BCOM2020-0011ADDITIONAL SITES
CHRONOLOGY
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
E-MAIL AARON HICKSON 2/18/2020 2/18/2020 EMAIL TO INTERWEST REGARDING DIGITAL SUBMITTAL
E-MAIL JAKE FUSON 3/12/2020 3/12/2020 NOTIFIED APPLICANT OF 1ST REVIEW CORRECTIONS.
E-MAIL JAKE FUSON 4/16/2020 4/16/2020 NOTIFIED APPLICANT OF 2ND REVIEW CORRECTIONS.
E-MAIL JAKE FUSON 5/4/2020 5/4/2020 NOTIFIED APPLICANT OF PLAN APPROVAL AND CONDITIONS
FOR ISSUANCE.
E-MAIL JAKE FUSON 9/15/2020 9/15/2020 NOTIFIED APPLICANT THAT REVISION 1 PLANS ARE
APPROVED AND FEE IS READY FOR PAYMENT.
E-MAIL JAKE FUSON 9/25/2020 9/25/2020
CERTIFICATE OF ACCEPTANCE FORM RECEIVED VIA EMAIL,
NOTIFIED CONTRACTOR THAT (3) ADDITIONAL CLOSEOUT
ENERGY FORMS WERE STILL REQUIRED.
Description: LA QUINTA NAIL BAR / 2,368SF NAIL SALON TENANT IMPROVEMENT
Type: BUILDING COMMERCIAL
(WEB)
Subtype: REMODEL Status: FINALED Applied: 2/14/2020 AHI
Parcel No: 600390029 Site Address: 79070 HIGHWAY 111 STE 103 LA QUINTA,CA 92253 Approved: 5/4/2020 JFU
Subdivision: PM 29351 Block: Lot: 11 Issued: 5/7/2020 Online
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 9/21/2021 AOR
Valuation: $50,000.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details: LA QUINTA NAIL BAR / 2,368 SF NAIL SALON TENANT IMPROVEMENT [VB/B-OCC/24-OL/SPRINKLED]. THIS PERMIT DOES NOT
INCLUDE ALTERATIONS TO FIRE-RESISTANCE RATED CONSTRUCTION, BUILDING SIGNAGE OR HVAC EQUIPMENT REPLACEMENT. NO
PATH OF TRAVEL UPGRADES REQUIRED PER ARCHITECT OF RECORD. TUMF ASSESSMENT NOT TRIGGERED PER 2018 HANDBOOK.
2019 CALIFORNIA BUILDING CODES.
REVISION 1 - ELECTRICAL DISTRIBUTION EQUIPMENT REVISION (REVISED SINGLE LINE DIAGRAM, POWER PLAN & PANEL SCHEDULE).
Printed: Tuesday, June 18, 2024 11:38:28 AM 1 of 19
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2020-0011
E-MAIL STEPHANIE SWANSTROM 5/6/2020 5/28/2020
Mr. Huynh,
I’ve attached the building application and the business
license you submitted. You listed Vincent Tran as your
contractor. I need the letter from Vincent stating he ’s no
longer the contractor. The business license is for the nail
salon, we will not issue a business license until your building
work is almost complete. Your contractor will need a business
license.
Mr. Huynh,
One more thing. If your contractor does not have worker’s
compensation, a sub-list will be required to obtain your
permit. Each sub-contractor will need a business license and
all the information across the entire line of the form will need
to be complete and check before permit issuance.
NOTE JACK LIMA 5/7/2020 5/7/2020
ADDED CONTRACTOR FEE TO THIS PERMIT UNDER
ADMINISTRATIVE 'CHANGE OF CONTRACTOR ACCOUNT'.
ONCE THE PERMIT FEES ARE PAID, I WILL MOVE THE FEES
OVER TO BUSINESS LICENSE # 768738.
FEES PAID - FUNDS TRANSFERRED PLEASE SEE ATTACHMENTS
FOR ORIGINAL RECEIPT.
NOTE KOHL HETRICK 3/4/2020 3/4/2020
Need to research. Appears to have added a demising wall to
create 2 tenant spaces where there was previously only 1
throughout the addressed building.
PENDING DOCUMENTS STEPHANIE SWANSTROM 5/6/2020 5/28/2020
LETTER FROM CONTRACTOR - VINCEN TRAN EXPLAINING
HE'S TO BE REMOVED FROM THE JOB
NEW CONTRACTOR - MAYBE SUBLIST TOO (EMAILED IT)
NEW CONTRACTOR - BUSINESS LICNESE.
PUBLIC COUNTER VISIT AARON HICKSON 3/10/2020 3/10/2020 LA QUINTA NAIL BAR BUSINESS LICENSE APPLICATION IN
FOLDER FRONT COUNTER WITH BUILDING APPLICATION
Printed: Tuesday, June 18, 2024 11:38:28 AM 2 of 19
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2020-0011
CONDITION
TYPE CONTACT DATE
ADDED
DATE
REQUIRED
DATE
SATISFIED STATUS REMARKS NOTES
READY TO ISSUE
CHECKLIST JAKE FUSON 2/18/2020 5/7/2020 5/7/2020 COMPLETE COMPLETE
-CONTRACTOR NEEDS BUSINESS LICENSE
-PROJECT VALUATION REQUIRED
-PATH OF TRAVEL FORM REQUIRED (SEE JF WITH
QUESTIONS)
UPDATE: P.O.T. FORM & VALUATION RECEIVED.
