Alta Verde - Coral Mountain TR 34243 BCPR2021-0028 (Plans D, D MOD, J, J MOD, Z) Solar Master Plans Revision 2SOLAR MASTER PLAN PERMIT PACKAGE ALTA VERDE BUILDERS 71905 HWY 111 SUITE GRANCHO MIRAGE, CA 92270 LA QUINTA, CALIFORNIA 92210 PLAN D, D MOD, J, J MOD, Z CODE INFORMATION APPLICABLE CODES, LAWS AND REGULATIONS 2019 CALIFORNIA RESIDENTIAL CODE (CRC) 2019 CALIFORNIA BUILDING CODE (CBC) 2019 CALIFORNIA FIRE CODE (CFC) 2019 CALIFORNIA ELECTRICAL CODE (CEC) 2019 CALIFORNIA MECHANICAL CODE (CMC) 2019 CALIFORNIA PLUMBING CODE (CPC) NOT TO SCALE SHEET GENERAL NOTES: SHEET INDEX VICINITY MAP SO L A R M A S T E R P L A N P E R M I T P A C K A G E PROJECT LOCATION RE V D E S C R I P T I O N D A T E D B C B R E V I S I O N S PVA-0 ELECT R I C A L E22659 Exp. 03-31-23R EGISTERE D P R O F ESSIONAL E N G I NEER STATE OF CA L I F O R NIA 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S C A L I C E N S E # : 8 9 0 8 9 5 FI L E : D - 0 1 1 4 6 3 6 - M P P P - 0 7 2 6 2 0 2 1 - S O L A R - P V A - 0 . d w g , U S E R : k e s p i n o z a , D A T E / T I M E : A p r 1 2 , 2 0 2 2 - 9 : 1 1 a m SOLAR ARCHITECTURAL DRAWINGS SOLAR STRUCTURAL DRAWINGS PVA-0 COVER PAGE PVA-1 PLAN D PVA-2 PLAN D MOD PVA-2.1 PLAN D MOD REVERSED PVA-3 PLAN J PVA-4 PLAN J MOD PVA-5 PLAN Z PL A N D , D M O D , J , J M O D , Z PVS-1 MOUNTING DETAILS SOLAR ELECTRICAL DRAWINGS PVE-1.1 ELECTRICAL SINGLE LINE DIAGRAM PVE-2 ELECTRICAL DETAILS PVE-3 ELECTRICAL DATA & SPECIFICATIONS PVE-1.2 ELECTRICAL SINGLE LINE DIAGRAM PVE-4 ELECTRICAL DATA & SPECIFICATIONS DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID CHECKED BY DATE CHECKED CO R A L M T N AL T A V E R D E B U I L D E R S 71 9 0 5 H W Y 1 1 1 S U I T E G LA Q U I N T A , C A L I F O R N I A 9 2 2 1 0 C002231 D-0120496 04-11-2022 KESPINOZA 04-11-2022 EOR RA N C H O M I R A G E , C A 9 2 2 7 0 ’ 05/02/2022 BCPR2021-0028 TO ELECTRIC UTILITY GRID (E) SERVICE POINT AND UTILITY METERING (N) LOAD CENTER (INSIDE GARAGE) 66" ABOVE SLAB UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) ROOF ACCESS POINT SQUARE HAT VENT (TYP.) TRANSITION BOX ROOF ACCESS POINT SEE PVE 1.2 FOR ELECTRICAL SINGLE DIAGRAM SHEET RE V D E S C R I P T I O N D A T E D B C B R E V I S I O N S SO L A R M A S T E R P L A N P E R M I T P A C K A G E PVA-1 PL A N D FI L E : D - 0 1 1 4 6 3 6 - M P P P - 0 7 2 6 2 0 2 1 - S O L A R - P V A - 1 . d w g , U S E R : k e s p i n o z a , D A T E / T I M E : A p r 1 2 , 2 0 2 2 - 8 : 5 7 a m PLAN ELEVATION ROOF TYPE ROOF PITCH SQUARE SYSTEM STORY SYSTEM SYSTEM PHASE NO. LOT NO. FOOTAGE SIZE HOME TYPE ORIENTATION LOCATION SCALE D FLAT ROOF FLAT 304 SQ. FT. 5.95 kW 1 - STORY 180° 28, 30, 34, 36, 65 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S C A L I C E N S E # : 8 9 0 8 9 5 DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID CHECKED BY DATE CHECKED NOTES: ROOFTOP PENETRATIONS AND/OR OBSTRUCTIONS NOT PERTAINING TO SOLAR INSTALLATION SHALL NOT BE LOCATED UNDER THE ARRAY. 