BCOM2021-0037Description: SILVERROCK / MONTAGE / 22,775SF SPA BUILDING
Type: BUILDING COMMERCIAL Subtype: STORES/CUSTOMER Status: ISSUED
Applied: 10/29/2019 AOR
(WEB) SERVICE
Approved: 7/21/2021 AOR
Parcel No: 777490012 Site Address: 79187 AHMANSON LN LA QUINTA,CA 92253
Subdivision: PM 33367 Block: Lot: 20
Issued: 7/22/2021 AMA
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning:
Finaled:
Valuation: $1,006,006.00 Occupancy Type: Construction Type:
Expired: 11/9/2022 DCL
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details: 22,775SF MONTAGE SPA BUILDING [VB/A3-B-S1/143-OL/CLASS A-FR/NFPA 13] THIS PERMIT DOES NOT INCLUDE POOL OR SPAS,
WATER FEATURES, BLOCK WALLS, EXTERIOR SITE LIGHTING OR FIRE SPRINKLER SYSTEM. DIF ASSESSED AT OFFICE/BUSINESS RATE
AND TUMF ASSESSED AT THE PER GUESTROOM RATE. MSHCP ASSESSED FOR ENTIRE SITE ON HOTEL SERVICES BUILDING PERMIT.
2016 CALIFORNIA BUILDING CODES.
7NT9
Applied to Approved
Approved to Issued
NAME TYPE
NAME
ADDRESSI
CITY
STATE
ZIP
PHONE
FAX
EMAIL
APPLICANT
THE ROBERT GREEN COMPANY
343 4TH AVE
SAN DIEGO
CA
92101
JOSH @THEROBERTG RE
ENCOMPANY.COM
CONTRACTOR
R D OLSON CONSTRUCTION INC
400 SPECTRUM CENTER
DR. STE 1200
IRVINE
1
CA
1
92618
1
1
1
KCARLISLE@RDOLSON.
1COM
OWNER
CITY OF LA QUINTA
P O BOX 1504
LA QUINTA
CA
1 92253
Printed: Tuesday, July 19, 2022 10:22:43 AM 1 of 20
_.:ff-- WYSiEMS
■
CLTD
DESCRIPTION
ACCOUNT
CITY
AMOUNT
PAID
PAID DATE
RECEIPT #
CHECK #
METHOD
PAID BY
BY
ART IN PUBLIC PLACES -
270-0000-43201
0
$5,030.03
$5,030.03
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
COMMERCIAL
ACCT
COMPANY
Total Paid for ART IN PUBLIC PLACES - AIPP: $5,030.03 $5,030.03
BSAS SB1473 FEE
101-0000-20306
0
$41.00
$41.00
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
ACCT
COMPANY
Total Paid for BUILDING STANDARDS ADMINISTRATION
$41.00 $41.00
BSA:
DIF - CIVIC CENTER
252-0000-43200
0
$8,495.08
$8,495.08
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
ACCT
COMPANY
DIF - FIRE PROTECTION
257-0000-43200
0
$3,894.53
$3,894.53
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
ACCT
COMPANY
DIF - STREET
255-0000-43200
0
$4,327.25
$4,327.25
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
MAINTENANCE
ACCT
COMPANY
DIF - TRANSPORTATION
250-0000-43200
0
$105,789.88
$105,789.88
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
ACCT
COMPANY
Total Paid for DIF - OFFICE/HOSPITAL: $122,506.74 $122,506.74
101-0000-42600
($118.03)
($118.03)
7/21/21
OFFSET
OFFSET
AOR
101-0000-42600
($93.38)
($93.38)
7/21/21
OFFSET
OFFSET
AOR
NON-RESIDENTIAL, EA
101-0000-42403
0
$442.75
$442.75
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
ADDITIONAL 2,OOOSF
ACCT
COMPANY
NON-RESIDENTIAL, EA
101-0000-42600
0
$118.03
$118.03
7/21/21
DEPOSIT
DEPOSIT
THE ROBERT GREEN
AOR
ADDITIONAL 2,000SF PC
COMPANY
NON-RESIDENTIAL,
101-0000-42403
0
$120.75
$120.75
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
FIRST 2,000SF
ACCT
COMPANY
NON-RESIDENTIAL,
101-0000-42600
0
$93.38
$93.38
7/21/21
DEPOSIT
DEPOSIT
THE ROBERT GREEN
AOR
FIRST 2,000SF PC
COMPANY
Total Paid for ELECTRICAL - NEW CONSTRUCTION 2019: $563.50 $563.50
Printed: Tuesday, July 19, 2022 10:22:43 AM 2 of 20
__ _.:ffwSYSiEMS
■
CLTD
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
RECEIPT #
CHECK #
METHOD
PAID BY
BY
FIRE NEW
101-0000-42421
0
$403.00
$403.00
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
COMMERCIAL
ACCT
COMPANY
Total Paid for FIRE FEES: $403.00 $403.00
101-0000-42600
($241.56)
($241.56)
7/21/21
OFFSET
OFFSET
AOR
101-0000-42600
($724.41)
($724.41)
7/21/21
OFFSET
OFFSET
AOR
101-0000-42600
($40.26)
($40.26)
7/21/21
OFFSET
OFFSET
AOR
101-0000-42600
($5.37)
($5.37)
7/21/21
OFFSET
OFFSET
AOR
101-0000-42600
($40.25)
($40.25)
7/21/21
OFFSET
OFFSET
AOR
101-0000-42600
($42.96)
($42.96)
7/21/21
OFFSET
OFFSET
AOR
101-0000-42600
($40.26)
($40.26)
7/21/21
OFFSET
OFFSET
AOR
AIR HANDLER
101-0000-42402
0
$724.50
$724.50
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
ACCT
COMPANY
AIR HANDLER PC
101-0000-42600
0
$241.56
$241.56
7/21/21
DEPOSIT
DEPOSIT
THE ROBERT GREEN
AOR
COMPANY
CONDENSER/COMPRES
101-0000-42402
0
$1,086.75
$1,086.75
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
SOR
ACCT
COMPANY
CONDENSER/COMPRES
101-0000-42600
0
$724.41
$724.41
7/21/21
DEPOSIT
DEPOSIT
THE ROBERT GREEN
AOR
SOR PC
COMPANY
EVAPORATIVE COOLER
101-0000-42402
0
$40.26
$40.26
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
ACCT
COMPANY
EVAPORATIVE COOLER
101-0000-42600
0
$40.26
$40.26
7/21/21
DEPOSIT
DEPOSIT
THE ROBERT GREEN
AOR
PC
COMPANY
EXHAUST HOOD
101-0000-42402
0
$13.42
$13.42
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
ACCT
COMPANY
EXHAUST HOOD PC
101-0000-42600
0
$5.37
$5.37
7/21/21
DEPOSIT
DEPOSIT
THE ROBERT GREEN
AOR
COMPANY
OTHER MECHANICAL
101-0000-42402
0
$40.25
$40.25
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
EQUIPMENT
ACCT
COMPANY
Printed: Tuesday, July 19, 2022 10:22:43 AM 3 of 20
__ _.:#?wSYSiEMS
■
CLTD
DESCRIPTION
ACCOUNT
QTY
AMOUNT
PAID
PAID DATE
RECEIPT #
CHECK #
METHOD
PAID BY
BY
OTHER MECHANICAL
101-0000-42600
0
$40.25
$40.25
7/21/21
DEPOSIT
DEPOSIT
THE ROBERT GREEN
AOR
EQUIPMENT PC
COMPANY
VENT FAN
101-0000-42402
0
$107.36
$107.36
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
ACCT
COMPANY
VENT FAN PC
101-0000-42600
0
$42.96
$42.96
