FSS2022-0320ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT SIMON CHAVERO 82417 priscilla ct indio CA 92201 (760)574-6512 simon@silveradofire.c
om
CONTRACTOR SILVERADO FIRE PROTECTION 82417 PRISCILLA
STREET
INDIO CA 92201 (760)574-6512 SIMON@SILVERADOFI
RE.COM
OWNER JERRY SANTUCCI 48220 VIA VALLARTA LA QUINTA CA 92253 (760)574-6512
CONDITIONS
Description: TRINITY PALMS /FIRE SPRINKLERS / BRES2022-0432
Type: FIRE SPRINKLER (WEB)Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 9/21/2022 AMA
Parcel No: 602111034 Site Address: 48230 VIA VALLARTA LA QUINTA,CA 92253 Approved: 9/21/2022 RWI
Subdivision: TR 27835 Block: Lot: 2 Issued: 11/23/2022 AMA
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 7/13/2023 LRO
Valuation: $11,700.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Wednesday, September 27, 2023 10:02:57 AM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0320
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD HYRO LRO 11/23/2022 11/23/2022 APPROVED
OVERHEAD ROUGH
PIPING LRO 11/23/2022 11/23/2022 APPROVED See Notes
Revised Plans and Calcs prior to final due to
Inspector LR finding a 3/4 inch water meter
when plans show 1 inch.
FIRE FINAL**LRO 7/13/2023 7/13/2023 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $167.00 $167.00 11/23/22 WEB13681 758268345 CREDIT simon chavero EPRS
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $250.00 $250.00 11/23/22 WEB13681 758268345 CREDIT simon chavero EPRS
Total Paid for FIRE FEES: $417.00 $417.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $11.00 $11.00 11/23/22 WEB13681 758268345 CREDIT simon chavero EPRS
Total Paid for RECORDS MANAGEMENT FEE: $11.00 $11.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 11/23/22 WEB13681 758268345 CREDIT simon chavero EPRS
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$433.00 $433.00
Printed: Wednesday, September 27, 2023 10:02:57 AM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0320
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 9/21/2022 Etrakit Public
Registration
1ST SUBMITTAL
SPRINKLER SPECS
VK-494 4.9 k Res 155
deg (2).pdf 1
DOC 9/21/2022 Etrakit Public
Registration
1ST SUBMITTAL PLAN
FP-2
Duplex La Quinta -
Sheet - FP-2 - Piping
Plan (1).pdf
1
DOC 9/21/2022 Etrakit Public
Registration
1ST SUBMITTAL PLAN
FP-1
Duplex La
Quinta.pdfSite Plan
(1).pdf
1
DOC 9/21/2022 Etrakit Public
Registration 1ST SUBMITTAL CVWD Results (1) (2).pdf 1
DOC 9/21/2022 Etrakit Public
Registration
1ST SUBMITTAL
HYDRAULIC CALCS 3 Document.pdfCalc-3.pdf 1
DOC 9/21/2022 Etrakit Public
Registration
1ST SUBMITTAL
HYDRAULIC CALCS 1
Document.pdfCalc-1
(3).pdf 1
DOC 9/21/2022 Etrakit Public
Registration
1ST SUBMITTAL
HYDRAULIC CALCS 4 Document.pdfCalc-4.pdf 1
DOC 6/27/2023 Etrakit Contractor VK-494 4.9 k Res 155
deg (6).pdf 1
DOC 6/27/2023 Etrakit Contractor Results (1) (4).pdf 1
DOC 6/27/2023 Etrakit Contractor Document.pdfCalc-3
(3).pdf 1
BOND INFORMATION
1ST FIRE - ETRAKIT
(2 WK)
REBECCA
WINSCOTT 9/21/2022 9/21/2022 APPROVED
1ST PERMIT TECH –
ETRAKIT (1 DAY)
ARMANDO
MAGALLON 9/21/2022 9/21/2022 COMPLETE
I HAVE DUPLICATED AN ADDITIONAL FSS PERMIT
FOR INSPECTION AS WELL AS RECORD KEEPING
PURPOSES. THE ATTACHED PLANS WERE ALL
MOVED OVER FROM FSS2022-0307 FOR REVIEW.
