Project Name:Nonresidential Building NRCC-PRF-01-E Page 1 of 19
Project Address:46-630 Washinton Street La Quinta 92253 Calculation Date/Time:10:01, Thu, Oct 18, 2018
Compliance Scope:NewComplete Input File Name:Washington Park (Retail).cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-09132018-5583 Report Generated at: 2018-10-18 10:02:00
A. PROJECT GENERAL INFORMATION
1.Project Location (city)La Quinta 8.Standards Version Compliance2016
2.CA Zip Code 92253 9.Compliance Software (version)EnergyPro 7.2
3.Climate Zone 15 10.Weather File PALM-SPRINGS-INTL_722868_CZ2010.epw
4.Total Conditioned Floor Area in Scope 11,654 ft2 11.Building Orientation (deg)(W) 270 deg
5.Total Unconditioned Floor Area 0 ft2 12.Permitted Scope of Work NewComplete
6.Total # of Stories (Habitable Above Grade)1 13 Building Type(s)Nonresidential
7.Total # of dwelling units 0 14 Gas Type NaturalGas
B. COMPLIANCE RESULTS FOR PERFORMANCE COMPONENTS (Annual TDV Energy Use, kBtu/ft 2-yr)§ 140.1
BUILDING COMPLIES
1. Energy Component 2. Standard Design (TDV)3. Proposed Design (TDV)4. Compliance Margin (TDV)5. Percent Better than Standard
Space Heating 2.09 1.01 1.08 51.7%
Space Cooling 132.29 113.22 19.07 14.4%
Indoor Fans 28.26 36.25 -7.99 -28.3%
Heat Rejection --------
Pumps & Misc.0.13 --0.13 --
Domestic Hot Water 5.86 3.13 2.73 46.6%
Indoor Lighting 101.54 101.54 --0.0%
COMPLIANCE TOTAL 270.17 255.15 15.02 5.6%
Receptacle 89.23 89.23 0.0 0.0%
Process --------
Other Ltg --------
Process Motors --------
TOTAL 359.40 344.38 15.0 4.2%
Project Name:Nonresidential Building NRCC-PRF-01-E Page 2 of 19
Project Address:46-630 Washinton Street La Quinta 92253 Calculation Date/Time:10:01, Thu, Oct 18, 2018
Compliance Scope:NewComplete Input File Name:Washington Park (Retail).cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-09132018-5583 Report Generated at: 2018-10-18 10:02:00
C. PRIORITY PLAN CHECK/ INSPECTION ITEMS (in order of highest to lowest TDV energy savings)
1st Space Cooling: Check envelope and mechanical Compliance Margin By Energy Component (from Table B column 4)
Space Cooling
Domestic Hot Water
Space Heating
Pumps & Misc.
Heat Rejection
Indoor Lighting
Indoor Fans
Penalty Energy Credit
2nd Domestic Hot Water: Check mechanical
3rd Space Heating: Check envelope and mechanical
4th Pumps & Misc.: Check mechanical
5th Heat Rejection: Check envelope and mechanical
6th Indoor Lighting: Check lighting
7th Indoor Fans: Check envelope and mechanical
D. EXCEPTIONAL CONDITIONS
The aged solar reflectance and aged thermal emittance must be listed in the Cool Roof Rating Council database of certified products. For projects where initial reflectance is used, the initial
reflectance must be listed, and the aged reflectance is calculated by the software program and used in the compliance model.
This project uses the Simplified Geometry Performance Modeling Approach which is not capable of modeling daylighting controls and assumes the prescriptive Secondary Daylit Control
requirements are met. PRESCRIPTIVE COMPLIANCE documentation (form NRCC-LTI-02-E) for the requirements of section 140.6(d) Automatic Daylighting Controls in Secondary Daylit Zones is
required.
This project includes Domestic Hot Water in the analysis. Please verify that Domestic Hot Water is included in the design for the permitted scope of work.
E. HERS VERIFICATION
This Section Does Not Apply
F. ADDITIONAL REMARKS
None Provided
Project Name:Nonresidential Building NRCC-PRF-01-E Page 3 of 19
Project Address:46-630 Washinton Street La Quinta 92253 Calculation Date/Time:10:01, Thu, Oct 18, 2018
Compliance Scope:NewComplete Input File Name:Washington Park (Retail).cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-09132018-5583 Report Generated at: 2018-10-18 10:02:00
G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY
Identify which building components use the performance or prescriptive path for compliance. “NA”= not in project
For components that utilize the performance path, indicate the sheet number that includes mandatory notes on plans.
