BELC2023-1051BUILDING PERMIT
DESIGN & DEVELOPMENT
DEPARTMENT
78-495 CALLE TAMPICO
LA QUINTA, CALIFORNIA 92253
PHONE (760) 777-7125
WWW.LAQUINTACA.GOV
APPLIED DATE: 11/15/2023
ISSUED DATE: 11/16/2023
Permit Type:
Permit Number:
Property Address:
APN:
Legal Description
Property Zoning:
Valuation:
Electrical
81180 LEGENDS WAY
BELC2023-1051
762310004
Lot 25 MB 285/51 TR 28838-1 AMENDED
$20,000.00
RL, 25
Owner:Stephanie McCartney
Applicant:MDESIGN GROUP - mariano ramirez
75145 St Charles Place #3, Palm Desert, CA
92211
Contractor:MARGARET A VARGAS
73000 Shadow Mountain Dr, Palm Desert, CA
92260
Declaration / Acknowledgement
PRIOR TO THE ISSUANCE OF THIS PERMIT FOR CONSTRUCTION, ALTERATION, IMPROVEMENT, DEMOLITION, OR REPAIR THE OWNER, APPLICANT AND/OR
CONTRACTOR UNDER PENALTY OF PERJURY HAVE AFFIRMED WHEN APPLICABLE, THROUGH THE SUBMITTAL OF FORMS OR BY OTHER ELECTRONIC MEANS, THE
FOLLOWING:
LICENSED CONTRACTOR OR OWNER-BUILDER DECLARATION (1 or 2)
1) They are licensed under provisions of Chapter 9 (commencing with
Section 7000) of Division 3 of the Business and Professions Code, and the
referenced
License is in full force and effect, or;
2) That they are exempt from the Contractors’ State License Law for the
reason(s) indicated by either (2)(a) and/or (2)(b), or (2)(c) where he or
she is exempt from licensure by a valid exemption. [Section 7031.5,
Business and Professions Code: Any city or county that requires a permit
to construct, alter, improve, demolish, or repair any structure, prior to its
issuance, also requires the applicant for the permit to file a signed
statement that he or she is licensed pursuant to the provisions of the
Contractors’ State License Law (Chapter (commencing with Section 7000)
of Division 3 of the Business and Professions
Code] Any violation of Section 7031.5 by any applicant for a permit
subjects the
applicant to a civil penalty of not more than five hundred dollars ($500).)
a) As owner of the property, or my employees with wages as their sole
compensation, will do all of or portions of the work, and the structure is
not intended or offered for sale (Section 7044, Business and Professions
Code: The Contractors’ State License Law does not apply to an owner of
property who, through employees’ or personal effort, builds or improves
the property, provided that the improvements are not intended or offered
for sale. If, however, the building or improvement is sold within one year of
completion, the Owner-Builder will have the burden of proving that it was
not built or improved for the purpose of sale.).
b) As owner of the property, will be exclusively contracting with licensed
c) Are exempt from licensure under the Contractors’ State License Law.
As an Owner-Builder, they acknowledge that, except for their personal
residence in which they must have resided in for at least one year prior to
completion of the improvements covered by this permit, they cannot legally
sell a structure built as an owner-builder if it has not been constructed in
its entirety by licensed contractors. It is understood that a copy of the
applicable law, Section 7044 of the Business and Professions Code, is
available upon request when this application was submitted at the
following Web site:
http://www.leginfo.ca.gov/calaw.html.
DECLARATION REGARDING CONSTRUCTION LENDING AGENCY (If
applicable)
A construction lender will be used for completion of the improvements
covered by this permit and the name and information of which is on file for
public inspection during the regular business hours of the public entity.
Failure of the applicant to indicate the construction lender on the
application does not relieve that person of the requirement to give the
WORKERS’ COMPENSATION DECLARATION (1, 2 or 3)
WARNING: FAILURE TO SECURE WORKERS’ COMPENSATION COVERAGE IS
UNLAWFUL, AND SHALL SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND
CIVIL FINES UP TO ONE HUNDRED THOUSAND DOLLARS ($100,000), IN ADDITION
TO THE COST OF COMPENSATION, DAMAGES AS PROVIDED FOR IN SECTION
3706 OF THE LABOR CODE, INTEREST, AND ATTORNEY’S FEES.
1) Has and will maintain a certificate of consent to self-insure for workers’
compensation, issued by the Director of Industrial Relations as provided for
by Section 3700 of the Labor Code, for the performance of the work for
which this permit is issued.
2) Has and will maintain workers’ compensation insurance, as required by
Section 3700 of the Labor Code, for the performance of the work for which
this permit is issued.
3) Certifies that, in the performance of the work for which this permit is
issued, shall not employ any person in any manner so as to become subject
to the workers’ compensation laws of California, and agree that, if should
become subject to the workers’ compensation provisions of Section 3700 of
the Labor Code, shall forthwith comply with those provisions.
