BUILDING ENERGY ANALYSIS REPORT I
PROJECT:
New Residence
53-732 Via Pisa, The Hideaway
La Quinta, CA 92253
Project Designer:
Helton, DeFord & Associates
1261 N. Big Spring Street
Anaheim, Ca 92807
(909) 957-4550
Report Prepared by:
Tim Scott
Scott Design and Title 24, Inc,
77-085 Michigan Drive
Palm Desert, Ca 92211
(760) 200-4780
Job Number:
Date:
1/25/2013
'16QE1V'ED
APR 22 2013
CDMCITY MU/V1L4 4Ur/V.r
ry D�yEtDpMENT
CITY OF LA QUINTA
BUILDING & SAFETY DEPT
APPROVED
FOR %ONSTRI1c:rnnti
�—�—�-4 1/b -1
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. this program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2008 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC — www.energysoft.com.
W
Y,
0
•
0
n
TABLE OF CONTENTS I
Cover Page 1
Table of Contents 2
Form CF -1 R Certificate of Compliance 3
Form MF -1 R Mandatory Measures Summary 12
HVAC System Heating and Cooling Loads Summary 15
Room Load Summary 18
Room Heating Peak Loads 21
Room Cooling Peak Loads 26
EnergyPro 5.1 by Energysoft Job Number: ID: User Number: 6712 1
•
•
•
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
New Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Add itioWNW ration
Date
1/25/2013
Project Address
53-732 Via Pisa, The Hideaway La Quint
California Energy Climate Zone
CA Climate Zone 15
I Total Cond. Floor Area
5,132
Addition
n/a
# of Stories
1
FIELD INSPECTION ENERGY CHECKLIST
O Yes O No HERS Measures --If Yes, A CF -4R must be provided per Part G of 5 of this form.
O Yes O No Special Features --If Yes, see Part 2 of 5 of this form for details.
INSULATION
Construction Type
Area Special
Cavity Features see Part 2 of 5 Status
Roof Wood Framed Attic R-38 5,132 Radiant Barrier New
Wall Wood Framed R-21 4,590 New
Slab Unheated Slab -on -Grade
None 5,132 Perim = 482' New
Door Opaque Door
None 24 New
FENESTRATION U- Exterior
Orientation Area Factor SHGC Overhang Sidefins Shades Status
Left (N) 195.0 0.390
0.32 none none Bug Screen New
Rear (E) 176.0 0.390
0.32 none none Bug Screen New
Rear (SE) 36.0 0.390
0.32 none none Bug Screen New
Right (S) 254.8 0.390
0.32 none none Bug Screen New
Right (S) 6.0 0.550
0.39 none none Bug Screen New
Front (w) 30.0 0.390
0.32 none none Bug Screen
New
Rear (E) 160.0 0.390
0.32 2.0 none Bug Screen
New
Rear (E) 205.0 0.390
0.32 15.0 none Bug Screen
New
Right (S) 230.0 0.550
0.39 15.0 none Bug Screen
New
Right (S) 110.0 0.390
0.32 10.0 none Bug Screen
New
Front (w) 18.0 0.390
0.32 15.0 none Bug Screen
New
HVAC SYSTEMS
Qty. Heating Min. Eff
Cooling Min. Eff Thermostat Status
1 Central Furnace 80% AFUE
Split Air Conditioner 15.0 SEER Setbacl.
New
1 Central Furnace 80% AFUE
Split Air Conditioner 16.0 SEER Setback
New
2 Central Furnace 80% AFUE
Split Air Conditioner 15.0 SEER Setback
New
HVAC DISTRIBUTION
Location Heating
Duct
Cooling Duct Location R -Value Status
HVAC 1 Ducted
Ducted Attic, Ceiling Ins, vented 3.0
New
HVAC 2 Ducted
Ducted Attic, Ceiling Ins, vented d.0
New
HVAC 3 & 4 Ducted
Ducted Attic, Ceiling Ins, vented 3.0
New
WATER HEATING
Qty. Type Gallons Min. Eff Distribution Status
2 Small Gas 75
0.65 All Pipes Ins
New
EnergyPro 5.1 by Ener Soft User Number: 6712
Run Code: 2013-01-25710:36:16 ID:
Page 3 of 31
•
•
•
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
New Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition./Alteration
Date
1/25/2013
'Project Address
53-732 Via Pisa, The Hideaway La Quint
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
5,132
Addition
n/a
# of Stories
1
FIELD INSPECTION ENERGY CHECKLIST
IZI Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION Area Special
Construction Type Cavity Features see Part 2 of 5 Status
FENESTRATION U- Exterior
Orientation Area Factor SHGC Overhang Sidefins Shades Status
Front (w) 80.0 0.950 0.49 2.0 none Bug Screen New
Front (w) 120.0 0.390 0.32 10.0 none Bug Screen New
HVAC SYSTEMS
Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status
HVAC DISTRIBUTION Duct
Location Heating Cooling Duct Location R -Value Status
WATER HEATING
Qty. Type Gallons Min. Eff Distribution Status
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-01-25710:36:16 ID:
Page 4 of 31
•
0
•
PERFORMANCE CERTIFICATE: Residential Part 2 of 5 CF -1 R
Project Name
New Residence
Building Type ® Single Family ❑ Addition Alone
1 ❑ Multi Family ❑ Existing+ Addition/Alteration
Date
1/25/2013
SPECIAL FEATURES INSPECTION CHECKLIST
The enforcement agency should pay special attention to the items specified in this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The enforcement agency
determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of
the special justification and documentation submitted.
The HVAC System HVAC 1 must serve only Sleeping Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
se arate thermostat. In addition the air flow re uirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
HIGH MASS Design - Venfy Thermal Mass: 7 8. It- Covered Slab Floor, 3.500" thick at Zone 1 Master Suite
HIGH MASS Design - Verify Thermal Mass: 422.0 ft' Exposed Slab Floor, 3.500" thick at Zone 1 Master Suite
HIGH MASS Design - Verify Thermal Mass: 332.0 ft2 Covered Slab Floor, 3.500" thick at Bedroom 4 -Office
HIGH MASS Design - Verify Thermal Mass: 63.0 ft' Exposed Slab Floor, 3.500" thick at Bedroom 4 -Office
The HVAC System HVAC 2 must serve only Sleeping Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
separate thermostat. In addition the air flow re uirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
HIGH ASS Design - Verify Thermal Mass: 371.0 ft' Covered Slab Floor, 3.500" thick at Guest Suite
HIGH MASS Design - Verify Thermal Mass: 72.0 ft' Exposed Slab Floor, 3.500" thick at Guest Suite
The HVAC System HVAC 3 & 4 must serve only Living Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
separate thermostat. In addition the air flow re uirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
HIGH MASS Design - Verify Thermal Mass: 182.0 ft' Covered Slab Floor, 3.500" thick at Living Zone
HIGH MASS Design - Verify Thermal Mass: 2,526.0 ft2 Exposed Slab Floor, 3.500" thick at Living Zone
HIGH MASS Design - Verify Thermal Mass: 316.0 ft2 Covered Slab Floor, 3.500" thick at Bedroom 3
HIGH MASS Design - Verify Thermal Mass: 60.0 ft2 Exposed Slab Floor, 3.500" thick at Bedroom 3
HERS REQUIRED VERIFICATION
Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a
completed CF -4R form for each of the measures listed below for final to be given.
The Cooling System Carrier 24AN6660158CVX110 includes credit for a 12.5 EER Condenser. A certified HERS rater must field verity the installation
of the correct Condenser.
