BMCH2022-0394 - Title 24BUILDING ENERGY ANALYSIS REPORT
PROJECT:
Project Designer:
Report Prepared by:
Job Number:
Date:
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2019 Building Energy Efficiency Standards.
This program developed by EnergySoft Software – www.energysoft.com.
,
79220 Hwy 111
Best Buy #1020
La Quinta, CA 92253
103 W. El Portal #c
Vander Veen Engineering Consultants
Jason Vander Veen
San Clemente, CA 92672
7/18/2022
08/20/2022
BMCH2022-0394
HVAC CHANGE OUT - (1)
ROOF TOP 10-TON
PACKAGE UNIT, WEIGHT
NOT TO EXCEED 1,600LBS
AS PERMITTED ON SHELL
BUILDING PLANS. 2019
CALIFORNIA BUILDING
CODES.
TABLE OF CONTENTS
Cover Page
Table of Contents
Form NRCC-MCH-E Mechanical Systems
1
2
3
Registration Number:Registration Date/Time:Registration Provider: Energysoft
CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
Schema Version: rev 20200601
Report Generated: 2022-07-18 22:42:44
STATE OF CALIFORNIA
Mechanical Systems
NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
This document is used to demonstrate compliance for mechanical systems that are within the scope of the permit application and are demonstrating compliance using the prescriptive
path outlined in §140.4, or §141.0(b)2 for alterations.
Project Name: Best Buy #1020 Report Page: (Page 1 of 9)
Project Address: 79220 Hwy 111 Date Prepared: 7/18/2022
A. GENERAL INFORMATION
01 Project Location (city)La Quinta 04 Total Conditioned Floor Area 2000
02 Climate Zone 5 05 Total Unconditioned Floor Area 0
03 Occupancy Types Within Project:06 # of Stories (Habitable Above Grade)1
Office (B)Retail (M)Non-refrigerated Warehouse (S)
Hotel/ Motel Guest Rooms (R-1)School (E)Healthcare Facility (I)
High-Rise Residential (R-2/R-3)Relocatable Class Bldg (E)Other (write in)See Table J
B. PROJECT SCOPE
This table Includes mechanical systems or components that are within the scope of the permit application and are demonstrating compliance using the prescriptive path outlined in
§140.4, or §141.0(b)2 for alterations.
01 02 03
Air System(s)Wet System Components Dry System Components
Heating Air System Water Economizer Air Economizer
Cooling Air System Pumps Electric Resistance Heat
Mechanical Controls System Piping Fan Systems
Mechanical Controls (existing to remain, altered
or new)Cooling Towers Ductwork (existing to remain, altered or new)
Chillers Ventilation
Boilers Zonal Systems/ Terminal Boxes
08/20/2022
BMCH2022-0394
STATE OF CALIFORNIA
Mechanical Systems
NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
Project Name: Best Buy #1020 Report Page: (Page 2 of 9)
Project Address: 79220 Hwy 111 Date Prepared: 7/18/2022
Registration Number:Registration Date/Time:Registration Provider: Energysoft
CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
Schema Version: rev 20200601
Report Generated: 2022-07-18 22:42:44
C. COMPLIANCE RESULTS
Table C will indicate if the project data input into the compliance document is compliant with mechanical requirements. This table is not editable by the user. If this table says "DOES
NOT COMPLY" or "COMPLIES with Exceptional Conditions" refer to Table D., or the table indicated as not compliant for guidance.
01
AND
02
AND
03
AND
04
AND
05
AND
06
AND
07
AND
08 09
System
Summary
§110.1,
§110.2,
§140.4
Pumps
§140.4(k)
Fans/
Economizers
§140.4(c),
§140.4(e)
System
Controls
§110.2,
§120.2,
§140.4(f)
Ventilation
§120.1
Terminal Box
Controls
§140.4(d)
Distribution
§120.3,
§140.4(l)
Cooling Towers
§110.2(e)2 Compliance Results
(See Table F)(See Table G)(See Table H)(See Table I)(See Table J)(See Table K)(See Table L)(See Table M)
Yes AND AND Yes AND Yes AND Yes AND AND Yes AND COMPLIES
Mandatory Measures Compliance (See Table Q for Details)COMPLIES
D. EXCEPTIONAL CONDITIONS
This table is auto-filled with uneditable comments because of selections made or data entered in tables throughout the form.