2ND FIRE (1 WK)KOHL
HETRICK 6/27/2023 7/4/2023 7/10/2023 APPROVED AS-BUILTS (NO FEE)
Printed: Wednesday, September 27, 2023 10:02:57 AM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0320
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 6/27/2023 Etrakit Contractor Document.pdfCalc-1
(14).pdf 1
DOC 6/27/2023 Etrakit Contractor
Duplex La
Quinta.pdfPiping (1)
(1).pdf
1
DOC 7/10/2023 KOHL HETRICK FSS2022-0320 - AS-
BUILTS APPROVED.pdf
FSS2022-0320 - AS-
BUILTS APPROVED.pdf 1
DOC 11/23/2022 LEILANI ROJAS LR Inspection Notes 11-
23-22 FSS2022-0320.pdf
LR Inspection Notes 11-
23-22 FSS2022-0320.pdf 1
DOC 11/23/2022 LEILANI ROJAS LR Inspection Notes 11-
23-22 FSS2022-0320.pdf
LR Inspection Notes 11-
23-22 FSS2022-
0320_1.pdf
0
DOC 9/21/2022 REBECCA WINSCOTT LQ FSS2022-0307 and
0320 DUPLEX (COA).pdf
LQ FSS2022-0307 and
0320 DUPLEX (COA).pdf 1
DOC 9/21/2022 REBECCA WINSCOTT
LQ FSS2022-0307 and
0320 Rancho La Quinta
DUPLEX.pdf
LQ FSS2022-0307 and
0320 Rancho La Quinta
DUPLEX.pdf
1
Printed: Wednesday, September 27, 2023 10:02:57 AM 4 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0320
Fire Department Notes
A. The installation of new fire sprinkler systems or modifications to existing systems shall
comply with the following:
NFPA 13D 2016
CBC 2019
CFC 2019
Local Municipal Codes
Requirements of the AHJ
All Manufacture Installation Guidelines
Note: When conflict arrises between existing codes and standards,
the most stringent shall apply.
B. The Fire Department Shall require the following inspections and tests.
1. Overhead installation and hydrostatic test, ( prior to cover ).
a. Normal opperating pressure when no FDC is installed.
b. 200psi when FDC is required.
c. Two hour minimum.
2. Final sprinkler and underground, ( prior to building final ).
a. All inspections shall be scheduled by the contractor of record.
b. Inspections shall be scheduled 24 hours in advance.
GENERAL NOTES
1.General: All materials and devices shall conform to 2016 NFPA 13D standards. Installation
shall conform to all applcable State and Local Codes.
2.Scope of Work: Install a new Residential Fire Protection System.
3.Piping: All overhead pipe and fittings shall be CPVC unless otherwise noted.
4.Design: NFPA 13D 2016 Edition and CFC Chapter 80 Standards.
5.System Demand @ Source. Two Sprinklers Flowing (16X16 Spacing):
31.3842 gpm @ 31.96psi ( 512 Max )
6.Water Supply Data: Water is supplied from public water main in street.
Static Pressure: 92.7
Information Source: CVWD
7.Sprinkler Head Spacing and Installation Requirements:Sprinklers shall not be located
Closer than 8'-0" apart where there is no intervening obstruction.
Sprinklers near potential obstruction shall be located per manufactures instructions.
8.Piping Supports: Piping shall be supported and restrained in conformance with local
plumbing codes and CPVC manufactures instructions . Eachpipe section that supplies
a drop to a sprinkler shall be secured no more than 12" from the drop to prevent laterial
and vertical movement.
9.Pipe lenghts are approximate for hydraulic calculation and plan review purposes only.
10.The owner shall furnish sufficant heat in all areas to prevent freezingof pipe.
11.Waterflow Switch and Alarm: By Others
a. A dedicated electrical circuit with a circuit breaker lock shall be provided for waterflow
horn/strobes.
b. An approved audible sprinkler waterflow alarm shall be visible from the street.
The device shall be listed for outdoor use.
An approved sign shall be placed at or near the device stating,
SPRINKLER FIRE ALARM - WHEN ALARM SOUNDS CALL 911
c. An approved audible sprinkler waterflow alarm module shall be conected to the
smoke detectors to alert occupants shall be provided.
NFPA 13D REFERANCE NOTES
1. NFPA 13D, Section 8.3.2
Sprinklers shall not be required in bathrooms of 55 sq. ft. and less.
2. NFPA 13D, Section 8.3.3
Sprinklers shall not be required in clothes closets, linen closets, and pantries
that meet all of the following conditions.
(1) The area of the space does not exceed 24 sq. ft.
(2) The walls and ceilings are surfaced with noncombustible or limited-combustible
material as defined in NFPA 220.
3.NFPA 13D Section 8.3.4
Sprinklers shall not be required in garages, open attached porches, carports, and
similar structures.
Note that CFC 2016 Chapter 80 Referance Standards requires attached garages,
attached porches, carports, and similar structures shall be sprinklered if there is
occupied living space above.
4. NFPA 13D Section 8.2.5.6 Shadow Areas
Shadow areas shall be permitted in the protection area of a sprinkler as long as
the cumulative dry areas do not exceed 15 sq. ft. (1.4 sq. m.) per sprinkler.