NOTICE TO APPLICANT (1, 2 and 3)
1) Each person upon whose behalf this application was made, each person
at whose request and for whose benefit work is being performed under or
pursuant to any permit issued as a result of this application, the owner, and
the applicant, each agrees to, and shall defend, indemnify and hold harmless
the City of La Quinta, its officers, agents, and employees for any act or
omission related to the work being performed under or following issuance of
this permit.
2) Any permit issued as a result of this application becomes null and void if
work is not commenced within 360 days from date of issuance of such
permit, or if cessation of work for 180 days will subject permit to
cancellation. On or after January 1, 2019, every permit issued shall become
invalid unless the work on the site authorized by such permit is commenced
within 12 months after its issuance, or if the work authorized on the site by
such permit is suspended or abandoned for a period of 12 months after the
time the work is commenced.
3) Certified that they read the application and state that the information
provided is correct. Agree to comply with all city and county ordinances and
state laws relating to building construction, and hereby authorize
representatives of this city to enter upon the above-mentioned property for
inspection purposes.
IMPORTANT: An Application for Permit was made to the Building Official,
subject to the conditions and restrictions set forth at the time of application,
which is now hereby an Issued Permit. If any part of the information being
supplied on this permit is inaccurate or untrue, please contact the City of La
Quinta at (760) 777-7125 immediately for correction.
Printed: 11/16/23 10:26 pm Page 1 of 4
Permit Type:
Permit Number:
Property Address:
Electrical
BELC2023-1051
81180 LEGENDS WAY
BUILDING PERMIT
construction lender preliminary notice from that duty.
Printed: 11/16/23 10:26 pm Page 2 of 4
Permit Type:
Permit Number:
Property Address:
Electrical
BELC2023-1051
81180 LEGENDS WAY
BUILDING PERMIT
400A ELECTRICAL SERVICE CHANGE OUT [200A EXISTING] SURGE PROTECTION DEVICE REQUIRED PER CEC 230.67, A TYPE 1 OR
2 SPD SHALL BE INSTALLED PRIOR TO RELEASE BEING SENT TO UTILITY. THIS PERMIT DOES NOT INCLUDE RELOCATION OF
EQUIPMENT OR ANY OTHER WORK. 2022 CALIFORNIA BUILDING CODES.
Use of Permit
Construction Details
200Existing Service(AMP)400NewService(AMP)NoYes/No
RLZoning LDRGeneral Plan Within La Quinta LimitsCity Limits
TR 28838-1 AMENDEDSubdivision Name 25Lot Number 93586Centerlines
2125.29Lot Size Lot 25 MB 285/51 TR
28838-1 AMENDED
Legal Description
Valuation Details
Type Group Sq Ft Value
Financial Information
Fee AmountFee Amount PaidInvoice No.
INV-00002455 $8.00 Technology Enhancement Fee $8.00
$30.51 Service Changeout / Upgrade $30.51
$21.36 Service Changeout / Upgrade PC $21.36
$115.94 Permit Issuance $115.94
$1.00 Building Standards Administration $1.00
$12.00 Digital Archiving and Records Management Fee - OTC $12.00
$4.72 Credit Card Convenience Fee $4.72
$193.53 $193.53 Total for Invoice INV-00002455
Grand Total for Permit $193.53 $193.53
Workflow / Inspections
Workflow Step / Action Name Action Type Start Date End Date
Review v.1 11/15/2023 0:00
Permit Tech Review v.1 Receive Submittal 11/15/2023 0:00 11/15/2023 15:39
Issue Permit v.1 11/15/2023 15:44 11/16/2023 14:26
Verify Contractor info & Conditions have been met v.1 Generic Action 11/15/2023 15:44
Verify & Invoice Fees v.1 Generic Action 11/16/2023 14:24
Verify Fee Payment & Issue Permit v.1 Generic Action 11/16/2023 14:26
Print, Attach, and Email Building Permit v.1 Create Report 11/16/2023 14:26 11/16/2023 14:26
Inspections v.1
Electrical Underground v.1 Inspection
Rough Electrical v.1 Inspection
Temp Use of Permanent Power v.1 Inspection
Final Inspections v.1
Final Electrical v.1 Inspection
Printed: 11/16/23 10:26 pm Page 3 of 4
Permit Type:
Permit Number:
Property Address:
Electrical
BELC2023-1051
81180 LEGENDS WAY
BUILDING PERMIT
Construction or work for which a permit is required shall be subject to inspection by the building official and such construction or work
shall remain visible and able to be accessed for inspection purposes until approved. Approval as a result of an inspection shall not be
construed to be an approval of a violation of the provisions of the applicable code and other ordinances of the jurisdiction. Inspections
presuming to give authority to violate or cancel the provisions of the applicable code and other ordinances of the jurisdiction shall not be
valid. It shall be the duty of the owner or the owner's authorized agent to cause the work to remain visible and able to be accessed for
inspection purposes. Neither the building official nor the jurisdiction shall be liable for expense entailed in the removal or replacement of
any material required to allow inspection.
It shall be the duty of the holder of the building permit or their duly authorized agent to notify the building official when work is ready for
inspection. It shall be the duty of the permit holder to provide access to and means for inspections of such work that are required by this
code.