Building Component Compliance Path Compliance Forms (required for submittal)Location of Mandatory Notes on
Plans
Envelope
Performance NRCC-PRF-ENV-DETAILS (section of the NRCC-PRF-01-E)
Prescriptive NRCC-ENV-01 / 02 / 03 / 04 / 05 / 06-E
NA
Mechanical
Performance NRCC-PRF-MCH-DETAILS (section of the NRCC-PRF-01-E)
Prescriptive NRCC-MCH-01 / 02 / 03 / 04 / 05 / 06 / 07-E
NA
Domestic Hot Water
Performance NRCC-PRF-PLB-DETAILS (section of the NRCC-PRF-01-E)
Prescriptive NRCC-PLB-01-E
NA
Lighting (Indoor Conditioned)
Performance NRCC-PRF-LTI-DETAILS (section of the NRCC-PRF-01-E)
Prescriptive NRCC-LTI-01 / 02 / 03 / 04 / 05-E
NA
Covered Process:
Commercial Kitchens
Performance S2 (section of the NRCC-PRF-01-E)
Prescriptive NRCC-PRC-01/ 03-E
NA
Covered Process:
Computer Rooms
Performance S3 (section of the NRCC-PRF-01-E)
Prescriptive NRCC-PRC-01/ 04-E
NA
Covered Process:
Laboratory Exhaust
Performance S4 (section of the NRCC-PRF-01-E)
Prescriptive NRCC-PRC-01/ 09-E
NA
Project Name:Nonresidential Building NRCC-PRF-01-E Page 4 of 19
Project Address:46-630 Washinton Street La Quinta 92253 Calculation Date/Time:10:01, Thu, Oct 18, 2018
Compliance Scope:NewComplete Input File Name:Washington Park (Retail).cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-09132018-5583 Report Generated at: 2018-10-18 10:02:00
G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY
The following building components are only eligible for prescriptive compliance. Indicate which are
relevant to the project.
The following building components may have mandatory requirements per Part 6. Indicate
which are relevant to the project.
Yes NA Prescriptive Requirement Compliance Forms Yes NA Mandatory Requirement Compliance Forms
Lighting (Indoor
Unconditioned) §140.6 NRCC-LTI-01 / 02 / 03 / 04 / 05-E
Commissioning: §120.8
Simple Systems
Complex Systems
NRCC-CXR-01 / 02 / 03 / 05-E
NRCC-CXR-01 / 02 / 04 / 05-E
Lighting (Outdoor) §140.7 NRCC-LTO-01 / 02 / 03-E Electrical: §130.5 NRCC-ELC-01-E
Lighting (Sign) §140.8 NRCC-LTS-01-E Solar Ready: §110.10 NRCC-SRA-01 / 02-E
Solar Thermal Water
Heating: §140.5 NRCC-STH-01-E
Covered Process: §120.6
Parking Garage
Commercial Refrigeration
Warehouse Refrigeration
Compressed Air
Process Boilers
NRCC-PRC-01-E
NRCC-PRC-02-E
NRCC-PRC-05-E
NRCC-PRC-06/07/08-E
NRCC-PRC-10-E
NRCC-PRC-11-E
Project Name:Nonresidential Building NRCC-PRF-01-E Page 5 of 19
Project Address:46-630 Washinton Street La Quinta 92253 Calculation Date/Time:10:01, Thu, Oct 18, 2018
Compliance Scope:NewComplete Input File Name:Washington Park (Retail).cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-09132018-5583 Report Generated at: 2018-10-18 10:02:00
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV)–
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance
(Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment.
Confirmed
Building Component Compliance Forms (required for submittal)Pass Fail
Envelope
NRCI-ENV-01-E - For all buildings
NRCA-ENV-02-F- NFRC label verification for fenestration
Mechanical
NRCI-MCH-01-E - For all buildings with Mechanical Systems
NRCA-MCH-02-A- Outdoor Air
NRCA-MCH-03-A – Constant Volume Single Zone HVAC
NRCA-MCH-04-H- Air Distribution Duct Leakage
NRCA-MCH-05-A- Air Economizer Controls
NRCA-MCH-06-A- Demand Control Ventilation
NRCA-MCH-07-A – Supply Fan Variable Flow Controls
NRCA-MCH-08-A- Valve Leakage Test
NRCA-MCH-09-A – Supply Water Temp Reset Controls
NRCA-MCH-10-A- Hydronic System Variable Flow Controls
NRCA-MCH-11-A – Auto Demand Shed Controls
NRCA-MCH-12-A- Packaged Direct Expansion Units
NRCA-MCH-13-A- Air Handling Units and Zone Terminal Units
NRCA-MCH-14-A- Distributed Energy Storage
NRCA-MCH-15-A – Thermal Energy Storage
NRCA-MCH-16-A- Supply Air Temp Reset Controls
NRCA-MCH-17-A – Condensate Water Temp Reset Controls
NRCA-MCH-18-A- Energy Management Controls Systems
NRCV-MCH-04-H- Duct Leakage Test
Project Name:Nonresidential Building NRCC-PRF-01-E Page 6 of 19
Project Address:46-630 Washinton Street La Quinta 92253 Calculation Date/Time:10:01, Thu, Oct 18, 2018
Compliance Scope:NewComplete Input File Name:Washington Park (Retail).cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-09132018-5583 Report Generated at: 2018-10-18 10:02:00
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV)–
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance
(Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment.
Confirmed
Building Component Compliance Forms (required for submittal)Pass Fail
Plumbing
NRCI-PLB-01-E - For all buildings with Plumbing Systems
NRCI-PLB-02-E - required on central systems in high‐rise residential, hotel/motel application.