The HVAC System HVAC 1 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 1 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
The Cooling System Carrier 24ANB624158CVX070 includes credit for a 13.0 EER Condenser. A certified HERS rater must field verify the installation
of the correct Condenser.
The HVAC System HVAC 2 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 2 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
The Cooling System Carrier 24ANB660158CVX110 includes credit for a 12.5 EER Condenser. A certified HERS rater must field verify the installation
of the correct Condenser.
The HVAC System HVAC 3 & 4 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 3 & 4 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
gyPr, 5.1 by EnergySoft User Number: 6712 RunCode: 2013-01-25710:36:16 ID: Page 5 of 31
[—E-n—er
•
•
•
PERFORMANCE CERTIFICATE: Residential Part 2 of 5) CF -1 R
Project Name
New Residence
Building Type ® Single Family ❑ Addition Alone
1 ❑ Multi Family ❑ Existing+ Additio-i/Alteration
Date
1/25/2013
SPECIAL FEATURES INSPECTION CHECKLIST
The enforcement agency should pay special attention to the items specified in this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The erforcement agency
determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of
the special justification and documentation submitted.
The Roof R-38 Roof(R.38.2x 14.16) includes credit for a Radiant Barrier that is Continuous meeting eligibility and installadon criteria as specified in
Residential Ap2endix RA4.2.2.
HERS REQUIRED VERIFICATION
Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a
completed CF -4R form for each of the measures listed below for final to be given.
—En—emyPro 5.1 by EnemySoft User Number: 6712 RunCode: 2013-01-25T10:36:16 ID: Page 6 of 31
•
•
PERFORMANCE CERTIFICATE: Residential Part 3 ,of 5) CF -1 R
Project Name
Building Type m Single Family ❑ Addition Alone
Date
New Residence
❑ Multi Family ElExisting+ Addition/Alteration
1/25/2013
ANNUAL ENERGY USE SUMMARY
Standard Proposed Margin
TDV kBtu/ft2 r
Space Heating 4.80 5.02 -0.22
Space Cooling 55.56 50.06 5.49
Fans 11.07 15.00 -3.93
Domestic Hot Water 7.11 7.65 -0.54
Pumps 0.00 0.00 0.00
Totals 78.53 77.74 0.79
Percent Better Than Standard: 1.0%
BUILDING COMPLIES - HERS VERIFICATION REQUIRED
Fenestration
Building Front Orientation: (w) 270 deg Ext. Walls/Roof Wall ArEa Area
Number of Dwelling Units: 1.00 (W) 14338 248
Fuel Available at Site: Natural Gas (N) x895 195
Raised Floor Area: 0 (E) '338 577
Slab on Grade Area: 5.132 (S) x,664 601
Average Ceiling Height: 12.1 Roof -132 0
Fenestration Average U -Factor: 0.44 TOTAL: 1,621
Average SHGC: 0.34 Fenestration/CFA Ratio: 31.6%
REMARKS
STATEMENT OF COMPLIANCE
This certificate of compliance lists the building features and specifications needed
to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the
Efficiency Standards of the California Code of Regulations.
The documentation author hereby certifies that the documentation is accurate and complete.
Documentation Author
Company Scott Design and Title 24, Inc,
1!2 3
Address 77-085 Michigan Drive Name Tim Scott
City/State/ZipCity/State/Zip Palm Desert, Ca 92211 Phone (760) 200-4780 Signed Date
The individual with overall design responsibility hereby certifies that the proposed building desicn represented in this set
of construction documents is consistent with the other compliance forms and worksheets, with he specifications, and
with any other calculations submitted with this permit application, and recognizes that compliance using duct design,
duct sealing, verification of refrigerant charge, insulation installation quality, and building envelope sealing require
installer testing and certification and field verification by an approved HERS rater.
Designer or Owner (per Business & Professions Code)
Company Helton, DeFord & Associates
Address 1261 N. Big Spring Street Name Jim Deford 2
Pioned
City/State/Zip Anaheim, Ca 92807 Phone (909) 957-4550 License # Date
Ener Pro 5.1 by Ene Soft User Number: 6712 RunCode: 2013-01-25710:36:16 /D: Page 7 of 31
•
•
•
CERTIFICATE OF COMPLIANCE: Residential
Part 4 of 5) CF -1 R
Project Name
New Residence
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
1112512013
OPAQUE SURFACE DETAILS
Surface
Type Area
U- Insulation Joint Appendix
Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
Roof
1,210
0.026 R-38
270
0 New 4.2.1-A9
Zone 1 Master Suite
Well
283
0.069 R-21
0
90 New 4.3.1-A6
Zone 1 Master Suite
Wall
238
0.669 R-21
90
90 New 4.3.1-A6
Zone 1 Master Suite
lNall
14
0.069 R-21
135
90 New 4.3.1-A6
Zone 1 Master Suite
Wall
276
0.069 R-21
1801
90 New 4.3.1-A6
Zone 1 Master Suite
Wall
45
0.069 R-21
270
90 New 4.3.1-A6
Zone 1 Master Suite
Slab
788
0.730 None
0
180 New 4.4.7-A1
Zone 1 Master Suite
Slab
422
0.730 None
0
180 New 4.4.7-A1
Zone 1 Master Suite
Roof
395
0.026 R-38
270
0 New 4.2.1-A9
Bdrm 4 -Office
Wall
108
6.069 R-21
0
90 New 4.3.1-A6
Bdrm 4 -Office
Wall
241
0.069 R-21
180
90 New 4.3.1-A6
Bdrm 4 -Office
Wall
25
0.069 0-21
270
90 New 4.3.1-A6
Bdrm 4 -Office
Slab
332
0.730 None
0
180 New 4.4.7-A1
Bdrm 4 -Office
Slab
63
0.730 None
0
180 New 4.4.7-A1
Bdrm 4 -Office
Roof
443
0.026 1 R-38
270
0 New 4.2.1-A9
Guest Suite
Wall
1 2711
0.069 1 R-21
0
90 New 14.3.1-A6
Guest Suite
FENESTRATION SURFACE DETAILS
ID
Type Area U -Factor
SHGC
Azm Status
Glazing Type
Location/Comments
1
Window
24.0 0.390 NFRC
0.32 NFRC 0 New
Double Non -Metal Tinted
Zone 1 Master Suite
2
Window
120.0 0.390 NFRC
0.32 NFRC 90 New
Double Non -Metal Tinted
Zone 1 Master Suite
3
Window
56.0 0.390 NFRC
0.32 NFRC 90 New
Double Non -Metal Tinted
Zone 1 Master Suite
4
Window
36.0 0.390 NFRC
0.32 NFRC 135 New
Double Non -Metal Tinted
Zone 1 Master Suite
5
Window
56.0 0.390 NFRC
0.32 NFRC 180 New
Double Non -Metal Tinted
Zone 1 Master Suite
6
Window
32.0 0.390 NFRC
0.32 NFRC 180 New
Double Non -Metal Tinted
Zone 1 Master Suite
7
Window
20.0 0.390 NFRC
0.32 NFRC 180 New
