Loading...
BCOM2023-0039 Test and Balance ReportTest and Balance Analysis Report FOR Luna Grill - Pavilion at La Quinta 79124 Highway 111 La Quinta, CA 92253 Architect Engineer JAG Contractor South Bay Mechanical Services This is to certify that American Air Balance Co., LLC has balanced the systems described herein to theiroptimum performance capabilities, unless otherwise noted in the project summary. The testing and balancinghas been performed in accordance with the standard reTuirements and procedures of the Associated Air Balance Council and the results of these tests are herein recorded. Certification #246404 DateMay 20, 2024 ApprovedBob Conboy Jr. AABC National Performance Guaranty Pursuant to the agreement between American Air Balance Co., LLC AABC Certified Testing & Balancing Agency and South Bay Mechanical Services Client All systems shall be tested and balanced in accordance with the project plans and specifications and to the optimum performance capabilities of the equipment. Testing and balancing shall be done in accordance with the standards published by the Associated Air Balance Council. If the Agency listed above fails to comply with the specifications for any reason other than termination of business by the AABC agency or equipment malfunction or inadequacy which prevents proper balancing of the systems, AABC will investigate and, if warranted, will provide supervisory personnel to assist the member Agency to perform work in accordance with AABC Standards. The supervision will be provided at no additional cost to building owner. This Guaranty is valid for one year from the date of submission of a test and balance report, provided the Agency is a current member of AABC, and may only be invoked in writing by the building owner, architect, or engineer of record. The Guaranty is limited to the terms and conditions as stated herein. Project Name Luna Grill - Pavilion at La Quinta Address 79124 Highway 111 La Quinta, CA 92253 Name of Engineer N/L Engineering Firm JAG Address Irvine, CA 92618 Email N/L Date 05/20/24 Associated Air Balance Council TBE # 21-01-123 AABC National Headquarters 1518 K Street, N.W. By Bob Conboy, Jr. Washington, D.C. 20005 AABC Certified TBE 15 Hubble # 200 Corporate Headquarters American Air Balance Co.., LLC  phone: 714-693-3700  fax: 714-693-9509  www. aabctab.com  mail@aabctab.com Test and Balance Analysis Report Certification for Luna Grill - Pavilion at La Quinta 79124 Highway 111 La Quinta, CA 92253 This is to certify that American Air Balance Co., LLC has balanced the systems described herein to their optimum performance capabilities, unless otherwise noted in the project summary. The testing and balancing has been performed in accordance with the standard requirements and procedures of the Associated Air Balance Council and the results of these tests are herein recorded. Certification Number 246404 Date May 20, 2024 Approved Bob Conboy Jr., Test and Balance Engineer Supervisor Managing Technician Michael Totten Brandon Berry 5obert A. Conboy, -r., TBE American Air Balance Co., LLC Ϯϭ-Ϭϭ-ϭϮϯ Michael -. Totten, TBE American Air Balance Co., LLC ϭϴ-Ϭϭ-ϭϭϰ Brandon L. Berry American Air Balance Co., LLC -0-1 Instrument Manufacturer Model Serial #Calib. Date Air Data Multi Meter Shortridge ADM 870C M17476 12/07/23 Amp Volt Meter Fluke 333 91756564 05/12/24 Drill Dewalt DCD771C2 303836 N/A Drill Charger Dewalt DW9116 N/A Flow Hood Shortridge 8405 N/A Hydrodata Meter Shortridge HDM-250 W20010 03/16/24 Ladder Husky 6'N/A N/A Laptop Computer Microsoft Surface Pro 6 023774594253 N/A Mobile Phone Apple iPhone SE3 64gb HVHGJYJ22G N/A Noncontact Thermometer Ray Tek Mini Temp RAYMT4U RAYL000669536 08/29/23 Pitot Tube Dwyer 48"160-48 N/A Pitot Tube Dwyer 24"160-24 N/A Psychrometer Probe Fieldpiece JL3RH 22036149AABH 07/19/23 Sound Meter Lutron SL-4010 Q214198 N/A Tac Chronometer Shimpo MT-200 167B5020P N/A TEST AND BALANCE INSTRUMENTATION The following instruments were used to successfully measure and set each device on this project. Page 1 of 1 Anaheim Phone: (714) 693-3700 / Fax: (714) 693-9509 Corporate Headquarters 4721 E. Hunter Ave. Anaheim, CA 92807 mail@aabctab.com Las Vegas Phone: (702) 255-7331 / Fax: (702) 294-1306 Definitions of Abbreviations, Terminology, Symbols & Conversions #: Symbol for PSI or Pounds per square inch Δ: Symbol for Delta - difference, net decrease or increase A:Nameplate Amps AABC: Associated Air Balance Council ABS:Absolute AC or ACU: Air Conditioner or Air Conditioning Unit ACCU: Air-Cooled Condensing Unit ACGIH: American Conference of Governmental Hygienists ACH Air Changes Per Hour ACT:Actual ADP: Apparatus Dew Point AEE: Association of Energy Engineers AFE: Association of Facility Engineering AHU: Air Handling Unit AK: Free Area Factor ALT:Altitude AMB:Ambient AMP:Ampere ANSI: American National Standards Institute AP: Access Point A-Scale or Db(A):A filtering system which roughly matches the response characteristics of the human ear ASHRAE: American Society of Heating, Air Conditioning and Refrigeration Engineers ASTM: American Society for Testing and Materials ATM:Atmosphere AVG:Average AZ: Azimuth B:Boiler