7/21/21
DEPOSIT
DEPOSIT
THE ROBERT GREEN
AOR
COMPANY
WALL HEATER
101-0000-42402
0
$80.49
$80.49
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
ACCT
COMPANY
WALL HEATER PC
101-0000-42600
0
$40.26
$40.26
7/21/21
DEPOSIT
DEPOSIT
THE ROBERT GREEN
AOR
COMPANY
Total Paid for MECHANICAL 2019: $2,093.03 $2,093.03
NEW CONSTRUCTION
101-0000-42400
0
$5,353.48
$5,353.48
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
PERMIT 2019
ACCT
COMPANY
Total Paid for NEW CONSTRUCTION PERMIT 2019: $5,353.48 $5,353.48
101-0000-42600
($3,106.87)
($3,106.87)
7/21/21
OFFSET
OFFSET
AOR
NEW CONSTRUCTION
101-0000-42600
0
$3,106.87
$3,106.87
7/21/21
DEPOSIT
DEPOSIT
THE ROBERT GREEN
AOR
PLAN CHECK 2019
COMPANY
NEW CONSTRUCTION
101-0000-42600
0
$190.36
$190.36
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
PLAN CHECK 2019
ACCT
COMPANY
Total Paid for NEW CONSTRUCTION PLAN CHECK 2019: $190.36 $190.36
PLAN CHECK DEPOSIT -
101-0000-42600
1
$5,806.06
$5,806.06
7/21/21
R66157
CTAAEC478
TRUST
THE ROBERT GREEN
AOR
COMMERCIAL
ACCOUNT
COMPANY
Total Paid for PLAN CHECK DEPOSIT - COMMERCIAL: $5,806.06 $5,806.06
101-0000-42600
($5.37)
($5.37)
7/21/21
OFFSET
OFFSET
AOR
101-0000-42600
($18.78)
($18.78)
7/21/21
OFFSET
OFFSET
AOR
101-0000-42600
($1,167.54)
($1,167.54)
7/21/21
OFFSET
OFFSET
AOR
101-0000-42600
($26.83)
($26.83)
7/21/21
OFFSET
OFFSET
AOR
101-0000-42600
($13.42)
($13.42)
7/21/21
OFFSET
OFFSET
AOR
Printed: Tuesday, July 19, 2022 10:22:43 AM 4 of 20
RWSYSiEMS
CLTD
DESCRIPTION
ACCOUNT
CITY
AMOUNT
PAID
PAID DATE
RECEIPT #
CHECK #
METHOD
PAID BY
BY
101-0000-42600
($67.10)
($67.10)
7/21/21
OFFSET
OFFSET
AOR
101-0000-42600
($40.25)
($40.25)
7/21/21
OFFSET
OFFSET
AOR
101-0000-42600
($13.42)
($13.42)
7/21/21
OFFSET
OFFSET
AOR
BACKFLOW DEVICE
101-0000-42401
0
$13.42
$13.42
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
ACCT
COMPANY
BACKFLOW DEVICE PC
101-0000-42600
0
$5.37
$5.37
7/21/21
DEPOSIT
DEPOSIT
THE ROBERT GREEN
AOR
COMPANY
BUILDING SEWER
101-0000-42401
0
$26.83
$26.83
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
ACCT
COMPANY
BUILDING SEWER PC
101-0000-42600
0
$18.78
$18.78
7/21/21
DEPOSIT
DEPOSIT
THE ROBERT GREEN
AOR
COMPANY
FIXTURE/TRAP
101-0000-42401
0
$1,167.54
$1,167.54
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
ACCT
COMPANY
FIXTURE/TRAP PC
101-0000-42600
0
$1,167.54
$1,167.54
7/21/21
DEPOSIT
DEPOSIT
THE ROBERT GREEN
AOR
COMPANY
GAS SYSTEM, 5+
101-0000-42401
0
$40.25
$40.25
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
OUTLETS
ACCT
COMPANY
GAS SYSTEM, 5+
101-0000-42600
0
$26.83
$26.83
7/21/21
DEPOSIT
DEPOSIT
THE ROBERT GREEN
AOR
OUTLETS PC
COMPANY
GREASE INTERCEPTOR
101-0000-42401
0
$40.25
$40.25
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
ACCT
COMPANY
GREASE INTERCEPTOR
101-0000-42600
0
$13.42
$13.42
7/21/21
DEPOSIT
DEPOSIT
THE ROBERT GREEN
AOR
PC
COMPANY
ROOF DRAIN
101-0000-42401
0
$67.10
$67.10
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
ACCT
COMPANY
ROOF DRAIN PC
101-0000-42600
0
$67.10
$67.10
7/21/21
DEPOSIT
DEPOSIT
THE ROBERT GREEN
AOR
COMPANY
WATER HEATER/VENT
101-0000-42401
0
$67.10
$67.10
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
ACCT
COMPANY
Printed: Tuesday, July 19, 2022 10:22:43 AM 5 of 20
__ _.:IF-wSYSiEMS
■
CLTD
DESCRIPTION
ACCOUNT
CITY
AMOUNT
PAID
PAID DATE
RECEIPT #
CHECK #
METHOD
PAID BY
BY
WATER HEATER/VENT
101-0000-42600
0
$40.25
$40.25
7/21/21
DEPOSIT
DEPOSIT
THE ROBERT GREEN
AOR
PC
COMPANY
WATER SYSTEM
101-0000-42401
0
$13.42
$13.42
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
INST/ALT/REP
ACCT
COMPANY
WATER SYSTEM
101-0000-42600
0
$13.42
$13.42
7/21/21
DEPOSIT
DEPOSIT
THE ROBERT GREEN
AOR
INST/ALT/REP PC
COMPANY
Total Paid for PLUMBING 2019:
$1,435.91
$1,435.91
RECORDS
MANAGEMENT FEE -
101-0000-42416
0
$21.00
$21.00
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
ACCT
COMPANY
MAJOR
Total Paid for RECORDS MANAGEMENT FEE - MAJOR:
$21.00
$21.00
SMI - COMMERCIAL
101-0000-20308
0
$281.68
$281.68
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
ACCT
COMPANY
Total Paid for STRONG MOTION INSTRUMENTATION SMI:
$281.68
$281.68
TECHNOLOGY
502-0000-43611
0
$5.00
$5.00
7/22/21
WEB8817
CTAAEC478
TRUST
THE ROBERT GREEN
ECON
ENHANCEMENT FEE
ACCT
COMPANY
Total Paid for TECHNOLOGY ENHANCEMENT FEE:
$5.00
$5.00
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR
SCHEDULED
COMPLETED
RESULT
REMARKS
NOTES
DATE
DATE
8/24/2021 2:44 PM R D OLSON
CONSTRUCTION INC
Montage Spa
Contact Name: R D OLSON CONSTRUCTION
UNDERGROUND ELEC
DCL
8/26/2021
8/26/2021
PARTIALLY
Underground Electrical
INC
APPROVED
Condu
Site Address: 79187 AHMANSON
LN
Phone:9494742001
e-Mail: jbloom@RDOLSON.COM
Printed: Tuesday, July 19, 2022 10:22:43 AM 6 of 20
RWSYSiEMS
UNDERGROUND ELEC
DCL
8/26/2021
8/26/2021
PARTIALLY
APPROVED
Montage Spa
Underground Electrical
Condu
- UNDERGROUND ELECTRICAL FOR SPA
ELECTRICAL ROOM WITH STUB TO POOL
EQUIPMENT ROOM 2. SEE SHEET HS E03.102
FOR APPROVAL NOTES.
8/23/2021 2:47 PM R D OLSON
CONSTRUCTION INC
Contact Name: R D OLSON CONSTRUCTION
Underground conduit at
INC
UNDERGROUND ELEC
DCL
8/26/2021
8/26/2021
CANCELED
the Spa/Treatment
Site Address: 79187 AHMANSON LN
Phone:9494742001
e-Mail: jbloom@RDOLSON.COM
- DUPLICATE INSPECTION.
10/11/2021 1:32 PM R D OLSON
CONSTRUCTION INC
12-1 Requested Inspection Time, please.
