LAQ-16-TI-030ADDITIONAL SITES
CHRONOLOGY
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
E-MAIL AARON HICKSON 3/20/2018 3/20/2018
RECEIVED EMAIL FROM MARIO GARCIA OF FELIX BROTHERS
CONSTRUCTION WITH ATTACHED SIGNED LETTER TO
REMOVE HIM AS THE CONTRACTOR FOR BCOM2016-0046
FOR THE 3RD TIME. PERMIT IS NOW ON HOLD UNTIL NEW
CONTRACTOR IS DETERMINED. BY OWNER
NOTE AARON HICKSON 12/26/2017 12/26/2017 PERMIT ON HOLD PER AJ . FOLDER IS IN UNDER
CONSTRUCTION.
NOTE ARMANDO MAGALLON 8/28/2017 8/28/2017
PLANS WERE LEFT ON MARY'S DESK. APPLICANT CAME TO
PICK UP CORRECTION LIST BUT THERE WERE NO ACTIVE
REVIEWS. I GAVE APPLICANT JOB SET AND CORRECTIONS LIST
BACK.
ENGINEER NEEDED A CORRECTION LIST TO BE ABLE TO GET
THE WORK AJ NEEDED TO BE PUT ON PLANS. JIM PROVIDED
CORRECTION LIST FOR ENGINEER.
Description: PALM TREE PALACE T.I.
Type: BUILDING COMMERCIAL Subtype: REMODEL Status: ISSUED Applied: 9/29/2016 MFA
Parcel No: 600030016 Site Address: 79660 HIGHWAY 111 STE 103 LA QUINTA,CA 92253 Approved: 12/1/2016 JJO
Subdivision: PM 31143 Block: Lot: 4 Issued: 1/11/2017 MFA
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled:
Valuation: $90,000.00 Occupancy Type: Construction Type: Expired: 1/21/2019 JFU
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details: REPLACE NEW HVAC, RESTROOM, CEILING, PLUMBING, ELECTRICAL, KITCHEN EQUIPMENT PER 2013 CALIFORNIA BUILDING CODE
REV #1 STRUC CALCS FOR NEW ROOF MOUNTED UNITS
REVISION 2 - FURTHER RELOCATION OF HVAC EQUIPMENT AND MAKE UP AIR UNITS TO COMPLY WITH EXHAUST FAN AND OTHER
CLEARANCES.
Printed: Wednesday, April 26, 2023 3:56:34 PM 1 of 17
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2016-0046
NOTE ARMANDO MAGALLON 9/8/2017 9/8/2017 JIM REVIEWED PLANS AND DECIDED TO SEND TO STR. I WILL
SEND OUT TO KURT FOR FIRST REVIEW STR REVISIONS
NOTE ARMANDO MAGALLON 12/19/2017 12/19/2017 REVISION 2 ISSUED
NOTE ARMANDO MAGALLON 2/27/2018 2/27/2018
CONTRACTOR HAS ISSUES WITH APPLICANT AND WANTED
TO BE REMOVED FROM PERMIT ONCE AGAIN, I RECEIVED A
LETTER STATING THAT HE WANTED TO BE RMOVED (WAS
PUT IN FILE). I SPOKE TO AJ AND INSTEAD OF PLACING
PERMIT ON HOLD I EXPIRED THE PERMIT SINCE NO PASSING
INSPECTIONS WERE CONDUCTED ON THE PROPERTY AND
EXPERITAION DATE HAD ALREADY PASSED. APPLICANT WILL
HAVE TO REQUEST AN EXTENSION FOR THIS PERMIT IF HE
WANTS IT REINSTATED.
NOTE JIM JOHNSON 9/22/2017 9/22/2017 PENDING STRUC FROM ESGIL
NOTE MARY FASANO 9/28/2017 9/28/2017 BROUGHT IN SIGNED PLANS
NOTE MARY FASANO 1/18/2018 1/18/2018
CONTRACTOR CAME IN TO REQUEST TO BE PUT BACK ON THE
PERMIT AS HE AND THE OWNER RESOLVED THE ISSUE. AJ
SAID WE DIDN'T NEED ANYTHING IN WRITING, HE JUST
NEEDED TO PAY THE FEE.
OFFICE MEETING JIM JOHNSON 8/28/2017 8/28/2017 PROVIDE CORRECTION LIST FOR APPLICANT TO GIVE TO
ENGINEER
PLAN CHECK COMMENTS
FROM CONSULTANT
RECEIVED
AARON HICKSON 12/7/2017 12/7/2017 PLAN CHECK RECEIVED APPROVABLE
PLAN CHECK COMMENTS
FROM CONSULTANT
RECEIVED
ARMANDO MAGALLON 9/21/2017 9/22/2017 APPROVABLE BUT NEED EOR STAMP.
