FSS2022-0251ADDITIONAL SITES
CHRONOLOGY
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
E-MAIL AARON HICKSON 6/30/2022 6/30/2022
Regarding the above permit submittal. A contractor must
apply with a contractor account. Alfa fire is not in our system.
To be in the system a business license is required. I have
attached the application. Once completed email the
application to lqbl@laquintaca.gov for processing. And we
can send a link for payment.
Also do you have cut sheets or any other documents for
review? The only attachments were the Plan and Hydraulic
calcs. If there are additional documents for review please
upload to the permit number above. Do not apply for a new
permit.
CONDITIONS
Description: New Fire Sprinkler system
Type: FIRE SPRINKLER (WEB)Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: ISSUED Applied: 6/29/2022 EPRS
Parcel No: 762250022 Site Address: 80820 VISTA LAZO LA QUINTA,CA 92253 Approved: 8/3/2022 KHET
Subdivision: TR 28034 Block: Lot: 22 Issued: 8/3/2022 ONLINE
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled:
Valuation: $15,000.00 Occupancy Type: Construction Type: Expired: 2/28/2023 KHET
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Thursday, April 13, 2023 3:38:31 PM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0251
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT Aracely Hernandez 7025 Woodley Ave, 213 Van Nuys CA 914066 (818)332-6868 aracely.alfafire@gmail.
com
CONTRACTOR ALFA FIRE PROTECTION 7025 WOODLEY AVE
APT 213
VAN NUYS CA 91406 (818)332-6868 ANTONIO@ALFAFIREP
ROTECTION.COM
OWNER felipe a dominguez 7025 Woodley Ave, 213 Van Nuys CA 914066 (818)332-6868 antonio@alfafireprotec
tion.com
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED COMPLETED RESULT REMARKS NOTES
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE FAILED OR
ADDITIONAL RE-
INSPECTION
101-0000-42421 0 $167.00 $0.00
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $250.00 $250.00 8/3/22 WEB12676 701185407 CREDIT Aracely Hernandez EPRS
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $250.00 $250.00 8/3/22 WEB12676 701185407 CREDIT Aracely Hernandez EPRS
Total Paid for FIRE FEES: $667.00 $500.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $11.00 $11.00 8/3/22 WEB12676 701185407 CREDIT Aracely Hernandez EPRS
Total Paid for RECORDS MANAGEMENT FEE: $11.00 $11.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 8/3/22 WEB12676 701185407 CREDIT Aracely Hernandez EPRS
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$683.00 $516.00
Printed: Thursday, April 13, 2023 3:38:31 PM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0251
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 6/29/2022 Etrakit Public
Registration
1ST SUBMITTAL
HYDRAULIC CALCS
PLAN80-820 VISTA LAZO
(CALC).pdf 1
DOC 6/29/2022 Etrakit Public
Registration
1ST SUBMITTAL FIRE
SPRINKLER PLAN
PLAN80-820 VISTA LAZO
(PLAN).pdf 1
DOC 8/2/2022 KOHL HETRICK
FSS2022-0251 -
APPROVED PLANS AND
CALCS.pdf
FSS2022-0251 -
APPROVED PLANS AND
CALCS.pdf
1
DOC 8/2/2022 KOHL HETRICK FSS2022-0251 - COA
AND JOB CARD.pdf
FSS2022-0251 - COA
AND JOB CARD.pdf 1
BOND INFORMATION
DATE DATE
OVERHEAD HYRO KHET 8/23/2022 8/23/2022 APPROVED
OVERHEAD ROUGH
PIPING KHET 8/23/2022 8/23/2022 DISAPPROVE
D SEE NOTES
INSPECTION PLAN NOTES IN ATTACHEMENTS
SEVERAL OBSTRUCTED HEAD LOCATIONS,
HVAC CLEARANCE ISSUES AND NO ATTEMPT
TO PROTECT AGAINST JACKETED WIRING
CONTACT WITH CPVC.
REINSPECTION REQUIRED - FEES APPLY
OVERHEAD ROUGH
PIPING KHET 9/1/2022 9/1/2022 APPROVED SEE NOTES All corrections completed.