Contact Name: R D OLSON CONSTRUCTION
INC
Site Address: 79187 AHMANSON LN
PARTIALLY
Perimeter footings
Phone: 9496971498
FOOTINGS
DCL
10/12/2021
10/12/2021
APPROVED
w/stem walls
a -Mail: Jbloom@rdolson.com
- S08.121/8 DETAIL REQUIRED. NOT
SHOWN ON PLANS. PROVIDE STAMPED RFI
DETAIL.- ALL PERIMETER FOOTINGS AND
STEM WALLS AT BUILDING ONLY. EXCLUDES
PRIVACY WALLS AND PLANTERS.
Printed: Tuesday, July 19, 2022 10:22:43 AM 7 of 20
__ _.:#7WSYSiEMS
10/15/2021 10:26 AM R D OLSON
CONSTRUCTION INC
Requesting AM INspection. This is for the
Fitness area plumbing of the Spa Building
Contact Name: R D OLSON CONSTRUCTION
INC
Site Address: 79187 AHMANSON LN
UNDERGROUND PLBG
DCL
10/18/2021
10/18/2021
PARTIALLY
eTRAKiT Inspection
Phone:9496971498
APPROVED
Request
a -Mail: jbloom@rdolson.com
- FITNESS RESTROOMS WITH SALON
FIXTURES PER HS - P02.301 - FIELD CHANGE
SINKS RELOCATED. CONTRACTOR TO
PROVIDE REVISED FLOOR PLAN FOR
CHANGES - SEE BULLETIN 1.
11/1/2021 1:18 PM R D OLSON
CONSTRUCTION INC
Contact Name: R D OLSON CONSTRUCTION
INC
PARTIALLY
eTRAKiT Inspection
Site Address: 79187 AHMANSON LN
TEMPLATE FOOTING
AMOR
11/2/2021
11/2/2021
APPROVED
Request
Phone:9496971498
e-Mail: jbloom@rdolson.com
Block wall ok per HS 202-202 at grade line N
3 - 4. Fitness room grade beams ok pending
third party verification of (10) hold Dows.
11/1/2021 1:19 PM R D OLSON
CONSTRUCTION INC
Contact Name: R D OLSON CONSTRUCTION
UNDERGROUND PLBG
AMOR
11/3/2021
11/3/2021
PARTIALLY
eTRAKiT Inspection
INC
APPROVED
Request
Site Address: 79187 AHMANSON LN
Phone:9496971498
e-Mail: jbloom@rdolson.com
Printed: Tuesday, July 19, 2022 10:22:43 AM 8 of 20
RWSYSiEMS
UNDERGROUND PLBG
AMOR
11/3/2021
11/3/2021
1. Spa building. Ok.
11/11/2021 7:55 AM R D OLSON
CONSTRUCTION INC
Electrical tie underground Tie in for Spa and
hotel
Contact Name: R D OLSON CONSTRUCTION
INC
Site Address: 79187 AHMANSON LN
Phone:9494742001
e-Mail: KCARLISLE@RDOLSON.COM
UNDERGROUND ELEC
JFU
11/15/2021
11/15/2021
PARTIALLY
eTRAKiT Inspection
APPROVED
Request
UNDERGROUND CONDUITS FROM MAIN
SWITCH BOARD'MSB-HVAT MONTAGE
HOTEL TO MAIN DISTRIBUTION BOARD
'MDB-HS" AT SPA BUILDING. OBSERVED (2)
4" CONDUITS AS SHOWN ON SINGLE LINE
DIAGRAMS ON HlE08.101 & HSE08.101, IN
ADDITION TO SEVERAL OTHER ADDITIONAL
CONDUITS FOR COMMUNICATION AND
OTHER CIRCUITRY.
11/15/2021 11:15 AM R D OLSON
CONSTRUCTION INC
Contact Name: R D OLSON CONSTRUCTION
INC
Site Address: 79187 AHMANSON LN
Phone:9497690002
GREASE INTERCEPTOR
JFU
11/16/2021
11/16/2021
APPROVED
please contact me @ 949-
a -Mail: Inaefke@rdolson.com
769-0002 (Lang)
750 GAL. PRE -FABRICATED GREASE
INTERCEPTER & SAMPLE BOX OUTSIDE
SERVICE PANTRY. THIS APPROVAL INCLUDES
THE TWO-WAY CLEANOUT, INTERCEPTOR
VENT, AND ASSOCIATED UNDERGROUND
PIPING.
Printed: Tuesday, July 19, 2022 10:22:43 AM 9 of 20
__ _.:#_r_wSYSiEMS
UNDERGROUND ELEC
JFU
11/18/2021
11/18/2021
PARTIALLY
APPROVED
eTRAKiT Inspection
Request
11/17/2021 11:48 AM R D OLSON
CONSTRUCTION INC
PM inspection if possible partial inspection
for treatment rooms and fitness
Contact Name: R D OLSON CONSTRUCTION
INC
Site Address: 79187 AHMANSON LN
Phone:9497690002
e-Mail: Inaefke@RDOLSON.COM
UNDERSLAB CONDUIT AND ELECTRICAL
BOXES AT FITNESS BUILDING ONLY.
11/18/2021 11:47 AM R D OLSON
CONSTRUCTION INC
partial re -inspection spa treatment rooms
AM please
Contact Name: R D OLSON CONSTRUCTION
UNDERGROUND ELEC
AOR
11/19/2021
11/19/2021
PARTIALLY
eTRAKiT Inspection
INC
APPROVED
Request
Site Address: 79187 AHMANSON LN
Phone:9497690002
e-Mail: Inaefke@RDOLSON.COM
TREATMENT ROOMS ONLY.
11/19/2021 11:38 AM R D OLSON
CONSTRUCTION INC
partial inspection for fitness slab
afternoon if possible please
Contact Name: R D OLSON CONSTRUCTION
INC
SLAB
DCL
11/22/2021
11/22/2021
CANCELED
eTRAKiT Inspection
Site Address: 79187 AHMANSON LN
Request
Phone:9497960002
e-Mail: Inaefke@RDOLSON.COM
(949) 769 0002 LANG NAEFKE
- CANCELLED PER PHONE REQUEST TO
PERMIT HUB.
Printed: Tuesday, July 19, 2022 10:22:43 AM 10 of 20
RWSYSiEMS
11/22/2021 2:14 PM R D OLSON
CONSTRUCTION INC
partial inspection for the fitness building
slab only
Contact Name: R D OLSON CONSTRUCTION
INC
PARTIALLY
eTRAKiT Inspection
Site Address: 79187 AHMANSON LN
SLAB
AOR
11/23/2021
11/23/2021
APPROVED
Request
Phone:9497690002
e-Mail: Inaefke@RDOLSON.COM
FITNESS / LOBBY SLAB INCLUDING
REMAINING FOOTINGS PREVIOUSLY
BLOCKED OUT, RFI 30 SHOWN FOR SLAB
REINFORCEMENT AT 16" ON CENTER.
11/23/2021 1:33 PM R D OLSON
CONSTRUCTION INC
this is for the pool equipment room at the
spa women"s spa . we also have health
inspection for it as well.
Contact Name: R D OLSON CONSTRUCTION
INC
UNDERGROUND PLBG
AOR
11/24/2021
11/24/2021
CANCELED
eTRAKiT Inspection
Site Address: 79187 AHMANSON LN
Request
Phone:9497690002
e-Mail: Inaefke@RDOLSON.COM
THIS INSPECTION REQUEST WAS FOR POOL
PLUMBING AT UNDER BUILDING SLAB
AREAS OF EQUIPMENT ROOM 2, SEE
BPOL2020-0123 FOR PARTIAL APPROVAL.
Printed: Tuesday, July 19, 2022 10:22:43 AM 11 of 20
__ _.:#?WSYSiEMS
12/6/2021 8:08 AM R D OLSON
CONSTRUCTION INC
Rebar inspection for Breezeway footings for
walls, treatment rms, and pool equipment
rm 2
Contact Name: R D OLSON CONSTRUCTION
INC
Site Address: 79187 AHMANSON LN
SLAB AOR 12/7/2021 12/7/2021 DISAPPROVE eTRAKiT Inspection Phone: 9497690002
D Request a -Mail: Inaefke@RDOLSON.COM
REBAR CLEARANCE NOT PROVIDED TO
EARTH AT BASE OF LOW GRADE DEEPEND
FOOTINGS PER ACI 318-7.7.1 -
ADDITIONALLY NOT ENOUGH INFORMATION
TO PERFORM INSPECTION OF CMU SCREEN
WALL FOOTINGS, SEPARATE REVIEW AND
APPROVAL REQUIRED FOR BLOCK WALLS.
