PV1TITLE PAGEVICINITY MAP
PROJECT DESCRIPTION
7.04 KW
ROOF MOUNTED
PHOTOVOLTAIC
ELECTRICAL
SYSTEM
22-SUNERGY 320W
MODULES
1-SUNNY BOY 7.0 US
240V INVERTER
ASPHALT SHINGLE
TILT 15°
SHEET #:
START DATE:
12/17/2020
PRINT DATE:Jun 3,
2021 (5:31 PM)
DWG. SCALE:NOTED
DRAWN BY:
ARMANDO
CARDENAS
RAUL
RESIDENCE
PROJECT INFORMATION:
OWNER:
ADDRESS:
53595 AVENIDA
VALLEJO.
LA QUINTA, CA 92253 CONTRACTOR SIGNATURE XPHOTOVOLTAIC GENERAL NOTES
1. ALL MATERIALS, EQUIPMENT, INSTALLATION AND WORK SHALL
COMPLY WITH THE FOLLOWING APPLICABLE CODES:
2. EXISTING PLUMBING VENTS, SKYLIGHTS, EXHAUST OUTLETS,
VENTILATION INTAKE OR OPENINGS SHALL NOT BE COVERED BY
PHOTOVOLTAIC SYSTEM.
3. ALL EQUIPMENT SHALL BE LISTED AND LABELED BY A
RECOGNIZED ELECTRICAL TESTING LABORATORY AND INSTALLED
PER THE LISTING REQUIREMENTS AND THE MANUFACTURERS
INSTRUCTIONS. (NEC 690.4(D))
4. ALL OUTDOOR EQUIPMENT SHALL BE NEMA3R RATED, INCLUDING
ALL ROOF MOUNTED TRANSITION BOXES AND SWITCHES.
5. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN
ACCORDANCE WITH NEC ARTICLE 250
6. ALL CIRCUITS CONNECTED TO MORE THAN ONE SOURCE SHALL
HAVE OVER CURRENT DEVICES LOCATED SO AS TO PROVIDE OVER
CURRENT PROTECTION FROM ALL SOURCES
[NEC 690.9(A)]
7. ALL PHOTOVOLTAIC (PV) MODULES SHALL BE MOUNTED ON THE
ROOF. ADDITIONAL EQUIPMENT OF THE PV SYSTEM SHALL BE
LOCATED OUTSIDE THE BUILDING NEAR THE MAIN ELECTRICAL
SERVICE [NEC 690.14(C)]
8. THE UTILITY INTERACTIVE INVERTERS SHALL AUTOMATICALLY
DE-ENERGIZE ITS OUTPUT TO THE CONNECTED ELECTRICAL
PRODUCTION AND DISTRIBUTION NETWORK UPON LOSS OF
VOLTAGE IN THE SYSTEM AND SHALL REMAIN IN THAT STATE UNTIL
THE GRID PROVIDER VOLTAGE HAS BEEN RESTORED
[NEC 690.61]
9. DUE TO THE FACT THAT PV MODULES ARE ENERGIZED WHENEVER
EXPOSED TO LIGHT, PV CONTRACTOR SHALL DISABLE THE ARRAY
DURING INSTALLATION AND SERVICE BY SHORT CIRCUITING, OPEN
CIRCUITING OR COVERING THE ARRAY [NEC 690.18]
10. ALL CONDUIT EXPOSED TO WEATHER SHALL BE LISTED AND
IDENTIFIED FOR USE IN DIRECT SUNLIGHT [NEC 690.31(B) 310.10(D)]
11. THE MODULE CONDUCTORS MUST BE TYPE USE-2 ORL LISTED
FOR PHOTOVOLTAIC (PV) WIRE [NEC 690.31(B)]
12. ALL CONDUCTORS SHALL BE MARKED ON EACH END FOR UNIQUE
IDENTIFICATION.
14. ALL THE NEC REQUIRED WARNING SIGNS, MARKINGS AND
LABELS SHALL BE POSTED ON EQUIPMENT AND DISCONNECTS
PRIOR TO ANY INSPECTION TO BE PERFORMED BY THE BUILDING
DEPARTMENT INSPECTOR.
15. PV SYSTEM CONNECTED ON THE LOAD SIDE OF THE SERVICE
DISCONNECTING MEANS OF THE OTHER SOURCE(S) AT ANY
DISTRIBUTION EQUIPMENT ON THE PREMISES SHALL MEET THE
FOLLOWING [NEC 690.64 & 705.12]
A.EACH SOURCE CONNECTION SHALL BE MADE AT A
DEDICATED CIRCUIT BREAKER OR FUSIBLE
DISCONNECTING MEANS [NEC 705.12(D)(1)]
B.THE SUM OF OF THE AMPERE RATING OF THE OVER
CURRENT DEVICES IN CURRENTS SUPPLYING POWER TO
THE BUS BAR OR CONDUCTOR SHALL NOT EXCEED 120%
OF THE RATING OF BUS BAR OR CONDUCTOR [NEC
705.12(D)(2)]
C.THE INTERCONNECTION POINT SHALL BE ON THE LINE
SIDE OF ALL GROUND-FAULT PROTECTION EQUIPMENT
[NEC 705.32]
D.EQUIPMENT CONTAINING OVER CURRENT IN CIRCUITS
SUPPLYING POWER TO A BUS BAR OR CONDUCTOR
SHALL BE MARKED TO INDICATE THE PRESENCE OF ALL
SOURCES. [NEC 705.12 (D)(4)]
E.CIRCUIT BREAKER, IF BACKFEED SHALL BE SUITABLE FOR
SUCH OPERATION [NEC 705.12(D)(5)
F.TO MINIMIZE OVERHEATING OF THE BUS BAR IN THE
PANEL BOARD MAIN CIRCUIT BREAKER AND THE PV
POWER SOURCE CIRCUIT BREAKER SHALL BE
PHYSICALLY LOCATED AT THE OPPOSITE END OF THE BUS
BAR.
16. METALLIC RACEWAYS OR METALLIC ENCLOSURES ARE
REQUIRED METHOD FOR INSIDE A BUILDING FOR PV SYSTEM. [NEC
690.31(E)]
17. FLEXIBLE, FINE STRANDED CABLES SHALL BE TERMINATED ONLY
WITH TERMINALS, LUGS, DEVICES OR CONNECTORS THAT ARE
IDENTIFIED AND LISTED FOR SUCH USE. [690.31(E)]
18. CONNECTORS SHALL BE OF LATCHING OR LOCKING TYPE.
CONNECTORS THAT ARE READILY ACCESSIBLE AND OPERATING
OVER 30 VOLTS SHALL REQUIRE A TOOL TO OPEN AND SHALL BE
MARKED "DO NOT DISCONNECT UNDER LOAD" OR "NOT FOR
CURRENT INTERRUPTING" [NEC 690.33(C) & (E)(2)
19.EQUIPMENT GROUNDING CONDUCTOR FOR PV MODULES
SMALLER THAN #6 AWG SHALL BE PROTECTED FROM PHYSICAL
DAMAGE BY RACEWAY OR CABLE ARMOR, [NEC 690.46 & 250.120(C)]
20. EQUIPMENT GROUNDING CONDUCTOR FOR PV SYSTEMS
WITHOUT GROUND FAULT PROTECTION (GFP) AND INSTALLED ON
NON-DWELLING UNIT MUST HAVE AMPACITY OF AT LEAST 2 TIMES
THE TEMPERATURE AND CONDUIT FILL CORRECTED CIRCUIT
CONDUCTOR AMPACITY. [NEC 690.45(B)]
21. FINE STRANDED CABLES USED FOR BATTERY TERMINALS
DEVICES AND CONNECTIONS REQUIRE LUGS AND TERMINALS
LISTED AND MARKED FOR THAT USE [NEC 690.74]
PROJECT INFORMATION
PROJECT NAME:
PROJECT ADDRESS:
BUILDING DEPARTMENT
JURISDICTION:
PV SYSTEM SIZE
IN KILOWATTS:
UTILITY INTERACTIVE:
CONTRACTOR:
CONTACT NUMBERS:
ADDRESS:
CONTRACTOR LICENSE
NUMBER:
53595 AVENIDA VALLEJO.
LA QUINTA, CA 92253
RAUL RESIDENCE
CITY OF LA QUINTA
7.04 KW
UTILITY INTERACTIVE
GOT SOLAR POWER
(760) 912-2700
30636 SHERWOOD ST
LUCERNE VALLEY, CA 9235
LIC. # 890815
A.P.N.774-122-017
NOTE: ALL CONSTRUCTION SHALL COMPLY WITH
THE 2019 CALIFORNIA BUILDING, RESIDENTIAL,
MECHANICAL, ELECTRICAL, PLUMBING, AND
GREEN BUILDING CODES AND THE LA QUINTA
MUNICIPAL CODE
BSOL2021-0062
7.04kW SOLAR
ARRAY - (22) 320W
SUNERGY SUN
72P-35F PANELS W/
(1) SUNNYBOY
7.0-US INVERTER
[396SF] 2019
CALIFORNIA
BUILDING CODES.