simon@silveradofire.com
Scale
Project number
Date
Drawn by
Checked by Silverado Fire ProtectionPO Box 11474Palm Desert, Ca.92255760-574-6512C-16 # 1068664
As indicated
8/6/2022 8:38:50 AMFP-1
Site Plan
Project Number
08-08-22
JA
SC
No. Description Date
RANCHO LA QUINTAA Duplex Unit48220 and 48230 Via Vallarta,Rancho La Quinta CC,La Quinta, Ca. 92253
INSPECTOR TEST DETAIL
5'
1" Ball Valve Access Panel
(By Others)
Exterior Wall of Building
Inspector Test to Terminate
in a Smooth Bore Corrosion
Resistant Orfice With a Flow
Equivalent to One Sprinkler
NOTE: Access Panel Shall have sign
Indicating Inspector Test
SPRINKLER PIPEINSULATION
BOTTOM CORD OF ROOF TRUSS
OR CEILING JOIST
PIPE INSULATION DETAIL
CPVC HANGERS
NO SCALE
TOLCO FIG. 24
DOUBLE-FASTENER
SIDE-MOUNT HANGER
(OR EQUAL)
SELF-DRILLING
HEX HEAD SCREW
TOLCO FIG. 23
DOUBLE-FASTENER
STRAP TYPE HANGER
(OR EQUAL)
TOLCO FIG. 28M
OFFSET HANGER
(OR EQUAL)
TOLCO FIG. 22
SINGLE-FASTENER
STRAP-TYPE HANGER
(OR EQUAL)
TOLCO FIG. 28
DOUBLE-FASTENER
STAND-OFF HANGER
(OR EQUAL)
TOLCO FIG. 29
DOUBLE-FASTENER
DOUBLE OFFSET HANGER
(OR EQUAL)
CPVC HANGER SPACING
PIPE SIZE
11/4"
1"
MAXIMUM SUPPORT SPACING
6'-6"
6'-0"
2"8'-0"
11/2"7'-0"
www.cadmando.co.uk
These blocks were brought to you by CADB locksFree.com.For all of your 2D & 3D CA D outsource requirements visit us:
C A D M A N D O
www.cadblocksfree.com
COVER WITH HINGED LID
FINISHED GRADE
DISC-TYPE WATER METER
PLUG VALVE(TYP.)UNION(TYP.)
M A T E R I A L L E G E N D
Scale: 1/4"=1'-0"
REFLECTED CEILING PLAN
w
w
w
w
w
w
w
Fire Sprinkler Riser Detail
TOR
BOR
Domestic
Supply
Check
Flow Control
1" CPVC
Flow Switch Note Wiring by Others
300psi Gage
Sprinkler Box with Wrench & two
Sprinkler Heads Each Type
1/2" Drain to
Outside1"1"1-1/4"Underground By Others
Notification Device
Wired by Others
not to scale
Module Must Connect to the Multi
Station Smoke Alarm System and
the Fire Sprinkler Flow Switch
( all wiring by others )
-
---
Water Supply Information
Static Pressure:
Residual Pressure:
Residual Flow:
Additional Hose Flow:
92.70 psi
82.30 psi
2800 GPM
0 GPM
Remote area number:
Occupancy classification:
Density:
Area of application:
Total water required
(including hose streams):
@ a required
system pressure
of:
Fire Protection System Demand:
No. of sprinklers calculated:
Inside Hose Streams:
Outside Hose
Streams:
Calc-1
R-3
2
Gpm/SqFt
512 Max SqFt
31.3842 GPM
53.9606 Psi
5 GPM
0 GPM
WM
3
4
SOR
BORTOR
DOM
1 5
2
1" WATER METER
WITH 15psi SHOWN AS
Worst Case Friction Loss
Supply Point
Remote area number:
Occupancy classification:
Density:
Area of application:
Total water required
(including hose streams):
@ a required
system pressure
of:
Fire Protection System Demand:
No. of sprinklers calculated:
Inside Hose Streams:
Outside Hose
Streams:
Calc-3
R-3
2
Gpm/SqFt
512 Max SqFt
31.3573 GPM
52.3503 Psi
5 GPM
0 GPM
6 10
7
WM2
8
9
SOR2
BOR2
TOR2
DOM2
Remote area number:
Occupancy classification:
Density:
Area of application:
Total water required
(including hose streams):
@ a required
system pressure
of:
Fire Protection System Demand:
No. of sprinklers calculated:
Inside Hose Streams:
Outside Hose
Streams:
Calc-4
1
Gpm/SqFt
400 Max SqFt
25.0242 GPM
47.0535 Psi
5 GPM
0 GPM
11
Calc-3
Calc-4
Calc-1
NOTIFICATION DEVICE BY OTHERS
1" RISER
1-1/4" PVC UNDERGROUND BY OTHERS1-1/4" PVC UNDERGROUND BY OTHERS1" RISER
1 1/4"29' -0"1 1/4"
6' -1"1" x 9' -9"1" x 4' -3"1"
3' -5"
1"
12' -8"
1"
9' -1"
1"
9' -1"
1"
2' -8"
1"
14' -2"1"3' -2"1"13' -0"1"10' -11"1"
2' -0"
1"
2' -0"
1"
10' -0"
1"
1' -6"
1"
1' -7"
1"
12' -0"
1"
10' -0"1"8' -6"1"5' -9"1"
6' -10"
1"
2' -8"1"8' -6"1"