Double Non -Metal Tinted
Zone 1 Master Suite
8
Window
6.0 0.550 NFRC
0.39 NFRC 180 New
Pocket Doors
Zone 1 Master Suite
9
Window
6.0 0.390 NFRC
0.32 NFRC 0 New
Double Non -Metal Tinted
Bdrm 4 -Office
10
Window
36.0 0.390 NFRC
0.32 NFRC 0 New
Double Non -Metal Tinted
Bdrm 4 -Office
11
Window
13.8 0.390 NFRC
0.32 NFRC 180 New
Double Non -Metal Tinted
Bdrm 4 -Office
12
Window
13.8 0.390 NFRC
0.32 NFRC 180 New
Double Non -Metal Tinted
Bdrm 4 -Office
13
Window
6.0 0.390 NFRC
0.32 NFRC 180 New
Double Non -Metal Tinted
Bdrm 4 -Office
14
Window
9.0 0.390 NFRC
0.32 NFRC 0 New
Double Non -Metal Tinted
Guest Suite
15
Window
24.0 0.390 NFRC
0.32 NFRC 0 New
Double Non -Metal Tinted
Guest Suite
16
lWindow
6.0 0.390 NFRC
0.32 NFRC 0 New
Double Non -Metal Tinted
Guest Suite
() Ll -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type SHGC
Window
Hat Wd
Ove hanq Left Fin
Len Hat LExt I RExt Dist Len
Ri ht Fin
Hat Dist Len H t
1
Bug Screen
0.76
2
Bug Screen
0.76
3
Bug Screen
0.76
4
Bug Screen
0.76
5
Bug Screen
0.76
6
Buq Screen
0.76
7
Bug Screen
0.76
8
Bug Screen
0.76
9
Buq Screen
0.76
Bu Screen
0.76Bu
Screen
0.76
F11
Bug Screen
0.76
Bu Screen
0.76
Buq Screen
0.76
15
Bug Screen
0.76
16
JBug Screen
0.76
Ener
Pro 5.1 by EnerqySoft User Number: 6712
RunCode: 2013-01-25710:36:16 /D:
Page 8 of 31
•
•
CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5) CF -1 R
Project Name
New Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
1/25/2013
OPAQUE SURFACE DETAILS
Surface
ape Area
U- Insulation
Factor Caviti I Exterior Frame Interior Frame Azm
Joint Appendix
Tilt I Status 4 Location/Comments
Wall
95
0.069 R-21
90
90 New 4.3.1-A6
Guest Suite
Wall
276
0.069 R-21
180
90 New 4.3.1-A6
Guest Suite
Wall
190
0.069 R-21
270
90 New 4.3.1-A6
Guest Suite
Slab
371
0.730 None
0
180 New 4.4.7-A1
Guest Suite
Slab
72
0.730 None
0
180 New 4.4.7-A1
Guest Suite
Roof
2,708
0.026 R-38
270
0 New 4.2.1-A9
Zone 3 Great/Game/Kitch
Wall
874
0.069 R-21
0
90 New 4.3.1-A6
Zone 3 Great/Game/Kitch
Door
24
0.500 None
0
90 New 4.5.1-A4
Zone 3 Great/Game/Kitch
Wall
279
0.069 R-21
90
90 New 4.3.1-A6
Zone 3 Great/Game/Kitch
Wall
89
0.069 R-21
180
90 New 4.3.1-A6
Zone 3 Great/Game/Kitch
Wall
700
0.069 R-21
2701
90 New 4.3.1-A6
Zone 3 Great/Game/Kitch
Slab
182
0.730 None
0
180 New 4.4.7-A1
Zone.3 GreabGamelKitch
Slab
2,526
0.730 None
0
180 New 4.4.7-A1
Zone 3 Great/Game/Kitch
Roof
376
0.026 R-38
270
0 New 4.2.1-A9
Bdrm 3
Wall
140
0.069 R-21
0
90 New 4.3.1-A6
1Bdrrn 3
Wall
135
0.069 R-21
90
90 New 4.3.1-A6
1Bdrrn 3
FENESTRATION SURFACE DETAILS
ID
Type Area LI -Factor'
SHGC2
Azm Status GlazingType
Location/Comments
17
Window
6.0 0.390 NFRC
0.32 NFRC 180 New
Double Non -Metal Tinted
Guest Suite
18
Window
13.8 0.390 NFRC
0.32 NFRC 180 New
Double Non -Metal Tinted
Guest Suite
19
Window
13.8 0.390 NFRC
0.32 NFRC 180 New
Double Non -Metal Tinted
Guest Suite
20
Window
30.0 0.390 NFRC
0.32 NFRC 270 New
Double Non -Metal Tinted
Guest Suite
21
Window
32.0 0.390 NFRC
0.32 NFRC 0 New
Double Non -Metal Tinted
IZone 3 Great/Game/Kitchen/N
22
Window
32.0 0.390 NFRC
0.32 NFRC 0 New
Double Non -Metal Tinted
JZone 3 Great/Game/Kitchen/N
23
Window
7.0 0.390 NFRC
0.32 NFRC 0 New
Double Non -Metal Tinted
Zone 3 Great/Game/Kitchen/N
24
Window
7.0 0.390 NFRC
0.32 NFRC 0 New
Double Non -Metal Tinted
Zone 3 GreatfGame/Kitche2
25
Window
4.0 0.390 NFRC
0.32 NFRC 0 New
Double Non -Metal Tinted
Zone 3 GreabGame/KitchenAV
26
Window
4.0 0.390 NFRC
0.32 NFRC 0 New
Double Non -Metal Tinted
Zone 3 Great/Game/Kitchen/N
27
Window
4.0 0.390 NFRC
0.32 NFRC 0 New
Double Non -Metal Tinted
Zone 3 GreaUGameXitchenM
28
Window
160.0 0.390 NFRC
0.32 NFRC 90 New
Double Non -Metal Tinted
Zone 3 Great/Game/Kitchenll
29
Window
205.0 0.390 NFRC
0.32 NFRC 90 New
Double Non -Metal Tinted
Zone 3 Great/Game/Kitchenfi
30
Window
230.0 0.550 NFRC
0.39 NFRC 180 New
Patio Doors
Zone 3 Great/Game/Kitchen/N
31
Window
110.0 0.390 NFRC
0.32 NFRC 180 New
Double Non -Metal Tinted
Zone 3 Great/Game/Kitchen/N
32
Window
18.0 0.390 NFRC
0.32 NFRC 270 New
Double Non -Metal Tinted
Zone 3 GreaUGame/Kitchen/N
(1) U -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type SHGC
Window
H t Wd
Ove hanq Left Fin
Len H t LExt RExt Dist Len
Ri ht Fin
H t Dist Len H t
17
Bug Screen
0.76
18
Bug Screen
0.76
19
Bug Screen
0.76
20
Bug Screen
0.76
21
Bug Screen
0.76
22
Bug Screen
0.76
23
Bug Screen
0.76
24
Bug Screen
0.76
25
Bug Screen
0.76
26
Bug Screen
0.76
27
Bug Screen
0.76
28
Bug Screen
0.76
10.0 16.0 2.0 0.1
2.0 2.0
29
Bug Screen
0.76
10.0 20.4 15.0 0.1
15.0 15.0
30
-Bug Screen
0.761
10.01 23.0 15.0 0.1
15.0 15.0
31
16ug Screen
0.761
10.01 11.0 10.0 0.1
10.0 10.0
32
JBug Screen
1 0.761
10.01 18.5 15.0 0.11
15.0 15.0
EnergyPro
5.1 by EnergySoft User Number.' 6712
Run Code: 2013.01-25710:36:16 ID:
Page 9 of 31
•
CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R
Project Name
New Residence
Building Type m Single Family ❑ Addition Alone
1 ❑ Multi Family ❑ Existing+ Addition/Alteration
Date
1112512013
OPAQUE SURFACE DETAILS
Surface U- Insulation Joint Appendix
Type Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
Wall
180 0.069 R-21
180 90 New 4.3.1-A6
Bdrm 3
Wall
130 0.069 R-21
270 90 New 4.3.1-A6
Bdrm 3
Slab
316 0.730 None
0 180 New 4.4.7-A1
Bdan 3
Slab
60 0.730 None
0 180 New 4.4.7-A1
Bdrm 3
FENESTRATION SURFACE DETAILS
ID
T e Area U -Factor SHGC
Azm Status GlazingType
Location/Comments
33
Window 20.0 0.950 NFRC 0.49 NFRC 270 New Entry Door
Zone 3 Great/Game/Kitchenfi
34
Window 40.0 0.950 NFRC 0.49 NFRC 270 New Entry Door
Zone 3 Great/GameMitchen/N
35
Window 20.0 0.950 NFRC 0.49 NFRC 270 New Ent Door
Zone 3 GreatlGameXitchenM
36
Window 120.0 0.390 NFRC 0.32 NFRC 270 New Double Non -Metal Tinted
Zone 3 GreaUGameXitchen/N
37
Window 48.0 0.390 NFRC 0.32 NFRC 180 New Double Non -Metal Tinted
Bdrm 3
38
Window 24.0 0.390 NFRC 0.32 NFRC 180 New Double Non -Metal Tinted
Bdrm 3
39
Window 3.8 0.390 NFRC 0.32 NFRC 180 New Double Non -Metal Tinted
Bdrm 3
40
