FSS2022-0243ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT J D MECHANICAL FIRE INC 82579 FLEMING WAY
SUITE D
INDIO CA 92201 (760)775-6220 AMANDA@JDMECHAN
ICAL.CO
CONTRACTOR J D MECHANICAL FIRE INC 82579 FLEMING WAY
SUITE D
INDIO CA 92201 (760)775-6220 AMANDA@JDMECHAN
ICAL.CO
OWNER KNICKERBOCKER TRUST 53639 FREMONT WAY LA QUINTA CA 92253 (760)775-6220
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
E-MAIL AARON HICKSON 6/14/2022 6/14/2022 REQUESTED FP-1 PLAN SHEET.
CONDITIONS
Description: LOT 96 KNICKERBOCKER
Type: FIRE SPRINKLER (WEB)Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 6/13/2022 ECON
Parcel No: 767710009 Site Address: 53639 FREMONT WY LA QUINTA,CA 92253 Approved: 8/16/2022 KHET
Subdivision: TR 33076-2 Block: Lot: 96 Issued: 8/17/2022 ONLINE
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 3/16/2023 LRO
Valuation: $10,000.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Thursday, April 13, 2023 3:23:01 PM 1 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0243
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD HYRO KHET 8/31/2022 8/31/2022 APPROVED No leaks
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE FAILED OR
ADDITIONAL FIELD
INSPECTIONS
(EXCESSIVE) EACH
101-0000-42421 0 $175.00 $175.00 3/13/23 WEB14608 196954276 CREDIT 1020141 ECON
FIRE FAILED OR
ADDITIONAL RE-
INSPECTION
101-0000-42421 0 $167.00 $167.00 9/13/22 WEB13031 723795836 CREDIT 1020141 ECON
FIRE PLAN REVISION
SUBMITTALS 101-0000-42420 0 $175.00 $175.00 3/3/23 WEB14509 825775897 CREDIT 1020141 ECON
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $250.00 $250.00 8/17/22 WEB12780 708702012 CREDIT 1020141 ECON
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $250.00 $250.00 8/17/22 WEB12780 708702012 CREDIT 1020141 ECON
Total Paid for FIRE FEES: $1,017.00 $1,017.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $11.00 $11.00 8/17/22 WEB12780 708702012 CREDIT 1020141 ECON
Total Paid for RECORDS MANAGEMENT FEE: $11.00 $11.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 8/17/22 WEB12780 708702012 CREDIT 1020141 ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$1,033.00 $1,033.00
Printed: Thursday, April 13, 2023 3:23:01 PM 2 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0243
BOND INFORMATION
OVERHEAD ROUGH
PIPING KHET 8/31/2022 8/31/2022 DISAPPROVE
D SEE ATTACHMENTS
Insulation protection throughout.
FAU coverage in mid attic.
As-built changes, require Revised plans and
calcs prior to final
OVERHEAD ROUGH
PIPING LIN 9/13/2022 9/13/2022 APPROVED Reinspection APPROVED OH Rough based on
KHetrick's redlined plans.
FIRE FINAL**KHET 3/6/2023 3/6/2023 DISAPPROVE
D SEE NOTES
CANCELLED DUE TO CORRECT
PLANS/REVISIONS ARE SUBMITTED AND
APPROVED
Missing 2 trim in mechanical closets where
heads were present. Patch/Paint work
around heads still present in some areas -
Needs to be complete.
FIRE FINAL**LRO 3/16/2023 3/16/2023 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST FIRE - ETRAKIT
(2 WK)
KOHL
HETRICK
6/13/2022 6/27/2022 7/18/2022 REVISIONS REQUIRED SEE ATTACHMENTS
1ST PERMIT TECH –
ETRAKIT (1 DAY)
PERMIT TECH
BUCKET
6/13/2022 6/14/2022 6/14/2022 COMPLETE
2ND FIRE (1 WK)KOHL
HETRICK
7/21/2022 7/28/2022 8/16/2022 APPROVED SEE ATTACHMENTS
3RD FIRE (1 WK)KOHL
HETRICK
2/17/2023 2/24/2023 3/1/2023 REVISIONS REQUIRED SEE ATTACHMENTS
4TH FIRE (1 WK)KOHL
HETRICK
3/1/2023 3/8/2023 3/2/2023 APPROVED SEE ATTACHMENTS
PARENT PROJECTS
Printed: Thursday, April 13, 2023 3:23:01 PM 3 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0243
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 6/13/2022 Etrakit Contractor 1ST SUBMITTAL FP-3
Knickerbocker
Residence.pdf2nd Floor
Piping.pdf
1
DOC 6/13/2022 Etrakit Contractor 1ST SUBMITTAL CVWD Scan_0190.pdf 1
DOC 6/13/2022 Etrakit Contractor 1ST SUBMITTAL SENJU 8464 Senju Concealed
4.9.pdf 1
DOC 6/13/2022 Etrakit Contractor 1ST SUBMITTAL
HYDRAULICS Document.pdfCalc-1.pdf 1
DOC 6/13/2022 Etrakit Contractor 1ST SUBMITTAL FP-2
Knickerbocker
Residence.pdf1st Floor
Piping.pdf
1
DOC 6/14/2022 Etrakit Contractor Knickerbocker
Residence.pdfSite.pdf 1
DOC 2/17/2023 Etrakit Contractor
Knickerbocker
Residence.pdf1st Floor
Piping
knickerbocker.pdf
1
DOC 2/17/2023 Etrakit Contractor
Knickerbocker
Residence.pdf2nd Floor
Piping
knickerbocker.pdf
1
DOC 2/17/2023 Etrakit Contractor
Knickerbocker
Residence.pdfSite
knickerbocker.pdf
1
DOC 2/17/2023 Etrakit Contractor 8464 Senju Concealed
4.9 knickerbocker.pdf 1
DOC 2/17/2023 Etrakit Contractor Document.pdfCalc-1
knickerbocker.pdf 1
DOC 2/17/2023 Etrakit Contractor Document.pdfCalc-3
knickerbocker.pdf 1
Printed: Thursday, April 13, 2023 3:23:01 PM 4 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0243
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 2/17/2023 Etrakit Contractor
VK496 K 3.0 Res
Concealed
knickerbocker.pdf
1
DOC 2/17/2023 Etrakit Contractor Scan_0001
knickerbocker.pdf 1
DOC 7/18/2022 KOHL HETRICK
FSS2022-0243 - 1ST
REVIEW - FIRE PLAN
CORRECTIONS.pdf
FSS2022-0243 - 1ST
REVIEW - FIRE PLAN
CORRECTIONS.pdf
1
DOC 7/21/2022 KOHL HETRICK
2nd Submittal
Knickerbocker
Residence.pdfSite.pdf
Knickerbocker
Residence.pdfSite_1.pdf 0
DOC 7/21/2022 KOHL HETRICK 2nd Submittal 8464
Senju Concealed 4.9.pdf
8464 Senju Concealed
4.9_1.pdf 0
DOC 7/21/2022 KOHL HETRICK 2nd Submittal
Document.pdfCalc-1.pdf
Document.pdfCalc-
1_1.pdf 0
DOC 7/21/2022 KOHL HETRICK 2nd Submittal
Document.pdfCalc-3.pdf Document.pdfCalc-3.pdf 0
DOC 7/21/2022 KOHL HETRICK
2nd Submittal
Knickerbocker
Residence.pdf1st
Floor.pdf
Knickerbocker
Residence.pdf1st
Floor.pdf
0
DOC 7/21/2022 KOHL HETRICK
2nd Submittal
Knickerbocker
Residence.pdf2nd
Floor.pdf
Knickerbocker
Residence.pdf2nd
Floor.pdf
0
DOC 7/21/2022 KOHL HETRICK 2nd Submittal
Scan_0001.pdf Scan_0001.pdf 0
DOC 7/21/2022 KOHL HETRICK 2nd Submittal VK496 K
3.0 Res Concealed.pdf
VK496 K 3.0 Res
Concealed.pdf 0
Printed: Thursday, April 13, 2023 3:23:01 PM 5 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0243
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 8/16/2022 KOHL HETRICK
FSS2022-0243 -
APPROVED PLANS AND
CALCS.pdf
FSS2022-0243 -
APPROVED PLANS AND
CALCS.pdf
1
DOC 8/16/2022 KOHL HETRICK FSS2022-0243 - COA
AND JOB CARD.pdf
FSS2022-0243 - COA
AND JOB CARD.pdf 1
DOC 8/31/2022 KOHL HETRICK FSS2022-0243 - 8-31-
2022 - Insp Notes.pdf
FSS2022-0243 - 8-31-
2022 - Insp Notes.pdf 1
DOC 3/1/2023 KOHL HETRICK
FSS2022-0243 - REVISED
PLANS AND CALCS -
CORRECTIONS.pdf
FSS2022-0243 - REVISED
PLANS AND CALCS -
CORRECTIONS.pdf
1
DOC 3/2/2023 KOHL HETRICK Gl4906 Residencial.pdf Gl4906 Residencial.pdf 1
DOC 3/2/2023 KOHL HETRICK GL5606 Res.pdf GL5606 Res.pdf 1
DOC 3/2/2023 KOHL HETRICK
FSS2022-0243 - REVISED
PLANS AND CALCS -
APPROVED.pdf
FSS2022-0243 - REVISED
PLANS AND CALCS -
APPROVED.pdf
1
Printed: Thursday, April 13, 2023 3:23:01 PM 6 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0243
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iverside County Fire DepartmentLa Quinta Office of the Fire MarshalBy:FIRE SAFETY SPECIALIST03/02/2023 3:36:03 PMThe approval of plans and specifications does notpermit the violation, deletion, omission or faultyinstallation of any requirements of Title 24 or anyLocal Ordinances. Construction shall remainaccessible and exposed for inspection purposesuntil approved by the Fire Department.PERMIT # -FSS2022-0243REVISED PLANS AND CALCSKohl HetrickReason: I am approving this documentContact Info: 760-409-5109
307021080308030802680ARCH26802880268026702670PAIR 2680PAIR 2680vintage50100 POCKET50100 POCKET268026802280228032802680267028803080268026802680409036802880Pair 2280Pair 22802880ARCH1"12' -6"1"0' -7"1"6' -9"1"16' -0"1"14' -9"1"7' -7"1"16' -0"1"8' -3"1"
14' -0"
1"
6' -0"
1"
14' -0"
1 1/2"
?
