FCMP2021-0009 Carmela Plan 2a u�tt
Project Details PROJECT NUMBER
` =�w City of La Qu i nta FCM P2021-0009
MoFT�• .
Description: CARMELA / FIRE SPRINKLER MASTER / PLAN TYPE 2
Status: APPROVED
Type: FIRE CONSTRUCTION MASTER PLAN (WEB)
Status Date: 4/13/2021
Subtype: FIRE SPRINKLER MASTER PLAN
Applied: 1/21/2021
Address: 81853 ALEGRE
Approved: 2/2/2021
City, State, Zip: LA QUINTA,CA92253
Closed:
Project Manager:
Expired:
Details:
ADDITIONAL SITES
CHRONOL
DAYS
REVIEWS
ACTIONS
INSPECTIONS
CONDITIONS
NAME TYPE
NAME
ADDRESSI
CITY
STATE
ZIP
PHONE
FAX
EMAIL
APPLICANT
FIRE SPRINKLER SYSTEMS INC
705 E HARRISON ST STE
CORONA
CA
92879
(951)272-2522
jamieb@fireinc.net
200
CONTRACTOR
FIRE SPRINKLER SYSTEMS INC
705 E HARRISON ST STE
CORONA
CA
92879
(951)272-2522
jamieb@fireinc.net
200
OWNER
VILLAGE SACRAMENTO INV
940 EMMETT AVE STE
BELMONT
CA
92253
(951)272-2522
jamieb@fireinc.net
200
CLTD
DESCRIPTION
ACCOUNT
CITY
AMOUNT
PAID
PAID DATE
RECEIPT #
CHECK #
METHOD
PAID BY
BY
FIRE STAFF - PER HOUR
101-0000-42420
1
$161.00
$161.00
3/14/21
WEB7628
094036
CREDIT
FIRE SPRINKLER
ECON
SYSTEMS INC
Printed: Friday, March 03, 2023 2:41:23 PM 1 of 3 CENTRALSOLIARE
a u�tt
Project Details PROJECT NUMBER
` =�w City of La Qu i nta FCM P2021-0009
MoFT�•
CLTD
DESCRIPTION
ACCOUNT
CITY
AMOUNT
PAID
PAID DATE
RECEIPT #
CHECK #
METHOD
PAID BY
BY
FIRE STAFF - PER HOUR
101-0000-42420
0.5
$80.50
$80.50
4/21/21
WEB7995
063517
CREDIT
FIRE SPRINKLER
ECON
SYSTEMS INC
Total Paid for FIRE FEES: $241.50 $241.50
RECORDS
MANAGEMENT FEE -
101-0000-42416
0
$21.00
$21.00
3/14/21
WEB7628
094036
CREDIT
FIRE SPRINKLER
ECON
SYSTEMS INC
MAJOR
Total Paid for RECORDS MANAGEMENT FEE - MAJOR: $21.00 $21.00
TECHNOLOGY
502-0000-43611
0
$5.00
$5.00
3/14/21
WEB7628
094036
CREDIT
FIRE SPRINKLER
ECON
ENHANCEMENT FEE
SYSTEMS INC
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
INSPECTION TYPE INSPECTOR SCHEDULED COMPLETED RESULT REMARKS NOTES
DATE DATE
RETURNED
REVIEW TYPE
REVIEWER
SENT DATE
DUE DATE
STATUS
REMARKS
NOTES
DATE
1ST FIRE (1WK)
KOHL
4/13/2021
4/20/2021
4/20/2021
APPROVED
REVISION 1
HETRICK
1ST FIRE (2WK)
KOHL
1/21/2021
2/4/2021
2/2/2021
APPROVED
SEE ATTACHMENTS
HETRICK
1ST PERMIT
ARMANDO
1/21/2021
1/22/2021
2/12/2021
COMPLETE
TECHNICIAN (1DAY)
MAGALLON
Attachment Type
CREATED
OWNER DESCRIPTION PATHNAME
SUBDIR
ETRAKIT ENABLED
DOC
1/21/2021
EtrakitContractor Application Application.pdf
1
Printed: Friday, March 03, 2023 2:41:23 PM 2 of 3 CENTRALSOLIARE
a u�tt
Project Details PROJECT NUMBER
` =�w City of La Qu i nta FCM P2021-0009
MoFT�• r
Attachment Type
CREATED
OWNER
DESCRIPTION
PATHNAME
SUBDIR
ETRAKIT ENABLED
DOC
1/21/2021
EtrakitContractor
Tracking Sheet
Building Tracking
1
Sheet.pdf
DOC
1/21/2021
EtrakitContractor
Fire Flow
Fire Flow Analysis.pdf
1
DOC
1/21/2021
EtrakitContractor
Fire Plan
Master Plan Type
1
2.2679. pdf
DOC
1/21/2021
EtrakitContractor
Hydraulic Calculations
Plan 2.2679 Hydraulic
1
Calculations.pdf
DOC
4/13/2021
KAYLI ALFORD
Revision 1
Revision 1
0
Application.pdf
Application.pdf
DOC
4/13/2021
KAYLI ALFORD
Revised Fire Flow
Revised Fire Flow
0
Analysis.pdf
Analysis.pdf
DOC
4/13/2021
KAYLI ALFORD
Revised Plan 2.2679
Revised Plan 2.2679
0
Calcs.pdf
Calcs.pdf
DOC
4/13/2021
KAYLI ALFORD
Revised Plan
Revised Plan
0
2.2679_1.pdf
2.2679_1.pdf
DOC
2/2/2021
KOHL HETRICK
FCMP2021-0009 -
Master Plan Type
1
APPROVED PLAN
2.2679_1.pdf
DOC
2/2/2021
KOHL HETRICK
FCMP2021-0009 - COA
FCMP2021-0009 - COA
1
LETTER.pdf
LETTER.pdf
FCMP2021-0009 -
FCMP2021-0009 -
DOC
4/20/2021
KOHL HETRICK
APPROVED PLANS -
APPROVED PLANS -
1
REVISION 1.pdf
REVISION 1.pdf
Printed: Friday, March 03, 2023 2:41:23 PM 3 of 3 CENTRALSQUARE
V Ra ■mow FREEDOM RESIDENTIAL
SENJU SPRINKLER CO., LTD. ,�.�((VV,,,,��<,�V.•.• coxceaLeD VFxDENr
�: bPRINKLER VNM94IKY.9I
Residential Lead Free Flat Concealed Sprinkler, - Th.
Pendent r.Nvnop.: a.sas.asot rm la N..: e"]ero' d°nfi°�nm�, e. ao .�sw.kmvc.m.wm
an oa.., x,sn"g. Nl4e
.: xaate-1Rep Em,n: nc
Motlel: RC-RES. K-Factor: 3.7. SIN: 558261
GENERAL DESCRIPTION g
."reM* nrorp a ipnn emee n meryrNvnM`"� N
earou�n°"A....... non�lo;�unlmm.
TE-1 BORE. N a RI,d rnYa.pllY enwenM.t.M bp.Ma ro,.,.m nem.s. I.a;7a;,ro "� mow 0n°
RRIANr rI.— x
ro amlN Dwaime u
per aynemt ro�Reslamel °pcuw a up 1p meneupnp
w;;railamstwlM,.apamm�Pmlonsme,ryawuwMln PorNam u. rmnnawa,'ma�>uw "sm'�vw�'m;.ure m. w"�sl"apes.`"`
]A(e dLPe4De0'1sK fedw lM1Y mesn lM1e ragtl�eeseslaemNl nox Inns rmm mlmmtlrnlouel t. LISTNGSANDAPPRONALS
pM ra
ene cnatxs 1 wmcel m'unmaM. Thb edNummeM Iron
IPo�Tnsxr axes Ins naetlMpronrodunngp lne plpelnYarpptrom tpnnperem stows Poanmw eanp
ndl pm spnnpar sysiams ara nM a swmMs rwnre serexy ern iixlen _HM tprwy
ea, Aaa.'aey °piinsei°:�'nla;mei e n:DTkhg %r»: . N)—d-.di, i—.r=a"piase.