CONTRACTOR BUSINESS LICENSE STILL
OUTSTANDING.
CONTRACTOR BUSINESS LICENSE RECIEVED.
TELEPHONE CALL STEPHANIE SWANSTROM 5/5/2020 5/5/2020
SPOKE TO MR. HUYAN, HE STATED HE'LL BE USING A
DIFERENT CONTRACTOR. I EXPLAINED HE'LL NEED TO GET A
LETTER FROM THE CURRENT CONTRACTOR (VINCENT TRAN)
STATING HE WILL NOT BE WORKING ON THE PROJECT.
ABOUT 10 MINUTES AFTER WE ENDED THE PHONE CALL, THE
CONTRACTOR CALLED ME STATING MR. HUYAN WAS
GETTING FRUSTRATED. I EXPLAINED EVERYTHING TO HIM AS
WELL.
THERE WAS A MESSAGE TO CALL MR. HUYAN, I CALLED AND
HAD TO EXPLAIN EVERYTHING AGAIN. HE STATED HE DIDN'T
LIST VINCEN TRAN AS THE CONTRACTOR. HE ASKED IF I
COULD FIND THE APPLICATION, I FOUND HIS APPLICATION
AND BUSINESS LICENSE APPLICATION WHERE HE LISTED
VINCEN AS THE CONTRACTOR AND THE BUSINESS LICENSE
FOR THE SALON. I EMAILED BOTH TO HIM AND CALLED HIM
BACK. HE SEEMED TO UNDERSTAND WE NEED THE LETTER
FROM THE CONTRACTOR AND THE NEW CONTRACTOR
WOULD NEED A BUINSESS LICNESE. I LATER EMAILD HIM THE
SUBLIST AS WELL, AND EXPLAINED IF HIS CONTRACTOR. (SEE
EMAIL)
CONDITIONS
Printed: Tuesday, June 18, 2024 11:38:28 AM 3 of 19
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2020-0011
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT DUNG HUYNH - APPLICANT 73866 VAN GOGH DR PALM DESERT CA 92211 DUNGTHHUYNH2000@
GMAIL.COM
CONTRACTOR MODEL BUILDERS INC 15030 GOLDEN WEST
CIR #11612
WESTMINISTER CA 92685 MODEL.BUILDERS@YA
HOO.COM
CONTRACTOR
(HISTORY) 1
CENTRAL PACIFIC DESIGN/BUILD 11061 STRATFORD
WAY
GARDEN GROVE CA 92840 VINCENT@CENTRALPA
CIFIC-DB.COM
OWNER INLAND AMERICAN LAQUINTA PAV P O BOX 9271 OAK BROOK IL 92253
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
RE-INSPECTION FEE 101-0000-42400 0 $80.50 $80.50 7/15/20 WEB5701 CREDIT MODEL BUILDERS INC ECON
RE-INSPECTION FEE 101-0000-42400 0 $80.50 $80.50 7/13/20 WEB5665 CREDIT MODEL BUILDERS INC ECON
Total Paid for ADMINISTRATIVE: $161.00 $161.00
HOURLY CHARGE - CITY
BUILDING STAFF 101-0000-42600 10 $104.00 $104.00 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
HOURLY CHARGE - CITY
BUILDING STAFF 101-0000-42600 0.75 $120.75 $120.75 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
HOURLY CHARGE - CITY
BUILDING STAFF 101-0000-42600 0.5 $80.50 $80.50 9/15/20 WEB6237 04290G CREDIT MODEL BUILDERS INC ECON
HOURLY CHARGE -
INTERWEST
STRUCTURAL PLAN
REVIEW
101-0000-42600 0.5 $62.50 $62.50 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
Total Paid for BLDG CITY STAFF - PER HOUR: $367.75 $367.75
BSAS SB1473 FEE 101-0000-20306 0 $2.00 $2.00 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
Total Paid for BUILDING STANDARDS ADMINISTRATION
BSA: $2.00 $2.00
Printed: Tuesday, June 18, 2024 11:38:28 AM 4 of 19
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2020-0011
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
NON-RESIDENTIAL, EA
ADDITIONAL 2,000SF 101-0000-42403 0 $40.25 $40.25 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
NON-RESIDENTIAL, EA
ADDITIONAL 2,000SF PC 101-0000-42600 0 $10.73 $10.73 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
NON-RESIDENTIAL,
FIRST 2,000SF 101-0000-42403 0 $120.75 $120.75 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
NON-RESIDENTIAL,
FIRST 2,000SF PC 101-0000-42600 0 $93.38 $93.38 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
Total Paid for ELECTRICAL - NEW CONSTRUCTION 2019: $265.11 $265.11
FIRE COMMERCIAL TI 101-0000-42421 0 $161.00 $161.00 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
FIRE COMMERCIAL TI
PC 101-0000-42420 0 $242.00 $242.00 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
Total Paid for FIRE FEES: $403.00 $403.00
EXHAUST HOOD 101-0000-42402 0 $13.42 $13.42 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
EXHAUST HOOD PC 101-0000-42600 0 $5.37 $5.37 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
OTHER MECHANICAL
EQUIPMENT 101-0000-42402 0 $40.25 $40.25 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
OTHER MECHANICAL
EQUIPMENT PC 101-0000-42600 0 $40.25 $40.25 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
