FSS2022-0449ADDITIONAL SITES
CHRONOLOGY
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT SOUTHWEST FIRE PROS 31410 RESERVE DRIVE
SUITE 2
THOUSAND
PALMS
CA 92276 (760)343-2233 MAUREEN@SWESTFIR
EPROS.COM
CONTRACTOR SOUTHWEST FIRE PROS 31410 RESERVE DRIVE
SUITE 2
THOUSAND
PALMS
CA 92276 (760)343-2233 MAUREEN@SWESTFIR
EPROS.COM
OWNER JEFF RIPPEE 52700 AVENIDA
VALLEJO
LA QUINTA CA 92253 (760)343-2233
CONDITIONS
Description: FIRE SPRINKLER
Type: FIRE SPRINKLER (WEB)Subtype: RESIDENTIAL - CUSTOM
HOMES
Status: FINALED Applied: 12/13/2022 ECON
Parcel No: 770230016 Site Address: 78761 DEACON DR E ,CA Approved: 12/19/2022 RWI
Subdivision: TR 28470-1 Block: Lot: 26 Issued: ONLINE
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 6/29/2023 LRO
Valuation: $7,150.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
FINANCIAL INFORMATION
Printed: Thursday, July 20, 2023 4:41:57 PM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0449
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
OVERHEAD ROUGH
PIPING LIN 1/24/2023 1/24/2023 APPROVED AS BUILTS REQUIRED
Changes in head location as well as riser
location. Premature insulation was partially
removed to observed all sprinkler system
components. As builts required.
OVERHEAD HYRO LIN 1/24/2023 1/24/2023 APPROVED AS BUILTS REQUIRED
FIRE FINAL**LRO 6/29/2023 6/29/2023 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
PARENT PROJECTS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED
101-0000-42421 0 $250.00 $250.00 12/23/22 WEB13907 775579506 CREDIT 1005165 ECON
FIRE SPRINKLER
SYSTEMS - SINGLE
FAMILY DETACHED PC
101-0000-42420 0 $250.00 $250.00 12/23/22 WEB13907 775579506 CREDIT 1005165 ECON
Total Paid for FIRE FEES: $500.00 $500.00
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $11.00 $11.00 12/23/22 WEB13907 775579506 CREDIT 1005165 ECON
Total Paid for RECORDS MANAGEMENT FEE: $11.00 $11.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $8.00 $8.00 12/23/22 WEB13907 775579506 CREDIT 1005165 ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $8.00 $8.00
TOTALS:$519.00 $519.00
Printed: Thursday, July 20, 2023 4:41:57 PM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0449
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 12/13/2022 Etrakit Contractor 1ST SUBMITTAL - PLAN
SET
Rippee Residence
Plans.pdf 1
DOC 12/13/2022 Etrakit Contractor
1ST SUBMITTAL -
HYDRAULIC
CALCULATIONS
Document.pdfCalc-1.pdf 1
DOC 12/13/2022 Etrakit Contractor CVWD FIRE FLOW Results.pdf 1
DOC 12/13/2022 Etrakit Contractor CUT SHEETS Senju Residential
Conceled Pendant.pdf 1
DOC 12/13/2022 Etrakit Contractor FIRE REVIEW
APPLICATION
FIRE REVIEW
APPLICATION.pdf 1