1/8" - 1'-0" CO R A L M T N AL T A V E R D E B U I L D E R S 71 9 0 5 H W Y 1 1 1 , S U I T E G LA Q U I N T A , C A L I F O R N I A 9 2 2 1 0 C002231 D-0120496 04-11-2022 KESPINOZA 04-11-2022 GBFS RA N C H O M I R A G E , C A 9 2 2 7 0 ELECT R I C A L E22659 Exp. 03-31-23R EGISTERED P R O F ESSIONAL E N G I NEER STATE OF CA L I F O R NIA 05/02/2022 BCPR2021-0028 TO ELECTRIC UTILITY GRID (E) SERVICE POINT AND UTILITY METERING (N) LOAD CENTER (INSIDE GARAGE) 66" ABOVE SLAB UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) SQUARE HAT VENT (TYP.) TRANSITION BOX (TYP.) ROOF ACCESS POINT FLAT SEE PVE 1.1 FOR ELECTRICAL SINGLE DIAGRAM ROOF ACCESS POINT SHEET RE V D E S C R I P T I O N D A T E D B C B R E V I S I O N S PVA-2 PL A N D M O D FI L E : D - 0 1 1 4 6 3 6 - M P P P - 0 7 2 6 2 0 2 1 - S O L A R - P V A - 1 . d w g , U S E R : k e s p i n o z a , D A T E / T I M E : A p r 1 2 , 2 0 2 2 - 8 : 5 7 a m PLAN ELEVATION ROOF TYPE ROOF PITCH SQUARE SYSTEM STORY SYSTEM SYSTEM PHASE NO. LOT NO. FOOTAGE SIZE HOME TYPE ORIENTATION LOCATION SCALE D MOD FLAT ROOF FLAT 286 SQ. FT. 5.60 kW 1 - STORY 180° 19, 26, 33 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S C A L I C E N S E # : 8 9 0 8 9 5 NOTES: ROOFTOP PENETRATIONS AND/OR OBSTRUCTIONS NOT PERTAINING TO SOLAR INSTALLATION SHALL NOT BE LOCATED UNDER THE ARRAY. 1/8" - 1'-0" CO R A L M T N AL T A V E R D E B U I L D E R S 71 9 0 5 H W Y 1 1 1 , S U I T E G LA Q U I N T A , C A L I F O R N I A 9 2 2 1 0 RA N C H O M I R A G E , C A 9 2 2 7 0 DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID CHECKED BY DATE CHECKED C002231 GBFS SO L A R M A S T E R P L A N P E R M I T P A C K A G E KESPINOZA ELECT R I C A L E22659 Exp. 03-31-23R EGISTERED P R O F ESSIONAL E N G I NEER STATE OF CA L I F O R NIA D-0120496 04-11-2022 04-11-2022 05/02/2022 BCPR2021-0028 TO ELECTRIC UTILITY GRID (E) SERVICE POINT AND UTILITY METERING (N) LOAD CENTER (INSIDE GARAGE) 66" ABOVE SLAB UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) SQUARE HAT VENT (TYP.) TRANSITION BOX (TYP.) ROOF ACCESS POINT FLAT SEE PVE 1.1 FOR ELECTRICAL SINGLE DIAGRAM ROOF ACCESS POINT SHEET RE V D E S C R I P T I O N D A T E D B C B R E V I S I O N S PVA-2.1 PL A N D M O D - R E V E R S E FI L E : D - 0 1 1 4 6 3 6 - M P P P - 0 7 2 6 2 0 2 1 - S O L A R - P V A - 1 . d w g , U S E R : k e s p i n o z a , D A T E / T I M E : A p r 1 2 , 2 0 2 2 - 8 : 5 7 a m PLAN ELEVATION ROOF TYPE ROOF PITCH SQUARE SYSTEM STORY SYSTEM SYSTEM PHASE NO. LOT NO. FOOTAGE SIZE HOME TYPE ORIENTATION LOCATION SCALE D MOD - REVERSE FLAT ROOF FLAT 286 SQ. FT. 5.60 kW 1 - STORY 180° 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S C A L I C E N S E # : 8 9 0 8 9 5 NOTES: ROOFTOP PENETRATIONS AND/OR OBSTRUCTIONS NOT PERTAINING TO SOLAR INSTALLATION SHALL NOT BE LOCATED UNDER THE ARRAY. 