12-1462 (SFD) Title 24BUILDING ENERGY ANALYSIS REPORT
PROJECT:
Mr & Mrs Richard Albers
80-270 Via Capri The Hideaway
La Quinta, CA 92253
Project Designer:
Residential Concepts
80-270 Via Capri The Hideaway
La Quinta, CA 92253
(760) 342-1709
w Report Prepared by:
Jon Scott
Scott Design and Title 24, Inc,
77=085 Michigan Drive
Palm Desert, Ca 92211
(760) 200-4780 CITY OF LA QUINTA
BUILDING & SAFETY DEPT.'
APPROVED
FOR CONSTRUCTIO
DA . 2 Z li:�' BY �SCd
Job Number: 12- l2
aF 11VED
Date:
DEC 2'0 2012
12/4/2012
BY:
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2008 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC — www.onergysoft.com. "
EnergyPro 5.1 byEnergySoft User Number. 6712 RunCode: 2012-12-04714:08:24 ID:
4 �4_
..ryY
�
�4
.
Y
�
� � _
-
�
�
� - 1„
�
F
0
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
Mr & Mrs Richard Albers
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
12/4/2012
Project Address
80-270 Via Capri The Hideaway La Quint
California Energy Climate Zone
CA Climate Zone 15
I Total Cond. Floor Area
5,06
Addition
n/a
# of Stories
1
FIELD INSPECTION ENERGY CHECKLIST
I I Yes ❑ No HERS Measures -- If Yes, A CF -413 must be provided per Part 2 of 5 of this form.
❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION
Construction Type
Area Special
Cavity Features see Part 2 of 5 Status
Roof Wood Framed Attic R-38 4,976 Radiant Barrier New
Wall Wood Framed R-21 3,899 New
Slab Unheated Slab -on -Grade None 5,003 Perim = 415' New
Door Opaque Door None 24 New
FENESTRATION U- Exterior
Orientation Area Factor SHGC Overhang Sidefins Shades Status
Skylight 4.0 0.550 0.67 none none None New
Left (Kq 128.0 0.530
0.46 none none Bug Screen New
Skylight 16.0 0.550
0.67 none none None , New
Rear (N) 400.0 0.530
0.46 none none Bug Screen New
Rear (NE) 80.0 0.530
0.46 none none Bug Screen New
Front (S) 170.0 0.530
0.46 none none Bug Screen New
Left (NKK 80.0 0.530
0.46 none none Bug Screen New
Skylight 4.0 0.550
0.67 none none None New
Right (E) 12.0 0.530
0.46 none none Bug Screen New
Front (SlAq 68.0 0.530
0.46 none none Bug Screen New
HVAC SYSTEMS
Ot . Heating Min. Eff
Cooling Min. Eff Thermostat Status
1 Central Furnace 80% AFUE
Split Air Conditioner 16.3 SEER Setback
New
2 Central Furnace 80% AFUE
Split Air Conditioner 16.0 SEER Setback
New
1 Central Furnace 80% AFUE
Split Air Conditioner 16.3 SEER Setback
New
HVAC DISTRIBUTION
Location Heating
Duct
Cooling Duct Location R -Value Status
HVAC 1 Ducted
Ducted Attic, Ceiling Ins, vented 4.2
New
HVAC 2 & 3 Ducted
Ducted Attic, Ceiling Ins, vented 4.2
New
HVAC 4 Ducted
Ducted Attic, Ceiling Ins, vented 4.2
New
WATER HEATING
Ot . Type Gallons Min. Eff Distribution Status
1 Small Gas 50
0.61 No Pipe Insulation
New
EnergyPro 5.1 by EnergySoft User Number.' 6712
RunCode: 2012-12-04714:08:24 ID:
Page 3 of 29
•
•
•
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
Mr & Mrs Richard Albers
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
12/4/2012
Project Address
80-270 Via Capri The Hideaway La Quint
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
5,000
Addition
n/a
# of Stories
1
FIELD INSPECTION ENERGY CHECKLIST
❑ Yes ❑ No HERS Measures -- If Yes, A CF -413 must be provided per Part 2 of 5 of this form.
❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION Area Special
Construction Type Cavity Features see Part 2 of 5 Status
FENESTRATION U- Exterior
Orientation Area Factor SHGC Overhang Sidefins Shades Status
HVAC SYSTEMS
Ot . Heating Min. Eff Cooling Min. Eff Thermostat Status
1 Central Furnace 80% AFUE Split Air Conditioner 14.5 SEER Setback
New
HVAC DISTRIBUTION Duct
Location Heating Cooling Duct Location R -Value Status
HVAC 5 Ducted Ducted Attic, Ceiling Ins, vented 4.2
New
WATER HEATING
Ot . Type Gallons Min. Eff Distribution Status
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 201 2-12-04 714:08:24 /D:
Page 4 of 29
•
•
•
PERFORMANCE CERTIFICATE: Residential Part 2 of 5 CF -1 R
Project Name
Mr & Mrs Richard Albers
Building Type ® Single Family ❑ Addition Alone
1 ❑ Multi Family ❑ Existing+ Addition/Alteration
Date
1121412012
SPECIAL FEATURES INSPECTION CHECKLIST
The enforcement agency should pay special attention to the items specified in this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The enforcement agency
determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of
the special justification and documentation submitted.
The HVAC System HVAC 1 must serve only Sleeping Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
se arate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential A endix R43.3 must be met.
H GH MASS' Design - Verify Thermal Mass: 646.0 ft2 Covered Slab"'Floor, 3.500" thick at Bedroom 2'& 3
HIGH MASS Design -Verity Thermal Mass: 160.0 ft2 Exposed Slab Floor, 3.500" thick at Bedroom 2 & 3
The HVAC System HVAC 2 & 3 must serve only Living Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
se arate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
HIGH MAS Design - Verify Thermal Mass: 630.0 ft2 Covered Slab Floor, 3.500" thick at Family Great Kitchen
HIGH MASS Design - Verify Thermal Mass: 1, 724.0 ft2 Exposed Slab Floor, 3.500" thick at Family Great Kitchen
The HVAC System HVAC 4 must serve only Sleeping Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
se arate thermostat. In addition the air flow re uirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
HIGH MASS Design -'Verify Thermal Mass: 949.0 ft2 Covered Slab Floor, 3.500" thick at Master
HIGH MASS Design - Verity Thermal Mass: 462.0 ft2 Exposed Slab Floor, 3.500" thick at Master
The HVAC System HVAC 5 must serve only Sleeping Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a
se arate t hermostat. In addition the air flow re uirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
H GH MASS Design - Verify Therm6l Mass: 2:0 ft2 Covered Slab Floor, 3.500" thick at Casita
33
HIGH MASS Design - Verify Thermal Mass: 100.0 112 Exposed Slab Floor, 3.500" thick at Casita
The Roof R-38 Roof(R.38.2x 14.16) includes credit for a Radiant Barrier that is Continuous meeting eligibility and installation criteria as specified in
Residential Appendix RA4.2.2.
