12-1040 (RER) Title 24BUILDING ENERGY ANALYSIS REPORT
PROJECT:,,
Residence Remodel
75-591 Talking Rock. CITy. 0
La Quinta CA 92253 F LA QUINTA,
BUILDING. &
SAFETY DEPT.
APPROVED,
Project Designer:
FOR CONSTRUCTION
Mike Perryman
75-591 Talking Rock DA rE 10 Zq 17- BY
La Quinta, CA 92553
(310)500 -8553
Report Prepared by:
Jon Scott
Scott Design and Title 24, Inc, -
77-085 Michigan Drive
Palm Desert, Ca 92211
OCTA247012,
BY.
Job Number -
Date:
10/18/2012''
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2008 Building Energy Efficiency Standards.
This program developedby EnergySoft, LLC — www.energysoft.com.
Ener Pro 5.1 by EnergySoft User Number 6712 RunCode: 2012-10-187I3:28:56 ID:
Ll
A
.- +,
j
�
.y
�
�
., - ;
j
�
.y
�
�
., - ;
•
•
•
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
Residence Remodel
Building Type m Single Family ❑ Addition Alone
❑ Multi Family m Existing+ Addition/Alteration 11011812012
Date
Project Address
75-591 Talking Rock La Quinta
California Energy Climate Zone
CA Climate Zone 15
I Total Cond. Floor Area
6,800
Addition
0
# of Stories
1
FIELD INSPECTION ENERGY CHECKLIST
❑ Yes IZI No HERS Measures -- If Yes, A CF -413 must be provided per Part 2 of 5 of this form.
❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION
Construction Type
Area Special
Cavity (ft) Features see Part 2 of 5 Status
Roof Wood Framed Attic R-19 2,500 Existing
Wall Wood Framed R-11 3,051 Existing
Wall Wood Framed R-13 1,080 Altered
Door Opaque Door None 32 Existing
Slab Unheated Slab -on -Grade None 6,800 Perim = 480' Existing
FENESTRATION U- Exterior
Orientation Area Factor SHGC Overhang Sidefins Shades Status
Skylight 32.0 0.550
0.67 none none None Existing
Skylight 24.0 0.550
0.67 none none None Existing
Front (NE) 134.0 1.190
0.83 none none Bug Screen Existing
Front (E) 104.0 1.190
0.83 none none Bug Screen Existing
Left (SE) 303.0 1.190
0.83 none none Bug Screen Existing
Left (S) 64.0 1.190
0.83 none none Bug Screen Existing
Rear (SVV) 63.0 1.190
0.83 none none Bug Screen Existing
Rear (SVIO 140.0 0.550
0.46 none none Bug Screen New
Rear (SVt9 140.0 1.190
0.83 none none Bug Screen Removed
Rear (Ko 176.0 1.190
0.83 none none Bug Screen Existing
Rear (M 140.0 0.550
0.46 none none Bug Screen New
HVAC SYSTEMS
Ot . Heating Min. Eff
Cooling Min. Eff Thermostat Status
4 Central Furnace 80% AFUE
Split Air Conditioner .9.0 SEER Setback
Existing
HVAC DISTRIBUTION
Location Heating
Duct
Cooling Duct Location R -Value Status
HVAC- Ducted
Ducted Attic, Ceiling Ins, vented 4.2
Existing
WATER HEATING
Ot . Type Gallons Min. Eff Distribution Status
Ener Pro 5.1 by Ener Soft User Number: 6712
RunCode: 2012-10-18T13:28:56 ID:
Page 3 of 14
r�
L
•
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
Residence Remodel
Building Type m Single Family ❑ Addition Alone
❑ Multi Family m Existing+ Addition/Alteration 11011812012
Date
Project Address
75-591 Talking Rock La Quinta
California'Energy Climate Zone
CA Climate Zone 15
I Total Cond. Floor Area
6,800
Addition
0
# of Stories
1
FIELD INSPECTION ENERGY CHECKLIST
❑ Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION
Construction Type
Area Special
Cavity (ft) Features see Part 2 of 5 Status
FENESTRATION U-
Orientation Area Factor
Exterior
SHGC Overhang Sidefins Shades Status
Rear (tom 140.0 1.190
0.83 none none Bug Screen Removed
Right (NtM 229.2 1.190
0.83 none none Bug Screen Existing
Right (N) 104.0 1.190
0.83 none none Bug Screen Existing
Right (N) 140.0 0.550
0.46 none none Bug Screen New
Right (N) 140.0 1.190.