DOC 6/22/2023 Etrakit Contractor As Built Plans FSS2022-0449 As Built
Plans.pdf 1
DOC 6/26/2023 KOHL HETRICK FSS2022-0449 - AS-
BUILTS - APPROVED.pdf
FSS2022-0449 - AS-
BUILTS - APPROVED.pdf 1
DOC 12/19/2022 REBECCA WINSCOTT
LQ FSS2022-0449
Rippee Residence
COA.pdf
LQ FSS2022-0449
Rippee Residence
COA.pdf
1
DOC 12/19/2022 REBECCA WINSCOTT LQ FSS2022-0449
Rippee Residence.pdf
LQ FSS2022-0449
Rippee Residence.pdf 1
BOND INFORMATION
1ST FIRE - ETRAKIT
(2 WK)
REBECCA
WINSCOTT 12/13/2022 12/29/2022 12/19/2022 APPROVED
1ST PERMIT TECH –
ETRAKIT (1 DAY)
PERMIT TECH
BUCKET 12/13/2022 12/14/2022 12/13/2022 COMPLETE
Printed: Thursday, July 20, 2023 4:41:57 PM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSS2022-0449
FSS2022-0449 AS-BUILTS
Kohler - K-2297 Kohler - K-2297
3'-0"393COATSPOWDER400 amp.FAU FAU
SEATSEATFAU FAUSEAT
TUB
A/C A/C
A/C A/C
48" R/O
361
3'-0"3933'-0"3935'-11_2"3'-41_
2"
393
4'-51_
2"
4'-31_
2"3'-0"
393 3'-0"39310"10" 10" 10"EQ.10"EQ.EQ.1'-0"EQ.1'-0"EQ.1'-0"EQ.1'-0"1'-1"1'-1"2'-0"2'-0"2'-0"2'-0"JJJJJJINSPECTOR TEST DETAIL
5'
1" Ball Valve Access Panel
(By Others)
Exterior Wall of Building
Inspector Test to Terminate
in a Smooth Bore Corrosion
Resistant Orfice With a Flow
Equivalent to One Sprinkler
NOTE: Access Panel Shall have sign
Indicating Inspector Test
CPVC HANGERS
NO SCALE
TOLCO FIG. 24
DOUBLE-FASTENER
SIDE-MOUNT HANGER
(OR EQUAL)
SELF-DRILLING
HEX HEAD SCREW
TOLCO FIG. 23
DOUBLE-FASTENER
STRAP TYPE HANGER
(OR EQUAL)
TOLCO FIG. 28M
OFFSET HANGER
(OR EQUAL)
TOLCO FIG. 22
SINGLE-FASTENER
STRAP-TYPE HANGER
(OR EQUAL)
TOLCO FIG. 28
DOUBLE-FASTENER
STAND-OFF HANGER
(OR EQUAL)
TOLCO FIG. 29
DOUBLE-FASTENER
DOUBLE OFFSET HANGER
(OR EQUAL)
CPVC HANGER SPACING
PIPE SIZE
11/4"
1"
MAXIMUM SUPPORT SPACING
6'-6"
6'-0"
2"8'-0"
11/2"7'-0"
SPRINKLER PIPEINSULATION
BOTTOM CORD OF ROOF TRUSS
OR CEILING JOIST
PIPE INSULATION DETAIL
www.cadmando.co.uk
These blocks were brought to you by CADBlocksFree.com.For all of your 2D & 3D CAD outsource requirements visit us:
C A D M A N D O
www.cadblocksfree.com
COVER WITH HINGED LID
FINISHED GRADE
DISC-TYPE WATER METER
PLUG VALVE(TYP.)UNION(TYP.)
1" WATER METER
5psi CALCED FOR
FRICTION LOSS
Water Supply Information
Static Pressure:
Residual Pressure:
Residual Flow:
Additional Hose Flow:
64.80 psi
61.80 psi
3550 GPM
0 GPM
1-1/4" RISER
INSPECTORS TESTNOTIFICATION DEVICE BY OTHERS1-1/2" PVC UNDERGROUND BY OTHERSGARAGE
10'-0"
BATH 3
9'-0"
BEDROOM 3
10'-0"
W.I.C.
9'-0"
COURTYARD
COVERED
ENTRY
ENTRY
12'-0"
9'-0"OFFICE
10'-0"
HALL
10'-0"
W.I.C.
9'-0"
BEDROOM 2
10'-0"
BATH 2
9'-0"LAUNDRY
10'-0"
PANTRY
10'-0"
KITCHEN
12'-0"DINING
12'-0"
GREAT
ROOM
15'-0"LOGGIA
PRIMARY
BEDROOM
13'-0"
PRIMARY
BATH
10'-0"
W.C.
9'-0"
W.I.C.
