Description: SIGNATURE / FIRE SPRINKLER PLAN / BRES2022-0470 / PLAN 8B
Type: FIRE SPRINKLER (WEB)Subtype: RESIDENTIAL - TRACT
HOMES
Status: FINALED Applied: 10/7/2022 ECON
Parcel No: 775220021 Site Address: 80132 CHAMPIONS WY LA QUINTA,CA 92253 Approved: 10/11/2022 JLIM
Subdivision: PM 20426 Block: Lot: 9 Issued: 10/12/2022 AMA
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 4/11/2023 LRO
Valuation: $1,540.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Wednesday, April 19, 2023 4:41:35 PM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0353
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING
KHET 12/5/2022 12/5/2022 NOT READY No fee
OVERHEAD HYRO KHET 12/5/2022 12/5/2022 NOT READY No fee
OVERHEAD HYRO LRO 1/11/2023 1/11/2023 APPROVED
OVERHEAD ROUGH
PIPING
LRO 1/11/2023 1/11/2023 APPROVED
FIRE FINAL**LRO 4/11/2023 4/11/2023 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST PERMIT TECH –
ETRAKIT (1 DAY)
JACK LIMA 10/7/2022 10/10/2022 10/11/2022 COMPLETE
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $167.00 $167.00 10/12/22 WEB13308 739503439 CREDIT 684600 ECON
Total Paid for FIRE FEES: $167.00 $167.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $11.00 $11.00 10/12/22 WEB13308 739503439 CREDIT 684600 ECON
Total Paid for RECORDS MANAGEMENT FEE: $11.00 $11.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $8.00 $8.00 10/12/22 WEB13308 739503439 CREDIT 684600 ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $8.00 $8.00
TOTALS:$186.00 $186.00
Printed: Wednesday, April 19, 2023 4:41:35 PM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0353
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 10/7/2022 Etrakit Contractor Application Lot 9 Plan 8
Application.pdf 1
DOC 10/7/2022 Etrakit Contractor Tracking Sheet Lot 9 Plan 8 Building
Tracking Sheet.pdf 1
DOC 1/11/2023 LEILANI ROJAS FSS2022-0353 Insp
Notes LMR 1-11-23.pdf
FSS2022-0353 Insp
Notes LMR 1-11-23.pdf 1
BOND INFORMATION
Printed: Wednesday, April 19, 2023 4:41:35 PM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0353
*FOR REFERENCE ONLYELEV.-2'FINISH GRADEELEV.-2'0' ELEV.2'¾"METERMETERPSI LOSSELEV.-2'MAINCITYELEV.5421TO DOMESTIC WATERCONTROL VALVE FOR DOMESTIC5 GPM ALLOWANCE7PVCMAX1½"70'COPPER K MAX1"30PRESSURE REGULATORTO BE SET AT 60 PSICOPPER L1½"OCCUPANCY:CONSTRUCTION:STORIES:FIRE SPRINKLER SYSTEM:DESIGNED AND INSTALLED PER 2016 NFPA 13D ALLRESIDENTIAL WITH A .05 DENSITY WITHIN AREAS.2V-B R3 / U CONCEALED RES. PENDENT SPRINKLERRISER LOCATION (PER DETAIL)NODE POINT FOR CALCULATIONRES. PENDENT SPRINKLERCHANGE IN ELEVATIONXXBUILDING AREA: 3,063 SQFT.APPROVAL STAMPSIGNATURE @ PGA WESTPLAN 8TRACT #36537LA QUINTA, CA.AHJ: LA QUINTA FIRE DEPARTMENTGENERAL NOTESLICENSE NO. 684600705 E. HARRISON ST., SUITE 200CORONA, CA 92879PH - 800-915-3473FAX - 951-272-2535CUSTOM, TRACT, MULTI-FAMILYAND COMMERCIALDESIGN, X.X.INEERING ANDINSTALLATIONN.T.S.IF SHEET IS LESS THANSHEET FP1 OF FP4SIZE - 24" X 36"SHEET ID24" X 