06/04/2021
DRIVEWAY
POOL
RESIDENCEPROPERTY LINEPROPERTY LINE AVENIDA VALLEJOPROPERTY LINE
PROPERTY LINESCALE : 1/16" = 1'-0"
2'-0"0'-0"4'-0"8'-0"16'-0"TILT 15°AZIMUTH 180PV2SITE PLANPROJECT DESCRIPTION
7.04 KW
ROOF MOUNTED
PHOTOVOLTAIC
ELECTRICAL
SYSTEM
22-SUNERGY 320W
MODULES
1-SUNNY BOY 7.0 US
240V INVERTER
ASPHALT SHINGLE
TILT 15°
SHEET #:
START DATE:
12/17/2020
PRINT DATE:Jun 3,
2021 (5:31 PM)
DWG. SCALE:NOTED
DRAWN BY:
ARMANDO
CARDENAS
RAUL
RESIDENCE
PROJECT INFORMATION:
OWNER:
ADDRESS:
53595 AVENIDA
VALLEJO.
LA QUINTA, CA 92253 CONTRACTOR SIGNATURE XEQUIPMENT ELEVATION
NOTES:
1. ALL PV SYSTEM COMPONENTS SHALL BE LISTED BY A
RECOGNIZED TESTING AGENCY ( I.E. UL ETC)
2. ALL WIRING MATERIAL SHALL BE SUITABLE FOR THE SUN
EXPOSURE AND WET LOCATIONS. FIELD APPLIED PROTECTIVE
COATINGS ARE NOT ACCEPTABLE.
3. WHERE THE TERMINAL OF THE DISCONNECTING MEANS MAY BE
ENERGIZED IN THE OPEN POSITION, A WARNING SIGN SHALL BE
MOUNTED ON OR ADJACENT TO THE DISCONNECTING MEANS,. THE
SIGN SHALL BE CLEARLY LEGIBLE AND HAVE THE FOLLOWING
WORDS:ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH THE LINE AND
LOAD SIDES MAY BE ENERGIZED IN
THE OPEN POSITION
4. ALL PV MODULES AND ASSOCIATED EQUIPMENT AND WIRING
MATERIAL SHALL BE PROTECTED FROM PHYSICAL DAMAGE.
5. IN ONE AND TWO FAMILY DWELLINGS, LIVE PARTS IN PV SOURCE
CIRCUITS AND PV OUTPUT CIRCUITS OVER 150 VOLTS TO GROUND
SHALL NOT BE ACCESSIBLE TO OTHER THAN QUALIFIED PERSONS
WHILE ENGERGIZED.
6. ALL FIELD INSTALLED JUNCTION, PULL AND OUTLET BOXES
LOCATED BEHIND MODULES OR PANELS SHALL BE ACCESSIBLE
DIRECTLY OR DISPLACEMENT OF A MODULE(S) OR PANEL(S)
SECURED BY REMOVABLE FASTENERS.
7. REMOVAL OF A DWP-INTERACTIVE INVERTER OR OTHER
EQUIPMENT SHALL NOT DISCONNECT THE BONDING CONNECTION
BETWEEN THE GROUNDING ELECTRODE CONDUCTOR AND THE
PHOTOVOLTAIC SOURCE AND/OR OUTPUT CIRCUIT GROUNDED
CONDUCTOR.
8. THE ROOF MOUNTED PHOTOVOLTAIC MODULES, PANELS OR
SOLAR VOLTAIC ROLL ROOFING MATERIAL SHALL HAVE THE SAME
OR BETTER LISTED FIRE-RESISTANCE RATING THAN THE BUILDING
ROOF COVERING MATERIAL
CONDUIT FROM ARRAY
NORTH
(E) 200A MAIN PANEL
W/200A MCB
(N) 40A BACKFEED
BREAKER
(E) 200A MAIN PANEL
W/200A MCB
(N) 40A BACKFEED
BREAKER
(N) SUNNY BOY 7.0-US
(N) SUNNY BOY 7.0-US
(N) 60 AMP A/C DISCONNECT
(N) 60 AMP A/C DISCONNECT
06/04/2021
SYSTEM SPECIFICATIONS
PV SYSTEM MODULES
NUMBER OF MODULES
MODULES PER STRING
INVERTER MANUFACTURER
INVERTER MODEL
NUMBER OF INVERTERS
ROOF MATERIAL
ROOF SLOPE, RISE/RUN
MOUNTING EQUIPMENT
RACKING SYSTEM
PV SYSTEM WEIGHT, LBS/ SF
AREA OF PV ARRAY
PERCENTAGE OF ROOF
COVERED
SUNERGY 320W
2X11
SUNNY BOY 7.0
SB-7.0-US
1
ASPHALT SHINGLE
15°
UNIRAC
UNIRAC
2.57 LBS/SF
387.2 SF
24.6%
HEIGHT ABOVE ROOF 3"-5"
22
CONDUIT DETAIL (TYP)
3/4" EMT CONDUIT
ROOF LEVEL
SS 3/4 " EMT STRAP
WOOD
1 1
2" MIN.
B
B
A A A A A A A
AAAA
B B B B B B B
B B
4'
1'-4"
J1
JUNCTION
BOX (TYP)
SCALE :
3/32" = 1'-0"
2'-0"0'-0"4'-0"8'-0"16'-0"
PV3PV LAYOUT1. ALL ELECTRICAL SYSTEMS SHALL COMPLY WITH THE LATEST
N.E.C.
2. ALL ROOFING PENETRATIONS SHALL EMBED IN STRUCTURAL
MEMBERS AND PROPER FLASHING SEALANT SHALL BE USED TO
PROVED WATERTIGHT ASSEMBLY.
3. NO PLUMBING OR MECHANICAL VENT SHALL BE COVERED BY
COLLECTORS.
GENERAL NOTES
PROJECT DESCRIPTION
7.04 KW
ROOF MOUNTED
PHOTOVOLTAIC
ELECTRICAL
SYSTEM
22-SUNERGY 320W
MODULES
1-SUNNY BOY 7.0 US
240V INVERTER
ASPHALT SHINGLE
TILT 15°
SHEET #:
START DATE:
12/17/2020
PRINT DATE:Jun 3,
2021 (5:31 PM)
DWG. SCALE:NOTED
DRAWN BY:
ARMANDO
CARDENAS
RAUL
RESIDENCE
PROJECT INFORMATION:
OWNER:
ADDRESS:
53595 AVENIDA
VALLEJO.
