Washington Street Apartments TR 12323 BCPR2017-0001 Phase 1Project Details PROJECT NUMBER
owsw lit"of La Qu i nta
BCPR2017-0001
O F Tt�"
Description: WASHINGTON STREET APARTMENTS / PHASE 1
Status: ARCHIVED
DAYS
REVIEWS 12
ACTIONS 3
INSPECTIONS
Type: BUILDING CONSTRUCTION PLAN REVIEW (WEB)
Status Date: 12/6/2017
Subtype: OTHER CONSTRUCTION
Applied: 6/22/2017
Address: WSA PH 1
Approved: 2/10/2018
City, State, Zip: LA QUINTA,CA92253
Closed:
Project Manager: AJ ORTEGA
Expired:
Details: WASHINGTON STREET APARTMENTS PHASE 1 OF CONSTRUCTION PLAN REVIEW -
INCLUDES NEW UNITS, REMODELED UNITS, COMMONS AND LAUNDRY
STRUCTURES
CONDITIONS
REVISION 1- REVISED FOUNDATION DESIGN AT PERIMETER PATIO FOOTINGS AND
SCREEN FENCE WALLS.
REVISION 2 - ADD SEPARATELY METERED 100A HOUSE PANELS AT EACH
RENOVATED BUILDING TO SERVE COMMON LOADS
CASE OPEN
OPEN
COMPLETED
CHRONOLOGY TYPE
STAFF NAME
ACTION DATE
COMPLETION DATE
NOTES
EMAIL RECEIVED FROM VINCE ROSATO
(VROSATO@STUDIOEARCHITECTS.COM) STATING THE
2ND PC SUBMITTAL
AJ ORTEGA
6/22/2017
7/13/2017
ENERGY DOCUMENTS HAVE BEEN UPLOADED, PROJECT HAS
RECEIVED
BEEN DETERMINED COMPLETE AND REVIEWS HAVE BEEN
CREATED
E TRAKIT RESUBMITTAL BY VINCE. pHASE 1 & 2 WERE IN
2ND PC SUBMITTAL
BURT HANADA
12/6/2017
12/6/2017
ATTACHMENTS, ARMANDO RELOCATED PHASE 2 INTO
RECEIVED
bcpr2017-0002.
EMAIL
BURT HANADA
12/27/2017
12/27/2017
notified applicant that outstanding corrections remain.
•
•
Printed: Monday, March 20, 2023 10:50:36 AM 1 of 8 CENTRALSQUARE
Project Details PROJECT NUMBER
-ows� City of La Quinta BCPR2017-0001
NAME TYPE
NAME
ADDRESSI
CITY
STATE
ZIP
PHONE
FAX
EMAIL
APPLICANT
STUDIO E ARCHITECTS
2258 FIRST AVENUE
SAN DIEGO
CA
92101
vrosato@studioearchit
ects.com
ARCHITECT
STUDIO E ARCHITECTS
2258 FIRST AVENUE
SAN DIEGO
CA
92101
vrosato@studioearchit
ects.com
CITY STAFF
AJ ORTEGA
78495 CALLE TAMPICO
LA QUINTA
CA
92253
aortega@la-quinta.org
CONTRACTOR
SUN COUNTRY BUILDERS INC DBA
SUN COUNTRY
138 CIVIC CENTER
DRIVE #204
VISTA
CA
92084
cmachinski@suncountr
ybuilders.net
DEVELOPER
RAY CARDINALE (CVHC)
45701 MONROE ST, STE
G
INDIO
I
CA
I
92201
I I
I
RAY.CARDINALE@CVH
IC.ORG
OWNER
REDEVELOPMENT AGENCY CITY OF
P O BOX 1504
LA QUINTA
CA
92203
�
�*p
DESCRIPTION
ACCOUNT
CITY
AMOUNT
7
PAID
PAID DATE
RECEIPT #
CHECK #
METHOD
PAID BY
CLTD
BY
HOURLY CHARGE - CITY
BUILDING STAFF
101-0000-42600
0.75
$120.00
$0.00
Total Paid for BUILDING STAFF - PER HOUR: $120.00 $0.00
I 1110F
INSPECTION TYPE
INSPECTOR
SCHEDULED
DATE
COMPLETED RESULT REMARKS
DATE
NOTES
REVIEW TYPE
REVIEWER
SENT DATE
DUE DATE
RETURNED
DATE
01
STATUS
REMARKS
NOTES
1ST BLDG (1WK)
JAKE FUSON
10/18/2018
10/23/2018
11/6/2018
APPROVED
REVISION 2: HOUSE
METERS
REVISION 2 - ADD SEPARATELY METERED 100A
HOUSE PANELS AT EACH RENOVATED BUILDING
TO SERVE COMMON LOADS.
Printed: Monday, March 20, 2023 10:50:36 AM 2 of 8 �4' CENTRALSQUARE
Project Details PROJECT NUMBER
-ows� City of La Quinta BCPR2017-0001
REVISION 1 - REVISED FOUNDATION DESIGN AT
1ST BLDG (1WK)
JAKE FUSON
6/13/2018
6/20/2018
6/13/2018
APPROVED
REVISION 1
PERIMETER PATIO FOOTINGS AND SCREEN FENCE
WALLS.
1ST BLDG NS (3WK)
BURT
7/13/2017
8/3/2017
8/2/2017
REVISIONS REQUIRED
COORDINATION
HANADA
REVIEW
1ST BLDG STR (2WK)
KURT CULVER
7/13/2017
7/27/2017
7/24/2017
REVISIONS REQUIRED
COMPLETE REVIEW
Prior to construction, applicant/developer shall
furnish two copies of the water system fire
hydrant plans to Fire Department for review and
approval. Plans shall be signed by a registered
civil engineer, and shall confirm hydrant type,
location, spacing, and minimum fire flow. Once
1ST FIRE (2WK)
RONALD
7/13/2017
7/27/2017
7/25/2017
READY FOR APPROVAL
SEE Conditions
plans are signed and approved by the local water
GRIESINGER
authority, the originals shall be presented to the
Fire Department for review and approval.
Prior to issuance of building permits, the water
system for fire protection must be provided as
approved by the Fire Department and the local
water authority.
1ST PLANNING
CARLOS
7/13/2017
7/27/2017
7/26/2017
READY FOR APPROVAL
(2WK)
FLORES
APPLICANT SHALL SUBMIT SEPARATE PLAN
CHECK APPLICATION AND PRECISE GRADING
1ST PUBLIC WORKS
AMY YU
7/13/2017
7/27/2017
7/27/2017
PENDING DOCUMENTS
PLAN FOR REVIEW.
STILL NEED PAD CERT AND COMPACTION FOR
(2WK)
BUILDING K, PHASE 1 COMMON AREA BUILDING,
AND PHASE 1 LAUNDRY
2ND BLDG NS (2WK)
BURT
12/6/2017
12/27/2017
12/27/2017
REVISIONS REQUIRED
COORDINATION
HANADA
REVIEW
COMPLETE REVIEW
2ND BLDG STR
(2WK)
KURT CULVER
12/6/2017
12/20/2017
2/2/2018
READY FOR APPROVAL
COMPLETE REVIEW
Remaining comments added to Response Letter
(not on plans).
Printed: Monday, March 20, 2023 10:50:36 AM 3 of 8 CENTRALSQUARE
Project Details PROJECT NUMBER
-ows� City of La Quinta BCPR2017-0001
2ND FIRE (3WK)
RONALD
12/6/2017
12/18/2017
12/12/2017
READY FOR APPROVAL
2 WK REVIEW
See conditions from 1st review
GRIESINGER
2ND PLANNING
CARLOS
12/6/2017
12/18/2017
12/14/2017
NOT REQUIRED
(2WK)
FLORES
3RD BLDG NS (2WK)
AJ ORTEGA
1/29/2018
2/12/2018
2/10/2018
APPROVED
INDIVIDUAL PERMITS CREATED
BOND INFORMATION
Attachment Type
CREATED
OWNER
DESCRIPTION
PATHNAME
SUBDIR
ETRAKIT ENABLED
SCHOOL FEE LETTER -
DOC
6/27/2018
ARMANDO MAGALLON
SCHOOL FEE LETTER -
WASHIGTON ST
0
WASHIGTON ST APTS
APTS.pdf
BCPR2017-0001 - 1ST
1ST SUBMITTAL ENERGY
DOC
7/13/2017
AJ ORTEGA
CALCULATIONS
SUBMITTAL ENERGY
0
(AMENITIES)
CALCULATIONS
(AMENITIES).pdf
BCPR2017-0001 - 1ST
DOC
7/13/2017
AJ ORTEGA
1ST SUBMITTAL PLAN
SUBMITTAL PLAN SET
0
SET (WITH ENERGY)
(WITH ENERGY).pdf
BCPR2017-0001 - 1ST
1ST SUBMITTAL
DOC
7/13/2017
AJ ORTEGA
STRUCTURAL
SUBMITTAL
0
STRUCTURAL
CALCULATIONS
CALCULATIONS.pdf
BCPR2017-0001 -
DOC
3/19/2018
AJ ORTEGA
ENERGY CALCULATIONS
ENERGY CALCULATIONS
1
(APPROVED)
(APPROVED).pdf
DOC
3/19/2018
AJ ORTEGA
PLAN SET (APPROVED)
BCPR2017-0001 - PLAN
1
SET (APPROVED).pdf
BCPR2017-0001 -
STRUCTURAL
DOC
3/19/2018
AJ ORTEGA
CALCULATIONS
STRUCTURAL
1
(APPROVED)
CALCULATIONS
(APPROVED).pdf
Printed: Monday, March 20, 2023 10:50:36 AM 4 of 8 CENTRALSQUARE
Project Details PROJECT NUMBER
-ows� City of La Quinta BCPR2017-0001
Attachment Type
CREATED
OWNER
DESCRIPTION
PATHNAME
SUBDIR
ETRAKIT ENABLED
BCPR2017-0001 -
REVISION 2 - 1ST
DOC
10/19/2018
AJ ORTEGA
SUBMITTAL ELECTRICAL
REVISION 2 - 1ST
1
SUBMITTAL ELECTRICAL
PLAN
PLAN.pdf
BCPR2017-0001 -
REVISION 2 - 1ST
DOC
10/19/2018
AJ ORTEGA
SUBMITTAL
REVISION 2 - 1ST
1
SUBMITTAL
TRANSMITTAL
TRANSMITTAL.pdf
BCPR2017-0001 1ST
DOC
8/9/2017
BURT HANADA
1ST REVIEW MARKUP
REVIEW MARKUP
0
SUMMARY.pdf
SUMMARY.pdf
BCPR2017-0001 - 2ND
2ND SUBMITTAL
REVIEW REDLINED
DOC
12/27/2017
BURT HANADA
OUTSTANDING
RESPONSE LETTER -
0
CORRECTIONS LIST
WSA PHASE 2 -
CoLQ.pdf
DOC
12/6/2017
EtrakitContractor
SOILS REPORT
BCPR2017-0001 - SOILS
1
REPORT.pdf
17-1205 WSA_Planning
DOC
12/6/2017
EtrakitContractor
2ND SUBMITTAL PLAN
Plan Check
0
CHECK RESPONSES
Responses —Phase 1 -
CoLQ.pdf
17-1205 WSA_Permit
DOC
12/6/2017
EtrakitContractor
2ND SUBMITTAL PLAN
Submittal 1_Phase 1
0
SET (PHASE 1)
(Complete).pdf
18-0129 WSA_Planning
3RD SUBMITTAL -
DOC
1/29/2018
EtrakitContractor
RESPONSE LETTER
Plan Plan Check
h Ceck
0
Responses 1 -
(PHASE 1)
Col-Q (Arch).pdf
18-0129 WSA_Permit
DOC
1/29/2018
EtrakitContractor
3RD SUBMITTAL PLAN
Submittal 3—Phase 1
0
SET (PHASE 1)
(Complete).pdf
Printed: Monday, March 20, 2023 10:50:36 AM 5 of 8 CENTRALSQUARE
Project Details PROJECT NUMBER
-ows� City of La Quinta BCPR2017-0001
Attachment Type
CREATED
OWNER
DESCRIPTION
PATHNAME
SUBDIR
ETRAKIT ENABLED
PLAN CHANGE -
19-0823 WSA (Phase 1) -
DOC
8/22/2019
EtrakitContractor
REVISED MOBILITY
Plan Change Submittal
1
UNITS
(Revised Moblity).pdf
BCPR2017-0001 -
REVISION 1 - REVISED
REVISION 1 - REVISED
DOC
6/13/2018
JAKE FUSON
FOUNDATION DETAIL
FOUNDATION DETAIL
1
AT PATIO SCREEN FENCE
AT PATIO SCREEN FENCE
WALLS
WALLS.pdf
BCPR2017-0001 -
REVISION 1 -
DOC
6/13/2018
JAKE FUSON
STRUCTURAL
REVISION 1 -
1
STRUCTURAL
CALCULATIONS
CALCULATIONS.pdf
BCPR2017-0001 - RFI -
DOC
7/16/2018
JAKE FUSON
RFI - REVISED PARTY
REVISED PARTY WALL
1
WALL DETAIL
DETAIL.pdf
BCPR2017-0001 - RFI -
RFI - CLARIFICATION OF
CLARIFICATION OF
DOC
7/16/2018
JAKE FUSON
NAILING AND BLOCKING
NAILING AND BLOCKING
1
AT ROOF DIAPHRAGMS
AT ROOF DIAPHRAGMS
ON RENOVATED UNITS
ON RENOVATED
UNITS.pdf
BCPR2017-0001 -
NOTICE OF PRODUCT
NOTICE OF PRODUCT
DOC
7/25/2018
JAKE FUSON
NAME CHANGE
NAME CHANGE
1
REGARDING 1-HOUR
REGARDING 1-HOUR
RATED WALLS
RATED WALLS.pdf
BCPR2017-0001 - RFI -
RFI - FRAMING AT
DOC
9/18/2018
JAKE FUSON
THERMAL CHIMNEYS AT
FRAMING AT THERMAL
1
CHIMNEYS AT
RENOVATION UNITS
RENOVATION UNITS.pdf
Printed: Monday, March 20, 2023 10:50:36 AM 6 of 8 CENTRALSQUARE
Project Details PROJECT NUMBER
-ows� City of La Quinta BCPR2017-0001
Attachment Type
CREATED
OWNER
DESCRIPTION
PATHNAME
SUBDIR
ETRAKIT ENABLED
STRUCTURAL
BCPR2017-0001- PHASE
DOC
9/18/2018
JAKE FUSON
OBSERVATION - PHASE
1 STRUCTURAL
1
1ONLY
OBSERVATION.pdf
BCPR2017-0001 - RFI -
RFI - FURRED CEILING
DOC
9/18/2018
JAKE FUSON
FRAMING AT
FURRED CEILING
1
FRAMING AT
RENOVATED UNITS
RENOVATED UNITS.pdf
BCPR2017-0001 - RFI -
RFI - ACCEPTABLE BOLTS
DOC
9/18/2018
JAKE FUSON
AT WOOD STRONG
ACCEPTABLE BOLTS AT
1
WOOD STRONG
WALLS
WALLS.pdf
BCPR2017-0001 - RFI -
DOC
9/19/2018
JAKE FUSON
RFI - ADDITIONAL LAYER
ADDITIONAL LAYER OF
1
OF OSB AT ROOFS
OSB AT ROOFS.pdf
BCPR2017-0001 -
REVISION 2 -
DOC
11/6/2018
JAKE FUSON
ELECTRICAL PLAN
REVISION 2 -
1
ELECTRICAL PLAN
(APPROVED)
(APPROVED).pdf
BCPR2017-0001 -
LETTER OF APPROVAL
LETTER OF APPROVAL
DOC
11/28/2018
JAKE FUSON
OF PARALLEL CURB
OF PARALLEL CURB
1
RAMP DESIGN BY CIVIL
RAMP DESIGN BY CIVIL
ENGINEER
ENGINEER.pdf
BCPR2017-0001 -
LETTER OF APPROVAL
LETTER OF APPROVAL
DOC
11/28/2018
JAKE FUSON
OF PARALLEL CURB
OF PARALLEL CURB
1
RAMP DESIGN CIVIL
RAMP DESIGN BY CIVIL
ENGINEERR
ENGINEER_1.pdf
PRELIMINARY LETTER
DOC
12/3/2018
JAKE FUSON
OF APPROVAL FROM
LETTER OF APPROVAL
1
HERS RATER -
FROM HERS RATER.pdf
BUILDINGS B, C and D
Printed: Monday, March 20, 2023 10:50:36 AM 7 of 8 CENTRALSQUARE
Project Details PROJECT NUMBER
-ows� City of La Quinta BCPR2017-0001
Attachment Type
CREATED
OWNER
DESCRIPTION
PATHNAME
SUBDIR
ETRAKIT ENABLED
BCPR2017-0001 - RFI -
RFI - ADDED ROOF
DOC
12/18/2018
JAKE FUSON
BEAMS TO SUPPORT
ADDED ROOF BEAMS
1
TO SUPPORT HIGH
HIGH RAFTERS
RAFTE RS. pdf
BCPR2017-0001 - 1ST
DOC
7/31/2017
KURT CULVER
1ST REVIEW PLAN SET
REVIEW PLAN SET
0
(REDLINED)
(REDLINED).pdf
Printed: Monday, March 20, 2023 10:50:36 AM 8 of 8 CENTRALSQUARE
G,Dc�,odGau�
FOR HIGHER QUALITY BUILDINGS '(6
(Transmitted Electronically)
November 28, 2018
Mr. Jame Wiatrak
Building Official & ADA Coordinator
City of La Quinta
78-495 Calle Tampico
La Quinta, California 92253
Dear Mr. Wiatrak
After reviewing the first three (3) buildings at Washington Street Apartments, it was determined that all
required HERS verifications in Buildings B, C, and D passed today. Based on the current installation and reporting
completed to date, there are no foreseeable impediments for results of buildings being tested going forward.
While all remaining buildings will be tested, we submit this letter with the assumption that the installation and
reporting from the general contractor (or General Contractor's subcontractor) will remain consistent with the
aforementioned buildings.
Sincerely,
r_ I
X41O 4
Bing Guerin, LEED AP BD+C, Green Rater, GPR, HERS, PMP
Associate Principal
213.455.3311 •8695 WASHINGTON BLVD #205 CULVER CITY CA 90232 • 624 BROADWAY #406 SAN DIEGO CA 92101
CERTIFICATE OF COMPLIANCE
Desert Sands Unified School District o c o
y y
47950 Dune Palms Road BEHu1J0AD A
r
r Cnr4 'ifiiae
Date: 6/27/2018 La Quinta, CA 92253 $. gA !NTI A' y
No.: 18-01013-1 (760)771-8515 o 1 .0 y
Owner: CVHC - WASHINGTON STREET APARTMENTS Email:
Address: 45-701 Monroe Street, Ste G Jurisdiction: La Quinta
City: Indio Tract #: Phase 1 and Phase 2
Type: Senior Residence
Lot #
Street No.
Street Name
Sq. Feet
APN Permit No.
Building K
42-800
Washington St
2788
609-040-007
Building L
42-800
Washington St
5595
609-040-007
Building M
42-800
Washington St
4183
609-040-007
Building N
42-800
Washington St
4223
609-040-007
Building Laundry/Maintenance
42-800
Washington St
966
609-040-007
Building Q
42-800
Washington St
4223
609-040-007
Building S
42-800
Washington St
4223
609-040-007
Building T
42-800
Washington St
4932
609-040-007
Building Commons
42-800
Washington St
1100
609-040-007
Building Commons
42-800
Washington St
2567
609-040-007
Building O
42-800
Washington St
4932
609-040-007
Building P
42-800
Washington St
5595
609-040-007
Building R
42-800
Washington St
5595
609-040-007
Building Commons
42-800
Washington St
2484
609-040-007
Comments:
At the present time, the Desert Sands Unified School District does not collect fees on garages/carports, covered patios/walkways, residential additions
under 500 square feet, detached accessory structures (spaces that do not contain facilities for living, sleeping, cooking eating, or sanitation) or replacement
mobile homes. It has been determined that the above -named owner is exempt from paying school fees at this time due to the following reason:
Senior Citizen Rate EXEMPTION NOT APPLICABLE
This certifies that school facility fess imposed pursuant to
Education Code Section 17620 and Government Code 65995 Et Seq.
in the amount of $0.56 X 53406 S.F. or $29,907.36 have been paid for the property listed above and that building
permits and/or Certificates of Occupancy for this square footage in the proposed project may now be issued.
