FSS2022-0436ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT K P S FIRE SPRINKLERS INC 760 SOUTH ROCHESTER
AVENUE
ONTARIO CA 91761 (909)980-9222 RValencia@kpspowerh
ome.com
CONTRACTOR K P S FIRE SPRINKLERS INC 760 SOUTH ROCHESTER
AVENUE
ONTARIO CA 91761 (909)980-9222 RValencia@kpspowerh
ome.com
OWNER DESERT CLUB ESTATES 50710 CALLE QUITO LA QUINTA CA 92253 (909)980-9222
CONDITIONS
Description: DESERT CLUB / FIRES SPRINKLERS / BRES2021-0708
Type: FIRE SPRINKLER (WEB)Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 11/23/2022 ECON
Parcel No: 770094003 Site Address: 50710 CALLE QUITO LA QUINTA,CA 92253 Approved: 12/19/2022 RWI
Subdivision: DESERT CLUB TR UNIT 5 Block: Lot: 48 Issued: ONLINE
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 6/30/2023 LRO
Valuation: $9,500.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details: 50710 CALLE QUITO LOT 48
FINANCIAL INFORMATION
Printed: Thursday, July 20, 2023 3:56:08 PM 1 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0436
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD HYRO KHET 12/29/2022 12/29/2022 APPROVED No leaks
OVERHEAD ROUGH
PIPING KHET 12/29/2022 12/29/2022 DISAPPROVE
D SEE NOTES
*As-Built Plans required prior to final
inspection.
Reinspection required:
- Add head in hall due to over-sized shadow
area.
- Need to confirm protection against contact
with jacketed electrical wiring throughout.
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE FAILED OR
ADDITIONAL FIELD
INSPECTIONS
(EXCESSIVE) EACH
101-0000-42421 0 $175.00 $175.00 12/30/22 WEB13944 779527623 CREDIT 954532 ECON
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $167.00 $167.00 12/20/22 WEB13875 773497758 CREDIT 954532 ECON
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $250.00 $250.00 12/20/22 WEB13875 773497758 CREDIT 954532 ECON
Total Paid for FIRE FEES: $592.00 $592.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $11.00 $11.00 12/20/22 WEB13875 773497758 CREDIT 954532 ECON
Total Paid for RECORDS MANAGEMENT FEE: $11.00 $11.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $8.00 $8.00 12/20/22 WEB13875 773497758 CREDIT 954532 ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $8.00 $8.00
TOTALS:$611.00 $611.00
Printed: Thursday, July 20, 2023 3:56:08 PM 2 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0436
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 11/23/2022 Etrakit Contractor 1ST SUBMITTAL
HYDRAULIC CALCS
50710 CALLE QUITO LOT
48 - CALCULATIONS.pdf 1
DOC 11/23/2022 Etrakit Contractor 1ST SUBMITTAL FIRE
FLOW
50710 CALLE QUITO LOT
48 - FIRE FLOW TEST.pdf 1
DOC 11/23/2022 Etrakit Contractor 1ST SUBMITTAL PLAN
50710 CALLE QUITO LOT
48 - FIRE SPRINKLER
PLAN.pdf
1
DOC 11/23/2022 Etrakit Contractor 1ST SUBMITTAL CUT
SHEETS
50710 CALLE QUITO LOT
48 - FS MATERIAL
BROCHURE.pdf
1
DOC 6/20/2023 Etrakit Contractor Calculations Delta 1
50710 CALLE QUITO LOT
48 CALCULATIONS
DELTA 1.pdf
1
BOND INFORMATION
OVERHEAD ROUGH
PIPING KHET 1/4/2023 1/4/2023 APPROVED
FIRE FINAL**LRO 6/30/2023 6/30/2023 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST FIRE - ETRAKIT
(2 WK)
REBECCA
WINSCOTT
11/23/2022 12/9/2022 12/19/2022 APPROVED
1ST PERMIT TECH –
ETRAKIT (1 DAY)
PERMIT TECH
BUCKET
11/23/2022 11/28/2022 11/23/2022 COMPLETE
2ND FIRE (1 WK)KOHL
HETRICK
6/22/2023 6/29/2023 6/27/2023 APPROVED AS-BUILTS (NO FEE)
PARENT PROJECTS
Printed: Thursday, July 20, 2023 3:56:08 PM 3 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0436
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 6/20/2023 Etrakit Contractor Fire Sprinkler Plan Delta
1
50710 CALLE QUITO LOT
48 FIRE SPRINKLER PLAN
DELTA 1.pdf
1
DOC 6/20/2023 Etrakit Contractor FS Material Brochure
Delta 1
50710 CALLE QUITO LOT
48 FS MATERIAL
BROCHURE DELTA 1.pdf
1
DOC 6/20/2023 Etrakit Contractor Inspector Notes
FSS222 0436 12 29 2722
Insp Notes (50710 Calle
Quito Lot 48).pdf
1
DOC 12/29/2022 KOHL HETRICK FSS222-0436 12-29-2722
- Insp Notes.pdf
FSS222-0436 12-29-2722
- Insp Notes.pdf 1
DOC 6/27/2023 KOHL HETRICK FSS2022-0436 - AS-
BUILTS - APPROVED.pdf
FSS2022-0436 - AS-
BUILTS - APPROVED.pdf 1
DOC 12/19/2022 REBECCA WINSCOTT LQ FSS2022-0436 Lot 48
COA.pdf
LQ FSS2022-0436 Lot 48
COA.pdf 1
DOC 12/19/2022 REBECCA WINSCOTT LQ FSS2022-0436 Lot 48
APPROVED.pdf
LQ FSS2022-0436 Lot 48