;a9J.nsakron
pwD.eaanpp rorpwamme,pa.Po,.a,L
srm.rm..ae-k...
m,mw,9 mw.am, m vTeaxae , a.vr .r ave emwm„m,r ro m. ewmw ,, mw
wxnp rv,..wp.rro vLm�;e..,.vr.rtnn a.w.m.mm, a,e,..w,w.mm.R
�,`Mw,w mw m. vrolewn,„rY.m,aa a..k.e x. vmv,r=vmnaw aepaae,L rM
TECHNICAL DATA
epmk MseanmmmNumnN (aM 9Nexet
m we,ppn nrvwnx.,saq
DAR,—
- gvMlPorR n,.n LVMnw (
:os•p nee, avr,wlwwN„Nx•v nrm Dp
.—I
Adj..-
utl.- amen(1 —1
wn�w i ory e.iy. nrem ei..x xmxY
'I`c:'Onmed.aY et.RY vm.re,,.a„YSM Y
}� sy
DrcouDut, uaYrRexes lo-aa
35ww�1.
OPERATION
ee"nm.d>p a. e1.r.d r,..,.e. R. s x`°p"•"no,n•°�ou�ranexp.°°nc'w'it°1:ss �e 1°I»pws:r newmee
.m M)
Im,
F
IANS
�p °
^a
Rw
DPb
pPxq
mwm
ryr)
mA
ILPxq
Bwm�
Id"n0.n
Caul
11
O.,
ro
I. I,
71
Lo AS
�
N,Imnn.
n
I4_
I_
IaTS,
IS AS
RPS
I-1,
sae,
I..,
Pm
1..
IS1,
Iaw4S1
I4 a)
I4s.z)
I. S
(493)
IS ES,
(n) Rw N4M Mn xMPM ILPu kp rod. M1 wees m use tnn minimum ak'u wenurta urine
ukwetawreurt npmlrelXFaaps Raro�m Xromu Dnp cmprb secMnroreem�n.
'Ye ma.xemm�twtmmee a°MaeaGtebmre GVt.VsfV VsW
VlklnproVK090 <.9 KFecrgraR,rkentlel CormaNkY PanYanL9pdnkler
..n°pYe`wwb.`
tm..c�w+.Po
12XII
M
�'
roi4x,4
N.a%wI
NOD
Iw�l
Mw
ro4a,
•
rarTVa
0A)
HaF1n
—E.
HAS
11
ER"
1,
row'
HYDRAULIC SYSTEM
This Nbmg is P.RRSEd by a
Hydraulically Designed
A.tOeJc Spnnlder System.
Dale Installed VIiT
Location CALC AREA
Number of Sprinldem 2
Basis of D.Eq
ow m .05 gpmh' qfL
] DENGHFD ARFAOF DMMARci
392 sg.ft.
System Demand 0
1. 4NATEA FL"RATE 25.D
2. 1HIWAL PRESSURE AT TH m
RASE OF THE RISER 25.5 si
MD16d By FlNSpnnkkr SyMEme, Inc.
HYDRAULIC NAMEPLATE
N.T.S.
13D GENERAL NOTES
>3A I xq`
7
waRR- DAvb IN ADVANCE OE THE
EMASTE
uL Ls)eD cP1.NAVEn PeaMarvENrLV AP xeD SON No unR 4�-
Ire EUNcr aN srt
1.
11. ISEL �uIRE11v SENJU. INSTALLED AT 14 ET. M-11M ePADNO
(SEE TETH. 12 (e ETECNo ATLEASTURE01 VIMNG IESTALLED AT t4 R. MAIL SPACING
La ce Quinta Offiof the Flre Marshal
BY: Kohl Hetdck TL -
FIRE SAFETY SPECIALIST
O4/20=21 2 33 32 M
Theapproval d plansbnd spS.M ad. -pot
permit -vbhfwp, delatmp, o—im or fa.Ey
Installation of any requirements of title 24 or any
#FCMP2021-0009 REV
APPROVAL STAMP
'FOR REFERENCE ONLY
PRESSURE
O9ES TO OM STIC
1
WATER
CONTROL VALVE FOR DOMESTIC
CSGPM ALLWVANCE
J.H.-DE
DELEViTER
� PSI LOSS
O4
OR
-wix 3aELEV. ED xAx -z ELEV.
UNDERGROUND DETAIL
N.T.S. (FOR REFERENCE ONLY)
THE ESTATES fa CARMEIA
.1-112
MAbTEAN 2. 11
PN SLIBMINTAT
LAQUIMA, CA.
AND. LA QUINTA FIRE DEPARTMENT
LEGAL DESCRIPTION
BUILDING SUMMARY
CO PIN bPRIM4ER
® WNCEALEDREs. PENDENT SPRINKLER
Qi RES. PENDENT SPRINKLER
O CHANGE IN D.EVATION
® RISER —ON (PER DETAIL)
® NODE POINT FOR CALCQIATION
/ RANGER TIC DETAIL
SYMBOLLEGEND
cow T.—Tw— 10 ,d ELIV
SPAAE SPANRLERSSINLL
NOi BE AEWNEDTO
PAWIAED PEA 5.1.1.2 cmz aneR
W.®-
®m
A�anooR� _
R.eeen— AVE fi -
ssr1. 1...T.... ATM—' OLW.
RISER DETAIL
N.T.S.
JOB NO: 320M
DATE: 111=1
DE— BV: C.P.
Table R • One Point of Restraint
p�R R ($
MAX.3 I iV1AX.t
One -Point
vertical
Restraint
RESTRAINT RESTRAINT
ONE -POINT ONE-POiNT
Nominal
-Ii'TS3
li r131
Pipe Size
Less than
Greater than
ANTS[ Inches
100 psi
iflfl psi
QN
(6,9 bar)
(6,9 bar)
3f4
0'-9"
0'-6"
DN20
(0,23 m)
(D,iS m)
QN25
(0,30 rri)
(0,23 m)
1-1f4
1'-4"
1'-D"
C3N32
(0,41 m)
(0.30 m)
1-1/2-3
2'-D"
1'-0"
DN40 - DNso
(o,si m)
(D,so rr,)
Table S • Two Points of Restraint
Nominal Pipe
"S"
"S>,
Size
Lass than
Greater than
ANSI Inches
140 psi
iQD psi
QN
(6,9 bar)
(6,9 bar)
3f4
4'-0"
3'-0"
DN20
(1,22 m)
(0,91 rtt)
1
5'-0"
4'-0"
[]N25
(1,52 m)
(1,22 m)
1-1/4
6'-D"
5'-0"
QN32
(1;$3 m)
{1,52 m}
1-11f2 - 3
7'-0"
T-D"
DN40 - DN80
(2,13 rrt)
(2,13 m).
S
Two -Point ANY DISTANCE �---- Vertical
Restraint
RES7RA#NT
T
W
O
-P
O
I
NT
January 2005
Garage Installation Snecificattons
Garage installation Specifications shall only apply for the installation of UL Listed
BlazeMaster CPVC pipe and fittings in garages requiring sprinkler protection per NFPA
13D and NFPA 13R. These Standards are defined in NFPA codes entitled 'One and Two
Family Dwellings and Mobile Homes' and in 'Residential Occupancies up to Four Stories
in Height'. As referenced in NFPA 13D Section 8.6.4,'Sprinklers are not required in garages,
open attached porches, carports or similar structures." The installation of TFP BlazeMaster
sprinkler pipe and fittings for use in garages requiring sprinkler protection per NFPA 13R
is only applicable to the UL listing of this product.
Requirements for Pipe, Fittings, Solvent Cement Systems, System Design, Installation,
Freeze Protection, and Penetrating Fire Related Walls and Partitions are covered in this
installation and technical handbook. Please read these sections of the manual carefully
prior to designing or installing TFP BlazeMaster pipe and fittings for garage installations.
The Installation of TFP BlazeMaster pipe and fittings in garages requiring sprinklers
Is only UL Listed and is not C-UL Listed.
