FCMP2020-0002 Griffin Ranch Plan 8a u�tt
Project Details PROJECT NUMBER
` =�w City of La Qu i nta FCM P2020-0002
MoFT�• .
Description: GRIFFIN RANCH / MASTER FIRE SPRINKLER PLAN 8
(4820)
Status: APPROVED
Type: FIRE CONSTRUCTION MASTER PLAN
Status Date: 1/28/2020
Subtype: FIRE SPRINKLER MASTER PLAN
Applied: 1/28/2020
Address: 81181 MERV GRIFFIN WY
Approved: 2/18/2020
City, State, Zip: LA QUINTA,CA92253
Closed:
Project Manager:
Expired:
Details:
Pr DAYS
REVIEWS
III ACTIONS
INSPECTIONS
CONDITIONS
0 0
•
CHRONOLOGYTYPE
STAFF NAME
ACTION DATE
COMPLETION DATE
NOTES
NOTE
KOHL HETRICK
2/18/2020
2/18/2020
FIRE REVIEW ASSISTED BY AFM CHRIS COX
NAME TYPE
NAME
ADDRESSI
CITY
STATE
ZIP
PHONE
FAX
EMAIL
APPLICANT
FIRE SPRINKLER SYSTEMS INC
705 E HARRISON ST STE
200
CORONA
CA
92879
jamieb@fireinc.net
CONTRACTOR
FIRE SPRINKLER SYSTEMS INC
705 E HARRISON ST STE
200
CORONA
CA
92879
jamieb@fireinc.net
OWNER
IOTA GRIFFIN
4675 MACARTHUR CT
NO 1550
NEWPORT
BEACH
CA
0
Printed: Wednesday, February 15, 2023 3:09:50 PM 1 of 3 CENTRALSOLIARE
a u�tt
Project Details PROJECT NUMBER
` =�w City of La Qu i nta FCM P2020-0002
MoFT�•
CLTD
DESCRIPTION
ACCOUNT
CITY
AMOUNT
PAID
PAID DATE
RECEIPT #
CHECK #
METHOD
PAID BY
BY
FIRE STAFF - PER HOUR
101-0000-42420
1.5
$241.50
$241.50
2/19/20
R59762
236666
CHECK
FIRE SPRINKLER
AHI
SYSTEMS INC
Total Paid for FIRE FEES: $241.50 $241.50
RECORDS
MANAGEMENT FEE -
101-0000-42416
0
$21.00
$21.00
2/19/20
R59762
236666
CHECK
FIRE SPRINKLER
AHI
SYSTEMS INC
MAJOR
Total Paid for RECORDS MANAGEMENT FEE - MAJOR: $21.00 $21.00
TECHNOLOGY
502-0000-43611
0
$5.00
$5.00
2/19/20
R59762
236666
CHECK
FIRE SPRINKLER
AHI
ENHANCEMENT FEE
SYSTEMS INC
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
INSPECTION TYPE INSPECTOR SCHEDULED COMPLETED RESULT REMARKS NOTES
DATE DATE
RETURNED
REVIEW TYPE
REVIEWER
SENT DATE
DUE DATE
STATUS
REMARKS
NOTES
DATE
1ST FIRE (2WK)
KOHL
1/28/2020
2/11/2020
2/18/2020
APPROVED
REVISED MASTER TRACT PLAN. APPLICANT
HETRICK
REFERENCED FSS2017-0038 - PLAN 8(4820).
1ST PERMIT
JACK LIMA
1/30/2020
1/30/2020
1/30/2020
COMPLETE
TECHNICIAN (1DAY)
:•RR •• •
IMF
Attachment Type
CREATED
OWNER
DESCRIPTION
PATHNAME
SUBDIR
ETRAKIT ENABLED
DOC
11/18/2021
JOSE DELGADO
Fire Review
Application.pdf
Fire Review
Application.pdf
0
Printed: Wednesday, February 15, 2023 3:09:50 PM 2 of 3 CENTRALSOLIARE
° Project Details PROJECT NUMBER
yow City of La Qu i nta FCM P2020-0002
OFTt
ILMM
Attachment Type
CREATED
OWNER
DESCRIPTION PATHNAME
SUBDIR
ETRAKIT ENABLED
DOC
11/18/2021
JOSE DELGADO
Hydraulics Calculation Hydraulics Calculation
Report.pdf Report.pdf
0
DOC
6/4/2020
KAYLI ALFORD
FCMP2020-0002.pdf FCMP2020-0002.pdf
0
Printed: Wednesday, February 15, 2023 3:09:50 PM 3 of 3 CENTRALSQUARE
Bulletin 006 Rev, I B.Aletin 135 yea. L
Model RFC30 (SIN RA061 1) c-i
SENJU SPRINKLER CO.,LTD. 13D/CRC 313.3 GENERAL NOTES
C
(D
Residential Lead Free Flat concealed Sprinkler,
Moded RFC43 (SIN RA0612) Modd F1 fl 2L-
Ammmkk& A�
e- R bi
Pendent- AUTOMATIC FIRE SPRINKLER SYSTEM HAS BEEN DESIGNED TO BE
Model RFC49 (SIN RA0616) iW1111111i ReSidenffd Sprinklillss for 8
INSTALLED IN ACCORDANCE WITH NFPA 13D 2016 EDITION AND THE
Model.- RC-RES, K-Factor., 3.7 SIN: SS8261
bi REQUIREMENTS OF THE CITY OF LA QUINTA VIRE DEPARTMENT.
Residential Flat Concealed ? I
Ila Dw4n Density of.05 gwN "
Sprinklers 2. THIS SPRINKLER SYSTEM SHALL BE TESTED AND INSPECTED BOTH
GENERAL DESCRIPTION THE ROUGH AND FINAL INSPECTION PRIOR TO OCCUPANCY BEING
GRANTED. THE JURISDICTIONAL FIRE PREVENTION OFFICE WILL BE
l6bM F1 Res Spirdftm wVineemd for ft bRwtfbw9 The Model RC-RES Residential Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder type. These NOTIFIED A MINIMUM OF TWO WORKING DAYS IN ADVANCE OF THE
A Residentbi Flat Conlawled are decorative and fast response. The Cover Plate Assembly hides the Deflector, Heat Responsive Element etc., which is in turn REQUESTED INSPECTION.
X
lo rrxxt the milinimurin doWgn dwi* of D5 gpnvV concealed above the ceiling. The cover plate has a flat profile, and its diameter is extremely small (2-5/8 inch, 68mm). The
QISprinkler engineered fcw a minimum push -on and/or thread -on, thread -off design of the concealed cover plate assembly allows easy installation of the cover plate. 3. THE INSTALLER SHALL PERFORM ALL REQUIRED ACCEPTANCE TESTS.
Types: Therefore, the Model RC-RES should be your first choice when aesthetics is the major consideration for ultimate appeal and
design density of 0.05 gpmff with F1 Figs 30 Pe -dent unbeatable performance is desired. The Model RC-RES Is designed for the residential occupancies and it is perfect for use In 4. NOTCHING, DRILLING, OR OTHERWISE PENETRATING STRUCTURAL
homes, hotels and other living quarters.
2. F1 Res 30 Recessed Pencemr-2 MEMBERS SHALL BE IN ACCORDANCE WITH CALIFORNIA BUILDING CODE.
low GPM requimments. 3. F1 Res 30 Recessed Pencerri-P The Model RC-RES is to be used in wet pipe residential sprinkler systems for One- and Two- Family Dwellings and
7W 4. F1 Flee 49 Pe,)dent Manufactured Homes per NFPA 13D; wet pipe residential sprinkler systems for Residential Occupancies up to and Including 5. TYPE OF PLASTIC PIPE TO BE CPVC MANUFACTURED BY BLAZEMASTER
Features 5. F1 Res 49 Recessed Pencerri-1 Four stories in Height per NFPA 13R; or, wet pipe sprinkler systems for the residential portions of any occupancies per NFPA 13. U.L. LISTED.
1. Very low water flow requirements. 6. F1 Flee 49 Recessed Pencemr-P The Model RC-RES has a 3.7 (53.3 LPM/bar If) K-factor that meets the required residential flow rates with minimal residual 6. ALL VALVES SHALL HAVE A PERMANENTLY AFFIXED SIGN INDICATING
7 F1 Res 58 Pe -dent F1 Ras 30: 49, 50 & 76 F1 Fes 30,411,58 & 73 pressure, which allows for smaller pipe sizes and water supply requirements.•
IT'S FUNCTION
AVENUE 51
Z
(n
B,
AVENUE 52
10
Z
0
U)
AVENUE 53
ILL.
AVENUE 54
w
ILL
SITE0
Lai
Z
0
Z
0
AVENUE
Z
0
(n
y
1ICINITY MAP
Lon
AIRPORT
BLVD
NTS
1an
�'
0
CL:
U)=5
aj
2)
UJ <
a
or",
-
0
CEP,
LU
0
U-1
ofo
uir
LUC
C=,3
MLM,
U,
55
Wp
0
2. Cover plate attachment (Plain or Perforated) For extended installation flexibility, the Model RC-RES provides 112 inch (12.8mm) vertical adjustment. This adjustment in N
8. F1 R39 58 Recessed Pencer�Fi Recessed PenderT., /F1 Reoesse: Piandert P:P Res W HS*Vj)( installation decreases the need for precise cutting ofthe pipe that drops to the sprinkler and allows for a perfect fit with a range of 7. PIPE SHALL BE HUNG FROM STRUCTURAL MEMBER PER THE UNIFORM VICINITY MAP w
With V (13rrm) Total adjustment. 9. F1 Flee 58 Recessed PencerrFP pipe lengths. PLUMBING CODE. PIPE CLAMPS AND SCREWS ARE MANUFACTURED BY
-1. F1 Res 76 Reces
3. Thread-On/Thread-Off or Push-Onfrhread -0. F1 Res 76 Ra-)::Ient encerrF1 The heat sensitivity and water distribution design of Model RC-RES allows for an increased chance of residents' escape or AFCON MFG. ARE U.L. LISTED AND ARE INSTALLED ACCORDING TO THE N.T.S.
sed P
AMNIN§kil.. -Y.- :: ;�evacuation in case of fire. However, residential fire sprinkler systems are not a substitute for fire safety awareness or fire safety HANGING REQUIREMENTS IN THEIR TECHNICAL DATA (SEE DETAIL).
W
Off cover attachment option. -2. F1 Res 76 P negsed Pencerr FP
construction required by building codes. GRIFFIN RANCH
4. Smooth aesthetic ceiling profile. -3. F1 R39 30 (—,P PendW 8. THE SPACING AND LOCATION OF SPRINKLERS SHALL CONFORM WITH MASTER PLANS
THE MANUFACTURES REQUIREMENTS AND THOSE CONTAINED IN
'4. F1 Flee 49 MP Pender-t TRACT 32879 PLAN 4820
"Lead Free" is defined in the Reduction of Lead in Drinking Water Act (S.3874) endorsed by AWWA!s Water Utility Council, and 5. Available in brass, chrome and black plated NFPA 13D, 2016 EDITION.
-5, F1 Res 58 MP Penderl California Assembly Bill #1953 as having less than or equal to a weighted average of 0.25% lead in wetted surface of pipes, §199
or painted finishes. Plain Cover Rate '6. F1 Res 76 COP P�andeM -- — -- — - — - — plumbing filings and fixtures. 9. IF REQUIRED BY A.H.J. THE ALARM INDICATING DEVICE SHALL BE LISTED Syslf FMS INC.
'7, F1 Res 44 H_P4V F" Res 3C49,58 & 76 F' Res 44 & 58 F1 Res 44 SWC FOR OUTSIDE SERVICE AND AUDIBLE FROM THE STREET THAT THE
Listings & A•
pproval -8. F1 Res 44 Room ' sed HSWF2 COP Pendent Recessi-d HSWF2 HOUSE IS ADDRESSED ON. LICENSE NO. 684600
1. Listed by Underwriters Laboratories, and -9. F1 Res 58 H_RV WARMNOS
20. F1 Res 58 H-RVX Florizonial sid%W, spr!nKtr3 (Figs. 5,6 & 7) are GquWN Oac- 10. SMOKE DETECTORS TO BE INSTALLED BY OTHERS. •
certified by UL for Canada (cULus) tim vA-en aboveceiling piong carriat be used. The Model RC-RES must be installed and maintained in accordance with the rules stated herein as well as in LA QUINTA, CA. CUSTOM, TRACT, MULTI -FAMILY
21. llaegffi HSWX compliance with the applicable standards of the National Fire Protection Association regulations and the standards of 11. RESIDENTIAL CONCEALED PENDENT SPRINKLERS ARE U.L. LISTED AND AND COMMERCIAL
22. F1 Flee 58 H_RV Recessed HSVVF2 The3rrr-ig69s,-Wlb pendert eprinkov- per -nit the effbent Lee any other authorities havingrjurisdiction. MANUFACTURED BY RELIABLE INSTALLED AT 14 FT. MAXIMUM SPACING AHJ: CITY OF LA QUINTA
23, F1 Res 44 SVVC: of reWerrila water supplies fa spri*jer.-mragie irasidentiEll In the event of this condition, consult the authorities baving jurisdiction for guidance and approval. (SEE TECH. DATA).
............... DESIGN, ENGINEERING AND
....... . ire pm7ectoi desigi. Failure to do so may impair the integrity of these devices.
Listings & Appiwals LEGAL DESCRIPTION INSTALLATION
UL Listing Categories Thalawllcw�l Reseprinklei-saresWi* aMireeredf(ri'm It is the responsibility of the installing contractor to provide a copy of this document to the owner or his representative, 12. PENDENT INTERMEDIATE TEMP. QUICK RESPONSE SPRINKLERS ARE U.L.
