BELC2019-0015 - Temp Golf Clubhouse ElectricalADDITIONAL SITES
CHRONOLOGY
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
E-MAIL AJ ORTEGA 3/20/2019 3/20/2019
EMAIL APPLICANT JOHN
(JOHN@THEROBERTGREENCOMPANY.COM) WITH
CONDITIONS FOR ISSUANCE OF PERMIT.
E-MAIL JAKE FUSON 8/1/2019 8/1/2019 NOTIFIED JOHN GAMLIN THAT REVISION 1 PLANS WERE
APPROVED.
PLAN CHECK SUBMITTAL
RECEIVED AJ ORTEGA 7/10/2019 7/15/2019
PLANS UPLOADED FOR REVISION TO PERMITTED SCOPE AND
FOR ADDITIONAL WORK, BASED ON PROPOSED SCOPE OF
WORK REVIEWS CREATED ON EXISTING PERMIT, NO
ADDITIONAL PERMIT REQUIRED.
PUBLIC COUNTER VISIT JACK LIMA 3/15/2019 3/15/2019 JOHN GAMLIN CAME TO THE COUNTER TO PAY PERMIT FEES.
Description: SILVERROCK / TEMPORARY CLUB HOUSE ELECTRICAL SERVICE
Type: ELECTRICAL (WEB)Subtype: Status: FINALED Applied: 1/29/2019 ECON
Parcel No: 777490007 Site Address: 79087 AHMANSON LN LA QUINTA,CA 92253 Approved: 3/21/2019 JLIM
Subdivision: PM 33367 Block: Lot: 14 Issued: 3/21/2019 JLIM
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning: Finaled: 8/22/2019 crw
Valuation: $25,000.00 Occupancy Type: Construction Type: Expired:
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details: TEMPORARY CLUBHOUSE 600A ELECTRICAL SERVICE WITH SITE SUBPANELS AND LIGHTING. THIS PERMIT DOES NOT INCLUDE
REVIEW OF TEMPORARY STRUCTURES; CLUBHOUSE BUILDING AND CART BARN SPRUNG STRUCTURES. DEFERRED SUBMITTAL OF
LIGHT POLE BASE CONSTRUCTION, POLE AND BASE HEIGHT TO MEET MANDATORY LIGHTING CONTROL REQUIREMENTS. 2016
CALIFORNIA BUILDING CODES.
REVISION 1: BRANCH CIRCUITS.
Printed: Tuesday, July 19, 2022 9:27:43 AM 1 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
BELC2019-0015
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT SilverRock Phase I, LLC 3551 FORTUNA RANCH
ROAD
ENCINITAS CA 92024 (760)238-2443 john@therobertgreenc
ompany.com
CONTRACTOR GRANITE CONSTRUCTION COMPANY P O BOX 50085 WATSONVILLE CA 95077-
5085
(760)238-2443 JOE.RICHARDSON@GCI
NC.COM
OWNER SilverRock Phase I, LLC 3551 FORTUNA RANCH
ROAD
ENCINITAS CA 92024 (760)238-2443 john@therobertgreenc
ompany.com
CONDITION
TYPE CONTACT DATE
ADDED
DATE
REQUIRED
DATE
SATISFIED STATUS REMARKS NOTES
READY TO ISSUE
CHECKLIST AJ ORTEGA 3/20/2019 3/21/2019 COMPLETE
CONTRACTOR INFORMATION (STATE LICENSE
WITH CITY BUSINESS LICENSE, AND
AUTHORIZATION OF SIGNEE) REQUIRED.
ADDED CONTRACTOR INFORMATION.
AUTHORIZED SIGNEE LIST ATTACHED TO
BUSINESS LICENSE. CHANGED STATUS OF PERMIT
TO ISSUED FROM APPROVED WITH CONDITIONS.
I MANUALLY CHANGED THE STATUS OF THIS
PERMIT TO ISSUED BECAUSE PERMIT HAD BEEN
PREVIOUSLY PAID.