10'-0"
KITCHENETTE
8'-0"
BATH 4
8'-0"
GUEST
BEDROOM
11'-0"1"1' -8"1"1' -5"1"5' -3"1"5' -3"1"5' -6"1"5' -5"1"5' -5"1"3' -9"1"1' -1"1"7' -3"1"2' -6"1"
14' -0"
1"
11' -6"1"2' -8"1"
12' -0"1"2' -8"1"
14' -0"1"5' -6"1"
7' -5"1"4' -3"1"3' -10"1"
7' -0"1"6' -6"1"
0' -8"1"8' -5"1"8' -4"1"
3' -9"
1"
2' -0"
1"
0' -10"
1"
4' -6"1"2' -3"1"11' -1"1"2' -0"1"
1' -1"1"0' -7"1"
9' -7"
1"
9' -5"
1"
3' -2"1"7' -10"1"3' -2"1"
8' -2"
1 1/4"
1' -1"1"7' -8"1"3' -8"1"
5' -0"1"7' -8"1"
8' -7"
1"
3' -1"1"0' -6"1"8' -4"1"8' -4"1"5' -2"1"
4' -11"1"2' -0"1"2' -0"1"
3' -6"1"8' -4"1"8' -4"1"8' -4"1"2' -8"1"
8' -7"1"6' -7"1"
5' -4"
1"
2' -1"
1"
0' -5"
1"
2' -7"1"3' -9"1"
8' -5"
1"
2' -6"1"3' -4"1"
9' -5"1"5' -1"1"
0' -10"
1"
2' -11"1"5' -10"1"
1' -4"
1"
5' -8"1"4' -7"1"5' -4"1"
4' -10"
1"
6' -8"1"1' -11"1"8' -5"1"7' -5"1"
0' -7"1"
2' -8"
1"
0' -6"1"5' -1"1"7' -1"1"
1' -7"1"1' -7"1"1' -10"1"2' -7"1" x 5' -0"1" x 5' -0"1" x 5' -0"N
Remote area number:
Occupancy classification:
Density:
Area of application:
Total water required
(including hose streams):
@ a required
system pressure
of:
Fire Protection System Demand:
No. of sprinklers calculated:
Inside Hose Streams:
Outside Hose
Streams:
Calc-1
R-3
2
Gpm/SqFt
512 Max SqFt
31.0424 GPM
51.9781 Psi
5 GPM
0 GPM2"68' -3"CALC-1
1
WM
8
SOR
11456
2 3
7
TOR
BOR
DOM
9
10
1"
1' -1"
1"
1' -8"1"8' -5"1"
4' -5"
1"
6' -1"
1"
3' -1"1"1' -8"1"5' -3"1" x 5' -0"1"8' -0"1" x 3' -10"1"
0' -11"1" x 10' -2"1"4' -4"1"
3' -0"
1"
1' -8"1"1' -8"1"8' -5"1"
7' -4"
1"
3' -0"1"2' -11"1"
4' -4"1"5' -7"1"4' -3"1"
11' -11"
1"
5' -3"
1"
3' -0"
1"
3' -1"
1"
3' -10"
1"
1' -7"
Fire Sprinkler Riser Detail
TOR
BOR
Domestic
Supply
Check
Flow Control
1-1/4" CPVC
Flow Switch Note Wiring by Others
300psi Gage
Sprinkler Box with Wrench & two
Sprinkler Heads Each Type
1/2" Drain to
Outside1-1/4"1-1/4"2" PVC Underground By Others
Notification Device
Wired by Others
not to scale
Module Must Connect to the Multi
Station Smoke Alarm System and
the Fire Sprinkler Flow Switch
( all wiring by others )
southwestfirepros.com
Scale
Project number
Date
Drawn by
Checked bySouthwest Fire Pros31410 Reserve Drive Suite # 2Thousand Palms, Ca 92276Phone (760) 343-2233Fax (760( 343-2210e-mail southwestfirepros.comLic. No. C-16 1005165As indicated
6/15/2023 4:18:16 PMFP-2
Piping Plan AS Builds
Project Number
RIPPEE
06-15-23
JA
CC
No. Description Date
RIPPEE RESIDENCETRADITION -LOT 2678761 Deacon Drive EastLa Quinta, Ca 922531/8" = 1'-0"1 Pipinig Plan
Sprinkler Schedule
No. of
Sprklrs Description
SIN
(Hydratec)K-Factor
Orifice
Size Temp
10 Senju 1/2 Light Pendent Recessed Temperature - 205 Finish - WH Quick Response
Model - V27 SIN - SS8464 K Factor - 4.9
SS8464 4.9 1/2" 205 °F
55 Senju 1/2 Residential Concealed Temperature -162 Finish - NT Fast Response Model -
Freedom SIN - SS8464 K Factor - 4.9
SS8464 4.9 1/2" 162 °F
: 65
Total No. of Sprinklers: 65
Kohler - K-2297 Kohler - K-2297