NRCI-PLB-03-E - Single dwelling unit systems in high‐rise residential, hotel/motel application.
NRCI-PLB-21-E - HERS verified central systems in high‐rise residential, hotel/motel application.
NRCI-PLB-22-E - HERS verified single dwelling unit systems in high‐rise residential, hotel/motel application.
NRCV-PLB-21-H- HERS verified central systems in high‐rise residential, hotel/motel application.
NRCV-PLB-22-H - HERS verified single dwelling unit systems in high‐rise residential, hotel/motel application.
NRCI-STH-01-E - Any solar water heating
Indoor Lighting
NRCI-LTI-01-E - For all buildings
NRCI-LTI-02-E - Lighting control system, or for an Energy Management Control System (EMCS)
NRCI-LTI-03-E - Line-voltage track lighting integral current limiter, or for a supplementary overcurrent protection panel used to
energize only line-voltage track lighting
NRCI-LTI-04-E - Two interlocked systems serving an auditorium, a convention center, a conference room, or a theater
NRCI-LTI-05-E - Lighting Control Credit Power Adjustment Factor (PAF)
NRCI-LTI-06-E - Additional wattage installed in a video conferencing studio
NRCA-LTI-02-A - Occupancy sensors and automatic time switch controls.
NRCA-LTI-03-A - Automatic daylighting controls
NRCA-LTI-04-A - Demand responsive lighting controls
Outdoor Lighting
NRCI-LTO-01-E – Outdoor Lighting
NRCI-LTO-02-E- EMCS Lighting Control System
NRCA-LTO-02-A - Outdoor Lighting Control
Sign Lighting NRCI-LTS-01-E – Sign Lighting
Electrical NRCI-ELC-01-E - Electrical Power Distribution
Photovoltaic NRCI-SPV-01-E Photovoltaic Systems
Project Name:Nonresidential Building NRCC-PRF-01-E Page 7 of 19
Project Address:46-630 Washinton Street La Quinta 92253 Calculation Date/Time:10:01, Thu, Oct 18, 2018
Compliance Scope:NewComplete Input File Name:Washington Park (Retail).cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-09132018-5583 Report Generated at: 2018-10-18 10:02:00
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV)–
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance
(Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment.
Confirmed
Building Component Compliance Forms (required for submittal)Pass Fail
Covered Process
NRCI-PRC-01-E Covered Processes
NRCA-PRC-01-F- Compressed Air Systems
NRCA-PRC-02-F- Kitchen Exhaust
NRCA-PRC-03-F- Garage Exhaust
NRCA-PRC-04-F- Refrigerated Warehouse- Evaporator Fan Motor Controls
NRCA-PRC-05-F- Refrigerated Warehouse- Evaporative Condenser Controls
NRCA-PRC-06-F- Refrigerated Warehouse- Air Cooled Condenser Controls
NRCA-PRC-07F- Refrigerated Warehouse- Variable Speed Compressor
NRCA-PRC-08-F- Electrical Resistance Underslab Heating System
I. ENVELOPE GENERAL INFORMATION (See NRCC-PRF-ENV-DETAILS for more information)
1.Total Conditioned Floor Area 11,654 ft2 5.Number of Floors Above Grade 1 Confirmed
2.Total Unconditioned Floor Area 0 ft2 6.Number of Floors Below Grade 0
PassFail3.Addition Conditioned Floor Area 0 ft2
4.Addition Unconditioned Floor Area 0 ft2
7. Opaque Surfaces & Orientation 8. Total Gross Surface Area 9. Total Fenestration Area 10. Window to Wall Ratio
North Wall 980 ft2 0 ft2 00.0%
East Wall 1,270 ft2 0 ft2 00.0%
South Wall 980 ft2 0 ft2 00.0%
West Wall 1,270 ft2 400 ft2 31.5%
Total 4,500 ft2 400 ft2 08.9%
Roof 11,654 ft2 0 ft2 00.0%
Project Name:Nonresidential Building NRCC-PRF-01-E Page 8 of 19
Project Address:46-630 Washinton Street La Quinta 92253 Calculation Date/Time:10:01, Thu, Oct 18, 2018
Compliance Scope:NewComplete Input File Name:Washington Park (Retail).cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-09132018-5583 Report Generated at: 2018-10-18 10:02:00
J. FENESTRATION ASSEMBLY SUMMARY § 110.6 Confirmed
1.2.3.4.5.6.7.8.9.PassFailFenestration Assembly Name /
Tag or I.D.
Fenestration Type / Product Type
/ Frame Type Certification Method1 Assembly Method Area ft2 Overall
U-factor
Overall
SHGC
Overall
VT Status2Double Non Metal Clear
VerticalFenestration
FixedWindow
N/A
NFRC Rated SiteBuilt 400 0.36 0.25 0.50 N
1 Newly installed fenestration shall have a certified NFRC Label Certificate or use the CEC default tables found in Table 110.6-A and Table 110.6-B. Center of Glass (COG) values are for the glass-only, determined by the manufacturer, and are shown for ease
of verification. Site-built fenestration values are calculated per Nonresidential Appendix NA6 and are used in the analysis.