•Installation Requirements
-Protection: TFP BlazeMaster CPVC pipe and fittings shall be installed concealed
behind protection consisting of a minimum of one layer of thick gypsum
wallboard or 1/2* thick plywood.
-Sprinkler Requirements: UL Listed, quick response, standard coverage, pendent
or sidewall sprinklers with a 225°F (107°C) maximum temperature rating shall be
utilized. All sprinklers shall be installed per the manufacturer's published
installation instructions.
-Installation Standard: The Listing for Garage Installations shall pertain to those
occupancies defined by NFPA 13R.
System Risers
In accordance with the UL listing, TFP BlazeMaster CPVC pipe and fittings may be used
as system risers in accordance with NFPA 13,13Dand 13R when subject to the following
additional limitations:
1. When installed protected (concealed) in accordance with NFPA 13D and 13R, the
minimum protection shall consist of either one layer of s/s' (9.5 mm) thick gypsum
wallboard or 1/2' (12.7 mm)thick plywood.
2. When installed without protection (exposed) in accordance with NFPA 13, 13D
and 13R, the following limitations shall apply:
- The riser shalt be installed below a smooth, flat, horizontal ceiling construction. A
Listed residential pendent sprinkler is to be installed with its deflector at the
distance from the ceiling specified in the sprinkler Listing.
OR
The riser shall be installed below a horizontal unfinished basement ceiling (in
accordance with NFPA 130) constructed utilizing nominal 2" x 10" or nominal 2' x
12"exposed solid wood joists on 16' centers. A Listed residential pendent
sprinkler is to be installed with its deflector a maximum of 13/; below the bottom
of the solid wood joist in anticipation of future installation of a finished ceiling.
When installing TFP BlazeMaster CPVC pipe and fittings in conjunction with 2' x 12'
solid wood joists, the maximum system working pressure under flooding conditions
shall not exceed 100 psi and the maximum system working pressure under static
(nonflotving) conditions shall not exceed 175 psi.
The Listed residential pendent sprinkler is to have 155°F (68°C) maximum
temperature rating and is to be installed at a maximum horizontal distance of 12
inches from the center fine of the riser. The system is to be designed based upon the
VA
Listed flows for the sprinkler selected except that the flow for a single sprinkler or
multiple sprinklers shall not be less than 11 gpm per sprinkler.
PLAN 2.2679 -FIRE SPRINKLER FLOOR PLAN
SIZE -SYSTEM PIPE: 3/4" thru 3"
MATERIAL -CARBON STEEL.
FINISH -Mil. Galvanized.
LISTING/APPROVAL -
` 203-EX 4231, EX 2551
FUNCTION -Support horizontal piping: CPVC, Copper or Steel.
Size 3/4" - 2" Prevents upward movement of pipe from pendent sprinkler discharge.
Stabilize vertical piping.
INSTALLATION -Per these instructions
including NFPA 13, 13R, 13D and CPVC manufacturers instructions.
install on horizontal or vertical mounting surface.
FASTENERS - UL Listed per NFPA 13
in WOOD:
3/4" - 3" CPVC PIPE - #905 screw - no pre -drill.
3/4" - 3" Steel and Copper pipe - #14 x 1 1/2" SMS or
1/4"x1 1/2" lag bolt - no pre -drill.
in STEEL: min. 18 GA.
3/4" - 3" CPVC, Copper and Steel pipe - 1/4" or #14 Tek Screw.
FEATURES
" Offset edge eliminates abrasion. Hang
* Retainer dimples secure hanger to pipe durin� installation.
* Required AFCON #905 screw included - 5/16 hex head.
ORDERING -Part #and pipe size.
CAN ALSO BE USED TO REPLACE - #500 Pipe Strap
#520 Tin Strap
510 FAST.
SIZE DIM.
3/4 2.126
1 2.312
1 1/4 3.170
1 1 /2 3.400
2 1/2 4.320
3 5.320
11
IPA
Restraint
Nominal Pipe Size (in.)
'/<"
1 "
1'/<"
1'/:"
2„
2,/:"
3„
3,/z ,
4"
5"
6"
8„
Steel pipe except threaded
N/A
12'-0"
12'-0"
15'-0"
15'-0"
15'-0"
15'-0"
15'-0"
15'-0"
15'-0"
15'-0"
15'-0"
lightwall
Threaded lightwall steel
N/A
12'-0"
12'-0"
12'-0"
12'-0"
12'-0"
12'-0"
N/A
N/A
N/A
N/A
N/A
pipe
Copper tube
8'-0"
8'-0"
10'-0"
10'-0"
12'-0"
12'-0"
12'-0"
15'-0"
15'-0"
15'-0"
15'-0"
15'-0"
CPVC
5'-6"
6'-0"
6-6"
T-0"
8'-0"
9'-0"
10'-0"
N/A
N/A
N/A
N/A
N/A
Polybutylene (IPS)
N/A
3'-9"
4'-7"
5'-0"
5'-11"
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Polybutylene (CTS)
2'-11"
3'-4"
3'-11"
4'-5"
5'-5"
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Ductile iron pipe
N/A
N/A
N/A
N/A
N/A
15'-0"
N/A
N/A
15'-0"
N/A
15'-0"
15'-0"
AFCON 5 10 HANGER (STEEL -COPPER - C. P. V.C.
NOT TO SCALE
"vf yi3�M44 vK3
i ,
SIZE -SYSTEM PIPE: 3/4" thru 2"
`
MATERIAL -Carbon Steel.
FINISH -Mil. Glavanized.
LISTING/APPROVAL -
`
203-EX 4231, EX 2551
PATENT - No. 6,648,278.
FUNCTION -Support horizontal piping: CPVC, Copper or Steel.
Provides listed vertical/horizontal restraint and prevents
upward movement of pipe from pendent sprinkler discharge.
Stabilize vertical piping.
INSTALLATION -Per these instructions
including NFPA 13, 13R, 13D and CPVC manufacturers instructions.
Install on horizontal or vertical mounting surface.
Snap over pipe then squeeze strap back allowing pipe to slide freely.
When #905 threads are exposed in wood, install #906 backing nut.
FASTENERS - UL Listed per NFPA 13
WOOD -CPVC pipe - #905 screw- no pre -drill.
Copper and Steel pipe - #14 SMS or 1/4 "x1 1/2" lag screw - no pre -drill.
Thru 5/8" gypsum board - 1/4"x 2" lag screw.
STEEL -min. 18 GA. -CPVC, Copper and Steil pipe - 1/4" or #14 Tek Screw.
CONCRETE: Required minimum load each fasterner = 5(wt)+2501bs.
2
FEATURES
` 1 1/2" Offset -loose fit allows pipe to slide.
` Common center -line for 3/4" and 1 ".
` Offset edge eliminates abrasion.
` AFCON #905 screw included - 5/16" hex head.
ORDERING -Part #and pipe size.
AFCON #906 backing nut sold serparately.
4
Rests
r,
II
#906
,
�1
1.50 3.00
i
0
Hanger/Restrainer
Nominal Pipe Size (in.)
,�„
1"
1'/<"
1'/z,
2„
2,�„
3"
3,/z,
4"
5„
6„
8„
Steel pipe except threaded
N/A
12'-0"
12'-0"
15'-0"
15'-0"
15'-0"
15'-0"
15'-0"
15'-0"
15'-0"
15'-0"
15-0"
lightwall
Threaded lightwall steel
N/A
12'-0"
12'-0"
12'-0"
12'-0"
12'-0"
12'-0"
N/A
N/A
N/A
N/A
N/A
pipe
Copper tube
8'-0"
8'-0"
10'-0"
10'-0"
12'-0"
12'-0"
12'-0"
15'-0"
15'-0"
15'-0"
15'-0"
15'-0"
CPVC
5'-6"
6'-0"
6-6"
T-0"
8'-0"
9'-0"
10'-0"
N/A
N/A
N/A
N/A
N/A
Polybutylene (IPS)
N/A
3'-9"
4'-7"
5'-0"
5'-11"
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Polybutylene (CTS)
2'-11"
3'-4"
3'-11"
4'-5"
5'-5"
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Ductile iron pipe
N/A
N/A
N/A
N/A
N/A
15'-0"
N/A
N/A
15'-0"
N/A
15'-0"
15'-0"
AFCON 514 HANGER (STEEL -COPPER - C. P. V.C. )
NOT TO SCALE
z
O
w
,bilize W
FIRi SFNIINIaiR
SYSTEMS INC.
