.63 0.01436 52.50 0.912
36 0.00 22.00 0.00 12.87 1.101 8.63 6FT 11.00 0.000
CPVC 150 2.91 0 63.50 0.912
34 0.00 22.00 0.00 12.23 1.00 0.00 0.01304 30.00 0.548
38 0.00 22.00 0.00 12.78 1.101 8.19 2F2T 12.00 0.000
CPVC 150 2.76 0 42.00 0.548
36 0.00 22.00 0.00 12.87 1.00 0.00 0.01437 33.00 0.575
40 0.00 22.00 0.00 13.45 1.101 8.63 2FT 7.00 0.000
CPVC 150 2.91 0 40.00 0.575
38 0.00 22.00 0.00 12.78 1.00 0.00 0.01305 39.00 0.665
40 0.00 22.00 0.00 13.45 1.101 8.19 5FE 12.00 0.000
CPVC 150 2.76 0 51.00 0.665
40 0.00 22.00 0.00 13.45 1.00 0.00 0.04938 13.00 1.383
42 0.00 22.00 0.00 14.83 1.101 16.81 F2E 15.00 0.000
CPVC 150 5.67 0 28.00 1.383
24 0.00 13.50 0.00 33.52 1.00 0.00 0.00000 36.50 0.000
44 0.00 22.00 0.00 29.84 1.101 0.00 6F 6.00 -3.681
CPVC 150 0.00 0 42.50 -3.680
26 0.00 13.50 0.00 33.52 1.00 0.00 0.00000 57.50 0.000
46 0.00 13.50 0.00 33.52 1.101 0.00 6F 6.00 0.000
CPVC 150 0.00 0 63.50 0.000
44 0.00 22.00 0.00 29.84 1.00 0.00 0.00000 43.00 0.000
46 0.00 13.50 0.00 33.52 1.101 0.00 6FE 13.00 3.681
CPVC 150 0.00 0 56.00 3.681
27 0.00 13.50 0.00 16.17 1.00 0.00 0.02008 30.50 1.074
48 0.00 13.50 0.00 17.24 1.101 10.34 4F2ET 23.00 0.000
CPVC 150 3.48 0 53.50 1.074
46 0.00 13.50 0.00 33.52 1.00 0.00 0.00000 50.00 0.000
50 0.00 12.50 0.00 33.96 1.101 0.00 8F4ET 41.00 0.433
CPVC 150 0.00 0 91.00 0.433
C:\ ...\Mad 54.fiw Monday, September 19, 2022, 11:46 AM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Living Water Designs Mad 54
Prescott, AZ 86301 Page 4
Fire Sprinkler Output Data
Overall Pipe Output Data (cont'd)
Beg.
End.
Node
Nodal
KFactor
(K)
Elevation
(feet)
Spk/Hose
Discharge
(gpm)
Residual
Pressure
(psi)
Nom. Dia.
Inside Dia.
C-Value
q (gpm)
Q (gpm)
Velocity
(fps)
F. L./ft
(psi/ft)
Fittings
Type-Grp
Pipe-Len.
Fit-Len.
Tot-Len.
