Loading...
FSS2022-0275ADDITIONAL SITES CHRONOLOGY CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES E-MAIL KOHL HETRICK 11/8/2022 11/8/2022 I spoke to Chuck today. He sent me the attached video showing the improvement in the residual pressure. Apparently the supply concern was resolved. Chris Cox Assistant Fire Marshal/Office of the Fire Marshal CAL FIRE/Riverside County Fire Department Description: RESIDENTIAL SPRINKLER SYSTEM 13D, 70 HEADS Type: FIRE SPRINKLER (WEB)Subtype: RESIDENTIAL - CUSTOM HOMES Status: FINALED Applied: 7/25/2022 EPRS Parcel No: 777220002 Site Address: 53343 VIA PALACIO LA QUINTA,CA 92253 Approved: 9/27/2022 KHET Subdivision: TR 29894-2 Block: Lot: 216 Issued: 9/27/2022 AHI Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 4/27/2023 LRO Valuation: $15,000.00 Occupancy Type: Construction Type: Expired: No. Buildings: 0 No. Stories: 0 No. Unites: 0 Details: 13D 70 SPRINKLERS APPROX. Printed: Friday, May 05, 2023 11:50:36 AM 1 of 6 Permit Details City of La Quinta PERMIT NUMBER FSS2022-0275 CONTACTS NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL APPLICANT chuck brown 21386 lilium ct moreno valley CA 92557 (951)712-4959 chuck92234@aol.com CONTRACTOR CHARLES F BROWN FIRE PROTECTION DESIGN 21386 LILIUM COURT MORENO VALLEY CA 92557 (951)712-4959 CHUCK92234@AOL.CO M OWNER DEWEY RES.53343 VIA PALACIO LA QUINTA CA 92253 (951)712-4959 SUNLITEINC@DC.RR.C OM E-MAIL KOHL HETRICK 11/17/2022 11/17/2022 RECEIVED EMAIL: Good Afternoon Kohl, Hope all is well. Per our conversation on 11/15/22, I have attached the as-builts, also I have entered them in the portal (Etrakit). As soon as the landscape, painting, etc, is complete I will call you to set up a Final Inspection, which all that will be needed per our conversation is a main drain test. Thank you and have a great weekend! Becky Baillie Office Manager/Designer Charles F. Brown Fire Sprinkler Design 760-413-7147 NOTE JOSE DELGADO 4/21/2023 4/25/2023 CONTRACTOR REQUESTED FINAL INSPECTION. PERMIT EXPIRED AS OF 3/26/23 (6 MOS FROM DATE OF LAST APPROVED INSPECTION). ADDED EXTENSION FEE OF $88 AND EXTENDED PERMIT TO 4/23/23 SO CONTRACTOR CAN PAY FEE VIA ETRAKIT. WILL ALSO REQUIRE AN EXTENSION REQUEST LETTER FROM CONTRACTOR. FEES HAVE BEEN PAID AND CONTRACTOR PROVIDED EXTENSION REQUEST. EXTENDING PERMIT FOR ANOTHER 6 MONTHS. CONDITIONS Printed: Friday, May 05, 2023 11:50:36 AM 2 of 6 Permit Details City of La Quinta PERMIT NUMBER FSS2022-0275 INSPECTIONS SEQID INSPECTION TYPE INSPECTOR SCHEDULED DATE COMPLETED DATE RESULT REMARKS NOTES OVERHEAD ROUGH PIPING KHET 9/29/2022 9/29/2022 APPROVED SEE ATTACHMENTS See Inspection Plan Notes in Attachments. Some items to be confirmed at final: Adequate flow and pressure (Water supply restricted) Head in soffits in garage. Spacing in bedroom exceeded. OVERHEAD HYRO KHET 9/29/2022 9/29/2022 APPROVED FINANCIAL INFORMATION DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD BY FIRE PERMIT EXTENSION (ADMIN PROCESSING) 101-0000-42420 0 $88.00 $88.00 4/24/23 WEB14968 857036906 CREDIT 499210 ECON FIRE SPRINKLER SYSTEMS - SINGLE FAMILY DETACHED 101-0000-42421 0 $250.00 $250.00 9/27/22 WEB13173 731970814 CREDIT 499210 ECON FIRE SPRINKLER SYSTEMS - SINGLE FAMILY DETACHED PC 101-0000-42420 0 $250.00 $250.00 9/27/22 WEB13173 731970814 CREDIT 499210 ECON Total Paid for FIRE FEES: $588.00 $588.00 RECORDS MANAGEMENT FEE 101-0000-42416 0 $11.00 $11.00 9/27/22 WEB13173 731970814 CREDIT 499210 ECON Total Paid for RECORDS MANAGEMENT FEE: $11.00 $11.00 TECHNOLOGY ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 9/27/22 WEB13173 731970814 CREDIT 499210 ECON Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00 TOTALS:$604.00 $604.00 Printed: Friday, May 05, 2023 11:50:36 AM 3 of 6 Permit Details City of La Quinta PERMIT NUMBER FSS2022-0275 ATTACHMENTS Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED DOC 7/27/2022 Etrakit Contractor calc 1 hd CALCONEHEADLOT216_ 1.pdf 1 DOC 7/27/2022 Etrakit Contractor calc 2 hd CALCTWOHEADLOT216_ 1.pdf 1 DOC 9/27/2022 Etrakit Contractor REVISED PLAN W NODES LOTKOHLBS 216 53343..WRKG PLAN .VIA PALACIO WORKING PLAN-FP-1.1.pdf 1 DOC 9/27/2022 Etrakit Contractor REVISED CALC W UG REVKOHLFIRSTFLRCALC TWOHEADLOT216.pdf 1 DOC 9/27/2022 Etrakit Contractor REVCALC80 REVKOHLCALCONEHEA DLOT216.pdf 1 DOC 11/17/2022 Etrakit Contractor AS BUILTS ASBUILTLOT 216 53343..WRKG PLAN .VIA PALACIO WORKING PLAN-FP-1.1.pdf 1 BOND INFORMATION FIRE FINAL**LRO 4/27/2023 4/27/2023 APPROVED See Notes All items from first initial overhead rough have been cleared at final. REVIEWS REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED DATE STATUS REMARKS NOTES 1ST FIRE - ETRAKIT (2 WK) KOHL HETRICK 7/25/2022 8/8/2022 9/5/2022 REVISIONS REQUIRED SEE ATTACHMENTS 1ST PERMIT TECH – ETRAKIT (1 DAY) AARON HICKSON 7/25/2022 7/26/2022 7/26/2022 COMPLETE 1ST FIRE (1 WK)KOHL HETRICK 9/27/2022 10/4/2022 9/27/2022 APPROVED SEE ATTACHMENTS PARENT PROJECTS Printed: Friday, May 05, 2023 11:50:36 AM 4 of 6 Permit Details City of La Quinta PERMIT NUMBER FSS2022-0275 ATTACHMENTS Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED DOC 4/24/2023 Etrakit Contractor Extension Letter DEWEY LETTER.pdf 1 DOC 7/25/2022 Etrakit Public Registration 1ST SUBMITTAL CUT SHEET VIC RES SPRINK LFII.pdf 1 DOC 7/25/2022 Etrakit Public Registration 1ST SUBMITTAL CUT SHEET 2 VIKING 4.9 CONCEALED FREEDOM RES.pdf 1 DOC 7/25/2022 Etrakit Public Registration 1ST SUBMITTAL CUT SHEET 3 VIKING 5.6 PEND..pdf 1 DOC 7/25/2022 Etrakit Public Registration 1ST SUBMITTAL FIRE SPRINKLER PLAN LOT 216 53343..WRKG PLAN .VIA PALACIO WORKING PLAN-FP- 1.1.pdf 1 DOC 7/25/2022 Etrakit Public Registration 1ST SUBMITTAL FLOW LETTER & RIVCO. FIRE LETTER FLOW TEST LOT 216 _ RIV.CO.FIRE.pdf 1 DOC 7/25/2022 Etrakit Public Registration 1ST SUBMITTAL HYDRAULIC CALC 1 CALCONEHEADLOT216.p df 1 DOC 7/25/2022 Etrakit Public Registration 1ST SUBMITTAL HYDRAULIC CALC 2 CALCTWOHEADLOT216. pdf 1 DOC 9/5/2022 KOHL HETRICK FSS2022-0275 - 1ST REVIEW - CORRECTIONS LETTER.pdf FSS2022-0275 - 1ST REVIEW - CORRECTIONS LETTER.pdf 1 DOC 9/5/2022 KOHL HETRICK FSS2022-0275 - 1ST REVIEW - FIRE PLAN CORRECTIONS.pdf FSS2022-0275 - 1ST REVIEW - FIRE PLAN CORRECTIONS.pdf 1 DOC 9/27/2022 KOHL HETRICK REVKOHLCALCTWOHEA DLOT216NEW.pdf REVKOHLCALCTWOHEA DLOT216NEW.pdf 1 DOC 9/27/2022 KOHL HETRICK FSS2022-0275 - APPROVED PLANS AND CALCS.pdf FSS2022-0275 - APPROVED PLANS AND CALCS.pdf 1 DOC 9/27/2022 KOHL HETRICK FSS2022-0275 - COA AND JOB CARD.pdf FSS2022-0275 - COA AND JOB CARD.pdf 1 Printed: Friday, May 05, 2023 11:50:36 AM 5 of 6 Permit Details City of La Quinta PERMIT NUMBER FSS2022-0275 ATTACHMENTS Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED DOC 11/2/2022 KOHL HETRICK FSS2022-0275 - 9-29- 2022 - INSP NOTES.pdf FSS2022-0275 - 9-29- 2022 - INSP NOTES.pdf 1 Printed: Friday, May 05, 2023 11:50:36 AM 6 of 6 Permit Details City of La Quinta PERMIT NUMBER FSS2022-0275 APPROVALS AND CONDITIONS   MODELNUMBERTRADENAMEPRODUCTMATERIAL MATERIALPRODUCTTRADENAMEMODELNUMBER MODELNUMBERTRADENAMEPRODUCTMATERIAL MATERIALPRODUCTTRADENAMEMODELNUMBER MODELNUMBERTRADENAMEPRODUCTMATERIAL MATERIALPRODUCTTRADENAMEMODELNUMBER MATERIALPRODUCTTRADENAMEMODELNUMBERMATERIALPRODUCTSTRADENAMEMODELNUMBER MODELNUMBERTRADENAMEPRODUCTMATERIAL MATERIALPRODUCTTRADENAMEMODELNUMBER MATERIALPRODUCTTRADENAMEMODELNUMBER MATERIALPRODUCTSTRADENAMEMODELNUMBER MATERIALPRODUCTTRADENAMEMODELNUMBER MATERIALPRODUCTSTRADENAMEMODELNUMBER MODELNUMBERTRADENAMEPRODUCTMATERIALMATERIALPRODUCTTRADENAMEMODELNUMBER MODELNUMBERTRADENAMEPRODUCTMATERIAL MATERIALPRODUCTTRADENAMEMODELNUMBER MATERIALPRODUCTTRADENAMEMODELNUMBERMATERIALPRODUCTTRADENAMEMODELNUMBER MATERIALPRODUCTTRADENAMEMODELNUMBER MATERIALPRODUCTTRADENAMEMODELNUMBERMATERIALPRODUCTTRADENAMEMODELNUMBER MATERIALPRODUCTTRADENAMEMODELNUMBERMATERIALPRODUCTTRADENAMEMODELNUMBERMATERIALPRODUCTTRADENAMEMODELNUMBERNO A.S. REQUIREDNO A.S. REQUIRED< LESS THAN 55 SQ. FT.NO A. S.< LESS THAN 55 SQ. FT.NO A. S.< LESS THAN 55 SQ. FT.NO A. S.< LESS THAN 55 SQ. FT.NO A. S.NORTHInstalled by others1" MeterUP200 ° UPRIGHT AT FAUswingswingUP TO 2ND FLOROPEN TO 2ND. FLR.SEE A.S. AT 2ND. FLR.UP PROOF CALC. 23.7 PSI BOR26.1 GPMMATERIALPRODUCTTRADENAMEMODELNUMBER MATERIALPRODUCTSTRADENAMEMODELNUMBER MODELNUMBERTRADENAMEPRODUCTMATERIAL MATERIALPRODUCTTRADENAMEMODELNUMBER MODELNUMBERTRADENAMEPRODUCTMATERIALMATERIALPRODUCTTRADENAMEMODELNUMBER < LESS THAN 55 SQ. FT.NO A. S.< LESS THAN 55 SQ. FT.NO A. S.1" TO BELOW1" to below1" TO BELOWNODE AT 1ST. FLR.NODE AT 1ST. FLR.NODE AT 1ST. FLR.FINISH FLOORTOP PLATE2ND FINISH FLOOR2ND FLR. TOP PLATE2ND FLR. TOP PLATEB. BAILLIEFP-1.13/3/20223/16,1/8" = 1'-0"SHEET TITLE: PIPING & DETAILSPROJECT:No. DATE DESCRIPTIONREVISIONS:C. BROWNVIKINGMODELSYMMAKEAUTOMATIC SPRINKLERSVIKINGCONTRACTOR:No. 1 9-26-22 CORR.16-FT X 16-FTAPPROVEDRiverside County Fire DepartmentLa Quinta Office of the Fire MarshalBy:FIRE SAFETY SPECIALIST09/27/2022 2:56:54 PMThe approval of plans and specifications does notpermit the violation, deletion, omission or faultyinstallation of any requirements of Title 24 or anyLocal Ordinances. Construction shall remainaccessible and exposed for inspection purposesuntil approved by the Fire Department.PERMIT # -FSS2022-02754 90s for beamObserved at rough residual maindrain flow of 25 psi. Possiblerestriction in CVWD meterassembly.Need to investigate and correctSoffit, add 2 heads.Confirm at finalUp 5-ftDrop 2-feet for 8-ftceiling. 5 90sOverspaced off onewall. Confirm correctedat final200f installedUp 5-ftKohl HetrickReason: I am approving this documentContact Info: 760-409-5109 APPROVALS AND CONDITIONS   MODELNUMBERTRADENAMEPRODUCTMATERIAL MATERIALPRODUCTTRADENAMEMODELNUMBER MODELNUMBERTRADENAMEPRODUCTMATERIAL MATERIALPRODUCTTRADENAMEMODELNUMBER MODELNUMBERTRADENAMEPRODUCTMATERIAL MATERIALPRODUCTTRADENAMEMODELNUMBER MATERIALPRODUCTTRADENAMEMODELNUMBERMATERIALPRODUCTSTRADENAMEMODELNUMBER MODELNUMBERTRADENAMEPRODUCTMATERIAL MATERIALPRODUCTTRADENAMEMODELNUMBER MATERIALPRODUCTTRADENAMEMODELNUMBER MATERIALPRODUCTSTRADENAMEMODELNUMBER MATERIALPRODUCTTRADENAMEMODELNUMBER MATERIALPRODUCTSTRADENAMEMODELNUMBER MODELNUMBERTRADENAMEPRODUCTMATERIALMATERIALPRODUCTTRADENAMEMODELNUMBER MODELNUMBERTRADENAMEPRODUCTMATERIAL MATERIALPRODUCTTRADENAMEMODELNUMBER MATERIALPRODUCTTRADENAMEMODELNUMBERMATERIALPRODUCTTRADENAMEMODELNUMBER MATERIALPRODUCTTRADENAMEMODELNUMBER MATERIALPRODUCTTRADENAMEMODELNUMBERMATERIALPRODUCTTRADENAMEMODELNUMBER MATERIALPRODUCTTRADENAMEMODELNUMBERMATERIALPRODUCTTRADENAMEMODELNUMBERMATERIALPRODUCTTRADENAMEMODELNUMBERNO A.S. REQUIREDNO A.S. REQUIRED< LESS THAN 55 SQ. FT.NO A. S.< LESS THAN 55 SQ. FT.NO A. S.< LESS THAN 55 SQ. FT.NO A. S.