Inspections
A building or structure shall not be used or occupied in whole or in part, and a change of occupancy of a building or structure or portion
thereof shall not be made, until the building official has issued a certificate of occupancy therefor as provided herein. Issuance of a
certificate of occupancy shall not be construed as an approval of a violation of the provisions of the applicable code and other ordinances
of the jurisdiction. Certificates presuming to give authority to violate or cancel the provisions of this code or other ordinances of the
jurisdiction shall not be valid.
Certificate of Occupancy
A person shall not make connections from a utility, a source of energy, fuel, or power, or a water system or sewer system to any building
or system that is regulated by the applicable code and other ordinances of the jurisdiction for which a permit is required, until approved by
the building official.
Service Utilities
Printed: 11/16/23 10:26 pm Page 4 of 4
PERMIT SNAPSHOT REPORT BELC2023-1051
FOR CITY OF LA QUINTA
Electrical 11/15/2023App Date:Project:Permit Type
City of La QuintaService Changeout/Upgrade 11/27/2024Exp Date:District:Work Class:
0.00Issued NOT COMPLETEDCompleted:Square Feet:Status:
Description:
Valuation:
400A ELECTRICAL SERVICE CHANGE OUT [200A EXISTING] SURGE PROTECTION DEVICE
REQUIRED PER CEC 230.67, A TYPE 1 OR 2 SPD SHALL BE INSTALLED PRIOR TO RELEASE BEING
SENT TO UTILITY. THIS PERMIT DOES NOT INCLUDE RELOCATION OF EQUIPMENT OR ANY OTHER
WORK. 2022 CALIFORNIA BUILDING CODES.
$20,000.00 Assigned To:Approval
Expire Date:11/16/2023
Parcel:Main762310004 Address:81180 Legends Way
La Quinta, CA 92253
Main Zone:
Applicant
MDESIGN GROUP - mariano
ramirez
75145 St Charles Place #3
Palm Desert, CA 92211
Business: (760) 219-3068
Applicant
MDESIGN GROUP - mariano
ramirez
75145 St Charles Place #3
Palm Desert, CA 92211
Business: (760) 219-3068
Owner
Stephanie McCartney
Home: (760) 219-3068
Contractor
MARGARET A VARGAS
73000 Shadow Mountain Dr
Palm Desert, CA 92260
Business: (818) 669-0713
Permit Custom Fields
Existing Service(AMP)200 NewService(AMP)400 Yes/No No
Zoning RL General Plan LDR City Limits Within La Quinta Limits
Subdivision Name TR 28838-1 AMENDED Lot Number 25 Centerlines 93586
Lot Size 2125.29 Legal Description Lot 25 MB 285/51 TR
28838-1 AMENDED
Attachment File Name Added On Added By Attachment Group Notes
Signature___11/15/2023.jpg 11/15/2023 14:38 ,Uploaded via CSS
SITE PLAN - NOT APPROVED SET.pdf 11/15/2023 15:39 Mendez, Deisy Other Misc Documents
SITE PLAN APPROVED.pdf 11/15/2023 15:41 Mendez, Deisy Available Online APPROVED SITE PLAN
*LQ Building Permit.pdf 11/16/2023 14:26 Service, EnerGov Available Online Building Permit at time of issuance
Inspection
Number Status Inspection Type Actual End DateActual Start DateScheduled End
Date
Scheduled Start
Date
Request
Date
IBLD-007881-202
3
Disapprove
d
Rough Electrical 11/28/2023 11/28/2023 0:00 11/28/2023 0:00 11/28/2023 10:01 11/28/2023 10:05
Inspectors: Hunt, Mark (Primary)
Checklist Item Description Passed Comments
Correction Correction No NOT READY, NEW PANEL IS NOT ON SITE
Correction Correction No A 400A MAIN SERVICE PANEL IS WIDER THAN THE EXISTING PANEL
AND REQUIRES REFRAMING AN EXTERIOR LOAD BEARING SHEAR
WALL, PROVIDE DETAIL FROM THE ENGINEER OF RECORD SHOWING
THE SEISMIC FIX
Created ByNote Date and Time Created
1.Deisy MendezUNABLE TO ROUTE THE FRAMING PLANS SINCE THIS IS AN
ELECTRICAL PERMIT - ADVISED TO SUBMIT THE FRAMING
CHANGES UNDER THE BRES2021-0095 PERMIT FOR REVIEW
AND APPROVAL
01/04/2024 8:57
Invoice No.Amount PaidFeeFee Amount
INV-00002455 $8.00 Technology Enhancement Fee $8.00