LA QUINTA, CA 92253 CONTRACTOR SIGNATURE XTRIBUTARY AREA
PER MOUNT: 10.8 SF
(E) 2"X6" ROOF
STRUCTURE @
16" O.C. (TYP)
MAX SPAN OF
8'-0"
(N) MOUNTS @
48" O.C. (TYP)
06/04/2021
3
4" EMT CONDUIT
2- #8 THWN-2
1- #8 NEUTRAL
1- #6 GROUND
INV
A
JUNCTION
BOX (TYP)
A
Δ2
Δ1
B
2- #10 PV WIRE
1- #6 GROUND Δ0
(E) AC
GROUNDING
ELECTRODE
40A
TO
EXISTING
LOADS
200A
G
(E) UTILITY
METER
#6 BARE COPPER
GROUND (TYP)
EGC
#6 BARE COPPER
GROUND (TYP)
EGC
1 11B
1 A11
(N) SUNNY BOY 7.0-US
(E) 200A MAIN PANEL
W/200A MCB
(N) 40A BACKFEED
BREAKER
3/4" EMT CONDUIT
4- #10 THWN-2
1- #8 GROUND
(N) 60 AMP A/C DISCONNECT
PV4THREE LINEDIAGRAM7.15 KW ROOF MOUNTED PV SYSTEM
WARNING
A PERMANENT WARNING LABEL
SHALL BE APPLIED TO THE
DISTRIBUTION EQUIPMENT WITH
THE FOLLOWING OR EQUIVALENT
MARKING
INVERTER OUTPUT CONNECTION
DO NOT RELOCATE OVERCURRENT
DEVICE
BUSS BAR CALCULATION
200 AMP X 1.2 = 240 AMP
240 AMP - 200 AMP MCB = 40 AMP
ALLOWABLE BACKFEED
PROJECT DESCRIPTION
7.04 KW
ROOF MOUNTED
PHOTOVOLTAIC
ELECTRICAL
SYSTEM
22-SUNERGY 320W
MODULES
1-SUNNY BOY 7.0 US
240V INVERTER
ASPHALT SHINGLE
TILT 15°
SHEET #:
START DATE:
12/17/2020
PRINT DATE:Jun 3,
2021 (5:32 PM)
DWG. SCALE:NOTED
DRAWN BY:
ARMANDO
CARDENAS
RAUL
RESIDENCE
PROJECT INFORMATION:
OWNER:
ADDRESS:
53595 AVENIDA
VALLEJO.
LA QUINTA, CA 92253 CONTRACTOR SIGNATURE XΔ1
Δ2
INVERTER A DATA (provided by manufacturer)
MAKE OF INVERTER
MODEL NUMBER
MAX. DC VOLT RATING
MAX. POWER @ 40 C
NOMINAL AC VOLTAGE
MAX. AC CURRENT
MAX. OCPD
SUNNY BOY
7.0 - US
480V
7750W
211-264V @ 240V
29.2A
INCLUDED
SYSTEM NOTES:
1- SUNNY BOY 7.0-US 240V INVERTER
2 STRINGS OF 11
22 MODULES TOTAL
CALCULATIONS: INVERTER A
MAX SYSTEM VOLTAGE = 240V
MAX CIRCUIT CURRENT = 18A X1.25 = 22.50A
AC OUTPUT: 29.2A X 1.25 =36.50A
MODULE DATA (provided by manufacturer)
MODULE RATINGS AT STC (Standard Test Conditions
MAKE OF MODULE
MODEL NUMBER
MAX. POWER POINT (MPP) CURRENT (IMPP)
MAX. POWER POINT (MPP) VOLTAGE (VMPP)
OPEN CIRCUIT VOLTAGE (VOC)
SHORT CIRCUIT CURRENT (ISC)
MAX. SERIES FUSE (OCPD)
MAX. POWER (PMAX)
MAX. VOLTAGE (TYPICAL LESS THAN 600V DC)
SUNERGY 320W
SUN 72P-35F
8.53A
37.5V
44.6V
9.03A
15A
320W
1000V
06/04/2021
LABEL # 5
A/C
DISCONNECT
INVERTER
JUNCTION
BOX
PV PANEL
ARRAY
LABEL # 6,12
LABEL # 5
LABEL # 5
LABEL # 9, 12 LABEL # 3, 8
LABEL # 1, 4,
7, 8, 10, 13, 14
MAIN
SERVICE
PANEL
NOTE: THIS IS A GENERIC DIAGRAM INTENDED FOR THE LOCATION OF WARNING LABELS. NOT ALL
EQUIPMENT DEPICTED HERE MAY BE A PART OF THIS PROJECT, OR IN THIS ORDER
CAUTION
POWER TO THIS BUILDING IS ALSO
SUPPLIED FROM THE FOLLWING
SOURCES WITH DISCONNECTS
LOCATED AS SHOWN
YOU
ARE
HERE
A/C DISCONNECT
ON GROUND
FLOOR
PV ARRAY
PV5WARNINGLABELSLABELING AND WARNING SIGNS
A. PURPOSE
PROVIDE EMERGENCY RESPONDERS WITH APPROPRIATE WARNING AND
GUIDANCE WITH RESPECT TO ISOLATING THE SOLAR ELECTRIC SYSTEM. THIS
CAN FACILITATE IDENTIFYING ENERGIZED ELECTRICAL LINES THAT CONNECT
THE SOLAR PANELS TO THE INVERTER, AS SHOULD NOT BE CUT WHEN
VENTING FOR SMOKE REMOVAL.
B. MAIN SERVICE DISCONNECT:
1. RESIDENTIAL BUILDINGS- THE MARKING MAY BE PLACED WITHIN THE
MAIN SERVICE DISCONNECT. THE MARKING SHALL BE PLACED ON THE
OUTSIDE COVER IF THE MAIN SERVICE DISCONNECT IS OPERABLE WITH
THE SERVICE PANEL CLOSED.
2. COMMERCIAL BUILDINGS- THE MARKINGS SHALL BE PLACED
ADJACENT TO THE MAIN SERVICE DISCONNECTCLEARLY VISIBLE FROM
THE LOCATION WHERE THE LEVER IS OPERATED
3. MARKINGS, VERBIAGE, FORMAT AND TYPE OF MATERIAL
a. VERBIAGE: CAUTION; SOLAR ELECTRIC SYSTEM CONNECTED
b. FORMAT:
(1) WHITE LETTERING ON A RED BACKGROUND
(2) MINIMUM 3/8 INCH LETTER HEIGHT
(3) ALL LETTERS SHALL BE CAPITALIZED
(4) ARIAL OR SIMILAR FONT, NON-BOLD
c. MATERIAL:
(1) REFLECTIVE, WEATHER RESISTANT MATERIAL SUITABLE
FOR THE ENVIRONMENT (USE UL-969) AS STANDARD FOR
WEATHER RATING): DURABLE ADHESIVE MATERIALS MEET
THIS REQUIREMENT.
C. MARKING REQUIREMENTS ON DC CONDUIT, RACEWAYS, ENCLOSURES,
CABLE ASSEMBLIES, DC COMBINERS AND JUNCTION BOXES;
1. MARKING: PLACEMENT, VERBIAGE, FORMAT AND TYPE OF
MATERIAL.
a. PLACEMENT: MARKINGS SHALL BE PLACED EVERY 10 (TEN)
FEET ON ALL INTERIOR AND EXTERIOR DC CONDUITS, RACEWAYS,
ENCLOSURES AND CABLE ASSEMBLIES, AT TURNS ABOVE AND/OR
BELOW PENETRATIONS, ALL DC COMBINERS AND JUNCTION
BOXES.
b. VERBIAGE: CAUTION SOLAR CIRCUIT
c. THE FORMAT AND TYPE OF MATERIAL SHALL ADHERE TO
SECTION B-3.B & C ABOVE
D. INVERTERS ARE NOT REQUIRED TO HAVE CAUTION MARKINGS
PROJECT DESCRIPTION
7.04 KW
ROOF MOUNTED
PHOTOVOLTAIC
ELECTRICAL
SYSTEM
22-SUNERGY 320W
MODULES
1-SUNNY BOY 7.0 US
240V INVERTER
ASPHALT SHINGLE
TILT 15°
SHEET #:
START DATE:
12/17/2020
PRINT DATE:Jun 3,
2021 (5:32 PM)
DWG. SCALE:NOTED
DRAWN BY:
ARMANDO
CARDENAS
RAUL
RESIDENCE
PROJECT INFORMATION:
OWNER:
ADDRESS:
53595 AVENIDA
VALLEJO.