(ft)
PF-(psi)
PE-(psi)
PT-(psi)
48 0.00 13.50 0.00 17.24 1.00 0.00 0.02007 49.50 1.796
52 0.00 13.50 0.00 19.04 1.101 10.34 7F4ET 40.00 0.000
CPVC 150 3.48 0 89.50 1.796
42 0.00 22.00 0.00 14.83 1.00 0.00 0.04938 11.50 0.913
53 0.00 13.50 0.00 19.42 1.101 16.81 E 7.00 3.681
CPVC 150 5.67 0 18.50 4.594
52 0.00 13.50 0.00 19.04 1.00 0.00 0.02007 31.00 1.124
54 0.00 14.50 0.00 19.73 1.101 10.34 F2E2T 25.00 -0.433
CPVC 150 3.48 0 56.00 0.691
53 0.00 13.50 0.00 19.42 1.00 0.00 0.04938 13.00 0.741
54 0.00 14.50 0.00 19.73 1.101 16.81 2F 2.00 -0.433
CPVC 150 5.67 0 15.00 0.308
50 0.00 12.50 0.00 33.96 1.00 0.00 0.00000 34.50 0.000
56 0.00 12.50 0.00 33.96 1.101 0.00 9F 9.00 0.000
CPVC 150 0.00 0 43.50 0.000
54 0.00 14.50 0.00 19.73 1.00 0.00 0.11982 63.50 13.360
58 0.00 10.50 0.00 34.82 1.101 27.15 10F4E2T 48.00 1.732
CPVC 150 9.15 0 111.50 15.092
56 0.00 12.50 0.00 33.96 1.00 0.00 0.00000 49.00 0.000
58 0.00 10.50 0.00 34.82 1.101 0.00 8F2E2T 32.00 0.866
CPVC 150 0.00 0 81.00 0.866
58 0.00 10.50 0.00 34.82 1.00 0.00 0.11985 3.00 1.198
100 0.00 10.50 0.00 36.02 1.101 27.15 E 7.00 0.000
CPVC 150 9.15 0 10.00 1.198
100 0.00 10.50 0.00 36.02 1.00 0.00 0.11985 11.00 3.068
125 0.00 0.00 0.00 43.64 1.101 27.15 2FEC 14.60 4.547
CPVC 150 9.15 0 25.60 7.615
125 0.00 0.00 0.00 43.64 1.00 0.00 0.16979 1.00 1.358
140 0.00 0.00 5.00 44.99 1.025 27.15 T 7.00 0.000
TYPE L COPPER TUBE 150 10.56 0 8.00 1.358
140 0.00 0.00 5.00 44.99 1.25 5.00 0.08332 4.00 1.100
160 0.00 -3.00 0.00 47.39 1.265 32.15 3EG 9.20 1.299
TYPE L COPPER TUBE 150 8.21 0 13.20 2.399
160 0.00 -3.00 0.00 47.39 2.00 0.00 0.01432 60.00 0.960
180 0.00 -3.00 0.00 48.35 1.816 32.15 F 7.00 0.000
HDPE SDR-9 150 3.98 0 67.00 0.960
C:\ ...\Mad 54.fiw Monday, September 19, 2022, 11:46 AM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Living Water Designs Mad 54
Prescott, AZ 86301 Page 5
Fire Sprinkler Output Summary
Hydraulically Most Demanding Sprinkler Node
HMD Sprinkler Node Number:5
HMD Actual Residual Pressure:7.05 psi
HMD Actual Flow:13.01 gpm
Sprinkler Summary
Sprinkler System Type:Wet
Specified Area Of Application: 512.00 ft²
Minimum Desired Density:0.050 gpm/ft²
Application Average Density:0.053 gpm/ft²
Application Average Area Per Sprinkler: 256.00 ft²
Sprinkler Flow:27.16 gpm
Average Sprinkler Flow:13.58 gpm
Flow Velocity And Imbalance Summary
Maximum Flow Velocity ( In Pipe 125 - 140 ) 10.56 ft/sec
Maximum Velocity Pressure ( In Pipe 125 - 140 ) 0.75 psi
Allowable Maximum Nodal Pressure Imbalance: 0.0100 psi
Actual Maximum Nodal Pressure Imbalance: 0.0094 psi
Actual Average Nodal Pressure Imbalance: 0.0051 psi
Actual Maximum Nodal Flow Imbalance: 0.0042 gpm
Actual Average Nodal Flow Imbalance: 0.0008 gpm
Overall Network Summary
Number Of Unique Pipe Sections: 36
Number Of Flowing Sprinklers:2
Pipe System Water Volume:35.39 gal
Sprinkler Flow:27.16 gpm
Non-Sprinkler Flow:5.00 gpm
Minimum Required Residual Pressure At System Inflow
Node:48.35 psi
Demand Flow At System Inflow Node: 32.15 gpm
C:\ ...\Mad 54.fiw Monday, September 19, 2022, 11:46 AM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Living Water Designs Mad 54
Prescott, AZ 86301 Page 6
Fire Sprinkler Output Data
Hydraulic Supply/Demand Graph
Pressure psiFlowrate(x100) gpm
58
5252
0
10
20
30
40
50
60
70
80
90
100
1 2 3 4 5 6 7 8 9 10
Supply Curve Data
Static Pressure: 58 psi
Test Residual Pressure: 52.2 psi
Test Flow Rate: 1000 gpm
Demand Curve Data
Calculated Residual Pressure: 48.35 psi
Calculated Flow Rate: 32.15 gpm
Excess Available Residual Pressure At Calculated Flow: 9.64 psi
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 0.00 psi
C:\ ...\Mad 54.fiw Monday, September 19, 2022, 11:46 AM
Page:1 of 8
Document No.U085167 Date:Nov/20/2019
SENJU SPRINKLER CO., LTD.