Window 3.8 0.390 NFRC 0.32 NFRC 180 New Double Non -Metal Tinted
Bdrm 3
I
I
i
1
(1) Ll -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Window
Exterior Shade Type SHGC H t I Wd
Ove hang Left Fin
Len H t LExt RExt Dist Len
Right Fin
H t Dist Len H t
33
Bug Screen 0.76 10.01 2.0 2.0 0.1 2.0 2.0
34
Bug Screen 0.76 10.0 4.0 2.0 0.1 2.0 2.0
35
Bug Screen 0.76 10.0 2.0 2.0 0.1 2.0 2.0
36
Bug Screen 0.76 10.0 12.0 10.0 0.1 10.0 10.0
37
Bug Screen 0.76
38
Bug Screen 0.76
39
Bug Screen 0.76
40
Bug Screen 0.76
EnergyPro
5.1 by EnergySoft User Number: 6712
RunCode: 2013-01-25710:36:16 ID:
Pae 10 of 31
•
•
0
CERTIFICATE OF COMPLIANCE: Residential Part 5 of 5
CF -1 R
Project Name
New Residence
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
1112512013
BUILDING ZONE INFORMATION
System Name Zone Name
Floor Area ft
New Existinq Altered Removed Volume Year Built
HVAC 1 Zone 1 Master Suite
1,210
14,278
Bedroom 4 -Office
395
3,832
HVAC 2 Guest Suite
443
4,430
HVAC 3 & 4 Living Zone
2,708
35,746
Bedroom 3
376
3,760
Totals 5,1321 01 01 0
HVAC SYSTEMS
System Name Qty. Heating Type
Min. Eff. Cooling Type Min. Eff. Thermostat Type Status
HVAC 1 1 Central Furnace
80% AFUE Split Air Conditioner 15.0 SEER Setback
New
HVAC 2 1 Central Furnace
80% AFUE S lit Air Conditioner 16.0 SEER Setback
New
HVAC 3 & 4 2 Central Furnace
80% AFUE Split Air Conditioner 15.0 SEER Setback
New
HVAC DISTRIBUTION
System Name Heating
Duct
Cooling Duct Location R -Value
Ducts
Tested? Status
HVAC 1 Ducted Ducted Attic, Ceiling Ins, vented 8.0
m New
HVAC 2 Ducted Ducted Attic, Ceiling Ins, vented 8.0
m New
HVAC 3 & 4 Ducted Ducted Attic, Ceiling Ins, vented 8.0
D New
WATER HEATING SYSTEMS
S stem Name
Ot .
Type
Distribution
Rated
Input
(Btu h)
Tank
Cap.
al
Energy
Factor
or RE
Standby
Loss or
Pilot
Ext.
Tank
Insul. R-
Value
Status
Bradford -White 75 Gal
2
Small Gas
All Pipes Ins
65,000
75
0.65
n/a
n/a
New
MULTI -FAMILY WATER
HEATING
DETAILS
HYDRONIC
HEATING
SYSTEM
PIPING
Control
Hot Water Piping Length
ft
- o
m
a —
System Name
Pipe
Len th
Pipe
Diameter
Insul.
Thick.
Oty. HP
Plenum Outside Buried
❑
Ener Pro 5.1 by EnergySoft User Number: 6712
RunCode: 2013-01-25710:36:16 ID:
Pae 11 of 31
r�
U
�J
MANDATORY MEASURES SUMMARY: Residential Pae 1 of 3 MF -1 R
Project Name
Date
New Residence
1 1/25/2013
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD, or CF -
1 R -ALT Form) shall supersede the items marked with an asterisk (*) below. This Mandatory Measures Summary shall be incorporated
into the permit documents, and the applicable features shall be considered by all parties as minimum component performance
specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R-
Form with plans.
Building Envelope Measures:
116(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§116(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified LI -Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of 10-111 (a).
117: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed.
118(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF -6R Form.
§118(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §118(i) when the
installation of a Cool Roof is specified on the CF -1 R Form.
*§1 50 a : Minimum R-19 insulation in wood -frame ceiling orequivalent LI -factor.
150(b): Loose fill insulation shall conform with manufacturer's installed design labeled R -Value.
*§1 50 c : Minimum R-13 insulation in wood -frame wall orequivalent Ll -factor.
*§1 50 d : Minimum R-13 insulation in raised wood -frame floor orequivalent LI -factor.
150(f): Air retarding wrap is tested labeled and installed according to ASTM E1677-95 2000 when specified on the CF -1 R Form.
150 : Mandato Vapor barrier installed in Climate Zones 14 or 16.
"§150(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance
rate is no qreater than 2.0perm/inch and shall be protected from physical damage and UV light deterioration.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
1 50 e 1 A: Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150(e)1 B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a with a readily accessible, operable, and tight -fitting damper and or a combustion -air control device.
§150(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the
outside of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110-§113: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy
Commission.
§113(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release
.valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of 113(c)5.
.§115: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances
'(appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and
'�s a heaters.
( 150(h): Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA.
150 i : Heating systems are equipped with thermostats that meet the setback requirements of Section 112(c).
§150(j)1 A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped
with insulation having an installed thermal resistance of R-12 or greater.
§150(j)1 B: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water
tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the
tank.
§1500)2: First 5 feet of hot and cold water pipes closest to water heater tank, non -recirculating systems, and entire length of
recirculating sections of hot water pipes are insulated per Standards Table 150-B.
§1500)2: Cooling system piping (suction, chilled water, or brine lines),and piping insulated between heating source and indirect hot
water tank shall be insulated to Table 150-B and Equation 150-A.
§150(j)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards Table
123-A.
150 ' 3A: Insulation is protected from damage, includino that due to sunlight, moisture equipment maintenance, and wind.
§150(j)3A: Insulation for chilled water piping and refrigerant suction lines includes a vapor retardant or is enclosed entirely in
conditioned space.
a§150(j)4: Solar water -heating systems and/or collectors are certified by the Solar Rating and Certification Corporation.