1"
2' -2"
1"
14' -0"
1"
14' -0"
1"
7' -5"
1"
1' -7"
1"
3' -1"
1"
0' -5"
1"
3' -2"
1"
4' -11"
1"
2' -4"
1"
9' -4"
1"
2' -9"
1"
2' -6"1"1' -1"1"1' -1"1"
2' -1"
1"
2' -11"1"6' -0"1"2' -11"1"9' -11"1"10' -11"1"10' -11"1"9' -7"1"8' -2"1"
2' -3"1"7' -0"1"
8' -0"
1"
7' -9"1"11' -8"1"9' -8"1"
2' -1"1"4' -6"1"
2' -5"
1"
0' -11"
1"
2' -2"
1"
13' -1"1"8' -3"1"
4' -7"
1"
13' -1"1"3' -6"1"12' -0"1"2' -5"1"3' -0"1"
5' -1"1"5' -4"1"
8' -6"
1"
3' -1"
1"
2' -5"1"2' -3"1"4' -3"1"3' -7"1"
5' -8"1"1' -0"1"
10' -0"
1"
1' -0"
1"
2' -3"1"5' -11"1"8' -10"1"
1' -5"1"2' -3"1"
12' -2"
1"
2' -3"1"3' -5"1"
10' -0"1"3' -9"1"
6' -7"1"4' -10"1"1' -11"1"
1' -3"1"5' -3"1"
2' -10"
1"
1' -8"
1"
3' -1"
1"
7' -9"
1"
2' -0"
1"
4' -6"
GARAGE
9'-0"
BEDROOM
SUITE 2
10'-0"BATH
10'-0"
LAUNDRY
10'-0"
STORAGE
10'-0"
GYM
10'-0"
OWNERS
BATH
10'-0"
HER W.I.C.
9'-0"HIS W.I.C.
9'-0"
OWNERS
BEDROOM
SLOPE
11'-4"
11'-4"W.C.
W.C.
COVERED
PATIO
GREAT ROOM
10'-6"
KITCHEN
10'-6"
PREP. KIT.
10'-6"
W.I.C.
10'-0"
BATH
9'-0:
BERROOM 4
10'-6"
COVEDED
OUTDOOR
BEDROOM 3
12'-0"
HALL
10'-0"
COURT YARD
8' - 3"NOTE
THIS 1st FLOOR SYSTEM IS
DESIGNED SEPERATE FROM
THE 2nd FLOOR SYSTEM.
UP NODES SHOWN ON 2nd
FLOOR DRAWING
NOTE:
THESE 4 HEADS SHALL
BE VIKING 3.0 K FACTOR
UP 2'
OVERSPACE CORRECTED
UP to 2nd
UP to 2nd
FAU MID ATTIC
FAU MID ATTIC
1" RISER
UP to 2nd1" x 0' -10"1"
12' -7"1"3' -5"1"9' -1"1"3' -5"1" x 1' -0"1" x 1' -0"1"
3' -2"1"6' -11"1"1' -6"1"3' -6"1"1' -3"1"6' -11"1"2' -5"1"
0' -9"
1"
2' -3"
1"
2' -3"1"5' -7"1"5' -8"1"0' -4"1" x 4' -0"1"6' -0"1" x 4' -0"1"
3' -10"
1"
3' -1"1"1' -2"1"
5' -5"
1"
5' -9"1"1' -2"1"
9' -8"1"1' -1"1"
9' -9"1"7' -1"1"
0' -6"1"5' -7"1"6' -4"1"
8' -8"1"8' -6"1"
1' -6"1"6' -0"1"6' -0"1"1' -3"1"1' -3"1"
15' -9"1"1' -11"1"0' -4"1" x 4' -0"1" x 7' -11"1"
3' -1"1" x 7' -11"1"1' -6"1"
2' -0"1"1' -1"1"
4' -0"1"1' -2"1"
6' -8"1"5' -8"1" x 1' -0"1"
0' -4"1"5' -10"1" x 1' -0"1 1/2"27' -6"1 1/2"4' -6"1"7' -6"1" x 13' -0"1"
3' -4"
1"
0' -9"1"4' -0"1" x 7' -11"1" x 2' -0"1"0' -4"1"
7' -0"
31' - 10"
15' - 11"8' - 11"jd@jdmechanical.co
Scale
Project number
Date
Drawn by
Checked by 82579 Fleming Way Suite DIndio Ca. 92201(760) 775-6220C-16 License # 1020141MECHANICALINC1/8" = 1'-0"3/1/2023 11:01:02 AMFP-2
1st Floor Piping Plan
2nd Correction
Project Number
Knickerbocker
03-01-23
JA
JDKNICKERBOCKERTRUSTRESIDENCE53639 Fremont WayLa Quinta, CaMadison Club Lot 96BSprinkler Schedule
No. of
Sprklrs Description
SIN
(Hydratec)K-Factor
Orifice
Size Temp
79 Globe 1/2 Light Concealed Temperature - 162 Finish - B Quick Response Model - Mirage
SIN - Gl4906 K Factor -4.90
Gl4906 4.9 1/2" 155 °F
14 Globe 1/2 Light Pendent Temperature - 200 Finish - C Special Response Model -
Micromatic SIN - Gl5606 K Factor - 4.9
Gl5606 4.9 1/2" 200 °F
10 Viking 1/2 Residential Concealed Temperature - 155 Finish - B Fast Response Model -
22773 SIN - VK496 K Factor - 3
VK496 3 1/2" 154 °F
: 103
Total No. of Sprinklers: 103
DECK 4
DECK 3
MECH.
DECK 1
ATTIC
LAUNDRY 2W.I.C 5A
DNTV TV
REF.
DN DNLINEN
LINEN
FLAT TV
Fire Sprinkler Riser Detail
1" CPVC to supply fire sprinkler system
TOR
BOR
Domestic
Supply
Check
Flow Control
1" CPVC
Flow Switch Note Wiring by Others
300psi Gage
Sprinkler Box with Wrench & two
Sprinkler Heads Each Type
1/2" Drain to
Outside1"1"1"
Potter Horn Strobe
Wired by Others
not to scale
Module Must Connect to the Multi
Station Smoke Alarm System and
the Fire Sprinkler Flow Switch
( all wiring by others )
INSPECTOR TEST DETAIL
5'
1" Ball Valve Access Panel
(By Others)
Exterior Wall of Building
Inspector Test to Terminate
in a Smooth Bore Corrosion
Resistant Orfice With a Flow
Equivalent to One Sprinkler
NOTE: Access Panel Shall have sign
Indicating Inspector Test
CPVC HANGERS
NO SCALE
TOLCO FIG. 24
DOUBLE-FASTENER
SIDE-MOUNT HANGER
(OR EQUAL)
SELF-DRILLING
HEX HEAD SCREW
TOLCO FIG. 23
DOUBLE-FASTENER
STRAP TYPE HANGER
(OR EQUAL)
TOLCO FIG. 28M
OFFSET HANGER
(OR EQUAL)
TOLCO FIG. 22
SINGLE-FASTENER
STRAP-TYPE HANGER
(OR EQUAL)
TOLCO FIG. 28
DOUBLE-FASTENER
STAND-OFF HANGER
(OR EQUAL)
TOLCO FIG. 29
DOUBLE-FASTENER
DOUBLE OFFSET HANGER
(OR EQUAL)
CPVC HANGER SPACING
PIPE SIZE
11/4"
1"
MAXIMUM SUPPORT SPACING
6'-6"
6'-0"
2"8'-0"
11/2"7'-0"
SPRINKLER PIPEINSULATION
BOTTOM CORD OF ROOF TRUSS
OR CEILING JOIST
PIPE INSULATION DETAIL
www.cadmando.co.uk
These blocks were brought to you by CADB locksFree.com.For all of your 2D & 3D CA D outsource requirements visit us:
C A D M A N D O
www.cadblocksfree.com
COVER WITH HINGED LID
FINISHED GRADE
DISC-TYPE WATER METER
PLUG VALVE(TYP.)UNION(TYP.)