UNDERGROUND ELEC
AOR
12/7/2021 2:55 PM R D OLSON
CONSTRUCTION INC
for spa building main
Contact Name: R D OLSON CONSTRUCTION
INC
Site Address: 79187 AHMANSON LN
12/8/2021 12/8/2021 NOT READY eTRAKiT Inspection phone: 9497690002
Request a -Mail: Inaefke@RDOLSON.COM
NOT TAKEN TO THIS AREA FOR INSPECTION,
RECALL WHEN READY OR IF FOR SLAB BOXES
APPROVAL CAN BE PROVIDED AT SLAB
INSPECTION.
Printed: Tuesday, July 19, 2022 10:22:43 AM 12 of 20
__ _.:N-r-wSYSiEMS
12/7/2021 2:47 PM R D OLSON
CONSTRUCTION INC
This is for re -inspection for equipment
building 2 and treatment rooms. we made
the corrections. I will also be requesting in
slab utilities (electrical) for the spa building
and equipment room 1 for pool plumbing for
PARTIALLY
eTRAKiT Inspection
today. noon inspection if possible.
SLAB
AOR
12/8/2021
12/8/2021
APPROVED
Request
Contact Name: R D OLSON CONSTRUCTION
INC
Site Address: 79187 AHMANSON LN
Phone:9497690002
e-Mail: Inaefke@RDOLSON.COM
POOL EQUIPMENT ROOM 2 AND
TREATMENT ROOM AREAS ONLY.
FOOTINGS
AOR
12/13/2021
12/13/2021
PARTIALLY
WALL AND WALKWAY CMU WALL FOOTINGS
APPROVED
AT BREEZWAY ONLY.
EIGHT (8) F3 TEMPLATE FOOTINGS AT
TEMPLATE FOOTING
AOR
12/13/2021
12/13/2021
APPROVED
BREEZEWAY ONLY, NO FURTHER TEMPLATE
INSPECTIONS WITHIN SCOPE OF WORK.
12/15/2021 2:32 PM R D OLSON
CONSTRUCTION INC
rebar inspection for reminder of the spa slab
noon inspection please. Thank you
Contact Name: R D OLSON CONSTRUCTION
INC
Site Address: 79187 AHMANSON LN
SLAB
DCL
12/16/2021
12/16/2021
NOT READY
eTRAKiT Inspection
phone: 9497690002
Request
a -Mail: Inaefke@RDOLSON.COM
- WORK INCOMPLETE. INFORMED
SUPERINTENDENT THAT INSPECTION
TIMEFRAMES ARE AVAILABLE EVERYDAY
AND SHOULD BE CHECKED WHEN
REQUESTING SPECIFIC INSPECTION TIMES.
Printed: Tuesday, July 19, 2022 10:22:43 AM 13 of 20
RWSYSiEMS
12/16/2021 11:37 AM R D OLSON
CONSTRUCTION INC
Re -inspection for spa slab rebar. early as
possible please.
Contact Name: R D OLSON CONSTRUCTION
INC
Site Address: 79187 AHMANSON LN
PARTIALLY eTRAKiT Inspection Phone: 9497690002
SLAB JAN 12/17/2021 12/17/2021 APPROVED Request e-Mail:lnaefke@RDOLSON.COM
Inspector MHU changed the inspection
assignment from MHU to JAN
MENS RESTROOMS,LOUNGE,SAUNA AND
MENS GARDEN
MENS RESTROOMS,LOUNGE,SAUNA AND
MENS GARDEN
BOND BEAM
DCL
1/7/2022 8:17 AM R D OLSON
CONSTRUCTION INC
footing previously inspected by AJ this is for
CMU walls partial
Contact Name: R D OLSON CONSTRUCTION
INC
PARTIALLY eTRAKiT Inspection Site Address: 79187 AHMANSON LN
1/10/2022 1/10/2022 APPROVED Request Phone:9497690002
e-Mail: Inaefke@RDOLSON.COM
dcl changed Inspection Type from FOOTINGS
to BOND BEAM
- TOP OUT AT BREEZEWAY WALLS AND
FIRST LIFT AT SCREENING WALLS.
Printed: Tuesday, July 19, 2022 10:22:43 AM 14 of 20
__ _.:17-wSYSiEMS
BOND BEAM
ROOF NAIL
JFU
DCL
1/18/2022 1
5/9/2022
1/18/2022
5/9/2022
PARTIALLY
APPROVED
PARTIALLY
APPROVED
AM inspection please
eTRAKiT Inspection
Request
1/14/2022 11:06 AM R D OLSON
CONSTRUCTION INC
High lift and 2nd lift inspection for CMU
walls at the mens and womens garden AM
inspection please
Contact Name: R D OLSON CONSTRUCTION
INC
Site Address: 79187 AHMANSON LN
Phone:9494742001
e-Mail: KCARLISLE@RDOLSON.COM
-TOP OUT (2ND LIFT) AT SCREEN WALLS AT
MEN'S GARDEN WHERE PREVIOUSLY
INSPECTED ON 1/11/2021.
-TOP OUT (SINGLE LIFT) AT CMU SCREENIG
WALLS AT WOMEN'S GARDEN AREA. GROUT
LIFTS AND CLEANOUTS TO COMPLY WITH
EOR'S NOTES ON SHEET MH 500.102
5/6/2022 12:55 PM R D OLSON
Partial inspection for Spa only not Fitness
building.
Contact Name: R D OLSON
Site Address: 79187 AHMANSON LN
Phone:9497690002
e-Mail: Inaefke@RDOLSON.COM
dcl changed Inspection Type from PRE -ROOF
to ROOF NAIL
- SPA BUILDING BOUNDARY AND EDGE
NAILING. REQUEST NAILING ON PARAPETS
AND CRICKETS WHEN READY.
Printed: Tuesday, July 19, 2022 10:22:43 AM 15 of 20
__ _.:17-wSYSiEMS
5/12/2022 2:10 PM R D OLSON
PM inspection please
Contact Name: R D OLSON
Site Address: 79187 AHMANSON LN
eTRAKiT Inspection
Phone: 9497690002
FOOTINGS
DCL
5/13/2022
5/13/2022
APPROVED
Request
a -Mail: Inaefke@RDOLSON.COM
- NORTH SIDE OF TREATMENT ROOMS AND
WEST SIDE OF SPA BUILDING WALK WAY
WALL FOOTINGS.
6/6/2022 9:24 AM R D OLSON
Am inspection please
Contact Name: R D OLSON
FRAMING
DCL
6/7/2022
6/7/2022
CANCELED
eTRAKiT Inspection
Site Address: 79187 AHMANSON LN
Request
Phone:9497690002
e-Mail: Inaefke@RDOLSON.COM
6/6/2022 9:22 AM R D OLSON
AM inspection please
Contact Name: R D OLSON
Site Address: 79187 AHMANSON LN
OKAY TO WRAP
DCL
6/7/2022
6/7/2022
NOT READY
eTRAKiT Inspection
phone: 9497690002
Request
a -Mail: Inaefke@RDOLSON.COM
- COMPLETE EXTERIOR MEP PENETRATIONS
AND FLASH WINDOWS/DOOR.
- BREEZEWAY AND FITNESS CENTER ONLY.
REQUEST ROOF NAIL INSPECTION FOR
PARAPETS WHEN READY.
ROOF NAIL
DCL
6/7/2022
6/7/2022
PARTIALLY
APPROVED
INCLUDES PARTIAL COMBO FOR FRAMING
AND MEP INSIDE ROOF TOP CHASE
BETWEEN EQUIPMENT ROOM AND SPA
BUILDING.