E. ADDITIONAL REMARKS
This table includes remarks made by the permit applicant to the Authority Having Jurisdiction.
STATE OF CALIFORNIA
Mechanical Systems
NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
Project Name: Best Buy #1020 Report Page: (Page 3 of 9)
Project Address: 79220 Hwy 111 Date Prepared: 7/18/2022
Registration Number:Registration Date/Time:Registration Provider: Energysoft
CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
Schema Version: rev 20200601
Report Generated: 2022-07-18 22:42:44
F. HVAC SYSTEM SUMMARY (DRY & WET SYSTEMS)
This table is used to demonstrate compliance for mechanical equipment with mandatory requirements found in §110.1 and §110.2(a) and prescriptive requirements found in §140.4(a),
§140.4(b) and §140.4(k) or §141.0(b)2 for alterations.
Dry System Equipment Sizing (includes air conditioners, condensers, heat pumps, VRF, furnaces and unit heaters)
01 02 03 04 05 06 07 08 09 10 11
Name or Item
Tag
Equipment Category per
Tables 110.2
Equipment Type per Tables 110.2 / Title
20
Smallest Size
Available1
§140.4(a)
Equipment Sizing per Mechanical Schedule (kBtu/h)
§140.4 (a&b)
Heating Output2,3 Cooling Output2,3 Load Calculations3,4
Per Design
(kBtu/h)
Rated
(kBtu/h)
Supp.
Heating
Output
(kBtu/h)
Sensible
Per Design
(kBtu/h)
Rated
(kBtu/h)
Total
Heating
Load
(kBtu/h)
Total
Sensible
Cooling
Load
(kBtu/h)
Rooftop-
Replacement 10
Tons
Unitary Heat Pumps Air-cooled, pkg (3 phase)NA: Load
Controls 72.91 120 0 103.08 94.59 34.45 105.39
1FOOTNOTES: Equipment shall be the smallest size, within the available options of the desired equipment line, necessary to meet the design heating and cooling loads of the building per
§140.4(a). Healthcare facilities are excepted.
2It is common practice to show rated output capacity on the equipment schedule. Sensible cooling output comes from specification sheet tables.
3 If equipment is heating only, leave cooling output and load blank. If equipment is cooling only, leave heating output and load blank.
4 Authority Having Jurisdiction may ask for load calculations used for compliance per §140.4(b).
STATE OF CALIFORNIA
Mechanical Systems
NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
Project Name: Best Buy #1020 Report Page: (Page 4 of 9)
Project Address: 79220 Hwy 111 Date Prepared: 7/18/2022
Registration Number:Registration Date/Time:Registration Provider: Energysoft
CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
Schema Version: rev 20200601
Report Generated: 2022-07-18 22:42:44
F. HVAC SYSTEM SUMMARY (DRY & WET SYSTEMS)
Dry System Equipment Efficiency (other than Package Terminal Air Conditioners (PTAC) and Package Terminal Heat Pumps (PTHP))
01 02 03 04 05 06 07 08 09
Name or Item
Tag
Size Category
(Btu/h)
Heating Mode Cooling Mode
Rating
Condition
( °F)
Efficiency Unit
Minimum
Efficiency
Required per
Tables 110.2 /
Title 20
Design Efficiency Efficiency Unit
Minimum
Efficiency
Required per
Tables 110.2 /
Title 20
Design Efficiency
Rooftop-
Replacement 10
Tons
>=65,000 and <135,000 COP 3.3 3.3 EER
IEER
11
12.2
11.3
12.9
G. PUMPS
This section does not apply to this project.
H. FAN SYSTEMS & AIR ECONOMIZERS
This table is used to demonstrate compliance with prescriptive requirements found in §140.4(c),§140.4(e) and §140.4(m) for fan systems. Fan systems serving only process loads are
exempt from these requirements and do not need to be included in Table H.