HERS REQUIRED VERIFICATION
Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a
completed CF -4R form for each of the measures listed below for final to be given.
The Cooling System York CZF030 TM8LX060Al2MP11 includes credit for a 13.3 EER Condenser A certified HERS rater must field verity the
installation of the correct Condenser.
The HVAC System HVAC 1 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 1 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
The Cooling System York CZF060 TM8LX100Al2MP11 includes credit for a 13.3 EER Condenser. A certified HERS rater must field verify the
installation of the correct Condenser.
The HVAC System HVAC 2 & 3 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 2 & 3 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
The Cooling System York CZF048 TMBLX100C20MP11 includes credit for a 13.5 EER Condenser. A certified HERS rater must field verify the
installation of the correct Condenser.
The HVAC System HVAC 4 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 4 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct '
leakage meets the specified criteria.
The Cooling System York YCJD18 TMBLX060Al2MP11 includes credit for a 12.5 EER Condenser. A certified HERS rater must field verify the
installation of the correct Condenser.
The HVAC System HVAC 5 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 5 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
I—E-n—emyPro 5.1 by EnerqySoft User Number., 6712 RunCode: 2012-12-04714:08:24 ID: Page 5 of 29
•
•
PERFORMANCE CERTIFICATE: Residential Part 3 of 5 CF -1 R
Project Name
Building Type m Single Family ❑ Addition Alone
Date
Mr & Mrs Richard Albers
❑ Multi Family ❑ Existing+'Addition/Alterationz
12/4/2012
ANNUAL ENERGY USE SUMMARY
Standard Proposed Margin
TDV kBtu/ft2- r
Space Heating 3.70 4.60. -0.91
Space Cooling 55.53 45.99 9.53
Fans 11.22 14.93 -3.71
Domestic Hot Water 7.30 7.07 0.23
Pumps 0.00 0.00 0.00
Totals 77.74 72.59 5.15
Percent Better Than Standard: 6.6%
BUILDING COMPLIES - HERS VERIFICATION REQUIRED
Fenestration
Building Front Orientation: (S) 180 deg Ext. Walls/Roof Wall Area Area
Number of Dwelling Units: 1.00 (S) 1,292 238
Fuel Available at Site: Natural Gas (W 1,258 208
Raised Floor Area: 0 (N) 1,259 480
Slab on Grade Area: 5,003 (E) 1,052 12
Average Ceiling Height: 11.9 Roof 5,000 24
Fenestration Average U -Factor: 0.53 TOTAL: 962
Average SHGC: 0.46 Fenestration/CFA Ratio: 19.2%
REMARKS
The Hideaway Lot # 54 & 55
STATEMENT OF COMPLIANCE
This certificate of compliance lists the building features and specifications needed
to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the
Efficiency Standards of the California Code of Regulations.
The documentation author hereby certifies that the documentation is accurate and complete.
Documentation Author
Company Scott Design and Title 24, Inc,
r` 12/4/2012
Jon Scott
Address 77-085 Michigan Drive Name V
City/State/ZipCity/State/Zip Palm Desert, Ca 92211 Phone (760) 200-4780 Signed Date
The individual with overall design responsibility hereby certifies that the proposed building design represented in this set
of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and
with any other calculations submitted with this permit application, and recognizes that compliance using duct.design,
duct sealing, verification of refrigerant charge, insulation installation quality, and building envelope sealing require
installer testing and certification and field verification by an approved HERS rater.
Designer or Owner (per Business & Professions Code)
Company Residential Concepts
Address 80-270 Via Capri The Hideaway Name Jerry W. Sherman
City/State/Zip La Quinta, CA 92253 Phone (760) 3424709 S ned License # Date
EnergyPro 5.1 by EnerqySoft user Number: 6712 Runcode: 2012-12-04714:08:24 ID: Page 6 of 29
•
•
•
CERTIFICATE OF COMPLIANCE:
Residential
(Part 4 of 5) CF -1 R
Project Name
Mr & Mrs Richard Albers
Building Type m Single Family ❑Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
1121412012
OPAQUE SURFACE DETAILS
Surface
T e Area
U- Insulation Joint Appendix
I Factor Cavit Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
Roof
802
0.026 R-38
0
20 New 4.2.1-A9
Bedroom 2 & 3
Wall
55
0.069 R-21
0
90 New 4.3.1-A6
Bedroom 2 & 3
Well
336
0.069 R-21
180
90 New 4.3.1-A6
Bedroom 2 & 3
Wall
348
0.069 R-21
270
90 New 4.3.1-A6
Bedroom 2 & 3
Slab
646
d. 730 None
0
180 New 4.4.7-A1
Bedroom 2 & 3
Slab
166
0.730 None
0
180 New 4.4.7-A1
Bedroom 2 & 3
Roof
2,338
0.026 R-38'
0
20 New 4.2.1-A9
Family Great Kitchen
Wall
482
0.069 R-21
0
90 New 4.3.1-A6
Family Great Kitchen
Wall
102
0.069 R-21
1 45
90 New 4.3.1-A6
Family Great Kitchen
Wall
196
0.069 R-21
90
90 1 New 4.3.1-A6
Family Great Kitchen
Wall
414
0.069 R-21
180
90 New 4.3.1-A6
Family Great Kitchen
Door
24
0.500 None
180
90 New 4.5.1-A4
Family Great Kitchen
Wall
490
0.069 R-21
270
90 New 4.3.1-A6
Family Great Kitchen
Wall
102
0.069 R-21
315
90 New 4.3.1-A6
Familz Great Kitchen
Slab
630
0.730 None
0
180 New 4.4.7-A1
