BCOM2022-0060DESIGN & DEVELOPMENT
DEPARTMENT
78-495 CALLE TAMPICO
LA QUINTA, CALIFORNIA 92253
Permit Type:
Permit Number
Property Address
APN:
Legal Description
Property Zoning:
Valuation:
BUILDING PERMIT
eca Qa�&a
CALIFORNIA
Building Commercial
BCOM2022-0060
46480 WASHINGTON ST STE 3
643020068
Parcel 2 PM 213/19 TR 32683
CR, 2
$50,000.00
Owner:
Applicant
PHONE (760) 777-7125
WWW.LAQUINTACA.GOV
APPLIED DATE: 10/26/2022
ISSUED DATE: 05/05/2023
WASHINGTON 111 LTD
80618 DECLARATION AVE, INDIO, CA 92253
David Solomon
11331 E. 183rd St. #367, Cerritos, CA, CA 90703
Contractor: PALM CAPITAL GROUP LLC dba PALM
CONSTRUCTION GROUP
205 E AVENIDA SAN JUAN, SAN CLEMENTE, CA
92672
PRIOR TO THE ISSUANCE OF THIS PERMIT FOR CONSTRUCTION, ALTERATION, IMPROVEMENT, DEMOLITION, OR REPAIR THE OWNER, APPLICANT AND/OR
CONTRACTOR UNDER PENALTY OF PERJURY HAVE AFFIRMED WHEN APPLICABLE, THROUGH THE SUBMITTAL OF FORMS OR BY OTHER ELECTRONIC MEANS, THE
FOLLOWING:
LICENSED CONTRACTOR OR OWNER -BUILDER DECLARATION (1 or 2)
1) They are licensed under provisions of Chapter 9 (commencing with
Section 7000) of Division 3 of the Business and Professions Code, and the
referenced
License is in full force and effect, or;
2) That they are exempt from the Contractors' State License Law for the
reason(s) indicated by either (2)(a) and/or (2)(b), or (2)(c) where he or
she is exempt from licensure by a valid exemption. [Section 7031.5,
Business and Professions Code: Any city or county that requires a permit
to construct, alter, improve, demolish, or repair any structure, prior to its
issuance, also requires the applicant for the permit to file a signed
statement that he or she is licensed pursuant to the provisions of the
Contractors' State License Law (Chapter (commencing with Section 7000)
of Division 3 of the Business and Professions
Code] Any violation of Section 7031.5 by any applicant for a permit
subjects the
applicant to a civil penalty of not more than five hundred dollars ($500).)
a) As owner of the property, or my employees with wages as their sole
compensation, will do all of or portions of the work, and the structure is
not intended or offered for sale (Section 7044, Business and Professions
Code: The Contractors' State License Law does not apply to an owner of
property who, through employees' or personal effort, builds or improves
the property, provided that the improvements are not intended or offered
for sale. If, however, the building or improvement is sold within one year of
completion, the Owner -Builder will have the burden of proving that it was
not built or improved for the purpose of sale.).
b) As owner of the property, will be exclusively contracting with licensed
c) Are exempt from licensure under the Contractors' State License Law.
As an Owner -Builder, they acknowledge that, except for their personal
residence in which they must have resided in for at least one year prior to
completion of the improvements covered by this permit, they cannot legally
sell a structure built as an owner -builder if it has not been constructed in
its entirety by licensed contractors. It is understood that a copy of the
applicable law, Section 7044 of the Business and Professions Code, is
available upon request when this application was submitted at the
following Web site:
http://www.leginfo.ca.gov/calaw.html.
DECLARATION REGARDING CONSTRUCTION LENDING AGENCY (If
applicable)
A construction lender will be used for completion of the improvements
covered by this permit and the name and information of which is on file for
public inspection during the regular business hours of the public entity.
Failure of the applicant to indicate the construction lender on the
WORKERS' COMPENSATION DECLARATION (1, 2 or 3)
WARNING: FAILURE TO SECURE WORKERS' COMPENSATION COVERAGE IS
UNLAWFUL, AND SHALL SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND
CIVIL FINES UP TO ONE HUNDRED THOUSAND DOLLARS ($100,000), IN ADDITION
TO THE COST OF COMPENSATION, DAMAGES AS PROVIDED FOR IN SECTION
3706 OF THE LABOR CODE, INTEREST, AND ATTORNEY'S FEES.
1) Has and will maintain a certificate of consent to self -insure for workers'
compensation, issued by the Director of Industrial Relations as provided for
by Section 3700 of the Labor Code, for the performance of the work for
which this permit is issued.
2) Has and will maintain workers' compensation insurance, as required by
Section 3700 of the Labor Code, for the performance of the work for which
this permit is issued.
3) Certifies that, in the performance of the work for which this permit is
issued, shall not employ any person in any manner so as to become subject
to the workers' compensation laws of California, and agree that, if should
become subject to the workers' compensation provisions of Section 3700 of
the Labor Code, shall forthwith comply with those provisions.
NOTICE TO APPLICANT (1, 2 and 3)
1) Each person upon whose behalf this application was made, each person
at whose request and for whose benefit work is being performed under or
pursuant to any permit issued as a result of this application, the owner, and
the applicant, each agrees to, and shall defend, indemnify and hold harmless
the City of La Quinta, its officers, agents, and employees for any act or
omission related to the work being performed under or following issuance of
this permit.
2) Any permit issued as a result of this application becomes null and void if
work is not commenced within 360 days from date of issuance of such
permit, or if cessation of work for 180 days will subject permit to
cancellation. On or after January 1, 2019, every permit issued shall become
invalid unless the work on the site authorized by such permit is commenced
within 12 months after its issuance, or if the work authorized on the site by
such permit is suspended or abandoned for a period of 12 months after the
time the work is commenced.
3) Certified that they read the application and state that the information
provided is correct. Agree to comply with all city and county ordinances and
state laws relating to building construction, and hereby authorize
representatives of this city to enter upon the above -mentioned property for
inspection purposes.
IMPORTANT: An Application for Permit was made to the Building Official,
subject to the conditions and restrictions set forth at the time of application,
which is now hereby an Issued Permit. If any part of the information being
supplied on this permit is inaccurate or untrue, please contact the City of La
Quinta at (760) 777-7125 immediately for correction.
Printed: 11/20/24 4:33 pm Page 1 of 6
1-311111]1Z"a4 NV,IkI
Permit Type: Building Commercial
Permit Number: BCOM2022-0060
Property Address: 46480 WASHINGTON ST STE 3
application does not relieve that person of the n
construction lender preliminary notice from that duty.
Printed: 11/20/24 4:33 pm Page 2 of 6
1-3111101Z"a4NJilkI
Permit Type: Building Commercial
Permit Number: BCOM2022-0060
Property Address: 46480 WASHINGTON ST STE 3
SALON CENTRIC / 2,530SF RETAIL TI/VB/M-OCC/34-OL/SPRINKLED *** 2,530SF RETAIL BEAUTY SHOP
TI/VB/M-OCC/34-OL/SPRINKLED [SALON CENTRIC] THIS PERMIT DOES NOT INCLUDE ALTERATION TO EXISTING LOAD BEARING OF
LATERAL RESISTING CONSTRUCTION. NO TUMF OR DIF ASSESSMENT BASED ON PREVIOUSLY APPROVED SHOPPING CENTER.
INTERIOR ONLY PATH OF TRAVEL IMPROVEMENTS, EXTERIOR NOT REQUIRED BASED ON AGREEMENT BETWEEN DEVELOPMEW
AND CITY. 2019 CALIFORNIA BUILDING CODES.
instruction Dpt;.
Commercial Work Type Remodel Building/Unit M: Stores, Markets, Gas Gross Square Footage 2530
Occupancy Station
Classification(s)
Conditioned Square 2530 Fire Sprinkler Square 2530 Number of Floors 1
Footage Footage
Occupant Load 34 Construction Type V-B Code Edition 2019
Remodel Area Square 2530
Footage
Number of Plumbing 2
Fixtures/Traps
Number of Dispensing 1
Units - Gas (TUMF)
Zoning CR
Subdivision Name TR 32683
Legal Description Parcel 2 PM 213/19 TR
32683
New Electrical Square 2530
Footage
Water System Install Yes
or Alteration?
City Development No
Impact Fee Applicable
General Plan CG
Lot Number 2
Miscellaneous
Mechanical
Transportation Uniform No
Mitigation Fee
Applicable
Art in Public Places No
Fund Exempt
City Limits Within La Quinta Limits
Lot Size 3676.29
I Type Group Sq Ft Value I
Printed: 11/20/24 4:33 pm Page 3 of 6
1-311111]1Z"a4 N IT, IkI
Permit Type: Building Commercial
Permit Number: BCOM2022-0060
Property Address: 46480 WASHINGTON ST STE 3
Invoice No. Fee
PERMIT-BCOM2022-00( REMODEL, EA ADDITIONAL 500SF PC
0 REMODEL, FIRST 100SF PC
WATER SYSTEM INST/ALT/REP PC
OTHER MECHANICAL EQUIPMENT
FIXTURE/TRAP
NON-RESIDENTIAL, FIRST 2,000SF PC
FIRE COMMERCIAL TI
WATER SYSTEM INST/ALT/REP
TECHNOLOGY ENHANCEMENT FEE
SMI - COMMERCIAL
OTHER MECHANICAL EQUIPMENT PC
NON-RESIDENTIAL, EA ADDITIONAL 2,000SF PC
REMODEL, FIRST 100SF
BSAS SB1473 FEE
REMODEL, EA ADDITIONAL 500SF
FIRE COMMERCIAL TI PC
NON-RESIDENTIAL, FIRST 2,000SF
RECORDS MANAGEMENT FEE - MAJOR
HOURLY CHARGE - INTERWEST STRUCTURAL PLAN REVIEW
FIXTURE/TRAP PC
NON-RESIDENTIAL, EA ADDITIONAL 2,000SF
Total for Invoice PERMIT-BCOM2022-0060
Grand Total for Permit
Fee Amount
Amount Paid
$105.05
$105.05
$162.81
$162.81
$14.59
$14.59
$43.77
$43.77
$29.18
$29.18
$101.54
$101.54
$175.00
$175.00
$14.59
$14.59
$8.00
$8.00
$14.00
$14.00
$43.77
$43.77
$11.67
$11.67
$59.52
$59.52
$2.00
$2.00
$131.30
$131.30
$263.00
$263.00
$131.30
$131.30
$22.00
$22.00
$312.50
$312.50
$29.18
$29.18
$43.77
$43.77
$1,718.54
$1,718.54
$1,718.54 $1,718.54
Workflow Step / Action Name
Action Type Start Date End Date
Inspections v.1
10/26/2022 0:00
FINAL INSPECTION v.1
Inspection
FINAL** v.2
Inspection
FINAL** v.1
Inspection
T-BAR/OVERHEAD v.2
Inspection
T-BAR/OVERHEAD v.1
Inspection
DRYWALL NAIL v.1
Inspection
UNDERGROUND PLBG v.2
Inspection
ROUGH ELEC v.1
Inspection
FRAMING v.1
Inspection
ROUGH PLBG v.1
Inspection
UNDERGROUND PLBG v.1
Inspection
Application Completeness Check v.1
Submittal Document Verification v.1
Generic Action
Confirm Fees Paid v.1
Generic Action
Plan Check v.1
Building M 1
Receive Submittal
Printed: 11/20/24 4:33 pm Page 4 of 6
Permit Type: Building Commercial
11111141110Ma4MYi1111
Permit Number: BCOM2022-0060
Property Address: 46480 WASHINGTON ST STE 3
Permit Issuance v.1
Contractor / Owner -Builder Information v.1
................................................................................................................................................................
Verify & Invoice Fees v.1
................................................................................................................................................................
Ready to Issue v.1
................................................................................................................................................................
Verify Fee Payment & Issue Permit v.1
................................................................................................................................................................
Print, Attach, and Email Building Permit v.1
Generic Action
.......................................................
Generic Action
.......................................................
Generic Action
.......................................................
Generic Action
.......................................................
Create Report
111.71./wl uvl I* - VVvwl 19v —vin VI IIII MF plvvCv V.1
Roof Nail v.1
Inspection
Okay to Wrap v.1
Inspection
Rough Fire Clearance v.1
Generic Action
Framing v.1
Inspection
Rough Electrical v.1
Inspection
Rough Mechanical v.1
Inspection
Rough Plumbing v.1
Inspection
Shower Pan v.1
Inspection
Insulation v.1
Inspection
Drywall Nail v.1
Inspection
T-Bar/Overhead v.1
Inspection
Exterior Lath v.1
Inspection
Gas Test v.1
Inspection
Sewer Connection v.1
Inspection
Temporary Power v.1 Inspection
p Y p
TempUse of Permanent Power v.1 Inspection
p
IN I01JOULIVI10 - VIIIaI V.1 VV/G I/GVLJ (—
Final Fire v.1 Inspection
Final Building v.1 Inspection 08/21/2023 14:59 08/21/2023 15:07
Final Building v.2 Inspection 08/29/2023 8:07 08/29/2023 8:07
VCI II1 CLU VI WUi FJG11 Y V.1
Iccl to (`ohifin�fo of (lnnl In�nry v 1
Printed: 11/20/24 4:33 pm Page 5 of 6
1-31111111]1Z"a4 N IT, IkI
Permit Type: Building Commercial
Permit Number: BCOM2022-0060
Property Address: 46480 WASHINGTON ST STE 3
Construction or work for which a permit is required shall be subject to inspection by the building official and such construction or work
shall remain visible and able to be accessed for inspection purposes until approved. Approval as a result of an inspection shall not be
construed to be an approval of a violation of the provisions of the applicable code and other ordinances of the jurisdiction. Inspections
presuming to give authority to violate or cancel the provisions of the applicable code and other ordinances of the jurisdiction shall not be
valid. It shall be the duty of the owner or the owner's authorized agent to cause the work to remain visible and able to be accessed for
inspection purposes. Neither the building official nor the jurisdiction shall be liable for expense entailed in the removal or replacement of
any material required to allow inspection.
It shall be the duty of the holder of the building permit or their duly authorized agent to notify the building official when work is ready for
inspection. It shall be the duty of the permit holder to provide access to and means for inspections of such work that are required by this
code.
A building or structure shall not be used or occupied in whole or in part, and a change of occupancy of a building or structure or portion
thereof shall not be made, until the building official has issued a certificate of occupancy therefor as provided herein. Issuance of a
certificate of occupancy shall not be construed as an approval of a violation of the provisions of the applicable code and other ordinances
of the jurisdiction. Certificates presuming to give authority to violate or cancel the provisions of this code or other ordinances of the
iurisdiction shall not be valid.
A person shall not make connections from a utility, a source of energy, fuel, or power, or a water system or sewer system to any building
or system that is regulated by the applicable code and other ordinances of the jurisdiction for which a permit is required, until approved by
the building official.
Printed: 11/20/24 4:33 pm Page 6 of 6
CERTIFICATE OF OCCUPANCY
DESIGN AND DEVELOPMENT DEPARTMENT
This Certificate is issued pursuant to the requirements of Chapter 1 Section 111 of the
California Building Code, certifying that, at the time of issuance, this structure was in
compliance with the provisions of the Building Code and the various ordinances of the City
regulating building construction and/or use.
BUILDING ADDRESS: 46480 WASHINGTON ST STE 3
Use Classification:
Occupancy Group: M: Stores, Markets, Type of Construction: V-B
Gas Station
Code Edition: 2019
By: Jake Fuson
Date: 8/29/2023 12: OO:OOAM
Building Official: AJ ORTEGA
ta
Qa�&cu
— GEM of the DESERT —
Sprinkler Installed: YES
Permit No.: BCOM2022-0060
Land Use Zone: CR
Occupant Load: 34
Owner of Building: WASHINGTON 111 LTD
Address: 80618 DECLARATION AVE
City, ST, ZIP: INDIO, CA 92253
POST IN A CONSPICUOUS PLACE
ffi IDSam
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
try.