EnergyPro 5.1 by EnergySoff User Number: 6712 Run Code: 2013-01-25710:36:16 ID: Page 12 of 31
•
1�
MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 MF -1 R
Project Name
Date
New Residence
1 1/25/2013
§150(m)1: All air -distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections
601, 602, 603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-
4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that meets the
applicable requirements of UL 181, UL 181 A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is
used to seal openings reater than 1/4 inch, the combination of mastic and either mesh or tape shall be used
§150(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may
contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area
of the ducts.
§150(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes
unless such tape is used in combination with mastic and draw bands.
150(m)7: Exhaust fans stems have back draft or automatic dampers.
§150(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated
dampers.
§150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar
radiation that can cause degradation of the material.
150 m 10: Flexible ducts cannot have porous inner cores.
§150(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air
Quality in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation
,.required in Section 4 of that Standard.
Pool and Spa Heating Systems and Equipment Measures:
§114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and
shall not use electric resistance heating ora pilot light.
§114(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction
and return lines, or built-up connections for future solar heating.
114(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover.
§114(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or
ro rammed to run only during off-peak electric demand periods.
150 : Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150 .
Residential Lighting Measures:
§150(k)1: High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies
contained in Table 150-C and is not a low efficacy luminaire asspecified by §150(k)2.
§150(k)3: The wattage of permanently installed luminaires shall be determined asspecified by §130(d).
"-§150(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than
20 kHz.
§150(k)5: Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall contain
only high efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line -voltage socket or line -
voltage lamp holder; OR shall be rated to consume no more than five watts of power as determined by §130(d), and shall not contain a
medium screw -base socket.
§150(k)6: Lighting integral to exhaust fans, in rooms other than kitchens, shall meet the applicable requirements of §150(k).
150(k)7: All switching devices and controls shall meet the requirements of §150(k)7.
§150(k)8: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft2 or 100 watts for dwelling units larger than 2,500 ft2 may be
exempt from the 50% high efficacy requirement when: all low efficacy luminaires in the kitchen are controlled by a manual on occupant
sensor, dimmer, energy management system (EMCS), or a multi -scene programmable control system; and all permanently installed
-luminaries in garages, laundry rooms, closets greater than 70 square feet, and utility rooms are high efficacy and controlled by a
manual -on occupant sensor.
§150(k)9: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of
illuminated cabinet.
EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2013-01-25710:36:16 ID: Page 13 of 31
1�
MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 MF -1 R
Project Name
Date
New Residence
1 1/25/2013
§150(k)10: Permanently installed luminaires in bathrooms, attached and detached garages, laundry rooms, closets and utility rooms
shall be high efficacy.
EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by a manual -on
occupant sensor certified to comply with the applicable requirements of §119.
EXCEPTION 2: Permanently installed low efficacy luminaires in closets less than 70 square feet are not required to be controlled by a
manual -on occupancy sensor.
§150(k)11: Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms,
closets, and utility rooms shall be high efficacy luimnaires. EXCEPTION 1: Permanently installed low efficacy luminaires shall be
allowed provided they are controlled by either a dimmer switch that complies with the applicable requirements of §119, or by a manual -
on occupant sensor that complies with the applicable requirements of §119. EXCEPTION 2: Lighting in detached storage building less
than 1000 square feet located on a residential site is not required to comply with 150 k 11.
§150(k)12: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters
Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the lumiunaire is airtight with air
leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between
the luminaire housing and ceiling.
§150(k)13: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more
-dwelling units, entrances, balconies, and porches, which are permanently mounted to a residential building or to other buildings on the
same lot shall be high efficacy. EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that
they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor,
and one of the following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an
astronomical time clock not having an override or bypass switch that disables the astronomical time clock; OR an energy management
control system (EMCS) not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2: Outdoor
luminaires used to comply with Exceptions to §150(k)13 may be controlled by a temporary override switch which bypasses the motion
sensing function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3: Permanently installed
luminaires in or around swimming pool, water features, or other location subject to Article 680 of the California Electric Code need not
be high efficacy luminaires.
§150(k)14: Internally illuminated address signs shall comply with Section 148; OR not contain a screw -base socket, and consume no
more than five watts of power as determined according to §130(d).
§150(k)15: Lighting for parking lots and carports with a total of for 8 or more vehicles per site shall comply with the applicable
requirements in Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable
requirements of Sections 130, 131, 134, and 146.
-§150(k)16: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more
,dwelling units shall be high efficacy luminaires. EXCEPTION: Permanently installed low efficacy luminaires shall be allowed provided
that they are controlled by an occupant sensors certified to comply with the applicable requirements of 119.
EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2013.01-25710:36:16 ID: Page 14 of 31
0
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
New Residence
Date
1/25/2013
System Name
HVAC 1
Floor Area
1,605
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL COOLING
CFM Sensible
Total Room Loads 1,135 20,776
Return Vented Lighting 0
Return Air Ducts 1,199
Return Fan 01
Ventilation 0 0
Supply Fan 0
Supply Air Ducts 1,199
TOTAL SYSTEM LOAD 1 23,175
PEAK COIL HTG.
PEAK
Heating System
Latent CFM
Sensible
Output perSystem 89,000
2,451 481
20,923
Total Output Btuh 89,000
Output Btuh/s ft 55.5
1,028
Cooling System
0
Output perSystem 57,5001
0 0
0
Total Output Btuh 57,500
2,451
0
Total Output ons 4.8
1,028
Total Output Btuh/s ft 35.8
Total Output s ft/Ton 335.0
1 22,980
'Air System
CFM perSystem
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
Carrier 24ANB660/58CVX110 39,016
7,496
89,000
Airflow cfm/s ft
1.25
Total Adjusted System Output 1 39,016
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
7,496 1 89,000
Aug 3 PM Jan 1 AM
Airflow cfm/Ton 417.4
Outside Air % 0.0%
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
ii :HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
i_ 26 OF
Outside Air
0 cfm
72 of
72 OF 113 °F 113 OF
n
[:ELL]
Heating Coil Supply Fan
113 OF
2,000 cfm ...................
ROOM
72 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air Ar
0 cfm
71 159 OF
I
71 /59°F 52/51 OF 52/51 OF
Cooling Coil Supply Fan 53 / 52 OF
2,000 cfm
51.6% -ROOM
70159 OF
l° EnergyPro 5.1 by EnergySoff
User Number: 6712 RunCode: 2013-01-25710:36:16 /D:
Page 15 of 31
0
0
"HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
New Residence
Date
1/25/2013
System Name
HVAC 2
Floor Area
443
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL COOLING
CFM Sensible
Total Room Loads 293 6,054
Return Vented Lighting 0
Return Air Ducts 350
Return Fan 01
Ventilation 0 0
Supply Fan 0
Supply Air Ducts 350
TOTAL SYSTEM LOAD 1 6,753
PEAK COIL HTG.
PEAK
Heating System
Latent CFM
Sensible
Output perSystem 51,000
769 144
9,016
Total Output Btuh 51,000
Output Btuh/s ft 115.1
443
.Cooling System
0
Output perSystem 24,000
0 0
0
Total Output Btuh 24,000
766
0
Total Output ons 2.0
443
Total Output Btuh/s ft 54.2
Total Output s ft/Ton 221.5
1 9,902
Air System
CFM perSystem
800
HVAC EQUIPMENT SELECTION
Airflow cfm
800
Carrier 24ANB624158CVX070 17,231
1,822
51,000
Airflow cfm/s ft 1.81
Alrf low cfm/Ton 400.0
Outside Air %
0.0%
Total Adjusted System Output 1 17,231
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
1,822 1 51,000
Aug 3 PM F Jan 1 AM
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
0 cfm
71 OF
71 OF 131 OF 131 OF
Heating Coil Supply Fan
131 OF
800 cfm
F'RO'0M_._...