< LESS THAN 55 SQ. FT.NO A. S.NORTHInstalled by others1" MeterUP200 ° UPRIGHT AT FAUswingswingUP TO 2ND FLOROPEN TO 2ND. FLR.SEE A.S. AT 2ND. FLR.UP PROOF CALC. 23.7 PSI BOR26.1 GPMMATERIALPRODUCTTRADENAMEMODELNUMBER MATERIALPRODUCTSTRADENAMEMODELNUMBER MODELNUMBERTRADENAMEPRODUCTMATERIAL MATERIALPRODUCTTRADENAMEMODELNUMBER MODELNUMBERTRADENAMEPRODUCTMATERIALMATERIALPRODUCTTRADENAMEMODELNUMBER < LESS THAN 55 SQ. FT.NO A. S.< LESS THAN 55 SQ. FT.NO A. S.1" TO BELOW1" to below1" TO BELOWNODE AT 1ST. FLR.NODE AT 1ST. FLR.NODE AT 1ST. FLR.FINISH FLOORTOP PLATE2ND FINISH FLOOR2ND FLR. TOP PLATE2ND FLR. TOP PLATEB. BAILLIEFP-1.13/3/20223/16,1/8" = 1'-0"SHEET TITLE: PIPING & DETAILSPROJECT:No. DATE DESCRIPTIONREVISIONS:C. BROWNVIKINGMODELSYMMAKEAUTOMATIC SPRINKLERSVIKINGCONTRACTOR:No. 1 9-26-22 CORR.16-FT X 16-FTAPPROVEDRiverside County Fire DepartmentLa Quinta Office of the Fire MarshalBy:FIRE SAFETY SPECIALIST09/27/2022 2:56:54 PMThe approval of plans and specifications does notpermit the violation, deletion, omission or faultyinstallation of any requirements of Title 24 or anyLocal Ordinances. Construction shall remainaccessible and exposed for inspection purposesuntil approved by the Fire Department.PERMIT # -FSS2022-0275Kohl HetrickReason: I am approving this documentContact Info: 760-409-5109 , HYDRAULIC CALCULATIONS FOR DEWEY RES. LOT 216 53-343 VIA PALACIO TWO HEAD CALC. LA QUINTA, CA. 92263 FILE NUMBER: DATE: SEP 27, 2022 -DESIGN DATA- OCCUPANCY CLASSIFICATION: 13D DENSITY: .05 gpm/sq. ft. AREA OF APPLICATION: 512 sq. ft. COVERAGE PER SPRINKLER: 256 sq. ft. NUMBER OF SPRINKLERS CALCULATED: 2 sprinklers TOTAL SPRINKLER WATER FLOW REQUIRED: 26.3 gpm TOTAL WATER REQUIRED (including hose): 31.3 gpm FLOW AND PRESSURE (@ BOR): 26.3 gpm @ 26.9 psi SPRINKLER ORIFICE SIZE: 1/2 inch NAME OF CONTRACTOR:CFB DESIGN/LAYOUT BY: BB AUTHORITY HAVING JURISDICTION: RIV. CO. FIRE CONTRACTOR CERTIFICATION NUMBER: 68786 CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 64616744 ) HRS SYSTEMS, INC. SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 9/27/2022 C:\USERS\CHARLES BROWN\DEWEYLOT216TWOHDSDF.SDF JOB TITLE: WATER SUPPLY ANALYSIS Static: 63.64 psi Resid: 40.17 psi Flow: 30.0 gpm -14.7 0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 20 30 40 50 60 70 80 90 100 FLOW (GPM) Note: (1) Dashed Lines indicate extrapolated values from Test Results G A U G E P R E S S U R E ( p s i ) A 1 2 B LEGEND 1 Available pressure 38.23 psi @ 31.3 gpm 2 Required pressure 34.23 psi @ 31.3 gpm A. Source Supply Curve B. System Demand Curve SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 9/27/2022 C:\USERS\CHARLES BROWN\DEWEYLOT216TWOHDSDF.SDF JOB TITLE: NFPA WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) SOURCE 63.6 40.2 30.0 38.2 31.3 34.2 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 31.3 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM OTHER HOSE STREAM ALLOWANCES 5.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.3 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES (FT) (PSI) (GPM) 1 22.0 - - - - 8.8 - - - 2 22.0 K= 4.90 7.0 13.0 3 22.0 K= 4.90 7.3 13.3 4 22.0 - - - - 8.8 - - - 5 22.0 - - - - 9.7 - - - 6 22.0 - - - - 10.0 - - - 7 22.0 - - - - 10.1 - - - 8 22.0 - - - - 10.2 - - - 9 22.0 - - - - 10.1 - - - 10 22.0 - - - - 10.0 - - - 11 22.0 - - - - 10.5 - - - 12 10.0 - - - - 15.3 - - - 13 10.0 - - - - 15.2 - - - 14 10.0 - - - - 15.3 - - - 15 10.0 - - - - 15.5 - - - 16 10.0 - - - - 15.5 - - - 17 10.0 - - - - 15.6 - - - 18 10.0 - - - - 15.6 - - - 19 10.0 - - - - 15.7 - - - 20 10.0 - - - - 15.7 - - - 21 10.0 - - - - 16.0 - - - 22 10.0 - - - - 15.9 - - - 23 10.0 - - - - 16.9 - - - 24 10.0 - - - - 15.5 - - - T 10.0 - - - - 17.8 - - - TOR 10.0 - - - - 20.5 - - - CV1 5.0 - - - - 23.3 - - - CV2 5.0 - - - - 23.4 - - - BOR -0.5 HOSE STREAM 26.9 5.0 MTR1 -0.5 - - - - 31.6 - - - MTR2 -0.5 - - - - 31.8 - - - SOURCE 0.0 SOURCE 34.2 31.3 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 9/27/2022 C:\USERS\CHARLES BROWN\DEWEYLOT216TWOHDSDF.SDF JOB TITLE: NFPA5 PIPE DATA Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 1 0.0 0.0 18.25 150 0.0 4 22.0 8.8 0.0 1.000 E: 7.0 7.00 -0.0 1 22.0 8.8 0.0 1.101 25.25 0.000 0.0 Pipe: 2 4.90 13.0 Disch 10.00 150 0.3 3 22.0 7.3 0.0 1.000 ---- 0.00 -0.0 2 22.0 7.0 13.0 1.101 10.00 0.031 0.3 Pipe: 3 4.90 13.3 Disch 7.00 150 1.5 4 22.0 8.8 13.0 1.000 T: 6.0 6.00 -0.0 3 22.0 7.3 26.3 1.101 13.00 0.113 1.5 Pipe: 4 0.0 26.3 3 8.00 150 0.9 5 22.0 9.7 -0.0 1 1.000 ---- 0.00 -0.0 4 22.0 8.8 26.3 1.101 8.00 0.113 0.9 Pipe: 5 0.0 26.3 4 10.50 150 0.3 6 22.0 10.0 -15.9 1.000 T: 6.0 6.00 -0.0 5 22.0 9.7 10.4 1.101 16.50 0.020 0.3 Pipe: 6 0.0 10.4 5 21.50 150 0.0 7 22.0 10.1 -8.5 1.000 E: 7.0 13.00 -0.0 6 22.0 10.0 1.8 1.101 T: 6.0 34.50 0.001 0.0 Pipe: 7 0.0 2.2 9 21.00 150 0.1 8 22.0 10.2 1.8 6 1.000 2E:14.0 14.00 -0.0 7 22.0 10.1 4.1 1.101 35.00 0.004 0.1 Pipe: 8 0.0 10.4 5 21.00 150 0.5 11 22.0 10.5 -1.8 1.000 2E:14.0 14.00 -0.0 6 22.0 10.0 8.5 1.101 35.00 0.014 0.5 Pipe: 9 0.0 5.6 10 12.66 150 0.0 7 22.0 10.1 -3.4 1.000 T: 6.0 6.00 -0.0 9 22.0 10.1 2.2 1.101 18.66 0.001 0.0 Pipe: 10 0.0 9.6 5 10.00 150 0.1 9 22.0 10.1 -4.0 1.000 ---- 0.00 -0.0 10 22.0 10.0 5.6 1.101 10.00 0.007 0.1 Pipe: 11 0.0 26.3 4 9.50 150 0.3 10 22.0 10.0 -16.7 1.000 T: 6.0 6.00 -0.0 5 22.0 9.7 9.6 1.101 15.50 0.018 0.3 Pipe: 12 0.0 26.3 4 17.50 150 5.5 13 10.0 15.2 -20.0 1.000 2E:14.0 14.00 5.2 5 22.0 9.7 6.3 1.101 31.50 0.008 0.3 Pipe: 13 0.0 9.6 5 17.50 150 5.3 12 10.0 15.3 -5.6 1.000 2E:14.0 14.00 5.2 10 22.0 10.0 4.0 1.101 31.50 0.003 0.1 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 9/27/2022 C:\USERS\CHARLES BROWN\DEWEYLOT216TWOHDSDF.SDF JOB TITLE: Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 14 0.0 5.6 10 17.50 150 5.3 14 10.0 15.3 -2.2 1.000 2E:14.0 14.00 5.2 9 22.0 10.1 3.4 1.101 31.50 0.003 0.1 Pipe: 15 0.0 0.0 46.50 150 0.2 15 10.0 15.5 3.4 9 1.000 E: 7.0 13.00 -0.0 14 10.0 15.3 3.4 1.101 T: 6.0 59.50 0.003 0.2 Pipe: 16 0.0 0.0 35.50 150 0.2 15 10.0 15.5 4.0 10 1.000 2E:14.0 20.00 -0.0 12 10.0 15.3 4.0 1.101 T: 6.0 55.50 0.003 0.2 Pipe: 17 0.0 0.0 34.50 150 0.3 16 10.0 15.5 6.3 5 1.000 T: 6.0 6.00 -0.0 13 10.0 15.2 6.3 1.101 40.50 0.008 0.3 Pipe: 18 0.0 4.0 12 11.79 150 0.0 16 10.0 15.5 3.4 14 1.000 ---- 0.00 -0.0 15 10.0 15.5 1.3 1.101 11.79 0.000 0.0 Pipe: 19 0.0 1.3 15 5.00 150 0.1 17 10.0 15.6 6.3 13 1.000 T: 6.0 6.00 -0.0 16 10.0 15.5 7.5 1.101 11.00 0.011 0.1 Pipe: 20 0.0 6.1 15 11.79 150 0.0 17 10.0 15.6 -2.8 1.000 T: 6.0 6.00 -0.0 18 10.0 15.6 3.3 1.101 17.79 0.002 0.0 Pipe: 21 0.0 4.0 12 5.00 150 0.1 18 10.0 15.6 3.4 14 1.000 T: 6.0 6.00 -0.0 15 10.0 15.5 6.1 1.101 11.00 0.008 0.1 Pipe: 22 0.0 6.1 15 35.00 150 0.1 19 10.0 15.7 -3.3 1.000 4E:28.0 34.00 -0.0 18 10.0 15.6 2.8 1.101 T: 6.0 69.00 0.002 0.1 Pipe: 23 0.0 0.0 15.00 150 0.0 20 10.0 15.7 2.8 18 1.000 ---- 0.00 -0.0 19 10.0 15.7 2.8 1.101 15.00 0.002 0.0 Pipe: 24 0.0 0.0 141.00 150 0.3 21 10.0 16.0 2.8 19 1.000 4E:28.0 28.00 -0.0 20 10.0 15.7 2.8 1.101 169.00 0.002 0.3 Pipe: 25 0.0 10.9 17 54.00 150 0.1 21 10.0 16.0 -8.2 1.000 T: 6.0 6.00 -0.0 22 10.0 15.9 2.7 1.101 60.00 0.002 0.1 Pipe: 26 0.0 3.3 18 8.00 150 0.3 22 10.0 15.9 7.5 16 1.000 T: 6.0 6.00 -0.0 17 10.0 15.6 10.9 1.101 14.00 0.022 0.3 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 9/27/2022 C:\USERS\CHARLES BROWN\DEWEYLOT216TWOHDSDF.SDF JOB TITLE: Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 27 0.0 10.9 17 65.00 150 1.0 23 10.0 16.9 -2.7 1.000 E: 7.0 13.00 -0.0 22 10.0 15.9 8.2 1.101 T: 6.0 78.00 0.013 1.0 Pipe: 28 0.0 2.7 22 66.0 78.66 150 0.9 23 10.0 16.9 2.8 20 1.000 66.00 -0.0 21 10.0 16.0 5.5 1.101 144.66 0.006 0.9 Pipe: 29 0.0 5.5 21 26.50 150 0.9 T 10.0 17.8 8.2 22 1.000 ---- 0.00 -0.0 23 10.0 16.9 13.7 1.101 26.50 0.034 0.9 Pipe: 30 0.0 0.0 21.50 150 5.3 24 10.0 15.5 4.1 7 1.000 2T:12.0 12.00 5.2 8 22.0 10.2 4.1 1.101 33.50 0.004 0.1 Pipe: 31 0.0 0.0 42.50 150 -5.0 11 22.0 10.5 4.1 8 1.000 2E:14.0 20.00 -5.2 24 10.0 15.5 4.1 1.101 T: 6.0 62.50 0.004 0.2 Pipe: 32 0.0 4.1 24 53.00 150 7.3 T 10.0 17.8 8.5 6 1.000 E: 7.0 19.00 5.2 11 22.0 10.5 12.6 1.101 2T:12.0 72.00 0.029 2.1 Pipe: 33 0.0 12.6 11 10.00 150 2.7 TOR 10.0 20.5 13.7 23 1.000 2E:14.0 14.00 -0.0 T 10.0 17.8 26.3 1.101 24.00 0.113 2.7 Pipe: 34 0.0 0.0 5.00 150 2.7 CV1 5.0 23.3 26.3 T 1.000 ---- 0.00 2.2 TOR 10.0 20.5 26.3 1.101 5.00 0.113 0.6 Pipe: 35 0.0 0.0 1.00 150 0.1 CV2 5.0 23.4 26.3 TOR 1.000 ---- 0.00 -0.0 CV1 5.0 23.3 26.3 1.101 1.00 0.113 0.1 Pipe: 36 0.0 0.0 5.50 140 3.5 BOR -0.5 26.9 26.3 CV1 1.000 E: 3.4 3.35 2.4 CV2 5.0 23.4 26.3 1.100 8.85 0.129 1.1 Pipe: 37 H.S. 5.0 Disch 80.00 140 4.7 MTR1 -0.5 31.6 26.3 CV2 1.250 ---- 0.00 -0.0 BOR -0.5 26.9 31.3 1.380 80.00 0.059 4.7 Pipe: 38 0.0 0.0 1.00 140 0.2 MTR2 -0.5 31.8 31.3 BOR 1.000 ---- 0.00 -0.0 MTR1 -0.5 31.6 31.3 1.049 1.00 0.224 0.2 Pipe: 39 Source 0.0 5.00 140 2.4 SOURCE 0.0 34.2 31.3 MTR1 1.000 T: 6.6 6.65 -0.2 MTR2 -0.5 31.8 31.3 1.049 11.65 0.224 2.6 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 9/27/2022 C:\USERS\CHARLES BROWN\DEWEYLOT216TWOHDSDF.SDF JOB TITLE: NOTES (HASS): (1) Calculations were performed by the HASS 2021 D computer program in accordance with NFPA13 (2020) under license no. 64616744 granted by HRS Systems, Inc. 208 Southside Square Petersburg, TN 37144 (931) 659-9760 (2) The system has been calculated to provide an average imbalance at each node of 0.004 gpm and a maximum imbalance at any node of 0.120 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 11.6 ft/sec at pipe 39. (4) Items listed in bold print on the cover sheet are automatically transferred from the calculation report. (5) Available pressure at source node SOURCE under full flow conditions is 36.37 psi with a flow of 32.54 gpm. (6) PIPE FITTINGS TABLE HASS Pipe Table Name: standard PAGE: A MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NTee -------------------------------------------------------- F F45Ell 1.049 2.00 5.00 2.00 5.00 6.00 1.00 10.00 2.00 5.00 1.00 1.380 3.00 6.00 2.00 7.00 6.00 1.00 10.00 10.00 6.00 1.50 PAGE: F MATERIAL: CPVC HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) F E T R K C G F45 Ell Tee RunT Kplg ChkVlv Gate 1.101 1.40 7.00 6.00 1.70 1.00 8.00 0.40 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 DATE: 9/27/2022 C:\USERS\CHARLES BROWN\DEWEYLOT216TWOHDSDF.SDF JOB TITLE: PAGE: * MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee -------------------------------------------------------- F F45Ell 1.100 2.52 6.30 2.52 6.30 7.56 1.26 12.60 2.52 6.30 1.26 , HYDRAULIC CALCULATIONS FOR DEWEY RES. LOT 216 53-343 VIA PALACIO ONE HEAD CALC. LA QUINTA, CA. 92263 FILE NUMBER: DATE: SEP 26, 2022 -DESIGN DATA- OCCUPANCY CLASSIFICATION: 13D DENSITY: .05 gpm/sq. ft. AREA OF APPLICATION: 400 sq. ft. COVERAGE PER SPRINKLER: 400 sq. ft. NUMBER OF SPRINKLERS CALCULATED: 1 sprinklers TOTAL SPRINKLER WATER FLOW REQUIRED: 20.0 gpm TOTAL WATER REQUIRED (including hose): 20.0 gpm FLOW AND PRESSURE (@ BOR): 20.0 gpm @ 33.2 psi SPRINKLER ORIFICE SIZE: 1/2 inch NAME OF CONTRACTOR:CFB DESIGN/LAYOUT BY: BB AUTHORITY HAVING