Residential Lead Free Flat Concealed Sprinkler,
Pendent,
Model: RC-RES, K-Factor: 4.9, SIN: SS8464
GENERAL DESCRIPTION
The Model RC-RES Residential Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder type. They
are decorative and fast responding. The Cover Plate Assembly hides the Deflector, Heat Responsive Element etc., which is
concealed above the ceiling. The cover plate has a flat profile, and its diameter is extremely small (2-5/8 inch, 68mm). The
push-on and/or thread-on, thread-off design of the concealed cover plate assembly allows for easy installation of the cover plate.
Therefore, the Model RC-RES should be your first choice when aesthetics is the major consideration for ultimate appeal and
unbeatable performance is desired. The Model RC-RES is designed for residential occupancies and is perfect for use in homes,
hotels and other living quarters.
The Model RC-RES is to be used in wet pipe residential sprinkler systems for One- and Two- Family Dwellings and
Manufactured Homes per NFPA 13D; wet pipe residential sprinkler systems for Residential Occupancies up to and Including
Four Stories in Height per NFPA 13R; or, wet pipe sprinkler systems for the residential portions of any occupancies per NFPA 13.
The Model RC-RES has a 4.9 (70.6 LPM/bar1/2) K-factor that meets the required residential flow rates with minimal residual
pressure, which allows for smaller pipe sizes and water supply requirements.
For extended installation flexibility, the Model RC-RES provides 1/2 inch (12.8mm) vertical adjustment. This adjustment in
installation decreases the need for precise cutting of the pipe that drops to the sprinkler and allows for a perfect fit with a range of
pipe lengths.
The heat sensitivity and water distribution design of Model RC-RES allows for an increased chance of residents to escape or
evacuate in case of a fire. However, residential fire sprinkler systems are not a substitute for fire safety awareness or fire safety
construction required by building codes.
“Lead Free” is defined in the Reduction of Lead in Drinking Water Act (S.3874) endorsed by AWWA’s Water Utility Council, and
California Assembly Bill #1953 as having less than or equal to a weighted average of 0.25% lead in wetted surface of pipes,
plumbing fittings and fixtures.
WARNINGS
The Model RC-RES must be installed and maintained in accordance with the rules stated herein as well as in
compliance with the applicable standards of the National Fire Protection Association regulations and the standards of
any other authorities having jurisdiction.
In the event of this condition, consult the authorities having jurisdiction for guidance and approval.
Failure to do so may impair the integrity of these devices.
It is the responsibility of the installing contractor to provide a copy of this document to the owner or their
representative, and in turn, it is the obligation of the owner to provide a copy of this document to a succeeding owner.
The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The
installing contractor or sprinkler manufacturer should be contacted with any related questions.
Page:2 of 8
Document No.U085167 Date:Nov/20/2019
TECHNICAL DATA
Approvals: cULus Listed
NSF/ANSI/CAN 61, NSF/ANSI 372
Sprinkler Identification Number (SIN): SS8464
Maximum Working Pressure: 175psi (12.1bar)
Discharge Coefficient (Nominal K-Factor):
K=4.9 GPM/psi1/2 (70.6 LPM/bar1/2)
Temperature Rating:
162°F (72°C) Sprinkler with 140°F (60°C) Cover Plate
175°F (79°C) Sprinkler with 140°F (60°C) Cover Plate
175°F (79°C) Sprinkler with 162°F (72°C) Cover Plate
205°F (96°C) Sprinkler with 162°F (72°C) Cover Plate
Color Code (Sprinkler)
162°F (72°C): Uncolored
175°F (79°C): White
205°F (96°C): White
Color Code (Cover Plate)
140°F (60°C): No Mark
162°F (72°C): White-Colored Mark
Vertical Adjustment: 1/2 inch (12.8 mm)
Cover Plate Finishes:
Standard Finishes-
White, Ivory, Beige, Brown, Black, Nickel,
Wood Grain
Custom Finishes-
Custom color and custom pattern cover plates are
available on special order. Contact a Senju
Sprinkler representative with any custom orders.