72 OF
ILJ
,COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112 / 78 OF
Outside Air
0 cfm
70 / 58 OF
70158 OF 50 / 49 OF 50 / 49 OF
Cooling Coil Supply Fan 51 / 49 OF
800 cfm h^
47.1 % ROOM
70 / 58 OF
EnergyPro 5.1 by EnergySoR
User Number: 6712 RunCode: 2013-01-25710:36:16 /D:
Page 16 of 31
.,HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
New Residence
Date
1/25/2013
System Name
HVAC 3 & 4
Floor Area
3,084
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
2
COIL
CFM
Total Room Loads 2,654
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 89,000
48,313
4,541 1,243
53,688
Total Output Btuh 178,000
0
Output Btuh/s ft 57.7
2,789
2,639
Xooling System
0
0
Output per System 57,5001
0
0 0
0
Total Output Btuh 115,000
0
2,789
1 53,8911 4,5411
0
Total Output ons 9.6
2,639
Total Output Btuh/s ft 37.3
Total Output s ft/Ton 321.8
58,965
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
4,000
Carrier 24ANB660/58CVX110 78,397
14,621
178,000
Airflow cfm/s ft
1.30
Airflow cfm/Ton 417.4
Outside Air % 0.0%
Total Adjusted System Output 1 78,3971
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
14,621
Aug 3 PM
1 178,000
Jan 1 AM
Outside Air cfm/s ft 0.00
values above given at ARI conditions
•Note:
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
0 cfm
71 OF
71 OF 113 OF 113 OF
ion
Heating Coil Supply Fan
113 OF
4,000 cfm
ROOM J1
72 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air Arc
0 cfm
71 r 59 °1=
4r 1
71 /59°F 52/51 OF 52/51 OF
Cooling Coil Supply Fan 53 152 OF
4,000 cfm
51.4% ROOM
70.! 59 o F
4 LL E I
EnergyPro 5.1 by EnergySoff
User Number: 6712 RunCode: 2013-01-25710:36:16 ID:
Page 17 of 31
0
i
•
ROOM LOAD SUMMARY
20,776
2,451
481
Project Name
New Residence
1,135
20,776 ?
Date
1/25/2013
System Name
HVAC 1
Floor Area
1,605
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
Zone Name Room Name
Mult. CFM Sensible Latent
CFM Sensible Latent
CFM Sensible
Zone 1 Master Suite Zone 1 Master Suite
1 924 16,916 1,746
924 16,916 1,746
347 15,102
Bonn 4 -Office Bedroom 4 -Office
1 211 3,860 705
211 3,860 7051
134 5,821
PAGE TOTAL
TOTAL"
1,135
20,776
2,451
481
20,923
1,135
20,776 ?
2,4511
481
20, 923
Total includes ventilation load for zonal systems.
EnergyPro 5.1 by EnerqySoft User Number., 6712 RunCode: 2013-01-25710:36:16 ID: Pae 18 of 31
•
•
•
ROOM LOAD SUMMARY
Project Name Date
New Residence 1/25/2013
System Name Floor Area
HVAC 2 443
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. CFM I Sensible I Latent CFM I Sensible I Latent CFM I Sensible
Guest Suite I Guest Suite 1 1 1 2931 6,0541 766 2931 6,0541 766 1441 9,016
PAGE TOTAL
TOTAL*
293
6,054
766
144
9,016
293
6,054
766
144
9,016
Total includes ventilation load for zonal systems.
EnemyPro 5.1 by Enem
ySoft User Number: 6712 RunCode: 2013-01-25710:36:16 /D: Pae 19 of 31
•
•
ROOM LOAD SUMMARY
Project Name Date
New Residence 1/25/2013
System Name Floor Area
HVAC 3 & 4 3,084
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK I COIL HTG. PEAK
Zone Name Room Name Mult. CFM Sensible Latent CFM Sensible Latent CFM Sensible
Zone 3 GreaUGame/Kitche Living Zone 1 2,414 43,954 3,861 2,414 43,954 3,861 1,084 46,795
Bdrm 3 Bedroom 3 1 1 1 2391 4,359 681 239 4,359 6811 160 6,893
PAGE TOTAL
TOTAL*
2,654
48,313
4,541
1,243
53,688
2,654
48,313
4,541
1,243
53,688
Total includes ventilation load for zonal systems.
EnergyPro 5.1 by EnerqySoft User Number., 6712 RunCode: 2013-01-25710:36:16 ID: Page 20 of 31
L�
El
ROOM HEATING PEAK LOADS
Project Name
New Residence
Date
1/25/2013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Zone 1 Master Suite
Floor Area 1,210.0 ft'
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction Area
R-38 Roof(R. 38.2x 14.16) 1,210.0 X
R-21 Wall (W.19.2x6.16) 856.0 X
Double Non -Metal Tinted 344.0 X
Pocket Doors 6.0 X
Slab -On -Grade perim = 44.0 X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Items shown with an asterisk (') denote conduction through an interior surface to
Infiltration:[ 1.00 X 1.064 X 1,210 X
Schedule Air Sensible Area Ceiling
Fraction
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT OF Btu/hr
46 = 1,447
46 = 2,717
46 = 6,171
46 = 152
46 = 1,478
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
Page Total 11,965
/60] X 46 = 3,138
AT
0.0260
0.0690
0.3900
0.5500
0.7300
another room
11.80 X 0.269
Height ACH
TOTAL HOURLY HEAT LOSS FOR ROOM 15,102
EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2013-01-25710:36:16 ID: Page 21 of 31
•
•
•
ROOM HEATING PEAK LOADS
Project Name
Date
New Residence
1/25/2013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Bedroom 4 -Office
Time of Peak Jan 1 AM
Floor Area 395.0 ft'
Outdoor Dry Bulb Temperature 26 OF
Indoor Dry Bulb Temperature 72 OF
Conduction Area
U -Value
AT 'F Btu/hr
R-38 Roof(R. 38.2x 14.16) 395.0
X 0.0260
X
46 = 472
R-21 Wall (W.19.2x6.16) 374.4
X 0.0690
X
46 = 1,188
Double Non -Metal Tinted 75.6
X 0.3900
X
46 = 1,356
Slab -On -Grade perim = 53.0
X 0.7300
X
46 = 1,780
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Items shown with an asterisk (') denote conduction through an interior surface
to another room
Page Total 4,797
Infiltration:[ 1.00 X 1.064 X 395 X
9.70 X 0.328
/60] X 46 = 1,024
Schedule Air Sensible Area
Ceiling Height ACH
AT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 5,821
EnergyPro 5.1 by EnergySoR User Number: 6712 RunCode: 2013-01-25710:36:16 ID: Page 22 of 31
•
•
ROOM HEATING PEAK LOADS
Project Name
New Residence
Date
1/25/2013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Guest Suite
Floor Area 443.0 ft'