JURISDICTION: RIV. CO. FIRE CONTRACTOR CERTIFICATION NUMBER: 68786 CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 64616744 ) HRS SYSTEMS, INC. SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 9/26/2022 C:\USERS\CHARLES BROWN\DEWEYLOT216ONEHDSDF.SDF JOB TITLE: WATER SUPPLY ANALYSIS Static: 63.64 psi Resid: 40.17 psi Flow: 30.0 gpm -14.7 0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 20 30 40 50 60 70 80 90 100 FLOW (GPM) Note: (1) Dashed Lines indicate extrapolated values from Test Results G A U G E P R E S S U R E ( p s i ) A 1 2 B LEGEND 1 Available pressure 52.53 psi @ 20.0 gpm 2 Required pressure 36.24 psi @ 20.0 gpm A. Source Supply Curve B. System Demand Curve SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 9/26/2022 C:\USERS\CHARLES BROWN\DEWEYLOT216ONEHDSDF.SDF JOB TITLE: NFPA WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) SOURCE 63.6 40.2 30.0 52.5 20.0 36.2 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 20.0 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 20.0 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES (FT) (PSI) (GPM) 1 22.0 K= 4.90 16.7 20.0 2 22.0 - - - - 18.4 - - - 3 22.0 - - - - 18.4 - - - 4 22.0 - - - - 18.4 - - - 5 22.0 - - - - 18.9 - - - 6 22.0 - - - - 19.1 - - - 7 22.0 - - - - 19.1 - - - 8 22.0 - - - - 19.2 - - - 9 22.0 - - - - 19.1 - - - 10 22.0 - - - - 19.1 - - - 11 22.0 - - - - 19.4 - - - 12 10.0 - - - - 24.4 - - - 13 10.0 - - - - 24.3 - - - 14 10.0 - - - - 24.4 - - - 15 10.0 - - - - 24.5 - - - 16 10.0 - - - - 24.5 - - - 17 10.0 - - - - 24.5 - - - 18 10.0 - - - - 24.5 - - - 19 10.0 - - - - 24.6 - - - 20 10.0 - - - - 24.6 - - - 21 10.0 - - - - 24.8 - - - 22 10.0 - - - - 24.7 - - - 23 10.0 - - - - 25.3 - - - 24 10.0 - - - - 24.5 - - - T 10.0 - - - - 25.9 - - - TOR 10.0 - - - - 27.5 - - - CV1 5.0 - - - - 30.0 - - - CV2 5.0 - - - - 30.1 - - - BOR -0.5 - - - - 33.2 - - - MTR1 -0.5 - - - - 35.2 - - - MTR2 -0.5 - - - - 35.3 - - - SOURCE 0.0 SOURCE 36.2 20.0 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 9/26/2022 C:\USERS\CHARLES BROWN\DEWEYLOT216ONEHDSDF.SDF JOB TITLE: NFPA5 PIPE DATA Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 1 4.90 20.0 Disch 18.25 150 1.7 4 22.0 18.4 0.0 1.000 E: 7.0 7.00 -0.0 1 22.0 16.7 20.0 1.101 25.25 0.068 1.7 Pipe: 2 0.0 0.0 10.00 150 0.0 3 22.0 18.4 0.0 1.000 ---- 0.00 -0.0 2 22.0 18.4 0.0 1.101 10.00 0.000 0.0 Pipe: 3 0.0 0.0 7.00 150 0.0 4 22.0 18.4 0.0 1.000 T: 6.0 6.00 -0.0 3 22.0 18.4 0.0 1.101 13.00 0.000 0.0 Pipe: 4 0.0 0.0 8.00 150 0.5 5 22.0 18.9 20.0 3 1.000 ---- 0.00 -0.0 4 22.0 18.4 20.0 1.101 8.00 0.068 0.5 Pipe: 5 0.0 20.0 4 10.50 150 0.2 6 22.0 19.1 -12.1 1.000 T: 6.0 6.00 -0.0 5 22.0 18.9 7.9 1.101 16.50 0.012 0.2 Pipe: 6 0.0 7.9 5 21.50 150 0.0 7 22.0 19.1 -6.5 1.000 E: 7.0 13.00 -0.0 6 22.0 19.1 1.4 1.101 T: 6.0 34.50 0.000 0.0 Pipe: 7 0.0 1.7 9 21.00 150 0.1 8 22.0 19.2 1.4 6 1.000 2E:14.0 14.00 -0.0 7 22.0 19.1 3.1 1.101 35.00 0.002 0.1 Pipe: 8 0.0 7.9 5 21.00 150 0.3 11 22.0 19.4 -1.4 1.000 2E:14.0 14.00 -0.0 6 22.0 19.1 6.5 1.101 35.00 0.009 0.3 Pipe: 9 0.0 4.3 10 12.66 150 0.0 7 22.0 19.1 -2.6 1.000 T: 6.0 6.00 -0.0 9 22.0 19.1 1.7 1.101 18.66 0.001 0.0 Pipe: 10 0.0 7.3 5 10.00 150 0.0 9 22.0 19.1 -3.0 1.000 ---- 0.00 -0.0 10 22.0 19.1 4.3 1.101 10.00 0.004 0.0 Pipe: 11 0.0 20.0 4 9.50 150 0.2 10 22.0 19.1 -12.7 1.000 T: 6.0 6.00 -0.0 5 22.0 18.9 7.3 1.101 15.50 0.011 0.2 Pipe: 12 0.0 20.0 4 17.50 150 5.4 13 10.0 24.3 -15.2 1.000 2E:14.0 14.00 5.2 5 22.0 18.9 4.8 1.101 31.50 0.005 0.2 Pipe: 13 0.0 7.3 5 17.50 150 5.3 12 10.0 24.4 -4.3 1.000 2E:14.0 14.00 5.2 10 22.0 19.1 3.0 1.101 31.50 0.002 0.1 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 9/26/2022 C:\USERS\CHARLES BROWN\DEWEYLOT216ONEHDSDF.SDF JOB TITLE: Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 14 0.0 4.3 10 17.50 150 5.2 14 10.0 24.4 -1.7 1.000 2E:14.0 14.00 5.2 9 22.0 19.1 2.6 1.101 31.50 0.002 0.0 Pipe: 15 0.0 0.0 46.50 150 0.1 15 10.0 24.5 2.6 9 1.000 E: 7.0 13.00 -0.0 14 10.0 24.4 2.6 1.101 T: 6.0 59.50 0.002 0.1 Pipe: 16 0.0 0.0 35.50 150 0.1 15 10.0 24.5 3.0 10 1.000 2E:14.0 20.00 -0.0 12 10.0 24.4 3.0 1.101 T: 6.0 55.50 0.002 0.1 Pipe: 17 0.0 0.0 34.50 150 0.2 16 10.0 24.5 4.8 5 1.000 T: 6.0 6.00 -0.0 13 10.0 24.3 4.8 1.101 40.50 0.005 0.2 Pipe: 18 0.0 3.0 12 11.79 150 0.0 16 10.0 24.5 2.6 14 1.000 ---- 0.00 -0.0 15 10.0 24.5 1.0 1.101 11.79 0.000 0.0 Pipe: 19 0.0 1.0 15 5.00 150 0.1 17 10.0 24.5 4.8 13 1.000 T: 6.0 6.00 -0.0 16 10.0 24.5 5.7 1.101 11.00 0.007 0.1 Pipe: 20 0.0 4.7 15 11.79 150 0.0 17 10.0 24.5 -2.1 1.000 T: 6.0 6.00 -0.0 18 10.0 24.5 2.5 1.101 17.79 0.001 0.0 Pipe: 21 0.0 3.0 12 5.00 150 0.1 18 10.0 24.5 2.6 14 1.000 T: 6.0 6.00 -0.0 15 10.0 24.5 4.7 1.101 11.00 0.005 0.1 Pipe: 22 0.0 4.7 15 35.00 150 0.1 19 10.0 24.6 -2.5 1.000 4E:28.0 34.00 -0.0 18 10.0 24.5 2.1 1.101 T: 6.0 69.00 0.001 0.1 Pipe: 23 0.0 0.0 15.00 150 0.0 20 10.0 24.6 2.1 18 1.000 ---- 0.00 -0.0 19 10.0 24.6 2.1 1.101 15.00 0.001 0.0 Pipe: 24 0.0 0.0 141.00 150 0.2 21 10.0 24.8 2.1 19 1.000 4E:28.0 28.00 -0.0 20 10.0 24.6 2.1 1.101 169.00 0.001 0.2 Pipe: 25 0.0 8.3 17 54.00 150 0.1 21 10.0 24.8 -6.2 1.000 T: 6.0 6.00 -0.0 22 10.0 24.7 2.1 1.101 60.00 0.001 0.1 Pipe: 26 0.0 2.5 18 8.00 150 0.2 22 10.0 24.7 5.7 16 1.000 T: 6.0 6.00 -0.0 17 10.0 24.5 8.3 1.101 14.00 0.013 0.2 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 9/26/2022 C:\USERS\CHARLES BROWN\DEWEYLOT216ONEHDSDF.SDF JOB TITLE: Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 27 0.0 8.3 17 65.00 150 0.6 23 10.0 25.3 -2.1 1.000 E: 7.0 13.00 -0.0 22 10.0 24.7 6.2 1.101 T: 6.0 78.00 0.008 0.6 Pipe: 28 0.0 2.1 22 66.0 78.66 150 0.5 23 10.0 25.3 2.1 20 1.000 66.00 -0.0 21 10.0 24.8 4.2 1.101 144.66 0.004 0.5 Pipe: 29 0.0 4.2 21 26.50 150 0.5 T 10.0 25.9 6.2 22 1.000 ---- 0.00 -0.0 23 10.0 25.3 10.4 1.101 26.50 0.020 0.5 Pipe: 30 0.0 0.0 21.50 150 5.3 24 10.0 24.5 3.1 7 1.000 2T:12.0 12.00 5.2 8 22.0 19.2 3.1 1.101 33.50 0.002 0.1 Pipe: 31 0.0 0.0 42.50 150 -5.1 11 22.0 19.4 3.1 8 1.000 2E:14.0 20.00 -5.2 24 10.0 24.5 3.1 1.101 T: 6.0 62.50 0.002 0.1 Pipe: 32 0.0 3.1 24 53.00 150 6.5 T 10.0 25.9 6.5 6 1.000 E: 7.0 19.00 5.2 11 22.0 19.4 9.6 1.101 2T:12.0 72.00 0.017 1.3 Pipe: 33 0.0 9.6 11 10.00 150 1.6 TOR 10.0 27.5 10.4 23 1.000 2E:14.0 14.00 -0.0 T 10.0 25.9 20.0 1.101 24.00 0.068 1.6 Pipe: 34 0.0 0.0 5.00 150 2.5 CV1 5.0 30.0 20.0 T 1.000 ---- 0.00 2.2 TOR 10.0 27.5 20.0 1.101 5.00 0.068 0.3 Pipe: 35 0.0 0.0 1.00 150 0.1 CV2 5.0 30.1 20.0 TOR 1.000 ---- 0.00 -0.0 CV1 5.0 30.0 20.0 1.101 1.00 0.068 0.1 Pipe: 36 0.0 0.0 5.50 140 3.1 BOR -0.5 33.2 20.0 CV1 1.000 E: 3.4 3.35 2.4 CV2 5.0 30.1 20.0 1.100 8.85 0.078 0.7 Pipe: 37 0.0 0.0 80.00 140 2.1 MTR1 -0.5 35.2 20.0 CV2 1.250 ---- 0.00 -0.0 BOR -0.5 33.2 20.0 1.380 80.00 0.026 2.1 Pipe: 38 0.0 0.0 1.00 140 0.1 MTR2 -0.5 35.3 20.0 BOR 1.000 ---- 0.00 -0.0 MTR1 -0.5 35.2 20.0 1.049 1.00 0.098 0.1 Pipe: 39 Source 0.0 5.00 140 0.9 SOURCE 0.0 36.2 20.0 MTR1 1.000 T: 6.6 6.65 -0.2 MTR2 -0.5 35.3 20.0 1.049 11.65 0.098 1.1 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 9/26/2022 C:\USERS\CHARLES BROWN\DEWEYLOT216ONEHDSDF.SDF JOB TITLE: NOTES (HASS): (1) Calculations were performed by the HASS 2021 D computer program in accordance with NFPA13 (2020) under license no. 64616744 granted by HRS Systems, Inc. 208 Southside Square Petersburg, TN 37144 (931) 659-9760 (2) The system has been calculated to provide an average imbalance at each node of 0.003 gpm and a maximum imbalance at any node of 0.090 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 7.4 ft/sec at pipe 39. (4) Items listed in bold print on the cover sheet are automatically transferred from the calculation report. (5) Available pressure at source node SOURCE under full flow conditions is 47.96 psi with a flow of 24.12 gpm. (6) PIPE FITTINGS TABLE HASS Pipe Table Name: standard PAGE: A MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NTee -------------------------------------------------------- F F45Ell 1.049 2.00 5.00 2.00 5.00 6.00 1.00 10.00 2.00 5.00 1.00 1.380 3.00 6.00 2.00 7.00 6.00 1.00 10.00 10.00 6.00 1.50 PAGE: F MATERIAL: CPVC HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) F E T R K C G F45 Ell Tee RunT Kplg ChkVlv Gate 1.101 1.40 7.00 6.00 1.70 1.00 8.00 0.40 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 DATE: 9/26/2022 C:\USERS\CHARLES BROWN\DEWEYLOT216ONEHDSDF.SDF JOB TITLE: PAGE: * MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee -------------------------------------------------------- F F45Ell 1.100 2.52 6.30 2.52 6.30 7.56 1.26 12.60 2.52 6.30 1.26 , HYDRAULIC CALCULATIONS FOR DEWEY RES. LOT 216 53-343 VIA PALACIO REV TWO HEAD CALC. LA QUINTA, CA. 92263 FILE NUMBER: DATE: SEP 26, 2022 -DESIGN DATA- OCCUPANCY CLASSIFICATION: 13D DENSITY: .05 gpm/sq. ft. AREA OF APPLICATION: 512 sq. ft. COVERAGE PER SPRINKLER: 256 sq. ft. NUMBER OF SPRINKLERS CALCULATED: 2 sprinklers TOTAL SPRINKLER WATER FLOW REQUIRED: 26.1 gpm TOTAL WATER REQUIRED (including hose): 31.1 gpm FLOW AND PRESSURE (@ BOR): 26.1 gpm @ 23.7 psi SPRINKLER ORIFICE SIZE: 1/2 inch NAME OF CONTRACTOR:CFB DESIGN/LAYOUT BY: BB AUTHORITY HAVING JURISDICTION: RIV. CO. FIRE CONTRACTOR CERTIFICATION NUMBER: 68786 CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 64616744 ) HRS SYSTEMS, INC. SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 9/26/2022LES BROWN\DOCUMENTS\HASSDATA\REVDEWEY2161ST.FLR2HDFFFF.SDF JOB TITLE: WATER SUPPLY ANALYSIS Static: 63.64 psi Resid: 40.17 psi Flow: 30.0 gpm -14.7 0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 20 30 40 50 60 70 80 90 100 FLOW (GPM) Note: (1) Dashed Lines indicate extrapolated values from Test Results G A U G E P R E S S U R E ( p s i ) A 1 2 B LEGEND 1 Available pressure 38.51 psi @ 31.1 gpm 2 Required pressure 30.93 psi @ 31.1 gpm A. Source Supply Curve B. System Demand Curve SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 9/26/2022LES BROWN\DOCUMENTS\HASSDATA\REVDEWEY2161ST.FLR2HDFFFF.SDF JOB TITLE: NFPA WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) SOURCE 63.6 40.2 30.0 38.5 31.1 30.9 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 31.1 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM OTHER HOSE STREAM ALLOWANCES 5.