$30.51 Service Changeout / Upgrade $30.51
$21.36 Service Changeout / Upgrade PC $21.36
$115.94 Permit Issuance $115.94
$1.00 Building Standards Administration $1.00
Page 1 of 278-495 Calle TampicoJanuary 09, 2024
PERMIT SNAPSHOT REPORT (BELC2023-1051)
$12.00 Digital Archiving and Records Management Fee - OTC $12.00
$4.72 Credit Card Convenience Fee $4.72
$193.53 $193.53 Total for Invoice INV-00002455
Grand Total for Permit $193.53 $193.53
Condition Description Date Created Satisfied
Contractor Information & Business
License
11/15/2023 YesContractor Information & Business License
Owner-Builder Acknowledgment
and Verification
11/15/2023 YesOWNER BUILDER PACKET AND COPY OF DRIVER LICENSE REQUIRED
Comments: Pulled as contractor
Sub-Contractor List 11/15/2023 YesSUB-CONTRACTOR LIST REQUIRED FOR OWNER BUILDERS
Comments: Pulled as contractor
Submittal Name Status Received Date Due Date Complete Date Resubmit Completed
ApprovedPermit Tech Review v.1 11/15/2023 11/16/2023 11/15/2023 No Yes
Completed
Date
Due
Date
Assigned
DateStatusAssigned UserDepartmentItem Review Name
Permit Tech Review (1 Day)HUB Complete 11/15/2023 11/16/2023 11/15/2023
Comments: APPROVED BY JF
Workflow Step / Action Name Action Type Start Date End Date
Review v.1 11/15/2023 0:00
Permit Tech Review v.1 Receive Submittal 11/15/2023 0:00 11/15/2023 15:39
Issue Permit v.1 11/15/2023 15:44 11/16/2023 14:26
Verify Contractor info & Conditions have been met v.1 Generic Action 11/15/2023 15:44
Verify & Invoice Fees v.1 Generic Action 11/16/2023 14:24
Verify Fee Payment & Issue Permit v.1 Generic Action 11/16/2023 14:26
Print, Attach, and Email Building Permit v.1 Create Report 11/16/2023 14:26 11/16/2023 14:26
Inspections v.1 11/27/2023 0:00
Electrical Underground v.1 Inspection
Rough Electrical v.1 Inspection 11/27/2023 0:00 11/28/2023 10:06
Rough Electrical v.2 Inspection 11/28/2023 0:00
Temp Use of Permanent Power v.1 Inspection
Final Inspections v.1
Final Electrical v.1 Inspection
Page 2 of 278-495 Calle TampicoJanuary 09, 2024
METER / MAIN
MAIN
400 AMP
CONDUIT PER
IID /SCE
M
#3 CU
GROUND
TO
UFER
1/0 CU
TO
GAS &
WATER
GENERAL LIGHTING AT 3W/ S.F. 3W / 3,886 S.F.=11,658
SMALL APPLIANCE CIRCUITS AT 1,500W EA.2/ 1,500 =3,000
VENT HOOD AT 750W EA.1/ 750 = 750
LAUNDRY CIRCUIT AT 1,500W EA.1/ 1,500 = 1,500
DISHWASHER AT 1,500W EA.1/ 1,500 = 1,500
DRYER AT 5,400W EA.1/ 5,400 = 5,400
EXISTING POOL EQUIPMENT 1X / 5,760 = 5,760
SUBTOTAL =29,568
1ST 10,000W AT 100%= 10,000
REMAINING AT 40%= 7,828
6.0 TONS REQUIRED AT 2,016W / TON 2,016W/ 10 TONS = 20,016
TOTAL = 37,844
MAIN SERVICE: 37,844W / 240V = 157 AMPS
USE 400AMP MAIN PANEL - CONTRACTOR TO VERY MINIMUM REQUIREMENTS
E1.10
ELECTRICAL LAYOUT IS SCHEMATIC AND CAN BE
RECONFIGURED BY GENERAL CONTRACTOR.
ELECTRICAL NOTES
PANEL DIAGRAM 21/4" = 1'-0"
SCALE
ELECTRICAL CALCULATIONS 31/4" = 1'-0"
SCALE
ELECTRICAL NOTES 11/4" = 1'-0"
SCALE
ALL DRAWING ARE THE PROPERTY OF MDESIGN GROUP
INC., AND ARE ONLY TO BE USED AS AN INSTRUMENT OF
S E R V I C E . T H E S E D R A W I N G S S H A L L N O T B E
R EPRODUCED OR MODIFIED IN ANY WAY WITHOUT THE
W R I T T E N C O N S E N T F R O M M D E S I G N G R O U P I N C .
SUBMISSION OF THESE DRAWINGS TO ANY THIRD PARTY
D OE S N OT R E LE ASE I N AN Y WAY THE COPYR IGHT AN D
OWNERSHIP OF DRAWINGS PROVISIONS LISTED HEREIN.
STATUS
DATE
PROJECT #
1ST SUBMITTAL
11/15/2023
220083
SHEET NAME
DESIGNER
OWNER
STEPHANIE MCCARTNEY
ADDRESS
81180 LEGENDS WAY
LA QUINTA, CA 92253
PROJECT TYPE PANEL UPGRADE
REVISIONS
NO.DESCRIPTION DATE
75145 ST CHARLES PLACE #3
PALM DESERT, CA 92211
T: 760-219-3068
C: 760-219-3068
D R A F T I N G , D E S I G N , A N D P E R M I T S E R V I C E S
M D E S I G N G R O U P , I N C .