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value AT
0.0260 X 46
0.0690 X 46
0.3900 X 46
0.7300 X 46
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
another room Page Total
10.00 X 0.318 / 60 X
Height ACH AT
Btu/hr
= 530
= 2,642
= 1,841
= 2,854
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
1 7,867
46 = 1,149
R-38 Roof(R.38.2x14.16)
443.0
R-21 Wall (W. 19.2x6.16)
832.4
Double Non -Metal Tinted
102.6
Slab -On -Grade
perim = 85.0
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X
Schedule Air Sensible
Fraction
through an interior surface
1.064 X 443 X
Area
TOTAL HOURLY HEAT LOSS FOR ROOM 9,016
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-01-25710:36:16 ID: Page 23 of 31
•
U
•
ROOM HEATING PEAK LOADS
Project Name
New Residence
Date
1/25/2013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Floor Area
Indoor Dry Bulb Temperature
Living Zone
2,708.0 ft'
72 OF
Time of Peak
Outdoor Dry Bulb Temperature
Jan 1 AM
26 OF
Conduction
Area U -Value
2,708.0 X 0.0260
1,942.0 X 0.0690
703.0 X 0.3900
24.0 X 0.5000
230.0 X 0.5500
80.0 X 0.9500
perm = 235.0 X 0.7300
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
through an interior surface to another room
X 2,708 X 13.20 X 0.241
Area Ceiling Height ACH
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT OF
46 =
46 =
46 =
46 =
46 =
46 =
46 =
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
Page Total
/60] X 46 =
AT
Btu/hr
3,239
6,164
12,612
552
5,819
3,496
7,891
39,773
7,022
R-38 Roof(R. 38.2x 14.16)
R-21 Wall (W.19.2x6.16)
Double Non -Metal Tinted
Wood Door
Patio Doors
Entry Door
Slab -On -Grade
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM
46,795
EnergyPro 5.1 by En erg Soft User Number: 6712
RunCode: 2013-01-25710:36:16
ID:
Page 24 of 31
C]
•
ROOM HEATING PEAK LOADS
Project Name
New Residence
Date
1/25/2013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Bedroom 3
Floor Area 376.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction Area
R-38 Roof(R. 38.2x 14.16) 376.0
R-21 Wall (W. 19.2x6.16) 585.4
Double Non -Metal Tinted 79.6
Slab -On -Grade Ferim = 65.0
Items shown with an asterisk (') denote conduction through an interior surface
Infiltration:[ 1.00 X 1.064 X 376 X
Schedule Air Sensible Area
Fraction
U -Value
X 0.0260
X 0.0690
X 0.3900
X 0.7300
AT Or
X 46 =
Btu/hr
450
X
X
46
=
=
1,858
46
1,428
X
46
=
2,183
X
X
X
X
X
X
X
X
X
=
=
=
X
X
=
=
X
X
=
=
X
X
X
X
X
X
=
=
X
=
X
X
X
X
=
X
=
X
=
X
X
X
X
X
=
=
X
=
X
X
X
X
=
=
X
X
X
=
=
X
X
X
X
X
X
X
=
=
=
=
=
X
X
X
X
X
X
to another room
10.00 X 0.318
Ceiling Height ACH
X
=
X =
Page Total
/60] }. 46
AT
5,918
= 975
TOTAL HOURLY HEAT LOSS FOR ROOM 6,893
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-01-25T10:36:16 ID: Page 25 of 31
0 0 ..
C7
,7
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
1
New Residence
1/25/2013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Zone 1 Master Suite
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,210.0 ft'
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
I Outdoor Daily Range: .
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
R-38 Roof(R.38.2x 14.16)
W 1,210.0 X 0.0260
X 56.0 =
1,762
R-21 Wall (W. 19.2x6.16)
(N) 283.0 X 0.0690
X 23.0 =
449
R-21 Wall (W. 19.2x6.16)
(E) 238.0 X 0.0690
X 33.0 =
542
R-21 Wall (W.19.2x6.16)
(SE) 14.0 X 0.0690
X 31.0 =
30
R-21 Wall (W. 19.2x6.16)
(S) 276.0 X 0.0690
X 26.0 =
495
R-21 Wall (W.19.2x6.16)
(W) 45.0 X 0.0690
X 33.0 =
102
X
X =
X
X =
X
X =
Page Total
3,380
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Unshaded
Shaded
Fenestration
Orientation Area GLF Area GLF
Btu/hr
1 M
(N) 0.0 X 19.7 +
24.0 X 19.7
= 472
IN
(E) 0.0 X 19.7 +
120.0 X 38.7
= 4,641
1P
(E) 0.0 X 19.7 +
56.0 X 38.7
= 2,166
1P
(SE) 0.0 X 19.7 +
36.0 X 27.0
= 973
IP
(S) 0.0 X 19.7 +
56.0 X 19.7
= 1,106
1P
(S) 0.0 X 19.7 +
32.0 X 19.7
= 632
1Q
(S) 0.0 X 19.7 +
20.0 X 19.7
= 395
112
(S) 0.0 X 25.5 +
6.0 X 25.6
= 153
X +
X
=
Page Total
10,538
Btu/hr
Internal Gain
Occupants
1.0 Occupants X 230
Btuh/occ.
230
Equipment
0.0 Dwelling Unit X 1,600
_
Btu -
0
Infiltration: 1.064
X 0.94 X 66.21 X a2 =
2,768
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
16,916
Latent Gain
Btu/hr
1�0 Occupants X 200
Btuh/occ. =
200
Occu ants
Infiltration: 4,771
X 0.94 X 66.21 X 0.00523 =
1,546
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
1,746
EnergyPro 5.1 by EnerqvSoft
user Number: 6712 RunCode: 2013-01-25710:36:16 ID:
Page 26 of 31
� ! e
•
•
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name7112512013
ate
New Residence
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Bedroom 4 -Office
Outdoor Dry Bulb Temperature
112 OF
Floor Area
395.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
R-38 Roof(R.38.2x 14.16)
(W) 395.0 X 0.0260
X
56.0 =
575
R-21 Wall (W. 19.2x6.16)
(N) 108.0 X 0.0690
X
23.0 =
171
R-21 Wall (W. 19.2x6.16)
(S) 241.4 X 0.0690
X
26.0 =
433
R-21 Wall (W.19.2x6.16)
(W) 25.0 X 0.0690
X
33.0 =
57
X
X
=
X
X
=
X
X
=
X
X
=
X_J
X
=
Page Total
1,237
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF
Area
GLF
Btu/hr
122
(N) 0.0 X 19.7 +
6.0
X 19.7 =
118
123
(N) 0.0 X 19.7 +
36.0
X 19.7 =
708
113
(S) 0.0 X 19.7 +
13.8
X 19.7 =
273
114
(S) 0.0 X 19.7 +
13.8
X 19.7 =
273
115
(S) 0.0 X 19.7 +
6.0
X 19.7 =
118
X +
X -
X +
X -
X +
X -
X +
X -
Page Total
1,490
Internal Gain
Btu/hr
Occu ants
1.0 Occupants X 230
Btuh/occ.
=
230
Equipment
0.0 Dwelling Unit X 1,600
Btu
=
0
Infiltration: 1.064
X 0.94 X 21.61 X 42 =
903
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
3,860
Latent Gain
Btu/hr
Occupants
10 Occupants X 200
Btuh/occ.