Residential Automatic Sprinklers LMCI by Uraerwtlers Labora:ories na and terriai rm-pones to rmel the semlwe 1e proWion applica- and in turn, it is the obligation of the owner to provide a copy of this document to a succeeding owner The owner is LISTED AND MANUFACTURED BY RELIABLE INSTALLED AT 14 FT. MAX. SPACING 705 E. HARRISON ST., SUITE 200
UL Cald ed -or Canaca ,CULL, ton needs of -he latest raddargal marloat Slaidards PL. 1T46 responsible for maintaining their fire protection system and devices in proper operating condition. The installing (SEE TECH. DATA). OCCUPANCY: R3/U CORONA, CA 92879
UL Guide Number Stanclxd). Upon fro conditims, rimig heal wises asprinK orb contractor orsprinkfe r manufacturer should be contacted iwiih any related questions. 13. PENDENT SPRINKLERS ARE AT LEAST 3 ft. FROM OBSTRUCTIONS E.G. LIGHT CONSTRUCTION: V-B PH - 800-915-3473
Sprinklers im.1 0 Dersity: Refer to Bulletin 176 nex-sensitm dement, 915M bUlb or inxioaa.uw% ileleasingire TECHNICAL DATA FIXTURES CEILING FANS, ETC. OR IN ACCORDANCE WITH TABLE 8.2.5.3.2 AND FAX - 951-272-2535
VKKW wal� r� vNaV f low, c Into ft -_ e Ilector, s-A n V Mr b I& Q 1 re SECTION 6.2.5.1. SPRINKLER LOCATIONS FOR CONTINUOUS OBSTRUCTIONS STORIES: 1•
UL Listing Category &Charge.- waler to ccrlrol afire. Approvals: �Ul_.S Listed, NSF-61-G ARE IN COMPLIANCE WITH 8.2.5.3. BUILDING AREA: 5,536 SQFT. The recipient of these plans
Producl Dewription RE-19icer1riEl AUtOMW.I^. Sprinkler sprinkler Identification Number (SIN): SS8261 hereby acknowledges that all
hnical 14. SOFFITS AND CABINETS TO BE PROVIDED WITH SPRINKLER COVERAGE IN FIRE SPRINKLER SYSTEM: plans, details, specifications or
TecData:
Model RFC30, RFC43 and RFC49 Concealed Residen- UL Guide Number Maximum Working Pres sure: 1175psi (112.1 bar) methods of installation
lial Sprinklers are fast response residential fusible solder * Trermal Sew. Solcered Elernerr (Link) cr Non naj Discharge Coefficient (Nominal K-Factor): ACCORDANCE WITH 8.2.5.5. DESIGNED AND INSTALLED PER 2016 NFPA 13D ALL contained in this set of plans is
3-nii glass oath RESIDENTIAL WITH A.05 DENSITY WITHIN AREAS. the sole property of Fire
link automatic sprinklers. Residential sprinklers differ K=3.7 GPM/psi1J2 (53.3 LPIMbarl") 15. SPARE SPRINKLERS SHALL NOT BE REQUIRED TO BE PROVIDED IN Sprinkler Systems, Inc. and
�hat any use of this set of plans
from standard sprinklers primarily in their response time Patents * SprirMar Pierre Brass Castirg Temperature Rating: ACCORDANCE WITH 5.1.1.2. SCOPE OF WORK: is prohibited and is a violation
US Patent No. E,516,893 applies to the Model F1 Res 49 o Spr!rR1_m'P,emLjre Rai ng: 175 psi 162F (729C) Sprinkler with 140T (60'C) Cover Plate
FIRE SPRINKLER DESIGNED AND INSTALLED PER 2016 of co out first
17ST (79'C) Spriniderwith 140T (60'C) Cover Plate copyright laws with
16. NFPA13D 8.3.5.1.1 WHERE THE FUEL -FIRED EQUIPMENT IS ABOVE ALL OF THE receiving perm
and water distribution patterns. Perforated Goner Plate & 58 �encenL Sprinkler 9 Facto ,y 1-ydrostat cally Tested to 500 psi NFPA 13D ALL RESIDENTIAL WITH A.05 DENSITY WITHIN ission from Fire
Model RFC30, RFC43 and RFC49 sprinklers discharge 175E (7 Spriniderwith 1627 (72'C) Cover Plate 7-1 OCCUPIED AREAS OF THE DWELLING UNIT, NO SPRINKLER PROTECTION SHALL AREAS RESIDENTIAL WITH A.05 DENSITY WITHIN AREAS. S rinkler Sistems.
Pal ,a,
water in a hemispherical pattern below the sprinkler de- and positively attached and blends into the ceiling, con- US Patent Nc. 7,353,682 app j_-, to Model 'IeS 44&58 Tr rea d S 122. It"N PT RA.) Color Code BE REQUIRED IN THE CONCEALED SPACE. SCOPE OF WORK TO START AT BASE OF RISER (NODE 104).
(Sprinkler) 1-7- K 0
HSNVSprinkefs
K-Facto, a0(432)(Acma)-F11iky.3DPendeTSprirWer 162T (72C): Uncolored
(lector. Residential distribution patterns are higher and cealing the most dependable fire protection available, an US Patent Na 7.784,555 applies to PAocld F I Res 44SINC 61.
4.0(734 iAAA)-F1Res4aPend9ntSPrnIdef 175T (79'C): White
generally contain a finer droplet size than standard sprin- automatic sprinkler system. sprinklers 5.21 (6a5),ALLdi,.FlRes5BPenden:&I-W*inider Color Code (Cover Plate)
kler patterns. The RFC30, RFC43 and RFC49 are UL Listed Residen- Product Description 7.8(139,VrW,:F1Res 7i5PWd9t5PrinW6r 140T (609C): No Mark
The combination of speed of operation and high dis- tial Sprinklers to be installed in the residential onions Nbdel F1 Res Per&jr sprinkeres �,Figs- 1, 2, 3, & 4) are fasr. 4.4(n(A::fual)-F1RasL4-I5W9XWer 11627 (72C): White -Colored Mark
BUILDING SUMMARY 0
reslym sprirklers comb dig exo9lent dljrabii), higl• Bwaitiv- Deneiiy- M inimirn 0. D5 gpmfi? Vertical Adjustment: 1112rinch (12.8 mm)_2E.z. x-0- krlUvrd�� S 'Nftl Fqlw ", Asfbty-
charge pattern required for residential sprinklers has of any occupancy in accordance with NFPA 13, 13R, & ay' gk-&-;= ard Imv prcAle ceiaora�ve desigi The F1 %s cover Plate Finishes: Z
demonstrated, in fire Testing, an ability for controlling 13D. Standard Finishes -
residential fires, and thereby providing significant evacu- The RFC30, RFC43 and RFC49 can reduce the need White, Ivory, Beige, Brown, Black, Nickel, LIJ
atio n time for occupants, for precise cutting of drop nipples, The threaded 00ver The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Eirmford, New York 10523 Wood Grain . ... ... ... ... .. . .. . ------ CONCEALED RES. PENDENT SPRINKLER r%
The RFC30, RFC43 and RFG49 Sprinklers provide the plate assembly can be adjusted without tools to fit ac- Custom Finishes-
v,ra cage. K-Siri.nt K17 k:j
PW,0�0 CONCEALED RES. PENDENT SPRINKLER
0 F"
Custom color and custom pattern cover plates are lit
best form of tire protection by combining an attractive ap- curately against the ceiling. The tire protection system X .40 N. LU
available on special order. Contact a Senju 1 7s�
pearance and It" (13mm) of cover adjustment for ease need not be shut down to adjust or remove the 00ver Sprinkler representative with any custom orders. RESIDENTIAL PENDENT SPRINKLER
Installation. The small diameter cover plate is easily plate assembly. bly. Please see chart on Page 8 for more detail. of instal Technical D;ata: F1 Res 30 Pendent and Recessed Pendent (SIN R351 1)
------ ---------------------------------------------- - --------------------------------------------------------------- -------------- - --------------------- - ------------------------------ CHANGE IN ELEVATION
.. W�_j
1;� Orifica 1 Wmc Preswirs lCorinklar Temp,. Patina Mm�. Ambient Tsmp, 1 Actual K I Sprinkler I-Grigth Physical Characteristics: Ref. Figure V, g�
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 oF c)c
sizo Inch(m" 1 psi(bar]i `F I Factor Inch (mrn]l
---------------------------------------------------- --------------------------- -------------------- -------------------- --- ---------------- ------------ ---------
RISER LOCATION (PER DETAIL)
�S.2� f12) 1 38 3 0 (413. 2) 1126(67)
175 70
COVFRFLATF SFF*,NtER
NODE POINT FOR CALCULATION <
Ordinniry Tamp. Rt4ing'! Intormodiato Tomp. Rating i
M wc I : Minimum 1 OPERATiON
Max. Goverago area OWFL80a) ............ ! (175IF179�0 Top of Ddl motor to Ceiling
Spacing .............. Flow
�_i� ............... .................. i Sp2cing
Ft x Ft Crn x m) ow M*sGurq I Flow VaGpwm inch (mm) HANGER TIC DETAIL
! gzt In case of fire, the sower component that holds together the Cover Plate and the Retainer melts. Then, the Cover Plate is
Thread
Nominal
Sprinkler
CCP Assembly
Max.
Ambient
K
Max.
Model
Size
Orifice
Temp Rating
Temp. Rating
Temp.
Factor
Pressure
(SIN)
Inch (mm)
Inch (mm)
psi (4ar)
OF
-C
-F
-C
-F
-C
RFC 30
!2 .16)
21/G4 (8,2j
186
74
35
100
38
3.0 43.2)
(RA061 1)
RFC 43
165
74
7
100
8
4.3 0321
17c,
(RA0612)
-T
RFC 49
100
38
4. 9 6)
(RA0616)
------- ---------- ------- -----------------------------------------
12 12 (3,1) x2,6'
...............................................
14 14 (4.2, x
r"r'u
12,13.6%
.. - ........
GPM (LJmjn) 1 PSI (bar) GPM (Urnin) i PSI (bar) I
— ------------------ ----------------------- — ----------------------- - ----------------------------------------------------------
n,-,t h (lmr 1A to a [:1 7 in 10
0 B,
a, po,-i'. .46) on
.. ............... ........... Be,
i I -Imeci per NFRA 13D: '311 E� (2:4'
.-,I i3 istalle�d in �azarns 'A to
iC r—7,8 6) 10 (0, yc�)
(I i 7 lv• 41' 4) U�, 4) iz�dinq F" e._g.4ct on i
released at once. As i� result, the Deflector drops down to the intended position. Two Heat Collectors are exposed to fire. and
when sufficient heat f, 9 n- the fire is recorded, I nte mal components of the sprinkler to fall apart. This leads to alloy the water flow
to be distributed on the affected by fire area. (Ref. Figure 2)
W
SYMBOLLEGE-ND
TABLEA. NFPA 13D & 13R WET PIPE HYDRAULIC DESIGN CRITERIA for Model SS8261
For MpEs refer to NI -PA 13'3�; or 13D
Technical Data: Ft Res 49 Pendent and Recessed Pendent (SIN R3516)
1 Max.
Sprinkler
Max.
Actual
Sprinkler
Thread
Nominal Orifice
Pressure
p. Rating
Temp.
Ambient Temp.
K
Length
Size
---------------------
Inch (mm)
------- ---------- ------------------ ------------ - Psi (bar) --------------
_I
- F7-- --
-------------- -
[ -
Factor
----------------------------
Inch (mm)
(R-Y-,)
1;
17i 12)
65
75
150 66
4,0 (70 6;
2.2E (5-7)
No . I bar 100 Kpa
RFC 30
Max. Coverage
Ordinary Temp. Rating
(1 65-F/74-C)
Top of Deflector
Installation
Minimum
Max. Spacing
area
to Ceiling
Type
Spacing
Ft x Ft (m x m) Ft (m)
Flow
Pressure
Inch (mm)
Ft (m)
----------------------- ------------- ------------------ -
GPM (Umin)
------------------------- ---
PSI (bar)
------------- -------
------------- -------------------- ------------------------------- ----------------------
-------------------------
- ----- ----- -----
-----------------
X 19 �3,63 x 12 1,31,6)
9 ('34,1)
9,0 M,8121:
-) ! 3.4)
S�T. oof h; Ce., gc i1/2 4 k, Wo 25
igs per NFPA 1 SD, 13R
'4 x � 4 (4,3, x 4 14 (4,3' J
1(
�0,76�
nstc;,I, to 2-1-,.4)
13 @d ;r! b-o rns !,,2 to
Ordinary Temp.
Rating
Intermediate
Temp. Rating
Top of Deflector
Minimum
Max. Coverage area
Max. Spacing
(155.
P)
(175-F/79-C)
to Ceiling
Spacing
Flow
Pressure
Flow
PresSUre
Ft x Ft (mx m)
Ft (m)
Inch(mm)
Ft)
- -- - ------------------- - -------------------------
------------ ------------ - --------------
G
-------- 1FM_(bM13)
F%0?9q___
..
....... F§!__( -------
-------------- - - - -
12 x 12 (3,6 x 3,6)
(3,65)
13 (49)
TO (-,)Ai'
13
7.0,'0,46)
S m oo# i C,,-, i I n g s 1 Y4 W, 4 (3 1 l to
102) LJS';7'g-72 Gsou*cheon..
1 Z x 14 (4,3 ) x 4,3,
4 14,3)
3 (49)
7.0 M,48!
13 "AG,
7 0 `0,48)
(25to 1 CZ, usin
.4 .;
1 6 x 16114,9 x 4,-9)
16 (4,�-)
13 (491,
7.0 (-01.4i5)
1,��
7 f,' 0, 4 8)
-G,
RSA red - Ce:;;r gs p9rNFPA.
8(2,4)
---------- ------------
-- -----------
------ ---------
---- --- -
1 _D, 1 3"t Cr 131 Ins:.aliec i-,
8 X 18 (5, _5 x 5
8 (iN,5)
17
12(0,83)
17 (84,3)
2 K-,
earn 11/4,.c `�L (31.
I
I
A A 4) t Is.rig -72 e sr, u;
2 0 x 20, (6, 1 x 63, 1.)
2 G (63, 1
2G(/6,11
1 1
Z)
, 14)
tc (24 to 444� ustrig F'
J
-------------------------- - - - - --------
-- - --- - -------------------------_-
-------------
...5 ...
_;1.;;�iJ,;_ ---------------------- - ---------------
1( - - ------------ -
------- - ----------------- -- -
k
For Cei'ing 7ype�3refGr o NFRA 13, 13R ci. 13D Fc: Ceiir'g ',ype-. refer ',o NFP,", 13, 13R oi 13D
Qrdinary,,
Intermediate
Maximum
Covera
Maximum
Temp'e'rat46 Rating
Temperature Rating
Deflector
Minimum
Areawe
Spacing
162T t72°C)
175°F (79°C}
to
Installation
Spacing
Flow ')l
Pressure
Flow (b)
Pressure"'
Ft. - Ft.
Ft.
Ceiling
Type
Ft
(in)
GPM
PSI
GPM
PSI
(m)
(in xm)
(LPM)
(bar)
(LPM)
(bar)
Smooth
Ceilings
3/8 to 7/8
12x 12
12
10
7.3
11
8.8
Inches.
(3.7x3.7)
(3.7)
(37.8)
(0.50)
(41.6)
(0-60)
Beamed
Ceilings
per NFPA
13or3 D, 113R
Concealed
8
(2.4)
Installed
in beam
3/8 to
14x 14
14
10
7.3
11
8.8
7/8
(4.3 x 4.3)
(4.3)
(37.8)
(0.50)
(41.6)
(0.60)
inches
below
bottom of
beam.
APPROVAL
County
Riverside County Fire Department
0 ffl
14�'� Mpfnal
.0
_�Hlcatiohsladfoneesn _2
The ap'prov�aof �pinnsand;sPec�
ot
permit the violation, deletion, Omission or faulty
installation
W
of any requirements of Title 24 or any
Local Ordinances. Construction shall remain
Z
accessible and exposed for inspection purposes unl�..
approved by the Fire Department,
I a a
Liu
Inc
01 lr%
L1J -C
06:
LU
C= 9=1
>
LU Q
RFC 43 fa`% For covera e area dimensions less than the above mentioned it needs to use the minimum renuired flow for the M _T_ rr% It
Ordinary Temp. Rating
Max. Coverage
Max. Spacing
(1 65-F/74-C)
Top of Deflector
Minimum
Installation
area
Ft x Ft (rin x nn)
Ft (m)
to Ceiling
Inch (mm)
; Spacing
Type Ft (m)
Flow
Pressure
GPM (Umin)
PSI (bar)
1? x 12 (3,6 x 3,6'
12 (3,6)
2 (4,5l
7 % zI,)
14 x 14 ;'4,3 x 4,3'
14 ( 4, 3),
13 (49)
91 (0.6311
S 71.0 Oti k CG; 1; 'W 1 13 C 95. 4,
16 x 16 (4,91 x 4,9
16
13 A(-))
9.1 0, 6 3 i
Ce;iings oc-;r NFPA 13-J, 13R or
Ccnc9P_,.Pc 812A:
13 q:all ed in beams 1/2 W 1 (13 to 2-SA)
18 x 18 �5;5 X 5,5'.