Fees Paid By: CC/Bank of America/Kenny Rodgers Check No.: 0846811029
Bank Name/Recipient of Certificate Telephone: 760-347-3157
Funding: Senior
By Scott L. Bailey
Superintendent
Fee Collected/ Exempted by: Arianne Catano Certificate Fees Due.: $29,907.36
n Original Payme,ijs) Rec'd: $0.00
New Payment Rec'!d: $29,907.36
Over/Under: $0.00
-NOTICE: Pursuant to Government Code Section 66020(d)(1), this will serve to notify you that the 90-day approval period In which you may protest the fees or
other payment Identified above will begin to run from the date on which the building or Installation permit for this project Is Issued, or from the date on
which those amounts are paid to the District(s) or to another public entity authorized to collect them on the Distrlct('s) behalf, whichever Is earlier.
Notice to Building Department: THIS DOCUMENT VALID ONLY IF IMPRINTED WITH EMBOSSED SEAL.
CERTIFICATE OF COMPLIANCE
Desert Sands Unified School District
47950 Dune Palms Road
Date: 6/27/2018 La Quinta, CA 92253
No.: 18-01014-1 (760)771-8515
Owner: CVHC - WASHINGTON STREET APARTMENTS Email:
Address: 45-701 Monroe Street, Ste G
City: Indio
Type: Single Family Residential
Lot #
Building K Management Unit
Building L Management Unit
Comments:
Street No. Street Name
42-800 Washington St
42-800 Washington St
Management Units
Cy J�1Fyo
0
BERMUIDDA DUNES
Y RINCOOIC, IAN EWgEELLS y
ACCHAi �Y
LA tlUINYA
p INDIo y
Jurisdiction: La Quinta
Tract #: Phase 1 and Phase 2
Sq. Feet APN Permit No.
1331 609-040-007
1180 609-040-007
At the present time, the Desert Sands Unified School District does not collect fees on garages/carports, covered patios/walkways, residential additions
under 500 square feet, detached accessory structures (spaces that do not contain facilities for living, sleeping, cooking eating, or sanitation) or replacement
mobile homes. It has been determined that the above -named owner is exempt from paying school fees at this time due to the following reason:
EXEMPTION NOT APPLICABLE
This certifies that school facility fess imposed pursuant to
Education Code Section 17620 and Government Code 65995 Et Seq.
in the amount of $3.48 X 2511 S.F. or $8,738.28 have been paid for the property listed above and that building
permits and/or Certificates of Occupancy for this square footage in the proposed project may now be issued.
Fees Paid By: CC/Bank of America/Kenny Rodgers Check No.: 0846811029
Bank Name/Recipient of Certificate Telephone: 760-347-3157
Funding: Residential
By Scott L. Bailey
Superintendent
Fee Collected/ Exempted by: Arianne Catano $8,73g 28
Certificate Fees Due:
Original Payment(s) Rec'd: $0.00
New Payment Rec'd: $8,738.28
Over,/Under: $0.00
NOTICE: Pursuant to Government Code Section 66020(d)(1), this will serve to notify you that the 90-day approval period in which you may protest the fees or
other payment identified above will begin to run from the date on which the building or installation permit for this project is issued, or from the date on
which those amounts are paid to the District(s) or to another public entity authorized to collect them on the District('s) behalf, whichever is earlier.
Notice to Building Department: THIS DOCUMENT VALID ONLY IF IMPRINTED WITH EMBOSSED SEAL.
�Tli
���• . pis � :�` �4
Request for Information 110-RO01
Detailed, RFIs Grouped by RFI Number
Washington Street Apartments -Phase 1 Project # 18-WASH 1
42-800 Washington Street Tel: Fax:
La Quinta, CA 92203
110-RO01 Date Created: 9/14/2018
Answer Company Answered By Author Company Authored By
Studio E Architects Vince Rosato Sun Country Builders Ken Kosman
2258 First Avenue 138 Civic Center Dr., #204
San Diego, CA 92101 Vista, CA 92084
Co -Respondent
Subject
Discipline
Strong Wall Anchor Bolts
Cc: Company: Name
Contact Name
Sun Country Builders
Andy Kroneberger
Sun Country Builders
Brian Wardwell
Sun Country Builders
Bruce Laiho
Sun Country Builders
DeAnna Parry
Studio E Architects
Eric Naslund
Sun Country Builders
Jay Stehlik
Sun Country Builders
Jim Watson
Sun Country Builders
Justin Vining
Sun Country Builders
Ken Kosman
Coachella Valley Housing Coalition Kenneth Rodgers
Coachella Valley Housing Coalition MaryAnn Ybarra
Coachella Valley Housing Coalition Ray Cardinale
Studio E Architects
Vince Rosato
RF
Copies Notes
1
1
1
1
1
1
1
1
Category
Question
Sheet S-Y1.0 shows SSTB28 ABs for the Simpson Shear Walls in the Laundry Room. The framer went with the
associated WSW -AB anchor bolts called out in the Simpson catalog. Building L is the same situation. The Building
Inspector saw SSTB28s specified as noted on plans and required us to install the SSTB28s in order to pour building M
slab. We need to confirm which anchor bolts to use in the future and need acceptance of the previously installed anchor
bolts.
Suggestion
Answer Date Answered:
WSW-ABs can be used in lieu of the SSTBs, provided the minimum embedment depth and edge distance are
maintained as shown on the manufacturer's drawings. See details 1/WSW1 and 21WSW1.
For WSW-AB1 bolts, W(min) = 31", de (min) =11".
Tanya Wei
TKJ Structural Engineering
-Prolog Manager Printed on: 9/14/2018 Prolog8 Page 1
The
Altuvri
Group
November 26, 2018
73-710 Fred Waring Dr., Ste. 219
Palm Desert, CA 92260
760.346.4750 Tel
760.340.0089 Fax
Building Official
Design and Development Department
City of La Quinta
78-495 Calle Tampico
La Quinta, CA 92253
RE: C1047 WEASHINGTON STREET APARTMENTS — DETECTABLE WARNING SURFACE DESIGN
To whom it may concern:
The placement of the detectable warning surface panels on curb ramps at the Washington
Street Apartment project as depicted on Detail 7 of the approved Phase I Precise Grading plan
set has my approval as an acceptable alternate placement. It is my intent that the detectable
panel surface extend only to the limit of the curb ramp to back of curb as shown on the detail in
order to avoid any conflict with the adjacent pavement surface or gutter flowline.
Si
Ja'Mhtsa, PE
Chief nrineer
The Altum Group
iames.bazua@thealtumgroup.com
(760) 346-4750
NO g63p4
Em.l2/31/14
4t
E-�
www.thealtumgroup.com
CertainTeed
SAINT-GOBAIN
December 12, 2017
Subject: ProRoco name change
To Whom It May Concern:
This is to advise that CertainTeed Gypsum changed the brand names of its paper faced gypsum
board products and finishing products for marketing purposes to leverage the recognition of the
CertainTeed name. The previous ProRoco Brand name was changed to CertainTee&'. There
were no product manufacturing changes made to any product formulations or manufacturing
processes as this was only a brand name change.
Please contact the Marketing Technical Services Department at 1-800-446-5284 if you
require additional information.
Regards,
n r
.
Mitchell Schittler, LEED APO BD+C
Manager, Marketing Technical Services
fTfTrr,
E
IN r-GOB��,IN
�0
CertslnTeed Gypsum
760 E. Swedesfoid Road • PO Box 860 • Valley Forge, PA 19482-0106 • USA • Tel; 1.610.341.7000 • www.cartalnteed.com
CertalnTeed Gypsum, Inc.
CertainTeed
SAINT-GOBAIN
October 18, 2013
To Whom It May Concern:
Subject: CertainTeed Gypsum Product Brand Name Change
This is to advise that CertainTeed Gypsum is in the process of changing the Brand
names of its paper faced gypsum board products and finishing products for marketing
purposes to leverage the recognition of the CertainTeed name. The previous ProRoc
Brand name is being changed to CertainTeed. An example of this Brand name change
is given below:
Previous Product Name
ProRoc Type X Gypsum Board
ProRoc One All Purpose
New Product Name
CertainTeed Type X Gypsum Board
CertainTeed One All Purpose
During the 2012-2013 transition period the ProRoc name may appear in product data
sheets or on the CertainTeed.com website while other items such as the board end
tapes reflect the new CertainTeed name. Third -party product certifications and listings
are also being changed to the CertainTeed name with many such as the UL Fire
Resistance Directory covering fire -rated Type X and Type C gypsum board products
recently completed.
We apologize for the product name confusion during this period, however, no changes
are being made to any product formulations or manufacturing processes.
Please contact the Marketing Technical Services Department at 1-800-233-8990 if you
require additional information.
Regards,
C
U 1
Douglas, C. Gehring, P.E., CSI, LEED Green Associate
Director, Marketing Technical Services
SA N" i O13AIN
CertalnTeed Gypsum
4300 W. Cypress Street • Suite 500 - Tampa, FL 33607 • USA • Tel: 1,813,286.3900 • Fax: 1.813.286.3991 • www.certainteed.com
CertainTeed Gypsum, Inc.
GA-600-2009 FIRE RESISTANCE DESIGN MANUAL
75
GA FILE NO. WP 5017
PROPRIETARY*
GYPSUM WALLBOARD, STEEL STUDS,
GLASS FIBER INSULATION
CHASE WALLS, NONCOMBUSTIBLE
One layer 5/e" proprietary type X gypsum wallboard or gypsum veneer base applied parallel
or at right angles to ONE SIDE of a double row of 2112" 25 gage steel studs 24" o.c. and
not less than 1" apart with 1" Type S drywall screws 8" o.c.
OPPOSITE SIDE: One layer 5/8" proprietary type X gypsum wallboard or gypsum veneer
base applied parallel or at right angles to studs with 1" Type S drywall screws 8" o.c.
Optional insulation in the cavity.
Vertical joints centered over studs and staggered one stud cavity on opposite sides of
studs, Horizontal joints on opposite sides need not be staggered or backed, Lateral
bracing on both sides of the wall not less than 5 feet on center vertically.
Sound tested with 31/2" glass fiber insulation friction fit on one side in cavity. (NLB)
PROPRIETARY GYPSUM BOARD
CertainTeed Gypsum Inc. - 5/e" ProRoc@ Type X Gypsum Panels
GA-600-2009 FIRE RESISTANCE DESIGN MANUAL
and partitions) shall not be permitted to be arbitrarily
used in a horizontal orientation.
14. Metal studs and runners are nominal 25 gage
unless otherwise specified.
15. Greater stud sizes (depths) shall be permitted to be
used in metal- or wood -stud systems. Metal studs of
heavier gage than those tested shall be permitted.
The assigned rating of any load -bearing system
shall also apply to the same system when used as a
nonload-bearing system. Indicated stud spacings
are maximums.
16. Specified floor -ceiling and roof -ceiling framing sizes
or truss dimensions are minimums. Greater joist or
truss sizes (depths) shall be permitted to be used in
metal- or wood -framed systems. Indicated joist and
truss spacings are maximums.
1 HOUR I I 50 to 54 STC
FIRE SOUND
Thickness: Minimum 71/4"
Approx. Weight: 7 psf
Fire Test: UL R3660, 06NK13008,
7-7-06; 07SR3014402,
12-18-07; 08CA14331,
6-18-08;
UL Design V469
Sound Test: RAL TL06-299, 8-10-06
7,
TKJ Structural Engineering
9820 Willow Creek Rd., Suite 455
San Diego, CA 92131
858.649.1700
'y www.tkjse.com
SITE VISIT REPORT
TO: Studio E Architects
ATTN: Eric Naslund
2258 First Ave
San Diego, CA 92101
FROM: Bo Jaquess, SE
TKJ Structural Engineering
SUBJECT: Washington Street Apartments — Phase I
TKJSE Job Number: 16010
DATE OF SITE VISIT: 9/7/2018
DATE OF REPORT: 9/10/2018
A site visit to the Washington Street Apartments — Phase I project was performed on the date
above. The following notes and observations were made:
1. Persons present on the job -walk: Jay Stehlik (Sun Country Builders), Bo Jaquess (TKJ
Structural Engineering.)
2. The general status of the various structures at the time of the job -walk were as follows:
a. Renovation units: roughly 95% of structural scope complete
b. Laundry Building: foundation concrete placed, walls roughly 95%framed
C. Bldg L: foundation concrete placed
d. Bldg M: foundation to be placed during the week of 9/10 (estimated)
3. The following items were observed were made during our job -walk. Where appropriate,
the proposed resolution is noted:
a. Existing Rehab Buildings A-1:
L Item #1: Shearwall elevations on Sheet SD-2.0 call for three (3) diameter epoxy epoxy anchor sill bolts at each shearwall. It was generally
observed that two (2) anchor bolts were present, per shearwall, and that
the anchor bolts were existing cast -in -place anchors.
Resolution: Install additional epoxy anchor sill bolts at all shearwall
locations so that the total number of sill bolts is no less than three (3), as
shown in structural drawings. Existing cast -in -place anchors may be
utilized in lieu of placing new anchors.
ii. Item #2: Edge -screws along the top edge of shearwalls, to the top -track of
the wall framing, were generally observed to be missing [Figure 3].
Resolution: Install #S screws at 3" on -center to top track of light -gauge
wall per structural shearwall schedule, 6/SD-51.
iii. Item #3: Framing for thermal chimneys appeared to be in general
conformance to the structural drawings. No further action required [Figure
4].
TKJ Structural Engineering
+ + 9820 Willow Creek Rd., Suite 455
San Diego, CA 92131
858.649.1700
www.tkjse.com
iv. Overall: In general, other than the items i and ii noted above, construction
appeared to be in general conformance to the structural drawings [Figures
1 & 2].
b, Laundry Building:
L Status: Foundation placed and wall framing nearing completion [Figure 8.1
ii. In general, foundation and framing appeared to be in general conformance
to the structural drawings.
C. Bldg L:
i. Status: Foundation concrete placed [Figure 5.1
ii. In general, foundation appeared to be in general conformance to the
structural drawings
d, Blde M:
L Status: Slab and footing reinforcement mostly in place. Anchor bolts and
holdowns generally in place, but not yet secured [Figures 5 & 7.]
ii. In general, foundation reinforcement and anchor bolt placement appeared
to be in general conformance to the structural drawings.
LITKJ Structural Engineering
9820 Willow Creek Rd., Suite 455
San Diego, CA 92131
858.649.1700
www.tkjse.coni
Photos
Figure 1: Rehab Buildings
Figure 2: Typical Rehab Building
TKJ Structural Engineering
9820 Willow Creek Rd., Suite 455
San Diego, CA 92131
858.649.1700
www.tkjse.com
Figure 3: Shearwall top -track with missing shearwall edge -screws
Figure 4: Typical solar chimney framing
TKJ Structural Engineering
9820 Willow Creek Rd., Suite 455
San Diego, CA 92131
858.649 1700
% www.tkjse.com
ti lvi-T (PION'.4
go
"IlAt
Figure 5: Building L Foundation
— «w
Figure 6: Building M Footing & Slab Reinforcing
Abbe
__: -Z— 1!%
Erica Zhou
To: Deanna Parry
Cc: Ken Kosman
Subject: RE: Roof nailing questions
From: Jay Stehlik
Sent: Friday, July 6, 2018 1:38 PM
To: Deanna Parry <ciparrv@suncountrybuilders.ne(>; Ken Kosman <KKosman@suncountrybuilder ywi>
Cc: Bruce Laiho <BLaiho @sunc:ountbuilders.net>; Jim Watson<iwa_tson@suncountrvbuilders.n(.,>;'Saul Miranda'
<.miranda(@Alwalldi.con,>
Subject: Roof nailing questions
Deanna,
We had the building inspector out to look at the roof nail on the first building D today. And he had questions he would
like the structural engineer to clarify.
1). On the roof framing plan sheet S-111.1 there is a blow up of the new patio roof area which shows the nailing Pattern
of 4" edge nailing and 12" field nailing (See photo attached). And it looks like it may need to be blocked and diaphragm
nailed. If so we need to have a detail showing what type of blocking etc.
2). The inspector is also requesting Clarification that the existing roof sheathing only needs to be nailed at 6" E.N. and
12" F.N. and does not need to have all edges blocked and nalled as well.
Please call me if you have any questions.
Thank You
Jay Stehlik
Sun Country Builders
C: (760)-691-6625
'stehlik@suncountrybuilders.net
ALI
SUN C OUN'I'RY BUII.DFRS
Washington Street Apartments -Phase 1
42-800 Washington Street
La Quinta, CA 92203
Answer Company Answered By
Studio E Architects Vince Rosato
2258 First Avenue
San Diego, CA 92101
Co -Respondent
Subject
Roof nailing questions
Request for Information 060
Detailed, RFIs Grouped by RFI Number
Project # 18-WASH 1
Tel: Fax:
Discipline
Cc: Company Name
Contact Name
Sun Country Builders
Brian Wardwell
Sun Country Builders
Bruce Laiho
Sun Country Builders
DeAnna Parry
Studio E Architects
Eric Naslund
Sun Country Builders
Jay Stehlik
Sun Country Builders
Jim Watson
Sun Country Builders
Justin Vining
Sun Country Builders
Ken Kosman
Coachella Valley Housing Coalition Kenneth Rodgers
Coachella Valley Housing Coalition MaryAnn Ybarra
Coachella Valley Housing Coalition Ray Cardinale
Studio E Architects
Vince Rosato
Author Company
Sun Country Builders
138 Civic Center Dr., #204
Vista, CA 92084
Author RFI Number
Copies Notes
1
1
1
1
1
1
1
1
1
1
1
1
Category
Authored By
DeAnna Parry
Question Date Required: 7/13/2018
Hi, Vince,
Please see below RFI from the Field with clarifications as requested by the Building Inspector
Suggestion
Answer
Date Answered:
Blocking is not required at the new or existing roof sheathing at the rehab buildings. 6" edge nailing is
acceptable for the existing roof sheathing.
Tanya Wei
TKJ Structural Engineering
Prolog Manager Printed on: 7/6/2018 Prolog8 Page 1
TO
�
�
�
�._\
33
f
<9E/
\ �,
Zm rn
M
�
��7K
�)
�
�
00
4
w �
§
�
�
CD
La
i\
cr (a
-0
}sue\.
$
2
AM
ENGINEERS + GEOLOGISTS + ENVIRONMENTAL SCIENTISTS
February 9, 2017
J.N. 11-290
THE ALTUM GROUP
73-255 El Paseo Drive, Suite 15
Palm Desert, California 92260
Attention: Mr. James Bazua
Subject: Updated Geotechnical Foundation Design Recommendations; Washington Street
Apartment Expansion Project, Southeast Corner of Washington Street and Hidden River
Road, City of La Quinta, Riverside County, California
References: See Attached List
Dear Mr. Bazua:
In accordance with your request, Petra Geosciences, Inc. (Petra) is providing updated geotechnical
foundation design recommendations for expansion of the subject Washington Street Apartment Project in
the City of La Quinta. Our geotechnical recommendations are based on the existing geotechnical reports
of record, and as -graded conditions, the requirements of the 2016 California Building Code (CBC), and our
engineering judgment and professional opinion.
General Site Overview
The existing apartment complex is located at the southeast corner of Washington Street and Hidden River
Road, in the City of La Quinta, Riverside County, California. The western portion of the 11.5 acre,
L-shaped site is currently improved with a one-story apartment complex, parking lot and driveway areas, a
clubhouse, concrete flatwork and landscaped areas. The eastern portion of the site is currently vacant.
As we understand, he proposed development will include constructing several new one-story apartment
buildings and associated improvements (asphalt parking lots, concrete walkways, underground utilities,
landscaped planter areas, and retention basins, etc.) within the vacant portion of the site. Following this
first phase of construction, the existing tenants will be relocated to the new apartments and the existing
apartment complex will be demolished and redeveloped with new one-story apartment buildings. It is
presumed that the apartment building structures will be of wood -frame construction with first -floor slabs
on -grade. No retaining walls are currently planned. Relatively minor site grading assumed to achieve the
planned grades. Therefore, site grading will essentially consist of over -excavation and recompaction of the
existing upper soils within the site to attain the finish grades.