PLAN CHECK PICKED UP STEPHANIE SWANSTROM 9/22/2017 9/22/2017 MARIO GARCIA PICKED UP PLANS SO THEY COULD BE SIGNED
PLAN CHECK SUBMITTAL
RECEIVED JACK LIMA 1/2/2019 1/2/2019
INDOOR LIGTHING, AUTOMATIC DAYLIGHTING, AND ENERGY
CONTROL SYSTEM FORMS SUBMITTED AT COUNTER FOR
REVIEW.
PLAN CHECK SUBMITTAL
RECEIVED MARY FASANO 9/29/2016 9/29/2016 SENT ONE SET OF PLANS TO PLANNING
Printed: Wednesday, April 26, 2023 3:56:34 PM 2 of 17
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2016-0046
PLAN CHECK SUBMITTAL
RECEIVED MARY FASANO 11/30/2017 11/30/2017 APPLICANT BROUGHT IN PLANS FOR 2ND REVISIONS. SENT
TO YOUNG AND PLANNING
PUBLIC COUNTER VISIT AARON HICKSON 12/26/2017 12/26/2017
MARIO GARCIA DROPPED OFF LETTER TO REMOVE FELIX
BROTHERS CONSTRUCTION FROM PERMIT # BCOM2016-
0046. LETTER IS IN ATTACHMENTS.
PUBLIC COUNTER VISIT AARON HICKSON 3/1/2018 3/1/2018 CONTRACTOR ADDED AGAIN
PUBLIC COUNTER VISIT AARON HICKSON 3/19/2018 3/19/2018
DACK LEE CAME IN TO FIND OPTIONS FOR FINISHING WORK
AS CONTRACTOR IS NOT AVAILABLE. ASKED AJ HE SAID
CONTRACTOR WOULD NEED TO REMOVE HIMSELF FROM
PERMIT SO A NEW CONTRACTOR COULD CONTINUE WORK
ON PROJECT.
PUBLIC COUNTER VISIT AARON HICKSON 3/27/2018 3/27/2018
DACK LEE ADDED NEW CONTRACTOR JLIN TO PERMIT. JLIN
APPLIED FOR CITY LIC. AND DACK LEE PAID CHANGE OF
CONTRACTOR FEE.
RESUBMITTAL MARY FASANO 11/23/2016 11/29/2016
THIS PLAN CHECK WAS SHIPPED IN BUT NOT SURE WHAT
DATE IT CAME IN. THE APPLICANT SAID SHE SHIPPED IT ON
11/17/2016. I SAW IT ON THE COUNTER AND PROCESSED IT.
SITE VISIT AJ ORTEGA 8/1/2017 8/1/2017
SPOKE WITH CONTRACTOR REGARDING ROOF TOP
MECHANICAL EQUIPMENT PLATFORMS, NO ENGINEERING
APPEARS TO HAVE BEEN PROVIDED FOR NEW EQUIPMENT,
ADDITIONAL ENGINEERING WILL BE REQUIRED TO BE
SUBMITTED, REVIEWED AND APPROVED PRIOR TO
PLACEMENT OF EQUIPMENT.
TELEPHONE CALL JAKE FUSON 12/18/2017 12/18/2017
NOTIFIED DACK LEE THAT PLANS WERE APPROVED AND
REVISION 2 WAS READY TO ISSUE (PAY FEES AND ISSUE
PLANS).
TELEPHONE CALL JIM JOHNSON 10/14/2016 10/14/2016 CALLED BING TO INFORM HER THAT THE PLANS HAVE
CORRECTION
TELEPHONE CALL JIM JOHNSON 12/2/2016 12/2/2016 CALLED BING ZHANG TO INFORM HER THE PLANS ARE
READFY TO ISSUE
TELEPHONE CALL JIM JOHNSON 9/22/2017 9/22/2017 CALLED MARVIN GARCIA TO INFORM HIM THE PLANS ARE
NOT SIGNED AND THE 8X11 SHEETS NEED A SEAL AND SIGN.