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.1 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES (FT) (PSI) (GPM) 1 22.0 - - - - 7.5 - - - 2 22.0 - - - - 7.5 - - - 3 22.0 - - - - 7.5 - - - 4 22.0 - - - - 7.5 - - - 5 22.0 - - - - 7.5 - - - 6 22.0 - - - - 7.6 - - - 7 22.0 - - - - 7.6 - - - 8 22.0 - - - - 7.7 - - - 9 22.0 - - - - 7.5 - - - 10 22.0 - - - - 7.5 - - - 11 22.0 - - - - 8.0 - - - 12 10.0 - - - - 12.6 - - - 13 10.0 - - - - 12.6 - - - 14 10.0 - - - - 12.6 - - - 15 10.0 - - - - 12.5 - - - 16 10.0 - - - - 12.5 - - - 17 10.0 - - - - 12.5 - - - 18 10.0 - - - - 12.3 - - - 19 10.0 - - - - 10.2 - - - 20 10.0 - - - - 9.7 - - - 20A 10.0 K= 4.90 7.0 13.0 20B 10.0 K= 4.90 7.2 13.1 20C 10.0 - - - - 7.5 - - - 21 10.0 - - - - 12.1 - - - 22 10.0 - - - - 12.5 - - - 23 10.0 - - - - 13.5 - - - 24 10.0 - - - - 13.0 - - - T 10.0 - - - - 14.7 - - - TOR 10.0 - - - - 17.3 - - - CV1 5.0 - - - - 20.1 - - - CV2 5.0 - - - - 20.2 - - - BOR -0.5 HOSE STREAM 23.7 5.0 MTR1 -0.5 - - - - 28.3 - - - MTR2 -0.5 - - - - 28.6 - - - SOURCE 0.0 SOURCE 30.9 31.1 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 9/26/2022LES BROWN\DOCUMENTS\HASSDATA\REVDEWEY2161ST.FLR2HDFFFF.SDF JOB TITLE: NFPA5 PIPE DATA Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 1 0.0 0.0 18.25 150 0.0 4 22.0 7.5 0.0 1.000 E: 7.0 7.00 -0.0 1 22.0 7.5 0.0 1.101 25.25 0.000 0.0 Pipe: 2 0.0 0.0 10.00 150 0.0 3 22.0 7.5 0.0 1.000 ---- 0.00 -0.0 2 22.0 7.5 0.0 1.101 10.00 0.000 0.0 Pipe: 3 0.0 0.0 7.00 150 0.0 4 22.0 7.5 0.0 1.000 T: 6.0 6.00 -0.0 3 22.0 7.5 0.0 1.101 13.00 0.000 0.0 Pipe: 4 0.0 0.0 8.00 150 0.0 5 22.0 7.5 0.0 1.000 ---- 0.00 -0.0 4 22.0 7.5 0.0 1.101 8.00 0.000 0.0 Pipe: 5 0.0 3.8 13 10.50 150 0.1 6 22.0 7.6 -0.0 4 1.000 T: 6.0 6.00 -0.0 5 22.0 7.5 5.6 1.101 16.50 0.007 0.1 Pipe: 6 0.0 5.0 9 21.50 150 0.0 6 22.0 7.6 -3.5 1.000 E: 7.0 13.00 -0.0 7 22.0 7.6 1.4 1.101 T: 6.0 34.50 0.001 0.0 Pipe: 7 0.0 5.0 9 21.00 150 0.1 8 22.0 7.7 -1.4 1.000 2E:14.0 14.00 -0.0 7 22.0 7.6 3.5 1.101 35.00 0.003 0.1 Pipe: 8 0.0 1.4 7 21.00 150 0.3 11 22.0 8.0 5.6 5 1.000 2E:14.0 14.00 -0.0 6 22.0 7.6 7.0 1.101 35.00 0.010 0.3 Pipe: 9 0.0 3.4 14 12.66 150 0.1 7 22.0 7.6 1.6 10 1.000 T: 6.0 6.00 -0.0 9 22.0 7.5 5.0 1.101 18.66 0.005 0.1 Pipe: 10 0.0 3.4 12 10.00 150 0.0 9 22.0 7.5 -1.8 1.000 ---- 0.00 -0.0 10 22.0 7.5 1.6 1.101 10.00 0.001 0.0 Pipe: 11 0.0 3.4 12 9.50 150 0.0 5 22.0 7.5 -1.6 1.000 T: 6.0 6.00 -0.0 10 22.0 7.5 1.8 1.101 15.50 0.001 0.0 Pipe: 12 0.0 0.0 17.50 150 -5.1 5 22.0 7.5 3.8 16 1.000 2E:14.0 14.00 -5.2 13 10.0 12.6 3.8 1.101 31.50 0.003 0.1 Pipe: 13 0.0 0.0 17.50 150 -5.1 10 22.0 7.5 3.4 15 1.000 2E:14.0 14.00 -5.2 12 10.0 12.6 3.4 1.101 31.50 0.003 0.1 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 9/26/2022LES BROWN\DOCUMENTS\HASSDATA\REVDEWEY2161ST.FLR2HDFFFF.SDF JOB TITLE: Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 14 0.0 0.0 17.50 150 -5.1 9 22.0 7.5 3.4 15 1.000 2E:14.0 14.00 -5.2 14 10.0 12.6 3.4 1.101 31.50 0.003 0.1 Pipe: 15 0.0 7.7 18 46.50 150 0.1 14 10.0 12.6 -4.4 1.000 E: 7.0 13.00 -0.0 15 10.0 12.5 3.4 1.101 T: 6.0 59.50 0.003 0.1 Pipe: 16 0.0 7.7 18 35.50 150 0.1 12 10.0 12.6 -4.3 1.000 2E:14.0 20.00 -0.0 15 10.0 12.5 3.4 1.101 T: 6.0 55.50 0.003 0.1 Pipe: 17 0.0 2.9 17 34.50 150 0.1 13 10.0 12.6 1.0 15 1.000 T: 6.0 6.00 -0.0 16 10.0 12.5 3.8 1.101 40.50 0.003 0.1 Pipe: 18 0.0 7.7 18 11.79 150 0.0 16 10.0 12.5 -6.7 1.000 ---- 0.00 -0.0 15 10.0 12.5 1.0 1.101 11.79 0.000 0.0 Pipe: 19 0.0 5.5 18 5.00 150 0.0 16 10.0 12.5 -2.7 1.000 T: 6.0 6.00 -0.0 17 10.0 12.5 2.9 1.101 11.00 0.002 0.0 Pipe: 20 0.0 13.2 19 11.79 150 0.1 17 10.0 12.5 -7.7 1.000 T: 6.0 6.00 -0.0 18 10.0 12.3 5.5 1.101 17.79 0.006 0.1 Pipe: 21 0.0 13.2 19 5.00 150 0.1 15 10.0 12.5 -5.5 1.000 T: 6.0 6.00 -0.0 18 10.0 12.3 7.7 1.101 11.00 0.012 0.1 Pipe: 22 0.0 0.0 35.00 150 2.2 18 10.0 12.3 13.2 20 1.000 4E:28.0 34.00 -0.0 19 10.0 10.2 13.2 1.101 T: 6.0 69.00 0.032 2.2 Pipe: 23 0.0 0.0 15.00 150 0.5 19 10.0 10.2 13.2 20C 1.000 ---- 0.00 -0.0 20 10.0 9.7 13.2 1.101 15.00 0.032 0.5 Pipe: 24 0.0 0.0 48.50 150 2.2 20 10.0 9.7 13.2 1.000 3E:21.0 21.00 -0.0 20C 10.0 7.5 13.2 1.101 69.50 0.032 2.2 Pipe: 25 0.0 0.0 92.50 120 4.6 21 10.0 12.1 12.9 1.000 E: 2.5 8.86 -0.0 20C 10.0 7.5 12.9 1.101 T: 6.3 101.36 0.045 4.6 Pipe: 26 4.90 13.0 Disch 8.00 150 0.4 20C 10.0 7.5 0.0 1.000 T: 6.0 6.00 -0.0 20A 10.0 7.0 13.0 1.101 14.00 0.031 0.4 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 9/26/2022LES BROWN\DOCUMENTS\HASSDATA\REVDEWEY2161ST.FLR2HDFFFF.SDF JOB TITLE: Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 27 4.90 13.1 Disch 4.00 150 0.3 20C 10.0 7.5 0.0 1.000 T: 6.0 6.00 -0.0 20B 10.0 7.2 13.1 1.101 10.00 0.031 0.3 Pipe: 28 0.0 12.9 20C 54.00 150 0.4 22 10.0 12.5 -7.1 1.000 T: 6.0 6.00 -0.0 21 10.0 12.1 5.7 1.101 60.00 0.007 0.4 Pipe: 29 0.0 5.5 18 8.00 150 0.0 22 10.0 12.5 -2.9 1.000 T: 6.0 6.00 -0.0 17 10.0 12.5 2.7 1.101 14.00 0.002 0.0 Pipe: 30 0.0 2.7 17 65.00 150 1.1 23 10.0 13.5 5.7 21 1.000 E: 7.0 13.00 -0.0 22 10.0 12.5 8.4 1.101 T: 6.0 78.00 0.014 1.1 Pipe: 31 0.0 12.9 20C 66.0 78.66 150 1.5 23 10.0 13.5 -5.7 1.000 66.00 -0.0 21 10.0 12.1 7.1 1.101 144.66 0.010 1.5 Pipe: 32 0.0 7.1 21 26.50 150 1.1 T 10.0 14.7 8.4 22 1.000 ---- 0.00 -0.0 23 10.0 13.5 15.5 1.101 26.50 0.043 1.1 Pipe: 33 0.0 0.0 21.50 150 5.3 24 10.0 13.0 3.5 7 1.000 2T:12.0 12.00 5.2 8 22.0 7.7 3.5 1.101 33.50 0.003 0.1 Pipe: 34 0.0 0.0 42.50 150 -5.0 11 22.0 8.0 3.5 8 1.000 2E:14.0 20.00 -5.2 24 10.0 13.0 3.5 1.101 T: 6.0 62.50 0.003 0.2 Pipe: 35 0.0 3.5 24 53.00 150 6.7 T 10.0 14.7 7.0 6 1.000 E: 7.0 19.00 5.2 11 22.0 8.0 10.6 1.101 2T:12.0 72.00 0.021 1.5 Pipe: 36 0.0 10.6 11 10.00 150 2.7 TOR 10.0 17.3 15.5 23 1.000 2E:14.0 14.00 -0.0 T 10.0 14.7 26.1 1.101 24.00 0.111 2.7 Pipe: 37 0.0 0.0 5.00 150 2.7 CV1 5.0 20.1 26.1 T 1.000 ---- 0.00 2.2 TOR 10.0 17.3 26.1 1.101 5.00 0.111 0.6 Pipe: 38 0.0 0.0 1.00 150 0.1 CV2 5.0 20.2 26.1 TOR 1.000 ---- 0.00 -0.0 CV1 5.0 20.1 26.1 1.101 1.00 0.111 0.1 Pipe: 39 0.0 0.0 5.50 140 3.5 BOR -0.5 23.7 26.1 CV1 1.000 E: 3.4 3.35 2.4 CV2 5.0 20.2 26.1 1.100 8.85 0.127 1.1 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 9/26/2022LES BROWN\DOCUMENTS\HASSDATA\REVDEWEY2161ST.FLR2HDFFFF.SDF JOB TITLE: Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 40 H.S. 5.0 Disch 80.00 140 4.7 MTR1 -0.5 28.3 26.1 CV2 1.250 ---- 0.00 -0.0 BOR -0.5 23.7 31.1 1.380 80.00 0.058 4.7 Pipe: 41 0.0 0.0 1.00 140 0.2 MTR2 -0.5 28.6 31.1 BOR 1.000 ---- 0.00 -0.0 MTR1 -0.5 28.3 31.1 1.049 1.00 0.222 0.2 Pipe: 42 Source 0.0 5.00 140 2.4 SOURCE 0.0 30.9 31.1 MTR1 1.000 T: 6.6 6.65 -0.2 MTR2 -0.5 28.6 31.1 1.049 11.65 0.222 2.6 NOTES (HASS): (1) Calculations were performed by the HASS 2021 D computer program in accordance with NFPA13 (2020) under license no. 64616744 granted by HRS Systems, Inc. 208 Southside Square Petersburg, TN 37144 (931) 659-9760 (2) The system has been calculated to provide an average imbalance at each node of 0.002 gpm and a maximum imbalance at any node of 0.069 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 11.6 ft/sec at pipe 42. (4) Items listed in bold print on the cover sheet are automatically transferred from the calculation report. (5) Available pressure at source node SOURCE under full flow conditions is 35.13 psi with a flow of 33.33 gpm. (6) PIPE FITTINGS TABLE HASS Pipe Table Name: standard SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 DATE: 9/26/2022LES BROWN\DOCUMENTS\HASSDATA\REVDEWEY2161ST.FLR2HDFFFF.SDF JOB TITLE: PAGE: A MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NTee -------------------------------------------------------- F F45Ell 1.049 2.00 5.00 2.00 5.00 6.00 1.00 10.00 2.00 5.00 1.00 1.380 3.00 6.00 2.00 7.00 6.00 1.00 10.00 10.00 6.00 1.50 PAGE: F MATERIAL: CPVC HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) F E T R K C G F45 Ell Tee RunT Kplg ChkVlv Gate 1.101 1.40 7.00 6.00 1.70 1.00 8.00 0.40 PAGE: * MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee -------------------------------------------------------- F F45Ell 1.100 2.52 6.30 2.52 6.30 7.56 1.26 12.60 2.52 6.30 1.26 1.101 2.53 6.33 2.53 6.33 7.59 1.27 12.66 2.53 6.33 1.27 Residential Connectign Charee Estimalg November 29,202L CustomerName: Sunlite Development, lnc.760-310:e800 06-07-09-3 Block No. Tract No. Apts:t fr.tr Parcel ilo. Address: Lot No. Type of Service: . ,777-229-442, 53343 Via Palacio, La Quinta Sire of Lot: n Phone No. Geo. LID: 2:",344 Triplex: 29894-2 R-l:kl Duplex: SWSC: S *,375.3+ Acres: ft.43 swsc: $:"3,*:"1".** lacre 2,436.00 Treatment:$2,q16/edu coilection: 52,+L5/edu 4Str"*# WSBFC: $ SCC: $ Meter surcharge: $2,479.4O Meter Size: Service Sire: Meter: 5 inch 1 inch Service: $ Meter & Service; $ Stand Alone * CVWD USES WORST CASE CONDITION [andscape plans approved. Tract 29894-2, The Hideaway, Per special agreement no WSBFC, and only TFC of SCC. Per dwg 31129 a 1" Service line exisist & per dwg 31110 a sewer lateral exists. PZ 2L- 12899 CVWD System Data Service Connection** Max. Flow*= 30 8Pm lnletPressure'=W 0utlet Pressure= 4A.!7 psi Meter Size =1 inch Service Size=inch 1 Prior to Pressure Resulating Valve +* For Calculation Purposes- Selice Connection lncludes: Service Connection Pipe=L', Meter stop, Meter, Check Valve & Shut Off Valve Backflow: $ Other: $ Sewer Lateral: $ Total: $1L,748.39 lnformation Supplied By Customer Domestic Water Demand* Max. Flow= Min. Pressure= Fire Sprinkler Demand* Max. Flow= Min. Pressure= System Tvpe: Mulri [5 gpm 20 3{i gpm :5:x Technician : Nancy lYlqoz Fees Approved by: Jlt''e- elDate: Pz= HGL= RES.f= RES./Hr= PROP. ELEV.= Calculations: Lake Cahuilla 145 6725 32 14 Ps is OK oate: lLlLT llilAppoved by: 35 psi Max.flow ,'METER 1 TRY: Fire Sprinkler Demand etc,E 63.64 6.00 17.47 3O,OO GPM -- -S$E t0 *Eowlde s(:rvice2[,;4rU^ ,,SERVICE 60 psi 1 Ps= HL-meter5 The meter sizing is for plan check purposes only. Ihe ultimate responsibility resides with the Engineer-of-Record for the project. c 91 620 CAL FIRE - RIVERSIDE UNIT RIVERSIDE COUNTY FIRE DEPARTMENT *ILLWEISf,R * FIRE f,}"tIEF., OFFICE OF THE FIRE MARSHAL - LA QUINTA 78495 Calle Tampico, La Quinta, CA92253 r Phone QOq777-7074. www.rvclire,org &,&rtnfe < ('il.ll,ottNl/\ -_ November 6,2021 Sunlite Dev. 77622 Country Club Dr. #5 Palm Desert,CA92260 Re: Residential Fire Access & Water Plan Review - HIDEAWAY LOT 216 BRES2021-0491 I 53343 VIA PALACIO, LA QUINTA, CA92253 The plans you submitted for the above referenced project have been reviewed by Riverside County Fire Deparffnent - Office of the Fire Marshal personnel and are approved with the following conditions. 1) Properry/Unit Addressing shall be provided. Minimum 4-inch+all numbers of contrasting color to their background shall be displayed on the structure and viewable from the roadway or posted at the driveway entrance and maintained visible. 2) The proposed structure requires a fire flow of 1,375 gallons per minute from a single hydrant located within 600-feet of all exterior portions of the structure. (CFC 507.5.1 & APPENDIX B) 3) Public/Private fire hydrants located in front of the property shall be provided with a minimum 3-feet radius around the hydrant of clearance of any obstructions, including vegetation. 