Please see chart on Page 8 for more detail.
Physical Characteristics: Ref. Figures 1 and 1-1
FIGURE 1. Model RC-RES K=4.9
FIGURE 1-1. Marking (Color Code)
OPERATION
In case of fire, the solder component that holds together the Cover Plate and the Retainer melts. Then the Cover Plate is
released at once. As a result, the Deflector drops down to the intended position. Two Heat Collectors are exposed to fire, and
when sufficient heat from the fire is reached, internal components of the sprinkler fall apart. This leads to the water flow to be
distributed on the affected fire area. (Ref. Figure 2)
FIGURE 2. OPERATION PROCESS (The figure is for illustrative purposes only)
Page:3 of 8
Document No.U085167 Date:Nov/20/2019
DESIGN CRITERIA
The herein stated rules for use and installation of Model RC-RES are provided by the manufacturer and must be strictly
implemented for safe and full results.
NOTES
Residential Fire Sprinkler Systems should only be designed and installed by individuals who are completely familiar
with automatic sprinkler system design, installation procedures, and techniques.
Several criteria may apply to the installation and usage of each sprinkler. Consequently, it is recommended that the
sprinkler system designer review and develop a working understanding of the complete list of criteria prior to initiating
the design of the sprinkler system.
Questions concerning sprinkler installation and usage criteria, which are not covered by the following instructions,
should be submitted to your contracted company. Include sketches and technical details, as appropriate.
In some instances, the requirements of this document may concern specifications which are more stringent, and which
take precedence over those specified in NFPA 13, 13D, 13R, or by the authority having jurisdiction.
The Model RC-RES must not be used in applications where the air pressure above the ceiling is greater than that below.
Inspect all sprinklers after installation to ensure that both the gap between the cover plate, ceiling and the 6 slots in the
cup are open and free from any air flow impediment.
The spray from the sprinkler is distributed radially outward and downward from the sprinkler deflector. Consequently,
the sprinklers must be located such that there will be no blind spaces shielded from spray by partitions, room dividers,
overhangs or other parts of the dwelling structure.
The number of sprinklers within each compartment (as defined by NFPA 13, 13D, or 13R) must be kept as few as
possible. Do NOT use more sprinklers than necessary to cover a particular space.
Use only the Cover Plate provided for the Model RC-RES. The sprinkler must be secured in place by firmly fastening the
sprinkler system piping to the structure. If the sprinkler is not properly secured in position, reaction forces resulting
from sprinkler operation could alter its orientation and its water distribution pattern.
Obstruction to Water Distribution
Locations of sprinklers must follow the obstruction rules of NFPA 13, 13D and 13R for Residential Sprinklers.
General Service Conditions
The Model RC-RES must only be utilized in WET PIPE sprinkler systems.
Heat Source Criteria
Refer to NFPA 13D, 13R or 13 for the requirements relating to the prevention of possible activation of the Heat Responsive
Element of Model RC-RES, due to the exposure of a heat source other than an actual fire.
Available Sprinkler Temperature Ratings
Sprinkler Temperature
Classification
Sprinkler Nominal
Temperature Rating
Maximum Ambient Ceiling
Temperature
Temperature Rating of the
Cover Plate Assembly
Ordinary 162°F (72°C) 100°F (38°C) 140°F (60°C)
Intermediate 175°F (79°C) 150°F (66°C) 140°F (60°C) 1)
Intermediate 175°F (79°C) 150°F (66°C) 162°F (72°C)
Intermediate 205°F (96°C) 150°F (66°C) 162°F (72°C)
1) Maximum ambient temperature for the Cover Plate Assembly is 100°F (38°C).
Precautionary Warnings for Corrosive Environments
Model RC-RES sprinklers should not be installed where they may be subjected to a corrosive environment including the
following:
(1) Chlorine ion and Chloride environment.
Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride. Exposure to this
environment may result in sprinklers operating under Non-Fire conditions or Not Operating when exposed to an actual fire.
(2) Sprinkler system piping with Copper.