Printed: Wednesday, April 26, 2023 3:56:34 PM 3 of 17
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2016-0046
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT BING ZHANG (760)469-0548 BING@HELLODRP.COM
CONTRACTOR JLIN CONSTRUCTION INC 1809 BAILEY AVE ROSEMEAD CA 91770 (760)469-0548
CONTRACTOR
(HISTORY)
FELIX BROTHERS CONSTRUCTION
COMPANY
1030 THIRD ST CALEXICO CA 92231 (760)469-0548
CONTRACTOR
(HISTORY) 1
FELIX BROTHERS CONSTRUCTION
COMPANY
1030 THIRD ST CALEXICO CA 92231 (760)469-0548
CONTRACTOR
(HISTORY) 2
FELIX BROTHERS CONSTRUCTION
COMPANY
1030 THIRD ST CALEXICO CA 92231 (760)469-0548
ENGINEER DRP, INC.119 S ATLANTIC BLVD
STE 228
MONTEREY
PARK
CA 91754 (760)469-0548
OWNER DUNES BUSINESS PARK P O BOX 1216 HERMOSA
BEACH
CA 92253 (760)469-0548
CONDITION
TYPE CONTACT DATE
ADDED
DATE
REQUIRED
DATE
SATISFIED STATUS REMARKS NOTES
READY TO ISSUE
CHECKLIST JIM JOHNSON 10/13/2016 1/11/2017 COMPLETE
HEALTH DEPT, AND CVWD APPROVAL REQUIRED.
CVWD AND HEALTH DEPT. APPROVAL BROUGHT
IN
READY TO ISSUE
CHECKLIST JIM JOHNSON 9/20/2017 9/29/2017 9/29/2017 COMPLETE PLANS NOT SIGNED, NEED EOR SEAL/SIGN 8X11
BEFORE WE ISSUE
TELEPHONE CALL JIM JOHNSON 9/22/2017 9/22/2017 CALLED MARVIN GARCIA TO INFORM HIM THE PLANS ARE
NOT SIGNED AND THE 8X11 SHEETS NEED A SEAL AND SIGN.
TELEPHONE CALL JIM JOHNSON 9/29/2017 9/29/2017 CALLED MARVIN TO INFORM HIM THE PLANS ARE READY TO
ISSUE
CONDITIONS
FINANCIAL INFORMATION
Printed: Wednesday, April 26, 2023 3:56:34 PM 4 of 17
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2016-0046
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
CHANGE OF
CONTR/ARCH/OWNER
PROCESSING
101-0000-42600 0 $104.55 $104.55 3/27/18 R33517 CASH DACK LEE AHI
CHANGE OF
CONTR/ARCH/OWNER
PROCESSING
101-0000-42600 0 $104.55 $104.55 1/18/18 R31246 BCOM2016
-0046 DEBIT FELIX BROTHERS
CONSTRUCTION CO MFA
Total Paid for ADMINISTRATIVE: $209.10 $209.10
HOURLY CHARGE - CITY
BUILDING STAFF 101-0000-42600 1 $156.00 $156.00 12/19/17 R30329 1040 CHECK GOLDEN MOUNTAIN
GROUP LLC AMA
HOURLY CHARGE - CITY
BUILDING STAFF 101-0000-42600 0.5 $76.00 $76.00 9/29/17 R28234 00001 CREDIT
CARD MARIO A FELIX MFA
HOURLY CHARGE -
ESGIL STRUCTURAL
ENGINEER
101-0000-42600 1 $120.00 $120.00 9/29/17 R28234 00001 CREDIT
CARD MARIO A FELIX MFA
HOURLY CHARGE - YES
STRUCTURAL PLAN
REVIEW ENGINEER
101-0000-42600 1 $95.00 $95.00 12/19/17 R30329 1040 CHECK GOLDEN MOUNTAIN
GROUP LLC AMA
Total Paid for BLDG CITY STAFF - PER HOUR: $447.00 $447.00
BSAS SB1473 FEE 101-0000-20306 0 $4.00 $4.00 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
Total Paid for BUILDING STANDARDS ADMINISTRATION
BSA: $4.00 $4.00
Credit Card Fee 101-0000-43505 0 $3.53 $3.53 9/29/17 R28234 00001 CREDIT
CARD MARIO A FELIX MFA
Total Paid for Credit Card Fee: $3.53 $3.53
NON-RESIDENTIAL, EA
ADDITION 2,000SF 101-0000-42403 0 $38.00 $38.00 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
NON-RESIDENTIAL, EA
ADDITION 2,000SF, PC 101-0000-42600 0 $10.13 $10.13 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
NON-RESIDENTIAL,
FIRST 2,000SF 101-0000-42403 0 $114.00 $114.00 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
Printed: Wednesday, April 26, 2023 3:56:34 PM 5 of 17
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2016-0046
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
NON-RESIDENTIAL,
FIRST 2,000SF, PC 101-0000-42600 0 $88.16 $88.16 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
Total Paid for ELECTRICAL - NEW CONSTRUCTION: $250.29 $250.29
CONDENSER/COMPRES
SOR 101-0000-42402 0 $114.00 $114.00 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
CONDENSER/COMPRES
SOR PC 101-0000-42600 0 $75.99 $75.99 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