*Clean set of as-builts required prior to finsl
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST FIRE - ETRAKIT
(2 WK)
KOHL
HETRICK
6/29/2022 7/14/2022 8/2/2022 APPROVED SEE ATTACHMENTS
1ST PERMIT TECH –
ETRAKIT (1 DAY)
AARON
HICKSON
6/29/2022 6/30/2022 7/5/2022 COMPLETE
PARENT PROJECTS
Printed: Thursday, April 13, 2023 3:38:31 PM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0251
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 8/23/2022 KOHL HETRICK FSS2022-0251 - 8-23-
2022 Insp Notes.pdf
FSS2022-0251 - 8-23-
2022 Insp Notes.pdf 1
Printed: Thursday, April 13, 2023 3:38:31 PM 4 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0251
APPROVEDRiverside County Fire DepartmentLa Quinta Office of the Fire MarshalBy:FIRE SAFETY SPECIALIST08/02/2022 4:41:54 PMThe approval of plans and specifications does notpermit the violation, deletion, omission or faultyinstallation of any requirements of Title 24 or anyLocal Ordinances. Construction shall remainaccessible and exposed for inspection purposesuntil approved by the Fire Department.PERMIT # -FSS2022-0251Relocated riser andmounted exterior200F ThroughoutHvac clearanceAdjust loc due tosmoke obstructionAdded head due tofan/lightRelocatefrom SmokeHvac clearanceProtect CPVC throughoutfrom contact with jacketedelec/data wiring.Kohl HetrickReason: I am approving this documentContact Info: 760-409-5109
APPROVEDRiverside County Fire DepartmentLa Quinta Office of the Fire MarshalBy:FIRE SAFETY SPECIALIST08/02/2022 4:41:54 PMThe approval of plans and specifications does notpermit the violation, deletion, omission or faultyinstallation of any requirements of Title 24 or anyLocal Ordinances. Construction shall remainaccessible and exposed for inspection purposesuntil approved by the Fire Department.PERMIT # -FSS2022-0251Kohl HetrickReason: I am approving this documentContact Info: 760-409-5109
ALFA FIRE PROTECTION
7025 WOODLEY AVE.
VAN NUYS, CA 91406
(818) 332-6868
Job Name : NICHOLSON RESIDENCE
Building : RESIDENTIAL
Location : 80-820 VISTA LAZO‚ LA QUINTA‚ CA 92253
System : S1
Contract :
Data File : 80-820 VISTA LAO.WXF
Computer Programs by Hydratec Inc. Revision: 50.52.1
ALFA FIRE PROTECTION Page 1
NICHOLSON RESIDENCE Date 06/11/22
HYDRAULIC DESIGN INFORMATION SHEET
Name - NICHOLSON RESIDENCE Date - 06/11/22
Location - 80-820 VISTA LAZO‚ LA QUINTA‚ CA 92253
Building - RESIDENTIAL System No. - S1
Contractor - ALFA FIRE PROTECTION Contract No. -
Calculated By - F.R. Drawing No. -
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height
OCCUPANCY - LIGHT HAZARD
S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D
Y Number of Sprinklers Flowing: ( )1 (X)2 ( )4 ( )
S ( )Other
T ( )Specific Ruling Made by Date
E
M Listed Flow at Start Point - 13 Gpm System Type
Listed Pres. at Start Point - 7 Psi (X) Wet ( ) Dry
D MAXIMUM LISTED SPACING 16 x 16 ( ) Deluge ( ) PreAction
E Domestic Flow Added - +5 Gpm Sprinkler or Nozzle
S Additional Flow Added - Gpm Make VIKING Model VK494
I Elevation at Highest Outlet - 16 Feet Size 1/2" K-Factor 4.9
G Note: Temperature Rating 200 DEG. F.
N
Calculation Gpm Required 31.11 Psi Required 51.218 AT BOR
Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test: Pump Data: Tank or Reservoir:
A Date of Test - Rated Cap. Cap.
T Time of Test - @ Psi Elev.
E Static (Psi) - 91.3 Elev.
R Residual (Psi) - 20 Other Well
Flow (Gpm) - 3600 Proof Flow Gpm
S Elevation -
P Location:
P
L Source of Information:
Y
Computer Programs by Hydratec Inc. Revision: 50.52.1
ALFA FIRE PROTECTIONPage 2 NICHOLSON RESIDENCEDate 06/11/22 10203040E50R60U70S80S90E100R110P120130140150400 800 1200 1600 2000 2400 2800 3200 3600FLOW ( N ^ 1.85 )City Water Supply:Demand:C1C2C1 - Static Pressure : 82.17 C2 - Residual Pressure: 18 C2 - Residual Flow : 3600 D1 - Elevation : 4.981 D2 - System Flow : 31.113 D2 - System Pressure : 65.300 Hose ( Demand ) : _______D3 - System Demand : 31.113 Safety Margin : 16.861 D1D2Water Supply Curve CComputer Programs by Hydratec Inc. Revision: 50.52.1
ALFA FIRE PROTECTIONPage 3 NICHOLSON RESIDENCEDate 06/11/22 Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow N * CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 O * CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 R * CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0 S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 6071 81 91 101 121 Unit Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used SummaryComputer Programs by Hydratec Inc. Revision: 50.52.1
ALFA FIRE PROTECTION Page 4
NICHOLSON RESIDENCE Date 06/11/22
Node Elevation K-Fact Pt Pn Flow Density Area Press
No.Actual Actual Req.