APPROVED.pdf 1
Printed: Thursday, July 20, 2023 3:56:08 PM 4 of 4
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0436
FSS2022-0436 AS-BUILTS
JSDJJJEFSD COSD COEFJSDJSD COSDEFJJEFEFFP-3AFP-3BFP-3CR3'-0"R3'-0"R3'-0"R3'-0"R3'-0"R3'-0"R3'-0"GARAGE9'-6"BATH 29'-6"W.I.C.9'-6"COATS9'-6"DROP9'-6"BEDROOM 29'-6"20'X20'HALL9'-6"OUTDOOR LIVING #39'-6"RETURNAIRHALL9'-6"LAU.9'-6"BEDROOM 39'-6"20'X20'W.I.C.9'-6"BATH 39'-6"W.I.C.9'-6"PREP. KITCHEN9'-6"20'X20'RETURNAIRDEN/OFFICE9'-6"ENTRY9'-6"PORCH9'-6"PDR.9'-6"PRIMARY BEDROOM9'-6"20'X20'HALL9'-6"W.I.C.9'-6"20'X20'HALL9'-6"TOILET9'-6"HALL9'-6"PRIMARY BATH9'-6"20'X20'OUTDOOR LIVING #19'-6"OUTDOOR LIVING #29'-6"DINING12'-1"KITCHEN12'-1"GREAT ROOM12'-1"R3'-0"PORTICO12'-1"LINTELLINTELLINTELLINTELLINTELLINTELLINTELLINTELLINTELLINTELLINTELLINTELLINTEL
LINTEL
LINTEL
LINTEL
LINTEL
LINTEL
LINTELATTICACCESSFAU INSIDE ATTICSEE FAU NOTEON THIS SHEET
ATTICACCESSFAU INSIDE ATTIC
SEE FAU NOTE
ON THIS SHEET
RETURNAIRRETURNAIRSOFFIT9'-6"1" FIRE SPRINKLER TORBORRISER WITH ACCESSPANEL ACCESSIBLE INSIDE GARAGE, SEESHEET FP-1 RISER DETAIL. 20'X20'LINTEL
HEAT ZONE
HEAT ZONE
FIRE PLACE
5'-5"4'-6"2'-8"8'-6"15'-212"6'-812"7'-0"13'-6"7'-1012"2'-6"4'-0"4'-512"3'-6"8'-1112"10'-0"5'-412"4'-8"1'-10"1'-8"4'-11"1'-9"3'-5"8'-5"3'-5"3'-11"4'-012"10'-0"9'-412"6'-1"4'-812"9'-012"10'-0"4'-7"3'-6"3'-9"2'-4"3'-9"2'-812"10'-0"4'-8"6'-6"4'-6"2'-0"9'-8"4'-912"9'-412"6'-312"14'-8"3'-8"13'-8"16'-0"7'-3"3'-8"14'-8"3'-8"4'-1112"10'-512"5'-8"5'-81
2"5'-81
2"7'-5"5'-91
2"
5'-9"4'-10"5'-81
2"1'-8"10'-0"4'-1"
4'-11
2"3'-512"4'-2"4'-10"
9'-61
2"4'-111
2"4'-9"7'-6"7'-6"4'-312"2'-31
2"
3'-11"3'-712"7'-6"16'-0"15'-3"10'-3"4'-0"7'-10"4'-9"
4'-9"2'-3"3'-6"3'-61
2"
4'-1"8'-0"1'-212"4'-912"8'-0"12138956SHADOW7 SQ FTSEE NOTE CH4D4D1H1D2H2D3H3H5D51210113471415FIRE SPRINKLER 1ST FLOOR PLANSCALE: ¼"=1'-0"GREAT ROOMMOST DEMANDING16' X 16' SPACING OUTDOOR LIVING #2PROOF CALCULATION16' X 16' SPACING PRIMARY BATHMOST DEMANDING20'X20' SPACING LINE OF CEILINGHEIGHT CHANGELINE OF CEILINGHEIGHT CHANGELINE OF CEILINGHEIGHT CHANGELINE OF CEILINGHEIGHT CHANGEREVISIONSTHE RECIPIENT OF THESE PLANS HEREBYACKNOWLEDGES THAT ALL PLANS, DETAILS,SPECIFICATIONS OR METHODS OF INSTALLATIONCONTAINED WITHIN THIS SET OF PLANS IS THESOLE PROPERTY OF KPS FIRE SPRINKLER INC.AND THAT ANY USE OF THIS SET OF PLANS ISPROHIBITED WITHOUT RECEIVING PERMISSIONFROM KPS FIRE SPRINKLER INC.FP-2
2
FIRE SPRINKLER PLAN AND HYDRAULIC CALCULATIONS DESCRIPTIONDATENO.RESIDUAL PRESSUREGPM DISCHARGEGPMPSIDESIGNED AREA OF DISCHARGE:NO. OF SPRINKLERSSYSTEM DEMAND AT THE BASE OF RISERBASIS OF DESIGNDENSITY:LOCATIONSQ.FT.GPM/SQ.FT.GPM DISCHARGEGPMPSISYSTEM DEMAND AT SOURCETYPE OF SPRINKLER(S)NPT SIZETEMPRATURE RATINGORIENTATIONK-FACTORSIN NUMBERRESPONSE TYPEPROTECTION AREA PER SPRINKLERSQ.FT.AUTOMATIC SPRINKLER SYSTEMTHIS BUILDING IS PROTECTEDBY A HYDRAULICALLY DESIGNEDHYDRAULIC - SYSTEMRESIDUAL PRESSUREPSI*SAFTEY FACTORPER NFPA 13D, 2016 EDITIONPRIMARY BATH1.051 HEAD CALC.21.01928.53026.01955.519400 (20'X20')31.326NOTE:-ALL PIPING TO BE 1", UNLESS OTHERWISE NOTED.-ALL ARM-OVERS TO BE 1".-ALL HEADS DROP TO BE 1".NOTE A:SOME AREAS FALL UNDER EXCEPTIONS FOR SPRINKLERHEAD REQUIREMENTS 2016 EDITION NFPA 13D SECTIONS8.3.2 , 8.3.3, 8.3.4, 8.3.5, 8.3.6, 8.3.7 AND 8.3.8. SEE PLANFOR EXCEPTION AREAS.NOTE B:CLOSET AREAS FALL UNDER EXCEPTIONS FORSPRINKLER HEAD REQUIREMENTS 2016 EDITION NFPA13D SECTION 8.2.7 SEE PLAN FOR EXCEPTION AREAS.CALCULATION NOTE:-20'X20' PROOF CALCULATION TO APPLY TO ALLROOMS THAT CONTAIN A 20'X20' SPRINKLER HEADNOTE.NOTE C:SPRINKLER HEAD PERMITTED TO HAVE A SHADOW AREAOF 15 SQUARE FEET PER 2016 EDITION NFPA 13DSECTION 8.2.5.6.BUILDING NOTE:HOUSE TO HAVE INTERCONNECTED SMOKE DETECTORS.FAU NOTE:WHERE THE FUEL-FIRED EQUIPMENT IS ABOVE ALL OFTHE OCCUPIED AREAS OF THE DWELLING UNIT, NOSPRINKLER PROTECTION SHALL BE REQUIRED IN THECONCEALED SPACE PER 2016 NFPA SECTION 8.3.5.1.1.2016 EDITION NFPA 13D NOTES:RESIDUAL PRESSUREGPM DISCHARGEGPMPSIDESIGNED AREA OF DISCHARGE:NO. OF SPRINKLERSSYSTEM DEMAND AT THE BASE OF RISERBASIS OF DESIGNDENSITY:LOCATIONSQ.FT.GPM/SQ.FT.GPM DISCHARGEGPMPSISYSTEM DEMAND AT SOURCETYPE OF SPRINKLER(S)NPT SIZETEMPRATURE RATINGORIENTATIONK-FACTORSIN NUMBERRESPONSE TYPEPROTECTION AREA PER SPRINKLERSQ.FT.AUTOMATIC SPRINKLER SYSTEMTHIS BUILDING IS