EVAPORATIVE COOLER 101-0000-42402 0 $38.01 $38.01 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
EVAPORATIVE COOLER
PC 101-0000-42600 0 $38.01 $38.01 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
EXHAUST HOOD 101-0000-42402 0 $38.01 $38.01 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
EXHAUST HOOD PC 101-0000-42600 0 $15.21 $15.21 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
FURNACE 101-0000-42402 0 $114.00 $114.00 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
FURNACE PC 101-0000-42600 0 $75.99 $75.99 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
VENT FAN 101-0000-42402 0 $25.34 $25.34 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
VENT FAN PC 101-0000-42600 0 $10.14 $10.14 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
Total Paid for MECHANICAL: $544.70 $544.70
BUILDING SEWER 101-0000-42401 0 $12.67 $12.67 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
BUILDING SEWER PC 101-0000-42600 0 $12.67 $12.67 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
Printed: Wednesday, April 26, 2023 3:56:34 PM 6 of 17
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2016-0046
INSPECTIONS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIXTURE/TRAP 101-0000-42401 0 $202.72 $202.72 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
FIXTURE/TRAP PC 101-0000-42600 0 $202.72 $202.72 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
GAS SYSTEM, 5+
OUTLETS 101-0000-42401 0 $38.00 $38.00 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
GAS SYSTEM, 5+
OUTLETS PC 101-0000-42600 0 $25.33 $25.33 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
GREASE INTERCEPTOR 101-0000-42401 0 $38.00 $38.00 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
GREASE INTERCEPTOR
PC 101-0000-42600 0 $12.67 $12.67 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
WATER HEATER/VENT 101-0000-42401 0 $12.67 $12.67 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
WATER HEATER/VENT
PC 101-0000-42600 0 $7.60 $7.60 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
WATER SYSTEM
INST/ALT/REP 101-0000-42401 0 $12.67 $12.67 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
WATER SYSTEM
INST/ALT/REP PC 101-0000-42600 0 $12.67 $12.67 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
Total Paid for PLUMBING FEES: $590.39 $590.39
SMI - COMMERCIAL 101-0000-20308 0 $25.20 $25.20 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
Total Paid for STRONG MOTION INSTRUMENTATION SMI: $25.20 $25.20
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 1/11/17 R21315 1012 CHECK GOLDEN MOUNTAIN
GROUP MFA
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$2,079.21 $2,079.21
Printed: Wednesday, April 26, 2023 3:56:34 PM 7 of 17
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2016-0046
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
INSULATION AOR 1/17/2017 1/17/2017 CANCELED
CANCELLED AT THE REQUEST OF
CONTRACTOR RECEIVED VIA VOICEMAIL,
WILL RECALL WHEN READY.
INSULATION AOR 3/6/2017 3/6/2017 APPROVED DEMISING WALL INSULATION ONLY.
UNDERGROUND PLBG AOR 4/7/2017 4/7/2017
APPROVED
W/EXCEPTIO
N
ALL PIPING APPROVED WITH EXCEPTION OF
TRAP PRIMER REQUIRED FOR KITCHEN
FLOOR DRAIN.
FRAMING JFU 7/5/2017 7/5/2017 PARTIALLY
APPROVED
INTERIOR PARTITIONS ONLY--DOES NOT
INCLUDE FURRED WALLS AT EAST AND WEST
DEMISING WALLS. FIRE DEPARTMENT
OVERHEAD APPROVAL REQUIRED PRIOR TO
INSTALLATION OF GYP. BOARD CEILINGS.
ROUGH ELEC JFU 7/5/2017 7/5/2017
APPROVED
W/EXCEPTIO
N
ROUGH ELECTRICAL AT INTERIOR
PARTITIONS AND HARD LID AREAS. FIRE
DEPARTMENT OVERHEAD APPROVAL
REQUIRED PRIOR TO INSTALLATION OF GYP.
BOARD CEILINGS.