INSPECTORS TEST
Calc-1
Water Supply Information
Static Pressure:
Residual Pressure:
Residual Flow:
Additional Hose Flow:
78.35 psi
58.19 psi
41 GPM
0 GPM
DOM
WM
6
1
3
2
Remote area number:
Occupancy classification:
Density:
Area of application:
Total water required
(including hose streams):
@ a required
system pressure
of:
Fire Protection System Demand:
No. of sprinklers calculated:
Inside Hose Streams:
Outside Hose
Streams:
Calc-1
R-3
2
Gpm/SqFt
512 Max SqFt
31.1224 GPM
45.4094 Psi
5 GPM
0 GPM
BEDROOM SUITE 7
8'-0"
BATH 7
8'-0"
STORAGE/MECH
SLOPE STORAGE/AV ROOM
SLOPE
TV LOUNGE
9'-6"
LOUNGE
9'-6"
8X10 BEAM
8X10 BEAM
8X10 BEAM
8X10 BEAM
BEDROOM SUITE 5
BUNK ROOM
9'-0"
BATH 5
8'-6"
BATH 6
8'-6"
BEDROOM SUITE
9'-6"
1 1/2"
43' -3"
1"
9' -7"
1"
4' -5"
1"
3' -6"1"
5' -0"
1"
1' -1"
1"
3' -10"1"7' -4"1"
8' -9"
1"
7' -4"
1"
2' -3"
1"
10' -7"1"3' -11"1"4' -1"1"
4' -7"
1"
3' -11"
1"
12' -0"
1"
8' -3"
1"
1' -6"1"2' -7"1"
9' -8"
1"
3' -2"
1"
5' -0"1"10' -7"1"10' -7"Up 1" x 9' -0"Dn 1" x 9' -0"4' - 1"8' - 6"
1" Supply from 1st Floor
5' - 10"Remote area number:
Occupancy classification:
Density:
Area of application:
Total water required
(including hose streams):
@ a required
system pressure
of:
Fire Protection System Demand:
No. of sprinklers calculated:
Inside Hose Streams:
Outside Hose
Streams:
Calc-3
R-3
3
Gpm/SqFt
432 Max SqFt
29.1051 GPM
38.2597 Psi
5 GPM
0 GPM
Calc-3
NOTE:
THESE 6 HEADS SHALL
BE VIKING 3.0 K FACTOR
NOTE 8' SPACING
UP2
DOWN to 1st
DOWN to 1st
DOWN to 1st
1"
3' -8"
1"
10' -1"
1"
7' -3"
1"
0' -8"
1"
0' -10"
1"
4' -8"1"4' -5"1"1' -0"1" x 22' -0"1"
4' -11"
1"
1' -6"
1"
0' -8"1"8' -8"1"
11' -7"
1"
1' -9"1"11' -8"1"
1' -0"1"3' -7"1"
2' -11"1"3' -7"1"2' -5"1"
9' -7"
1"
1' -0"1"3' -8"1"
5' -9"1"0' -8"1"
0' -8"1" x 8' -11"1"7' -4"1"
3' -3"20' - 1"21' - 1"1 1/2"4' -6"1 1/2"38' -0"Supply Point
7
4
BOR
5 SOR
TOR
UP1
8
12' - 0"
14
13
10
9
11 12
jd@jdmechanical.co
Scale
Project number
Date
Drawn by
Checked by 82579 Fleming Way Suite DIndio Ca. 92201(760) 775-6220C-16 License # 1020141MECHANICALINCAs indicated
3/1/2023 11:02:17 AMFP-3
2nd Floor Piping Plan
2nd Correction
Project Number
Knickerbocker
03-01-23
JA
JDKNICKERBOCKERTRUSTRESIDENCE53639 Fremont WayLa Quinta, Ca. 92253Madison Club Lot 96B1/8" = 1'-0"1 2nd Floor Piping
Sprinkler Schedule
No. of
Sprklrs Description
SIN
(Hydratec)K-Factor
Orifice
Size Temp
79 Globe 1/2 Light Concealed Temperature - 162 Finish - B Quick Response Model - Mirage
SIN - Gl4906 K Factor -4.90
Gl4906 4.9 1/2" 155 °F
14 Globe 1/2 Light Pendent Temperature - 200 Finish - C Special Response Model -
Micromatic SIN - Gl5606 K Factor - 4.9
Gl5606 4.9 1/2" 200 °F
10 Viking 1/2 Residential Concealed Temperature - 155 Finish - B Fast Response Model -
22773 SIN - VK496 K Factor - 3
VK496 3 1/2" 154 °F
: 103
Total No. of Sprinklers: 103
JD Mechanical Fire
82579 Fleming Way Suite D
Your Street Address 2
Indio, Ca. 92201
760-775-6220
Job Name : Knickerbocker Residence
Drawing :
Location : 53639 FREMONT WAY
Remote Area : Calc-1
Contract :
Data File : Knickerbocker Residence Area Calc-1.WXF
Computer Programs by Hydratec Inc. Revision: 50.54.4
JD Mechanical FirePage 1 Knickerbocker ResidenceDate 10203040E50R60U70S80S90E100R110P12013014015010 20 30 40 50 60 70 80 90FLOW ( N ^ 1.85 )City Water Supply:Demand:C1C2C1 - Static Pressure : 78.35 C2 - Residual Pressure: 58.19 C2 - Residual Flow : 41 D1 - Elevation : 9.177 D2 - System Flow : 31.122 D2 - System Pressure : 45.409 Hose ( Demand ) : _______D3 - System Demand : 31.122 Safety Margin : 20.834 D1D2Water Supply CurveComputer Programs by Hydratec Inc. Revision: 50.54.4
JD Mechanical FirePage 2 Knickerbocker ResidenceDate Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24 N * CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 O * CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 R * CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used SummaryComputer Programs by Hydratec Inc. Revision: 50.54.4
JD Mechanical Fire Page 3
Knickerbocker Residence Date
SUPPLY ANALYSIS
Node at Static Residual Available
Source Pressure Pressure Flow Pressure Total Demand Required Pressure
SOR 78.35 58.19 41.0 66.243 31.12 45.409
NODE ANALYSIS
Pressure Discharge
Node Tag Elevation Node Type at Node at Node Notes
1 18.19 4.9 7.04 13.0 0.05 256
2 19.0 7.03
3 19.0 7.65
4 19.0 9.17
UP2 10.0 25.57
TOR 10.0 33.47
DOM -1.53 40.53 5.0
BOR -3.0 42.63
5 -3.0 45.25
WM -3.0 45.31
7 -3.0 45.38
SOR -3.0 45.41
6 18.19 4.9 7.17 13.12 0.05 256
8 19.0 7.65
Flow Summary - NFPA
Computer Programs by Hydratec Inc. Revision: 50.54.4
JD Mechanical Fire Page 4
Knickerbocker Residence Date
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
1 18.19 4.90 13.00 1 N 7.0 3.970 150 7.040
to 7.000 -0.351
2 19 13.0 1.101 10.970 0.0307 0.337 Vel = 4.38
2 19 0.0 1 R 1.0 12.300 150 7.026
to N 7.0 8.000 0.0
3 19 13.0 1.101 20.300 0.0306 0.622 Vel = 4.38
3 19 -1.23 1 5R 5.0 39.500 150 7.648
to 3O 15.0 20.000 0.0
4 19 11.77 1.101 59.500 0.0255 1.519 Vel = 3.97
4 19 14.35 1 6O 30.0 64.110 150 9.167
to 4R 4.0 48.000 3.898
UP2 10 26.12 1.101 2N 14.0 112.110 0.1115 12.502 Vel = 8.80
UP2 10 0.0 1 2N 14.0 51.890 150 25.567
to O 5.0 19.000 0.0
TOR 10 26.12 1.101 70.890 0.1115 7.905 Vel = 8.80
TOR 10 0.0 1 N 7.0 11.530 150 33.472
to 7.000 4.994
DOM -1.53 26.12 1.101 18.530 0.1115 2.066 Vel = 8.80
DOM -1.53 + 5.00 5.00 1 N 7.0 1.470 150 40.532
to R 1.0 8.000 0.637
BOR -3 31.12 1.101 9.470 0.1542 1.460 Vel = 10.49
BOR -3 0.0 1.5 2N 18.0 86.160 150 42.629
to 18.000 0.0
5 -3 31.12 1.598 104.160 0.0251 2.617 Vel = 4.98
5 -3 0.0 1 0.420 150 45.246
to 0.0
WM -3 31.12 1.101 0.420 0.1548 0.065 Vel = 10.49
WM -3 0.0 1 0.420 150 45.311
to 0.0
7 -3 31.12 1.101 0.420 0.1548 0.065 Vel = 10.49
7 -3 0.0 1.5 1.330 150 45.376
to 0.0
SOR -3 31.12 1.598 1.330 0.0248 0.033 Vel = 4.98
0.0
SOR 31.12 45.409 K Factor = 4.62
6 18.19 4.90 13.12 1 N 7.0 13.660 150 7.171
to R 1.0 13.000 -0.351
8 19 13.12 1.101 O 5.0 26.660 0.0312 0.832 Vel = 4.42
8 19 1.23 1 4R 4.0 32.160 150 7.652
to O 5.0 9.000 0.0
4 19 14.35 1.101 41.160 0.0368 1.515 Vel = 4.84
0.0
4 14.35 9.167 K Factor = 4.74
3 19 1.23 1 R 1.0 7.330 150 7.648
to 1.000 0.0
8 19 1.23 1.101 8.330 0.0005 0.004 Vel = 0.41
0.0
8 1.23 7.652 K Factor = 0.44
Final Calculations : Hazen-Williams
Computer Programs by Hydratec Inc. Revision: 50.54.4
JD Mechanical Fire Page 5
Knickerbocker Residence Date
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
Final Calculations : Hazen-Williams