36" IT IS A REDUCEDSCALEPRINT SCALEREDUCE ACCORDINGLYNO. DATE REVISION12345CLASSIFICATIONC-16LICENSE NO.684600FIREPROTECTIONCONTRACTORFSTATEOFCALIFORNIAThe recipient of these planshereby acknowledges that allplans, details, specifications ormethods of installationcontained in this set of plans isthe sole property of FireSprinkler Systems, Inc. andthat any use of this set of plansis prohibited and is a violationof copyright laws without firstreceiving permission from FireSprinkler Systems.DRAWN BY:320341/4/21JOB NO:DATE:C.P.WOODBRIDGE PACIFICSIGNATURE @ PGA WESTBY:LA QUINTA, CAPLAN 8GENERAL NOTES AND LEGEND13D GENERAL NOTES12.11.10.9.8.7.6.5.4.3.2.1.AUTOMATIC FIRE SPRINKLER SYSTEM HAS BEEN DESIGNED TO BEINSTALLED IN ACCORDANCE WITH NFPA 13D, 2016 EDITION AND THEREQUIREMENTS OF THE CITY OF LA QUINTA FIRE DEPARTMENT.THIS SPRINKLER SYSTEM SHALL BE TESTED AND INSPECTED BOTHTHE ROUGH AND FINAL INSPECTION PRIOR TO OCCUPANCY BEINGGRANTED. THE JURISDICTIONAL FIRE PREVENTION OFFICE WILL BE NOTIFIED A MINIMUM OF TWO WORKING DAYS IN ADVANCE OF THE REQUESTED INSPECTION.THE INSTALLER SHALL PERFORM ALL REQUIRED ACCEPTANCE TESTS,NOTCHING, DRILLING, OR OTHERWISE PENETRATING STRUCTURALMEMBERS SHALL BE IN ACCORDANCE WITH CALIFORNIA BUILDING CODE.TYPE OF PLASTIC PIPE TO BE CPVC MANUFACTURED BY BLAZEMASTERU.L. LISTED.ALL VALVES SHALL HAVE A PERMANENTLY AFFIXED SIGN INDICATINGIT'S FUNCTION.PIPE SHALL BE HUNG FROM STRUCTURAL MEMBER PER THE UNIFORMPLUMBING CODE. PIPE CLAMPS AND SCREWS ARE MANUFACTURED BYAFCON MFG. ARE U.L. LISTED AND ARE INSTALLED ACCORDING TO THEHANGING REQUIREMENTS IN THEIR TECHNICAL DATA (SEE DETAIL).THE SPACING AND LOCATION OF SPRINKLERS SHALL CONFORM WITHTHE MANUFACTURES REQUIREMENTS AND THOSE CONTAINED IN NFPA 13D, 2016 EDITION.IF REQUIRED BY A.H.J. THE ALARM INDICATING DEVICE SHALL BE LISTEDFOR OUTSIDE SERVICE AND AUDIBLE FROM THE ADDRESS THAT THE HOUSE IS ADDRESSED ON. SMOKE DETECTORS TO BE INSTALLED BY OTHERS.RESIDENTIAL CONCEALED PENDENT SPRINKLERS ARE U.L. LISTED ANDMANUFACTURED BY SENJU. INSTALLED AT 14 FT. MAXIMUM SPACING(SEE TECH. DATA).PENDENT INTERMEDIATE TEMP. QUICK RESPONSE SPRINKLERS ARE U.L. LISTED AND MANUFACTURED BY VIKING INSTALLED AT 14 FT. MAX. SPACING(SEE TECH. DATA).13. PENDENT SPRINKLERS ARE AT LEAST 3 ft. FROM OBSTRUCTIONS E.G. LIGHTFIXTURES, CEILING FANS, ETC. OR IN ACCORDANCE WITH TABLE 8.2.5.4.2 ANDSECTION 8.2.5.1. SPRINKLER LOCATIONS FOR CONTINUOUS OBSTRUCTIONSARE IN COMPLIANCE WITH 8.2.5.4.14. SOFFITS AND CABINETS TO BE PROVIDED WITH SPRINKLER COVERAGE INACCORDANCE WITH 8.2.5.5.UNDERGROUND DETAILN.T.S. (FOR REFERENCE ONLY)RISER DETAILN.T.S.HYDRAULIC NAMEPLATEN.T.S.VICINITY MAPN.T.S.LEGAL DESCRIPTIONHANGER TIC DETAILBUILDING SUMMARYSYMBOL LEGENDHYDRAULIC SYSTEMThis Building is Protected by aHydraulically DesignedAutomatic Sprinkler System.Date InstalledLocationNumber of SprinklersBasis of Design1. DENSITY2. DESIGNED AREA OF DISCHARGESystem Demand1. WATER FLOW RATE2. RESIDUAL PRESSURE