VENT FAN 101-0000-42402 0 $40.26 $40.26 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
VENT FAN PC 101-0000-42600 0 $16.11 $16.11 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
Total Paid for MECHANICAL 2019: $155.66 $155.66
PLAN CHECK DEPOSIT -
ADDITION/REMODEL 101-0000-42600 1 $125.00 $125.00 2/14/20 R59644 1015 CHECK LA QUINTA NAIL BAR AHI
Total Paid for PLAN CHECK DEPOSIT - ADDITION/REMODEL: $125.00 $125.00
FIXTURE/TRAP 101-0000-42401 0 $308.66 $308.66 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
FIXTURE/TRAP PC 101-0000-42600 0 $308.66 $308.66 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
Printed: Tuesday, June 18, 2024 11:38:28 AM 5 of 19
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2020-0011
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
GAS SYSTEM, 1-4
OUTLETS 101-0000-42401 0 $13.42 $13.42 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
GAS SYSTEM, 1-4
OUTLETS PC 101-0000-42600 0 $26.83 $26.83 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
WATER HEATER/VENT 101-0000-42401 0 $13.42 $13.42 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
WATER HEATER/VENT
PC 101-0000-42600 0 $8.05 $8.05 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
WATER SYSTEM
INST/ALT/REP 101-0000-42401 0 $13.42 $13.42 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
WATER SYSTEM
INST/ALT/REP PC 101-0000-42600 0 $13.42 $13.42 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
Total Paid for PLUMBING 2019: $705.88 $705.88
RECORDS
MANAGEMENT FEE -
MAJOR
101-0000-42416 0 $21.00 $21.00 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
Total Paid for RECORDS MANAGEMENT FEE - MAJOR: $21.00 $21.00
101-0000-42600 ($69.76)($69.76)5/4/20 OFFSET OFFSET JFU
101-0000-42600 ($54.74)($54.74)5/4/20 OFFSET OFFSET JFU
REMODEL, EA
ADDITIONAL 500SF 101-0000-42400 0 $120.75 $120.75 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
REMODEL, EA
ADDITIONAL 500SF PC 101-0000-42600 0 $96.60 $96.60 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
REMODEL, FIRST 100SF 101-0000-42400 0 $54.74 $54.74 5/4/20 DEPOSIT DEPOSIT JFU
REMODEL, FIRST 100SF
PC 101-0000-42600 0 $69.76 $69.76 5/4/20 DEPOSIT DEPOSIT JFU
REMODEL, FIRST 100SF
PC 101-0000-42600 0 $79.97 $79.97 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
Total Paid for REMODEL 2019: $297.32 $297.32
101-0000-42600 ($0.50)($0.50)5/4/20 OFFSET OFFSET JFU
Printed: Tuesday, June 18, 2024 11:38:28 AM 6 of 19
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2020-0011
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
UNDERGROUND PLBG AOR 5/13/2020 5/13/2020
APPROVED
W/EXCEPTIO
N
eTRAKiT Inspection
Request
5/12/2020 2:26 PM MODEL BUILDERS INC
Contact Name: MODEL BUILDERS INC
Site Address: 79070 HIGHWAY 111 STE 103
Phone: 7143269188
e-Mail: MODEL.BUILDERS@YAHOO.COM
ALL AREAS APPROVED WITH EXCEPTION OF
THE WASHER REQUIRES STANDPIPE
INSTALLATION AND THE BACK ROOM SINKS
NEED SEPARATE VENTING BASED ON ABOVE
SLAB ROUGH IN PIPING OR SEPARATE DRAIN
PIPES.
GAS LINE/TEST AOR 6/10/2020 6/10/2020 APPROVED
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
SMI - COMMERCIAL 101-0000-20308 0 $0.50 $0.50 5/4/20 DEPOSIT DEPOSIT JFU
Total Paid for STRONG MOTION INSTRUMENTATION SMI: $0.00 $0.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
ALTERATIONS/ADDITIO
NS - NON-RESIDENTIAL 101-0000-42400 0 $161.00 $161.00 5/7/20 WEB5066 CREDIT MODEL BUILDERS INC ECON
Total Paid for ZONING CLEARANCE - PLANNING PLAN
CHECK: $161.00 $161.00
TOTALS:$2,669.72 $2,669.72
Printed: Tuesday, June 18, 2024 11:38:28 AM 7 of 19
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2020-0011
ROUGH PLBG AOR 6/10/2020 6/10/2020 APPROVED eTRAKiT Inspection
Request
6/9/2020 10:07 AM MODEL BUILDERS INC
I would like to make appointment inspection
for slab rebar. electrical, plumbing and
framing.
Contact Name: MODEL BUILDERS INC
Site Address: 79070 HIGHWAY 111 STE 103
Phone: 7143269188
e-Mail: MODEL.BUILDERS@YAHOO.COM
INCLUDES CORRECTION OF UNDERGROUND
PLUMBING EXCEPTIONS.