Computer Programs by Hydratec Inc. Revision: 50.54.4
JD Mechanical Fire
82579 Fleming Way Suite D
Your Street Address 2
Indio, Ca. 92201
760-775-6220
Job Name : Knickerbocker Residence
Drawing :
Location :
Remote Area : Calc-3
Contract :
Data File : Knickerbocker Residence Area Calc-3.WXF
Computer Programs by Hydratec Inc. Revision: 50.54.4
JD Mechanical FirePage 1 Knickerbocker ResidenceDate 10203040E50R60U70S80S90E100R110P12013014015010 20 30 40 50 60 70 80 90FLOW ( N ^ 1.85 )City Water Supply:Demand:C1C2C1 - Static Pressure : 78.35 C2 - Residual Pressure: 58.19 C2 - Residual Flow : 41 D1 - Elevation : 9.177 D2 - System Flow : 29.105 D2 - System Pressure : 38.260 Hose ( Demand ) : _______D3 - System Demand : 29.105 Safety Margin : 29.395 D1D2Water Supply CurveComputer Programs by Hydratec Inc. Revision: 50.54.4
JD Mechanical FirePage 2 Knickerbocker ResidenceDate Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24 N * CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 O * CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 R * CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used SummaryComputer Programs by Hydratec Inc. Revision: 50.54.4
JD Mechanical Fire Page 3
Knickerbocker Residence Date
SUPPLY ANALYSIS
Node at Static Residual Available
Source Pressure Pressure Flow Pressure Total Demand Required Pressure
SOR 78.35 58.19 41.0 67.655 29.11 38.26
NODE ANALYSIS
Pressure Discharge
Node Tag Elevation Node Type at Node at Node Notes
9 18.19 3 7.1 7.99 0.05 144
10 19.0 6.93
11 19.0 7.03
12 19.0 9.15
UP2 10.0 20.29
TOR 10.0 27.1
DOM -1.53 33.88 5.0
BOR -3.0 35.8
5 -3.0 38.12
WM -3.0 38.17
7 -3.0 38.23
SOR -3.0 38.26
13 18.19 3 7.2 8.05 0.05 144
14 18.19 3 7.22 8.06 0.05 144
Flow Summary - NFPA
Computer Programs by Hydratec Inc. Revision: 50.54.4
JD Mechanical Fire Page 4
Knickerbocker Residence Date
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
9 18.19 3.00 7.99 1 N 7.0 7.240 150 7.100
to 7.000 -0.351
10 19 7.99 1.101 14.240 0.0125 0.178 Vel = 2.69
10 19 8.06 1 R 1.0 1.310 150 6.927
to 1.000 0.0
11 19 16.05 1.101 2.310 0.0450 0.104 Vel = 5.41
11 19 8.06 1 2O 10.0 12.000 150 7.031
to 10.000 0.0
12 19 24.11 1.101 22.000 0.0961 2.115 Vel = 8.12
12 19 0.0 1 3R 3.0 43.390 150 9.146
to 3O 15.0 32.000 3.898
UP2 10 24.11 1.101 2N 14.0 75.390 0.0961 7.245 Vel = 8.12
UP2 10 0.0 1 2N 14.0 51.890 150 20.289
to O 5.0 19.000 0.0
TOR 10 24.11 1.101 70.890 0.0961 6.814 Vel = 8.12
TOR 10 0.0 1 N 7.0 11.530 150 27.103
to 7.000 4.994
DOM -1.53 24.11 1.101 18.530 0.0961 1.780 Vel = 8.12
DOM -1.53 + 5.00 5.00 1 N 7.0 1.470 150 33.877
to R 1.0 8.000 0.637
BOR -3 29.11 1.101 9.470 0.1362 1.290 Vel = 9.81
BOR -3 0.0 1.5 2N 18.0 86.160 150 35.804
to 18.000 0.0
5 -3 29.11 1.598 104.160 0.0222 2.312 Vel = 4.66
5 -3 0.0 1 0.420 150 38.116
to 0.0
WM -3 29.11 1.101 0.420 0.1357 0.057 Vel = 9.81
WM -3 0.0 1 0.420 150 38.173
to 0.0
7 -3 29.11 1.101 0.420 0.1357 0.057 Vel = 9.81
7 -3 0.0 1.5 1.330 150 38.230
to 0.0
SOR -3 29.11 1.598 1.330 0.0226 0.030 Vel = 4.66
0.0
SOR 29.11 38.260 K Factor = 4.71
13 18.19 3.00 8.05 1 O 5.0 0.810 150 7.204
to 5.000 -0.351
10 19 8.05 1.101 5.810 0.0127 0.074 Vel = 2.71
0.0
10 8.05 6.927 K Factor = 3.06
14 18.19 3.00 8.06 1 N 7.0 6.070 150 7.217
to 7.000 -0.351
11 19 8.06 1.101 13.070 0.0126 0.165 Vel = 2.72
0.0
11 8.06 7.031 K Factor = 3.04
Final Calculations : Hazen-Williams
Computer Programs by Hydratec Inc. Revision: 50.54.4
FREEDOM® RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK496 (K3.0)TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 1 of 5
Form No. F_032218 20.01.03 Rev 20.1
1. DESCRIPTION
Viking Freedom® Residential Concealed Pendent Sprinkler VK496 is a small thermosensitive, glass-bulb residential sprinkler designed for installation on concealed pipe systems where the appearance of a smooth ceiling is desired. The orifice design, with a K-Factor of 3.0 (43.2 metric*), allows the sprinkler’s efficient use of available water supplies for the hydraulically designed fire-protection system. The fast response glass bulb operating element and special deflector characteristics meet the challenges of residential sprinkler standards.
The sprinkler is pre-assembled with a threaded adapter for installation with a low-profile small-diameter cover assembly installed flush to the ceiling. The two-piece design allows installation and testing of the sprinkler prior to installation of the cover plate. The “push-on”, “thread-off” design of the concealed cover plate assembly allows easy installation of the cover plate after the system has been tested and the ceiling finish has been applied, while also providing up to 1/2” (13 mm) of vertical adjustment. The cover assembly can be removed and reinstalled, allowing temporary removal of ceiling panels without taking the sprinkler system out of service or removing the sprinkler. The Electroless Nickel PTFE (ENT) coating has been investigated for installation in corrosive atmospheres and is C-UL-US-EU Listed as corrosion resistant as indicated in the Approval Charts. The ENT finish is only available for the sprinkler assembly, the cover plate is not plated.
2. LISTINGS AND APPROVALS
UL Listed (C-UL-US-EU): Category VKKW
Refer to the Approval Charts and Design Criteria on for C-UL-US-EU Listing
requirements that must be followed.
3. TECHNICAL DATASpecifications:Minimum Operating Pressure: Refer to the Approval Chart.Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar).Thread size: 1/2” (15 mm) NPT Nominal K-Factor: 3.0 U.S. (43.2 metric*)Glass-bulb fluid temperature rated to -65 °F (-55 °C)
* Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric
K-factor shown by 10.0.
Material Standards:Sprinkler Body: Brass UNS-C84400 or QM BrassDeflector: Phosphor Bronze UNS-C51000Deflector Pins: Stainless Steel UNS-S30200Button: Brass UNS-C31600Pip Cap and Insert Assembly: Copper UNS-C11000 and SS UNS-S30400Compression Screw: 18-8 Stainless SteelYoke: UNS-S43000 Stainless Steel or Phosphor Bronze UNS-C51000Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE TapeCover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc PlatingShipping Cap: PolyethyleneCover Plate Materials:Cover Plate Assembly: Copper UNS-C11000 and Brass UNS-C26800Spring: Beryllium NickelSolder: Eutectic
Available Finishes and Temperature Ratings:
Finish Brass ENT
Suffix A JN
Temperature 155 °F (68 °C)200°F (93 °C)
Suffix B E
Ordering Information: Refer to Tables 1 and 2.