Offices Strategically Positioned Throughout Southern California
RIVERSIDE COUNTY OFFICE
40880 County Center Drive, Suite R, Temecula, CA 92591
T:951.600.9271 F:951.719.1499
For more information visit us online at www.petra-inc.com
THE ALTUM GROUP February 9, 2017
Washington Street Apartment Expansion Project/La Quinta J.N. 11-290
Page 2
Site Reconnaissance and Literature Review
A representative of Petra conducted a recent site reconnaissance on January 16, 2017 to observe the existing
site conditions. Petra reviewed the Preliminary Geotechnical Investigation report (Petra, 2011 a) for the
subject property, as well as the Geotechnical Report Update and Review of Preliminary Precise Grading
Plan (Petra, 2016).
The existing apartment complex within the northwestern portion of the property remains occupied by
tenants. The vacant portion of the subject property remains undeveloped. Chain -link fencing exists along
the northern edge of undeveloped area. A concrete block wall exists along the southern property boundary.
Native, thin vegetation covers a majority of this portion of the site, with scattered small native bushes.
Larger, denser native vegetation was noted locally along the northern edge of the site. The west portion of
the property fronting Washington Street is at a similar elevation that the adjacent apartments to the north;
however, offsite development along the southern property is higher in elevation with differences on the
order of 2 to 6 feet. Overall the property slopes gently to the east. Generally, site conditions are similar to
those observed during our previous field assessment (Petra, 2011 a).
Site Surface and Subsurface Conditions
Based on our subsurface observations and laboratory testing during our preliminary evaluation of the
property (Petra, 2011 a), soils were found to consisted of thin veneer of surficial undocumented fills
underlain by natural alluvial deposits that extended to the maximum explored depth of 51.5 feet. Earth
materials onsite are estimated to be very low in expansion potential. Our testing also encountered a
negligible exposure to sulfates, a low exposure to chlorides and also found site soils to be corrosive to
buried metallic elements.
Updated Foundation Design Considerations
Seismic Design Parameters
Earthquake loads on earthen structures and buildings are a function of ground acceleration which may be
determined from the site -specific ground motion analysis. Alternatively, a design response spectrum can
be developed for the site based on the code guidelines. To provide the design team with the parameters
necessary to construct the design acceleration response spectrum for this project, we used the computer
applications that are available on the United States Geological Survey (USGS) website,
http://geohazards.us sg gov/. Specifically, the Design Maps website
1 PETRA SOLID AS A ROCK
THE ALTUM GROUP
Washington Street Apartment Expansion Project/La Quinta
February 9, 2017
J.N. 11-290
Page 3
hqp://geohazards.usgs.gov/designmaps/us/gpplicatigg.php was used to calculate the ground motion
parameters.
To run the above computer applications, site latitude, longitude, risk category and knowledge of "Site
Class" are required. The site class definition depends on the average shear wave velocity, Vs30, within the
upper 30 meters (approximately 100 feet) of site soils. A shear wave velocity of 900 feet per second (i.e.,
275 meters per second) for the upper 100 feet was used for the site based on engineering experience and
judgment. The following table, Table 1, provides parameters required to construct the site -specific
acceleration response spectrum based 2016 CBC guidelines.
10p
PTRA SOLID AS A HOCK
THE ALTUM GROUP
Washington Street Apartment Expansion Project/La Quinta
TABLE 1
Seismic Design Parameters
February 9, 2017
J.N. 11-290
Page 4
Ground Motion Parameters
Specific Reference 7
Parameter
Value
Unit
Site Latitude (North)
-
33.7373
°
Site Longitude (West)
-
-116.3026
°
Site Class Definition (1,2)
Section 1613.3.2
D
-
Assumed Risk Category (I)
Table 1604.5
I/II/III
-
Mw - Earthquake Magnitude (3)
USGS 2008 Interactive Deaggregation Tool
8.18
-
S, - Mapped Spectral Response Acceleration (1,2)
Figure 1613.3.1(1)
1.689
g
SI -Mapped Spectral Response Acceleration (1,2)
Figure 1613.3.1(2)
0.802
g
Fa - Site Coefficient (1,2)
Table 1613.3.3(1)
1.0
-
F,, - Site Coefficient (1,2)
Table 1613.3.3(2)
1.5
-
Smms - Adjusted Maximum Considered Earthquake
Spectral Response Acceleration (1,2)
Equation 16-37
1.689
g
Sm, - Adjusted Maximum Considered Earthquake
Spectral Response Acceleration (1,2)
Equation 16-38
1.203
g
I
SDS - Design Spectral Response Acceleration (1,2)
Equation 16-39
1.126
g F
SDI - Design Spectral Response Acceleration (1,2)
Equation 16-40
0.802
g F
L = 0.2 SDI/ SDs (4)
Section 11.3
0.142
S
Ts = SDI/ SDs (4)
Section 11.3
0.712
S
TL - Long Period Transition Period (4)
Figure 22-12
8
S
FPGA - Site Coefficient (4)
Figure 22-7
1.000
-
PGAm - Peak Ground Acceleration at MCE 14, ">
Equation 11.8-1
0.677
g
Design PGA z (% PGAM) - Slope Stability (2, t)
Similar to Equations 16-39 & 16-40
0.451
g
Design PGA ;z� (0.4 SDs) — Short Retaining Walls (4,1)
Equation 11.4-5
0.450
g
CRs - Short Period Risk Coefficient (4)
Figure 22-17
1.015
-
CRI - Long Period Risk Coefficient (4)
Figure 22-18
0.979
-
Seismic Design Category
Section 1613.3.5
E
-
References:
(I) California Building Code (CBC), 2016, California Code of Regulations, Title 24, Part 2, Volume I and II.
(2) USGS Seismic Design Web Application — http://geohazards.usgs. ovg /designmaps/us/application.phhp
0) USGS 2008 Interactive Deaggregation Tool - htt2s://geohazards.us,as.gov/dea,ggint/2008/
(4) American Society of Civil Engineers (ASCE/SEI), 2010, Minimum Design Load for Buildings and Other Structures, Standards 7-10.
Related References:
Federal Emergency Management Agency (FEMA), 2009, NEHERP (National Earthquake Hazards Reduction Program) Recommended
Seismic Provision for New Building and Other Structures (FEMA P-750).
Notes:
* PGA Calculated at the MCE return period of 2475 years (2 percent chance of exceedance in 50 years).
t PGA Calculated at the Design Level of % of MCE; approximately equivalent to a return period of 475 years (10 percent
chance of exceedance in 50 years).
t PGA Calculated for short, stubby retaining walls with an infinitesimal (zero) fundamental period.
§ The designation provided herein may be superseded by the structural engineer in accordance with Section 1613.3.5.1, if
applicable.
1 PETRA SOLID ASAROCK
THE ALTUM GROUP February 9, 2017
Washington Street Apartment Expansion Project/La Quinta J.N. 11-290
Page 5
Data provided by the United States Geological Survey (USGS, 2008) listed a mean magnitude of 7.7 for
the subject property pertaining to an event effecting multiple segments the San Andreas and South San
Andreas Fault zones. It should be noted that review comments by the local agency consultants indicated
that the typically stated magnitude for a multi -segment event along the San Andreas Fault is about 8.18.
As a result, more conservative values are utilized herein.
FOUNDATION DESIGN GUIDELINES
Allowable Bearing Capacity, Estimated Settlement and Lateral Resistance
Allowable Soil Bearing Capacities
Pad Footings
A basic allowable soil bearing capacity of 1,500 pounds per square foot, including dead and live loads, may
be utilized for design of 24-inch square pad footing and 12-inch-wide continuous footings founded at a
minimum depth of 12 inches below the lowest adjacent final grade. This value may be increased by 20
percent for each additional foot of depth and by 10 percent for each additional foot of width to a maximum
value of 2,500 pounds per square foot. Recommended allowable bearing values include both dead and live
loads, and may be increased by one-third for short duration wind and seismic forces.
Continuous Footings
An allowable soil bearing capacity of 1,500 pounds per square foot may be utilized for design of continuous
footings founded at a minimum depth of 12 inches below the lowest adjacent final grade. This value may
be increased by 20 percent for each additional foot of depth and by 10 percent for each additional foot of
width, to a maximum value of 2,500 pounds per square foot. The recommended allowable bearing value
includes both dead and live loads, and may be increased by one-third for short duration wind and seismic
forces.
Estimated Footing Settlement
Based on the allowable bearing values provided above, total settlement of the footings under the anticipated
loads is expected to be on the order of 0.5 inch in areas where the depth of fill does not exceed approximately
10 feet. Differential settlement is expected to be less than 0.25 inch over a horizontal span of 20 feet for
this condition. The majority of settlement is likely to take place as footing loads are applied or shortly
thereafter.
Dynamic and total settlement values are provided in Petra's response letter to the City of La Quinta Public
Works Department review dated October 20, 2011.
1 PETRA SOLID AS A ROCK
THE ALTUM GROUP February 9, 2017
Washington Street Apartment Expansion Project/La Quinta J.N. 11-290
Page 6
Lateral Resistance
A passive earth pressure of 250 pounds per square foot per foot of depth, to a maximum value of
2,500 pounds per square foot, may be used to determine lateral bearing resistance for footings. In addition,
a coefficient of friction of 0.30 times the dead load forces may be used between concrete and the supporting
soils to determine lateral sliding resistance. The above values may be increased by one-third when
designing for transient wind or seismic forces. It should be noted that the above values are based on the
condition where footings are cast in direct contact with compacted fill. In cases where the footing sides are
formed, all backfill placed against the footings upon removal of forms should be compacted to at least
90 percent of the applicable maximum dry density.
Guidelines for Footings and Slabs on -Grade Design and Construction
The results of our laboratory tests performed on representative samples of near -surface soils within the site
at the completion of grading indicate that these materials predominantly exhibit expansion indices that are
less than 20. As indicated in Section 1803.5.3 of 2016 California Building Code (2016 CBC), these soils
are considered non -expansive and, as such, the design of slabs on -grade is considered to be exempt from
the procedures outlined in Sections 1808.6.2 of the 2016 CBC and may be performed using any method
deemed rational and appropriate by the project structural engineer. However, the following minimum
recommendations are presented herein for conditions where the project design team may require
geotechnical engineering guidelines for design and construction of footings and slabs on -grade the project
site.
The design and construction guidelines that follow are based on the above soil conditions and may
be considered for reducing the effects of variability in fabric, composition and, therefore, the
detrimental behavior of the site soils such as excessive short- and long-term total and differential
heave or settlement. These guidelines have been developed on the basis of the previous experience
of this firm on projects with similar soil conditions. Although construction performed in
accordance with these guidelines has been found to reduce post -construction movement and/or
distress, they generally do not positively eliminate all potential effects of variability in soils
characteristics and future heave or settlement.
It should also be noted that the suggestions for dimension and reinforcement provided herein are
performance -based and intended only as preliminary guidelines to achieve adequate performance
under the anticipated soil conditions. However, they should not be construed as replacement for
structural engineering analyses, experience and judgment. The project structural engineer,
architect and/or civil engineer should make appropriate adjustments to slab and footing
dimensions, and reinforcement type, size and spacing to account for internal concrete forces (e.g.,
thermal, shrinkage and expansion) as well as external forces (e.g., applied loads) as deemed
1 PETRA SOLID AS A ROCK
THE ALTUM GROUP
Washington Street Apartment Expansion Project/La Quinta
February 9, 2017
J.N. 11-290
Page 7
necessary. Consideration should also be given to minimum design criteria as dictated by local
building code requirements.
Conventional Slab on -Grade System
Given the expansion index of less than 20, as generally exhibited by onsite soils, we recommend that
footings and floor slabs be designed and constructed in accordance with the following minimum criteria.
Footinjzs
1. Exterior continuous footings supporting one- and two-story structures should be founded at a minimum
depth of 12 inches below the lowest adjacent final grade, respectively. Interior continuous footings
may be founded at a minimum depth of 10 inches below the top of the adjacent finish floor slabs.
2. In accordance with Table 1809.7 of 2016 CBC for light -frame construction, all continuous footings
should have minimum widths of 12 inches for one- and two-story construction. We recommend all
continuous footings should be reinforced with a minimum of two No. 4 bars, one top and one bottom.
A minimum 12-inch-wide grade beam founded at the same depth as adjacent footings should be
provided across garage entrances or similar openings (such as large doors or bay windows). The grade
beam should be reinforced with a similar manner as provided above.
4. Interior isolated pad footings, if required, should be a minimum of 24 inches square and founded at a
minimum depth of 12 inches below the bottoms of the adjacent floor slabs for one- and two-story
buildings. Pad footings should be reinforced with No. 4 bars spaced a maximum of 18 inches on centers,
both ways, placed near the bottoms of the footings.
Exterior isolated pad footings intended for support of roof overhangs such as second -story decks, patio
covers and similar construction should be a minimum of 24 inches square and founded at a minimum
depth of 18 inches below the lowest adjacent final grade. The pad footings should be reinforced with
No. 4 bars spaced a maximum of 18 inches on centers, both ways, placed near the bottoms of the
footings. Exterior isolated pad footings may need to be connected to adjacent pad and/or continuous
footings via tie beams at the discretion of the project structural engineer.
6. The minimum footing dimensions and reinforcement recommended herein may be modified (increased
or decreased subject to the constraints of Chapter 18 of the 2016 CBC) by the structural engineer
responsible for foundation design based on his/her calculations, engineering experience and judgment.
Building Floor Slabs
Concrete floor slabs should be a minimum 4 inches thick and reinforced with No. 3 bars spaced a
maximum of 24 inches on centers, both ways. Alternatively, the structural engineer may recommend
the use of prefabricated welded wire mesh for slab reinforcement. For this condition, the welded wire
mesh should be of sheet type (not rolled) and should consist of 6x6/W2.9xW2.9 WWF (per the Wire
Reinforcement Institute, WRI, designation) or stronger. All slab reinforcement should be supported on
concrete chairs or brick to ensure the desired placement near mid -depth. Care should be exercised to
prevent warping of the welded wire mesh between the chairs in order to ensure its placement at the
desired mid -slab position.
1 PETRA SOLID AS A ROCK
THE ALTUM GROUP
Washington Street Apartment Expansion Project/La Quinta
February 9, 2017
J.N. 11-290
Page 8
Slab dimension, reinforcement type, size and spacing need to account for internal concrete forces (e.g.,
thermal, shrinkage and expansion) as well as external forces (e.g., applied loads), as deemed necessary.
2. Living area concrete floor slabs and areas to receive moisture sensitive floor covering should be
underlain with a moisture vapor retarder consisting of a minimum 10-mil-thick polyethylene or
polyolefin membrane that meets the minimum requirements of ASTM E96 and ASTM E 1745 for vapor
retarders (such as Husky Yellow Guard®, Stego® Wrap, or equivalent). All laps within the membrane
should be sealed, and at least 2 inches of clean sand should be placed over the membrane to promote
uniform curing of the concrete. To reduce the potential for punctures, the membrane should be placed
on a pad surface that has been graded smooth without any sharp protrusions. If a smooth surface cannot
be achieved by grading, consideration should be given to lowering the pad finished grade an additional
inch and then placing a 1-inch-thick leveling course of sand across the pad surface prior to the
placement of the membrane.
At the present time, some slab designers, geotechnical professionals and concrete experts view
the sand layer below the slab (blotting sand) as a place for entrapment of excess moisture that
could adversely impact moisture -sensitive floor coverings. As a preventive measure, the
potential for moisture intrusion into the concrete slab could be reduced if the concrete is placed
directly on the vapor retarder. However, if this sand layer is omitted, appropriate curing
methods must be implemented to ensure that the concrete slab cures uniformly. A qualified
materials engineer with experience in slab design and construction should provide
recommendations for alternative methods of curing and supervise the construction process to
ensure uniform slab curing. Additional steps would also need to be taken to prevent puncturing
of the vapor retarder during concrete placement.
Garage floor slabs should be a minimum 4 inches thick and reinforced in a similar manner as living
area floor slabs. Garage slabs should also be poured separately from adjacent wall footings with a
positive separation maintained using 3/4-inch-minimum felt expansion joint material. To control the
propagation of shrinkage cracks, garage floor slabs should be quartered with weakened plane joints.
Consideration should be given to placement of a moisture vapor retarder below the garage slab, similar
to that provided in Item 2 above, should the garage slab be overlain with moisture sensitive floor
covering.
4. Presaturation of the subgrade below floor slabs will not be required; however, prior to placing concrete,
the subgrade below all dwelling and garage floor slab areas should be thoroughly moistened to achieve
a moisture content that is at least equal to or slightly greater than optimum moisture content. This
moisture content should penetrate to a minimum depth of 12 inches below the bottoms of the slabs.
5. The minimum dimensions and reinforcement recommended herein for building floor slabs may be
modified (increased or decreased subject to the constraints of Chapter 18 of the 2016 CBC) by the
structural engineer responsible for foundation design based on his/her calculations, engineering
experience and judgment.
Post -Tensioned Slab on -Grade System (Optional)
In consideration of the expansion index of less than 20, as predominantly exhibited by onsite soils, any
rational and appropriate procedure may be chosen by the project structural engineer for the design of post -
tensioned slabs on -grade. Should the design engineer choose to follow the most current procedure
1 PETRA SOLID AS A ROCK
THE ALTUM GROUP
Washington Street Apartment Expansion Project/La Quinta
February 9, 2017
J.N. 11-290
Page 9
published by the Post -Tensioning Institute (PTI DC10.5-12), the following minimum design criteria are
provided Table 2, below.
TABLE 2
Post -Tensioned Slab on -Grade Design Parameters for PTI Procedure
Soil Information
Approximate Depth of Constant Suction, feet
9
Approximate Soil Suction, pF
3.9
Inferred Thornthwaite Index:
-20
Average Edge Moisture Variation Distance, em in feet:
Center Lift
9.0
Edge Lift
5.5
Anticipated Swell, ym in inches:
Center Lift
0.25
Edge Lift
0.45
Modulus of Subprade Reaction
The modulus of subgrade reaction for design of load bearing elements depends on the size of the element
and soil -structure interaction. However as a fist level of approximation, this value may be assumed to be
125 pounds per cubic inch.
Minimum Design Recommendations
The soil values provided above may be utilized by the project structural engineer to design post -tensioned
slabs on -ground in accordance with Section 1808.6.2 of the 2016 CBC and the PTI publication. Thicker
floor slabs and larger footing sizes may be required for structural reasons and should govern the design if
more restrictive than the minimum recommendations provided below:
1. Exterior continuous footings for one- and two-story structures should be founded at a minimum depth
of 12 inches below the lowest adjacent finished ground surface. Interior footings may be founded at a
minimum depth of 10 inches below the tops of the adjacent finish floor slabs.
2. In accordance with Table 1809.7 of 2016 CBC for light -frame construction, all continuous footings
should have minimum widths of 12 inches for one- and two-story construction. We recommend all
continuous footings should be reinforced with a minimum of two No. 4 bars, one top and one bottom.
Alternatively, post -tensioned tendons may be utilized in the perimeter continuous footings in lieu of
the reinforcement bars.
A minimum 12-inch-wide grade beam founded at the same depth as adjacent footings should be
provided across the garage entrances or similar openings (such as large doors or bay windows). The
grade beam should be reinforced in a similar manner as provided above.
1 PETRA SOLID AS A ROCK
THE ALTUM GROUP
Washington Street Apartment Expansion Project/La Quinta
February 9, 2017
J.N. 11-290
Page 10
4. Exterior isolated pad footings intended for support of roof overhangs such as second -story decks, patio
covers and similar construction should be a minimum of 24 inches square and founded at a minimum
depth of 18 inches below the lowest adjacent final grade. The pad footings should be reinforced with
No. 4 bars spaced a maximum of 18 inches on centers, both ways, placed near the bottoms of the
footings. Exterior isolated pad footings may need to be connected to adjacent pad and/or continuous
footings via tie beams at the discretion of the project structural engineer.
The thickness of the floor slabs should be determined by the project structural engineer with
consideration given to the expansion index of the onsite soils; however; we recommend that a minimum
slab thickness of 4 inches be considered.