ROUGH ELEC AOR 6/10/2020 6/10/2020 PARTIALLY
APPROVED
eTRAKiT Inspection
Request
6/9/2020 10:07 AM MODEL BUILDERS INC
I would like to make appointment inspection
for slab rebar. electrical, plumbing and
framing.
Contact Name: MODEL BUILDERS INC
Site Address: 79070 HIGHWAY 111 STE 103
Phone: 7143269188
e-Mail: MODEL.BUILDERS@YAHOO.COM
WALLS ONLY, CEILINGS NOT READY, AND
SWITCHING OF LIGHTING IN DAYLIT AREAS
NOT CONTROLLED BY MANDATORY
MEASURES.
FRAMING AOR 6/10/2020 6/10/2020 PARTIALLY
APPROVED
eTRAKiT Inspection
Request
6/9/2020 10:07 AM MODEL BUILDERS INC
I would like to make appointment inspection
for slab rebar. electrical, plumbing and
framing.
Contact Name: MODEL BUILDERS INC
Site Address: 79070 HIGHWAY 111 STE 103
Phone: 7143269188
e-Mail: MODEL.BUILDERS@YAHOO.COM
Printed: Tuesday, June 18, 2024 11:38:28 AM 8 of 19
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2020-0011
FRAMING AOR 6/10/2020 6/10/2020 PARTIALLY
APPROVED
eTRAKiT Inspection
Request
WALLS INCLUDING DEMISING WALL ONLY,
CORRECTIONS REQUIRED AT HARD LID
CEILING FRAMING AS IT DOES NOT MATCH
APPROVED DETAILING.
OVERHEAD ROUGH
PIPING KHET 6/23/2020 6/23/2020 APPROVED
FRAMING DCL 6/24/2020 6/24/2020 DISAPPROVE
D
eTRAKiT Inspection
Request
6/23/2020 3:43 PM MODEL BUILDERS INC
Ceiling framing and drywall
Contact Name: MODEL BUILDERS INC
Site Address: 79070 HIGHWAY 111 STE 103
Phone: 7143269188
e-Mail: MODEL.BUILDERS@YAHOO.COM
- KICKERS MISSING AT 48" ON CENTER PER
PERIMETER SOFFIT DETAIL.- INSTALL
MECHANICAL REGISTERS AT WAX ROOMS
AND COMPLETE RETURN AIR DUCTING.-
MAIN AREA SOFFITS NOT PER PLAN. RFI
FROM EOR REQUIRED FOR ALTERNATE
DIAGONAL AND VERTICAL STUD SPACING
AND ATTACHMENT.
DRYWALL NAIL DCL 6/24/2020 6/24/2020 NOT READY eTRAKiT Inspection
Request
6/23/2020 3:43 PM MODEL BUILDERS INC
Ceiling framing and drywall
Contact Name: MODEL BUILDERS INC
Site Address: 79070 HIGHWAY 111 STE 103
Phone: 7143269188
e-Mail: MODEL.BUILDERS@YAHOO.COM
- WALLS INCOMPLETE. CALL IN WHEN
READY.
Printed: Tuesday, June 18, 2024 11:38:28 AM 9 of 19
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2020-0011
ROUGH MECH JFU 7/2/2020 7/2/2020
APPROVED
W/EXCEPTIO
N
eTRAKiT Inspection
Request
6/30/2020 7:53 PM MODEL BUILDERS INC
Drop Ceiling framing. and rough mechanical
Contact Name: MODEL BUILDERS INC
Site Address: 79070 HIGHWAY 111 STE 103
Phone: 7143269188
e-Mail: MODEL.BUILDERS@YAHOO.COM
DOES NOT INCLUDE FRAMING--SEE
FRAMING COMMENTS.
FRAMING JFU 7/2/2020 7/2/2020 DISAPPROVE
D
eTRAKiT Inspection
Request
6/30/2020 7:53 PM MODEL BUILDERS INC
Drop Ceiling framing. and rough mechanical
Contact Name: MODEL BUILDERS INC
Site Address: 79070 HIGHWAY 111 STE 103
Phone: 7143269188
e-Mail: MODEL.BUILDERS@YAHOO.COM
SUSPENDED HARD LID CEILING AND SOFFIT
FRAMING DO NOT MATCH APPROVED
PLANS. RFI'S OR REVISED CONSTRUCTION
REQUIRED, REINSPECTION FEE ASSESSED.
T-BAR/OVERHEAD JFU 7/2/2020 7/2/2020
APPROVED
W/EXCEPTIO
N
INSPECTED T-BAR/OVERHEAD AT LAUNDRY
ROOM. CONSTRUCTION IS APPROVABLE
ASIDE FROM THE INSTALLATION OF A
COMPRESSION STRUT. CONTRACTOR
AGREES TO PULL DOWN CEILING TILES AT A
LATER INSPECTION OR THE FINAL
INSPECTION TO DEMONSTRATE
COMPLIANCE.
T-BAR/OVERHEAD JFU 7/14/2020 7/14/2020 APPROVED PREVIOUS COMMENT RESOLVED AT
LAUNDRY AREA.
