FSINSP2020-0002ADDITIONAL SITES
CHRONOLOGY
CONDITION
TYPE CONTACT DATE
ADDED
DATE
REQUIRED
DATE
SATISFIED STATUS REMARKS NOTES
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
E-MAIL AARON HICKSON 6/15/2020 6/18/2020 EMAIL TO APPLICANT TO UPLOAD NEW PLAN AS FILE IS
CORRUPTED. ASKED FIRE IF THIS IS CORRECT PERMIT TYPE.
E-MAIL AARON HICKSON 6/30/2020 6/30/2020 RECEIVED SITE PLAN BY EMAIL ATTACHED FOR CONTRACTOR.
ASSIGNED REVIEW.
E-MAIL KOHL HETRICK 7/2/2020 7/2/2020 Requested manufacturer specifications for the monitoring
unit.
NOTE STEPHANIE SWANSTROM 7/8/2020 7/8/2020 BUSINESS LICENSE FEE COLLECTED FROM PERMIT FSINP2020-
0002, TO PAY LIC-0111960.
TELEPHONE CALL KOHL HETRICK 7/6/2020 7/6/2020 Left VM requesting equipment information and specification
documents.
CONDITIONS
Description: CO2 Monitoring Device, Alalox Model Type AX60+ installation
Type: FIRE SPECIAL INSPECTION
(WEB)
Subtype: Status: APPROVED-CONDITIONS Applied: 6/12/2020 ECON
Parcel No: 643020029 Site Address: 78935 HIGHWAY 111 LA QUINTA,CA 92253 Approved: 7/6/2020 KHET
Subdivision: PM 30903 Block: Lot: 5 Issued: 7/6/2020 Online
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled:
Valuation: $2,500.00 Occupancy Type: Construction Type: Expired: 1/2/2021 ECON
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details:
Printed: Thursday, February 16, 2023 3:57:11 PM 1 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSINSP2020-0002
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT Danny Cantero 8613 Helms Ave Rancho
Cucamonga
CA 91730 (909)244-4994 dcantero@superiorem
p.com
BILL TO Superior EMP Inc.8613 Helms Ave Rancho
Cucamonga
CA 91730 (909)244-4994
CONTRACTOR SUPERIOR ELECTRICAL MECHANICAL
& PLUMBIN
8613 HELMS AVE RANCHO
CUCAMONGA
CA 91730 (909)244-4994 dcantero@superiorem
p.com
OWNER TARGET CORP 3667 Valley Blvd MINNEAPOLIS MN 92253 (909)244-4994
READY TO ISSUE
CHECKLIST KOHL HETRICK 7/6/2020 7/6/2020 PENDING FEE INCREASE DUE TO 1-HOUR PC RESOURCING
DOCUMENTS AND COMPILING.
INSPECTIONS
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
PARENT PROJECTS
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
FIRE SPECIAL
INSPECTION 101-0000-42421 0 $161.00 $161.00 6/12/20 WEB5454 584821 CREDIT SUPERIOR ELECTRICAL
MECHANICAL ECON
FIRE STAFF - PER HOUR 101-0000-42420 0.5 $80.50 $80.50 7/6/20 R61517 LIC-
0111960 CREDIT Danny Cantero SSW
Total Paid for FIRE FEES: $241.50 $241.50
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 6/12/20 WEB5454 584821 CREDIT SUPERIOR ELECTRICAL
MECHANICAL ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$246.50 $246.50
Printed: Thursday, February 16, 2023 3:57:11 PM 2 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSINSP2020-0002
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 6/30/2020 AARON HICKSON
1ST SUBMITTAL SITE
PLAN target 1867 - la
quinta-2.pdf
target 1867 - la quinta-
2.pdf 0
DOC 7/6/2020 KOHL HETRICK
P0159-4170 Ax60+
Protduct
Information.pdf
P0159-4170 Ax60+
Protduct
Information.pdf
1
DOC 7/6/2020 KOHL HETRICK P0159-861 Ax60+
Datasheet - AST.pdf
P0159-861 Ax60+
Datasheet - AST.pdf 1
DOC 7/6/2020 KOHL HETRICK
FSINSP2020-0002 - CO2
ALARM - APPROVED
PLANS.pdf
FSINSP2020-0002 - CO2
ALARM - APPROVED
PLANS.pdf
1
DOC 7/6/2020 KOHL HETRICK
FSINSP2020-0002 -
TARGET CO2 ALARM -
COA and JOB CARD.pdf
FSINSP2020-0002 -
TARGET CO2 ALARM -
COA and JOB CARD.pdf
1
BOND INFORMATION
1ST PERMIT TECH (1
DAY)
AARON
HICKSON 6/12/2020 6/15/2020 6/19/2020 INCOMPLETE
1ST FIRE (1 WK)KOHL
HETRICK 6/30/2020 7/7/2020 7/6/2020 APPROVED SEE ATTACHMENTS
Printed: Thursday, February 16, 2023 3:57:11 PM 3 of 3
Permit Details
City of La Quinta
PERMIT NUMBER
FSINSP2020-0002
O2Ax60+
Multi-gas Safety Monitor with Data Output Module
CO2
The Ax60+ is a wall-mountable gas safety device for monitoring oxygen
and carbon dioxide. Based on the popular Ax60 CO2 detector, the new
Ax60+ can also be supplied with O2 sensor modules which provides an
early warning of both oxygen depletion and oxygen enrichment. The CO2
and O2 sensors are interchangeable and can be fully integrated as part of a
multi-point, multi-gas detection and alarm system.