PUBLIC COUNTER VISIT JACK LIMA 3/21/2019 3/21/2019
ADDED CONTRACTOR INFORMATION. AUTHORIZED SIGNEE
LIST ATTACHED TO BUSINESS LICENSE. CHANGED STATUS OF
PERMIT TO ISSUED FROM APPROVED WITH CONDITIONS. I
MANUALLY CHANGED THE STATUS OF THIS PERMIT TO
ISSUED BECAUSE PERMIT HAD BEEN PREVIOUSLY PAID.
RESUBMITTAL AJ ORTEGA 3/15/2019 3/18/2019
ATTACHMENTS UPLOADED 3/15/2019 APPEAR TO BE FOR
PERMIT BELC2019-0014, EMAIL SENT TO APPLICANT JOHN
(JOHN@THEROBERTGREENCOMPANY.COM) REQUESTING
CLARIFICATION IF HE INTENDED TO SUBMIT BOTH PROJECTS,
WAITING FOR RESPONSE BEFORE PROCEEDING WITH
CREATING REVIEWS AS PROJECT IS CURRENTLY INCOMPLETE.
CONDITIONS
Printed: Tuesday, July 19, 2022 9:27:43 AM 2 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
BELC2019-0015
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
HOURLY CHARGE - CITY
BUILDING STAFF 101-0000-42600 1 $160.00 $160.00 8/1/19 WEB3958 CREDIT SOFIA INVESTMENTS,
INC/RGC ECON
Total Paid for BLDG CITY STAFF - PER HOUR: $160.00 $160.00
BSAS SB1473 FEE 101-0000-20306 0 $1.00 $1.00 3/15/19 R46578 1039 CHECK SilverRock Phase I, LLC JLIM
Total Paid for BUILDING STANDARDS ADMINISTRATION
BSA: $1.00 $1.00
Credit Card Fee 101-0000-43505 0 $2.88 $2.88 8/1/19 WEB3958 CREDIT SOFIA INVESTMENTS,
INC/RGC ECON
Total Paid for Credit Card Fee: $2.88 $2.88
OTHER ELECTRICAL
EQUIPMENT 101-0000-42403 0 $53.36 $53.36 3/15/19 R46578 1039 CHECK SilverRock Phase I, LLC JLIM
OTHER ELECTRICAL
EQUIPMENT PC 101-0000-42600 0 $53.36 $53.36 3/15/19 R46578 1039 CHECK SilverRock Phase I, LLC JLIM
POLE LIGHTS, FIRST 10 101-0000-42403 0 $26.68 $26.68 3/15/19 R46578 1039 CHECK SilverRock Phase I, LLC JLIM
POLE LIGHTS, FIRST 10
PC 101-0000-42600 0 $26.68 $26.68 3/15/19 R46578 1039 CHECK SilverRock Phase I, LLC JLIM
POWER APPARATUS 101-0000-42403 0 $26.68 $26.68 3/15/19 R46578 1039 CHECK SilverRock Phase I, LLC JLIM
POWER APPARATUS PC 101-0000-42600 0 $26.68 $26.68 3/15/19 R46578 1039 CHECK SilverRock Phase I, LLC JLIM
TEMP POWER SERVICE 101-0000-42403 0 $26.68 $26.68 3/15/19 R46578 1039 CHECK SilverRock Phase I, LLC JLIM
TEMP POWER SERVICE
PC 101-0000-42600 0 $18.68 $18.68 3/15/19 R46578 1039 CHECK SilverRock Phase I, LLC JLIM
Total Paid for ELECTRICAL: $258.80 $258.80
PERMIT ISSUANCE 101-0000-42404 0 $101.40 $101.40 3/15/19 R46578 1039 CHECK SilverRock Phase I, LLC JLIM
Total Paid for PERMIT ISSUANCE: $101.40 $101.40
RECORDS
MANAGEMENT FEE 101-0000-42416 0 $10.00 $10.00 3/15/19 R46578 1039 CHECK SilverRock Phase I, LLC JLIM
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $10.00
Printed: Tuesday, July 19, 2022 9:27:43 AM 3 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
BELC2019-0015
INSPECTIONS
SEQID INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
UNDERGROUND ELEC AOR 4/30/2019 4/30/2019
APPROVED
W/EXCEPTIO
N
UNDERGROUND FEEDER FROM SERVICE TO
DB1, AND DB1 TO CB1, CB2, PRESSURE
WASHER AND FIRST JUNCTION BOX ON
LIGHT POLE RUN - DOES NOT INCLUDE
RISERS AT DB1 OR CONDUCTORS.
