Estates at Point Happy TR 31348 BCPR2024-0002PLAN SNAPSHOT REPORT BCPR2024-0002
FOR CITY OF LA QUINTA
Building Construction Plan Review 03/06/2024App Date:Plan No.:Plan Type:BCPR2024-0002
City of La QuintaBuilding Construction Plan Review 03/06/2025Exp Date:District:Work Class:
0.00Expired NOT COMPLETEDCompleted:Square Feet:Status:
Description:
Valuation:
POINT HAPPY / SOLAR PHOTOVOLTAIC MASTER PLANS FOR PLAN TYPES 1, 1X, & 2 FOR THE
2022 CODE CYCLE. INDIVIDUAL PERMITS TO BE ISSUED FOR EACH ADDRESS. 2022 CALIFORNIA
BUILDING CODES.
ALL PLAN TYPES: 6.08kW SOLAR ARRAY w/ 10kWh E.S.S. - (15) 405W Q.PEAK DUO BLK
ML-G10+ MODULES W/ IQ7HS-66-M-US MICROINVERTERS + ENPHASE IQ COMBINER 5C PANEL, (2)
5kWh ENPHASE 5P BATTERIES + IQ SYSTEM CONTROLLER 3 [300SF]. SOLAR ARRAY TO BE
ORIENTED BETWEEN 105°-300° AZIMUTH.
$0.00 Assigned To:Approval
Expire Date:NOT AVAILABLE
Parcel:Main643240044 Address:Point Happy
Main Zone:
Applicant
SunPower Corporation
Systems
1414 HARBOUR WAY SOUTH
#1901 RICHMOND, CA 94804
Applicant
Amy Clemans
1414 HARBOUR WAY S SUITE
1901 RICHMOND, CA 94804
Applicant
Tim Witz - SUNPOWER
25092 Pappas Rd Ramona, CA
92065
Plan Custom Fields
Tract / Subdivision
Name
Point Happy Tract Number 31348 Model/Series Name 1, 1X, 2
Number of Plan Types 3 Other Notes Code Edition 2022
Specific Plan Number Image Corridor Sound Corridor
Is this a revision?No Zoning RL General Plan ROW
City Limits Within La Quinta City
Limits
Acreage 2.3 Subdivision Name TR 31348 AMEND
Lot Number I Legal Description Lot I MB 390/1 TR 31348
AMEND
Centerlines 88528, 87924, 88204,
88526, 87927, 88529,
87925, 87928, 87929,
87926
Lot Size 13510.9
Attachment File Name Added On Added By Attachment Group Notes
Signature_Amy_Clemans_3/6/2024.jpg 03/06/2024 15:57 Clemans, Amy Uploaded via CSS
BCPR2024-0002 - 2ND REVIEW
CORRECTION LIST.pdf
05/03/2024 11:51 Fuson, Jake Available Online
TAKEOFF SHEETS.pdf 06/25/2024 15:27 Fuson, Jake
SOLAR MASTER PLAN PC4_v4.pdf 06/25/2024 15:46 Fuson, Jake Available Online Construction Plan Set
Created ByNote Date and Time Created
Page 1 of 378-495 Calle TampicoMarch 24, 2025
PLAN SNAPSHOT REPORT (BCPR2024-0002)
1.Elizabeth MolinaFrom: Elizabeth Molina
Sent: Friday, May 3, 2024 1:42 PM
To: Amy.Clemans@sunpower.com;
Tim.Witz@sunpowercorp.com;
Permitting.Ontario@sunpowercorp.com
Subject: BCPR2024-0002 (POINT HAPPY)
Hello,
The status of your permit was updated to ‘Revisions
Requested’. Please login to the HUB Online Portal to access the
correction list for the completed review.