•
LICENSE N0.684600
•
CUSTOM, TRACT, MULTI -FAMILY
AND COMMERCIAL
•
DESIGN, X.X.INEERING AND
INSTALLATION
•
705 E. HARRISON ST., SUITE 200
CORONA, CA 92879
PH - 800-915-3473
FAX - 951-272-2535
•
The recipient of these plans
hereby acknowledges that all
plans, details, specifications or
methods of installation
contained in this set of plans is
the sole property of Fire
Sprinkler Systems, Inc. and
that any use of this set of plans
is prohibited and is a violation
of copyright laws without first
receiving permission from Fire
Sorinkler Svstems.
)
ilize
TOTAL LIVING AREA - 2,679 SQ. FT.
GARAGE AREA- 601 SQ. FT.
DESIGN AND INSTALLATION SHALL
CONFORM TO NFPA 13D, 2016 ED.
NOTES:
1. ALL HEAD SPACING TO BE 14'x14', UNLESS OTHERWISE
NOTED.
2. ALL PIPES TO BE'/4' CPVC, UNLESS OTHERWISE NOTED.
3. PIPE CLEARANCES MUST BE IN ACCORDANCE WITH NFPA
13-9.3.4.
4. HANGERS SHOWN FOR REFERENCE PURPOSES ONLY.
HANGER SPACING TO BE PER TABLES ON THIS SHEET.
5. ALL PIPING INSTALLED WITHIN THE ATTIC SHALL BE
PROVIDED WITH MIN. 6" INSULATION ON THE ATTIC SIDE OF
THE PIPING TO AVOID EXPOSURE OF THE PIPING TO
TEMPERATURES IN EXCESS OF THE PIPES RATED
TEMPERATURE (2016 NFPA 13D 7.7).
6. SPRINKLERS SHALL NOT BE REQUIRED IN BATHROOMS OF
55sgft. AND LESS. (SECTION 8.3.2.)
7. SPRINKLERS SHALL NOT BE REQUIRED IN CLOTHES
RISER CLOSETS, LINEN CLOSETS, AND PANTRIES THAT MEET ALL
LOCATION OF THE FOLLOWING REQUIREMENTS:
(1) THE AREA OF THE SPACE DOES NOT EXCEED 24sgft.
(2) THE WALLS AND CEILINGS ARE SURFACED WITH
NONCOMBUSTIBLE OR LIMITED -COMBUSTIBLE
MATERIALS AS DEFINED IN NFPA 220.
8. 8.2.5.1.2 THE DISTANCE SHALL BE MEASURED FROM THE
CENTER OF THE SPRINKLER TO THE CENTER OF THE
OBSTRUCTION.
9. 8.2.5.6 SHADOW AREAS SHALL BE PERMITTED IN THE
PROTECTION AREA OF A SPRINKLER AS LONG AS THE
CUMULATIVE DRY AREA DO NOT EXCEED 15sgft (1.4 sqm)
PER SPRINKLER.
/Y1LU
100
-
04
0
ZQ
N
Cfl
M
co
*k
0
Q
J
Q
CV �
m
U
� rn
U z
N COQ
�
CV Z
M�
�
~��
0
LU
Z J
? m
Q
0of -W
C)
a
J
W
� c~n
JOB NO: 32046
DATE: 1 /13/21
DRAWN BY: C.P.
�CT ION
QCO,y�
� CLASSIFICATION
C-16
* LICENSE N0.
684600
J�gTF OF C A` \Q
SIZE - 24" X 36"
SCALE
114" =1'
I IF SHEET IS LESS THAN
24" X 36" IT IS A REDUCED
PRINT SCALE
REDUCE ACCORDINGLY
SHEET ID
FIRE SPRINKLER PLAN
SHEET FP2 OF FP4
OPT. PLAN 2X.2679 CASITA
+1 HEAD / IN LIEU OF: COURTYARD
SCALE: 1 /4" = V-0"
Z
O
U)
w
vow
WFSS
FIRE SPRINKLER
SYSTEMS INC.
•
LICENSE NO.684600
•
CUSTOM, TRACT, MULTI -FAMILY
AND COMMERCIAL
•
DESIGN, ENGINEERING AND
INSTALLATION
•
705 E. HARRISON ST., SUITE 200
CORONA, CA 92879
PH - 800-915-3473
FAX - 951-272-2535
•
The recipient of these plans
hereby acknowledges that all
plans, details, specifications or
methods of installation
contained in this set of plans is
the sole property of Fire
Sprinkler Systems, Inc. and
that any use of this set of plans
is prohibited and is a violation
of copyright laws without first
receiving permission from Fire
Sprinkler Svstems.
MCI;
LOCATION
Q
J
Q
CV
00
m
U
rn U Z
� co O
i-
N CO Q00
N Z ~
0
W
Z J? m
Q
0-W
Q J
H U)
LQ
JOB NO: 32046
DATE: 1 /13/21
DRAWN BY: C.P.
�OT ION
CLASSIFICATION
C-16
* LICENSE NO.
684600
J�gTF OF C A` \�O���Q
SIZE - 24" X 36"
SCALE
1 /4" =1'
IF SHEET IS LESS THAN
24" X 36" IT IS A REDUCED
PRINT SCALE
REDUCE ACCORDINGLY
SHEET ID
OPTIONS
SHEET FP3 OF FP4
A
12
3.5 l i
RADIANT
14 \ FD5
D5
R:30
12
13.5
0
GARAGE STORAGE
G
R:13-
4" DIA. G.I. DRYER VENT TO
O.S.A. (MAX. 14'-0") INSTALL
WITH APPROVED LINT TRAP
AND BAC"--nnn"n—
DRYER VENT ROUTE
GREAT ROOM
SECTIONS - 'A' SPANISH
R:13
CALIFORNIA ROOM
IK&
C
SECTIONS - @ PRE -PLOT CASITA - 'A' SPANISH
r
r
Z
O
w
Of
rw W____
_�(, FSSj
FIRi SPRINKLiR
SYSTEMS INC.
•
LICENSE NO.684600
•
CUSTOM, TRACT, MULTI -FAMILY
AND COMMERCIAL
•
DESIGN, X.X.INEERING AND
INSTALLATION
•
705 E. HARRISON ST., SUITE 200
CORONA, CA 92879
PH - 800-915-3473
FAX - 951-272-2535
•
The recipient of these plans
hereby acknowledges that all
plans, details, specifications or
methods of installation
contained in this set of plans is
the sole property of Fire
Sprinkler Systems, Inc. and
that any use of this set of plans
is prohibited and is a violation
of copyright laws without first
receiving permission from Fire
Sprinkler Svstems.
J
Z
0
LU
U
Z
LU
ry
LU
LL
LU
ry
ry
0
LL
V )
Z
0
U
LU
Cn
Q
J
Q
C
N
m
U
rn
�CID :::)
U z
o
c14 a)
z
Q
Z
C V
0, z
co
U
Q �
Q
Q 0- �
< C1
< W
U)
W
:Ei
II-E
JOB NO: 32046
DATE: 1 /13/21
DRAWN BY: C.P.
�,GT ION CO T
ti
CLASSIFICATION 9�
C-16
* LICENSE NO.
684600
J�9TF OF C A` \�o���Q
SIZE - 24" X 36" I
SCALE
1 /4" =1'
IF SHEET IS LESS THAN
24" X 36" IT IS A REDUCED
PRINT SCALE
REDUCE ACCORDINGLY
SHEET ID
SECTIONS
SHEET FP4 OF FP4
FIRE SPRINKLER SYSTEMS, INC.
705 E. HARRISON ST. SUITE 200
CORONA, CA.