0.83 none none Bug Screen Removed
HVAC SYSTEMS
Ot . Heating Min. Eff Cooling Min. Eff Thermostat Status
HVAC DISTRIBUTION
Location Heating
Duct
Cooling Duct Location R -Value Status
WATER HEATING
Ot . Type Gallons Min. Eff Distribution Status
Ener Pro 5.1 by EnergySoft User Number 6712 RunCode: 2012-10-187'13:28:56 /D:
Page 4 of 14
•
•
PERFORMANCE CERTIFICATE: Residential (Part 2 of 5) CF -1 R
Project Name
Remodel
Building Type ® Single Family ❑ Addition Alone
❑Multi Family m Existing+ Addition/Alteration8/2012
7Da/,,,Residence
SPECIAL FEATURES INSPECTION CHECKLIST
The enforcement agency should pay special attention to the items specified in this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The enforcement agency
determines the adequacy of the justification,,and may reject a building or design that otherwise complies based on the adequacy of
the special justification and documentation submitted.
HERS REQUIRED VERIFICATION
Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a
completed CF -4R form for each of the measures listed below for final to be given.
Ene Pro 5.1 b Ene Soft User Number: 6712 RunCode: 2012-10-18713:28:56 ID: Pa ge 5 of 14
•
PERFORMANCE CERTIFICATE: Residential (Part 3 of 5) CF -1 R
Project Name
Building Type m Single Family ❑ Addition Alone
Date
Residence Remodel
❑ Multi Family m Existing+ Addition/Alteration
10/18/201
ANNUAL ENERGY USE SUMMARY .
Standard Proposed Margin
TDV kBtu/ft2 r
Space Heating 10.77 9.15 1.62
Space Cooling 203.98 190.53 13.45
Farts 32.64 30.41 2.23
Domestic Hot Water 5.29 5.29 0.00
Pumps 0.00 0.00 0.00
Totals 252.68 235.38 17.30
Percent Better Than Standard: 6.8
BUILDING COMPLIES - NO HERS VERIFICATION REQUIRED
Fenestration
Building Front Orientation: (NE) 30 deg Ext. Walls/Roof Wall Area Area
Number of Dwelling Units: 1.00 (NE) 1,240 238
Fuel Available at Site: Natural Gas (SE) 1,340 367
Raised Floor Area: 0 (SK9 2,060 519
Slab on Grade Area: 6,800 (NKK 1,120 473
Average Ceiling Height: 14.0 Roof 2,556 56
Fenestration . Average U -Factor: 1.02 TOTAL: 1,653
Average SHGC: 0.73 Fenestration/CFA Ratio: 24.3%
REMARKS
.Traditions Country Club .
STATEMENT OF COMPLIANCE
This certificate of compliance lists the building features and specifications needed
to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the
Efficiency Standards of the California Code of Regulations.
The documentation author hereby certifies that the documentation is accurate and complete.
Documentation Author
Company Scott Design and Title 24, Inc,
/18 oi,
Address 77-085 Michigan Drive Name Jon Scott
City/State/ZipCity/State/Zip Palm Desert, Ca 92211 Phone (760) 200-4780 Signed Date
The individual with overall design responsibility hereby certifies that the proposed building design represented in this set
,of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and
with,any other calculations submitted with this permit application, and recognizes that compliance using duct design,
duct sealing, verification of refrigerant charge, insulation installation quality, and building envelope sealing require
installer testing and certification and field verification by an approved HERS rater.