Sprinkler systems should be constructed in compliance with the applicable standards and the requirements for copper
piping when copper piping is used in the sprinkler system. (Reference standards NFPA 13, ASTM B813, B828, and CDA
(Copper Development Association) – Solder Joint)
Page:4 of 8
Document No.U085167 Date:Nov/20/2019
All residual flux must be removed from the interior and exterior of the copper piping by thoroughly flushing before
installation of the Sprinkler Heads. Otherwise, residues of flux may cause corrosion and/or leakage in the sprinkler system.
Hydraulic Design Criteria
The minimum required sprinkler flow rates for systems designed to NFPA 13D or 13R are given in TABLE A as a function of
temperature rating and the maximum allowable coverage area. The sprinkler flow rate is the minimum required discharge from
the most hydraulically demanding sprinkler from each of the total number of “design sprinklers” as specified in NFPA 13D or
13R.
For systems designed to NFPA 13, the number of designed sprinklers is to be the four most hydraulically demanding sprinklers.
The minimum required discharge from each of the four sprinklers is to be the greater of the following:
・ The flow rates given in TABLE A for NFPA 13D and 13R as a function of temperature rating and maximum allowable
coverage area.
・ A minimum discharge of 0.1GPM/sq.ft. [4.07LPM/sq.m] over the “design area” comprised of the four most hydraulically
demanding sprinklers for the actual coverage area being protected by the four sprinklers.
TABLE A. NFPA 13D & 13R WET PIPE HYDRAULIC DESIGN CRITERIA for Model SS8464
For systems with ceiling types smooth flat horizontal, or beamed, or sloped, in accordance with NFPA 13D, 13R or 13 as
applicable.
Ordinary
Temperature Rating
162°F (72°C)
Intermediate
Temperature Rating
175°F (79°C)
Intermediate
Temperature Rating
205°F (96°C)
Maximum
Coverage
Area(a)
Ft. × Ft.
(m ×m)
Maximum
Spacing
Ft.
(m)
Flow(b)
GPM
(LPM)
Pressure(b)
PSI
(bar)
Flow(b)
GPM
(LPM)
Pressure(b)
PSI
(bar)
Flow(b)
GPM
(LPM)
Pressure(b)
PSI
(bar)
Deflector
to
Ceiling
Installation
Type
Minimum
Spacing
Ft.
(m)
12×12
(3.7×3.7)
12
(3.7)
13
(49.2)
7.0
(0.48)
13
(49.2)
7.0
(0.48)
13
(49.2)
7.0
(0.48)
14×14
(4.3×4.3)
14
(4.3)
13
(49.2)
7.0
(0.48)
13
(49.2)
7.0
(0.48)
13
(49.2)
7.0
(0.48)
16×16
(4.9×4.9)
16
(4.9)
13
(49.2)
7.0
(0.48) ― ― 13
(49.2)
7.0
(0.48)
18×18
(5.5×5.5)
18
(5.5)
17
(64.4)
12.0
(0.83) ― ― 17
(64.4)
12.0
(0.83)
20×20
(6.1×6.1)
20
(6.1)
21
(79.5)
18.4
(1.27) ― ― 21
(79.5)
18.4
(1.27)
Smooth
Ceilings
3/8 to 7/8
Inches.
Beamed
Ceilings
per NFPA
13D, 13R
or 13
Installed in
beam
3/8 to 7/8
inches
below
bottom of
beam.
Concealed 8
(2.4)
(a) For coverage area dimensions less than the above mentioned, it needs to use the minimum required flow for the
Next Higher Coverage Area listed.
(b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are
calculated using the nominal K-Factor. Refer to Hydraulic Design Criteria Section for details.
Sprinkler Spacing Criteria
The minimum spacing between sprinklers is 8 feet (2.4m). The maximum spacing between sprinklers cannot go beyond the
coverage area calculated by using the specific hydraulic factors. (Ref. TABLE A)
Page:5 of 8
Document No.U085167 Date:Nov/20/2019
INSTALLATION
The Model RC-RES must be installed in accordance with the following instructions:
NOTES
Do not use any sprinklers which have been subjected to potential mechanical damage. Do not use any sprinklers which
show deformation or cracking in either the Sprinkler or the Protective Cap.
Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the
potential for damage to the sprinklers that could cause improper operation or non-operation.
The Protective Cap must remain on the sprinkler during installation. After the installation is completed, the Protective
Cap must be removed to place the sprinkler in service.