Printed: Tuesday, June 18, 2024 11:38:28 AM 10 of 19
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2020-0011
FRAMING JFU 7/14/2020 7/14/2020 DISAPPROVE
D
eTRAKiT Inspection
Request
7/13/2020 9:59 AM MODEL BUILDERS INC
Hi, I would like to make appointments
ceiling framing and drywall nails inspection.
Thank you
Contact Name: MODEL BUILDERS INC
Site Address: 79070 HIGHWAY 111 STE 103
Phone: 7143269188
e-Mail: MODEL.BUILDERS@YAHOO.COM
SAME ISSUES EXIST AT SOFFITS.
REINSPECTION FEE ASSESSED.
DRYWALL NAIL JFU 7/14/2020 7/14/2020 PARTIALLY
APPROVED
eTRAKiT Inspection
Request
7/13/2020 10:00 AM MODEL BUILDERS INC
Contact Name: MODEL BUILDERS INC
Site Address: 79070 HIGHWAY 111 STE 103
Phone: 7143269188
e-Mail: MODEL.BUILDERS@YAHOO.COM
WAX ROOMS ONLY.
FRAMING AOR 7/15/2020 7/15/2020 eTRAKiT Inspection
Request
7/14/2020 12:51 PM MODEL BUILDERS INC
ceiling kicker frame.
Contact Name: MODEL BUILDERS INC
Site Address: 79070 HIGHWAY 111 STE 103
Phone: 7143269188
e-Mail: MODEL.BUILDERS@YAHOO.COM
SAME ISSUES EXIST AT SOFFITS - MET WITH
OWNER AND CONTRACTOR ONSITE TO
DISCUSS THE RFI REQUIRED FROM THE EOR,
BUSINESS CARD GIVEN TO EMAIL REVISED
DETAILING.
GAS RELEASE AOR 7/16/2020 7/16/2020 APPROVED GAS RELEASE SENT.
Printed: Tuesday, June 18, 2024 11:38:28 AM 11 of 19
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2020-0011
FRAMING JFU 7/21/2020 7/21/2020 APPROVED eTRAKiT Inspection
Request
7/20/2020 2:54 PM MODEL BUILDERS INC
Hi,
I would like to make appointment for ceiling
framing.
Contact Name: MODEL BUILDERS INC
Site Address: 79070 HIGHWAY 111 STE 103
Phone: 7143269188
e-Mail: MODEL.BUILDERS@YAHOO.COM
PREVIOUS CORRECTIONS RESOLVED, OKAY
TO APPLY GYPSUM BOARD AT SOFFITS.
DRYWALL NAIL JFU 7/27/2020 7/27/2020 APPROVED eTRAKiT Inspection
Request
7/23/2020 10:14 PM MODEL BUILDERS INC
drywall Nail
Contact Name: MODEL BUILDERS INC
Site Address: 79070 HIGHWAY 111 STE 103
Phone: 7143269188
e-Mail: MODEL.BUILDERS@YAHOO.COM
ALL REMAINING AREAS.
TEMP USE OF PERM PWR JFU 7/28/2020 7/28/2020
APPROVED
W/EXCEPTIO
N
eTRAKiT Inspection
Request
7/27/2020 3:21 PM MODEL BUILDERS INC
Please bring application document for TI
owner if he need to pay temporary power
fees. Thank you.
Contact Name: MODEL BUILDERS INC
Site Address: 79070 HIGHWAY 111 STE 103
Phone: 7143269188
e-Mail: MODEL.BUILDERS@YAHOO.COM
Printed: Tuesday, June 18, 2024 11:38:28 AM 12 of 19
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2020-0011
TEMP USE OF PERM PWR JFU 7/28/2020 7/28/2020
APPROVED
W/EXCEPTIO
N
eTRAKiT Inspection
Request
DISTRIBUTION EQUIPMENT DOES NOT
APPEAR TO MATCH PLANS. PER
CONTRACTOR, "PANEL B" HAS BEEN
ELIMINATED AND ALL BRANCH CIRCUITRY IS
NOW SUPPLIED BY "PANEL A" AND FED BY A
SINGLE METER. ELECTRICAL FLOOR PLAN,
PANEL SCHEDULES AND SINGLE LINE
DIAGRAM MUST BE REVISED PRIOR TO
FINAL INSPECTION, HOWEVER THE
INSTALLATIONS ARE PROTECTED AND
APPEAR TO BE SAFE FOR UTILIZATION, SO A
RELEASE WILL BE SENT TO THE UTILITY WITH
THE CONDITION THAT THE PLANS GET
REVISED AND APPROVED AND A
REINSPECTION IS SCHEDULED TO VERIFY
COMPLIANCE WITH THE NEW APPROVED
PLANS.
FINAL**AOR 9/9/2020 9/9/2020 CANCELED eTRAKiT Inspection
Request
9/8/2020 12:55 PM MODEL BUILDERS INC
Final electrical, plumbing, mechanical and
final building.
Contact Name: MODEL BUILDERS INC
Site Address: 79070 HIGHWAY 111 STE 103
Phone: 7143269188
e-Mail: MODEL.BUILDERS@YAHOO.COM
T/I FINAL KHET 9/10/2020 9/10/2020 APPROVED REMOTE VIDEO
INSPECTION
FIRE CLEARANCE GRANTED. MINOR ITEMS
TO BE FOLLOWED UP WITH UNDER THE FIRE
ANNUAL CASE.