M D E S I G N A N D A S S O C I A T E S @ O U T L O O K . C O M
DANIEL GRIFFITH
1. ALL 120-VOLT, SINGLE PHASE, 15- AND 20-AMPERE BRANCH CIRCUITS
(NEW, MODIFIED, REPLACED, OR EXTENDED) SUPPLYING OUTLETS OR
DEVICES INSTALLED IN DWELLING UNIT KITCHENS, FAMILY ROOMS, DINING
ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS
OR SIMILAR ROOMS OR AREAS SHALL BE PROTECTED BY A LISTED
ARC-FAULT CIRCUIT INTERRUPTER, COMBINATION TYPE, INSTALLED TO
PROVIDE PROTECTION OF THE BRANCH CIRCUIT OR BY ANY OF THE
OTHER MEANS DESCRIBED IN 210.12(A)(2) THROUGH (6). (CEC 210.12(A))
2. ALL INTERIOR AND EXTERIOR LIGHT FIXTURES SHALL BE A HIGH
EFFICACY TYPE FIXTURE AND HAVE A CONTROL DEVICE / SYSTEM IN
ACCORDANCE WITH THE 2022 CALIFORNIA BUILDING ENERGY EFFICIENCY
STANDARDS / TITLE 24, SECTION 150.0(K))
3. KITCHEN RECEPTACLES AT KITCHEN COUNTER SHALL BE INSTALLED
ABOVE THE SPLASH OR DIRECTLY IN THE SPLASH IF THE SPLASH EXTENDS
ABOVE 6". GFCI RECEPTACLES SHALL BE INSTALLED EVERY 48" ON
CENTER. COORDINATE ALL LOCATIONS PRIOR TO INSTALLING
ROUGH-IN-BOXES.
4. PROVIDE RECEPTACLE FOR THE MICROWAVE APPLIANCE. PROVIDE
DEDICATED 20AMP CIRCUIT.
5. RECEPTACLES FOR REFRIGERATOR SHALL BE INSTALLED +48" ABOVE
FINISHED FLOOR. PROVIDE A 20AMP DEDICATED CIRCUIT FOR EACH
APPLIANCE.
6. MOUNT SWITCHES AND CONVENIENCE OUTLETS AT KITCHEN,
BATHROOMS, AND LAUNDRY ROOM COUNTERS HORIZONTALLY AT 40"
ABOVE SLAB TO CENTER OF PLATE.
7. ALL FIXED APPLIANCES SHALL BE SECURELY FASTEN IN PLACE.
8. PROVIDE AT LEAST TWO 20-AMPERE SMALL APPLIANCE BRANCH
CIRCUITS TO SERVE KITCHEN, BREAKFAST ROOM, AND DINING ROOM.
SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
9.FOR GARBAGE DISPOSAL AND DISHWASHER, INSTALL A HALF
SWITCHED DUPLEX RECEPTACLE AND INSTALL BELOW SINK. CONNECT
THESWITCHED SIDE OF THE RECEPTACLE TO A MOTOR RATED WALL
SWITCH OR TO THE SINK MOUNTED AIR SWITCH AND PROVIDE A
DEDICATED CIRCUIT FOR EACH APPLIANCE WITH A COMMON TRIP DEVICE.
10.PROVIDE A JUNCTION BOX WITH PROPER SUPPORTS FOR PENDANT
LIGHT FIXTURES.
12.MOUNT CONVENIENCE RECEPTACLES HORIZONTALLY WITH BOTTOM
OF BOX 3' ABOVE SLAB.
13.ALL CONVENIENCE OUTLETS TO BE ON GFI SEPARATE FROM
INTERIOR G.F.I. PROTECTED CIRCUITS.
14.TYPICAL LIGHT SWITCH MOUNTING HEIGHT TO BE 37" ABOVE SLAB
TO CENTER OF PLATE. MOUNT SWITCHES AND CONVENIENCE OUTLETS AT
KITCHEN, BATHROOMS, AND LAUNDRY ROOM COUNTERS HORIZONTALLY
AT 40" ABOVE SLAB TO CENTER OF PLATE.
15.ALL SMOKE DETECTORS & CARBON MONOXIDE ALARMS ARE TO
REMAIN. IF ANY ARE TO BE REPLACED, PROVIDE A INVENSYS "FIREX" 12000
SERIES "FADCM" SMOKE & CARBON MONOXIDE ALARM. DETECTORS SHALL
BE CONNECTED TOGETHER WITH YELLOW WIRE AND ALL CONNECTED TO
A COMMON DEDICATED CIRCUIT. DETECTORS SHALL BE PROVIDED WITH A
BATTER BACKUP AND AUDIBLE ALARM. PROVIDE PROVISIONS TOLOCK-ON
THE SMOKE DETECTOR CIRCUIT BREAKER. INTERCONNECTED SO THAT
THE ACTIVATION OF ONE ALARM SHALL ACTIVATE ALL OTHER ALARMS IN
THE DWELLING UNIT.