4) Dwelling Units shall maintain a minimum 3-feet clear width Egress Court from emergency escape windows and doors of sleeping rooms and shall deposit to the front of the properfy or public way. (Ref. CBC 1028.4 / CRC R311.1) 5) A Residential Fire Sprinkler system shall be installed in compliance with CRC R313. CA Licensed Contractor (C-16) shall submit plans and details for review and approval prior to system installation and Rough Inspections. The Fire Department approved plans and conditions letter must be at the job site. Applicant shall be responsible to contact the Fire Department to schedule inspections. Requests for inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7t31. All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal staffat (760)777-7A74. Kohl Hetrick - Fire Safety Specialist Series RFII — 5.6 K-factor “Royal Flush II” Concealed Pendent Sprinklers Quick & Standard Response, Standard Coverage Page 1 of 6 SEPTEMBER 2011 TFP181 IMPORTANT Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Technical Services 800-381-9312 +1-401-781-8220 www.tyco-fire.com General Description The TYCO Series RFII Quick Response (3-mm bulb) and Standard Response (5-mm bulb), 5.6 K-Factor, “Royal Flush II” Concealed Pendent Sprin- klers are decorative sprinklers featur- ing a flat cover plate designed to con- ceal the sprinkler. These sprinklers are optimal for architecturally sensitive ar- eas such as hotel lobbies, office build- ings, churches, and restaurants. Each sprinkler includes a Cover Plate/ Retainer Assembly and a Sprinkler/ Support Cup Assembly. The separa- ble, two-piece assembly design pro- vides the following benefits: • Allows installation of the sprinklers and pressure testing of the fire pro- tection system prior to installation of a suspended ceiling or application of the finish coating to a fixed ceiling. • Permits the removal of suspended ceiling panels for access to building service equipment without having to first shut down the fire protection system and remove sprinklers. • Provides for 1/2 inch (12,7 mm) of vertical adjustment to allow a mea- sure of flexibility in determining the length of fixed piping to cut for the sprinkler drops. The Series RFII Sprinklers are shipped with a Disposable Protective Cap. The Protective Cap is temporarily removed during installation and replaced to help protect the sprinkler during ceiling in- stallation or finish. The tip of the Pro- tective Cap can be used to mark the center of the ceiling hole into plaster board or ceiling tiles by gently push- ing the ceiling product against the Pro- tective Cap. When ceiling installation is complete, the Protective Cap is re- moved and the Cover Plate/Retainer Assembly is installed. As an option, the Series RFII Standard Response (5-mm bulb) “Royal Flush II” Concealed Pendent Sprinklers can be fitted with a silicone Air and Dust Seal. (Refer to Figure 5.) The Air and Dust Seal is intended for sensitive areas where it is desirable to prevent air and dust from the area above the ceiling to pass through the cover plate. NOTICE The Series RFII Concealed Pendent Sprinklers described herein must be installed and maintained in compli- ance with this document and with the applicable standards of the National Fire Protection Association, in addi- tion to the standards of any authori- ties having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Sprinkler Identification Number (SIN) TY3531 — 3 mm bulb TY3551 — 5 mm bulb TFP181 Page 2 of 6 Technical Data Sprinkler ApprovalsApprovals apply only to the service conditions indicated in the Design Criteria section. • TY3531 (3-mm Bulb) is UL Listed, C-UL Listed, VdS Approved (Certif- icate No. G4090007), and NYC Ap- proved (MEA 353-01-E) as Quick Response. • TY3531 (3-mm Bulb) is FM and LPCB Approved (Ref. No. 094a/10) Approved as Standard Response. Factory Mutual and LPCB do not approve any concealed sprinklers for quick response. • TY3551 (5-mm Bulb) is UL Listed, C-UL Listed, FM Approved, LPCB Approved (Ref. No. 094a/9), and NYC Approved (MEA 353-01-E) as Standard Response. Approvals for Air and Dust Seal UL and C-UL Listed for use with the RFII Standard Response Concealed Sprinkler (TY3551). Maximum Working Pressure Maximum 250 psi (17,3 bar) by UL, C-UL, and NYC Maximum 175 psi (12,1 bar) by FM, VdS, and LPCB Temperature Rating 155°F (68°C) Sprinkler with 139°F (59°C) Plate 200°F (93°C) Sprinkler with 165°F (74°C) Plate Discharge Coefficient K= 5.6 GPM/psi1/2 (80,6 LPM/bar1/2) Adjustment 1/2 inch (12,7 mm) Finishes See the Ordering Procedure section. Physical Characteristics Frame . . . . . . . . . . . . . . . . . . . Bronze Support Cup. . . . . . . . . . . . . .Chrome Plated Steel Guide Pins .........Stainless Steel Deflector .................Bronze Compression Screw . . . . . . . . . Brass Bulb ......................Glass Cap .............Bronze or Copper Sealing Assembly . . . . . . . . .Beryllium Nickel w/ TEFLON Cover Plate . . . . . . . . . . . . . . . . Brass Retainer . . . . . . . . . . . . . . . . . . Brass Ejection Spring ......Stainless Steel SPRINKLER/SUPPORT CUP ASSEMBLY COVER PLATE/RETAINER ASSEMBLY GUIDEPINS (2) DEFLECTOR (DROPPEDPOSITION) COMPRESSION SCREW DEFLECTOR SUPPORTCUP WITH ROLL FORMEDTHREADS FRAME 1/2" NPT CAP BULB SEALING ASSEMBLY RETAINERWITH THREAD DIMPLES EJECTION SPRING SOLDERTABS (3)COVERPLATE THREAD INTOSUPPORT CUP UNTIL MOUNTING SURFACE ISFLUSH WITH CEILING FIGURE 1 MODEL RFII CONCEALED SPRINKLER ASSEMBLY TFP181 Page 3 of 6 Design Criteria The TYCO Series RFII Concealed Pen- dent Sprinklers are intended for fire protection systems designed in ac- cordance with the standard instal- lation rules recognized by the appli- cable Listing or Approval agency; for example, UL Listing is based on NFPA 13 and VdS Approval is based on the CEA 4001. For more information on LPCB and VdS Approvals, contact Tyco Fire Sup- pression & Building Products at the following office: Enschede, Netherlands Telephone: 31-53-428-4444 Fax: 31-53-428-3377 The Series RFII Concealed Pendent Sprinklers are only listed and approved with the Series RFII Concealed Cover Plates having a factory applied finish. NOTICE Do not use the Series RFII in applica- tions where the air pressure above the ceiling is greater than that be- low. Down drafts through the Sprin- kler/Support Cup Assembly can delay sprinkler operation in a fire situation. Operation When exposed to heat from a fire, the Cover Plate, normally soldered to the Retainer at three points, falls away to expose the Sprinkler/Support Cup Assembly. The Deflector—supported by the Guide Pins—then drops down to its operational position. The glass Bulb contains a fluid that ex- pands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass Bulb, activating the sprinkler and allowing water to flow. COVER PLATE PROFILE DEPTH DIMENSION B 1/2" (12,7 mm) THREADED ADJUSTMENTD FACE OF SPRINKLER FITTING MANUFACTURER PRESET GAP 3/32" (2,4 mm) FACE OF CEILING, RETAINING RING MOUNTING SURFACE SPRINKLER SUPPORT CUP ASSEMBLY CLEARANCE HOLE DIAMETER DIMENSION C DEFLECTOR IN DROPPED POSITION 3/16" to 11/16" (4,8 to 17,5 mm) REFERENCE COVER PLATE RETAINER ASSEMBLY COVER PLATE DIAMETER DIMENSION A A: 3-1/4 inches (82,6 mm)C: 2-3/8 to 2-5/8 inches (60,3 to 66,7 mm) B: 3/16 inches (4,8 mm)D: 1-3/4 to 2-1/4 inches (44,5 to 57,2 mm) FIGURE 2 SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS TFP181 Page 4 of 6 CLEARANCE HOLE SUPPORT CUP SPRINKLER AIR AND DUST SEALCOVER PLATE LIP OF RETAINER FACE OF CEILING ORIENT SEAL BEVEL AS SHOWNCOVER PLATE RETAINER ASSEMBLY FIGURE 5 OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551) FRAME ARM SUPPORT CUP 7/8" (23 mm) SQUARE ACCEPTS 1/2" SOCKET DRIVE ALIGN ARROWS WITH FRAME ARMS FIGURE 3 RFII SPRINKLER WRENCH FIGURE 4 DISPOSABLE PROTECTIVE CAP TFP181 Page 5 of 6 Installation The TYCO Series RFII must be in- stalled in accordance with the follow- ing instructions. NOTICE Do not install any bulb-type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bub- ble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm) for the 155°F/68°C and 3/32 inch (2,4 mm) for the 200°F/93°C temperature ratings. Obtain a 1/2 inch NPT sprinkler joint by applying a minimum to maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels of torque can dis- tort the sprinkler Inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for in- sufficient adjustment in the Sprinkler by under- or over-tightening the Sprin- kler/Support Cup Assembly. Re-adjust the position of the sprinkler fitting to suit. Step 1. Install the sprinkler only in the pendent position with the center-line of the sprinkler perpendicular to the mounting surface. Step 2. Remove the Protective Cap. Step 3. With pipe thread sealant ap- plied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting. Step 4. Wrench-tighten the sprinkler using only the RFII Sprinkler Wrench. (Refer to Figure 3.) Apply the RFII Sprinkler Wrench to the Sprinkler as shown in Figure 3. Step 5. Replace the Protective Cap by pushing it upwards until it bottoms out against the Support Cup. (Refer to Figure 4.) The Protective Cap helps prevent damage to the Deflector and Arms during ceiling installation and/or finish. You can also use the Protective Cap to locate the center of the clear- ance hole by gently pushing the ceiling material up against the center point of the Protective Cap. NOTICE As long as the Protective Cap remains in place, the system is considered “Out of Service”. Step 6. After the ceiling has been com- pleted with the 2-1/2 inch (63,5 mm) di- ameter clearance hole and in prepa- ration for installing the Cover Plate/ Retainer Assembly, remove and dis- card the Protective Cap. Verify that the Deflector moves up and down freely. If the Sprinkler is damaged and the Deflector does not move up and down freely, replace the entire Sprinkler. Do not attempt to modify or repair a damaged sprinkler. Step 7. When installing an Air and Dust Seal, refer to Figure 5; otherwise, pro- ceed to Step 8. To attach the Air and Dust Seal, verify the angle of the out- side edge of the seal is oriented ac- cording to Figure 5. Start the edge of the Retainer in the grooved slot of the Air and Dust Seal and continue around the retainer until the entire Air and Dust Seal is engaged. Step 8. Screw on the Cover Plate/ Retainer Assembly until the Retainer (shown in Figure 2) or the Air and Dust Seal (shown in Figure 5) contacts the ceiling. Do not continue to screw on the Cover Plate/Retainer Assembly so that it lifts a ceiling panel out of its normal position. If you cannot engage the Cover Plate/Retainer Assembly with the Support Cup or you cannot engage the Cover Plate/Retainer As- sembly sufficiently to contact the ceil- ing, you must reposition the Sprinkler Fitting. Care and Maintenance The TYCO Series RFII must be maintained and serviced in accordance with the following instructions. NOTICE Before closing a fire protection sys- tem main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection sys- tem from the proper authorities and no- tify all personnel who may be affected by this action. Absence of the Cover Plate/Retainer Assembly can delay sprinkler opera- tion in a fire situation. When properly installed, there is a nominal 3/32 inch (2,4 mm) air gap be- tween the lip of the Cover Plate and the ceiling, as shown in Figure 2. This air gap is necessary for proper operation of the sprinkler. If the ceil- ing requires repainting after sprinkler installation, ensure that the new paint does not seal off any of the air gap. Do not pull the Cover Plate relative to the Enclosure. Separation may result. Replace sprinklers that: • are leaking or exhibiting visible signs of corrosion. • were modified or over-heated. Never paint, plate, coat, or otherwise alter automatic sprinklers after they leave the factory. Never repaint facto- ry-painted Cover Plates. If necessary, replace them with factory-painted units. Non-factory applied paint can adversely delay or prevent sprinkler operation in the event of a fire. Exercise care to avoid damage to sprinklers before, during, and after in- stallation. Replace sprinklers damaged by dropping, striking, wrench twisting, wrench slipping, or the like. Also, re- place any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Refer to the Installation section.) If you must remove a sprinkler, do not reinstall it or a replacement without re- installing the Cover Plate/Retainer As- sembly. If a Cover Plate/Retainer As- sembly becomes dislodged during service, replace it immediately. Responsibility lies with sprinkler own- ers for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (for exam- ple, NFPA 25), in addition to the stan- dards of any other authorities having jurisdiction. Contact the installing con- tractor or sprinkler manufacturer re- garding any questions. Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accor- dance with local requirements and/or national code. TFP181 Page 6 of 6 Copyright © 2008, 2011 Tyco Fire Protection Products. All rights reserved. TEFLON is trademark of The DuPont Corporation. Limited Warranty Products manufactured by Tyco Fire Protection Products (TFPP) are war- ranted solely to the original Buyer for ten (10) years against defects in ma- terial and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFPP. No warran- ty is given for products or components manufactured by companies not af- filiated by ownership with TFPP or for products and components which have been subject to misuse, improper in- stallation, corrosion, or which have not been installed, maintained, modified or repaired in accordance with applicable Standards of the National Fire Protec- tion Association, and/or the standards of any other Authorities Having Juris- diction. Materials found by TFPP to be defective shall be either repaired or re- placed, at TFPP’s sole option. TFPP neither assumes, nor authorizes any person to assume for it, any other ob- ligation in connection with the sale of products or parts of products. TFPP shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer’s representatives. In no event shall TFPP be liable, in contract, tort, strict liability or under any other legal theory, for inciden- tal, indirect, special or consequential damages, including but not limited to labor charges, regardless of whether TFPP was informed about the possibil- ity of such damages, and in no event shall TFPP’s liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, ex- press or implied, including warranties of merchantability and fitness for a particular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name. Sprinkler/Support Cup Assembly Specify: (SIN), (temperature rating from below) Series RFII Concealed Pendent Sprinkler, P/N (specify). 155°F/68°C 200°F/93°C TY3531 51-792-1-155 51-792-1-200 TY3551 51-790-1-155 51-790-1-200 Separately Ordered Cover Plate/ Retainer Assembly: Specify: (temperature rating from be- low) Series RFII Concealed Cover Plate with (finish), P/N (specify). 139°F/59°C(a) 165°F/74°C(b) Brass ..........56-792-1-135 56-792-1-165 Chrome ........56-792-9-135 56-792-9-165 Brushed Chrome ........56-792-8-135 56-792-8-165 Signal White (RAL 9003) ....56-792-4-135 56-792-4-165 Grey White (RAL 9002) ....56-792-0-135 56-792-0-165 Pure White (c) (RAL 9010) ....56-792-3-135 56-792-3-165 Custom ........56-792-X-135 56-792-X-165 (a) For use with 155°F/68°C sprinklers. (b) For use with 200°F/93°C sprinklers. (c) Eastern Hemisphere sales only. Sprinkler Wrench Specify: RFII Sprinkler Wrench, P/N 56-000-1-075. Air and Dust Seal Specify: Air and Dust Seal, P/N 56-908-1-001. MICROFAST® QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6) TECHNICAL DATA Form No. F_033314 16.10.06 Rev 16.4 Page 1 of 6 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com 1. DESCRIPTION The Viking Microfast® Quick Response Pendent Sprinkler VK302 is a small thermo- sensitive glass bulb spray sprinkler available with various finishes and temperature ratings to meet design requirements. The special Polyester and Electroless Nickel PTFE (ENT) coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive atmos- pheres and are listed/approved as corrosion resistant as indicated in the Approval Charts. (Note: FM Global approves ENT finish as corrosion resistant. FM Global has no approval classification for Polyester coatings as corrosion resistant.) 2. LISTINGS AND APPROVALS cULus Listed: Category VNIV FM Approved: Class Series 2000 VdS Approved: Certificates G414009 and G414010 LPCB Approved CE Certified: Standard EN 12259-1:1999, A3:2006 Certificate of Constancy of Performance 0832-CPR-S0021 CCCF Approved: Approved by the China Certification Center for Fire Products (CCCF) Refer to Approval Chart 1 and Design Criteria cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Minimum Operating Pressure: 7 psi (0.5 bar) Rated to 175 psi (12 bar) water working pressure Factory tested hydrostatically to 500 psi (34.5 bar) Thread size: 1/2” NPT, 15 mm BSP Nominal K-Factor: 5.6 U.S. (80.6 metric**) Glass-bulb fluid temperature rated to -65 °F (-55 °C) Overall Length: 2-1/4” (58 mm) *cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi (0.35 bar). Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass Deflector: Phosphor Bronze UNS-C51000 or Copper UNS-C19500 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 For Polyester Coated Sprinklers: Belleville Spring-Exposed For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap - ENT plated. Ordering Information: (Also refer to the current Viking price list.) Order Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, and ENT = JN Temperature Suffix: 135 °F (57 °C) = A, 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, 286 °F (141 °C) = G For example, sprinkler VK302 with a Brass finish and a 155 °F (68 °C) temperature rating = Part No. 12979AB Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the current Viking price list.) Replaces Form No. F_033314 Rev 16.3 (Removed term-upright) MICROFAST® QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6) TECHNICAL DATA Form No. F_033314 16.10.06 Rev 16.4 Page 2 of 6 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Sprinkler Wrenches: A. Standard Wrench: Part No. 10896W/B (available since 2000). B. Wrench for Recessed Pendent Sprinklers: Part No. 13655W/B** (available since 2006) C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool*** Part No. 15915 (available since 2010) **A ½” ratchet is required (not available from Viking). ***Allows use from the floor by attaching a length of 1” diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F_051808. Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A (available since 1971) B. Twelve-head capacity: Part No. 01725A (available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Viking Microfast® Quick Response Pendent Sprinkler VK302 is available through a network of domestic and international dis- tributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking’s current list price schedule or contact Viking directly. Figure 1: Standard Sprinkler Wrench 10896W/B Protective Sprinkler Cap Wrench FlatProtective Sprinkler Clip MICROFAST® QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6) TECHNICAL DATA Form No. F_033314 16.10.06 Rev 16.4 Page 3 of 6 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Bulb Color Ordinary 135 °F (57 °C)100 °F (38 °C)Orange Ordinary 155 °F (68 °C)100 °F (38 °C)Red Intermediate 175 °F (79 °C)150 °F (65 °C)Yellow Intermediate 200 °F (93 °C)150 °F (65 °C)Green High 286 °F (141 °C)225 °F (107 °C)Blue Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT Corrosion-Resistant Coatings3: White Polyester, and Black Polyester. ENT in all temperature ratings except 135 °F (57 °C) Footnotes 1 The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are com- patible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester and ENT coatings. For ENT coated automatic sprinklers, the waterway is coated. Figure 2: Wrench 13655W/B for Recessed Pendent Sprinklers Carefully slide the wrench sideways around the protective cap, ensuring engagement with the sprinkler wrench flats Sprinkler wrench 13655W/B** for recessed pendent sprinklers ** A 1/2” ratchet is required (not available from Viking) MICROFAST® QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6) TECHNICAL DATA Form No. F_033314 16.10.06 Rev 16.4 Page 4 of 6 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Approval Chart 1 (UL) The Viking Microfast® Quick Response Pendent Sprinkler VK302 Maximum 175 PSI (12 Bar) WWP Base Part Number1 SIN Sprinkler Style Thread Size Nominal K-Factor Overall Length Listings and Approvals3 (Refer also to Design Criteria.) NPT BSP U.S.metric2 Inches mm cULus4 VdS LPCB 7 12979 VK302 Pendent 1/2”15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2, C2X A1 A1Z, B1Y D1Z, C1Y ---- 19780 VK302 Pendent 1/2” --5.6 80.6 2-1/4 58 ----------D3 NOTICE - Product Below - Limited Availability (Contact Local Viking Office) 06662B VK302 Pendent 1/2”15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2, C2X ---------- 18021 VK302 Pendent 1/2”15 mm 5.6 80.6 2-1/4 58 A1X, B1Y A1 A1X, B1Y D1X, C1Y8 D1X, C1Y9 -- Approved Temperature Ratings A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C) B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) C - 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) D - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C) Approved Finishes 1 - Brass, Chrome, White Polyester5,6, Black Polyes- ter5,6 2 - ENT5 3 - Chrome Approved Escutcheons X - Standard surface-mounted escutcheon or the Viking Micromatic® Model E-1 Recessed Escutcheon Y - Standard surface-mounted escutcheon or the Viking Microfast® Model F-1 Adjustable Escutcheon, or recessed with the Viking Micro- matic® Model E-1, E-2, or E-3 Recessed Escutcheon Z - Standard surface-mounted escutcheon or the Viking Microfast® Model F-1 Adjustable Escutcheon Footnotes 1 Base part number shown. For complete part number, refer to Viking’s current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 This table shows the listings and approvals available at the time of printing. Other approvals may be in process. 