PROTECTEDBY A HYDRAULICALLY DESIGNEDHYDRAULIC - SYSTEMRESIDUAL PRESSUREPSI*SAFTEY FACTORPER NFPA 13D, 2016 EDITIONGREAT ROOM2.052 HEAD CALC.26.29620.47131.29655.625256 (16' X 16') 31.218RESIDUAL PRESSUREGPM DISCHARGEGPMPSIDESIGNED AREA OF DISCHARGE:NO. OF SPRINKLERSSYSTEM DEMAND AT THE BASE OF RISERBASIS OF DESIGNDENSITY:LOCATIONSQ.FT.GPM/SQ.FT.GPM DISCHARGEGPMPSISYSTEM DEMAND AT SOURCETYPE OF SPRINKLER(S)NPT SIZETEMPRATURE RATINGORIENTATIONK-FACTORSIN NUMBERRESPONSE TYPEPROTECTION AREA PER SPRINKLERSQ.FT.AUTOMATIC SPRINKLER SYSTEMTHIS BUILDING IS PROTECTEDBY A HYDRAULICALLY DESIGNEDHYDRAULIC - SYSTEMRESIDUAL PRESSUREPSI*SAFTEY FACTORPER NFPA 13D, 2016 EDITIONOUTDOOR LIVING #22.052 HEAD CALC.26.00719.55931.00754.231256 (16' X 16') 32.612SENJU1/2"162°CONCEALED4.9SS8464FAST RESPONSENOTE D:SPRINKLERS SHALL NOT BE REQUIRED FOR CEILINGPOCKETS THAT MEET THE CONDITION PER 2016 EDITIONNFPA 13D SECTION 8.3.7.SENJU1/2"162°CONCEALED4.9SS8464FAST RESPONSESENJU1/2"205°CONCEALED4.9SS4451FAST RESPONSEFire ♦ Security ♦ Connectivity
760 S. ROCHESTER AVE. STE B
ONTARIO, CA 91761
PH: (909)980-9222 C-16 LIC# 954532 FAX: (909)980-44777.5.6 TEMPERATURE RATINGS.7.5.6.1 SPRINKLERS INSTALLED WHERE MAXIMUM AMBIENTCEILING TEMPERATURES DO NOT EXCEED 100°F (38°C) SHALLBE ORDINARY TEMPERATURE-RATED ORINTERMEDIATE-TEMPERATURE RATED SPRINKLERSTHROUGHOUT UNLESS MODIFIED BY THE REQUIREMENTS OF7.5.6.3.7.5.6.2 SPRINKLERS INSTALLED WHERE MAXIMUM AMBIENTCEILING TEMPERATURES ARE BETWEEN 101°F AND 150°F(38°C AND 65°C) SHALL BE INTERMEDIATETEMPERATURE-RATED SPRINKLERS UNLESS MODIFIED BY7.5.6.3.7.5.6.3* THE FOLLOWING PRACTICES SHALL BE OBSERVEDWHEN INSTALLING RESIDENTIAL SPRINKLERS UNLESS HIGHEREXPECTED AMBIENT TEMPERATURES REQUIRE A HIGHERTEMPERATURE RATING:(1)SPRINKLERS UNDER GLASS OR PLASTIC SKYLIGHTSEXPOSED TO DIRECT RAYS OF THE SUN SHALL BE OFINTERMEDIATE TEMPERATURE CLASSIFICATION.(2)SPRINKLERS IN AN UNVENTILATED CONCEALED SPACEUNDER AN UNINSULATED ROOF OR IN AN UNVENTILATEDATTIC SHALL BE OF INTERMEDIATE TEMPERATURECLASSIFICATION.(3)*SPRINKLERS INSTALLED NEAR SPECIFIC HEAT SOURCESTHAT ARE IDENTIFIED IN TABLE 7.5.6.3 SHALL BE OF THETEMPERATURE RATING INDICATED IN TABLE 7.5.6.3UNLESS SPRINKLERS ARE LISTED FOR POSITIONINGCLOSER TO THE HEAT SOURCE.(4)SPRINKLERS INSTALLED IN SAUNAS AND STEAM ROOMSWHERE THE MAXIMUM AMBIENT CEILING TEMPERATURESARE BETWEEN 151°F AND 225°F (66°C TO 107°C) SHALL BEHIGH TEMPERATURE-RATED SPRAY SPRINKLERS.BUILDING SUMMARY
TOTAL LIVING AREA:
3RD FLOOR AREA:
1ST FLOOR AREA:
2ND FLOOR AREA:
GARAGE AREA:
SQ.FT.
SQ.FT.
SQ.FT.
SQ.FT.
SQ.FT.
PLAN:OCCUPANCY:
AHJ:CONSTRUCT. TYPE:
R3 / U
VB City of La Quinta
3297
888
3297
N/A
N/A
APN # 770-094-003
Haven Enterprises Inc
KPS FIRE SPRINKLERS INC
C-16 LICENSE # 954532
760 S. ROCHESTER AVE. SUITE B
ONTARIO, CA 91761
(800) 457-7252
Job Name :Haven Enterprises Inc - 50710 CALLE QUITO LOT 48
Drawing :
Location :50710 CALLE QUITO - LOT 48, LA QUINTA, CA 92253
Remote Area :GREAT ROOM
Contract :N/A
Data File :GREAT ROOM (2-HEAD) CALC - 16X16.wxtmp
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 1
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
HYDRAULIC DESIGN INFORMATION SHEET
Name - Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date - 11/09/2022
Location - 50710 CALLE QUITO - LOT 48, LA QUINTA, CA 92253
Building - System No. - GREAT ROOM
Contractor - KPS FIRE SPRINKLER‚ INC Contract No. - N/A
Calculated By - BL Drawing No. -
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height 12'-1"
OCCUPANCY - R3 / U
S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D
Y Number of Sprinklers Flowing: ( )1 (X)2 ( )4 ( )
S ( )Other
T ( )Specific Ruling Made by Date
E
M Listed Flow at Start Point - 13 Gpm System Type
Listed Pres. at Start Point - 7 Psi (X) Wet ( ) Dry
D MAXIMUM LISTED SPACING 16 x 16 ( ) Deluge ( ) PreAction
E Domestic Flow Added - 5 Gpm Sprinkler or Nozzle
S Additional Flow Added - Gpm Make SENJU RC-RES Model SS8464
I Elevation at Highest Outlet - 19'-4"Feet Size 1/2" K-Factor 4.9
G Note: Temperature Rating 162
N
Calculation Gpm Required Psi Required At BOR
Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test: Pump Data: Tank or Reservoir:
A Date of Test - 12/13/2021 Rated Cap. Cap.
T Time of Test - N/A @ Psi Elev.
E Static (Psi) - 96.5=86.85 Elev.