CO2 sensor alarm set points are pre-configured ready to meet:
PROVIDING NICHE CUSTOM
GAS DETECTION SINCE 1981
KEY FEATURES
• Multi-point, multi-gas,
distributed monitoring system
• 4-channel flexibility allowing any
fixed sensor combination
• Central display unit for remote
operation and control
• User-configurable alarms, set-
points and relay outputs
• Built-in software for operation
and maintenance tasks
• Ability to connect to a BMS or
central control panel
GASES DETECTED
Relay output 1
Relay output 2
Optional Beacon
Central Display
Quick Connect
Hard Wired
You can have 4 alarms per
sensor, to a maximum of 8
alarms per system.
Universal PSU
100 V to 240 V
50—60 Hz
AC input
CO2
Sensor
CO2
Sensor
O2
Sensor
O2
Sensor
Alarm
or
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
OPTIONALwww.analox.net
USA regulations (OSHA, NBIC,
NFPA and IFC) :
TWA - 5000ppm (0.5%)
AL1 - 5000ppm (0.5%)
AL2 - 15000ppm (1.5%)
AL3 - 30000ppm (3%)
European/International regulations
(EH40):
TWA - 5000ppm (0.5%)
AL1 - 15000ppm (1.5%)
CO2 - 30000ppm (3%)
Offering a quick, ‘out of the box’ installation. Set points can also be user
configured to ensure compliance in any part of the world.
A Data Output Module can now be purchased as an accessory for the
Ax60+. The module uses 4-20mA and MODBUS RTU communications
to transmit real time updates of sensor activity and status to a Building
Management System (BMS) or central control panel.
UK & USA
Quality Design,
Manufacturing & Service
SPECIFICATIONS
Analox has a policy of continuous improvement and we reserve the right to upgrade or change specifications without prior notice.
Full technical specifications are available upon request and can be found in the User Manual.
If you require a datasheet in another language please contact us.
Alarm set points can
be changed by the user.
P0159-861-12
info@analox.biz
UK: +44 (0) 1642 711400
US: (714) 891-4478
(877) SAFE AIR
Sensor Specification
Variable CO2 Sensor O2 Sensor
Gas detected Carbon Dioxide Oxygen
Measurement technique Infrared Electrochemical cell
Range 0.1% to 5%0.1% to 25%
Default alarm set-points USA regulations (OSHA, NBIC, NFPA and IFC) :
TWA - 5000ppm (0.5%)
AL1 - 5000ppm (0.5%)
AL2 - 15000ppm (1.5%)
AL3 - 30000ppm (3%)
European/International regulations (EH40):
TWA - 5000ppm (0.5%)
AL1 - 15000ppm (1.5%)
CO2 - 30000ppm (3%)
18% (low), 19.5% (low), 23% (high)
IP rating IP55 IP55
Warranty 5 years 5 years graded
Response time (T90) <30 seconds (T90) <30 seconds
Sensor Warm Up Time 60 Minutes
Dimensions 2”/52mm x 5.1”/132mm x 3”/72mm (w x h x d)2”/52mm x 5.1”/132mm x 3”/72mm (w x h x d)
System Specification
Variable System
Warm-up time 40 seconds
Operating
temperature range
−5 °C to +50 °C, +23 °F to +122 °F
Approvals CE, EN50270, IEC 61010 (UL), DIN 6653
(TUV)
Warranty 5 years electronics
Central Display Specification
Variable Central Display
Display LCD dot matrix (backlit)
Relays 2 x high powered configurable relays,
rated for 250V AC/ 30V DC, 3A max
IP rating IP54
Maximum power
consumption
<24 W
Power supply
accepts inputs from
100 - 240V ~ 1.5A
Dimensions 2.6”/67mm x 4”/106mm x 6.9”/175mm
(w x h x d)
Alarm Specification
Variable Alarm
Strobe white LED strobe > 100 cd
(optional blue, red and amber filters)
Sounder min 80 dBA @3 m (9.8 feet)
IP rating IP55
Warranty 5 years electronics
Dimensions 1.7”/45mm x 5.1”/132mm x 3”/72mm (w
x h x d)
Data Output Module Specification - Communication
Technology: 4-20mA & MODBUS RTU
Variable 4-20mA MODBUS
Channels of
communication
4 (1 per sensor)1 over RS 485
Dimensions are as
per alarm
Sensor measured
variable CO2 or O2
All variables,
alarm status and
faults
OFFICE OF THE FIRE MARSHAL – LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
July 6, 2020
Superior Electrical Mechanical & Plumbing
8613 Helms Avenue
Rancho Cucamonga, CA 91730
Re: CO2 Detector/Alarm Plan Review – TARGET (BEVERAGE DISPENSERS)
FSINSP2020-0002 / 78935 HIGHWAY 111, LA QUINTA, CA 92253
The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
1) Carbon Dioxide Alarm Monitoring systems shall be installed as required by CFC 5307.3.2 when the
Ventilation (5307.3.1) option is not utilized in relation to beverage dispensing operations utilizing
100+ pounds of insulated liquid carbon dioxide.