4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada. 5 cULus Listed as corrosion-resistant. 6 Other colors are available on request with the same Listings and Approvals as the standard colors. 7 CE Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001. 8 CE Certified, Standard EN 12259-1, EC-certificates of conformity 0832-CPD-2001 and 0832-CPD-2003. 9 MED Certified, Standard EN 12259-1, EC-certificates of conformity 0832-MED-1003 and 0832-MED-1008. DESIGN CRITERIA - UL (Also refer to Approval Chart 1 above.) cULus Listing Requirements: The Viking Microfast® Quick Response Pendent Sprinkler VK302 is cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers. • Designed for use in Light and Ordinary occupancies. • The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and stan- dards, whenever applicable. MICROFAST® QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6) TECHNICAL DATA Form No. F_033314 16.10.06 Rev 16.4 Page 5 of 6 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Approval Chart 2 (FM) The Viking Microfast® Quick Response Pendent Sprinkler VK302 Maximum 175 PSI (12 Bar) WWP Base Part Number1 SIN Sprinkler Style Thread Size Nominal K-Factor Overall Length FM Approvals3 (Refer also to Design Criteria.)NPT BSP U.S.metric2 Inches mm 12979 VK302 Pendent 1/2”15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2X, C2 NOTICE - Product Below - Limited Availability (Contact Local Viking Office) 06662B VK302 Pendent 1/2”15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2X, C2 18021 VK302 Pendent 1/2”15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y Approved Temperature Ratings A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C) B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) C - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C) D - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C) Approved Finishes 1 - Brass, Chrome, White Polyester4, and Black Polyester4 2 - ENT5 Approved Escutcheons X - Standard surface-mounted escutcheon or the Viking Micromatic® Model E-1 Recessed Escutcheon Y - Standard surface-mounted escutcheon or the Viking Microfast® Model F-1 Adjustable Escutcheon, or recessed with the Viking Micromatic® Model E-1 or E-2 Recessed Escutcheon Z - Standard surface-mounted escutcheon or the Viking Microfast® Model F-1 Adjustable Escutcheon Footnotes 1 Base part number shown. For complete part number, refer to Viking’s current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 This table shows the FM Approvals available at the time of printing. Other approvals may be in process. 4 Other colors are available on request with the same Approvals as the standard colors. 5 FM approved as corrosion resistant. DESIGN CRITERIA - FM (Also refer to Approval Chart 2 above.) FM Approval Requirements: The Viking Microfast® Quick Response Pendent Sprinkler VK302 is FM Approved as quick response Non-storage pendent sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. MICROFAST® QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6) TECHNICAL DATA Form No. F_033314 16.10.06 Rev 16.4 Page 6 of 6 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Figure 4: Sprinkler Dimensions with the Model E-1 and E-2 Recessed Escutcheons Figure 3: Sprinkler Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon 1/2” (15 mm) NPT 2-1/4” (57 mm)1-3/4” (45 mm) 2” (51 mm)Max. 2-1/8” (54 mm) 1-1/2” (38 mm)Min. Installed with a standard 1/8” surface-mounted escutcheon Installed with a Microfast Model F-1 Adjustable Escutcheon Ceiling Opening Size: 2-5/16” (59 mm) minimum 2-1/2” (64 mm) maximum Note: At maximum, adapter is exposed 1/2” (13 mm) from face of ceiling 1-3/4” (45 mm)Max. 2-1/8” (54 mm) 1-1/8” (29 mm)Min. 2”” (51 mm)Max. 1-1/8” (29 mm)Min. 2-1/8” (54 mm) Ceiling Opening Size: 2-5/16” (59 mm) minimum 2-1/2” (64 mm) maximum Installed with a Model E-1 Recessed Escutcheon Installed with a Model E-2 Thread-on Recessed Escutcheon Replaces Form No. F_033314 Rev 16.3 (Removed term-upright) FREEDOM® RESIDENTIAL CONCEALED PENDENT SPRINKLER VK494 (K4.9) TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com Page 1 of 5 Form No. F_012116 18.10.11 Rev 18.1.P65 1. DESCRIPTION Viking Freedom® Residential Concealed Pendent Sprinkler VK494 is a small thermosensitive, glass-bulb residential sprinkler designed for installation on concealed pipe systems where the appearance of a smooth ceiling is desired. The orifice design, with a K-Factor of 4.9 (70.6 metric*), allows the sprinkler’s efficient use of available water supplies for the hydraulically designed fire-protection system. The fast response glass bulb operating element and special deflector characteristics meet the challenges of residential sprinkler standards. The sprinkler is pre-assembled with a threaded adapter for installation with a low-profile small-diameter cover assembly installed flush to the ceiling. The two-piece design allows installation and testing of the sprinkler prior to installation of the cover plate. The “push-on”, “thread-off” design of the concealed cover plate assembly allows easy installation of the cover plate after the system has been tested and the ceiling finish has been applied, while also providing up to 1/2” (13 mm) of vertical adjustment. The cover assembly can be removed and reinstalled, allowing temporary removal of ceiling panels without taking the sprinkler system out of service or removing the sprinkler. The Electroless Nickel PTFE (ENT) coating has been investigated for installation in corrosive atmospheres and is C-UL-US-EU Listed as corrosion resistant as indicated in the Approval Charts. The ENT finish is only available for the sprinkler assembly, the cover plate is not plated. 2. LISTINGS AND APPROVALS UL Listed (C-UL-US-EU): Category VKKW Refer to the Approval Charts and Design Criteria on for C-UL-US-EU Listing requirements that must be followed. 3. TECHNICAL DATASpecifications:Minimum Operating Pressure: Refer to the Approval Chart.Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar).Thread size: 1/2” (15 mm) NPT Nominal K-Factor: 4.9 U.S. (70.6 metric*)Glass-bulb fluid temperature rated to -65 °F (-55 °C) * Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. Material Standards:Sprinkler Body: Brass UNS-C84400 or QM BrassDeflector: Phosphor Bronze UNS-C51000Deflector Pins: Stainless Steel UNS-S30200Button: Brass UNS-C36000Pip Cap and Insert Assembly: Copper UNS-C11000 and SS UNS-S30400Compression Screw: 18-8 Stainless SteelYoke: UNS-S43000 Stainless Steel or Phosphor Bronze UNS-C51000Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE TapeCover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc PlatingShipping Cap: Polyethylene Cover Plate Materials:Cover Plate Assembly: Copper UNS-C11000 and Brass UNS-C26800 or Stainless Steel UNS-S30400Spring: Beryllium NickelSolder: EutecticOrdering Information: (Also refer to the current Viking price list.)Viking Freedom® Residential Concealed Pendent Sprinkler VK494 and Cover Plate Assembly must be ordered separately:Sprinkler: Order Sprinkler VK494 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass = A and ENT = JNTemperature Suffix: 155 °F (68 °C) = B, 200 °F (93 °C) = EFor example, sprinkler VK494 with a Brass finish and a 200 °F (93 °C) temperature rating = Part No. 20759AE.Standard Cover Plates: Base Part No. 13504 (2-3/4” diameter), Base Part No. 13642 (3-5/16” diameter), or Base Part No. 15394 (square cover plate, 3-5/16”) Stainless Steel Cover Plates (not availble with any finish or paint): Base Part No. 21876 (2-3/4” diameter) or Base Part No. 21875 (3-5/16” diameter). Replaces Form No. F_012116 Rev 18.1 (Added P65 Warning.) FREEDOM® RESIDENTIAL CONCEALED PENDENT SPRINKLER VK494 (K4.9) TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com Page 2 of 5 Form No. F_012116 18.10.11 Rev 18.1.P65 Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover temperature rating to the base part number:Finish Suffix: Polished Chrome = F, Brushed Chrome = F-/B, Bright Brass = B, Antique Brass = B-/A, Brushed Brass = B-/B, Brushed Copper = E-/B, Painted White = M-/W, Painted Ivory = M-/I, Painted Black = M-/BTemperature Suffix: 135 °F/57 °C = A For example, cover 13504 with a Polished Chrome finish and a 135 °F/57 °C temperature rating = 13504FA. Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the Viking website.)Sprinkler Wrenches**:A. Heavy Duty Part No. 14047W/B** (available since 2006), orB. Head Cabinet Wrench Part No. 14031*** (available since 2006) C. Optional Concealed Cover Plate Installer Tool Part No. 14412 (available since 2007)D. Optional Large Concealed Cover Plate Installer Tool Part No. 14867 (available since 2007) **Requires a ½” ratchet (not available from Viking). ***Also optional for removal of the protective cap. Ideal for sprinkler cabinets. Sprinkler Cabinet: Part No. 01731A (available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches, releasing the deflector. Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand, causing the glass to shatter, releasing the yoke and pip cap and sealing spring assembly. . Water flowing through the sprinkler orifice strikes the deflector, forming a uniform spray pattern over a specific area of coverage determined by the water supply pres-sure at the sprinkler to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking Sprinkler Model VK494 is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEEFor details of warranty, refer to Viking’s current list price schedule or contact Viking directly. TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Temperature Rating of the Cover Assembly (Required)3 Cover Plate Base Part Number4 Large Cover Plate Base Part Number4 Square Cover Plate Base Part Number4 Bulb Color Ordinary 155 °F (68 °C)100 °F (38 °C)135 °F (57 °C)13504 or 218766 13642 or 218756 15394 Red Intermediate 200 °F (93 °C)150 °F (65 °C)135 °F (57 °C)13504 or 218766 13642 or 218756 15394 Green Sprinkler Finishes: Brass and ENT Cover Plate Finishes6: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or Painted Black Corrosion Resistant Coatings5: ENT Footnotes 1. The sprinkler temperature rating is stamped on the deflector. 2. Based on NFPA-13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3. Maximum ambient temperature for cover assembly is 100 °F (38 °C). 4. Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 5. The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway. For ENT coated sprinklers, the Belleville spring is exposed. 