R Residual (Psi) - 94.2=84.78 Other Well
Flow (Gpm) - 700 Proof Flow Gpm
S Elevation - -6 FT
P Location: HYDRANT NEAR 50710 CELLE QUITO, LA QUINTA
P APN 770-094-003
L Source of Information: COACHELLA VALLEY WATER DISTRICT
Y STEVE KEALER - (760) 992-4855
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 2
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
10
20
30
40
E 50
R 60
U 70
S 80
S 90
E 100
R 110
P 120
130
140
150
100 200 300 400 500 600 700 800 900
FLOW ( N ^ 1.85 )
City Water Supply:Demand:
C1 C2
C1 - Static Pressure :86.85
C2 - Residual Pressure:84.78
C2 - Residual Flow :700
D1 - Elevation : 7.832
D2 - System Flow :26.296
D2 - System Pressure : 55.625
Hose ( Demand ):5
D3 - System Demand :31.296
Safety Margin : 31.218
D1
D2
D3
Water Supply Curve
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 3
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
Fitting Legend
Abbrev.Name ½¾1 1¼1½2 2½3 3½4 5 6 8 10 12 14 16 18 20 24
Ad Male/Female Adapter 1 1.5 2 2.8 3.5 4.5 5.5 6.5 9 14
Bv Ball Valve 2.25 2.25 2 2.5 2.25 10
Cpcv CPVC Check Valve 0 0 1 7 9 11
E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50
Kav K Copper Angle Valve 0 7 14 14 18 28
Kcs K Copper Corporation Stop 0 0 4.08 4.08 4.08 4.08
Ktee K Copper Tee Or Cross (Flow Turned 90 Degrees)0 3 6 5 8 12
Lelbw L Copper 90 Degreel Elbow 0 2 3 3 4 6
Ltee L Copper Tee Or Cross (Flow Turned 90 Degrees)0 4 7 6 9 12
N *CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0
O *CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0
R *CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with *. The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
Fittings Used Summary
Computer Programs by Hydratec Inc. Revision: 50.5520.727
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Fittings Used Summary
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 4
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
SUPPLY ANALYSIS
Node at Static Residual Available
Source Pressure Pressure Flow Pressure Total Demand Required Pressure
SRC 86.85 84.78 700.0 86.843 31.3 55.625
NODE ANALYSIS
Pressure Discharge
Node Tag Elevation Node Type at Node at Node Notes
H1 9.5 10.66
H2 9.5 10.65
H3 9.5 10.63
H4 12.083 4.9 7.04 13.0 0.05 256
H5 12.083 4.9 7.36 13.3 0.05 256
D1 10.0 10.45
1 10.0 10.45
D2 10.0 10.43
2 10.0 10.43
D3 10.0 10.41
3 10.0 10.41
4 10.0 10.35
5 10.0 9.73
6 12.583 8.34
D4 12.583 7.05
D5 12.583 7.39
7 12.583 7.6
8 12.583 8.49
9 10.0 9.93
10 10.0 10.46
11 12.583 9.36
12 12.583 9.39
13 10.0 10.53
14 10.0 10.59
15 10.0 12.99
TOR 10.0 14.87
BOR 2.0 20.47
POC 2.0 21.24
DS 2.0 23.5 5.0
UG1 -3.0 26.12
UG2 -3.0 30.09
UG3 -1.5 29.76
M1 -1.5 31.36
M2 -1.5 35.58
UG4 -1.5 39.88
SRC -6.0 55.63
Flow Summary - NFPA
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 5
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe *******Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
H1 9.500 0.0 1 N 7.0 0.500 150 10.662
to 7.000 -0.217
D1 10 0.0 1.101 7.500 0.0001 0.001 Vel = 0
0.0
D1 0.0 10.446 K Factor = 0
H2 9.500 0.0 1 N 7.0 0.500 150 10.646
to 7.000 -0.217
D2 10 0.0 1.101 7.500 0.0001 0.001 Vel = 0
0.0
D2 0.0 10.430 K Factor = 0
H3 9.500 0.0 1 N 7.0 0.500 150 10.628
to 7.000 -0.217
D3 10 0.0 1.101 7.500 0 0.0 Vel = 0
0.0
D3 0.0 10.411 K Factor = 0
H4 12.083 4.90 13.00 1 N 7.0 0.500 150 7.039
to 7.000 -0.217
D4 12.583 13.0 1.101 7.500 0.0307 0.230 Vel = 4.38
0.0
D4 13.00 7.052 K Factor = 4.90
H5 12.083 4.90 13.30 1 N 7.0 0.500 150 7.363
to 7.000 -0.217
D5 12.583 13.3 1.101 7.500 0.0320 0.240 Vel = 4.48
0.0
D5 13.30 7.386 K Factor = 4.89
D1 10 0.0 1 O 5.0 0.500 150 10.446
to 5.000 0.0
1 10 0.0 1.101 5.500 0 0.0 Vel = 0
1 10 -2.41 1 R 1.0 10.458 150 10.446
to 1.000 0.0
2 10 -2.41 1.101 11.458 -0.0014 -0.016 Vel = 0.81
0.0
2 -2.41 10.430 K Factor = -0.75
D2 10 0.0 1 O 5.0 0.500 150 10.430
to 5.000 0.0
2 10 0.0 1.101 5.500 0 0.0 Vel = 0
2 10 -2.41 1 2R 2.0 11.792 150 10.430
to 2.000 0.0
3 10 -2.41 1.101 13.792 -0.0014 -0.019 Vel = 0.81
0.0
3 -2.41 10.411 K Factor = -0.75
D3 10 0.0 1 O 5.0 0.542 150 10.411
to 5.000 0.0
3 10 0.0 1.101 5.542 0 0.0 Vel = 0
3 10 -2.41 1 2O 10.0 30.625 150 10.411
to 4R 4.0 14.000 0.0
4 10 -2.41 1.101 44.625 -0.0013 -0.060 Vel = 0.81
Final Calculations : Hazen-Williams
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 6
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe *******Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
4 10 -10.18 1 R 1.0 13.375 150 10.351
to N 7.0 8.000 0.0
5 10 -12.59 1.101 21.375 -0.0289 -0.618 Vel = 4.24
5 10 0.0 1 N 7.0 2.583 150 9.733
to 7.000 -1.119
6 12.583 -12.59 1.101 9.583 -0.0288 -0.276 Vel = 4.24
6 12.583 0.0 1 2R 2.0 23.458 150 8.338
to 2.000 0.0
7 12.583 -12.59 1.101 25.458 -0.0289 -0.736 Vel = 4.24
0.0
7 -12.59 7.602 K Factor = -4.57
D4 12.583 13.00 1 O 5.0 12.917 150 7.052
to 5.000 0.0
7 12.583 13.0 1.101 17.917 0.0307 0.550 Vel = 4.38
0.0
7 13.00 7.602 K Factor = 4.71
D5 12.583 13.30 1 O 5.0 1.750 150 7.386
to 5.000 0.0
7 12.583 13.3 1.101 6.750 0.0320 0.216 Vel = 4.48
7 12.583 0.41 1 R 1.0 18.167 150 7.602
to N 7.0 8.000 0.0
8 12.583 13.71 1.101 26.167 0.0338 0.885 Vel = 4.62
8 12.583 0.0 1 N 7.0 2.583 150 8.487
to 7.000 1.119
9 10 13.71 1.101 9.583 0.0338 0.324 Vel = 4.62
9 10 0.0 1 R 1.0 13.667 150 9.930
to O 5.0 6.000 0.0
14 10 13.71 1.101 19.667 0.0338 0.665 Vel = 4.62
0.0
14 13.71 10.595 K Factor = 4.21
4 10 10.18 1 10R 10.0 110.167 150 10.351
to 3O 15.0 25.000 0.0
15 10 10.18 1.101 135.167 0.0195 2.639 Vel = 3.43
0.0
15 10.18 12.990 K Factor = 2.82
1 10 2.41 1 N 7.0 5.125 150 10.446
to 7.000 0.0
10 10 2.41 1.101 12.125 0.0013 0.016 Vel = 0.81
10 10 0.0 1 N 7.0 2.583 150 10.462
to 7.000 -1.119
11 12.583 2.41 1.101 9.583 0.0014 0.013 Vel = 0.81
11 12.583 0.0 1 2R 2.0 19.250 150 9.356
to N 7.0 9.000 0.0
12 12.583 2.41 1.101 28.250 0.0013 0.038 Vel = 0.81
12 12.583 0.0 1 N 7.0 2.583 150 9.394
to 7.000 1.119
13 10 2.41 1.101 9.583 0.0014 0.013 Vel = 0.81
13 10 0.0 1 5R 5.0 35.958 150 10.526
to 2O 10.0 15.000 0.0
14 10 2.41 1.101 50.958 0.0014 0.069 Vel = 0.81
Final Calculations : Hazen-Williams
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 7
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe *******Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
14 10 13.70 1 6R 6.0 41.500 150 10.595
to O 5.0 11.000 0.0
15 10 16.11 1.101 52.500 0.0456 2.395 Vel = 5.43
15 10 10.19 1 R 1.0 8.667 150 12.990
to N 7.0 8.000 0.0
TOR 10 26.3 1.101 16.667 0.1129 1.881 Vel = 8.86
0.0
TOR 26.30 14.871 K Factor = 6.82
TOR 10 26.30 1 Cpcv 1.913 8.000 150 14.871
to 2R 2.0 10.912 3.465
BOR 2 26.3 1.101 N 7.0 18.912 0.1129 2.135 Vel = 8.86
BOR 2 0.0 1 Ad 3.825 3.000 150 20.471
to 3.825 0.0
POC 2 26.3 1.101 6.825 0.1130 0.771 Vel = 8.86
POC 2 0.0 1 Ltee 9.45 2.000 150 21.242
to Ad 2.7 12.150 0.0
DS 2 26.3 1.025 14.150 0.1599 2.263 Vel = 10.23
0.0
DS 26.30 23.505 K Factor = 5.42
DS 2 H5 31.30 1.5 Ad 3.808 5.000 150 23.505
to Lelbw 4.352 8.160 2.166
UG1 -3 31.3 1.505 13.160 0.0340 0.447 Vel = 5.64
UG1 -3 0.0 1.5 4E 22.749 130.000 150 26.118
to 22.749 0.0
UG2 -3 31.3 1.59 152.749 0.0260 3.973 Vel = 5.06
UG2 -3 0.0 1.5 E 5.687 1.500 150 30.091
to Ad 4.976 10.664 -0.650
UG3 -1.500 31.3 1.59 12.164 0.0261 0.317 Vel = 5.06
UG3 -1.500 0.0 1 Ad 2.7 1.500 150 29.758
to Bv 3.037 5.738 0.0
M1 -1.500 31.3 1.025 7.238 0.2208 1.598 Vel = 12.17
M1 -1.500 0.0 1 1.000 150 31.356
to 4.000 * * Fixed Loss = 4
M2 -1.500 31.3 1.025 1.000 0.2200 0.220 Vel = 12.17
M2 -1.500 0.0 1 Kav 16.354 0.500 150 35.576
to 16.354 0.0
UG4 -1.500 31.3 0.995 16.854 0.2551 4.299 Vel = 12.91
UG4 -1.500 0.0 1 Ad 2.336 40.000 150 39.875
to Kcs 4.766 14.111 1.949
SRC -6 31.3 0.995 Ktee 7.009 54.111 0.2550 13.801 Vel = 12.91
0.0
SRC 31.30 55.625 K Factor = 4.20
Final Calculations : Hazen-Williams
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC
C-16 LICENSE # 954532
760 S. ROCHESTER AVE. SUITE B
ONTARIO, CA 91761
(800) 457-7252
Job Name :Haven Enterprises Inc - 50710 CALLE QUITO LOT 48
Drawing :
Location :50710 CALLE QUITO - LOT 48, LA QUINTA, CA 92253
Remote Area :OUTDOOR LIVING2
Contract :N/A
Data File :OUTDOOR LIVING 2 (2-HEAD) CALC - 16X16.wxtmp
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 1
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
HYDRAULIC DESIGN INFORMATION SHEET
Name - Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date - 11/09/2022
Location - 50710 CALLE QUITO - LOT 48, LA QUINTA, CA 92253
Building - System No. - OUTDOOR LIVING2
Contractor - KPS FIRE SPRINKLER‚ INC Contract No. - N/A
Calculated By - BL Drawing No. -
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height 9'-6"
OCCUPANCY - R3 / U
S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D
Y Number of Sprinklers Flowing: ( )1 (X)2 ( )4 ( )
S ( )Other
T ( )Specific Ruling Made by Date
E
M Listed Flow at Start Point - 13 Gpm System Type
Listed Pres. at Start Point - 7 Psi (X) Wet ( ) Dry
D MAXIMUM LISTED SPACING 16 x 16 ( ) Deluge ( ) PreAction
E Domestic Flow Added - 5 Gpm Sprinkler or Nozzle
S Additional Flow Added - Gpm Make SENJU RC-RES Model SS4451
I Elevation at Highest Outlet - Feet Size 1/2" K-Factor 4.9
G Note: Temperature Rating 205
N
Calculation Gpm Required Psi Required At BOR
Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test: Pump Data: Tank or Reservoir:
A Date of Test - 12/13/2021 Rated Cap. Cap.
T Time of Test - N/A @ Psi Elev.
E Static (Psi) - 96.5=86.85 Elev.
R Residual (Psi) - 94.2=84.78 Other Well
Flow (Gpm) - 700 Proof Flow Gpm
S Elevation - -6 FT
P Location: HYDRANT NEAR 50710 CELLE QUITO, LA QUINTA
P APN 770-094-003
L Source of Information: COACHELLA VALLEY WATER DISTRICT
Y STEVE KEALER - (760) 992-4855
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 2
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
10
20
30
40
E 50
R 60
U 70
S 80
S 90
E 100
R 110
P 120
130
140
150
100 200 300 400 500 600 700 800 900
FLOW ( N ^ 1.85 )
City Water Supply:Demand:
C1 C2
C1 - Static Pressure :86.85
C2 - Residual Pressure:84.78
C2 - Residual Flow :700
D1 - Elevation : 6.713
D2 - System Flow :26.007
D2 - System Pressure : 54.231
Hose ( Demand ):5
D3 - System Demand :31.007
Safety Margin : 32.612
D1
D2
D3
Water Supply Curve
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 3
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
Fitting Legend
Abbrev.Name ½¾1 1¼1½2 2½3 3½4 5 6 8 10 12 14 16 18 20 24
Ad Male/Female Adapter 1 1.5 2 2.8 3.5 4.5 5.5 6.5 9 14
Bv Ball Valve 2.25 2.25 2 2.5 2.25 10
Cpcv CPVC Check Valve 0 0 1 7 9 11
E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50
Kav K Copper Angle Valve 0 7 14 14 18 28
Kcs K Copper Corporation Stop 0 0 4.08 4.08 4.08 4.08
Ktee K Copper Tee Or Cross (Flow Turned 90 Degrees)0 3 6 5 8 12
Lelbw L Copper 90 Degreel Elbow 0 2 3 3 4 6
Ltee L Copper Tee Or Cross (Flow Turned 90 Degrees)0 4 7 6 9 12
N *CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0
O *CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0
R *CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with *. The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