AT THE BASE OF THE RISERInstalled By Fire Sprinkler Systems, Inc.1/4/21CALC AREA 12.05 gpm/sq.ft.392 sq.ft.25.2 gpm32.7 psiRESIDUALSTATIC66.8 - 10% = 60.1 PSI72.9 - 10% = 65.6 PSIWATER FLOW INFORMATIONFLOW1,500 GPMMAIN DRAIN VALVEDRAIN TO EXTERIORRUBBER FACED CHECK VALVEELEV.GAUGE1/2"CPVC TO SYSTEM11'CPVC RISER1"10ALL WORK FOR FIRE SPRINKLERSYSTEMS, INC. TO BEGIN AT B.O.R.14-1/2" x 14-1/2"ACCESS DOOR1" CPVC52.5 PSI LOSS15. SPARE SPRINKLERS SHALL NOT BE REQUIRED TO BE PROVIDED IN ACCORDANCE WITH 5.1.1.2NOT BE REQUIRED TOSPARE SPRINKLERS SHALLPROVIDEDPER 5.1.1.23MASTER PLAN SUBMITTAL67ELEV.4'ELEV.2'STATIC PRESSURE = 79.8 PSIPSI LOSS - 6.972.9 PSIPSI LOSS = 6.9x .43416'HIGHEST PAD ELEV. @ 503'TEST HYDRANT ELEV. @ 487'ELEV. DIFFERENCE = RES. PRESSURE = 73.7 PSIPSI LOSS - 6.966.8 PSIVICINITY MAPCONCEALED RES. PENDENT SPRINKLERMASTER PLAN SUBMITTAL16.NFPA13D 8.3.5.1.1 WHERE THE FUEL-FIRED EQUIPMENT IS ABOVE ALL OF THE OCCUPIED AREAS OF THE DWELLING UNIT, NO SPRINKLER PROTECTION SHALL BE REQUIRED IN THE CONCEALED SPACE. TRACT #365376/18/21AS-BUILT PER INSPECTOR (C.H.)APPROVEDRiverside County Fire DepartmentLa Quinta Office of the Fire MarshalBy:FIRE SAFETY SPECIALIST06/30/2021 1:04:57 PMThe approval of plans and specifications does notpermit the violation, deletion, omission or faultyinstallation of any requirements of Title 24 or anyLocal Ordinances. Construction shall remainaccessible and exposed for inspection purposesuntil approved by the Fire Department.PERMIT # -FCMP2021-0008REVISED PLANSKohl HetrickReason: I am approving this documentContact Info: 760-219-6057Date: 2021.06.30 13:06:36-07'00'
LICENSE NO. 684600
705 E. HARRISON ST., SUITE 200
CORONA, CA 92879
PH - 800-915-3473
FAX - 951-272-2535
CUSTOM, TRACT, MULTI-FAMILY
AND COMMERCIAL
DESIGN, X.X.INEERING AND
INSTALLATION
1/4" = 1'
IF SHEET IS LESS THAN
SIZE - 24" X 36"
SHEET ID
24" X 36" IT IS A REDUCED
SCALE
PRINT SCALE
REDUCE ACCORDINGLY
CLASSIFICATION
C-16
LICENSE NO.
684600FIREPROTECTIONCO
N
T
R
ACTORFST
A
TE
OF C A L IF O RNIAThe recipient of these plans
hereby acknowledges that all
plans, details, specifications or
methods of installation
contained in this set of plans is
the sole property of Fire
Sprinkler Systems, Inc. and
that any use of this set of plans
is prohibited and is a violation
of copyright laws without first
receiving permission from Fire
Sprinkler Systems.
FIRE SPRINKLER PLAN
SHEET FP2 OF FP4
DESIGN AND INSTALLATION SHALL
CONFORM TO NFPA 13D, 2016 ED.
TOTAL LIVING AREA -
GARAGE AREA-
2nd FLOOR AREA -
1st FLOOR AREA - 2,017 SQ. FT.
513 SQ. FT.
2,530 SQ. FT.
533 SQ. FT.NO.DATEREVISION12345TV
C6
TV
C6
SD
D W
CM SD SD
TV
C6
JSCALE: 1/4" = 1'-0"
PLAN 8 - 1ST FLOOR SPRINKLER PLAN
HEAT ZONE
COVERED
OUTDOOR
DINING ROOM
VOLUME CLG.
LIVING ROOM
VOLUME CLG.
MASTER BEDROOM
10'-0" CLG.
19 SQFT.
MASTER BATH
10'-0" CLG.
W.I.C.
9'-0" CLG.
LAUNDRY
9'-0" CLG.
BATH 2
9'-0" CLG.
PANTRY
10'-0" CLG.
GARAGE
10'-0" CLG.
KITCHEN
10'-0" CLG.
CAB.
8 SQFT.
CAB.