Family Great Kitchen
-family
Slab
1,724
0.730 None
0
180 New 4.4.7-A1
Great Kitchen
FENESTRATION SURFACE DETAILS
ID
Type
Area I LI -Factor'
SHGCz
Azm Status
Glazing Type
Location/Comments
1
Skylight
4.0 0.550 Default
0.67 Default
0 New
Double Non Metal Clear
Bedroom 2 & 3
2
Window
30.0 0.530 1 NFRC
0.46 NFRC
270 New
Dual Metal Tint
Bedroom 2 & 3
3
Window
48.0 0.530 1 NFRC
0.46 NFRC
270 New
Dual Metal Tint
Bedroom 2 & 3
4
Skylight
Default
16.0P0.530
0.67 Default
0 New
Double Non Metal Clear
Family Great Kitchen
5
Window
120.0 NFRC
0.46 NFRC
0 New
Dual Metal Tint
Family Great Kitchen
6
Window
120.0 NFRC
0.46 NFRC
0 New
Dual Metal Tint
Family Great Kitchen
7
Window
36.0 NFRC
0.46 NFRC
0 New
Dual Metal Tint
Family Great Kitchen
8
Window
80.0 NFRC
0.46 NFRC
45 New
Dual Metal Tint
Family Great Kitchen
9
Window
24.0 NFRC
0.46 NFRC
180 New
Dual Metal Tint
Family Great Kitchen
10
Window
6.0 0.530 NFRC
0.46 NFRC
180 New
Dual Metal Tint
Family Great Kitchen
11
Window
60.0 0.530 NFRC
0.46 NFRC
180 New
Dual Metal Tint
Family Great Kitchen
12
Window
80.0 0.530 NFRC
0.46 NFRC
180 New
Dual Metal Tint
Family Great Kitchen
13
Window
80.0 0.530 NFRC
0.46 NFRC
315 New
Dual Metal Tint
Family Great Kitchen
14
Skylight
4.0 0.550 Default
0.67 Default
0 New
I Double Non Metal Clear
Master
15
Window
120.0 0.530 NFRC
0.461NFRC
1 0 New
I Dual Metal Tint
Master
16
Window
4.0 0.530 NFRC
0.46 NFRC
1 0 New
I Dual Metal Tint
Master
(1) U -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type SHGC
Window
Hat Wd
Ove hang Left Fin
Len H t LExt RExt Dist Len
Right in
H t Dist Len Hat
1
None
1.00
2
Bug Screen
0.76
3
Bug Screen
0.76
4
lNone
1.00
5
Bug Screen
0.76
6
Buq Screen
0.76
7
Bug Screen
0.76
8
Bug Screen
0.76
9
Bug Screen
0.76
10
Bug Screen
0.76
11
Bug Screen
0.76
12
Bug Screen
0.76
13
Bug Screen
0.76
14
None
1.00
15
Buq Screen
0.76
16
Bug Screen
1 0.76
EnemyPro
5.1 by EnemySoft User Number: 6712 RunCode: 2012-12-04714:08:24 ID:
Page 7 of 29
•
•
•
CERTIFICATE OF COMPLIANCE: Residential
Part 4 of 25L__ CF -1 R
Project Name
Mr & Mrs Richard Albers
Building Type 0 Single Family
❑ Multi Family
❑ Addition Alone
❑ Existing+ Addition/Alteration
Date
12/4/2012
OPAQUE SURFACE DETAILS
Surface LI Insulation Joint Appendix
Type Area Factor CavitYTExterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
Roof
1,404 0.026 R-38
0 20 New
4.2.1-A9
Master
Wall
140 0.069 R-21
0 90 New
4.3.1-A6
Master
Wall
608 0.069 R-21
90 90 New
4.3.1-A6
Master
Wall
88 0.069 R-21
180 90 New
4.3.1-A6
Master
Slab
949 0.730 None
0 180 New
4.4.7-A1
Master
Slab
462 0.730 None
0 186 New
4.4.7-A1
Master
Roof
432 0.026 R-38
0 20 New
4.2.1-A9
Casita
Wall
236 0.069 R-21
90 90 New
4.3.1-A6
Casita
Wall
100 0.069 R-21
180 90 New
4.3.1-A6
Casita
Wall
921 0.069 R-21
225 90 New
4.3.1-A6
Casita
Wall
110 0.069 R-21
270 90 New
4.3.1-A6
Casita
Slab
332 0.730 None
0 186 New
4.4.7-A 1
Casita
Slab
160 0.730 None
0 180 New
4.4.7-A1
Casita
FENESTRATION SURFACE DETAILS
ID
Type Area LI -Factor SHGC
Azm Status Glazing Type
Location/Comments
17
Window 4.0 0.530 NFRC 0.46 NFRC 90 New Dual Metal Tint
Master
18
Window 4.0 0.530 NFRC 0.46 NFRC 90 New Dual Metal Tint
Master
19
Window 4.0 0.530 NFRC 0.46 NFRC 90 New Dual Metal Tint
Casita
20
Window 68.6 0.530 NFRC 0.46 NFRC 225 New Dual Metal Tint
Casita
21
Window 50.0 0.530 NFRC 0.46 NFRC 270 New Dual Metal Tint
Casita
(1) LI -Factor Type: 1161 = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Window
Exterior Shade Type SHGC HqA Wd
Ove hang
Len H t LExt RExt
Left Fin
Dist Len
Right in
H t Dist Len H t
17
Bug Screen 0.76
18
Bug Screen 0.76
19
Bug Screen 0.76
20
Bug Screen 0.76
21
Bug Screen 0.76
EnefgyPro
5.1 by EnergySoft User Number: 6712
RunCode: 2012-12-04714:08:24
ID:
Page 8 of 29
•
•
•
CERTIFICATE OF COMPLIANCE: Residential Part 5 of 5)
CF -1 R
Project Name
Mr & Mrs Richard Albers
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
12/4/2012
BUILDING ZONE INFORMATION
System Name Zone Name
Floor Area ft
New Existing Altered Removed Volume
Year Built
HVAC 1 Bedroom 2 8 3
806
8,060
HVAC 2 & 3 Family Great Kitchen
2,354
32,956
HVAC 4 Master
1,408
14,080
HVAC 5 Casita
432
4,320
Totals 51000 0 01. 0
'HVAC SYSTEMS
System Name Qty. HeatingT e
Min. Eff. CoolingType Min. Eff. Thermostat Type
Status
HVAC 1 1 Central Furnace
80% AFUE Split Air Conditioner 16.3 SEER Setback
New
HVAC 2 & 3 2 Central Furnace
80% AFUE S lit Air Conditioner 16.0 SEER Setback
New
HVAC 4 1 Central Furnace
80 % AFUE Split Air Conditioner 16.3 SEER Setback
New
HVAC 5 1 Central Furnace
80% AFUE Split Air Conditioner 14.5 SEER Setback
New
HVAC DISTRIBUTION
System Name Heating
Duct
Cooling Duct Location R -Value
Ducts
Tested? Status
HVAC 1 Ducted Ducted Attic, Ceiling Ins, vented 4.2
m
New
HVAC 2 & 3 Ducted Ducted Attic, Ceiling Ins, vented 4.2
m
New
HVAC 4 Ducted Ducted Attic, Ceiling Ins, vented 4.2
d
New
HVAC 5 1 Ducted Ducted JAttic, Ceiling Ins, vented 4.21
El
I New
WATER HEATING SYSTEMS
S stem Name O
Type
Distribution
Rated
Input
Btuh
Tank
Cap.
al
Energy Standby
Factor Loss or
or RE Pilot
Ext.