6. Stainless Steel versions are not available with any finishes or paint. FREEDOM® RESIDENTIAL CONCEALED PENDENT SPRINKLER VK494 (K4.9) TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com Page 3 of 5 Form No. F_012116 18.10.11 Rev 18.1.P65 Approval ChartViking VK494, 4.9 K-Factor Residential Concealed Pendent Sprinkler For systems designed to NFPA 13D or NFPA 13R. For systems designed to NFPA 13, refer to the design criteria. For Ceiling types refer to current editions of NFPA 13, 13R or 13D S p r i n k l e r B a s e Part Number 1 SIN NPT Thread Size Nominal K-Factor Maximum Water Wor- king PressureInchesmmU.S.metric 2 20759 VK494 1/2 15 4.9 70.6 175 psi (12 bar) Max. Coverage Area 6 W X L Ft. X Ft. (m X m) Flow GPM (LPM) Pressure PSI (bar)Deflector to Ceiling Installation Type Listings and Approvals3,5 Minimum Spacing Ft. (m)155 °F (68 °C), 200 °F (93 °C) Temperature Rated Sprinklers 4 12 X 12 (3.7 X 3.7) 13 (49.2) 7.0 (0.48) Refer to Figure 2 Concealed with Cover Plate Assembly. See Footnote 8. See Footnotes 7,9, 10, & 11 8 (2.4) 14 X 14 (4.3 X 4.3) 13 (49.2) 7.0 (0.48) 16 X 16 (4.9 X 4.9) 13 (49.2) 7.0 (0.48) 18 X 18 (5.5 X 5.5) 17 (64.4) 12.0 (0.83) 20 X 20 (6.1 X 6.1) 20 (75.7) 16.7 (1.15) Footnotes 1. Part number shown is the base part number. For complete part number, refer to current Viking price schedule. 2. Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3. This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. Refer also to Design Criteria. 4. Listed by Underwriter’s Laboratories, Inc. for use in the U.S., Canada, and European Union. 5. Meets New York City requirements, effective July 1, 2008. 6. For areas of coverage smaller than shown, use the “Flow” and “Pressure” for the next larger area listed. Flows and pressures listed are per sprinkler. The distance from sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the minimum “Flow” and “Pressure” used. 7. Cover Temperature Rating is 135 °F (57 °C). Cover Part No. 135041, 136421 (large diameter), or 153941 (square cover plate). 8. Other paint colors are available on request with the same listings as the standard finish colors. Stainless Steel cover plates are not available with any finishes or paint. Listings and approvals apply for any paint manufacturer. Contact Viking for additional information. Custom colors are indicated on a label inside the cover assembly. Refer to Figure 3. 9. Accepted Cover Plate Finishes are: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or Painted Black 8. 10. C-UL-US-EU Listed as corrosion resistant - Electroless Nickel PTFE (ENT) 11. Stainless Steel Cover plate temperature rating is 135 °F (57 °C). Stainless Steel Cover Part Numbers: 218761 and 218751 (large diameter). FREEDOM® RESIDENTIAL CONCEALED PENDENT SPRINKLER VK494 (K4.9) TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com Page 4 of 5 Form No. F_012116 18.10.11 Rev 18.1.P65 DESIGN CRITERIA (Also refer to the Approval Chart on page 3.) UL Listing Requirements (C-UL-US-EU): When using Viking Residential Concealed Pendent Sprinkler VK494 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of cover-age and minimum water supply requirements shown in the Approval Chart. For systems designed to NFPA 13: The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following: • The flow rates given in the Approval Chart for NFPA 13D and NFPA 13R applications for each listed area of coverage, or • Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the “design area” in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13. • Minimum distance between residential sprinklers: 8 ft. (2.4 m). NOTE: Concealed sprinklers must be installed in neutral or negative pressure plenums only. IMPORTANT: Always refer to Bulletin Form No. F_080415 - Best Practices for Residential Sprinkler Handling and Installation. Also refer to Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be in-stalled in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA and any other similar Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Final approval and acceptance of all residential sprinkler installations must be obtained from the Authorities Having Jurisdiction. Sprinkler and Adapter Assembly • Protective cap removed • Use wrench 14047W/B** Step 1: Carefully slide the wrench sideways around the deflector and pins Sprinkler Wrench Part No. 14047W/B** ** A 1/2” ratchet is required (Not available from Viking) 2-1/4” (57 mm) diameter opening required in the ceiling. Step 2: Carefully press the wrench upward and turn slightly to ensure engagement with the sprinkler wrench flats. Figure 1: Sprinkler Installation and Proper Wrench Usage NEVER install the sprinkler by applying the installation wrench across the frame arms. DO NOT overtighten. Use only the designated sprinkler wrenches, Viking Part Numbers 14047W/B** or 14031**. A leak tight seal should be achieved by turning the sprinkler clockwise 1 to 1-1/2 turns beyond finger tight. Sprinkler wrench flat Sprinkler frame arms FREEDOM® RESIDENTIAL CONCEALED PENDENT SPRINKLER VK494 (K4.9) TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com Page 5 of 5 Form No. F_012116 18.10.11 Rev 18.1.P65 Figure 2: Sprinkler Dimensions and Cover Installation 1/2” (15 mm) NPT 2-1/4”(58 mm)2-9/16” (65 mm)Maximum 2-1/16” (52 mm)Minimum 2-3/4” (70 mm) or 3-5/16” (84 mm)NOTE: Upon sprinkler activation, the deflector descends to approximately 13/16” (21 mm) below the sprinkler body. Figure 3: Identification of Custom Paint for Concealed Covers All custom color painted cover plates will have an identifying label affixed to the inside of the cover that indicates the custom color and will have a representative sample (a paint dot) of the paint on the label.FACTORY APPLIE D C USTO M P AI NT COLORFigure 4: Square Cover Assembly 15394 3-5/16” (84 mm) Replaces Form No. F_012116 Rev 18.1 (Added P65 Warning.) OFFICE OF THE FIRE MARSHAL – LA QUINTA 78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074 • www.rvcfire.org September 27, 2022 Charles Brown Fire Protection Design 21386 Lilium Court Moreno Valley, CA 92557 Re: Residential Fire Sprinkler Plan Review – DEWEY RESIDENCE FSS2022-0275 / 53343 VIA PALACIO, LA QUINTA, CA 92253 The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions. Permanently marked identification signs shall be attached to all control valves. The following inspections/tests are required to be witnessed by Office of the Fire Marshal Staff: (a) Overhead Rough and Hydro static test: All piping shall be visible and pumped at normal operating pressure. *No jacketed electrical and data wiring shall be in contact with, nor have the potential to contact CPVC piping once insulation is installed. (b) Final inspection The Fire Department approved plans and conditions letter must be at the job site. Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131. All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal staff at (760)777-7074. Kohl Hetrick - Fire Safety Specialist 78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131 RIVERSIDE COUNTY FIRE PROTECTION PLANNING RECORD OF INSPECTIONS / PERMIT CARD THIS CARD IS TO REMAIN ON SITE AT ALL TIMES. INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE. JOB ADDRESS: 53343 VIA PALACIO PERMIT#: FSS2022-0275 DATE ISSUED: 9/27/2022 DESCRIPTION: DEWEY RESIDENCE CONTRACTOR: CHARLES BROWN FIRE PROTECTION HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS Thrust block pre-pour Door fan test UG rough piping Abort test UG hydro Mechanical shutdown Flush Detector test Final E F Deluge/pre-action SPRINKLER U.G. Final E F Thrust block pre-pour UST/AST TANK UG rough piping Installation UG hydro Removal Flush Emergency shut off Final E F Primary piping FIRE SPRINKLER Secondary piping Weld inspection Dispensers & shear valves Overhead rough piping Final E F Overhead hydro MISC. INSPECTIONS UG flush / OK to connect Spray booths Main drain/inspectors’ test Hood/duct extinguishing High pile storage High pile rack storage In-rack sprinklers H.P. vents/access/corridors Hose racks Tract access/hydrant verification Final E F Access & Address verification HOOD EXTINGUISHING OTHER CONST. PERMIT Detection system Function test Gas/electrical shut-off Nozzle model/placement Fire alarm connection Final E F SPRAY BOOTHS FIRE CODE PERMIT(S) Installation Air flow test Mechanical interlock Extinguishing system Fire alarm connection Final E F FIRE ALARM KNOX SYSTEM Rough-wire inspection Building Knox box Function test Gate access Knox box/padlock Duct detectors/velocity BUILDING INSPECTIONS 24 hr. battery test T/I final Sprinkler monitoring Shell final Final E F Final for occupancy FINAL INSPECTION DATE: INSPECTORS SIGNATURE: **WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE** 78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131 INSPECTION NOTES 1. Sway bracing and hangers will be inspected at the time of rough piping inspection. 2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler Systems) 3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required. 4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test. 5. Contractor shall supply all testing equipment, access and operating instructions at time of test. 6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the affected system to be covered or hidden. POLICIES ON FIELD INSPECTIONS A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when scheduling inspections. For City of La Quinta inspections call: (760) 777-7131. B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence without approved plans. C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required to schedule the necessary inspections and be present on site for inspections. D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not on site or where previously noted corrections have not been completed. E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into the structure until clearance has been granted by the Fire Dept and Building Official. F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official. INSPECTION NOTES: THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS. THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180 DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE. THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY. CHARLES F. BROWN FIRE SPRINKLER DESIGN C16-499210 21386 LILIUM COURT MORENO VALLEY, CA 92557 PH# (951) 712-4959 FAX # (951)-213-2493 DATE: April 24, 2023 City of La Quinta Fire ATTN: Jose 78495 Calle Tampico La Quinta, CA 90058 C.F.B. FIRE is pleased to present the following proposal for your project: PROJECT NAME: Single Family Residence COMPLETE ADDRES: 53343 Via Palacio, La Quinta DESCRIPTION: Single Family 13D system To Whom It May Concern: As discussed with Jose on April 24, 2023, this letter is to address the permit expiration/extension of the above referenced project. Due to unforeseen construction delays we were unable to get our final inspection which requires us to get an extension. The additional fees have been paid and we are requesting an extension of the Fire Sprinkler permit. Sincerely, Chuck Brown Fire Sprinkler Design Signature