POWDER
10'-0" CLG.
44 SQFT.
BEDROOM 2
10'-0" CLG.
16 SQFT.
PORCH
GOLF CART GARAGE
10'-0" CLG.
30 SQFT.UP ¾" x 10'-0"HEAT ZONE
RISER
LOCATION
10
3'-7"5'-2"3'10'-1"3'-6"4'-7"3'-8"2'-5"3'-2"5'5'-11"2'-3"6'-5"7'-10"4'-8"
2'-10"3'-7"3'-3"4'-11"7'11"6'-3"1'-7"9"3'6'-5"3'-7"3'-1"9"9'-3"10"3'-6"
13'-10"1'5'-6"1'4'-10"
4'-3"
18'9"2'2'-11"
3'9"1'-1"3'-7"4'-5"4'-5"3'-3"
3'-1"5'5'5'5'5'-5"13'-8"8'-2"8'-1"
6'-7"1'-11"9'-6"6'
7'4'-1"5'-10"5'-8"4'-10"8'-7"6'-5"6'-6"
3'8'8'5'4'UP ¾" x 10'-0"UP ¾" x 10'-0"UP ¾" x 10'-0"20'x20' SPACING
20'x20' SPACING
LINE OF
FLOOR ABOVE
LINE OF
FLOOR ABOVE
OPEN TO
ABOVE
LINE OF
FLOOR ABOVE
*1½" STRUCT.
PENETRATION*
1112
13
SIZE - SYSTEM PIPE: 3/4" thru 3"
MATERIAL - CARBON STEEL.
FINISH - Mil. Galvanized.
LISTING/APPROVAL -
203-EX 4231, EX 2551
FUNCTION - Support horizontal piping: CPVC, Copper or Steel.
Size 3/4" - 2" Prevents upward movement of pipe from pendent sprinkler discharge.
Stabilize vertical piping.
INSTALLATION - Per these instructions
including NFPA 13, 13R, 13D and CPVC manufacturers instructions.
install on horizontal or vertical mounting surface.
FASTENERS - UL Listed per NFPA 13
in WOOD:
3/4" - 3" CPVC PIPE - #905 screw - no pre-drill.
3/4" - 3" Steel and Copper pipe - #14 x 1 1/2" SMS or
1/4"x1 1/2" lag bolt - no pre-drill.
in STEEL: min. 18 GA.
3/4" - 3" CPVC, Copper and Steel pipe - 1/4" or #14 Tek Screw.
FEATURES
* Offset edge eliminates abrasion.
* Retainer dimples secure hanger to pipe during installation.
* Required AFCON #905 screw included - 5/16" hex head.
ORDERING - Part # and pipe size.
CAN ALSO BE USED TO REPLACE - #500 Pipe Strap
#520 Tin Strap
StabilizeHanger
Restraint
2.126
2.312
3.170
3.400
4.320
5.3203
2 1/2
1 1/2
1 1/4
1
3/4
510
SIZE
FAST.
DIM.
AFCON 510 HANGER (STEEL - COPPER - C.P.V.C.)
NOT TO SCALE
Nominal Pipe Size (in.)
¾"1"1¼"1½"2"2½"3"3½"4"5"6"8"
N/A 12'-0"12'-0"15'-0"15'-0"15'-0"15'-0"15'-0"15'-0"15'-0"15'-0"
12'-0"N/A
15'-0"
12'-0"12'-0"12'-0"12'-0"12'-0"N/A N/A N/A N/A N/A
8'-0"8'-0"10'-0"10'-0"12'-0"12'-0"12'-0"15'-0"15'-0"15'-0"15'-0"15'-0"
5'-6"6'-0"6'-6"7'-0"8'-0"9'-0"10'-0"N/A N/A N/A N/A N/A
N/A 3'-9"4'-7"5'-0"5'-11"N/A N/A N/A N/A N/A N/A N/A
2'-11"3'-4"3'-11"4'-5"5'-5"N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A 15'-0"N/A N/A 15'-0"N/A 15'-0"15'-0"
Steel pipe except threaded
lightwall
Threaded lightwall steel
pipe
Copper tube
CPVC
Polybutylene (IPS)
Polybutylene (CTS)
Ductile iron pipe
1.50
#905 #906
AFCON 514 HANGER (STEEL - COPPER - C.P.V.C.)
NOT TO SCALE
Restraint
Restraint
Nominal Pipe Size (in.)