Thank you,
05/03/2024 13:41
Invoice No.Amount PaidFeeFee Amount
INV-00007516 $366.00 Hourly Charge - City Building Staff $366.00
$8.00 Technology Enhancement Fee $8.00
$23.00 Digital Archiving and Records Management Fee $23.00
$397.00 $397.00 Total for Invoice INV-00007516
Grand Total for Plan $397.00 $397.00
Submittal Name Status Received Date Due Date Complete Date Resubmit Completed
Requires Re-submitBuilding Review v.1 03/07/2024 03/14/2024 03/12/2024 Yes Yes
Completed
Date
Due
Date
Assigned
DateStatusAssigned UserDepartmentItem Review Name
Building (1WK)Building Fuson, Jake Revisions Required 03/07/2024 03/14/2024 03/12/2024
Comments: PC1
Correction Type Category Corrective ActionComments Resolved Create
Date
Resolved
Date
Building Review -
Correction
Building Review -
Correction
See attached 1st Review
Correction List.
No 03/12/2024
Submittal Name Status Received Date Due Date Complete Date Resubmit Completed
Requires Re-submitBuilding Review v.2 03/25/2024 04/01/2024 04/11/2024 Yes Yes
Completed
Date
Due
Date
Assigned
DateStatusAssigned UserDepartmentItem Review Name
Building (1WK)Building Fuson, Jake Revisions Required 03/25/2024 04/01/2024 04/11/2024
Comments: See "Corrections" tab.
Correction Type Category Corrective ActionComments Resolved Create
Date
Resolved
Date
Building Review -
Correction
Building Review -
Correction
1)The DC system size of
the proposed array does not
match the system modeled in
the approved energy report
for Plan 2, which is modeled at
6.16kW. Please revise array
system size to match what
was approved with the
energy modeling for this home.
The most recent approved
energy documents still show
6.16kW minimum system size
for Plan 2.
2)Each ESS disconnecting
means shall plainly indicate
whether it is in the open (off)
or closed (on) position and be
permanently marked "ENERGY
STORAGE SYSTEM
DISCONNECT." The
disconnecting means shall be
legibly marked in the field to
No 04/11/2024
Page 2 of 378-495 Calle TampicoMarch 24, 2025
PLAN SNAPSHOT REPORT (BCPR2024-0002)
indicate the nominal ESS ac
voltage and maximum ESS dc
voltage. Please add this
signage to the plans. (CEC
706.15(C)) Please indicate the
field marking of the ESS
disconnect to include the
nominal ac voltage and
maximum dc voltage.
Submittal Name Status Received Date Due Date Complete Date Resubmit Completed
CanceledBuilding Review v.3 04/16/2024 04/23/2024 05/03/2024 Yes Yes
Completed
Date
Due
Date
Assigned
DateStatusAssigned UserDepartmentItem Review Name
Building (1WK)Building Fuson, Jake Revisions Required 04/16/2024 04/23/2024 05/03/2024
Comments: See attached 2nd Review Correction List.
Correction Type Category Corrective ActionComments Resolved Create
Date
Resolved
Date
Building Review -
Correction
Building Review -
Correction
See attached 2nd Review
Correction List.
No 04/16/2024
Submittal Name Status Received Date Due Date Complete Date Resubmit Completed
ApprovedBuilding Review v.4 05/22/2024 05/29/2024 06/25/2024 No Yes
Completed
Date
Due
Date
Assigned
DateStatusAssigned UserDepartmentItem Review Name
Building (1WK)Building Fuson, Jake Approved 05/22/2024 05/29/2024 06/25/2024
Correction Type Category Corrective ActionComments Resolved Create
Date
Resolved
Date
Building Review -
Correction
Building Review -
Correction
See attached 2nd Review
Correction List.
Yes 05/22/2024 06/25/2024
Workflow Step / Action Name Action Type Start Date End Date
Plan Check v.1 06/25/2024 15:46
Building Review v.1 Receive Submittal 03/07/2024 0:00 03/12/2024 15:53
Building Review v.2 Receive Submittal 03/25/2024 0:00 04/11/2024 12:14
Building Review v.3 Receive Submittal 04/16/2024 0:00 05/03/2024 13:40
Building Review v.4 Receive Submittal 05/22/2024 0:00 06/25/2024 15:46
Linked Records v.1
Linked Permits v.1 Create Sub Permit
Page 3 of 378-495 Calle TampicoMarch 24, 2025