1/8" - 1'-0" CO R A L M T N AL T A V E R D E B U I L D E R S 71 9 0 5 H W Y 1 1 1 , S U I T E G LA Q U I N T A , C A L I F O R N I A 9 2 2 1 0 RA N C H O M I R A G E , C A 9 2 2 7 0 DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID CHECKED BY DATE CHECKED C002231 GBFS SO L A R M A S T E R P L A N P E R M I T P A C K A G E KESPINOZA ELECT R I C A L E22659 Exp. 03-31-23R EGISTERED P R O F ESSIONAL E N G I NEER STATE OF CA L I F O R NIA D-0120496 04-11-2022 04-11-2022 05/02/2022 BCPR2021-0028 TRANSITION BOX TO ELECTRIC UTILITY GRID (E) SERVICE POINT AND UTILITY METERING (N) LOAD CENTER (INSIDE GARAGE) 66" ABOVE SLAB UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) SQUARE HAT VENT (TYP.) ROOF ACCESS POINT ROOF ACCESS POINT SEE PVE 1.2 FOR ELECTRICAL SINGLE DIAGRAM SHEET RE V D E S C R I P T I O N D A T E D B C B R E V I S I O N S PVA-3 PL A N J FI L E : D - 0 1 1 4 6 3 6 - M P P P - 0 7 2 6 2 0 2 1 - S O L A R - P V A - 1 . d w g , U S E R : k e s p i n o z a , D A T E / T I M E : A p r 1 2 , 2 0 2 2 - 8 : 5 7 a m PLAN ELEVATION ROOF TYPE ROOF PITCH SQUARE SYSTEM STORY SYSTEM SYSTEM PHASE NO. LOT NO. FOOTAGE SIZE HOME TYPE ORIENTATION LOCATION SCALE J FLAT ROOF FLAT 304 SQ. FT. 5.95 kW 1 - STORY 180° 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S C A L I C E N S E # : 8 9 0 8 9 5 NOTES: ROOFTOP PENETRATIONS AND/OR OBSTRUCTIONS NOT PERTAINING TO SOLAR INSTALLATION SHALL NOT BE LOCATED UNDER THE ARRAY. 1/8" - 1'-0" CO R A L M T N AL T A V E R D E B U I L D E R S 71 9 0 5 H W Y 1 1 1 , S U I T E G LA Q U I N T A , C A L I F O R N I A 9 2 2 1 0 RA N C H O M I R A G E , C A 9 2 2 7 0 DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID CHECKED BY DATE CHECKED C002231 GBFS SO L A R M A S T E R P L A N P E R M I T P A C K A G E KESPINOZA ELECT R I C A L E22659 Exp. 03-31-23R EGISTERED P R O F ESSIONAL E N G I NEER STATE OF CA L I F O R NIA D-0120496 04-11-2022 04-11-2022 05/02/2022 BCPR2021-0028 TO ELECTRIC UTILITY GRID (E) SERVICE POINT AND UTILITY METERING (N) LOAD CENTER (INSIDE GARAGE) 66" ABOVE SLAB UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) TRANSITION BOX SQUARE HAT VENT (TYP.) ROOF ACCESS POINT ROOF ACCESS POINT SEE PVE 1.1 FOR ELECTRICAL SINGLE DIAGRAM SHEET RE V D E S C R I P T I O N D A T E D B C B R E V I S I O N S PVA-4 PL A N J M O D FI L E : D - 0 1 1 4 6 3 6 - M P P P - 0 7 2 6 2 0 2 1 - S O L A R - P V A - 1 . d w g , U S E R : k e s p i n o z a , D A T E / T I M E : A p r 1 2 , 2 0 2 2 - 8 : 5 7 a m PLAN ELEVATION ROOF TYPE ROOF PITCH SQUARE SYSTEM STORY SYSTEM SYSTEM PHASE NO. LOT NO. FOOTAGE SIZE HOME TYPE ORIENTATION LOCATION SCALE J MOD FLAT ROOF FLAT 286 SQ. FT. 5.60 kW 1 - STORY 180° 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S C A L I C E N S E # : 8 9 0 8 9 5 NOTES: ROOFTOP PENETRATIONS AND/OR OBSTRUCTIONS NOT PERTAINING TO SOLAR INSTALLATION SHALL NOT BE LOCATED UNDER THE ARRAY. 