Use a torque of 7 to 14 ft·lbs (9.5 to 19.0 N·m) to achieve a 1/2 inch NPT sprinkler joint. If you exceed the recommended
maximum torque, this could result in damage to the sprinkler inlet, which may lead to leakage from the sprinkler.
Use only NR-H model wrench socket for installation of RC-RES sprinklers. Use of any other wrench or socket is
prohibited and may cause damage to the sprinkler.
In case of insufficient adjustment in Cover Plate installation, do not try to overly tighten, screw the sprinkler too loosely
or make any modification to the cover plate assembly. Readjust the sprinkler fitting for a better fit.
Do not rotate the Cap Remover RC to the left with force when placing the two hook arms into place. The installed
sprinkler may become loosened, which may cause water leakage.
Installing Procedure
Step 1
The installation requirements for the sprinkler are as follows: to be installed only in the pendent position with the waterway
perpendicular to the ceiling. Install the sprinkler fitting so that the distance from the face of the fitting to the mounting surface
will be nominally 2 inches (50.8mm) as shown in Figure 3.
Step 2
With pipe thread sealant applied to the threads, hand tighten the sprinkler into the sprinkler fitting. Then tighten it with the
Socket NR-H or Ratchet (3/8” drive) & Socket NR-H Combination (Ref. Figure 4). The teeth of the Socket must fit perfectly
with the grooves on the Sprinkler for proper installation (Ref. Figure 4).
Step 3
If desired, the Protective Cap may also be used to locate the center of the clearance hole by gently pushing the ceiling
material against the center point of the Protective Cap. Before the installation of the ceiling, the sprinkler installation can be
started with a 2-3/8 inch (60mm) diameter clearance hole (Ref. Figure 3). Use the “Vertical Adjustment” indicator on the
Protective Cap to check for proper installation height (Ref. Figure 3).
Step 4
Use the Cap Remover RC to remove the Protective Cap (Ref. Figure 5), and then push or screw a Cover Plate Assembly on
the Cup of the Sprinkler by hand until its flange just has contact with the ceiling (Ref. Figure 6 and Figure 7). Stop tightening
the Cover Plate Assembly once the flange has contact with the ceiling. If the ceiling has been lifted from its normal position in
the process of tightening the Cover Plate Assembly, readjust the cover plate assembly as necessary. If the flange of the Cover
Plate Assembly cannot contact the ceiling sufficiently, readjust the sprinkler fitting as necessary. When properly installed,
there is a nominal 1/16 inch (1.6mm) air gap between the lip of the Cover Plate and the ceiling, as shown in Figure 6.
FIGURE 3. INSTALLATION
FIGURE 4. RATCHET & SOCKET
Page:6 of 8
Document No.U085167 Date:Nov/20/2019
FIGURE 5. PROTECTIVE CAP REMOVAL
FIGURE 6. INSTALLATION (COVER PLATE ASSEMBLY)
FIGURE 7. INSTALLATION (CORRECT and INCORRECT)
Page:7 of 8
Document No.U085167 Date:Nov/20/2019
CARE AND MAINTENANCE
The following instructions must be implemented for the maintenance and service of the Model RC-RES.
NOTES
Wet pipe sprinkler systems must be maintained at a minimum temperature of 40°F / 4°C to prevent freezing and bursting
of the pipe and/or sprinklers.
Automatic sprinklers are not to be tested with a heat source. Operation of the heat responsive element can result.
Absence of a Cover Plate Assembly may delay the response time of the sprinkler in case of a fire.
Install the cover plate assembly properly, as shown in Figure 6. Improper installation of the cover plate assembly may
cause improper operation or non-operation.
If the ceiling is to be repainted after the installation of the Sprinkler, care must be exercised to ensure that the new paint
does not seal off any of the air gap.
Factory painted Cover Plates must not be repainted. They should be replaced, if necessary, by factory painted cover
plates. Non-factory applied paint may adversely delay or prevent sprinkler operation in case of a fire.
Do not pull the Cover Plate. Separation may result.
In preparation for maintenance of the fire protection system, permission to close the main control valve must be
obtained from the proper authorities, and all affected parties by this action, and must be informed before the
maintenance session can commence.