Tank
Insul. R-
Value
Status
G50T236 American Stand 1
Small Gas
No Pipe Insulation
40,000
50
0.61 n/a
n/a
New
MULTI -FAMILY WATER HEATING
DETAILS
I
HYDRONIC
HEATING SYSTEM
PIPING
Control O . HP
Hot Water Piping Length
ft
N
a
System Name
Pipe
Length
Pipe
Diameter
Insul.
Thick.
Plenum Outside Buried
EnergyPro 5.1 by EnergySoft User Number.' 6712
RunCode: 2012-12-04T14:08:24 ID:
Page 9 of 29
MANDATORY MEASURES SUMMARY: Residential (Pagel of -3 M
Project Name "
Mr & Mrs Richard Albers
.-1R
Date
12/4/2012
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD, or CF -
1 R -ALT Form) shall supersede the items marked with an asterisk (') below. This Mandatory Measures Summary shall be incorporated
into the permit documents, and the applicable features shall be considered by all parties as minimum component performance
specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R
Form with plans.
Building Envelope Measures:
116(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§116(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of 10-111 (a).
117: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed.
118(a): Insulationspecified or installed meets Standards for Insulatinq Material. Indicate type and include on CF -6R Form.
§118(1): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §118(i) when the
installation of a Cool Roof is specified on the•CF-1 R Form.
*§150(a): Minimum R-19 insulation in wood -frame ceiling orequivalent LI-factor.
§150(b): Loose fill insulation shall conform with manufacturer's installed design labeled R -Value. '
*§150(c): Minimum R-13 insulation in wood -frame wall orequivalent U -factor.
*§150(d): Minimum R-13 insulation in raised wood -frame floor orequivalent LI-factor.
4150(f): Air retarding wrap is tested labeled and installed according to ASTM E1677-95(2000) when specified on the CF -1R Form.
&150(q): Mandatory Vapor barrier installed in Climate Zones 14 or 16.
§150(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance
rate is no greater than 2.0perm/inch and shall be protected from physical damage and UV light deterioration.
Fireplaces, Decorative Gas Appliance s and Gas Log Measures:
150 e 1 A: Masonry or factory -built file laces have a closable metal or qlass door covering the entire opening of the firebox.
§150(e)1 B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a with a readilyaccessible, operable, and tight -fitting damper and or a combustion -air control device.
§150(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the
outside of the buildin , are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110-§113: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy
Commission. `
§113(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release
valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of §113(c)5.
§115: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances
(appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and
spa heaters.
§150(h): Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA.
150(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 112(c).
§1500)1 A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped
with insulation having an installed thermal resistance of R-12 or greater. `
§1500)113: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water
tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the
tank.
§1500)2: First 5 feet of hot and cold water pipes closest to water heater tank, non -recirculating systems, and entire length of
recirculating sections of hot water pipes are insulated per Standards Table 150-13.
§1500)2: Cooling system piping (suction, chilled water, or brine Iines),and piping insulated between heating source and indirect hot
water tank shall be insulated to Table 150-B and Equation 150-A.
§1500)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards Table
123-A. -
150 ' 3A: Insulation is protected from damage, including that due to sunlight, moisture a ui ment maintenance and wind.
§1 500)3A: Insulation for chilled water piping and refrigerant suction lines includes a vapor retardant or is enclosed entirely in
conditioned space.
150(m)4: Solar water -heating systems and/or collectors are certified by the Solar Rating and Certification Corporation.
EnergyPro 5.1 by EnergySoff User Number: 6712 RunCode: 2012-12-04714:08:24 ID: Page 10 of 29
•
C
MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 MF -1 R
Project Name
Date
Mr & Mrs Richard Albers
12/4/2012
§150(m)1: All air -distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections
601, 602, 603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-
4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that meets the
applicable requirements of UL 181, UL 181 A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is
used to seal openings reater than 1/4 inch, the combination of mastic and either mesh or tape shall be used
§150(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than'sealed
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may
contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area
of the ducts.
§150(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes'
unless such tae is used in combination with mastic and draw bands.
150(m)7: Exhaust fans stems have back draft or automatic dampers.
§150(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated
dampers.
§150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar
radiation that can cause degradation of the material.
150 m 10: Flexible ducts cannot have porous inner cores.
§150(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation acid Acceptable Indoor Air
Quality in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation
required in Section 4 of that Standard.
Pool and Spa Heating Systems and Equipment Measures:
§114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and
shall not use electric resistance heating ora pilot light.
§114(6)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction
and return lines, or built-up connections for future solar heating.
6114(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover.
§114(b)3: Pools shall have directional inlets'that adequately mix the pool water, and a time switch that will allow all pumps to be set or
programmed to run only during off-peak electric demand periods.
150 : Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150 .
Residential Lighting Measures:
§150(k)1: High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies
contained in Table 150-C and is not a low efficacy luminaire asspecified by §150(k)2.
150(k)3: The wattage of permanently installed luminaires shall be determined asspecified by §130(d).
§150(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than
20 kHz.
§150(k)5: Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall contain
only high efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line -voltage socket or line -
voltage lamp holder; OR shall be rated to consume no more than five watts of power as determined by §130(d), and shall not contain a
medium screw -base socket.
150(k)6: Lighting integral to exhaust.fans, in rooms other than kitchens shall meet the applicable requirements of §150(k).
150(k)7: All switching devices and controls shall meet the requirements of §150(k)7.
§150(k)8: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft2 or 100 watts for dwelling units larger than 2,500 ft2 may be
exempt from the 50% high efficacy requirement when: all low efficacy luminaires in the kitchen are controlled by a manual on occupant
sensor, dimmer, energy management system (EMCS), or a multi -scene programmable control system; and all permanently installed
luminaries in garages, laundry rooms, closets greater than 70 square feet, and utility rooms are high efficacy and controlled by a
manual -on occupant sensor.
§150(k)9: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of
illuminated cabinet.
EnergyPro 5.1 by EnergySoft User Number., 6712 RunCode: 2012-12-04714:08:24 ID: Page 11 of 29
0
0
MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 MF -1 R
Project Name
Date
Mr & Mrs Richard Albers
92/4/2092
§150(k)l0: Permanently installed luminaires in bathrooms, attached and detached garages, laundry rooms, closets and utility rooms
shall be high efficacy.
EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by a manual -on
occupant sensor certified to comply with the applicable requirements of §119.