2 Status: N - New, A – Altered, E – Existing
Taking compliance credit for fenestration shading devices?(if "Yes", see NRCC-PRF-ENV-DETAILS for more information)No
K. OPAQUE SURFACE ASSEMBLY SUMMARY § 120.7/ § 140.3 Confirmed
1.2.3.4.5.6.7.8.PassFailSurface Name Surface Type Area (ft2)Framing
Type
Cavity
R-Value
Continuous
R-Value
U-Factor / F-Factor
/ C-Factor Status1R19 Wall6 ExteriorWall 4500 Wood 19 NA U-Factor: 0.072 N
R-30 Roof No Attic13 Roof 11654 Wood 30 NA U-Factor: 0.034 N
Slab On Grade15 UndergroundFloor 11654 NA 0 NA F-Factor: 0.730 N
R19 Wall61 InteriorWall 980 Wood 19 NA U-Factor: 0.069 N
1 Status: N - New, A – Altered, E – Existing
L. ROOFING PRODUCT SUMMARY § 140.3 Confirmed
1.2.3.4.5.6.7.PassFailProduct Type Product Density
(lb/ft2)
Aged Solar
Reflectance
Thermal
Emittance SRI Cool Roof
Credit
Roofing Product
Description
R-30 Roof No Attic13 5.813 0.63 0.85 Not Provided Yes CRRC Prod. ID: R-30 Roof
No Attic
Project Name:Nonresidential Building NRCC-PRF-01-E Page 9 of 19
Project Address:46-630 Washinton Street La Quinta 92253 Calculation Date/Time:10:01, Thu, Oct 18, 2018
Compliance Scope:NewComplete Input File Name:Washington Park (Retail).cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-09132018-5583 Report Generated at: 2018-10-18 10:02:00
M. HVAC SYSTEM SUMMARY (see NRCC-PRF-MCH-DETAILS for more information)§ 110.1 / § 110.2
Dry System Equipment 1 (Fan & Economizer info included below in Table N)Confirmed
1.2.3.4.5.6.7.8.9.10.11.PassFailEquip Name Equip Type
System Type
(Simple 2 or
Complex 3)
Qty
Total Heating
Output
(kBtu/h)
Supp Heat
Source (Y/N)
Supp Heat
Output
(kBtuh)
Total Cooling
Output
(kBtu/h)
Efficiency
Acceptance
Testing
Required? (Y/N)
4 Status5Cooling Heating
RTU - 1 2 SZAC
(Packaged3Phase)Simple 2 114 No 0 115 EER-12.2 AFUE-80.0 Yes N
RTU - 3 4 SZAC
(Packaged3Phase)Simple 2 114 No 0 115 EER-12.2 AFUE-80.0 Yes N
1 Dry System Equipment includes furnaces, air handling units, heat pumps, etc.
2 Simple Systems must complete NRCC-CXR-03-E commissioning design review form
3 Complex Systems must complete NRCC-CXR-04-E commissioning design review form
4 A summary of which acceptance tests are applicable is provided in NRCC-PRF-MCH-DETAILS
5 Status: N - New, A – Altered, E – Existing
Wet System Equipment 1 Pumps Confirmed
12.13.14.15.16.17.18.19.20.21.22.23.24.PassFailEquip Name Equip Type Qty Vol (gal)Rated Capacity
(kBtu/h)Efficiency Standby Loss
Tank
Ext. R
Value
Qty GPM HP VSD
(Y/N)Status2Standard Gas Tankless2 Instantaneous 2 1.00 199 EF: 0.94 SBLF: NA NA NA No N