1/8" - 1'-0" CO R A L M T N AL T A V E R D E B U I L D E R S 71 9 0 5 H W Y 1 1 1 , S U I T E G LA Q U I N T A , C A L I F O R N I A 9 2 2 1 0 RA N C H O M I R A G E , C A 9 2 2 7 0 DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID CHECKED BY DATE CHECKED C002231 GBFS SO L A R M A S T E R P L A N P E R M I T P A C K A G E KESPINOZA ELECT R I C A L E22659 Exp. 03-31-23R EGISTERED P R O F ESSIONAL E N G I NEER STATE OF CA L I F O R NIA D-0120496 04-11-2022 04-11-2022 05/02/2022 BCPR2021-0028 (E) SERVICE POINT AND UTILITY METERING (N) LOAD CENTER (INSIDE GARAGE) 66" ABOVE SLAB UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) TRANSITION BOX SQUARE HAT VENT (TYP.) ROOF ACCESS POINT ROOF ACCESS POINT FLAT SEE PVE 1.2 FOR ELECTRICAL SINGLE DIAGRAM TO ELECTRIC UTILITY GRID SHEET RE V D E S C R I P T I O N D A T E D B C B R E V I S I O N S PVA-5 PL A N Z FI L E : D - 0 1 1 4 6 3 6 - M P P P - 0 7 2 6 2 0 2 1 - S O L A R - P V A - 1 . d w g , U S E R : k e s p i n o z a , D A T E / T I M E : A p r 1 2 , 2 0 2 2 - 8 : 5 7 a m PLAN ELEVATION ROOF TYPE ROOF PITCH SQUARE SYSTEM STORY SYSTEM SYSTEM PHASE NO. LOT NO. FOOTAGE SIZE HOME TYPE ORIENTATION LOCATION SCALE Z FLAT ROOF FLAT 286 SQ. FT. 5.60 kW 1 - STORY 180° 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S C A L I C E N S E # : 8 9 0 8 9 5 NOTES: ROOFTOP PENETRATIONS AND/OR OBSTRUCTIONS NOT PERTAINING TO SOLAR INSTALLATION SHALL NOT BE LOCATED UNDER THE ARRAY. 1/8" - 1'-0" CO R A L M T N AL T A V E R D E B U I L D E R S 71 9 0 5 H W Y 1 1 1 , S U I T E G LA Q U I N T A , C A L I F O R N I A 9 2 2 1 0 RA N C H O M I R A G E , C A 9 2 2 7 0 DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID CHECKED BY DATE CHECKED C002231 GBFS SO L A R M A S T E R P L A N P E R M I T P A C K A G E KESPINOZA ELECT R I C A L E22659 Exp. 03-31-23R EGISTERED P R O F ESSIONAL E N G I NEER STATE OF CA L I F O R NIA D-0120496 04-11-2022 04-11-2022 05/02/2022 BCPR2021-0028 SHEET RE V D E S C R I P T I O N D A T E D B C B R E V I S I O N S NOT TO SCALE 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S C A L I C E N S E # : 8 9 0 8 9 5 FI L E : S T . d w g , U S E R : k e s p i n o z a , D A T E / T I M E : J u l 2 6 , 2 0 2 1 - 1 1 : 5 4 p m DRAWN BY PROJECT DATE DRAWN OPPORTUNITY CHECKED BY DATE CHECKED CO R A L M T N AL T A V E R D E B U I L D E R S 71 9 0 5 H W Y 1 1 1 S U I T E G LA Q U I N T A , C A L I F O R N I A 9 2 2 1 0 C002231 EOR RA N C H O M I R A G E , C A 9 2 2 7 0 KESPINOZA D-0120496 04-11-2022 04-11-2022 05/02/2022 BCPR2021-0028 FIGURE A: SINGLE LINE DIAGRAM - 5.60 kWDC 2 A DC AC DC AC 1 SUNPOWER MODULES AC MODULE EXTENSION CABLE NM CABLE OR EQ INSTALLED IN WALL CAVITY --EGC BARE CU CU-NM-B INTEGRATED MICROINVERTER B ATTIC ROOFTOP 8 AC MODULESBRANCH CIRCUIT #2 8 AC MODULESBRANCH CIRCUIT #1 SPR-X21-350-BLK-E-AC #10 #10 SPR-X21-350-BLK-E-AC (240) UTILITY BIDIRECTIONAL METER (NOT CENTER-FED)INCOMING SOURCE FEED H MCB (E)MAIN SERVICE PANEL 200A, 120/240V, 1PH, 3W GND EXISTING GND TO HOUSE LOADS BREAKERS SHALL BE INSTALLED OPPOSITE END OF THE MAIN BREAKER *MSP MAX PV BREAKER (A) = X 120% - =200A, 2P 30A, 2P 200A, 2P 200A, 2P 40A, 2P GND 3 NOTE: FOR SOLAR PHOTOVOLTAIC ONLY. NO ADDITIONAL LOADS TO BE APPLIED (N)LOAD CENTER 100A OR