System
Name:
Rooftop-
Replacement 10
Tons
Economizer:1 NA: Special OA filtration Economizer
Controls:
Designed per §140.4(e) and
(m)System Fan Type:Constant Volume
01 02 03 04 05 06 07 08
Fan Name or
Item Tag Fan Function Qty Maximum Design Supply Airflow
(CFM)HP Unit2 Design HP
Fan Power Pressure Drop Adjustment - Table 140.4-B
Device Design Airflow through
Device (CFM)
SF Supply 1 4000 BHP 1.5 NA NA
Total System Design Supply Airflow (CFM):4000 Total System Design
(B)HP:1.5 Maximum System Fan
Power (B)HP:
1 FOOTNOTES: Computer room economizers must meet requirements of §140.9(a) and will be documented on the NRCC-PRC-E document.
2 The unit used for HP must be consistent for all fans within a system.
STATE OF CALIFORNIA
Mechanical Systems
NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
Project Name: Best Buy #1020 Report Page: (Page 5 of 9)
Project Address: 79220 Hwy 111 Date Prepared: 7/18/2022
Registration Number:Registration Date/Time:Registration Provider: Energysoft
CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
Schema Version: rev 20200601
Report Generated: 2022-07-18 22:42:44
I. SYSTEM CONTROLS
This table is used to demonstrate compliance with mandatory controls in §110.2 and §120.2 and prescriptive controls in §140.4(f) and (n) or requirements in §141.0(b)2E for altered
space conditioning systems.
01 02 03 04 05 06 07 08 09
System Name System
Zoning
Conditioned
Floor Area
Being Served
(ft2)
Thermostats
§110.2(b) & (c)1,
§120.2(a)or §141.0(b)2E
Shut-Off
Controls
§120.2(e)
Isolation
Zone
Controls
§120.2(g)
Demand Response
§110.12 and §120.2(b)
Supply Air
Temp. Reset
§140.4(f)
Window Interlocks per
§140.4(n)
Rooftop-Replacement 10
Tons Single zone <= 25,000 ft2 Setback
NA: 7 day
per
§120.2(e)1
4 Hour Timer NA: Serves temp. sensitive
process
NA:
Alteration NA: Alteration Project
1FOOTNOTES: Gravity gas wall heaters, gravity floor heaters, gravity room heaters, non-central electric heaters, fireplaces or decorative gas appliances, wood stoves are not required to
have setback thermostats.
*Notes: Controls with a * require a note in the space below explaining how compliance is achieved. EX: system 1: SA Temp Reset: Exempt because zones compliant with §140.4(d) ;
EXCEPTION 1 to §140.4(f)
J. VENTILATION AND INDOOR AIR QUALITY
This table is used to demonstrate compliance with mandatory ventilation requirements in §120.1 and §120.2(e)3B for all nonresidential, high-rise residential and hotel/motel
occupancies. For alterations, only ventialtion systems being altered within the scope of the permit application need to be documented in this table. In lieu of this table, the required
outdoor ventilation rates and airflows may be shown on the plans or the calculations can be presented in a spreadsheet.
01 Check the box if the project is showing ventilation calculations on the plans, or attaching the calculations instead of completing this table.
02 Check this box if the project included Nonresidential or Hotel/Motel spaces
Check this box if the project included new or altered high-rise residential dwelling units.
03 Check the box if the project is using natural ventilation in any nonresidential or hotel/motel spaces to meet required ventilation rates per §120.1(c)2.