1 Wet System Equipment includes boilers, chillers, cooling towers, water heaters, etc.
2 Status: N - New, A – Altered, E – Existing
Discrepancy between modeled and designed equipment sizing?(if "Yes", see Table F. "Additional Remarks" for an explanation)No
Project Name:Nonresidential Building NRCC-PRF-01-E Page 10 of 19
Project Address:46-630 Washinton Street La Quinta 92253 Calculation Date/Time:10:01, Thu, Oct 18, 2018
Compliance Scope:NewComplete Input File Name:Washington Park (Retail).cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-09132018-5583 Report Generated at: 2018-10-18 10:02:00
N. ECONOMIZER & FAN SYSTEMS SUMMARY1 § 140.4 Confirmed
1.2.3.4.5.PassFailEquip Name
Outside
Air Supply Fan Return Fan
Economizer Type
(if present)
CFM CFM HP BHP
TSP
(inch
WC)
Control CFM HP BHP
TSP
(inch
WC)
Control
RTU - 1 2 584 4000 1.000 1.000 0.95 ConstantVolume NA NA NA NA NA NoEconomizer
RTU - 3 4 581 4000 1.000 1.000 0.95 ConstantVolume NA NA NA NA NA NoEconomizer
1 Mechanical ventilation calculations and exhaust fans are included in the NRCC-PRF-MCH-DETAILS section
O. EQUIPMENT CONTROLS § 120.2 Confirmed
1.2.3.PassFailEquip Name Equip Type Controls
RTU - 1 2 SZAC
No DCV Controls
No Economizer
No Supply Air Temp. Control
No Optimum Start
No Evaporative Cooler
No Heat Recovery
RTU - 3 4 SZAC
No DCV Controls
No Economizer
No Supply Air Temp. Control
No Optimum Start
No Evaporative Cooler
No Heat Recovery
DHW1 - SHW Service Hot Water, Primary Only Fixed Temperature Control, No DDC
No Heat Recovery
Project Name:Nonresidential Building NRCC-PRF-01-E Page 11 of 19
Project Address:46-630 Washinton Street La Quinta 92253 Calculation Date/Time:10:01, Thu, Oct 18, 2018
Compliance Scope:NewComplete Input File Name:Washington Park (Retail).cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-09132018-5583 Report Generated at: 2018-10-18 10:02:00
P. SYSTEM DISTRIBUTION SUMMARY § 120.4/ § 140.4(I)
Dry System Distribution Confirmed
1.2.3.4.5.6.PassFailEquip Name Equip Type
Duct Leakage and
Sealing Required per
140.4(l)
Duct Leakage will be
verified per NA1 and
NA2
Ducts
Status1Insulation
R-Value Location
RTU - 1 2 SZAC No No 4.2 Conditioned N
RTU - 3 4 SZAC No No 4.2 Conditioned N
1 Status: N - New, E – Existing
Does the Project Include Zonal Systems? (if "Yes", see NRCC-PRF-MCH-DETAILS for system information)No
Does the Project Include a Solar Hot Water System? (if "Yes", see NRCC-PRF-MCH-DETAILS for system information)No
Multifamily or Hotel/ Motel Occupancy? (if "Yes", see NRCC-PRF-MCH-DETAILS for DHW system information)No
Q. INDOOR CONDITIONED LIGHTING GENERAL INFO (see NRCC-PRF-LTI-DETAILS for more info)3 § 140.6
Confirmed
1.2.3.4.5.PassFailOccupancy Type 1 Conditioned Floor Area 2
(ft2)
Installed Lighting Power
(Watts)
Lighting Control Credits
(Watts)Additional (Custom) Allowance
Area Category Footnotes
(Watts)Tailored Method (Watts)
Retail Merchandise Sales,
Wholesale Showroom 11,654 13,985 0 0 0
Building Totals:11,654 13,985 0 0 0
1 See Table 140.6-C
2 See NRCC-LTI-01-E for unconditioned spaces
3Lighting information for existing spaces modeled is not included in the table
R. INDOOR CONDITIONED LIGHTING SCHEDULE (Adapted from NRCC-LTI-01-E)1 § 130.0
This Section Does Not Apply
1If lighting power densities were used in the compliance model Building Departments will need to check prescriptive forms for Luminaire Schedule details.
S1. COVERED PROCESS SUMMARY – ENCLOSED PARKING GARAGES § 140.9
This Section Does Not Apply
Project Name:Nonresidential Building NRCC-PRF-01-E Page 12 of 19
Project Address:46-630 Washinton Street La Quinta 92253 Calculation Date/Time:10:01, Thu, Oct 18, 2018
Compliance Scope:NewComplete Input File Name:Washington Park (Retail).cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-09132018-5583 Report Generated at: 2018-10-18 10:02:00
S2. COVERED PROCESS SUMMARY – COMMERCIAL KITCHENS § 140.9
This Section Does Not Apply
S3. COVERED PROCESS SUMMARY – COMPUTER ROOMS § 140.9
This Section Does Not Apply
S4. COVERED PROCESS SUMMARY – LABORATORY EXHAUSTS § 140.9
This Section Does Not Apply
T. UNMET LOAD HOURS
This Section Does Not Apply
U. ENERGY USE SUMMARY
Energy Component Standard Design Site
(MWh)
Proposed Design Site
(MWh)
Margin
(MWh)
Standard Design Site
(MBtu)
Proposed Design Site
(MBtu)
Margin
(MBtu)
Space Heating 0.0 ----14.1 7.0 7.1
Space Cooling 47.6 40.4 7.2 ------
Indoor Fans 11.3 18.2 -6.9 ------
Heat Rejection ------------
Pumps & Misc.0.1 ----------
Domestic Hot Water ------47.3 25.1 22.2
Indoor Lighting 48.4 48.4 0.0 ------
COMPLIANCE TOTAL 107.4 107.0 0.4 61.4 32.1 29.3
Receptacle 42.4 42.4 0.0 ------
Process ------------
Other Ltg ------------
Process Motors ------------
TOTAL 149.8 149.4 0.4 61.4 32.1 29.3
E12899
M023887______________________ 10/28/2018Architect of RecordC-27769700 S. Flower Street, 22nd FloorLos Angeles, CA 90017(213) 800-9400
Project Name:Nonresidential Building NRCC-PRF-01-E Page 14 of 19
Project Address:46-630 Washinton Street La Quinta 92253 Calculation Date/Time:10:01, Thu, Oct 18, 2018
Compliance Scope:NewComplete Input File Name:Washington Park (Retail).cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-09132018-5583 Report Generated at: 2018-10-18 10:02:00
NRCC-PRF-ENV-DETAILS -SECTION START-
A. OPAQUE SURFACE ASSEMBLY DETAILS Confirmed
1.2.3.4.PassFailSurface Name Surface Type Description of Assembly Layers Notes
R19 Wall6 ExteriorWall
Stucco - 7/8 in.