S1 10.0 4.9 7.1 na 13.06 0.05 13 7.1
S2 10.0 4.9 7.1 na 13.06 0.05 13 7.1
1 11.0 7.19 na
2 11.0 11.7 na
3 11.0 13.85 na
4 14.0 13.67 na
5 14.0 17.38 na
6 12.0 19.25 na
7 12.0 28.24 na
8 16.0 27.84 na
9 16.0 29.96 na
TR 16.0 34.75 na 5.0
BR 2.0 51.22 na
UG -1.5 53.2 na
WM -1.5 57.15 na
CM -1.5 65.3 na
The maximum velocity is 12.1 and it occurs in the pipe between nodes TR and BR
Pressure / Flow Summary - STANDARD
Computer Programs by Hydratec Inc. Revision: 50.52.1
ALFA FIRE PROTECTION Page 5
NICHOLSON RESIDENCE Date 06/11/22
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
S1 13.06 1.101 N 7.0 5.000 7.100 K Factor = 4.90
to 150.0 O 5.0 12.000 -0.433
1 13.06 0.0309 0.0 17.000 0.525 Vel = 4.40
0.0
13.06 7.192 K Factor = 4.87
S2 13.06 1.101 N 7.0 5.000 7.100 K Factor = 4.90
to 150.0 O 5.0 12.000 -0.433
1 13.06 0.0309 0.0 17.000 0.525 Vel = 4.40
0.0
13.06 7.192 K Factor = 4.87
1 26.11 1.101 4R 4.0 31.417 7.192
to 150.0 O 5.0 9.000 0.0
2 26.11 0.1114 0.0 40.417 4.504 Vel = 8.80
2 0.0 1.101 R 1.0 11.333 11.696
to 150.0 N 7.0 8.000 0.0
3 26.11 0.1115 0.0 19.333 2.155 Vel = 8.80
3 0.0 1.101 N 7.0 3.000 13.851
to 150.0 0.0 7.000 -1.299
4 26.11 0.1114 0.0 10.000 1.114 Vel = 8.80
4 0.0 1.101 2R 2.0 24.333 13.666
to 150.0 N 7.0 9.000 0.0
5 26.11 0.1115 0.0 33.333 3.715 Vel = 8.80
5 0.0 1.101 N 7.0 2.000 17.381
to 150.0 0.0 7.000 0.866
6 26.11 0.1114 0.0 9.000 1.003 Vel = 8.80
6 0.0 1.101 13R 13.0 60.667 19.250
to 150.0 N 7.0 20.000 0.0
7 26.11 0.1114 0.0 80.667 8.990 Vel = 8.80
7 0.0 1.101 N 7.0 5.000 28.240
to 150.0 0.0 7.000 -1.732
8 26.11 0.1113 0.0 12.000 1.336 Vel = 8.80
8 0.0 1.101 R 1.0 13.000 27.844
to 150.0 O 5.0 6.000 0.0
9 26.11 0.1115 0.0 19.000 2.118 Vel = 8.80
9 0.0 1.101 2R 2.0 27.000 29.962
to 150.0 2N 14.0 16.000 0.0
TR 26.11 0.1114 0.0 43.000 4.792 Vel = 8.80
0.0
26.11 34.754 K Factor = 4.43
TR 31.11 1.025 2E 5.4 15.000 34.754 Qa = 5.00
to 150.0 S 6.75 18.900 9.063 * Fixed Loss = 3
BR 31.11 0.2183 T 6.75 33.900 7.401 Vel = 12.10
Fsp 0.0
BR 0.0 1.265 E 2.967 3.000 51.218
to 150.0 0.0 2.967 1.516
UG 31.11 0.0784 0.0 5.967 0.468 Vel = 7.94
UG 0.0 1.38 N 8.0 69.000 53.202
to 150.0 0.0 8.000 0.0
WM 31.11 0.0513 0.0 77.000 3.950 Vel = 6.67
Final Calculations - Hazen-Williams - 2007
Computer Programs by Hydratec Inc. Revision: 50.52.1
ALFA FIRE PROTECTION Page 6
NICHOLSON RESIDENCE Date 06/11/22
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
WM 0.0 1.025 0.0 19.000 57.152
to 150.0 0.0 0.0 4.000 * Fixed Loss = 4
CM 31.11 0.2183 0.0 19.000 4.148 Vel = 12.10
0.0
31.11 65.300 K Factor = 3.85
Final Calculations - Hazen-Williams
Computer Programs by Hydratec Inc. Revision: 50.52.1
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
August 2, 2022
Alfa Fire Protection
7025 Woodley Ave #213
Van Nuys, CA 91406
Re: Residential Fire Sprinkler Plan Review – HIDEAWAY – LOT 22
FSS2022-0251 / 80820 VISTA LAZO, LA QUINTA, CA 92253
The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
Permanently marked identification signs shall be attached to all control valves.
The following inspections/tests are required to be witnessed by Office of the Fire Marshal Staff:
(a) Overhead Rough and Hydro static test: All piping shall be visible and pumped at normal
operating pressure. *No jacketed electrical and data wiring shall be in contact with, nor have the
potential to contact CPVC piping once insulation is installed.
(b) Final inspection
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 80820 VISTA LAZO PERMIT#: FSS2022-0251 DATE
ISSUED: 8/2/2022
DESCRIPTION: HIDEAWAY LOT 22 CONTRACTOR: ALFA FIRE PROTECTION
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.