3' -6"
1"
12' -0"
1"
12' -0"
1"
12' -0"
1"
3' -10"1"4' -5"1"6' -3"1"4' -10"1"
2' -2"1"5' -7"1"
3' -4"
1"
8' -4"
1"
3' -1"
1"
12' -0"
1"
2' -3"
1"
5' -8"
1"
1' -0"
1"
2' -6"
1"
2' -5"
1"
7' -10"
1"
7' -10"
1"
3' -6"
1 1/4"
5' -0"1 1/4"6' -1"1 1/4"41' -5"1" x 9' -3"1" x 4' -9"1"
6' -9"
1"
2' -11"
1"
7' -3"
1"
11' -0"
1"
11' -0"
1"
3' -10"
1"
7' -2"
1"
5' -5"
1"
0' -10"
1"
2' -7"
1"
2' -4"
1"
5' -5"
1"
3' -5"1"9' -1"1"7' -7"1"3' -5"1"
6' -3"
1"
1' -6"
1"
3' -4"1"7' -7"1"8' -11"1"6' -6"1"
8' -6"
1"
6' -11"
1"
6' -0"
1"
6' -0"
1"
2' -5"1"6' -5"1"6' -7"1"
6' -0"
1"
6' -0"
1"
5' -7"
1"
3' -8"
1"
7' -9"
1"
5' -11"
1"
3' -10"
1"
1' -3"1"4' -7"INSPECTORS TEST
INSPECTORS TEST
PATIO
PATIO
GREAT
ROOM
14'-0"
GREAT
ROOM
14'-0"
KITCHEN
14'-0"
KITCHEN
14'-0"
ENTRY
ENTRY
MASTER
10'-0"
MASTER
10'-0"
M
BATH
10'-0"
M
BATH
10'-0"
POW
10'-0"
POW
10'-0"
BED 2
10'-0"
BED 2
10'-0"
BATH
BATH
LAUNDRY
LAUNDRY
HALL
HALL
HALL
HALL
GARAGE
10'-0"
GARAGE
10'-0"
1" WATER METER
WITH 15psi SHOWN AS
Worst Case Friction Loss
simon@silveradofire.com
Scale
Project number
Date
Drawn by
Checked by Silverado Fire ProtectionPO Box 11474Palm Desert, Ca.92255760-574-6512C-16 # 1068664
As indicated
8/11/2022 8:08:20 AMFP-2
Piping Plan
Project Number
08-08-22
JA
SC
No. Description Date
RANCHO LA QUINTAA Duplex Unit48220 and 48230 Via Vallarta,Rancho La Quinta CC,La Quinta, Ca. 92253Sprinkler Schedule
No. of
Sprklrs Description
SIN
(Hydratec)K-Factor
Orifice
Size Temp
39 Viking 1/2 Light Concealed Temperature - 155 Finish - B Quick Response Model - Mirage
SIN - VK494 K Factor - 4.9
VK494 4.9 1/2" 155 °F
8 Viking 1/2 Light Pendent Temperature - 175 Finish - C Special Response Model -
Micromatic SIN - VK494 K Factor - 4.9
VK494 4.9 1/2" 175 °F
: 47
Total No. of Sprinklers: 47
Silverado Fire Protection
PO Box 11474
Palm Desert, Ca. 92255
760-574-6512
Job Name : Duplex La Quinta
Drawing :
Location : Via Vallarta
Remote Area : Calc-1
Contract :
Data File : Duplex La Quinta Area Calc-1.WXF
Computer Programs by Hydratec Inc. Revision: 50.54.4
Silverado Fire ProtectionPage 1 Duplex La QuintaDate 10203040E50R60U70S80S90E100R110P120130140150300 600 900 1200 1500 1800 2100 2400 2700FLOW ( N ^ 1.85 )City Water Supply:Demand:C1C2C1 - Static Pressure : 92.7 C2 - Residual Pressure: 82.3 C2 - Residual Flow : 2800 D1 - Elevation : 7.445 D2 - System Flow : 31.384 D2 - System Pressure : 53.961 Hose ( Demand ) : _______D3 - System Demand : 31.384 Safety Margin : 38.737 D1D2Water Supply CurveComputer Programs by Hydratec Inc. Revision: 50.54.4
Silverado Fire ProtectionPage 2 Duplex La QuintaDate Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24 N * CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 O * CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 R * CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used SummaryComputer Programs by Hydratec Inc. Revision: 50.54.4
Silverado Fire Protection Page 3
Duplex La Quinta Date
SUPPLY ANALYSIS
Node at Static Residual Available
Source Pressure Pressure Flow Pressure Total Demand Required Pressure
SOR 92.7 82.3 2800.0 92.697 31.38 53.961
NODE ANALYSIS
Pressure Discharge
Node Tag Elevation Node Type at Node at Node Notes
1 14.19 4.9 7.04 13.0 0.05 256
2 15.0 7.3
TOR 11.0 26.85
DOM 1.22 33.1 5.0
BOR -3.0 36.69
3 -3.0 38.82
WM -3.0 53.88
4 -3.0 53.94
SOR -3.0 53.96
5 14.19 4.9 7.46 13.38 0.05 256
Flow Summary - NFPA
Computer Programs by Hydratec Inc. Revision: 50.54.4
Silverado Fire Protection Page 4
Duplex La Quinta Date
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
1 14.19 4.90 13.00 1 N 7.0 12.810 150 7.040
to 7.000 -0.351