Vapor permeable felt - 1/8 in.
Wood framed wall, 16in. OC, 5.5in., R-19
Gypsum Board - 1/2 in.
R-30 Roof No Attic13 Roof
Asphalt shingles - 1/4 in.
Vapor permeable felt - 1/8 in.
Plywood - 1/2 in.
Air - Cavity - Wall Roof Ceiling - 4 in. or more
Wood framed roof, 16in. OC, 11.25in., R-30
Gypsum Board - 1/2 in.
Slab On Grade15 UndergroundFloor
Slab Type = UnheatedSlabOnGrade
Insulation Orientation = None
Insulation R-Value = R0
R19 Wall61 InteriorWall
Stucco - 7/8 in.
Vapor permeable felt - 1/8 in.
Wood framed wall, 16in. OC, 5.5in., R-19
Gypsum Board - 1/2 in.
B. OVERHANG DETAILS (Adapted from NRCC-ENV-02-E)
This Section Does Not Apply
C. OPAQUE DOOR SUMMARY Confirmed
1.2.3.4.5.6.7.
Pass FailOpaque Door Assembly Name
/ Tag or I.D.Door Type Certification Method Operation Area Overall
U-factor Status1
Wood Door11 WoodGreaterThanOrEqualTo1.75inThickDoor DefaultPerformance Swinging 105 0.500 N
1 Status: N - New, A – Altered, E – Existing
Project Name:Nonresidential Building NRCC-PRF-01-E Page 15 of 19
Project Address:46-630 Washinton Street La Quinta 92253 Calculation Date/Time:10:01, Thu, Oct 18, 2018
Compliance Scope:NewComplete Input File Name:Washington Park (Retail).cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-09132018-5583 Report Generated at: 2018-10-18 10:02:00
NRCC-PRF-MCH-DETAILS -SECTION START-
A. MECHANICAL VENTILATION AND REHEAT (Adapted from 2016-NRCC-MCH-03-E)Confirmed
1. DESIGN AIR FLOWS 2. VENTILATION (§ 120.1)PassFailCONDITIONED
ZONE NAME HEATING/COOLING SYSTEMIDDESIGN PRIMARY AIR FLOW(CFM)DESIGN PRIMARY MINIMUMAIR FLOW (CFM)MINIMUM PRIMARY AIRFLOW FRACTIONMAXIMUM HEATING AIRFLOW (CFM)MAXIMUM HEATING AIRFLOW FRACTIONDDC CONTROL (Y/N)VENT SYSTEM IDCONDITIONED AREA (ft2)MIN. VENT PER AREA(CFM/ft2)DESIGN NUM. OF PEOPLEMIN. VENT PER PERSON(CFM/person)REQ'D VENT AIR FLOW (CFM)DESIGN VENT AIR FLOW(CFM)TRANSFER AIRFLOW (CFM)DCV (Y/N)Operable Window Interlock §140.4(n) (Y/N)
1-Suite A RTU - 1 2 8,000 NA 0.00 NA NA N RTU - 1 2 5,844 NA 48.71 24.00 1,169 1,169 NA N NA
2-Suite B RTU - 3 4 8,000 NA 0.00 NA NA N RTU - 3 4 5,810 NA 48.43 24.00 1,162 1,162 NA N NA
TOTAL 11,654 97.14 2,331 2,331 NA
B. ZONAL SYSTEM AND TERMINAL UNIT SUMMARY § 140.4
1.2.3.4.5.6.7.8.Confirmed
System ID System Type Qty
Rated Capacity
(kBtuh)
Economizer Zone Name
Airflow (cfm)Fan
PassFailHeating Cooling Design Min.Min.
Ratio BHP Cycles ECM
Motor
1-Suite A-Trm Uncontrolled 2 NA NA NA 1-Suite A 8000 NA 0.00 NA NA
2-Suite B-Trm Uncontrolled 2 NA NA NA 2-Suite B 8000 NA 0.00 NA NA
C. EXHAUST FAN SUMMARY
This Section Does Not Apply
Project Name:Nonresidential Building NRCC-PRF-01-E Page 16 of 19
Project Address:46-630 Washinton Street La Quinta 92253 Calculation Date/Time:10:01, Thu, Oct 18, 2018
Compliance Scope:NewComplete Input File Name:Washington Park (Retail).cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-09132018-5583 Report Generated at: 2018-10-18 10:02:00
D. DHW EQUIPMENT SUMMARY –(Adapted from NRCC-PLB-01)§ 110.3 Confirmed
1.2.3.4.5.6.7.8.9.10.11.PassFailDHW Name Heater
Element Type Tank Type Qty Tank Vol
(gal)
Rated Input
(kBtu/h)Efficiency
Tank
Insulation
R-value
(Int/Ext)
Standby Loss
Fraction
Heat Pump
Type
Tank Location
or Ambient
Condition
Standard Gas
Tankless2 Gas Instantaneous 2 1.00 199 EF: 0.94 NA SBLF: NA NA NA
E. MULTI-FAMILY CENTRAL DHW SYSTEM DETAILS
This Section Does Not Apply
F. SOLAR HOT WATER HEATING SUMMARY (Adapted from NRCC-STH-01)
This Section Does Not Apply
G. MECHANICAL HVAC ACCEPTANCE TESTS & FORMS (Adapted from 2016-NRCC-MCH-01-E)§ RA4
Declaration of Required Acceptance Certificates (NRCA)– Acceptance Certificates that may be submitted. (Retain copies and verify forms are completed and signed to post in field for Field
Inspector to verify).