FINAL**JFU 9/14/2020 9/14/2020 DISAPPROVE
D
eTRAKiT Inspection
Request
9/10/2020 5:10 PM MODEL BUILDERS INC
I would like to make schedule for Final
Building inspection. Thank you.
Contact Name: MODEL BUILDERS INC
Site Address: 79070 HIGHWAY 111 STE 103
Phone: 7143269188
e-Mail: MODEL.BUILDERS@YAHOO.COM
Printed: Tuesday, June 18, 2024 11:38:28 AM 13 of 19
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2020-0011
FINAL**JFU 9/14/2020 9/14/2020 DISAPPROVE
D
eTRAKiT Inspection
Request
-SUBMIT THE ELECTRICAL PLAN REVISION
FOR REVIEW, SEE INSPECTION NOTES FROM
7/28/2020
-COMPLETE THE BUSINESS LICENSE
ISSUANCE PROCESS
-PROVIDE A DIRECT ELECTRICAL
CONNECTION WITH DISCONNECT FOR THE
WATER HEATER
-ONE OF THE HAND SINKS IN THE MAIN
ROOM MUST BE ACCESSIBLE PER CBC
11B-606
-PROVIDE NRCI AND NRCA FORMS FOR
INDOOR LIGHTING
FINAL**AOR 9/16/2020 9/16/2020 DISAPPROVE
D
ALL ITEMS CORRECTED WITH EXCEPTION TO
PROVIDING LIGHTING INSTALLATION AND
ACCEPTANCE FORMS.
FINAL**AOR 9/21/2021 9/21/2021 APPROVED
FOUND OPEN PERMIT DURING 'EXPIRED
PERMIT AUDIT' - BASED ON FORMS
ATTACHED 10/6/2020 BEING APPROVAL,
BUT NEVER FOLLOWED UP WITH
PREVIOUSLY, THE STATUS IS BEING
UPDATED TO SHOW THE WORK HAS SINCE
BEEN COMPLETED.
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST PLANNING (2
WK)
SIJIFREDO
FERNANDEZ 2/14/2020 2/28/2020 2/18/2020 READY FOR APPROVAL
1ST PUBLIC WORKS
(2 WK)AMY YU 2/14/2020 2/28/2020 2/27/2020 COMPLETE NO COMMENTS
1ST FIRE (2 WK)KOHL
HETRICK 2/14/2020 2/28/2020 3/6/2020 REVISIONS REQUIRED
PARENT PROJECTS
Printed: Tuesday, June 18, 2024 11:38:28 AM 14 of 19
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2020-0011
1ST PERMIT TECH (1
DAY)
AARON
HICKSON 2/14/2020 2/18/2020 2/18/2020 COMPLETE
1ST BLDG
COMPLETE (2 WK)INTERWEST 2/14/2020 2/28/2020 3/3/2020 REVISIONS REQUIRED
1ST BLDG NS (2 WK)JAKE FUSON 2/14/2020 2/28/2020 3/12/2020 REVISIONS REQUIRED SEE 1ST REVIEW - COMPLETE CORRECTION LIST.
2ND BLDG
COMPLETE (1 WK)INTERWEST 4/7/2020 4/14/2020 4/13/2020 REVISIONS REQUIRED
2ND BLDG NS –
ETRAKIT (1 WK)JAKE FUSON 4/7/2020 4/14/2020 4/15/2020 REVISIONS REQUIRED SEE 2ND REVIEW CORRECTION LIST.
FIRE GENERAL CONDITIONS
Fire Department approval is based upon the 2019
CBC requirements for B Occupancies with an
occupant load of 24. It is prohibited to use,
process or store any materials in the occupancy
that would classify it as a Group H occupancy,
without further review and approval.
DEFERRED SUBMITTALS REQUIRED
1) FIRE SPRINKLER – Tenant Improvement plans
must be submitted and reference the installing
contractor performing the work. Permit fees will
be required.
2) FIRE ALARM/MONITORING SYSTEM – Tenant
Improvement plans must be submitted per NFPA
72 as required by the California Building Code,
California Fire Code and designed in accordance
with adopted standards. A C-10 licensed
contractor must submit plans to the Fire
Department office for review and approval prior
to installation. Permit fees will be required.
PRIOR TO FINAL INSPECTION
1) Provide keys to the tenant space for inclusion
in the main building Knox Box. Key(s) shall have
durable and legible tags affixed for identification
of the correlating tenant space.
2) Approved building address shall be placed in
Printed: Tuesday, June 18, 2024 11:38:28 AM 15 of 19
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2020-0011
BOND INFORMATION
2ND FIRE - ETRAKIT
(1 WK)
KOHL
HETRICK 4/7/2020 4/14/2020 4/15/2020 READY FOR APPROVAL SEE NOTES FOR
CONDITIONS
such a position as to be plainly visible and legible
from the street and rear access if applicable.
Building address numbers shall be a minimum of
12”. Minimum 6” tall suite addressing shall be
provided to both the front and rear entrances. All
addressing must be legible and of a contrasting
color with the to be visible from the street at all
hours.