ROUGH MECH JFU 7/5/2017 7/5/2017
APPROVED
W/EXCEPTIO
N
ROUGH MECHANICAL AT HARD LID AREAS.
FIRE DEPARTMENT OVERHEAD APPROVAL
REQUIRED PRIOR TO INSTALLATION OF GYP.
BOARD CEILINGS.
ROUGH PLBG JFU 7/5/2017 7/5/2017 PARTIALLY
APPROVED
ROUGH PLUMBING AT INTERIOR
PARTITIONS. DOES NOT INCLUDE FUEL
PIPING AT KITCHEN AREA. FIRE
DEPARTMENT OVERHEAD APPROVAL
REQUIRED PRIOR TO INSTALLATION OF GYP.
BOARD CEILINGS.
ROUGH PLBG JFU 7/24/2017 7/24/2017 APPROVED
COMPLETE APPROVAL OF ROUGH
PLUMBING, INCLUDES GAS PIPING AT EAST
WALL OF KITCHEN.
DRYWALL NAIL AOR 8/1/2017 8/1/2017 APPROVED
Printed: Wednesday, April 26, 2023 3:56:34 PM 8 of 17
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2016-0046
GREASE INTERCEPTOR JFU 8/30/2017 8/30/2017 PARTIALLY
APPROVED
WATER TEST OF INTERCEPTOR TANK ONLY.
RECALL WHEN CVWD INSPECTION
APPROVAL HAS BEEN GIVEN, "SAMPLE
TANK" HAS BEEN PUT IN PLACE AND ALL
ASSOCIATED WASTE AND VENT PIPING HAS
BEEN INSTALLED.
ROUGH MECH JFU 10/3/2017 10/3/2017 DISAPPROVE
D
INSPECTION SCHEDULED FOR THE NEW
HVAC UNITS INSTALLED.
CORRECTIONS:
-UNITS NOT LOCATED PER APPROVED PLAN.
REVISE PLANS/CALCS OR CONSTRUCTION AS
NECESSARY.
-PLUMBING VENTS, WATER HEATER VENT
MAY NOT BE LOCATED WITHI 10' OF MAKE-
UP AIR UNITS AND FRESH AIR INTAKES
-HOOD EXHAUST MAY NOT BE LOCATED
WITHIN 10' OF FRESH AIR INTAKE
-ADDITIONAL ROOFTOP UNITS (WALK-IN
FREEZER CONDENSERS) HAVE BEEN
INSTALLED AND ARE NOT ON PLANS OR
ENGINEERING
ROUGH ELEC JFU 10/3/2017 10/3/2017 PARTIALLY
APPROVED
ROUGH CONDUIT FROM SERVICE TO
SUBPANEL AND ROUGH CONDUIT FROM
SUBPANEL TO NEW HVAC UNITS.
CONDUCTOR SIZING, TYPE, INSTALLATION,
ETC YET TO BE INSPECTED.
GREASE INTERCEPTOR JFU 10/3/2017 10/3/2017 APPROVED
ROUGH MECH AOR 1/26/2018 1/26/2018 PARTIALLY
APPROVED
MECHANICAL EQUIPMENT PENETRATION
AND LOADING FRAMING PER REVISION 2
ENGINEERING
Printed: Wednesday, April 26, 2023 3:56:34 PM 9 of 17
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2016-0046
TEMP USE OF PERM PWR JFU 6/6/2018 6/6/2018 NOT READY
NO ACCESS TO SERVICE PANEL TO INSPECT
FEEDER CONDUCTORS, OCPD AND BRANCH
CIRCUIT WIRING. CONTRACTOR TO RECALL
WHEN EQUIPMENT MAY BE OPENED AND
ACCESSIBLE AND ELECTRICIAN IS ON SITE TO
FACILITATE AND OPEN/CLOSE EQUIPMENT.
T-BAR/OVERHEAD JFU 6/6/2018 6/6/2018 DISAPPROVE
D
-FIRE OVERHEAD APPROVAL REQUIRED
-EMT ABOVE T-BAR CEILINGS MUST BE
SECURED PER CEC 358 AND MAY NOT
PROVIDE SUPPORT FOR THE EQUIPMENT
(I.E. J-BOXES) WHICH MUST BE
INDIVIDUALLY SECURED AS REQUIRED BY
THE CEC
-PHOTOSENSING CONTROLS NOT INSTALLED
AT DAYLIGHITNG AREAS
T-BAR/OVERHEAD JFU 6/8/2018 6/8/2018 CANCELED
CONTRACTOR STAED HE WANTED A T-BAR
GRID INSPECTION ONLY BUT OVERHEAD
ITEMS MUST BE COMPLETE. PREVIOUS
CORRECTIONS STILL APPLY?INSPECTION
CANCELED.