6. As an alternative to designing 4-inch-thick post -tensioned slabs with perimeter footings as described in
Items 1 and 2 above, the structural engineer may design the foundation system using a thickened slab
design. The minimum thickness of this uniformly thick slab should be 8 inches. The engineer in charge
of post -tensioned slab design may also opt to use any combination of slab thickness and footing
embedment depth as deemed appropriate based on their engineering experience and judgment.
7. Living area concrete floor slabs and areas to receive moisture sensitive floor covering should be
underlain with a moisture vapor retarder consisting of a minimum 10-mil-thick polyethylene or
polyolefin membrane that meets the minimum requirements of ASTM E96 and ASTM E 1745 for vapor
retarders (such as Husky Yellow Guard®, Stego® Wrap, or equivalent). All laps within the membrane
should be sealed, and at least 2 inches of clean sand should be placed over the membrane to promote
uniform curing of the concrete. To reduce the potential for punctures, the membrane should be placed
on a pad surface that has been graded smooth without any sharp protrusions. If a smooth surface cannot
be achieved by grading, consideration should be given to lowering the pad finished grade an additional
inch and then placing a 1-inch-thick leveling course of sand across the pad surface prior to the
placement of the membrane.
At the present time, some slab designers, geotechnical professionals and concrete experts view
the sand layer below the slab (blotting sand) as a place for entrapment of excess moisture that
could adversely impact moisture -sensitive floor coverings. As a preventive measure, the
potential for moisture intrusion into the concrete slab could be reduced if the concrete is placed
directly on the vapor retarder. However, if this sand layer is omitted, appropriate curing
methods must be implemented to ensure that the concrete slab cures uniformly. A qualified
materials engineer with experience in slab design and construction should provide
recommendations for alternative methods of curing and supervise the construction process to
ensure uniform slab curing. Additional steps would also need to be taken to prevent puncturing
of the vapor retarder during concrete placement.
8. Garage floor slabs should be designed in a similar manner as living area floor slabs. Consideration
should be given to placement of a moisture vapor retarder below the garage slab, similar to that provided
in Item 6 above, should the garage slab be overlain with moisture sensitive floor covering.
9. Pre -saturation of the subgrade below floor slabs will not be required; however, prior to placing concrete,
the subgrade below all dwelling and garage floor slab areas should be thoroughly moistened to achieve
a moisture content that is at least equal to or slightly greater than optimum moisture content. This
moisture content should penetrate to a minimum depth of 12 inches below the bottoms of the slabs.
1 PETRA SOLID AS A ROCK
THE ALTUM GROUP
Washington Street Apartment Expansion Project/La Quinta
February 9, 2017
J.N. 11-290
Page 11
10. The minimum footing dimensions and reinforcement recommended herein may be modified (increased
or decreased subject to the constraints of Chapter 18 of the 2016 CBC) by the structural engineer
responsible for foundation design based on his/her calculations, engineering experience and judgment.
Foundation Excavation Observations
Foundation excavations should be observed by a representative of this firm to document that they have been
excavated into competent bearing soils prior to the placement of forms, reinforcement or concrete. The
excavations should be trimmed neat, level and square. All loose, sloughed or moisture -softened soils and/or
any construction debris should be removed prior to placing of concrete. Excavated soils derived from
footing and/or utility trenches should not be placed in building slab -on -grade areas or exterior concrete
flatwork areas unless the soils are compacted to at least 90 percent of maximum dry density.
General Corrosivity Screening
As a screening level study, limited chemical and electrical tests were performed on representative samples
of onsite soils to identify potential corrosive characteristics of these soils. The following sections present
the test results and an interpretation of current codes and guidelines that are commonly used in our industry
as they relate to the adverse impact of chemical contents and electrical resistance of the site soils on various
components of the proposed structures in contact with site soils.
A variety of test methods are available to quantify corrosive potential of soils for various elements of
construction materials. Depending on the test procedures adopted, characteristics of the leachate that is
used to extract the target chemicals from the soils and the test equipment; the results can vary appreciably
for different test methods in addition to those caused by variability in soil composition. The testing
procedures referred to herein are considered to be typical for our industry and have been adopted and/or
approved by many public or private agencies. In drawing conclusions from the results of our chemical and
electrical laboratory testing and providing mitigation guidelines to reduce the detrimental impact of
corrosive site soils on various components of the structure in contact with site soils, heavy references were
made to 2016 California Building Code (2016 CBC) and American Concrete Institute publication (2014
Building Code Requirements for Structural Concrete, ACI 318-14). Where relevant information was not
available in these codes, references were made to guidelines developed by California Department of
Transportation (Caltrans), Post -Tensioning Institute (PTI DC10.5-12) and other reputable institutions
and/or publications. Specifically, the reference to Caltrans approach were made because their risk
management protocol for highway bridges are considered comparable to those for residential or commercial
ltp
PETRA SOLID AS A ROCK
THE ALTUM GROUP
Washington Street Apartment Expansion Project/La Quinta
February 9, 2017
J.N. 11-290
Page 12
structures and that Post Tensioning Institute (PTI), in part, accepts and uses Caltrans' relevant corrosivity
criteria for post -tensioned slabs on -grade.
It should be noted that Petra does not practice corrosion engineering; therefore, the test results, opinion
and engineering judgment provided herein should be considered as general guidelines only. Additional
analyses would be warranted, especially, for cases where buried metallic building materials (such as copper
and cast or ductile iron pipes) in contact with site soils are planned for the project. In many cases, the
project geotechnical engineer may not be informed of these choices. Therefore, for conditions where such
elements are considered, we recommend that other, relevant project design professionals (e.g., the architect,
landscape architect, civil and/or structural engineer) also consider recommending a qualified corrosion
engineer to conduct additional sampling and testing of near -surface soils during the final stages of site
grading to provide a complete assessment of soil corrosivity. Recommendations to mitigate the detrimental
effects of corrosive soils on buried metallic and other building materials that may be exposed to corrosive
soils should be provided by the corrosion engineer as deemed appropriate.
Concrete in Contact with Site Soils
Soils containing soluble sulfates beyond certain threshold levels as well as acidic soils are considered to be
detrimental to long-term integrity of concrete placed in contact with such soils. For the purpose of this
study, soluble sulfates (S042-) concentration in soils determined in accordance with California Test Method
No. 417. Soil acidity, as indicated by hydrogen -ion concentration (pH), was determined in accordance with
California Test Method No. 643. The soil acid severity rating is adopted from The United States
Department of Agriculture, Natural Resources Conservation Service classification.
Article 1904.1 of Section 1904 of the 2016 CBC indicates that structural concrete shall conform to the
durability requirements of ACI 318. Concrete durability is impacted by exposure to water soluble
chemicals and its resistance to fluid penetration. Section 19.3 of Chapter 19 of ACI 318-14 provides
guidelines for assigning exposure categories and classes for various conditions. Exposure Category S,
which is subdivided to four Exposure Classes of SO, S1, S2 and S3, applies to concrete in contact with soil
or water containing deleterious amounts of water soluble ions.
The results of our limited in-house laboratory tests indicate that on -site soils contain a water-soluble sulfate
content of 0.004 percent by weight. Based on Table 19.3.1.1 of ACI 318-14, the Exposure Class SO is
appropriate for onsite soils. For this exposure class, Table 19.3.2.1 of ACI 318-14 provides that no
restriction for cement type or maximum water -cement ratio for the fresh concrete would be required.
1 PETRA SOLID AS A ROCK
THE ALTUM GROUP February 9, 2017
Washington Street Apartment Expansion Project/La Quinta J.N. 11-290
Page 13
Further, this table indicates that the concrete minimum unconfined strength should not be less than
2,500 psi.
The results of limited in-house testing of representative samples indicate that soils within the subject site
are slightly alkaline with respect to pH (a pH of 7.4). Based on this finding and according to Table 8.22.2
of Caltrans' 2003 Bridge Design Specifications (2003 BDS) requirements (which consider the combined
effects of soluble sulfates and soil pH), a commercially available Type II Modified cement may be used.
The guidelines provided herein should be evaluated and confirmed, or modified, in its entirety by the project
structural engineer and the contractor responsible for concrete placement for structural concrete used in
exterior and interior footings, interior slabs on -ground, garage slabs, walls foundation and concrete exposed
to weather such as driveways, patios, porches, walkways, ramps, steps, curbs, etc.
Metals Encased in Concrete
Soils containing a soluble chloride concentration beyond a certain threshold level are considered corrosive
to metallic elements such as reinforcement bars, tendons, cables, bolts, anchors, etc. that are encased in
concrete that, in turn, is in contact with such soils. For the purpose of this study, soluble chlorides (Cl) in
soils were determined in accordance with California Test Method No. 422.
As stated earlier, Article 1904.1 of Section 1904 of the 2016 CBC indicates that structural concrete shall
conform to the durability requirements of ACI 318. Concrete durability is impacted by exposure to water
soluble chemicals and its resistance to fluid penetration. Section 19.3 of Chapter 19 of ACI 318-14 provides
guidelines for assigning exposure categories and classes for various conditions. Exposure Category C,
which is subdivided to three Exposure Classes of CO, C 1, and C2, applies to nonprestressed and prestressed
concrete exposed to conditions that require additional protection against corrosion of reinforcement.
According to Table 19.3.1.1 of ACI 318-14, the Exposure Class CO is appropriate for reinforced concrete
that remains dry or protected from moisture. Similarly, the Exposure Class Cl is appropriate for reinforced
concrete that is exposed to moisture but not to external sources of chlorides. And, lastly, the Exposure
Class C2 is appropriate for reinforced concrete that is exposed to moisture and external sources of chlorides
as "deicing chemicals, salt, brackish water, seawater, or spray from these sources".
Based on our understanding of the project, it is our professional opinion that the Exposure Class Cl is
appropriate for a majority of reinforced concrete, to be placed at the site that are in contact with site soils.
It should be noted, however, that the Exposure Class C2 is more appropriate for reinforced concrete that
is planned for pool walls and decking, should such features be considered for the project.
1 PETRA SOLID AS A ROCK
THE ALTUM GROUP
Washington Street Apartment Expansion Project/La Quinta
February 9, 2017
J.N. 11-290
Page 14
The results of our limited laboratory tests performed indicate that onsite soils contain a water-soluble
chloride concentration of 125 parts per million (ppm). No maximum water/cement ratio for the fresh
concrete is prescribed by ACI 318 for Exposure Class C1 condition. Table 19.3.2.1 of ACI 318-14
indicates that concrete minimum unconfined compressive strength, f should not be less than 2,500 psi.
For Exposure Class C2 condition, Table 19.3.2.1 of ACI 318-14 requires that the maximum water/cement
ratio of the fresh concrete should not exceed 0.40 and concrete minimum unconfined compressive strength,
f c, should not be less than 5,000 psi.
The guidelines provided herein should be evaluated and confirmed, or modified, in its entirety by the project
structural engineer for reinforced concrete placement for structural concrete used in exterior and interior
footings, interior slabs on -ground, garage slabs, walls foundation and concrete exposed to weather such as
driveways, patios, porches, walkways, ramps, steps, curbs, etc.
It should be noted that another source of elevated chloride -ion concentration can be the chloride content of
water that is used to prepare the fresh concrete at the plant. The protection against high chloride
concentration in fresh concrete should, therefore, be provided by concrete suppliers for the project.
Metallic Elements in Contact with Site Soils
Elevated concentrations of soluble salts in soils tend to induce low level electrical currents in metallic
objects in contact with such soils. This process promotes metal corrosion and can lead to distress to building
metallic components that are in contact with site soils. The minimum electrical resistivity measurement
provides a simple indication of relative concentration of soluble salts in the soil and, therefore, is widely
used to estimate soil corrosivity with regard to metals. For the purpose of this investigation, the minimum
resistivity in soils is measured in accordance with California Test Method No. 643. The soil corrosion
severity rating is adopted from the Handbook of Corrosion Engineering by Pierre R. Roberge.
The minimum electrical resistivity for onsite soils was found to be 4,000 ohm -cm based on limited
testing. The result indicates that on -site soils are Corrosive to ferrous metals and copper. As such, any
ferrous metal or copper components of the subject buildings (such as cast iron or ductile iron piping, copper
tubing, etc.) that are expected to be placed in direct contact with site soils should be protected against
detrimental effects of corrosive soils. Such protection could include the use of galvanized tubing, coated
pipes, wrapping or encasing these metallic objects in special protection wrappings or conduits or devising
a cathodic protection system. It should be noted that at this time Petra is not aware of any plans to
incorporate such items for the proposed buildings. Should such elements be considered for these building,
1 PETRA SOLID AS A ROCK
THE ALTUM GROUP February 9, 2017
Washington Street Apartment Expansion Project/La Quinta J.N. 11-290
Page 15
we recommend that a corrosion engineer to be consulted to provide appropriate recommendations for long
term protection of metallic elements in contact with site soils.
Plan Reviews, Future Improvements and/or Grading
Petra should review the precise grading plans when they become available and provide further geotechnical
recommendations. If additional site improvements are considered in the future, our firm should be notified
so that we may provide design recommendations to mitigate movement, settlement and/or tilting of the
structures. Potential problems can develop when drainage on the pads and slopes is altered in any way such
as placement of fill and construction of new walkways, patios, landscape walls, swimming pools, spas
and/or planters. Therefore, it is recommended that we be engaged to review the final design drawings or
specifications prior to any new construction. If we are not provided the opportunity to review these
documents with respect to the geotechnical aspects of new construction, it should not be assumed that the
recommendations provided herein are wholly or impart applicable to the proposed improvements.
REPORT LIMITATIONS
This report is based on the proposed residential tract and the geotechnical observations made during our
literature review of the prior consultant's grading report and our recent assessment within the site. No
representatives of Petra were present during the previous grading activities that have been completed at this
site. This report has been prepared consistent with that level of care being provided by other professionals
providing similar services at the same locale and in the same time period. The contents of this report are
professional opinions and as such, are not to be considered a guaranty or warranty.
Based on our findings, the conclusions and recommendations presented herein and within the referenced
report by our firm were prepared in conformance with generally accepted professional engineering
practices.
1 PETRA SOLID AS A ROCK
THE ALTUM GROUP
Washington Street Apartment Expansion Project/La Quinta
February 9, 2017
J.N. 11-290
Page 16
This opportunity to be of service is sincerely appreciated. If you have any additional questions or concerns,
please feel free contact this office.
Respectfully submitted,
PETRA GEOSCIENCES, INC.
l
Edward Lump
Associate Geologist
CEG 1924
z.5%7
Grayson R. Walker, GE
Principal Engineer �oe�
GE 871
GE 871
EL/GRW/lmv
OF CAUF��/
Distribution: (1) Addressee (electronic copy)
(3) Addressee
Attachments: References
Figure 1 — Site Location Map
Appendix A — Seismic Design Parameters Summary Report
lto PETRA SOLID AS A ROCK
THE ALTUM GROUP February 9, 2017
Washington Street Apartment Expansion Project/La Quinta J.N. 11-290
Page 17
REFERENCES
American Concrete Institute publication, 2014 Building Code Requirements for Structural Concrete,
ACI 318-14.
International Building Code, 2015, 2016 California Building Code, California Code of Regulations,
Title 24, Par 2, Volume 2 of 2, Based on the 2015 International Building Code, California Building
Standards Commission.
Petra Geotechnical, Inc., 2011 a, Preliminary Geotechnical Investigation, Proposed Washington Street
Apartment Expansion, Southeast Corner of Washington Street and Hidden River Road, City of La
Quinta, Riverside County, California, J.N. 290-11, dated August 31.
201 lb, Response to City of La Quinta Public Works Department Review Comments, Proposed
Washington Street Apartment Expansion, Southeast Corner of Washington Street and Hidden River
Road, City of La Quinta, Riverside County, California, prepared for The Altum Group, J.N. 290-
11, dated October 20.
2013, Geotechnical Report Update, Proposed Washington Street Apartment Expansion, Southeast
Corner of Washington Street and Hidden River Road, City of La Quinta, Riverside County,
California, prepared for The Altum Group, J.N. 11-290, dated April 9.
Petra Geosciences, Inc., 2016, Geotechnical Report Update and Review of Preliminary Precise Grading
Plan, Proposed Washington Street Apartment Expansion, Southeast Corner of Washington Street
and Hidden River Road, City of La Quinta, Riverside County, California, J.N. 11-290, dated May
25.
Post -Tensioning Institute, DC10.5-12 "Standard Requirements for Design of Shallow Post -Tensioned
Concrete Foundations on Expansive Soils.
Wire Reinforcement Institute (WRI), 1996, Design of Slabs on Ground.
1 PETRA SOLID AS A ROCK
FIGURES
PETFMSOUR AS A ROCK
GEOSCIENCES"
IL
i
j I
�µ�"T-
1�v
frfRwtD 0�'
r ru 4WLA
42
r�
nM o�
I �.
0 � M I �-f '3
—now,
'►CDrSW
OPY : • • ? \j
�\ �-Vm
SITE
h)iT AOU1. •►'f
All
Bermuda
Uuncg tN -
D*
C a
An 0
4
O
t
o11t If $1
1� �1
a
a
�] o
LEGEND PETRoA 880 COUNTY CENTER DRIVE, SUITE R
EGEOSCIENMECULA, CALIFORNIA 9CES, INC.
2591
PHONE: (951) 600-9271
COSTAMESA MURRIETA PALM DESERT SANTACLARITA
- Approximate Site Location
Site Location Map
Washington Street Apartments Expansion
La Quinta, Riverside County, California
DATE: February2017 J.N.: 11-290 Figure 1
DWG BY: epl SCALE: NTS
APPENDIX A
SEISMIC DESIGN PARAMETERS SUMMARY REPORT
PETRA;nl In AS A ROCK f
� GEOSCIENCES-,
Design Maps Summary Report Page 1 of 2
USGS Design Maps Summary Report
User -Specified Input
Report Title 11-290
Fri January 13, 2017 18:18:59 urc
Building Code Reference Document ASCE 7-10 Standard
(which utilizes USES hazard data available in 2008)
Site Coordinates 33.73730N, 116.3026°W
Site Soil Classification Site Class D - "Stiff Soil"
Risk Category I/II/III
n
9S*
��• ��• �• i Thouaancl{'almt
Cat}redralC{ty '• e�•n.a..
---
• �mort
Rancho
Mirage
= Palm Desert Indla
n
-'Af�ilGl tiF ` -
.Coachella
r la Quinn i ,
'L
USGS-Provided Output
Ss = 1.689 g SNs = 1.689 g S.s = 1.126 g
S1= 0.802g S„1= 1.203g S.l= 0.802g
For information on how the SS and S1 values above have been calculated from probabilistic (risk -targeted) and
deterministic ground motions in the direction of maximum horizontal response, please return to the application and
select the "2009 NEHRV building code reference document.
MCER Response Spectrum
1.9-
1.70
1.53
1.3G
1.19
Or 1.0�
to 0.95
0.69
0.51
0.34
0.1?
0.00
0.00 0.20 0.40 0.G0 0.20 1.00 1.20 1.40 1.60 1,90 2.00
Period, T (sec)
Design Response Spectrum
1 20
1.02
0.96
0.24
O� 0.72
0.60
0.49
0.36
0.24
0.12
0.00
0.00 0.20 0.40 O. GO 0.00 1.00 1.20 1.40 1.60 1.20 2.00
Period, T (sec)
For PGA., T,, C, and Ca, values, please view the detailed report.
http://earthquake.usgs.gov/designmaps/us/sutnm,try.php?template=minimal&latitude=33.7... 1 /13/2017
Design Maps Summary Report
Page 2 of 2
Although this information is a product of the U.S. Geological Survey, we provide no warranty, expressed or implied, as to the
accuracy of the data contained therein. This tool is not a substitute for technical subject -matter knowledge.
http://earthquake.usgs.gov/desigmnaps/us/summary.php?template=minimal&latitude=33.7... 1 /13/2017
Design Maps Detailed Report
Page 1 of 6
USGS Design Maps Detailed Report
ASCE 7-10 Standard (33.73730N, 116.30261W)
Site Class D — "Stiff Soil", Risk Category I/II/III
Section 11.4.1 — Mapped Acceleration Parameters
Note: Ground motion values provided below are for the direction of maximum horizontal
spectral response acceleration. They have been converted from corresponding geometric
mean ground motions computed by the USGS by applying factors of 1.1 (to obtain SS) and
1.3 (to obtain S,). Maps in the 2010 ASCE-7 Standard are provided for Site Class B.