3'-0"393COATSPOWDER400 amp.FAU FAU
SEATSEATFAU FAUSEAT
TUB
A/C A/C
A/C A/C
48" R/O
361
3'-0"3933'-0"3935'-11_2"3'-41_
2"
393
4'-51_
2"
4'-31_
2"3'-0"
393 3'-0"39310"10"10"10" EQ. 10"EQ.EQ.1'-0"EQ.1'-0"EQ.1'-0"EQ.1'-0"1'-1"1'-1"2'-0"2'-0"2'-0"2'-0"JJJJJJINSPECTOR TEST DETAIL
5'
1" Ball Valve Access Panel
(By Others)
Exterior Wall of Building
Inspector Test to Terminate
in a Smooth Bore Corrosion
Resistant Orfice With a Flow
Equivalent to One Sprinkler
NOTE: Access Panel Shall have sign
Indicating Inspector Test
CPVC HANGERS
NO SCALE
TOLCO FIG. 24
DOUBLE-FASTENER
SIDE-MOUNT HANGER
(OR EQUAL)
SELF-DRILLING
HEX HEAD SCREW
TOLCO FIG. 23
DOUBLE-FASTENER
STRAP TYPE HANGER
(OR EQUAL)
TOLCO FIG. 28M
OFFSET HANGER
(OR EQUAL)
TOLCO FIG. 22
SINGLE-FASTENER
STRAP-TYPE HANGER
(OR EQUAL)
TOLCO FIG. 28
DOUBLE-FASTENER
STAND-OFF HANGER
(OR EQUAL)
TOLCO FIG. 29
DOUBLE-FASTENER
DOUBLE OFFSET HANGER
(OR EQUAL)
CPVC HANGER SPACING
PIPE SIZE
11/4"
1"
MAXIMUM SUPPORT SPACING
6'-6"
6'-0"
2"8'-0"
11/2"7'-0"
SPRINKLER PIPEINSULATION
BOTTOM CORD OF ROOF TRUSS
OR CEILING JOIST
PIPE INSULATION DETAIL
www.cadmando.co.uk
These blocks were brought to you by CADB locksFree.com.For all of your 2D & 3D CA D outsource requirements visit us:
C A D M A N D O
www.cadblocksfree.com
COVER WITH HINGED LID
FINISHED GRADE
DISC-TYPE WATER METER
PLUG VALVE(TYP.)UNION(TYP.)
1" WATER METER
5psi CALCED FOR
FRICTION LOSS
Water Supply Information
Static Pressure:
Residual Pressure:
Residual Flow:
Additional Hose Flow:
64.80 psi
61.80 psi
3550 GPM
0 GPM
1-1/4" RISER
INSPECTORS TESTNOTIFICATION DEVICE BY OTHERS1-1/2" PVC UNDERGROUND BY OTHERSGARAGE
10'-0"
BATH 3
9'-0"
BEDROOM 3
10'-0"
W.I.C.
9'-0"
COURTYARD
COVERED
ENTRY
ENTRY
12'-0"
9'-0"OFFICE
10'-0"
HALL
10'-0"
W.I.C.
9'-0"
BEDROOM 2
10'-0"
BATH 2
9'-0"LAUNDRY
10'-0"
PANTRY
10'-0"
KITCHEN
12'-0"DINING
12'-0"
GREAT
ROOM
15'-0"LOGGIA
PRIMARY
BEDROOM
13'-0"
PRIMARY
BATH
10'-0"
W.C.
9'-0"
W.I.C.
10'-0"
KITCHENETTE
8'-0"
BATH 4
8'-0"
GUEST
BEDROOM
11'-0"1"1' -8"1"1' -5"1"1' -6"1"1' -0"1"1' -6"1"3' -2"1"5' -6"1"5' -5"1"5' -5"1"1' -1"1"1' -1"1"2' -9"1"
1' -6"1"7' -3"1"1' -6"1"1' -0"1"4' -10"1"4' -10"1" x 9' -8"1"
14' -0"
1"
11' -6"1"2' -8"1"
12' -0"1"2' -8"1"
14' -0"1"5' -6"1"
5' -0"1"2' -8"1"
5' -0"1"2' -9"1"3' -10"1"
7' -0"1"6' -6"1"
8' -0"
1"
0' -8"1"8' -5"1"8' -4"1"
3' -9"
1"
2' -0"
1"
0' -10"
1"
4' -6"1"2' -3"1"11' -1"1"2' -0"1"
1' -1"1"0' -7"1"
9' -7"
1"
9' -5"
1"
3' -2"1"7' -10"1"3' -2"1"
8' -2"
1 1/4"
1' -1"1"7' -8"1"3' -8"1"
5' -0"1"7' -8"1"6' -6"1"
8' -7"
1"
3' -1"1"0' -6"1"8' -4"1"8' -4"1"7' -1"1"7' -1"1"
4' -11"1"2' -0"1"2' -0"1"
3' -6"1"8' -4"1"8' -4"1"8' -4"1"2' -8"1"
8' -7"1"6' -7"1"
5' -4"
1"
2' -1"
1"
0' -5"
1"
2' -7"
1"
5' -0"1"3' -9"1"3' -5"1"
3' -0"1"3' -5"1"
4' -5"
1"
8' -5"1"9' -3"1"
2' -6"1"0' -8"1"
11' -11"1"3' -4"1"
9' -5"
1"
1' -1"1"5' -1"1"
0' -10"
1"
2' -11"1"9' -8"1"
1' -4"1"2' -4"1"
5' -8"1"4' -7"1"5' -4"1"