Designer or Owner (per Business & Professions Code)
Company Mike Perryman
Address 75-591 Talking Rock Name Mike Perryman
City/State/zip La Quint;, CA 92553 Phone (310) 500-8553 Signed License # Date
EnerqvPro 5.1 by Ener.QvSdft User Number: 6712 RunCode: 2012-10-18713:28:56 /D: Page 6 of 14
W]
CERTIFICATE OF COMPLIANCE:
Residential
(Part 4 of 5) CF -1 R
Project Name
Residence Remodel
Building Type m Single Family ❑ Addition Alone
❑ Multi Family m Existing+ Addition/Alteration
Date
1&1812012
OPAQUE SURFACE DETAILS
Surface
Type Area
U- Insulation . Joint Appendix
Factor Cavit Exterior Frame Interior Frame Azm Tilt Status - 4 Location/Comments
Roof
2,500
0.049 R-19
0
'0 Existing 4.2.1-A4
Residence
Wall
826
0.110 R-11
30
90 Existing 4.3.1-A2
+ Residence
Wall
176
0.110 R-11
75 _
90 Existing 4.3.1-A2
Residence
Wall
657
_0.110 R-11
120
90 Existing 4.3.1-A2
- Residence
Wall
316
0.110 R-11
165
90 Existing 4.3.1-A2
Residence '
Wall.
757
0.110 R-11
210
90 Existing - 4.3.1-A2
Residence
Wall
360
0.102 R-13'
210
90 Altered 4.3.1-A3 (E=4.3.1 -A2) Residence
Wall
64
0.110 R-11
255
90 Existing 4.3.1-A2
Residence
Wall
360
0.102 R-13
255
90 Altered 4.3.1-A3 E=4.3.1 -A2 Residence
Wall
219
0.110 R-11
300
90 Existing 4.3.1-A2
Residence
Door
32
0.500 None
300
90 Existing 4.5.1-A4
Residence
Wall
36
0.110 R-11
345
90 Existing 4.3.1-A2
Residence
Wall
360
0.102 R-13
345
90 Altered 4.3.1-A3 E=4.3. I-A2j Residence
Slab
6,800
0.730 None
0
180 Existing 4.4.7-A1
Residence
FENESTRATION SURFACE DETAILS
'
ID
Type
Area LI -Factor'
SHGC -
Azm Status
Glazing Type
Location/Comments
1
Skylight
32.0 0.550 1 Default
0.67 Default
0 Existing
Double Non Metal Clear
Residence
2
Skylight
24.0 • 0.550 Default
0.67 Default
0 Existing
Double Non Metal Clear
Residence
3
Window
20.0 1.190 Default
0.83 Default
30 Existin
Sin le Metal Clear
Residence
4
Window
20.0 1.190 Default
0.83 Default
' 30 Existing
Single Metal Clear
Residence
5 ' Window
25.0 1.190 Default
0.83 Default
30 Existing
Single Metal Clear
Residence
6
Window
20.0 1.190 Default.
0.83 Default
30 Existing
Single Metal Clear
Residence
7
Window
9.0 1.190 Default
0.83 Default
30 Existing
Single Metal Clear
Residence
8
Window
40.0 1.190 Default
0.83 Default
30 Existing
Single Metal Clear
Residence
9
Window
40.0 1.190 Default
0.83 Default
75 Existing
Single Metal Clear'
Residence
10
Window
64.0 1.190 Default
0.83 Default
75 Existing
Single Metal Clear
Residence
11
Window
64.0 1.190 Default.
0.83 Default
120 Existing
Single Metal Clear
Residence
12
Window
36.0. , 1.190 Default
0.83 Default
120 Existing
Single Metal Clear
Residence
13 • Window
9.0 1.190 Default
.0.83 Default
120 Existing
Single Metal Clear
Residence
14
Window
9.0 1.190 Default
.0.83 Default
120 Existing
Single Metal Clear
Residence
15
Window
48.0 1.190 Default
0.83 Default
1120 Existing
Single Metal Clear
Residence
16
Window
48.0 1.190 Default
0.83 Default
120 Existing
Single Metal Clear
Residence
(1) Ll -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS -
. ..
'
ID
Exterior Shade Type SHGC-
Window
' H t Wd
Ove hang Left Fin
Len H t LExt RffxF Dist . Len
Right Fin
H t Dist Len H t
1
None
1.00
2
None
1.00
.