18 5,
18(68)
17.5 (1,21)
20 x 20 1 x 6,1)
2
23 . 8 .. 1 ,9 4 "t
Next Higher Coverage Area listed. C:1
(b) Requirement is based on minimum flow in GPM/LPM from each sprinkler. The associated residual pressures are CL
;!� <
calculated using the nominal K-Factor. Refer to Hydraulic Design Criteria Section for details. :Z =
5 Co :Z
U-1 11—
(c) For systems with ceiling types smooth flat horizontal, or beamed, or sloped, in accordance with the 2013 Edition of 00 LLJ
NFPA 13D, 13R or 13 as applicable. 04 a _J
APPROVAL STAMP <
<
At TOR REFERENCE ONLY
PRESSURE REGULATOR PRESSURE REGULATOR CPVC TO SYSTEM 11' ELEV. FROM FINISH GRADE
HYDRAULIC
TO BE SET AT 60 PSI TO BE SET AT 60 PSI
1MLIC SYSTEM. TO DOMESTIC WATER TO DOMESTIC WATER JOB NO: 31630
C e i I ii r i g typ f er t c) F F 'A 3, 13 1 o i � 130 CONTROL VALVE FOR DOMESTIC CONTROL VALVE FOR DOMESTIC a.
SPARE SPRINKLERS SHALL DATE: 8/15/17
This Building is Protected by a 5 GPM ALLOWANCE 5 GPM ALLOWANCE NOT BE REQUIRED TO BE =DRAWN BY: M.N.
RFC 49 Hydraulically Designed PROVIDED PER 5.1.1.2
Ordinary Temp, Rating
Max. Coverage Top of Deflector Minimunn;
Max. Spacing (1650 40c) Installation Automatic Sprinkler System.
area -------------- ------- ------------ ---------- __ -------------------- to Ceiling Spacing 1 CPVC RISER
Ft (m) Flow Pressure Type 2' ELEV. �,cl ION COST
Date Installed 8/15/17 GAUGE
7 441 C IFICATION
Ft x Ft (m x m) GPM Urnin) PSI (bar ) Inch (mm) Ft (m) ZELEV.
12 x 12 13,6 x 3,C" (3.61 13140) 0 � C, 4.'
Location CALC AREA 2
14-1/2" x 30"
7 U_
13 xl4z-)� 0;10:48)
14 x 14 14,3 x 4,& IA (4,311 R 'E NO
Number of Sprinklers 2 ACCESS DOOR Smooth C_11r,,_, -V'l [0 1 (13 to 2SAf CONTROL BALL VALVE CONTROL BALL VALVE LICE
7 Of �'C,48) IRP��med Ce ings per NFPA 13D, 13R or
16 x 16 .�4,9 x 4,9';' 6 (4,91 13 %49) Conci;alec 8 (2 4) Basis of Design
0
3 :.stint d in be ar n s to 1 (13 lo 21,EA)
1. DENSITY .05 gpm/sq.ft.
(64,3) 12 0 (0,831
18 X 18 15,5 X 5,51 0, 5' 17
2. DESIGNED AREA OF DISCHARGE I DRAIN VALVE
20 x 20 8x 6,1 20 (6,1) 20 (175, 73) 16. 7 11 1 414
512 sq.ft.
to
O'ELEV. FINISH GRADE O'ELEV. NFPA 13,13Rcr 13-1 System Demand FINISH GRADE DRAT TO EXTERIOR SIZE - 24" X 36"
1. WATER FLOW RATE 32.5 gpm 106 STATIC 82.8 - 10% 74.52 PSI I
2. RESIDUAL PRESSURE AT THE 1%" COPPER L W MASTER METER BLMJ 11/4" COPPER L V METER 4'ELEVRESIDUAL 74.82 -10% = 67.34 PSI SCALE
9.5 PSI LOSS 4 PSI LOSS RUBE R FACED CHECK VALVE . FLOW 2,300 GPM N.T.S.
BASE OF THE RISER 38.4 psi 111411 VC 1" COPPER K 11/4" PVC 1" COPPER K 3 PSI OSS
METER cITy WATER FLO IN INFORMA L/ON
MAIN mAIN) IF SHEET IS LESS THAN
METER CITY
Installed By Fire Sprinkler Systems, Inc.O W(�) 1�1 DO3 24" X 36" IT IS A REDUCED
-2' ELEV. 70'MAX � 30'MAX 100 -2' ELEV. 70'MAX � 30' MAX 100 PRINT SCALE
0 Ld REDUCE ACCORDINGLY
-2 ELEV. -2 ELEV. -2 ELEV. -2 ELEV. ZELEV.
SHEET ID
HYDRAULIC NAMEPLATE ALT. UNDERGROUND DETAIL UNDERGROUND DETAIL RISER DETAIL GENERAL NOTES
N.T.S. N.T.S. (FOR REFERENCE ONLY) N.T.S. (FOR REFERENCE ONLY) N.T.S. SHEETFP1 OF FP4
M
1-HR. AND 2-HR. GYPSUM WALL ASSEMBLY
1 OR 2 HOUR FIRE RATED THROUGH PENETRATION FIRESTOP FOR SINGLE
PLASTIC PIPE THROUGH GYPSUM WALLS USING
BLAZEMASTER CAULK & WALK
F RATING =1-HR. AND 2-HR.
T RATING =1-HR. AND 2-HR. DRAWING NOT TO SCALE
1. PRE -RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY
A) THE F RATING =1 HOUR IF THERE IS ONE LAYER OF GYPSUM WALLBOARD.
B THE F RATING = 2 HOUR IF THERE ARE TWO LAYERS OF GYPSUM WALLBOARD.
2. PLASTIC PIPE - A) NOM. 2" DIAM. (OR SMALLER) SCH. 40 PVC PIPE
B) NOM. 2" DIAM. (OR SMALLER) CPVC PIPE,
THE ANNULAR SPACE RANGE SHALL BE ,MIN.1/4" TO MAX 1-3/8".
NOTE: FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS.
3. BLAZEMASTER CAULK & WALK - MIN. 1/2" THICKNESS OF SEALANT APPLIED WITHIN OPENING.
ADDITIONAL SEALANT TO BE INSTALLED SUCH THAT A MIN. 1/4" CROWN
IS FORMED AROUND THE PENETRATING ITEM.
NOTE: THE F & T RATINGS OF THE SYSTEM IS EQUAL TO THE FIRE RATING OF THE WALL ASSEMBLY.
UL/cUL SYSTEM NO. WL2151
HYDRAULIC SYSTEM
This Building is Protected by a
Hydraulically Designed
Automatic Sprinkler System.
Date Installed 8/15/17
Location CALC AREA 1
Number of Sprinklers 2
Basis of Design
1. DENSITY .05 gpm/sq.ft.
2. DESIGNED AREA OF DISCHARGE
512 sq.ft.
System Demand
1. WATER FLOW RATE 25 gpm
2. RESIDUAL PRESSURE AT THE
BASE OF THE RISER 36.2 psi
Installed By Fire Sprinkler Systems, Inc.
,Y1
3
I
£
£
I
1 I RETR
VERANDA �,
12'-0"CLG. 0 x �
s 112'-0" C G.
-10, '-10" --. MORNING ROOM
22 w EI 12'-0"CLG.
210^ CALCARE42Ell
13'-6" -
T - a
� .. __ 10'-0" CLG. _. _ _ 11'-0" CLG. ..... 11'-0"CLG.
......... ...... _ .......,.......11'-0" OLG............. __ a ., ....... __.._ GAME ROOM - .� I 1 2" GR C � OM
4-6"
IF-
01
�� MASTER BEDR00 1'_3" ' [ �� ( = o ( r 1
12'-0"CLG. �l b M
10
,r4
5 21 5 23 ( 10'-3" 6' 8" 8" 13'-3" 6' 6" '
i C, € F.
i€ ,
01
` ( I i
gg ( HEAT ONE I ( SHAD,V„WSAREA
m r I o I `2SQ o
1
13'-6" €
3,
12'-0"CLG.
€ j I FT0_-0.CG l
5-�"____
3"Mal 5 4" i j I = 4'-11" r_2" 6 6" ATT C'
Ah
N Ask `� } ARESS I 1"
d
10 0"CCG %w1
__....,..... ,_ __.__._.t _..�.�.._v-_...... 1 , Ii............._ _.�.....,_ i ..�....,, .„_,_,....uf .. `_��---_........... _____ ._._..,,.... ..,.._.�... ______ ..___..... __,_...... _ ..�,..- .... _..�.... ._ .,,,,..,..,,,. _____ ....._........ _ �.... 1 _ .,...,,,.,,.,.,.--•i,1 ?`fin
_ _
11.0 CL
_. ._....,.,.,.. ...._...__ ..__._....._.....,..._. _._._. .____. ..,.....__ W___ ...._.._._ ...._......... ._.._........ ......__..-. __.-.._. ___,__ _......_.. _.._._... .._..�_ ....... 0 CLG.
+) HALL 0 CLG. m
y 12'-0" CLG 12'-0" CLG. b.._} . -.,[ M
to
�[ i 1'-0" CLG Y2'-7" I -�'�` GQ r , tt D NING ROOM
6'-10" 5'-2" 3'
�56 27 �o,
2'-8 20 �' 8" g'.1" 9, " 3" 8' _ low,
^ 4 0 9 4 1� 0"CLG.
1 12� 9" 8�
,
j 1 'CLG. { i01 8 7
n . [ B R M 2^ P WDER
10'-0' CL 24 SQFT SQFT
Aft
1 .....,,.._. 9'"9'p" CLG.
p� i 1 46 S 39 ISQFT
i £ ; __....__....__....., I�€B £' i r•
I GUEST SUITE ✓ i
10'-0'CLG.
ENTRY 1 I '40 SQFT.
j 1' 1r-0"CLG _. `I egg' 9 FT.
9'-0"CLG. 0�-6" CLG.. _. I `�_ 21� 4'-3"
21 SQFT.__.._
CV
i o j z ## 5
3 lij i s[_ i
_
m..........-,.. ! ..._ I W:CC. 1.....1 i € 9'-0" CLG. _.__, .,,,__-_,,,,, _ . ? _ _ ""--
,_... _. .__._....-'-� �"`, ` ''-0" CLG.
__.__..
r__
f=:j I
I 10'-0'CLG. to%
LAUl 12Y
i
i
€ I
I
64.
20'x20' SPACING , 2'-6'
01
2 20x2O SPACIN I L 10, L
1
4'-10"� Ga, i 1
t
;n I rn
I
{ I
_ -O" -CLG,
8 SQ�.
IBEDROOM3
10'-0" CLG. 01
I € CALCARE41
20'x20' SPACING
( 13
it01
M
8' I I
l
,aDii
i
10'-0 CLG
COURTYARD
401,
is '-10" r4
d = € ATTIC
i I ACCESS S.
BEDROOM 2
10'-0" CLG.
I € 5£
b-6" CLG. € cf
-10'
11-7
i1 f
BATHR60M 3
9'-0"CLG i r
40
�a
10'-T CLG.
PLAN 4820 (141X141) FIRE SPRINKLER PLAN
SCALE: 3/16" =1'-0"
- T-10" _J_0�
v
s t 2CAR 'GARAGE
,i
10'-0"CLG.
72
i
j 10,
- i
8 3"
i
6-4
8'
- 7'
KITCHEN
12'-0" CLG.
E
5'-3"
RISER
LOC
SIZE - SYSTEM PIPE: 3/4" thru 3"
MATERIAL - CARBON STEEL.
FINISH - Mil. Galvanized.
LSTING/APPROVAL -
203-EX 4231, EX 2551
FUNCTION - Support horizontal piping: CPVC, Copper or Steel.
Size 3/4" - 2" Prevents upward movement of pipe from pendent sprinkler discharge.
Stabilize vertical piping.
INSTALLATION - Per these instructions
including NFPA 13, 13R, 13D and CPVC manufacturers instructions.
install on horizontal or vertical mounting surface.
FASTENERS - UL Listed per NFPA 13
in WOOD:
3/4" - 3" CPVC PIPE - #905 screw - no pre -drill.
3/4" - 3" Steel and Copper pipe - #14 x 1 1/2" SMS or
1/4"x1 1/2" lag bolt - no pre -drill.
in STEEL: min. 18 GA.
3/4" - 3" CPVC, Copper and Steel pipe - 1/4" or #14 Tek Screw.
FEATURES
' Offset edge eliminates abrasion.
` Retainer dimples secure hanger to pipe during installation.
* Required AFCON #905 screw included - 5/16" hex head.
ORDERING - Part # and pipe size.
CAN ALSO BE USED TO REPLACE - #500 Pipe Strap
#520 Tin Strap
Hang
510 FAST.
SIZE DIM.
3/4 12.126
1 2.312
1 1/4 3.170
1 1/2 3.400
2 1/2 4.320
3 15.320
Nominal Pipe Size (in.)
<"
1"
1'/4"
1'/2"
2"
2'/2"
3"
3'/"
4"
5"
6"
8"
Steel pipe except threaded
N/A
12'-0"
12'-0"
15'-0"
15'-0"
15'-0"
15'-0"
15-0"
1 V-0"
15'-0"
15'-0"
15'-0"
lightwall
Threaded lightwall steel
N/A
12'-0"
12'-0"
12'-0"
12'-0"
12'-0"
12'4'
N/A
N/A
N/A
N/A
N/A
pipe
Copper tube
8'-0"
8'-0"
10'-0"
10'-0"
12'-0"
12'-0"
12'-0"
15'-0"
15'-0"
15'-0"
15'-0"
15'-0'
CPVC
5'-6"
6'-0"
6'-6"
T-0"
8'-0"
9'-0"
10-4-N/A
N/A
NIA
N/A
N/A
Polybutylene (IPS)
N/A
3'-9"
4W.,
5'-0"
5'-11"
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Polybutylene (CTS)
2'-11"
3'-4"
X-11"
4'-5"
5'-5"
N/A
N/A
NIA
N/A
N/A
N/A
N/A
Ductile iron pipe
N/A
N/A
N/A
N/A
N/A
15'-0"
N/A
N/A
15'-0"
N/A
15'-0"
15'-0"
AFCON 510 HANGER (STEEL - COPPER - C.P. V. C. )
NOT TO SCALE
#905 #906
" 7.50 3�00
1
SIZE - SYSTEM PIPE: 3/4" thru 2"
MATERIAL - Carbon Steel.
I FNISH - Mil. Gaavanized.
LSTING/APPROVAL -
``' Hanger/Restrainer
203-EX 4231, EX 2551
PATENT - No. 6,648,278.
FUNCTION - Support horizontal piping: CPVC, Copper or Steel.
Provides listed vertical/horizontal restraint and prevents
upward movement of pipe from pendent sprinkler discharge.
Stabilize vertical piping.
INSTALLATION - Per these instructions Rests
including NFPA 13, 13R, 13D and CPVC manufacturers instructions.
Install on horizontal or vertical mounting surface.
Snap over pipe then squeeze strap back allowing pipe to slide freely.
When #905 threads are exposed in wood, install #906 backing nut.
FASTENERS - UL Listed per NFPA 13
WOOD - CPVC pipe - #905 screw- no pre -drill.