Fittings Used Summary
Computer Programs by Hydratec Inc. Revision: 50.5520.727
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Fittings Used Summary
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 4
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
SUPPLY ANALYSIS
Node at Static Residual Available
Source Pressure Pressure Flow Pressure Total Demand Required Pressure
SRC 86.85 84.78 700.0 86.844 31.01 54.231
NODE ANALYSIS
Pressure Discharge
Node Tag Elevation Node Type at Node at Node Notes
H1 9.5 4.9 7.04 13.0 0.05 256
H2 9.5 4.9 7.05 13.01 0.05 256
H3 9.5 7.97
H4 12.083 8.77
H5 12.083 8.77
D1 10.0 7.05
1 10.0 7.22
D2 10.0 7.06
2 10.0 7.23
D3 10.0 7.75
3 10.0 7.75
4 10.0 9.45
5 10.0 9.53
6 12.583 8.45
D4 12.583 8.55
D5 12.583 8.55
7 12.583 8.55
8 12.583 8.65
9 10.0 9.81
10 10.0 7.51
11 12.583 6.63
12 12.583 7.31
13 10.0 8.66
14 10.0 9.88
15 10.0 12.16
TOR 10.0 14.0
BOR 2.0 19.56
POC 2.0 20.31
DS 2.0 22.53 5.0
UG1 -3.0 25.14
UG2 -3.0 29.04
UG3 -1.5 28.7
M1 -1.5 30.27
M2 -1.5 34.49
UG4 -1.5 38.72
SRC -6.0 54.23
Flow Summary - NFPA
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 5
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe *******Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
H1 9.500 4.90 13.00 1 N 7.0 0.500 150 7.039
to 7.000 -0.217
D1 10 13.0 1.101 7.500 0.0307 0.230 Vel = 4.38
0.0
D1 13.00 7.052 K Factor = 4.90
H2 9.500 4.90 13.01 1 N 7.0 0.500 150 7.046
to 7.000 -0.217
D2 10 13.01 1.101 7.500 0.0308 0.231 Vel = 4.38
0.0
D2 13.01 7.060 K Factor = 4.90
H3 9.500 0.0 1 N 7.0 0.500 150 7.969
to 7.000 -0.217
D3 10 0.0 1.101 7.500 0 0.0 Vel = 0
0.0
D3 0.0 7.752 K Factor = 0
H4 12.083 0.0 1 N 7.0 0.500 150 8.765
to 7.000 -0.217
D4 12.583 0.0 1.101 7.500 0.0001 0.001 Vel = 0
0.0
D4 0.0 8.549 K Factor = 0
H5 12.083 0.0 1 N 7.0 0.500 150 8.765
to 7.000 -0.217
D5 12.583 0.0 1.101 7.500 0.0001 0.001 Vel = 0
0.0
D5 0.0 8.549 K Factor = 0
D1 10 13.00 1 O 5.0 0.500 150 7.052
to 5.000 0.0
1 10 13.0 1.101 5.500 0.0307 0.169 Vel = 4.38
1 10 -11.41 1 R 1.0 10.458 150 7.221
to 1.000 0.0
2 10 1.59 1.101 11.458 0.0006 0.007 Vel = 0.54
0.0
2 1.59 7.228 K Factor = 0.59
D2 10 13.01 1 O 5.0 0.500 150 7.060
to 5.000 0.0
2 10 13.01 1.101 5.500 0.0305 0.168 Vel = 4.38
2 10 1.59 1 2R 2.0 11.792 150 7.228
to 2.000 0.0
3 10 14.6 1.101 13.792 0.0380 0.524 Vel = 4.92
0.0
3 14.60 7.752 K Factor = 5.24
D3 10 0.0 1 O 5.0 0.542 150 7.752
to 5.000 0.0
3 10 0.0 1.101 5.542 0 0.0 Vel = 0
3 10 14.60 1 2O 10.0 30.625 150 7.752
to 4R 4.0 14.000 0.0
4 10 14.6 1.101 44.625 0.0380 1.696 Vel = 4.92
Final Calculations : Hazen-Williams
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 6
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe *******Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
4 10 -10.34 1 R 1.0 13.375 150 9.448
to N 7.0 8.000 0.0
5 10 4.26 1.101 21.375 0.0039 0.083 Vel = 1.44
5 10 0.0 1 N 7.0 2.583 150 9.531
to 7.000 -1.119
6 12.583 4.26 1.101 9.583 0.0040 0.038 Vel = 1.44
6 12.583 0.0 1 2R 2.0 23.458 150 8.450
to 2.000 0.0
7 12.583 4.26 1.101 25.458 0.0039 0.099 Vel = 1.44
0.0
7 4.26 8.549 K Factor = 1.46
D4 12.583 0.0 1 O 5.0 12.917 150 8.549
to 5.000 0.0
7 12.583 0.0 1.101 17.917 0 0.0 Vel = 0
0.0
7 0.0 8.549 K Factor = 0
D5 12.583 0.0 1 O 5.0 1.750 150 8.549
to 5.000 0.0
7 12.583 0.0 1.101 6.750 0 0.0 Vel = 0
7 12.583 4.26 1 R 1.0 18.167 150 8.549
to N 7.0 8.000 0.0
8 12.583 4.26 1.101 26.167 0.0039 0.102 Vel = 1.44
8 12.583 0.0 1 N 7.0 2.583 150 8.651
to 7.000 1.119
9 10 4.26 1.101 9.583 0.0039 0.037 Vel = 1.44
9 10 0.0 1 R 1.0 13.667 150 9.807
to O 5.0 6.000 0.0
14 10 4.26 1.101 19.667 0.0039 0.076 Vel = 1.44
0.0
14 4.26 9.883 K Factor = 1.36
4 10 10.33 1 10R 10.0 110.167 150 9.448
to 3O 15.0 25.000 0.0
15 10 10.33 1.101 135.167 0.0201 2.711 Vel = 3.48
0.0
15 10.33 12.159 K Factor = 2.96
1 10 11.41 1 N 7.0 5.125 150 7.221
to 7.000 0.0
10 10 11.41 1.101 12.125 0.0241 0.292 Vel = 3.85
10 10 0.0 1 N 7.0 2.583 150 7.513
to 7.000 -1.119
11 12.583 11.41 1.101 9.583 0.0241 0.231 Vel = 3.85
11 12.583 0.0 1 2R 2.0 19.250 150 6.625
to N 7.0 9.000 0.0
12 12.583 11.41 1.101 28.250 0.0241 0.681 Vel = 3.85
12 12.583 0.0 1 N 7.0 2.583 150 7.306
to 7.000 1.119
13 10 11.41 1.101 9.583 0.0241 0.231 Vel = 3.85
13 10 0.0 1 5R 5.0 35.958 150 8.656
to 2O 10.0 15.000 0.0
14 10 11.41 1.101 50.958 0.0241 1.227 Vel = 3.85
Final Calculations : Hazen-Williams
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 7
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe *******Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
14 10 4.26 1 6R 6.0 41.500 150 9.883
to O 5.0 11.000 0.0
15 10 15.67 1.101 52.500 0.0434 2.276 Vel = 5.28
15 10 10.34 1 R 1.0 8.667 150 12.159
to N 7.0 8.000 0.0
TOR 10 26.01 1.101 16.667 0.1106 1.843 Vel = 8.77
0.0
TOR 26.01 14.002 K Factor = 6.95
TOR 10 26.01 1 Cpcv 1.913 8.000 150 14.002
to 2R 2.0 10.912 3.465
BOR 2 26.01 1.101 N 7.0 18.912 0.1106 2.092 Vel = 8.77
BOR 2 0.0 1 Ad 3.825 3.000 150 19.559
to 3.825 0.0
POC 2 26.01 1.101 6.825 0.1106 0.755 Vel = 8.77
POC 2 0.0 1 Ltee 9.45 2.000 150 20.314
to Ad 2.7 12.150 0.0
DS 2 26.01 1.025 14.150 0.1567 2.217 Vel = 10.11
0.0
DS 26.01 22.531 K Factor = 5.48
DS 2 H5 31.01 1.5 Ad 3.808 5.000 150 22.531
to Lelbw 4.352 8.160 2.166
UG1 -3 31.01 1.505 13.160 0.0334 0.439 Vel = 5.59
UG1 -3 0.0 1.5 4E 22.749 130.000 150 25.136
to 22.749 0.0
UG2 -3 31.01 1.59 152.749 0.0256 3.906 Vel = 5.01
UG2 -3 0.0 1.5 E 5.687 1.500 150 29.042
to Ad 4.976 10.664 -0.650
UG3 -1.500 31.01 1.59 12.164 0.0256 0.312 Vel = 5.01