3
Bug Screen
0.76
4
Bug Screen
0.76
5
Bug Screen
0.76
,
6
Bug Screen
0.76
7
Bug Screen -
0.76
8
Bug Screen
0.76
9
Bug Screen
0.76
10
Bug Screen
0.76
11
Bug Screen
0.76
12
Bug Screen
0.76
13
Bug Screen
0.76
14
-Bug Screen
0.76
15
IBug Screen'
0.76
16
18ug Screen
0.76
s
Ener Pro 5.1 by Ener Sof User Number: 6712. Run Code: 2012-10-18713:28:56 ID,
Page 7 of 14
•
•
•
CERTIFICATE OF COMPLIANCE:
Residential
(Part 4 of 5) CF -1 R
Project Name
Residence Remodel
Building Type m Single Family ❑ Addition Alone
❑ Multi Family m Existing+ Addition/Alteration
Date
10/18/2012
OPAQUE SURFACE DETAILS
Surface U- Insulation Joint Appendix
Type Area Factor -C-a-V-it-YTExterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
FENESTRATION SURFACE DETAILS
ID
Type Area
LI -Factor'
SHGC
Azm Status
Glazing Type
Location/Comments
17
Window 36.0
1.190 Default
0.83 Default
120 Existing
Single Metal Clear
Residence
18
Window 1.0
1.190 Default
0.83 Default
120 Existing
Single Metal Clear
Residence
19
Window 1.0
1.190 Default
0.83 Default
120 Existing
Single Metal Clear
Residence
20
Window 1.0
1.190 Default
0.83 Default
120 Existing
Single Metal Clear
Residence
21
Window 1.0
1.190 Default
6.83 Default
120 Existing
Single Metal Clear
Residence
22
Window 9.0
1.190 Default
0.83 Default
120 Existing
Single Metal Clear
Residence
23
Window 40.0
1.190 Default
0.83 Default
120 Existing
Single Metal Clear
Residence
24
Window 64.0
1.190 Default
0.83 Default
165 Existing
Single Metal Clear
Residence
25
Window 63.0
1.190 Default
0.83 Default
210 Existing
Single Metal Clear
Residence
26
Window 105.0
0.550 NFRC
0.46 NFRC
210 New
Dual non Metal Tint
Residence
27
Window 35.0
0.550 NFRC
0.46 NFRC
210 New
Dual non Metal Tint
Residence
28
Window 105.0
1.190 Default
0.83 Default
210 Removed
Single Metal Clear
Residence
29
Window 35.0
1.190 Default
0.83 Default
210 Removed
Single Metal Clear
Residence
30
Window 48.0
1.190 Default
0.83 Default
255 Existing
Single Metal Clear
Residence
31
Window 105.0
0.550 NFRC
0.46 NFRC
255 New
Dual non Metal Tint
Residence
32
Window 35.01
0.550 NFRC
0.46 NFRC
255 New
Dual non Metal Tint
Residence
(1) LI -Factor Type:
2 SHGC Type:
116-A = Default Table from Standards, NFRC = Labeled Value
116-B =Default Table from Standards, NFRC =Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type
SHGC
Window
H t Wd
Ove hanq Left Fin Ri ht in
Len H t LExt RExt Dist Len H t Dist Len H t
17
Bug Screen
0.76
18
Bug Screen
0.76
19
Bug Screen
0.76
20
Bug Screen
0.76
21
Bug Screen
0.76
22
Bu4 Screen
6.76
23
Bug Screen
0.76
24
Bug Screen
0.76
25
Bug Screen
0.76
26
Bug Screen
0.76
27
Bug Screen
0.76
28
Bug Screen
0.76
29
Bug Screen
0.76
30
Bug Screen
0.76
31
JBug Screen
0.76
32
JBug Screen
0.76
EnergyPro
5.1 by Ener Soft
User Number: 6712 RunCode: 2012-10-18T13:28:56 ID:
Page 8 of 14
•
CERTIFICATE OF COMPLIANCE:
Residential
(Part 4 of 5) CF -1 R
Project Name
Residence Remodel
Building Type m Single Family ❑ Addition Alone
❑ Multi Family 0 Existing+ Addition/Alteration
Date
11011812012
OPAQUE SURFACE DETAILS
Surface U- Insulation Joint Appendix
Type Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
FENESTRATION SURFACE DETAILS
ID
Type Area
LI -Factor'
SHGC
Azm Status Glazing Type
Location/Comments
33
Window 64.0
1.190 Default
0.83 1 Default
255 Existing Single Metal Clear