LA QUINTA, CA 92253 CONTRACTOR SIGNATURE XWARNING
ELECTRIC SHOCK HAZARD
IF GROUND FAULT IS INDICATED NORMALLY GROUNDED
CONDUCTORS MAY BE UNGROUNDED AND ENERGIZED
PHOTOVOLTAIC
"A/C" DISCONNECT
TO BE LOCATED ON EXTERNAL A/C
DISCONNECT
A/C DISCONNECT TO BE
PERMANENTLY MARKED AS FOLLOWS
PHOTOVOLTAIC
"D/C" DISCONNECT
TO BE LOCATED ON EXTERNAL D/C
DISCONNECT
D/C DISCONNECT TO BE
PERMANENTLY MARKED AS FOLLOWS
WARNING
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS ON BOTH THE
LINE AND LOAD SIDES MAY BE ENERGIZED IN
THE OPEN POSITION
Caution
SOLAR ELECTRIC
SYSTEM
CONNECTED
TO BE APPLIED TO THE INSIDE OR
THE OUTSIDE OF THE MAIN
ELECTRICAL PANEL
Caution
PHOTOVOLTAIC
SYSTEM CIRCUIT
BREAKER IS
BACKFED
TO BE PLACED AT DEDICATED CIRCUIT
BREAKER (NEC 690.64(B)(4)(7))
WARNING
DUAL POWER SUPPLY
PHOTOVOLTAIC SYSTEM
TO BE LOCATED ON EXTERIOR OF MAIN
ELECTRICAL PANEL
CAUTION: SOLAR P.V. CIRCUIT
TO BE APPLIED TO ALL INTERIOR AND/OR EXTERIOR CONDUIT
AND RACEWAYS EVERY 10 (TEN) FEET, AT TURNS AND ABOVE
AND OR/BELOW ALL PENETRATIONS
ELECTRIC SERVICE PANEL TO BE PERMANENTLY
MARKED AS FOLLOWS
SYSTEM CHARACTERISTICS
SYSTEM SIZE:
SYSTEM OPEN CIRCUIT VOLTAGE:
SYSTEM OPERATING VOLTAGE:
SYSTEM OPERATING CURRENT:
SYSTEM SHORT CIRCUIT CURRENT:
KW
V DC
V DC
AMPS
AMPS
A/C SYSTEM CHARACTERISTICS
SYSTEM VOLTAGE:
MAXIMUM CURRENT:
VOLTS
AMPS
WARNING
INVERTER OUTPUT CONNECTION
DO NOT RELOCATE OVERCURRENT
DEVICE
AS PERMANENT WARNING LABEL SHALL BE
APPLIED TO THE DISTRIBUTION
EQUIPMENT 2008 NEC 690.64(B)(7)
TO BE LOCATED AT POINT OF INTERCONNECTION
TO PLACED INSIDE DC DISCONNECT (NEC 690.53)
#1
#2
#3
#4
#5
#6
#7
#8
#9
#10
#11
WARNING
ELECTRIC SHOCK HAZARD. THE
DC CONDUCTORS OF THIS
PHOTOVOLTAIC SYSTEM ARE
UNGROUNDED AND MAY BE
ENERGIZED
#12
TO BE LOCATED AT MAIN SERVICE PANEL
#13
#14
480
7.15
380
9.33
15.0
240
26.25
ORANGE/BLACK
RED/WHITE
YELLOW/WHITE
RED/WHITE
ORANGE/BLACK
RED/BLACK
RED/BLACK
ORANGE/BLACK
ORANGE/BLACK
BLACK/WHITE
YELLOW/BLACK
ORANGE/BLACK
06/04/2021
9;46,
===
==
Ministry of Industry and Information entrusted the CTC tested
the solar module samples randomly detected in Hainan basePOLY CRYSTALLINE MODULE
IEC61215 / IEC61730 / IEC61701 /
IEC62716 /IEC62804
INMETRO
Anti-PID
System voltage durability
PPP 58042
Additional
Environmental
Tests
Salt Mist Corrosion
IEC 61701
Ammonia Corrosion
IEC 62716
12 Years Manufacturing Warranty
12 Years 90% Power Output
25 Years 80% Power Output
100%5
0
12
18
25
97.5%
90%
80%
Year
'JJKJ<GR[
K
,
X
U
S
=
G
X
X
G
T
Z
_
QUALIFICATIONS AND CERTIFICATES
Strong mechanical load capacity
Color classification
Super strong frame
Current division
IP68 junction box and connector have a high degree of waterproof,
effectively resist the harsh environment;
The junction box carries a current of 15A, ensuring high current flow
through the modules;
Glue-spilled tank has a double-layer waterproof, cross-section with
hook-shaped aluminum frame, enhanced by 10% of the mechanical load
strength;
The module refines the current division, thus effectively reducing the loss
Of up to 2% due to mismatch and increasing the power output of the
system;
Excellent salt spray resistance, anti-ammonia and anti PID, TUV, SUD
certification approved;
Passed the 2400pa wind load and 5400pa snow load test, ensuring that
the module has a stable mechanical life;
Modules are packaged according to color classification, to achieve
consistent appearance after installation;
SUNERGY USA WORKS LLC
www.sunergyworks.com
MECHANICAL DRAWINGS
ELECTRICAL CHARACTERISTICS
Maximum Power At STC(Pmax)
Short Circuit Current(Isc)
Open Circuit Voltage(Voc)
Maximum Power Current(Impp)
Maximum Power Voltage(Vmpp)
Module Efficiency
Power Tolerance
TEMPERATURE CHARACTERISTICS
I-V CURVES
Norminal Operating Cell Temperature(Noct)
Temperature Coefficient Of Pmax
Temperature Coefficient Of Voc
Temperature Coefficient Of Lsc
ȭrȭ
ȭ
ȭ
ȭ
PACKING CONFIGURATION
Container
Pieces Per Pallet
Pallets Per Container
Pieces Per Container
ȑ-6
ȑ-6ȑ.7
SYSTEM INTEGRATION PARAMETERS
Maximum System Voltage
Maximum Series Fuse
Increased Snowload Acc.to Iec 61215
Operating Temperature
Number Of Bypass Diodes
VDC 1000V
15A
5400Pa
-40d+85ȭ
3
STC: 1000W/m2 irradiance, 25°C cell temperature, AM1.5.
=
'
<
'
<
d
=
'
<
'
<
d
MECHANICAL SPECIFICATION
Cell Type
Number Of Cells
Dimensions(AxBxC)
Weights
Front Glass
Frame
Junction Box
Connector
Output Cables
Poly Crystalline 156.75x156.75mm
72č6x12Ď
1950x990x35mm
22.5kg
3.2mm Tempered Low Iron Glass
Clear Anodized Aluminum Alloy
Ip68,with Bypass Diodes
Mc4 Compatible
Tuv,±length 900mm,4.0mm²
=
'
<
'
<
d
NOCT
Maximum Power At STC(Pmax)
Short Circuit Current(Isc)
Open Circuit Voltage(Voc)
Maximum Power Current(Impp)
Maximum Power Voltage(Vmpp)
NOCT: Irradiance at 800W/m² , Ambient Temperature 20°C , wind speed 1m/s .