Replaces Form No. F_032218 Rev 19.1
(Replaced cover part numbers.)
FREEDOM® RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK496 (K3.0)TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 2 of 5
Form No. F_032218 20.01.03 Rev 20.1
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches, releasing the deflector. Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand, causing the glass to shatter, releasing the yoke and pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the deflector, forming a uniform spray pattern over a specific area of coverage determined by the water supply pressure at the sprinkler to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCERefer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Sprinkler Model VK496 is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEEFor details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
TABLE 1: ORDERING INFORMATION
Instructions: Using the sprinkler base part number,
(1) add the suffix for the desired Finish
(2) add the suffix for the desired Temperature Rating.
(3) Order a cover plate (refer to Table 2)
Sprinkler
Base Part
No.
Size 1: Finishes 2: Temperature Ratings
NPT
Inch
BSPT
mm Description Suffix1 Nominal Rating Bulb Color Max. Ambient Ceiling
Temperature2 Suffix
22773 1/2 --Brass A 155 °F (68 °C)Red 100 °F (38 °C)B
ENT 3,4 JN 200 °F (93 °C)Green 150 °F (65 °C)E
Example: 22773AE =
200 °F (93 °C) Temperature Rated Sprinkler
with a standard Brass finish.
Accessories
Sprinkler Wrenches (see Figure 1):
A. Heavy Duty Part Number: 14047WB5
B. Head Cabinet Wrench Part Number: 140316
Sprinkler Cabinet:
Part number 01731A.
Footnotes
1. Where a dash (-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above.
2. Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
3. UL Listed as corrosion resistant.
4. The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These tests cannot and
do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed
environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway.
5. Requires a 1/2” ratchet which is not available from us.
6. Optional for removal of the protective cap. Ideal for sprinkler cabinets.
FREEDOM® RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK496 (K3.0)TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 3 of 5
Form No. F_032218 20.01.03 Rev 20.1
TABLE 2: COVER PLATE ORDERING INFORMATION
Instructions: Using the cover plate base part number,
(1) add the suffix for the desired Finish
(2) add the suffix for the required Cover Plate Nominal Rating.
Cover Plate
Base Part
Number4
Size
Inch (mm)Style
1: Finishes Temperature Rating Matrix1,2
Description Suffix6
Cover Plate
Nominal Rating
(Required)
Sprinkler
Nominal Rating
Sprinkler Max.
Ambient Ceiling
Temperature2
Suffix
23190 2-3/4 (70)Round Polished Chrome F 135 °F (57 °C)155 °F (68 °C)100 °F (38 °C)A
23174 3-5/16 (84)Round Brushed Chrome F-/B 165 °F (73 °C)3 200 °F (93 °C)150 °F (65 °C)C
23179 3-5/16 (84)Square Bright Brass B
Corrosion Resistant Sprinkler Coating: ENT5
Example: 23190MA/W =
135 °F (57 °C) Temperature Rated 2-3/4” (70 mm) Diameter
Round Cover Plate with a Painted White finish.
Antique Brass B-/A
Brushed Brass B-/B
Brushed Copper E-/B
Painted White M-/W
Painted Ivory M-/I
Painted Black M-/B
Footnotes
1. The sprinkler temperature rating is stamped on the deflector.
2. Based on NFPA-13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
3. Maximum ambient temperature for cover assembly is 100 °F (38 °C).
4. Part number shown is the base part number. For complete part number, refer to current our price list schedule.
5. The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and
do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed
environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway. For ENT coated sprinklers, the Belleville
spring is exposed.
6. Where a dash (-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above.
FREEDOM® RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK496 (K3.0)TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 4 of 5
Form No. F_032218 20.01.03 Rev 20.1
APPROVAL CHART VK496, 3.0 K-Factor Residential Concealed Pendent Sprinkler
For systems designed to NFPA 13D or NFPA 13R. For systems designed to NFPA 13, refer to the design criteria. For Ceiling types refer to current editions of NFPA 13, 13R or 13D
S p r i n k l e r B a s e
Part Number 1 SIN Thread Size Nominal K-Factor Maximum Water Working PressureInchesmmU.S.metric 2
22773 VK496 1/2 15 3.0 43.2 175 psi (12 bar)
Maximum
Coverage Area 5
W X L
Ft. X Ft.
(m X m)
All Temperatures Deflector
to Ceiling Installation Type
Listings and
Approvals3 Minimum Spacing
Ft.
(m)Flow
gpm (Lpm)
Pressure
PSI (bar)
4
12 X 12
(3.7 X 3.7)
8
(30.3)
7.1
(0.49)
Refer to
Figure 2
Concealed with Cover
Plate Assembly. See
Footnotes 6 & 7.
See Footnotes 3, 4, and 8 8
(2.4)
14 X 14
(4.3 X 4.3)
12
(45.4)
16
(1.1)
16 X 16
(4.9 X 4.9)
15
(56.8)
25
(1.72)
Footnotes
1. Part number shown is the base part number. For complete part number, refer to current our price schedule.
2. Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3. This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approv-
als. Refer also to Design Criteria.
4. Listed by Underwriter’s Laboratories, Inc. for use in the U.S., Canada, and European Union.
5. For areas of coverage smaller than shown, use the “Flow” and “Pressure” for the next larger area listed. Flows and pressures listed are per sprinkler. The distance from
sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the minimum “Flow” and “Pressure” used.
6. Other paint colors are available on request with the same listings as the standard finish colors. Listings and approvals apply for any paint manufacturer. Contact Viking
for additional information. Custom colors are indicated on a label inside the cover assembly. Refer to Figure 3.
7. Accepted Cover Plate Finishes are: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or
Painted Black 6.
8. C-UL-US-EU Listed as corrosion resistant - Electroless Nickel PTFE (ENT)
FREEDOM® RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK496 (K3.0)TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 5 of 5
Form No. F_032218 20.01.03 Rev 20.1
DESIGN CRITERIA
(Also refer to the Approval Chart on page 3.)
UL Listing Requirements (C-UL-US-EU):
When using Viking Residential Concealed Pendent Sprinkler VK496 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of cover-age and minimum water supply requirements shown in the Approval Chart.
For systems designed to NFPA 13: The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following:
• The flow rates given in the Approval Chart for NFPA 13D and NFPA 13R applications for each listed area of coverage, or
• Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the “design area” in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13.
• Minimum distance between residential sprinklers: 8 ft. (2.4 m).
NOTE: Concealed sprinklers must be installed in neutral or negative pressure plenums only.
IMPORTANT: Always refer to Bulletin Form No. F_080415 - Best Practices for Residential Sprinkler Handling and Installation. Also refer to Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be in-stalled in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA and any other similar Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Final approval and acceptance of all residential sprinkler installations must be obtained from the Authorities Having Jurisdiction.
Sprinkler and Adapter Assembly
• Protective cap removed
• Use wrench 14047W/B**
Step 1:
Carefully slide the wrench sideways around
the deflector and pins
Sprinkler Wrench
Part No. 14047W/B**
** A 1/2” ratchet is required (Not available from Viking)
2-1/4” (57 mm)
diameter opening
required in the
ceiling.
Step 2:
Carefully press the wrench upward and turn slightly to ensure engagement with
the sprinkler wrench flats.
Figure 1: Sprinkler Installation and Proper Wrench Usage
NEVER install the sprinkler by applying the installation
wrench across the frame arms. DO NOT overtighten.
Use only the designated sprinkler wrenches, Viking
Part Numbers 14047W/B** or 14031**. A leak tight seal
should be achieved by turning the sprinkler clockwise 1 to 1-1/2 turns beyond finger tight.
Sprinkler
wrench flat
Sprinkler frame arms
FREEDOM® RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK496 (K3.0)TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 6 of 5
Form No. F_032218 20.01.03 Rev 20.1
Figure 2: Sprinkler Dimensions and Cover Installation
1/2” (15 mm) NPT
2-1/4”(58 mm)2-9/16” (65 mm)Maximum 2-1/16” (52 mm)Minimum
2-3/4” (70 mm) or
3-5/16” (84 mm)NOTE: Upon sprinkler activation, the deflector descends
to approximately 13/16” (21 mm) below the sprinkler body.
Figure 3: Identification of Custom Paint for Concealed Covers
All custom color painted cover plates will have an
identifying label affixed to the inside of the cover that
indicates the custom color and will have a representative
sample (a paint dot) of the paint on the label.
Figure 4: Square Cover Assembly 23179
3-5/16” (84 mm)
Replaces Form No. F_032218 Rev 19.1
(Replaced cover part numbers.) FACTORY APPLIE D C USTO
M
P
AI
NT COLOR
Page:1 of 8
Document No.U085167 Date:Nov/20/2019
SENJU SPRINKLER CO., LTD.