3) Install portable fire extinguishers per Title 19,
but not less than 2A10BC in rating. All new and
existing portable fire extinguishers shall have
current annual servicing performed and tagged.
4) A durable sign stating: "THIS DOOR TO REMAIN
UNLOCKED WHEN THIS SPACE IS OCCUPIED" shall
be placed on or adjacent to the front exit doors.
The sign shall be in letters not less than one inch
high on a contrasting background (A <300, B, F, M
and S).
5) Illuminated Exit Signage and Egress
Illumination placement and functional test will be
witnessed by OFM Fire Inspector at time of final
inspection.
The Fire Department approved plans and
conditions letter must be at the job site.
Applicant/installer shall be responsible to contact
the Fire Department to schedule inspections.
Requests for inspections are to be made at least
48 hours in advance and may be arranged by
calling (760)777-7131.
3RD BLDG NS –
ETRAKIT (1 WK)JAKE FUSON 4/23/2020 4/30/2020 5/4/2020 APPROVED
1ST BLDG NS -
ETRAKIT (1 DAY)JAKE FUSON 9/15/2020 9/16/2020 9/15/2020 APPROVED REVISION 1
REVISION 1 - ELECTRICAL DISTRIBUTION
EQUIPMENT REVISION (REVISED SINGLE LINE
DIAGRAM, POWER PLAN & PANEL SCHEDULE).
Printed: Tuesday, June 18, 2024 11:38:28 AM 16 of 19
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2020-0011
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 2/14/2020 AARON HICKSON 1ST SUBMITTAL PLAN
SET - 1 OF 4 1OF4.pdf 1
DOC 2/14/2020 AARON HICKSON 1ST SUBMITTAL PLAN
SET - 2 OF 4 2OF4.pdf 1
DOC 2/14/2020 AARON HICKSON 1ST SUBMITTAL PLAN
SET - 3 OF 4 3OF4.pdf 1
DOC 2/14/2020 AARON HICKSON 1ST SUBMITTAL PLAN
SET - 4 OF 4 4OF4.pdf 1
DOC 10/6/2020 EtrakitContractor Electrical report La.Quinta.E.report5.pdf 1
DOC 10/6/2020 EtrakitContractor Electrical report La.Quinta.E.report_1.pd
f 1
DOC 10/6/2020 EtrakitContractor Electrical report La.Quinta.E.report1.pdf 1
DOC 10/6/2020 EtrakitContractor Electrical report La.Quinta.E.report2.pdf 1
DOC 10/6/2020 EtrakitContractor Electrical report La.Quinta.E.report3.pdf 1
DOC 10/6/2020 EtrakitContractor Electrical report La.Quinta.E.report4.pdf 1
DOC 4/6/2020 EtrakitPublicReg
2ND SUBMITTAL -
CORRECTION
RESPONSES (BUILDING)
BCOM2020-0011 - 1ST
REVIEW - COMPLETE
CORRECTION LIST
_1.pdf
1
DOC 4/6/2020 EtrakitPublicReg
2ND SUBMITTAL -
CORRECTION
RESPONSES (FIRE)
BCOM2020-0011 - LQ
NAIL BAR TI - FIRE
CORRECTIONS_1.pdf
1
DOC 4/7/2020 EtrakitPublicReg 2ND SUBMITTAL - PLAN
SET
LA QUINTA NAIL BAR-
CORRECTED FILES.pdf 1
DOC 4/23/2020 EtrakitPublicReg 3RD SUBMITTAL - PLAN
SET
BCOM2020-0011 Nail
Salon plans.pdf 1
DOC 4/23/2020 EtrakitPublicReg
3RD SUBMITTAL -
CORRECTION
RESPONSES
2ND CORRECTIONS
RESPOND.pdf 1
Printed: Tuesday, June 18, 2024 11:38:28 AM 17 of 19
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2020-0011
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 4/23/2020 EtrakitPublicReg FLOOR SINK BASKET floor sink-GWS-FS-
BSI.pdf 1
DOC 4/23/2020 EtrakitPublicReg PIPE HOOK Plumbing IAPMO.pdf 1
DOC 7/17/2020 EtrakitPublicReg SOFIT DETAIL FOR
INSPECTOR SOFIT DETAIL.pdf 1
DOC 3/3/2020 INTERWEST 1ST REVIEW -
INTERWEST INVOICE
La Quinta - 202001524;
BCOM2020-0011 -
Invoice 57773.pdf
1
DOC 4/13/2020 INTERWEST 2ND REVIEW -
INTERWEST COMMENTS
202001524 PC2 -
BCOM2020-00011