Test Description MCH-02AMCH-03AMCH-04AMCH-05AMCH-06AMCH-07AMCH-08AMCH-09AMCH-10AMCH-11AMCH-12AMCH-13AMCH-14AMCH-15AMCH-16AMCH-17AMCH-18AConfirmed
Equipment
Requiring
Testing or
Verification
# of
units Outdoor AirSingle Zone UnitaryAir Dist. DuctsEconomizer ControlsDCVSupply Fan VAVValve leakageSupply Water Temp.ResetHyd. Variable FlowControlAuto Demand ShedControlFDD for DX UnitsAuto FDD for Air &ZoneDist. Energy StorageDX ACTES SystemsSupply Air Temp. ResetCondenser WaterReset ControlsECMSPassFailDHW1 -
SHW 1 ----------------------------------
RTU - 1 2 2 X X ------------------------------
RTU - 3 4 2 X X ------------------------------
Project Name:Nonresidential Building NRCC-PRF-01-E Page 17 of 19
Project Address:46-630 Washinton Street La Quinta 92253 Calculation Date/Time:10:01, Thu, Oct 18, 2018
Compliance Scope:NewComplete Input File Name:Washington Park (Retail).cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-09132018-5583 Report Generated at: 2018-10-18 10:02:00
H. EVAPORATIVE COOLER SUMMARY
This Section Does Not Apply
NRCC-PRF-LTI-DETAILS -SECTION START-
A. INDOOR CONDITIONED LIGHTING CONTROL CREDITS (Adapted from NRCC-LTI-02-E)§ 140.6
This Section Does Not Apply
B. INDOOR CONDITIONED LIGHTING MANDATORY LIGHTING CONTROLS (Adapted from NRCC-LTI-02-E)§ 130.1
This Section Does Not Apply
§130.1(a) = Manual area controls; §130.0(b) = Multi Level; §130.1(c) = Auto Shut-Off; §130.1(d) = Mandatory Daylight; §130.1(e) = Demand Responsive
C. TAILORED METHOD CONDITIONED LIGHTING POWER ALLOWANCE SUMMARY AND CHECKLIST (Adapted from NRCC-LTI-04-E)§ 140.6
General lighting power (see Table D)0
General lighting power from special function areas (see Table E)NA
Additional "use it or lose it" (See Table G)0
Total watts 0
D. GENERAL LIGHTING POWER (Adapted from NRCC-LTI-04-E)§ 140.6-D
This Section Does Not Apply
E. GENERAL LIGHTING FROM SPECIAL FUNCTION AREAS (Adapted from NRCC-LTI-04-E)§ 140.6(c) 3H
Room Number Primary Function Area Illuminance Value
(LUX)
Room Cavity Ratio
(Table G)Allowed LPD Floor Area (ft2)Allowed Watts
Confirmed
Pass Fail
NA NA NA NA NA NA NA
Note: Tailored Method for Special Function Areas is not currently implemented
F. ROOM CAVITY RATIO (Adapted from NRCC-LTI-04-E)
Rectangular Spaces
Room Number Task/Activity Description Room Length (ft)Room Width (ft)Room Cavity Height (ft)RCR
Confirmed
Pass Fail
NA NA NA NA NA NA
Project Name:Nonresidential Building NRCC-PRF-01-E Page 18 of 19
Project Address:46-630 Washinton Street La Quinta 92253 Calculation Date/Time:10:01, Thu, Oct 18, 2018
Compliance Scope:NewComplete Input File Name:Washington Park (Retail).cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-09132018-5583 Report Generated at: 2018-10-18 10:02:00
Non-Rectangular Spaces
This Section Does Not Apply
Note: All applicable spaces are listed under the Non-Rectangular Spaces table
G. ADDITIONAL “USE IT OR LOSE IT” (Adapted from NRCC-LTI-04-E)
1.2.3.4.
Allowed Watts
Confirmed
Wall Display Combined Floor Display and Task
Lighting
Combined Ornamental and Special
Effects Lighting Very Valuable Merchandise PassFail0 0 0 0 0
5. Wall Display
This Section Does Not Apply
6. Floor Display and Task Lighting
This Section Does Not Apply
7. Combined Ornamental and Special Effects Lighting
This Section Does Not Apply
8. Very Valuable Merchandise
This Section Does Not Apply
H. INDOOR & OUTDOOR LIGHTING ACCEPTANCE TESTS & FORMS (Adapted from NRCC-LTI-01-E and NRCC-LTO-01-E)§ 130.4
Declaration of Required Acceptance Certificates (NRCA) –Acceptance Certificates that must be verified in the field. (Retain copies and verify forms are completed and signed to post in field for
Field Inspector to verify).