Residential Lead Free Flat Concealed Sprinkler,
Pendent,
Model: RC-RES, K-Factor: 4.9, SIN: SS8464
GENERAL DESCRIPTION
The Model RC-RES Residential Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder type. They
are decorative and fast responding. The Cover Plate Assembly hides the Deflector, Heat Responsive Element etc., which is
concealed above the ceiling. The cover plate has a flat profile, and its diameter is extremely small (2-5/8 inch, 68mm). The
push-on and/or thread-on, thread-off design of the concealed cover plate assembly allows for easy installation of the cover plate.
Therefore, the Model RC-RES should be your first choice when aesthetics is the major consideration for ultimate appeal and
unbeatable performance is desired. The Model RC-RES is designed for residential occupancies and is perfect for use in homes,
hotels and other living quarters.
The Model RC-RES is to be used in wet pipe residential sprinkler systems for One- and Two- Family Dwellings and
Manufactured Homes per NFPA 13D; wet pipe residential sprinkler systems for Residential Occupancies up to and Including
Four Stories in Height per NFPA 13R; or, wet pipe sprinkler systems for the residential portions of any occupancies per NFPA 13.
The Model RC-RES has a 4.9 (70.6 LPM/bar1/2) K-factor that meets the required residential flow rates with minimal residual
pressure, which allows for smaller pipe sizes and water supply requirements.
For extended installation flexibility, the Model RC-RES provides 1/2 inch (12.8mm) vertical adjustment. This adjustment in
installation decreases the need for precise cutting of the pipe that drops to the sprinkler and allows for a perfect fit with a range of
pipe lengths.
The heat sensitivity and water distribution design of Model RC-RES allows for an increased chance of residents to escape or
evacuate in case of a fire. However, residential fire sprinkler systems are not a substitute for fire safety awareness or fire safety
construction required by building codes.
“Lead Free” is defined in the Reduction of Lead in Drinking Water Act (S.3874) endorsed by AWWA’s Water Utility Council, and
California Assembly Bill #1953 as having less than or equal to a weighted average of 0.25% lead in wetted surface of pipes,
plumbing fittings and fixtures.
WARNINGS
The Model RC-RES must be installed and maintained in accordance with the rules stated herein as well as in
compliance with the applicable standards of the National Fire Protection Association regulations and the standards of
any other authorities having jurisdiction.
In the event of this condition, consult the authorities having jurisdiction for guidance and approval.
Failure to do so may impair the integrity of these devices.
It is the responsibility of the installing contractor to provide a copy of this document to the owner or their
representative, and in turn, it is the obligation of the owner to provide a copy of this document to a succeeding owner.
The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The
installing contractor or sprinkler manufacturer should be contacted with any related questions.
Page:2 of 8
Document No.U085167 Date:Nov/20/2019
TECHNICAL DATA
Approvals: cULus Listed
NSF/ANSI/CAN 61, NSF/ANSI 372
Sprinkler Identification Number (SIN): SS8464
Maximum Working Pressure: 175psi (12.1bar)
Discharge Coefficient (Nominal K-Factor):
K=4.9 GPM/psi1/2 (70.6 LPM/bar1/2)
Temperature Rating:
162°F (72°C) Sprinkler with 140°F (60°C) Cover Plate
175°F (79°C) Sprinkler with 140°F (60°C) Cover Plate
175°F (79°C) Sprinkler with 162°F (72°C) Cover Plate
205°F (96°C) Sprinkler with 162°F (72°C) Cover Plate
Color Code (Sprinkler)
162°F (72°C): Uncolored
175°F (79°C): White
205°F (96°C): White
Color Code (Cover Plate)
140°F (60°C): No Mark
162°F (72°C): White-Colored Mark
Vertical Adjustment: 1/2 inch (12.8 mm)
Cover Plate Finishes:
Standard Finishes-
White, Ivory, Beige, Brown, Black, Nickel,
Wood Grain
Custom Finishes-
Custom color and custom pattern cover plates are
available on special order. Contact a Senju
Sprinkler representative with any custom orders.
Please see chart on Page 8 for more detail.
Physical Characteristics: Ref. Figures 1 and 1-1
FIGURE 1. Model RC-RES K=4.9
FIGURE 1-1. Marking (Color Code)
OPERATION
In case of fire, the solder component that holds together the Cover Plate and the Retainer melts. Then the Cover Plate is
released at once. As a result, the Deflector drops down to the intended position. Two Heat Collectors are exposed to fire, and
when sufficient heat from the fire is reached, internal components of the sprinkler fall apart. This leads to the water flow to be
distributed on the affected fire area. (Ref. Figure 2)
FIGURE 2. OPERATION PROCESS (The figure is for illustrative purposes only)
Page:3 of 8
Document No.U085167 Date:Nov/20/2019
DESIGN CRITERIA
The herein stated rules for use and installation of Model RC-RES are provided by the manufacturer and must be strictly
implemented for safe and full results.
NOTES
Residential Fire Sprinkler Systems should only be designed and installed by individuals who are completely familiar
with automatic sprinkler system design, installation procedures, and techniques.
Several criteria may apply to the installation and usage of each sprinkler. Consequently, it is recommended that the
sprinkler system designer review and develop a working understanding of the complete list of criteria prior to initiating
the design of the sprinkler system.
Questions concerning sprinkler installation and usage criteria, which are not covered by the following instructions,
should be submitted to your contracted company. Include sketches and technical details, as appropriate.
In some instances, the requirements of this document may concern specifications which are more stringent, and which
take precedence over those specified in NFPA 13, 13D, 13R, or by the authority having jurisdiction.
The Model RC-RES must not be used in applications where the air pressure above the ceiling is greater than that below.
Inspect all sprinklers after installation to ensure that both the gap between the cover plate, ceiling and the 6 slots in the
cup are open and free from any air flow impediment.
The spray from the sprinkler is distributed radially outward and downward from the sprinkler deflector. Consequently,
the sprinklers must be located such that there will be no blind spaces shielded from spray by partitions, room dividers,
overhangs or other parts of the dwelling structure.
The number of sprinklers within each compartment (as defined by NFPA 13, 13D, or 13R) must be kept as few as
possible. Do NOT use more sprinklers than necessary to cover a particular space.
Use only the Cover Plate provided for the Model RC-RES. The sprinkler must be secured in place by firmly fastening the
sprinkler system piping to the structure. If the sprinkler is not properly secured in position, reaction forces resulting
from sprinkler operation could alter its orientation and its water distribution pattern.
Obstruction to Water Distribution
Locations of sprinklers must follow the obstruction rules of NFPA 13, 13D and 13R for Residential Sprinklers.
General Service Conditions
The Model RC-RES must only be utilized in WET PIPE sprinkler systems.
Heat Source Criteria
Refer to NFPA 13D, 13R or 13 for the requirements relating to the prevention of possible activation of the Heat Responsive
Element of Model RC-RES, due to the exposure of a heat source other than an actual fire.
Available Sprinkler Temperature Ratings
Sprinkler Temperature
Classification
Sprinkler Nominal
Temperature Rating
Maximum Ambient Ceiling
Temperature
Temperature Rating of the
Cover Plate Assembly
Ordinary 162°F (72°C) 100°F (38°C) 140°F (60°C)
Intermediate 175°F (79°C) 150°F (66°C) 140°F (60°C) 1)
Intermediate 175°F (79°C) 150°F (66°C) 162°F (72°C)
Intermediate 205°F (96°C) 150°F (66°C) 162°F (72°C)
1) Maximum ambient temperature for the Cover Plate Assembly is 100°F (38°C).
Precautionary Warnings for Corrosive Environments
Model RC-RES sprinklers should not be installed where they may be subjected to a corrosive environment including the
following:
(1) Chlorine ion and Chloride environment.
Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride. Exposure to this
environment may result in sprinklers operating under Non-Fire conditions or Not Operating when exposed to an actual fire.
(2) Sprinkler system piping with Copper.
Sprinkler systems should be constructed in compliance with the applicable standards and the requirements for copper
piping when copper piping is used in the sprinkler system. (Reference standards NFPA 13, ASTM B813, B828, and CDA
(Copper Development Association) – Solder Joint)
Page:4 of 8
Document No.U085167 Date:Nov/20/2019
All residual flux must be removed from the interior and exterior of the copper piping by thoroughly flushing before
installation of the Sprinkler Heads. Otherwise, residues of flux may cause corrosion and/or leakage in the sprinkler system.
Hydraulic Design Criteria
The minimum required sprinkler flow rates for systems designed to NFPA 13D or 13R are given in TABLE A as a function of
temperature rating and the maximum allowable coverage area. The sprinkler flow rate is the minimum required discharge from
the most hydraulically demanding sprinkler from each of the total number of “design sprinklers” as specified in NFPA 13D or
13R.
For systems designed to NFPA 13, the number of designed sprinklers is to be the four most hydraulically demanding sprinklers.