Adjustments for other Site Classes are made, as needed, in Section 11.4.3.
From Figure 22-1 f1' SS = 1.689 g
From Figure 22-2 E_] S, = 0.802 g
Section 11.4.2 — Site Class
The authority having jurisdiction (not the USGS), site -specific geotechnical data, and/or
the default has classified the site as Site Class D, based on the site soil properties in
accordance with Chapter 20.
Table 20.3-1 Site Classification
Site Class
A. Hard Rock
B. Rock
C. Very dense soil and soft rock
b. Stiff Soil
E. Soft clay soil
F. Soils requiring site response
analysis in accordance with Section
21.1
VS R or N,.,, Sy
>5,000 ft/s N/A N/A
2,500 to 5,000 ft/s N/A N/A
1,200 to 2,500 ft/s >50 >2,000 psf
600 to 1,200 ft/s 15 to 50 1,000 to 2,000 psf
<600 ft/s <15 <1,000 psf
Any profile with more than 10 ft of soil having the characteristics:
• Plasticity index PI > 20,
• Moisture content w >_ 40%, and
• Undrained shear strength s. < 500 psf
See Section 20.3.1
For SI: 1ft/s = 0.3048 m/s llb/ft2 = 0.0479 kN/m2
littp://eartliquake.usgs.gov/designniaps/us/repoi-t.php?template=minimal&latitude=33.7373... 1 /13/2017
Design Maps Detailed Report
Page 2 of 6
Section 11.4.3 - Site Coefficients and Risk -Targeted Maximum Considered Earthquake
(MCE,) Spectral Response Acceleration Parameters
Table 11.4-1: Site Coefficient F.
Site Class Mapped MCE , Spectral Response Acceleration Parameter at Short Period
Ss -< 0.25 Sy = 0.50 SS = 0.75 SS = 1.00 SS >_ 1.25
A
0.8
0.8 0.8 0.8
0.8
B
1.0
1.0 1.0 1.0
1.0
C
1.2
1.2 1.1 1.0
1.0
D
1.6
1.4 1.2 1.1
1.0
E
2.5
1.7 1.2 0.9
0.9
F
See Section 11.4.7 of ASCE 7
Note: Use straight-line
interpolation for intermediate values of S.,
For Site Class = D and S. = 1.689 9, F. = 1.000
Table 11.4-2: Site Coefficient F,
Site Class Mapped MCE , Spectral Response Acceleration Parameter at 1-s Period
S,50.10 S,=0.20 S,=0.30 S,=0.40 S,>!0.50
A
0.8
0.8 0.8 0.8
0.8
B
1.0
1.0 1.0 1.0
1.0
C
1.7
1.6 1.5 1.4
1.3
D
2.4
2.0 1.8 1.6
1.5
E
3.5
3.2 2.8 2.4
2.4
F
See Section 11.4.7 of ASCE 7
Note: Use straight-line
interpolation for intermediate values of S,
For Site Class = D and S, = 0.802 9, F, = 1.500
littp://earthquake.usgs.gov/designmaps/us/report.php'?template=minimal&latitude=33.7373... 1 /13/2017
Design Maps Detailed Report
Page 3 of 6
Equation (11.4-1):
Equation (11.4-2):
SMs = F.Ss = 1.000 x 1.689 = 1.689 g
SM, = F,,S, = 1.500 x 0.802 = 1.203 g
Section 11.4.4 — Design Spectral Acceleration Parameters
Equation (11.4-3):
Equation (11.4-4):
Section 11.4.5 — Design Response Spectrum
From Figure 22-12 E31
SDS = % SMS = % x 1.689 = 1.126 g
SD►=%SM,=%x1.203=0.802g
T, = 8 seconds
Figure 11.4-1: Design Response Spectrum
T<T,:S,=Sa(0.4+0.6TIT,)
S,,=1.125 -- ToSTST8:S.=SDS
a
Ts<TsT,:S�=S�,IT
T>TL:S.=SMTL/T'
S„-0.802=------------- '
t '
r '
r
r
r
r i
T. 0.142 T, 0.7121.000
Parbd T (sac)
http://earthquake.usgs.gov/designmaps/us/report.php?template=minimal&latitude=33.7373... 1 / 13/2017
Design Maps Detailed Report
Page 4 of 6
Section 11.4.6 — Risk -Targeted Maximum Considered Earthquake (MCER) Response
Spectrum
The MCEN Response Spectrum is determined by multiplying the design response spectrum above by
1.5.
c
0
� S••, � 1.2�)3
a
v
u
v
Q
0
VI
C
0
a
4)
d
cc
t
d
n
W
T = 0.1-4 T = q 71 1 ,y
Period, T (sec)
http://earthquake.usgs.gov/designinaps/us/report.php?template=minimal&latitude=33.7373... 1 / 13/2017
Design Maps Detailed Report
Page 5 ol' 6
Section 11.8.3 - Additional Geotechnical Investigation Report Requirements for Seismic
Design Categories D through F
From Figure 22-71"1 PGA = 0.677
Equation (11.8-1): PGA, = F,,,,PGA = 1.000 x 0.677 = 0.677 g
Table 11.8-1: Site Coefficient Fes,,
Site
Mapped MCE Geometric Mean Peak Ground Acceleration, PGA
Class
PGA 5
PGA = PGA = PGA =
PGA >_
0.10
0.20 0.30 0.40
0.50
A
0.8
0.8 0.8 0.8
0.8
B
1.0
1.0 1.0 1.0
1.0
C
1.2
1.2 1.1 1.0
1.0
D
1.6
1.4 1.2 1.1
1.0
E
2.5
1.7 1.2 0.9
0.9
F
See Section 11.4.7 of ASCE 7
Note: Use straight-line
interpolation for intermediate values of PGA
For Site Class = D and PGA = 0.677 g, F,.„ = 1.000
Section 21.2.1.1 - Method 1 (from Chapter 21 - Site -Specific Ground Motion Procedures
for Seismic Design)
From Figure 22-17")
From Figure 22-18 "1
Ca,, = 1.015
C,, = 0.979
http://earthquake.usgs.gov/designniaps/us/report.php?template=minimal&latitude=33.7373... 1 /13/2017
Design Maps Detailed Report
Page 6 of 6
Section 11.6 — Seismic Design Category
'Fable 11.6-1 Seismic Desion Cateaory Based on Short Period Resnnnce ArrPlaratinn Param,- cpr
VALUF. OF SO,
RISK CATEGORY
I or II
III
IV
SOS < 0.1679
A
A
A
0.167g 5 SOS < 0.33g
B
B
C
0.33g 5 SOS < 0.50g
C
C
D
0.50g 5 SOS
D
D
D
For Risk Category = I and So: = 1.126 g, Seismic Design Category = D
Table 11.6-2 Seismic Design Cateaory Based on 1-S Period Resnnnce ArrelPration ParamatPr
VALUE OF S„
RISK CATEGORY
I or II
III
IV
So, < 0.067g
A
A
A
0.0679 5 So, < 0.133g
B
B
C
0.133g 5 So, < 0.20g
C
C
D
0.20g 5 So,
D
D
D
For Risk Category = I and So, = 0.802 g, Seismic Design Category = D
Note: When S, is greater than or equal to 0.75g, the Seismic Design Category is E for
buildings in Risk Categories I, II, and III, and F for those in Risk Category IV, irrespective
of the above.
Seismic Design Category - "the more severe design category in accordance with
Table 11.6-1 or 11.6-2" = E
Note: See Section 11.6 for alternative approaches to calculating Seismic Design Category.
References
1. Figure 22-1:
http://earthquake.usgs.gov/hazards/designmaps/downloads/pdfs/2010_ASCE-7_Figure_22-1.pdf
2. Figure 22-2:
http://earthquake. usgs.gov/hazards/designmaps/downloads/pdfs/2010_ASCE-7_Figure_22-2.pdf
3. Figure 22-12: http://earthquake.usgs.gov/hazards/designmaps/downloads/pdfs/2010 ASCE-7_Figure_22-
12.pdf
4. Figure 22-7:
http://earthquake.usgs.gov/hazards/designmaps/downloads/pdfs/2010 ASCE-7_Figure_22-7.pdf
5. Figure 22-17: http://earthquake.usgs.gov/hazards/designmaps/downloads/pdfs/2010_ASCE-7_Figure_22-
17.pdf
6. Figure 22-18: http://earthquake.usgs.gov/hazards/designmaps/downloads/pdfs/2010_ASCE-7_Figure_22-
18.pdf
http://earthquake.usgs.gov/designmaps/us/repoi-t.l)lip?template- minimal&latitude=33.7373... 1/13/2017
^
A
� w
as �+
>' ^ Cie
N � a
o E
o
a" cd
..� 0
00
�j bA� `DNA
U
�� o
= 000
II II •."
b w
cCi,.._, N UQ
xu
cV c�s�•5
96 e6 9 p
pjezey o/ uognquluoo %
E
0
0
r
l
N
s9 R
s
01� H
9y
1y
O�1g.
l
h0
�o
SS
W
0
D
o
N
91 O
V
N
M
V
v
v
G
w
V
w
w
V
v
O
O
N
m
E
■
a
_
o
v
v
�0 a
v
v
a
N
w
wv�
p V)
SS
as
V
w
V
N
V
v�
O
a
E
■
■
I!I
'0 0
Page 1 of 5
*** Deaggregation of Seismic Hazard at One Period of Spectral Accel. ***
** Data from U.S.G.S. National Seismic Hazards Mapping Project, 2008 version *`
PSHA Deaggregation. `kcontributions. site: 11-290 long: 116.303 W., lat: 33.737 N.
Vs30(m/s)= 275.0 (some WUS atten. models use Site Class not Vs30).
NSHMP 2007-08 See USGS OFR 2008-1128. dM=0.2 below
Return period: 2475 yrs.
Exceedance PGA=0.8691
g.
Weight
#Pr(at least one
eq with
median motion>=PGA
in 50 yrsj=0.00000
#This deaggregation corresponds to
Mean Hazard w/all
GMPEs
DIST(KM)
MAG(MW)
ALL EPS
EPSILON>2
1<EPS<2
0<EPS<l-1<EPS<0
-
7.5
5.05
0.646
0.639
0.007
0.000
0.000
7.6
5.20
1.410
1.262
0.148
0.000
0.000
12.1
5.21
0.084
0.084
0.000
0.000
0.000
7.6
5.40
1.532
1.207
0.325
0.000
0.000
12.2
5.40
0.131
0.131
0.000
0.000
0.000
7.7
5.60
1.550
1.099
0.451
0.000
0.000
12.3
5.60
0.174
0.174
0.000
0.000
0.000
7.7
5.80
1.469
0.973
0.496
0.000
0.000
12.6
5.80
0.210
0.210
0.000
0.000
0.000
7.3
6.02
2.017
1.221
0.796
0.000
0.000
13.9
5.99
0.210
0.210
0.000
0.000
0.000
7.0
6.20
2.671
1.427
1.243
0.000
0.000
14.7
6.20
0.320
0.320
0.000
0.000
0.000
7.0
6.40
2.649
1.150
1.490
0.010
0.000
14.1
6.40
0.523
0.509
0.014
0.000
0.000
7.0
6.65
3.252
2.205
1.015
0.032
0.000
13.5
6.60
0.284
0.277
0.007
0.000
0.000
23.4
6.60
0.051
0.051
0.000
0.000
0.000
7.6
6.84
13.413
8.214
5.171
0.029
0.000
13.5
6.80
0.411
0.389
0.021
0.000
0.000
24.6
6.78
0.053
0.053
0.000
0.000
0.000
7.6
6.99
13.818
6.866
6.936
0.016
0.000
12.6
6.99
0.411
0.336
0.075
0.000
0.000
24.0
7.00
0.062
0.062
0.000
0.000
0.000
7.6
7.17
14.076
5.250
8.534
0.292
0.000
15.4
7.21
0.223
0.174
0.049
0.000
0.000
35.9
7.23
0.153
0.153
0.000
0.000
0.000
7.4
7.41
12.935
4.091
7.785
1.059
0.000
14.4
7.41
0.330
0.222
0.109
0.000
0.000
23.7
7.40
0.065
0.064
0.000
0.000
0.000
34.5
7.39
0.330
0.330
0.000
0.000
0.000
7.4
7.63
7.403
2.077
4.421
0.905
0.000
13.3
7.55
0.260
0.161
0.099
0.000
0.000
33.8
7.58
0.879
0.879
0.000
0.000
0.000
7.5
7.78
6.207
1.568
3.709
0.930
0.000
33.8
7.79
0.486
0.473
0.012
0.000
0.000
7.5
7.97
7.239
1.647
4.308
1.284
0.000
14.1
7.95
0.060
0.031
0.030
0.000
0.000
7.4
8.19
1.448
0.309
0.850
0.289
0.000
7.4
8.39
0.060
0.012
0.036
0.013
0.000
Summary statistics for
Contribution from this
Mean src-site R= 8
Modal src-site R= 7
MODE R*= 7.6km; M*=
Computed -Rate -Ex 0.405E-03
2<EPS<-1
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
EPS<-2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
above PSHA PGA deaggregation, R=distance, e=epsilon:
GMPE M : 100.0
4 km; M= 7.06; eps0= 1.48. Mean calculated for all sources.
6 km; M= 7.17; eps0= 1.36 from peak (R,M) bin
7.17; EPS.INTERVAL: 1 to 2 sigma I CONTRIB.- 8.534
Principal sources (faults, subduction, .random seismicity having > 3`d contribution)
Source Category:
% contr.
R(km)
M
epsilon0 (mean values).
California A -faults
76.80
8.3
7.31
1.42
CA Compr. crustal gridded
17.25
7.9
5.96
1.71
San Gorgonio Zone gridded
5.38
9.3
7.11
1.59
Individual fault hazard details
if its contribution
to mean hazard > 2%:
Fault ID
contr.
Rcd(km)
M
epsilon0 Site-to-src azimuth(d)
S. S.Andr..;CO aPriori
7.78
7.7
6.98
1.57 44.4
littps://geohazards.usgs.gov/deaggint/2008/out/11-290_2017.01.13_19.28.32.txt 1 /l 3/2017
Page 2 of' 5
S. S.Andr.;SSB+BG aPriori
4.28
7.4
7.32
1.32
28.0
S. S.Andr.;BG+CO aPriori
3.53
7.5
7.36
1.29
28.0
S. S.Andr.;NSB+SSB+BG aPriori
2.11
7.4
7.45
1.27
28.0
S. S.Andr.;SSB+BG+CO aPriori
2.24
7.4
7.52
1.24
28.0
SSAndr.;NSB+SSB+BG+CO aPriori
2.39
7.4
7.62
1.20
28.0
SSAnd;SM+NSB+SSB+BG+CO aPriori
2.71
7.4
7.82
1.14
28.0
S. San Andreas;CO MoBal
26.88
7.7
6.95
1.60
44.4
S. San Andreas;BG+CO MoBal
2.20
7.5
7.36
1.29
28.0
S. San Andreas;SM+NSB+SSB+BG+CO
2.17
7.4
7.82
1.14
28.0
S. San Andreas Unsegmented A-flt
5.30
7.8
7.74
1.21
24.6
#*********End of deaggregation corresponding
to Mean Hazard w/all GMPEs
*********#
PSHA Deaggregation. %contributions.
site: 11-290
long: 116.303 W.,
lat: 33.737 N.
Vs30(m/s)= 275.0 (some WUS atten.
models use
Site Class
not Vs30).
NSHMP 2007-08 See USGS OFR 2008-1128. dM=0.2 below
Return period: 2475 yrs.
Exceedance PGA-0.8691
g. Weight
#Pr[at least one
eq with
median motion>=PGA
in 50 yrsj=0.00000
*This deaggregation corresponds
to
Boore-Atkinson 2008
DIS'r(KM)
MAG(MW)
ALL EPS
EPSILON>2
1<EPS<2
0<EPS<1
-1<EPS<0 -
7.0
5.05
0_028
0.028
0.000
0.000
0.000
7.2.
5.21
0.083
0.083
0.000
0.000
0.000
7.3
5.40
0.131
0.131
0.000
0.000
0.000
7.5
5.60
0.177
0.177
0.000
0.000
0.000
7.6
5.80
0.216
0.216
0.000
0.000
0.000
7.0
6.02
0.403
0.393
0.011
0.000
0.000
14.2.
6.00
0.029
0.029
0.000
0.000
0.000
6.7
6.20
0.603
0.566
0.038
0.000
0.000
14.9
6.21
0.072
0.072
0.000
0.000
0.000
6.8
6.40
0.615
0.559
0.056
0.000
0.000
14.4
6.40
0.141
0.141
0.000
0.000
0.000
23.9
6.43
0.038
0.038
0.000
0.000
0.000
7.3
6.67
1.479
1.165
0.314
0.000
0.000
14.0
6.60
0.157
0.157
0.000
0.000
0.000
23.5
6.59
0.050
0.050
0.000
0.000
0.000
7.6
6.85
6.389
4.151
2.237
0.000
0.000
14.0
6.80
0.240
0.240
0.000
0.000
0.000
24.6
6.78
0.052
0.052
0.000
0.000
0.000
7.7
6.99
6.665
3.495
3.170
0.000
0.000
12.9
6.99
0.224
0.221
0.003
0.000
0.000
24.1
7.00
0.057
0.057
0.000
0.000
0.000
35.9
7.00
0.028
0.028
0.000
0.000
0.000
7.6
7.17
7.023
2.729
4.294
0.000
0.000
15.7
7.21
0.135
0.133
0.002
0.000
0.000
25.0
7.19
0.037
0.037
0.000
0.000
0.000
35.9
7.23
0.153
0.153
0.000
0.000
0.000
44.8
7.16
0.022
0.022
0.000
0.000
0.000
53.7
7.23
0.022
0.022
0.000
0.000
0.000
7.4
7.42
5.444
2.053
3.295
0.096
0.000
14.5
7.41
0.182
0.170
0.013
0.000
0.000
24.0
7.40
0.050
0.050
0.000
0.000
0.000
34.5
7.39
0.324
0.324
0.000
0.000
0.000
7.4
7.63
3.316
1.034
2.078
0.204
0.000
13.5
7.56
0.133
0.112
0.021
0.000
0.000
24.3
7.56
0.024
0.024
0.000
0.000
0.000
33.8
7.58
0.827
0.827
0.000
0.000
0.000
53.4
7.58
0.037
0.037
0.000
0.000
0.000
7.5
7.78
2.809
0.771
1.781
0.258
0.000
14.2
7.81
0.030
0.016
0.014
0.000
0.000
33.8
-1.79
0.436
0.424
0.012
0.000
0.000
7.5
7.97
3.261
0.810
2.050
0.401
0.000
14.6
7.95
0.039
0.018
0.021
0.000
0.000
33.7
7.98
0.041
0.036
0.005
0.000
0.000
53.8
7.98
0.028
0.028
0.000
0.000
0.000
7.4
8.19
0.654
0.154
0.402
0.098
0.000
Computed -Rate -Ex 0.174E-03
2<EPS<-1
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
EPS<-2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
https:Hgeohazards.usgs.gov/deaggint/2008/out/i 1-290_2017.01.13_ 19.28.32.txt 1 / 13/2017
Page 3 of 5
7.4 8.39 0.027 0.006 0.017 0.005 0.000 0.000 0.000
Summary statistics for above PSHA PGA deaggregation, R=distance, e=epsilon:
Contribution from this GMPE(E): 43.1
Mean src-site R= 9.2 km; M= 7.21; eps0= 1.54. Mean calculated for all sources.
Modal src-site R= 7.6 km; Mn 7.17; eps0= 1.39 from peak (R,M) bin
MODE R*= 7.6km; M*= 7.18; EPS.INTERVAL: 1 to 2 sigma % CONTRIB.= 4.294
Principal sources (faults, subduction, random seismicity having > 3% contribution)
Source Category:
contr.
R(km)
M
epsilon0
(mean values).
California A -faults
37.26
9.0
7.30
1.50
Individual fault hazard details if
its contribution
to
mean hazard
> 2%:
Fault ID %
contr.