16.SINGLE OR MULTIPLE STATION SMOKE ALARM/CARBON MONOXIDE
ALARMS SHALL BE INSTALLED AT ALL OF THE FOLLOWING LOCATIONS: ON
THE CEILING OR WALL OUTSIDE OF EACH SEPARATE SLEEPING AREA, IN
THE IMMEDIATE VICINITY OF BEDROOMS, IN EACH ROOM USED FOR
SLEEPING PURPOSES,IN ENCLOSED COMMON STAIRWELLS OF
APARTMENT COMPLEXES AND OTHER MULTIPLE-DWELLING COMPLEXES.
17.EXHAUST FANS LOCATED IN BATH AND SHOWER AREAS SHALL BE
CONTROLLED BY A HUMIDISTAT. THE HUMIDISTAT SHALL BE ACCESSIBLE.
18.EXHAUST FANS FOR KITCHENS SHALL BE A MINIMUM OF 100 CFM.
19.LUMINARIES (LIGHT FIXTURES), LIGHTING OUTLETS, AND/OR CEILING
FANS LOCATED OVER SPA OR HOT TUB OR WITHIN 5 FEET OF THE INSIDE
WALLS OF THE SPA OR HOT TUB SHALL BE A MINIMUM OF 7'-6" ABOVE THE
MAXIMUM WATER LEVEL AND SHALL BE PROTECTED BY A GROUND-FAULT
CIRCUIT INTERRUPTER. LUMINARIES SHALL BE SUITABLE FOR DAMP.
LOCATIONS PER CEC 2022.
20.RECEPTACLE OUTLET LOCATIONS WILL COMPLY WITH CEC ARTICLE
210.52
A.TAMPER RESISTANT RECEPTACLES FOR ALL LOCATIONS DESCRIBED IN
210.52 (I.E., ALL RECEPTACLES IN A DWELLING.)
B.WEATHER RESISTANT TYPE FOR RECEPTACLES INSTALLED IN DAMP
OR WET LOCATIONS (OUTSIDE)
C.ARC-FAULT PROTECTION FOR ALL OUTLETS (NOT JUST
RECEPTACLES) LOCATED IN ROOMS DESCRIBED IN NEC 210.12(A):
KITCHENS, LAUNDRY AREAS, FAMILY, LIVING, BEDROOMS, DINING, HALLS,
ETC.
D.PROVIDE AT LEAST ONE 20A BRANCH CIRCUIT TO SERVE LAUNDRY
OUTLETS. SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS. CEC210.11(C)
(3)
21.ALL LIGHTING SHALL BE HIGH EFFICACY (FLUORESCENT, LED). LED
LIGHTING SYSTEMS AND GU-24 LAMP HOLDER SHALL BE LISTED BY
ENERGY COMMISSION AND SHALL MEET THE REQUIREMENTS OF TABLE
150-C.
WATTS LUMENS/WATTS
5. AT LEAST ONE WALL RECEPTACLE OUTLET SHALL BE INSTALLED
WITHIN 3 FEET OF THE EDGE AND ADJACENT TO EACH BASIN LOCATION
AND SHALL BE GFCI PROTECTED. THE OUTLET SHALL BOT BE INSTALLED
IN A FACE UP POSITION.
9. ALL FANS EXHAUST 3' FEET AWAY FROM AN EXTERIOR OPENING.
10. ALL LIGHTS OVER SHOWER OR BATHTUB ENCLOSED BY WALLS AND
ENCLOSURES SHALL BE MARKED " SUITABLE FOR WET LOCATIONS". ALL
LIGHTS OVER A BATHTUB WITH NO ENCLOSURE SHALL BE MARKED
"SUITABLE FOR DAMP LOCATIONS". NO RECEPTACLES ARE PERMITTED IN
A BATHTUB OR SHOWER SPACE.
11. NOT USED
12. CARBON MONOXIDE AND SMOKKE ALARMS ARE REQUIRED IN AREAS
LEADING TO BEDROOMS AND ON EACH FLOOR LEVEL.
13. ALL KNOB TUBE WIRING THAT IS EXPOSED WHEN WALLS ARE OPENED
IS TO BE REMOVED BACK TO THE ATTIC OR UNDER FLOOR ACCESSIBLE
SPACES AND SPLICED IN A JUNCTION BOX WITH ROMEX, OR OTHER
APPROVED WIRING METHOD, TO BE RUN BACK TO THE ORIGINAL
LOCATION. KNOB TUBE BOXES MUST BE REPLACED TO ACCOMMODATE
NEW WIRING TYPE. IF REMOVAL OR WIRING WOULD NECESSITATE
OPENING OF ADDITIONAL WALLS NOT IN SCOPE, AND THE WIRING IS IN
SOUND CONDITION, THEN IT MAY REMAIN.
5 OR LESS
>5 TO 15
>15 TO 40
OVER 40
30
45
60
90
1.ALL PERMANENT LIGHTING IN BATHROOMS THAT ARE TO BE
REMODELED SHALL BE HIGH EFFICACY (E.G. FLUORESCENT) OR SHALL BE
CONTROLLED BY A MOTION SENSOR.