MOUNTING HOLES
,
䌙
,,
GROUNDING HOLES
SIDE VIEWff
FRONT VIEW
ޜਨᶑ⸱䌙
ff,
,,
f
BACK VIEW
I-V Gurves at SUN325-72P at different Irradiances
Cell Temp25ȭ
CurrentͧAͨVoltage(V)
Power voltage current curve at different temperature
Normalizedlsc,Voc,Pmaxč%Ď)KRR:KSVKXGZ[XKȭ
=
'
<
'
<
d
=
'
<
'
<
d
SUNNY BOY 3.0-US / 3.8-US / 5.0-US / 6.0-US / 7.0-US / 7.7-US
Power with a purpose
The residential PV market is changing rapidly. Your bottom line matters more than ever—so we’ve designed a superior
residential solution to help you decrease costs at every stage of your business operations. The Sunny Boy 3.0-US/3.8-
US/5.0-US/6.0-US/7.0-US/7.7-US join the SMA lineup of field-proven solar technology backed by the world’s #1
service team. This improved residential solution features ShadeFix, SMA’s proprietary technology that optimizes system
performance. ShadeFix also provides superior power production with a reduced component count versus competitors,
which provides maximum reliability. No other optimized solution generates more power or is as easy as systems featuring
SMA ShadeFix and SunSpec certified devices. Finally, SMA Smart Connected will automatically detect errors and initiate
the repair and replacement process so that installers can reduce service calls and save time and money.
Value-Added Improvements
• SunSpec certified technology
for cost-effective module-level
shutdown
• Advanced AFCI compliant to UL
1699B for arc fault protection
Optimized Power Production
• ShadeFix, SMA’s proprietary shade
management solution, produces
more power than alternatives
• Reduced component count provides
maximum system reliability
Trouble-Free Service
• SMA Service Mobile App
provides simplified, expedited
field service
• Equipped with SMA Smart
Connected, a proactive service
solution that is integrated into
Sunny Portal
Reduced Labor
• New Installation Assistant with
direct access via smartphone
minimizes time in the field
• Advanced communication
interface with fewer components
creates 50% faster setup and
commissioning
SUNNY BOY 3.0-US / 3.8-US / 5.0-US / 6.0-US / 7.0-US / 7.7-US
SB3.0-1SP-US-41 / SB3.8-1SP-US-41 / SB5.0-1SP-US-41 / SB6.0-1SP-US-41SB7.0-1SP-US-41 / SB7.7-1SP-US-41 / SB3.0-1TP-US-41 / SB3.8-1TP-US-41SB5.0-1TP-US-41 / SB6.0-1TP-US-41 / SB7.0-1TP-US-41 / SB7.7-1TP-US-41www.SMA-America.com
*** Listed warranty terms are applicable in SMA-designated primary support
countries, including the U.S., Canada, and Mexico. Reduced terms or restrictions may
apply in other Americas regions and territories including the Pacific and Caribbean.
Accessories
External WLAN antennaEXTANT-US-40 SunSpec CertifiedRapid ShutdownReceivers
Cellular Modem KitCELLMODKIT-US-10Revenue Grade Meter KitRGM05KIT-US-10
Technical data Sunny Boy 3.0-US Sunny Boy 3.8-US Sunny Boy 5.0-US
208 V 240 V 208 V 240 V 208 V 240 V
Input (DC)
Max. PV power 4800 Wp 6144 Wp 8000 Wp
Max. DC voltage 600 V
Rated MPP voltage range 155 - 480 V 195 - 480 V 220 – 480 V
MPPT operating voltage range 100 – 550 V
Min. DC voltage / start voltage 100 V / 125 V
Max. operating input current per MPPT 10 A
Max. short circuit current per MPPT 18 A
Number of MPPT tracker / string per MPPT tracker 2/1 3 / 1
Output (AC)
AC nominal power 3000 W 3000 W 3330 W 3840 W 5000 W 5000 W
Max. AC apparent power 3000 VA 3000 VA 3330 VA 3840 VA 5000 VA 5000 VA
Nominal voltage / adjustable 208 V / ●240 V / ●208 V / ●240 V / ●208 V / ●240 V / ●
AC voltage range 183 – 229 V 211 – 264 V 183 – 229 V 211 – 264 V 183 – 229 V 211 – 264 V
AC grid frequency 60 Hz / 50 Hz
Max. output current 14.5 A 12.5 A 16.0 A 16.0 A 24.0 A 21.0 A
Power factor (cos ϕ) / harmonics 1 / < 4 %
Output phases / line connections 1 / 2
Efficiency
Max. efficiency 97.2 %97.6 %97.3 %97.6 %97.3 %97.6 %
CEC efficiency 96.0 %96.5 %96.5 %96.5 %96.5 %97.0 %
Protection devices
DC disconnect device / DC reverse polarity protection ● / ●
Ground fault monitoring / Grid monitoring ●
AC short circuit protection ●
All-pole sensitive residual current monitoring unit (RCMU)●
Arc fault circuit interrupter (AFCI)●
Protection class / overvoltage category I / IV
General data
Dimensions (W / H / D) in mm (in)535 x 730 x 198 (21.1 x 28.5 x 7.8)
Packaging dimensions (W / H / D) in mm (in)600 x 800 x 300 (23.6 x 31.5 x 11.8)
Weight / packaging weight 26 kg (57 lb) / 30 kg (66 lb)
Temperature range: operating / non-operating –25°C …+60°C / –40°C …+60°C
Environmental protection rating NEMA 3R
Noise emission (typical)39 dB(A)
Internal power consumption at night < 5 W
Topology / cooling concept transformerless / convection
Features
Ethernet ports 2
Secure Power Supply ●*
Display (2 x 16 characters)●
2.4 GHz WLAN / External WLAN antenna ●/○
ShadeFix technology for string level optimization ●
Cellular (4G / 3G) / Revenue Grade Meter ○/○**
Warranty: 10 / 15 / 20 years ***●/○/○
Certificates and approvals UL 1741, UL 1741 SA incl. CA Rule 21 RSD, UL 1998, UL 1699B Ed. 1, IEEE1547, FCC Part 15 (Class A & B),
CAN/CSA V22.2 107.1-1, HECO Rule 14H, PV Rapid Shutdown System Equipment
● Standard features ○ Optional features — Not available
NOTE: US inverters ship with gray lids. Data at nominal conditions * Not compatible with SunSpec shutdown devices **Standard in SBX.X-1TP-US-41
Type designation SB3.0-1SP-US-41 / SB3.0-1TP-US-41 SB3.8-1SP-US-41 / SB3.8-1TP-US-41 SB5.0-1SP-US-41 / SB5.0-1TP-US-41
POWER+ SOLUTION
The SMA Power+ Solution combines legendary SMA inverter
performance and SunSpec certified shutdown devices in one
cost-effective, comprehensive package. In addition, SMA
ShadeFix technology optimizes power production and provides
greater reliability than alternatives.
This rapid shutdown solution fulfills UL 1741, NEC 2014, and
NEC 2017 requirements and is certified to the power line-based
SunSpec Rapid Shutdown communication signal over DC wires,
making it the most simple and cost-effective rapid shutdown
solution on the market.
Visit www.SMA-America.com for more information.