Residence
34
Window 64.0
1.190 Default
0.83 Default
255 Existing Single Metal Clear
Residence
35
Window 105.0
1.190 Default
0.83 Default
255 Removed Single Metal Clear
Residence
36
Window 35.0
1.190 Default
0.83 Default
255 Removed Single Metal Clear
Residence
37
Window 64.0
1.190 Default
0.83 Default
300 Existing Single Metal Clear
Residence
38
Window 64.0
1.190 Default
0.83 Default
300 Existing Single Metal Clear
Residence
39
Window 40.0
1.190 Default
0.83 Default
300 Existing Single Metal Clear
Residence
40
Window 6.0
1.190 Default
0.83 Default
300 Existing Single Metal Clear
Residence
41
Window 6.0
1.190 Default
0.83 Default
300 Existing Single Metal Clear
Residence
42
Window 40.2
1.190 Default
0.83 Default
300 Existing Single Metal Clear
Residence
43
Window 9.0
1.190 Default
0.83 Default
300 Existing Single Metal Clear
Residence
44
Window 40.0
1.190 Default
0.83 Default
345 Existing Single Metal Clear
Residence
45
Window 105.0
0.550 NFRC
0.46 NFRC
345 New Dual non Metal Tint
Residence
46
Window 35.0
0.550 NFRC
0.46 NFRC
345 New Dual non Metal Tint
Residence
47
Window 64.0
1.190 Default
0.83 Default
345 Existing Single Metal Clear
Residence
48
Window 105.0
1.190 Default
0.83 Default
345 Removed Single Metal Clear
Residence
(1) Ll -Factor Type:
2 SHGC Type:
116-A = Default Table from Standards, NFRC = Labeled Value
116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type
SHGC
Window
H t Wd
Ove hang
Len H t LExt RExt Dist
Left Fin Right Fin
Len H t Dist Len H t
33
Bug Screen
0.76
34
Bug Screen
0.76
35
Bug Screen
0.76
36
Bug Screen
0.76
37
Bug Screen
0.76
38
Bug Screen
0.76
39
Bug Screen
0.76
40
Bug Screen
0.76
41
Bug Screen
0.76
42
Bug Screen
0.76
43
Bug Screen
0.76
44
Bug Screen
0.76
45
Bug Screen
0.76
46
Bug Screen
0.76
47
Bug Screen
0.76
48
JBug Screen
0.76
Ener Pro 5.1 by Ener Soft
User Number. 6712 RunCode: 2012-10-18713:28:56 ID:
Page 9 of 14
•
C]
0
• • •- '. •
Projectr.
Residence Remodel
Single Family ■ Addition Alone
Multi Family 10 Existing+ Add ition/Alte ration
OPAQUE SURFACE DETAILS
W-11 ivill-li�� -----joint Appendix
4 Location/Comments
FENESTRATION0
�Emm
0 MI: PRIM Single Metal Clear
. ... E
Fri dil .-
Exterior Shade Type
•
•
•
CERTIFICATE OF COMPLIANCE: Residential (Part 5 of 5)
CF -1 R
Project Name
Residence Remodel
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ® Existing+ Addition/Alteration
Date
110/18/2012
BUILDING ZONE INFORMATION
System Name Zone Name New
Floor Area ft
Existing Altered Removed Volume Year Built
HVAC- Residence
6,800
95,200 1989
Totals 1 01 6,8001 01 0
HVAC SYSTEMS
' System Name Qty. Heating Type Min. Eff. Cooling Type Min. Eff. Thermostat Type Status
HVAC 4 Central Furnace 80% AFUE Split Air Conditioner 9.0 SEER Setback
Existing
HVAC DISTRIBUTION
System Name Heating Cooling
Duct
Duct Location R -Value
Ducts
Tested? Status
HVAC Ducted Ducted Attic, Ceiling Ins, vented 4.2
❑ Existing
WATER HEATING SYSTEMS
S stem Name
Ot .
Type
Distribution
Rated
Input
Btuh
Tank
Cap.
al
Energy
Factor
or RE
Standby
Loss or
Pilot
Ext.
Tank
Insul. R-
Value
Status
Standard 50 gal or Less
1
Small Gas
All Pipes Ins
40,000
50
0.57
n/a
n/a
Existing
MULTI -FAMILY WATER
HEATING
DETAILS
HYDRONIC
HEATING SYSTEM
PIPING
Control
Hot Water Piping Length
ft
C
0
a y
Q c
System Name
Pipe
Length
Pipe
Diameter
Insul.