Copper and Steel pipe - #14 SMS or 1/4 "xl 1/2" lag screw - no pre -drill.
Thru 5/8" sum board - 1/4"x 2" lag 9 screw.
STEEL - min. 18 GA. - CPVC, Copper and Steil pipe - 1/4" or #14 Tek Screw.
CONCRETE: Required minimum load each fasterner = 5(wt)+250lbs.
2
FEATURES
1 1/2" Offset- loose fit allows pipe to slide.
Common center -line for 3/4" and 1 ".
Offset edge eliminates abrasion.
AFCON #905 screw included - 5116" hex head.
ORDERING - Part # and pipe size.
AFCON #906 backing nut sold serparately.
Nominal Pipe Size in
%"
1"
1%4"
1I/V
2"
21"
3"
3%"
4"
5"
6"
8"
Steel pipe except threaded
lightwall
N/A
12'-0"
12'-0"
15'-0'
15'-0"
15-0"
15'-0"
15'-0"
15'-0"
15'-0"
15'-0"
15'-0"
Threaded lightwall steel
N/A
12'-0"
12'-0"
12'-0"
12'-0"
12'-0"
12'-0'
NIA
N/A
N/A
N/A
N/A
Pipe
Copper tube
8'-0"
8'-0"
10'-0"
10'-0"
12'-0"
12'-0"
12'-0"
15-0"
15'-0"
15'-0"
15'-0"
15'-0"
CPVC
5'-6"
6'-0"
6'-6"
7'-0"
F-0"
9'-0"
10'-0"
N/A
N/A
N/A
N/A
N/A
Polybutylene (IPS)
NIA
3'-9"
4'-7"
5'4'
5'-11"
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Polybutylene (CTS)
2'-11"
T-4"
3'-11"
4'-5"
5'-5"
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Ductile iron pipe
N/A
NIA
/
N/A
N/A
N/A
15'-0"
N/A
N/A
15'-0"
N/A
15'-0"
15'-0"
AFCON 514 HANGER (STEEL - COPPER - C. P. V. C.)
NOT TO SCALE
RIL
Riverside County Fire Department
Office of
Fire marshal
By:
'me approval of plans and specifications does not:
permit the violation, deletion, omission or faulty
installation of any requirements of Title 24 or any
Local Ordinances. Construction shall remain
<ccessible and exposed for inspection purposes until
approved by the Fire Department.
Aize
FLOOR AREA - 4,820 SQFT.
TOTAL LIVING AREA - 4,820 SQFT.
GARAGE AREA- 716 SQFT.
DESIGN AND INSTALLATION SHALL
CONFORM TO NFPA 13D, 2016 ED.
NOTES:
1. ALL HEAD SPACING TO BE 14'x14', UNLESS OTHERWISE
NOTED.
2. ALL PIPES TO BE %" CPVC, UNLESS OTHERWISE NOTED.
3. PIPE CLEARANCES MUST BE IN ACCORDANCE WITH NFPA
13-9.3.4.
4. HANGERS SHOWN FOR REFERENCE PURPOSES ONLY.
HANGER SPACING TO BE PER TABLES ON THIS SHEET.
5. SPRINKLERS SHALL NOT BE REQUIRED IN BATHROOMS OF
55sgft. AND LESS. (SECTION 8.3.2.)
6. SPRINKLERS SHALL NOT BE REQUIRED IN CLOTHES
CLOSETS, LINEN CLOSETS, AND PANTRIES THAT MEET ALL
OF THE FOLLOWING REQUIREMENTS:
(1) THE AREA OF THE SPACE DOES NOT EXCEED 24sgft.
(2) THE WALLS AND CEILINGS ARE SURFACED WITH
NONCOMBUSTIBLE OR LIMITED -COMBUSTIBLE
MATERIALS AS DEFINED IN NFPA 220.
9. 8.2.5.1.2 THE DISTANCE SHALL BE MEASURED FROM THE
CENTER OF THE SPRINKLER TO THE CENTER OF THE
OBSTRUCTION.
10. 8.2.5.6 SHADOW AREAS SHALL BE PERMITTED IN THE
PROTECTION AREA OF A SPRINKLER AS LONG AS THE
CUMULATIVE DRY AREA DO NOT EXCEED 15sgft (1.4 sqm)
PER SPRINKLER.
Z
U
�
Z
O
W
d
Ina
O
C7LL
Z
O
Z)
(D
W
Q
w
w
O
ME
w
v
W
M_
Q
J_
Q
o
an
LU
an
Ell
�
o
Q
m
N
Oz
ibilize
CV
-
LICENSE NO.684600
•
CUSTOM, TRACT, MULTI -FAMILY
AND COMMERCIAL
•
DESIGN, ENGINEERING AND
INSTALLATION
•
705 E. HARRISON ST., SUITE 200
CORONA, CA 92879
PH - 800-915-3473
FAX - 951-272-2535
•
The recipient of these plans
hereby acknowledges that all
plans, details, specifications or
methods of installation
contained in this set of plans is
the sole property of Fire
Sprinkler Systems, Inc. and
that any use of this set of plans
is prohibited and is a violation
of copyright laws without first
receiving permission from Fire
Sprinkler
S stems.
1=
tin
m
M
C3
�*
N
Co
CO
N
�
w
ut
z
U3
X
X
z
Q
a-d
U:)
_X
N
co
w
J
Y
Z
N
r`.n
in
CA
O
O
ti
n
ti
c.i
U_
ti
M
o
rn
O
iO®m
U3
J
Z
CAWmZrnW
C:)
Z
O
�
OC3
WZLLa�Z
C-C
WU
O
O
ILL:
:D
J
m
J
m
Z
Q
Z
W
Q
J
Q
J
Of
Ix
O
00
0-
Q
00 = m W
r`
CN [� J
U
JOB NO: 31630
DATE: 8/15/17
DRAWN BY: M.N.
Q�Q1 lr'T I ON Cp T
ti
C SI ATION 9n�
r� C-16
* ICENS
s 00 �
�9TF OF CAS\F���\
SIZE - 24" X 36"
SCALE
3/16" =1'
IF SHEET IS LESS THAN
24" X 36" 1T IS A REDUCED
PRINT SCALE
REDUCE ACCORDINGLY J
SHEET ID
FIRE SPRINKLER PLAN
SHEET FP2 OF FP4
L=\
Z�
a
U
O
WQ ri-
m O
OR W
O =5z:
I w
v o
�t Q
QJ -_-�
W¢
Qu
Q
O
W �_ N
< �� N
In O_
O
Z
�n r V �
9'-0" CLG. 8'-7" = 4'1-- `
12'-0" CLG. C?
d 3.4" N ;
STISTEMS INC
5'-11° 2£_8w __ ( •
3' �0,., �, LICENSE NO.684600
TT
NG ROOM
" CLG. _ •
4' p 1 4' s r E
l CUSTOM, TRACT, MULTIFAMILY
' ; ` ` AND COMMERCIAL
10 SQFT. { i •
I $'-7" 1'-9„ l DESIGN, ENGINEERING AND
INSTALLATION
..................... i °
2'-8"�; I 705 E. HARRISON ST., SUITE 200
_____.
€. a' I CORONA, CA 92879
€ BRfikf OOM� [� r— € PH - 800-915-3473
10-0
40 SQFT.
FAX - 95-272-2535
The recipient of these plans
QFT. 9 S1
T _ I hereby acknowledges that all
i
I plans, details, specifications or
methods of installation
( ED contained in this set of plans is
4'-3" the sole property of Fire
Sprinkler Systems, Inc. and
that any use of this set of plans
" - is prohibited and is a violation
2-8 -
of
k8'-0"CLG.
M ` eceopnright ermssinithout from Fet
pl _ _ U _ ....., _ S rinkler S stems.
�._„
E
20'x20' SPACING " __.. 1` 6'-10
m_
_.� 2-6
- E
£ t ;,,
_ 8'
I9'4'CLG M _______ -_______—_____-_�_�_.._.._-- — — — ________..__—.______ ______..___,_.
I i
UND Y
10+.0" QLG. I
2 CAR GARAGE
I 10' 0" CLG. r
M
f £ [
+
"
7 9" 7r - 4
I t �„
an 14' 3" 3,-2" .,.
-10", 1a
7"CO
vJ
I ' ATTiCr 10' S 3
(° ACCESS!'!
92 SQFj 8'-3".t.... O
_{ o o
61
I S
5' �
� F F
10'-5" 1 I_ 10'-3" 8 1'- " j12' 6" 3'- "
16'-10"
1 ? I + s
I 4 $ {
�t RISER
I i OC
si O
_ m. ___ ___ ______.__-__.__.____ _.._
100
s
con Z
Z Q U
-ja Q
CL Q
I
LLI
o
LLI
GARAGE OPTION
�V
l Q
;l
{ SCALE 1/4" =1'-0"
— 3'-2" i
i 3 JOB NO: 31630
DATE: 8/15/17
DRAWN BY: M.N.
<v C SI ATI N
APKOVAL C-16
Riverside Count/ Fire Department ,* LIC
Office�e Fire marshal 68460
i-he approval of plans and specifications does not
� �9TF OF CAS\F��
permit the violation, deletion, omission orfauity
f1stallation of any requirements of Title 24 or any
Local Ordinances. Construction shall remain
accessible and exposed for inspection purposes until SIZE - 24" X 36"
approved by the Fire Department,
SCALE
1 /4" =1'
IF SHEET IS LESS THAN
24" X 36" IT IS A REDUCED
PRINT SCALE
REDUCE ACCORDINGLY
SHEET ID
OPTIONS
SHEET FP3 OF FP4
Table R • One Point of Restraint
R R
MAX. i MAX.
One -Point
Vertical
Restraint
RESTRAINT - RESTRAINT
ONE -POINT ONE -POINT
Nominal
"R"
"R„
Pipe Size
Less than
Greater than
ANSI Inches
100 psi
100 psi
DN
{6,9 bar}
{6,9 bar}
3/4
0'-9"
0'-6"
DN20
(0,23 m)
{0,15 m)
t
DN25
(0,3D m}
(0,23 m}
DN32
(D,41 m)
(0,30 m)
QN40 - DN80
(D,61 m}
(D,3O m}
Table S • Two Points of Restraint
S
f-'—ML—I
Two -Point
ANY DISTANCE —i
Vertical
Restraint
RESTRAINT
TWO -POINT
Nominal Pipe
"S"
<,S„
Size
Less than
Greater than
ANSI inches
100 psi-
100 psi
ON
{6,9 bar}
(6,9 bar)
3/4
4'-0"
3'-0"
DN2D
{1,22 m).
{0,91 m)
t
4'-D"
DN25
{1,52 m}
(1,22 m)
1-t/4
6'-0"
5'-O"
DN32
(1;83 m)
(1,52 m)
1-1/2-3
T-0"
T-O"
DN40 - DN84
{2,13 m)
(2,13 m).
January 2005
Serene Installation Specifications
Garage Installation Specifications shall only apply. for the installation of UL Listed
BlazeMastere CPVC pipe and fittings in garages requiring sprinkler protection per NFPA
13D and NFPA 13R. These Standards are defined in NFPA codes entitled 'One and Twp
Family Dwellings and Mobile Homes' and in 'Residential Occupancies up to Four Stories
in Height'. As referenced in NFPA 130 Section 8.6.4,'Sprinkiers are not required in garages,
open attached porches, carports or similar structures' The installation of TFP BlazeMaster
sprinkler pipe and fittings for use in garages requiring sprinkler protection per NFPA 13R
is only applicable to the UL Listing of this product.
Requirements for Pipe. Fittings, Solvent Cement Systems, System Design, installation,
Freeze Protection, and Penetrating Fire Related Walls and Partitions are covered in this
installation and technical handbook. Please read these sections of the manual carefully
prior to designing or installing TFP BlazeMaster pipe and fittings for garage installations.
The installation of TFP BlazeMaster pipe and fittings in garages requiring sprinklers
Is only OL Listed and is not C-uL Listed.
• installation Requirements
Protection: TFP BlazeMaster CPVC pipe and fittings shall be installed concealed
behind protection consisting of a minimum of one layer of a/a' thick gypsum
wallboard or Vz' thick plywood.
- Sprinkler Requirements: UL Listed, quick response, standard coverage, pendent
or sidewall sprinklers with a 225°F If 07°C) maximum temperature rating shall be
utilized. All sprinklers shall be. installed per the manufacturer's published
installation instructions.
Installation Standard: The Listing for Garage Installations shall pertain to those
occupancies defined by NFPA 13R.
Wtem Risers
In accordance with the UL Listing, TFP BlazeMaster CPVC pipe and fittings may be used
as system risers in accordance with NFPA 13, 13D and 13R when subject to the following
additional limitations:
1. When Installed protected (concealed) in accordance with NFPA 13D and 13R, the
minimum protection shall consist of either one layer of Ya' (9.5 mm) thick gypsum
wallboard or lh (12.7 mm) thick plywood.
2. When installed without protection (exposed) in accordance with NFPA 13, 13D
and 13R, the following limitations shall apply:
- The riser shalt be installed below a smooth, flat, horizontal ceiling construction. A
Listed residential pendent sprinkler is to be installed with its deflector at the
distance from the ceiling specified in the sprinkler Listing.
OR
The riser shall be installed below a horizontal unfinished basement ceiling (in
accordance with NFPA 13D) constructed utilizing nominal 2' x 10' or nominal 2' x
12' exposed solid wood joists on 16' centers, A Listed residential pendent
sprinkler is to be installed with its deflector a maximum of #all below the bottom
of the solid wood joist in anticipation of future installation of a finished ceiling.
When installing TFP BlazeMaster CPVC pipe and fittings in conjunction with 2' x 12'
solid wood joists, the maximum system working pressure under flowing conditions
shall not exceed 100 psi and the maximum system working pressure under static
(nonfiowing) conditions shall not exceed 175 psi.
The Listed residential pendent sprinkler is to have 155°F (68°C) maximum
temperature rating and is to be installed at a maximum horizontal distance of 12
inches from the center line of the riser. The system is to be designed based upon the
Listed flows for the sprinkler selected except that the flow for a single sprinkler or
multiple sprinklers shall not be less than 11 gpm per sprinkler.
Fig. 29 - Double Offset Hanger & Restrainer for CPVC
Plastic Pope C � US Li5tf0
Size Range — Available in 3/4" and 1" pipe sizes
Material — Pre -Galvanized Steel
Function — Intended to perform as a hanger and restrainer for
1/2"
'1.500
CPVC, plastic fire sprinkler pipe. Provides double offset 1 x
1 1/2" from mounting surface. This design will ease installation by
eliminating the need for wood block extension and allow retro-fit
attachment of hanger to sprinkler pipe.
-
Features —
46 i
• Thumb tab provides protection to restrain pipe in rough job site
be bent for listed installation_
e. ® 1.500
conditions. Tab is not required to
• Offset edge eliminates abrasion.
• Attaches easily to wood structure with two special #10 x 1 hex
p
head self -threading screws furnished with product.
• Can be used as a single offset hanger by aligning "dimples"
O
4
with top of mounting surface and utilizing two fasteners in two of
the three holes provided.
O
Approvals — Underwriters' Laboratories Listed in the USA (UL)
;
and Canada (cUL) as a hanger and restrainer to support fire
I
l
sprinkler systems. Meets and exceeds requirements of NFPA 13,
i
13R and 13D.
Finish — Pre -Galvanized
r
Order By — Figure number and pipe size.