=
200
Infiltration: 4,771
X 0.94 X 21.61 X 0.00523 =
505
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
705
Ene Pro 5.1 by Ener Soft
User Number: 6712 RunCode: 2013-01-25710:36:16 ID:
Page 27 of 31
•
•
0
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name7112512013
te
New Residence
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Guest Suite
Outdoor Dry Bulb Temperature
112 OF
Floor Area
443.0 8Z
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature
70 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
R-38 Roof(R.38.2x14.16)
(lM 443.0 X 0.0260
X
56.0 =
645
R-21 Wall (W. 19.2x6.16)
(N) 271.0 X 0.0690
X
23.0 =
430
R-21 Wall (W. 19.2x6.16)
(E) 95.0 X 0.0690
X
33.0 =
216
R-21 Wall (W. 19.2x6.16)
(S) 276.4 X 0.0690
X
26.0 =
496
R-21 Wall (W. 19.2x6.16)
(W) 190.0 X 0.0690
X
33.0 =
433
X
X
=
X
X
=
X
X
=
X J
X L=
Page Total
2,220
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area
GLF
Btu/hr
120
(N) 0.0 X 19.7 +
9.0
X 19.7 =
177
is
(N) 0.0 X 19.7 +
24.0
X 19.7 =
472
121
(N) 0.0 X 19.7 +
6.0
X 19.7 =
118
116
(S) 0.0 X 19.7 +
6.0
X 19.7 =
118
117
(S) 0.0 X 19.7 +
13.8
X 19.7 =
273
118
(S) 0.0 X 19.7 +
13.8
X 19.7 =
273
119
(W) 0.0 X 19.7 +
30.0
X 38.7 =
1,160
X +
X =
X +
1XI=
Page Total
2,591
Internal Gain
Btu/hr
Occupants
1.0 Occupants X 230
Btuh/occ.
=
230
Equipment
0.0 Dwelling Unit X 1,600
Btu
=
0
Infiltration: 1.064
X 0.94 X 24.24 X 42 =
1,013
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
6,054
Latent Gain
Btu/hr
Occupants
1.0 Occupants X 200
Btuh/occ.
=
200
Infiltration: 4,771
X 0.94 X 24.24 X 0.00523 =
566
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
766
EnemvPro 5.1 by EnemySoft
User Number: 6712 Run Code: 2013-01-25710:36:16 ID:
Page 28 of 31
r�
U
•
0
RESIDENTIAL ROOM COOLING LOAD SUMMARY I
Project Name Date
New Residence 1 1/25/2013
ROOM INFORMATION DESIGN CONDITIONS
Room Name Living Zone Outdoor Dry Bulb Temperature 112 OF
Floor Area 2,708.0 ft' Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temaerature 70 OF Outdoor Daily Range: 34 OF
Ooaaue Surfaces
R-38 Roof(R.38.2x 14.16)
R-21 Wall (W.19.2x6.16)
Wood Door
R-21 Wall (W.19.2x6.16)
R-21 Wall (W. 19.2x6.16)
R-21 Wall (W. 19.2x6.16)
Orientation
(N)
(E)
(S)
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CTD'
=
=
=
=
=
=
=
=
2,708.0
0.0260
56.0
874.0
0.0690
23.0
24.0
0.5000
23.0
279.0
0.0690
33.0
89.0
0.0690
26.0
700.0
0.0690
33.0
0.0
19.7
4.0
19.7
0.0
19.7
4.0
J
I=
19.7
4.0
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded Unshaded
Fenestration
104
105
106
107
109
110
111
1J
1L
(N)
(E)
Btu/hr
3,943
1,387
276
635
160
1,594
1 7.9951
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
(
:(
GLF
=
=
=
=
=
=
=
=
=
0.0
19.7
32.0
19.7
0.0
19.7
32.0
19.7
0.0
19.7
7.0
19.7
0.0
19.7
7.0
19.7
0.0
19.7
4.0
19.7
0.0
19.7
4.0
19.7
0.0
19.7
4.0
19.7
24.0
19.7
136.0
38.7
205.0
19.7
0.0
38.7
Page Total
Btu/hr
630
630
138
138
79
79
79
5,732
4,033
11,536
Internal Gain tstu/nr
Occupants 2.0 Occupants X 230 Btuh/occ. 4
Equipment 1.0 Dwelling Unit X 1,600 Btu
Infiltration: 1.064 X 0.94 X 148.18 X 42 = C
Air Sensible CFM ELA AT
I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 43,954
Latent Gain Btu/hr
400
Occupants 2.0 Occupants X 200 Btuh/occ. =
Infiltration: 4.771 X 0.94 X 148.18 X 0.00523 = 3,461
Air Sensible CFM ELA AW
F-1
LJ
•
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
New Residence
1 1/25/2013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Living Zone
Outdoor Dry Bulb Temperature
112 OF
Floor Area
2,708.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature
70 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
o
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area GLF
Btu/hr
1 C
(S) 230.0 X- 25.5 +
0.0 X
25.6
= 5,859
1K
(S) 110.0 X 19.7 +
0.0 X
19.7
= 2,164
124
(w) 18.0 X 19.7 +
0.0 X
38.7
= 354
1A
(W) 3.0 X 37.2 +
17.0 X
66.3
= 1,238
1A
(W) 6.0 X 37.2 +
34.0 X
66.3
= 2,476
1A
(W) 3.0 X 37.2 +
17.0 X
66.3
= 1,238
18
(W) 94.8 X 19.7 +
25.2 X
38.7
= Z840
X +
X
=
X +1
X
=
Page Total
16,169
Internal Gain
Btu/hr-
tu/hrOccu
ants
Occupants
2.0 Occupants X 230
Btuh/occ.
=
460
Equipment
1.0 Dwelling Unit X 1,600
Btu
=
1,600
Infiltration: 1.064
X 0.94 X 148.18 X 42 =
6,194
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
43,954
Latent Gain
Btu/hr
Occupants
2.0 Occupants X 200
Btuh/occ.
=
400
Infiltration: 4,771
X 0.94 X 148.18 X 0.00523 =
3,461
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
3,861
EnergyPro 5.1 by Ene Soft
User Number: 6712 RunCode: 2013-01-25710:36:16 ID:
Pa a 30 of 31
-
•
0
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project NameDate
New Residence
1/25/2013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Bedroom 3
Outdoor Dry Bulb Temperature
112 OF
Floor Area
376.0 ft'
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature
70 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
R-38 Roof(R. 38.2x 14.16)
(W) 376.0 X 0.0260
X
56.0 =
547
R-21 Wall (W.19.2x6.16)
(N) 140.0 X 0.0690
X
23.0 =
222
R-21 Wall (W.19.2x6.16)
(E) 135.0 X 0.0690
X
33.0 =
307
R-21 Wall (W.19.2x6.16)
(S) 180.4 X 0.0690
X
26.0 =
324
R-21 Wall (W.19.2x6.16)
130.0 X 0.0690
X
33.0 =
296
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
1,687
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area
GLF
Btu/hr
1D
(S) 0.0 X 19.7 +
48.0 X
19.7 =
948
1D
(S) 0.0 X 19.7 +
24.0 X
19.7 =
474
100
(S) 0.0 X 19.7 +
3.8 X
19.7 =
75
101
(S) 0.0 X 19.7 +
3.8 X
19.7 =
75
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X + I
X
=
Page Total
1,572
Internal Gain
Btu/hr
Occupants
1.0 Occupants X 230
Btuh/occ.
=
230
Equipment
0.0 Dwelling Unit X 1,600
Btu
=
0
Infiltration: 1.064
X 0.94 X 20.57 X 42 =
860
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
4,359
Latent Gain
Btu/hr
Occupants
1.0 Occupants X 200
Btuh/occ.
=
200
Infiltration: 4,771
X 0.94 X 20.57 X
1
481
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
681
EnergyPro 5.1 by Enem Soft
User Number: 6712 RunCode: 2013-01-25x10:36:16 ID:
Page 31 of 31