Test Description
Indoor Outdoor Confirmed
NRCA-LTI-02-A NRCA-LTI-03-A NRCA-LTI-04-A NRCA-LTO-02-A
PassFailEquipment Requiring
Testing or Verification # of units Occ Sensors / Auto Time
Switch Auto Daylight Demand Responsive Outdoor Controls
Occupant Sensors 1
Automatic Time Switch 0
Automatic Daylighting 1
Project Name:Nonresidential Building NRCC-PRF-01-E Page 19 of 19
Project Address:46-630 Washinton Street La Quinta 92253 Calculation Date/Time:10:01, Thu, Oct 18, 2018
Compliance Scope:NewComplete Input File Name:Washington Park (Retail).cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-09132018-5583 Report Generated at: 2018-10-18 10:02:00
H. INDOOR & OUTDOOR LIGHTING ACCEPTANCE TESTS & FORMS (Adapted from NRCC-LTI-01-E and NRCC-LTO-01-E)§ 130.4
Declaration of Required Acceptance Certificates (NRCA) –Acceptance Certificates that must be verified in the field. (Retain copies and verify forms are completed and signed to post in field for
Field Inspector to verify).
Test Description
Indoor Outdoor Confirmed
NRCA-LTI-02-A NRCA-LTI-03-A NRCA-LTI-04-A NRCA-LTO-02-A
PassFailEquipment Requiring
Testing or Verification # of units Occ Sensors / Auto Time
Switch Auto Daylight Demand Responsive Outdoor Controls
Demand Responsive 1
Outdoor Controls 1
ENVELOPE MANDATORY MEASURES: NONRESIDENTIAL ENV-MM
Project Name Date
DESCRIPTION
Building Envelope Measures:
§110.8(a): Installed insulating material shall have been certified by the manufacturer to comply with the California Quality
Standards for insulating material, Title 20 Chapter 4, Article 3.
§110.8(c): All Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of
Sections 2602 and 707 of Title 24, Part 2.
§110.8(g): Heated slab floors shall be insulated according to the requirements in Table 110.8-A.
§110.7(a): All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed,
weatherstripped or otherwise sealed.
§110.6(a):
Manufactured fenestration products and exterior doors shall have air infiltration rates not exceeding 0.3 cfm/ft.² of
window area, 0.3 cfm/ft.² of door area for residential doors, 0.3 cfm/ft.² of door area for nonresidential single doors
(swinging and sliding), and 1.0 cfm/ft.² for nonresidential double doors (swinging).
§110.6(a): Fenestration U-factor shall be rated in accordance with NFRC 100, or the applicable default U-factor.
§110.6(a) : Fenestration SHGC shall be rated in accordance with NFRC 200, or NFRC 100 for site-built fenestration, or the
applicable default SHGC.
§110.6(b): Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be
weatherstripped (except for unframed glass doors and fire doors).
§120.7(a):
The opaque portions of the roof/ceiling that separates conditioned spaces from unconditioned spaces or ambient air
shall meet the applicable U-Factor requirements as follows:
Metal Building- The weighted average U-factor of the roof assembly shall not exceed 0.098.
Wood Framed and Others- The weighted average U-factor of the roof assembly shall not exceed 0.075.
§120.7(b):
The opaque portions of walls that separate conditioned spaces from unconditioned spaces or ambient air shall meet the
applicable U-factor as follows:
Metal Building- The weighted average U-factor of the wall assembly shall not exceed 0.113.
Metal Framed- The weighted average U-factor of the wall assembly shall not exceed 0.151.
Light Mass Walls- A 6 inch or greater Hollow Core Concrete Masonry Unit shall have a U-factor not to exceed 0.440.
Heavy Mass Walls- An 8 inch or greater Hollow Core Concrete Masonry Unit shall have a U-factor not to exceed
0.690.
Wood Framed and Others- The weighted average U-factor of the wall assembly shall not exceed 0.110.
Spandrel Panels and Opaque Curtain Wall- The weighted average U-factor of the spandrel panels and opaque
curtain wall assembly shall not exceed 0.280.
Demising Walls-. The opaque portions of framed demising walls shall meet the requirements of Item A or B below:
A. Wood framed walls shall be insulated to meet a U -factor not greater than 0.099.
B. Metal Framed walls shall be insulated to meet a U-factor not greater than 0.151.
§120.7(c):
The opaque portions of floors and soffits that separate conditioned spaces from unconditioned spaces or ambient air
shall meet the applicable U-Factor requirements as follows:
Raised Mass Floors- Shall have a minimum of 3 inches of lightweight concrete over a metal deck or the weighted
average U-factor of the floor assembly shall not exceed 0.269.
Other Floors-The weighted average U-factor of the floor assembly shall not exceed 0.071.
Washington Park (Retail)10/18/2018