EQUIVALENT, 120/240V, 1PH 20A, 2P 20A, 2P TAG 1 2 5 SOURCE CIRCUIT TRANSITION BOX (N) LOAD CENTER PV PRODUCTION METER SEPARATE AC DISCONNECT DESCRIPTION SOLAR AC MODULE / BRANCH 3 4 FIGURE C: ELECTRICAL CALCULATIONS ELECTRICAL NOTES 1. ALL SEAL TIGHT FLEXIBLE METAL CONDUIT (OR EQUIVALENT) TO BE BONDED TO GROUND AT COUPLINGS ON BOTH ENDS. 2. CONDUIT ENTRY/CONNECTION TO ELECTRICAL ENCLOSURES SHALL BE SUITABLE FOR GROUNDING AND SHALL BE SEALED AGAINST ENVIRONMENT, SUCH AS WATER, INSECTS AND RODENTS. CONDUIT SHALL NOT ENTER FROM TOP OF ELECTRICAL EQUIPMENT IN OUTDOOR LOCATIONS WITHOUT SITE-SPECIFIC APPROVAL FROM SUNPOWER. IF GRANTED APPROVAL FOR TOP ENTRY, ONLY RIGID CONDUIT WITH MEYERS HUBS TO BE USED. 3. PROPER LISTING EXPECTED FOR CONDITIONS OF USE ON ALL LUGS, FITTINGS, CRIMPS, ETC. 4. ALL CONDUIT BEND RADII TO CONFORM TO THE CEC MINIMUM BEND RADII REQUIREMENTS. 5. MINIMUM CLEARANCE SHALL BE MAINTAINED PER CEC FOR ALL NEW EQUIPMENTS TO BE INSTALLED. 6. EXISTING GROUNDING ELECTRODE SYSTEM MUST MEET CEC AND LOCAL UTILITY REQUIREMENTS. 7. COPPER CONDUCTORS SHALL BE USED UNLESS SPECIFIED. 8. TYPE NM (ROMEX) CONDUCTORS ARE ALLOWED FOR INTERNAL AND ATTIC RUNS AND SHALL BE INSTALLED MEETING CEC REQUIREMENTS. 9. AC WIRING SHALL UPSIZE IF VOLTAGE DROP EXCEEDS 2%. 10. RUN CONDUCTORS IN EXISTING CONDUIT WHEN AVAILABLE PROVIDED IT HAS NO OTHER CONDUCTORS RUNNING THROUGH IT. 11. IF MAIN SERVICE PANEL IS TO BE UPGRADED, IT WILL BE PERMITTED AND INSTALLED BY A THIRD PARTY. 12. CONDUIT SIZE BASED ON 2 BENDS MAXIMUM. ANY ADDITIONAL BENDS MAY REQUIRE UPSIZE. NOTE : SUNPOWER 15A MONITORING BREAKER CAN BE RELOCATED TO OTHER LOAD CENTER OR SUB-PANEL WITHIN THE HOUSE FOR CONSTRUCTION FEASIBILITY. BELOW ARE OPTIONAL OFFERINGS AND SHALL ONLY BE INSTALLED IF THE HOMEOWNER SIGNS A SPECIFIC CONTRACT WITH SUNPOWER. SUNPOWER MONITORING SYSTEM AS DC POWER IS INTERNAL TO THE MODULE, GROUNDING ELECTRODE CONDUCTOR (GEC) FOR THE MODULE OR ARRAY IS NOT REQUIRED. 1 2 CONDUCTOR / CONDUIT SCHEDULE DESCRIPTION & CONDUCTOR TYPE CONDUCTOR SIZE(AWG) 2 1 SUNPOWER PROVIDED AC MODULES EXTENSION CABLE, LISTED AS AN ASSEMBLY NUMBER OF CONDUCTORS CONDUIT/ CABLE TYPE CONDUIT SIZE (WHEN NEEDED) #12 TYPE-ER, PER BRANCH CIRCUIT --WITH EGCA B TAG OPTIONAL ETHERNET CONNECTION TO DSL/CABLE MODEM CAT5e CURRENT TRANSFORMERS (100A) INSTALLED ON THE CUSTOMER SIDE OF THE PANEL 1#14 NM CABLE OR EQ INSTALLED IN WALL CAVITY #22 NMFC CU-NM-B AWG TWISTED PAIR EGC BARE CU 3 INSTALLED IN WALL CAVITY 1/2" -- PRODUCTION CURRENT TRANSFORMERS (100A) SUNPOWER MONITORING PVS6 E #14 3 D E E D #6 15A, 2P EATON DG221URB OR EQUIVALENT LOCATED OUTSIDE WITH VISIBLE KNIFE BLADES 5 NM CABLE OR EQ INSTALLED IN WALL CAVITY --EGC BARE CU CU-NM-B 3 1 GND C C UTILITY-LOCKABLE SAFETY SWITCH 30A, 240VAC #10 #10 NOTE: THIS SINGLE LINE DIAGRAM IS APPLICABLE TO: PLAN J MOD PLAN D MOD EL E C T R I C A L S I N G L E L I N E D I A G R A M & S P E C I F I C A T I O N SHEET RE V D E S C R I P T I O N D A T E D B C B R E V I