Technical data Sunny Boy 6.0-US Sunny Boy 7.0-US Sunny Boy 7.7-US
208 V 240 V 208 V 240 V 208 V 240 V
Input (DC)
Max. PV power 9600 Wp 11200 Wp 12320 Wp
Max. DC Voltage 600 V
Rated MPP Voltage range 220 – 480 V 245 - 480 V 270 - 480 V
MPPT operating voltage range 100 – 550 V
Min. DC voltage / start voltage 100 V / 125 V
Max. operating input current per MPPT 10 A
Max. short circuit current per MPPT 18 A
Number of MPPT tracker / string per MPPT tracker 3 / 1
Output (AC)
AC nominal power 5200 W 6000 W 6660 W 7000 W 6660 W 7680 W
Max. AC apparent power 5200 VA 6000 VA 6660 VA 7000 VA 6660 VA 7680 VA
Nominal voltage / adjustable 208 V / ●240 V / ●208 V / ●240 V / ●208 V / ●240 V / ●
AC voltage range 183 – 229 V 211 – 264 V 183 – 229 V 211 – 264 V 183 – 229 V 211 – 264 V
AC grid frequency 60 Hz / 50 Hz
Max. output current 25.0 A 25.0 A 32.0 A 29.2 A 32.0 A 32.0 A
Power factor (cos ϕ) / harmonics 1 / < 4 %
Output phases / line connections 1 / 2
Efficiency
Max. efficiency 97.3 %97.7 %97.3 %97.9 %97.3 %97.5 %
CEC efficiency 96.5 %97.0 %96.5 %97.0 %96.5 %97.0 %
Protection devices
DC disconnect device / DC reverse polarity protection ● / ●
Ground fault monitoring / Grid monitoring ●
AC short circuit protection ●
All-pole sensitive residual current monitoring unit (RCMU)●
Arc fault circuit interrupter (AFCI)●
Protection class / overvoltage category I / IV
General data
Dimensions (W / H / D) in mm (in)535 x 730 x 198 (21.1 x 28.5 x 7.8)
Packaging Dimensions (W / H / D) in mm (in)600 x 800 x 300 (23.6 x 31.5 x 11.8)
Weight / packaging weight 26 kg (57 lb) / 30 kg (66 lb)
Temperature range: operating / non-operating –25°C …+60°C / –40°C …+60°C
Environmental protection rating NEMA 3R
Noise emission (typical)39 dB(A)45 dB(A)
Internal power consumption at night < 5 W
Topology / cooling concept transformerless / convection transformerless / fan
Features
Ethernet ports 2
Secure Power Supply ●*
Display (2 x 16 characters)●
2.4 GHz WLAN / External WLAN antenna ●/○
ShadeFix technology for string level optimization ●
Cellular (4G / 3G) / Revenue Grade Meter ○/○**
Warranty: 10 / 15 / 20 years ***●/○/○
Certificates and approvals UL 1741, UL 1741 SA incl. CA Rule 21 RSD, UL 1998, UL 1699B Ed. 1, IEEE1547, FCC Part 15 (Class A & B),
CAN/CSA V22.2 107.1-1, HECO Rule 14H, PV Rapid Shutdown System Equipment
● Standard features ○ Optional features — Not available
NOTE: US inverters ship with gray lids. Data at nominal conditions * Not compatible with SunSpec shutdown devices **Standard in SBX.X-1TP-US-41
Type designation SB6.0-1SP-US-41 / SB6.0-1TP-US-41 SB7.0-1SP-US-41 / SB7.0-1TP-US-41 SB7.7-1SP-US-41 / SB7.7-1TP-US-41
Speed the completion of customer proposals and maximize the efficiency of your design
team with the Sunny Boy-US series, which provides a new level of flexibility in system
design by offering:
» Hundreds of stringing configurations and multiple independent MPPTs
» SMA’s proprietary ShadeFix technology optimizes power production
» Diverse application options including on- and off-grid compatibility
SBxx-US-DS-en-38 SMA and Sunny Boy are registered trademarks of SMA Solar Technology AG. Printed on FSC-certified paper. All products and services described as well as technical data are subject to change, even for reasons of country-specific deviations, at any time without notice. SMA assumes no liability for errors or omissions. For current information, see www.SMA-Solar.com.SMA wants to enable your sales team by arming them with an abundance of feature/
benefit support. Show your customers the value of the Sunny Boy-US series by utilizing:
» The opportunity to join the SMA PowerUP network of installers who receive in-depth
training, enhanced service, and prioritized marketing support
» SMA’s 35 year history and status as the #1 global inverter manufacturer instills homeowners
with peace of mind and the long-term security they demand from a PV investment
» The most economical solution for shade mitigation with superior power production
Ensure that your back office business operations run smoothly and succinctly while
mitigating potential errors. The Sunny Boy-US series can help achieve cost savings in
these areas by providing:
» An integrated DC disconnect that simplifies equipment stocking and allows for a single
inverter part number
» All communications integrated into the inverter, eliminating the need to order
additional equipment
Expedite your operations in the field by taking advantage of the new Sunny Boy’s
installer-friendly feature set including:
» Direct access via smartphone and utilization of SMA’s Installation Assistant, which
minimizes time/labor spent in the field and speeds the path to commissioning
» Simple commissioning and monitoring setup in a single online portal
» The fastest, easiest installation thanks to SMA ShadeFix and SunSpec certified
shutdown devices
SMA understands the factors that contribute to lifetime PV ownership cost, that’s why
the Sunny Boy-US series was designed for maximum reliability and backstopped by an
unmatched service offering. Benefit from:
» SMA Smart Connected, a proactive service solution integrated into Sunny Portal that
automatically detects errors and initiates the repair and replacement process
» The SMA Service Mobile App, which provides simplified, expedited field service
SIMPLE, FLEXIBLE DESIGN
VALUE-DRIVEN SALES ENABLEMENT
IMPROVED STOCKING AND ORDERING
STREAMLINED INSTALLATION AND COMMISSIONING
SUPERIOR SERVICE
LEGAL NOTICE
DRAWING NOT TO SCALE
ALL DIMENSIONS ARE
NOMINAL
PRODUCT PROTECTED BY
ONE OR MORE US PATENTS
SOLARMOUNT
PART & ASSEMBLY
10/26/2017
PRO SERIES
BONDING CLAMPS
REVISION DATE:
DRAWING TYPE:
DESCRIPTION:SM-A01PRODUCT LINE:
1411 BROADWAY BLVD. NE
ALBUQUERQUE, NM 87102 USA
PHONE: 505.242.6411
WWW.UNIRAC.COM SHEET
END CLAMP
MID CLAMP
11 2 "11 16 "
PRO SERIES END CLAMP PRO SERIES MID CLAMP
END CAP
INCLUDED WITH END CLAMP
11 16 "
17 16 "
1"
30mm to 51mm
MODULE FRAME
PART # TABLE
P/N DESCRIPTION
302035M ENDCLAMP PRO
302030M MIDCLAMP PRO - MILL
302030D MIDCLAMP PRO - DRK
LEGAL NOTICE
DRAWING NOT TO SCALE
ALL DIMENSIONS ARE
NOMINAL
PRODUCT PROTECTED BY
ONE OR MORE US PATENTS
SOLARMOUNT
PART & ASSEMBLY
10/26/2017
BONDING TOP
CLAMPS
REVISION DATE:
DRAWING TYPE:
DESCRIPTION:SM-A01APRODUCT LINE:
1411 BROADWAY BLVD. NE
ALBUQUERQUE, NM 87102 USA
PHONE: 505.242.6411
WWW.UNIRAC.COM SHEET
PART # TABLE
P/N DESCRIPTION
302027C SM BND MIDCLAMP BC SS
302027D SM BND MIDCLAMP BC DRK SS
302028C SM BND MIDCLAMP EF SS
302028D SM BND MIDCLAMP EF DRK SS
302029C SM BND MIDCLAMP DK SS
302029D SM BND MIDCLAMP DK DRK SS
FOR BONDING END CLAMP
REFER TO SHEET SM-P05
MID CLAMP
END CLAMP
BONDING SM MID CLAMP BONDING SM END CLAMP
17 8 "
15 16"
1 4 "
11 2 "
13 16 "
1 8 "
VARIES - REFER TO
SHEET SM-P05
P1 4 "
P5 16 "
DETAIL B
MID CLAMP TRIM CONNECTIONTRIM
DETAIL A
TRIM END CLIP
A
B
LEGAL NOTICE
DRAWING NOT TO SCALE
ALL DIMENSIONS ARE
NOMINAL
PRODUCT PROTECTED BY
ONE OR MORE US PATENTS
SOLARMOUNT
PART & ASSEMBLY
9/27/2017
SM TRIM END CLIP
REVISION DATE:
DRAWING TYPE:
DESCRIPTION:SM-A02PRODUCT LINE:
1411 BROADWAY BLVD. NE
ALBUQUERQUE, NM 87102 USA
PHONE: 505.242.6411
WWW.UNIRAC.COM SHEET
1 15 16 "
3 1 16 "
PART # TABLE
P/N DESCRIPTION LENGTH
206072D-B SM TRIM DRK 168"
008025S SM TRIM END CLIP
-
TRIM
MODULE FRAME
END CLIP
LEGAL NOTICE
DRAWING NOT TO SCALE
ALL DIMENSIONS ARE
NOMINAL
PRODUCT PROTECTED BY
ONE OR MORE US PATENTS
SOLARMOUNT
KIT DETAIL
9/24/2018
FLASHKIT PRO
REVISION DATE:
DRAWING TYPE:
DESCRIPTION:SM-A03PRODUCT LINE:
1411 BROADWAY BLVD. NE
ALBUQUERQUE, NM 87102 USA
PHONE: 505.242.6411
WWW.UNIRAC.COM SHEET
NOTES:
1. INSTALLATION TO BE COMPLETED IN ACCORDANCE WITH MANUFACTURER'S WRITTEN SPECIFICATIONS
AND INSTALLATION INSTRUCTIONS.