Rcd(km)
M
epsilon0
Site-to-src azimuth(d)
S. S.Andr.;CO aPriori
3.77
7.7
6.98
1.61
44.4
S. S.Andr.;SSB+BG aPriori
2.02
7.4
7.31
1.37
28.0
S. S.Andr.;BG+CO aPriori
1.62
7.5
-1.36
1.36
28.0
S. S.Andr.;NSB+SSB+BG aPriori
0.98
7.4
7.45
1.33
28.0
S. S.Andr.;SSBtBG+CO aPriori
1.02
7.4
7.52
1.31
28.0
SSAndr.;NSB+SSB+SG+CO aPriori
1.08
7.4
7.61
1.28
28.0
SSAnd;SM+NSB+SSB+BG+CO aPriori
1.22
7.4
7.82
1.22
28.0
S. San Andreas;CO MoBal
13.09
7.7
6.95
1.63
44.4
S. San Andreas;BG+CO Modal
1.01
7.5
7.35
1.36
28.0
S. San Andreas;SM+NSB+SSB+BG+CO
0.98
7.4
7.82
1.22
28.0
S. San Andreas Unsegmented A-flt
2.50
8.0
7.73
1.30
24.6
#*********End of deagqregation corresponding
to Boor.e-Atkinson
2008
PSHA Deaggregation. %contributions. site: 11-290 long: 116.303 W., lat: 33.737 N.
Vs30(m/s)= 275.0 (some WUS atten. models use Site Class not Vs30).
NSHMP 2007-08 See USGS OFR 2008-1128. dM=0.2 below
Return period: 2475 yrs. Exceedance PGA =0.8691 g. Weight * Computed Rate Ex 0.151E-04
#Pr[at least one
eq with
median motion>=PGA
in 50 yrs]=0.00000
#This deagqregation corresponds to
Campbell-Bozorgnia 2006
DIST(KM)
MAG(MW)
ALL_EPS
EPSILON>2
1<EPS<2
0<EPS<1
-1<EPS<0-2<EPS<-1
EPS<-2
7.2
5.05
0.043
0.043
0.000
0.000
0.000
0.000
0.000
7.4
5.21
0.135
0.135
0.000
0.000
0.000
0.000
0.000
7.5
5.41
0.225
0.225
0.000
0.000
0.000
0.000
0.000
11.9
5.45
0.002
0.002
0.000
0.000
0.000
0.000
0.000
7.6
5.60
0.264
0.264
0.000
0.000
0.000
0.000
0.000
12.1
5.61
0.009
0.009
0.000
0.000
0.000
0.000
0.000
7.7
5.80
0.243
0.243
0.000
0.000
0.000
0.000
0.000
12.1
5.80
0.012
0.012
0.000
0.000
0.000
0.000
0.000
7.3
6.01
0.288
0.288
0.000
0.000
0.000
0.000
0.000
13.1
5.99
0.012
0.012
0.000
0.000
0.000
0.000
0.000
6.9
6.20
0.397
0.394
0.004
0.000
0.000
0.000
0.000
14.3
6.20
0.022
0.022
0.000
0.000
0.000
0.000
0.000
6.9
6.40
0.456
0.426
0.030
0.000
0.000
0.000
0.000
13.6
6.40
0.050
0.050
0.000
0.000
0.000
0.000
0.000
5.5
6.60
0.261
0.226
0.035
0.000
0.000
0.000
0.000
12.6
6.60
0.032
0.032
0.000
0.000
0.000
0.000
0.000
5.8
6.80
0.207
0.181
0.027
0.000
0.000
0.000
0.000
12.4
6.80
0.038
0.038
0.000
0.000
0.000
0.000
0.000
6.9
7.00
0.211
0.192
0.018
0.000
0.000
0.000
0.000
12.1
6.99
0.041
0.041
0.000
0.000
0.000
0.000
0.000
7.6
7.18
0.270
0.251
0.019
0.000
0.000
0.000
0.000
14.8
7.20
0.016
0.016
0.000
0.000
0.000
0.000
0.000
7.1
7.40
0.245
0.218
0.027
0.000
0.000
0.000
0.000
14.2
7.41
0.023
0.023
0.000
0.000
0.000
0.000
0.000
7.1
7.60
0.108
0.098
0.011
0.000
0.000
0.000
0.000
12.8
7.55
0.019
0.019
0.000
0.000
0.000
0.000
0.000
7.4
7.78
0.046
0.046
0.000
0.000
0.000
0.000
0.000
7.4
7.97
0.047
0.047
0.000
0.000
0.000
0.000
0.000
7.4
8.22
0.007
0.007
0.000
0.000
0.000
0.000
0.000
Summary statistics for above PSHA PGA deagqregation, R=distance, e=epsilon:
littps://geoha7ards.usgs.gov/deaggint/2008/ouUI 1-290_2017.01.13_ 19.28.32.txt 1 / 13/2017
Page 4 or 5
Contribution from this GMPE(%): 3.7
Mean src-site R= 7.5 km; M= 6.42; eps0- 1.97. Mean calculated for all sources.
Modal src-site R= 6.9 km; M= 6.40; eps0- 1.75 from peak (R,M) bin
MODE R*= 6.9km; M*= 6.40; EPS.INTERVAL: 1 to 2 sigma % CONTRIB.= 0.426
Principal sources (faults, subduction, random seismicity having > 3% contribution)
Source Category: % contr. R(km) M epsilon0 (mean values).
Individual fault hazard details if its contribution to mean hazard > 2%:
Fault ID % contr. Rcd(km) M epsilon0 Site-to-src
S. S.Andr.;CO aPriori
S. S.Andr.;SSB+BG aPriori
S. S.Andr.;BG+CO aPriori
S. S.Andr.;NSB+SSB+BG aPriori
S. S.Andr.;SSB+BG+CO aPriori
SSAndr.;NSB+SSB+BG+CO aPriori
SSAnd;SM+NSB+SSB+BG4CO aPriori
S. San Andreas;CO MoBal
S. San Andreas;BG+CO MoBal
S. San Andreas;SM+NSB+SSB+BG+CO
S. San Andreas Unsegmented A-flt
0.04
7.7
7.08
2.53
44.4
0.04
7.4
7.31
2.42
28.0
0.03
7.5
7.36
2.41
28.0
0.02
7.4
7.45
2.40
28.0
0.02
7.4
7.51
2.39
28.0
0.02
7.4
7.61
2.38
28.0
0.02
7.4
7.82
2.35
28.0
0.12
7.7
7.06
2.54
44.4
0.02
7.5
7.35
2.41
28.0
0.02
7.4
7.82
2.35
28.0
0.00
0.0
0.00
0.00
24.6
azimuth(d)
#*********End of deaggregation corresponding to Campbell-Bozorgnia 2008 *********#
PSHA Deaggregation. %contributions. site: 11-290 long: 116.303 W., lat: 33.737 N.
Vs30(m/s)= 275.0 (some WUS atten. models use Site Class not Vs30).
NSHMP 2007-08 See USGS OFR 2008-1128. dM=0.2 below
Return period:
2475 yrs.
Exceedance PGA=0.8691 g.
Weight
#Pr[at least
one
eq with
median motion>=PGA
in 50 yrs]-0.00000
#This deaggregation
corresponds to
Chiou-Youngs 2008
DIST(KM)
MAG(MW)
ALL_EPS
EPSILON>2
1<EPS<2
0<EPS<l-1<EPS<0 -
7.6
5.05
0.575
0.575
0.000
0.000
0.000
7.6
5.20
1.192
1.172
0.020
0.000
0.000
12.1
5.21
0.084
0.084
0.000
0.000
0.000
7.7
5.40
1.177
1.082
0.095
0.000
0.000
12.2
5.40
0.129
0.129
0.000
0.000
0.000
7.7
5.60
1.109
0.948
0.161
0.000
0.000
12.4
5.60
0.160
0.160
0.000
0.000
0.000
7.8
5.80
1.011
0.806
0.205
0.000
0.000
12.6
5.80
0.184
0.184
0.000
0.000
0.000
7.4
6.01
1.326
1.062
0.264
0.000
0.000
13.9
5.99
0.169
0.169
0.000
0.000
0.000
7.1
6.20
1.670
1.241
0.428
0.000
0.000
14.7
6.20
0.226
0.226
0.000
0.000
0.000
7.1
6.40
1.578
1.030
0.548
0.000
0.000
14.0
6.40
0.331
0.331
0.000
0.000
0.000
6.9
6.65
1.511
1.174
0.337
0.000
0.000
13.0
6.60
0.095
0.095
0.000
0.000
0.000
7.6
6.84
6.818
4.209
2.609
0.000
0.000
12.8
6.80
0.132
0.131
0.000
0.000
0.000
7.6
6.99
6.943
3.429
3.510
0.003
0.000
12.3
6.99
0.146
0.145
0.001
0.000
0.000
7.6
7.16
7.124
2.594
4.191
0.339
0.000
14.9
7.21
0.072
0.071
0.001
0.000
0.000
7.4
7.41
6.930
2.088
4.007
0.835
0.000
14.3
7.41
0.125
0.118
0.007
0.000
0.000
7.4
7.63
3.954
1.040
2.247
0.667
0.000
13.1
7.55
0.108
0.089
0.019
0.000
0.000
33.8
7.60
0.052
0.052
0.000
0.000
0.000
7.5
7.78
3.352
0.752
1.928
0.672
0.000
33.8
7.80
0.049
0.049
0.000
0.000
0.000
7.5
7.97
3.932
0.791
2.258
0.883
0.000
7.4
8.19
0.787
0.149
0.448
0.191
0.000
7.4
8.39
0.033
0.006
0.019
0.008
0.000
Computed_Rate_Ex 0.2.15E-03
2<EPS<-1
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
EPS<-2
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
Summary statistics for above PSHA PGA deaggregation, R=distance, e=epsilon:
https:Hgeohazards.usgs.gov/deaggint/2008/out/11-290_2017.01.13_19.28.32.txt 1/13/2017
Page 5 of 5
Contribution from this GMPE(%): 53.2
Mean src-site R- 7.8 km; M= 6.99; eps0= 1.40. Mean calculated for all sources.
Modal src-site R- 7.6 km; M= 7.16; eps0- 1.29 from peak (R,M) bin
MODE R*= 7.6km; M*- 6.84; EPS.INTERVAL: 1 to 2 sigma % CONTRIB.= 4.209
Principal sources (faults, subduction, random seismicity having > 3% contribution)
Source Category: %
contr.
R(km)
M
epsilon0
(mean values).
California A -faults
39.05
7.7
7.32
1.33
CA Compr. crustal gridded
11.75
8.0
5.88
1.61
Individual fault hazard details if
its contribution
to mean hazard > 2%:
Fault ID B
contr.
Rcd(km)
M
epsilon0
Site-to-src azimuth(d)
S. S.Andr.;CO aPriori
3.97
7.7
6.98
1.53
44.4
S. S.Andr.;SSB+BG aPriori
2.21
7.4
7.32
1.25
28.0
S. S.Andr.;BG+CO aPriori
1.87
7.5
7.36
1.21
28.0
S. S.Andr.;NSB+SSB+BG aPriori
1.11
7.4
7.46
1.19
28.0
S. S.Andr.;SSB+BG+CO aPriori
1.20
7.4
7.52
1.16
28.0
SSAndr.;NSB+SSB+BG+CO aPriori
1.29
7.4
7.62
1.12
28.0
SSAnd;SM+NSB+SSB+BG+CO aPriori
1.46
7.4
7.82
1.06
28.0
S. San Andreas;CO Modal
13.67
7.7
6.96
1.56
44.4
S. San Andreas;BG+CO Modal
1.16
7.5
7.36
1.21
28.0
S. San Andreas;SM+NSB+SSB+BG+CO
1.17
7.4
7.82
1.05
28.0
S. San Andreas Unsegmented A-flt
2.80
7.6
7.75
1.12
24.6
#*********End of deaggregation corresponding
to Chiou-Youngs
2008
*********#
******************** Southern California ****************************************
https://geohazards.usgs.gov/deaggint/2008/out/11-290_2017.01.13_ 19.28.32.txt 1 /13/2017
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 1 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
A. PROJECT GENERAL INFORMATION
1.Project Location (city)La Quinta 8.Standards Version Compliance2016
2.CA Zip Code 9.Compliance Software (version)EnergyPro 7.1
3.Climate Zone 15 10.Weather File PALM-SPRINGS-INTL_722868_CZ2010.epw
4.Total Conditioned Floor Area in Scope 3,096 ft2 11.Building Orientation (deg)(N) 0 deg
5.Total Unconditioned Floor Area 354 ft2 12.Permitted Scope of Work NewComplete
6.Total # of Stories (Habitable Above Grade)1 13 Building Type(s)Nonresidential
7.Total # of dwelling units 0 14 Gas Type NaturalGas
B. COMPLIANCE RESULTS FOR PERFORMANCE COMPONENTS (Annual TDV Energy Use, kBtu/ft 2-yr)§ 140.1
BUILDING COMPLIES
1. Energy Component 2. Standard Design (TDV)3. Proposed Design (TDV)4. Compliance Margin (TDV)5. Percent Better than Standard
Space Heating 0.43 2.66 -2.23 -518.6%
Space Cooling 239.97 229.92 10.05 4.2%
Indoor Fans 186.66 123.85 62.81 33.6%
Heat Rejection --------
Pumps & Misc.--------
Domestic Hot Water 20.12 16.83 3.29 16.4%
Indoor Lighting 64.82 49.14 15.68 24.2%
COMPLIANCE TOTAL 512.00 422.40 89.60 17.5%
Receptacle 114.40 114.40 0.0 0.0%
Process --------
Other Ltg --------
TOTAL 626.40 536.80 89.6 14.3%
BCPR2017-0001 -
BUILDING
CONSTRUCTION PLAN
REVIEW FOR
WASHINGTON STREET
APARTMENTS PHASE 1
CITY OF LA QUINTA
BUILDING DIVISION
APPROVED
FOR CONSTRUCTION
BY: DATE: 03/19/2018
BUILDING H – BRES2018-0052
BUILDING J – BRES2018-0053
BUILDING K – BRES2018-0041
BUILDING L – BRES2018-0042
BUILDING M – BRES2018-0043
BUILDING N – BRES2018-0044
COMMONS – BCOM2018-0008
LAUNDRY/MAINTENANCE – BCOM2018-0009
PHASE 1 BUILDING PERMITS
BUILDING A – BRES2018-0045
BUILDING B – BRES2018-0046
BUILDING C – BRES2018-0047
BUILDING D – BRES2018-0048
BUILDING E – BRES2018-0049
BUILDING F – BRES2018-0050
BUILDING G – BRES2018-0051
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 2 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
C. PRIORITY PLAN CHECK/ INSPECTION ITEMS (in order of highest to lowest TDV energy savings)
1st Indoor Fans: Check envelope and mechanical Compliance Margin By Energy Component (from Table B column 4)
Indoor Fans
Indoor Lighting
Space Cooling
Domestic Hot Water
Heat Rejection
Pumps & Misc.
Space Heating
Penalty Energy Credit
2nd Indoor Lighting: Check lighting
3rd Space Cooling: Check envelope and mechanical
4th Domestic Hot Water: Check mechanical
5th Heat Rejection: Check envelope and mechanical
6th Pumps & Misc.: Check mechanical
7th Space Heating: Check envelope and mechanical
D. EXCEPTIONAL CONDITIONS
The aged solar reflectance and aged thermal emittance must be listed in the Cool Roof Rating Council database of certified products. For projects where initial reflectance is used, the initial
reflectance must be listed, and the aged reflectance is calculated by the software program and used in the compliance model.
This project includes Domestic Hot Water in the analysis. Please verify that Domestic Hot Water is included in the design for the permitted scope of work.
E. HERS VERIFICATION
This Section Does Not Apply
F. ADDITIONAL REMARKS
Initial design is based on 50% CD documents provided by Studio E Architects dated 04/29/16 - Originally created on EP6.8.0.2
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 3 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY
Identify which building components use the performance or prescriptive path for compliance. “NA”= not in project
For components that utilize the performance path, indicate the sheet number that includes mandatory notes on plans.
Building Component Compliance Path Compliance Forms (required for submittal)Location of Mandatory Notes on
Plans
Envelope
Performance NRCC-PRF-ENV-DETAILS (section of the NRCC-PRF-01-E)
Prescriptive NRCC-ENV-01 / 02 / 03 / 04 / 05 / 06-E
NA
Mechanical
Performance NRCC-PRF-MCH-DETAILS (section of the NRCC-PRF-01-E)
Prescriptive NRCC-MCH-01 / 02 / 03 / 04 / 05 / 06 / 07-E
NA
Domestic Hot Water
Performance NRCC-PRF-PLB-DETAILS (section of the NRCC-PRF-01-E)
Prescriptive NRCC-PLB-01-E
NA
Lighting (Indoor Conditioned)
Performance NRCC-PRF-LTI-DETAILS (section of the NRCC-PRF-01-E)
Prescriptive NRCC-LTI-01 / 02 / 03 / 04 / 05-E
NA
Covered Process:
Commercial Kitchens
Performance S2 (section of the NRCC-PRF-01-E)
Prescriptive NRCC-PRC-01/ 03-E
NA
Covered Process:
Computer Rooms
Performance S3 (section of the NRCC-PRF-01-E)
Prescriptive NRCC-PRC-01/ 04-E
NA
Covered Process:
Laboratory Exhaust
Performance S4 (section of the NRCC-PRF-01-E)
Prescriptive NRCC-PRC-01/ 09-E
NA
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 4 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY
The following building components are only eligible for prescriptive compliance. Indicate which are
relevant to the project.
The following building components may have mandatory requirements per Part 6. Indicate
which are relevant to the project.
Yes NA Prescriptive Requirement Compliance Forms Yes NA Mandatory Requirement Compliance Forms
Lighting (Indoor
Unconditioned) §140.6 NRCC-LTI-01 / 02 / 03 / 04 / 05-E
Commissioning: §120.8
Simple Systems
Complex Systems
NRCC-CXR-01 / 02 / 03 / 05-E
NRCC-CXR-01 / 02 / 04 / 05-E
Lighting (Outdoor) §140.7 NRCC-LTO-01 / 02 / 03-E Electrical: §130.5 NRCC-ELC-01-E
Lighting (Sign) §140.8 NRCC-LTS-01-E Solar Ready: §110.10 NRCC-SRA-01 / 02-E
Solar Thermal Water
Heating: §140.5 NRCC-STH-01-E
Covered Process: §120.6
Parking Garage
Commercial Refrigeration
Warehouse Refrigeration
Compressed Air
Process Boilers
NRCC-PRC-01-E
NRCC-PRC-02-E
NRCC-PRC-05-E
NRCC-PRC-06/07/08-E
NRCC-PRC-10-E
NRCC-PRC-11-E
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 5 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV)–
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance
(Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment.
Confirmed
Building Component Compliance Forms (required for submittal)Pass Fail
Envelope
NRCI-ENV-01-E - For all buildings
NRCA-ENV-02-F- NFRC label verification for fenestration
Mechanical
NRCI-MCH-01-E - For all buildings with Mechanical Systems
NRCA-MCH-02-A- Outdoor Air
NRCA-MCH-03-A – Constant Volume Single Zone HVAC
NRCA-MCH-04-H- Air Distribution Duct Leakage
NRCA-MCH-05-A- Air Economizer Controls
NRCA-MCH-06-A- Demand Control Ventilation
NRCA-MCH-07-A – Supply Fan Variable Flow Controls
NRCA-MCH-08-A- Valve Leakage Test
NRCA-MCH-09-A – Supply Water Temp Reset Controls
NRCA-MCH-10-A- Hydronic System Variable Flow Controls
NRCA-MCH-11-A – Auto Demand Shed Controls
NRCA-MCH-12-A- Packaged Direct Expansion Units
NRCA-MCH-13-A- Air Handling Units and Zone Terminal Units
NRCA-MCH-14-A- Distributed Energy Storage
NRCA-MCH-15-A – Thermal Energy Storage
NRCA-MCH-16-A- Supply Air Temp Reset Controls
NRCA-MCH-17-A – Condensate Water Temp Reset Controls
NRCA-MCH-18-A- Energy Management Controls Systems
NRCV-MCH-04-H- Duct Leakage Test
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 6 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV)–
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance
(Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment.
Confirmed
Building Component Compliance Forms (required for submittal)Pass Fail
Plumbing
NRCI-PLB-01-E - For all buildings with Plumbing Systems
NRCI-PLB-02-E - required on central systems in high‐rise residential, hotel/motel application.