EXCEPTION 2: Permanently installed low efficacy luminaires in closets less than 70 square feet are not required to be controlled by a
manual -on occupancy sensor.
§150(k)l 1: Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms,
closets, and utility rooms shall be high efficacy luimnaires. EXCEPTION 1: Permanently installed low efficacy luminaires shall be
allowed provided they are controlled by either a dimmer switch that complies with the applicable requirements of §119, or by a manual -
on occupant sensor that complies with the applicable requirements of §119. EXCEPTION 2: Lighting in detached storage building less
than 1000 square feet located on a residential site is not required to comply with 150 k 11.
§150(k)l2: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters
Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the lumiunaire is airtight with air
leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between
the luminaire housin .and ceiling.
§150(k)13: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more
dwelling units, entrances, balconies, and porches, which are permanently mounted to a residential building or to other buildings on the
same lot shall be high efficacy. EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that
they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor,
and one of the following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an
astronomical time clock not having an override or bypass switch that disables the astronomical time clock; OR an energy management
control system (EMCS) not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2: Outdoor
luminaires used to comply with Exceptionl to §150(k)13 may be controlled by a temporary override switch which bypasses the motion
sensing function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3: Permanently installed
luminaires in or around swimming pool, water features, or other location subject to Article 680 of the California Electric Code need not
be high efficacy luminaires.
§150(k)14: Internally illuminated address signs shall comply with Section 148; OR not contain a screw -base socket, and consume no
more than five watts of power as determined according to §130(d).
§150(k)15: Lighting for parking lots and carports with a total of for 8 or more vehicles per site shall comply with the applicable
requirements in Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable
requirements of Sections 130, 131, 134, and 146.
§150(k)16: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more
dwelling units shall be high efficacy luminaires. EXCEPTION: Permanently installed low efficacy. luminaires shall be allowed provided
that they are controlled by an occupant sensors certified to comply with the applicable requirements of 119.
I
EnergyPro5.1 by EnergySoft User Number: 6712 RunCode: 2012-12-04714:08:24 ID: Page 12 of 29
•
0
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Mr & Mrs Richard Albers
Date
12/4/2012
System Name
HVAC 1
Floor Area
806
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL COOLING PEAK
CFM Sensible
Total Room Loads 1,018 16,404
Return Vented Lighting 0
Return Air Ducts 1,391
Return Fan 0
Ventilation F 0 0
Supply Fan 0
Supply Air Ducts 1,391
TOTAL SYSTEM LOAD 1 19,186
COIL HTG.
Latent CFM
1,6301 200
0 0
1,630
PEAK
Heating System
Sensible
Output perSystem 51,000
9,916
Total Output Btuh 51,000
Output Btuh/ ft 63.3
705
Cooling System
0
Output perSystem 28,500
0
Total Output Btuh 28,500
0
Total Output ons 2.4
705
Total Output Btuh/s ft 35.4
Total Output s ft/Ton 339.4
11,325
Air System
CFM perSystem
1,000
HVAC EQUIPMENT SELECTION
Airflow cfm
1,000
York CZF030TM8L.X060Al2MP11 18,892
Total Adjusted System Output 18,8921
(Adjusted for Peak Design conditions)
I TIME OF SYSTEM PEAK
4,553 51,000
4,553 51,000
Aug 3 PM I Jan 1 AM
Airflow cfm/s ft 124
Airflow cfm/Ton 421.1
Outside Air % 0.0%1
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 71 OF
Outside Air
0 cfm Supply Fan
AL 1,000 cfm
71 of
71 OF 119 OF
Heating Coil
119 OF
--
ROOM
72 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78 OF 71!60°F 71/60°F 54/53°F
o
Outside Air Ar
0 cfm Supply Fan Cooling Coil
1,000 cfm
54.8%
71 / 60 OF
55 / 53 OF
ROOM
701 60 OF
�E�,eyPro 5.1 by EnergySoff
User Number. 6712 RunCode: 2012-12-04714:08:24 ID:
Page 13 of 29
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
.Project
Name
Mr & Mrs Richard Albers
Date
12/4/2012
System Name
HVAC 2 & 3
Floor Area
2,354
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
2
COIL COOLING PEAK COIL HTG.
CFM Sensible Latent CFM
Total Room Loads 1,872 36,068 3,608 841
Return Vented Lighting 0
Return Air Ducts 3,058
Return Fan o
Ventilation 0 0 0 0
Supply Fan 0
Supply Air Ducts 3,058
TOTAL SYSTEM LOAD 1 42,185 3,608
PEAK
Heating System
Sensible
Output erSystem 89,000
36,344
Total Output Btuh 178,000
Output Btuh/s ft 75.6
2,582
Cooling System
0
Output erSystem 58,500
0
Total Output Btuh 117,000
0
Total Output ons 9.8
2,582
Total Output Btuh/s ft 49.7
Total Output s ftrron 241.4
1 41,509
Air System
-
CFM perSystem
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
4,000
York CZF060 TM8l_X100Al2MP11 83,204
10,518
178,000
1 178,000
Jan 1 AM
Alrflow cfm/s ft 1.70
Airflow cfmrron 410.3
Outside Air % 0.0%
Total Adjusted System Output 1 83,204
(Adjusted for Peak Design conditions)
1 TIME OF SYSTEM PEAK
10,518
Aug 3 PM
Outside Alr cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 71 OF
Outside Air
0 cfm Supply Fan
4,000 cfm
71 OF
71 OF 113 OF
Heating Coil
113 OF
ROOM
72 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F 71158°F 71 /58°F 51 /50°F
o _
Outside Air Ar
0 cfm Supply Fan Cooling Coil
4,000 cfm
48.9%
71 158 of
52 / 51 OF
,......__.................._............ R, .
ROOM
70158 OF
EnergyPro 5.1 by EnergySoff User Number.' 6712 RunCode: 2012-12-04714:08:24 ID:
Page 14 of 29
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
.Project
Name
Mr & Mrs Richard Albers
Date
12/4/2012
System Name
HVAC 4
Floor Area
1,408
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL COOLING PEAK COIL HTG.