2.ALL LIGHT FIXTURES THAT ARE TO BE RECESSED INTO INSULATED
CEILINGS (CAN LIGHTS) SHALL BE INSULATED CONTACTED (I.C.) RATED SO
THAT INSULATION CAN BE PLACED OVER THEM. THE LIGHT FIXTURE
HOUSING SHALL BE AIRTIGHT TO PREVENT CONDITIONED ARE ESCAPING
INTO THE ATTIC OR CEILING CAVITY AND UNCONDITIONED ARE
INFILTRATING FROM THE ATTIC OR CEILING CAVITY INTO THE CONDITIONED
SPACE.
3.OUTLETS FOR OTHER EQUIPMENT WITHIN THE SAME BATHROOM
SHALL BE PERMITTED TO BE SUPPLIED FROM THE 20-AMP BRANCH CIRCUIT
WHEN THE CIRCUIT SUPPLIES A SINGLE BATHROOM.
1.ALL INSTALLED LUMINAIRES SHALL BE HIGH-EFFICACY IN
ACCORDANCE WITH ES TABLE 150.0-A. LIGHT SOURCES
THAT ARE NOT MARKED "JA8-2016-E SHALL NOT BE
INSTALLED IN ENCLOSED LUMINAIRES. ES 150.0(K)
2.IN BATHROOMS, GARAGES, LAUNDRY ROOMS, AND UTILITY
ROOMS AT LEAST ONE LUMINAIRE SHALL BE CONTROLLED
BY A VACANCY SENSOR.
3.DIMMERS OR VACANCY SENSORS SHALL CONTROL ALL LED
STYLE LUMINAIRES. TWO EXCEPTIONS: FIXUTRES
INSTALLED IN HALLWAYS OR (CLOSETS UNDER 70 SF.)
4.RECESSED CAN LIGHT FIXTURES SHALL BE IC LISTED, AIR
TIGHT LABELED, AND NOT BE EQUIPPED WITH A STANDARD
MEDIUM BASE SCREW SHELL LAMP HOLDER. ES 150.0(K)
5.SFD OUTDOOR LIGHT FIXTURES THAT ARE ATTACHED TO A
BUILDING ARE REQUIRED TO BE HIGH EFFICACY, BE
MANUALLY ON/OFF SWITCH CONTROLLED, AND HAVE BOTH
MOTION SENSOR AND PHOTOCELL CONTROL. SEE ES
150.0(K) 3 FOR ADDITIONAL CONTROL OPTIONS.
6.PROVIDE AT LEAST ONE 120V-20A BRANCH CIRCUIT TO
SERVE BATHROOM RECEPTACLES. SUCH CIRCUITS SHALL
HAVE NO OTHER OUTLETS. CEC210.11(C) (3)
7.PROVIDE AT LEAST ONE 20A BRANCH CIRCUIT TO SERVE
LAUNDRY OUTLETS. SUCH CIRCUITS SHALL HAVE NO
OTHER OUTLETS. CEC210.11(C) (3)
14.IF APPLICABLE: FOR A SINGLE-FAMILY DWELLING, THE
SERVICE DISCONNECTING MEANS SHALL HAVE A RATING
OF NOT LESS THAN 200 AMPERES WITH A SERVICE PANEL
BUSS RATING OF A MINIMUM OF 225 AMPERES. THIS
APPLIES TO BOTH NEW SFD’S AND ALL EXISTING SFD’S
THAT ARE REPLACING THEIR ELECTRICAL SERVICES.
16. BATHROOM CIRCUITING SHALL BE EITHER:
a)A 20-AMPERE CIRCUIT DEDICATED TO EACH BATHROOM,
OR
b)AT LEAST ONE 20 AMPERE CIRCUIT SUPPLYING ONLY
BATHROOM RECEPTACLE OUTLETS.
PROJECT DATA
SCOPE OF WORK
REMOVE EXISTING 200 AMP PANEL
ADD NEW 400 AMP PANEL
PROPERTY OWNER:
STEPHANIE MCCARTNEY AND DANIEL GRIFFITH
81180 LEGENDS WAY
LA QUINTA, CA 92253
PROJECT ADDRESS
81180 LEGENDS WAY
LA QUINTA, CA 92253
APN: 762-310-004
LEGAL DESCRIPTION:
LOT 25 MB 285/51 TR 28838
PROJECT AREAS
LOT SIZE: 15,6823 S.F.
EXISTING LIVING AREA: 3,886.00 S.F.