BHP: Brake Horsepower BP:Boiling Point BSC: Building Systems Commissioning BTU: British Thermal Unit BTUH: British Thermal Units per Hour C:Celsius C to C: Center to Center CAV: Constant Air Volume or Continuous Air Volume CC:Cooling Coil CCW:Counter-Clockwise CD:Ceiling Diffuser CEG: Ceiling Exhaust Grille CER: Ceiling Exhaust Register CFM: Cubic Feet per Minute CH:Chiller   Anaheim Phone: (714) 693-3700 / Fax: (714) 693-9509 Corporate Headquarters 4721 E. Hunter Ave. Anaheim, CA 92807 mail@aabctab.com Las Vegas Phone: (702) 255-7331 / Fax: (702) 294-1306   Definitions of Abbreviations, Terminology, Symbols & Conversions CHW or CHWS: Chilled Water Supply CHWR: Chilled Water Return CM² Square Centimeters CM/SEC Centometers per Second CMD: Count Mean Diameter Cp Specific Heat: water = 1.0 BTU / lb per °F air = 0.24 BTU / lb per °F CP or P: Circulating Pump CPT: Capacity Performance Testing (Building Commissioning) CR: Ceiling Register CRR: Ceiling Return Register CT: Cooling Tower CU: Condensing Unit CUH: Cabinet Unit Heating CV: Specific Heat at Constant Volume CV: Valve Constant CW: Chilled Water CWR: Condenser Water Return CW or CWS: Condenser Water Supply DAT: Discharge Air Temperature Db: Decibel DB: Dry Bulb DC: Direct Current DD: Direct Drive Delta (Δ): Difference - net decrease or increase DIA: Diameter DNL: Data Not Listed DOP: Dioctyl Phthalate, an aerosol generated by blowing air through liquid Dioctyl Phthalate (mean particle diameter is between 0.2 and 0.4 microns) Δ P: Differential Pressure or Pressure Drop, net change in Pressure DPT: Dew Point Temperature DSTD: Standard Air Density, equals 0.075 lb / Cu. Ft. @ 29.92 in, Hg Δ T: Differential Temperature, net change in temperature EAT: Entering Air Temperature EC: Evaporative Cooler Economizer: Controls and componentry that allow an air handler to logically utilize outdoor air for cooling as opposed to the use of mechanical cooling EDC: Electric Duct Coil EDH: Electric Duct Heater EER: Energy Efficiency Ratio EF or E: Exhaust Fan EFF: Efficiency EG: Exhaust Grille EMCS: Energy Management Control System(s)   Anaheim Phone: (714) 693-3700 / Fax: (714) 693-9509 Corporate Headquarters 4721 E. Hunter Ave. Anaheim, CA 92807 mail@aabctab.com Las Vegas Phone: (702) 255-7331 / Fax: (702) 294-1306   Definitions of Abbreviations, Terminology, Symbols & Conversions EMF: Electromotive Force EMS Energy Management System(s) ENT: Entering EP: Electro-Pneumatic Switches ER: Exhaust Register ESD: Electrostatic Discharge ESP: External Static Pressure EWT: Entering Water Temperature °F: Degrees Fahrenheit F to F: Face to Face FAF: Forced Air Fan FCU: Fan Coil Unit FDA: Food and Drug Administration FG: Floor Grille FH: Fume Hood FIV: Field Installation Verification (Building Commissioning) FLA: Full Load Amperage FLTS: Filters FP: Freezing Point FPB: Fan Powered Box FPM: Feet Per Minute FPS: Feet Per Second FPT: Functional Performance Testing (Building Commissioning) FR: Floor Register FTU: Fan Terminal Unit G or g: Gravitational Constant GA: Gauge GC: General Contractor GPH: Gallons Per Hour GPM: Gallons Per Minute GR: Grain - measurement of actual moisture in an air sample, 7000 grains = one pound of water GSD: Geometric Standard Division H: Enthalpy H2O: Water HC: Heating Coil HD: Head pressure measured in inches or feet of water Heater O.L.: Thermal Overload protection for motors located at the motor starter HEPA: High Efficiency Particulate Arrestance HEPA Filter: High Efficiency Particulate Air Filter Hg: Mercury HOA: Hand/Off/Auto switch HP: HorsePower HPS: High Pressure Steam   Anaheim Phone: (714) 693-3700 / Fax: (714) 693-9509 Corporate Headquarters 4721 E. Hunter Ave. Anaheim, CA 92807 mail@aabctab.com Las Vegas Phone: (702) 255-7331 / Fax: (702) 294-1306   Definitions of Abbreviations, Terminology, Symbols & Conversions HPU: Heat Pump Unit HRC: Heat Recovery Coil or Heat Reclaim Coil HTHW: High Temperature Hot Water HV: Heating Ventilator HVAC: Heating, Ventilating & Air Conditioning HW: Hot Water HWR: Hot Water Return or Heating Water Return HWS: Hot Water Supply or Heating Water Supply HX: Heat exchanger Hydronic: Indicates the use or conveyance of liquid for thermal transfer Hz: Hertz I.D.: Inside Diameter I/O: Input / Output ID: Impeller Diameter (pump) IES: Institute of Environmental Sciences IV: Inlet Vanes K: Correction Factor KW: Kilowatts KWH: Kilowatt Hour LAT: Leaving Air Temperature L/S: Lter per Second LD: Linear Diffuser LF: Linear Foot LPS: Low Pressure Steam LPS: Liters Per Second LTD: Least Temperature Difference LTHW: Low Temperature Hot Water LV or LVG: Leaving LWG: Low Wall Grille LWR: Low Wall Register LWT: Leaving Water Temperature MAU or MUA: Make-up Air Unit or Make-Up Air MAX: Maximum MB: Mixing Box MBH: Mega BTU's per Hour MET: Mean Effective Temperature Micron: 1.0 x 10-6 meter Mil.: 2.54 x 10-5 meter MIN Minimum MM: Millimeters MM X MM: Millimeters by Millimeters MMD: Mass Mean Diameter MTD: Mean Temperature Difference MVD: Manual Volume Damper   Anaheim Phone: (714) 693-3700 / Fax: (714) 693-9509 Corporate Headquarters 4721 E. Hunter Ave. Anaheim, CA 92807 mail@aabctab.com Las Vegas Phone: (702) 255-7331 / Fax: (702) 294-1306   Definitions of Abbreviations, Terminology, Symbols & Conversions MZ: MultiZone N/A: Not Applicable or Not Available NASA: National Aeronautics and Space Administration NC: Noise Criteria or Normally Closed NIC: Not in Contract N/L: Not Listed NM: Not Measured NO: Normally Open NPFC: Naval Publications and Forms Center NPSHA: Net Positive Suction Head Available NS: Not Specified NSF: National Sanitation Foundation NTIS: National Technical Information Service NTS: Not To Scale NVL: No Valid Location for Testing OB: Octave Band - a range of frequency where the highest frequency of the band is double the lowest frequency of the band. The band is usually specified by the center frequency. The preferred octave bands are designated by the following center frequencies: 31.5, 63, 125, 250, 500, 1000, 2000, 4000, 8000, 16000. OBD: Opposed Blade Damper O.D.: Outside Diameter OAT: Outside Air Temperature OPT: Operational Performance Testing (Building Commissioning) O.S.A. or OA: Outside Air P.E.: Professional Engineer P: Circulating Pump Pa: Pascal - 1 Pascal = 6.894 x 10-³ psi PCT: Percent PD: Differential Pressure or Pressure Drop PE: Pneumatic Electric Switch PF: Power Factor PH: Phase(s) PHC: PreHeat Coil PMP: Circulating Pump PNC: Preferred Noise Criterion Curves PPM: Parts Per Million PSI: Pounds per Square Inch PSIA: Pounds per Square Inch Absolute PSIG: Pounds per Square Inch Gauge PSL: Polystyrene Latex Spheres - used to generate an aerosol challenge medium where electronic & semi-conductor products are manufactured PWR: Power   Anaheim Phone: (714) 693-3700 / Fax: (714) 693-9509 Corporate Headquarters 4721 E. Hunter Ave. Anaheim, CA 92807 mail@aabctab.com Las Vegas Phone: (702) 255-7331 / Fax: (702) 294-1306   Definitions of Abbreviations, Terminology, Symbols & Conversions R: Rankine (absolute temperature) - Rankine = 1.8 Kelvin RA: Return Air RAT: Return Air Temperature RCC: Room Criterion Curves RD: Round (for sizes) REQ: Required RF: Return air Fan RH: Relative Humidity RHC: ReHeat Coil RPM: Revolutions Per Minute RTU: Roof Top Unit S: Entropy SA: Supply Air SAR: Supply Air Register SAT: Supply Air Temperature SD: Smoke detector or Smoke Damper SEER: Season Energy Efficient Ratio SEF: Smoke Exhaust Fan SF (AIR): Supply Fan SF (ELECT): Service Factor SF (MOTOR): Safety Factor by which actual amps can exceed rated amperage, at the expense of expected motor life SHC: Steam Heating Coil SMACNA: Sheet Metal and Air Conditioning Contractors National Association SP: SetPoint SP: Static Pressure S.P. "W.C.": Static Pressure resistance measured in inches of Water Column SP VOLUME: Specific Volume SPF: Stairwell Pressurization Fan SQ: Square STD: Standard SWG: SideWall Grille SWR: SideWall Register SWS: SideWall Supply T STAT: Thermostat TAB: Testing, Adjusting and Balancing TD: Differential Temperature - Net temperature decrease or increase TDH: Total Dynamic Head or Total Dead Head (pressure differential when flow equals zero) T.I. Travel In T.O. Travel Out THROW: Distance an air stream travels after leaving an air outlet before the air stream velocity is reduced to approximately 50 fpm Anaheim Phone: (714) 693-3700 / Fax: (714) 693-9509 Corporate Headquarters 4721 E. Hunter Ave. Anaheim, CA 92807 mail@aabctab.com Las Vegas Phone: (702) 255-7331 / Fax: (702) 294-1306 Definitions of Abbreviations, Terminology, Symbols & Conversions TON (Air Cond.): Equals 12,000 BTU per hour TP: Traverse Point or Test Point. TP (Motor): Thermal Protected (opens motor circiutry if rated amps are exceeded) TR:Thermal Resistance TSP: Total Static Pressure UH:Unit Heater ULPA Filter: Ultra Low Penetration Air Filter UV: Unit Ventilator V: Volt or Voltage VA:Volt Atmossphere VAC:Vacuum VAV: Variable Air Volume VD:Volume Damper VEL:Velocity VFD: Variable Frequency Drive (electric motor speed controller) VP: Velocity Pressure W:Watts WB:Wet Bulb W.G.:Water Gage WT:Weight WTR:Water Z:Zone Zoning: The practice of dividing a building into small sections for heating and cooling control, selected so that one thermostat can be used to determine each section's heating & cooling requirements Anaheim Phone: (714) 693-3700 / Fax: (714) 693-9509 Corporate Headquarters 4721 E. Hunter Ave. Anaheim, CA 92807 mail@aabctab.com Las Vegas Phone: (702) 255-7331 / Fax: (702) 294-1306 Page 1 of 3 Luna Grill - Pavilion at La Quinta La Quinta, CA 92253 CERT #246404 American Air Balance Co., Inc is a Testing and Balancing Agency that engages in testing, adjusting and balancing of air and water moving systems. American Air Balance Co., Inc. does not undertake the construction of HVAC systems, fans, ductwork, terminal boxes, dampers, air distribution or other components. Additionally, our firm does not undertake construction of other building systems, such as walls, doors, windows, lights, that may have a direct affect on the performance of the system(s) being tested. This report represents the optimal obtainable results given the limits of the installed system and the existing conditions at the time of certification. The data and information provided herein is factual, accurate and based upon the information provided in addition to the existing conditions of the building at the time the tests were conducted. Each system’s component installation and design dictates limitations and test parameters. System specific procedures must be followed to duplicate the results listed herein. American Air Balance Co., Inc. employs the standards and procedures per the latest version of the AABC National Standards and Test and Balance Procedures, as applicable, unless otherwise dictated by the project specifications and/or project system specific requirements. Verification of the report contents must be carried out within 45 days of certification and shall be accomplished by our Field Technician, using the same instruments, under the same test conditions used to develop this report; otherwise this project warranty is null and void. Our office must receive requests for field verification in writing within 30 days of certification. American Air Balance Co., Inc. makes no representation or warranty that the systems and data contained herein will remain in the condition recorded beyond the date of certification. Adjustment(s), change(s) and/or tampering with component of the systems will affect the values listed herein. Changes, modifications and/or adjustment to the building structure, systems and/or sub systems, including but not limited to Architectural, Mechanical, Electrical, Plumbing, Building Automation Controls and Fire/Life Safety Alarm Systems will adversely affect the integrity of the systems and alter the data listed herein. Any such changes void American Air Balance Co., Inc.’s warranty and the AABC National Performance Guaranty. Proper building and HVAC system(s) maintenance must be followed to maintain efficient conditions. Improper system maintenance directly affects system performance. Anaheim Phone: (714) 693-3700 / Fax: (714) 693-9509 Corporate Headquarters 4721 E. Hunter Ave. Anaheim, CA 92807 mail@aabctab.com Las Vegas Phone: (702) 255-7331 / Fax: (702) 294-1306 Page 2 of 3 Explanation of “K” Value and Flow Hood Readings Air distribution was read with a Shortridge Flow Hood; Air Data Multi-Meter, model ADM-860, where possible, and where 1.0 is listed as the effective area, “K” in our report, unless otherwise noted. This flow hood is a direct reading instrument that compensates and corrects for hood backpressure, altitude, density and temperature when appropriate; therefore a 1.0 is listed as the effective area. The velocity listed in this report reflects the velocity through the flow hood and not the diffuser neck or face. Scope of Work American Air Balance Co., Inc. has been requested to provide a Test and Balance for the above referenced project. This work is inclusive of: • Certification of Air Moving System. • Title 24. Project Specific Comments This section of our report is used to describe project special conditions, system observations and/or operational comments. At times, as applicable, items that remain outstanding and/or values that are not with the allowable project tolerances are footnoted on each individual test sheet will also be listed herein. American Air Balance Co., Inc. has noted the following upon conclusion of the Test and Balance of this project: General Notes: • All air moving equipment and associated air distribution have been measured, balanced, and recorded under normal operating conditions. • All final filters were inspected and confirmed to be installed and clean of any debris. Anaheim Phone: (714) 693-3700 / Fax: (714) 693-9509 Corporate Headquarters 4721 E. Hunter Ave. Anaheim, CA 92807 mail@aabctab.com Las Vegas Phone: (702) 255-7331 / Fax: (702) 294-1306 Page 3 of 3 Grease Duct Velocity Calculations and Final Measured Numbers: KEF-1 • Shaft Size: 18” Round • Area (Sq. Ft.): 1.77 • Velocity (Feet Per Minute): 1876 • Airflow (CFM): 3320 KEF-2 • Shaft Size: 14” Round • Area (Sq. Ft.): 1.07 • Velocity (Feet Per Minute): 2014 • Airflow (CFM): 2155 Luna Grill - Pavilion at La Quinta Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 TABLE OF CONTENTS ------------------------------- RTU-1 - Air Moving Equipment Test 1...................................................................... RTU-1 S.P. PROFILE - Static Pressure Profile 2................................................. RTU-1 OUTSIDE AIR - Air Distribution Schedule 3.............................................. RTU-1 SUPPLY AIR - Air Distribution Schedule 4................................................ RTU-1 RETURN AIR - Air Distribution Schedule 5............................................... RTU-2 - Air Moving Equipment Test 6...................................................................... RTU-2 S.P. PROFILE - Static Pressure Profile 7................................................. RTU-2 OUTSIDE AIR - Air Distribution Schedule 8.............................................. RTU-2 SUPPLY AIR - Air Distribution Schedule 9................................................ RTU-2 RETURN AIR - Air Distribution Schedule 10............................................... RTU-3 - Air Moving Equipment Test 11...................................................................... RTU-3 S.P. PROFILE - Static Pressure Profile 12................................................. RTU-3 OUTSIDE AIR - Air Distribution Schedule 13.............................................. RTU-3 SUPPLY AIR - Air Distribution Schedule 14................................................ RTU-3 RETURN AIR - Air Distribution Schedule 15............................................... MUA-1 - Air Moving Equipment Test 16..................................................................... MUA-1 S.P. PROFILE - Static Pressure Profile 17................................................ MUA-1 SUPPLY AIR - Air Distribution Schedule 18............................................... TEMPERATURE DATA - Temperature Test 19.................................................... EF-1A - Exhaust Fan Equipment Test 20.................................................................... EF-1A S.P. PROFILE - Static Pressure Profile 21................................................. EF-1A EXHAUST AIR - Air Distribution Schedule 22.............................................. EF-1B - Exhaust Fan Equipment Test 23.................................................................... EF-1B S.P. PROFILE - Static Pressure Profile 24................................................. EF-1B EXHAUST AIR - Air Distribution Schedule 25.............................................. KEF-1 - Exhaust Fan Equipment Test 26.................................................................... KEF-1 S.P. PROFILE - Static Pressure Profile 27................................................. KEF-1 EXHAUST AIR - Air Distribution Schedule 28.............................................. KEF-2 - Exhaust Fan Equipment Test 29.................................................................... KEF-2 S.P. PROFILE - Static Pressure Profile 30................................................. KEF-2 EXHAUST AIR - Air Distribution Schedule 31.............................................. May 20, 2024 PROJECT DESCRIPTION Air Moving Equipment Test Luna Grill - Pavilion at La Quinta RTU-1 Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Fan Information FAN NUMBER SERVING FAN MANUFACTURER MODEL FAN SERIAL NUMBER MOTOR MANUFACTURER CFM Required Actual Total - Air Dist. Return O.S.A S.P. Required Actual Suction Discharge Total EFFICIENCY POWER FACTOR Conditions Required Actual Motor (HP/RPM) Motor (Volts/Phase) Motor Amps Brake HorsePower Service Factor Fan RPM MOTOR SHEAVE % OPEN FAN SHEAVE DRIVE BELTS CTR. TO CTR.MOTOR T.I. T.O. V.F.D. HERTZ SET POINT OPERATING STATIC PRESSURE SET POINT RTU-1 DINING CARRIER XYE08A2B3AA1A111A2 N2G3763953 BALDOR FR: 56HZ 2850 2875 N/A -1.02 2440 2445 N/A 0.49 410 430 External 0.60 Total SP 1.51 2.40 1750 2.40 1761 230 3 213 3 7.20 7.20 7.20 6.29 6.35 6.41 1.91 0.87 0.70 1.15 N/L 773 025 1VL44 X 5/8" 100% AK74 X 1.0" (1) A-48 16.75 2.50 3.00 60.0 N/A 1 025 REQUIRED INFORMATION IS NOT LISTED. May 20, 2024 PROJECT DESCRIPTION Static Pressure Profile Luna Grill - Pavilion at La Quinta RTU-1 S.P. PROFILE Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 SF OSA RA FI L T E R CO O L I N G C O I L SA A B C -0.79 -1.02 0.49 ABC 2 May 20, 2024 PROJECT DESCRIPTION Air Distribution Schedule Luna Grill - Pavilion at La Quinta RTU-1 OUTSIDE AIR Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Data Req. Req. Actual Actual Room No. Terminal No. Terminal Size K VEL CFM VEL CFM RTU-1 OSA-1 32 X 9 2.000 205 410 215 430 Totals:410 430 3 May 20, 2024 PROJECT DESCRIPTION Air Distribution Schedule Luna Grill - Pavilion at La Quinta RTU-1 SUPPLY AIR Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Data Req. Req. Actual Actual Room No. Terminal No. Terminal Size K VEL CFM VEL CFM DINING 1 18 X 10 1.000 500 500 510 510 DINING 2 18 X 10 1.000 500 500 485 485 DINING 3 18 X 10 1.000 500 500 520 520 RESTROOM 1 4 6 X 6 1.000 75 75 75 75 RESTROOM 2 5 6 X 6 1.000 75 75 75 75 DATA ROOM 6 12 X 12 1.000 200 200 205 205 DINING 7 18 X 10 1.000 500 500 490 490 DINING 8 18 X 10 1.000 500 500 515 515 Totals:2850 2875 4 May 20, 2024 PROJECT DESCRIPTION Air Distribution Schedule Luna Grill - Pavilion at La Quinta RTU-1 RETURN AIR Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Data Req. Req. Actual Actual Room No. Terminal No. Terminal Size K VEL CFM VEL CFM DINING R-1 20 X 20 1.000 1220 1220 1135 1135 028 DINING R-2 20 X 20 1.000 1220 1220 1115 1115 028 DATA ROOM R-3 12 X 12 1.000 200 200 195 195 Totals:2640 2445 028 THE RETURN AIR QUANTITY WAS PROPORTIONED TO ALLOW FOR DESIGN MINIMUM O.S.A. 5 May 20, 2024 PROJECT DESCRIPTION Air Moving Equipment Test Luna Grill - Pavilion at La Quinta RTU-2 Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Fan Information FAN NUMBER SERVING FAN MANUFACTURER MODEL FAN SERIAL NUMBER MOTOR MANUFACTURER CFM Required Actual Total - Air Dist. Return O.S.A S.P. Required Actual Suction Discharge Total EFFICIENCY POWER FACTOR Conditions Required Actual Motor (HP/RPM) Motor (Volts/Phase) Motor Amps Brake HorsePower Service Factor Fan RPM MOTOR SHEAVE % OPEN FAN SHEAVE DRIVE BELTS CTR. TO CTR.MOTOR T.I. T.O. V.F.D. HERTZ SET POINT OPERATING STATIC PRESSURE SET POINT RTU-2 DINING CARRIER XYE08A2B3AA1A111A2 N2G3740407 BALDOR FR: 56HZ 2850 2885 N/A -1.05 2440 2460 N/A 0.48 410 425 External 0.60 Total SP 1.53 2.40 1750 2.40 1764 230 3 214 3 7.20 7.20 7.20 6.26 6.39 6.43 1.92 0.87 0.70 1.15 N/L 778 025 1VL44 X 5/8" 100% AK74 X 1.0" (1) A-48 16.75 2.50 3.00 60.0 N/A 6 025 REQUIRED INFORMATION IS NOT LISTED. May 20, 2024 PROJECT DESCRIPTION Static Pressure Profile Luna Grill - Pavilion at La Quinta RTU-2 S.P. PROFILE Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 SF OSA RA FI L T E R CO O L I N G C O I L SA A B C -0.81 -1.05 0.48 ABC 7 May 20, 2024 PROJECT DESCRIPTION Air Distribution Schedule Luna Grill - Pavilion at La Quinta RTU-2 OUTSIDE AIR Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Data Req. Req. Actual Actual Room No. Terminal No. Terminal Size K VEL CFM VEL CFM RTU-2 OSA-1 32 X 9 2.000 205 410 213 425 Totals:410 425 8 May 20, 2024 PROJECT DESCRIPTION Air Distribution Schedule Luna Grill - Pavilion at La Quinta RTU-2 SUPPLY AIR Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Data Req. Req. Actual Actual Room No. Terminal No. Terminal Size K VEL CFM VEL CFM DINING 1 18 X 10 1.000 475 475 490 490 DINING 2 18 X 10 1.000 475 475 475 475 DINING 3 18 X 10 1.000 475 475 465 465 DINING 4 18 X 10 1.000 475 475 485 485 DINING 5 18 X 10 1.000 475 475 490 490 DINING 6 18 X 10 1.000 475 475 480 480 Totals:2850 2885 9 May 20, 2024 PROJECT DESCRIPTION Air Distribution Schedule Luna Grill - Pavilion at La Quinta RTU-2 RETURN AIR Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Data Req. Req. Actual Actual Room No. Terminal No. Terminal Size K VEL CFM VEL CFM DINING R-1 20 X 20 1.000 1220 1220 1210 1210 DINING R-2 20 X 20 1.000 1220 1220 1250 1250 Totals:2440 2460 10 May 20, 2024 PROJECT DESCRIPTION Air Moving Equipment Test Luna Grill - Pavilion at La Quinta RTU-3 Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Fan Information FAN NUMBER SERVING FAN MANUFACTURER MODEL FAN SERIAL NUMBER MOTOR MANUFACTURER CFM Required Actual Total - Air Dist. Return O.S.A S.P. Required Actual Suction Discharge Total Conditions Required Actual Motor (HP/RPM) Motor (Volts/Phase) Motor Amps Service Factor Fan RPM MOTOR SHEAVE % OPEN FAN SHEAVE DRIVE BELTS V.F.D. HERTZ SET POINT OPERATING STATIC PRESSURE SET POINT RTU-3 KITCHEN CARRIER 50GCQJ06A2A5A 1124C08243 CARRIER 2000 2015 N/A -0.65 1620 1630 N/A 0.39 380 385 External 1.20 Total SP 1.04 2.40 N/A 2.40 N/A 025, 026 208 1 213 1 N/A 9.20 N/A N/A 7.84 N/A 1.00 D.D. D.D. 026 DIRECT DRIVE D.D. DIRECT DRIVE DIRECT DRIVE 60.0 N/A 11 025 REQUIRED INFORMATION IS NOT LISTED. 026 D.D. = DIRECT DRIVE FAN May 20, 2024 PROJECT DESCRIPTION Static Pressure Profile Luna Grill - Pavilion at La Quinta RTU-3 S.P. PROFILE Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 SF OSA RA FI L T E R CO O L I N G C O I L SA A B C -0.43 -0.65 0.39 ABC 12 May 20, 2024 PROJECT DESCRIPTION Air Distribution Schedule Luna Grill - Pavilion at La Quinta RTU-3 OUTSIDE AIR Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Data Req. Req. Actual Actual Room No. Terminal No. Terminal Size K VEL CFM VEL CFM RTU-3 OSA-1 27 X 13 2.440 156 380 158 385 Totals:380 385 13 May 20, 2024 PROJECT DESCRIPTION Air Distribution Schedule Luna Grill - Pavilion at La Quinta RTU-3 SUPPLY AIR Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Data Req. Req. Actual Actual Room No. Terminal No. Terminal Size K VEL CFM VEL CFM KITCHEN 1 24 X 24 1.000 400 400 410 410 KITCHEN 2 24 X 24 1.000 400 400 405 405 KITCHEN 3 24 X 24 1.000 400 400 385 385 KITCHEN 4 24 X 24 1.000 400 400 400 400 KITCHEN 5 24 X 24 1.000 400 400 415 415 Totals:2000 2015 14 May 20, 2024 PROJECT DESCRIPTION Air Distribution Schedule Luna Grill - Pavilion at La Quinta RTU-3 RETURN AIR Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Data Req. Req. Actual Actual Room No. Terminal No. Terminal Size K VEL CFM VEL CFM KITCHEN R-1 24 X 24 1.000 540 540 530 530 KITCHEN R-2 24 X 24 1.000 540 540 555 555 KITCHEN R-3 24 X 24 1.000 540 540 545 545 Totals:1620 1630 15 May 20, 2024 PROJECT DESCRIPTION Air Moving Equipment Test Luna Grill - Pavilion at La Quinta MUA-1 Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Fan Information FAN NUMBER SERVING FAN MANUFACTURER MODEL FAN SERIAL NUMBER MOTOR MANUFACTURER CFM Required Actual Total - Air Dist. Return O.S.A S.P. Required Actual Suction Discharge Total EFFICIENCY POWER FACTOR Conditions Required Actual Motor (HP/RPM) Motor (Volts/Phase) Motor Amps Brake HorsePower Service Factor Fan RPM MOTOR SHEAVE % OPEN FAN SHEAVE DRIVE BELTS V.F.D. HERTZ SET POINT OPERATING STATIC PRESSURE SET POINT MUA-1 KITCHEN HOOD CAPTIVEAIRE SYSTEMS A3-24D 6064933 TECO FR: 213T 4200 4265 N/A -0.35 0 0 N/A 0.33 4200 4265 External 0.50 Total SP 0.68 3.00 1175 3.00 N/A 026 230 3 226 3 9.20 9.20 9.20 5.53 5.61 5.58 2.13 0.89 0.82 1.15 D.D. D.D. 026 DIRECT DRIVE D.D. DIRECT DRIVE DIRECT DRIVE 35.7 N/A 16 026 D.D. = DIRECT DRIVE FAN May 20, 2024 PROJECT DESCRIPTION Static Pressure Profile Luna Grill - Pavilion at La Quinta MUA-1 S.P. PROFILE Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 SF OSA CO O L I N G C O I L FI L T E R SA A B C D -0.07 -0.18 -0.35 0.33 ABCD 17 May 20, 2024 PROJECT DESCRIPTION Air Distribution Schedule Luna Grill - Pavilion at La Quinta MUA-1 SUPPLY AIR Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Data Req. Req. Actual Actual Room No. Terminal No. Terminal Size K VEL CFM VEL CFM KITCHEN 1 242 X 18 30.250 139 4200 141 4265 Totals:4200 4265 18 May 20, 2024 PROJECT DESCRIPTION Temperature Test Luna Grill - Pavilion at La Quinta TEMPERATURE DATA Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Data Ent. Ent. EQUIPMENT ID DB WB LV DB LV WB OSA DB OSA WB RTU-1 COOL 74.1 63.7 54.4 52.6 99.3 87.5 RTU-1 HEAT 74.4 101.3 99.3 87.5 RTU-2 COOL 74.2 63.9 54.8 52.9 99.3 87.5 RTU-2 HEAT 74.4 102.1 99.3 87.5 RTU-3 COOL 73.8 63.2 54.3 52.2 99.3 87.5 RTU-3 HEAT 74.2 100.9 99.3 87.5 MUA-1 COOL 99.3 87.5 76.8 64.5 99.3 87.5 19 May 20, 2024 PROJECT DESCRIPTION Exhaust Fan Equipment Test Luna Grill - Pavilion at La Quinta EF-1A Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Exhaust Fan Information FAN NUMBER FAN SIZE FAN MANUFACTURER MOTOR MANUFACTURER Exhaust Fan Conditions Required Actual CFM-Fan Fan Static Pressure Motor HP Motor RPM Motor (Volts/Phase) Motor Amps Fan RPM Service Factor MOTOR SHEAVE % OPEN FAN SHEAVE DRIVE BELTS V.F.D. HERTZ SET POINT OPERATING STATIC PRESSURE SET POINT EF-1A SP-B150-QD GREENHECK GREENHECK 80 85 0.100 0.120 5.800 N/A 184, 150 625 N/A 026 115 1 119 1 N/A 0.13 N/A N/A 0.11 N/A D.D D.D 026 1.00 DIRECT DRIVE D.D DIRECT DRIVE DIRECT DRIVE N/A N/A 20 026 D.D. = DIRECT DRIVE FAN 150 HORSEPOWER IS NOT LISTED. 184 REQUIRED LISTED IN WATTS. May 20, 2024 PROJECT DESCRIPTION Static Pressure Profile Luna Grill - Pavilion at La Quinta EF-1A S.P. PROFILE Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 EF EA A B -0.04 0.08 AB 21 May 20, 2024 PROJECT DESCRIPTION Air Distribution Schedule Luna Grill - Pavilion at La Quinta EF-1A EXHAUST AIR Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Data Req. Req. Actual Actual Room No. Terminal No. Terminal Size K VEL CFM VEL CFM RESTROOM 1 1 12 X 10 1.000 80 80 85 85 Totals:80 85 22 May 20, 2024 PROJECT DESCRIPTION Exhaust Fan Equipment Test Luna Grill - Pavilion at La Quinta EF-1B Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Exhaust Fan Information FAN NUMBER FAN SIZE FAN MANUFACTURER MOTOR MANUFACTURER Exhaust Fan Conditions Required Actual CFM-Fan Fan Static Pressure Motor HP Motor RPM Motor (Volts/Phase) Motor Amps Fan RPM Service Factor MOTOR SHEAVE % OPEN FAN SHEAVE DRIVE BELTS V.F.D. HERTZ SET POINT OPERATING STATIC PRESSURE SET POINT EF-1B SP-B150-QD GREENHECK GREENHECK 80 80 0.100 0.110 5.800 N/A 184, 150 625 N/A 026 115 1 119 1 N/A 0.13 N/A N/A 0.11 N/A D.D D.D 026 1.00 DIRECT DRIVE D.D DIRECT DRIVE DIRECT DRIVE N/A N/A 23 026 D.D. = DIRECT DRIVE FAN 150 HORSEPOWER IS NOT LISTED. 184 REQUIRED LISTED IN WATTS. May 20, 2024 PROJECT DESCRIPTION Static Pressure Profile Luna Grill - Pavilion at La Quinta EF-1B S.P. PROFILE Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 EF EA A B -0.04 0.07 AB 24 May 20, 2024 PROJECT DESCRIPTION Air Distribution Schedule Luna Grill - Pavilion at La Quinta EF-1B EXHAUST AIR Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Data Req. Req. Actual Actual Room No. Terminal No. Terminal Size K VEL CFM VEL CFM RESTROOM 2 1 12 X 10 1.000 80 80 80 80 Totals:80 80 25 May 20, 2024 PROJECT DESCRIPTION Exhaust Fan Equipment Test Luna Grill - Pavilion at La Quinta KEF-1 Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Exhaust Fan Information FAN NUMBER FAN SIZE FAN MANUFACTURER MOTOR MANUFACTURER EFFICIENCY POWER FACTOR Exhaust Fan Conditions Required Actual CFM-Fan Fan Static Pressure Motor HP Brake Horsepower Motor RPM Motor (Volts/Phase) Motor Amps Fan RPM Service Factor MOTOR SHEAVE % OPEN FAN SHEAVE DRIVE BELTS V.F.D. HERTZ SET POINT OPERATING STATIC PRESSURE SET POINT KEF-1 DU180HFA CAPTIVEAIRE SYSTEMS TECO FR: 184T 3300 3320 1.180 0.940 2.000 2.000 2.50 0.88 0.81 1165 N/A 026 230 3 226 3 7.51 7.51 7.51 6.62 6.75 6.71 D.D. D.D. 026 1.15 DIRECT DRIVE D.D. DIRECT DRIVE DIRECT DRIVE 66.80 N/A 26 026 D.D. = DIRECT DRIVE FAN May 20, 2024 PROJECT DESCRIPTION Static Pressure Profile Luna Grill - Pavilion at La Quinta KEF-1 S.P. PROFILE Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 EF EA A B -0.81 0.13 AB 27 May 20, 2024 PROJECT DESCRIPTION Air Distribution Schedule Luna Grill - Pavilion at La Quinta KEF-1 EXHAUST AIR Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Data Req. Req. Actual Actual Room No. Terminal No. Terminal Size K VEL CFM VEL CFM KITCHEN FLTR-1 20 X 16 1.780 199 355 041 KITCHEN FLTR-2 20 X 16 1.780 208 370 KITCHEN FLTR-3 20 X 16 1.780 205 365 KITCHEN FLTR-4 20 X 16 1.780 225 400 KITCHEN FLTR-5 20 X 16 1.780 233 415 KITCHEN FLTR-6 20 X 16 1.780 222 395 KITCHEN FLTR-7 20 X 16 1.780 200 355 KITCHEN FLTR-8 20 X 16 1.780 186 330 KITCHEN FLTR-9 20 X 16 1.780 188 335 Totals: 3320 041 REQUIRED CFM NOT LISTED FOR AIR DISTRIBUTION 28 May 20, 2024 PROJECT DESCRIPTION Exhaust Fan Equipment Test Luna Grill - Pavilion at La Quinta KEF-2 Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Exhaust Fan Information FAN NUMBER FAN SIZE FAN MANUFACTURER MOTOR MANUFACTURER EFFICIENCY POWER FACTOR Exhaust Fan Conditions Required Actual CFM-Fan Fan Static Pressure Motor HP Brake Horsepower Motor RPM Motor (Volts/Phase) Motor Amps Fan RPM Service Factor MOTOR SHEAVE % OPEN FAN SHEAVE DRIVE BELTS V.F.D. HERTZ SET POINT OPERATING STATIC PRESSURE SET POINT KEF-2 DU180HFA CAPTIVEAIRE SYSTEMS TECO FR: 182T 2100 2155 1.002 0.790 1.500 1.500 1.68 0.87 0.81 1170 N/A 026 230 3 225 3 6.01 6.01 6.01 4.46 4.63 4.58 D.D. D.D. 026 1.15 DIRECT DRIVE D.D. DIRECT DRIVE DIRECT DRIVE 52.50 N/A 29 026 D.D. = DIRECT DRIVE FAN May 20, 2024 PROJECT DESCRIPTION Static Pressure Profile Luna Grill - Pavilion at La Quinta KEF-2 S.P. PROFILE Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 EF EA A B -0.68 0.11 AB 30 May 20, 2024 PROJECT DESCRIPTION Air Distribution Schedule Luna Grill - Pavilion at La Quinta KEF-2 EXHAUST AIR Las Vegas Corporate Headerquarters 4721 E. Hunter Ave Anaheim, CA 92807 Anaheim Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509 Data Req. Req. Actual Actual Room No. Terminal No. Terminal Size K VEL CFM VEL CFM KITCHEN FLTR-1 20 X 16 1.780 199 355 041 KITCHEN FLTR-2 20 X 16 1.780 205 365 KITCHEN FLTR-3 20 X 16 1.780 219 390 KITCHEN FLTR-4 20 X 16 1.780 202 360 KITCHEN FLTR-5 20 X 16 1.780 188 335 KITCHEN FLTR-6 20 X 16 1.780 197 350 Totals: 2155 041 REQUIRED CFM NOT LISTED FOR AIR DISTRIBUTION 31 TH I S D R A W I N G I S A S C H E M A T I C D I A G R A M , F O R R E F E R E N C E O N L Y , T H A T C O R R E S P O N D S T O T H E T E S T A N D B A L A N C E A N A L Y S I S R E P O R T P R O V I D E D B Y A M E R I C A N A I R B A L A N C E C O M P A N Y A N D S H O U L D O N L Y B E U S E D F O R C O R R E L A T I O N T O T H E T E S T A N D B A L A N C E A N A L Y S I S R E P O R T . THIS DRAWING AND THE INFORMATION HERE-IN RELATING TO AMERICAN AIR BALANCE COMPANY AND ITS CLIENT HAS BEEN FURNISHED IN CONFIDENCE FOR THE PRIVATE USE OF THE AUTHORIZED PERSONNEL ONLY. NO PART HEREOF SHALL BE COPIED, DUPLICATED, DISTRIBUTED, DISCLOSED, OR MADE AVAILABLE TO OTHERS OR USED TO ANY EXTENT WHATSOEVER EXCEPT AS EXPRESSLY AUTHORIZED IN WRITING BY AMERICAN AIR BALANCE COMPANY AND ITS CLIENT. ANY PERSON, FIRM, OR CORPORATION RECEIVING THIS DOCUMENT SHALL BE DEEMED TO HAVE AGREED TO THE FOREGOING RESTRICTIONS. THIS DRAWING AND THE INFORMATION HERE-IN RELATING TO AMERICAN AIR BALANCE COMPANY AND ITS CLIENT HAS BEEN FURNISHED IN CONFIDENCE FOR THE PRIVATE USE OF THE AUTHORIZED PERSONNEL ONLY. NO PART HEREOF SHALL BE COPIED, DUPLICATED, DISTRIBUTED, DISCLOSED, OR MADE AVAILABLE TO OTHERS OR USED TO ANY EXTENT WHATSOEVER EXCEPT AS EXPRESSLY AUTHORIZED IN WRITING BY AMERICAN AIR BALANCE COMPANY AND ITS CLIENT. ANY PERSON, FIRM, OR CORPORATION RECEIVING THIS DOCUMENT SHALL BE DEEMED TO HAVE AGREED TO THE FOREGOING RESTRICTIONS. TH I S D R A W I N G I S A S C H E M A T I C D I A G R A M , F O R R E F E R E N C E O N L Y , T H A T C O R R E S P O N D S T O T H E T E S T A N D B A L A N C E A N A L Y S I S R E P O R T P R O V I D E D B Y A M E R I C A N A I R B A L A N C E C O M P A N Y A N D S H O U L D O N L Y B E U S E D F O R C O R R E L A T I O N T O T H E T E S T A N D B A L A N C E A N A L Y S I S R E P O R T . Phone: (714) 693-3700 Las Vegas Fax: (702) 294-1306 Phone: (702) 255-7331 Fax: (714) 693-9509 Anaheim, CA 92807 4721 E. Hunter Ave. Headquarters Anaheim Online mail@aabctab.com www.aabctab.com Air Balance Co., LLC American Schematic Diagram Based On Project Reference Sheet Number Project Number ScaleDate Sheet Title Project Mechanical EngineerProject Architect Of Sheets Drawn by Project Title LUNA GRILL PAVILION AT LA QUINTA 79124 HIGHWAY 111 LA QUINTA, CALIFORNIA 92253 JAG 246404 05-20-24 NTS RE AIR DISTRIBUTION PLAN M101 01 01 RECTANGULAR SUPPLY AIR RISER CIRCULAR SUPPLY AIR RISER RECTANGULAR SUPPLY AIR DIFFUSER RECTANGULAR SUPPLY AIR DROP CIRCULAR SUPPLY AIR DIFFUSER CIRCULAR SUPPLY AIR DROP DESCRIPTIONS TEST AND BALANCE ANALYSIS LEGEND SYMBOL CIRCULAR RETURN AIR RISER CIRCULAR RETURN AIR GRILLE CIRCULAR RETURN AIR DROP RECTANGULAR RETURN AIR RISER RECTANGULAR RETURN AIR GRILLE RECTANGULAR RETURN AIR DROP RECTANGULAR EXHAUST AIR RISER RECTANGULAR EXHAUST AIR DROP CIRCULAR EXHAUST AIR RISER RECTANGULAR EXHAUST AIR GRILLE CIRCULAR EXHAUST AIR GRILLE CIRCULAR EXHAUST AIR DROP CIRCULAR OUTSIDE AIR RISER CIRCULAR OUTSIDE AIR DROP CIRCULAR OUTSIDE AIR GRILLE RECTANGULAR OUTSIDE AIR RISER RECTANGULAR OUTSIDE AIR DROP RECTANGULAR OUTSIDE AIR GRILLE DUCT DETECTOR REFERENCEDD 1 DUCT DETECTOR EQUIPMENT REFERENCE TRAVERSED FAN REFERENCE DUCT TRAVERSE REFERENCE EXHAUST AIR GRILLE REFERENCE EXHAUST FAN REFERENCE OUTSIDE AIR GRILLE REFERENCE OUTSIDE AIR FAN REFERENCE RETURN AIR GRILLE REFERENCE RETURN FAN REFERENCE SUPPLY FAN REFERENCE SUPPLY AIR VAV BOX REFERENCE SUPPLY AIR DIFFUSER REFERENCE AH-1 1-1 AH-1 R-1 EF-1 1 AH-1 OSA-1 AH-1 DT-1 U P P L Y S T U R N E R H A U S X E T S A O I S M C AH-1 RTU-2 RTU-2 4 RTU-2 1 RTU-2 2 RTU-2 3 RTU-2 5 RTU-2 6 RTU-1 RTU-1 1 RTU-1 2 RTU-1 3 RTU-1 8 RTU-1 7 RTU-1 6 RTU-1 5 RTU-1 4 RTU-2 R-2 RTU-2 R-1 RTU-1 R-1 RTU-1 R-2 RTU-1 R-3 RTU-3 1 RTU-3 2 RTU-3 3 RTU-3 5 RTU-3 4 MUA-1 1 KEF-1 FLT-1-9 KEF-2 FLT-1-6 RTU-3 R-1 RTU-3 R-2 RTU-3 R-3 EF-1B 1 EF-1A 1 EF-1A EF-1B HOOD-1 HOOD-2