Do NOT enclose any sprinklers within drapes, curtains, or valances.
Do NOT hang anything from the sprinklers.
Do NOT clean the sprinklers with soap and/or water, detergents, ammonia, cleaning fluids, or other chemicals. Remove
dust, lint, cobwebs, cocoons, insects, and larvae by gently brushing with a feather duster or gently vacuuming with a
soft bristle (i.e., dusting) brush attachment.
Exercise suitable safety precautions in the use and storage of highly flammable materials. The rapid rate of fire
development and spread of these materials can reduce the ability of the sprinkler system to aid in the control of a fire
involving such hazards.
Leaking or corroded sprinklers must be replaced.
Automatic Sprinklers must be kept in a cool and dry place.
Automatic sprinklers must never be physically altered, such as painted, plated, or coated, once shipped from the
factory. If the sprinklers have been in any way modified, they must be replaced.
Great caution must be applied to prevent damage to the sprinklers at all stages - before, during, and after installation.
Damaged units because of dropping, hitting, over-tightening, or wrench slippage, must be replaced.
The Model RC-RES must only be replaced with pendent sprinklers which are listed for residential fire protection service
and which have the same nominal K-Factor, the same coverage area, and the same or lower flow ratings (as indicated
under TABLE A “Hydraulic Design Criteria”).
When remodeling, such as by adding false beams or light fixtures or changing the location of compartment walls, first
verify that the new construction will not violate the installation requirements of the applicable standards of NFPA. Alter
the new construction and/or the sprinkler system to suit the requirements of this document and the applicable NFPA
regulations.
The owner is responsible for the maintenance of the sprinkler system, including inspection and testing of its
compliance with this document, as well as the standards of the National Fire Protection Association (e.g., NFPA 25),
and the regulations of any other authorities having jurisdiction. The owner should direct any questions regarding the
above rules and regulations to the installing contractors or the sprinkler manufacturer. It is recommended that
automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with
NFPA 25.
Limited Warranty
For details of warranty, refer to Sales Contract.
Page:8 of 8
Document No.U085167 Date:Nov/20/2019
ORDER PROCEDURE
When placing an order, please contact a local distributor with the following information (Model Name, Temperature Rating and
Finish).
Sprinkler
Model: RC-RES
(SIN: SS8464, Residential Flat Concealed Sprinkler, Pendent, K4.9, Temperature: 162°F (72°C) or 175°F (79°C) or
205°F (96°C))
Cover Plate Assembly
2-5/8 inch (φ68mm) or 3-1/4 inch (φ83mm) or 2-5/8 inch square (□68mm), Order Separately from Sprinkler
Please refer to the chart below for available sizes, temperature, and finishes.
Standard Finishes Custom Finishes White Ivory Beige Brown Black Nickel Copper Wood Grain Custom Color Custom Pattern
2-5/8" Round, 140°F ○ ○ - - - - - - ○ ○
3-1/4" Round, 140°F ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
2-5/8" Square, 140°F ○ - - - - - - - ○ ○
2-5/8" Round, 162°F ○ - - - - - - - ○ ○
3-1/4" Round, 162°F ○ - - - - - - - ○ ○
Tools for Installation of Model RC-RES
・Socket NR-H
For use with a 3/8” drive ratchet (not included)
・Socket NR-H Plastic
For use with a 1/2” drive ratchet (not included)
・Cap Remover RC
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
July 13, 2022
J D Mechanical Fire Inc
82579 Fleming Way #D
Indio, CA 92201
Re: Residential Fire Sprinkler Plan Review – CLOUD NINE RESOTR
FSS2022-0231 / 53060 ROSS AVE, LA QUINTA, CA 92253
The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
Permanently marked identification signs shall be attached to all control valves.
The following inspections/tests are required to be witnessed by Office of the Fire Marshal Staff:
(a) Overhead Rough and Hydro static test: All piping shall be visible and pumped at normal
operating pressure. *No jacketed electrical and data wiring shall be in contact with, nor have the
potential to contact CPVC piping once insulation is installed.
(b) Final inspection
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 53060 ROSS AVENUE PERMIT#: FSS2022-0231 DATE
ISSUED: 7/13/2022
DESCRIPTION: MADISON CLUB – LOT 54 CONTRACTOR: J D MECHANICAL FIRE INC
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.