Thick.
Ot . HP
Plenum Outside Buried
Ener Pro 5.1 by EnergySoft User Number: 6712 Run Code: 201 2-10-1 8 713:28:56 ID:
Pae 11 of 14
t.
MANDATORY MEASURES SUMMARY: Residential Pae 1 of 3 MF -1 R
Project Name
Residence Remodel
Date
110/18/2012
j_
t.
MANDATORY MEASURES SUMMARY: Residential Pae 1 of 3 MF -1 R
Project Name
Residence Remodel
Date
110/18/2012
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD; or CF=
1 R -ALT Form) shall supersede the' items marked with an asterisk (") below. This Mandatory Measures Summary shall be incorporated
into the permit documents, and the applicable features shall be considered by all parties as minimum component performance.
specifications whether, they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R
Form with plans.
Building Envelope Measures:
116(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§116(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of 10-111 (a).
Exterior doors and windows are weather-stripped; •all joints and penetrations are caulked and sealed.
_117:
118(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF -6R Form.
§118(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §118(1) when the
installation of a Cool, Roof is s ecified on the CF -1 R Form.'
*§1 50 a : Minimum R-19 insulation'in wood -frame ceiling orequivalent U -factor.
§150(b): Loose fill insulation shall conform with manufacturer's installed design Ialieled.R-Value.
*§150(c): Minimum R-13 insulation in wood -frame wall orequivalent U -factor.
*§150(d): Minimum R-13 insulation in raised wood -frame floor orequivalent U -factor:
§150(f): Air retarding wrap is tested labeled, and installed according to ASTM E1677-95(2000) when specified on the CF -1R Form.
150 : Mandatory Vapor barrier installed in Climate Zones 14"or 16.
'§150(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance
rate is no greater than 2.0perm/inch and shall be protected from physical damage and UV light deterioration.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
150 a 1A: Masonry or facto -built fire laces have a closable metal or glass door C'oveririq the entire opening of the firebox.
§150(e)1 B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a with a readily accessible, operable, and tight -fitting damper and or a combustion -air control device. '
§150(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor.air is vented to the
outside of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110-§113: HVAC equipment, water heaters, showerheads, faucets andallother regulated appliances are certified by the Energy
Commission.
"§113(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release
valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of §113(c)5:
.-§115: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances ;
(appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and
spa heaters. "
150(h): Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACOA.
§1500): Heatinq systems are equipped with thermostats that meet the setback re uirements of Section 112(c).
§150(j)1 A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped
with insulation having an installed thermal resistance of R-12 or greater. • '``
§150(j)1 B: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water
tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the
tank.
§150(j)2: First 5 feet of hot and cold water pipes closest to water heater tank, non -recirculating systems, and entire length of
recirculatina sections of hot water pipes are insulated per Standards Table.150-13. '
§150(j)2: Cooling system piping (suction, chilled water, or brine lines),and piping insulated between heating source and indirect hot
-water tank shall be insulated to Table 150 -Band Equation -150-A. '
§150(j)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards Table
-123-A.
150(i)3A: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
-§150(j)3A: Insulation for chilled water piping and refrigerant suction lines includes a vapor retardant or is enclosed entirely in
conditioned space.
150(i)4: Solar water -heating slstems and/or collectors are certified by the Solar Ratin and Certification Corporation. ,
EnergyPro 5,1 by EnergySoft User Number: 6712 RunCode: 2012-10-18713:28:56 ID: Page 12 of 14
� s ,
-MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 MF -1 R
Project Name
Date "
Residence Remodel
11011812012
.§150(m)1: All air -distribution system ducts and plenums'installed, are sealed and insulated to meet the requirements of CMC Sections
601, 602, 603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-
-4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that meets the
;applicable requirements of UL 181, UL 181 A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is
used to seal openings reater than 1/4 inch, the combination of mastic and either mesh or tape shall be used
§150(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may
contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area
of the ducts.
§150(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes
unless such tape is used in combination with mastic and draw bands.
150(m)7: Exhaust fans stems have back draft or automatic dampers.
§150(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated
dampers.
§150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar
radiation that can cause degradation of the material.