2 15 13.0 1.101 19.810 0.0307 0.608 Vel = 4.38
2 15 13.38 1 9R 9.0 98.860 150 7.297
to 2N 14.0 58.000 1.732
TOR 11 26.38 1.101 7O 35.0 156.860 0.1136 17.818 Vel = 8.89
TOR 11 0.0 1 R 1.0 9.780 150 26.847
to N 7.0 8.000 4.236
DOM 1.22 26.38 1.101 17.780 0.1136 2.020 Vel = 8.89
DOM 1.22 + 5.00 5.00 1 N 7.0 4.220 150 33.103
to 7.000 1.828
BOR -3 31.38 1.101 11.220 0.1565 1.756 Vel = 10.57
BOR -3 0.0 1.25 N 8.0 34.920 150 36.687
to 8.000 0.0
3 -3 31.38 1.394 42.920 0.0497 2.131 Vel = 6.60
3 -3 0.0 1 0.400 150 38.818
to 15.000 * * Fixed Loss = 15
WM -3 31.38 1.101 0.400 0.1550 0.062 Vel = 10.57
WM -3 0.0 1 0.400 150 53.880
to 0.0
4 -3 31.38 1.101 0.400 0.1575 0.063 Vel = 10.57
4 -3 0.0 1.25 0.360 150 53.943
to 0.0
SOR -3 31.38 1.394 0.360 0.0500 0.018 Vel = 6.60
0.0
SOR 31.38 53.961 K Factor = 4.27
5 14.19 4.90 13.38 1 O 5.0 0.810 150 7.460
to 5.000 -0.351
2 15 13.38 1.101 5.810 0.0324 0.188 Vel = 4.51
0.0
2 13.38 7.297 K Factor = 4.95
Final Calculations : Hazen-Williams
Computer Programs by Hydratec Inc. Revision: 50.54.4
Southwest Fire Pros
31401 Reserve Drive Suite 2
Route 111
Thousand Palms, Ca.92276
760-343-2233
Job Name : Duplex La Quinta
Drawing :
Location : Via Vallarta
Remote Area : Calc-4
Contract :
Data File : Duplex La Quinta Area Calc-4.WXF
Computer Programs by Hydratec Inc. Revision: 50.54.4
Southwest Fire ProsPage 1 Duplex La QuintaDate 10203040E50R60U70S80S90E100R110P120130140150300 600 900 1200 1500 1800 2100 2400 2700FLOW ( N ^ 1.85 )City Water Supply:Demand:C1C2C1 - Static Pressure : 92.7 C2 - Residual Pressure: 82.3 C2 - Residual Flow : 2800 D1 - Elevation : 5.713 D2 - System Flow : 25.024 D2 - System Pressure : 47.054 Hose ( Demand ) : _______D3 - System Demand : 25.024 Safety Margin : 45.645 D1D2Water Supply CurveComputer Programs by Hydratec Inc. Revision: 50.54.4
Southwest Fire ProsPage 2 Duplex La QuintaDate Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24 N * CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 O * CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 R * CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used SummaryComputer Programs by Hydratec Inc. Revision: 50.54.4
Southwest Fire Pros Page 3
Duplex La Quinta Date
SUPPLY ANALYSIS
Node at Static Residual Available
Source Pressure Pressure Flow Pressure Total Demand Required Pressure
SOR2 92.7 82.3 2800.0 92.698 25.02 47.054
NODE ANALYSIS
Pressure Discharge
Node Tag Elevation Node Type at Node at Node Notes
11 10.19 4.9 16.7 20.02 0.05 256
TOR2 11.0 21.56
DOM2 1.72 26.75 5.0
BOR2 -3.0 30.01
8 -3.0 31.78
WM2 -3.0 46.82
9 -3.0 46.86
SOR2 -3.0 47.05
Flow Summary - NFPA
Computer Programs by Hydratec Inc. Revision: 50.54.4
Southwest Fire Pros Page 4
Duplex La Quinta Date
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
11 10.19 4.90 20.02 1 N 7.0 45.370 150 16.700
to 4O 20.0 31.000 -0.351
TOR2 11 20.02 1.101 4R 4.0 76.370 0.0682 5.208 Vel = 6.75
TOR2 11 0.0 1 R 1.0 9.280 150 21.557
to N 7.0 8.000 4.019
DOM2 1.72 20.02 1.101 17.280 0.0682 1.179 Vel = 6.75
DOM2 1.72 + 5.00 5.00 1 N 7.0 4.720 150 26.755
to 7.000 2.044
BOR2 -3 25.02 1.101 11.720 0.1030 1.207 Vel = 8.43
BOR2 -3 0.0 1.25 N 8.0 46.250 150 30.006
to 8.000 0.0
8 -3 25.02 1.394 54.250 0.0326 1.771 Vel = 5.26
8 -3 0.0 1 0.400 150 31.777
to 15.000 * * Fixed Loss = 15
WM2 -3 25.02 1.101 0.400 0.1025 0.041 Vel = 8.43
WM2 -3 0.0 1 0.400 150 46.818
to 0.0
9 -3 25.02 1.101 0.400 0.1025 0.041 Vel = 8.43
9 -3 0.0 1.25 5.950 150 46.859
to 0.0
SOR2 -3 25.02 1.394 5.950 0.0328 0.195 Vel = 5.26
0.0
SOR2 25.02 47.054 K Factor = 3.65
Final Calculations : Hazen-Williams