2) Carbon Dioxide sensors shall be provided within 12 inches of the floor in the area where the gas is
expected to accumulate or other approved locations.
3) The system shall: (1) Activate an audible and visible supervisory alarm at a normally attended
location upon detection of a carbon dioxide concentration of 5,000 PPM (0.5%); (2) Activate an
audible visible alarm within the room or immediate area where the system is installed upon detection
of a carbon dioxide concentration of 30,000 PPM (3%).
4) CFC 916.9 Signage: Signs shall be provided adjacent to gas detection system alarm signaling
devices that advise occupants of the nature of the signals and actions to take in response to the
signal.
5) CFC 916.11 Inspection, Testing & Sensor Calibration: Inspection and testing of gas detection
systems shall be conducted not less than annually, Sensor calibration shall be confirmed at the time
of sensor installation and calibration shall be performed at the frequency specified by the sensor
manufacturer. The Fire Department approved plans and conditions letter must be at the job site.
6) NFPA 704 hazard placard and signage is required to be displayed at approved locations.
7) A final inspection along with system activation testing is required to be observed by the Office of the
Fire Marshal.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
RIVERSIDE COUNTY FIRE PROTECTION PLANNING
RECORD OF INSPECTIONS / PERMIT CARD
THIS CARD IS TO REMAIN ON SITE AT ALL TIMES.
INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE.
JOB
ADDRESS: 78935 HIGHWAY 111 (TARGET) PERMIT#: FSINSP2020-0002 DATE
ISSUED: 7/6/2020
DESCRIPTION: CO2 ALARM SYSTEM (BEVERAGE DISP.) CONTRACTOR: SUPERIOR ELEC., MECH. & PLUMBING
HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS
Thrust block pre-pour Door fan test
UG rough piping Abort test
UG hydro Mechanical shutdown
Flush Detector test
Final E F Deluge/pre-action
SPRINKLER U.G. Final E F
Thrust block pre-pour UST/AST TANK
UG rough piping Installation
UG hydro Removal
Flush Emergency shut off
Final E F Primary piping
FIRE SPRINKLER Secondary piping
Weld inspection Dispensers & shear valves
Overhead rough piping Final E F
Overhead hydro MISC. INSPECTIONS
UG flush / OK to connect Spray booths
Main drain/inspectors’ test Hood/duct extinguishing
High pile storage High pile rack storage
In-rack sprinklers H.P. vents/access/corridors
Hose racks Tract access/hydrant verification
Final E F Access & Address verification
HOOD EXTINGUISHING OTHER CONST. PERMIT
Detection system
Function test
Gas/electrical shut-off
Nozzle model/placement
Fire alarm connection
Final E F
SPRAY BOOTHS FIRE CODE PERMIT(S)
Installation CO2 SENSOR
Air flow test CO2 MONITOR
Mechanical interlock CO2 ALARM
Extinguishing system SIGNAGE
Fire alarm connection
Final E F
FIRE ALARM KNOX SYSTEM
Rough-wire inspection Building Knox box
Function test Gate access Knox box/padlock
Duct detectors/velocity BUILDING INSPECTIONS
24 hr. battery test T/I final
Sprinkler monitoring Shell final
Final E F Final for occupancy
FINAL INSPECTION DATE: INSPECTORS SIGNATURE:
**WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE**
78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131
INSPECTION NOTES
1. Sway bracing and hangers will be inspected at the time of rough piping inspection.
2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler
Systems)
3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required.
4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test.
5. Contractor shall supply all testing equipment, access and operating instructions at time of test.
6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the
affected system to be covered or hidden.
POLICIES ON FIELD INSPECTIONS
A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when
scheduling inspections. For City of La Quinta inspections call: (760) 777-7131.
B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence
without approved plans.
C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required
to schedule the necessary inspections and be present on site for inspections.
D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not
on site or where previously noted corrections have not been completed.
E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into
the structure until clearance has been granted by the Fire Dept and Building Official.
F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance
has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official.
INSPECTION NOTES:
THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE
AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS.
THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180
DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE.
THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE
REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY.