Andalusia TR 31681-3 BCPR2020-0004 (Plan 22) 2019 Code UpdateADDITIONAL SITES
CHRONOLOGY
CHRONOLOGY TYPE STAFF NAME ACTION DATE COMPLETION DATE NOTES
COUNTER VISIT AARON HICKSON 1/27/2020 1/27/2020 PLAN CHECK DEPOSIT LOWERED PER AJ
NOTE AARON HICKSON 2/18/2020 2/18/2020 PLAN CHECK RECEIVED FROM INTERWEST REVISIONS
REQUIRED
NOTE ARMANDO MAGALLON 2/18/2020 2/18/2020 PLANS HAVE BEEN RECEIVED FROM OUTSIDE COSULTANT
WITH CORRECTIONS
EMAIL DUANE CLAYTON 3/10/2020 3/10/2020 - INFORMED APPLICANT THAT PLAN REVIEW IS COMPLETE
AND REQUIRES REVISIONS.
1ST PC PICKED UP JACK LIMA 3/11/2020 3/11/2020 PLANS SUBMITTAL PACKAGE RECEIVED BY NOLAN SPARKS.
EMAIL DUANE CLAYTON 4/23/2020 4/23/2020 - INFORMED APPLICANT THAT PLAN REVIEW IS COMPLETE
AND APPROVED.
CONDITIONS
Description: ANDALUSIA / 2019 CODE UPDATE / PLAN 22 Status: APPROVED
Type: BUILDING CONSTRUCTION PLAN REVIEW Status Date: 4/14/2020
Subtype: TRACT RESIDENTIAL Applied: 1/24/2020
Address: 59000 MADISON ST Approved:
City, State, Zip: LA QUINTA,CA92253 Closed:
Project Manager: Expired:
Details: CODE UPDATE FOR 3560 SF DWELLING - PLAN 22 [VB/RES-3/CLASS A-FR/13D] THIS
PERMIT DOES NOT INCLUDE POOL, SPA, BLOCK WALLS OR DRIVEWAY APPROACH.
2019 CALIFORNIA BUILDING CODES.
Printed: Wednesday, December 20, 2023 10:41:45 AM 1 of 6
Project Details
City of La Quinta
PROJECT NUMBER
BCPR2020-0004
CONTACTS
NAME TYPE NAME ADDRESS1 CITY STATE ZIP PHONE FAX EMAIL
APPLICANT NOLAN SPARKS /SUNRISE LQ, LLC 81570 CARBONERAS LA QUINTA CA 92253 NSPARKS@RANCHOLA
QUINTA.COM
CONTRACTOR NATIONAL MORTGAGE & LAND
COMPANY
300 EAGLE DANCE
CIRCLE
PALM DESERT CA 92211
OWNER T D DESERT DEV 81570 CARBONERAS LA QUINTA CA 0
FINANCIAL INFORMATION
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
101-0000-42600 ($241.50)($241.50)4/23/20 OFFSET OFFSET DCL
101-0000-42600 ($200.00)($200.00)4/23/20 OFFSET OFFSET DCL
101-0000-42600 ($250.00)($250.00)4/23/20 OFFSET OFFSET DCL
101-0000-42600 ($58.50)($58.50)4/23/20 OFFSET OFFSET DCL
HOURLY CHARGE - CITY
BUILDING STAFF 101-0000-42600 1.5 $241.50 $241.50 4/23/20 DEPOSIT DEPOSIT DCL
HOURLY CHARGE -
INTERWEST PLANS
EXAMINER
101-0000-42600 2 $200.00 $200.00 4/23/20 DEPOSIT DEPOSIT DCL
HOURLY CHARGE -
INTERWEST PLANS
EXAMINER
101-0000-42600 1 $100.00 $100.00 5/5/20 WEB5047 CREDIT
NATIONAL
MORTGAGE & LAND
COMPA
ECON
HOURLY CHARGE -
INTERWEST
STRUCTURAL PLAN
REVIEW
101-0000-42600 2 $250.00 $250.00 4/23/20 DEPOSIT DEPOSIT DCL
HOURLY CHARGE -
INTERWEST
STRUCTURAL PLAN
REVIEW
101-0000-42600 1 $58.50 $58.50 4/23/20 DEPOSIT DEPOSIT DCL
Printed: Wednesday, December 20, 2023 10:41:45 AM 2 of 6
Project Details
City of La Quinta
PROJECT NUMBER
BCPR2020-0004
INSPECTIONS
INSPECTION TYPE INSPECTOR SCHEDULED
DATE
COMPLETED
DATE
RESULT REMARKS NOTES
REVIEWS
DESCRIPTION ACCOUNT QTY AMOUNT PAID PAID DATE RECEIPT #CHECK #METHOD PAID BY CLTD
BY
HOURLY CHARGE -
INTERWEST
STRUCTURAL PLAN
REVIEW
101-0000-42600 0 $66.50 $66.50 5/5/20 WEB5047 CREDIT
NATIONAL
MORTGAGE & LAND
COMPA
ECON
Total Paid for BUILDING STAFF - PER HOUR: $166.50 $166.50
BUILDING TRACT
RESIDENTIAL
CONSTRUCTION PLAN
DEPOSIT
101-0000-42600 1 $750.00 $750.00 1/24/20 MR829 867270 CREDIT
CARD NOLAN SPARKS AHI
Total Paid for BUILDING TRACT RESIDENTIAL
CONSTRUCTION PLAN DEPOSIT: $750.00 $750.00
RECORDS
MANAGEMENT FEE -
MAJOR
101-0000-42416 0 $21.00 $21.00 4/14/20 WEB4889 CREDIT
NATIONAL
MORTGAGE & LAND
COMPA
ECON
Total Paid for RECORDS MANAGEMENT FEE - MAJOR: $21.00 $21.00
TECHNOLOGY
ENHANCEMENT FEE 502-0000-43611 0 $5.00 $5.00 4/14/20 WEB4889 CREDIT
NATIONAL
MORTGAGE & LAND
COMPA
ECON
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $5.00
TOTALS:$942.50 $942.50
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED
DATE STATUS REMARKS NOTES
1ST BLDG
COMPLETE (3WK)INTERWEST 1/27/2020 2/14/2020 2/17/2020 REVISIONS REQUIRED PC1 comments to be delivered via GSO Tracking #
547991454.
Printed: Wednesday, December 20, 2023 10:41:45 AM 3 of 6
Project Details
City of La Quinta
PROJECT NUMBER
BCPR2020-0004
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 3/10/2020 DUANE CLAYTON
1ST REVIEW
CORRECTION LIST - CITY
OF LA-QUINTA
59000 MADISON -
BCPR2020-0004 - PLAN
22 - 1ST REVIEW
CORRECTION LIST - CITY
OF LA-QUINTA.pdf
0
DOC 4/29/2020 DUANE CLAYTON
APPROVED -
ARCHITECTURAL
DRAWINGS
59000 MADISON
(BCPR2020-0004) -
APPROVED -
ARCHITECTURAL
DRAWINGS - PLANS 24
AND 22.pdf
1
DOC 4/30/2020 DUANE CLAYTON APPROVED - ENERGY
DOCUMENTS - PLAN 22
59000 MADISON
(BCPR2020-0004) -
APPROVED - ENERGY
DOCUMENTS - PLAN
22.pdf
1
BOND INFORMATION
1ST BLDG NS (3WK)DUANE
CLAYTON 1/24/2020 2/14/2020 3/10/2020 REVISIONS REQUIRED - SEE ATTACHMENTS FOR 1ST REVIEW
CORRECTION LIST.
1ST FIRE (2WK)KOHL
HETRICK 1/24/2020 2/7/2020 2/18/2020 NOT REQUIRED
1ST PLANNING
(2WK)
CARLOS
FLORES 1/24/2020 2/7/2020 2/6/2020 READY FOR APPROVAL
1ST PUBLIC WORKS
(2WK)AMY YU 1/24/2020 2/7/2020 2/6/2020 READY FOR APPROVAL FOOTPRINT NOT CHANGED PER NOLAN
2ND BLDG
COMPLETE (2WK)INTERWEST 4/14/2020 4/28/2020 4/22/2020 APPROVED DIGITAL RESUBMITTAL. PLEASE SEE 2ND
SUBMITTAL DOCUMENTS IN ATTACHMENTS.
2ND BLDG NS (2WK)DUANE
CLAYTON 4/14/2020 4/28/2020 4/23/2020 APPROVED - SEE APPROVED PLAN AND DOCUMENTS IN
ATTACHMENTS.
Printed: Wednesday, December 20, 2023 10:41:45 AM 4 of 6
Project Details
City of La Quinta
PROJECT NUMBER
BCPR2020-0004
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 4/30/2020 DUANE CLAYTON
APPROVED -
STRUCTURAL
CALCULATIONS - PLAN
22
59000 MADISON
(BCPR2020-0004) -
APPROVED -
STRUCTURAL
CALCULATIONS - PLAN
22.pdf
1
DOC 4/30/2020 DUANE CLAYTON APPROVED - TRUSS
PACKAGE - PLAN 22
59000 MADISON
(BCPR2020-0004) -
APPROVED - TRUSS
PACKAGE - PLAN 22.pdf
1
DOC 4/14/2020 EtrakitContractor 2ND SUBMITTAL - TITLE
24 Plan 22 T-24 Calcs.pdf 1
DOC 4/14/2020 EtrakitContractor 2ND SUBMITTAL - STR
CALCS Plan 22 Str calcs.pdf 1
DOC 4/14/2020 EtrakitContractor 2ND SUBMITTAL - ARC
RESPONSE
Plan 22 Arch
Response.pdf 1
DOC 4/14/2020 EtrakitContractor 2ND SUBMITTAL - STR
RESPONSE
Plan 22 Str
Response.pdf 1
DOC 4/14/2020 EtrakitContractor 2ND SUBMITTAL - PLAN
SET
Plan 22_2nd Submittal
Set 3-27-20.pdf 1
DOC 4/14/2020 EtrakitContractor 2ND SUBMITTAL -
TRUSS CALCS Plan 22 Trusses.pdf 1
DOC 2/17/2020 INTERWEST
La Quinta - 202000968;
BCPP2020-0004 -
Invoice 57376.pdf
La Quinta - 202000968;
BCPP2020-0004 -
Invoice 57376.pdf
0
DOC 3/5/2020 INTERWEST 202000967 (BCPP2020-
0004) - PC1.docx
202000967 (BCPP2020-
0004) - PC1.docx 0
DOC 4/22/2020 INTERWEST 202000967 (BCPP2020-
004) PCF.docx
202000967 (BCPP2020-
004) PCF.docx 0
Printed: Wednesday, December 20, 2023 10:41:45 AM 5 of 6
Project Details
City of La Quinta
PROJECT NUMBER
BCPR2020-0004
ATTACHMENTS
Attachment Type CREATED OWNER DESCRIPTION PATHNAME SUBDIR ETRAKIT ENABLED
DOC 4/22/2020 INTERWEST
La Quinta - 202000967;
BCPP2020-0003 -
Invoice 59286.pdf
La Quinta - 202000967;
BCPP2020-0003 -
Invoice 59286.pdf
0
Printed: Wednesday, December 20, 2023 10:41:45 AM 6 of 6
Project Details
City of La Quinta
PROJECT NUMBER
BCPR2020-0004
INTERWEST C O N S U L T I N G G R O U P
Remit to:
Interwest Consulting Group
P.O. Box 18330
Boulder, CO 80308
Direct questions to:
Malia Aipia Powers (916) 512-6812
maipiapowers@interwestgrp.com
Invoice No.:57376
Invoice Date:2/17/2020
Jurisdiction No.:BCPP2020-0004
Interwest Job No.:202000968
Residential - Andalusia Country Club - Plan 26
59000 Madison
Professional Services for the Period February 1 through February 17, 2020
Bill to:
City of La Quinta
Attention James "JW" Wiatrak, Building Official
78-495 Calle Tampico
La Quinta, CA 92253
Project Hours Total
Invoice Total 2 $225.00
Person Title Week End Hours Rate Total
Bryan Montes Plan Check Engineer 2/14/2020 1 $125.00 $125.00
Adrienne Peterson ICC Certified Plans
Examiner
2/14/2020 1 $100.00 $100.00
Labor 2 $225.00
BUILDING ENERGY ANALYSIS REPORT
PROJECT:
Project Designer:
Report Prepared by:
Job Number:
Date:
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2019 Building Energy Efficiency Standards.
This program developed by EnergySoft Software – www.energysoft.com.
74991 JONI DR #9
GLS ARCHITECTURE GROUP INC.
PALM DESERT, CA 92260
760 340.3528
59000 MADISON ANDALUSIA C.C.
PLAN # 22
LA QUINTA, CA 92253
title24ofthedesert@gmail.com
TITLE 24 OF THE DESERT SERVICES INC.
760 278.1840,
20 - GLS /001 - 004 - 2R
3/18/2020
04/23/2020
TABLE OF CONTENTS
Form MF-1R Mandatory Measures Summary
HVAC System Heating and Cooling Loads Summary
Cover Page
Table of Contents
Form CF1R-PRF-01-E Certificate of Compliance
Form RMS-1 Residential Measures Summary
21
25
1
2
3
19
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:PLAN 22 ANDALUSIA Calculation Date/Time:2020-03-18T13:49:55-07:00 (Page 1 of 16)
Calculation Description:Title 24 Analysis Input File Name:2R - 004 - ANDALUSIA - PLAN 22 65 LOTS.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.100
Schema Version: rev 20190401
Report Generated: 2020-03-18 13:52:58
GENERAL INFORMATION
01 Project Name PLAN 22 ANDALUSIA
02 Run Title Title 24 Analysis
03 Project Location 59000 MADISON ANDALUSIA C.C.
04 City LA QUINTA 05 Standards Version 2019
06 Zip code 92253 07 Software Version EnergyPro 8.0
08 Climate Zone 15 09 Front Orientation (deg/ Cardinal)AllOrientations
10 Building Type SingleFamily 11 Number of Dwelling Units 1
12 Project Scope NewConstruction 13 Number of Bedrooms 4
14 New Cond. Floor Area (ft
2)0 15 Number of Stories 1
16 Existing Cond. Floor Area (ft
2)n/a 17 Fenestration Average U-factor 0.29
18 Total Cond. Floor Area (ft
2)3560 19 Glazing Percentage (%)23.93%
20 ADU Bedroom Count 0 21 ADU Conditioned Floor Area 0
COMPLIANCE RESULTS
01 Building Complies with Computer Performance
02 This building incorporates features that require field testing and/or verification by a certified HERS rater under the supervision of a CEC-approved HERS provider.
03 This building incorporates one or more Special Features shown below
220-P010011795B-000-000-0000000-0000 2020-03-18 14:21:54 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:PLAN 22 ANDALUSIA Calculation Date/Time:2020-03-18T13:49:55-07:00 (Page 2 of 16)
Calculation Description:Title 24 Analysis Input File Name:2R - 004 - ANDALUSIA - PLAN 22 65 LOTS.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.100
Schema Version: rev 20190401
Report Generated: 2020-03-18 13:52:58
ENERGY DESIGN RATING
Energy Design Ratings
Efficiency¹ (EDR)Total² (EDR)Efficiency¹ (EDR)Total² (EDR)
Standard Design 46.8 23.2
Proposed Designs
North Facing 45.5 21.8 1.3 1.4
East Facing 46.7 23 0.1 0.2
South Facing 42.9 19.2 3.9 4
West Facing 45.6 22 1.2 1.2
RESULT:3:COMPLIES
¹ Efficiency EDR includes improvements to the building envelope and more efficient equipment
² Total EDR includes efficiency and demand response measures such as photovoltaic (PV) systems and batteries
³ Building complies when efficiency and total compliance margins are greater than or equal to zero
•Standard Design PV Capacity: 6.54 kWdc
•Proposed PV Capacity Scaling: North (6.54 kWdc) East (6.54 kWdc) South (6.54 kWdc) West (6.54 kWdc)
220-P010011795B-000-000-0000000-0000 2020-03-18 14:21:54 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:PLAN 22 ANDALUSIA Calculation Date/Time:2020-03-18T13:49:55-07:00 (Page 3 of 16)
Calculation Description:Title 24 Analysis Input File Name:2R - 004 - ANDALUSIA - PLAN 22 65 LOTS.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.100
Schema Version: rev 20190401
Report Generated: 2020-03-18 13:52:58
ENERGY USE SUMMARY
Energy Use (kTDV/ft
2-yr)Standard Design Proposed Design Compliance Margin Percent Improvement
Space Heating 1.88 2.41 -0.53 -28.2
Space Cooling 85.65 80.05 5.6 6.5
IAQ Ventilation 2.28 2.28 0 0
Water Heating 5.99 7.23 -1.24 -20.7
Self Utilization Credit n/a 0 0 n/a
North Facing Compliance Total 95.8 91.97 3.83 4
Space Heating 1.88 3.52 -1.64 -87.2
Space Cooling 85.65 82.47 3.18 3.7
IAQ Ventilation 2.28 2.28 0 0
Water Heating 5.99 7.23 -1.24 -20.7
Self Utilization Credit n/a 0 0 n/a
East Facing Compliance Total 95.8 95.5 0.3 0.3
Space Heating 1.88 2.78 -0.9 -47.9
Space Cooling 85.65 72.46 13.19 15.4
IAQ Ventilation 2.28 2.28 0 0
Water Heating 5.99 7.23 -1.24 -20.7
Self Utilization Credit n/a 0 0 n/a
South Facing Compliance Total 95.8 84.75 11.05 11.5
Space Heating 1.88 2.24 -0.36 -19.1
Space Cooling 85.65 80.73 4.92 5.7
IAQ Ventilation 2.28 2.28 0 0
Water Heating 5.99 7.23 -1.24 -20.7
Self Utilization Credit n/a 0 0 n/a
West Facing Compliance Total 95.8 92.48 3.32 3.5
REQUIRED PV SYSTEMS
01 02 03 04 05 06 07 08 09 10 11
220-P010011795B-000-000-0000000-0000 2020-03-18 14:21:54 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:PLAN 22 ANDALUSIA Calculation Date/Time:2020-03-18T13:49:55-07:00 (Page 4 of 16)
Calculation Description:Title 24 Analysis Input File Name:2R - 004 - ANDALUSIA - PLAN 22 65 LOTS.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.100
Schema Version: rev 20190401
Report Generated: 2020-03-18 13:52:58
DC System Size
(kWdc)Exception Module Type Array Type Power Electronics CFI Azimuth
(deg)
Tilt
Input
Array Angle
(deg)Tilt: (x in 12)
Inverter Eff.
(%)
6.54 NA Standard Fixed (roof
mount)none true n/a n/a n/a n/a 96
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
•PV System: 6.54 kWdc
•Insulation below roof deck
•Window overhangs and/or fins
HERS FEATURE SUMMARY
The following is a summary of the features that must be field-verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional
detail is provided in the buildng tables below. Registered CF2Rs and CF3Rs are required to be completed in the HERS Registry
Building-level Verifications:
•Quality insulation installation (QII)
•Indoor air quality ventilation
Cooling System Verifications:
•Minimum Airflow
•Verified EER
•Verified SEER
•Verified Refrigerant Charge
•Fan Efficacy Watts/CFM
Heating System Verifications:
•Verified HSPF
•Verified heat pump rated heating capacity
HVAC Distribution System Verifications:
•Duct leakage testing
Domestic Hot Water System Verifications:
•-- None --
BUILDING - FEATURES INFORMATION
01 02 03 04 05 06 07
Project Name Conditioned Floor Area (ft
2)Number of Dwelling
Units Number of Bedrooms Number of Zones
Number of Ventilation
Cooling Systems
Number of Water
Heating Systems
PLAN 22 ANDALUSIA 3560 1 4 4 0 1
220-P010011795B-000-000-0000000-0000 2020-03-18 14:21:54 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:PLAN 22 ANDALUSIA Calculation Date/Time:2020-03-18T13:49:55-07:00 (Page 5 of 16)
Calculation Description:Title 24 Analysis Input File Name:2R - 004 - ANDALUSIA - PLAN 22 65 LOTS.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.100
Schema Version: rev 20190401
Report Generated: 2020-03-18 13:52:58
ZONE INFORMATION
01 02 03 04 05 06 07
Zone Name Zone Type HVAC System Name Zone Floor Area (ft
2)Avg. Ceiling Height Water Heating System 1 Water Heating System 2
Z1- 1225 Conditioned AC-1 -1 1225 10 DHW Sys 1 N/A
Z2 - 828 Conditioned AC-2 -2 828 10 DHW Sys 1 N/A
Z3 - 1063 Conditioned AC-3 -3 1063 10 DHW Sys 1 N/A
Z4 - 444 Conditioned AC-4 -4 444 10 DHW Sys 1 N/A
OPAQUE SURFACES
01 02 03 04 05 06 07 08
Name Zone Construction Azimuth Orientation Gross Area (ft
2)Window and Door
Area (ft2)
Tilt (deg)
N - 460 Z1- 1225 R-21 Wall 0 Front 460 23 90
E - 325 Z1- 1225 R-21 Wall 180 Back 325 161.844 90
S - 120 Z1- 1225 R-21 Wall 180 Back 120 48 90
W - 355 Z1- 1225 R-21 Wall 270 Right 355 256 90
N - 49 Z2 - 828 R-21 Wall 0 Front 49 0 90
S - 432 Z2 - 828 R-21 Wall 180 Back 432 71.5 90
W - 190 Z2 - 828 R-21 Wall 270 Right 264 96 90
N - 422 Z3 - 1063 R-21 Wall 0 Front 422 96.46 90
E - 40 Z3 - 1063 R-21 Wall 90 Left 40 0 90
S - 373 Z3 - 1063 R-21 Wall 180 Back 373 36.999 90
W - 165 Z3 - 1063 R-21 Wall 270 Right 165 22 90
N - 235 Z4 - 444 R-21 Wall 0 Front 235 39.996 90
W - 65 Z4 - 444 R-21 Wall 270 Right 65 24 90
1225 Z1- 1225 R-38 + R-21 --n/a n/a 1225 n/a n/a
828 Z2 - 828 R-38 + R-21 --n/a n/a 828 n/a n/a
1063 Z3 - 1063 R-38 + R-21 --n/a n/a 1063 n/a n/a
220-P010011795B-000-000-0000000-0000 2020-03-18 14:21:54 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:PLAN 22 ANDALUSIA Calculation Date/Time:2020-03-18T13:49:55-07:00 (Page 6 of 16)
Calculation Description:Title 24 Analysis Input File Name:2R - 004 - ANDALUSIA - PLAN 22 65 LOTS.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.100
Schema Version: rev 20190401
Report Generated: 2020-03-18 13:52:58
OPAQUE SURFACES
01 02 03 04 05 06 07 08
Name Zone Construction Azimuth Orientation Gross Area (ft
2)Window and Door
Area (ft2)
Tilt (deg)
444 Z4 - 444 R-38 + R-21 --n/a n/a 444 n/a n/a
ATTIC
01 02 03 04 05 06 07 08
Name Construction Type Roof Rise (x in 12)Roof Reflectance Roof Emittance Radiant Barrier Cool Roof
Attic Z1- 1225 Attic RoofZ1- 1225 Ventilated 4 0.1 0.85 No No
Attic Z2 - 828 Attic RoofZ2 - 828 Ventilated 4 0.1 0.85 No No
Attic Z3 - 1063 Attic RoofZ3 - 1063 Ventilated 4 0.1 0.85 No No
Attic Z4 - 444 Attic RoofZ4 - 444 Ventilated 4 0.1 0.85 No No
FENESTRATION / GLAZING
01 02 03 04 05 06 07 08 09 10 11 12 13 14
Name Type Surface Orientation Azimuth Width
(ft)
Height
(ft)Mult.Area
(ft2)U-factor U-factor
Source SHGC
SHGC
Sourc
e
Exterior
Shading
2020 - 1 Window N - 460 Front 0 1 4 0.29 NFRC 0.2 NFRC Bug Screen
2020 - 2 Window N - 460 Front 0 1 4 0.29 NFRC 0.2 NFRC Bug Screen
3050 - 4 Window N - 460 Front 0 3 5 1 15 0.29 NFRC 0.2 NFRC Bug Screen
80120 - 6 Window E - 325 Back 180 8 12 1 96 0.29 NFRC 0.2 NFRC Bug Screen
41070 - 7 Window E - 325 Back 180 4.83 7 1 33.84 0.29 NFRC 0.2 NFRC Bug Screen
4080 - 8 Window E - 325 Back 180 4 8 1 32 0.29 NFRC 0.2 NFRC Bug Screen
6080 - 12 Window S - 120 Back 180 6 8 1 48 0.29 NFRC 0.2 NFRC Bug Screen
(3) 2880 - 11 Window W - 355 Right 270 8 8 1 64 0.29 NFRC 0.2 NFRC Bug Screen
160120 - 10 Window W - 355 Right 270 16 12 1 192 0.29 NFRC 0.2 NFRC Bug Screen
3056 - 19 Window S - 432 Back 180 3 5.5 1 16.5 0.29 NFRC 0.2 NFRC Bug Screen
3056 - 18 Window S - 432 Back 180 3 5.5 1 16.5 0.29 NFRC 0.2 NFRC Bug Screen
3056 - 17 Window S - 432 Back 180 3 5.5 1 16.5 0.29 NFRC 0.2 NFRC Bug Screen
220-P010011795B-000-000-0000000-0000 2020-03-18 14:21:54 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:PLAN 22 ANDALUSIA Calculation Date/Time:2020-03-18T13:49:55-07:00 (Page 7 of 16)
Calculation Description:Title 24 Analysis Input File Name:2R - 004 - ANDALUSIA - PLAN 22 65 LOTS.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.100
Schema Version: rev 20190401
Report Generated: 2020-03-18 13:52:58
FENESTRATION / GLAZING
01 02 03 04 05 06 07 08 09 10 11 12 13 14
Name Type Surface Orientation Azimuth Width
(ft)
Height
(ft)Mult.Area
(ft2)U-factor U-factor
Source SHGC
SHGC
Sourc
e
Exterior
Shading
2056 - 16 Window S - 432 Back 180 2 5.5 1 11 0.29 NFRC 0.2 NFRC Bug Screen
2056 - 15 Window S - 432 Back 180 2 5.5 1 11 0.29 NFRC 0.2 NFRC Bug Screen
12080 - 14 Window W - 190 Right 270 12 8 1 96 0.29 NFRC 0.2 NFRC Bug Screen
3056 - 13 Window N - 422 Front 0 11 10 0 16.5 0.29 NFRC 0.2 NFRC Bug Screen
6080 - 21 Window N - 422 Front 0 11 10 0 47.96 0.29 NFRC 0.2 NFRC Bug Screen
5056 - 22 Window N - 422 Front 0 1 27.5 0.29 NFRC 0.2 NFRC Bug Screen
1630 - 23 Window N - 422 Front 0 1 4.5 0.29 NFRC 0.2 NFRC Bug Screen
1630 - 31 Window S - 373 Back 180 1.5 3 1 4.5 0.29 NFRC 0.2 NFRC Bug Screen
1630 - 30 Window S - 373 Back 180 1.5 3 1 4.5 0.29 NFRC 0.2 NFRC Bug Screen
1630 - 29 Window S - 373 Back 180 1.5 3 1 4.5 0.29 NFRC 0.2 NFRC Bug Screen
1630 - 28 Window S - 373 Back 180 1.5 3 1 4.5 0.29 NFRC 0.2 NFRC Bug Screen
1630 - 27 Window S - 373 Back 180 1.5 3 1 4.5 0.29 NFRC 0.2 NFRC Bug Screen
1630 - 26 Window S - 373 Back 180 1.5 3 1 4.5 0.29 NFRC 0.2 NFRC Bug Screen
2050 - 20 Window S - 373 Back 180 1.5 3 2 10 0.29 NFRC 0.2 NFRC Bug Screen
2056 - 25 Window W - 165 Right 270 2 5.5 1 11 0.29 NFRC 0.2 NFRC Bug Screen
2056 - 25 2 Window W - 165 Right 270 2 5.5 1 11 0.29 NFRC 0.2 NFRC Bug Screen
5056 - 33 Window N - 235 Front 0 1 27.5 0.29 NFRC 0.2 NFRC Bug Screen
2056 - 32 Window N - 235 Front 0 2 5.5 1 12.5 0.29 NFRC 0.2 NFRC Bug Screen
OPAQUE DOORS
01 02 03 04
Name Side of Building Area (ft
2)U-factor
3080 W - 65 24 0.5
220-P010011795B-000-000-0000000-0000 2020-03-18 14:21:54 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:PLAN 22 ANDALUSIA Calculation Date/Time:2020-03-18T13:49:55-07:00 (Page 8 of 16)
Calculation Description:Title 24 Analysis Input File Name:2R - 004 - ANDALUSIA - PLAN 22 65 LOTS.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.100
Schema Version: rev 20190401
Report Generated: 2020-03-18 13:52:58
OVERHANGS AND FINS
01 02 03 04 05 06 07 08 09 10 11 12 13 14
Window
Overhang Left Fin Right Fin
Depth Dist Up
Left
Extent
Right
Extent Flap Ht.Depth Top Up Dist L Bot Up Depth Top Up Dist R Bot Up
3050 - 4 15 1.5 6 2 0 0 0 0 0 0 0 0 0
80120 - 6 10 1.5 6 2 0 0 0 0 0 0 0 0 0
41070 - 7 1 1 2 2 0 0 0 0 0 0 0 0 0
4080 - 8 4 1.5 3.5 3.5 0 0 0 0 0 0 0 0 0
6080 - 12 21 1.5 4 2 0 0 0 0 0 0 0 0 0
(3) 2880 - 11 1 1 2 2 0 0 0 0 0 0 0 0 0
160120 - 10 15 1.5 6 2 0 0 0 0 0 0 0 0 0
3056 - 19 1 1 2 2 0 0 0 0 0 0 0 0 0
3056 - 18 1 1 2 2 0 0 0 0 0 0 0 0 0
3056 - 17 1 1 2 2 0 0 0 0 0 0 0 0 0
2056 - 16 1 1 2 2 0 0 0 0 0 0 0 0 0
2056 - 15 1 1 2 2 0 0 0 0 0 0 0 0 0
12080 - 14 8 1.5 3.5 3.5 1 0 0 0 0 0 0 0 0
3056 - 13 1 1 2 2 0 0 0 0 0 0 0 0 0
6080 - 21 1 1 2 2 0 0 0 0 0 0 0 0 0
1630 - 31 1 1 2 2 0 0 0 0 0 0 0 0 0
1630 - 30 1 1 2 2 0 0 0 0 0 0 0 0 0
220-P010011795B-000-000-0000000-0000 2020-03-18 14:21:54 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:PLAN 22 ANDALUSIA Calculation Date/Time:2020-03-18T13:49:55-07:00 (Page 9 of 16)
Calculation Description:Title 24 Analysis Input File Name:2R - 004 - ANDALUSIA - PLAN 22 65 LOTS.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.100
Schema Version: rev 20190401
Report Generated: 2020-03-18 13:52:58
OVERHANGS AND FINS
01 02 03 04 05 06 07 08 09 10 11 12 13 14
Window
Overhang Left Fin Right Fin
Depth Dist Up
Left
Extent
Right
Extent Flap Ht.Depth Top Up Dist L Bot Up Depth Top Up Dist R Bot Up
1630 - 29 1 1 2 2 0 0 0 0 0 0 0 0 0
1630 - 28 1 1 2 2 0 0 0 0 0 0 0 0 0
1630 - 27 1 1 2 2 0 0 0 0 0 0 0 0 0
1630 - 26 1 1 2 2 0 0 0 0 0 0 0 0 0
2050 - 20 1 1 2 2 0 0 0 0 0 0 0 0 0
2056 - 25 1 1 2 2 0 0 0 0 0 0 0 0 0
2056 - 25 2 1 1 2 2 0 0 0 0 0 0 0 0 0
2056 - 32 6 1 2 2 0 0 0 0 0 0 0 0 0
SLAB FLOORS
01 02 03 04 05 06 07
Name Zone Area (ft2)Perimeter (ft)Edge Insul. R-value and Depth Carpeted Fraction Heated
1225 2 Z1- 1225 1225 0.1 None 80%No
828 2 Z2 - 828 828 0.1 None 80%No
1063 2 Z3 - 1063 1063 0.1 None 80%No
444 2 Z4 - 444 444 0.1 None 80%No
220-P010011795B-000-000-0000000-0000 2020-03-18 14:21:54 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:PLAN 22 ANDALUSIA Calculation Date/Time:2020-03-18T13:49:55-07:00 (Page 10 of 16)
Calculation Description:Title 24 Analysis Input File Name:2R - 004 - ANDALUSIA - PLAN 22 65 LOTS.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.100
Schema Version: rev 20190401
Report Generated: 2020-03-18 13:52:58
OPAQUE SURFACE CONSTRUCTIONS
01 02 03 04 05 06 07 08
Construction Name Surface Type Construction Type Framing Total Cavity
R-value
Interior / Exterior
Continuous
R-value
U-factor Assembly Layers
R-21 Wall Exterior Walls Wood Framed Wall 2x6 @ 16 in. O. C.R-21 None / None 0.069
Inside Finish: Gypsum Board
Cavity / Frame: R-21 / 2x6
Exterior Finish: 3 Coat Stucco
R-0 Wall Interior Walls Wood Framed Wall 2x4 @ 16 in. O. C.R-0 None / None 0.277
Inside Finish: Gypsum Board
Cavity / Frame: no insul. / 2x4
Other Side Finish: Gypsum Board
R-21 Wall1 Interior Walls Wood Framed Wall 2x6 @ 16 in. O. C.R-21 None / None 0.064
Inside Finish: Gypsum Board
Cavity / Frame: R-21 / 2x6
Other Side Finish: Gypsum Board
Attic RoofZ1- 1225 Attic Roofs
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-21 None / None 0.055
Roofing: Light Roof (Asphalt Shingle)
Roof Deck: Wood
Siding/sheathing/decking
Cavity / Frame: R-13.0 / 2x4
Around Roof Joists: R-8.0 insul.
Attic RoofZ2 - 828 Attic Roofs
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-21 None / None 0.055
Roofing: Light Roof (Asphalt Shingle)
Roof Deck: Wood
Siding/sheathing/decking
Cavity / Frame: R-13.0 / 2x4
Around Roof Joists: R-8.0 insul.
Attic RoofZ3 - 1063 Attic Roofs
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-21 None / None 0.055
Roofing: Light Roof (Asphalt Shingle)
Roof Deck: Wood
Siding/sheathing/decking
Cavity / Frame: R-13.0 / 2x4
Around Roof Joists: R-8.0 insul.
Attic RoofZ4 - 444 Attic Roofs
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-21 None / None 0.055
Roofing: Light Roof (Asphalt Shingle)
Roof Deck: Wood
Siding/sheathing/decking
Cavity / Frame: R-13.0 / 2x4
Around Roof Joists: R-8.0 insul.
220-P010011795B-000-000-0000000-0000 2020-03-18 14:21:54 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:PLAN 22 ANDALUSIA Calculation Date/Time:2020-03-18T13:49:55-07:00 (Page 11 of 16)
Calculation Description:Title 24 Analysis Input File Name:2R - 004 - ANDALUSIA - PLAN 22 65 LOTS.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.100
Schema Version: rev 20190401
Report Generated: 2020-03-18 13:52:58
OPAQUE SURFACE CONSTRUCTIONS
01 02 03 04 05 06 07 08
Construction Name Surface Type Construction Type Framing Total Cavity
R-value
Interior / Exterior
Continuous
R-value
U-factor Assembly Layers
R-38 + R-21 --
Ceilings (below
attic)
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-38 None / None 0.025
Over Ceiling Joists: R-28.9 insul.
Cavity / Frame: R-9.1 / 2x4
Inside Finish: Gypsum Board
BUILDING ENVELOPE - HERS VERIFICATION
01 02 03 04
Quality Insulation Installation (QII)Quality Installation of Spray Foam Insulation Building Envelope Air Leakage CFM50
Required Not Required Not Required n/a
WATER HEATING SYSTEMS
01 02 03 04 05 06 07
Name System Type Distribution Type Water Heater Name (#)Solar Fraction (%)Compact Distribution HERS Verification
DHW Sys 1
Domestic Hot Water
(DHW)
Standard Distribution
System DHW Heater 1 (2)0 None n/a
WATER HEATERS
01 02 03 04 05 06 07 08 09 10 11 12
Name
Heating
Element
Type
Tank Type
#
Units
Tank
Vol.
(gal)
Energy
Factor or
Efficiency
Input Rating
or Pilot
Tank
Insulation
R-value
(Int/Ext)
Standby Loss
or Recovery
Eff.
1st Hr. Rating
or Flow Rate
NEEA Heat Pump
Brand or Model /
Other
Tank Location or
Ambient Condition
DHW Heater 1 Natural Gas
Consumer
Instantaneous 2 0 0.92-UEF 200000-
Btu/Hr 0 n/a n/a n/a n/a
220-P010011795B-000-000-0000000-0000 2020-03-18 14:21:54 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:PLAN 22 ANDALUSIA Calculation Date/Time:2020-03-18T13:49:55-07:00 (Page 12 of 16)
Calculation Description:Title 24 Analysis Input File Name:2R - 004 - ANDALUSIA - PLAN 22 65 LOTS.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.100
Schema Version: rev 20190401
Report Generated: 2020-03-18 13:52:58
WATER HEATING - HERS VERIFICATION
01 02 03 04 05 06 07 08
Name Pipe Insulation Parallel Piping Compact Distribution
Compact Distribution
Type Recirculation Control
Central DHW
Distribution
Shower Drain Water
Heat Recovery
DHW Sys 1 - 1/2 Not Required Not Required Not Required None Not Required Not Required Not Required
SPACE CONDITIONING SYSTEMS
01 02 03 04 05 06 07 08 09
Name System Type
Heating Unit
Name
Cooling Unit
Name Fan Name Distribution Name
Required
Thermostat Type
Heating
Equipment Count
Cooling
Equipment Count
AC-1 -1
Heat pump
heating cooling
Heat Pump System
1
Heat Pump System
1 HVAC Fan 1
Air Distribution
System 1
Setback 1 1
AC-2 -2
Heat pump
heating cooling
Heat Pump System
2
Heat Pump System
2 HVAC Fan 2
Air Distribution
System 2
Setback 1 1
AC-3 -3
Heat pump
heating cooling
Heat Pump System
3
Heat Pump System
3 HVAC Fan 3
Air Distribution
System 3
Setback 1 1
AC-4 -4
Heat pump
heating cooling
Heat Pump System
4
Heat Pump System
4 HVAC Fan 4
Air Distribution
System 4
Setback 1 1
HVAC - HEAT PUMPS
01 02 03 04 05 06 07 08 09 10 11
Name System Type Number of Units
Heating Cooling Zonally
Controlled
Compressor
Type HERS Verification
HSPF/COP Cap 47 Cap 17 SEER EER
Heat Pump System 1 Central split HP 1 9.5 60000 45000 16 13 Not Zonal
Single
Speed
Heat Pump System
1-hers-htpump
Heat Pump System 2 Central split HP 1 9.5 36000 27000 16 13 Not Zonal
Single
Speed
Heat Pump System
2-hers-htpump
Heat Pump System 3 Central split HP 1 9.5 36000 27000 16 13 Not Zonal
Single
Speed
Heat Pump System
3-hers-htpump
220-P010011795B-000-000-0000000-0000 2020-03-18 14:21:54 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:PLAN 22 ANDALUSIA Calculation Date/Time:2020-03-18T13:49:55-07:00 (Page 13 of 16)
Calculation Description:Title 24 Analysis Input File Name:2R - 004 - ANDALUSIA - PLAN 22 65 LOTS.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.100
Schema Version: rev 20190401
Report Generated: 2020-03-18 13:52:58
HVAC - HEAT PUMPS
01 02 03 04 05 06 07 08 09 10 11
Name System Type Number of Units
Heating Cooling Zonally
Controlled
Compressor
Type HERS Verification
HSPF/COP Cap 47 Cap 17 SEER EER
Heat Pump System 4 Central split HP 1 9.5 24000 18000 16 13 Not Zonal
Single
Speed
Heat Pump System
4-hers-htpump
HVAC HEAT PUMPS - HERS VERIFICATION
01 02 03 04 05 06 07 08 09
Name Verified Airflow Airflow Target Verified EER Verified SEER
Verified Refrigerant
Charge Verified HSPF
Verified Heating
Cap 47
Verified Heating
Cap 17
Heat Pump System
1-hers-htpump Required 360 Required Required Yes Yes Yes Yes
Heat Pump System
2-hers-htpump Required 360 Required Required Yes Yes Yes Yes
Heat Pump System
3-hers-htpump Required 360 Required Required Yes Yes Yes Yes
Heat Pump System
4-hers-htpump Required 360 Required Required Yes Yes Yes Yes
HVAC - DISTRIBUTION SYSTEMS
01 02 03 04 05 06 07 08 09 10 11 12
Duct Ins.
R-value Duct Location Surface Area
Name Type Design Type Supply Return Supply Return Supply Return Bypass
Duct Duct Leakage HERS Verification
Air Distribution
System 1
Unconditioned attic Non-Verified R-8 R-8 Attic Attic n/a n/a
No
Bypass
Duct
Sealed and
Tested
Air Distribution System
1-hers-dist
Air Distribution
System 2
Unconditioned attic Non-Verified R-8 R-8 Attic Attic n/a n/a
No
Bypass
Duct
Sealed and
Tested
Air Distribution System
2-hers-dist
220-P010011795B-000-000-0000000-0000 2020-03-18 14:21:54 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:PLAN 22 ANDALUSIA Calculation Date/Time:2020-03-18T13:49:55-07:00 (Page 14 of 16)
Calculation Description:Title 24 Analysis Input File Name:2R - 004 - ANDALUSIA - PLAN 22 65 LOTS.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.100
Schema Version: rev 20190401
Report Generated: 2020-03-18 13:52:58
HVAC - DISTRIBUTION SYSTEMS
01 02 03 04 05 06 07 08 09 10 11 12
Duct Ins.
R-value Duct Location Surface Area
Name Type Design Type Supply Return Supply Return Supply Return Bypass
Duct Duct Leakage HERS Verification
Air Distribution
System 3
Unconditioned attic Non-Verified R-8 R-8 Attic Attic n/a n/a
No
Bypass
Duct
Sealed and
Tested
Air Distribution System
3-hers-dist
Air Distribution
System 4
Unconditioned attic Non-Verified R-8 R-8 Attic Attic n/a n/a
No
Bypass
Duct
Sealed and
Tested
Air Distribution System
4-hers-dist
HVAC DISTRIBUTION - HERS VERIFICATION
01 02 03 04 05 06 07 08 09
Name Duct Leakage
Verification
Duct leakage
target (%)
Verified Duct
Location
Verified Duct
Design Buried Ducts
Deeply Buried
Ducts
Low-leakage Air
Handler
Low Leakage
Ducts Entirely in
Conditioned
Space
Air Distribution
System 1-hers-dist
Yes 5 Not Required Not Required Not Required Credit not taken Not Required No
Air Distribution
System 2-hers-dist
Yes 5 Not Required Not Required Not Required Credit not taken Not Required No
Air Distribution
System 3-hers-dist
Yes 5 Not Required Not Required Not Required Credit not taken Not Required No
Air Distribution
System 4-hers-dist
Yes 5 Not Required Not Required Not Required Credit not taken Not Required No
220-P010011795B-000-000-0000000-0000 2020-03-18 14:21:54 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:PLAN 22 ANDALUSIA Calculation Date/Time:2020-03-18T13:49:55-07:00 (Page 15 of 16)
Calculation Description:Title 24 Analysis Input File Name:2R - 004 - ANDALUSIA - PLAN 22 65 LOTS.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.100
Schema Version: rev 20190401
Report Generated: 2020-03-18 13:52:58
HVAC - FAN SYSTEMS
01 02 03 04
Name Type Fan Power (Watts/CFM)Name
HVAC Fan 1 HVAC Fan 0.5 HVAC Fan 1-hers-fan
HVAC Fan 2 HVAC Fan 0.5 HVAC Fan 2-hers-fan
HVAC Fan 3 HVAC Fan 0.5 HVAC Fan 3-hers-fan
HVAC Fan 4 HVAC Fan 0.5 HVAC Fan 4-hers-fan
HVAC FAN SYSTEMS - HERS VERIFICATION
01 02 03
Name Verified Fan Watt Draw Required Fan Efficiency (Watts/CFM)
HVAC Fan 1-hers-fan Required 0.5
HVAC Fan 2-hers-fan Required 0.5
HVAC Fan 3-hers-fan Required 0.5
HVAC Fan 4-hers-fan Required 0.5
IAQ (INDOOR AIR QUALITY) FANS
01 02 03 04 05 06
Dwelling Unit IAQ CFM IAQ Watts/CFM IAQ Fan Type IAQ Recovery Effectiveness (%)HERS Verification
SFam IAQVentRpt 138 0.25 Default 0 Yes
220-P010011795B-000-000-0000000-0000 2020-03-18 14:21:54 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:PLAN 22 ANDALUSIA Calculation Date/Time:2020-03-18T13:49:55-07:00 (Page 16 of 16)
Calculation Description:Title 24 Analysis Input File Name:2R - 004 - ANDALUSIA - PLAN 22 65 LOTS.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.100
Schema Version: rev 20190401
Report Generated: 2020-03-18 13:52:58
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:Documentation Author Signature:
Company:Signature Date:
Address:CEA/ HERS Certification Identification (If applicable):
City/State/Zip:Phone:
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1.I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance.
2.I certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations.
3.The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets,
calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
Responsible Designer Name:Responsible Designer Signature:
Company:Date Signed:
Address:License:
City/State/Zip:Phone:
Easy to Verify
at CalCERTS.com
ARMANDO CHAVEZ
TITLE 24 OF THE DESERT
74800 shirley #62
PALM DESERT, CA 92260
2020-03-18 14:21:19
N.A.
760-278-1840
Ruben Romero
GLS ARCHITECTURE GROUP INC
74491 JONI DR SUITE #9
Palm Desert, CA 92260
2020-03-18 14:21:54
N.A.
760-340-3528
Digitally signed by CalCERTS. This digital signature is provided in order to secure the content of this registered document, and in no way implies Registration
Provider responsibility for the accuracy of the information.
220-P010011795B-000-000-0000000-0000 2020-03-18 14:21:54 CalCERTS inc.
RESIDENTIAL MEASURES SUMMARY RMS-1
Project Name Building Type Single Family Addition Alone Date
Multi Family Existing+ Addition/Alteration
Project Address California Energy Climate Zone Total Cond. Floor Area Addition # of Units
INSULATION Area
Construction Type Cavity (ft2) Special Features Status
FENESTRATION Total Area: Glazing Percentage: New/Altered Average U-Factor:
Orientation Area(ft2) U-Fac SHGC Overhang Sidefins Exterior Shades Status
HVAC SYSTEMS
Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status
HVAC DISTRIBUTION Duct
Location Heating Cooling Duct Location R-Value Status
WATER HEATING
Qty. Type Gallons Min. Eff Distribution Status
PLAN # 22
59000 MADISON ANDALUSIA C.C. LA QUINTA
0.20
Opaque Door
3/18/2020
4
CA Climate Zone 15 3,560 1
Wood Framed
Roof
Slab
Wall
Demising
Door
Wood Framed Attic
Unheated Slab-on-Grade
Wood Framed
3,560
3,560
2,943
220
24
- no insulation -
R 38
- no insulation -
R 21
- no insulation -New
New
New
New
New
Add=R-21.0
Perim = 0'
n/a
Front (N)
Front (N)
Rear (S)
Rear (S)
Rear (S)
Rear (S)
Right (W)
Right (W)
Right (W)
Front (N)
86.0
67.5
15.0
96.0
142.3
32.0
48.0
96.0
192.0
64.5
0.290
0.290
0.290
0.290
0.290
0.290
0.290
0.290
0.290
0.290
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
21.0
1.0
none
15.0
10.0
1.0
4.0
8.0
15.0
1.0
none
none
none
none
none
none
none
none
none
none
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
New
New
New
New
New
New
New
New
New
New
16.0 SEER
Split Heat Pump
1
1
1
Split Heat Pump
Split Heat Pump
Split Heat Pump
Split Heat Pump
Split Heat Pump
9.50 HSPF
9.50 HSPF
9.50 HSPF
New
New
New16.0 SEER
16.0 SEER
Setback
Setback
Setback
New
Attic
AC-3 -
AC-1 -
AC-2 -
Ducted
Ducted
Ducted
Ducted
Ducted
Ducted
New
New
Attic
Attic
8.0
8.0
8.0
Standard2Small Instantaneous Gas 0.920 New
ID: 20 - GLS /001 - 004 - 2R Page 19 of 28EnergyPro 8.0 by EnergySoft SoftwareUser Number: 20648
Front (N)12.5 0.290 0.20 6.0 none N/A New
852 23.9%0.29
RESIDENTIAL MEASURES SUMMARY RMS-1
Project Name Building Type Single Family Addition Alone Date
Multi Family Existing+ Addition/Alteration
Project Address California Energy Climate Zone Total Cond. Floor Area Addition # of Units
INSULATION Area
Construction Type Cavity (ft2) Special Features Status
FENESTRATION Total Area: Glazing Percentage: New/Altered Average U-Factor:
Orientation Area(ft2) U-Fac SHGC Overhang Sidefins Exterior Shades Status
HVAC SYSTEMS
Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status
HVAC DISTRIBUTION Duct
Location Heating Cooling Duct Location R-Value Status
WATER HEATING
Qty. Type Gallons Min. Eff Distribution Status
PLAN # 22
59000 MADISON ANDALUSIA C.C. LA QUINTA
3/18/2020
4
CA Climate Zone 15 3,560 1n/a
16.0 SEER1Split Heat Pump Split Heat Pump9.50 HSPF NewSetback
AtticAC-4 -DuctedDucted New8.0
ID: 20 - GLS /001 - 004 - 2R Page 20 of 28EnergyPro 8.0 by EnergySoft SoftwareUser Number: 20648
852 23.9%0.29
2019 Low-Rise Residential Mandatory Measures Summary
NOTE: Low-rise residential buildings subject to the Energy Standards must comply with all applicable mandatory measures, regardless of the compliance approach
used. Review the respective section for more information. *Exceptions may apply.
(Original 08/2019)
Building Envelope Measures:
§ 110.6(a)1:
Air Leakage. Manufactured fenestration, exterior doors, and exterior pet doors must limit air leakage to 0.3 cfm per square foot or less
when tested per NFRC-400, ASTM E283 or AAMA/WDMA/CSA 101/I.S.2/A440-2011.*
§ 110.6(a)5:Labeling. Fenestration products and exterior doors must have a label meeting the requirements of Section 10-111(a).
§ 110.6(b):
Field fabricated exterior doors and fenestration products must use U-factors and solar heat gain coefficient (SHGC) values from Tables
110.6-A, 110.6-B, or JA4.5 for exterior doors. They must be caulked and/or weather stripped.*
§ 110.7:
Air Leakage. All joints, penetrations, and other openings in the building envelope that are potential sources of air leakage must be caulked,
gasketed, or weather stripped.
§ 110.8(a):Insulation Certification by Manufacturers. Insulation must be certified by the Department of Consumer Affairs, Bureau of Household Goods
and Services (BHGS).
§ 110.8(g):Insulation Requirements for Heated Slab Floors. Heated slab floors must be insulated per the requirements of Section 110.8(g).
§ 110.8(i):
Roofing Products Solar Reflectance and Thermal Emittance. The thermal emittance and aged solar reflectance values of the roofing
material must meet the requirements of § 110.8(i) and be labeled per §10-113 when the installation of a cool roof is specified on the CF1R.
§ 110.8(j):Radiant Barrier. When required, radiant barriers must have an emittance of 0.05 or less and be certified to the Department of Consumer Affairs.
§ 150.0(a):
Ceiling and Rafter Roof Insulation. Minimum R-22 insulation in wood-frame ceiling; or the weighted average U-factor must not exceed 0.043.
Minimum R-19 or weighted average U-factor of 0.054 or less in a rafter roof alteration. Attic access doors must have permanently attached
insulation using adhesive or mechanical fasteners. The attic access must be gasketed to prevent air leakage. Insulation must be installed in
direct contact with a continuous roof or ceiling which is sealed to limit infiltration and exfiltration as specified in § 110.7, including but not limited
to placing insulation either above or below the roof deck or on top of a drywall ceiling.*
§ 150.0(b):Loose-fill Insulation. Loose fill insulation must meet the manufacturer’s required density for the labeled R-value.
§ 150.0(c):
Wall Insulation. Minimum R-13 insulation in 2x4 inch wood framing wall or have a U-factor of 0.102 or less, or R-20 in 2x6 inch wood framing or
have a U-factor of 0.071 or less, (R-19 in 2x6 or U-factor of 0.074 or less). Opaque non-framed assemblies must have an overall assembly U-
factor not exceeding 0.102, equivalent to an installed value of R-13 in a wood framed assembly. Masonry walls must meet Table 150.1-A or B.*
§ 150.0(d):Raised-floor Insulation. Minimum R-19 insulation in raised wood framed floor or 0.037 maximum U-factor.*
§ 150.0(f):
Slab Edge Insulation. Slab edge insulation must meet all of the following: have a water absorption rate, for the insulation material alone without
facings no greater than 0.3%; have a water vapor permeance no greater than 2.0 perm per inch; be protected from physical damage and UV
light deterioration; and, when installed as part of a heated slab floor, meet the requirements of § 110.8(g).
§ 150.0(g)1:
Vapor Retarder. In climate zones 1 through 16, the earth floor of unvented crawl space must be covered with a Class I or Class II vapor
retarder. This requirement also applies to controlled ventilation crawl space for buildings complying with the exception to § 150.0(d).
§ 150.0(g)2:
Vapor Retarder. In climate zones 14 and 16, a Class I or Class II vapor retarder must be installed on the conditioned space side of all
insulation in all exterior walls, vented attics, and unvented attics with air-permeable insulation.
§ 150.0(q):
Fenestration Products. Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors must have a
maximum U-factor of 0.58; or the weighted average U-factor of all fenestration must not exceed 0.58.*
Fireplaces, Decorative Gas Appliances, and Gas Log Measures:
§ 110.5(e)Pilot Light. Continuously burning pilot lights are not allowed for indoor and outdoor fireplaces.
§ 150.0(e)1:Closable Doors. Masonry or factory-built fireplaces must have a closable metal or glass door covering the entire opening of the firebox.
§ 150.0(e)2:
Combustion Intake. Masonry or factory-built fireplaces must have a combustion outside air intake, which is at least six square inches in area
and is equipped with a readily accessible, operable, and tight-fitting damper or combustion-air control device.*
§ 150.0(e)3:Flue Damper. Masonry or factory-built fireplaces must have a flue damper with a readily accessible control.*
Space Conditioning, Water Heating, and Plumbing System Measures:
§ 110.0-§ 110.3: Certification. Heating, ventilation and air conditioning (HVAC) equipment, water heaters, showerheads, faucets, and all other regulated
appliances must be certified by the manufacturer to the Energy Commission.*
§ 110.2(a):HVAC Efficiency. Equipment must meet the applicable efficiency requirements in Table 110.2-A through Table 110.2-K.*
§ 110.2(b):
Controls for Heat Pumps with Supplementary Electric Resistance Heaters. Heat pumps with supplementary electric resistance heaters
must have controls that prevent supplementary heater operation when the heating load can be met by the heat pump alone; and in which the
cut-on temperature for compression heating is higher than the cut-on temperature for supplementary heating, and the cut-off temperature for
compression heating is higher than the cut-off temperature for supplementary heating.*
§ 110.2(c):
Thermostats. All heating or cooling systems not controlled by a central energy management control system (EMCS) must have a
setback thermostat.*
§ 110.3(c)4:
Water Heating Recirculation Loops Serving Multiple Dwelling Units. Water heating recirculation loops serving multiple dwelling units must
meet the air release valve, backflow prevention, pump priming, pump isolation valve, and recirculation loop connection requirements of §
110.3(c)4.
§ 110.3(c)6:Isolation Valves. Instantaneous water heaters with an input rating greater than 6.8 kBTU per hour (2 kW) must have isolation valves with hose
bibbs or other fittings on both cold and hot water lines to allow for flushing the water heater when the valves are closed.
§ 110.5:
Pilot Lights. Continuously burning pilot lights are prohibited for natural gas: fan-type central furnaces; household cooking appliances (appli-
ances without an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt); and pool and spa heaters.*
§ 150.0(h)1:
Building Cooling and Heating Loads. Heating and/or cooling loads are calculated in accordance with the ASHRAE Handbook,
Equipment Volume, Applications Volume, and Fundamentals Volume; the SMACNA Residential Comfort System Installation Standards
Manual; or the ACCA Manual J using design conditions specified in § 150.0(h)2.
2019 Low-Rise Residential Mandatory Measures Summary
§ 150.0(h)3A:
Clearances. Air conditioner and heat pump outdoor condensing units must have a clearance of at least 5 feet from the outlet of any dryer vent.
§ 150.0(h)3B:
Liquid Line Drier. Air conditioners and heat pump systems must be equipped with liquid line filter driers if required, as specified by the
manufacturer’s instructions.
§ 150.0(j)1:
Storage Tank Insulation. Unfired hot water tanks, such as storage tanks and backup storage tanks for solar water-heating systems, must have
a minimum of R-12 external insulation or R-16 internal insulation where the internal insulation R-value is indicated on the exterior of the tank.
§ 150.0(j)2A:
Water Piping, Solar Water-heating System Piping, and Space Conditioning System Line Insulation. All domestic hot water piping must
be insulated as specified in Section 609.11 of the California Plumbing Code. In addition, the following piping conditions must have a minimum
insulation wall thickness of 1 inch or a minimum insulation R-value of 7.7: the first 5 feet of cold water pipes from the storage tank; all hot water
piping with a nominal diameter equal to or greater than 3/4 inch and less than 1 inch; all hot water piping with a nominal diameter less than 3/4
inch that is: associated with a domestic hot water recirculation system, from the heating source to storage tank or between tanks, buried below
grade, and from the heating source to kitchen fixtures.*
§ 150.0(j)3:Insulation Protection. Piping insulation must be protected from damage, including that due to sunlight, moisture, equipment maintenance, and
wind as required by Section 120.3(b). Insulation exposed to weather must be water retardant and protected from UV light (no adhesive tapes).
Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space must include, or be protected by, a
Class I or Class II vapor retarder. Pipe insulation buried below grade must be installed in a waterproof and non-crushable casing or sleeve.
§ 150.0(n)1:
Gas or Propane Water Heating Systems. Systems using gas or propane water heaters to serve individual dwelling units must include all of
the following: A dedicated 125 volt, 20 amp electrical receptacle that is connected to the electric panel with a 120/240 volt 3 conductor, 10
AWG copper branch circuit, within 3 feet from the water heater without obstruction. Both ends of the unused conductor must be labeled with the
word “spare” and be electrically isolated. Have a reserved single pole circuit breaker space in the electrical panel adjacent to the circuit breaker
for the branch circuit and labeled with the words “Future 240V Use”; a Category III or IV vent, or a Type B vent with straight pipe between the
outside termination and the space where the water heater is installed; a condensate drain that is no more than 2 inches higher than the base of
the water heater, and allows natural draining without pump assistance; and a gas supply line with a capacity of at least 200,000 Btu per hour.
§ 150.0(n)2:Recirculating Loops. Recirculating loops serving multiple dwelling units must meet the requirements of § 110.3(c)5.
§ 150.0(n)3:
Solar Water-heating Systems. Solar water-heating systems and collectors must be certified and rated by the Solar Rating and Certification
Corporation (SRCC), the International Association of Plumbing and Mechanical Officials, Research and Testing (IAPMO R&T), or by a listing
agency that is approved by the Executive Director.
Ducts and Fans Measures:
§ 110.8(d)3:
Ducts. Insulation installed on an existing space-conditioning duct must comply with California Mechanical Code (CMC) Section 604.0. If a
contractor installs the insulation, the contractor must certify to the customer in writing, that the insulation meets this requirement.
§ 150.0(m)1:
CMC Compliance. All air-distribution system ducts and plenums must meet the requirements of the CMC Section 601.0, 602.0, 603.0, 604.0,
605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition. Portions of supply-air and return-air
ducts and plenums must be insulated to a minimum installed level of R-6.0 or a minimum installed level of R-4.2 when ducts are entirely in
conditioned space as confirmed through field verification and diagnostic testing (RA3.1.4.3.8). Portions of the duct system completely exposed
and surrounded by directly conditioned space are not required to be insulated. Connections of metal ducts and inner core of flexible ducts must
be mechanically fastened. Openings must be sealed with mastic, tape, or other duct-closure system that meets the applicable requirements of
UL 181, UL 181A, or UL 181B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than
¼ inch, the combination of mastic and either mesh or tape must be used. Building cavities, support platforms for air handlers, and plenums
designed or constructed with materials other than sealed sheet metal, duct board or flexible duct must not be used to convey conditioned air.
Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms must not be compressed to cause
reductions in the cross-sectional area.*
§ 150.0(m)2:
Factory-Fabricated Duct Systems. Factory-fabricated duct systems must comply with applicable requirements for duct construction,
connections, and closures; joints and seams of duct systems and their components must not be sealed with cloth back rubber adhesive duct
tapes unless such tape is used in combination with mastic and draw bands.
§ 150.0(m)3:
Field-Fabricated Duct Systems. Field-fabricated duct systems must comply with applicable requirements for: pressure-sensitive tapes,
mastics, sealants, and other requirements specified for duct construction.
§ 150.0(m)7:
Backdraft Damper. Fan systems that exchange air between the conditioned space and outdoors must have backdraft or automatic dampers.
§ 150.0(m)8:
Gravity Ventilation Dampers. Gravity ventilating systems serving conditioned space must have either automatic or readily accessible,
manually operated dampers in all openings to the outside, except combustion inlet and outlet air openings and elevator shaft vents.
§ 150.0(m)9:
Protection of Insulation. Insulation must be protected from damage, sunlight, moisture, equipment maintenance, and wind. Insulation exposed
to weather must be suitable for outdoor service. For example, protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular
foam insulation must be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation.
§ 150.0(m)10:Porous Inner Core Flex Duct. Porous inner core flex ducts must have a non-porous layer between the inner core and outer vapor barrier.
§ 150.0(m)11:
Duct System Sealing and Leakage Test. When space conditioning systems use forced air duct systems to supply conditioned air to an
occupiable space, the ducts must be sealed and duct leakage tested, as confirmed through field verification and diagnostic testing, in
accordance with § 150.0(m)11 and Reference Residential Appendix RA3.
§ 150.0(m)12:
Air Filtration. Space conditioning systems with ducts exceeding 10 feet and the supply side of ventilation systems must have MERV 13 or
equivalent filters. Filters for space conditioning systems must have a 2 inch depth or can be 1 inch if sized per Equation 150.0-A. Pressure drops
and labeling must meet the requirements in §150.0(m)12. Filters must be accessible for regular service.*
§150.0(m)13:
Space Conditioning System Airflow Rate and Fan Efficacy. Space conditioning systems that use ducts to supply cooling must have a hole
for the placement of a static pressure probe, or a permanently installed static pressure probe in the supply plenum. Airflow must be ≥ 350 CFM
per ton of nominal cooling capacity, and an air-handling unit fan efficacy ≤ 0.45 watts per CFM for gas furnace air handlers and ≤ 0.58 watts per
CFM for all others. Small duct high velocity systems must provide an airflow ≥ 250 CFM per ton of nominal cooling capacity, and an air-handling
unit fan efficacy ≤ 0.62 watts per CFM. Field verification testing is required in accordance with Reference Residential Appendix RA3.3.*
2019 Low-Rise Residential Mandatory Measures Summary
Requirements for Ventilation and Indoor Air Quality:
§150.0(o)1:
Requirements for Ventilation and Indoor Air Quality. All dwelling units must meet the requirements of ASHRAE Standard 62.2, Ventilation
and Acceptable Indoor Air Quality in Residential Buildings subject to the amendments specified in § 150.0(o)1.
§150.0(o)1C:
Single Family Detached Dwelling Units. Single family detached dwelling units, and attached dwelling units not sharing ceilings or floors with
other dwelling units, occupiable spaces, public garages, or commercial spaces must have mechanical ventilation airflow provided at rates
determined by ASHRAE 62.2 Sections 4.1.1 and 4.1.2 and as specified in § 150.0(o)1C.
§150.0(o)1E:
Multifamily Attached Dwelling Units. Multifamily attached dwelling units must have mechanical ventilation airflow provided at rates in
accordance with Equation 150.0-B and must be either a balanced system or continuous supply or continuous exhaust system. If a balanced
system is not used, all units in the building must use the same system type and the dwelling-unit envelope leakage must be ≤ 0.3 CFM at 50 Pa
(0.2 inch water) per square foot of dwelling unit envelope surface area and verified in accordance with Reference Residential Appendix RA3.8.
§150.0(o)1F:
Multifamily Building Central Ventilation Systems. Central ventilation systems that serve multiple dwelling units must be balanced to provide
ventilation airflow for each dwelling unit served at a rate equal to or greater than the rate specified by Equation 150.0-B. All unit airflows must be
within 20% of the unit with the lowest airflow rate as it relates to the individual unit’s minimum required airflow rate needed for compliance.
§ 150.0(o)1G:Kitchen Range Hoods. Kitchen range hoods must be rated for sound in accordance with Section 7.2 of ASHRAE 62.2.
§ 150.0(o)2:Field Verification and Diagnostic Testing. Dwelling unit ventilation airflow must be verified in accordance with Reference Residential
Appendix RA3.7. Kitchen range hoods must be verified in accordance with Reference Residential Appendix RA3.7.4.3 to confirm it is
rated by HVI to comply with the airflow rates and sound requirements as specified in Section 5 and 7.2 of ASHRAE 62.2.
Pool and Spa Systems and Equipment Measures:
§ 110.4(a):
Certification by Manufacturers. Any pool or spa heating system or equipment must be certified to have all of the following: a thermal efficiency
that complies with the Appliance Efficiency Regulations; an on-off switch mounted outside of the heater that allows shutting off the heater
without adjusting the thermostat setting; a permanent weatherproof plate or card with operating instructions; and must not use electric
resistance heating.*
§ 110.4(b)1:
Piping. Any pool or spa heating system or equipment must be installed with at least 36 inches of pipe between the filter and the heater, or
dedicated suction and return lines, or built-in or built-up connections to allow for future solar heating.
§ 110.4(b)2:Covers. Outdoor pools or spas that have a heat pump or gas heater must have a cover.
§ 110.4(b)3:
Directional Inlets and Time Switches for Pools. Pools must have directional inlets that adequately mix the pool water, and a time switch that
will allow all pumps to be set or programmed to run only during off-peak electric demand periods.
§ 110.5:Pilot Light. Natural gas pool and spa heaters must not have a continuously burning pilot light.
§ 150.0(p):
Pool Systems and Equipment Installation. Residential pool systems or equipment must meet the specified requirements for pump sizing, flow
rate, piping, filters, and valves.*
Lighting Measures:
§ 110.9:
Lighting Controls and Components. All lighting control devices and systems, ballasts, and luminaires must meet the applicable requirements
of § 110.9.*
§ 150.0(k)1A:Luminaire Efficacy. All installed luminaires must meet the requirements in Table 150.0-A.
§ 150.0(k)1B:
Blank Electrical Boxes. The number of electrical boxes that are more than 5 feet above the finished floor and do not contain a luminaire or
other device must be no greater than the number of bedrooms. These electrical boxes must be served by a dimmer, vacancy sensor control, or
fan speed control.
§ 150.0(k)1C:
Recessed Downlight Luminaires in Ceilings. Luminaires recessed into ceilings must meet all of the requirements for: insulation contact (IC)
labeling; air leakage; sealing; maintenance; and socket and light source as described in § 150.0(k)1C.
§ 150.0(k)1D:
Electronic Ballasts for Fluorescent Lamps. Ballasts for fluorescent lamps rated 13 watts or greater must be electronic and must have an
output frequency no less than 20 kHz.
§ 150.0(k)1E:
Night Lights, Step Lights, and Path Lights. Night lights, step lights and path lights are not required to comply with Table 150.0-A or be
controlled by vacancy sensors provided they are rated to consume no more than 5 watts of power and emit no more than 150 lumens.
§ 150.0(k)1F:
Lighting Integral to Exhaust Fans. Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust hoods)
must meet the applicable requirements of § 150.0(k).*
§ 150.0(k)1G:Screw based luminaires. Screw based luminaires must contain lamps that comply with Reference Joint Appendix JA8.*
§ 150.0(k)1H:
Light Sources in Enclosed or Recessed Luminaires. Lamps and other separable light sources that are not compliant with the JA8 elevated
temperature requirements, including marking requirements, must not be installed in enclosed or recessed luminaires.
§ 150.0(k)1I:
Light Sources in Drawers, Cabinets, and Linen Closets. Light sources internal to drawers, cabinetry or linen closets are not required to
comply with Table 150.0-A or be controlled by vacancy sensors provided that they are rated to consume no more than 5 watts of power, emit no
more than 150 lumens, and are equipped with controls that automatically turn the lighting off when the drawer, cabinet or linen closet is closed.
§ 150.0(k)2A:Interior Switches and Controls. All forward phase cut dimmers used with LED light sources must comply with NEMA SSL 7A.
§ 150.0(k)2B:Interior Switches and Controls. Exhaust fans must be controlled separately from lighting systems.*
§ 150.0(k)2C:
Interior Switches and Controls. Lighting must have readily accessible wall-mounted controls that allow the lighting to be manually
turned ON and OFF.*
§ 150.0(k)2D:Interior Switches and Controls. Controls and equipment must be installed in accordance with manufacturer’s instructions.
§ 150.0(k)2E:
Interior Switches and Controls. Controls must not bypass a dimmer, occupant sensor, or vacancy sensor function if the control is installed to
comply with § 150.0(k).
§ 150.0(k)2F:Interior Switches and Controls. Lighting controls must comply with the applicable requirements of § 110.9.
2019 Low-Rise Residential Mandatory Measures Summary
§ 150.0(k)2G:
Interior Switches and Controls. An energy management control system (EMCS) may be used to comply with control requirements if it:
provides functionality of the specified control according to § 110.9; meets the Installation Certificate requirements of § 130.4; meets the
EMCS requirements of § 130.0(e); and meets all other requirements in § 150.0(k)2.
§ 150.0(k)2H:Interior Switches and Controls. A multiscene programmable controller may be used to comply with dimmer requirements in § 150.0(k) if it
provides the functionality of a dimmer according to § 110.9, and complies with all other applicable requirements in § 150.0(k)2.
§ 150.0(k)2I:Interior Switches and Controls. In bathrooms, garages, laundry rooms, and utility rooms, at least one luminaire in each of these spaces must
be controlled by an occupant sensor or a vacancy sensor providing automatic-off functionality. If an occupant sensor is installed, it must be
initially configured to manual-on operation using the manual control required under Section 150.0(k)2C.
§ 150.0(k)2J:Interior Switches and Controls. Luminaires that are or contain light sources that meet Reference Joint Appendix JA8 requirements for
dimming, and that are not controlled by occupancy or vacancy sensors, must have dimming controls.*
§ 150.0(k)2K:Interior Switches and Controls. Under cabinet lighting must be controlled separately from ceiling-installed lighting systems.
§ 150.0(k)3A:
Residential Outdoor Lighting. For single-family residential buildings, outdoor lighting permanently mounted to a residential building, or to other
buildings on the same lot, must meet the requirement in item § 150.0(k)3Ai (ON and OFF switch) and the requirements in either
§ 150.0(k)3Aii (photocell and either a motion sensor or automatic time switch control) or § 150.0(k)3Aiii (astronomical time clock), or an EMCS.
§ 150.0(k)3B:
Residential Outdoor Lighting. For low-rise residential buildings with four or more dwelling units, outdoor lighting for private patios, entrances,
balconies, and porches; and residential parking lots and carports with less than eight vehicles per site must comply with either Section
150.0(k)3A or with the applicable requirements in Sections 110.9, 130.0, 130.2, 130.4, 140.7 and 141.0.
§ 150.0(k)3C:
Residential Outdoor Lighting. For low-rise residential buildings with four or more dwelling units, any outdoor lighting for residential parking lots
or carports with a total of eight or more vehicles per site and any outdoor lighting not regulated by Section 150.0(k)3B or Section 150.0(k)3D must
comply with the applicable requirements in Sections 110.9, 130.0, 130.2, 130.4, 140.7 and 141.0.
§ 150.0(k)4:
Internally illuminated address signs. Internally illuminated address signs must comply with § 140.8; or must consume no more than 5 watts of
power as determined according to § 130.0(c).
§ 150.0(k)5:
Residential Garages for Eight or More Vehicles. Lighting for residential parking garages for eight or more vehicles must comply with the
applicable requirements for nonresidential garages in Sections 110.9, 130.0, 130.1, 130.4, 140.6, and 141.0.
§ 150.0(k)6A:
Interior Common Areas of Low-rise Multifamily Residential Buildings. In a low-rise multifamily residential building where the total interior
common area in a single building equals 20 percent or less of the floor area, permanently installed lighting for the interior common areas in that
building must be comply with Table 150.0-A and be controlled by an occupant sensor.
§ 150.0(k)6B:
Interior Common Areas of Low-rise Multifamily Residential Buildings. In a low-rise multifamily residential building where the total interior
common area in a single building equals more than 20 percent of the floor area, permanently installed lighting for the interior common areas in
that building must:
i.Comply with the applicable requirements in Sections 110.9, 130.0, 130.1, 140.6 and 141.0; and
ii.Lighting installed in corridors and stairwells must be controlled by occupant sensors that reduce the lighting power in each space by at least
50 percent. The occupant sensors must be capable of turning the light fully on and off from all designed paths of ingress and egress.
Solar Ready Buildings:
§ 110.10(a)1:
Single Family Residences. Single family residences located in subdivisions with ten or more single family residences and where the
application for a tentative subdivision map for the residences has been deemed complete and approved by the enforcement agency, which
do not have a photovoltaic system installed, must comply with the requirements of § 110.10(b) through § 110.10(e).
§ 110.10(a)2:Low-rise Multifamily Buildings. Low-rise multi-family buildings that do not have a photovoltaic system installed must comply with the
requirements of § 110.10(b) through § 110.10(d).
§ 110.10(b)1:
Minimum Solar Zone Area. The solar zone must have a minimum total area as described below. The solar zone must comply with access,
pathway, smoke ventilation, and spacing requirements as specified in Title 24, Part 9 or other Parts of Title 24 or in any requirements adopted
by a local jurisdiction. The solar zone total area must be comprised of areas that have no dimension less than 5 feet and are no less than 80
square feet each for buildings with roof areas less than or equal to 10,000 square feet or no less than 160 square feet each for buildings with
roof areas greater than 10,000 square feet. For single family residences, the solar zone must be located on the roof or overhang of the building
and have a total area no less than 250 square feet. For low-rise multi-family buildings the solar zone must be located on the roof or overhang of
the building, or on the roof or overhang of another structure located within 250 feet of the building, or on covered parking installed with the
building project, and have a total area no less than 15 percent of the total roof area of the building excluding any skylight area. The solar zone
requirement is applicable to the entire building, including mixed occupancy.*
§ 110.10(b)2:Azimuth. All sections of the solar zone located on steep-sloped roofs must be oriented between 90 degrees and 300 degrees of true north.
§ 110.10(b)3A: Shading. The solar zone must not contain any obstructions, including but not limited to: vents, chimneys, architectural features, and roof
mounted equipment.*
§ 110.10(b)3B:
Shading. Any obstruction located on the roof or any other part of the building that projects above a solar zone must be located at least twice the
distance, measured in the horizontal plane, of the height difference between the highest point of the obstruction and the horizontal projection of
the nearest point of the solar zone, measured in the vertical plane.*
§ 110.10(b)4:
Structural Design Loads on Construction Documents. For areas of the roof designated as a solar zone, the structural design loads for roof
dead load and roof live load must be clearly indicated on the construction documents.
§ 110.10(c):
Interconnection Pathways. The construction documents must indicate: a location reserved for inverters and metering equipment and a
pathway reserved for routing of conduit from the solar zone to the point of interconnection with the electrical service; and for single family
residences and central water-heating systems, a pathway reserved for routing plumbing from the solar zone to the water-heating system.
§ 110.10(d):
Documentation. A copy of the construction documents or a comparable document indicating the information from § 110.10(b) through
§ 110.10(c) must be provided to the occupant.
§ 110.10(e)1:Main Electrical Service Panel. The main electrical service panel must have a minimum busbar rating of 200 amps.
§ 110.10(e)2:
Main Electrical Service Panel. The main electrical service panel must have a reserved space to allow for the installation of a double pole circuit
breaker for a future solar electric installation. The reserved space must be permanently marked as “For Future Solar Electric”.
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name Date
System Name Floor Area
ENGINEERING CHECKS SYSTEM LOAD
Number of Systems COIL COOLING PEAK COIL HTG. PEAK
Heating System CFM Sensible Latent CFM Sensible
Output per System Total Room Loads
Total Output (Btuh) Return Vented Lighting
Output (Btuh/sqft) Return Air Ducts
Cooling System Return Fan
Output per System Ventilation
Total Output (Btuh) Supply Fan
Total Output (Tons) Supply Air Ducts
Total Output (Btuh/sqft)
Total Output (sqft/Ton) TOTAL SYSTEM LOAD
Air System
CFM per System HVAC EQUIPMENT SELECTION
Airflow (cfm)
Airflow (cfm/sqft)
Airflow (cfm/Ton)
Outside Air (%) Total Adjusted System Output
Outside Air (cfm/sqft) (Adjusted for Peak Design conditions)
Note: values above given at ARI conditions TIME OF SYSTEM PEAK
HEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak)
COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak)
PLAN # 22 3/18/2020
AC-1 -1,225
1
60,000
60,000
49.0
60,000
60,000
5.0
49.0
245.0
2,000
2,000
1.63
400.0
0.0%
0.00
1,190
20,608
0
0
0
1,489
0
468
12,232
0
-1,489
00
468
0
1,190
050,528
41624,476
50,528
37,474
0 37,474
5 TON 16/13/9.5
Aug 3 PM Jan 1 AM
1,033 416 307
26 ºF
Outside Air
0 cfm
68 ºF 105 ºF 106 ºF
105 ºF
68 ºF 68 ºF
112 / 73 ºF 76 / 62 ºF 55 / 54 ºF
56 / 54 ºF
75 / 61 ºF76 / 62 ºF
0 cfm
Outside Air
2,000 cfm
Supply Fan
46.3%
2,000 cfm
Supply FanHeating Coil
11,678
56 / 54 ºF
Cooling Coil
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name Date
System Name Floor Area
ENGINEERING CHECKS SYSTEM LOAD
Number of Systems COIL COOLING PEAK COIL HTG. PEAK
Heating System CFM Sensible Latent CFM Sensible
Output per System Total Room Loads
Total Output (Btuh) Return Vented Lighting
Output (Btuh/sqft) Return Air Ducts
Cooling System Return Fan
Output per System Ventilation
Total Output (Btuh) Supply Fan
Total Output (Tons) Supply Air Ducts
Total Output (Btuh/sqft)
Total Output (sqft/Ton) TOTAL SYSTEM LOAD
Air System
CFM per System HVAC EQUIPMENT SELECTION
Airflow (cfm)
Airflow (cfm/sqft)
Airflow (cfm/Ton)
Outside Air (%) Total Adjusted System Output
Outside Air (cfm/sqft) (Adjusted for Peak Design conditions)
Note: values above given at ARI conditions TIME OF SYSTEM PEAK
HEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak)
COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak)
PLAN # 22 3/18/2020
AC-2 -828
1
36,000
36,000
43.5
36,000
36,000
3.0
43.5
276.0
1,200
1,200
1.45
400.0
0.0%
0.00
641
11,099
0
0
0
1,489
0
246
6,447
0
-1,489
00
246
0
641
029,636
28113,869
29,636
22,485
0 22,485
3 TON 16/13/9.5
Aug 3 PM Jan 1 AM
496 281 329
26 ºF
Outside Air
0 cfm
68 ºF 85 ºF 87 ºF
86 ºF
68 ºF 68 ºF
112 / 73 ºF 76 / 60 ºF 52 / 51 ºF
54 / 52 ºF
75 / 60 ºF76 / 60 ºF
0 cfm
Outside Air
1,200 cfm
Supply Fan
41.5%
1,200 cfm
Supply FanHeating Coil
5,451
53 / 52 ºF
Cooling Coil
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name Date
System Name Floor Area
ENGINEERING CHECKS SYSTEM LOAD
Number of Systems COIL COOLING PEAK COIL HTG. PEAK
Heating System CFM Sensible Latent CFM Sensible
Output per System Total Room Loads
Total Output (Btuh) Return Vented Lighting
Output (Btuh/sqft) Return Air Ducts
Cooling System Return Fan
Output per System Ventilation
Total Output (Btuh) Supply Fan
Total Output (Tons) Supply Air Ducts
Total Output (Btuh/sqft)
Total Output (sqft/Ton) TOTAL SYSTEM LOAD
Air System
CFM per System HVAC EQUIPMENT SELECTION
Airflow (cfm)
Airflow (cfm/sqft)
Airflow (cfm/Ton)
Outside Air (%) Total Adjusted System Output
Outside Air (cfm/sqft) (Adjusted for Peak Design conditions)
Note: values above given at ARI conditions TIME OF SYSTEM PEAK
HEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak)
COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak)
PLAN # 22 3/18/2020
AC-3 -1,063
1
36,000
36,000
33.9
36,000
36,000
3.0
33.9
354.3
1,200
1,200
1.13
400.0
0.0%
0.00
587
10,169
0
0
0
1,489
0
300
7,850
0
-1,489
00
300
0
587
029,632
36112,832
29,632
22,485
0 22,485
3 TON 16/13/9.5
Aug 3 PM Jan 1 AM
452 361 403
26 ºF
Outside Air
0 cfm
68 ºF 85 ºF 87 ºF
86 ºF
68 ºF 68 ºF
112 / 73 ºF 75 / 60 ºF 52 / 51 ºF
54 / 52 ºF
75 / 60 ºF75 / 60 ºF
0 cfm
Outside Air
1,200 cfm
Supply Fan
41.5%
1,200 cfm
Supply FanHeating Coil
6,962
53 / 52 ºF
Cooling Coil
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name Date
System Name Floor Area
ENGINEERING CHECKS SYSTEM LOAD
Number of Systems COIL COOLING PEAK COIL HTG. PEAK
Heating System CFM Sensible Latent CFM Sensible
Output per System Total Room Loads
Total Output (Btuh) Return Vented Lighting
Output (Btuh/sqft) Return Air Ducts
Cooling System Return Fan
Output per System Ventilation
Total Output (Btuh) Supply Fan
Total Output (Tons) Supply Air Ducts
Total Output (Btuh/sqft)
Total Output (sqft/Ton) TOTAL SYSTEM LOAD
Air System
CFM per System HVAC EQUIPMENT SELECTION
Airflow (cfm)
Airflow (cfm/sqft)
Airflow (cfm/Ton)
Outside Air (%) Total Adjusted System Output
Outside Air (cfm/sqft) (Adjusted for Peak Design conditions)
Note: values above given at ARI conditions TIME OF SYSTEM PEAK
HEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak)
COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak)
PLAN # 22 3/18/2020
AC-4 -444
1
24,000
24,000
54.1
24,000
24,000
2.0
54.1
222.0
800
800
1.80
400.0
0.0%
0.00
283
4,895
0
0
0
1,489
0
120
3,140
0
-1,489
00
120
0
283
019,717
1516,949
19,717
14,990
0 14,990
2TON 16/13/9.5
Aug 3 PM Jan 1 AM
222 151 155
26 ºF
Outside Air
0 cfm
68 ºF 85 ºF 87 ºF
87 ºF
68 ºF 68 ºF
112 / 73 ºF 75 / 60 ºF 52 / 51 ºF
54 / 52 ºF
75 / 60 ºF75 / 60 ºF
0 cfm
Outside Air
800 cfm
Supply Fan
41.2%
800 cfm
Supply FanHeating Coil
1,892
54 / 52 ºF
Cooling Coil