UG3 -1.500 0.0 1 Ad 2.7 1.500 150 28.704
to Bv 3.037 5.738 0.0
M1 -1.500 31.01 1.025 7.238 0.2169 1.570 Vel = 12.06
M1 -1.500 0.0 1 1.000 150 30.274
to 4.000 * * Fixed Loss = 4
M2 -1.500 31.01 1.025 1.000 0.2170 0.217 Vel = 12.06
M2 -1.500 0.0 1 Kav 16.354 0.500 150 34.491
to 16.354 0.0
UG4 -1.500 31.01 0.995 16.854 0.2507 4.225 Vel = 12.80
UG4 -1.500 0.0 1 Ad 2.336 40.000 150 38.716
to Kcs 4.766 14.111 1.949
SRC -6 31.01 0.995 Ktee 7.009 54.111 0.2507 13.566 Vel = 12.80
0.0
SRC 31.01 54.231 K Factor = 4.21
Final Calculations : Hazen-Williams
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC
C-16 LICENSE # 954532
760 S. ROCHESTER AVE. SUITE B
ONTARIO, CA 91761
(800) 457-7252
Job Name :Haven Enterprises Inc - 50710 CALLE QUITO LOT 48
Drawing :
Location :50710 CALLE QUITO - LOT 48, LA QUINTA, CA 92253
Remote Area :PRIMARY BATH
Contract :N/A
Data File :PRIMARY BATH (1-HEAD) CALC - 20X20.wxtmp
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 1
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
HYDRAULIC DESIGN INFORMATION SHEET
Name - Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date - 11/09/2022
Location - 50710 CALLE QUITO - LOT 48, LA QUINTA, CA 92253
Building - System No. - PRIMARY BATH
Contractor - KPS FIRE SPRINKLER‚ INC Contract No. - N/A
Calculated By - BL Drawing No. -
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height 9'-6"
OCCUPANCY - R3 / U
S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D
Y Number of Sprinklers Flowing: (X)1 ( )2 ( )4 ( )
S ( )Other
T ( )Specific Ruling Made by Date
E
M Listed Flow at Start Point - 21 Gpm System Type
Listed Pres. at Start Point - 18.4 Psi (X) Wet ( ) Dry
D MAXIMUM LISTED SPACING 20 x 20 ( ) Deluge ( ) PreAction
E Domestic Flow Added - 5 Gpm Sprinkler or Nozzle
S Additional Flow Added - Gpm Make SENJU RC-RES Model SS8464
I Elevation at Highest Outlet - 19'-4"Feet Size 1/2" K-Factor 4.9
G Note: Temperature Rating 162
N
Calculation Gpm Required Psi Required At BOR
Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test: Pump Data: Tank or Reservoir:
A Date of Test - 12/13/2021 Rated Cap. Cap.
T Time of Test - N/A @ Psi Elev.
E Static (Psi) - 96.5=86.85 Elev.
R Residual (Psi) - 94.2=84.78 Other Well
Flow (Gpm) - 700 Proof Flow Gpm
S Elevation - -6 FT
P Location: HYDRANT NEAR 50710 CELLE QUITO, LA QUINTA
P APN 770-094-003
L Source of Information: COACHELLA VALLEY WATER DISTRICT
Y STEVE KEALER - (760) 992-4855
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 2
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
10
20
30
40
E 50
R 60
U 70
S 80
S 90
E 100
R 110
P 120
130
140
150
100 200 300 400 500 600 700 800 900
FLOW ( N ^ 1.85 )
City Water Supply:Demand:
C1 C2
C1 - Static Pressure :86.85
C2 - Residual Pressure:84.78
C2 - Residual Flow :700
D1 - Elevation : 6.713
D2 - System Flow :21.019
D2 - System Pressure : 55.519
Hose ( Demand ):5
D3 - System Demand :26.019
Safety Margin : 31.326
D1
D2
D3
Water Supply Curve
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 3
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
Fitting Legend
Abbrev.Name ½¾1 1¼1½2 2½3 3½4 5 6 8 10 12 14 16 18 20 24
Ad Male/Female Adapter 1 1.5 2 2.8 3.5 4.5 5.5 6.5 9 14
Bv Ball Valve 2.25 2.25 2 2.5 2.25 10
Cpcv CPVC Check Valve 0 0 1 7 9 11
E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50
Kav K Copper Angle Valve 0 7 14 14 18 28
Kcs K Copper Corporation Stop 0 0 4.08 4.08 4.08 4.08
Ktee K Copper Tee Or Cross (Flow Turned 90 Degrees)0 3 6 5 8 12
Lelbw L Copper 90 Degreel Elbow 0 2 3 3 4 6
Ltee L Copper Tee Or Cross (Flow Turned 90 Degrees)0 4 7 6 9 12
N *CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0
O *CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0
R *CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with *. The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
Fittings Used Summary
Computer Programs by Hydratec Inc. Revision: 50.5520.727
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Fittings Used Summary
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 4
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
SUPPLY ANALYSIS
Node at Static Residual Available
Source Pressure Pressure Flow Pressure Total Demand Required Pressure
SRC 86.85 84.78 700.0 86.845 26.02 55.519
NODE ANALYSIS
Pressure Discharge
Node Tag Elevation Node Type at Node at Node Notes
H1 9.5 19.7
H2 9.5 19.55
H3 9.5 4.9 18.4 21.02 0.05 400
H4 12.083 19.81
H5 12.083 19.81
D1 10.0 19.49
1 10.0 19.49
D2 10.0 19.34
2 10.0 19.34
D3 10.0 18.74
3 10.0 19.16
4 10.0 20.49
5 10.0 20.57
6 12.583 19.49
D4 12.583 19.59
D5 12.583 19.59
7 12.583 19.59
8 12.583 19.69
9 10.0 20.85
10 10.0 19.64
11 12.583 18.65
12 12.583 19.02
13 10.0 20.26
14 10.0 20.93
15 10.0 22.41
TOR 10.0 23.65
BOR 2.0 28.53
POC 2.0 29.04
DS 2.0 30.53 5.0
UG1 -3.0 33.02
UG2 -3.0 35.84
UG3 -1.5 35.42
M1 -1.5 36.55
M2 -1.5 40.71
UG4 -1.5 43.76
SRC -6.0 55.52
Flow Summary - NFPA
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 5
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe *******Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
H1 9.500 0.0 1 N 7.0 0.500 150 19.702
to 7.000 -0.217
D1 10 0.0 1.101 7.500 0.0001 0.001 Vel = 0
0.0
D1 0.0 19.486 K Factor = 0
H2 9.500 0.0 1 N 7.0 0.500 150 19.553
to 7.000 -0.217
D2 10 0.0 1.101 7.500 0 0.0 Vel = 0
0.0
D2 0.0 19.336 K Factor = 0
H3 9.500 4.90 21.02 1 N 7.0 0.500 150 18.400
to 7.000 -0.217
D3 10 21.02 1.101 7.500 0.0747 0.560 Vel = 7.08
0.0
D3 21.02 18.743 K Factor = 4.86