4' -10"
1"
6' -8"
1"
2' -11"
1"
2' -5"
1"
1' -8"1"1' -11"1"0' -7"1"8' -5"1"8' -3"1"8' -3"1"7' -5"1"7' -5"1"
4' -5"
1"
0' -7"1"
6' -1"
1"
3' -1"1"1' -8"1"
2' -8"
1"
0' -6"1"5' -1"1"
5' -0"1"0' -6"1" x 4' -4"1"4' -5"1"7' -1"1"
1' -7"1"1' -7"1"1' -10"1"2' -7"1"7' -0"1" x 5' -0"1" x 5' -0"1" x 5' -0"1" x 5' -0"N
Remote area number:
Occupancy classification:
Density:
Area of application:
Total water required
(including hose streams):
@ a required
system pressure
of:
Fire Protection System Demand:
No. of sprinklers calculated:
Inside Hose Streams:
Outside Hose
Streams:
Calc-1
R-3
2
Gpm/SqFt
512 Max SqFt
31.122 GPM
52.7525 Psi
5 GPM
0 GPM
10
1
7
WM
9
SOR
BOR
TOR
12465
2
3
DOM
11
8
2"
15' -0"2"68' -3"CALC-1
Supply Point
1314
Fire Sprinkler Riser Detail
TOR
BOR
Domestic
Supply
Check
Flow Control
1-1/4" CPVC
Flow Switch Note Wiring by Others
300psi Gage
Sprinkler Box with Wrench & two
Sprinkler Heads Each Type
1/2" Drain to
Outside1-1/4"1-1/4"2" PVC Underground By Others
Notification Device
Wired by Others
not to scale
Module Must Connect to the Multi
Station Smoke Alarm System and
the Fire Sprinkler Flow Switch
( all wiring by others )
Southwest Fire Pros
31401 Reserve Drive Suite 2
Route 111
Thousand Palms, Ca.92276
760-343-2233
Job Name : 78761 Deacon Drive La Quinta, Ca
Drawing :
Location : Same
Remote Area : Calc-1
Contract :
Data File : 78761 Deacon Drive La Quinta, Ca Area Calc-1.WXF
Computer Programs by Hydratec Inc. Revision: 50.54.4
Southwest Fire ProsPage 1 78761 Deacon Drive La Quinta, CaDate 10203040E50R60U70S80S90E100R110P120130140150400 800 1200 1600 2000 2400 2800 3200 3600FLOW ( N ^ 1.85 )City Water Supply:Demand:C1C2C1 - Static Pressure : 64.8 C2 - Residual Pressure: 61.8 C2 - Residual Flow : 3550 D1 - Elevation : 5.713 D2 - System Flow : 31.122 D2 - System Pressure : 52.752 Hose ( Demand ) : _______D3 - System Demand : 31.122 Safety Margin : 12.047 D1D2Water Supply CurveComputer Programs by Hydratec Inc. Revision: 50.54.4
Southwest Fire ProsPage 2 78761 Deacon Drive La Quinta, CaDate Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24 N * CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 O * CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 R * CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used SummaryComputer Programs by Hydratec Inc. Revision: 50.54.4
Southwest Fire Pros Page 3
78761 Deacon Drive La Quinta, Ca Date
SUPPLY ANALYSIS
Node at Static Residual Available
Source Pressure Pressure Flow Pressure Total Demand Required Pressure
SOR 64.8 61.8 3550.0 64.8 31.12 52.752
NODE ANALYSIS
Pressure Discharge
Node Tag Elevation Node Type at Node at Node Notes
1 10.19 4.9 7.04 13.0 0.05 256
2 11.0 7.1
3 11.0 15.1
4 11.0 18.55
5 11.0 20.79
6 11.0 20.95
13 11.0 25.25
14 11.0 25.29
TOR 11.0 36.72
DOM 1.37 42.86 5.0
BOR -3.0 46.5
7 -3.0 46.81
8 -3.0 47.6
WM -3.0 52.64
9 -3.0 52.7
SOR -3.0 52.75
10 10.19 4.9 7.17 13.12 0.05 256