¾"1"1¼"1½"2"2½"3"3½"4"5"6"8"
N/A 12'-0"12'-0"15'-0"15'-0"15'-0"15'-0"15'-0"15'-0"15'-0"15'-0"
12'-0"N/A
15'-0"
12'-0"12'-0"12'-0"12'-0"12'-0"N/A N/A N/A N/A N/A
8'-0"8'-0"10'-0"10'-0"12'-0"12'-0"12'-0"15'-0"15'-0"15'-0"15'-0"15'-0"
5'-6"6'-0"6'-6"7'-0"8'-0"9'-0"10'-0"N/A N/A N/A N/A N/A
N/A 3'-9"4'-7"5'-0"5'-11"N/A N/A N/A N/A N/A N/A N/A
2'-11"3'-4"3'-11"4'-5"5'-5"N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A 15'-0"N/A N/A 15'-0"N/A 15'-0"15'-0"
Steel pipe except threaded
lightwall
Threaded lightwall steel
pipe
Copper tube
CPVC
Polybutylene (IPS)
Polybutylene (CTS)
Ductile iron pipe
SIZE - SYSTEM PIPE: 3/4" thru 2"
MATERIAL - Carbon Steel.
FINISH - Mil. Glavanized.
LISTING/APPROVAL -
INSTALLATION - Per these instructions
PATENT - No. 6,648,278.
203-EX 4231, EX 2551
Stabilize vertical piping.
Install on horizontal or vertical mounting surface.
FUNCTION - Support horizontal piping: CPVC, Copper or Steel.
WOOD - CPVC pipe - #905 screw- no pre-drill.
Provides listed vertical/horizontal restraint and prevents
Thru 5/8" gypsum board - 1/4"x 2" lag screw.
upward movement of pipe from pendent sprinkler discharge.
When #905 threads are exposed in wood, install #906 backing nut.
including NFPA 13, 13R, 13D and CPVC manufacturers instructions.
Snap over pipe then squeeze strap back allowing pipe to slide freely.
STEEL - min. 18 GA. - CPVC, Copper and Stell pipe - 1/4" or #14 Tek Screw.
FASTENERS - UL Listed per NFPA 13
CONCRETE: Required minimum load each fasterner = 5(wt)+250lbs.
Copper and Steel pipe - #14 SMS or 1/4 "x1 1/2" lag screw - no pre-drill.
2
FEATURES
* 1 1/2" Offset - loose fit allows pipe to slide.
* Common center-line for 3/4" and 1".
* Offset edge eliminates abrasion.
* AFCON #905 screw included - 5/16" hex head.
ORDERING - Part # and pipe size.
AFCON #906 backing nut sold serparately.
3.00
Stabilize
Hanger/Restrainer
DRAWN BY:
32034
1/4/21
JOB NO:
DATE:
C.P.WOODBRIDGE PACIFICSIGNATURE @ PGA WESTBY:LA QUINTA, CAPLAN 8MASTER PLAN SUBMITTALTRACT #36537SENJUVIKING3.73.0205°175°14'x14'14'x14'SPACINGTEMP.K-FAC.SYMBOLMODELMANUF.SIN #SS8261VK470FREEDOMPENDENT7/16"7/16"ORIFICERC-RESCONC. PEND.136QUANTITY2TOTAL SPRINKLERS IN THIS SHEET:21---------VIKING4.9200°20'x20'VK4947/16"FREEDOMCONC. PEND.NOTES:
1.ALL HEAD SPACING TO BE 14'x14', UNLESS OTHERWISE
NOTED.
2.ALL PIPES TO BE ¾" CPVC, UNLESS OTHERWISE NOTED.
3.PIPE CLEARANCES MUST BE IN ACCORDANCE WITH NFPA
13-9.3.4.
4.HANGERS SHOWN FOR REFERENCE PURPOSES ONLY.
HANGER SPACING TO BE PER TABLES ON THIS SHEET.
5.ALL PIPING INSTALLED WITHIN THE ATTIC SHALL BE
PROVIDED WITH MIN. 6" INSULATION ON THE ATTIC SIDE OF
THE PIPING TO AVOID EXPOSURE OF THE PIPING TO
TEMPERATURES IN EXCESS OF THE PIPES RATED
TEMPERATURE (2016 NFPA 13D 7.7).
6.SPRINKLERS SHALL NOT BE REQUIRED IN BATHROOMS OF
55sqft. AND LESS. (SECTION 8.3.2.)
7.SPRINKLERS SHALL NOT BE REQUIRED IN CLOTHES
CLOSETS, LINEN CLOSETS, AND PANTRIES THAT MEET ALL
OF THE FOLLOWING REQUIREMENTS:
(1) THE AREA OF THE SPACE DOES NOT EXCEED 24sqft.