The minimum required discharge from each of the four sprinklers is to be the greater of the following:
・ The flow rates given in TABLE A for NFPA 13D and 13R as a function of temperature rating and maximum allowable
coverage area.
・ A minimum discharge of 0.1GPM/sq.ft. [4.07LPM/sq.m] over the “design area” comprised of the four most hydraulically
demanding sprinklers for the actual coverage area being protected by the four sprinklers.
TABLE A. NFPA 13D & 13R WET PIPE HYDRAULIC DESIGN CRITERIA for Model SS8464
For systems with ceiling types smooth flat horizontal, or beamed, or sloped, in accordance with NFPA 13D, 13R or 13 as
applicable.
Ordinary
Temperature Rating
162°F (72°C)
Intermediate
Temperature Rating
175°F (79°C)
Intermediate
Temperature Rating
205°F (96°C)
Maximum
Coverage
Area(a)
Ft. × Ft.
(m ×m)
Maximum
Spacing
Ft.
(m)
Flow(b)
GPM
(LPM)
Pressure(b)
PSI
(bar)
Flow(b)
GPM
(LPM)
Pressure(b)
PSI
(bar)
Flow(b)
GPM
(LPM)
Pressure(b)
PSI
(bar)
Deflector
to
Ceiling
Installation
Type
Minimum
Spacing
Ft.
(m)
12×12
(3.7×3.7)
12
(3.7)
13
(49.2)
7.0
(0.48)
13
(49.2)
7.0
(0.48)
13
(49.2)
7.0
(0.48)
14×14
(4.3×4.3)
14
(4.3)
13
(49.2)
7.0
(0.48)
13
(49.2)
7.0
(0.48)
13
(49.2)
7.0
(0.48)
16×16
(4.9×4.9)
16
(4.9)
13
(49.2)
7.0
(0.48) ― ― 13
(49.2)
7.0
(0.48)
18×18
(5.5×5.5)
18
(5.5)
17
(64.4)
12.0
(0.83) ― ― 17
(64.4)
12.0
(0.83)
20×20
(6.1×6.1)
20
(6.1)
21
(79.5)
18.4
(1.27) ― ― 21
(79.5)
18.4
(1.27)
Smooth
Ceilings
3/8 to 7/8
Inches.
Beamed
Ceilings
per NFPA
13D, 13R
or 13
Installed in
beam
3/8 to 7/8
inches
below
bottom of
beam.
Concealed 8
(2.4)
(a) For coverage area dimensions less than the above mentioned, it needs to use the minimum required flow for the
Next Higher Coverage Area listed.
(b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are
calculated using the nominal K-Factor. Refer to Hydraulic Design Criteria Section for details.
Sprinkler Spacing Criteria
The minimum spacing between sprinklers is 8 feet (2.4m). The maximum spacing between sprinklers cannot go beyond the
coverage area calculated by using the specific hydraulic factors. (Ref. TABLE A)
Page:5 of 8
Document No.U085167 Date:Nov/20/2019
INSTALLATION
The Model RC-RES must be installed in accordance with the following instructions:
NOTES
Do not use any sprinklers which have been subjected to potential mechanical damage. Do not use any sprinklers which
show deformation or cracking in either the Sprinkler or the Protective Cap.
Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the
potential for damage to the sprinklers that could cause improper operation or non-operation.
The Protective Cap must remain on the sprinkler during installation. After the installation is completed, the Protective
Cap must be removed to place the sprinkler in service.
Use a torque of 7 to 14 ft·lbs (9.5 to 19.0 N·m) to achieve a 1/2 inch NPT sprinkler joint. If you exceed the recommended
maximum torque, this could result in damage to the sprinkler inlet, which may lead to leakage from the sprinkler.
Use only NR-H model wrench socket for installation of RC-RES sprinklers. Use of any other wrench or socket is
prohibited and may cause damage to the sprinkler.
In case of insufficient adjustment in Cover Plate installation, do not try to overly tighten, screw the sprinkler too loosely
or make any modification to the cover plate assembly. Readjust the sprinkler fitting for a better fit.
Do not rotate the Cap Remover RC to the left with force when placing the two hook arms into place. The installed
sprinkler may become loosened, which may cause water leakage.
Installing Procedure
Step 1
The installation requirements for the sprinkler are as follows: to be installed only in the pendent position with the waterway
perpendicular to the ceiling. Install the sprinkler fitting so that the distance from the face of the fitting to the mounting surface
will be nominally 2 inches (50.8mm) as shown in Figure 3.
Step 2
With pipe thread sealant applied to the threads, hand tighten the sprinkler into the sprinkler fitting. Then tighten it with the
Socket NR-H or Ratchet (3/8” drive) & Socket NR-H Combination (Ref. Figure 4). The teeth of the Socket must fit perfectly
with the grooves on the Sprinkler for proper installation (Ref. Figure 4).
Step 3
If desired, the Protective Cap may also be used to locate the center of the clearance hole by gently pushing the ceiling
material against the center point of the Protective Cap. Before the installation of the ceiling, the sprinkler installation can be
started with a 2-3/8 inch (60mm) diameter clearance hole (Ref. Figure 3). Use the “Vertical Adjustment” indicator on the
Protective Cap to check for proper installation height (Ref. Figure 3).
Step 4
Use the Cap Remover RC to remove the Protective Cap (Ref. Figure 5), and then push or screw a Cover Plate Assembly on
the Cup of the Sprinkler by hand until its flange just has contact with the ceiling (Ref. Figure 6 and Figure 7). Stop tightening
the Cover Plate Assembly once the flange has contact with the ceiling. If the ceiling has been lifted from its normal position in
the process of tightening the Cover Plate Assembly, readjust the cover plate assembly as necessary. If the flange of the Cover
Plate Assembly cannot contact the ceiling sufficiently, readjust the sprinkler fitting as necessary. When properly installed,
there is a nominal 1/16 inch (1.6mm) air gap between the lip of the Cover Plate and the ceiling, as shown in Figure 6.
FIGURE 3. INSTALLATION
FIGURE 4. RATCHET & SOCKET
Page:6 of 8
Document No.U085167 Date:Nov/20/2019
FIGURE 5. PROTECTIVE CAP REMOVAL
FIGURE 6. INSTALLATION (COVER PLATE ASSEMBLY)
FIGURE 7. INSTALLATION (CORRECT and INCORRECT)
Page:7 of 8
Document No.U085167 Date:Nov/20/2019
CARE AND MAINTENANCE
The following instructions must be implemented for the maintenance and service of the Model RC-RES.
NOTES
Wet pipe sprinkler systems must be maintained at a minimum temperature of 40°F / 4°C to prevent freezing and bursting
of the pipe and/or sprinklers.
Automatic sprinklers are not to be tested with a heat source. Operation of the heat responsive element can result.
Absence of a Cover Plate Assembly may delay the response time of the sprinkler in case of a fire.
Install the cover plate assembly properly, as shown in Figure 6. Improper installation of the cover plate assembly may
cause improper operation or non-operation.
If the ceiling is to be repainted after the installation of the Sprinkler, care must be exercised to ensure that the new paint
does not seal off any of the air gap.
Factory painted Cover Plates must not be repainted. They should be replaced, if necessary, by factory painted cover
plates. Non-factory applied paint may adversely delay or prevent sprinkler operation in case of a fire.
Do not pull the Cover Plate. Separation may result.
In preparation for maintenance of the fire protection system, permission to close the main control valve must be
obtained from the proper authorities, and all affected parties by this action, and must be informed before the
maintenance session can commence.
Do NOT enclose any sprinklers within drapes, curtains, or valances.
Do NOT hang anything from the sprinklers.
Do NOT clean the sprinklers with soap and/or water, detergents, ammonia, cleaning fluids, or other chemicals. Remove
dust, lint, cobwebs, cocoons, insects, and larvae by gently brushing with a feather duster or gently vacuuming with a
soft bristle (i.e., dusting) brush attachment.
Exercise suitable safety precautions in the use and storage of highly flammable materials. The rapid rate of fire
development and spread of these materials can reduce the ability of the sprinkler system to aid in the control of a fire
involving such hazards.
Leaking or corroded sprinklers must be replaced.
Automatic Sprinklers must be kept in a cool and dry place.
Automatic sprinklers must never be physically altered, such as painted, plated, or coated, once shipped from the
factory. If the sprinklers have been in any way modified, they must be replaced.
Great caution must be applied to prevent damage to the sprinklers at all stages - before, during, and after installation.
Damaged units because of dropping, hitting, over-tightening, or wrench slippage, must be replaced.
The Model RC-RES must only be replaced with pendent sprinklers which are listed for residential fire protection service
and which have the same nominal K-Factor, the same coverage area, and the same or lower flow ratings (as indicated
under TABLE A “Hydraulic Design Criteria”).
When remodeling, such as by adding false beams or light fixtures or changing the location of compartment walls, first
verify that the new construction will not violate the installation requirements of the applicable standards of NFPA. Alter
the new construction and/or the sprinkler system to suit the requirements of this document and the applicable NFPA
regulations.