UNDERGROUND ELEC AOR 5/1/2019 5/1/2019 APPROVED
RISER INSTALLATION AND LIGHT POLE RUN
ONLY, NO OTHER UG WORK WITHIN
PERMITTED SCOPE.
SLAB DCL 5/3/2019 5/3/2019 APPROVED - NOTE SPECIAL INSPECTION REQUIRED FOR
WEDGE ANCHORS AT GEAR BOX.
UNDERGROUND ELEC JFU 7/31/2019 7/31/2019 CANCELED INSPECTION CANCELED BY CHRIS KING.
FOOTINGS JFU 8/6/2019 8/6/2019 APPROVED
(1) PARKING LOT LIGHT STANDARD FOOTING
ONLY. APPROVED PER ATTACHED RFI FOR
UPDATED FOOTING DESIGN.
ROUGH ELEC AOR 8/12/2019 8/14/2019 PARTIALLY
APPROVED
SEE BCOM2019-0029 FOR MISPLACED
INSPECTION - REINSPECTION TO CONFIRM
INSTALLATION OF APPRORIATE OCPD
LOCKING DEVICE (PER JFUSON REVIEW OF
EQUIPMENT DEVICE IS ACCEPTABLE) AND
INSTALLATION AT CART BARNS, PANELS
NOW LABELED AND WITH GFCI
PROTECTION, PENDING FINAL INSTALLATION
OF CART CHARGERS FOR FINAL APPROVAL.
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 3/15/19 R46578 1039 CHECK SilverRock Phase I, LLC JLIM
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$539.08 $539.08
Printed: Tuesday, July 19, 2022 9:27:43 AM 4 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
BELC2019-0015
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 2/7/2019 AJ ORTEGA
1ST REVIEW PLAN
MARKUP WITH
SUMMARY
BELC2019-0015 - 1ST
REVIEW PLAN MARKUP
WITH SUMMARY.pdf
1
DOC 3/20/2019 AJ ORTEGA ELECTRICAL PLAN
(APPROVED)
BELC2019-0015 -
ELECTRICAL PLAN
(APPROVED).pdf
1
BOND INFORMATION
FINAL**AOR 8/22/2019 8/22/2019 APPROVED
REVIEWS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE
STATUS REMARKS NOTES
1ST BLDG NS -
ETRAKIT (1 DAY)AJ ORTEGA 1/29/2019 1/30/2019 2/7/2019 REVISIONS REQUIRED SEE ATTACHED 1ST REVIEW PLAN MARKUPS AND
SUMMARY.
2ND BLDG NS –
ETRAKIT (1 WK)
AJ ORTEGA 3/18/2019 3/25/2019 3/20/2019 APPROVED
1ST BLDG NS -
ETRAKIT (1 WK)JAKE FUSON 7/10/2019 7/17/2019 7/23/2019 REVISIONS REQUIRED REVISION 1: BRANCH
CIRCUITS
-PROVIDE APPROVAL FROM ENGINEER FOR
INSTALLATION OF (4) LIGHT FIXTURES AT LIGHT
POLE AS DETAIL PROVIDED ONLY ALLOWS (2)
15LB FIXTURES
-UPDATE PANEL SCHEDULE AND SINGLE LINE
DIAGRAM TO INCLUDE CONDUIT & CONDUCTOR
SIZES AS WELL AS CIRCUIT INFORMATION AT
PANEL
2ND BLDG NS –
ETRAKIT (1 WK)
JAKE FUSON 7/31/2019 8/7/2019 8/1/2019 APPROVED BRANCH CIRCUITS REVISION 1: BRANCH CIRCUITS.