RESIDENTIAL SPRINKLER SYSTEM
HYDRAULICS CALCULATION REPORT
FOR
THE ESTATES @ CARMELA
LA QUINTA, CA.
TRACT #31874-1 & 2 *PLAN 2
*10% TAKEN OFF WATER SUPPLY FOR SAFETY MARGIN
CALC AREA 1
Date: 4/6/2021
File No: 32046
Data File Name: PLAN 2.rdf
SPRINKLER SPACING
196.0 sq. ft./spklr.(max) Max. Dist. Bet. Spklrs:
14.0 ft.
Min. Dist. Bet. Spklrs: 8.0 Max. Dist. Spklr. to Wall:
7.0 ft.
SPRINKLER SPECIFICATIONS
Mfr: Senju Descr: SS8261 Pend.RC-RES(14xl4) K=3.70
Calculated K Factor for Arm-Overs & Drops:
1.0 ft. x 0.874 in. Drop: K=3.61 (Incl. 1 Tee)
0.0 ft. x 0.874 in. Arm -Over: K=3.59 (Incl. 1 Tee
& 1 Ell)
PIPE SPECIFICATIONS
Type: CPVC HWC: 150
WATER SUPPLY
Source: Public Test Date: By:
Static: 67.2 psi Resid: 64.1 psi Flow: 920.0 gpm
Public Main Size: 8 in
Domestic Demand: 5.0 gpm at node number 5
SPRINKLER DEMAND
No.Spklrs. Min Spklr. Press. Node Total Avail.
Req'd
Flowing Flow (psi) No. Flow Press.
Press.
1 10.0 7.7 16 15.0 67.2
31.6
2 10.0 7.7 16 25.0 67.2
47.8
REVIEWING AUTHORITY
LA QUINTA FIRE DEPARTMENT
RESULTS OF ANALYSIS
PIPE &
NODE DATA
*
FLOW ANALYSIS
* 1 sprinkler
flowing *
2 sprinklers
flowing
FIXD
P #
END LEN
FIT.
LOSS
EL
SP *DISCH
FLOW
PF
PT *DISCH
FLOW
PF
PT
HWC
NOD DIA
EQV.LN
PUMP
(FT)
(K) *(GPM)
FL/FT
PE
(PSI)*(GPM)
FL/FT
PE
(PSI)
------------------------------------
---------------------
---------------------
1
1
60.00
BG ----
-2.0
SRCE ----
15.0
4.30
31.6
----
25.0
11.09
47.8
150
2
0.995
6.0 ----
-2.0
---- ----
0.07
0.00
27.3
----
0.17
0.00
36.7
2
2
1.00
-7.0
-2.0
---- ----
15.0
0.27
27.3
----
25.0
0.69
36.7
150
3
0.745
0.0 ----
-2.0
---- ----
0.27
0.00
20.0
----
0.69
0.00
29.1
3
3
70.00
3L ----
-2.0
---- ----
15.0
0.65
20.0
----
25.0
1.66
29.1
150
4
1.590
27.0 ----
-2.0
---- ----
0.01
0.00
19.4
----
0.02
0.00
27.4
4
4
4.00
L ----
-2.0
---- ----
15.0
0.07
19.4
----
25.0
0.18
27.4
150
5
1.505
4.0 ----
2.0
-5 5
0.01
1.73
17.6
5
0.02
1.73
25.5
5
5
2.00
R ----
2.0
-5 5
10.0
0.06
17.6
5
20.0
0.20
25.5
150
6
1.101
1.0 ----
4.0
---- ----
0.02
0.87
16.6
----
0.07
0.87
24.4
6
6
1.00
-2.5
4.0
---- ----
10.0
0.02
16.6
----
20.0
0.07
24.4
150
7
1.101
0.0 ----
4.0
---- ----
0.02
0.00
14.1
----
0.07
0.00
21.8
7
7
6.00
2R ----
4.0
---- ----
10.0
0.15
14.1
----
20.0
0.54
21.8
150
10
1.101
2.0 ----
10.0
---- ----
0.02
2.60
11.4
----
0.07
2.60
18.7
8
10
9.00
L ----
10.0
---- ----
10.0
0.76
11.4
----
20.0
2.72
18.7
150
11
0.874
4.0 ----
10.0
---- ----
0.06
0.00
10.6
----
0.21
0.00
16.0
9
11
59.50
LB6R ----
10.0
---- ----
5.6
1.43
10.6
----
11.1
5.09
16.0
150
12
0.874
13.0 ----
10.0
---- ----
0.02
0.00
9.2
----
0.07
0.00
10.9
10
12
33.00
L2B2R ----
10.0
---- ----
3.8
0.44
9.2
----
6.8
1.28
10.9
150
13
0.874
12.0 ----
10.0
---- ----
0.01
0.00
8.8
----
0.03
0.00
9.6
11
13
1.00
B ----
10.0
---- ----
0.0
0.00
8.8
----
0.0
0.00
9.6
150
14
0.874
3.0 ----
10.0
---- ----
0.00
0.00
8.8
----
0.00
0.00
9.6
12
13
39.00
2E5R ----
10.0
---- ----
3.8
0.45
8.8
----
6.8
1.31
9.6
150
15
0.874
7.0 ----
10.0
---- ----
0.01
0.00
8.3
----
0.03
0.00
8.3
13
15
6.00
LR ----
10.0
---- ----
10.0
0.64
8.3
----
10.0
0.64
8.3
150
16
0.874
5.0 ----
10.0
3.61 10.0
0.06
0.00
7.7
10.0
0.06
0.00
7.7
14
15
10.00
B ----
10.0
---- ----
-6.2
0.31
8.3
----
-3.2
0.09
8.3
150
17
0.874
3.0 ----
10.0
---- ---- -0.02
0.00
8.6
---- -0.01
0.00
8.4
15
17
5.50
LB ----
10.0
---- ----
0.0
0.00
8.6
----
10.0
0.73
8.4
150
18
0.874
7.0 ----
10.0
3.61 ----
0.00
0.00
8.6
10.0
0.06
0.00
7.7
16
17
17.50
B2R ----
10.0
---- ----
-6.2
0.53
8.6
---- -13.2
2.19
8.4
150
19
0.874
5.0 ----
10.0
---- ---- -0.02
0.00
9.1
---- -0.10
0.00
10.6
17
19
22.50
3R ----
10.0
---- ----
-1.7
0.06
9.1
----
-4.3
0.31
10.6
150
12
0.874
3.0 ----
10.0
---- ---- -0.00
0.00
9.2
---- -0.01
0.00
10.9
18 19 82.00 4L3B8R ---- 10.0 ---- ---- -4.4 1.48 9.1 ---- -8.9 5.40 10.6
150 11 0.874 33.0 ---- 10.0 ---- ---- -0.01 0.00 10.6 ---- -0.05 0.00 16.0
Legend:
P - Pipe #
DIA - Pipe Diameter
EQV. LN - Pipe Equivalent Length
PUMP - Pump Pressure
SP - K-Factor
FLOW - Flow Rate
PF - Pressure Loss due to Friction
PT - Total Pressure at Node
Fitting Code Letters:
Node Notes
Pipe Notes
LEN - Pipe Length
FIT. - Pipe Fittings
FIXD LOSS - Fixed Loss Device
EL - Node Elevation
DISCH - Discharge in gpm
FL/FT - Friction Loss per Foot
PE - Pressure Loss due to Elevation
E=45 Ell, L=90 Ell, B=TeeBch, R=TeeRun, C=Couplg, S=SwgChk, G=GatVly, X= X, Y= Y, Z=
The maximum velocity of water flow occurs in pipe 2
at 11.04 ft/s with 1 sprinkler flowing.
The maximum velocity of water flow occurs in pipe 2
at 18.40 ft/s with 2 sprinklers flowing.