`-----------
PAT ENT PENDING
:.3
�V
oil �
ri
r
e55sCia hp=x.he-ad f as cD
aer afore c� a; er nstallater of
:I rsnmorinn to the nna na±;c rnt
Single Offset
11
lk
Cr
BUILDING SEC
SCALE: 1/4" = F-Ott
BUILDING SECTION
SCALE: 1/4" = F-0"
TION
APPROVAL
side County Fire Department
°1e - Fire Marshal
of p ans and specifications does not
the :,violation, deletion, omission or faulty
L.fifatir,n of any requirements of Title 24 or any
C,,iiiwnces. Construction shall remain
L i,osed for inspection purposes until
a
U
-1
1 .1
0t
cD�
O
Lu
O_
N
O
UJ
1_117"il
W
�V'
Q
J
Cl<
Lt1�
m
Q
Q
Q
W
co
�_
0
N
Q
M
N
�
o
ZN
M
�F
r >
8 K1
0
LICENSE NO.684600
0
CUSTOM, TRACT, MULTI -FAMILY
AND COMMERCIAL
•
DESIGN, ENGINEERING AND
INSTALLATION
0
705 E. HARRISON ST., SUITE 200
CORONA, CA 92879
PH - 800-915-3473
FAX - 951-272-2535
0
The recipient of these plans
hereby acknowledges that all
plans, details, specifications or
methods of installation
contained in this set of plans is
the sole property of Fire
Sprinkler Systems, Inc. and
that any use of this set of plans
is prohibited and is a violation
of copyright laws, without first
receivina permission from Fire
V )
Z
0
U
W
0
N
00
U
ZZ
Q
a
U
n-
F-
<C
Z
tY rn
Z
m Z
Wti
U CO
UJ
<0
J
JOB NO: 31630
DATE: 8/15/17
DRAWN BY: M.N.
Q�o��C1 I ON
C IF[ TION 90.1
O
u_ �7
* I NO.
8 0
��9TF OF CAL�F���\Q
SIZE - 24" X 36"
SCALE
114" =1'
IF SHEET IS LESS THAN
24" X 36" IT IS A REDUCED
PRINT SCALE
REDUCE ACCORDINGLY
SHEET ID
SECTIONS
SHEET FP4 OF FP4
DATE: ./24/2020 S:\2017\31630\CALCS\4820.rdf Page 1
FIRE SPRINKLER SYSTEMS
705 E. HARRISON, SUITE 200
CORONA,CA 92879
RESIDENTIAL SPRINKLER SYSTEM
HYDRAULICS CALCULATION REPORT
FOR
GRIFFIN RANCH
LA QUINTA, CA
PLAN 4820
1016 TAKEN OFF WATER SUPPLY FOR SAFETY MARGIN
CALC AREA 1
Date: 1/24/2020
File No: 31630
Data File Name: 4820.rdf
SPRINKLER SPACING
400.0 sq. ft./spklr.(max) Max. Dist. Bet. Spklrs:
20.0 ft.
Min. Dist. Bet. Spklrs: 8.0 Max. Dist. Spklr. to Wall:
10.0 ft.
SPRINKLER SPECIFICATIONS
Mfr: Reliable Descr: RFC49 PEND(20x20) K=4.90
Calculated K Factor for Arm-Overs & Drops:
1.0 ft. x 0.874 in. Drop: K=4.71 (Incl. 1 Tee)
0.0 ft. x 0.874 in. Arm -Over: K=4.67 (Incl. 1 Tee
& 1 Ell)
PIPE SPECIFICATIONS
Type: CPVC HWC: 150
WATER SUPPLY
Source: Public Test Date: By:
Static: 74.5 psi Resid: 67.3 psi Flow:2300.0 gpm
Public Main Size: 8 in
Domestic Demand: 5.0 gpm at node number 104
SPRINKLER DEMAND
No.Spklrs. Min Spklr. Press. Node Total Avail.
Req'd
Flowing Flow (psi) No. Flow Press.
Press.
1 20.0 18.0 13 25.0 74.5
52.0
1 20.0 18.0 13 25.0 74.5
52.n
w
REVIEWING AUTHORITY
W
LU
N
CITY OF LA QUINTA FIRE DEPT.
N z
LU
U
z oW
Q �o
W
o
Q
W
0
cs,
DATE: ,/24/2020 S:\2017\31630\CALLS\4820.rdf Page 2
RESULTS OF ANALYSIS
PIPE & NODE DATA
*
FLOW ANALYSIS
* 1 sprinkler
flowing * 1 sprinklers flowing
FIXD
P #
END LEN
FIT.
LOSS
EL SP *DISCH
FLOW
PF
PT *DISCH
FLOW
PF
PT
HWC
NOD DIA
EQV.LN
PUMP
(FT)
(K) *(GPM)
FL/FT
PE (PSI)*(GPM)
FL/FT
PE (PSI)
1
100
30.00
BG
----
-2.0
SRCE ----
25.0
6.05
52.0 ----
25.0
6.06
52.0
150
101
0.995
6.0
----
-2.0
---- ----
0.17
0.00
45.9 ----
0.17
0.00
45.9
2
101
1.00
-4.0
-2.0
---- ----
25.0
0.17
45.9 ----
25.0
0.17
45.9
150
102
0.995
0.0
----
-2.0
---- ----
0.17
0.00
41.8 ----
0.17
0.00
41.8
3
102
70.00
3L
----
-2.0
---- ----
25.0
3.45
41.8 ----
25.0
3.45
41.8
150
103
1.360
24.0
----
-2.0
---- ----
0.04
0.00
38.3 ----
0.04
0.00
38.3
4
103
4.00
LG
----
-2.0
---- ----
25.0
0.37
38.3 ----
25.0
0.37
38.3
150
104
1.265
3.0
----
2.0
-5 5
0.05
1.73
36.2 5
0.05
1.73
36.2
5
104
2.00
L
----
2.0
-5 5
20.0
0.48
36.2 5
20.0
0.48
36.2
150
105
1.101
5.0
----
4.0
---- -•---
0.07
0.87
34.9 ----
0.07
0.87
34.9
6
105
1.00
-3.0
4.0
---- ----
20.0
0.07
34.9 ----
20.0
0.07
34.9
150
106
1.101
0.0
----
4.0
---- ----
0.07
0.00
31.8 ----
0.07
0.00
31.8
7
106
7.00
2L
----
4.0
---- ----
20.0
1.16
31.8 ----
20.0
1.16
31.8
150
10
1.101
10.0
----
11.0
---- ----
0.07
3.03
27.6 ----
0.07
3.03
27.6
8
10
7.50
LR
----
11.0
---- ----
20.0
2.62
27.6 ----
20.0
2.62
27.6
150
11
0.874
5.0
----
11.0
---- ----
0.21
0.00
25.0 ----
0.21
0.00
25.0
9
11
67.00
L7R
----
11.0
---- ----
11.9
6.27
25.0 ----
11.9
6.27
25.0
150
12
0.874
11.0
----
11.0
---- ----
0.08
0.00
18.7 ----
0.08
0.00
18.7
10
12
0.50
B
----
11.0
---- ----
20.0
0.73
18.7 ----
20.0
0.73
18.7
150
13
0.874
3.0
----
11.0
4.71 20.0
0.21
0.00
18.0 20.0
0.21
0.00
18.0
11
12
9.50
R
----
11.0
---- ----
-8.1
0.41
18.7 ----
-8.1
0.41
18.7
150
14
0.874
1.0
----
11.0
---- ----
-0.04
0.00
19.1 ----
-0.04
0.00
19.1
12
14
2.00
L
----
11.0
•---- ----
-8.1
0.23
19.1 - -
-8.1
0.23
19.1
150
15
0.874
4.0
----
13.0
---- - --
-0.04
0.87
18.5 _---
-0.04
0.87
18.5
13
15
10.00
LBR
----
13.0
---- ----
-8.1
0.70
18.5 ----
-8.1
0.70
18.5
150
16
0.874
8.0
---
13.0
---- ----
-0.04
0.00
19.2 - --
-0.04
0.00
19.2
14
16
2.00
L
----
13.0
-- - ----
-8.1
0.23
19.2 ----
-8.1
0.23
19.2
150
17
0.874
4.0
----
11.0
---- ----
-0.04
0.87
20.3 ----
-0.04
0.87
20.3
15
17
17.50
LBR
----
11.0
----• ----
-8.1
1.00
20.3 ---
-8.1
1.00
20.3
150
18
0.874
8.0
-- -
11.0
---- ----
-0.04
0.00
21.3 ----
-0.04
0.00
21.3
16
18
2.00
L
----
11.0
---- ----
-8.1
0.23
21.3 ----
-8.1
0.23
21.3
150
19
0.874
4.0
----
13.0
---- ----
-0.04
0.87
20.7 ----
-0.04
0.87
20.7
17
19
5.50
L
----
13.0
---- ----
-8.1
0.37
20.7 ----
-8.1
0.37
20.7
DATE: 1/24/2020
S:\2017\31630\CALCS\4820.rdf
Page 3
150
20
0.874
4.0 ----
13.0 ----
---- -0.04
0.00
21.1
---- -0.04
0.00
21.1
18
20
17.00
3R ----
13.0
- -3.7
0.19
21.1
---- -3.7
0.19
21.1
150
21
0.874
3.0 ----
13.0 ----
---- -0.01
0.00
21.2
---- -0.01
0.00
21.2
19
21
15.00
LB ----
13.0 ----
---- 0.0
0.00
21.2
- -- 0.0
0.00
21.2
150
22
0.874
7.0 ----
13.0 ----
---- 0.00
0.00
21.2
---- 0.00
0.00
21.2
20
21
5.00
B ----
13.0 ----
---- -3.7
0.07
21.2
---- -3.7
0.07
21.2
150
23
0.874
3.0 ----
13.0 ----
---- -0.01
0.00
21.3
---- -0.01
0.00
21.3
21
23
9.00
B ----
13.0 ----
---- -3.7
0.11
21.3
---- -3.7
0.11
21.3
150
24
0.874
3.0 ----
13.0 ----
---- -0.01
0.00
21.4
---- -0.01
0.00
21.4
22
24
69.50
7R ----
13.0 ----
---- -3.7
0.71
21.4
---- -3.7
0.71
21.4
150
25
0.874
7.0 ----
13.0 ----
---- -0.01
0.00
22.1
---- -0.01
0.00
22.1
23
25
13.00
BR ----
13.0
-3.7
0.16
22.1
---- -3.7
0.16
22.1
150
26
0.874
4.0 ----
13.0 ----
---- -0.01
0.00
22.3
---- -0.01
0.00
22.3
24
26
2.00
L ----
13.0 ----
---- -3.7
0.06
22.3
---- -3.7
0.06
22.3
150
27
0.874
4.0 ----
11.0
- -0.01
0.87
23.2
---- -0.01
0.87
23.2
25
27
2.50
L ----
11.0 ----
---- -3.7
0.06
23.2
-- - -3.7
0.06
23.2
150
28
0.874
4.0 ----
11.0 ----
---- -0.01
0.00
23.3
---- -0.01
0.00
23.3
26
28
17.50
L2BR ----
11.0 ----
---- 4.4
0.36
23.3
---- 4.4
0.36
23.3
150
29
0.874
11.0 ----
11.0 ----
---- 0.01
0.00
22.9
---- 0.01
0.00
22.9
27
29
2.00
L ----
11.0 ----
-- - 4.4
0.08
22.9
---- 4.4
0.08
22.9
150
30
0.874
4.0 ----
13.0 ----
---- 0.01
0.87
22.0
---- 0.01
0.87
22.0
28
30
59.50
LB7R ----
13.0
4.4
0.92
22.0
---- 4.4
0.92
22.0
150
20
0.874
14.0 ----
13.0 ---•-
---- 0.01
0.00
21.1
---- 0.01
0.00
21.1
29
28
36.00
B5R ----
11.0 ----
---- -8.1
1.72
23.3
---- -8.1
1.72
23.3
150
11
0.874
8.0 ----
11.0 ----
---- -0.04
0.00
25.0
---- -0.04
0.00
25.0
Node Notes
Pipe Notes
Legend:
P - Pipe # LEN - Pipe Length
DIA - Pipe Diameter FIT. - Pipe Fittings
EQV. LN - Pipe Equivalent Length FIXD LOSS - Fixed Loss Device
PUMP - Pump Pressure EL - Node Elevation
SP - K-Factor DISCH - Discharge in gpm
FLOW - Flow Rate FL/FT - Friction Loss per Foot
PF - Pressure Loss due to Friction PE - Pressure Loss due to Elevation
PT - Total Pressure at Node
Fitting Code Letters:
E=45 Ell, L=90 Ell, B=TeeBch, R=TeeRun, C=Couplg, S=SwgChk, G=GatVly, X= X, Y= Y, Z
DATE: 1/24/2020 S:\2017\31630\CALCS\4820.rdf Page 4
The maximum velocity of water flow occurs in pipe 8
at 10.70 ft/s with 1 sprinkler flowing.
The maximum velocity of water flow occurs in pipe 8
at 10.70 ft/s with 1 sprinklers flowing.
PIPE FITTINGS TABLE
Pipe Table Name: standard.npt
PAGE: C
MATERIAL: CPVC HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E
L B R
C
S
G
X
Y
Z
45 Ell
90 Ell TeeBch TeeRun
Couplg
SwgChk
GatVly
X
Y
Z
0.874
1.00
4.00 3.00 1.00
1.00
5.00
2.00
0.00
0.00
0.00
1.101
1.00
5.00 5.00 1.00
1.00
8.00
2.00
0.00
0.00
0.00
PAGE: K
MATERIAL: Copper Tube-K
HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E
L B R
C
S
G
X
Y
Z
45 Ell
90 Ell TeeBch TeeRun Couplg
SwgChk
GatVly
X
Y
Z
0.995
1.00
2.00 6.00 2.00
2.00
6.00
0.00
0.00
0.00
0.00
PAGE: L
MATERIAL: Copper Tube-L
HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E
L B R
C
S
G
X
Y
Z
45 Ell
90 Ell TeeBch TeeRun Couplg
SwgChk
GatVly
X
Y
Z
1.265
1.00
3.00 6.00 2.00
2.00
7.00
0.00
0.00
0.00
0.00
PAGE: P
MATERIAL: PVC HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E
L B R
C
S
G
X
Y
Z
45 Ell
90 Ell TeeBch TeeRun Couplg
SwgChk
GatVly
X
Y
Z
1.360
2.00
8.00 6.00 1.00
1.00
11.00
3.00
0.00
0.00
0.00
Sprinkler system has been hydraulically calculated with the
HASS HOUSE 3.8.0 computer program (License No. 50081444)
to provide an average imbalance of 0.010 gpm at each node and
a maximum imbalance of 0.08 gpm with one sprinkler
flowing, and 0.010 gpm at each node and maximum imbalance
of 0.02 gpm with 1 sprinklers flowing in accordance
with NFPA 13 and 13D or 13R.
The minimum source pressure is 20.0 psi with a minimum required pressure
of 52.0 psi and a 7 minute flow of 175 gal. and a 10 minute flow of 250.0 gallons.
The minimum pressure at any node is 18.0 psi at node 13.