PARENT PROJECTS
Printed: Tuesday, July 19, 2022 9:27:43 AM 5 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
BELC2019-0015
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 2/1/2019 EtrakitContractor
1ST SUBMITTAL
TEMPORARY CLUB
HOUSE ELECTRICAL
PLANS
BELC2019-0015 - 1ST
SUBMITTAL
TEMPORARY CLUB
HOUSE ELECTRICAL
PLANS.pdf
1
DOC 3/18/2019 EtrakitContractor 2ND SUBMITTAL
APPLICANT RESPONSES
BELC2019-0015 - 2ND
SUBMITTAL APPLICANT
RESPONSES.pdf
1
DOC 3/18/2019 EtrakitContractor
2ND SUBMITTAL
TEMPORARY CLUB
HOUSE ELECTRICAL
PLANS
BELC2019-0015 - 2ND
SUBMITTAL
TEMPORARY CLUB
HOUSE ELECTRICAL
PLANS.pdf
1
DOC 7/10/2019 EtrakitContractor SR TC Cart Barn Interior
Electrical - Description Changes Narrative.pdf 1
DOC 7/10/2019 EtrakitContractor
SR TC Cart Barn Interior
Electrical - Electrical
Plan Set
Silver Rock - Temporary
Clubhouse and Cart
Barn -ELECTRICAL SET 7-
10-19.pdf
1
DOC 7/29/2019 EtrakitContractor Approved Site Electrical
Set_Updated 7.29.2019
Silver Rock - Temporary
Clubhouse and Cart
Barn - Electrical Set 7-29
-19.pdf
1
DOC 8/1/2019 JAKE FUSON REVISION 1 - APPROVED
ELECTRICAL PLANS
BELC2019-0015 -
REVISION 1 - APPROVED
ELECTRICAL PLANS.pdf
1
DOC 8/6/2019 JAKE FUSON RFI - REVISED LIGHT
POLE FOOTING DETAIL
BELC2019-0015 - RFI -
REVISED LIGHT POLE
FOOTING DETAIL.pdf
1
Printed: Tuesday, July 19, 2022 9:27:43 AM 6 of 6
Permit Details
City of La Quinta
PERMIT NUMBER
BELC2019-0015
STRUCTURAL STAMP
PROVIDED FOR DESIGN
OF LIGHT POLE
FOUNDATION ONLY
18'-0" TALL x 5"
WIDE POST MAX
(2) 15 LBS LIGHTS MAX
18" MAX
6"
M
A
X
20
BASE PLATE AND
ANCHORAGE PER
POLE MFR
A615
4'-6"
MIN.
PER MFR
(4)
POLE BASE DEAIL FOR UP TO 18'-0" TALL POLE WITH 30" TALL BASE.
1044 Pioneer Way, Suite E. El Cajon CA, 92020
Telephone: 619.334.6020 ext 212 Email: acortez@rbcengineers.com
July 10, 2019
Project Name: Silver Rock Temporary Clubhouse and Cart Barn
Project Address: 79087 Ahmanson Lane
Electrical Changes Narrative – Delta 2
E0.01 COVER SHEET:
· Updated sheet index.
E0.02 TITLE 24 FORMS:
· Updated T24.
E2.01 SITE LIGHTING PLAN:
· Updated note #2.
· Shown note #2 on site
· Update luminaire schedule
· Added light pole base detail
E3.01 SITE POWER PLAN:
· Updated DB1 feeders.
E3.02 CART BARN ELECTRICAL PLAN:
· Added sheet.
E8.01 SINGLE LINE DIAGRAM:
· Updated DB1 feeders.
E9.01 PANEL SCHEDULE:
· Update panel schedule CB1 & CB2.
· Revised Voltage drop calculations.
· Revised Fault current schedule.