(2) THE WALLS AND CEILINGS ARE SURFACED WITH
NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE
MATERIALS AS DEFINED IN NFPA 220.
8. 8.2.5.1.2 THE DISTANCE SHALL BE MEASURED FROM THE
CENTER OF THE SPRINKLER TO THE CENTER OF THE
OBSTRUCTION.
9. 8.2.5.6 SHADOW AREAS SHALL BE PERMITTED IN THE
PROTECTION AREA OF A SPRINKLER AS LONG AS THE
CUMULATIVE DRY AREA DO NOT EXCEED 15sqft (1.4 sqm)
PER SPRINKLER.
U
P
¾
"
x
1
0
'
-
0
"UP ¾" x 10'-0"1
1 6/18/21AS-BUILT PER INSPECTOR (C.H.)
J
TV
C6
SD
TV
C6
SD
CM
CM
SD
SCALE: 1/4" = 1'-0"
PLAN 8 - 2ND FLOOR SPRINKLER PLAN
LOFT
9'-0" CLG.
ATTIC
ACCESS
BEDROOM 3
9'-0" CLG.
BATH 3
9'-0" CLG.
LICENSE NO. 684600
705 E. HARRISON ST., SUITE 200
CORONA, CA 92879
PH - 800-915-3473
FAX - 951-272-2535
CUSTOM, TRACT, MULTI-FAMILY
AND COMMERCIAL
DESIGN, X.X.INEERING AND
INSTALLATION
1/4" = 1'
IF SHEET IS LESS THAN
SIZE - 24" X 36"
SHEET ID
24" X 36" IT IS A REDUCED
SCALE
PRINT SCALE
REDUCE ACCORDINGLY
CLASSIFICATION
C-16
LICENSE NO.
684600FIREPROTECTIONCO
N
T
R
ACTORFST
A
TE
OF C A L IF O RNIAThe recipient of these plans
hereby acknowledges that all
plans, details, specifications or
methods of installation
contained in this set of plans is
the sole property of Fire
Sprinkler Systems, Inc. and
that any use of this set of plans
is prohibited and is a violation
of copyright laws without first
receiving permission from Fire
Sprinkler Systems.
FIRE SPRINKLER PLAN
SHEET FP3 OF FP4
DESIGN AND INSTALLATION SHALL
CONFORM TO NFPA 13D, 2016 ED.NO.DATEREVISION12345TOTAL LIVING AREA -
GARAGE AREA-
2nd FLOOR AREA -
1st FLOOR AREA - 2,017 SQ. FT.
513 SQ. FT.
2,530 SQ. FT.
533 SQ. FT.
HEAT ZONE
56 SQ. FT.
13 SQ. FT.
5'-3"10'-5"11'-9"7'-11"1'-10"2'-3"1'-7"4'-4"7'-2"4'-1"4'-10"8'-9"6"
2'-5"5'-3"8'-3"5'-3"8'-3"5'-3"
13'1'-7"2'-5"6"
13'-6"7'6'-4"
12'14'6'-7"7'3'-7"4'-6"6'-5"10'5'-7"1'
-
2
"5'-4"DN ¾" x 10'-0"DN ¾" x 10'-0"DN ¾" x 10'-0"D
N
¾
"
x
1
0
'
-
0
"
20'x20' SPACING
OPEN TO
BELOW
REQUIRED
PER 8.2.5.6
(6 SQ. FT.)
NO A/S
REQUIRED
PER 8.2.5.6
(2 SQ. FT.)
NO A/S
R.A.G.
14
15
2322
18
19
16
17
20
21
CALC AREA 2
CALC AREA 1
4'
SIZE - SYSTEM PIPE: 3/4" thru 3"
MATERIAL - CARBON STEEL.
FINISH - Mil. Galvanized.
LISTING/APPROVAL -
203-EX 4231, EX 2551
FUNCTION - Support horizontal piping: CPVC, Copper or Steel.
Size 3/4" - 2" Prevents upward movement of pipe from pendent sprinkler discharge.
Stabilize vertical piping.
INSTALLATION - Per these instructions
including NFPA 13, 13R, 13D and CPVC manufacturers instructions.
install on horizontal or vertical mounting surface.
FASTENERS - UL Listed per NFPA 13
in WOOD:
3/4" - 3" CPVC PIPE - #905 screw - no pre-drill.
3/4" - 3" Steel and Copper pipe - #14 x 1 1/2" SMS or
1/4"x1 1/2" lag bolt - no pre-drill.
in STEEL: min. 18 GA.