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
DATE: 1/24/2020 S:\2017\31630\CALCS\4820.rdf
Page 5
75.0
67.5
P
60.0
R
E
52.5
S
S
45.0
U
R
E 37.5
30.0,
i
P
22.5
S
I
15.0
)
T
7.5
WATER SUPPLY CURVE
D
0.0 -F�� -h- - - - -
04 8 12 16 20 24 28 32 36
FLOW (GPM)
Static = 74.5 psi, Residual = 67.3 psi @ 2300 gpm
(1 sprinkler flowing) (1 sprinklers flowing)
A = Available Water Supply C = Available Water Supply
74.5 psi @ 25.0 gpm 74.5 psi @ 25.0 gpm
B = Required Water Supply D = Required Water Supply
52.0 psi @ 25.0 gpm 52.0 psi @ 25.0 gpm
I
40
DATE: 1/24/2020 S:\2017\31630\CALCS\4820.rdf
Page 1
FIRE SPRINKLER SYSTEMS
705 E. HARRISON, SUITE 200
CORONA,CA 92879
RESIDENTIAL SPRINKLER SYSTEM
HYDRAULICS CALCULATION REPORT
FOR
GRIFFIN RANCH
LA QUINTA, CA
PLAN 4820
10% TAKEN OFF WATER SUPPLY FOR SAFETY MARGIN
CALC AREA 2
Date: 1/24/2020
File No: 31630
Data File Name: 4820.rdf
SPRINKLER SPACING
196.0 sq. ft./spklr.(max) Max. Dist. Bet. Spklrs:
14.0 ft.
Min. Dist. Bet. Spklrs: 8.0 Max. Dist. Spklr. to Wall:
7.0 ft.
SPRINKLER SPECIFICATIONS
Mfr: Senju Descr: SS8261 Pend.RC-RES(14xl4) K=3.70
Calculated K Factor for Arm-Overs & Drops:
1.0 ft. x 0.874 in. Drop: K=3.61 (Incl. 1 Tee)
0.0 ft. x 0.874 in. Arm -Over: K=3.59 (Incl. 1 Tee
& 1 Ell)
PIPE SPECIFICATIONS
Type: CPVC HWC: 150
WATER SUPPLY
Source: Public Test Date: By:
Static: 74.5 psi Resid: 67.3 psi Flow:2300.0 gpm
Public Main Size: 8 in
Domestic Demand: 5.0 gpm at node number 104
SPRINKLER DEMAND
No.Spklrs. Min Spklr. Press. Node Total Avail.
Req'd
Flowing Flow (psi) No. Flow Press.
Press.
1 10.0 7.7 22 15.0 74.5
29.6
2 10.0 7.7 22 25.7 74.5
45.4
REVIEWING AUTHORITY
CITY OF LA QUINTA FIRE DEPT.
DATE: 1/24/2020 S:\2017\31630\CALLS\4820.rdf Page 2
RESULTS OF ANALYSIS
PIPE & NODE DATA
*
FLOW ANALYSIS
* 1 sprinkler
flowing
* 2 sprinklers
flowing
FIXD
P #
END LEN
FIT.
LOSS
EL
SP *DISCH
FLOW
PF
PT *DISCH
FLOW
PF
PT
HWC
NOD DIA
EQV.LN
PUMP
(FT)
(K) *(GPM)
FL/FT
PE (PSI)*(GPM)
FL/FT
PE (PSI)
1
100
30.00
BG
----
-2.0
SRCE ----
15.0
2.35
29.6 ----
25.7
6.38
45.4
150
101
0.995
6.0
----
-2.0
---- ----
0.07
0.00
27.3 ----
0.18
0.00
39.0
2
101
1.00
-4.0
-2.0
---- -- -
15.0
0.07
27.3 ----
25.7
0.18
39.0
150
102
0.995
0.0
----
-2.0
---
0.07
0.00
23.2 ----
0.18
0.00
34.9
3
102
70.00
3L
----
-2.0
---- ----
15.0
1.34
23.2 ----
25.7
3.64
34.9
150
103
1.360
24.0
----
-2.0
---- --•--
0.01
0.00
21.9 ----
0.04
0.00
31.2
4
103
4.00
LG
----
-2.0
---- ----
15.0
0.14
21.9 ----
25.7
0.39
31.2
150
104
1.265
3.0
_---
2.0
-5 5
0.02
1.73
20.0 5
0.06
1.73
29.1
5
104
2.00
L
----
2.0
-5 5
10.0
0.13
20.0 5
20.7
0.51
29.1
150
105
1.101
5.0
----
4.0
---- ----
0.02
0.87
19.0 ----
0.07
0.87
27.7
6
105
1.00
-3.0
4.0
--
10.0
0.02
19.0 ----
20.7
0.07
27.7
150
106
1.101
0.0
----
4.0
---- ----
0.02
0.00
16.0 ----
0.07
0.00
24.7
7
106
7.00
2L
----
4.0
---- ----
10.0
0.32
16.0 ----
20.7
1.24
24.7
150
10
1.101
10.0
----
11.0
---- ----
0.02
3.03
12.6 ----
0.07
3.03
20.4
8
10
7.50
LR
----
11.0
•---
10.0
0.73
12.6 -----
20.7
2.80
20.4
150
11
0.874
5.0
----
11.0
---- ----
0.06
0.00
11.9 ----
0.22
0.00
17.6
9
11
67.00
L7R
----
11.0
---- ----
3.8
0.77
11.9 ----
7.8
2.89
17.6
150
12
0.874
11.0
----
11.0
---- ----
0.01
0.00
11.1 ----
0.04
0.00
14.7
10
12
0.50
B
----
11.0
---- _---
0.0
0.00
11.1 ----
0.0
0.00
14.7
150
13
0.874
3.0
----
11.0
---- ----
0.00
0.00
11.1 _---
0.00
0.00
14.7
11
12
9.50
R
----
11.0
---- ---•-
3.8
0.10
11.1 ----
7.8
0.39
14.7
150
14
0.874
1.0
----
11.0
---•- ----
0.01
0.00
11.0 ----
0.04
0.00
14.3
12
14
2.00
L
----
11.0
---- ----
3.8
0.06
11.0 ----
7.8
0.22
14.3
150
15
0.874
4.0
----
13.0
---- ----
0.01
0.87
10.1 ----
0.04
0.87
13.2
13
15
10.00
LBR
----
13.0
--
3.8
0.18
10.1 ----
7.8
0.67
13.2
150
16
0.874
8.0
-----
13.0
---- ----
0.01
0.00
9.9 ----
0.04
0.00
12.6
14
16
2.00
L
----
13.0
---- -----
3.8
0.06
9.9 ----
7.8
0.22
12.6
150
17
0.874
4.0
----
11.0
---- -•---
0.01
0.87
10.7 ----
0.04
0.87
13.2
15
17
17.50
LBR
----
11.0
---- ----
3.8
0.25
10.7 ----
7.8
0.95
13.2
150
18
0.874
8.0
-_--
11.0
---- ----
0.01
0.00
10.5 ----
0.04
0.00
12.3
16
18
2.00
L
----
11.0
---- •-•---
3.8
0.06
10.5 ----
7.8
0.22
12.3
150
19
0.874
4.0
----
13.0
-
0.01
0.87
9.5 ----
0.04
0.87
11.2
17
19
5.50
L
----
13.0
----- ----
3.8
0.09
9.5 ----
7.8
0.35
11.2
DATE: 1/24/2020
S:\2017\31630\CALLS\4820.rdf
Page 3
150
20
0.874
4.0 ----
13.0
----
---- 0.01
0.00
9.5
----
0.04
0.00
10.8
18
20
17.00
3R ----
13.0
----
---- 6.5
0.52
9.5
----
13.0
1.88
10.8
150
21
0.874
3.0 ----
13.0
----
---- 0.03
0.00
8.9
----
0.09
0.00
8.9
19
21
15.00
LB ----
13.0
----
---- 10.0
1.28
8.9
----
10.0
1.28
8.9
150
22
0.874
7.0 ----
13.0
3.61
10.0 0.06
0.00
7.7
10.0
0.06
0.00
7.7
20
21
5.00
B ----
13.0
----
---- -3.5
0.07
8.9
----
3.0
0.05
8.9
150
23
0.874
3.0 ----
13.0
----
---- -0.01
0.00
9.0
----
0.01
0.00
8.9
21
23
9.00
B ----
13.0
----
---- -3.5
0.10
9.0
----
3.0
0.07
8.9
150
24
0.874
3.0 ----
13.0
3.61
-_-- -0.01
0.00
9.1
10.7
0.01
0.00
8.8
22
24
69.50
7R ----
13.0
3.61
---- -3.5
0.64
9.1
10.7
-7.7
2.77
8.8
150
25
0.874
7.0 - --
13.0
----
---- -0.01
0.00
9.7
---
-0.04
0.00
11.6
23
25
13.00
BR ----
13.0
----
---- -3.5
0.14
9.7
----
-7.7
0.62
11.6
150
26
0.874
4.0 ----
13.0
----
---- -0.01
0.00
9.9
-_--
-0.04
0.00
12.2
24
26
2.00
L ----
13.0
----
---- -3.5
0.05
9.9
----
-7.7
0.22
12.2
150
27
0.874
4.0 ----
11.0
- -0.01
0.87
10.8
----
-0.04
0.87
13.3
25
27
2.50
L ----
11.0
-
-- -3.5
0.05
10.8
----
-7.7
0.24
13.3
150
28
0.874
4.0 ----
11.0
----
---- -0.01
0.00
10.9
----
-0.04
0.00
13.5
26
28
17.50
L2BR ----
11.0
----
---- 2.6
0.14
10.9
----
5.1
0.48
13.5
150
29
0.874
11.0 ----
11.0
----
---- 0.00
0.00
10.7
----
0.02
0.00
13.0
27
29
2.00
L ----
11.0
----
---- 2.6
0.03
10.7
----
5.1
0.10
13.0
150
30
0.874
4.0 ----
13.0
----
---- 0.00
0.87
9.8
----
0.02
0.87
12.1
28
30
59.50
LB7R ----
13.0
----
---- 2.6
0.36
9.8
----
5.1
1.25
12.1
150
20
0.874
14.0 ----
13.0
----
---- 0.00
0.00
9.5
----
0.02
0.00
10.8
29
28
36.00
B5R ----
11.0
----
---- -6.2
1.04
10.9
----
-12.9
4.08
13.5
150
11
0.874
8.0 ----
11.0
--
-0.02
0.00
11.9
-- -
-0.09
0.00
17.6
Node Notes
Pipe Notes
Legend:
P - Pipe # LEN - Pipe Length
DIA - Pipe Diameter FIT. - Pipe Fittings
EQV. LN - Pipe Equivalent Length FIXD LOSS - Fixed Loss Device
PUMP - Pump Pressure EL - Node Elevation
SP - K-Factor DISCH - Discharge in gpm
FLOW - Flow Rate FL/FT - Friction Loss per Foot
PF - Pressure Loss due to Friction PE - Pressure Loss due to Elevation
PT - Total Pressure at Node
Fitting Code Letters:
E=45 Ell, L=90 Ell, B=TeeBch, R=TeeRun, C=Couplg, S=SwgChk, G=GatVly, X= X, Y= Y, Z
DATE: 1/24/2020 S:\2017\31630\CALCS\4820.rdf Page 4
The maximum velocity of water flow occurs in pipe 2
at 6.19 ft/s with 1 sprinkler flowing.
The maximum velocity of water flow occurs in pipe 8
at 11.09 ft/s with 2 sprinklers flowing.
PIPE FITTINGS TABLE
Pipe Table Name: standard.npt
PAGE: C
MATERIAL: CPVC HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E
L B R
C
S
G
X
Y
Z
45 Ell
90 Ell TeeBch TeeRun
Couplg
SwgChk
GatVly
X
Y
Z
0.874
1.00
4.00 3.00 1.00
1.00
5.00
2.00
0.00
0.00
0.00
1.101
1.00
5.00 5.00 1.00
1.00
8.00
2.00
0.00
0.00
0.00
PAGE: K
MATERIAL: Copper Tube-K
HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
( in)
E
L B R
C
S
G
X
Y
Z
45 Ell
90 Ell TeeBch TeeRun
Couplg
SwgChk
GatVly
X
Y
Z
0.995
1.00
2.00 6.00 2.00
2.00
6.00
0.00
0.00
0.00
0.00
PAGE: L
MATERIAL: Copper Tube-L
HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E
L B R
C
S
G
X
Y
Z
45 Ell
90 Ell TeeBch TeeRun Couplg
SwgChk
GatVly
X
Y
Z
1.265
1.00
3.00 6.00 2.00
2.00
7.00
0.00
0.00
0.00
0.00
PAGE: P
MATERIAL: PVC HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E
L B R
C
S
G
X
Y
Z
45 Ell
90 Ell TeeBch TeeRun Couplg
SwgChk
GatVly
X
Y
Z
1.360
2.00
8.00 6.00 1.00
1.00
11.00
3.00
0.00
0.00
0.00
Sprinkler system has been hydraulically calculated with the
HASS HOUSE 3.8.0 computer program (License No. 50081444)
to provide an average imbalance of 0.010 gpm at each node and
a maximum imbalance of 0.07 gpm with one sprinkler
flowing, and 0.010 gpm at each node and maximum imbalance
of 0.10 gpm with 2 sprinklers flowing in accordance
with NFPA 13 and 13D or 13R.
The minimum source pressure is 20.0 psi with a minimum required pressure
of 45.4 psi and a 7 minute flow of 180 gal. and a 10 minute flow of 257.3 gallons.
The minimum pressure at any node is 7.7 psi at node 22.
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
DATE: 1/24/2020 S:\2017\31630\CALLS\4820.rdf
Page 5
75.0 A
67.5
P 1
60.01
R
E
52.5'
S
S
45.0
U
R
37.5
E
{ 30.0
P
22.5
S
7.5
0.0
04 8 12
OB
WATER SUPPLY CURVE
C
CD
I _
16 20 24 28 32
FLOW (GPM)
I
36 40
Static = 74.5 psi, Residual = 67.3 psi @ 2300 gpm
(1 sprinkler flowing) (2 sprinklers flowing)
A = Available Water Supply C = Available Water Supply
74.5 psi @ 15.0 gpm 74.5 psi @ 25.7 gpm
B = Required Water Supply D = Required Water Supply
29.6 psi @ 15.0 gpm 45.4 psi @ 25.7 gpm
DATE: 1/24/2020 S:\2017\31630\CALLS\4820_ALT.rdf
Page 1
FIRE SPRINKLER SYSTEMS
705 E. HARRISON, SUITE 200
CORONA,CA 92879
RESIDENTIAL SPRINKLER SYSTEM
HYDRAULICS CALCULATION REPORT
FOR
GRIFFIN RANCH
LA QUINTA, CA
PLAN 4820 ALT.
10% TAKEN OFF WATER SUPPLY FOR SAFETY MARGIN
CALC AREA 1
Date: 1/24/2020
File No: 31630
Data File Name: 4820 ALT.rdf
SPRINKLER SPACING
400.0 sq..ft./spklr.(max) Max. Dist, Bet. Spklrs: 20.0 ft.
Min. Dist. Bet. Spklrs: 8.0 Max. Dist. Spklr. to Wall: 10.0 ft.