The owner is responsible for the maintenance of the sprinkler system, including inspection and testing of its
compliance with this document, as well as the standards of the National Fire Protection Association (e.g., NFPA 25),
and the regulations of any other authorities having jurisdiction. The owner should direct any questions regarding the
above rules and regulations to the installing contractors or the sprinkler manufacturer. It is recommended that
automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with
NFPA 25.
Limited Warranty
For details of warranty, refer to Sales Contract.
Page:8 of 8
Document No.U085167 Date:Nov/20/2019
ORDER PROCEDURE
When placing an order, please contact a local distributor with the following information (Model Name, Temperature Rating and
Finish).
Sprinkler
Model: RC-RES
(SIN: SS8464, Residential Flat Concealed Sprinkler, Pendent, K4.9, Temperature: 162°F (72°C) or 175°F (79°C) or
205°F (96°C))
Cover Plate Assembly
2-5/8 inch (φ68mm) or 3-1/4 inch (φ83mm) or 2-5/8 inch square (□68mm), Order Separately from Sprinkler
Please refer to the chart below for available sizes, temperature, and finishes.
Standard Finishes Custom Finishes White Ivory Beige Brown Black Nickel Copper Wood Grain Custom Color Custom Pattern
2-5/8" Round, 140°F ○ ○ - - - - - - ○ ○
3-1/4" Round, 140°F ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
2-5/8" Square, 140°F ○ - - - - - - - ○ ○
2-5/8" Round, 162°F ○ - - - - - - - ○ ○
3-1/4" Round, 162°F ○ - - - - - - - ○ ○
Tools for Installation of Model RC-RES
・Socket NR-H
For use with a 3/8” drive ratchet (not included)
・Socket NR-H Plastic
For use with a 1/2” drive ratchet (not included)
・Cap Remover RC
NOV 2016 GFS-150a (Formerly A-38)
“THE INCH”
QUICK RESPONSE
AUTOMATIC SPRINKLER
MODEL GL5606
ONE INCH A DJUSTABLE
FLAT PLATE CONCEALED PENDENTDESCRIPTION AND OPERATION
QUICK RESPONSE
WHITE FLAT PLATE
CONCEALED PENDENT
TECHNICAL DATA
SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
The Globe Quick Response GL5606 Adjustable Concealed Pendent Sprinkler has a low profi le,
aesthetically pleasing design. It provides sprinkler operations approximately six times faster than
ordinary sprinklers and can be installed wherever standard concealed spray sprinklers are specifi ed
when allowed by the applicable standards. This sprinkler offers the additional feature of greatly in-
creased safety to life and should be used advisedly and under the direction of approving authorities
having jurisdiction. The sprinkler is available with a nominal 1" of adjustment and a low profi le cover
plate assembly. All that is seen at the ceiling is a 3 5/16" diameter ceiling plate or an optional 2 3/4"
diameter ceiling plate color fi nished to match the specifi er's exact requirements. The GL Series
Concealed Sprinkler may be virtually invisible as it does not interrupt the "smooth fl ow" of the ceiling.
Globe's GL5606 Concealed Sprinkler utilizes a 3mm frangible glass ampule which is located above
the ceiling and concealed from view by the ceiling plate.
The provided protective cap needs to be removed in order to install the sprinkler with the proper
wrench. The protective cap must be replaced on the sprinkler until the time the cover plate is to be
installed. The "push on - screw off" designed cover plate is easily installed and with a nominal 1" of
adjustment makes it easier to get a proper fi t at the ceiling.
Operation of the sprinkler occurs when heat build up causes the solder holding the cover plate
to the support shell to melt allowing the cover plate to fall clear. Continued heat build up causes the
3mm glass bulb to burst allowing the defl ector to drop down and distribute water in an approved
pattern to extinguish or control the fi re.
3 5/16” diameter plate
2 3/4” diameter plate
See reverse side for Approvals and Specifi cations.
Temperature Ratings -
135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 155°F (68°C) Cover Plate
175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate
200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate
Water Working Pressure Rating - 175 psi (12 Bars)
Factory tested hydrostatically to 500 psi (34 Bars)
Maximum low temperature glass bulb rating is -67°F (-55°C)
Frame - bronze Defl ector - brass Screw - brass
Lodgement Wire - stainless steel Bulb seat - copper
Spring - nickel alloy Seal - tefl on Drop Pin - stainless steel
Bulb - glass with alcohol based solution, 3mm size
Cover Plate - brass Upper Escutcheon Assembly - steel
NOTE: Globe’s wrench P/N 332765 must be used to install this sprinkler.
CLASSIFICATION AVAILABLE SPRINKLER
TEMPERATURES BULB COLOR N.F.P.A. MAXIMUM CEILING
TEMPERATURE
ORDINARY
INTERMEDIATE
135°F/155°F
175°F/200°F
57°C/68°C
79°C/93°C
ORANGE/RED
YELLOW/GREEN
100°F
150°F
38°C
66°C
NOV 2016 GFS-150a (Formerly A-38)
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
1FINISHES AVAILABLE ON SPECIAL ORDER.
2FOR PLATES OTHER THAN WHITE, CONTACT GLOBE FOR ORDERING SPECIFICATIONS.
SPECIFICATIONS
1 7/8" DIA.1 7/8" DIA.
2 3/4" MAX.
1 7/8" MIN.
2 3/4" DIA.1/8"
2 1/4" DIA. MIN.
HOLE IN CEILING
FLAT COVER PLATE
SUPPORT
SHELL
DEFLECTOR
DROP PIN
CUP
1" x 1/2"
REDUCER
1" x 1/2"
REDUCER
CUP
DEFLECTOR
DROP PINSUPPORT
SHELL
FLAT COVER PLATE
2 1/4" DIA. MIN.
HOLE IN CEILING
2 3/4" MAX.
1 7/8" MIN.
1/8"3 5/16" DIA.CEILING CEILING
1SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
CROSS SECTIONS
ORDERING INFORMATION
PRINTED U.S.A.
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
FAX 989-846-9231
www.globesprinkler.com
989-846-4583
1-800-248-0278
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufactured
products found to be defective in material or workmanship for a
period of one year from date of shipment.
For specifi c details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price List).
Quantity Model Number Style Orifi ce
Thread Size Temperature Finishes desired
Quantity - Wrenches - P/N 332765
Quantity - Protective Caps - P/N 332695
1” ADJUSTMENT FLAT PLATE CONCEALED PENDENT
SPECIFY
“THE INCH”
QUICK RESPONSE
AUTOMATIC SPRINKLER
MODEL GL5606
ONE INCH A DJUSTABLE
FLAT PLATE CONCEALED PENDENT
APPROVALS
NOMINAL
“K” FACTOR THREAD SIZE LENGTH
FLAT COVER
PLATE FINISHES
5.6
(80 metric)
1/2”NPT
(15mm)
2 1/2”
(6.4cm)
Chrome
White Painted
Other Finishes1,2
STYLE SIN
MODEL HAZARD1
135°F (57°C) Flat Cover Plate 155°F (68°C) Flat Cover Plate
cULus *FM
NYC-DOB
MEA
101-92-E**135°F (57°C)
Sprinkler
155°F (68°C)
Sprinkler
**155°F (68°C)
Sprinkler
175°F (79°C)
Sprinkler
200°F (93°C)
Sprinkler
Adjustable
Concealed
Pendent
GL5606 LH/OH X X X X X X X X
*FM APPROVED AS STANDARD RESPONSE
**NO FM APPROVALS
OH: ORDINARY HAZARD
LH: LIGHT HAZARD
FLAT COVER
PLATE SIZES
WHITE 135°F (57°C)
PART #
WHITE 155°F (68°C)
PART #
CHROME 135°F (57°C)
PART #
CHROME 155°F (68°C)
PART #
2 3/4” DIA. 332726 332731 332724 332729
3 5/16” DIA. 332706 332711 332704 332709
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
August 16, 2022
J D Mechanical Fire Inc
82579 Fleming Way #D
Indio, CA 92201
Re: Residential Fire Sprinkler Plan Review – KNICKERBOCKER – MADISON CLUB LOT 96
FSS2022-0243 / 53639 FREMONT WAY, LA QUINTA, CA 92253
The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
Permanently marked identification signs shall be attached to all control valves.
The following inspections/tests are required to be witnessed by Office of the Fire Marshal Staff:
(a) Overhead Rough and Hydro static test: All piping shall be visible and pumped at normal
operating pressure. *No jacketed electrical and data wiring shall be in contact with, nor have the
potential to contact CPVC piping once insulation is installed.
(b) Final inspection
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 53639 FREMONT WAY PERMIT#: FSS2022-0243 DATE
ISSUED: 8/16/2022
DESCRIPTION: KNICKERBOCKER – LOT 96 CONTRACTOR: J D MECHANICAL FIRE INC.
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.