Computer Programs by Hydratec Inc. Revision: 50.54.4
Southwest Fire Pros
31401 Reserve Drive Suite 2
Route 111
Thousand Palms, Ca.92276
760-343-2233
Job Name : Duplex La Quinta
Drawing :
Location : Via Vallarta
Remote Area : Calc-3
Contract :
Data File : Duplex La Quinta Area Calc-3.WXF
Computer Programs by Hydratec Inc. Revision: 50.54.4
Southwest Fire ProsPage 1 Duplex La QuintaDate 10203040E50R60U70S80S90E100R110P120130140150300 600 900 1200 1500 1800 2100 2400 2700FLOW ( N ^ 1.85 )City Water Supply:Demand:C1C2C1 - Static Pressure : 92.7 C2 - Residual Pressure: 82.3 C2 - Residual Flow : 2800 D1 - Elevation : 7.445 D2 - System Flow : 31.357 D2 - System Pressure : 52.350 Hose ( Demand ) : _______D3 - System Demand : 31.357 Safety Margin : 40.347 D1D2Water Supply CurveComputer Programs by Hydratec Inc. Revision: 50.54.4
Southwest Fire ProsPage 2 Duplex La QuintaDate Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24 N * CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 O * CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 R * CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used SummaryComputer Programs by Hydratec Inc. Revision: 50.54.4
Southwest Fire Pros Page 3
Duplex La Quinta Date
SUPPLY ANALYSIS
Node at Static Residual Available
Source Pressure Pressure Flow Pressure Total Demand Required Pressure
SOR2 92.7 82.3 2800.0 92.697 31.36 52.35
NODE ANALYSIS
Pressure Discharge
Node Tag Elevation Node Type at Node at Node Notes
6 14.19 4.9 7.04 13.0 0.05 256
7 15.0 7.27
TOR2 11.0 24.39
DOM2 1.72 30.37 5.0
BOR2 -3.0 34.24
8 -3.0 36.93
WM2 -3.0 51.99
9 -3.0 52.06
SOR2 -3.0 52.35
10 14.19 4.9 7.43 13.36 0.05 256
Flow Summary - NFPA
Computer Programs by Hydratec Inc. Revision: 50.54.4
Southwest Fire Pros Page 4
Duplex La Quinta Date
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
6 14.19 4.90 13.00 1 N 7.0 11.810 150 7.040
to 7.000 -0.351
7 15 13.0 1.101 18.810 0.0307 0.577 Vel = 4.38
7 15 13.36 1 N 7.0 89.730 150 7.266
to 9R 9.0 46.000 1.732
TOR2 11 26.36 1.101 6O 30.0 135.730 0.1134 15.389 Vel = 8.88
TOR2 11 0.0 1 R 1.0 9.280 150 24.387
to N 7.0 8.000 4.019
DOM2 1.72 26.36 1.101 17.280 0.1134 1.960 Vel = 8.88
DOM2 1.72 + 5.00 5.00 1 N 7.0 4.720 150 30.366
to 7.000 2.044
BOR2 -3 31.36 1.101 11.720 0.1563 1.832 Vel = 10.57
BOR2 -3 0.0 1.25 N 8.0 46.250 150 34.242
to 8.000 0.0
8 -3 31.36 1.394 54.250 0.0495 2.688 Vel = 6.59
8 -3 0.0 1 0.400 150 36.930
to 15.000 * * Fixed Loss = 15
WM2 -3 31.36 1.101 0.400 0.1575 0.063 Vel = 10.57
WM2 -3 0.0 1 0.400 150 51.993
to 0.0
9 -3 31.36 1.101 0.400 0.1575 0.063 Vel = 10.57
9 -3 0.0 1.25 5.950 150 52.056
to 0.0
SOR2 -3 31.36 1.394 5.950 0.0494 0.294 Vel = 6.59
0.0
SOR2 31.36 52.350 K Factor = 4.33
10 14.19 4.90 13.36 1 O 5.0 0.810 150 7.430
to 5.000 -0.351
7 15 13.36 1.101 5.810 0.0322 0.187 Vel = 4.50
0.0
7 13.36 7.266 K Factor = 4.96
Final Calculations : Hazen-Williams
Computer Programs by Hydratec Inc. Revision: 50.54.4
FREEDOM® RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 1 of 5
Form No. F_012116 18.10.11 Rev 18.1.P65
1. DESCRIPTION
Viking Freedom® Residential Concealed Pendent Sprinkler VK494 is a small
thermosensitive, glass-bulb residential sprinkler designed for installation on
concealed pipe systems where the appearance of a smooth ceiling is desired. The
orifice design, with a K-Factor of 4.9 (70.6 metric*), allows the sprinkler’s efficient
use of available water supplies for the hydraulically designed fire-protection
system. The fast response glass bulb operating element and special deflector
characteristics meet the challenges of residential sprinkler standards.