CFM Sensible Latent CFM
Total Room Loads 866 15,846 2,3991 340
Return Vented Lighting 0
Return Air Ducts 1,344
Return Fan 0
Ventilation 0 0 0 0
Supply Fan 0
Supply Air Ducts 1,344
TOTAL SYSTEM LOAD 1 18,533 2,399
PEAK
Heating System
Sensible
Output per System 71,000
14,661
Total Out ut (li 71,000
Output Btuh/s ft 50.4
1,042
Cooling System
0
Output per System 46,500
0
Total Output Btuh 46,500
0
Total Output ons 3.9
1,042
Total Output Btuh/s ft 33.0
Total Output s ft/Ton 363.4
1 16,744
Air System
CFM per System
1,600
HVAC EQUIPMENT SELECTION
Airflow cfm
1,600
York CZF048TM8LX100C20MP11 31,957
5,691
71,000
Airflow cfm/s ft 1.14
Total Adjusted System Output 1 31,957
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
5,691 1 71,000
Aug 3 PM I Jan 1 AM
Airflow cfm/Ton 412.9
Outside Air % 0.0%
Outside Air cfm/s ft 0.00
values above given at ARI conditions
•Note:
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 71 OF
Outside Air
0 cfm Supply Fan
1,600 cfm
71 of
71 OF 1130F
Heating Coil
112 OF
--..------- ....... _
ROOM NJ
72 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
•
112/78°F 71 /59°F 71 /59°F 52/51 OF
Outside Air
0 cfm Supply Fan Cooling Coil
1,600 cfm 51.5%
71 /59°F
53 / 51 OF
ROOM -A
70/59°F
EnergyPro5.1 by EnergySoft
User Number.' 6712 RunCode: 2012-12-04714:08:24 ID:
Page 15 of 29
All
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Mr & Mrs Richard Albers
Date
12/4/2012
System Name
HVAC 5
Floor Area
432
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 571
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation o
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK
Sensible
10,642
0
902
0
0
0
902
1 12,4461
COIL HTG.
Latent CFM
1,152 100
0 0
1,152
PEAK
Heating System
Sensible
Output per System 51,000
8,334
Total Output Btuh 51,000
Output Btuh/s ft 118.1
592
Cooling System
0
Output per System 18,000
0
Total Output Btuh 18,000
0
Total Output ons 1.5
592
Total Output Btuh/s ft 41.7
Total Output s ft/Ton 288.0
9,518
Air System
CFM per System
600
HVAC EQUIPMENT SELECTION
Airflow cfm
600
York YCJD18TM8LX060Al2MP11
Total Adjusted System Output
(Adjusted for Peak Design conditions)
I TIME OF SYSTEM PEAK
12,991
12,991
1,549 51,000
1,549 51,000
Aug 3 PM I Jan 1 AM
Airflow cfm/s ft 1.39
Airflow cfm/Ton 400.0
Outside Air % 0.0%
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
26 OF 71 OF
Outside Air
0 cfm Supply Fan
600 cfm
71 OF
71 OF 151 OF
Heating Coil
150 OF
—
ROOM
r M
72 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling
Peak
112/78°F 71 /59°F 71 /59°F 51 /50°F
Outside Air c
0 cfm Supply Fan Cooling Coil
600 cfm
71 / 59 OF
3
52 / 51 OF
50.1 % ROOM
-JI
70/ 58 OF
EnergyPro 5.1 by EnergySoft
User Number 6712 RunCode: 2012-12-04714:08:24
ID:
Page 16 of 29
0
•
•
ROOM LOAD SUMMARY
Project Name Date
Mr & Mrs Richard Albers 12/4/2012
System Name Floor Area ' '
HVAC 1 806
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. CFM Sensible Latent CFM Sensible I Latent CFM Sensible
Bedroom 2 & 3 Bedroom 2 & 3 1 1 1,0181 16,4041 1,630 1,0181 16,4041 1,630 200 9,916
PAGE TOTAL
TOTAL'
1,018
16,4041
1,6301
200
9,916
1,018
16,404
1,630
200
9,916
Total includes ventilation load for zonal systems.
EnergyPro 5.1 by EnerqySoft User Number: 6712 RunCode: 2 0 1 2-1 2-04 714:08:24 ID: Pae 17 of 29
ROOM LOAD SUMMARY
Project Name .
Mr & Mrs Richard Albers
Date
12/4/2012
System Name
HVAC 2 & 3
Floor Area
2,354
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
Zone Name Room Name
Mult. CFM Sensible Latent
CFM
Sensible Latent
CFM Sensible
Family Great Kitchen Family Great Kitchen
1 1,872 36,068 3,608
1,872
36,068
3,608
841 36,344
' Total includes ventilation load for zonal systems.
PAGE TOTAL
TOTAL '
1,872
1,872
36,068
36,068
,3,608
3,608
841 36,344
841 36,344
Ene Pro 5.1 6 Ene Soft User Number: 6712
RunCode: 2012-12-04714:08:24
ID:
Pae 18 of 29
0
•
•
ROOM LOAD SUMMARY
Project Name Date
Mr & Mrs Richard Albers 12/4/2012
'System Name Floor Area
HVAC 4 1,408
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. I CFM I Sensible Latent CFM Sensible Latent CFM Sensible
Master Master 1 866 15,846 2,399 866 15,846 2,399 340 14,661
ides ventilation load for zonal
5.1 by EnemySoR User N
PAGE TOTAL
TOTAL'
866
15,846
2,399
340
14,661
866
15,846
2,399
340
14,661
•
ROOM LOAD SUMMARY
Project Name Date
Mr & Mrs Richard Albers 12/4/2012
System Name Floor Area
HVAC 5 432
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. I UNITSensible I Latent CFM Sensible Latent CFM
Sensible
LCasita Casita 1 571 10,642 1,152 � 571 10,642 1,152 1001 8,334
* Total includes
PAGE TOTAL
TOTAL*
571
10,6421
1,152
100
8,334
571
10,642
1,152
100
8,334
•
•
•
ROOM HEATING PEAK LOADS
Project Name
Mr & Mrs Richard Albers
Date
12/4/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Floor Area
Indoor Dry Bulb Temperature
Bedroom 2 & 3
806.0 ft'
72 OF
Time of Peak
Outdoor Dry Bulb Temperature
Jan 1 AM
26 OF
Conduction
Area U -Value -
802.0 X 0.0260 X
4.0 X 0.5500 X
739.0 X 0.0690 X
78.0 X 0.5300 X
perim = 75.0 X 0.7300 X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X`
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
through an interior surface to another room
X 806 X 10.00 X 0.318
Area Ceiling Height ACH
AT OF
46 =
46 =
46 =
46 =
46 =
=
=
=
=
=
=
=
=
=
=
_
=
=
=
=
=
=
=
=
=
=
=
=
=
Page Total
/60] X 46
AT
Btu/hr
959
101
2,346
1,902
2,519
7,826
= 2,090
R-38 Roof(R.38.2x 14.16)
Double Non Metal Clear
R-21 Wall (W.21.2x6.16)
Dual Metal Tint
Slab -On -Grade
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM
9,916
Energ Pro 5.1 by EnergySoR User Number: 6712