Printed: Tuesday, July 19, 2022 10:22:43 AM 16 of 20
__ _.:#?wSYSiEMS
OKAY TO WRAP
DCL
6/23/2022
6/23/2022
NOT READY
eTRAKiT Inspection
Request
6/22/2022 1:40 PM R D OLSON
Contact Name: R D OLSON
Site Address: 79187 AHMANSON LN
Phone:9496109375
e-Mail: aalarcon@RDOLSON.COM
- NOT READY.
6/27/2022 12:47 PM R D OLSON
partial inspection on treatment patio
exterior walls so I can close up the walls.
Contact Name: R D OLSON
Site Address: 79187 AHMANSON LN
PARTIALLY
eTRAKiT Inspection
Phone: 9497690002
ROUGH ELEC
JFU
6/28/2022
6/28/2022
APPROVED
Request
e-Mail:lnaefke@RDOLSON.COM
APPROVAL OF FMC CONDUIT AT ROOFTOP
WHERE INSULATION WILL COVER CONDUIT
AND A SECOND LAYER OF PLYWOOD WILL
COVER THESE CRICKETED AREAS.
6/27/2022 12:27 PM R D OLSON
Partial water, waste, vents, treatment rooms
and partial gas on the spa building
Contact Name: R D OLSON
Site Address: 79187 AHMANSON LN
PARTIALLY
Phone: 9497690002
ROUGH PLBG
JFU
6/28/2022
6/28/2022
APPROVED
PM inspection please
a -Mail: Inaefke@RDOLSON.COM
APPROVAL OFWATER PIPING AT ROOFTOP
WHERE INSULATION WILL COVER CONDUIT
AND A SECOND LAYER OF PLYWOOD WILL
COVER THESE CRICKETED AREAS.
Printed: Tuesday, July 19, 2022 10:22:43 AM 17 of 20
__ _.:IF-wSYSiEMS
6/29/2022 3:27 PM R D OLSON
roof insulation inspections
Contact Name: R D OLSON
Site Address: 79187 AHMANSON LN
Phone:9497690002
INSULATION
JFU
6/30/2022
6/30/2022
PARTIALLY
11 am inspection please
a -Mail: Inaefke@RDOLSON.COM
APPROVED
ROOF DECK INSULATION BETWEEN ROOF
DIAPHRAGM AND UPPER LAYER OF
SHEATHING (PER ROOF ASSEMBLY B) AT
FITNESS PORTION OF BUILDING ONLY.
7/5/2022 2:18 PM R D OLSON
for the remaining roof insulation for the spa
building as well as treatment patio wall
insulation.
Contact Name: R D OLSON
INSULATION
DCL
7/6/2022
7/6/2022
PARTIALLY
Pm / end of day
Site Address: 79187 AHMANSON LN
APPROVED
inspection please
Phone:9497690002
e-Mail: Inaefke@RDOLSON.COM
- ABOVE ROOF DECK AT TREATMENT
ROOMS AND SPA.
7/8/2022 6:37 AM R D OLSON
whole building
Contact Name: R D OLSON
Site Address: 79187 AHMANSON LN
Phone:9497690002
ROOF NAIL
JFU
7/11/2022
7/11/2022
PARTIALLY
eTRAKiT Inspection
a -Mail: Inaefke@RDOLSON.COM
APPROVED
Request
2ND LAYER OF ROOF SHEATHING (UPPER
LAYER) AT ALL AREAS EXCEPT MECHANICAL
WELLS AND MECHANICAL DOGHOUSE
STRUCTURES.
Printed: Tuesday, July 19, 2022 10:22:43 AM 18 of 20
__ _.:#rWSYSiEMS
ROOF NAIL
JFU
7/12/2022 1
7/12/2022
CANCELED
eTRAKiT Inspection
Request
7/11/2022 2:10 PM R D OLSON
Any time Thank you.
Contact Name: R D OLSON
Site Address: 79187 AHMANSON LN
Phone:9497690002
e-Mail: Inaefke@RDOLSON.COM
SEE ROOF NAIL INSPECTION APPROVAL
DATED 7/11/2022.
BOND INFORMATION
Attachment Type
CREATED
OWNER
ATTACHMENTS
DESCRIPTION PATHNAME
SUBDIR
ETRAKIT ENABLED
BCOM2021-0037 -
SCHOOL FEE
DOC
7/21/2021
AJ ORTEGA
CERTIFICATION OF
SCHOOL FEE
1
CERTIFICATION OF
COMPLIANCE
COMPLIANCE.pdf
BCOM2021-0037 -
DOC
7/21/2021
AJ ORTEGA
WASTE MANAGEMENT
WASTE MANAGEMENT
1
PLAN
PLAN.pdf
CVAG - SilverRock
CVAG - SilverRock
DOC
7/21/2021
AJ ORTEGA
Overall Assessment
Overall Assessment
0
Response(2021-07-
Response(2021-07-16)
16).pdf
BCOM2021-0037 -
DOC
7/21/2021
AJ ORTEGA
HEALTH DEPARTMENT
HEALTH DEPARTMENT
1
APPROVAL
APPROVAL.pdf
Printed: Tuesday, July 19, 2022 10:22:43 AM 19 of 20
__ _.:N-r-wSYSiEMS
Attachment Type
CREATED
OWNER
ATTACHMENTS
DESCRIPTION
PATHNAME
SUBDIR
ETRAKIT ENABLED
BCOM2021-0037 -
DOC
7/21/2021
AJ ORTEGA
CVWD APPROVAL (SPA)
CVWD APPROVAL
1
(SPA).pdf
BCOM2021-0037 - FIRE
DOC
7/21/2021
AJ ORTEGA
FIRE CONDITIONS OF
CONDITIONS OF
1
APPROVAL
APPROVAL.pdf
Printed: Tuesday, July 19, 2022 10:22:43 AM 20 of 20
__ _.:N-r-wSYSiEMS
�J,IATFR COACHELLA VALLEY WATER DISTRICT
O�STRIGC P.O. BOX 1058, COACHELLA, CALIFORNIA 92236 (760) 398-2651
INVOICE Date:3/23/2020
SUBJECT: PM 37207, SILVERROCK, 25000 SILVERROCK WAY, LA QUINTA, "MONTAGE HOTEL SPA" (SOURCE
CONTROL ONLY)
ROBERT GREENE Project: 20-10874
3551 FORTUNA RANCH RD. Project Date: 2/26/2020
Amount Due: $50.00
ENCINITAS, CA 92024 GEO: 06-07-05-3
Planner: SARA LOPEZ
TO INSURE PROPER CREDIT, PLEASE RETURN THIS PORTION WITH
REMITTANCE AND INCLUDE THE PROJECT ON YOUR CHECK
t Fee Type Description Charge Amount Total Amount
1.00 SA APP/WAIVER FEE SOURCE CNTRL 1 $60.001 $50.00
$50.00
Paid$ r — MHI)%
Development Services DepaWent
MAR 2 5 202D
Coachella Valiayy Water District
75-515 Hovely Lane East
Palm Desert, CA 92211
SUBJECT: PM 37207. SILVERROCK. 25000 SILVERROCK WAY, LA QUINTA. 'MONTAGE HOTEL SPA" (SOURCE CONTROL CN'_Y)
COACHELLA VALLEY WATER DISTRICT
P.O. BOX 1058, COACHELLA, CALIFORNIA 92236 (760) 398-2651
Pagel
COACHf LLA VALLEY NVA'rER DISTRICT
Hovicv Lane East
q75-515
Palrn Deserl, California 92211
(760) 398-2651
APPLICATION FOR WASTEWATER SOURCE CONTROL PLAN APPROVAL
\PI'I.K'•\`1T 1;0 nit tlu, fhnn a nh a cop} of a SCALED plot plan I . '•20' W I' 40' SCALE) dra\+n to Mstiio spec ticaii s A nonrelundahlc riling fee t+
rcqurnal i,I,Lti i'i; aPPtnau,m i, .uurnitiml Cliccl musi be made payable to the Cwche'la t•alley Wait! District .Appro+ai of thtc 4p;1, rahan shall remain t aad t •t
a P;nrts1 niv in nccrd ant: ! I l � c.t: from dale of payment NOTEs AL L USERS DISCHARGuNG FAT, OIL, AND/OR GlMtSE, LOCATED R4 A MULT1.