2. PACKAGING: KITS OF 10
PART # TABLE
P/N DESCRIPTION
004055M FLASHKIT PRO MILL
004055D FLASHKIT PRO DRK
8 1 16 "
2"
1 7 8 "
12"
3 8 "1 1 4 "
2 7 8 "
3 8 " HEX FLANGE NUT
3 8 "-16 X 1" SS SERRATED T-BOLT
LEGAL NOTICE
DRAWING NOT TO SCALE
ALL DIMENSIONS ARE
NOMINAL
PRODUCT PROTECTED BY
ONE OR MORE US PATENTS
SOLARMOUNT
PART & ASSEMBLY
11/19/2018
L-FOOT
REVISION DATE:
DRAWING TYPE:
DESCRIPTION:SM-A11PRODUCT LINE:
1411 BROADWAY BLVD. NE
ALBUQUERQUE, NM 87102 USA
PHONE: 505.242.6411
WWW.UNIRAC.COM SHEET
SOLARMOUNT LIGHT
ON L-FOOT
SOLARMOUNT STANDARD
ON L-FOOT
SOLARMOUNT HD
ON L-FOOT
MAXIMUM
HEIGHT
MAXIMUM
HEIGHT
MAXIMUM
HEIGHT
MINIMUM
HEIGHT
MINIMUM
HEIGHT
4 15 16 "
4 9 16 "
311 16 "
3 5 8 "4"
L-FOOT
3 8 "-16 X 3 4 " T BOLT
3 8 "-16
FLANGE NUT
2"
P3 8 "
213 16 "
17 8 "
5 16 "
213 16 "MINIMUM
HEIGHT
LEGAL NOTICE
DRAWING NOT TO SCALE
ALL DIMENSIONS ARE
NOMINAL
PRODUCT PROTECTED BY
ONE OR MORE US PATENTS
SOLARMOUNT
PART & ASSEMBLY
9/27/2017
L-FOOT
REVISION DATE:
DRAWING TYPE:
DESCRIPTION:SM-A04PRODUCT LINE:
1411 BROADWAY BLVD. NE
ALBUQUERQUE, NM 87102 USA
PHONE: 505.242.6411
WWW.UNIRAC.COM SHEET
SOLARMOUNT LIGHT
ON L-FOOT
L-FOOT
2"2"
3"
1 4 "Ø3 8 "
3 8 "-16 X 3 4 " T BOLT
3 8 "-16
FLANGE NUT
PART # TABLE
P/N DESCRIPTION
304001C L-FOOT SERR W/T-BOLT CLR
304001D L-FOOT SERR W/T-BOLT DRK
NOTES:
1. L-FOOT CAN BE INSTALLED IN TWO ORIENTATIONS, PLEASE REFER TO INSTRUCTIONS IN THE QUICK START GUIDE.
2 7 16 "MINIMUM
HEIGHT
3 11 16 "MAXIMUM
HEIGHT
SOLARMOUNT STANDARD
ON L-FOOT
SOLARMOUNT HD
ON L-FOOT
4 1 2 "
4 7 8 "
3 11 16 "3 5 16 "
MAXIMUM
HEIGHT
MAXIMUM
HEIGHT
MINIMUM
HEIGHT
MINIMUM
HEIGHT
LEGAL NOTICE
DRAWING NOT TO SCALE
ALL DIMENSIONS ARE
NOMINAL
PRODUCT PROTECTED BY
ONE OR MORE US PATENTS
SOLARMOUNT
PART & ASSEMBLY
9/27/2017
BONDING SPLICE
BAR
REVISION DATE:
DRAWING TYPE:
DESCRIPTION:SM-A05PRODUCT LINE:
1411 BROADWAY BLVD. NE
ALBUQUERQUE, NM 87102 USA
PHONE: 505.242.6411
WWW.UNIRAC.COM SHEET
BONDING SPLICE BAR
4"
1 1 2 "
15 16 "
TYPICAL SPLICE BAR DETAIL
TYPICAL EXPANSION JOINT DETAIL
1 2 "
#12 X 3 4 " SELF DRILLING SS SCREWS INCLUDED
NOTE THAT ONLY 2 SCREWS ARE
USED AT AN EXPANSION JOINT.
THE SPLICE BAR DOES NOT BOND
ACROSS AN EXPANSION JOINT.
SEE INSTALLATION GUIDE FOR
INSTRUCTION.
PART # TABLE
P/N DESCRIPTION
303018C BND SPLICE BAR SERRATED CLR
303018D BND SPLICE BAR SERRATED DRK
DETAIL A
FRONT L-FOOT HINGE DETAIL B
REAR TILT LEG
A
B
LEGAL NOTICE
DRAWING NOT TO SCALE
ALL DIMENSIONS ARE
NOMINAL
PRODUCT PROTECTED BY
ONE OR MORE US PATENTS
SOLARMOUNT TILT
ASSEMBLY
9/27/2017
LOW PROFILE TILT
REVISION DATE:
DRAWING TYPE:
DESCRIPTION:SM-A07PRODUCT LINE:
1411 BROADWAY BLVD. NE
ALBUQUERQUE, NM 87102 USA
PHONE: 505.242.6411
WWW.UNIRAC.COM SHEET
NOTES:
1. SEE SM TiH INSTALLATION GUIDE FOR ASSEMBLY INSTRUCTIONS.
DETAIL A
L FOOT
DETAIL B
REAR TILT LEG
A
B
LEGAL NOTICE
DRAWING NOT TO SCALE
ALL DIMENSIONS ARE
NOMINAL
PRODUCT PROTECTED BY
ONE OR MORE US PATENTS
SOLARMOUNT TILT
ASSEMBLY
9/27/2017
HIGH PROFILE TILT
REVISION DATE:
DRAWING TYPE:
DESCRIPTION:SM-A08PRODUCT LINE:
1411 BROADWAY BLVD. NE
ALBUQUERQUE, NM 87102 USA
PHONE: 505.242.6411
WWW.UNIRAC.COM SHEET
NOTES:
1. SEE SM TiH INSTALLATION GUIDE FOR ASSEMBLY INSTRUCTIONS.
LEGAL NOTICE
DRAWING NOT TO SCALE
ALL DIMENSIONS ARE
NOMINAL
PRODUCT PROTECTED BY
ONE OR MORE US PATENTS
SOLARMOUNT TILT
ASSEMBLY
9/27/2017
ADJUSTABLE TILT
LEG
REVISION DATE:
DRAWING TYPE:
DESCRIPTION:SM-A09PRODUCT LINE:
1411 BROADWAY BLVD. NE
ALBUQUERQUE, NM 87102 USA
PHONE: 505.242.6411
WWW.UNIRAC.COM SHEET
1 5 8 "
STRUT
LENGTHS
SQUARE TUBE
LENGTHS
1 13 16 "
1 16 "
1"
Ø3 8"
1"
Ø3 8 "
1 16 "
TILT LEG TABLE
P/N DESCRIPTION
TOTAL
ADJUSTABLE
LENGTHS
SQUARE
TUBE STRUT
307107M SM ADJ TILT LEG,
8"-12", W/HDW 8" to 12" 8" 8"
307115M SM ADJ TILT LEG,
18"-30", W/HDW 18" to 30" 18" 18"
307120M SM ADJ TILT LEG,
26"-44", W/HDW 26" to 44" 26" 26"
307134M SM ADJ TILT LEG,
40"-72", W/HDW 40" to 72" 40" 40"
ADJUSTABLE
LENGTHS
3 8 "-16 SS FLANGE NUT
3 8 "-16 x 3" SS HEX BOLT
3 8 " x 11 2 " x 1 8 " HD FENDER WASHER
L-FEET NOT INLCUDED
IN TILT LEG KITS
3 8 "-16 x 11 4 " SS HEX BOLT
3 8 " x 1
1 2 " x 1 8 " HD FENDER WASHER
3 8 "-16 STRUT NUT
DETAIL A
A
LEGAL NOTICE
DRAWING NOT TO SCALE
ALL DIMENSIONS ARE
NOMINAL
PRODUCT PROTECTED BY
ONE OR MORE US PATENTS
SOLARMOUNT HD
PART & ASSEMBLY
9/27/2017
BOTTOM CLIP
REVISION DATE:
DRAWING TYPE:
DESCRIPTION:SM-A10PRODUCT LINE:
1411 BROADWAY BLVD. NE
ALBUQUERQUE, NM 87102 USA
PHONE: 505.242.6411
WWW.UNIRAC.COM SHEET
1"1"
1 1 4 "
BOTTOM CLIP
PART # TABLE
P/N DESCRIPTION
302000C SMHD BOTTOM CLIPS W/HDW CLR
1 4 "-20 X
3 4 "SSHEXHEADBOLT
1 4 " FLAT WASHER
1 4 "-20 SS FLANGE NUT
LEGAL NOTICE
DRAWING NOT TO SCALE
ALL DIMENSIONS ARE
NOMINAL
PRODUCT PROTECTED BY
ONE OR MORE US PATENTS
SOLARMOUNT
PART DETAIL
9/11/2017
STANDARD RAIL
REVISION DATE:
DRAWING TYPE:
DESCRIPTION:SM-P01PRODUCT LINE:
1411 BROADWAY BLVD. NE
ALBUQUERQUE, NM 87102 USA
PHONE: 505.242.6411
WWW.UNIRAC.COM SHEET
2 9 16 "
1 4 " BOLT LOCATION
3 8 " BOLT LOCATION
PART # TABLE
P/N DESCRIPTION LENGTH
320132M SM RAIL 132" MILL 132"
310132C SM RAIL 132" CLR 132"
320168M SM RAIL 168" MILL 168"
310168C SM RAIL 168" CLR 168"
320168D SM RAIL 168" DRK 168"
320208M SM RAIL 208" MILL 208"
310208C SM RAIL 208" CLR 208"
320240M SM RAIL 240" MILL 240"
310240C SM RAIL 240" CLR 240"
310240D SM RAIL 240" DRK 240"
LEGAL NOTICE
DRAWING NOT TO SCALE
ALL DIMENSIONS ARE
NOMINAL
PRODUCT PROTECTED BY
ONE OR MORE US PATENTS
SOLARMOUNT
PART DETAIL
9/11/2017
LIGHT RAIL
REVISION DATE:
DRAWING TYPE:
DESCRIPTION:SM-P02PRODUCT LINE:
1411 BROADWAY BLVD. NE
ALBUQUERQUE, NM 87102 USA
PHONE: 505.242.6411
WWW.UNIRAC.COM SHEET
PART # TABLE
P/N DESCRIPTION LENGTH
315168M SM LIGHT RAIL 168" MILL 168"
315168D SM LIGHT RAIL 168" DRK 168"
315240M SM LIGHT RAIL 240" MILL 240"
315240D SM LIGHT RAIL 240" DRK 240"
1 11 16 "
1 4 " BOLT LOCATION
3 8 " BOLT LOCATION
LEGAL NOTICE
DRAWING NOT TO SCALE
ALL DIMENSIONS ARE
NOMINAL
PRODUCT PROTECTED BY
ONE OR MORE US PATENTS
SOLARMOUNT
PART DETAIL
9/11/2017
HD RAIL
REVISION DATE:
DRAWING TYPE:
DESCRIPTION:SM-P03PRODUCT LINE:
1411 BROADWAY BLVD. NE
ALBUQUERQUE, NM 87102 USA
PHONE: 505.242.6411
WWW.UNIRAC.COM SHEET
3"
1 7 8 "
3 8 " BOLT LOCATION
BOTTOM CLIP SLOT
1 4 " BOLT LOCATION
PART # TABLE
P/N DESCRIPTION LENGTH
410144M SMHD, RAIL 144" MILL 144"
410168M SMHD, RAIL 168" MILL 168"
410204M SMHD, RAIL 204" MILL 204"
410240M SMHD, RAIL 240" MILL 240"
LEGAL NOTICE
DRAWING NOT TO SCALE
ALL DIMENSIONS ARE
NOMINAL
PRODUCT PROTECTED BY
ONE OR MORE US PATENTS
SOLARMOUNT
PART DETAIL
9/27/2017
END CAPS
REVISION DATE:
DRAWING TYPE:
DESCRIPTION:SM-P04PRODUCT LINE:
1411 BROADWAY BLVD. NE
ALBUQUERQUE, NM 87102 USA
PHONE: 505.242.6411
WWW.UNIRAC.COM SHEET
SOLARMOUNT STANDARD RAIL
SOLARMOUNT LIGHT RAIL
15 16 "
27 8 "
3 4 "
END CAP
OPTIONAL BREAK/CUT LINE
PUSH IN
FRICTION FIT
NOTES:
1. END CAP INCLUDED WITH EVERY END CLAMP.
2. END CAP FITS SOLARMOUNT LIGHT AND STANDARD RAIL PROFILES.
B CLAMP
30mm to 32mm Module Thickness
(1.18" to 1.26")C CLAMP
33mm to 36mm Module Thickness
(1.30" to 1.42")
D CLAMP
38mm to 40mm Module Thickness
(1.50" to 1.57")
E CLAMP
50mm to 51mm Module Thickness
(1.97" to 2.00")F CLAMP
45mm to 47mm Module Thickness
(1.77" to 1.85")
K CLAMP
39mm to 41mm Module Thickness
(1.54" to 1.61")
TYPICAL END CLAMP DETAILS
LEGAL NOTICE
DRAWING NOT TO SCALE
ALL DIMENSIONS ARE
NOMINAL
PRODUCT PROTECTED BY
ONE OR MORE US PATENTS
SOLARMOUNT
PART DETAIL
9/27/2017
END CLAMPS -
TOP MOUNTING
REVISION DATE:
DRAWING TYPE:
DESCRIPTION:SM-P05PRODUCT LINE:
1411 BROADWAY BLVD. NE
ALBUQUERQUE, NM 87102 USA
PHONE: 505.242.6411
WWW.UNIRAC.COM SHEET
1 5 16 "
2 1 16 "
1 19 32 "1 7 16 "
1 13 16 "1 5 8 "
1 4 "Ø
1 1 2 "
3 16 "
PART # TABLE
P/N DESCRIPTION
302021C SM ENDCLAMP B CLR AL
302021D SM ENDCLAMP B DRK AL
302022C SM ENDCLAMP C CLR AL
302022D SM ENDCLAMP C DRK AL
302023C SM ENDCLAMP D CLR AL
302023D SM ENDCLAMP D DRK AL
303024C SM ENDCLAMP E CLR AL
302024D SM ENDCLAMP E DRK AL
302025C SM ENDCLAMP F CLR AL
302025D SM ENDCLAMP F DRK AL
302026C SM ENDCLAMP K CLR AL
302026D SM ENDCLAMP K DRK AL