3/4" - 3" CPVC, Copper and Steel pipe - 1/4" or #14 Tek Screw.
FEATURES
* Offset edge eliminates abrasion.
* Retainer dimples secure hanger to pipe during installation.
* Required AFCON #905 screw included - 5/16" hex head.
ORDERING - Part # and pipe size.
CAN ALSO BE USED TO REPLACE - #500 Pipe Strap
#520 Tin Strap
StabilizeHanger
Restraint
2.126
2.312
3.170
3.400
4.320
5.3203
2 1/2
1 1/2
1 1/4
1
3/4
510
SIZE
FAST.
DIM.
AFCON 510 HANGER (STEEL - COPPER - C.P.V.C.)
NOT TO SCALE
Nominal Pipe Size (in.)
¾"1"1¼"1½"2"2½"3"3½"4"5"6"8"
N/A 12'-0"12'-0"15'-0"15'-0"15'-0"15'-0"15'-0"15'-0"15'-0"15'-0"
12'-0"N/A
15'-0"
12'-0"12'-0"12'-0"12'-0"12'-0"N/A N/A N/A N/A N/A
8'-0"8'-0"10'-0"10'-0"12'-0"12'-0"12'-0"15'-0"15'-0"15'-0"15'-0"15'-0"
5'-6"6'-0"6'-6"7'-0"8'-0"9'-0"10'-0"N/A N/A N/A N/A N/A
N/A 3'-9"4'-7"5'-0"5'-11"N/A N/A N/A N/A N/A N/A N/A
2'-11"3'-4"3'-11"4'-5"5'-5"N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A 15'-0"N/A N/A 15'-0"N/A 15'-0"15'-0"
Steel pipe except threaded
lightwall
Threaded lightwall steel
pipe
Copper tube
CPVC
Polybutylene (IPS)
Polybutylene (CTS)
Ductile iron pipe
1.50
#905 #906
AFCON 514 HANGER (STEEL - COPPER - C.P.V.C.)
NOT TO SCALE
Restraint
Restraint
Nominal Pipe Size (in.)
¾"1"1¼"1½"2"2½"3"3½"4"5"6"8"
N/A 12'-0"12'-0"15'-0"15'-0"15'-0"15'-0"15'-0"15'-0"15'-0"15'-0"
12'-0"N/A
15'-0"
12'-0"12'-0"12'-0"12'-0"12'-0"N/A N/A N/A N/A N/A
8'-0"8'-0"10'-0"10'-0"12'-0"12'-0"12'-0"15'-0"15'-0"15'-0"15'-0"15'-0"
5'-6"6'-0"6'-6"7'-0"8'-0"9'-0"10'-0"N/A N/A N/A N/A N/A
N/A 3'-9"4'-7"5'-0"5'-11"N/A N/A N/A N/A N/A N/A N/A
2'-11"3'-4"3'-11"4'-5"5'-5"N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A 15'-0"N/A N/A 15'-0"N/A 15'-0"15'-0"
Steel pipe except threaded
lightwall
Threaded lightwall steel
pipe
Copper tube
CPVC
Polybutylene (IPS)
Polybutylene (CTS)
Ductile iron pipe
SIZE - SYSTEM PIPE: 3/4" thru 2"
MATERIAL - Carbon Steel.
FINISH - Mil. Glavanized.
LISTING/APPROVAL -
INSTALLATION - Per these instructions
PATENT - No. 6,648,278.
203-EX 4231, EX 2551
Stabilize vertical piping.
Install on horizontal or vertical mounting surface.
FUNCTION - Support horizontal piping: CPVC, Copper or Steel.
WOOD - CPVC pipe - #905 screw- no pre-drill.
Provides listed vertical/horizontal restraint and prevents
Thru 5/8" gypsum board - 1/4"x 2" lag screw.
upward movement of pipe from pendent sprinkler discharge.
When #905 threads are exposed in wood, install #906 backing nut.
including NFPA 13, 13R, 13D and CPVC manufacturers instructions.
Snap over pipe then squeeze strap back allowing pipe to slide freely.
STEEL - min. 18 GA. - CPVC, Copper and Stell pipe - 1/4" or #14 Tek Screw.
FASTENERS - UL Listed per NFPA 13
CONCRETE: Required minimum load each fasterner = 5(wt)+250lbs.
Copper and Steel pipe - #14 SMS or 1/4 "x1 1/2" lag screw - no pre-drill.
2
FEATURES
* 1 1/2" Offset - loose fit allows pipe to slide.
* Common center-line for 3/4" and 1".