SUM BVIL.014G WILL REQUIRE A SEPARATE LATERAL bPP.THE MALNSFIVER LINE FOR GREASEimrERCEPTOR CONNECTION
C%'%%*D Source Control will insprrt the rspmed cressr plumbirg and the installed interceptor Please call (7601 398-2661 \3536 JB hours in adunce it,
schedule Ins eetion4s).
Apenr. Contoeior, Contac' Penor
Addrns City State Zip
Tc1crhvnc
A,drew M.criallen►o
225 8,oadway Smile 10C San D'opo CA 92101
(619; 223 3131
TrkPtvnnr --
ttuber Adders+ y - Cry Ha:: Z'
Robert Green 3551 Fortuna Rance Rand Encinitas CA 02024 1
(760) 634 65e3
lob Su: Adams% City Zip
25.000 SilverRock Way La Oulnta 92253
Dus:reu T57te Dmrf $tutne++ As
(. Ot-sTkj-L- SdvetAOCKLodOingLrC
NOTE: NO PLANS WILL BE APPROVED UNTIL T1i1S APPLICATION IS COMPLETF AN') PLAN• CHECK FEES ARE PAID
Tv a or Construction etc ❑ Remodel Hours of Upcmunn -Ea—m-10pm Cnnl ng'rowerts) ❑
For Vehicle Serc ice
For Food Service
O Wand Bays ❑ Trench Itrains i Ft;
)i Water Softener ❑ G,irbase Crmders) n Digester{;
D Roll over ❑ Seance bay(s) _
Niultiscn•tee (reusahic) 20 °. Single Scntce dlsP(3sabL-)_80
❑ Tunncl(s) ❑ Pans Washer
Sating Capacity Internal Fxtcrnal 50
CJ Spill Containment (Solvent O Aqucous 0 1
Sealing with S isrers or Healers
17 Hydraulic Lifts ❑Work Sink(s)
Bat Seaun Bnr Seavyip vnih Fo,.d Scn ice
0�VNFR/REPRESENTATWE DECLARATION I cemfv lha. I have rod the entire application and slate that all informatr in :s carrccl
understand that the fee 2motint is based on my declaration of information or thin futrn and tttai utcorreci inlurniatiwt is grounds for reje::r. • :,l Ili-
submitied plans 1 also understand that plans may be discarded if nor ptcked up Nvillnn stitty 160) days of appio+•ai. or raum and that m• Die ti ter i
inspection of my emahlishmeni will be coad ictrd until nil requested infonnaiajr• has been recnted and plane hate been arpro-d
5ignai.irc ���— Date t /ti /2t!
FOR D1STRICTME ONLY
No. ofSvornts I Type ofSystertt(c1 Pretreatment F.Rutpmrnl ---
0 Grease inierLepint lnlercepiut \failed
❑ Nesc ❑ Existing
❑ SandlOil
U ® Connect to Sc%c:r ❑ Addition 0 i-int Trap ❑ Point nrCornectwN Sample Stuituo
❑ Feplacemrni 0 C'lonficr ❑ Utgesicris.
r .,--- Size as
REMARKS: — - - --
'Discharges containing fats, oils, or grease (FOG) must be routed to Montage Hotel or Montage pool
rease_interceptors.
'No saltregenerativt-svater softeners allowed in CY.-WD jurisdic-doni only exchangeable bottles
systems are perm ssible.—
---- -
Thisappheatton
]/n� /�
IDcond,unr•,ll. ;,rhrn•c L7 Aprre..ed
F7 /,2t-L/ -5 1, V LI )
'Scc Rcmar l a
r es Q he.t
S notate-
I)atr 31a� ab
Date
3 Zs/a.Q2c�
CAL FIRE - RIVERSIDE UNIT
RIVERSIDE COUNTY FIRE DEPARTMENT �Cv
SHAWN C. NEWMAN - FIRE CHIT
OFFICE OF THE FIRE MARSHAL — LA QUINTA
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
July 2, 2020
Gensler San Diego
225 Broadway Ste 100
San Diego, CA 92101
Re: New Buildings - Fire Plan Review — MONTAGE HOTEL, SPA & POOL STRUCTURES
BCPR2019-0006 / 52-000 SILVERROCK WAY, LA QUINTA, CA 92253
The building plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
Fire Department approval is based upon the 2016 CBC requirements for A-2, A-3 & B occupancies. It is
prohibited to use, process or store any materials in the occupancy that would classify it as a Group H
occupancy, without further review and approval.
ACCESS
Fire Department emergency vehicle apparatus access road locations and design shall be in accordance with
the California Fire Code, Riverside County Ordinance 460, Riverside County Ordinance 787 and Riverside
County Fire Department Standards.
1) Certain designed areas will be required to be maintained as fire lanes and will require approved signs
and/or stenciling in red with CVC 22500.1 conspicuously posted.
2) Vehicle access gates shall be provided with KNOX Box, Padlock or Key -switch access. Automatic gates
shall also have Opticom IR receivers.
3) Approved street signs shall be installed and visible.
4) No Traffic Calming Devices shall be installed.
WATER
1) The Fire Department is required to set a minimum fire flow for the construction of all buildings using
the procedure established in the 2016 CFC.
a. MONTAGE HOTEL: A fire flow of 2,250 gpm flow @ 20 psi residual pressure from a
minimum of 2 fire hydrants flowing simultaneously/cumulatively for a 2-hour duration. This
water supply must be available within 400-feet of the project before vertical construction
begins.
i. Fire Flow requirement based on currently proposed 28,000 square feet structure of
type V-B construction. A 50% reduction due to the provision of required fire sprinkler
system has been included.
b. MONTAGE SPA: A fire flow of 1,875 gpm flow @ 20 psi residual pressure from a
minimum of 2 fire hydrants flowing simultaneously/cumulatively for a 2-hour duration. This
water supply must be available within 400-feet of the project before vertical construction
begins.
i. Fire Flow requirement based on currently proposed 20,000 square feet structure of
type V-B construction. A 50% reduction due to the provision of required fire sprinkler
system has been included.
MONTAGE POOL STRUCTURES: A fire flow of 1,000 gpm flow @ 20 psi residual
pressure from a minimum of 2 fire hydrants flowing simultaneously/cumulatively for a 2-hour
duration. This water supply must be available within 400-feet of the project before vertical
construction begins.
i. Fire Flow requirement based on currently proposed 4,000 square feet structure of type
V-B construction. A 50% reduction due to the provision of required fire sprinkler
system has been included.
1) Applicant and/or developer shall separately submit off -site water system plans to the Fire Department
office for review. Plans must be signed by a registered Civil Engineer and/or water purveyor prior to Fire
Marshal review and approval. Mylar will be signed by the Fire Marshal after review and approval.
DEFERRED SUBMITTALS REQUIRED
1) PRIVATE FIRE MAIN — System plans in compliance with NFPA 24 must be submitted to the Fire
Department for review and approval. Hydraulic Calculations are required. Permit fees will be required.
2) FIRE SPRINKLER SYSTEM - Install a complete fire sprinkler system per NFPA 13. System plans
must be submitted to the Fire Department for review and approval. The plans and documents shall
include certification and signature from the Structural Engineer attesting that the plans are compliant
with structural loading and design for the building. Permit fees will be required.
3) FIRE ALARM/MONITORING SYSTEM - Install a MANUAL fire alarm system as per NFPA 72
required by the California Building Code, California Fire Code and designed in accordance with adopted
standards. A C-10 licensed contractor must submit plans to the Fire Department office for review and
approval prior to installation. Permit fees will be required.
4) KITCHEN HOOD SUPPRESSION SYSTEM - A UL 300 hood/duct fire extinguishing system must be
installed over the cooking equipment as required by the California Fire Code, California Mechanical
Code and adopted standards. System plans must be submitted to the Fire Department for review, along
with current plan check/inspection fee. Permit fees will be required.