TEMP USE OF PERM PWR JFU 6/8/2018 6/8/2018 APPROVED
GREASE INTERCEPTOR JFU 6/19/2018 6/19/2018 CANCELED
SEWER CONNECTION JFU 6/22/2018 6/22/2018
APPROVED
W/EXCEPTIO
N
BUILDING SEWER CLEANOUT MUST BE
EXTENDED TO GRADE. VERIFY AT FINAL
INSPECTION.
ROUGH MECH JFU 7/2/2018 7/2/2018 PARTIALLY
APPROVED
WELDING AT (3) GREASE DUCTS--DOES NOT
INCLUDE DUCT WRAP.
INSULATION JFU 7/5/2018 7/5/2018 APPROVED ROOF INSULATION REPLACED WHERE
REMOVED DURING CONSTRUCTION.
ROUGH MECH JFU 7/5/2018 7/5/2018 PARTIALLY
APPROVED
1ST LAYER OF DUCT WRAP AT (3) GREASE
EXHAUST DUCTS.
ROUGH MECH JFU 7/9/2018 7/9/2018 APPROVED 2ND LAYER OF DUCT WRAP AT (3) GREASE
DUCTS.
Printed: Wednesday, April 26, 2023 3:56:34 PM 10 of 17
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2016-0046
T-BAR/OVERHEAD JFU 7/19/2018 7/19/2018 NOT READY NO ONE ON SITE, DOORS LOCKED. NO
ACCESS NOTES PROVIDED.
T-BAR/OVERHEAD JFU 7/20/2018 7/20/2018 APPROVED PREVIOUS CORRECTIONS RESOLVED.
GAS LINE/TEST JFU 7/24/2018 7/24/2018 NOT READY NO ANSWER AT FRONT DOORS, DOORS
LOCKED, NO ACCESS NOTES PROVIDED.
GAS LINE/TEST JFU 7/25/2018 7/25/2018 APPROVED
FINAL**JFU 8/31/2018 8/31/2018 NOT READY
APPROVED PLAN NOT ON SITE.
CONTRACTOR TO LOCATE APPROVED PLANS
AND RECALL.
FINAL**JFU 9/13/2018 9/13/2018 DISAPPROVE
D
-BUSINESS LICENSE REQUIRED
-SUBMIT ENERGY DOCUMENTS
(MECHANICAL & ELECTRICAL)
-MAX OCPD EXCEEDED AT HVAC UNITS
-LABEL EACH AC UNIT INDIVIDUALLY
-PLUMBING VENT REQUIRES 10' CLEARANCE
TO MAKE-UP AIR
-SUBMIT AIR BALANCE REPORT
-SUBMIT COPY OF HEALTH DEPARTMENT
APPROVAL
FINAL**JFU 9/17/2018 9/17/2018 PARTIALLY
APPROVED
NO FURTHER SITE VISIT REQUIRED
HOWEVER THE FOLLOWING ITEMS MUST BE
COMPLETED PRIOR TO FINAL APPROVAL:-
SUBMIT ENERGY DOCUMENTS (MECH AND
ELEC)-SUBMIT AIR BALANCE REPORT-
PROVIDE HEALTH DEPARTMENT APPROVAL-
OBTAIN BUSINESS LICENSE
UPDATE: MECHANICAL ENERGY
DOCUMENTS, AIR BALANCE, AND HEALTH
DEPARTMENT APPROVAL TO OPERATE
RECEIVED (ALL ARE ATTACHED). FINAL
ELECTRICAL ENERGY DOCUMENTS AND
BUSINESS LICENSE STILL OUTSTANDING.
Printed: Wednesday, April 26, 2023 3:56:34 PM 11 of 17
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2016-0046
FINAL**JFU 9/17/2018 9/17/2018 PARTIALLY
APPROVED
UPDATE: FINAL ELECTRICAL ENERGY
DOCUMENTS RECEIVED (ALL ARE
ATTACHED). BUSINESS LICENSE STILL
OUTSTANDING.
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST BLDG NS (2 WK)JIM JOHNSON 9/29/2016 10/13/2016 10/13/2016 REVISIONS REQUIRED
1ST PLANNING (2
WK)
CARLOS
FLORES 9/29/2016 10/13/2016 10/12/2016 READY FOR APPROVAL
FIRE KOHL
HETRICK 10/25/2016 11/8/2016 11/8/2016 INCOMPLETE Only provided with 2
of 16 pg See attached correction letter in attachments.