PIPE FITTINGS TABLE
Pipe Table Name: standard.npt
PAGE: C
MATERIAL: CPVC HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E L B R
C
S
G
X
Y
Z
45 Ell 90 Ell TeeBch TeeRun
Couplg
SwgChk
GatVly
X
Y
Z
0.874
1.00 4.00 3.00 1.00
1.00
5.00
2.00
0.00
0.00
0.00
1.101
1.00 5.00 5.00 1.00
1.00
8.00
2.00
0.00
0.00
0.00
PAGE: K
MATERIAL: Copper Tube-K
HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E L B R
C
S
G
X
Y
Z
45 Ell 90 Ell TeeBch TeeRun
Couplg
SwgChk
GatVly
X
Y
Z
0.745
0.00 1.00 3.00 1.00
1.00
0.00
0.00
0.00
0.00
0.00
0.995
1.00 2.00 6.00 2.00
2.00
6.00
0.00
0.00
0.00
0.00
PAGE: L
MATERIAL: Copper Tube-L
HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E L B R
C
S
G
X
Y
Z
45 Ell 90 Ell TeeBch TeeRun
Couplg
SwgChk
GatVly
X
Y
Z
1.505
2.00 4.00 9.00 3.00
3.00
10.00
0.00
0.00
0.00
0.00
PAGE: P
MATERIAL: PVC HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E L B R
C
S
G
X
Y
Z
45 Ell 90 Ell TeeBch TeeRun
Couplg
SwgChk
GatVly
X
Y
Z
1.590
2.00 9.00 8.00 1.00
1.00
14.00
3.00
0.00
0.00
0.00
Sprinkler system has been hydraulically
calculated
with
the
HASS
HOUSE 2020.0.12 computer program
(License
No. )
to provide an average imbalance
of 0.010
gpm at
each node
and
a maximum imbalance of 0.17 gpm
with one
sprinkler
flowing, and 0.010 gpm at each node
and
maximum
imbalance
of 0.08 gpm with 2 sprinklers flowing
in
accordance
with NFPA 13 and 13D or 13R.
The minimum source pressure is 20.0 psi with a minimum required pressure
of 47.8 psi and a 7 minute flow of 175 gal. and a 10 minute flow of 250.0 gallons.
The minimum pressure at any node is 7.7 psi at node 16.
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
WATER SUPPLY CURVE
75.0
67.5
P
60.0
R
E
52.5
S
S
45.0
U
R
37.5
E
30.0
P
22.5
S
I
15.0
7.5
0.0
04 8 12 16 20 24 28 32 36 40
FLOW (GPM)
Static
= 67.2 psi, Residual
= 64.1 psi @ 920 gpm
(1 sprinkler
flowing)
(2 sprinklers flowing)
A = Available
Water Supply
C = Available Water
Supply
67.2 psi @
15.0 gpm
67.2 psi @ 25.0
gpm
B = Required Water Supply
D = Required Water
Supply
31.6 psi @
15.0 gpm
47.8 psi @ 25.0
gpm
FIRE SPRINKLER SYSTEMS, INC.
705 E. HARRISON ST. SUITE 200
CORONA, CA.
RESIDENTIAL SPRINKLER SYSTEM
HYDRAULICS CALCULATION REPORT
FOR
THE ESTATES @ CARMELA
LA QUINTA, CA.
TRACT #31874-1 & 2 *PLAN 2
*10% TAKEN OFF WATER SUPPLY FOR SAFETY MARGIN
CALC AREA 2
Date: 4/6/2021
File No: 32046
Data File Name: PLAN 2.rdf
SPRINKLER SPACING
400.0 sq. ft./spklr.(max) Max. Dist. Bet. Spklrs:
20.0 ft.
Min. Dist. Bet. Spklrs: 8.0 Max. Dist. Spklr. to Wall:
10.0 ft.
SPRINKLER SPECIFICATIONS
Mfr: Viking Descr: VK494 Conc.Pend.(20x20) K=4.90
Calculated K Factor for Arm-Overs & Drops:
1.0 ft. x 0.874 in. Drop: K=4.71 (Incl. 1 Tee)
0.0 ft. x 0.874 in. Arm -Over: K=4.67 (Incl. 1 Tee
& 1 Ell)
PIPE SPECIFICATIONS
Type: CPVC HWC: 150
WATER SUPPLY
Source: Public Test Date: By:
Static: 67.2 psi Resid: 64.1 psi Flow: 920.0 gpm
Public Main Size: 8 in
Domestic Demand: 5.0 gpm at node number 5
SPRINKLER DEMAND
No.Spklrs. Min Spklr. Press. Node Total Avail.
Req'd
Flowing Flow (psi) No. Flow Press.
Press.
1 20.0 18.0 14 25.0 67.2
59.4
1 20.0 18.0 14 25.0 67.2
59.4
REVIEWING AUTHORITY
LA QUINTA FIRE DEPARTMENT
RESULTS OF ANALYSIS
PIPE &
NODE DATA
*
FLOW ANALYSIS
* 1 sprinkler
flowing * 1 sprinklers
flowing
FIXD
P #
END LEN
FIT.
LOSS
EL
SP *DISCH
FLOW
PF
PT *DISCH
FLOW
PF
PT
HWC
NOD DIA
EQV.LN
PUMP
(FT)
(K) *(GPM)
FL/FT
PE
(PSI)*(GPM)
FL/FT
PE
(PSI)
------------------------------------
--------------------- ---------------------
1
1
60.00
BG ----
-2.0
SRCE ----
25.0
11.11
59.4 ----
25.0
11.10
59.4
150
2
0.995
6.0 ----
-2.0
---- ----
0.17
0.00
48.3 ----
0.17
0.00
48.3
2
2
1.00
-7.0
-2.0
---- ----
25.0
0.69
48.3 ----
25.0
0.69
48.3
150
3
0.745
0.0 ----
-2.0
---- ----
0.69
0.00
40.6 ----
0.69
0.00
40.6
3
3
70.00
3L ----
-2.0
---- ----
25.0
1.66
40.6 ----
25.0
1.66
40.6
150
4
1.590
27.0 ----
-2.0
---- ----
0.02
0.00
38.9 ----
0.02
0.00
38.9
4
4
4.00
L ----
-2.0
---- ----
25.0
0.18
38.9 ----
25.0
0.18
38.9
150
5
1.505
4.0 ----
2.0
-5 5
0.02
1.73
37.0 5
0.02
1.73
37.0
5
5
2.00
R ----
2.0
-5 5
20.0
0.20
37.0 5
20.0
0.20
37.0
150
6
1.101
1.0 ----
4.0
---- ----
0.07
0.87
35.9 ----
0.07
0.87
35.9
6
6
1.00
-2.5
4.0
---- ----
20.0
0.07
35.9 ----
20.0
0.07
35.9
150
7
1.101
0.0 ----
4.0
---- ----
0.07
0.00
33.4 ----
0.07
0.00
33.4
7
7
6.00
2R ----
4.0
---- ----
20.0
0.54
33.4 ----
20.0
0.54
33.4
150
10
1.101
2.0 ----
10.0
---- ----
0.07
2.60
30.2 ----
0.07
2.60
30.2
8
10
9.00
L ----
10.0
---- ----
20.0
2.72
30.2 ----
20.0
2.72
30.2
150
11
0.874
4.0 ----
10.0
---- ----
0.21
0.00
27.5 ----
0.21
0.00
27.5
9
11
59.50
LB6R ----
10.0
---- ----
11.2
5.23
27.5 ----
11.2
5.23
27.5
150
12
0.874
13.0 ----
10.0
---- ----
0.07
0.00
22.3 ----
0.07
0.00
22.3
10
12
33.00
L2B2R ----
10.0
---- ----
11.6
3.43
22.3 ----
11.6
3.43
22.3
150
13
0.874
12.0 ----
10.0
---- ----
0.08
0.00
18.8 ----
0.08
0.00
18.8
11
13
1.00
B ----
10.0
---- ----
20.0
0.84
18.8 ----
20.0
0.84
18.8
150
14
0.874
3.0 ----
10.0
4.71 20.0
0.21
0.00
18.0 20.0
0.21
0.00
18.0
12
13
39.00
2E5R ----
10.0
---- ----
-8.4
1.94
18.8 ----
-8.4
1.94
18.8
150
15
0.874
7.0 ----
10.0
---- ---- -0.04
0.00
20.8 ---- -0.04
0.00
20.8
13
15
6.00
LR ----
10.0
---- ----
0.0
0.00
20.8 ----
0.0
0.00
20.8
150
16
0.874
5.0 ----
10.0
---- ----
0.00
0.00
20.8 ----
0.00
0.00
20.8
14
15
10.00
B ----
10.0
---- ----
-8.4
0.55
20.8 ----
-8.4
0.55
20.8
150
17
0.874
3.0 ----
10.0
---- ---- -0.04
0.00
21.3 ---- -0.04
0.00
21.3
15
17
5.50
LB ----
10.0
---- ----
0.0
0.00
21.3 ----
0.0
0.00
21.3
150
18
0.874
7.0 ----
10.0
---- ----
0.00
0.00
21.3 ----
0.00
0.00
21.3
16
17
17.50
B2R ----
10.0
---- ----