S I O N S NOT TO SCALE 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S C A L I C E N S E # : 8 9 0 8 9 5 ELECT R I C A L E22659 Exp. 03-31-23R EGISTERED P R O F ESSIONAL E N G I NEER STATE OF CA L I F O R NIA DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID CHECKED BY DATE CHECKED CO R A L M T N AL T A V E R D E B U I L D E R S 71 9 0 5 H W Y 1 1 1 S U I T E G LA Q U I N T A , C A L I F O R N I A 9 2 2 1 0 C002231 EOR RA N C H O M I R A G E , C A 9 2 2 7 0 KESPINOZA D-0120496 04-11-2022 04-11-2022 05/02/2022 BCPR2021-0028 FIGURE A: SINGLE LINE DIAGRAM - 5.95 kWDC 2 A DC AC DC AC 1 SUNPOWER MODULES AC MODULE EXTENSION CABLE NM CABLE OR EQ INSTALLED IN WALL CAVITY --EGC BARE CU CU-NM-B INTEGRATED MICROINVERTER B ATTIC ROOFTOP 8 AC MODULESBRANCH CIRCUIT #2 9 AC MODULESBRANCH CIRCUIT #1 SPR-X21-350-BLK-E-AC #10 #10 SPR-X21-350-BLK-E-AC (240) UTILITY BIDIRECTIONAL METER (NOT CENTER-FED)INCOMING SOURCE FEED H MCB (E)MAIN SERVICE PANEL 200A, 120/240V, 1PH, 3W GND EXISTING GND TO HOUSE LOADS BREAKERS SHALL BE INSTALLED OPPOSITE END OF THE MAIN BREAKER *MSP MAX PV BREAKER (A) = X 120% - =200A, 2P 30A, 2P 200A, 2P 200A, 2P 40A, 2P GND 3 NOTE: FOR SOLAR PHOTOVOLTAIC ONLY. NO ADDITIONAL LOADS TO BE APPLIED (N)LOAD CENTER 100A OR EQUIVALENT, 120/240V, 1PH 20A, 2P 20A, 2P TAG 1 2 5 SOURCE CIRCUIT TRANSITION BOX (N) LOAD CENTER PV PRODUCTION METER SEPARATE AC DISCONNECT DESCRIPTION SOLAR AC MODULE / BRANCH 3 4 FIGURE C: ELECTRICAL CALCULATIONS ELECTRICAL NOTES 1. ALL SEAL TIGHT FLEXIBLE METAL CONDUIT (OR EQUIVALENT) TO BE BONDED TO GROUND AT COUPLINGS ON BOTH ENDS. 2. CONDUIT ENTRY/CONNECTION TO ELECTRICAL ENCLOSURES SHALL BE SUITABLE FOR GROUNDING AND SHALL BE SEALED AGAINST ENVIRONMENT, SUCH AS WATER, INSECTS AND RODENTS. CONDUIT SHALL NOT ENTER FROM TOP OF ELECTRICAL EQUIPMENT IN OUTDOOR LOCATIONS WITHOUT SITE-SPECIFIC APPROVAL FROM SUNPOWER. IF GRANTED APPROVAL FOR TOP ENTRY, ONLY RIGID CONDUIT WITH MEYERS HUBS TO BE USED. 3. PROPER LISTING EXPECTED FOR CONDITIONS OF USE ON ALL LUGS, FITTINGS, CRIMPS, ETC. 4. ALL CONDUIT BEND RADII TO CONFORM TO THE CEC MINIMUM BEND RADII REQUIREMENTS. 5. MINIMUM CLEARANCE SHALL BE MAINTAINED PER CEC FOR ALL NEW EQUIPMENTS TO BE INSTALLED. 6. EXISTING GROUNDING ELECTRODE SYSTEM MUST MEET CEC AND LOCAL UTILITY REQUIREMENTS. 7. COPPER CONDUCTORS SHALL BE USED UNLESS SPECIFIED. 8. TYPE NM (ROMEX) CONDUCTORS ARE ALLOWED FOR INTERNAL AND ATTIC RUNS AND SHALL BE INSTALLED MEETING CEC REQUIREMENTS. 9. AC WIRING SHALL UPSIZE IF VOLTAGE DROP EXCEEDS 2%. 10. RUN CONDUCTORS IN EXISTING CONDUIT WHEN AVAILABLE PROVIDED IT HAS NO OTHER CONDUCTORS RUNNING THROUGH IT. 11. IF MAIN SERVICE PANEL IS TO BE UPGRADED, IT WILL BE PERMITTED AND INSTALLED BY A THIRD PARTY. 12. CONDUIT SIZE BASED ON 2 BENDS MAXIMUM. ANY ADDITIONAL BENDS MAY REQUIRE UPSIZE. NOTE : SUNPOWER 15A MONITORING BREAKER CAN BE RELOCATED TO OTHER LOAD CENTER OR SUB-PANEL WITHIN THE HOUSE FOR CONSTRUCTION FEASIBILITY. BELOW ARE OPTIONAL OFFERINGS AND SHALL ONLY BE INSTALLED IF THE HOMEOWNER SIGNS A SPECIFIC CONTRACT WITH SUNPOWER. SUNPOWER MONITORING SYSTEM AS DC POWER IS INTERNAL TO THE MODULE, GROUNDING ELECTRODE CONDUCTOR (GEC) FOR THE MODULE OR ARRAY IS NOT REQUIRED. 