The sprinkler is pre-assembled with a threaded adapter for installation with a
low-profile small-diameter cover assembly installed flush to the ceiling. The two-
piece design allows installation and testing of the sprinkler prior to installation
of the cover plate. The “push-on”, “thread-off” design of the concealed cover
plate assembly allows easy installation of the cover plate after the system has
been tested and the ceiling finish has been applied, while also providing up to
1/2” (13 mm) of vertical adjustment. The cover assembly can be removed
and reinstalled, allowing temporary removal of ceiling panels without taking
the sprinkler system out of service or removing the sprinkler. The Electroless
Nickel PTFE (ENT) coating has been investigated for installation in corrosive
atmospheres and is C-UL-US-EU Listed as corrosion resistant as indicated in the
Approval Charts. The ENT finish is only available for the sprinkler assembly, the
cover plate is not plated.
2. LISTINGS AND APPROVALS
UL Listed (C-UL-US-EU): Category VKKW
Refer to the Approval Charts and Design Criteria on for C-UL-US-EU Listing
requirements that must be followed.
3. TECHNICAL DATA
Minimum Operating Pressure: Refer to the Approval Chart.
Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to
500 psi (34.5 bar).
Thread size: 1/2” (15 mm) NPT
Nominal K-Factor: 4.9 U.S. (70.6 metric*)
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
* Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the
metric K-factor shown by 10.0.
Sprinkler Body: Brass UNS-C84400 or QM Brass
Deflector: Phosphor Bronze UNS-C51000
Deflector Pins: Stainless Steel UNS-S30200
Button: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and SS UNS-S30400
Compression Screw: 18-8 Stainless Steel
Yoke: UNS-S43000 Stainless Steel or Phosphor Bronze UNS-C51000
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating
Shipping Cap: Polyethylene
Cover Plate Assembly: Copper UNS-C11000 and Brass UNS-C26800 or Stainless Steel UNS-S30400
Spring: Beryllium Nickel
Solder: Eutectic
(Also refer to the current Viking price list.)
Viking Freedom® Residential Concealed Pendent Sprinkler VK494 and Cover Plate Assembly must be ordered separately:
Order Sprinkler VK494 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the
temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A and ENT = JN
Temperature Suffix: 155 °F (68 °C) = B, 200 °F (93 °C) = E
For example, sprinkler VK494 with a Brass finish and a 200 °F (93 °C) temperature rating = Part No. 20759AE.
Base Part No. 13504 (2-3/4” diameter), Base Part No. 13642 (3-5/16” diameter),
or Base Part No. 15394 (square cover plate, 3-5/16”)
Base Part No. 21876 (2-3/4” diameter) or Base Part No.
21875 (3-5/16” diameter).
Replaces Form No. F_012116 Rev 18.1
(Added P65 Warning.)
FREEDOM® RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 2 of 5
Form No. F_012116 18.10.11 Rev 18.1.P65
Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover
temperature rating to the base part number:
Finish Suffix: Polished Chrome = F, Brushed Chrome = F-/B, Bright Brass = B, Antique Brass = B-/A, Brushed Brass = B-/B, Brushed
Copper = E-/B, Painted White = M-/W, Painted Ivory = M-/I, Painted Black = M-/B
Temperature Suffix: 135 °F/57 °C = A
For example, cover 13504 with a Polished Chrome finish and a 135 °F/57 °C temperature rating = 13504FA.
Refer to Table 1.
(Also refer to the Viking website.)
A. Heavy Duty Part No. 14047W/B** (available since 2006), or
B. Head Cabinet Wrench Part No. 14031*** (available since 2006)
C. Optional Concealed Cover Plate Installer Tool Part No. 14412 (available since 2007)
D. Optional Large Concealed Cover Plate Installer Tool Part No. 14867 (available since 2007)
**Requires a ½” ratchet (not available from Viking). ***Also optional for removal of the protective cap. Ideal for sprinkler cabinets.