11 11.0 7.0
12 11.0 18.04
Flow Summary - NFPA
Computer Programs by Hydratec Inc. Revision: 50.54.4
Southwest Fire Pros Page 4
78761 Deacon Drive La Quinta, Ca Date
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
1 10.19 4.90 13.00 1 N 7.0 6.510 150 7.040
to 7.000 -0.351
2 11 13.0 1.101 13.510 0.0307 0.415 Vel = 4.38
2 11 13.12 1 N 7.0 51.690 150 7.104
to O 5.0 20.000 0.0
3 11 26.12 1.101 8R 8.0 71.690 0.1115 7.994 Vel = 8.80
3 11 -11.20 1 4N 28.0 47.260 150 15.098
to O 5.0 40.000 0.0
4 11 14.92 1.101 7R 7.0 87.260 0.0396 3.452 Vel = 5.03
4 11 11.20 1 2R 2.0 13.060 150 18.550
to O 5.0 7.000 0.0
5 11 26.12 1.101 20.060 0.1115 2.237 Vel = 8.80
5 11 0.0 1 R 1.0 0.440 150 20.787
to 1.000 0.0
6 11 26.12 1.101 1.440 0.1118 0.161 Vel = 8.80
6 11 0.0 1 6R 6.0 32.550 150 20.948
to 6.000 0.0
13 11 26.12 1.101 38.550 0.1115 4.299 Vel = 8.80
13 11 0.0 1.25 1.090 150 25.247
to 0.0
14 11 26.12 1.394 1.090 0.0349 0.038 Vel = 5.49
14 11 0.0 1 3R 3.0 64.540 150 25.285
to 7O 35.0 38.000 0.0
TOR 11 26.12 1.101 102.540 0.1115 11.435 Vel = 8.80
TOR 11 0.0 1 R 1.0 9.630 150 36.720
to N 7.0 8.000 4.171
DOM 1.37 26.12 1.101 17.630 0.1115 1.966 Vel = 8.80
DOM 1.37 + 5.00 5.00 1 N 7.0 4.370 150 42.857
to 7.000 1.893
BOR -3 31.12 1.101 11.370 0.1541 1.752 Vel = 10.49
BOR -3 0.0 1.5 N 9.0 3.330 150 46.502
to 9.000 0.0
7 -3 31.12 1.598 12.330 0.0251 0.310 Vel = 4.98
7 -3 0.0 2 N 11.0 83.290 150 46.812
to 11.000 0.0
8 -3 31.12 2.003 94.290 0.0084 0.789 Vel = 3.17
8 -3 0.0 1 0.230 150 47.601
to 5.000 * * Fixed Loss = 5
WM -3 31.12 1.101 0.230 0.1522 0.035 Vel = 10.49
WM -3 0.0 1 0.420 150 52.636
to 0.0
9 -3 31.12 1.101 0.420 0.1548 0.065 Vel = 10.49
9 -3 0.0 1.5 2.050 150 52.701
to 0.0
SOR -3 31.12 1.598 2.050 0.0249 0.051 Vel = 4.98
0.0
SOR 31.12 52.752 K Factor = 4.28
10 10.19 4.90 13.12 1 O 5.0 0.810 150 7.170
to 5.000 -0.351
11 11 13.12 1.101 5.810 0.0313 0.182 Vel = 4.42
Final Calculations : Hazen-Williams
Computer Programs by Hydratec Inc. Revision: 50.54.4
Southwest Fire Pros Page 5
78761 Deacon Drive La Quinta, Ca Date
Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf
11 11 0.0 1 R 1.0 2.300 150 7.001
to 1.000 0.0
2 11 13.12 1.101 3.300 0.0312 0.103 Vel = 4.42
0.0
2 13.12 7.104 K Factor = 4.92
3 11 11.20 1 10R 10.0 59.270 150 15.098
to 3O 15.0 67.000 0.0
12 11 11.2 1.101 6N 42.0 126.270 0.0233 2.940 Vel = 3.77
12 11 0.0 1 2O 10.0 12.000 150 18.038
to 10.000 0.0
4 11 11.2 1.101 22.000 0.0233 0.512 Vel = 3.77
0.0
4 11.20 18.550 K Factor = 2.60
Final Calculations : Hazen-Williams
Computer Programs by Hydratec Inc. Revision: 50.54.4
Approvals:
Sprinkler Identification Number (SIN):
Maximum Working Pressure:
Discharge Coefficient (Nominal K-Factor):
Temperature Rating:
Color Code (Sprinkler)
Color Code (Cover Plate)
Vertical Adjustment:
Cover Plate Finishes:
Standard Finishes-
Custom Finishes-
Please see chart on Page 8 for more detail.