Deferred Submittals Required:
1) Fire Sprinkler – Tenant Improvement plans
must be submitted and reference the installing
contractor performing the work. Permit fees in
the amount of $614.00 will be required.
2) Fire Alarm – Tenant Improvement plans must
be submitted and reference the installing
contractor performing the work. Permit fees in
the amount of $627.00 will be required.
3) Kitchen Hood Suppression – Tenant
Improvement plans must be submitted and
reference the installing contractor performing the
work. Permit fees in the amount of $215.00 will
be required.
4) High-Pile & Rack Storage – Tenant
Improvement plans must be submitted showing
the changes of layout and type of racks and
shelving as affected by this tenant improvement.
PARENT PROJECTS
Printed: Wednesday, April 26, 2023 3:56:34 PM 12 of 17
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2016-0046
FIRE
LISA
NOTTINGHA
M
11/18/2016 11/18/2016 11/18/2016 READY FOR APPROVAL
- CONDITION
Permit fees in the amount of $348.00 will be
required.
Buildings/facilities
1) Install Knox Key Lock box, mounted per
recommended standard of the Knox Company. If
the building/facility is protected with a fire alarm
system or burglar alarm system, the lock boxes
will require "tamper" monitoring. Special forms
are available from this office for the ordering of
the Key Switch. This form must be authorized
and signed by this office for the correctly coded
system to be purchased.
2) Provide keys to the tenant space for inclusion
in the main building Knox Box. Key(s) shall have
durable and legible tags affixed for identification
of the correlating tenant space.
3) Approved building address shall be placed in
such a position as to be plainly visible and legible
from the street and rear access if applicable.
Building address numbers shall be a minimum of
12”. Minimum 6” tall suite addressing shall be
provided to both the front and rear entrances. All
addressing must be legible and of a contrasting
color with the background and adequately
illuminated to be visible from the street at all
hours.
Other requirements:
1) Install portable fire extinguishers per Title 19,
but not less than 2A10BC in rating. All new and
existing portable fire extinguishers shall have
current annual servicing performed and tagged.
2) All kitchen hood suppression systems must
have current servicing performed and tagged.
3) All kitchen hood and ventilation systems shall
have records of inspection and necessary cleaning
in compliance with CFC 609.
Printed: Wednesday, April 26, 2023 3:56:34 PM 13 of 17
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2016-0046
4) Applicable room door(s) shall be posted
“ELECTRICAL ”, “FACP”, “FIRE RISER” and “ROOF
ACCESS” on the outside of the door so it is visible
and in a contrasting color.
5) A durable sign stating "This door to remain
unlocked during business hours" shall be placed
on or adjacent to the front exit doors. The sign
shall be in letters not less than one inch high on a
contrasting background.
6) Illuminated Exit Signage and Egress
Illumination placement and functional test will be
witnessed by OFM Fire Inspector at time of final
inspection.
7) Each room with an occupancy load of over fifty
people shall be posted in a conspicuous place on
an approved.
8) All egress doors shall comply with the
California Building Code for proper door
hardware.
The Fire Department approved plans and
conditions letter must be at the job site or NO
inspection will be performed.
Applicant/installer shall be responsible to contact
the Fire Department to schedule inspections.
Requests for inspections are to be made at least
72 hours in advance and may be arranged by
calling (760)863-8886.
SUBJECT TO FIELD INSPECTION - Nothing in our
review shall be construed as encompassing
structural integrity. Review of this plan does not
authorize or approve any omission or deviation
from all applicable regulations. Final approval is
subject to field inspection.