RunCode: 2012-12-04714:08:24 ID:
Page 91 of 29
•
•
•
ROOM HEATING PEAK LOADS
Project Name
Date
Mr & Mrs Richard Albers
12/4/2012 '
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Family Great Kitchen
Time of Peak
Jan 1 AM
Floor Area 2,354.0 ft'
Outdoor Dry Bulb Temperature
26 OF
Indoor Dry Bulb Temperature 72 OF
Conduction Area
U -Value
AT °F
Btu/hr
R-38 Roof(R.38.2x14.16) 2,338.0
X 0.0260
X
46
=
2,796
Double Non Metal Clear 16.0
X 0.5500
X
46
=
405
R-21 Wall (W.21.2x6.16) 1,786.0
X 0.0690
X
46
=
5,669
Dual Metal Tint 606.0
X 0.5300
X
46
=
14,774
Wood Door 24.0 X 0.5000
X
46
=
552
Slab -On -Grade perim = 180.0 X 0.7300
X
46
=
6,044
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Items shown with an asterisk (') denote conduction through an interior surface to another room
Page Total
30,240
Infiltration:[ 1.00 X 1.064 X 2,354 X 14.00 X 0:227
/60] X
46
= 6,104
Schedule Air Sensible Area
Ceiling Height ACH
AT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM
36,344
EnergyPro 5.1 by EnergySoR User Number: 6712 RunCode: 2012-12-04714:08:24
ID:
Page 22 of 29
.0
ROOM HEATING PEAK LOADS
Project Name
Date
Mr & Mrs Richard Albers
12/4/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Master
Time of Peak
Jan 1 AM
Floor Area
1,408.0 ft'
Outdoor Dry Bulb Temperature
26 OF
Indoor Dry Bulb Temperature
72 OF
Conduction
Area U -Value
AT OF
Btu/hr
R-38 Roof(R. 38.2x 14.16)
1,404.0 X 0.0260
X
46 =
1,679
Double Non Metal Clear
4.0 X 0.5500
X
46 =
101
R-21 Wall (W.21.2x6.16)
836.0 X 0.0690
X
46 =
2,653
Dual Metal Tint
132.0 X 0.5300
X
46 =
3,218
Slab -On -Grade
perim = 100.0 X 0.7300
X
46 =
3,358
X
X
—
X
X
=
X
X
_
X
X
=
X
X
=
X
X
=
X
X
=
x
X
=
X
X
=
X
X
—
X
X
_
X
X
—
X
X
_
X
X
=
X
X
=
X
X
=
X
X
=
X
X
X
X
=
X
X
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Items shown with an asterisk (') denote conduction through
an interior surface to another room
Page Total
11,010
Infiltration:[ 1.00 X 1.064 X 1,408 X 10.00 X 0.318
/ 60 ] :X 46 =
3,651
Schedule Air Sensible
Area Ceiling Height ACH
AT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM
14,661
EnergyPro 5.1 by Energ Soft User Number. 6712
RunCode: 2012-12-04714:08:24
ID:
Page 23 of 29
C]
•
ROOM HEATING PEAK LOADS
Project Name
Date
Mr & Mrs Richard Albers
12/4/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Casita
Time of Peak
Jan 1 AM
Floor Area
432.0 ft2
Outdoor Dry Bulb Temperature
26 OF
Indoor Dry Bulb Temperature
72 OF
Conduction
Area V -Value
AT OF
Btu/hr
R-38 Roof(R.38.2x14.16)
432.0 X 0.0260 X
46 =
517
R-21 Wall (W.21.2x6.16)
538.0 X 0.0690 X
46 =
1,708
Dual Metal Tint
122.0 X 0.5300 X
46 =
2,974
Slab -On -Grade
perim = 60.0 X 0.7300 X
46 =
2,015
X X
=
X X
=
X X
=
X X
=
X X
=
X X
=
X X
=
X . X
=
X X
=
X X
=
X X
X X
=
X X
=
X X
=
X X
=
X X
=
X X
=
X X
=
X X
=
X X
=
X X
=
X X
=
X X
=
X X
=
X X
=
X X
=
X X
=
Items shown with an asterisk (') denote conduction through an interior surface to another room
Page Total
7.213
Infiltration:[ 1.00 X 1.064 X 432 X 10.00 X 0.318
/60] X 46
= 1,120
Schedule Air Sensible
Area Ceiling Height ACH
AT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM
8,334
Energ Pro 5.1 by EnergySoft User Number: 6712
RunCode: 2012-12-04714:08:24 ID:
Page 24 of 29
•
C]
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Mr & Mrs Richard Albers
1214/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Bedroom 2 & 3
Outdoor Dry Bulb Temperature
112 OF
Floor Area
806.0 ft'
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
R-38 Roof(R.38.2x 14.16)
(N) 802.0 X 0.0260
X 77.0 =
1,606
R-21 Wall (W.21.2x6.16)
(N) 55.0 X 0.0690
X 31.0 =
118
R-21 Wall (W.21.2x6.16)
(S) 336.0 X 0.0690
X 38.0 =
881
R-21 Wall .(W.21.2x6.16)
(IM 348.0 X 0.0690
X 55.0 =
1,321
X
X =
X
X
X
X =
X
X =
X
X =
Page Total
3,925
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area GLF
Btu/hr
Skylight
(N) 0.0 X 45.2 +
4.0 X 204.4
= 818
Window
(W) 0.0 X 33.4 +
30.0 X 101.6
= 3,049
Window
0.0 X 33.4 +
48.0 X 101.6
= 4,879
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
Page Total
8,745
Internal Gain
Btu/hr
-Occu ants
3.0 Occupants X 230
Btuh/occ. =
690
Equipment
1.0 Dwelling Unit X 1,200
Btu =
1,200
Infiltration: 1.064
X 0.94 X 44.10 X 42 =
1,844
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
16,404
Latent Gain
Btu/hr
Occupants
3.0 Occupants X L 200
Btuh/occ. =
600
Infiltration: 4,771
X 0.94 X 44.10 X 0.00523 =
1,030
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
1,630
EnemvPro 5.1 by EnerovSoft
User Number: 6712 RunCode: 2012-12-04714:08:24 ID:
Page 25 of 29
•
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Mr & Mrs Richard Albers 12/4/2012
ROOM INFORMATION DESIGN CONDITIONS
Room Name Family Great Kitchen Outdoor Dry Bulb Temperature 112 OF
Floor Area 2,354.0 rt' Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 70 OF Outdoor Dailv Ranae: 34 OF
Ooaoue Surfaces
R-38 Roof(R.38.2x 14.16)
R-21 Wall (W 21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
Wood Door
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
Orientation
(S) I
err
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
Z338.0
0.0260
56.0
482.0
0.0690
23.0
102.0
0.0690
29.0
196.0
0.0690
33.0
414.0
0.0690
26.0
24.01
0.5000
26.0
490.0
0.0690
33.0
102.0
0.06901
30.2
24.0
27.8
0.0
27.7
6.0
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded Unshaded
I Fpnpctratinn
Skylight
Window
Window
Window
Window
Window
Window
Window
Window
nripntatinn
(N)
(N)
(N)
(N)
(NE)
(S)
(S)
(S)
(S)
3,404
765
204
446
743
312
1,116
213
1 7,2031
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X.