1 2 CONDUCTOR / CONDUIT SCHEDULE DESCRIPTION & CONDUCTOR TYPE CONDUCTOR SIZE(AWG) 2 1 SUNPOWER PROVIDED AC MODULES EXTENSION CABLE, LISTED AS AN ASSEMBLY NUMBER OF CONDUCTORS CONDUIT/ CABLE TYPE #12 TYPE-ER, PER BRANCH CIRCUIT --WITH EGCA B TAG OPTIONAL ETHERNET CONNECTION TO DSL/CABLE MODEM CAT5e CURRENT TRANSFORMERS (100A) INSTALLED ON THE CUSTOMER SIDE OF THE PANEL 1#14 NM CABLE OR EQ INSTALLED IN WALL CAVITY #22 NMFC CU-NM-B AWG TWISTED PAIR EGC BARE CU 3 INSTALLED IN WALL CAVITY 1/2" -- PRODUCTION CURRENT TRANSFORMERS (100A) SUNPOWER MONITORING PVS6 E #14 3 D E E D #6 15A, 2P EATON DG221URB OR EQUIVALENT LOCATED OUTSIDE WITH VISIBLE KNIFE BLADES 5 NM CABLE OR EQ INSTALLED IN WALL CAVITY --EGC BARE CU CU-NM-B 3 1 GND C C UTILITY-LOCKABLE SAFETY SWITCH 30A, 240VAC #10 #10 CONDUIT SIZE (WHEN NEEDED) NOTE: THIS SINGLE LINE DIAGRAM IS APPLICABLE TO: PLAN J PLAN D PLAN Z EL E C T R I C A L S I N G L E L I N E D I A G R A M & S P E C I F I C A T I O N SHEET RE V D E S C R I P T I O N D A T E D B C B R E V I S I O N S NOT TO SCALE 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S C A L I C E N S E # : 8 9 0 8 9 5 ELECT R I C A L E22659 Exp. 03-31-23R EGISTERED P R O F ESSIONAL E N G I NEER STATE OF CA L I F O R NIA DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID CHECKED BY DATE CHECKED CO R A L M T N AL T A V E R D E B U I L D E R S 71 9 0 5 H W Y 1 1 1 S U I T E G LA Q U I N T A , C A L I F O R N I A 9 2 2 1 0 C002231 EOR RA N C H O M I R A G E , C A 9 2 2 7 0 KESPINOZA D-0120496 04-11-2022 04-11-2022 05/02/2022 BCPR2021-0028 CONICAL FLASHING CYLINDRICAL FLASHINGCONDUIT ENTRY / EXIT DETAIL PULLBOX MOUNTING - FLAT ROOF FIGURE 2: WIRING ROOF PENETRATION CROSS SECTION FIGURE 1: ELECTRICAL SIGNAGES/STICKERS SIGNAGE NOTES WARNING POWER SOURCE OUTPUT CONNECTION DO NOT RELOCATE THIS OVERCURRENT DEVICE TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUTDOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM PHOTOVOLTAIC SYSTEM COMBINER PANEL: DO NOT ADD LOADS PHOTOVOLTAIC SYSTEM AC DISCONNECT RATED AC OUTPUT CURRENT: NOMINAL OPERATING AC VOLTAGE: AMPS VOLTS AMPS VOLTS PHOTOVOLTAIC POINT OF INTERCONNECTION WARNING: ELECTIC SHOCK HAZARD. DO NOT TOUCH TERMINALS. TERMINALS ON BOTH THE LINE AND LOAD SIDE MAY BE ENERGIZED IN THE OPEN POSITION. FOR SERVICE DE-ENERGIZE BOTH SOURCE AND MAIN BREAKER PV POWER SOURCE MAXIMUM RATED AC OUTPUT CURRENT: MAXIMUM OPERATING AC VOLTAGE: PHOTOVOLTAIC SYSTEM AC DISCONNECT RATED AC OUTPUT CURRENT: NOMINAL OPERATING AC VOLTAGE: AMPS VOLTS AMPS VOLTS PHOTOVOLTAIC POINT OF INTERCONNECTION WARNING: ELECTIC SHOCK HAZARD. DO NOT TOUCH TERMINALS. TERMINALS ON BOTH THE LINE AND LOAD SIDE MAY BE ENERGIZED IN THE OPEN POSITION. FOR SERVICE DE-ENERGIZE BOTH SOURCE AND MAIN BREAKER