2ND BLDG NS (1
WK)JIM JOHNSON 11/23/2016 12/2/2016 12/1/2016 APPROVED
Printed: Wednesday, April 26, 2023 3:56:34 PM 14 of 17
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2016-0046
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 12/26/2017 AARON HICKSON CONTRACTOR
REMOVAL LETTER
CONTRACTOR
REMOVAL.pdf 0
DOC 9/20/2017 AJ ORTEGA
REVISION 1 - 1ST
REVIEW STRUCTURAL
TRANSMITTAL
BCOM2016-0046 -
REVISION 1 - 1ST
REVIEW STRUCTURAL
TRANSMITTAL.pdf
0
DOC 9/20/2017 AJ ORTEGA
REVISION 1 - 1ST
REVIEW STRUCTURAL
FEE SHEET
BCOM2016-0046 -
REVISION 1 - 1ST
REVIEW STRUCTURAL
FEE SHEET.pdf
0
BOND INFORMATION
1ST BLDG NS (2 WK)JIM JOHNSON 9/8/2017 9/22/2017 9/20/2017 APPROVED-
CONDITIONS REV 1
REV 1:HVAC UNIT RELOCATION/ADDITION
PLANS NOT SIGNED
1ST BLDG STR (2
WK)KURT CULVER 9/8/2017 9/22/2017 9/19/2017 READY FOR APPROVAL
- CONDS REV 1 REV 1:HVAC UNIT RELOCATION/ADDITION
1ST BLDG NS (1
DAY)JIM JOHNSON 9/28/2017 9/29/2017 9/29/2017 APPROVED
1ST BLDG NS (2 WK)JAKE FUSON 11/30/2017 12/14/2017 12/18/2017 APPROVED REVISION 2
REVISION 2 - FURTHER RELOCATION OF HVAC
EQUIPMENT AND MAKE UP AIR UNITS TO
COMPLY WITH EXHAUST FAN AND OTHER
CLEARANCES.
1ST BLDG STR (2
WK)
YOUNG
ENGINEERING 11/30/2017 12/14/2017 12/8/2017 READY FOR APPROVAL REV: 2
1ST PLANNING (2
WK)
CARLOS
FLORES 11/30/2017 12/14/2017 12/8/2017 READY FOR APPROVAL REV: 2
3RD BLDG NS (1 WK)JAKE FUSON 1/2/2019 1/10/2019 1/7/2019 NOT REQUIRED
THIS REVIEW WAS CREATED BY COUNTER STAFF
TO REVIEW THE FINAL ENERGY COMPLIANCE
DOCUMENTATION HOWEVER AN OFFICIAL
REVIEW IS NOT REQUIRED.
Printed: Wednesday, April 26, 2023 3:56:34 PM 15 of 17
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2016-0046
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 12/6/2017 BRONZ YOUNG
1ST CHECK -
STRUCTURAL
TRANSMITTAL.pdf
1ST CHECK -
STRUCTURAL
TRANSMITTAL.pdf
0
DOC 11/19/2018 JAKE FUSON
OUTDOOR AIR
ACCEPTANCE - NRCA-
MCH-02-A
BCOM2016-0046 -
OUTDOOR AIR
ACCEPTANCE - NRCA-
MCH-02-A.pdf
1
DOC 11/19/2018 JAKE FUSON HEALTH DEPARTMENT
APPROVAL TO OPERATE
BCOM2016-0046 -
HEALTH DEPARTMENT
APPROVAL TO
OPERATE.pdf
1
DOC 11/19/2018 JAKE FUSON AIR BALANCE REPORT BCOM2016-0046 - AIR
BALANCE REPORT.pdf 1
DOC 1/7/2019 JAKE FUSON
FINAL ENERGY
ACCEPTANCE AND
INSTALLATION FORMS -
ELECTRICAL ONLY
BCOM2016-0046 - FINAL
ENERGY ACCEPTANCE
AND INSTALLATION
FORMS - ELECTRICAL
ONLY.pdf
1
DOC 12/1/2016 JIM JOHNSON
2ND REVIEW NON-
STRUCTURAL
RESPONSES
CORR BCOM2016-
0046.pdf 0
DOC 8/28/2017 JIM JOHNSON
1ST REVIEW NON-
STRUCTURAL
CORRECTIONS
79-660 HWY 111 REV
1.docx 0
DOC 11/8/2016 KOHL HETRICK 1ST REVIEW FIRE
CORRECTIONS LETTER
LAQ-16-TI-030 - PALM
TREE PALACE - TI BLDG
PC - CORRECTIONS.docx
0
DOC 1/17/2017 MARY FASANO CVWD APPROVAL BCOM2016-0046 CVWD
APPROVAL.pdf 0
DOC 1/17/2017 MARY FASANO ENVIRONMENTAL
HEALTH APPROVAL
BCOM2016-0046 EHS
APPROVAL.pdf 0
Printed: Wednesday, April 26, 2023 3:56:34 PM 16 of 17
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2016-0046
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 5/22/2018 MARY FASANO Permit Details Permit Details.pdf
IMAGE 3/20/2018 AARON HICKSON CONTRACTOR
REMOVAL 03192018
CONTRACTOR
REMOVAL.jpg 0
Printed: Wednesday, April 26, 2023 3:56:34 PM 17 of 17
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2016-0046