SPRINKLER SPECIFICATIONS
Mfr: Reliable Descr: RFC49 PEND(20x20) K=4.90
Calculated K Factor for Arm-Overs & Drops:
1.0 ft. x 0.874 in. Drop: K=4.71 (Incl. 1 Tee)
0.0 ft. x 0.874 in. Arm -Over: K=4.67 (Incl. 1 Tee & 1 Ell)
PIPE SPECIFICATIONS
Type: CPVC HWC: 150
WATER SUPPLY
Source: Public Test Date: By:
Static: 74.5 psi Resid: 67.3 psi F1ow:2300.0 gpm
Public Main Size: 8 in
Domestic Demand: 5.0 gpm at node number 104
SPRINKLER DEMAND
No.Spklrs. Min Spklr. Press
Flowing Flow (psi)
1 20.0 18.0
1 20.0 18.0
REVIEWING AUTHORITY
CITY OF LA QUINTA FIRE DEPT.
Node Total Avail. Req'd
No. Flow Press. Press.
13 25.0 74.5 58.0
13 25.0 74.5 58.0
DATE: 1/24/2020 S:\2017\31630\CALCS\4820-ALT.rdf Page 2
RESULTS OF ANALYSIS
PIPE & NODE DATA
*
FLOW
ANALYSIS
*
1 sprinkler
flowing
* 1 sprinklers
flowing
FIXD
P #
END LEN
FIT.
LOSS
EL
SP *DISCH
FLOW
PF
PT *DISCH
FLOW
PF
PT
HWC
NOD DIA
EQV.LN
PUMP
(FT)
(K) *(GPM)
FL/FT
PE (PSI)*(GPM)
FL/FT
PE (PSI)
------------------------------------
---------------------
---------------------
1
100
30.00
BG
----
-2.0
SRCE
---- 25.0
6.06
58.0 ----
25.0
6.06
58.0
150
101
0.995
6.0
----
-2.0
----
---- 0.17
0.00
52.0 ----
0.17
0.00
52.0
2
101
1.00
-9.5
-2.0
----
---- 25.0
0.69
52.0 ----
25.0
0.69
52.0
150
102
0.745
0.0
----
-2.0
----
---- 0.69
0.00
41.8 ----
0.69
0.00
41.8
3
102
70.00
3L
----
-2.0
----
---- 25.0
3.45
41.8 ----
25.0
3.45
41.8
150
103
1.360
24.0
----
-2.0
----
---- 0.04
0.00
38.3 ----
0.04
0.00
38.3
4
103
4.00
LG
----
-2.0
----
---- 25.0
0.37
38.3 ----
25.0
0.37
38.3
150
104
1.265
3.0
----
2.0
-5
5 0.05
1.73
36.2 5
0.05
1.73
36.2
5
104
2.00
L
----
2.0
-5
5 20.0
0.48
36.2 5
20.0
0.48
36.2
150
105
1.101
5.0
----
4.0
----
---- 0.07
0.87
34.9 ----
0.07
0.87
34.9
6
105
1.00
-3.0
4.0
----
---- 20.0
0.07
34.9 ----
20.0
0.07
34.9
150
106
1.101
0.0
----
4.0
----
••--•• 0.07
0.00
31.8 ----
0.07
0.00
31.8
7
106
7.00
2L
----
4.0
----
---- 20.0
1.16
31.8 ----
20.0
1.16
31.8
150
10
1.101
10.0
----
11.0
----
---- 0.07
3.03
27.6 ----
0.07
3.03
27.6
8
10
7.50
LR
----
11.0
----
---- 20.0
2.62
27.6 ----
20.0
2.62
27.6
150
11
0.874
5.0
----
11.0
----
- -- 0.21
0.00
25.0 ----
0.21
0.00
25.0
9
11
67.00
L7R
----
11.0
----
---- 11.9
6.29
25.0 ----
11.9
6.29
25.0
150
12
0.874
11.0
----
11.0
----
---- 0.08
0.00
18.7 ----
0.08
0.00
18.7
10
12
0.50
B
----
11.0
----
---- 20.0
0.73
18.7 ----
20.0
0.73
18.7
150
13
0.874
3.0
----
11.0
4.71
20.0 0.21
0.00
18.0 20.0
0.21
0.00
18.0
11
12
9.50
R
----
11.0
----
---- -8.1
0.41
18.7 ----
-8.1
0.41
18.7
150
14
0.874
1.0
----
11.0
----
---- -0.04
0.00
19.1 ---- -0.04
0.00
19.1
12
14
2.00
L
----
11.0
----
---- -8.1
0.23
19.1 ----
-8.1
0.23
19.1
150
15
0.874
4.0
---
13.0
----
---- -0.04
0.87
18.5 ---- -0.04
0.87
18.5
13
15
10.00
LBR
----
13.0
----
---- -8.1
0.70
18.5 ----
-8.1
0.70
18.5
150
16
0.874
8.0
----
13.0
----
---- -0.04
0.00
19.2 ---- -0.04
0.00
19.2
14
16
2.00
L
----
13.0
----
---- -8.1
0.23
19.2 ----
-8.1
0.23
19.2
150
17
0.874
4.0
----
11.0
----
---- -0.04
0.87
20.3 ---- -0.04
0.87
20.3
15
17
17.50
LBR
-- -
11.0
----
---- -8.1
0.99
20.3 ----
-8.1
0.99
20.3
150
18
0.874
8.0
----
11.0
----
---- -0.04
0.00
21.3 ---- -0.04
0.00
21.3
16
18
2.00
L
----
11.0
----
---- -8.1
0.23
21.3 -- -
-8.1
0.23
21.3
150
19
0.874
4.0
----
13.0
---
- -- -0.04
0.87
20.7 ---- -0.04
0.87
20.7
DATE: 1/24/2020 S:\2017\31630\CALCS\4820_ALT.rdf Page 3
17
19
5.50
L
---- 13.0
---- ---- -8.1
0.37
20.7 ----
-8.1
0.37
20.7
150
20
0.874
4.0
---- 13.0
---- ---- -0.04
0.00
21.0 ----
-0.04
0.00
21.0
18
20
17.00
4R
---- 13.0
---- ---- -3.8
0.20
21.0 ----
-3.8
0.20
21.0
150
21
0.874
4.0
---- 13.0
---- ---- -0.01
0.00
21.2 ----
-0.01
0.00
21.2
19
21
15.00
LBR
---- 13.0
---- ---- 0.0
0.00
21.2 ----
0.0
0.00
21.2
150
22
0.874
8.0
---- 13.0
---- ---- 0.00
0.00
21.2 ----
0.00
0.00
21.2
20
21
5.00
B
---- 13.0
---- ---- -3.8
0.08
21.2 ----
-3.8
0.08
21.2
150
23
0.874
3.0
---- 13.0
---- ---- -0.01
0.00
21.3 ----
-0.01
0.00
21.3
21
23
10.00
B
---- 13.0
---- ---- 0.0
0.00
21.3 ----
0.0
0.00
21.3
150
24
0.874
3.0
---- 13.0
---- ---- 0.00
0.00
21.3 ----
0.00
0.00
21.3
22
23
56.00
9R
---- 13.0
---- ---- -3.8
0.62
21.3 ----
-3.8
0.62
21.3
150
25
0.874
9.0
- -- 13.0
---- ---- -0.01
0.00
21.9 ----
-0.01
0.00
21.9
23
25
26.50
B2R
---- 13.0
---- ---- -3.8
0.30
21.9 ----
-3.8
0.30
21.9
150
26
0.874
5.0
---- 13.0
---- ---- -0.01
0.00
22.2 ----
-0.01
0.00
22.2
24
26
2.00
L
---- 13.0
---- ---- -3.8
0.06
22.2 -- -
-3.8
0.06
22.2
150
27
0.874
4.0
---- 11.0
---- ---- -0.01
0.87
23.2 ----
-0.01
0.87
23.2
25
27
2.50
L
---- 11.0
---- ---- -3.8
0.06
23.2 ----
-3.8
0.06
23.2
150
28
0.874
4.0
---- 11.0
---- ---- -0.01
0.00
23.2 ----
-0.01
0.00
23.2
26
28
17.50
2LBR
- -- 11.0
---- ---- 4.3
0.36
23.2 - --
4.3
0.36
23.2
150
29
0.874
12.0
---- 11.0
---- ---- 0.01
0.00
22.9 ----
0.01
0.00
22.9
27
29
2.00
L
---- 11.0
---- ---- 4.3
0.07
22.9 ----
4.3
0.07
22.9
150
30
0.874
4.0
---- 13.0
---- ---- 0.01
0.87
21.9 ----
0.01
0.87
21.9
28
30
59.50
LB7R
---- 13.0
---- ---- 4.3
0.89
21.9 ----
4.3
0.89
21.9
150
20
0.874
14.0
---- 13.0
---- ---- 0.01
0.00
21.0 ----
0.01
0.00
21.0
29
28
38.00
B5R
---- 11.0
---- ---- -8.1
1.79
23.2 ----
-8.1
1.79
23.2
150
11
0.874
8.0
---- 11.0
---- ---- -0.04
0.00
25.0 ----
-0.04
0.00
25.0
Node Notes
Pipe Notes
Legend:
P -
Pipe #
LEN -
Pipe Length
DIA
- Pipe Diameter
FIT.
- Pipe Fittings
EQV.
LN - Pipe Equivalent Length
FIXD
LOSS - Fixed Loss Device
PUMP
- Pump Pressure
EL -
Node Elevation
SP -
K-Factor
DISCH
- Discharge in gpm
FLOW
- Flow Rate
FL/FT
- Friction Loss per Foot
PF -
Pressure Loss due to Friction
PE -
Pressure Loss due to Elevation
PT -
Total Pressure at Node
Fitting Code Letters:
E=45 Ell, L=90 Ell, B=TeeBch,
R=TeeRun,
C=Couplg, S=SwgChk, G=GatVly, X= X,
DATE: 1/24/2020 S:\2017\31630\CALCS\4820_ALT.rdf Page 4
The maximum velocity of water flow occurs in pipe 2
at 18.40 ft/s with 1 sprinkler flowing.
The maximum velocity of water flow occurs in pipe 2
at 18.40 ft/s with 1 sprinklers flowing.
PIPE FITTINGS TABLE
Pipe Table Name: standard.npt
PAGE: C
MATERIAL: CPVC HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E
L B R
C
S
G
X
Y
Z
45 Ell
90 Ell TeeBch TeeRun
Couplg
SwgChk
GatVly
X
Y
Z
0.874
1.00
4.00 3.00 1.00
1.00
5.00
2.00
0.00
0.00
0.00
1.101
1.00
5.00 5.00 1.00
1.00
8.00
2.00
0.00
0.00
0.00
PAGE: K
MATERIAL: Copper Tube-K
HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E
L B R
C
S
G
X
Y
Z
45 Ell
90 Ell TeeBch TeeRun
Couplg
SwgChk
GatVly
X
Y
Z
0.745
0.00
1.00 3.00 1.00
1.00
0.00
0.00
0.00
0.00
0.00
0.995
1.00
2.00 6.00 2.00
2.00
6.00
0.00
0.00
0.00
0.00
PAGE: L
MATERIAL: Copper Tube-L
HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E
L B R
C
S
G
X
Y
Z
45 Ell
90 Ell TeeBch TeeRun
Couplg
SwgChk
GatVly
X
Y
Z
1.265
1.00
3.00 6.00 2.00
2.00
7.00
0.00
0.00
0.00
0.00
PAGE: P
MATERIAL: PVC HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E
L B R
C
S
G
X
Y
Z
45 Ell
90 Ell TeeBch TeeRun
Couplg
SwgChk
GatVly
X
Y
Z
1.360
2.00
8.00 6.00 1.00
1.00
11.00
3.00
0.00
0.00
0.00
Sprinkler system has been hydraulically calculated with the
HASS HOUSE 3.8.0 computer program (License No. 50081444)
to provide an average imbalance of 0.010 gpm at each node and
a maximum imbalance of 0.01 gpm with one sprinkler
flowing, and 0.010 gpm at each node and maximum imbalance
of 0.01 gpm with 1 sprinklers flowing in accordance
with NFPA 13 and 13D or 13R.
The minimum source pressure is 20.0 psi with a minimum required pressure
of 58.0 psi and a 7 minute flow of 175 gal. and a 10 minute flow of 250.0 gallons.
The minimum pressure at any node is 18.0 psi at node 13.
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
DATE,: 1/24/2020 S:\2017\31630\CALCS\4820—ALT.rdf
Page 5
WATER SUPPLY CURVE
75.0 — -- C -
67.5
P t60.OD
D
E
52.5
S
S
45.0
U
R
37.5
E
{
30.0
P
22.5
S
I
15.0
7.5
-
0.0
04 8 12 16 20 24 28 32 36
FLOW (GPM)
Static = 74.5 psi, Residual = 67.3 psi @ 2300 gpm
(1 sprinkler flowing) (1 sprinklers flowing)
A = Available Water Supply C = Available Water Supply
74.5 psi @ 25.0 gpm 74.5 psi @ 25.0 gpm
B = Required Water Supply D = Required Water Supply
58.0 psi @ 25.0 gpm 58.0 psi @ 25.0 gpm
40
DATD: 1/24/2020 S:\2017\31630\CALCS\4820—ALT.rdf
Page 1
FIRE SPRINKLER SYSTEMS
705 E. HARRISON, SUITE 200
CORONA,CA 92879
RESIDENTIAL SPRINKLER SYSTEM
HYDRAULICS CALCULATION REPORT
FOR
GRIFFIN RANCH
LA QUINTA, CA
PLAN 4820 ALT.
10o TAKEN OFF WATER SUPPLY FOR SAFETY MARGIN
CALC AREA 2
Date: 1/24/2020
File No: 31630
Data File Name: 4820 ALT.rdf
SPRINKLER SPACING
196.0 sq. ft./spklr.(max) Max. Dist. Bet. Spklrs: 14.0 ft.
Min. Dist. Bet. Spklrs: 8.0 Max. Dist. Spklr. to Wall: 7.0 ft.
SPRINKLER SPECIFICATIONS
Mfr: Senju Descr: SS8261 Pend.RC-RES(14xl4) K=3.70
Calculated K Factor for Arm-Overs & Drops:
1.0 ft. x 0.874 in. Drop: K=3.61 (Incl. 1 Tee)
0.0 ft. x 0.874 in. Arm -Over: K=3.59 (Incl. 1 Tee & 1 Ell)
PIPE SPECIFICATIONS
Type: CPVC HWC: 150
WATER SUPPLY
Source: Public Test Date: By:
Static: 74.5 psi Resid: 67.3 psi Flow:2300.0 gpm
Public Main Size: 8 in
Domestic Demand: 5.0 gpm at node number 104
SPRINKLER DEMAND
No.Spklrs. Min Spklr. Press
Flowing Flow (psi)
1 10.0 7.7
2 10.0 7.7
REVIEWING AUTHORITY
CITY OF LA QUINTA FIRE DEPT.
Node Total Avail. Req'd
No. Flow Press. Press.
22 15.0 74.5 35.4
22 25.3 74.5 51.0
DATE: 1/24/2020 S:\2017\31630\CALCS\4820-ALT.rdf Page 2
RESULTS OF
ANALYSIS
PIPE & NODE DATA
*
FLOW
ANALYSIS
* 1 sprinkler
flowing
* 2 sprinklers
flowing
FIXD
P #
END LEN
FIT.