PV POWER SOURCE MAXIMUM RATED AC OUTPUT CURRENT: MAXIMUM OPERATING AC VOLTAGE: ( kWDC) ( kWDC) ( kWDC) ( kWDC) POWER TO THIS BUILDING IS ALSO SUPPLIED FROMTHE FOLLOWING SOURCES WITH DISCONNECTSLOCATED AS SHOWN: CAUTION: PHOTOVOLTAICAC DISCONNECT PHOTOVOLTAICARRAY ON ROOF MAIN SERVICEPANEL SOLAR LOADCENTER DRIVEWAY 16/17 MODULES/MICRO-INVERTERSPR-X21-350-BLK-E-AC (240) STANCHIONON RACK (FLAT ROOF) 22.27 240 22.27 240 20.96 240 20.96 240 5.95 5.95 5.60 AC SOLAR DISCONNECT TYPICAL DIRECTORY PLACARD EL E C T R I C A L D E T A I L S SHEET RE V D E S C R I P T I O N D A T E D B C B R E V I S I O N S NOT TO SCALE SP R - X 2 1 - 3 5 0 - B L K - E - A C ( 2 4 0 ) ELECT R I C A L E22659 Exp. 03-31-23R EGISTERED P R O F ESSIONAL E N G I NEER STATE OF CA L I F O R NIA 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S C A L I C E N S E # : 8 9 0 8 9 5 R E V I S I O N S PVE-2 DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID CHECKED BY DATE CHECKED CO R A L M T N AL T A V E R D E B U I L D E R S 71 9 0 5 H W Y 1 1 1 S U I T E G LA Q U I N T A , C A L I F O R N I A 9 2 2 1 0 C002231 D-0120496 04-12-2022 KESPINOZA 04-12-2022 EOR RA N C H O M I R A G E , C A 9 2 2 7 0 05/02/2022 BCPR2021-0028 EL E C T R I C A L D A T A & S P E C I F I C A T I O N S SHEET RE V D E S C R I P T I O N D A T E D B C B R E V I S I O N S NOT TO SCALE FI L E : D- 0 1 1 6 7 6 6 -M P P P - 0 7 2 6 2 0 2 1 - S O L A R - P V E - 4 . d w g , U S E R : k e s p i n o z a , D A T E / T I M E : S e p 1 2 , 2 0 2 1 - 1 1 : 3 1 p m 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S C A L I C E N S E # : 8 9 0 8 9 5 ELECT R I C A L E22659 Exp. 03-31-23R EGISTERE D P R O F ESSIONAL E N G I NEER STATE OF CA L I F O R NIA DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID CHECKED BY DATE CHECKED CO R A L M T N AL T A V E R D E B U I L D E R S 71 9 0 5 H W Y 1 1 1 S U I T E G LA Q U I N T A , C A L I F O R N I A 9 2 2 1 0 C002231 EOR RA N C H O M I R A G E , C A 9 2 2 7 0 KESPINOZA D-0120496 04-11-2022 04-11-2022 INVISIMOUNT DATA SHEET CERTIFICATE OF COMPLIANCE CLASS A FIRE RATING UL LISTING PG 1/3 CLASS A FIRE RATING UL LISTING PG 2/3 CLASS A FIRE RATING UL LISTING PG 3/3 EL E C T R I C A L D A T A & S P E C I F I C A T I O N S SHEET RE V D E S C R I P T I O N D A T E D B C B R E V I S I O N S NOT TO SCALE FI L E : D- 0 1 1 6 7 6 6 -M P P P - 0 7 2 6 2 0 2 1 - S O L A R - P V E - 4 . d w g , U S E R : k e s p i n o z a , D A T E / T I M E : S e p 1 2 , 2 0 2 1 - 1 1 : 5 2 p m 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S C A L I C E N S E # : 8 9 0 8 9 5 ELECT R I C A L E22659 Exp. 03-31-23R EGISTERE D P R O F ESSIONAL E N G I NEER STATE OF CA L I F O R NIA DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID CHECKED BY DATE CHECKED CO R A L M T N AL T A V E R D E B U I L D E R S 71 9 0 5 H W Y 1 1 1 S U I T E G LA Q U I N T A , C A L I F O R N I A 9 2 2 1 0 C002231 EOR RA N C H O M I R A G E , C A 9 2 2 7 0 KESPINOZA D-0120496 04-11-2022 04-11-2022