46243 79070 HWY
111.docx
0
DOC 4/13/2020 INTERWEST 2ND REVIEW -
INTERWEST INVOICE
La Quinta - 202001524;
BCOM2020-0011 -
Invoice 58845.pdf
0
DOC 3/12/2020 JAKE FUSON 1ST REVIEW - REDLINED
PLAN SET
BCOM2020-0011 - 1ST
REVIEW - REDLINED
PLAN SET.pdf
1
DOC 3/12/2020 JAKE FUSON
1ST REVIEW -
COMPLETE CORRECTION
LIST
BCOM2020-0011 - 1ST
REVIEW - COMPLETE
CORRECTION LIST .pdf
1
DOC 4/16/2020 JAKE FUSON 2ND REVIEW
CORRECTION LIST
BCOM2020-0011 - 2ND
REVIEW CORRECTION
LIST.pdf
1
DOC 5/4/2020 JAKE FUSON APPROVED PLAN SET
BCOM2020-0011 -
APPROVED PLAN
SET.pdf
1
DOC 5/5/2020 JAKE FUSON
PATH OF TRAVEL
UPGRADE
DETERMINATION
BCOM2020-0011 - PATH
OF TRAVEL UPGRADE
DETERMINATION.pdf
1
Printed: Tuesday, June 18, 2024 11:38:28 AM 18 of 19
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2020-0011
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 9/15/2020 JAKE FUSON REVISION 1 - 1ST
SUBMITTAL
BCOM2020-0011 -
REVISION 1 - 1ST
SUBMITTAL.pdf
1
DOC 9/15/2020 JAKE FUSON REVISION 1 - APPROVED
ELECTRICAL PLAN
BCOM2020-0011 -
REVISION 1 - APPROVED
ELECTRICAL PLAN.pdf
1
DOC 9/25/2020 JAKE FUSON
CERTIFICATE OF
ACCEPTANCE - INDOOR
LIGHTING - NRCA-LTI-02
-A
BCOM2020-0011 -
NRCA-LTI-02-A.pdf 1
DOC 3/17/2020 JACK LIMA 1ST REVIEW -
INTERWEST COMMENTS
202001524 PC1 -
BCOM2020-00011
46243 79070 HWY
111.docx
0
DOC 5/7/2020 JACK LIMA CHANGE OF
CONTRACTOR
CHANGE OF
CONTRACTOR.pdf 0
DOC 5/7/2020 JACK LIMA
OpenReceipt - UNPAID
and TRANSFERRED BL
CHARGES
OpenReceipt.pdf 0
DOC 3/6/2020 KOHL HETRICK 1ST REVIEW - FIRE
CORRECTIONS
BCOM2020-0011 - LQ
NAIL BAR TI - FIRE
CORRECTIONS.pdf
1
Printed: Tuesday, June 18, 2024 11:38:28 AM 19 of 19
Permit Details
City of La Quinta
PERMIT NUMBER
BCOM2020-0011
CT.BKR/ BKR/CT.# LTG REC M/SC A B C POLE POLE A B C M/SC REC LTG #PEDICURE 1. 2 960 20/2 20/1 1350 1 2. REFRIG.PEDICURE 3. 2 960 20/2 20/1 2250 1 4. WASHERPEDICURE 5. 2 960 20/2 20/1 1800 1 6. DRYERPEDICURE 7. 2 960 20/2 20/1 1200 2 8. WAITING.1PEDICURE 9. 2 960 20/2 20/1 1800 2 10. GFI. RESTROOM 1.2PEDICURE 11. 2 960 20/2 20/1 1800 4 12. WAX-1. HALL WAYPEDICURE 13. 2 960 20/2 20/1 1800 4 14. WAX-2. GFI. COUNTER 1PEDICURE 15. 2 960 20/2 20/1 1800 4 16. WAX-2. GFI. COUNTER 2PEDICURE 17. 2 960 20/2 20/1 1200 3 18. RECEPTION. NAIL DRYERNAILS BAR 19. 4 1800 20/1 20/1 1200 2 20. WAITING.2NAILS BAR 21. 4 1800 20/1 20/1 1200 2 22. TELEVISIONNAILS BAR 23. 4 1800 20/1 20/12 24. TELEVISIONNAILS BAR 25. 4 1800 20/1 20/1 300 1 26. ROOF FANRESTROOM FAN 1.2 (TANDEM BREAKER) 27. 2 60 20/2 20/2 120 2 28.LAUNDRY FAN. BOOSTER FAN (TANDEM BREAKER)EXISTING AC 1 (5 TONS) 29. 1 1 5840 30/3 30/3 5840 1 1 30. EXISTING AC 2 (5 TONS)- 31. 5840 30/3 30/3 5840 32. -- 33.5840 30/3 30/3 5840 34. -TIMER 35. 1 24 20/1 20/1 1200 7 36. EXIT SIGN/ EMERGENCY LIGHTSHOW WINDOW 37. 1 1800 20/1 20/1 393 15 38. LIGHTSLIGHTS 39. 44 908 20/1 20/1 988 34 40. LIGHTS41.20/1 20/1 760 40 42. LIGHTS12344 12380 11428 13350 13403 11928 Sub totalTotal A Phase =Total B Phase =Total C Phase = EXISTING PANEL 25694 VA25783 VASub totalOUTLETSPANEL : "P"BREAKER : MOUNTINGOUTLETS= 207A23356 VAVOLTAGE / PHASE : 120/208 3 PH. 4W.VOLT AMPS74833 VABUS : 225 AMPS 65KAICTOTAL LOAD =VOLT AMPSREVISION 1BCOM2020-0011REVISED SINGLE LINEDIAGRAM, POWER PLAN ANDPANEL SCHEDULE09/15/2020