Nonresidential and Hotel/ Motel Ventilation Systems
04 05 06 07
System Name Rooftop-Replacement 10 Tons System Design OA CFM
Airflow1 500 System Design
Transfer Air CFM 0
Air Filtration per §120.1(c) and §141.0(b)2 2
Provided per §120.1(c) (NR and
Hotel/Motel))
08 09 10 11 12 13 14 15 16
STATE OF CALIFORNIA
Mechanical Systems
NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
Project Name: Best Buy #1020 Report Page: (Page 6 of 9)
Project Address: 79220 Hwy 111 Date Prepared: 7/18/2022
Registration Number:Registration Date/Time:Registration Provider: Energysoft
CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
Schema Version: rev 20200601
Report Generated: 2022-07-18 22:42:44
J. VENTILATION AND INDOOR AIR QUALITY
Space Name
ot item Tag
Mechanical Ventilation Required per §120.1(c)3 3 Exh. Vent per §120.1(c)4
DCV or Sensor Controls per §120.1(d)3,
§120.1(d)5, and §120.1(e)3 6Occupancy Type4
Conditioned
Floor Area
(ft2)
# of Shower
heads/
toilets
# of
people5
Required
Min OA
CFM
Required
Min CFM
Provided per Design
CFM
Retail Retail sales 2000 500 0 0
DCV Provided per
§120.1(d)4
Occ Sensor NA: Not required
space type
17 Total System Required Min OA CFM 500 18 Ventilation for this System Complies?Yes
1 FOOTNOTES: System CFM should include both mechanical and natural ventilation for the zone/system
2 Air filtration requirements apply to the following three system types per §120.1(c)1A : space conditioning systems utilizing ducts to supply air to occupiable space; supply-only
ventilation systems providing outside air to occupiable space; supply side of balanced ventilation systems including heat recovery and energy recovery ventilation systems providing
outside air to occupiable space.
3 Uniform Mechanical Code may have more stringent ventilation requirements; the most stringent code requirement takes precedence.
4 See Standards Tables 120.1-A and 120.1-B.
5 For lecture halls with fixed seating, the expected number of occupants shall be shall be determined in accordance with the California Building Code.
6 §120.2(e)3 requires systems serving rooms that are required by §130.1(c) to have lighting occupancy sensing controls to also have occupancy sensing zone controls for ventilation.
Examples of spaces which require lighting occupancy sensors include offices 250ft2 or smaller, multipurpose rooms less than 1,000 ft2, classrooms, conference rooms, restrooms, aisles
and open areas in warehouses, library book stack aisles, corridors, stairwells, parking garages, and loading and unloading zones, unless excepted by §130.1(c).
K. TERMINAL BOX CONTROLS
This section does not apply to this project.
L. DISTRIBUTION (DUCTWORK and PIPING)
This table is used to show compliance with mandatory pipe insulation requirements found in §120.3 and prescriptive requirements found in §140.4(l) for duct leakage testing.
Duct Leakage Sealing
STATE OF CALIFORNIA
Mechanical Systems
NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
Project Name: Best Buy #1020 Report Page: (Page 7 of 9)
Project Address: 79220 Hwy 111 Date Prepared: 7/18/2022
Registration Number:Registration Date/Time:Registration Provider: Energysoft
CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
Schema Version: rev 20200601
Report Generated: 2022-07-18 22:42:44
L. DISTRIBUTION (DUCTWORK and PIPING)
The answers to the questions below apply to the following duct systems:Rooftop-Replacement 10
Tons Duct leakage testing triggered for these systems?No
11 No The scope of the project includes only duct systems serving healthcare facilities
12 Yes Duct system provides conditioned air to an occupiable space for a constant volume, single zone, space-conditioning system.
13 Yes The space conditioning system serves less than 5,000 ft2 of conditioned floor area.
14 No The combined surface area of the ducts in the following locations is more than 25% of the total surface area of the entire duct system:
Outdoors
In a space directly under a roof that has a U-factor greater than the u-factor of the ceiling, or if the roof does not meet the
requirements of §140.3(a)1B or if the roof has fixed vents or openings to the outside/ unconditioned spaces
In an unconditioned crawl space
In other unconditioned spaces
15 The scope of the project includes extending an existing duct system, which is constructed, insulated or sealed with asbestos.
16 The scope of the project includes an existing duct system that is documented to have been previously sealed as confirmed through field verification
and diagnostic testing in accordance with procedures in the Reference Nonresidential Appendix NA2.
17 Yes Duct system shall be sealed in acordance with the California Mechanical Code
M. COOLING TOWERS
This section does not apply to this project.