H4 12.083 0.0 1 N 7.0 0.500 150 19.809
to 7.000 -0.217
D4 12.583 0.0 1.101 7.500 0 0.0 Vel = 0
0.0
D4 0.0 19.592 K Factor = 0
H5 12.083 0.0 1 N 7.0 0.500 150 19.809
to 7.000 -0.217
D5 12.583 0.0 1.101 7.500 0 0.0 Vel = 0
0.0
D5 0.0 19.592 K Factor = 0
D1 10 0.0 1 O 5.0 0.500 150 19.486
to 5.000 0.0
1 10 0.0 1.101 5.500 0 0.0 Vel = 0
1 10 -8.19 1 R 1.0 10.458 150 19.486
to 1.000 0.0
2 10 -8.19 1.101 11.458 -0.0131 -0.150 Vel = 2.76
0.0
2 -8.19 19.336 K Factor = -1.86
D2 10 0.0 1 O 5.0 0.500 150 19.336
to 5.000 0.0
2 10 0.0 1.101 5.500 0 0.0 Vel = 0
2 10 -8.19 1 2R 2.0 11.792 150 19.336
to 2.000 0.0
3 10 -8.19 1.101 13.792 -0.0131 -0.180 Vel = 2.76
0.0
3 -8.19 19.156 K Factor = -1.87
D3 10 21.02 1 O 5.0 0.542 150 18.743
to 5.000 0.0
3 10 21.02 1.101 5.542 0.0745 0.413 Vel = 7.08
3 10 -8.19 1 2O 10.0 30.625 150 19.156
to 4R 4.0 14.000 0.0
4 10 12.83 1.101 44.625 0.0299 1.336 Vel = 4.32
Final Calculations : Hazen-Williams
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 6
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe *******Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
4 10 -8.57 1 R 1.0 13.375 150 20.492
to N 7.0 8.000 0.0
5 10 4.26 1.101 21.375 0.0039 0.083 Vel = 1.44
5 10 0.0 1 N 7.0 2.583 150 20.575
to 7.000 -1.119
6 12.583 4.26 1.101 9.583 0.0040 0.038 Vel = 1.44
6 12.583 0.0 1 2R 2.0 23.458 150 19.494
to 2.000 0.0
7 12.583 4.26 1.101 25.458 0.0038 0.098 Vel = 1.44
0.0
7 4.26 19.592 K Factor = 0.96
D4 12.583 0.0 1 O 5.0 12.917 150 19.592
to 5.000 0.0
7 12.583 0.0 1.101 17.917 0 0.0 Vel = 0
0.0
7 0.0 19.592 K Factor = 0
D5 12.583 0.0 1 O 5.0 1.750 150 19.592
to 5.000 0.0
7 12.583 0.0 1.101 6.750 0 0.0 Vel = 0
7 12.583 4.26 1 R 1.0 18.167 150 19.592
to N 7.0 8.000 0.0
8 12.583 4.26 1.101 26.167 0.0039 0.102 Vel = 1.44
8 12.583 0.0 1 N 7.0 2.583 150 19.694
to 7.000 1.119
9 10 4.26 1.101 9.583 0.0039 0.037 Vel = 1.44
9 10 0.0 1 R 1.0 13.667 150 20.850
to O 5.0 6.000 0.0
14 10 4.26 1.101 19.667 0.0039 0.076 Vel = 1.44
0.0
14 4.26 20.926 K Factor = 0.93
4 10 8.57 1 10R 10.0 110.167 150 20.492
to 3O 15.0 25.000 0.0
15 10 8.57 1.101 135.167 0.0142 1.919 Vel = 2.89
0.0
15 8.57 22.411 K Factor = 1.81
1 10 8.19 1 N 7.0 5.125 150 19.486
to 7.000 0.0
10 10 8.19 1.101 12.125 0.0130 0.158 Vel = 2.76
10 10 0.0 1 N 7.0 2.583 150 19.644
to 7.000 -1.119
11 12.583 8.19 1.101 9.583 0.0130 0.125 Vel = 2.76
11 12.583 0.0 1 2R 2.0 19.250 150 18.650
to N 7.0 9.000 0.0
12 12.583 8.19 1.101 28.250 0.0130 0.368 Vel = 2.76
12 12.583 0.0 1 N 7.0 2.583 150 19.018
to 7.000 1.119
13 10 8.19 1.101 9.583 0.0130 0.125 Vel = 2.76
13 10 0.0 1 5R 5.0 35.958 150 20.262
to 2O 10.0 15.000 0.0
14 10 8.19 1.101 50.958 0.0130 0.664 Vel = 2.76
Final Calculations : Hazen-Williams
Computer Programs by Hydratec Inc. Revision: 50.5520.727
KPS FIRE SPRINKLERS INC Page 7
Haven Enterprises Inc - 50710 CALLE QUITO LOT 48 Date 11/09/2022
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe *******Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
14 10 4.25 1 6R 6.0 41.500 150 20.926
to O 5.0 11.000 0.0
15 10 12.44 1.101 52.500 0.0283 1.485 Vel = 4.19
15 10 8.58 1 R 1.0 8.667 150 22.411
to N 7.0 8.000 0.0
TOR 10 21.02 1.101 16.667 0.0746 1.244 Vel = 7.08
0.0
TOR 21.02 23.655 K Factor = 4.32
TOR 10 21.02 1 Cpcv 1.913 8.000 150 23.655
to 2R 2.0 10.912 3.465
BOR 2 21.02 1.101 N 7.0 18.912 0.0746 1.410 Vel = 7.08
BOR 2 0.0 1 Ad 3.825 3.000 150 28.530
to 3.825 0.0
POC 2 21.02 1.101 6.825 0.0746 0.509 Vel = 7.08
POC 2 0.0 1 Ltee 9.45 2.000 150 29.039
to Ad 2.7 12.150 0.0
DS 2 21.02 1.025 14.150 0.1057 1.495 Vel = 8.17
0.0
DS 21.02 30.534 K Factor = 3.80
DS 2 H5 26.02 1.5 Ad 3.808 5.000 150 30.534
to Lelbw 4.352 8.160 2.166
UG1 -3 26.02 1.505 13.160 0.0242 0.318 Vel = 4.69
UG1 -3 0.0 1.5 4E 22.749 130.000 150 33.018
to 22.749 0.0
UG2 -3 26.02 1.59 152.749 0.0185 2.824 Vel = 4.20
UG2 -3 0.0 1.5 E 5.687 1.500 150 35.842
to Ad 4.976 10.664 -0.650
UG3 -1.500 26.02 1.59 12.164 0.0185 0.225 Vel = 4.20
UG3 -1.500 0.0 1 Ad 2.7 1.500 150 35.417
to Bv 3.037 5.738 0.0
M1 -1.500 26.02 1.025 7.238 0.1568 1.135 Vel = 10.12
M1 -1.500 0.0 1 1.000 150 36.552
to 4.000 * * Fixed Loss = 4
M2 -1.500 26.02 1.025 1.000 0.1570 0.157 Vel = 10.12
M2 -1.500 0.0 1 Kav 16.354 0.500 150 40.709
to 16.354 0.0
UG4 -1.500 26.02 0.995 16.854 0.1812 3.054 Vel = 10.74
UG4 -1.500 0.0 1 Ad 2.336 40.000 150 43.763
to Kcs 4.766 14.111 1.949
SRC -6 26.02 0.995 Ktee 7.009 54.111 0.1812 9.807 Vel = 10.74
0.0
SRC 26.02 55.519 K Factor = 3.49
Final Calculations : Hazen-Williams
Computer Programs by Hydratec Inc. Revision: 50.5520.727
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
December 19, 2022
KPS
Re: Residential Fire Sprinkler Plan Review – Lot 48
FSS2022-0436 / 50710 Calle Quito
The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
Permanently marked identification signs shall be attached to all control valves.
The following inspections/tests are required to be witnessed by Office of the Fire Marshal Staff:
(a) Overhead Rough and Hydro static test: All piping shall be visible and pumped at normal
operating pressure. *No jacketed electrical and data wiring shall be in contact with, nor have the
potential to contact CPVC piping once insulation is installed.
(b) Final inspection
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Rebecca Winscott - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 50710 Calle Quito PERMIT#: FSSS2022-0436 DATE
ISSUED: 121922
DESCRIPTION: Lot 48 – Residence CONTRACTOR: KPS
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.