150 m 10: Flexible ducts cannot have porous inner cores.
1150(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air
Quality in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation
required in Section 4 of that Standard.
Pool and Spa Heating Systems and Equipment Measures:
§114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and
shall not use electric resistance heating ora pilot light.
§114(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction
and return lines, or built-up connections for future solar,heatin .
114(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover.
§114(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or
programmed to run only during off-peak electric demand periods.
150 :Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150 .
-Residential Lighting Measures:
-•§150(k)1: High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies
,contained in Table 150-C and is not a low efficacy luminaire asspecified by §150(k)2.
150(k)3: The wattage of permanently installed luminaires shall be determined asspecified by §130(d).
§150(k)4: Ballasts for fluorescent lamps•rated 13 Watts or greater shall be electronic and shall have an output frequency no less than
•
20 kHz.
§150(k)5: Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall contain
only high efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line -voltage socket or line -
voltage lamp holder; OR shall be ratted to consume no more than five watts of power as determined by. §130(d), and shall not contain a
medium screw -base socket.
§150(k)6: Lighting integral exhaust fans, in rooms other than kitchens, shall'meet the applicable requirements of §150(k).
-to
150(k)7: All switching devices and controls shall meet the requirements of §150(k)7.
§150(k)8: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft2 or 100 watts for dwelling units larger than 2,500 ft2 may be
exempt from the 50% high efficacy requirement when: all low efficacy luminaires in the kitchen are controlled by a manual on occupant
_
sensor, dimmer, energy management system (EMCS), or a multi -scene programmable control system; and all permanently installed
-luminaries in garages; laundry rooms, closets greater than 70 square feet, and utility rooms are high efficacy and controlled by a
`manual -on occupant sensor.*
=§150(k)9: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of
illuminated cabinet.
EnergyPro 5.1 by En ergySoft User Number. 6712 RunCode: 2012-10-18T13:28:56 ,, ID: Page 13 of 14
0
�4
0
MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 MF -1 R
Project Name
Date
Residence Remodel
11011812012
§150(k)10: Permanently installed luminaires in bathrooms, attached and detached garages, laundry rooms, closets and utility rooms
shall be high efficacy.
EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by a manual -on
occupant sensor certified to comply with the applicable requirements of §119.
.EXCEPTION 2: Permanently installed low efficacy luminaires in closets less than 70 square.feet are not required to be controlled by a
manual -on occupancy sensor.
§150(k)11: Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms,
closets, and utility rooms shall be high efficacy luimnaires. EXCEPTION 1: Permanently installed low efficacy luminaires shall be
allowed provided they are controlled by either a dimmer switch that complies with the applicable requirements of §119, or by a manual -
on occupant sensor that complies with the applicable requirements of §119. EXCEPTION 2: Lighting in detached storage building less
than 1000 square feet located on a residential site is not required to comply with §150 k 11.
§150(k)l2: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters
Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the lumiunaire is airtight with air
leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between
the luminaire housing and ceiling.
§150(k)l3: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more
dwelling units, entrances, balconies, and porches, which are permanently mounted to a residential building or to other buildings on the
.same lot shall be high efficacy. EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that
-they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor,
Nand one of the following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an
astronomical time clock not having an override or bypass switch that disables the astronomical time clock; OR an energy management
control system (EMCS) not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2: Outdoor
luminaires used to comply,with Exceptions to §150(k)13 may be controlled by a temporary override switch which bypasses the motion
sensing function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3: Permanently installed
luminaires in or around swimming pool, water features, or other location subject to Article 680 of the California Electric Code need not
be high efficacy luminaires.
§150(k)14: Internally illuminated address signs shall comply with Section 148; OR not contain a screw -base socket, and consume no
more than five watts of power as determined according to §130(d).
§150(k)l5: Lighting for parking lots and.carports with a'total of for 8 or more vehicles per site shall comply with the applicable
requirements in Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable
requirements of Sections 130, 131, 134, and 146.
§150(k)16: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more
,dwelling units shall be high efficacy luminaires. EXCEPTION: Permanently installed low efficacy luminaires shall be allowed provided
that they are controlled by an occupant sensors certified to comply with the applicable requirements of 119.
EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2012-10-18713:28:56 /D: Page 14 of 14