NRCI-PLB-03-E - Single dwelling unit systems in high‐rise residential, hotel/motel application.
NRCI-PLB-21-E - HERS verified central systems in high‐rise residential, hotel/motel application.
NRCI-PLB-22-E - HERS verified single dwelling unit systems in high‐rise residential, hotel/motel application.
NRCV-PLB-21-H- HERS verified central systems in high‐rise residential, hotel/motel application.
NRCV-PLB-22-H - HERS verified single dwelling unit systems in high‐rise residential, hotel/motel application.
NRCI-STH-01-E - Any solar water heating
Indoor Lighting
NRCI-LTI-01-E - For all buildings
NRCI-LTI-02-E - Lighting control system, or for an Energy Management Control System (EMCS)
NRCI-LTI-03-E - Line-voltage track lighting integral current limiter, or for a supplementary overcurrent protection panel used to
energize only line-voltage track lighting
NRCI-LTI-04-E - Two interlocked systems serving an auditorium, a convention center, a conference room, or a theater
NRCI-LTI-05-E - Lighting Control Credit Power Adjustment Factor (PAF)
NRCI-LTI-06-E - Additional wattage installed in a video conferencing studio
NRCA-LTI-02-A - Occupancy sensors and automatic time switch controls.
NRCA-LTI-03-A - Automatic daylighting controls
NRCA-LTI-04-A - Demand responsive lighting controls
Outdoor Lighting
NRCI-LTO-01-E – Outdoor Lighting
NRCI-LTO-02-E- EMCS Lighting Control System
NRCA-LTO-02-A - Outdoor Lighting Control
Sign Lighting NRCI-LTS-01-E – Sign Lighting
Electrical NRCI-ELC-01-E - Electrical Power Distribution
Photovoltaic NRCI-SPV-01-E Photovoltaic Systems
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 7 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV)–
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance
(Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment.
Confirmed
Building Component Compliance Forms (required for submittal)Pass Fail
Covered Process
NRCI-PRC-01-E Refrigerated Warehouse
NRCA-PRC-01-F- Compressed Air Systems
NRCA-PRC-02-F- Kitchen Exhaust
NRCA-PRC-03-F- Garage Exhaust
NRCA-PRC-04-F- Refrigerated Warehouse- Evaporator Fan Motor Controls
NRCA-PRC-05-F- Refrigerated Warehouse- Evaporative Condenser Controls
NRCA-PRC-06-F- Refrigerated Warehouse- Air Cooled Condenser Controls
NRCA-PRC-07F- Refrigerated Warehouse- Variable Speed Compressor
NRCA-PRC-08-F- Electrical Resistance Underslab Heating System
I. ENVELOPE GENERAL INFORMATION (See NRCC-PRF-ENV-DETAILS for more information)
1.Total Conditioned Floor Area 3,096 ft2 5.Number of Floors Above Grade 1 Confirmed
2.Total Unconditioned Floor Area 354 ft2 6.Number of Floors Below Grade 0
Pa
s
s
Fa
i
l
3.Addition Conditioned Floor Area 0 ft2
4.Addition Unconditioned Floor Area 0 ft2
7. Opaque Surfaces & Orientation 8. Total Gross Surface Area 9. Total Fenestration Area 10. Window to Wall Ratio
North Wall 1,236 ft2 165 ft2 13.3%
East Wall 1,110 ft2 487 ft2 43.9%
South Wall 1,404 ft2 743 ft2 52.9%
West Wall 434 ft2 68 ft2 15.6%
Total 4,184 ft2 1,463 ft2 35.0%
Roof 3,096 ft2 0 ft2 00.0%
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 8 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
J. FENESTRATION ASSEMBLY SUMMARY § 110.6 Confirmed
1.2.3.4.5.6.7.8.9.
Pa
s
s
Fa
i
lFenestration Assembly Name /
Tag or I.D.
Fenestration Type / Product Type
/ Frame Type Certification Method1 Assembly Method Area ft2 Overall
U-factor
Overall
SHGC
Overall
VT
St
a
t
u
s
2
New Storefront
VerticalFenestration
CurtainWall
N/A
NFRC Rated SiteBuilt 1200 0.41 0.22 0.53 N
New Glass Door
VerticalFenestration
GlazedDoor
N/A
NFRC Rated Manufactured 120 0.45 0.23 0.53 N
New Storefront P
VerticalFenestration
CurtainWall
N/A
NFRC Rated SiteBuilt 143 0.41 0.22 0.53 N
1 Newly installed fenestration shall have a certified NFRC Label Certificate or use the CEC default tables found in Table 110.6-A and Table 110.6-B. Center of Glass (COG) values are for the glass-only, determined by the manufacturer, and are shown for ease
of verification. Site-built fenestration values are calculated per Nonresidential Appendix NA6 and are used in the analysis.
2 Status: N - New, A – Altered, E – Existing
Taking compliance credit for fenestration shading devices?(if "Yes", see NRCC-PRF-ENV-DETAILS for more information)No
K. OPAQUE SURFACE ASSEMBLY SUMMARY § 120.7/ § 140.3 Confirmed
1.2.3.4.5.6.7.8.
Pa
s
s
Fa
i
l
Surface Name Surface Type Area (ft2)Framing
Type
Cavity
R-Value
Continuous
R-Value
U-Factor / F-Factor
/ C-Factor
St
a
t
u
s
1
R-30 Metal Seam Roof - Gr10 Roof 3450 Metal 30 NA U-Factor: 0.056 N
Slab On Grade13 UndergroundFloor 3450 NA 0 NA F-Factor: 0.730 N
R-19 Wall15 ExteriorWall 4822 Wood 19 NA U-Factor: 0.072 N
R-11 Wall83 InteriorWall 252 Wood 11 NA U-Factor: 0.103 N
1 Status: N - New, A – Altered, E – Existing
L. ROOFING PRODUCT SUMMARY § 140.3 Confirmed
1.2.3.4.5.6.7.
Pa
s
s
Fa
i
l
Product Type Product Density
(lb/ft2)
Aged Solar
Reflectance
Thermal
Emittance SRI Cool Roof
Credit
Roofing Product
Description
R-30 Metal Seam Roof - Gr10 4.65104 0.35 0.83 Not Provided Yes CRRC Prod. ID: R-30 Metal
Seam Roof - Grey
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 9 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
M. HVAC SYSTEM SUMMARY (see NRCC-PRF-MCH-DETAILS for more information)§ 110.1 / § 110.2
Dry System Equipment 1 (Fan & Economizer info included below in Table N)Confirmed
1.2.3.4.5.6.7.8.9.10.11.
Pa
s
s
Fa
i
l
Equip Name Equip Type
System Type
(Simple 2 or
Complex 3)
Qty
Total Heating
Output
(kBtu/h)
Supp Heat
Source (Y/N)
Supp Heat
Output
(kBtuh)
Total Cooling
Output
(kBtu/h)
Efficiency
Acceptance
Testing
Required? (Y/N)
4
St
a
t
u
s
5CoolingHeating
Multipurpose +
Hall + Kit SZHP (Split3Phase)Simple 2 54 No 0 52 SEER-14.0 /
EER-11.0 HSPF-8.2 Yes N
Multipurpose +
Hall + Kit3 Exhaust ((null))Simple 1 0 No 0 0 NA NA No N
Washrooms28 Exhaust ((null))Simple 2 0 No 0 0 NA NA No N
Office SZHP (Split3Phase)Simple 1 24 No 0 23 SEER-13.0 /
EER-11.5 HSPF-7.7 Yes N
Laundry +
Maintenance SZHP (Split3Phase)Simple 1 33 No 0 31 SEER-14.0 /
EER-11.5 HSPF-8.2 Yes N
Laundry70 Exhaust ((null))Simple 1 0 No 0 0 NA NA No N
1 Dry System Equipment includes furnaces, air handling units, heat pumps, etc.
2 Simple Systems must complete NRCC-CXR-03-E commissioning design review form
3 Complex Systems must complete NRCC-CXR-04-E commissioning design review form
4 A summary of which acceptance tests are applicable is provided in NRCC-PRF-MCH-DETAILS
5 Status: N - New, A – Altered, E – Existing
Wet System Equipment 1 Pumps Confirmed
12.13.14.15.16.17.18.19.20.21.22.23.24.
Pa
s
s
Fa
i
l
Equip Name Equip Type Qty Vol (gal)Rated Capacity
(kBtu/h)Efficiency Standby Loss
Tank
Ext. R
Value
Qty GPM HP VSD
(Y/N)
St
a
t
u
s
2
WH1 Rheem PRO+G40-36U
RH62 Storage 2 40 36 EF: 0.680 NA NA NA NA NA No N
WH3 Rinnai RL94E69 Instantaneous 6 1 199 EF: 0.820 NA NA NA NA NA No N
1 Wet System Equipment includes boilers, chillers, cooling towers, water heaters, etc.
2 Status: N - New, A – Altered, E – Existing
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 10 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
Discrepancy between modeled and designed equipment sizing?(if "Yes", see Table F. "Additional Remarks" for an explanation)No
N. ECONOMIZER & FAN SYSTEMS SUMMARY1 § 140.4 Confirmed
1.2.3.4.5.
Pa
s
s
Fa
i
l
Equip Name
Outside
Air Supply Fan Return Fan
Economizer Type
(if present)
CFM CFM HP BHP
TSP
(inch
WC)
Control CFM HP BHP
TSP
(inch
WC)
Control
Multipurpose +
Hall + Kit 401 2000 0.750 0.750 1.43 ConstantVolume NA NA NA NA NA NoEconomizer
Office 35 700 0.400 0.400 1.81 ConstantVolume NA NA NA NA NA NoEconomizer
Laundry +
Maintenance 143 1170 0.510 0.510 1.38 ConstantVolume NA NA NA NA NA NoEconomizer
1 Mechanical ventilation calculations and exhaust fans are included in the NRCC-PRF-MCH-DETAILS section
O. EQUIPMENT CONTROLS § 120.2 Confirmed
1.2.3.Pa
s
s
Fa
i
l
Equip Name Equip Type Controls
Multipurpose + Hall + Kit SZHP
No DCV Controls
No Economizer
No Supply Air Temp. Control
No Optimum Start
No Evaporative Cooler
Multipurpose + Hall + Kit3 Exhaust
No DCV Controls
Economizer type not properly specified
No Supply Air Temp. Control
No Optimum Start
No Evaporative Cooler
Washrooms28 Exhaust
No DCV Controls
Economizer type not properly specified
No Supply Air Temp. Control
No Optimum Start
No Evaporative Cooler
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 11 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
O. EQUIPMENT CONTROLS § 120.2 Confirmed
1.2.3.Pa
s
s
Fa
i
l
Equip Name Equip Type Controls
Office SZHP
No DCV Controls
No Economizer
No Supply Air Temp. Control
No Optimum Start
No Evaporative Cooler
Laundry + Maintenance SZHP
No DCV Controls
No Economizer
No Supply Air Temp. Control
No Optimum Start
No Evaporative Cooler
Laundry70 Exhaust
No DCV Controls
Economizer type not properly specified
No Supply Air Temp. Control
No Optimum Start
No Evaporative Cooler
Commons1 - SHW Service Hot Water, Primary Only Fixed Temperature Control, No DDC
Laundry68 - SHW Service Hot Water, Primary Only Fixed Temperature Control, No DDC
P. SYSTEM DISTRIBUTION SUMMARY § 120.4/ § 140.4(I)
Dry System Distribution Confirmed
1.2.3.4.5.
Pa
s
s
Fa
i
l
Equip Name Equip Type Duct Leakage and Sealing
Required per 140.4(l)
Duct Leakage will be
verified per NA1 and
NA2
Ducts
Insulation R-Value Location
Multipurpose + Hall + Kit SZHP No No 8 Conditioned
Office SZHP No No 8 Conditioned
Laundry + Maintenance SZHP No No 8 Conditioned
Does the Project Include Zonal Systems? (if "Yes", see NRCC-PRF-MCH-DETAILS for system information)No
Does the Project Include a Solar Hot Water System? (if "Yes", see NRCC-PRF-MCH-DETAILS for system information)No
Multifamily or Hotel/ Motel Occupancy? (if "Yes", see NRCC-PRF-MCH-DETAILS for DHW system information)No
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 12 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
Q. INDOOR CONDITIONED LIGHTING GENERAL INFO (see NRCC-PRF-LTI-DETAILS for more info)3 § 140.6
Confirmed
1.2.3.4.5.
Pa
s
s
Fa
i
l
Occupancy Type 1 Conditioned Floor Area 2
(ft2)
Installed Lighting Power
(Watts)
Lighting Control Credits
(Watts)Additional (Custom) Allowance
Area Category Footnotes
(Watts)Tailored Method (Watts)
Lounge, Recreation 1,474 893 0 0 0
Corridors, Restrooms, Stairs,
and Support Areas 482 248 0 0 0
Exercise Room 287 220 0 0 0
Office (250 square feet in
floor area or less)232 110 0 0 0
Laundry 621 477 0 0 0
Building Totals:3,096 1,948 0 0 0
1 See Table 140.6-C
2 See NRCC-LTI-01-E for unconditioned spaces
3Lighting information for existing spaces modeled is not included in the table
R. INDOOR CONDITIONED LIGHTING SCHEDULE (Adapted from NRCC-LTI-01-E)1 § 130.0
Luminaire Schedule (includes all permanent installed lighting in
conditioned space, and portable lighting over 0.3 w/ft2 in
offices)
Installed Watts (Conditioned)Confirmed
Name or Item Tag
Complete Luminaire Description (i.e.,
3-lamp fluorescent troffer, F32T8,
one dimmable electronic ballast)
Watts per luminaire
How Wattage is Determined
Total Number
Luminaires Installed Watts Pass FailCEC Default
from NA8
According to
§130.0(c)
F10 F10 52 Yes No 12 624
F11 F11 52 Yes No 10 520
F12 F12 55 Yes No 12 660
F8 F8 48 Yes No 3 144
1If lighting power densities were used in the compliance model Building Departments will need to check prescriptive forms for Luminaire Schedule details.
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 13 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
S1. COVERED PROCESS SUMMARY – ENCLOSED PARKING GARAGES § 140.9
This Section Does Not Apply
S2. COVERED PROCESS SUMMARY – COMMERCIAL KITCHENS § 140.9
This Section Does Not Apply
S3. COVERED PROCESS SUMMARY – COMPUTER ROOMS § 140.9
This Section Does Not Apply
S4. COVERED PROCESS SUMMARY – LABORATORY EXHAUSTS § 140.9
This Section Does Not Apply
T. UNMET LOAD HOURS
This Section Does Not Apply
U. ENERGY USE SUMMARY
Energy Component Standard Design Site
(MWh)
Proposed Design Site
(MWh)
Margin
(MWh)
Standard Design Site
(MBtu)
Proposed Design Site
(MBtu)
Margin
(MBtu)
Space Heating --0.5 --0.8 ----
Space Cooling 23.6 22.6 1.0 ------
Indoor Fans 25.5 16.9 8.6 ------
Heat Rejection ------------
Pumps & Misc.------------
Domestic Hot Water ------43.3 36.2 7.1
Indoor Lighting 8.6 6.5 2.1 ------
COMPLIANCE TOTAL 57.7 46.5 11.2 44.1 36.2 7.9
Receptacle 15.1 15.1 0.0 0.8 0.8 0.0
Process ------------
Other Ltg ------------
TOTAL 72.8 61.6 11.2 44.9 37.0 7.9
7/12/2017
A C17113
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 15 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
NRCC-PRF-ENV-DETAILS -SECTION START-
A. OPAQUE SURFACE ASSEMBLY DETAILS Confirmed
1.2.3.4.Pa
s
s
Fa
i
l
Surface Name Surface Type Description of Assembly Layers Notes
R-30 Metal Seam Roof -
Gr10 Roof
Asphalt shingles - 1/4 in.
Vapor permeable felt - 1/8 in.
Plywood - 1/2 in.
Air - Cavity - Wall Roof Ceiling - 4 in. or more
Metal framed roof, 24in. OC, 11.25in., R-30
Gypsum Board - 1/2 in.
Slab On Grade13 UndergroundFloor
Slab Type = UnheatedSlabOnGrade
Insulation Orientation = None
Insulation R-Value = R0
R-19 Wall15 ExteriorWall
Stucco - 7/8 in.
Vapor permeable felt - 1/8 in.
Wood framed wall, 16in. OC, 5.5in., R-19
Gypsum Board - 1/2 in.
R-11 Wall83 InteriorWall
Stucco - 7/8 in.
Vapor permeable felt - 1/8 in.
Wood framed wall, 16in. OC, 3.5in., R-11
Gypsum Board - 1/2 in.
B. OVERHANG DETAILS (Adapted from NRCC-ENV-02-E)
This Section Does Not Apply
C. OPAQUE DOOR SUMMARY Confirmed
1.2.3.4.5.6.7.
Pass FailOpaque Door Assembly Name
/ Tag or I.D.Door Type Certification Method Operation Area Overall
U-factor Status1
Metal Door41 MetalUninsulatedDoubleLayerDoor DefaultPerformance Swinging 72 0.700 N
1 Status: N - New, A – Altered, E – Existing
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 16 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
NRCC-PRF-MCH-DETAILS -SECTION START-
A. MECHANICAL VENTILATION AND REHEAT (Adapted from 2016-NRCC-MCH-03-E)Confirmed
1. DESIGN AIR FLOWS 2. VENTILATION (§ 120.1)
Pa
s
s
Fa
i
l
CONDITIONED
ZONE NAME
HE
A
T
I
N
G
/
C
O
O
L
I
N
G
S
Y
S
T
E
M
ID
DE
S
I
G
N
P
R
I
M
A
R
Y
A
I
R
F
L
O
W
(C
F
M
)
DE
S
I
G
N
P
R
I
M
A
R
Y
M
I
N
I
M
U
M
AI
R
F
L
O
W
(
C
F
M
)
MI
N
I
M
U
M
P
R
I
M
A
R
Y
A
I
R
FL
O
W
F
R
A
C
T
I
O
N
MA
X
I
M
U
M
H
E
A
T
I
N
G
A
I
R
FL
O
W
(
C
F
M
)
MA
X
I
M
U
M
H
E
A
T
I
N
G
A
I
R
FL
O
W
F
R
A
C
T
I
O
N
DD
C
C
O
N
T
R
O
L
(
Y
/
N
)
VE
N
T
S
Y
S
T
E
M
I
D
CO
N
D
I
T
I
O
N
E
D
A
R
E
A
(
f
t
2
)
MI
N
.
V
E
N
T
P
E
R
A
R
E
A
(C
F
M
/
f
t
2
)
DE
S
I
G
N
N
U
M
.
O
F
P
E
O
P
L
E
MI
N
.
V
E
N
T
P
E
R
P
E
R
S
O
N
(C
F
M
/
p
e
r
s
o
n
)
RE
Q
'
D
V
E
N
T
A
I
R
F
L
O
W
(
C
F
M
)
DE
S
I
G
N
V
E
N
T
A
I
R
F
L
O
W
(C
F
M
)
TR
A
N
S
F
E
R
A
I
R
F
L
O
W
(
C
F
M
)
DC
V
(
Y
/
N
)
Op
e
r
a
b
l
e
W
i
n
d
o
w
I
n
t
e
r
l
o
c
k
§
14
0
.
4
(
n
)
(
Y
/
N
)
1-Multipurpose +
Hall + Kit
Multipurpo
se + Hall +
Kit
1,542 NA NA NA NA N
Multipurpo
se + Hall +
Kit
1,474 NA 49 15.0 737 737 NA N NA
2-Washrooms
Multipurpo
se + Hall +
Kit
158 NA NA NA NA N
Multipurpo
se + Hall +
Kit
151 NA 1 30.0 23 23 NA N NA
4-Fitness
Multipurpo
se + Hall +
Kit
300 NA NA NA NA N
Multipurpo
se + Hall +
Kit
287 NA 3 15.0 43 43 NA N NA
6-Office Office 700 NA NA NA NA N Office 232 NA 1 30.0 35 35 NA N NA
7-Laundry
Laundry +
Maintenan
ce
763 NA NA NA NA N
Laundry +
Maintenan
ce
621 NA 3 30.0 93 93 NA N NA
8-Maintenance
Room
Laundry +
Maintenan
ce
407 NA NA NA NA N
Laundry +
Maintenan
ce
331 NA 2 30.0 50 50 NA N NA
TOTAL 3,450 NA NA NA NA
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 17 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
B. ZONAL SYSTEM AND TERMINAL UNIT SUMMARY § 140.4
1.2.3.4.5.6.7.8.Confirmed
System ID System Type Qty
Rated Capacity
(kBtuh)
Economizer Zone Name
Airflow (cfm)Fan
Pa
s
s
Fa
i
l
Heating Cooling Design Min.Min.