-8.4
0.95
21.3 ----
-8.4
0.95
21.3
150
19
0.874
5.0 ----
10.0
---- ---- -0.04
0.00
22.3 ---- -0.04
0.00
22.3
17
19
22.50
3R ----
10.0
---- ----
0.3
0.00
22.3 ----
0.3
0.00
22.3
150
12
0.874
3.0 ----
10.0
---- ----
0.00
0.00
22.3 ----
0.00
0.00
22.3
18 19 82.00 4L3B8R ---- 10.0 ---- ---- -8.8 5.23 22.3 ---- -8.8 5.23 22.3
150 11 0.874 33.0 ---- 10.0 ---- ---- -0.05 0.00 27.5 ---- -0.05 0.00 27.5
Legend:
P - Pipe #
DIA - Pipe Diameter
EQV. LN - Pipe Equivalent Length
PUMP - Pump Pressure
SP - K-Factor
FLOW - Flow Rate
PF - Pressure Loss due to Friction
PT - Total Pressure at Node
Fitting Code Letters:
Node Notes
Pipe Notes
LEN - Pipe Length
FIT. - Pipe Fittings
FIXD LOSS - Fixed Loss Device
EL - Node Elevation
DISCH - Discharge in gpm
FL/FT - Friction Loss per Foot
PE - Pressure Loss due to Elevation
E=45 Ell, L=90 Ell, B=TeeBch, R=TeeRun, C=Couplg, S=SwgChk, G=GatVly, X= X, Y= Y, Z=
The maximum velocity of water flow occurs in pipe 2
at 18.40 ft/s with 1 sprinkler flowing.
The maximum velocity of water flow occurs in pipe 2
at 18.40 ft/s with 1 sprinklers flowing.
PIPE FITTINGS TABLE
Pipe Table Name: standard.npt
PAGE: C
MATERIAL: CPVC HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E L B R
C
S
G
X
Y
Z
45 Ell 90 Ell TeeBch TeeRun
Couplg
SwgChk
GatVly
X
Y
Z
0.874
1.00 4.00 3.00 1.00
1.00
5.00
2.00
0.00
0.00
0.00
1.101
1.00 5.00 5.00 1.00
1.00
8.00
2.00
0.00
0.00
0.00
PAGE: K
MATERIAL: Copper Tube-K
HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E L B R
C
S
G
X
Y
Z
45 Ell 90 Ell TeeBch TeeRun
Couplg
SwgChk
GatVly
X
Y
Z
0.745
0.00 1.00 3.00 1.00
1.00
0.00
0.00
0.00
0.00
0.00
0.995
1.00 2.00 6.00 2.00
2.00
6.00
0.00
0.00
0.00
0.00
PAGE: L
MATERIAL: Copper Tube-L
HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E L B R
C
S
G
X
Y
Z
45 Ell 90 Ell TeeBch TeeRun
Couplg
SwgChk
GatVly
X
Y
Z
1.505
2.00 4.00 9.00 3.00
3.00
10.00
0.00
0.00
0.00
0.00
PAGE: P
MATERIAL: PVC HWC: 150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E L B R
C
S
G
X
Y
Z
45 Ell 90 Ell TeeBch TeeRun
Couplg
SwgChk
GatVly
X
Y
Z
1.590
2.00 9.00 8.00 1.00
1.00
14.00
3.00
0.00
0.00
0.00
Sprinkler system has been hydraulically
calculated
with
the
HASS
HOUSE 2020.0.12 computer program
(License
No. )
to provide an average imbalance
of 0.010
gpm at
each node
and
a maximum imbalance of 0.01 gpm
with one
sprinkler
flowing, and 0.010 gpm at each node
and
maximum
imbalance
of 0.04 gpm with 1 sprinklers flowing
in
accordance
with NFPA 13 and 13D or 13R.
The minimum source pressure is 20.0 psi with a minimum required pressure
of 59.4 psi and a 7 minute flow of 175 gal. and a 10 minute flow of 250.0 gallons.
The minimum pressure at any node is 18.0 psi at node 14.
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
WATER SUPPLY CURVE
75.0
67.5
P
60.0
R
E
52.5
S
S
45.0
U
R
37.5
E
30.0
P
22.5
S
I
15.0
7.5
0.0
04 8 12 16 20 24 28 32 36 40
FLOW (GPM)
Static
= 67.2 psi, Residual
= 64.1 psi @ 920 gpm
(1 sprinkler
flowing)
(1 sprinklers flowing)
A = Available
Water Supply
C = Available Water
Supply
67.2 psi @
25.0 gpm
67.2 psi @ 25.0
gpm
B = Required Water Supply
D = Required Water
Supply
59.4 psi @
25.0 gpm
59.4 psi @ 25.0
gpm
Z
Domestic Water System Flow Analysis
Coachella Valley Water District
75515 Hovley Lane East
Palm Desert, CA 92211
Domestic Water System Flow Analysis (Hydraulic Model)
Requested By:
D.R. Horton
Date:
11/23/20
Address:
2280 Wardlow Circle, Suite 100
Corona, CA 92878
APN:
Req. Fire Flow:
gpm at 20psi for hours.
Contact Name:
Mario Ornelas
Project Name:
Carmela
Phone:
(951) 7395481
Email:
maornelas@drhorton.com
Cell:
(951) 415-4568
Domestic Water System
Flow Analysis Location:
HYDRANT ON THE NE CORNER OF PALAZO STREET AND ALEGRE STREET, CARMELA, LA QUINTA,
GEO 6-7-10-1, PZ 20-11625
Model Information
Requested •
Test 1 Test 2 Test 3 Test 4 Flow Domestic
Flow Analysis Description
Elevation (Ft):
-19.11
None
system flow
available
without
exceeding
Steady State, Dynamic (psi):
76.38
Residual Pressure (psi):
72.89
Fire Flow Tested (gpm):
920
N/A
CVWD's
Combined Total:
N/A
criteria.
Tested Model Junction:
J3588
Duration:
2 hours
Demand Conditions:
ESP Peak Day Demand (PDD)
Reservoir No./Level (s):
6723/12.0', 6725/27.0', 6726/26.5'
Pumps Operating No's:
Pumps On
Pressure Zone and HGL:
Lake Cahuilla (146')
Model:
ESP 2015 Domestic Water Hydraulic Model (24hr)
Comments:
The domestic water system is capable of providing 920 gpm for 2 hours that satisfies CVWD's minimum pressure,
velocity, and/or head loss criteria. This simulated system flow analysis may not include all facilities that may be
required for this development/project. Please check with Development Services for further information on all
required facilities. The theoretical flow to drop the residual pressure to 20 psi is greater than 5,000 gpm. Please
note the theoretical flow exceeds CVWD's design criteria on the domestic water network
l.r.- "n F
These results are based on hydraulic modelling and not a guarantee that CVWD's domestic water system will have the capacity to
supply water to the project at the flows or pressures indicated. It is important to note that the capacity of the on -site fire system,
meters, service lines, backflow assemblies and other appurtenances were not considered in this analysis, which may alter actual
flows or pressures. Due to continuous changes in the system, CVWD only considers this system flow analysis valid for six months
from date of modelling/analysis. These system flow analysis comments are for plan check purposes only. The ultimate design
responsibility resides with the Engineer -of -Record for this Project.