Physical Characteristics:
In case of fire, the solder component that holds together the Cover Plate and the Retainer melts. Then the Cover Plate is
released at once. As a result, the Deflector drops down to the intended position. Two Heat Collectors are exposed to fire, and
when sufficient heat from the fire is reached, internal components of the sprinkler fall apart. This leads to the water flow to be
distributed on the affected fire area. (Ref. Figure 2)
DESIGN CRITERIA
The herein stated rules for use and installation of Model RC-RES are provided by the manufacturer and must be strictly
implemented for safe and full results.
Locations of sprinklers must follow the obstruction rules of NFPA 13, 13D and 13R for Residential Sprinklers.
The Model RC-RES must only be utilized in WET PIPE sprinkler systems.
Refer to NFPA 13D, 13R or 13 for the requirements relating to the prevention of possible activation of the Heat Responsive
Element of Model RC-RES, due to the exposure of a heat source other than an actual fire.
Available Sprinkler Temperature Ratings
Sprinkler Temperature
Classification
Sprinkler Nominal
Temperature Rating
Maximum Ambient Ceiling
Temperature
Temperature Rating of the
Cover Plate Assembly
Ordinary 162°F (72°C) 100°F (38°C) 140°F (60°C)
Intermediate 175°F (79°C 150°F (66°C) 140°F (60°C) 1)
Intermediate 175°F (79°C) 150°F (66°C) 162°F (72°C)
1) Maximum ambient temperature for the Cover Plate Assembly is 100°F (38°C).
Model RC-RES sprinklers should not be installed where they may be subjected to a corrosive environment including the
following:
Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride. Exposure to this
environment may result in sprinklers operating under Non-Fire conditions or Not Operating when exposed to an actual fire.
Sprinkler systems should be constructed in compliance with the applicable standards and the requirements for copper
piping when copper piping is used in the sprinkler system. (Reference standards NFPA 13, ASTM B813, B828, and CDA
(Copper Development Association) – Solder Joint)
All residual flux must be removed from the interior and exterior of the copper piping by thoroughly flushing before
installation of the Sprinkler Heads. Otherwise, residues of flux may cause corrosion and/or leakage in the sprinkler system.
The minimum required sprinkler flow rates for systems designed to NFPA 13D or 13R are given in TABLE A as a function of
temperature rating and the maximum allowable coverage area. The sprinkler flow rate is the minimum required discharge from
the most hydraulically demanding sprinkler from each of the total number of “design sprinklers” as specified in NFPA 13D or
13R.
For systems designed to NFPA 13, the number of designed sprinklers is to be the four most hydraulically demanding sprinklers.
The minimum required discharge from each of the four sprinklers is to be the greater of the following:
The flow rates given in TABLE A for NFPA 13D and 13R as a function of temperature rating and maximum allowable
coverage area.
A minimum discharge of 0.1GPM/sq.ft. [4.07LPM/sq.m] over the “design area” comprised of the four most hydraulically
demanding sprinklers for the actual coverage area being protected by the four sprinklers.
For systems with ceiling types smooth flat horizontal, or beamed, or sloped, in accordance with NFPA 13D, 13R or 13 as
applicable.
Ordinary
Temperature Rating
162°F (72°C)
Intermediate
Temperature Rating
175°F (79°C)
Maximum
Coverage
Area(a)
Ft. × Ft.
(m ×m)
Maximum
Spacing
Ft.
(m)
Flow(b)
GPM
(LPM)
Pressure(b)
PSI
(bar)
Flow(b)
GPM
(LPM)
Pressure(b)
PSI
(bar)
Deflector
to
Ceiling
Installation
Type
Minimum
Spacing
Ft.
(m)
12×12
(3.7×3.7)
12
(3.7)
13
(49.2)
7.0
(0.48)
13
(49.2)
7.0
(0.48)
14×14
(4.3×4.3)
14
(4.3)
13
(49.2)
7.0
(0.48)
13
(49.2)
7.0
(0.48)
15×15
(4.6×4.6)
15
(4.6)
13
(49.2)
7.0
(0.48)
13
(49.2)
7.0
(0.48)
16×16
(4.9×4.9)
16
(4.9)
13
(49.2)
7.0
(0.48)
14
(53.0)
8.2
(0.57)
18×18
(5.5×5.5)
18
(5.5)
17
(64.3)
12.0
(0.83)
18
(68.1)
13.5
(0.93)
20×20
(6.1×6.1)
20
(6.1)
21
(79.5)
18.4
(1.27)
Smooth
Ceilings
3/8 to 7/8
Inches.