Ratio BHP Cycles ECM
Motor
4-Fitness-Trm Uncontrolled 2 NA NA NA 4-Fitness 300 NA NA NA NA
2-Washrooms-Trm Uncontrolled 2 NA NA NA 2-Washrooms 158 NA NA NA NA
1-Multipurpose + Hall
+ Kit-Trm Uncontrolled 2 NA NA NA 1-Multipurpose + Hall +
Kit 1542 NA NA NA NA
6-Office-Trm Uncontrolled 1 NA NA NA 6-Office 700 NA NA NA NA
8-Maintenance
Room-Trm Uncontrolled 1 NA NA NA 8-Maintenance Room 407 NA NA NA NA
7-Laundry-Trm Uncontrolled 1 NA NA NA 7-Laundry 763 NA NA NA NA
C. EXHAUST FAN SUMMARY Confirmed
1.2.3.4.5.6.Pa
s
s
Fa
i
l
System ID Zone Name Qty CFM Motor BHP Total Static Pressure (in H20)
Multipurpose + Hall + Kit3 1-Multipurpose + Hall + Kit 1 3761 0.750 0.76
Washrooms28 2-Washrooms 2 100 0.027 1.04
Laundry70 7-Laundry 1 250 0.065 0.99
D. DHW EQUIPMENT SUMMARY –(Adapted from NRCC-PLB-01)§ 110.3 Confirmed
1.2.3.4.5.6.7.8.9.10.11.12.
Pa
s
s
Fa
i
l
DHW Name
Heater
Element
Type
Tank Type Qty Tank Vol
(gal)
Rated Input
(kBtu/h)Efficiency
Tank
Insulation
R-value
(Int/Ext)
Pilot Energy
(Btu/h)Standby Loss Heat Pump
Type
Tank
Location or
Ambient
Condition
WH1 Rheem
PRO+G40-36U
RH62
Gas Storage 2 80 72 EF: 0.680 NA 0 NA NA
WH3 Rinnai
RL94E69 Gas Instantaneous 6 6 1194 EF: 0.820 NA 0 NA NA
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 18 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
E. MULTI-FAMILY CENTRAL DHW SYSTEM DETAILS
This Section Does Not Apply
F. SOLAR HOT WATER HEATING SUMMARY (Adapted from NRCC-STH-01)
This Section Does Not Apply
G. MECHANICAL HVAC ACCEPTANCE TESTS & FORMS (Adapted from 2016-NRCC-MCH-01-E)§ RA4
Declaration of Required Acceptance Certificates (NRCA)– Acceptance Certificates that may be submitted. (Retain copies and verify forms are completed and signed to post in field for Field
Inspector to verify).
Test Description
MC
H
-
0
2
A
MC
H
-
0
3
A
MC
H
-
0
4
A
MC
H
-
0
5
A
MC
H
-
0
6
A
MC
H
-
0
7
A
MC
H
-
0
8
A
MC
H
-
0
9
A
MC
H
-
1
0
A
MC
H
-
1
1
A
MC
H
-
1
2
A
MC
H
-
1
3
A
MC
H
-
1
4
A
MC
H
-
1
5
A
MC
H
-
1
6
A
MC
H
-
1
7
A
MC
H
-
1
8
A
Confirmed
Equipment
Requiring
Testing or
Verification
# of
units
Ou
t
d
o
o
r
A
i
r
Si
n
g
l
e
Z
o
n
e
U
n
i
t
a
r
y
Ai
r
D
i
s
t
.
D
u
c
t
s
Ec
o
n
o
m
i
z
e
r
C
o
n
t
r
o
l
s
DC
V
Su
p
p
l
y
F
a
n
V
A
V
Va
l
v
e
l
e
a
k
a
g
e
Su
p
p
l
y
W
a
t
e
r
T
e
m
p
.
Re
s
e
t
Hy
d
.
V
a
r
i
a
b
l
e
F
l
o
w
Co
n
t
r
o
l
Au
t
o
D
e
m
a
n
d
S
h
e
d
Co
n
t
r
o
l
FD
D
f
o
r
D
X
U
n
i
t
s
Au
t
o
F
D
D
f
o
r
A
i
r
&
Zo
n
e
Di
s
t
.
E
n
e
r
g
y
S
t
o
r
a
g
e
DX
A
C
TE
S
S
y
s
t
e
m
s
Su
p
p
l
y
A
i
r
T
e
m
p
.
R
e
s
e
t
Co
n
d
e
n
s
e
r
W
a
t
e
r
Re
s
e
t
C
o
n
t
r
o
l
s
EC
M
S
Pa
s
s
Fa
i
l
Commons1
- SHW 1 ----------------------------------
Laundry68 -
SHW 1 --------------X ------------------
Multipurpos
e + Hall + Kit 2 X X ------------------------------
Multipurpos
e + Hall +
Kit3
1 ----------------------------------
Washrooms
28 2 ----------------------------------
Office 1 X X ------------------------------
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 19 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
G. MECHANICAL HVAC ACCEPTANCE TESTS & FORMS (Adapted from 2016-NRCC-MCH-01-E)§ RA4
Declaration of Required Acceptance Certificates (NRCA)– Acceptance Certificates that may be submitted. (Retain copies and verify forms are completed and signed to post in field for Field
Inspector to verify).
Test Description
MC
H
-
0
2
A
MC
H
-
0
3
A
MC
H
-
0
4
A
MC
H
-
0
5
A
MC
H
-
0
6
A
MC
H
-
0
7
A
MC
H
-
0
8
A
MC
H
-
0
9
A
MC
H
-
1
0
A
MC
H
-
1
1
A
MC
H
-
1
2
A
MC
H
-
1
3
A
MC
H
-
1
4
A
MC
H
-
1
5
A
MC
H
-
1
6
A
MC
H
-
1
7
A
MC
H
-
1
8
A
Confirmed
Equipment
Requiring
Testing or
Verification
# of
units
Ou
t
d
o
o
r
A
i
r
Si
n
g
l
e
Z
o
n
e
U
n
i
t
a
r
y
Ai
r
D
i
s
t
.
D
u
c
t
s
Ec
o
n
o
m
i
z
e
r
C
o
n
t
r
o
l
s
DC
V
Su
p
p
l
y
F
a
n
V
A
V
Va
l
v
e
l
e
a
k
a
g
e
Su
p
p
l
y
W
a
t
e
r
T
e
m
p
.
Re
s
e
t
Hy
d
.
V
a
r
i
a
b
l
e
F
l
o
w
Co
n
t
r
o
l
Au
t
o
D
e
m
a
n
d
S
h
e
d
Co
n
t
r
o
l
FD
D
f
o
r
D
X
U
n
i
t
s
Au
t
o
F
D
D
f
o
r
A
i
r
&
Zo
n
e
Di
s
t
.
E
n
e
r
g
y
S
t
o
r
a
g
e
DX
A
C
TE
S
S
y
s
t
e
m
s
Su
p
p
l
y
A
i
r
T
e
m
p
.
R
e
s
e
t
Co
n
d
e
n
s
e
r
W
a
t
e
r
Re
s
e
t
C
o
n
t
r
o
l
s
EC
M
S
Pa
s
s
Fa
i
l
Laundry +
Maintenanc
e
1 X X ------------------------------
Laundry70 1 ----------------------------------
H. EVAPORATIVE COOLER SUMMARY
This Section Does Not Apply
NRCC-PRF-LTI-DETAILS -SECTION START-
A. INDOOR CONDITIONED LIGHTING CONTROL CREDITS (Adapted from NRCC-LTI-02-E)§ 140.6
Lighting Control Credits Schedule (includes all lighting controls installed in conditioned space for
compliance credit per §140.6(a)2 and Table 140.6-A)Control Credit Calculation
√ If Acceptance
Test Required
Confirmed
Location in
Building
Occupancy Type (must meet
requirements of Table 140.6-A)
Type/Description of Lighting
Control (i.e., partial on occupancy
sensor, manual dimming, etc.)
# of Units
Watts of
Controlled
Lighting
Power
Adjustment
Factor
Control Credit
Watts Pass Fail
S-1-
Multipurpose +
Hall + Kit
Lounge, Recreation - none specified -1 0.00 0
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 20 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
A. INDOOR CONDITIONED LIGHTING CONTROL CREDITS (Adapted from NRCC-LTI-02-E)§ 140.6
Lighting Control Credits Schedule (includes all lighting controls installed in conditioned space for
compliance credit per §140.6(a)2 and Table 140.6-A)Control Credit Calculation
√ If Acceptance
Test Required
Confirmed
Location in
Building
Occupancy Type (must meet
requirements of Table 140.6-A)
Type/Description of Lighting
Control (i.e., partial on occupancy
sensor, manual dimming, etc.)
# of Units
Watts of
Controlled
Lighting
Power
Adjustment
Factor
Control Credit
Watts Pass Fail
S-1-
Multipurpose +
Hall + Kit
Lounge, Recreation - none specified -1 0.00 0
S-1-
Multipurpose +
Hall + Kit
Lounge, Recreation - none specified -1 0.00 0
S-2-Washrooms Corridors, Restrooms, Stairs, and
Support Areas - none specified -1 0.00 0
S-4-Fitness Exercise Room - none specified -1 0.00 0
S-6-Office Office (250 square feet in floor
area or less)- none specified -1 0.00 0
S-7-Laundry Laundry - none specified -1 0.00 0
S-7-Laundry Laundry - none specified -1 0.00 0
S-8-
Maintenance
Room
Corridors, Restrooms, Stairs, and
Support Areas - none specified -1 0.00 0
B. INDOOR CONDITIONED LIGHTING MANDATORY LIGHTING CONTROLS (Adapted from NRCC-LTI-02-E)§ 130.1
This Section Does Not Apply
§130.1(a) = Manual area controls; §130.0(b) = Multi Level; §130.1(c) = Auto Shut-Off; §130.1(d) = Mandatory Daylight; §130.1(e) = Demand Responsive
C. TAILORED METHOD CONDITIONED LIGHTING POWER ALLOWANCE SUMMARY AND CHECKLIST (Adapted from NRCC-LTI-04-E)§ 140.6
General lighting power (see Table D)0
General lighting power from special function areas (see Table E)NA
Additional "use it or lose it" (See Table G)0
Total watts 0
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 21 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
D. GENERAL LIGHTING POWER (Adapted from NRCC-LTI-04-E)§ 140.6-D
This Section Does Not Apply
E. GENERAL LIGHTING FROM SPECIAL FUNCTION AREAS (Adapted from NRCC-LTI-04-E)§ 140.6(c) 3H
Room Number Primary Function Area Illuminance Value
(LUX)
Room Cavity Ratio
(Table G)Allowed LPD Floor Area (ft2)Allowed Watts
Confirmed
Pass Fail
NA NA NA NA NA NA NA
Note: Tailored Method for Special Function Areas is not currently implemented
F. ROOM CAVITY RATIO (Adapted from NRCC-LTI-04-E)
Rectangular Spaces
Room Number Task/Activity Description Room Length (ft)Room Width (ft)Room Cavity Height (ft)RCR
Confirmed
Pass Fail
NA NA NA NA NA NA
Non-Rectangular Spaces
This Section Does Not Apply
Note: All applicable spaces are listed under the Non-Rectangular Spaces table
G. ADDITIONAL “USE IT OR LOSE IT” (Adapted from NRCC-LTI-04-E)
1.2.3.4.
Allowed Watts
Confirmed
Wall Display Combined Floor Display and Task
Lighting
Combined Ornamental and Special
Effects Lighting Very Valuable Merchandise Pa
s
s
Fa
i
l
0 0 0 0 0
5. Wall Display
This Section Does Not Apply
6. Floor Display and Task Lighting
This Section Does Not Apply
Project Name:Washington Amenities Phase 1 NRCC-PRF-01-E Page 22 of 22
Project Address:42-800 Washington Street La Quinta Calculation Date/Time:15:24, Tue, Jun 20, 2017
Compliance Scope:NewComplete Input File Name:20170620_Washington Apts Phase
1_Amenities_T242016.cibd16x
CA Building Energy Efficiency Standards- 2016 Nonresidential Compliance Report Version: NRCC-PRF-01-E-05312017-4377 Report Generated at: 2017-06-20 15:25:50
7. Combined Ornamental and Special Effects Lighting
This Section Does Not Apply
8. Very Valuable Merchandise
This Section Does Not Apply
H. INDOOR & OUTDOOR LIGHTING ACCEPTANCE TESTS & FORMS (Adapted from NRCC-LTI-01-E and NRCC-LTO-01-E)§ 130.4
Declaration of Required Acceptance Certificates (NRCA) –Acceptance Certificates that must be verified in the field. (Retain copies and verify forms are completed and signed to post in field for
Field Inspector to verify).
Test Description
Indoor Outdoor Confirmed
NRCA-LTI-02-A NRCA-LTI-03-A NRCA-LTI-04-A NRCA-LTO-02-A
Pa
s
s
Fa
i
lEquipment Requiring
Testing or Verification # of units Occ Sensors / Auto Time
Switch Auto Daylight Demand Responsive Outdoor Controls
Occupant Sensors 0
Automatic Time Switch 0
Automatic Daylighting 0
Demand Responsive 0
Outdoor Controls 0
1-LINE
DIAGRAM
EXIST.
BLDGS
E0.3
Project
THE PICTORIAL AND GRAPHIC EXPRESSIONS DISPLAYED WITH THIS WORK ARE COPYRIGHTED UNDER THE LAWS OF THE UNITED STATES, TITLE 17, U.S. CODE. UNDER SECTION 106 OF THE COPYRIGHT ACT, THE ARCHITECT SHALL MAINTAIN THE EXCLUSIVE RIGHT OF THE REPRODUCTION, DISPLAY OR ANY DERIVATION OF THIS WORK.
Phase 1
15121
City of La Quinta
La Quinta, California
11/06/2018
REVISION 2
BCPR2017-0001
ADD SEPARATELY METERED
100A HOUSE PANELS AT EACH
RENOVATED BUILDING TO
SERVE COMMON LOADS
PANEL
SCHEDULES
E0.9
120/240V, 1ø, 3W
MAIN:100A, 2P MOUNTING: FLUSH
PANEL DEVICE MIN A.I.C. RATING:FEED: BOTTOM
øA øB øA øB
* GENERAL LTG/RECEPT 1 20 * 20 2 SMALL APPLIANCE
* GENERAL LTG/RECEPT 3 20 *20 4 SMALL APPLIANCE
* GENERAL LTG/RECEPT 5 20 *20 6 REFRIGERATOR
GFI REC - BATHROOMS 7 20 *20 8 GARBAGE DISPOSER
GFI REC - BATHROOMS 9 20 *20 10 WH-4
*** SMOKE DETECTORS 11 20 *20 12 TFC-1
CU-2 13 50 *15 14 FC-2
-15 2P *2P 16 -
SPACE 17 *18 SPACE
SPACE 19 *20 SPACE
SPACE 21 *22 SPACE
SPACE 23 *24 SPACE
øA = 0 øB =
TOTAL CONNECTED VA =0 KVA * PROVIDE ARC-FAULT CIRCUIT BREAKER.
+ 25% LCL = KVA ** SEE RESIDENTIAL LOAD CALCULATIONS.
TOTAL 0 KVA *** PROVIDE CIRCUIT BREAKER LOCK-ON DEVICE.
** CONNECTED LOAD =0 A
MINIMUM FEEDER SIZE =0 A
PANEL "K5"
LOCATION: K5 (3BR UNIT)
BUS RATING 100A
10000A
LOCATION VOLTAMPS LTG REC MIS LOCATIONCIR BRK A B
BRK
0
CIR MIS REC LTG
VOLTAMPS
120/240V, 1ø, 3W
MAIN:100A, 2P MOUNTING: FLUSH
PANEL DEVICE MIN A.I.C. RATING:FEED: BOTTOM
øA øB øA øB
* GENERAL LTG/RECEPT 1 20 * 20 2 SMALL APPLIANCE
* GENERAL LTG/RECEPT 3 20 *20 4 SMALL APPLIANCE
* GENERAL LTG/RECEPT 5 20 *20 6 REFRIGERATOR
GFI REC - BATHROOMS 7 20 *20 8 GARBAGE DISPOSER
GFI REC - BATHROOMS 9 20 *20 10 WH-4
*** SMOKE DETECTORS 11 20 *20 12 TFC-1
CU-2 13 50 *15 14 FC-2
-15 2P *2P 16 -
SPACE 17 *18 SPACE
SPACE 19 *20 SPACE
SPACE 21 *22 SPACE
SPACE 23 *24 SPACE
øA = 0 øB =
TOTAL CONNECTED VA =0 KVA * PROVIDE ARC-FAULT CIRCUIT BREAKER.
+ 25% LCL = KVA ** SEE RESIDENTIAL LOAD CALCULATIONS.
TOTAL 0 KVA *** PROVIDE CIRCUIT BREAKER LOCK-ON DEVICE.
** CONNECTED LOAD =0 A
MINIMUM FEEDER SIZE =0 A
PANEL "M7"
LOCATION: M7 (2BR UNIT)
BUS RATING 100A
10000A
LOCATION VOLTAMPS LTG REC MIS LOCATIONCIR BRK A B
BRK
0
CIR MIS REC LTG
VOLTAMPS
120/240V, 1ø, 3W
MAIN:80A, 2P MOUNTING: FLUSH
PANEL DEVICE MIN A.I.C. RATING:FEED: BOTTOM
øA øB øA øB
* GENERAL LTG/RECEPT 1 20 * 20 2 SMALL APPLIANCE
* GENERAL LTG/RECEPT 3 20 *20 4 SMALL APPLIANCE
GFI REC - BATHROOMS 5 20 *20 6 REFRIGERATOR
SPARE 7 20 *20 8 GARBAGE DISPOSER
SPARE 9 20 *20 10 WH-2
*** SMOKE DETECTORS 11 20 *20 12 TFC-1
CU-1 13 25 *15 14 FC-1
-15 2P *2P 16 -
SPACE 17 *18 SPACE
SPACE 19 *20 SPACE
SPACE 21 *22 SPACE
SPACE 23 *24 SPACE
øA = 0 øB =
TOTAL CONNECTED VA =0 KVA * PROVIDE ARC-FAULT CIRCUIT BREAKER.
+ 25% LCL = KVA ** SEE RESIDENTIAL LOAD CALCULATIONS.
TOTAL 0 KVA *** PROVIDE CIRCUIT BREAKER LOCK-ON DEVICE.
** CONNECTED LOAD =0 A
MINIMUM FEEDER SIZE =0 A
PANEL "K1"
LOCATION: K1 (TYP. FOR NEW 1BR UNITS)
BUS RATING 100A
10000A
LOCATION VOLTAMPS LTG REC MIS LOCATIONCIR BRK A B
BRK
0
CIR MIS REC LTG
VOLTAMPS
Project
THE PICTORIAL AND GRAPHIC EXPRESSIONS DISPLAYED WITH THIS WORK ARE COPYRIGHTED UNDER THE LAWS OF THE UNITED STATES, TITLE 17, U.S. CODE. UNDER SECTION 106 OF THE COPYRIGHT ACT, THE ARCHITECT SHALL MAINTAIN THE EXCLUSIVE RIGHT OF THE REPRODUCTION, DISPLAY OR ANY DERIVATION OF THIS WORK.
Phase 1
15121
City of La Quinta
La Quinta, California
11/06/2018
REVISION 2
Project #:
Date:
858.649.1700 www.tkjse.com
San Diego, California 92131
9820 Willow Creek Rd., Ste. 455
820 Willow Creek Rd., Ste. 455
an Diego, CA 92131
hone: 858.649.17009820 Willow Creek Rd, Ste. 455
16010
6/11/2018
Washington Street SSK-5R4