Should you have any questions or need additional information, please contact me at (760) 398-2661, ext. 2397.
Completed By:
Date: U 31 ,lo
Page 1 of 1 ENG DS-016
Z
(8/31/15)
r------------------------------------------------------------------------------------------------
I I
I 6-7-3-4 I
I
I
I
I
I
I
I
I
I
I
1
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I N
I
I I
I �
I �
I
I
I
I
I
I
I
I
I
I
1
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
1
N 1 W
I I�
I
I
I
I
1
I
1
I
I
I
I
I
I
I
1
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
-----
I o iao 200 aoo soo ON
-- I
CAL FIRE - RIVERSIDE UNIT
RIVERSIDE COUNTY FIRE DEPARTMENT
OFFICE OF THE FIRE MARSHAL — LA QUINTA CALIFORNIA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
February 2, 2021
Fire sprinkler Systems INC.
705 E. Harrison St #200
Corona, CA 92879
Re: Residential Fire Sprinkler Plan Review — THE ESTATES @ CARMELA
FCMP2021-0009 / MASTER PLAN 2
The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
Contractor shall separately apply and pay fees for the various Production Home lots associated with this
project as each will be handled under separate permit.
Permanently marked identification signs shall be attached to all control valves.
The following inspections/tests are required to be witnessed by Office of the Fire Marshal Staff:
(a) Overhead Rough and Hydro static test: All piping shall be visible and pumped at normal
operating pressure. *No jacketed electrical and data wiring shall be in contact with, nor have the
potential to contact CPVC piping once insulation is installed.
(b) Final inspection
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
OFFICE USE ONLY:
REVIEW DATE:
❑ APPROVED ❑ CORRECTIONS CALIFORNIA
CALLED FOR PICKUP:
DESIGN & DEVELOPMENT DEPARTMENT
78-495 Calle Tampico
PICKED UP:
La Quinta, California 92253
(760) 777-7125 / FAX (760) 777-7011
FIRE REVIEW
APPLICATION
❑ SUBMITTAL #
[R] REVISION # 1
PERMIT NO.
APPLICANT/OWNER INFORMATION
Applicant Name:
FIRE SPRINKLER SYSTEMS, INC Owner Name:
D.R. HORTON
Mailing Address:
705 E. HARRISON ST. #200, CORONA CA 92879 Site Address:
MASTER PLAN TYPE 2
Phone Number:
951-272-2522 Project
THE ESTATES @ CARMELA / TRACT# 31874-1 & 2 / PLAN TYPE 2/ 31 HEADS
jamieb@fireinc.net Description:
(Include # of sprinkler heads)
Email:
Pursuant to a Cooperative Agreement to Provide Fire Services, the Riverside County Fire Department serves as the City's fire
department, and
the County designee serves as the City's fire chief. Applicant recognizes this contracted arrangement and
shall comply with
County Fire Department directions.
CONTRACTOR INFORMATION
Contractor Name:
FIRE SPRINKLER SYSTEMS, INC.
Contractor #:
684600 Signature:
Contact Person:
JAM I E B I SH I P
Mailing Address:
705 E. HARRISON ST., #200 Print Name:
JAMIE BISHIP
City, State, Zip:
CORONA, CA 92879 Phone Number:
951-272-2522
Business License #:
762890 Email Address:
jamieb@fireinc.net
A. APPLICATION TYPE
FIRE SPRINKLER SYSTEM
STORAGE TANKS
❑ NEW COMMERCIAL/INDUSTRIAL
------------
❑ DISPENSERS ONLY
HOURLY@161/HR
❑ 0-35,000 SQ FT
$670
❑ ABOVEGROUND
HOURLY@161/HR
❑ 35,001-75,000 SQ FT
$791
SUPRESSION SYSTEM
❑ 75,001-120,000 SQ FT
$992
❑ HOOD & DUCT
$418
❑ 120,001 AND UP
$1234
❑ OTHER SUPRESSION SYSTEM
HOURLY@161/HR
❑ TENANT IMPROVEMENTS - FIRE SPRINKLER
$418
MASTER PLAN
❑ RESIDENTIAL SPRINKLER SYSTEMS
------------
❑ MASTER PLAN HOURLY@161/HR
❑ 1-50 SPRINKLER HEADS
$418
MISC
❑ 51-100 SPRINKLER HEADS
$498
❑ PYRO
$740
❑ OVER 100 SPRINKLER HEADS
$579
❑ HAZMAT
HOURLY@161/HR
❑ RESIDENTIAL TRACT HOME (EA.) ADDITIONAL
------------
❑ HIGH PILE RACK STORAGE
HOURLY@161/HR
❑ 1-50 SPRINKLER HEADS
$176
❑ PRIVATE FIRE MAINS
$901
❑ 51-100 SPRINKLER HEADS
$257
❑ TECHNICAL REPORT RESEARCH
HOURLY@161/HR
❑ OVER 100 SPRINKLER HEADS
$337
❑ FIRE PUMPS
$659
❑ MULTI -FAMILY (3 OR MORE)
$590
❑ STANDPIPE SYSTEMS
$579
FIRE ALARM SYSTEM
❑ WATER TANKS
$418
❑ COMMERCIAL - SPRINKLER MONITORING
$418
❑ REVISION
$161
❑ COMMERCIAL - FIRE ALARM SYSTEM
$1062
❑ OTHER
HOURLY@161/HR
Each application type includes a Technology Enhancement Fee of $5 & Records Management Fee of $10 or $21 REVISED 12/6/2019
*For permits billed at an hourly rate, these fees will be added at time of payment.
Bin #
City of La Quints
Building 8z Safety Division
P.O. Box 1504, 78-495 Calle Tampico
La.Quinta, CA 92253 - (760) 777-7012
Building Permit Application and Tracking Sheet
Permit #
Project Address: MASTER PLAN TYPE 2
Owner's Name: D.R. HORTON
A.P.Number:
Address:2280 WARDLOW CIRCLE #100
Legal Description: MASTER PLAN TYPE 2
Contractor: FIRE SPRINKLER SYSTEMS, INC
City, ST, Zip: CORONA, CA 92880 pa
Telephone U.;£;$�.,G
Address: 705 E. HARRISON ST. #200
Project Description:
City, ST, Zip: CORONA, CA 92879
INSTALLATION OF RESIDENTIAL FIRE SPRINKLERS
Telephone: 951-272-2522
{y �k ,r>Y "'`' 'f
32 HEADS / 3,280 SF
State Lic. # : 684600 City Lie. #.: 762890
Arch., Engr., Designer:
Address:
City, ST, Zip:
Telephone:
State Lic. #: . ,., � z? s"
Name of Contact Person: JAM I E B I S H I P
Construction Type: .V_g Occupancy: R3/U
Project type (eirete one): New Add'n Alter Repair Demo
Sq. Ft.: 3,280 S F "St es: 1 #Units: N/A
Telephone # of Contact Person: 951-272-2522
Estimated Value of Project: $1, 586.00
APPLICANT: DO NOT WRITE BELOW THIS LINE
#
Submittal
Req'd
Reed
TRACKING
PERMIT FEES
Plan Sets
Plan Check submitted
Item Amouat
Structural Cales.
Reviewed, ready for corrections
Plan Check Deposit
Truss Calcs.
Called Contact Person
Plan Check Balance
Title 24 Cales.
Plans picked up
Construction
Flood plain plan
Plans resubmitted
Mechanical
Grading plan
r' Review, ready for correctionslissue
Electrical
Subcontactor List
Called Contact Person
Plumbing
Grant Deed
Plans picked up
S.M.I.
11.0A. Approval
Plans resubmitted
Grading
IN HOUSE:-
'"' Review; ready for eorrectionsfissue
Developer Impact Fee
Planning Approval
Called Contact Person
A.I.P.P.
Pub. Wks. Appr
Date of permit issue
School Fees
Total Permit Fees