5) ABOVEGROUND HAZARDOUS CHEMICAL STORAGE TANK(S) — Plans and specifications shall
be submitted to the Fire Department for review and approval. Permit fees will be required. (This permit
type includes fuel -fired generators)
6) REFRIGERATION EQUIPMENT — An operational permit is required to operate a mechanical refrigeration unit
or system regulated by Chapter 6 in the CFC. (>220-pounds Class Al refrigerant / >30-pounds all other classes)
System plans must be submitted to the Fire Department for review. Permit fees will be required.
PRIOR TO FINAL
1) Approved building address shall be placed in such a position as to be plainly visible and legible from the
street and rear access if applicable. Building address numbers shall be a minimum of 12". Minimum 6"
tall suite addressing shall be provided to both the front and rear entrances. All addressing must be legible
and of a contrasting color with the background to be visible from the street at all hours.
2) Install Knox Key Lock box, mounted not higher than 6-feet above grade at approved location. Provide
keys to the tenant space (all tenants), utility rooms and elevator services for inclusion in the main
building Knox Box. Key(s) shall have durable and legible tags affixed for identification of the
correlating tenant space.
3) Submit flame-retardant certification(s) by applicator or manufacturer, along with CSFM Listing, for all
decorative materials used in this facility. Samples of flame-retardant material(s) may be required for
flame spread testing. All required treated materials must have a current CSFM approval tag affixed to
each item or panel. (Prior to building final inspection)
4) Install portable fire extinguishers per Title 19, but not less than 2A1OBC in rating, at the approved
locations. Additional placements may be required at time of inspection.
5) Occupancies storing or using significant volumes of hazardous materials shall appropriately display the
required NFPA 704 Hazard Placard on the exterior access to the yards, buildings and rooms where the
hazardous materials is located.
6) Applicable room door(s) shall be posted "ELECTRICAL", "FACP", "FIRE RISER" and "ROOF
ACCESS" on the outside of the door so it is visible and in a contrasting color.
7) Room occupancy load, as approved by the Building Official, shall be posted in a conspicuous place near
the main exit from the room(s). The location shall be approved by the Fire Department office. Posting
shall be by means of an approved durable sign having a contrasting color from the background to which
it is attached. The owner shall maintain signs in a legible manner. No person shall deface, remove or
change the occupant load on the sign except as authorized by the Building Official and/or Fire
Department office. (Prior to building final inspection)
8) Illuminated Exit Signage and Egress Illumination placement and functional test will be witnessed by
OFM Fire Inspector.
9) Fire rated assemblies shall be maintained in compliance with applicable codes and industry standards.
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7074.
Kohl Hetrick - Fire Safety Specialist
County of Riverside
DEPARTMENTOF ENVIRONMENTAL HEALTH
P.O. BOX 7909 • RIVERSIDE, CA92513-7909
KEITH JONES, DIRECTOR
Protecting People and the E-van—,
FOOD ESTABLISHMENT PLAN APPROVAL NOTICE
Plan Check # 47179 Date 5/5/2020
Project Name Silver Rock Lodging (H1
and Hs)
Plans Submitted by Veit Kugel
Address 52-000 Silver Rock Road
Phone 619-557-2529
Owner Robert Green Address 3551 Fortuna Ranch Road, Encinitas CA Phone 760-634-6543
The plans are now approved subject to the conditions listed below and the attached compliance sheet.
1. Note: As per email received on 5/5/2020 from Veit Kugel the flooring note VCT means
commercial continuous sheet vinyl.
2. Provide grease interceptor approval install letter from the sewer agency prior to final
inspection.
3. Provide air balance report for all exhaust and make up air prior to final inspection.
4. The bar cover must be present and installed at time of final inspection.
CONSTRUCTION INSPECTIONS: Contact the Plan Checkerfor a Preliminary Inspection when construction is
approximately 80% complete, with plumbing, rough ventilation, and rough equipment installed. Request for inspection
should be made at least five (5) working days in advance.
"ALL ELECTRICAL, PLUMBING, MECHANICAL, AND STRUCTURAL REPAIRS AND INSTALLATIONS SHALL BE
DONE UNDER PERMIT FROM THE APPROPRIATE BUILDING & SAFETY DEPARTMENT (CITY OR COUNTY) --
A FINAL INSPECTION MUST be made upon completion of ALL work including finished details. APPROVAL to operate
shall not be granted, or remodeled areas approved to operate, until the facility has passed the FINAL INSPECTION, and
"APPLICATION TO OPERATE" has been completed and PERMIT FEES have been paid.
Request for inspection should be made at least five (5) working days in advance.
PLANS CHECKED BY Tracey Ford Phone 760-863-8287
I acknowledge the corrections noted herein and as indicated on the plans and agree to incorporate them during
construction: �w�"] �_ /,�
Signature_ Date 05.05.2020
Company Name Gensler
Corona Hemet
Indio
Murrieta
Palm Springs
Riverside -west Riverside -Fast
2275 S. Main St ON SW S. Sanderson #200
47-950 Arabia St "A"
38740 Sky Canyon Dr.
544 S. Pasco Dorotea
4065 County Circle 3880 Leman St.
Corona, Ca 92882 Hemet, Ca 92545
Indio, Ca 92201
Murrieta, Ca 92563
Palm Springs, Ca
Riverside, Ca 92503 Riverside, Ca 92501
(951) 273-9140 (951) 766.2824
(760) 863-8287
(951) 461-0284
92264
(951) 358-5172 (951) 955-8%2
760.320-1048
Office Locations 0 Blythe
• Corona • Hemet • Indio • Murrieta • Palm
Springs • Riverside
Phone (888)722-4234
www.rivcoeh.org
Date: 7/12/2021
No.: 21-02079-1
Owner: SilverRock Phase 1
Address: 79187 Ahmanson Ln
City: La Quinta
Type: Commercial
Lot # Street No.
79187
Comments:
CERTIFICATE OF COMPLIANCEC(o
PDE
Desert Sands Unified School Dist ERT
47950 Dune Palms Road SA DS
La Quinta, CA 92253 UNIFIED
(760)771-8515 SCHOOL
DISTRICT
Email: josh@therobertgreencompany.com
Jurisdiction: La Quinta
Tract #:
Street Name Sq. Feet APN Permit No.
Ahmanson Ln 11678 777-490-012
At the present time, the Desert Sands Unified School District does not collect fees on garages/carports, covered patios/walkways, residential additions
under 500 square feet, detached accessory structures (spaces that do not contain facilities for living, sleeping, cooking eating, or sanitation) or replacement
mobile homes. It has been determined that the above -named owner is exempt from paying school fees at this time due to the following reason:
EXEMPTION NOT APPLICABLE
This certifies that school facility fess imposed pursuant to
Education Code Section 17620 and Government Code 65995 Et Seq.
in the amount of $0.66 X 11678 S.F. or $7,707.48 have been paid for the property listed above and that building
permits and/or Certificates of Occupancy for this square footage in the proposed project may now be issued.
Fees Paid By: CC/ Bank of ALnerica/ Josh Frantz
Bank Name/Recipient of Certificate
By Scott L. Bailey
Superintendent
Fee Collected/ Exempted by: Yazmin Henry
Check No.: 0929922823
Telephone: 805-804-2454
Funding: Commercial
Certificate Fees Due: $7,707.48
Original Payment(s) Rec'd: $0.00
New Payment Rec'd: $7,707.48
Over/Under: $0.00
NOTICE: Pursuant to Government Code Section 66020(d)(1), this will serve to notify you that the 90-day approval period in which you may protest the fees or
other payment identified above will begin to run from the date on which the building or installation permit for this project is issued, or from the date on
which those amounts are paid to the District(s) or to another public entity authorized to collect them on the District('s) behalf, whichever is earlier.
Notice to Building Department: THIS DOCUMENT VALID ONLY IF IMPRINTED WITH EMBOSSED SEAL.