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
=
0.0
36.7
16.0
127.4
0.0
27.7
120.0
27.7
0.0
27.7
120.0
27.7
0.0
27.7
36.0
27.7
0.0
27.7
80.0
42.5
0.0
27.7
24.0
27.8
0.0
27.7
6.0
27.8
0.0
27.7
60.0
27.8
0.0
1 27.7
80.0
27.8
Page Total
Btu/hr
2,038
3,320
3,320
996
3,397
667
167
1,667
2,222
17, 794
d Gain
nts
3.0
Occupants
X
230 Btuh/occ.
Btu/hr
ent
1.0
Dwelling Unit
X
1,600 Btu
1.1
(Infiltration: 1.064 X 0.94 X 128.81 X 42
Air Sensible CFM ELA 6T
I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 36,0681
Latent Gain Btu/hr
Occupants 3.0 Occupants X 200 Btuh/occ. = 600
Infiltration: 4,771 X 0.94 X 128.81 X 0.00523 = 3,008
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT
•
•
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Mr & Mrs Richard Albers
12/4/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Family Great Kitchen
Outdoor Dry Bulb Temperature
112 OF
Floor Area 2,354.0 /t'
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
Outdoor Daily Range:
34 OF
Opaque Surfaces Orientation Area U -Factor
CLTD'
Btu/hr
X.
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
0
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area GLF Area
GLF
Btu/hr
Window (NIM 0.0 X 27.7 +
80.0 X 42.5
= 3,397
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
Page Total
3,397
Internal Gain
Btu/hr—
tu/hrOccu
ants 3.0 Occupants X 230
Occupants
Btuh/occ. =
690
Equipment 1.0 Dwelling Unit X 1,600
Btu
=
1,600
Infiltration: 1.064 X 0.94 X 128.81 X 42 =
5,384
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
36,068
Latent Gain
Btu/hr
Occupants 3.0 Occupants X 200
Btuh/occ. =
600
Infiltration: 4,771 X 0.94 X 128.81 X 0.00523 =
3,008
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
3,608
EnemvPro 5.1 by EnemySoft User Number: 6712 RunCode: 2012-12-04714:08:24 ID:
Page 27 of 29
C]
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Mr & Mrs Richard Albers
12/4/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Master
Outdoor Dry Bulb Temperature
112 OF
Floor Area 1,408.0 ft'
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces Orientation Area U -Factor
CLTD'
Btu/hr
R-38 Roof(R.38.2x 14.16) (N) 1,404.0 X 0.0260
X
77.0 =
2,811
R-21 Wall (W.21.2x6.16) (N) 140.0 X 0.0690
X
31.0 =
299
R-21 Wall (W.21.2x6.16) (E) 608.0 X 0.0690
X
44.0 =
1,846
R-21 Wall (W.21.2x6.16) (S) 88.0 X 0.0690
X
38.0 =
231
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
5,187
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area GLF Area
GLF
Btu/hr
Skylight (N) 0.0 X 45.2 +
4.0
X 204.4
= 818
Window (N) 0.0 X 33.4 +
120.0
X 33.4
= 4,003
Window (N)• 0.0 X 33.4 +
4.0
X 33.4
= 133
Window (E) 0.0 X 33.4 +
4.0
X 74.3
= 297
Window (E) 0.0 X 33.4 +
4.0
X 74.3
= 297
X +
X
=
X +
X
=
X +
X
=
X 1 +1
X
=
Page Total
5,549
Internal Gain
Btu/hr
Occupants 3.0 Occupants X 2301
Btuh/occ.
=1
E690
Equipment 1.0 Dwelling Unit X 1,200
Btu
=
1,200
Infiltration: 1.064 X 0.94 X 77.05 X 42 =
3,221
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
15,846
Latent Gain
Btu/hr
Occupants 3.0 Occupants X 200
Btuh/occ.
=
600
Infiltration: 4,771 X 0.94 X 77.05 X 0.00523 =
1,799
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
2,399
EnemvPro 5.1 by EnemySoft User Number., 6712 RunCode: 2012-12-04714:08:24 ID:
Pa a 28 of 29
•
•
0
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Mr & Mrs Richard Albers
1 12/4/2012
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Casita
Outdoor Dry Bulb Temperature
112 OF
Floor Area 432.0 ft'
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OFI
Outdoor Daily Range:
34 OF
Opaque Surfaces Orientation Area U -Factor
CLTD'
Btu/hr
R-38 Roof(R.38.2x 14.16) (N) 432.0 X 0.0260
X 56.0 =
629
R-21 Wall (W.21.2x6.16) (E) 236.0 X 0.0690
X 33.0 =
537
R-21 Wall '(W.21.2x6.16) (S) 100.0 X 0.0690
X 26.0 =
179
R-21 Wall (W.21.2x6.16) (S K9 92.0 X 0.0690
X 31.0 =
197
R-21 Wall (W.21.2x6.16) (K9 110.0 X 0.0690
X 33.0 . =
250
X
X =
X
X =
X
X =
X
X =
Page Total
1, 793
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation. Area GLF Area GLF
Btu/hr
Window (E) 0.0 •X 27.7 +
4:0 X 55.0
= 220
Window (SK9 0.0 X 27.7 +
68.0 X 38.3
= 2,602
Window (W) 0.0 X 27.7 +
50.0 X 55.0
= 2,749
X +
X
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
Page Total
5,570
Internal Gain
Btu/hr
Occupants 3.0 Occupants X 230
Btuh/occ. =
690
Equipment 1.0 Dwelling Unit X 1,600
Btu =
1,600
Infiltration: 1.064 X 0.94 X 23.64 X 42 =
988
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
10,642
Latent Gain
Btu/hr
Occupants 3.0 Occupants • X 200
Btuh/occ. _.
600
Infiltration: 4,771 X 0.94 X 23.64 X 0.00523 =
552
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
1,152
EnemvPro 5.1 by EnerovSoft User Number: 6712 Runcode: 2012-12-04T14:08.24 ID:
Page 29 of 29