1.1
I
�
es, iptr ; z,�
Control Valves.— Identification Sign
N ��Ae�Da
Refe[e�Rcs
13.3.1
�17"t1aYe
p6/30123$
P
i
�T r
1.2
1
Control Valves — Inspection
13.3.2
P
1.3
1
Waterflow Alarm Devices
5.2.5
P
1.4
1
Supervisory Devices
5.2.5
P
1.5
1
Gauges (Wet Pipe Systems)
5.2.4.1
P
1.6
1
Enter Water Supply Pressure Below Riser Check
5.2.4.1
psi
psi
psi
psi
1.7
1
Enter Water Supply Pressure Above Riser Check
5.2.4.1
95 psi
psi
psi
psi
1.8
1
Pressure Readings Acceptable
5.2.4.1
P
1.9
1
Hydraulic Design Information Sign
(for hydraulically designed systems)
5.2.6
P
1.10
I
General Information Sign
(not required for system prior to 2007 edition of NFPA 13)
5.2.8
N/A
1.11
I
Heat Tape
5.2.7
N/A
1.12
1
Spare Sprinklers
5.2.1.4
P
1.13
1
Fire Department Connections
13.7
P
1.14
1
Alarm Valves — Exterior Inspection
13.4A
N/A
1.15
1
Pressure Reducing Valves
13.5.1.1
N/A
1.16
I
Backflow Preventers
13.6.1
P
1.17
1
Small Hose Connections - Hose Valve*
5.1.6, 13.5.2
13.5.5.1
N/A
1.18
I
PRV — Fire Sprinkler Systems
13.5.1.1
N/A
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, 11, or III
standpipe systems.
Form AES 2.1 Sept. 3, 2013
= Inspection. T = Test M = Maintenance
P = Pass F = Fail N/A = Not Applicable
NJxk A...
k't 'TMA,a'ir1s v.„,x z�,.4a.."P,,.
:a°Descr..ed:Date�,..Gomrnents�O
�p#�����".,.
1P
F"NIA
_•a wa..,, a. fin ca,m+�wa ,;f2ference
i �,�,, u,
�i
1 A 9
1
Sprinklers
5.2.1
06/30/23
P
1.20
1
Buildings (Freeze Protection)
4.1.1.1
Owner's Responsibility
N/A
1.21
1 I
Pipe and Fittings
5.2.2
06/30/23
P
1.22
1
Hangers
5.2.3
06/30/23
P
1.23
1
Seismic Braces
5.2.3
06/30/23
P
2.1
T
Field Service Test Required
5.3.1
If REQUIRED, Enter'F' until
N/A
(Send Report to Fire Code Official)
results are returned from Lab
2.2
T
Recalled Sprinklers
Title 19
06/30/23
P
If not present= Pass;. If eresent = Fail
904.1 c
2.3
T
Water Flow Alarm Devices
5.3.3
06/30/23
40 sec.
P
90 sec: maximum - Enter Time
13.2.6
2.4
T .
Main Drain Test:
13.2.5
06/30/23
P
(Enter data on Page 1 of this form)
13.3.3.4
2.5
T
Control Valve -Position
13.3.3.2
06/30/23
P
2.6
T
Control Valve - Operation
13.3.3.1
06/30/23
P
2.7
T
Supervisory Devices
13.3.3.5
06/30/23
P
2.8
T
Backflow Preventer Assemblies
13.6.2
N/A
2 9
T
Small Hose Connections*
13.5.2.3
N/A
w/PRV Hose Valves — Partial Flow Test
13.5.3.3
2.10
T
PRV — Fire Sprinkler Systems
13.5.1.3
N/A
3.13 11
M
Control Valves
13.3.4
06/30/23
P
3.2
M
Small Hose Connections*
13.5.6.3
N/A
Obstruction Investigation required
Yes
3.3
M
(if "Yes', see Deficiencies and Comments Section
14.3
06/30/23
No
P
for Results.)
3.4
M
System Returned to Service
4.5.3
06/30123
Nos
P
* Small
hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, 11, or III
standpipe
systems.
Form AES 2.1 Sept. 3, 2013
I hereby certifythat the.fire protection equipment listed above has been fully inspected, tested, and maintained on this date by
the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable
except as noted in the "Deficiencies and Comments" section of this form.
Check boz.ifAnnual Inspection, Testing & Maintenance Items are Completed in the Indicated Quarter
Date 0630
_Print�_Name_ 3
Nick Co___..�_._._....
Signature "
Form AES 2.1 Sept. 3, 2013
12iser
Nox
T d1 fx sF k r 2 4
,„Locatlop d
D ameter
pa€etrae€r '
to€ttat Stat<c
- PressureFressurg�
Resadpaf
rFina) Static
Pressure ;,
v
1
Outside of Suite 1 inside access panel
3"
1 1/4"
85
75
80
P
This building has more than 5 risers. See additional AES 2.9 form attached Number of AES 2.9 forms attached:
1
I = Inspection .. T =.Test • M = Maintenance
IEe'm �� 1s zM, LS x`y , x Descnptron ed'.;
Reference
P = Pass F = Fail N/A = NotApplicable
Date, k'Comments�rrly PF N/A�
r
1.1
I
Control, Valves — Identification Sign
13.3.1
12/01/22
P
1.2
1
Control Valves — Inspection
13.3.2
12/01/22
P
1.3
1
Waterfiow Alarm Devices
5.2.5
12/01/22
P
1.4
1
Supervisory Devices
5.2.5
12/01/22
P
1.5
1
Gauges (Wet Pipe Systems)
52.4.1
12/01/22
P
1.6
1
Hydraulic Design Information Sign
(For hydraulically designed systems)
5_2,6
12/01/22
P
1.7
1
Enter Water Supply Pressure Below Riser Check
5.2.4.1
psi
NA
1.8
1
Enter Water Supply Pressure Above Riser Check
5.2.4.1
12/01/22
85 psi
P
1.9
1
Pressure Readings Acceptable
5.2.4.1
12/01/22
P
1.10
I
General Information Sign
(not required for system prior to 2007 Edition NFPA 13)
5 2 8
NA
1.11
1
Heat Tape
5.2.7
NA
1.12
1
Spare Sprinklers
52.1.4
12/01/22
P
1.13
1
Fire Department Connections
13.7
12/01/22
P
1.14
1
Alarm Valves —Exterior Inspection
13.4.1
NA
1.15
1
Pressure Reducing Valves
13.5.1.1
NA
1.16
1
Backfiow Preventers
13.6.1
NA
Form AES 2.2 Sept_ 3, 2013
Contractor or Licensed Owner Information
Building Name Washington 111. LLC {v Name Desert Fire Extinguisher CO., INC
Address 46480 Washington St ' Job # 5 Year Inspection 27491504
CityLa Quinta, Ca. 92253 INA
i Inspection T Test M Maintenance
P = Pass F = Fail N/A = Not Applicable
s �r DeIte
m scnpt�on
NFPA 25 CA=ed
.
€?ate '' Comrinents fJnlyP F;hllAp"s
:Reference
1.17
1
Small Hose Connections - Hose Valve*
5.1.6, 13.5.2
13.5.5.1
NIA
1.18
1
RRV — Fire Sprinkler Systems
13.5.1.1
N/A
1.19
I
Buildings (Freeze Protection)
4.1.1.1
Owner's Responsibility
NIA
1.20
1
Sprinklers
5.2.1
12/01/22
p
1.21
1
Sprinklers --Accessible Concealed Space
5.2.1.1.6
12/Q1/22
p
1.22
1 1
Pipe and Fittings
5.2.2
12/01/22
p
123
1
Pipe and Fittings -Accessible Concealed Space
5.2.2.3
12/01/22
P
1.24
i
Hangers
5.2.3
12/01/22
p
1.25
1
Hangers- Accessible Concealed Space
5.2.3.3
12/01/22
P
1.26
1
Seismic Braces
5.2.3
12/01/22
p
1.27
1
Seismic. Braces -Accessible Concealed Space
5.2.3.3
12/01/22
P
1.28
1
Unsprinklered Areas
CFC 901.4
12/01/22
ElYes
V No
2.1
T
Field Service Test Required
If REQUIRED, Enter'F' until
Send Report to Fire Code Official5.3.1
results are returned from Lab
NIA
22
T
Recalled Sprinklers
Title 19
/f not present = Pass; if present = Fait
904.1(c)
12101 /22
p
2.3
T
Water Flow Alarm Devices
5.3.3
90 secs max. Enter lime
13.2.6
12/01/22
35 sec.
P
2A
T
Main Drain Test
13-2.5
(Enter data on Page 9 of this form)
13.3.3.4
12/01/22
P
2.5
T
Control Valve -'Position
13.3.3.2
12/01/22
P
2.6
T
Control Valye — Operation
13.3.3.1
12/01/22
p
2.7
T
Supervisory Devices
13.3.3.5
12/01/22
p
2.8
T
BackfI6vv Preventer Assemblies
13-6.2
N/A
2 9
T
Small Hose.Connections*
13.5.2.3
w/PRV Hose. Valves — Partial Flow Test
13.5.3.3
N/A
2.10
T
PRV— Fire Sprinkler Systems
13.5.1.3
N/A
2.11
T:
ISmalf-H.ose
Pressure Gauges - Calibration
5.3-2
12/01/22
p
2.12
T
Connections*
13.5.6.2.2
NIA
* Small
hose connections are hose valves and optional hose supplied by the fire sprinkler system.
They do not include Class 1, 11, or III
standpipe systems_
Form AES 2.2 Sept. 3, 2013
Property Information
Building Name g } Washin ton 111 1_LC
Address 46480 Washington St 9
City La Quinta, Ca: 92253 -mn�
Form AES 2.2
Contractor or Licensed Owner Information
rvarne Desert Fire Extinguisher CO_ INC
Job # 5 Year Inspection 27491504
Sept. 3, 2013
� STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Project Name and Address
Authority Having Jurisdiction
Salon Centric TI
CITY OF LA QUINTA
46480 Washington St., #3
BCOM2022-0060
La Quinta 92253
Permit Iss. Date: 5/5/2023
■❑Construction inspection and functional testing comply Date Submitted 7/26/23
❑Does not comply �to AHJ:
This document is used to demonstrate compliance with acceptance requirements in
Intent: §130.4(a)4, §160.5(e)1D and Reference Nonresidential Appendix NA7.6.2 for shut-off
lighting controls. Attach additional sets of pages 1 through 8, as required, for all
controls that must be tested.
Indicate all types of shut-off controls tested for this project
❑
Automatic time switch lighting controls (Tables A-1 and B-1 of this document should be
completed)
Occupant sensing lighting controls (including occupant sensors, partial -ON occupant
❑■
sensors, partial -OFF occupant sensors, and/or vacancy sensors) (Tables A-2 and B-2 of this
document should be completed)
❑
Multi zone occupant sensing lighting controls in office spaces larger than 250 square feet
Tables A-2 and B-3 of this document should be completed)
Automatic Time Switch Lighting Controls
Table A-1. Automatic Time Switch Lighting Controls Construction Ins ection
Code
Step
Entry
Item
Reference
1
❑
The automatic time switch controls are shown on
NA7.6.2.5(a)
Ian documents and are installed.
NA7.6.2.5(b)
Automatic time switch controls are programmed
§110.9(b)1Aii
§130.1(c)1A
2
❑
with acceptable weekday, weekend, and holiday
§130.1(c)4
(if applicable) schedules.
§160.5(b)4Cia
§160.5(b)4Civ
Document weekday, weekend, and holidays
3
❑
schedules, as well as all set-up and preference
NA7.6.2.5(c)
program settings.
4
❑
The correct time and date are properly set in the
NA7.6.2.5(d)
automatic time switch controls.
5
❑
The battery backup (if applicable) is installed and
NA7.6.2.5(e)
energized.
§110.9 b 1
Manual override time limit is set to no more than 2
NA7.6.2.5(f)
6
❑
hours, OR
§110.9(b)1Ai
The automatic time switch control's manual
§130.1(c)3B
override time is exempt from the 2-hour limit.
§160.5 b 4Ciiib
`' TP CardoCaxrnislalnog axKed MIng Page 1 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Step
Item
Code
Reference
Manual override switches located remotely from
NA7.6.2.5(g)
area with controlled luminaires allow the user to
§130.1(c)3A
7
❑
see the controlled luminaires or have a visual
§130.1(a)
signal or display showing the current state of the
§160.5(b)4Ciiia
controlled luminaires.
§160.5 b 4A
❑ Pass
N/A
❑ Fail
Construction Inspection Compliance.
N/A
Table B-1: Automatic Time Switch Lighting Controls Functional Testing
Buildinq: Back Stock Floor:l 1 Room: Storaae Control: Occ Sensor
Code
Step
Entry
Functional Test
Reference
1
No Entry
Occupied Test. Simulate occupied condition in
NA7.6.2.6(a)
the controlled space.
1.1
❑ Yes
The automatic time switch control turns on the
NA7.6.2.6(a)1
❑ No
controlled lighting.
2
No Entry
Unoccupied Test. Simulate an unoccupied
NA7.6.2.6(b)
condition in the controlled space.
2.1
❑ Yes
The automatic time switch control turns off all
NA7.6.2.6(b)1
§130.1(c)1A
❑ No
controlled lighting.
§ 160.5 b 4Cia
For the area controlled by an automatic time
switch control with a configured automatic holiday
NA7.6.2.6(b)2
2.2
❑ Yes
shut-off, the controlled lighting can be turned off
§110.9(b)1Aii
❑ No
automatically by the holiday shut-off, OR the
§130.1(c)4
automatic time switch control is exempt from
§160.5(b)4Civ
incor orating an automatic holiday shut-off.
For the area controlled by an automatic time
switch control with a time override located in and
NA7.6.2.6(b)3
❑ Yes
for the area, the lighting can be turned on
§110.9(b)1Ai
2.3
❑ No
manually by initiating the time override. The
§130.1(c)3B
lighting is configured to remain on for no more
§160.5(b)4Ciiib
than 2 hours OR the area is exempt from the 2-
hour time override limit.
N/A
0 Pass
❑ Fail
Functional Testing Compliance.
N/A
&TP CaFbrmAMMMW`"I" Page 2 of 9 January 1, 2023
cALCmtrnN halting Pr rm
4
'� �� STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Occupant Sensing Lighting Controls
Table A-2: Occupant Sensina Liahtina Control Construction Inspection
Code
Step
Entry
Item
Reference
1
❑E
The occupant sensing lighting controls are shown
NA7.6.2.1(a)
on plan documents and are installed.
Occupant sensing lighting control is installed per
manufacturer's instructions to minimize false
2
❑■
triggering — such as to install an occupancy sensor
NA7.6.2.1(c)
away from HVAC diffusers to avoid probable false
triggerin .
N/A
0 Pass
❑ Fail
Construction Inspection Compliance.
N/A
Table 13-2: Occupant Sensing Lighting Control Functional Testing
Buildina: Back Stock I Floor:1 I Room:Storaae I Control:Occ Sensor
Step
Entry
Functional Test
Code
Reference
❑ Yes
Control is representative of sample. If sampling
N/A❑
No
method is used, attach a page listing untested
NA7.6.2.2
controls in sample.
1
No Entry
Unoccupied Test. Simulate an unoccupied
NA7.6.2.3(a)
condition in the controlled space.
`' TP CardoCaxrnislalnog axKed MIng Page 3 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Code
Step
Entry
Functional Test
Reference
The occupant sensing control turn the controlled
lighting off or partially off, if applicable, in 20
minutes or less from start of an unoccupied
condition. In addition:
For partial -on occupant sensing controls,
1
occupant sensing controls and vacancy sensing
§110.9(b)4A
§110. (b)4
controls, the controlled lighting is turned off in
unoccupied condition.
In the partial off state, partial OFF occupant
sensing controls automatically reduce lighting
power by at least 50 percent, OR:
• For warehouses with metal halide or high
pressure sodium lighting, automatically
§130.1(c)6A-C
reduce lighting power by at least 40
§130.1(c)7A
percent.
• For aisle ways and open areas in
§160.5(b)4Cvia
warehouses in which the installed lighting
❑■ Yes
power is 80 percent or less of the value
1.1
❑ No
allowed under the Area Category Method,
automatically reduce lighting power by at
least 40 percent.
• In corridors and stairwells that provide
access to guestrooms in hotel/motels in
which the installed lighting power is 80
percent or less of the value allowed under
the Area Category Method, automatically
reduce lighting power by at least 40
percent.
For parking garages, parking areas, and loading
and unloading areas, occupant sensing controls
§130.1(c)7B
have at least one control step between 20 to 50
§160.5(b)4Cviib
percent of design lighting power, OR Occupant
sensing controls for metal halide luminaires with a
lamp plus ballast mean system efficacy of 75
lumens per watt, in parking garages, parking
areas, and loading and unloading areas, have at
least one control step between 20 to 60 percent
of design lighting power.
2
No Entry
Occupied Test. Simulate an occupied condition in
NA7.6.2.3(b)
the controlled space.
2.1
❑■ Yes
No ❑
Status indicator or annunciator operates correctly.
NA7.6.2.3(b)1
§110.9b4C
`' TP CardornislalnaxKed ogMIng Page 4 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Step
Entry
Functional Test
Code
Reference
Immediately upon an occupied condition:
NA7.6.2.3(b)2
• The occupant sensing control or partial off
occupant sensing control turns on
controlled lighting; OR
• The vacancy sensing control indicate a
space is occupied and the controlled
2.2
0 Yes
lighting can be turned on manually; OR
❑ No
• The partial -on occupant sensing controls
automatically turns on the controlled
§130.1(c)5A
lighting at between 50 to 70 percent of
§160.5(b)4Cva
controlled lighting power. After the partial -
on stage, manual switches can be activated
to turn on the controlled lighting at full
controlled lighting ower.
N/A
0 Pass
❑ Fail
Functional Testing Compliance.
N/A
Table B-3: Multi -Zone Occupant Sensing Lighting Controls Functional Testing
Buildinq: Back Stock Floor:1 Room: Storage Control: Occ Sensor
Code
Step
Entry
Functional Test
Reference
❑ Yes
Control is representative of sample. If sampling
N/A
❑ No
method is used, attach a page listing untested
NA7.6.2.2
controls in sample.
Occupied Control Zone Test. Simulate an
1
No Entry
occupied condition in the control zone controlled
NA7.6.2.4(a)
by the occupant sensor.
1.1
Yes
Immediately upon occupancy of the control zone,
NA7.6.2.4(a)1
❑ No
the occupant sensors turn on controlled lighting.
Enter the illuminance value in footcandles (fc)
measured at a location in the control zone where
the controlled lighting is at full light output or
designed light output if it has been documented
that dimming luminaires have been intentionally
1.2
Enter Value
tuned to less than full output and the design
NA7.6.2.4(a)2
illuminance levels are provided.
Informational note: Automatic daylighting controls
may need to be temporarily overridden to achieve
full or designed light output for the test.
1.3
❑ Yes
Signal sensitivity is adequate to achieve desired
NA7.6.2.4(a)3
❑ No
control.
1.4
❑ Yes
❑No
Status indicator or annunciator operates properly.
NA7.6.2.4(a)4
§110.9b4C
�,
QrUprnlBhdwu.Koo lghting Page 5 of 9 January 1, 2023
C, L&TP GONnIS arammp Program
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Code
Step
Entry
Functional Test
Reference
Unoccupied Control Zone Test. Simulate an
unoccupied condition in the control zone
2
No Entry
controlled by the occupant sensor. Confirm that at
NA7.6.2.4(b)
least one other control zone within the office
space is occupied.
The occupant sensor uniformly reduces light
NA7.6.2.4(b)1
2.1
❑ Yes
output of the controlled lighting in 20 minutes or
§130.1(c)6Dii
❑ No
less from the start of the unoccupied condition in
§160.5(b)4CvibII
the control zone.
Enter the illuminance value during unoccupancy in
2.2
Enter Value
footcandles (fc) measured at the same location as
NA7.6.2.4(b)2
in Step 1.2.
Calculate the ratio of the illuminance during
2.3
NaN
unoccupancy to the illuminance at full or designed
NA7.6.2.4(b)2
light output in %. ([Step 2.2 / Step 1.2] x 100
2.4
❑ Yes
The ratio of illuminance from Step 2.3 is no more
NA7.6.2.4(b)2
§130.1(c)6Dii
❑ No
than 20%.
§160.5 b 4CvibII
The occupant sensing control does not trigger a
false on from movement outside of the control
zone or from HVAC operation.
❑ Yes
Informational note: The field of view of occupant
2.5
❑ No
sensors in the adjacent control zones in office
NA7.6.2.4(b)3
spaces larger than 250 square feet may overlap,
but the field of view should stay away from an
adjacent enclosed space that is not part of the
office space, like conference rooms, and private
offices.
2.6
❑ Yes
Signal sensitivity is adequate to achieve desired
NA7.6.2.4(b)4
❑ No
control.
Control Zone Size Test. Follow the procedures
3
No Entry
described in either Method 1 (Steps 3.1 — 3.1.3)
NA7.6.2.4(c)
OR Method 2 (Steps 3.2 — 3.2.4
`� TP CaFbrm�`"I" Page 6 of 9 January 1, 2023
cALCmtrn. halting Pr rm
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Code
Step
Entry
Functional Test
Reference
Method 1: Simulate an unoccupied condition in
the control zone controlled by the occupant
sensor while standing in an adjacent control zone.
Determine the "edge" of the control zone
controlled by the occupant sensor by moving
toward the occupant sensor until the lights
3.1
No Entry
controlled by the occupant sensor turn on to
NA7.6.2.4(c)
simulate an occupied condition for that control
Method 1
zone.
Informational note: While moving toward the
occupant sensor, making additional movements,
motions, or sounds may be necessary to trigger
the occupant sensor.
Enter the distance in feet (ft) measured from the
3.1.1
"edge" of the control zone to the spot that is
NA7.6.2.4(c)
directly below the occupant sensor. This is the
Method 1
radius of the control zone.
3.1.2
Calculate the area (in ftz) of the control zone by
NA7.6.2.4(c)
using the formula: Area = 3.14*radius2.
Method 1
NA7.6.2.4(c)
3.1.3
❑ Yes
The area of the control zone (Step 3.1.2) is less
Method 1
❑ No
than or equal to 600 square feet.
§130.1(c)6Di
§160.5 b 4CvibI
3.2
No Entry
Method 2: Simulate an unoccupied condition for
NA7.6.2.4(c)
the entire offices ace.
Method 2
Walk through the space and count the number of
NA7.6.2.4(c)
3.2.1
zones of lighting that turn on automatically. Enter
Method 2
the number of zones that turn on automatically.
Enter the area of the office space (in ftz) from
construction plans or from other information
NA7.6.2.4(c)2
3.2.2
source such as construction documents or
Method 2
Nonresidential Certificates of Compliance
N RCCs .
Divide the area of the office by the number of
NA7.6.2.4(c)3
3.2.3
NaN
zones. Enter the value in square feet. This
Method 2
calculated value is the assessed control zone size.
NA7.6.2.4(c)4
3.2.4
❑ Yes
The area of the control zone is less than or equal
Method 2
❑ No
to 600 square feet.
§130.1(c)6Di
160.5 b 4CvibI
corlrprnl0Adv�ooUghting Page 7 of 9 January 1, 2023
cAL&TP Gas= lfalmng Program
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Step
Entry
Functional Test
Code
Reference
Unoccupied Office Test. Simulate an
unoccupied condition in all control zones
NA7.6.2.4(d)
❑Yes
controlled by all occupant sensors in the office.
§130.1(c)6Diii§1
4
❑ No
In 20 minutes or less from the start of the
60.5(b)4CvibIII
unoccupied condition of the entire office, all
controlled lighting in the office is turned off.
N/A
0 Pass
❑ Fail
Functional Testing Compliance.
N/A
`' TP CardoCaxrnislalnog axKed MIng Page 8 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Declaration Statement
Signatory
Document Author
07/26/2023
I assert that this Certificate of Acceptance documentation is accurate and complete.
Sign Here:
Field Technician
Jeff Bernardino, Integrated Power &
I certify the following under penalty of perjury, under the laws of the State of California:
Lighting, Inc. , TC A813601 ,ATT/RP,
(951)270-0575
The information provided on this Certificate of Acceptance is true and correct. I am the person who
performed the acceptance verification reported on this Certificate of Acceptance (Field Technician). The
construction or installation identified on this Certificate of Acceptance complies with the applicable
acceptance requirements indicated in the plans and specifications approved by the enforcement agency,
Sign Below:
and conforms to the applicable acceptance requirements and procedures specified in Reference
J�__
Nonresidential Appendix NA7. I have confirmed that the Certificate(s) of Installation for the construction or
installation identified on this Certificate of Acceptance has been completed and signed by the responsible
Select Date 07/26/2023
builder/installer and has been posted or made available with the building ermit s issued for the building.
Signed:
Responsible Person
Jeff Bernardino, Integrated Power &
I certify the following under penalty of perjury, under the laws of the State of California:
Lighting Inc, 993105, ATT/RP, (951)
270-0575
I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and
I have reviewed the information provided on this Certificate of Acceptance. I am eligible under Division 3
of the Business and Professions Code in the applicable classification to accept responsibility for the system
design, construction or installation of features, materials, components, or manufactured devices for the
scope of work identified on this Certificate of Acceptance and attest to the declarations in this statement
(responsible acceptance person). The information provided on this Certificate of Acceptance substantiates
that the construction or installation identified on this Certificate of Acceptance complies with the
acceptance requirements indicated in the plans and specifications approved by the enforcement agency,
Sign Below:
and conforms to the applicable acceptance requirements and procedures specified in Reference
J
Nonresidential Appendix NA7. I have confirmed that the Certificate(s) of Installation for the construction
or installation identified on this Certificate of Acceptance has been completed and is posted or made
available with the building permit(s) issued for the building. I will ensure that a completed, signed copy of
this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the
Select Date
building, and made available to the enforcement agency for all applicable inspections. I understand that a
Signed: 07/26/2023
signed copy of this Certificate of Acceptance is required to be included with the documentation the builder
provides to the building owner at occupancy.
CarlrQmla AdvaKed llgMing
cAL �\
TP Lontn lialmngPrDgram Page 3 of 3 January 1, 2023
� STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Project Name and Address
Authority Having Jurisdiction
Salon Centric TI
CITY OF LA QUINTA
46480 Washington St., #3
BCOM2022-0060
La Quinta 92253
Permit Iss. Date: 5/5/2023
■❑Construction inspection and functional testing comply Date Submitted 7/26/23
❑Does not comply �to AHJ:
This document is used to demonstrate compliance with acceptance requirements in
Intent: §130.4(a)4, §160.5(e)1D and Reference Nonresidential Appendix NA7.6.2 for shut-off
lighting controls. Attach additional sets of pages 1 through 8, as required, for all
controls that must be tested.
Indicate all types of shut-off controls tested for this project
❑
Automatic time switch lighting controls (Tables A-1 and B-1 of this document should be
completed)
Occupant sensing lighting controls (including occupant sensors, partial -ON occupant
❑■
sensors, partial -OFF occupant sensors, and/or vacancy sensors) (Tables A-2 and B-2 of this
document should be completed)
❑
Multi zone occupant sensing lighting controls in office spaces larger than 250 square feet
Tables A-2 and B-3 of this document should be completed)
Automatic Time Switch Lighting Controls
Table A-1. Automatic Time Switch Lighting Controls Construction Ins ection
Code
Step
Entry
Item
Reference
1
❑
The automatic time switch controls are shown on
NA7.6.2.5(a)
Ian documents and are installed.
NA7.6.2.5(b)
Automatic time switch controls are programmed
§110.9(b)1Aii
§130.1(c)1A
2
❑
with acceptable weekday, weekend, and holiday
§130.1(c)4
(if applicable) schedules.
§160.5(b)4Cia
§160.5(b)4Civ
Document weekday, weekend, and holidays
3
❑
schedules, as well as all set-up and preference
NA7.6.2.5(c)
program settings.
4
❑
The correct time and date are properly set in the
NA7.6.2.5(d)
automatic time switch controls.
5
❑
The battery backup (if applicable) is installed and
NA7.6.2.5(e)
energized.
§110.9 b 1
Manual override time limit is set to no more than 2
NA7.6.2.5(f)
6
❑
hours, OR
§110.9(b)1Ai
The automatic time switch control's manual
§130.1(c)3B
override time is exempt from the 2-hour limit.
§160.5 b 4Ciiib
`' TP CardoCaxrnislalnog axKed MIng Page 1 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Step
Item
Code
Reference
Manual override switches located remotely from
NA7.6.2.5(g)
area with controlled luminaires allow the user to
§130.1(c)3A
7
❑
see the controlled luminaires or have a visual
§130.1(a)
signal or display showing the current state of the
§160.5(b)4Ciiia
controlled luminaires.
§160.5 b 4A
❑ Pass
N/A
❑ Fail
Construction Inspection Compliance.
N/A
Table B-1: Automatic Time Switch Lighting Controls Functional Testing
Buildinq: Retail / Cashi i Floor:l 1 Room: Retail / Cashier Control: Occ Sensor
Code
Step
Entry
Functional Test
Reference
1
No Entry
Occupied Test. Simulate occupied condition in
NA7.6.2.6(a)
the controlled space.
1.1
❑ Yes
The automatic time switch control turns on the
NA7.6.2.6(a)1
❑ No
controlled lighting.
2
No Entry
Unoccupied Test. Simulate an unoccupied
NA7.6.2.6(b)
condition in the controlled space.
2.1
❑ Yes
The automatic time switch control turns off all
NA7.6.2.6(b)1
§130.1(c)1A
❑ No
controlled lighting.
§ 160.5 b 4Cia
For the area controlled by an automatic time
switch control with a configured automatic holiday
NA7.6.2.6(b)2
2.2
❑ Yes
shut-off, the controlled lighting can be turned off
§110.9(b)1Aii
❑ No
automatically by the holiday shut-off, OR the
§130.1(c)4
automatic time switch control is exempt from
§160.5(b)4Civ
incor orating an automatic holiday shut-off.
For the area controlled by an automatic time
switch control with a time override located in and
NA7.6.2.6(b)3
❑ Yes
for the area, the lighting can be turned on
§110.9(b)1Ai
2.3
❑ No
manually by initiating the time override. The
§130.1(c)3B
lighting is configured to remain on for no more
§160.5(b)4Ciiib
than 2 hours OR the area is exempt from the 2-
hour time override limit.
N/A
0 Pass
❑ Fail
Functional Testing Compliance.
N/A
&TP CaFbrmAMMMW`"I" Page 2 of 9 January 1, 2023
cALCmtrnN halting Pr rm
4
'� �� STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Occupant Sensing Lighting Controls
Table A-2: Occupant Sensina Liahtina Control Construction Inspection
Code
Step
Entry
Item
Reference
1
❑E
The occupant sensing lighting controls are shown
NA7.6.2.1(a)
on plan documents and are installed.
Occupant sensing lighting control is installed per
manufacturer's instructions to minimize false
2
❑■
triggering — such as to install an occupancy sensor
NA7.6.2.1(c)
away from HVAC diffusers to avoid probable false
triggerin .
N/A
0 Pass
❑ Fail
Construction Inspection Compliance.
N/A
Table B-2: Occupant Sensing Lighting Control Functional Testing
Buildina: Retail / Cashie Floor:1 I Room: Retail / Cashier I Control: Occ Sensor
Step
Entry
Functional Test
Code
Reference
❑ Yes
Control is representative of sample. If sampling
N/A❑
No
method is used, attach a page listing untested
NA7.6.2.2
controls in sample.
1
No Entry
Unoccupied Test. Simulate an unoccupied
NA7.6.2.3(a)
condition in the controlled space.
`' TP CardoCaxrnislalnog axKed MIng Page 3 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Code
Step
Entry
Functional Test
Reference
The occupant sensing control turn the controlled
lighting off or partially off, if applicable, in 20
minutes or less from start of an unoccupied
condition. In addition:
For partial -on occupant sensing controls,
1
occupant sensing controls and vacancy sensing
§110.9(b)4A
§110. (b)4
controls, the controlled lighting is turned off in
unoccupied condition.
In the partial off state, partial OFF occupant
sensing controls automatically reduce lighting
power by at least 50 percent, OR:
• For warehouses with metal halide or high
pressure sodium lighting, automatically
§130.1(c)6A-C
reduce lighting power by at least 40
§130.1(c)7A
percent.
• For aisle ways and open areas in
§160.5(b)4Cvia
warehouses in which the installed lighting
❑■ Yes
power is 80 percent or less of the value
1.1
❑ No
allowed under the Area Category Method,
automatically reduce lighting power by at
least 40 percent.
• In corridors and stairwells that provide
access to guestrooms in hotel/motels in
which the installed lighting power is 80
percent or less of the value allowed under
the Area Category Method, automatically
reduce lighting power by at least 40
percent.
For parking garages, parking areas, and loading
and unloading areas, occupant sensing controls
§130.1(c)7B
have at least one control step between 20 to 50
§160.5(b)4Cviib
percent of design lighting power, OR Occupant
sensing controls for metal halide luminaires with a
lamp plus ballast mean system efficacy of 75
lumens per watt, in parking garages, parking
areas, and loading and unloading areas, have at
least one control step between 20 to 60 percent
of design lighting power.
2
No Entry
Occupied Test. Simulate an occupied condition in
NA7.6.2.3(b)
the controlled space.
2.1
❑■ Yes
No ❑
Status indicator or annunciator operates correctly.
NA7.6.2.3(b)1
§110.9b4C
`' TP CardornislalnaxKed ogMIng Page 4 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Step
Entry
Functional Test
Code
Reference
Immediately upon an occupied condition:
NA7.6.2.3(b)2
• The occupant sensing control or partial off
occupant sensing control turns on
controlled lighting; OR
• The vacancy sensing control indicate a
space is occupied and the controlled
2.2
0 Yes
lighting can be turned on manually; OR
❑ No
• The partial -on occupant sensing controls
automatically turns on the controlled
§130.1(c)5A
lighting at between 50 to 70 percent of
§160.5(b)4Cva
controlled lighting power. After the partial -
on stage, manual switches can be activated
to turn on the controlled lighting at full
controlled lighting ower.
N/A
0 Pass
❑ Fail
Functional Testing Compliance.
N/A
Table B-3: Multi -Zone Occupant Sensing Lighting Controls Functional Testing
Buildinq: Retail / Cashi i Floor:1 1 Room: Retail / Cashier Control: Occ Sensor
Code
Step
Entry
Functional Test
Reference
❑ Yes
Control is representative of sample. If sampling
N/A
❑ No
method is used, attach a page listing untested
NA7.6.2.2
controls in sample.
Occupied Control Zone Test. Simulate an
1
No Entry
occupied condition in the control zone controlled
NA7.6.2.4(a)
by the occupant sensor.
1.1
Yes
Immediately upon occupancy of the control zone,
NA7.6.2.4(a)1
❑ No
the occupant sensors turn on controlled lighting.
Enter the illuminance value in footcandles (fc)
measured at a location in the control zone where
the controlled lighting is at full light output or
designed light output if it has been documented
that dimming luminaires have been intentionally
1.2
Enter Value
tuned to less than full output and the design
NA7.6.2.4(a)2
illuminance levels are provided.
Informational note: Automatic daylighting controls
may need to be temporarily overridden to achieve
full or designed light output for the test.
1.3
❑ Yes
Signal sensitivity is adequate to achieve desired
NA7.6.2.4(a)3
❑ No
control.
1.4
❑ Yes
❑No
Status indicator or annunciator operates properly.
NA7.6.2.4(a)4
§110.9b4C
�,
QrUprnlBhdwu.Koo lghting Page 5 of 9 January 1, 2023
C, L&TP GONnIS arammp Program
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Code
Step
Entry
Functional Test
Reference
Unoccupied Control Zone Test. Simulate an
unoccupied condition in the control zone
2
No Entry
controlled by the occupant sensor. Confirm that at
NA7.6.2.4(b)
least one other control zone within the office
space is occupied.
The occupant sensor uniformly reduces light
NA7.6.2.4(b)1
2.1
❑ Yes
output of the controlled lighting in 20 minutes or
§130.1(c)6Dii
❑ No
less from the start of the unoccupied condition in
§160.5(b)4CvibII
the control zone.
Enter the illuminance value during unoccupancy in
2.2
Enter Value
footcandles (fc) measured at the same location as
NA7.6.2.4(b)2
in Step 1.2.
Calculate the ratio of the illuminance during
2.3
NaN
unoccupancy to the illuminance at full or designed
NA7.6.2.4(b)2
light output in %. ([Step 2.2 / Step 1.2] x 100
2.4
❑ Yes
The ratio of illuminance from Step 2.3 is no more
NA7.6.2.4(b)2
§130.1(c)6Dii
❑ No
than 20%.
§160.5 b 4CvibII
The occupant sensing control does not trigger a
false on from movement outside of the control
zone or from HVAC operation.
❑ Yes
Informational note: The field of view of occupant
2.5
❑ No
sensors in the adjacent control zones in office
NA7.6.2.4(b)3
spaces larger than 250 square feet may overlap,
but the field of view should stay away from an
adjacent enclosed space that is not part of the
office space, like conference rooms, and private
offices.
2.6
❑ Yes
Signal sensitivity is adequate to achieve desired
NA7.6.2.4(b)4
❑ No
control.
Control Zone Size Test. Follow the procedures
3
No Entry
described in either Method 1 (Steps 3.1 — 3.1.3)
NA7.6.2.4(c)
OR Method 2 (Steps 3.2 — 3.2.4
`� TP CaFbrm�`"I" Page 6 of 9 January 1, 2023
cALCmtrn. halting Pr rm
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Code
Step
Entry
Functional Test
Reference
Method 1: Simulate an unoccupied condition in
the control zone controlled by the occupant
sensor while standing in an adjacent control zone.
Determine the "edge" of the control zone
controlled by the occupant sensor by moving
toward the occupant sensor until the lights
3.1
No Entry
controlled by the occupant sensor turn on to
NA7.6.2.4(c)
simulate an occupied condition for that control
Method 1
zone.
Informational note: While moving toward the
occupant sensor, making additional movements,
motions, or sounds may be necessary to trigger
the occupant sensor.
Enter the distance in feet (ft) measured from the
3.1.1
"edge" of the control zone to the spot that is
NA7.6.2.4(c)
directly below the occupant sensor. This is the
Method 1
radius of the control zone.
3.1.2
Calculate the area (in ftz) of the control zone by
NA7.6.2.4(c)
using the formula: Area = 3.14*radius2.
Method 1
NA7.6.2.4(c)
3.1.3
❑ Yes
The area of the control zone (Step 3.1.2) is less
Method 1
❑ No
than or equal to 600 square feet.
§130.1(c)6Di
§160.5 b 4CvibI
3.2
No Entry
Method 2: Simulate an unoccupied condition for
NA7.6.2.4(c)
the entire offices ace.
Method 2
Walk through the space and count the number of
NA7.6.2.4(c)
3.2.1
zones of lighting that turn on automatically. Enter
Method 2
the number of zones that turn on automatically.
Enter the area of the office space (in ftz) from
construction plans or from other information
NA7.6.2.4(c)2
3.2.2
source such as construction documents or
Method 2
Nonresidential Certificates of Compliance
N RCCs .
Divide the area of the office by the number of
NA7.6.2.4(c)3
3.2.3
NaN
zones. Enter the value in square feet. This
Method 2
calculated value is the assessed control zone size.
NA7.6.2.4(c)4
3.2.4
❑ Yes
The area of the control zone is less than or equal
Method 2
❑ No
to 600 square feet.
§130.1(c)6Di
160.5 b 4CvibI
corlrprnl0Adv�ooUghting Page 7 of 9 January 1, 2023
cAL&TP Gas= lfalmng Program
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Step
Entry
Functional Test
Code
Reference
Unoccupied Office Test. Simulate an
unoccupied condition in all control zones
NA7.6.2.4(d)
❑Yes
controlled by all occupant sensors in the office.
§130.1(c)6Diii§1
4
❑ No
In 20 minutes or less from the start of the
60.5(b)4CvibIII
unoccupied condition of the entire office, all
controlled lighting in the office is turned off.
N/A
0 Pass
❑ Fail
Functional Testing Compliance.
N/A
`' TP CardoCaxrnislalnog axKed MIng Page 8 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Declaration Statement
Signatory
Document Author
07/26/2023
I assert that this Certificate of Acceptance documentation is accurate and complete.
Sign Here:
Field Technician
Jeff Bernardino, Integrated Power &
I certify the following under penalty of perjury, under the laws of the State of California:
Lighting, Inc. , TC-A813601 ,ATT/RP,
(951)270-0575
The information provided on this Certificate of Acceptance is true and correct. I am the person who
performed the acceptance verification reported on this Certificate of Acceptance (Field Technician). The
construction or installation identified on this Certificate of Acceptance complies with the applicable
acceptance requirements indicated in the plans and specifications approved by the enforcement agency,
Sign Below:
and conforms to the applicable acceptance requirements and procedures specified in Reference
J
Nonresidential Appendix NA7. I have confirmed that the Certificate(s) of Installation for the construction or
installation identified on this Certificate of Acceptance has been completed and signed by the responsible
Select Date 07/26/2023
builder/installer and has been posted or made available with the building permit(s) issued for the building.
Signed:
Responsible Person
Jeff Bernardino, Integrated Power &
I certify the following under penalty of perjury, under the laws of the State of California:
Lighting Inc, 993105, ATT/RP, (951)
270-0575
I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and
I have reviewed the information provided on this Certificate of Acceptance. I am eligible under Division 3
of the Business and Professions Code in the applicable classification to accept responsibility for the system
design, construction or installation of features, materials, components, or manufactured devices for the
scope of work identified on this Certificate of Acceptance and attest to the declarations in this statement
(responsible acceptance person). The information provided on this Certificate of Acceptance substantiates
that the construction or installation identified on this Certificate of Acceptance complies with the
acceptance requirements indicated in the plans and specifications approved by the enforcement agency,
Sign Below:
and conforms to the applicable acceptance requirements and procedures specified in Reference
Nonresidential Appendix NA7. I have confirmed that the Certificate(s) of Installation for the construction
or installation identified on this Certificate of Acceptance has been completed and is posted or made
available with the building permit(s) issued for the building. I will ensure that a completed, signed copy of
this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the
Select Date
building, and made available to the enforcement agency for all applicable inspections. I understand that a
Signed: 07/26/2023
signed copy of this Certificate of Acceptance is required to be included with the documentation the builder
provides to the building owner at occupancy.
C
cAL % TP D �Islralning gProgramPage 3 of 3 January 1, 2023
� STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Project Name and Address
Authority Having Jurisdiction
Salon Centric TI
CITY OF LA QUINTA
46480 Washington St., #3
BCOM2022-0060
La Quinta 92253
Permit Iss. Date: 5/5/2023
■❑Construction inspection and functional testing comply Date Submitted 7/26/23
❑Does not comply �to AHJ:
This document is used to demonstrate compliance with acceptance requirements in
Intent: §130.4(a)4, §160.5(e)1D and Reference Nonresidential Appendix NA7.6.2 for shut-off
lighting controls. Attach additional sets of pages 1 through 8, as required, for all
controls that must be tested.
Indicate all types of shut-off controls tested for this project
❑
Automatic time switch lighting controls (Tables A-1 and B-1 of this document should be
completed)
Occupant sensing lighting controls (including occupant sensors, partial -ON occupant
❑■
sensors, partial -OFF occupant sensors, and/or vacancy sensors) (Tables A-2 and B-2 of this
document should be completed)
❑
Multi zone occupant sensing lighting controls in office spaces larger than 250 square feet
Tables A-2 and B-3 of this document should be completed)
Automatic Time Switch Lighting Controls
Table A-1. Automatic Time Switch Lighting Controls Construction Ins ection
Code
Step
Entry
Item
Reference
1
❑
The automatic time switch controls are shown on
NA7.6.2.5(a)
Ian documents and are installed.
NA7.6.2.5(b)
Automatic time switch controls are programmed
§110.9(b)1Aii
§130.1(c)1A
2
❑
with acceptable weekday, weekend, and holiday
§130.1(c)4
(if applicable) schedules.
§160.5(b)4Cia
§160.5(b)4Civ
Document weekday, weekend, and holidays
3
❑
schedules, as well as all set-up and preference
NA7.6.2.5(c)
program settings.
4
❑
The correct time and date are properly set in the
NA7.6.2.5(d)
automatic time switch controls.
5
❑
The battery backup (if applicable) is installed and
NA7.6.2.5(e)
energized.
§110.9 b 1
Manual override time limit is set to no more than 2
NA7.6.2.5(f)
6
❑
hours, OR
§110.9(b)1Ai
The automatic time switch control's manual
§130.1(c)3B
override time is exempt from the 2-hour limit.
§160.5 b 4Ciiib
`' TP CardoCaxrnislalnog axKed MIng Page 1 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Step
Item
Code
Reference
Manual override switches located remotely from
NA7.6.2.5(g)
area with controlled luminaires allow the user to
§130.1(c)3A
7
❑
see the controlled luminaires or have a visual
§130.1(a)
signal or display showing the current state of the
§160.5(b)4Ciiia
controlled luminaires.
§160.5 b 4A
❑ Pass
N/A
❑ Fail
Construction Inspection Compliance.
N/A
Table B-1: Automatic Time Switch Lighting Controls Functional Testing
Buildinq: Office Floor:l 1 Room: Office < 250 sf Control: Occ Sensor
Code
Step
Entry
Functional Test
Reference
1
No Entry
Occupied Test. Simulate occupied condition in
NA7.6.2.6(a)
the controlled space.
1.1
❑ Yes
The automatic time switch control turns on the
NA7.6.2.6(a)1
❑ No
controlled lighting.
2
No Entry
Unoccupied Test. Simulate an unoccupied
NA7.6.2.6(b)
condition in the controlled space.
2.1
❑ Yes
The automatic time switch control turns off all
NA7.6.2.6(b)1
§130.1(c)1A
❑ No
controlled lighting.
§ 160.5 b 4Cia
For the area controlled by an automatic time
switch control with a configured automatic holiday
NA7.6.2.6(b)2
2.2
❑ Yes
shut-off, the controlled lighting can be turned off
§110.9(b)1Aii
❑ No
automatically by the holiday shut-off, OR the
§130.1(c)4
automatic time switch control is exempt from
§160.5(b)4Civ
incor orating an automatic holiday shut-off.
For the area controlled by an automatic time
switch control with a time override located in and
NA7.6.2.6(b)3
❑ Yes
for the area, the lighting can be turned on
§110.9(b)1Ai
2.3
❑ No
manually by initiating the time override. The
§130.1(c)3B
lighting is configured to remain on for no more
§160.5(b)4Ciiib
than 2 hours OR the area is exempt from the 2-
hour time override limit.
N/A
0 Pass
❑ Fail
Functional Testing Compliance.
N/A
&TP CaFbrmAMMMW`"I" Page 2 of 9 January 1, 2023
cALCmtrnN halting Pr rm
4
'� �� STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Occupant Sensing Lighting Controls
Table A-2: Occupant Sensina Liahtina Control Construction Inspection
Code
Step
Entry
Item
Reference
1
❑E
The occupant sensing lighting controls are shown
NA7.6.2.1(a)
on plan documents and are installed.
Occupant sensing lighting control is installed per
manufacturer's instructions to minimize false
2
❑■
triggering — such as to install an occupancy sensor
NA7.6.2.1(c)
away from HVAC diffusers to avoid probable false
triggerin .
N/A
0 Pass
❑ Fail
Construction Inspection Compliance.
N/A
Table B-2: Occupant Sensing Lighting Control Functional Testing
Buildina: Office I Floor:1 I Room: Office < 250 sf I Control: Occ Sensor
Step
Entry
Functional Test
Code
Reference
❑ Yes
Control is representative of sample. If sampling
N/A❑
No
method is used, attach a page listing untested
NA7.6.2.2
controls in sample.
1
No Entry
Unoccupied Test. Simulate an unoccupied
NA7.6.2.3(a)
condition in the controlled space.
`' TP CardoCaxrnislalnog axKed MIng Page 3 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Code
Step
Entry
Functional Test
Reference
The occupant sensing control turn the controlled
lighting off or partially off, if applicable, in 20
minutes or less from start of an unoccupied
condition. In addition:
For partial -on occupant sensing controls,
1
occupant sensing controls and vacancy sensing
§110.9(b)4A
§110. (b)4
controls, the controlled lighting is turned off in
unoccupied condition.
In the partial off state, partial OFF occupant
sensing controls automatically reduce lighting
power by at least 50 percent, OR:
• For warehouses with metal halide or high
pressure sodium lighting, automatically
§130.1(c)6A-C
reduce lighting power by at least 40
§130.1(c)7A
percent.
• For aisle ways and open areas in
§160.5(b)4Cvia
warehouses in which the installed lighting
❑■ Yes
power is 80 percent or less of the value
1.1
❑ No
allowed under the Area Category Method,
automatically reduce lighting power by at
least 40 percent.
• In corridors and stairwells that provide
access to guestrooms in hotel/motels in
which the installed lighting power is 80
percent or less of the value allowed under
the Area Category Method, automatically
reduce lighting power by at least 40
percent.
For parking garages, parking areas, and loading
and unloading areas, occupant sensing controls
§130.1(c)7B
have at least one control step between 20 to 50
§160.5(b)4Cviib
percent of design lighting power, OR Occupant
sensing controls for metal halide luminaires with a
lamp plus ballast mean system efficacy of 75
lumens per watt, in parking garages, parking
areas, and loading and unloading areas, have at
least one control step between 20 to 60 percent
of design lighting power.
2
No Entry
Occupied Test. Simulate an occupied condition in
NA7.6.2.3(b)
the controlled space.
2.1
❑■ Yes
No ❑
Status indicator or annunciator operates correctly.
NA7.6.2.3(b)1
§110.9b4C
`' TP CardornislalnaxKed ogMIng Page 4 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Step
Entry
Functional Test
Code
Reference
Immediately upon an occupied condition:
NA7.6.2.3(b)2
• The occupant sensing control or partial off
occupant sensing control turns on
controlled lighting; OR
• The vacancy sensing control indicate a
space is occupied and the controlled
2.2
❑■ Yes
lighting can be turned on manually; OR
❑ No
• The partial -on occupant sensing controls
automatically turns on the controlled
§130.1(c)5A
lighting at between 50 to 70 percent of
§160.5(b)4Cva
controlled lighting power. After the partial -
on stage, manual switches can be activated
to turn on the controlled lighting at full
controlled lighting ower.
N/A
0 Pass
❑ Fail
Functional Testing Compliance.
N/A
Table B-3: Multi -Zone Occuuant Sensin
Controls Functional Testin
Buildinq: Office I Floor:1 I Room: Office < 250 sf I Control: Occ Sensor
Code
Step
Entry
Functional Test
Reference
❑ Yes
Control is representative of sample. If sampling
N/A
❑ No
method is used, attach a page listing untested
NA7.6.2.2
controls in sample.
Occupied Control Zone Test. Simulate an
1
No Entry
occupied condition in the control zone controlled
NA7.6.2.4(a)
b the occu ant sensor.
1.1
Yes
Immediately upon occupancy of the control zone,
NA7.6.2.4(a)1
❑ No
the occupant sensors turn on controlled lighting.
Enter the illuminance value in footcandles (fc)
measured at a location in the control zone where
the controlled lighting is at full light output or
designed light output if it has been documented
that dimming luminaires have been intentionally
1.2
Enter Value
tuned to less than full output and the design
NA7.6.2.4(a)2
illuminance levels are provided.
Informational note: Automatic daylighting controls
may need to be temporarily overridden to achieve
full or designed light output for the test.
1.3
❑ Yes
Signal sensitivity is adequate to achieve desired
NA7.6.2.4(a)3
❑ No
control.
1.4
❑ Yes
❑No
Status indicator or annunciator operates properly.
NA7.6.2.4(a)4
§110.9b4C
�,
QrUprnlBhdwu.Koo lghting Page 5 of 9 January 1, 2023
C, L&TP GONnIS arammp Program
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Code
Step
Entry
Functional Test
Reference
Unoccupied Control Zone Test. Simulate an
unoccupied condition in the control zone
2
No Entry
controlled by the occupant sensor. Confirm that at
NA7.6.2.4(b)
least one other control zone within the office
space is occupied.
The occupant sensor uniformly reduces light
NA7.6.2.4(b)1
2.1
❑ Yes
output of the controlled lighting in 20 minutes or
§130.1(c)6Dii
❑ No
less from the start of the unoccupied condition in
§160.5(b)4CvibII
the control zone.
Enter the illuminance value during unoccupancy in
2.2
Enter Value
footcandles (fc) measured at the same location as
NA7.6.2.4(b)2
in Step 1.2.
Calculate the ratio of the illuminance during
2.3
NaN
unoccupancy to the illuminance at full or designed
NA7.6.2.4(b)2
light output in %. ([Step 2.2 / Step 1.2] x 100
2.4
❑ Yes
The ratio of illuminance from Step 2.3 is no more
NA7.6.2.4(b)2
§130.1(c)6Dii
❑ No
than 20%.
§160.5 b 4CvibII
The occupant sensing control does not trigger a
false on from movement outside of the control
zone or from HVAC operation.
❑ Yes
Informational note: The field of view of occupant
2.5
❑ No
sensors in the adjacent control zones in office
NA7.6.2.4(b)3
spaces larger than 250 square feet may overlap,
but the field of view should stay away from an
adjacent enclosed space that is not part of the
office space, like conference rooms, and private
offices.
2.6
❑ Yes
Signal sensitivity is adequate to achieve desired
NA7.6.2.4(b)4
❑ No
control.
Control Zone Size Test. Follow the procedures
3
No Entry
described in either Method 1 (Steps 3.1 — 3.1.3)
NA7.6.2.4(c)
OR Method 2 (Steps 3.2 — 3.2.4
`� TP CaFbrm�`"I" Page 6 of 9 January 1, 2023
cALCmtrn. halting Pr rm
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Code
Step
Entry
Functional Test
Reference
Method 1: Simulate an unoccupied condition in
the control zone controlled by the occupant
sensor while standing in an adjacent control zone.
Determine the "edge" of the control zone
controlled by the occupant sensor by moving
toward the occupant sensor until the lights
3.1
No Entry
controlled by the occupant sensor turn on to
NA7.6.2.4(c)
simulate an occupied condition for that control
Method 1
zone.
Informational note: While moving toward the
occupant sensor, making additional movements,
motions, or sounds may be necessary to trigger
the occupant sensor.
Enter the distance in feet (ft) measured from the
3.1.1
"edge" of the control zone to the spot that is
NA7.6.2.4(c)
directly below the occupant sensor. This is the
Method 1
radius of the control zone.
3.1.2
Calculate the area (in ftz) of the control zone by
NA7.6.2.4(c)
using the formula: Area = 3.14*radius2.
Method 1
NA7.6.2.4(c)
3.1.3
❑ Yes
The area of the control zone (Step 3.1.2) is less
Method 1
❑ No
than or equal to 600 square feet.
§130.1(c)6Di
§160.5 b 4CvibI
3.2
No Entry
Method 2: Simulate an unoccupied condition for
NA7.6.2.4(c)
the entire offices ace.
Method 2
Walk through the space and count the number of
NA7.6.2.4(c)
3.2.1
zones of lighting that turn on automatically. Enter
Method 2
the number of zones that turn on automatically.
Enter the area of the office space (in ftz) from
construction plans or from other information
NA7.6.2.4(c)2
3.2.2
source such as construction documents or
Method 2
Nonresidential Certificates of Compliance
N RCCs .
Divide the area of the office by the number of
NA7.6.2.4(c)3
3.2.3
NaN
zones. Enter the value in square feet. This
Method 2
calculated value is the assessed control zone size.
NA7.6.2.4(c)4
3.2.4
❑ Yes
The area of the control zone is less than or equal
Method 2
❑ No
to 600 square feet.
§130.1(c)6Di
160.5 b 4CvibI
corlrprnl0Adv�ooUghting Page 7 of 9 January 1, 2023
cAL&TP Gas= lfalmng Program
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Step
Entry
Functional Test
Code
Reference
Unoccupied Office Test. Simulate an
unoccupied condition in all control zones
NA7.6.2.4(d)
❑Yes
controlled by all occupant sensors in the office.
§130.1(c)6Diii§1
4
❑ No
In 20 minutes or less from the start of the
60.5(b)4CvibIII
unoccupied condition of the entire office, all
controlled lighting in the office is turned off.
N/A
0 Pass
❑ Fail
Functional Testing Compliance.
N/A
`' TP CardoCaxrnislalnog axKed MIng Page 8 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Declaration Statement
Signatory
Document Author
07/26/2023
I assert that this Certificate of Acceptance documentation is accurate and complete.
Sign Here:
J�_
Field Technician
Jeff Bernardino, Integrated Power &
I certify the following under penalty of perjury, under the laws of the State of California:
Lighting, Inc. , TC-A813601 ,ATT/RP,
(951)270-0575
The information provided on this Certificate of Acceptance is true and correct. I am the person who
performed the acceptance verification reported on this Certificate of Acceptance (Field Technician). The
construction or installation identified on this Certificate of Acceptance complies with the applicable
acceptance requirements indicated in the plans and specifications approved by the enforcement agency,
Sign Below:
and conforms to the applicable acceptance requirements and procedures specified in Reference
t
Nonresidential Appendix NA7. I have confirmed that the Certificate(s) of Installation for the construction or
installation identified on this Certificate of Acceptance has been completed and signed by the responsible
Select Date 07/26/2023
builder/installer and has been posted or made available with the building permit(s) issued for the building.
Signed:
Responsible Person
Jeff Bernardino, Integrated Power &
I certify the following under penalty of perjury, under the laws of the State of California:
Lighting Inc, 993105, ATT/RP, (951)
270-0575
I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and
I have reviewed the information provided on this Certificate of Acceptance. I am eligible under Division 3
of the Business and Professions Code in the applicable classification to accept responsibility for the system
design, construction or installation of features, materials, components, or manufactured devices for the
scope of work identified on this Certificate of Acceptance and attest to the declarations in this statement
(responsible acceptance person). The information provided on this Certificate of Acceptance substantiates
that the construction or installation identified on this Certificate of Acceptance complies with the
acceptance requirements indicated in the plans and specifications approved by the enforcement agency,
Sign Below:
and conforms to the applicable acceptance requirements and procedures specified in Reference
Nonresidential Appendix NA7. I have confirmed that the Certificate(s) of Installation for the construction
or installation identified on this Certificate of Acceptance has been completed and is posted or made
available with the building permit(s) issued for the building. I will ensure that a completed, signed copy of
this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the
Select Date
building, and made available to the enforcement agency for all applicable inspections. I understand that a
Signed: 07/26/2023
signed copy of this Certificate of Acceptance is required to be included with the documentation the builder
provides to the building owner at occupancy.
C
cAL % TP D �Islralning gProgramPage 3 of 3 January 1, 2023
� STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Project Name and Address
Authority Having Jurisdiction
Salon Centric TI
CITY OF LA QUINTA
46480 Washington St., #3
BCOM2022-0060
La Quinta 92253
Permit Iss. Date: 5/5/2023
■❑Construction inspection and functional testing comply Date Submitted 7/26/23
❑Does not comply �to AHJ:
This document is used to demonstrate compliance with acceptance requirements in
Intent: §130.4(a)4, §160.5(e)1D and Reference Nonresidential Appendix NA7.6.2 for shut-off
lighting controls. Attach additional sets of pages 1 through 8, as required, for all
controls that must be tested.
Indicate all types of shut-off controls tested for this project
❑
Automatic time switch lighting controls (Tables A-1 and B-1 of this document should be
completed)
Occupant sensing lighting controls (including occupant sensors, partial -ON occupant
❑■
sensors, partial -OFF occupant sensors, and/or vacancy sensors) (Tables A-2 and B-2 of this
document should be completed)
❑
Multi zone occupant sensing lighting controls in office spaces larger than 250 square feet
Tables A-2 and B-3 of this document should be completed)
Automatic Time Switch Lighting Controls
Table A-1. Automatic Time Switch Lighting Controls Construction Ins ection
Code
Step
Entry
Item
Reference
1
❑
The automatic time switch controls are shown on
NA7.6.2.5(a)
Ian documents and are installed.
NA7.6.2.5(b)
Automatic time switch controls are programmed
§110.9(b)1Aii
§130.1(c)1A
2
❑
with acceptable weekday, weekend, and holiday
§130.1(c)4
(if applicable) schedules.
§160.5(b)4Cia
§160.5(b)4Civ
Document weekday, weekend, and holidays
3
❑
schedules, as well as all set-up and preference
NA7.6.2.5(c)
program settings.
4
❑
The correct time and date are properly set in the
NA7.6.2.5(d)
automatic time switch controls.
5
❑
The battery backup (if applicable) is installed and
NA7.6.2.5(e)
energized.
§110.9 b 1
Manual override time limit is set to no more than 2
NA7.6.2.5(f)
6
❑
hours, OR
§110.9(b)1Ai
The automatic time switch control's manual
§130.1(c)3B
override time is exempt from the 2-hour limit.
§160.5 b 4Ciiib
`' TP CardoCaxrnislalnog axKed MIng Page 1 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Step
Item
Code
Reference
Manual override switches located remotely from
NA7.6.2.5(g)
area with controlled luminaires allow the user to
§130.1(c)3A
7
❑
see the controlled luminaires or have a visual
§130.1(a)
signal or display showing the current state of the
§160.5(b)4Ciiia
controlled luminaires.
§160.5 b 4A
❑ Pass
N/A
❑ Fail
Construction Inspection Compliance.
N/A
Table B-1: Automatic Time Switch Lighting Controls Functional Testing
Buildinq: Restroom Floor:l 1 Room: Restroom Control: Occ Sensor
Code
Step
Entry
Functional Test
Reference
1
No Entry
Occupied Test. Simulate occupied condition in
NA7.6.2.6(a)
the controlled space.
1.1
❑ Yes
The automatic time switch control turns on the
NA7.6.2.6(a)1
❑ No
controlled lighting.
2
No Entry
Unoccupied Test. Simulate an unoccupied
NA7.6.2.6(b)
condition in the controlled space.
2.1
❑ Yes
The automatic time switch control turns off all
NA7.6.2.6(b)1
§130.1(c)1A
❑ No
controlled lighting.
§ 160.5 b 4Cia
For the area controlled by an automatic time
switch control with a configured automatic holiday
NA7.6.2.6(b)2
2.2
❑ Yes
shut-off, the controlled lighting can be turned off
§110.9(b)1Aii
❑ No
automatically by the holiday shut-off, OR the
§130.1(c)4
automatic time switch control is exempt from
§160.5(b)4Civ
incor orating an automatic holiday shut-off.
For the area controlled by an automatic time
switch control with a time override located in and
NA7.6.2.6(b)3
❑ Yes
for the area, the lighting can be turned on
§110.9(b)1Ai
2.3
❑ No
manually by initiating the time override. The
§130.1(c)3B
lighting is configured to remain on for no more
§160.5(b)4Ciiib
than 2 hours OR the area is exempt from the 2-
hour time override limit.
N/A
0 Pass
❑ Fail
Functional Testing Compliance.
N/A
&TP CaFbrmAMMMW`"I" Page 2 of 9 January 1, 2023
cALCmtrnN halting Pr rm
4
'� �� STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Occupant Sensing Lighting Controls
Table A-2: Occupant Sensina Liahtina Control Construction Inspection
Code
Step
Entry
Item
Reference
1
❑E
The occupant sensing lighting controls are shown
NA7.6.2.1(a)
on plan documents and are installed.
Occupant sensing lighting control is installed per
manufacturer's instructions to minimize false
2
❑■
triggering — such as to install an occupancy sensor
NA7.6.2.1(c)
away from HVAC diffusers to avoid probable false
triggerin .
N/A
0 Pass
❑ Fail
Construction Inspection Compliance.
N/A
Table B-2: Occupant Sensing Lighting Control Functional Testing
Buildina: Restroom I Floor:1 I Room: Restroom I Control: Occ Sensor
Step
Entry
Functional Test
Code
Reference
❑ Yes
Control is representative of sample. If sampling
N/A❑
No
method is used, attach a page listing untested
NA7.6.2.2
controls in sample.
1
No Entry
Unoccupied Test. Simulate an unoccupied
NA7.6.2.3(a)
condition in the controlled space.
`' TP CardoCaxrnislalnog axKed MIng Page 3 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Code
Step
Entry
Functional Test
Reference
The occupant sensing control turn the controlled
lighting off or partially off, if applicable, in 20
minutes or less from start of an unoccupied
condition. In addition:
For partial -on occupant sensing controls,
1
occupant sensing controls and vacancy sensing
§110.9(b)4A
§110. (b)4
controls, the controlled lighting is turned off in
unoccupied condition.
In the partial off state, partial OFF occupant
sensing controls automatically reduce lighting
power by at least 50 percent, OR:
• For warehouses with metal halide or high
pressure sodium lighting, automatically
§130.1(c)6A-C
reduce lighting power by at least 40
§130.1(c)7A
percent.
• For aisle ways and open areas in
§160.5(b)4Cvia
warehouses in which the installed lighting
❑■ Yes
power is 80 percent or less of the value
1.1
❑ No
allowed under the Area Category Method,
automatically reduce lighting power by at
least 40 percent.
• In corridors and stairwells that provide
access to guestrooms in hotel/motels in
which the installed lighting power is 80
percent or less of the value allowed under
the Area Category Method, automatically
reduce lighting power by at least 40
percent.
For parking garages, parking areas, and loading
and unloading areas, occupant sensing controls
§130.1(c)7B
have at least one control step between 20 to 50
§160.5(b)4Cviib
percent of design lighting power, OR Occupant
sensing controls for metal halide luminaires with a
lamp plus ballast mean system efficacy of 75
lumens per watt, in parking garages, parking
areas, and loading and unloading areas, have at
least one control step between 20 to 60 percent
of design lighting power.
2
No Entry
Occupied Test. Simulate an occupied condition in
NA7.6.2.3(b)
the controlled space.
2.1
❑■ Yes
No ❑
Status indicator or annunciator operates correctly.
NA7.6.2.3(b)1
§110.9b4C
`' TP CardornislalnaxKed ogMIng Page 4 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Step
Entry
Functional Test
Code
Reference
Immediately upon an occupied condition:
NA7.6.2.3(b)2
• The occupant sensing control or partial off
occupant sensing control turns on
controlled lighting; OR
• The vacancy sensing control indicate a
space is occupied and the controlled
2.2
0 Yes
lighting can be turned on manually; OR
❑ No
• The partial -on occupant sensing controls
automatically turns on the controlled
§130.1(c)5A
lighting at between 50 to 70 percent of
§160.5(b)4Cva
controlled lighting power. After the partial -
on stage, manual switches can be activated
to turn on the controlled lighting at full
controlled lighting ower.
N/A
0 Pass
❑ Fail
Functional Testing Compliance.
N/A
Table B-3: Multi -Zone Occupant Sensing Lighting Controls Functional Testing
Buildinq: Restroom I Floor:1 1 Room: Restroom Control: Occ Sensor
Code
Step
Entry
Functional Test
Reference
❑ Yes
Control is representative of sample. If sampling
N/A
❑ No
method is used, attach a page listing untested
NA7.6.2.2
controls in sample.
Occupied Control Zone Test. Simulate an
1
No Entry
occupied condition in the control zone controlled
NA7.6.2.4(a)
b the occu ant sensor.
1.1
Yes
Immediately upon occupancy of the control zone,
NA7.6.2.4(a)1
❑ No
the occupant sensors turn on controlled lighting.
Enter the illuminance value in footcandles (fc)
measured at a location in the control zone where
the controlled lighting is at full light output or
designed light output if it has been documented
that dimming luminaires have been intentionally
1.2
Enter Value
tuned to less than full output and the design
NA7.6.2.4(a)2
illuminance levels are provided.
Informational note: Automatic daylighting controls
may need to be temporarily overridden to achieve
full or designed light output for the test.
1.3
❑ Yes
Signal sensitivity is adequate to achieve desired
NA7.6.2.4(a)3
❑ No
control.
1.4
❑ Yes
❑No
Status indicator or annunciator operates properly.
NA7.6.2.4(a)4
§110.9b4C
�,
QrUprnlBhdwu.Koo lghting Page 5 of 9 January 1, 2023
C, L&TP GONnIS arammp Program
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Code
Step
Entry
Functional Test
Reference
Unoccupied Control Zone Test. Simulate an
unoccupied condition in the control zone
2
No Entry
controlled by the occupant sensor. Confirm that at
NA7.6.2.4(b)
least one other control zone within the office
space is occupied.
The occupant sensor uniformly reduces light
NA7.6.2.4(b)1
2.1
❑ Yes
output of the controlled lighting in 20 minutes or
§130.1(c)6Dii
❑ No
less from the start of the unoccupied condition in
§160.5(b)4CvibII
the control zone.
Enter the illuminance value during unoccupancy in
2.2
Enter Value
footcandles (fc) measured at the same location as
NA7.6.2.4(b)2
in Step 1.2.
Calculate the ratio of the illuminance during
2.3
NaN
unoccupancy to the illuminance at full or designed
NA7.6.2.4(b)2
light output in %. ([Step 2.2 / Step 1.2] x 100
2.4
❑ Yes
The ratio of illuminance from Step 2.3 is no more
NA7.6.2.4(b)2
§130.1(c)6Dii
❑ No
than 20%.
§160.5 b 4CvibII
The occupant sensing control does not trigger a
false on from movement outside of the control
zone or from HVAC operation.
❑ Yes
Informational note: The field of view of occupant
2.5
❑ No
sensors in the adjacent control zones in office
NA7.6.2.4(b)3
spaces larger than 250 square feet may overlap,
but the field of view should stay away from an
adjacent enclosed space that is not part of the
office space, like conference rooms, and private
offices.
2.6
❑ Yes
Signal sensitivity is adequate to achieve desired
NA7.6.2.4(b)4
❑ No
control.
Control Zone Size Test. Follow the procedures
3
No Entry
described in either Method 1 (Steps 3.1 — 3.1.3)
NA7.6.2.4(c)
OR Method 2 (Steps 3.2 — 3.2.4
`� TP CaFbrm�`"I" Page 6 of 9 January 1, 2023
cALCmtrn. halting Pr rm
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Code
Step
Entry
Functional Test
Reference
Method 1: Simulate an unoccupied condition in
the control zone controlled by the occupant
sensor while standing in an adjacent control zone.
Determine the "edge" of the control zone
controlled by the occupant sensor by moving
toward the occupant sensor until the lights
3.1
No Entry
controlled by the occupant sensor turn on to
NA7.6.2.4(c)
simulate an occupied condition for that control
Method 1
zone.
Informational note: While moving toward the
occupant sensor, making additional movements,
motions, or sounds may be necessary to trigger
the occupant sensor.
Enter the distance in feet (ft) measured from the
3.1.1
"edge" of the control zone to the spot that is
NA7.6.2.4(c)
directly below the occupant sensor. This is the
Method 1
radius of the control zone.
3.1.2
Calculate the area (in ftz) of the control zone by
NA7.6.2.4(c)
using the formula: Area = 3.14*radius2.
Method 1
NA7.6.2.4(c)
3.1.3
❑ Yes
The area of the control zone (Step 3.1.2) is less
Method 1
❑ No
than or equal to 600 square feet.
§130.1(c)6Di
§160.5 b 4CvibI
3.2
No Entry
Method 2: Simulate an unoccupied condition for
NA7.6.2.4(c)
the entire offices ace.
Method 2
Walk through the space and count the number of
NA7.6.2.4(c)
3.2.1
zones of lighting that turn on automatically. Enter
Method 2
the number of zones that turn on automatically.
Enter the area of the office space (in ftz) from
construction plans or from other information
NA7.6.2.4(c)2
3.2.2
source such as construction documents or
Method 2
Nonresidential Certificates of Compliance
N RCCs .
Divide the area of the office by the number of
NA7.6.2.4(c)3
3.2.3
NaN
zones. Enter the value in square feet. This
Method 2
calculated value is the assessed control zone size.
NA7.6.2.4(c)4
3.2.4
❑ Yes
The area of the control zone is less than or equal
Method 2
❑ No
to 600 square feet.
§130.1(c)6Di
160.5 b 4CvibI
corlrprnl0Adv�ooUghting Page 7 of 9 January 1, 2023
cAL&TP Gas= lfalmng Program
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Step
Entry
Functional Test
Code
Reference
Unoccupied Office Test. Simulate an
unoccupied condition in all control zones
NA7.6.2.4(d)
❑Yes
controlled by all occupant sensors in the office.
§130.1(c)6Diii§1
4
❑ No
In 20 minutes or less from the start of the
60.5(b)4CvibIII
unoccupied condition of the entire office, all
controlled lighting in the office is turned off.
N/A
0 Pass
❑ Fail
Functional Testing Compliance.
N/A
`' TP CardoCaxrnislalnog axKed MIng Page 8 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Declaration Statement
Signatory
Document Author
Jeff Bernardino, Integrated Power &
I assert that this Certificate of Acceptance documentation is accurate and complete.
Lighting,07/26/2023
Sign Here:
Field Technician
Jeff Bernardino, Integrated Power &
I certify the following under penalty of perjury, under the laws of the State of California:
Lighting, Inc. , TC-A813601 ,ATT/RP,
(951)270-0575
The information provided on this Certificate of Acceptance is true and correct. I am the person who
performed the acceptance verification reported on this Certificate of Acceptance (Field Technician). The
construction or installation identified on this Certificate of Acceptance complies with the applicable
acceptance requirements indicated in the plans and specifications approved by the enforcement agency,
Sign Below:
and conforms to the applicable acceptance requirements and procedures specified in Reference
J
Nonresidential Appendix NA7. I have confirmed that the Certificate(s) of Installation for the construction or
installation identified on this Certificate of Acceptance has been completed and signed by the responsible
Select Date 07/26/2023
builder/installer and has been posted or made available with the building permit(s) issued for the building.
Signed:
Responsible Person
Jeff Bernardino, Integrated Power &
I certify the following under penalty of perjury, under the laws of the State of California:
Lighting Inc, 993105, ATT/RP, (951)
270-0575
I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and
I have reviewed the information provided on this Certificate of Acceptance. I am eligible under Division 3
of the Business and Professions Code in the applicable classification to accept responsibility for the system
design, construction or installation of features, materials, components, or manufactured devices for the
scope of work identified on this Certificate of Acceptance and attest to the declarations in this statement
(responsible acceptance person). The information provided on this Certificate of Acceptance substantiates
that the construction or installation identified on this Certificate of Acceptance complies with the
acceptance requirements indicated in the plans and specifications approved by the enforcement agency,
Sign Below:
and conforms to the applicable acceptance requirements and procedures specified in Reference
1
Nonresidential Appendix NA7. I have confirmed that the Certificate(s) of Installation for the construction
�J
or installation identified on this Certificate of Acceptance has been completed and is posted or made
available with the building permit(s) issued for the building. I will ensure that a completed, signed copy of
this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the
Select Date
building, and made available to the enforcement agency for all applicable inspections. I understand that a
Signed: 07/26/2023
signed copy of this Certificate of Acceptance is required to be included with the documentation the builder
provides to the building owner at occupancy.
C
cAL % TP D �Islralning gProgramPage 3 of 3 January 1, 2023
� STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Project Name and Address
Authority Having Jurisdiction
Salon Centric TI
CITY OF LA QUINTA
46480 Washington St., #3
BCOM2022-0060
La Quinta 92253
Permit Iss. Date: 5/5/2023
■❑Construction inspection and functional testing comply Date Submitted 7/26/23
❑Does not comply �to AHJ:
This document is used to demonstrate compliance with acceptance requirements in
Intent: §130.4(a)4, §160.5(e)1D and Reference Nonresidential Appendix NA7.6.2 for shut-off
lighting controls. Attach additional sets of pages 1 through 8, as required, for all
controls that must be tested.
Indicate all types of shut-off controls tested for this project
❑
Automatic time switch lighting controls (Tables A-1 and B-1 of this document should be
completed)
Occupant sensing lighting controls (including occupant sensors, partial -ON occupant
❑■
sensors, partial -OFF occupant sensors, and/or vacancy sensors) (Tables A-2 and B-2 of this
document should be completed)
❑
Multi zone occupant sensing lighting controls in office spaces larger than 250 square feet
Tables A-2 and B-3 of this document should be completed)
Automatic Time Switch Lighting Controls
Table A-1. Automatic Time Switch Lighting Controls Construction Ins ection
Code
Step
Entry
Item
Reference
1
❑
The automatic time switch controls are shown on
NA7.6.2.5(a)
Ian documents and are installed.
NA7.6.2.5(b)
Automatic time switch controls are programmed
§110.9(b)1Aii
§130.1(c)1A
2
❑
with acceptable weekday, weekend, and holiday
§130.1(c)4
(if applicable) schedules.
§160.5(b)4Cia
§160.5(b)4Civ
Document weekday, weekend, and holidays
3
❑
schedules, as well as all set-up and preference
NA7.6.2.5(c)
program settings.
4
❑
The correct time and date are properly set in the
NA7.6.2.5(d)
automatic time switch controls.
5
❑
The battery backup (if applicable) is installed and
NA7.6.2.5(e)
energized.
§110.9 b 1
Manual override time limit is set to no more than 2
NA7.6.2.5(f)
6
❑
hours, OR
§110.9(b)1Ai
The automatic time switch control's manual
§130.1(c)3B
override time is exempt from the 2-hour limit.
§160.5 b 4Ciiib
`' TP CardoCaxrnislalnog axKed MIng Page 1 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Step
Item
Code
Reference
Manual override switches located remotely from
NA7.6.2.5(g)
area with controlled luminaires allow the user to
§130.1(c)3A
7
❑
see the controlled luminaires or have a visual
§130.1(a)
signal or display showing the current state of the
§160.5(b)4Ciiia
controlled luminaires.
§160.5 b 4A
❑ Pass
N/A
❑ Fail
Construction Inspection Compliance.
N/A
Table B-1: Automatic Time Switch Lighting Controls Functional Testing
Buildinq: Hallwav Floor:l 1 Room: Hallwav Control: Occ Sensor
Code
Step
Entry
Functional Test
Reference
1
No Entry
Occupied Test. Simulate occupied condition in
NA7.6.2.6(a)
the controlled space.
1.1
❑ Yes
The automatic time switch control turns on the
NA7.6.2.6(a)1
❑ No
controlled lighting.
2
No Entry
Unoccupied Test. Simulate an unoccupied
NA7.6.2.6(b)
condition in the controlled space.
2.1
❑ Yes
The automatic time switch control turns off all
NA7.6.2.6(b)1
§130.1(c)1A
❑ No
controlled lighting.
§ 160.5 b 4Cia
For the area controlled by an automatic time
switch control with a configured automatic holiday
NA7.6.2.6(b)2
2.2
❑ Yes
shut-off, the controlled lighting can be turned off
§110.9(b)1Aii
❑ No
automatically by the holiday shut-off, OR the
§130.1(c)4
automatic time switch control is exempt from
§160.5(b)4Civ
incor orating an automatic holiday shut-off.
For the area controlled by an automatic time
switch control with a time override located in and
NA7.6.2.6(b)3
❑ Yes
for the area, the lighting can be turned on
§110.9(b)1Ai
2.3
❑ No
manually by initiating the time override. The
§130.1(c)3B
lighting is configured to remain on for no more
§160.5(b)4Ciiib
than 2 hours OR the area is exempt from the 2-
hour time override limit.
N/A
0 Pass
❑ Fail
Functional Testing Compliance.
N/A
&TP CaFbrmAMMMW`"I" Page 2 of 9 January 1, 2023
cALCmtrnN halting Pr rm
4
'� �� STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Occupant Sensing Lighting Controls
Table A-2: Occupant Sensina Liahtina Control Construction Inspection
Code
Step
Entry
Item
Reference
1
❑E
The occupant sensing lighting controls are shown
NA7.6.2.1(a)
on plan documents and are installed.
Occupant sensing lighting control is installed per
manufacturer's instructions to minimize false
2
❑■
triggering — such as to install an occupancy sensor
NA7.6.2.1(c)
away from HVAC diffusers to avoid probable false
triggerin .
N/A
0 Pass
❑ Fail
Construction Inspection Compliance.
N/A
Table B-2: Occupant Sensing Lighting Control Functional Testing
Buildina: Hallwav I Floor:1 I Room: Hallwav I Control: Occ Sensor
Step
Entry
Functional Test
Code
Reference
❑ Yes
Control is representative of sample. If sampling
N/A❑
No
method is used, attach a page listing untested
NA7.6.2.2
controls in sample.
1
No Entry
Unoccupied Test. Simulate an unoccupied
NA7.6.2.3(a)
condition in the controlled space.
`' TP CardoCaxrnislalnog axKed MIng Page 3 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Code
Step
Entry
Functional Test
Reference
The occupant sensing control turn the controlled
lighting off or partially off, if applicable, in 20
minutes or less from start of an unoccupied
condition. In addition:
For partial -on occupant sensing controls,
1
occupant sensing controls and vacancy sensing
§110.9(b)4A
§110. (b)4
controls, the controlled lighting is turned off in
unoccupied condition.
In the partial off state, partial OFF occupant
sensing controls automatically reduce lighting
power by at least 50 percent, OR:
• For warehouses with metal halide or high
pressure sodium lighting, automatically
§130.1(c)6A-C
reduce lighting power by at least 40
§130.1(c)7A
percent.
• For aisle ways and open areas in
§160.5(b)4Cvia
warehouses in which the installed lighting
❑■ Yes
power is 80 percent or less of the value
1.1
❑ No
allowed under the Area Category Method,
automatically reduce lighting power by at
least 40 percent.
• In corridors and stairwells that provide
access to guestrooms in hotel/motels in
which the installed lighting power is 80
percent or less of the value allowed under
the Area Category Method, automatically
reduce lighting power by at least 40
percent.
For parking garages, parking areas, and loading
and unloading areas, occupant sensing controls
§130.1(c)7B
have at least one control step between 20 to 50
§160.5(b)4Cviib
percent of design lighting power, OR Occupant
sensing controls for metal halide luminaires with a
lamp plus ballast mean system efficacy of 75
lumens per watt, in parking garages, parking
areas, and loading and unloading areas, have at
least one control step between 20 to 60 percent
of design lighting power.
2
No Entry
Occupied Test. Simulate an occupied condition in
NA7.6.2.3(b)
the controlled space.
2.1
❑■ Yes
No ❑
Status indicator or annunciator operates correctly.
NA7.6.2.3(b)1
§110.9b4C
`' TP CardornislalnaxKed ogMIng Page 4 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Step
Entry
Functional Test
Code
Reference
Immediately upon an occupied condition:
NA7.6.2.3(b)2
• The occupant sensing control or partial off
occupant sensing control turns on
controlled lighting; OR
• The vacancy sensing control indicate a
space is occupied and the controlled
2.2
0 Yes
lighting can be turned on manually; OR
❑ No
• The partial -on occupant sensing controls
automatically turns on the controlled
§130.1(c)5A
lighting at between 50 to 70 percent of
§160.5(b)4Cva
controlled lighting power. After the partial -
on stage, manual switches can be activated
to turn on the controlled lighting at full
controlled lighting ower.
N/A
0 Pass
❑ Fail
Functional Testing Compliance.
N/A
Table B-3: Multi -Zone Occupant Sensing Lighting Controls Functional Testing
Buildinq: Hallway I Floor:1 Room: Hallway Control: Occ Sensor
Code
Step
Entry
Functional Test
Reference
❑ Yes
Control is representative of sample. If sampling
N/A
❑ No
method is used, attach a page listing untested
NA7.6.2.2
controls in sample.
Occupied Control Zone Test. Simulate an
1
No Entry
occupied condition in the control zone controlled
NA7.6.2.4(a)
by the occupant sensor.
1.1
Yes
Immediately upon occupancy of the control zone,
NA7.6.2.4(a)1
❑ No
the occupant sensors turn on controlled lighting.
Enter the illuminance value in footcandles (fc)
measured at a location in the control zone where
the controlled lighting is at full light output or
designed light output if it has been documented
that dimming luminaires have been intentionally
1.2
Enter Value
tuned to less than full output and the design
NA7.6.2.4(a)2
illuminance levels are provided.
Informational note: Automatic daylighting controls
may need to be temporarily overridden to achieve
full or designed light output for the test.
1.3
❑ Yes
Signal sensitivity is adequate to achieve desired
NA7.6.2.4(a)3
❑ No
control.
1.4
❑ Yes
❑No
Status indicator or annunciator operates properly.
NA7.6.2.4(a)4
§110.9b4C
�,
QrUprnlBhdwu.Koo lghting Page 5 of 9 January 1, 2023
C, L&TP GONnIS arammp Program
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Code
Step
Entry
Functional Test
Reference
Unoccupied Control Zone Test. Simulate an
unoccupied condition in the control zone
2
No Entry
controlled by the occupant sensor. Confirm that at
NA7.6.2.4(b)
least one other control zone within the office
space is occupied.
The occupant sensor uniformly reduces light
NA7.6.2.4(b)1
2.1
❑ Yes
output of the controlled lighting in 20 minutes or
§130.1(c)6Dii
❑ No
less from the start of the unoccupied condition in
§160.5(b)4CvibII
the control zone.
Enter the illuminance value during unoccupancy in
2.2
Enter Value
footcandles (fc) measured at the same location as
NA7.6.2.4(b)2
in Step 1.2.
Calculate the ratio of the illuminance during
2.3
NaN
unoccupancy to the illuminance at full or designed
NA7.6.2.4(b)2
light output in %. ([Step 2.2 / Step 1.2] x 100
2.4
❑ Yes
The ratio of illuminance from Step 2.3 is no more
NA7.6.2.4(b)2
§130.1(c)6Dii
❑ No
than 20%.
§160.5 b 4CvibII
The occupant sensing control does not trigger a
false on from movement outside of the control
zone or from HVAC operation.
❑ Yes
Informational note: The field of view of occupant
2.5
❑ No
sensors in the adjacent control zones in office
NA7.6.2.4(b)3
spaces larger than 250 square feet may overlap,
but the field of view should stay away from an
adjacent enclosed space that is not part of the
office space, like conference rooms, and private
offices.
2.6
❑ Yes
Signal sensitivity is adequate to achieve desired
NA7.6.2.4(b)4
❑ No
control.
Control Zone Size Test. Follow the procedures
3
No Entry
described in either Method 1 (Steps 3.1 — 3.1.3)
NA7.6.2.4(c)
OR Method 2 (Steps 3.2 — 3.2.4
`� TP CaFbrm�`"I" Page 6 of 9 January 1, 2023
cALCmtrn. halting Pr rm
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Code
Step
Entry
Functional Test
Reference
Method 1: Simulate an unoccupied condition in
the control zone controlled by the occupant
sensor while standing in an adjacent control zone.
Determine the "edge" of the control zone
controlled by the occupant sensor by moving
toward the occupant sensor until the lights
3.1
No Entry
controlled by the occupant sensor turn on to
NA7.6.2.4(c)
simulate an occupied condition for that control
Method 1
zone.
Informational note: While moving toward the
occupant sensor, making additional movements,
motions, or sounds may be necessary to trigger
the occupant sensor.
Enter the distance in feet (ft) measured from the
3.1.1
"edge" of the control zone to the spot that is
NA7.6.2.4(c)
directly below the occupant sensor. This is the
Method 1
radius of the control zone.
3.1.2
Calculate the area (in ftz) of the control zone by
NA7.6.2.4(c)
using the formula: Area = 3.14*radius2.
Method 1
NA7.6.2.4(c)
3.1.3
❑ Yes
The area of the control zone (Step 3.1.2) is less
Method 1
❑ No
than or equal to 600 square feet.
§130.1(c)6Di
§160.5 b 4CvibI
3.2
No Entry
Method 2: Simulate an unoccupied condition for
NA7.6.2.4(c)
the entire offices ace.
Method 2
Walk through the space and count the number of
NA7.6.2.4(c)
3.2.1
zones of lighting that turn on automatically. Enter
Method 2
the number of zones that turn on automatically.
Enter the area of the office space (in ftz) from
construction plans or from other information
NA7.6.2.4(c)2
3.2.2
source such as construction documents or
Method 2
Nonresidential Certificates of Compliance
N RCCs .
Divide the area of the office by the number of
NA7.6.2.4(c)3
3.2.3
NaN
zones. Enter the value in square feet. This
Method 2
calculated value is the assessed control zone size.
NA7.6.2.4(c)4
3.2.4
❑ Yes
The area of the control zone is less than or equal
Method 2
❑ No
to 600 square feet.
§130.1(c)6Di
160.5 b 4CvibI
corlrprnl0Adv�ooUghting Page 7 of 9 January 1, 2023
cAL&TP Gas= lfalmng Program
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Step
Entry
Functional Test
Code
Reference
Unoccupied Office Test. Simulate an
unoccupied condition in all control zones
NA7.6.2.4(d)
❑Yes
controlled by all occupant sensors in the office.
§130.1(c)6Diii§1
4
❑ No
In 20 minutes or less from the start of the
60.5(b)4CvibIII
unoccupied condition of the entire office, all
controlled lighting in the office is turned off.
N/A
0 Pass
❑ Fail
Functional Testing Compliance.
N/A
`' TP CardoCaxrnislalnog axKed MIng Page 8 of 9 January 1, 2023
STATE OF CALIFORNIA SHUT-OFF LIGHTING CONTROL 2022-CEC-NRCA-LTI-02-A
Declaration Statement
Signatory
Document Author
07/26/2023
I assert that this Certificate of Acceptance documentation is accurate and complete.
Sign Here:
Field Technician
Jeff Bernardino, Integrated Power &
I certify the following under penalty of perjury, under the laws of the State of California:
Lighting, Inc. , TC-A813601 ,ATT/RP,
(951)270-0575
The information provided on this Certificate of Acceptance is true and correct. I am the person who
performed the acceptance verification reported on this Certificate of Acceptance (Field Technician). The
construction or installation identified on this Certificate of Acceptance complies with the applicable
acceptance requirements indicated in the plans and specifications approved by the enforcement agency,
Sign Below:
and conforms to the applicable acceptance requirements and procedures specified in Reference
J
Nonresidential Appendix NA7. I have confirmed that the Certificate(s) of Installation for the construction or
installation identified on this Certificate of Acceptance has been completed and signed by the responsible
Select Date 07/26/2023
builder/installer and has been posted or made available with the building permit(s) issued for the building.
Signed:
Responsible Person
Jeff Bernardino, Integrated Power &
I certify the following under penalty of perjury, under the laws of the State of California:
Lighting Inc, 993105, ATT/RP, (951)
270-0575
I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and
I have reviewed the information provided on this Certificate of Acceptance. I am eligible under Division 3
of the Business and Professions Code in the applicable classification to accept responsibility for the system
design, construction or installation of features, materials, components, or manufactured devices for the
scope of work identified on this Certificate of Acceptance and attest to the declarations in this statement
(responsible acceptance person). The information provided on this Certificate of Acceptance substantiates
that the construction or installation identified on this Certificate of Acceptance complies with the
acceptance requirements indicated in the plans and specifications approved by the enforcement agency,
Sign Below:
and conforms to the applicable acceptance requirements and procedures specified in Reference
Nonresidential Appendix NA7. I have confirmed that the Certificate(s) of Installation for the construction
or installation identified on this Certificate of Acceptance has been completed and is posted or made
available with the building permit(s) issued for the building. I will ensure that a completed, signed copy of
this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the
Select Date
building, and made available to the enforcement agency for all applicable inspections. I understand that a
Signed: 07/26/2023
signed copy of this Certificate of Acceptance is required to be included with the documentation the builder
provides to the building owner at occupancy.
C
cAL % TP D �Islralning gProgramPage 3 of 3 January 1, 2023
STATE OF CALIFORNIA
Indoor Lighting
CALIFORNIA ENERGY COMMISSION
CERTIFICATEINSTALLATION NRCI-LTI-01-E
This Certificate of Installation documents the installation of indoor lighting features, materials, components, and manufactured devices required to demonstrate compliance with Title
24, Part 6 per 10.103(a)3 for low-rise residential and low-rise mixed -use occupancies.
Project Name: Salon Centric TI
Report Page: (Page 1 of 7)
Project Address:
Date Prepared: 2023-07-26T13:33:51-04:00
A. GENERAL INFORMATION
01
Project Location (city)
La Quinta
04
Authority Having Jurisdiction
City of La Quinta
02
Zip Code
92253
05
Building Permit #
BCOM2022-0060
03
Date of Permit Set used for construction
2023-04-17
06
Date of As -built Set
2023-05-04
B. INSTALLER SCOPE
This table indicates the construction systems and materials documented on this Certificate of Installation.
01
02
03
Luminaires
Space Types
Controls'
El
General Lighting
®
Conditioned
❑
Time -switch
®
Occupant Sensors
®
Dimmers
❑
Daylighting
❑
Interlocked Systems
®
Shut-off
El
Decorative/ Accent
El
Unconditioned
Area Controls
El
Demand Response
El®
Video Conferencing Studio
Controls
®
Multi -Level
❑
Institutional Tuning
FOTNOTES: If an Energy Managment Control System (EMCS) or Lighting Contol System is installed to function as another type of lighting control, the type oflighting controlfor which
nctions is indicated. Example: if the EMCS is acting as a time -switch control, "Time -switch" is checked here.
C. COMPLIANCE RESULTS
This table indicates whether the as -built conditions documented in this form are equal or better than what was documented on the permitted Certificate of Compliance. If the
installation is not equal or better, Section 10-103(a)28 requires the Certificate of Compliance form to be revised accordingly to demonstrate compliance.
01
INSTALLED FEATURES EXACTLY MATCH DESIGN ON PERMITTED CERTIFICATE OF COMPLIANCE
Documented as -built conditions should be verified by inspector from Authority Having Jurisdiction to comply.
Registration Number:
Generated Date/Time:
Documentation Software: Energy Code Ace
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Compliance ID: 83253-0123-0006
Schema Version: rev 20220901 Report Generated: 2023-07-26 10:33:55
STATE OF CALIFORNIA
Indoor Lighting
CALIFORNIA ENERGY COMMISSION
CERTIFICATEINSTALLATION NRCI-LTI-01-E
Project Name: Salon Centric TI
Report Page: (Page 2 of 7)
Date Prepared: 2023-07-26T13:33:51-04:00
D. EXCEPTIONAL CONDITIONS
This table is auto filled with uneditable comments because of field conditions noted by the installer that may impact requirements documented on the Certificate of Compliance.
A luminaire was selected as Not in Scope in the Indoor Lighting Fixture Schedule Table. Please ensure that this luminaire was claimed as in scope on anoher another Certificate of
Installation CI-LTI Indoor Lighting form
Selections made in CA Certificate Table have been changed by the permit applicant. See Table E. Additional Remarks for permit applicant's explanation.
E. INSTALLER NOTES
This table includes remarks made by the installer to the Authority Having Jurisdiction.
{NRCA-LTI-03-A Explanation} Not Required < 120 Watts in zone
F. INSTALLATION DETAILS
The following tables indicate performance requirements as documented on the permitted Certificate of Compliance for all systems and components included in Table B. Installer Scope.
Also included are the as -built conditions documented by the installer/documentation author.
Registration Number:
Generated Date/Time:
Documentation Software: Energy Code Ace
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Compliance ID: 83253-0123-0006
Schema Version: rev 20220901 Report Generated: 2023-07-26 10:33:55
STATE OF CALIFORNIA
Indoor Lighting
CALIFORNIA ENERGY COMMISSION
CERTIFICATEINSTALLATION NRCI-LTI-01-E
Project Name: Salon Centric TI
Report Page: (Page 3 of 7)
Date Prepared: 2023-07-26T13:33:51-04:00
Indoor Lighting Controls
01
02
03
04
05
06
07
08
09
10
Primary
Demand
Manual Area
Multi -Level
Shut -Off
Primary/Skylit
Secondary
Interlocked
Area Description
Controls compliance
Function Area
Response
Controls
Controls
Controls
Daylighting
Daylighting
Systems
NA < 4,000W
Per C of C
subject to
Annunciated
NA: Restrooms
Occupancy
p y
NA: Not dya lit
NA: Not dya lit
No
INSTALLED FEATURES
multilevel
Sensor
zone
zone
EXACTLY MATCH
RESTROOM
Restroom
DESIGN ON PERMITTED
CERTIFICATE OF
As -built
NA < 4,000W
Occupancy
NA: Not daylit
NA: Not daylit
Conditions
subject to
Annunciated
NA: Restrooms
Sensor
zone
zone
No
COMPLIANCE
multilevel
NA < 4,000W
Per C of C
subject to
Annunciated
NA: Enclosed
Occupancy
p Y
NA: Not da lit
Y
NA: Not da lit
Y
No
INSTALLED FEATURES
Commercial
multilevel
area <100SF
Sensor
zone
zone
EXACTLY MATCH
BACK STOCK
Industrial
Storage Area
DESIGN ON PERMITTED
CERTIFICATE OF
As -built
NA < 4OOOW
NA: Enclosed
Occupancy
NA: Not daylit
NA: Not daylit
Conditions
subject to
Annunciated
area <100SF
Sensor
zone
zone
No
COMPLIANCE
multilevel
NA < 4,000W
Per C of C
subject to
Annunciated
NA: Enclosed
Occupancy
p y
NA: Not dya lit
NA: Not dya lit
No
INSTALLED FEATURES
OFFICE
Office (<-250
square feet
q
multilevel
area <100SF
Sensor
zone
zone
EXACTLY MATCH
DESIGN ON PERMITTED
NA < 4,000W
As -built
NA: Enclosed
Occupancy
NA: Not daylit
NA: Not daylit
CERTIFICATE OF
Conditions
subject to
Annunciated
area <100SF
Sensor
zone
zone
No
COMPLIANCE
multilevel
NA < 4,000W
Per C of C
subject to
Annunciated
NA: Enclosed
Occupancy
p y
NA: Not dya lit
NA: Not dya lit
No
INSTALLED FEATURES
multilevel
area <100SF
Sensor
zone
zone
EXACTLY MATCH
HALL
Corridor
DESIGN ON PERMITTED
CERTIFICATE OF
As -built
NA < 4 OOOW
NA: Enclosed
Occupancy
NA: Not daylit
NA: Not daylit
Conditions
subject to
Annunciated
area <100SF
Sensor
zone
zone
No
COMPLIANCE
multilevel
Registration Number:
Generated Date/Time:
Documentation Software: Energy Code Ace
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Compliance ID: 83253-0123-0006
Schema Version: rev 20220901 Report Generated: 2023-07-26 10:33:55
STATE OF CALIFORNIA
Indoor Lighting
CALIFORNIA ENERGY COMMISSION
CERTIFICATEINSTALLATION NRCI-LTI-01-E
Project Name: Salon Centric TI
Report Page: (Page 4 of 7)
Date Prepared: 2023-07-26T13:33:51-04:00
Indoor Lighting Controls
NA < 4,000W
Per C of C
subject to
Annunciated
Dimmer
Occupancy
Included
Included
No
INSTALLED FEATURES
multilevel
Sensor
EQUAL OR BETTER
BACK ROOM
Lounge
THAN PERMITTED
As -built
NA < 4 OOOW
Occupancy
NA: General Ltg
NA: General Ltg
CERTIFICATE OF
Conditions
subject to
Annunciated
Dimmer
Sensor
< 120W
< 120W
No
COMPLIANCE
multilevel
NA < 4,000W
NA: Enclosed
Occupancy
p Y
NA: Not daylit
Y
NA: Not daylit
Y
INSTALLED FEATURES
Per C of C
Electrical
subject to
Annunciated
No
DATA
Mechancial
Telephone
multilevel
area <100SF
Sensor
zone
zone
EXACTLY MATCH
DESIGN ON PERMITTED
NA < 4,000W
As -built
Room
NA: Enclosed
Occupancy
NA: Not daylit
NA: Not daylit
CERTIFICATE OF
Conditions
subject to
Annunciated
area <100SF
Sensor
zone
zone
No
COMPLIANCE
multilevel
NA < 4,000W
Per C of C
subject to
Annunciated
NA: <= 80 % LP
Occupancy
p Y
NA: <= 80 % LP
NA: <= 80 % LP
No
INSTALLED FEATURES
multilevel
(alt only)
Sensor
(alt only)
(alt only)
EXACTLY MATCH
RETAIL SPACE
Grocery Sales
DESIGN ON PERMITTED
CERTIFICATE OF
As -built
NA < 4 OOOW
NA: <= 80 % LP
Occupancy
NA: <= 80 % LP
NA: <= 80 % LP
Conditions
subject to
Annunciated
(alt only)
Sensor
(alt only)
(alt only)
No
COMPLIANCE
multilevel
NA < 4,000W
NA: General Ltg
Occupancy
NA: Not daylit
NA: Not daylit
INSTALLED FEATURES
Per C of C
subject to
Annunciated
<_ 0.5W/SF
Sensor
zone
zone
No
EXACTLY MATCH
CASHIER
All Other Space
Types
multilevel
DESIGN ON PERMITTED
CERTIFICATE OF
As -built
NA < 4,000W
NA: General Ltg
Occupancy
NA: Not daylit
NA: Not daylit
Conditions
subject to
Annunciated
<= 0.5W/SF
Sensor
zone
zone
No
COMPLIANCE
multilevel
Registration Number:
Generated Date/Time:
Documentation Software: Energy Code Ace
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Compliance ID: 83253-0123-0006
Schema Version: rev 20220901 Report Generated: 2023-07-26 10:33:55
STATE OF CALIFORNIA
Indoor Lighting
CALIFORNIA ENERGY COMMISSION
CERTIFICATEINSTALLATION NRCI-LTI-01-E
Project Name: Salon Centric TI
Report Page: (Page 5 of 7)
Date Prepared: 2023-07-26T13:33:51-04:00
Lighting Controls Functionality
Functionality listed for all lighting control systems must be installed and programmed
Dimmers
Installed controls that provide dimmer functionality:
A. Are capable of reducing lighting power consumption be a minimum of 65% when at its lowest setting;
B. ; Provide reduced flicker operation, meaning that directly controlled light sources shall be provided electrical power such that the light output has an amplitude modulation of
less than 30% for frequencies less than 200 Hz without causing premature lamp failure;
C. Provide an off setting that produces a zero lumen output;
D. For wall box dimmers and associated switches designed for use in three way circuit, be capable of turning lights off, and on to the level set by the dimmer if the lights are off;
E. Indicator lights integral to lighting controls shall consume no more than one watt of per indicator light.
Occupant Sensing Controls
Installed occupant sensing controls include occupant sensors, motion sensors, and vacancy sensors, including those with a Partial -ON or Partial -OFF function:
A. Are capable of automatically turning the controlled lights in the area either off or down no more than 20 minutes after the area has been vacated;
B. ; For manual -on controls, have a grace period of no less than 15 seconds and no more than 30 seconds to turn on lighting automatically after the sensor has timed out;
C. Provide a visible status signal that indicates that the device is operating properly, or that it has failed or malfunctioned. The visible status may have an override that turns off the
signal.
D. Indicator lights integral to lighting controls shall consume no more than one watt of per indicator light.
E. NOTE: Occupant Sensing Control systems may consist of a combination of single or multilevel Occupant, Motion, or Vacancy Sensor Controls, provided that components installed
to comply with manual -on requirements shall not be capable of conversion by occupants from manual -on to automatic -on functionality.
F. Sensors that are used by occupant sensing controls to detect occupants shall meet all of the following requirements:
i. Shall not incorporate switches or mechanical devices that allow the sensor to be disabled without changing the settings of the control.
ii. Sensors that utilize ultrasonic radiation for detection of occupants shall comply with 21 C.F.R. part 1002.12, not emit audible sound and not emit ultrasound in excess of
the decibel levels shown in Table 110.9-A measured no more than five feet from the source, on axis.
iii. Sensors that utilize microwave radiation for detection of occupants shall comply with 47 C.F.R. parts 2 and 15 and not emit radiation in excess of 1 milliwatt per square
centimeter measured at no more than 5 centimeters from the emission surface of the device.
Registration Number:
Generated Date/Time:
Documentation Software: Energy Code Ace
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Compliance ID: 83253-0123-0006
Schema Version: rev 20220901 Report Generated: 2023-07-26 10:33:55
STATE OF CALIFORNIA
Indoor Lighting
CALIFORNIA ENERGY COMMISSION
CERTIFICATEINSTALLATION NRCI-LTI-01-E
Project Name: Salon Centric TI
Report Page: (Page 6 of 7)
Date Prepared: 2023-07-26T13:33:51-04:00
Lighting Controls Functionality
Functionality listed for all lighting control systems must be installed and programmed
TABLE 110.9-A - ULTRASOUND MAXIMUM DECIBEL VALUES
Mid -frequency of Sound Pressure
Third -Octave Band (in kHz)
Third -Octave Band (in dB reference 20
micropascals)
Less than 20
80
20 or more to less than 25
105
25 or more to less than 31.5
110
31.5 or more
31.5 or more
G. ACCEPTANCE TESTS & FIELD VERIFICATION
The following Acceptance Tests related to the systems or materials documented on this NRCI have been indicated on the permitted Certificate of Compliance (NRCC) as being required to
comply with Title 24, Part 6.
Form/Title
Systems To Be Field Verified
Certificates of Acceptance
Lighting Acceptance Tests must be completed by a certified Acceptance Testing Technician and NRCA forms completed through an approved Acceptance Test Technician Certification
Provider database. The Certificate of Acceptance (NRCA) forms indicated below will be required by the Authority Having Jurisdiction to demonstrate compliance.
NRCA-LTI-02-A - Must be submitted for all new, added or altered shut-off lighting controls
RESTROOM; BACK STOCK; OFFICE;
HALL; BACK ROOM; DATA; RETAIL
SPACE; CASHIER
NRCA-LTI-03-A - Must be submitted for all new, added or altered automatic daylight controls.
NRCA-LTI-04-A -Must be submitted for all new, added or altered demand responsive lighting controls.
NRCA-LTI-05-A. - Must be submitted for Institutional Tuning Power Adjustment Factor (PAF)
A copy of this Certificate of Installation should be distributed to the certified Acceptance Test Technician(s) who will perform the acceptance test(s). Title 24, Part 6 Section
10-103(a)3F also requires this Certificate of Installation be posted or made available to the Authority Having Jurisdiction for all applicable inspections.
Registration Number:
Generated Date/Time:
Documentation Software: Energy Code Ace
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Compliance ID: 83253-0123-0006
Schema Version: rev 20220901 Report Generated: 2023-07-26 10:33:55
STATE OF CALIFORNIA
Indoor Lighting
CALIFORNIA ENERGY COMMISSION
CERTIFICATEINSTALLATION NRCI-LTI-01-E
Project Name: Salon Centric TI
Report Page: (Page 7 of 7)
Project Address:
IDate Prepared: 2023-07-26T13:33:51-04:00
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Documentation Author Signature:
Jeff Bernardino
Company:
Signature Date:
Integrated Power & Lighting, Inc.
Address:
CEA/ HERS Certification Identification (if applicable):
City/State/Zip:
Phone:
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. 1 am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction, or installation of features, materials, components, or
manufactured devices for the scope of work identified on this Certificate of Installation and attest to the declarations in this statement (responsible builder/installar), otherwise I am an authorized representative of the
responsible builder/installer.
3. The constructed or installed features, materials, components or manufactured devices (the installation) identified on this Certificate of Installation conforms to all applicable codes and regulations, and the installation
conforms to the requirements given on the plans and specifications approved by the enforcement agency.
4. 1 reviewed a copy of the Certificate of Compliance approved by the enforcement agency that identifies the specific requirements for the scope of constructions or installation identified on this Certificate of Installation,
and I have ensured that the requirements that apply to the construction or installation have been met.
5. 1 will ensure that a completed signed copy of this Certificate of Installation shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all
applicable inspections. I understand that a completed signed copy of this Certificate of Installation is required to be included with the documentation the builder provides to the building owner at occupancy.
Responsible Builder/Installer Name:
Responsible Builder/Installer Signature:
Company Name: (Installing Subcontractor or General Contractor Builder/Owner)
Position With Company (Title):
Address:
CSLB License:
City/State/Zip:
Phone:
Date Signed:
12023-07-26
Registration Number:
Generated Date/Time:
Documentation Software: Energy Code Ace
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Compliance ID: 83253-0123-0006
Schema Version: rev 20220901 Report Generated: 2023-07-26 10:33:55
es1'. zax�
DEN & BURROW
LLC.
Project: Salon Centric, BCOM2022-0060
By Alec Calzada
PATH OF TRAVEL UPGRADE DETERMINATION
In accordance with the 2019 California Building Code (CBC) Section 1113-202.4, exception 8, the cost of compliance with
Section 1113-202.4 is allowed to be limited to 20% of the adjusted construction cost of the alterations, structural repairs
or additions when the adjusted construction cost does not exceed the current valuation threshold.
Construction cost for proposed project (not including costs of improvements to the path of travel to the area of
alteration): $ 80,000 (A)
Cost of alterations to areas on this path of travel undertaken during the preceding three-year period which did not
provide an accessible path of travel to the area of alteration (as applicable): $ 0 (B)
Adjusted construction cost (C) = (A) + (B) $ 80,000 (C)
PATH OF TRAVEL CONSTRUCTION COSTS:
Elements serving the area of alteration
Is element in
If not, will element be
Proposed cost of
based on priority
compliance with
upgraded to current
compliance with
current Chapter
Chapter 1113? (Y/N)
current
1113?(Y/N)
Chapter11B
1. An accessible entrance
Y
$
2. An accessible route (interior and
$
exterior) to the
Y
altered area
3. At least one accessible restroom for
$
each gender or a single accessible unisex,
N
Y
15,000
single user or family restroom
4. Accessible public telephones
N/A
$
5. Accessible drinking fountains
N/A
$
6. When possible, additional accessible
elements such as:
a. Parking
N/A
$
b.Storage
N/A
$
c. Signs
N/A
$
d. Alarms
N/A
$
e. Other
$
Total cost of providing compliant path of
$ 15,000 (D)
travel elements:
COST OF PATH OF TRAVEL UPGRADES AS PERCENTAGE OF ADJUSTED CONSTRUCTION COST:
Compliance of path of travel upgrades as % of adjusted construction cost: (E)% =
18.75 % (E)
(D) / (C)
Note: This may not be less than 20%
CAL FIRE - RIVERSIDE UNIT
RIVERSIDE COUNTY FIRE DEPARTMENT
OFFICE OF THE FIRE MARSHAL — LA QUINTA c,,LIFoRMA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
March 22, 2023
David Solomon
11331 E 183rd Street #367
Cerritos, CA 90703
Re: Tenant Improvement Construction - Fire Plan Review — SALON CENTRIC
BCOM2022-0060 / 46480 WASHINGTON STREET #3, LA QUINTA, CA 92253
The building plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
Fire Department approval is based upon the 2022 CBC requirements for M occupancies. It is prohibited to
use, process or store any materials in the occupancy that would classify it as a Group H occupancy, without
further review and approval.
DEFERRED SUBMITTALS REQUIRED
1) FIRE SPRINKLER SYSTEM - Tenant Improvement plans must be submitted and reference the
installing contractor performing the work. Permit fees will be required.
PRIOR TO FINAL
1) Minimum 6" tall suite addressing shall be provided to both the front and rear entrances. All addressing
must be legible and of a contrasting color with the background to be visible from the street at all hours.
2) Provide keys to the tenant space (all tenants), utility rooms and elevator services for inclusion in the
main building Knox Box. Key(s) shall have durable and legible tags affixed for identification of the
correlating tenant space.
3) Install portable fire extinguishers per Title 19, but not less than 2AIOBC in rating. Contact a certified
extinguisher company for proper placement and spacing of equipment.
4) A durable sign stating: "THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE IS
OCCUPIED" shall be placed on or adjacent to the front exit doors. The sign shall be in letters not less
than one inch high on a contrasting background (A <300, B, F, M and S).
5) Illuminated Exit Signage and Egress Illumination placement and functional test will be witnessed by
OFM Fire Inspector at time of final inspection.
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
IqIIIIIiiiIj!!!!!
E5T. ;oa[
DEN & BURROW
LLC.
Project: Salon Centric, BCOM2022-0060
46480 Washington St.
La Quinta, CA
Field Change Letter
08/17/2023
By Alec Calzada
DESCRIPTION:
After review of the existing HVAC equipment and system installed at the subject project location it has
been determined that it is unnecessary to replace or upgrade the existing HVAC system.
Therefore, the declarations of acceptance noted under section "O" within the MCH Report on sheet
T24.2 are not required for this project.
Please contact me for any questions or concerns.
1 , 7
Alec Calzada�
alec@denandburrow.com 1 (909)754-0209 1 denandburrow.com Page 1 of 1
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
Gmail George Fancher <george@paimconstructiongrp.com>
RE: URGENTM Building TI final Conditions of Approval
Rojas, Leilani@CALFIRE <Leilani.Rojas@fire.ca.gov> Tue, Aug 29, 2023 at 6:14 AM
To: George Fancher <george@palmconstructiongrp.com>
Cc: HUHN Jeff <JHuhn@saloncentric.com>, andrew lujan <andrew@palmconstructiongrp.com>, Daniel Moreno
<daniel@palmconstructiongrp.com>
George,
Looks good, you are all clear to open.
Thanks,
Leilani Rojas
Fire Systems Inspector / Office of the Fire Marshal
Cal Fire/Riverside County Fire Department
City of La Quinta
Desk: 760-777-7158 1 Mobile: 760-218-8125
Inspection Hotline: 760-777-7131
78495 Calle Tampico, La Quinta, CA 92253
leilani.rojas@fire.ca.gov I www.rvcfire.org
Sch: Tues-Fri
Leadership, Competence, Integrity, Safety, Customer Service
The Office of the County Fire Marshal is committed to facilitating fire and life safety solutions by empowering its
employees to serve our community through innovation and partnership.
From: George Fancher <george@palmconstructiongrp.com>
Sent: Monday, August 28, 2023 3:34 PM
To: Rojas, Leilani@CALFIRE <Leilani.Rojas@fire.ca.gov>
Cc: HUHN Jeff <JHuhn@saloncentric.com>; andrew lujan <andrew@pal mconstructiongrp.com>; Daniel Moreno
<daniel@palmconstructiongrp.com>
Subject: Fwd: URGENT!!! Building TI final Conditions of Approval
Warning: this message is from an external user and should be treated with caution.
Hello Leilani,
Please see the passing Fire Alarm Inspection report attached.
Best regards,
George Fancher
Project Manager
Palm Construction Group
949.507.7901
George@PalmConstructionGrp.com
Pal mConstructionGrp.com
---------- Forwarded message ---------
From: Martha Inga <marthainga@jacktarrdc.com>
Date: Mon, Aug 28, 2023 at 3:29 PM
Subject: URGENT!!! Building TI final Conditions of Approval
To: HUHN Jeff <JHuhn@saloncentric.com>, George Fancher<george@palmconstructiongrp.com>
Jeff:
We finally obtained the inspection report attached hereto for your perusal.
Thank you,
Martha Inga
Assistant to Jack Tarr
Washington 111, Ltd.
30240 Rancho Viejo Road, Suite B
San Juan Capistrano, CA 92675
(949) 443-1234 Ext. 131
(714) 609-2500 Cell
(949) 443-1233 Fax
marthainga@iacktarrdc.com
From: Service <service@comtronl.com>
Sent: Monday, August 28, 2023 3:04 PM
To: Martha Inga <marthainga@jacktarrdc.com>
Subject: RE: URGENT!!! Building TI final Conditions of Approval
Here it is thank you.
From: Martha Inga[maiIto: marthainga@jacktarrdc.com]
Sent: Monday, August 28, 2023 2:56 PM
To: Service
Subject: RE: URGENT!!! Building TI final Conditions of Approval
Brandi:
We are still waiting for the report.
Thank you,
Martha Inga
Assistant to Jack Tarr
Washington 111, Ltd.
30240 Rancho Viejo Road, Suite B
San Juan Capistrano, CA 92675
(949) 443-1234 Ext. 131
(714) 609-2500 Cell
(949) 443-1233 Fax
marthainga@iacktarrdc.com