Beamed
Ceilings
per NFPA
13D, 13R
or 13
Installed
in beam
3/8 to 7/8
inches
below
bottom of
beam.
Concealed 8
(2.4)
(a) For coverage area dimensions less than the above mentioned, it needs to use the minimum required flow for the
Next Higher Coverage Area listed.
(b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are
calculated using the nominal K-Factor. Refer to Hydraulic Design Criteria Section for details.
The minimum spacing between sprinklers is 8 feet (2.4m). The maximum spacing between sprinklers cannot go beyond the
coverage area calculated by using the specific hydraulic factors. (Ref. TABLE A)
The Model RC-RES must be installed in accordance with the following instructions:
The installation requirements for the sprinkler are as follows: to be installed only in the pendent position with the waterway
perpendicular to the ceiling. Install the sprinkler fitting so that the distance from the face of the fitting to the mounting surface
will be nominally 2 inches (50.8mm) as shown in Figure 3.
With pipe thread sealant applied to the threads, hand tighten the sprinkler into the sprinkler fitting. Then tighten it with the
Socket NR-H or Ratchet (3/8” drive) & Socket NR-H Combination (Ref. Figure 4). The teeth of the Socket must fit perfectly
with the grooves on the Sprinkler for proper installation (Ref. Figure 4).
If desired, the Protective Cap may also be used to locate the center of the clearance hole by gently pushing the ceiling
material against the center point of the Protective Cap. Before the installation of the ceiling, the sprinkler installation can be
started with a 2-3/8 inch (60mm) diameter clearance hole (Ref. Figure 3). Use the “Vertical Adjustment” indicator on the
Protective Cap to check for proper installation height (Ref. Figure 3).
Use the Cap Remover RC to remove the Protective Cap (Ref. Figure 5), and then push or screw a Cover Plate Assembly on
the Cup of the Sprinkler by hand until its flange just has contact with the ceiling (Ref. Figure 6 and Figure 7). Stop tightening
the Cover Plate Assembly once the flange has contact with the ceiling. If the ceiling has been lifted from its normal position in
the process of tightening the Cover Plate Assembly, readjust the cover plate assembly as necessary. If the flange of the Cover
Plate Assembly cannot contact the ceiling sufficiently, readjust the sprinkler fitting as necessary. When properly installed,
there is a nominal 1/16 inch (1.6mm) air gap between the lip of the Cover Plate and the ceiling, as shown in Figure 6.
The following instructions must be implemented for the maintenance and service of the Model RC-RES.
When placing an order, please contact a local distributor with the following information (Model Name, Temperature Rating and
Finish).
Model: RC-RES
(SIN: SS8464, Residential Flat Concealed Sprinkler, Pendent, K4.9, Temperature: 162°F (72°C) or 175°F (79°C) )
2-5/8 inch (68mm) or 3-1/4 inch (83mm) or 2-5/8 inch square (68mm), Order Separately from Sprinkler
Please refer to the chart below for available sizes, temperature, and finishes.
Standard Finishes Custom Finishes
2-5/8" Round, 140°F - - - - - -
3-1/4" Round, 140°F
2-5/8" Square, 140°F - - - - - - -
2-5/8" Round, 162°F - - - - - - -
3-1/4" Round, 162°F - - - - - - -
Socket NR-H
For use with a 3/8” drive ratchet (not included)
Socket NR-H Plastic
For use with a 1/2” drive ratchet (not included)
Cap Remover RC
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
December 19, 2022
Southwest Fire
Re: Residential Fire Sprinkler Plan Review – Rippee Residence
FSS2022-0449 / 78761 Deacon Dr E
The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
Permanently marked identification signs shall be attached to all control valves.
The following inspections/tests are required to be witnessed by Office of the Fire Marshal Staff:
(a) Overhead Rough and Hydro static test: All piping shall be visible and pumped at normal
operating pressure. *No jacketed electrical and data wiring shall be in contact with, nor have the
potential to contact CPVC piping once insulation is installed.
(b) Final inspection
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Rebecca Winscott - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 78761 Deacon Dr E PERMIT#: FSS2022-0449 DATE
ISSUED: 121922
DESCRIPTION: Rippee Residence CONTRACTOR: Southwest Fire
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation
Air flow test
Mechanical interlock
Extinguishing system
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.