BUILDING DATA:
ZONING: R
OCCUPANCY TYPE: R3/U
CONSTRUCTION TYPE: VB
FIRE SPRINKLERS: NO
YEAR BUILT: 1999
PROJECT IS APPROVED UNDER
CITY OF LA QUINTA
DEPARTMENT OF CODE COMPLIANCE:
ALL CONTRACTORS AND SUBCONTRACTORS SHALL HAVE A CURRENT
BUSINESS LICENCE PRIOR TO PERMIT ISSUANCE PER MUNICIPAL
CODE, TITLE 5. ALL CONTRACTORS AND/OR OWNER-BUILDERS MUST
SUBMIT CERTIFICATE OF WORKER'S COMPENSATION INSURANCE
COVERAGE PRIOR TO THE ISSUANCE OF A BUILDING PERMIT PER
CALIFORNIA LABOR CODE, SECTION 1800. GENERAL CONTRACTORS
AND/OR OWNER-BUILDERS SHALL COMPLETE AND SUBMIT A
CONTRACTOR'S LIST FROM THE DEPARTMENT OF CODE COMPLIANCE
PRIOR TO REQUEST FOR FINAL INSPECTION.
DEPARTMENT OF BUILDING AND SAFETY :
APPROVED TEMPORARY SANITARY FACILITIES ( I.E. CHEMICAL
TOILETS) SHALL BE IN THE CONSTRUCTION SITE PRIOR TO REQUEST
FOR FIRST INSPECTION ). HEALTH AND SAFETY CODE SECTION 5406.
CONTRACTOR AND/OR OWNER SHALL PROVIDE A TRASH BIN TO
INSURE PROPER CLEAN-UP OF ALL BUILDING MATERIALS. STORAGE OF
BUILDING MATERIALS OR DEBRIS SHALL BE CONFINED TO THE LOT FOR
WHICH THE PERMIT IS ISSUED. ADJACENT VACANT PROPERTIES MAY
NOT BE UTILIZED FOR THIS PURPOSE UNLESS WRITTEN PERMISSION
OF THE OWNER IS ON FILE WITH THIS OFFICE. THE PUBLIC RIGHT OF
WAY SHALL BE MAINTAINED IN A CLEAR CONDITION AT ALL TIMES.
2019 CALIFORNIA BUILDING CODE CBC
2019 CALIFORNIA RESIDENTIAL CODE CRC
2019 CALIFORNIA MECHANICAL CODE CMC
2019 CALIFORNIA PLUMBING CODE CPC
2019 CALIFORNIA ELECTRICAL CODE CEC
2019 CALIFORNIA FIRE CODE CFC
2019 CALIFORNIA GREEN BUILDING STANDARDS CODE CALGREEN
2019 CALIFORNIA ENERGY CODE CEC
TITLE 24, PART 2, CALIFORNIA ADMINISTRATIVE CODE HANDICAP
COMPLIANCE REGULATIONS AND ALL OTHER LOCAL CODES,
ORDINANCES AND STATE AMENDMENTS.
11/15/2023Deisy Mendez
400A ELECTRICAL SERVICE
CHANGE OUT [200A
EXISTING] SURGE
PROTECTION DEVICE
REQUIRED PER CEC 230.67,
A TYPE 1 OR 2 SPD SHALL
BE INSTALLED PRIOR TO
RELEASE BEING SENT TO
UTILITY. THIS PERMIT DOES
NOT INCLUDE RELOCATION
OF EQUIPMENT OR ANY
OTHER WORK. 2022
CALIFORNIA BUILDING
CODES.
BELC2023-1051
REMOVE EXISTING 200 AMP PANEL
ELECTRICAL METER AND NEW 400 AMPS MAIN
DISCONNECT AND MAIN PANEL WITH #3 REBAR
UNDERGROUND WITH ACORN CLAMP
CONNECTED TO COLD WATER PIPE
E1.11
ELECTRICAL LAYOUT IS SCHEMATIC AND CAN BE
RECONFIGURED BY GENERAL CONTRACTOR.
ELECTRICAL PLAN 11/4" = 1'-0"
SCALE
ELECTRICAL PLAN
ALL DRAWING ARE THE PROPERTY OF MDESIGN GROUP
INC., AND ARE ONLY TO BE USED AS AN INSTRUMENT OF
S E R V I C E . T H E S E D R A W I N G S S H A L L N O T B E
R EPRODUCED OR MODIFIED IN ANY WAY WITHOUT THE
W R I T T E N C O N S E N T F R O M M D E S I G N G R O U P I N C .
SUBMISSION OF THESE DRAWINGS TO ANY THIRD PARTY
D OE S N OT R EL E ASE I N AN Y WAY THE COPY R IGHT AN D
OWNERSHIP OF DRAWINGS PROVISIONS LISTED HEREIN.
STATUS
DATE
PROJECT #
1ST SUBMITTAL
11/15/2023
220083
SHEET NAME
DESIGNER
OWNER
STEPHANIE MCCARTNEY
ADDRESS
81180 LEGENDS WAY
LA QUINTA, CA 92253
PROJECT TYPE PANEL UPGRADE
REVISIONS
NO.DESCRIPTION DATE
75145 ST CHARLES PLACE #3
PALM DESERT, CA 92211
T: 760-219-3068
C: 760-219-3068
D R A F T I N G , D E S I G N , A N D P E R M I T S E R V I C E S
M D E S I G N G R O U P , I N C .
M D E S I G N A N D A S S O C I A T E S @ O U T L O O K . C O M
DANIEL GRIFFITH