Part No. 01731A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches,
releasing the deflector. Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand,
causing the glass to shatter, releasing the yoke and pip cap and sealing spring assembly. . Water flowing through the sprinkler
orifice strikes the deflector, forming a uniform spray pattern over a specific area of coverage determined by the water supply pres -
sure at the sprinkler to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Sprinkler Model VK494 is available through a network of domestic and international distributors. See The Viking Corporation
web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
1 2 3 4 4 4
Ordinary 155 °F (68 °C)100 °F (38 °C)135 °F (57 °C)13504 or
218766
13642 or
218756 15394 Red
Intermediate 200 °F (93 °C)150 °F (65 °C)135 °F (57 °C)13504 or
218766
13642 or
218756 15394 Green
Brass and ENT
6: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted
White, Painted Ivory, or Painted Black
5: ENT
1.The sprinkler temperature rating is stamped on the deflector.
2.Based on NFPA-13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
3.Maximum ambient temperature for cover assembly is 100 °F (38 °C).
4.Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
5.The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and
do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed
environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway. For ENT coated sprinklers, the Belleville
spring is exposed.
6.Stainless Steel versions are not available with any finishes or paint.
FREEDOM® RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 3 of 5
Form No. F_012116 18.10.11 Rev 18.1.P65
1 SIN -
U.S.2
20759 VK494 1/2 15 4.9 70.6 175 psi (12 bar)
6 GPM
(LPM)3,5
155 °F (68 °C), 200 °F (93 °C) Temperature
Rated Sprinklers
4
12 X 12
(3.7 X 3.7)
13
(49.2)
7.0
(0.48)
Refer to Figure 2
Concealed with
Cover Plate
Assembly.
See Footnote 8.
See Footnotes 7,9, 10,
& 11 8
(2.4)
14 X 14
(4.3 X 4.3)
13
(49.2)
7.0
(0.48)
16 X 16
(4.9 X 4.9)
13
(49.2)
7.0
(0.48)
18 X 18
(5.5 X 5.5)
17
(64.4)
12.0
(0.83)
20 X 20
(6.1 X 6.1)
20
(75.7)
16.7
(1.15)
1.Part number shown is the base part number. For complete part number, refer to current Viking price schedule.
2.Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3.This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals.
Refer also to Design Criteria.
4.Listed by Underwriter’s Laboratories, Inc. for use in the U.S., Canada, and European Union.
5.Meets New York City requirements, effective July 1, 2008.
6.For areas of coverage smaller than shown, use the “Flow” and “Pressure” for the next larger area listed. Flows and pressures listed are per sprinkler. The distance from
sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the minimum “Flow” and “Pressure” used.
7.Cover Temperature Rating is 135 °F (57 °C). Cover Part No. 135041, 136421 (large diameter), or 153941 (square cover plate).
8.Other paint colors are available on request with the same listings as the standard finish colors. Stainless Steel cover plates are not available with any finishes or paint.
Listings and approvals apply for any paint manufacturer. Contact Viking for additional information. Custom colors are indicated on a label inside the cover assembly.
Refer to Figure 3.
Accepted Cover Plate Finishes are: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or
Painted Black 8.
10.C-UL-US-EU Listed as corrosion resistant - Electroless Nickel PTFE (ENT)
11.Stainless Steel Cover plate temperature rating is 135 °F (57 °C). Stainless Steel Cover Part Numbers: 218761 and 218751 (large diameter).
FREEDOM® RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 4 of 5
Form No. F_012116 18.10.11 Rev 18.1.P65
DESIGN CRITERIA
(Also refer to the Approval Chart on page 3.)
:
When using Viking Residential Concealed Pendent Sprinkler VK494 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of cover -
age and minimum water supply requirements shown in the Approval Chart.
For systems designed to NFPA 13: The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The minimum
required discharge from each of the four sprinklers is to be the greater of the following:
•The flow rates given in the Approval Chart for NFPA 13D and NFPA 13R applications for each listed area of coverage,
•Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the “design area” in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13.
•Minimum distance between residential sprinklers: 8 ft. (2.4 m).
NOTE:
-
•
•
Step 1: Step 2:
FREEDOM® RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 5 of 5
Form No. F_012116 18.10.11 Rev 18.1.P65
NOTE:
to approximately 13/16” (21 mm) below the sprinkler body.
All custom color painted cover plates will have an
identifying label affixed to the inside of the cover that
indicates the custom color and will have a representative
sample (a paint dot) of the paint on the label.
Replaces Form No. F_012116 Rev 18.1
(Added P65 Warning.)
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
September 21, 2022
Silverado Fire Protection
Re: Residential Fire Sprinkler Plan Review – Rancho La Quinta DUPLEX
48220 & 48230 Via Vallarta
The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
Permanently marked identification signs shall be attached to all control valves.
The following inspections/tests are required to be witnessed by Office of the Fire Marshal Staff:
(a) Overhead Rough and Hydro static test: All piping shall be visible and pumped at normal
operating pressure. *No jacketed electrical and data wiring shall be in contact with, nor have the
potential to contact CPVC piping once insulation is installed.
(b) Final inspection
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Rebecca Winscott - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 48220 & 48230 Via Vallarta PERMIT#: FSS2022-0307 / 0320 DATE
ISSUED: 9-21-22
DESCRIPTION: Rancho La Quinta DUPLEX CONTRACTOR: Silverado Fire Protection
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.