LOSS
EL
SP *DISCH
FLOW
PF
PT *DISCH
FLOW
PF
PT
HWC
NOD DIA
EQV.LN
PUMP
(FT)
(K) *(GPM)
FL/FT
PE (PSI)*(GPM)
FL/FT
PE (PSI)
1
100
30.00
BG
----
-2.0
SRCE ----
15.0
2.34
35.4 ----
25.3
6.19
51.0
150
101
0.995
6.0
----
-2.0
---- ----
0.07
0.00
33.1 ----
0.17
0.00
44.8
2
101
1.00
-9.5
-2.0
---- ----
15.0
0.27
33.1 ----
25.3
0.71
44.8
150
102
0.745
0.0
----
-2.0
---- ----
0.27
0.00
23.3 ----
0.71
0.00
34.6
3
102
70.00
3L
----
-2.0
---- ----
15.0
1.34
23.3 ----
25.3
3.53
34.6
150
103
1.360
24.0
----
-2.0
---- ----
0.01
0.00
21.9 ----
0.04
0.00
31.1
4
103
4.00
LG
----
-2.0
-- ----
15.0
0.14
21.9 ----
25.3
0.37
31.1
150
104
1.265
3.0
•--
2.0
-5 5
0.02
1.73
20.1 5
0.05
1.73
29.0
5
104
2.00
L
----
2.0
-5 5
10.0
0.13
20.1 5
20.3
0.49
29.0
150
105
1.101
5.0
----
4.0
---- ----
0.02
0.87
19.1 ----
0.07
0.87
27.6
6
105
1.00
-3.0
4.0
---- --
10.0
0.02
19.1 ----
20.3
0.07
27.6
150
106
1.101
0.0
----
4.0
---- ----
0.02
0.00
16.1 ----
0.07
0.00
24.5
7
106
7.00
2L
----
4.0
---- ----
10.0
0.32
16.1 ----
20.3
1.19
24.5
150
10
1.101
10.0
----
11.0
---- ----
0.02
3.03
12.7 ----
0.07
3.03
20.3
8
10
7.50
LR
----
11.0
---- ----
10.0
0.73
12.7 ----
20.3
2.69
20.3
150
11
0.874
5.0
----
11.0
---- ----
0.06
0.00
12.0 ----
0.22
0.00
17.6
9
11
67.00
L7R
----
11.0
---- ----
3.9
0.78
12.0 ----
7.8
2.85
17.6
150
12
0.874
11.0
----
11.0
---- ----
0.01
0.00
11.2 ---
0.04
0.00
14.8
10
12
0.50
B
---
11.0
---- -_--
0.0
0.00
11.2 ----
0.0
0.00
14.8
150
13
0.874
3.0
----
11.0
---- ----
0.00
0.00
11.2 ----
0.00
0.00
14.8
11
12
9.50
R
----
11.0
---- ----
3.9
0.10
11.2 ----
7.8
0.38
14.8
150
14
0.874
1.0
----
11.0
---- ----
0.01
0.00
11.1 ---
0.04
0.00
14.4
12
14
2.00
L
----
11.0
---- ----
3.9
0.06
11.1 ----
7.8
0.22
14.4
150
15
0.874
4.0
----
13.0
---- ----
0.01
0.87
10.2 ----
0.04
0.87
13.3
13
15
10.00
LBR
----
13.0
---- ----
3.9
0.18
10.2 ----
7.8
0.66
13.3
150
16
0.874
8.0
----
13.0
---- ----
0.01
0.00
10.0 ----
0.04
0.00
12.6
14
16
2.00
L
----
13.0
--- ----
3.9
0.06
10.0 ----
7.8
0.22
12.6
150
17
0.874
4.0
----
11.0
---- ----
0.01
0.87
10.8 ----
0.04
0.87
13.3
15
17
17.50
LBR
----
11.0
---- ----
3.9
0.25
10.8 ----
7.8
0.93
13.3
150
18
0.874
8.0
----
11.0
---- ----
0.01
0.00
10.5 ----
0.04
0.00
12.3
16
18
2.00
L
----
11.0
---- ----
3.9
0.06
10.5 ----
7.8
0.22
12.3
150
19
0.874
4.0
----
13.0
---- ----
0.01
0.87
9.6 ----
0.04
0.87
11.3
DATE: 1/24/2020 S:\2017\31630\CALCS\4820_ALT.rdf Page 3
17
19
5.50
L ----
13.0
---- ---- 3.9
0.09
9.6 ----
7.8
0.35
11.3
150
20
0.874
4.0 ----
13.0
---- ---- 0.01
0.00
9.5 ----
0.04
0.00
10.9
18
20
17.00
4R ----
13.0
---- ---- 6.4
0.53
9.5 ----
12.8
1.93
10.9
150
21
0.874
4.0 ----
13.0
---- ---- 0.03
0.00
9.0 ----
0.09
0.00
9.0
19
21
15.00
LBR ----
13.0
---- ---- 10.0
1.34
9.0 ----
10.0
1.34
9.0
150
22
0.874
8.0 ----
13.0
3.61 10.0 0.06
0.00
7.7 10.0
0.06
0.00
7.7
20
21
5.00
B ----
13.0
---- ---- -3.6
0.07
9.0 ----
2.8
0.04
9.0
150
23
0.874
3.0 ----
13.0
---- ---- -0.01
0.00
9.1 ----
0.01
0.00
8.9
21
23
10.00
B ---
13.0
---- ---- 0.0
0.00
9.1 ----
10.3
0.80
8.9
150
24
0.874
3-0 ----
13.0
3.61 ---- 0.00
0.00
9.1 10.3
0.06
0.00
8.1
22
23
56.00
9R ----
13.0
---- ---- -3.6
0.57
9.1 ----
-7.5
2.23
8.9
150
25
0.874
9.0 ----
13.0
---- ---- -0.01
0.00
9.6 ----
-0.03
0.00
11.2
23
25
26.50
B2R ----
13.0
---- - -- -3.6
0.28
9.6 ----
-7.5
1.08
11.2
150
26
0.874
5.0 ----
13.0
---- ---- -0.01
0.00
9.9 ----
-0.03
0.00
12.3
24
26
2.00
L ----
13.0
---- ---- -3.6
0.05
9.9 - --
-7.5
0.21
12.3
150
27
0.874
4.0 ----
11.0
---- ---- -0.01
0.87
10.8 ----
-0.03
0.87
13.3
25
27
2.50
L ---
11.0
---- ---- -3.6
0.06
10.8 ----
-7.5
0.22
13.3
150
28
0.874
4.0 ----
11.0
---- ---- -0.01
0.00
10.9 ----
-0.03
0.00
13.5
26
28
17.50
2LBR ----
11.0
---- ---- 2.5
0.14
10.9 ---
5.0
0.48
13.5
150
29
0.874
12.0 ----
11.0
---- ---- 0.00
0.00
10.8 ----
0.02
0.00
13.1
27
29
2.00
L ----
11.0
--••- ---- 2.5
0.03
10.8 ----
5.0
0.10
13.1
150
30
0.874
4.0 ----
13.0
---- ---- 0.00
0.87
9.9 --•--
0.02
0.87
12.1
28
30
59.50
LB7R ----
13.0
---- ---- 2.5
0.34
9.9 ----
5.0
1.19
12.1
150
20
0.874
14.0 ----
13.0
---- ---- 0.00
0.00
9.5 ----
0.02
0.00
10.9
29
28
38.00
B5R ----
11.0
---- ---- -6.1
1.09
10.9 ----
-12.5
4.06
13.5
150
11
0.874
8.0 ----
11.0
---- ---- -0.02
0.00
12.0 ----
-0.09
0.00
17.6
Node Notes
Pipe Notes
Legend:
P -
Pipe #
LEN -
Pipe Length
DIA
- Pipe Diameter
FIT.
- Pipe Fittings
EQV.
LN - Pipe Equivalent Length
FIXD
LOSS - Fixed Loss Device
PUMP
- Pump Pressure
EL -
Node Elevation
SP -
K-Factor
DISCH
- Discharge in gpm
FLOW
- Flow Rate
FL/FT
- Friction Loss per Foot
PF -
Pressure Loss due to Friction
PE -
Pressure Loss due to Elevation
PT -
Total Pressure at Node
Fitting Code Letters:
E=45 Ell, L=90 Ell, B=TeeBch,
R=TeeRun,
C=Couplg, S=SwgChk, G=GatVly, X= X,
DATE•: 1/24/2020 S:\2017\31630\CALCS\4820_ALT.rdf Page 4
The maximum velocity of water flow occurs in pipe 2
at 11.04 ft/s with 1 sprinkler flowing.
The maximum velocity of water flow occurs in pipe 2
at 18.63 ft/s with 2 sprinklers flowing.
PIPE FITTINGS TABLE
Pipe Table Name: standard.npt
PAGE: C
MATERIAL: CPVC HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E
L B R
C
S
G
X
Y
Z
45 Ell
90 Ell TeeBch TeeRun
Couplg
SwgChk GatVly
X
Y
Z
0.874
1.00
4.00 3.00 1.00
1.00
5.00
2.00
0.00
0.00
0.00
1.101
1.00
5.00 5.00 1.00
1.00
8.00
2.00
0.00
0.00
0.00
PAGE: K
MATERIAL: Copper Tube-K
HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E
L B R
C
S
G
X
Y
Z
45 Ell
90 Ell TeeBch TeeRun Couplg
SwgChk
GatVly
X
Y
Z
0.745
0.00
1.00 3.00 1.00
1.00
0.00
0.00
0.00
0.00
0.00
0.995
1.00
2.00 6.00 2.00
2.00
6.00
0.00
0.00
0.00
0.00
PAGE: L
MATERIAL: Copper Tube-L
HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E
L B R
C
S
G
X
Y
Z
45 Ell
90 Ell TeeBch TeeRun Couplg
SwgChk
GatVly
X
Y
Z
1.265
1.00
3.00 6.00 2.00
2.00
7.00
0.00
0.00
0.00
0.00
PAGE: P
MATERIAL: PVC HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E
L B R
C
S
G
X
Y
Z
45 Ell
90 Ell TeeBch TeeRun Couplg
SwgChk
GatVly
X
Y
Z
1.360
2.00
8.00 6.00 1.00
1.00
11.00
3.00
0.00
0.00
0.00
Sprinkler system has been hydraulically calculated with the
HASS HOUSE 3.8.0 computer program (License No. 50081444)
to provide an average imbalance of 0.010 gpm at each node and
a maximum imbalance of 0.17 gpm with one sprinkler
flowing, and 0.010 gpm at each node and maximum imbalance
of 0.12 gpm with 2 sprinklers flowing in accordance
with NFPA 13 and 13D or 13R.
The minimum source pressure is 20.0 psi with a minimum required pressure
of 51.0 psi and a 7 minute flow of 177 gal. and a 10 minute flow of 253.2
The minimum pressure at any node is 7.7 psi at node 22.
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
gallons.
DATE-. 1/24/2020 S:\2017\31630\CALCS\4820_ALT.rdf
Page 5
WATER SUPPLY CURVE
7 5. 0— p, `C
67.5
P l
60.0
R
E l
S 52.5
S 1
45.0
U
R
E 37.5 C
B
30.0
P
22.5
S
I 1
15.0
}
7.5
0.0
04 8 12 16 20 24 28 32 36
FLOW (GPM)
Static = 74.5 psi, Residual = 67.3 psi @ 2300 gpm
(1 sprinkler flowing) (2 sprinklers flowing)
A = Available Water Supply C = Available Water Supply
74.5 psi @ 15.0 gpm 74.5 psi @ 25.3 gpm
B = Required Water Supply D = Required Water Supply
35.4 psi @ 15.0 gpm 51.0 psi @ 25.3 gpm
40
OFFICE USE ONLY:
REVIEW DATE:
❑ APPROVED ❑ CORRECTIONS CALIFORNIA W
CALLED FOR PICKUP: DESIGN & DEVELOPMENT DEPARTMENT
78-495 Calle Tampico
PICKED UP: La Quinta, California 92253
(760) 777-7125 / FAX (760) 777-7011
FIRE REVIEW APPLICATION
❑ SUBMITTAL # 0 REVISION #
APPLICANT/OWNER INFORMATION
�f
F E. B 1 '_' 2020
DESIGN & DEVkG UPIaiENT ULPARTMEN
FCM I2020-0002
PERMIT NO,
Applicant Name:
FIRE SPRINKLER SYSTEMS, INC
Owner Name:
LENNAR
Mailing Address:
705 E. HARRISON ST. #200, CORONA CA 92879
Site Address:
MASTER PLAN 8(4820) AS -BUILT
Phone Number:
951-272-2522
Project
PRESTIGE / TRACT# 32879 / PLAN TYPE 8(4820) / 66 HEADS
jamieb@fireinc.net
Description,
(Include # of sprinkler heads)
Email:
Pursuant to a Cooperative Agreement to Provide Fire Services,
the Riverside County
Fire Department serves as the City's fire
department, and the County designee serves as the City's fire chief. Applicant recognizes this contracted arrangement and
_shall comply with
County Fire Department directions.
CONTRACTOR INFORMATION
Contractor Name:
FIRE SPRINKLER SYSTEMS, INC.
Contractor #:
684600
Signature:
Contact Person:
JAMIE BISHIP
Mailing Address:
705 E. HARRISON ST., #200
Print Name:
A IE BI IP
City, State, Zip:
CORONA, CA 92879
Phone Number:
951-272-2522
Business License #:
762890
Email Address:
jamieb@fireinc.net
A. APPLICATION TYPE
FIRE SPRINKLER SYSTEM
STORAGE TANKS
❑ NEW COMMERCIAL/INDUSTRIAL
_ _________
❑ DISPENSERS ONLY
HOURLY@161/HR
❑ 0-35,000 SQ FT
$670
❑ ABOVE GROUND
HOURLY@161/HR
❑ 35,001-75,000 SQ FT
$791
SUPRESSION SYSTEM
❑ 75,001-120,000 SQ FT
$992
❑ HOOD & DUCT
$418
❑ 120,001 AND UP
$1234
❑ OTHER SUPRESSION SYSTEM
HOURLY@161/HR
❑ TENANT IMPROVEMENTS - FIRE SPRINKLER
$418
MASTER PLAN
O RESIDENTIAL SPRINKLER SYSTEMS
---------
❑ MASTER PLAN HOURLY@161/HR
❑ 1-50 SPRINKLER HEADS
$418
MISC
❑ 51-100 SPRINKLER HEADS
$498
❑ PYRO
$740
❑ OVER 100 SPRINKLER HEADS
$579
❑ HAZMAT
HOURLY@161/HR
❑ RESIDENTIAL TRACT HOME (EA.) ADDITIONAL
------------
❑ HIGH PILE RACK STORAGE
HOURLY@161/HR
❑ 1-50 SPRINKLER HEADS
$176
❑ PRIVATE FIRE MAINS
$901
❑ 51-100 SPRINKLER HEADS
$257
❑ TECHNICAL REPORT RESEARCH
HOURLY@161/HR
❑ OVER 100 SPRINKLER HEADS
$337
❑ FIRE PUMPS
$659
❑ MULTI -FAMILY (3 OR MORE)
$590
❑ STANDPIPE SYSTEMS
$579
FIRE ALARM SYSTEM
❑ WATER TANKS
$418
❑ COMMERCIAL - SPRINKLER MONITORING
$418
❑ REVISION
$161
❑ COMMERCIAL - FIRE ALARM SYSTEM
1 $1062
❑ OTHER
HOURLY@161/HR
Each application type includes a I echnology Enhancement Fee of SS b Recoras Management Fee of 51u or yZ1 REVISEu 1Z/b/ZU19
*For permits billed at an hourly rate, these fees will be added at time of payment.