* Offset edge eliminates abrasion.
* AFCON #905 screw included - 5/16" hex head.
ORDERING - Part # and pipe size.
AFCON #906 backing nut sold serparately.
3.00
Stabilize
Hanger/Restrainer
DRAWN BY:
32034
1/4/21
JOB NO:
DATE:
C.P.WOODBRIDGE PACIFICSIGNATURE @ PGA WESTBY:LA QUINTA, CAPLAN 8MASTER PLAN SUBMITTALTRACT #36537SENJUVIKING3.73.0205°175°14'x14'14'x14'SPACINGTEMP.K-FAC.SYMBOLMODELMANUF.SIN #SS8261VK470FREEDOMPENDENT7/16"7/16"ORIFICERC-RESCONC. PEND.7-QUANTITY1TOTAL SPRINKLERS IN THIS SHEET:8---------VIKING4.9200°20'x20'VK4947/16"FREEDOMCONC. PEND.NOTES:
1.ALL HEAD SPACING TO BE 14'x14', UNLESS OTHERWISE
NOTED.
2.ALL PIPES TO BE ¾" CPVC, UNLESS OTHERWISE NOTED.
3.PIPE CLEARANCES MUST BE IN ACCORDANCE WITH NFPA
13-9.3.4.
4.HANGERS SHOWN FOR REFERENCE PURPOSES ONLY.
HANGER SPACING TO BE PER TABLES ON THIS SHEET.
5.ALL PIPING INSTALLED WITHIN THE ATTIC SHALL BE
PROVIDED WITH MIN. 6" INSULATION ON THE ATTIC SIDE OF
THE PIPING TO AVOID EXPOSURE OF THE PIPING TO
TEMPERATURES IN EXCESS OF THE PIPES RATED
TEMPERATURE (2016 NFPA 13D 7.7).
6.SPRINKLERS SHALL NOT BE REQUIRED IN BATHROOMS OF
55sqft. AND LESS. (SECTION 8.3.2.)
7.SPRINKLERS SHALL NOT BE REQUIRED IN CLOTHES
CLOSETS, LINEN CLOSETS, AND PANTRIES THAT MEET ALL
OF THE FOLLOWING REQUIREMENTS:
(1) THE AREA OF THE SPACE DOES NOT EXCEED 24sqft.
(2) THE WALLS AND CEILINGS ARE SURFACED WITH
NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE
MATERIALS AS DEFINED IN NFPA 220.
8. 8.2.5.1.2 THE DISTANCE SHALL BE MEASURED FROM THE
CENTER OF THE SPRINKLER TO THE CENTER OF THE
OBSTRUCTION.
9. 8.2.5.6 SHADOW AREAS SHALL BE PERMITTED IN THE
PROTECTION AREA OF A SPRINKLER AS LONG AS THE
CUMULATIVE DRY AREA DO NOT EXCEED 15sqft (1.4 sqm)
PER SPRINKLER.DN ¾" x 10'-0"DN ¾" x 10'-0"3'
4'-6"3'-9"2'1
1 6/18/21AS-BUILT PER INSPECTOR (C.H.)
LICENSE NO. 684600
705 E. HARRISON ST., SUITE 200
CORONA, CA 92879
PH - 800-915-3473
FAX - 951-272-2535
CUSTOM, TRACT, MULTI-FAMILY
AND COMMERCIAL
DESIGN, X.X.INEERING AND
INSTALLATION
AS SHOWN
IF SHEET IS LESS THAN
SIZE - 24" X 36"
SHEET ID
24" X 36" IT IS A REDUCED
SCALE
PRINT SCALE
REDUCE ACCORDINGLY
CLASSIFICATION
C-16
LICENSE NO.
684600FIREPROTECTIONCO
N
T
R
ACTORFST
A
TE
OF C A L IF O RNIAThe recipient of these plans
hereby acknowledges that all
plans, details, specifications or
methods of installation
contained in this set of plans is
the sole property of Fire
Sprinkler Systems, Inc. and
that any use of this set of plans
is prohibited and is a violation
of copyright laws without first
receiving permission from Fire
Sprinkler Systems.SECTIONS FOR REFERENCE ONLYSECTIONS
SHEET FP4 OF FP4NO.DATEREVISION12345DRAWN BY:
32034
1/4/21
JOB NO:
DATE:
C.P.WOODBRIDGE PACIFICSIGNATURE @ PGA WESTBY:LA QUINTA, CAPLAN 8MASTER PLAN SUBMITTALTRACT #365376/18/21AS-BUILT PER INSPECTOR (C.H.)