N. DECLARATION OF REQUIRED CERTIFICATES OF INSTALLATION
Selections have been made based on information provided in previous tables of this document. If any selection needs to be changed, please explain why in Table E Additional Remarks.
These documents must be provided to the building inspector during construction and can be found online at
https://www.energy.ca.gov/title24/2019standards/2019_compliance_documents/Nonresidential_Documents/NRCI/
Form/Title Field Inspector
Pass Fail
NRCI-MCH-01-E - Must be submitted for all buildings
STATE OF CALIFORNIA
Mechanical Systems
NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
Project Name: Best Buy #1020 Report Page: (Page 8 of 9)
Project Address: 79220 Hwy 111 Date Prepared: 7/18/2022
Registration Number:Registration Date/Time:Registration Provider: Energysoft
CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
Schema Version: rev 20200601
Report Generated: 2022-07-18 22:42:44
O. DECLARATION OF REQUIRED CERTIFICATES OF ACCEPTANCE
Selections have been made based on information provided in previous tables of this document. If any selection needs to be changed, please explain why in Table E Additional Remarks.
These documents must be provided to the building inspector during construction and can be found online at
https://www.energy.ca.gov/title24/2019standards/2019_compliance_documents/Nonresidential_Documents/NRCA/
Form/Title Systems/Spaces To Be Field
Verified
Field Inspector
Pass Fail
NRCA-MCH-02-A - Outdoor Air must be submitted for all newly installed HVAC units. Note: MCH-02-A can be performed in
conjunction with MCH-07-A Supply Fan VFD Acceptance (if applicable) since testing activities overlap.
York XP120C;
NRCA-MCH-03-A - Constant Volume Single Zone HVAC NOTE: This form does not automatically move to "Yes'. If Constant
Volume Single Zone HVAC Systems are included in the scope, permit applicant should move this form to "Yes".
York XP120C;
NRCA-MCH-06-A Demand Control Ventilation Systems must be submitted for all systems required to employ demand
controlled ventilation (refer to §120.1(c)3 ) can vary outside ventilation flow rates based on maintaining interior carbon
dioxide (CO2) concentration setpoints.
York XP120C;
NRCA-MCH-11-A Automatic Demand Shed Controls York XP120C;
P. DECLARATION OF REQUIRED CERTIFICATES OF VERIFICATION
There are no NRCV forms required for this project.
Q. MANDATORY MEASURES DOCUMENTATION LOCATION
This table is used to indicate where mandatory measures are documented in the plan set or construction documentation.
01 02
Compliance with Mandatory Measures documented through MCH
Mandatory Measures Note Block Yes M-Sheets
STATE OF CALIFORNIA
Mechanical Systems
NRCC-MCH-E CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
Project Name: Best Buy #1020 Report Page: (Page 9 of 9)
Project Address: 79220 Hwy 111 Date Prepared: 7/18/2022
Registration Number:Registration Date/Time:Registration Provider: Energysoft
CA Building Energy Efficiency Standards - 2019 Nonresidential Compliance Report Version: 2019.1.003
Schema Version: rev 20200601
Report Generated: 2022-07-18 22:42:44
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Jason Vander Veen
Documentation Author Signature:
Company:
Vander Veen Engineering Consultants
Signature Date:
2022-07-18
Address:
103 W. El Portal #c
CEA/ HERS Certification Identification (if applicable):
City/State/Zip:
San Clemente CA 92672
Phone:
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1.The information provided on this Certificate of Compliance is true and correct.
2.I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer)
3.The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements
of Title 24, Part 1 and Part 6 of the California Code of Regulations.
4.The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations,
plans and specifications submitted to the enforcement agency for approval with this building permit application.
5.I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable
inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy.
Responsible Designer Name:
VanderVeen Engineering Consultants, Inc
Responsible Designer Signature:
Company:
VanderVeen Engineering Consultants, Inc
Date Signed:
2022-07-18
Address:
28362 Vincent Moraga, Suite A1
License:
City/State/Zip:
Temecula CA 92591
Phone:
M34874