Building Permit Number. #BCPR2019-0006
Project Description: SFR
Exempt: ❑
(Materials may contain hazardous wastes and
are not subject to recycling provisions)
Construction Debris Management Plan
Plan Submittal Date; 10/27/2020
Montage La Quinta - Main Hotel & Spa
Job SiteAddressl 52-000 SilverRock Way
Owners Namel SilverRock Development Co.
Number. Street, or PO BoxJ 343 Fourth Ave.
City, State, Postal Codel San Diego, CA
Owner's Phone Number) 760-634-6543
Owner's E•Mail Address jpshiatherobertgreencompany.corn
Project Manager's Name
Project Manager's Phone Number
Project Manager's E-mail Address
Builder / Contractor
Number, Street or PO Box
City, State, Postal Code
Project Square Footage)
Gary Hoskins
949-222-3761
ghoskrnsCardq son.com
R.D. Olson
400 Spectrum Center Dr
Irvine, CA
97,000
Approval By Burrtec `�!✓i //�
Date of City Approval
Materials To Be Discarded:
Product
Trash
Asphalt
Brick/Block
Cardboard
Commingled
Concrete
Drywall
Donated / Reuse"
"Describe Items
Tons
360.00 Not recyclable
0.00 Recyclable
0.00 Recyclable
26.00 Recvclable
485.00 Recyclable
51.00 Recyclable
0.00 Recyclable
Totals: Recycle Trash
892.0 1 360.0
Product
Masonry (broken)
Plaster
Scrap Metal
Tile (floor)
Tile (roof)
Wood
Landscape Debris
Tons
0.00 Recyclable
121 00 Rxyclabw
0.00 Recyclable
10.00 Recyclable
14.00 Recyclable
185.00 Recyclable
0.00 Recyclable
Projected Diversion:
71.25%
I understand it is the property owner's responsibility to submit copies of weight tickets or receipts to the District
Environmental Coordinator as these hauls occur. I hereby certify that completion. implementation and adherence of the
Debris Management Plan (DMP) for the above named project shall guarantee that at least 65% of the jobsite waste is diverted
from landfilling. The remaining material will be recycled or reused I will divert, for recycling or re -use, remaining materials
generated from the first day of the project through the completion of the project in accordance with this plan. This DMP is issued
in the name of the property owner(s) and shall remain their property throughout the construction and/or demolition project. A
contractor serving as agent of the owner may obtain a DMP for the owner. However, the DMP is still issued in the name of the
property owner(s) and the owner retains legal responsibility for ensuring that the provisions of the DMP are adhered to. The
property owner(s) and general contractor shall be kept informed of the diversion progress through bi-monthly reports. If self -
hauling, all refuse material from this project site must be taken to an approved recycler or transfer station.
owner i Developer / Project Manager / Superintendant Date
Construction Debris Management Plan
Summary of Requirements
As of January 1, 2017, The Green Building Standards Code (CALGreen) requires that the construction of
most new structures in the State of California comply with sections 4.408 and 5.408 of the code in
accordance with Assembly Bill 939 requiring that no more than 35% of jobsite waste be disposed of as
trash at local land fill sites and transfer stations Exceptions may be made for certain projects under
certain conditions.
The City of La ouinta is committed to the highest level of environmental respect, to conserving our
precious natural resources and setting an example to provide for a better world for generations to come.
Recycling helps keep reusable resources out of landfills and will also reduce disposal costs.
IMPORTANT: Burrtec Waste & Recycling Services is the City's franchise
hauler. If you choose to self -haul any recyclables or trash, you must
provide copies of all weight tickets and/or receipts from the transfer
station. landfill, or recycler as the job progresses. Clean-up companies
and other haulers are not permitted to haul waste or recyclables from the
City of La Quinta. Self -haul weight tickets should be submitted to: Mike
Veto, District Environmental Coordinator - mveto@burrtecdesert.com, or
faxed to (760) 340-0417, or mailed to: 41575 Eclectic Street, Palm
Desert, CA. 92260.
AJ Ortega
From: Peter Satin <psatin@cvag.org>
Sent: Friday, July 16, 2021 11:27 AM
To: AJ Ortega
Subject: RE: City of La Quinta - TUMF and MSHCP Assessment Question (SilverRock Resort)
EXTERNAL: This message originated outside of the City of La Quinta. Please use proper judgement and caution when opening
attachments, clicking links or responding to requests for information.
Hi AJ,
For the current project, the conference center, spa, meeting room, and shared services building all constitute ancillary
uses and need not be included in the final TUMF calculation. While the total area of the spa is now moot, I would have
included the pool decks and potentially the gardens, especially if the latter would host classes.
As for the LDMF, III defer to the standard practice of the City. Our primary concern would be if any of these buildings
were to expand in the future, that we be easily able to ascertain how much may have already been paid.
Please continue to touch base as these joint resort/residential projects come online, and let me know if there is anything
else I can provide for the current project.
Best,
Peter Satin
Regional Planner
Coachella Valley Association of Governments
psatin@cvag.org
0: 760.346.1127 ext. 118
C: 925.270.5498
From: AJ Ortega <Aortega@laquintaca.gov>
Sent: Friday, 9 July, 2021 16:34
To: Peter Satin <psatin@cvag.org>
Subject: City of La Quinta - TUMF and MSHCP Assessment Question (SilverRock Resort)
Hi Peter,
Have another Project that I need to run by you to make sure we have it right — The highly anticipated
SilverRock Resort Project is getting close to being able to pull permits, and based on some new
information you have provided regarding un-enclosed and un-roofed areas, and un-enclosed roofed
spaces, I wanted to make sure my logic of "integral to the performance of the principal business" are in -
line with your methodology. Then also I am having a hard time with the "ancillary uses" text and how a
hotel includes "supporting facilities such as restaurants, cocktail lounges, meeting and banquet rooms or
convention facilities, limited recreational facilities and/or other retail and service shops."
Exhibits and Area Lists are provided for both the Montage Hotel Services Building and the Montage Spa
Building for your review. I have in Blue the TUMF Area with notes in certain areas identifying reasoning for
Assessment, in Red is the Roofed Area Totaled, and in Yellow/Black is the "within the principal outside
faces of the exterior wall" Area Totaled. For various reasons more and more areas of certain things need
to be calculated to be able to complete the permit fees correctly, too complicated.
I am not actually doing the permits for the Meeting Rooms, Convention Center or Shared Services
Buildings yet (thought I would still include them for the basis of your decision), so with that "ancillary
uses" text and hotels include "supporting facilities", shouldn't this be similar to how a resort golf course
isn't only played by hotel guests, a spa or convention center also receive outside business from that of the
guest rooms. How would it be fair for a hotel without these features to be assessed with a methodology
that did take into account additional trips generated by having a hotel/spa or hotel/convention center...
even in reverse if the hotel methodology didn't account for outside business trips, wouldn't it definitely be
missing that trip assessment - Maybe I have this all wrong?
To hopefully make it easier for you to respond, my basic questions and concerns are as follows:
1. The 2018 TUMF Handbook has for Hotels in Section 4.6, "Supporting facilities" and 'For the sake of
calculating the TUMF, all of the ancillary uses are considered as one use under the Hotel category",
does this mean the separate Spa, Meeting Room, Convention Center and Shared Services Building
Square Footages will not be Assessed in addition to the Number of Guest Rooms?
2. If not disqualified from above, in the attached exhibit for the Spa Building, do you feel the outside
areas that I have both included and omitted accurately follow the methodology for the proposed
scope of work?
3. Being the Hotel Services Buildings (which includes the Pool Services and Equipment Buildings) and
the Spa Building are on one site is it acceptable to collect the whole LDMF Commercial Acreage on
a single permit vs trying to do some percentage calculation and applying it to the separate building
permits that will ultimately be issued for construction?
As always thank you for your help.
�i�•.i'.—
AJ Ortega I Building Official
Design and Development Department
City of La Quinta
78495 Calle Tampico I La Quinta, CA 92253
Phone 760.777.7018
www.laquintaca.gov
www.i)lavinlaciuinta.com
WARNING: External email. Please verify sender before opening attachments or clicking on links.