BCOM2023-0039 Test and Balance ReportTest and Balance Analysis Report
FOR
Luna Grill - Pavilion at La Quinta
79124 Highway 111
La Quinta, CA 92253
Architect
Engineer JAG
Contractor South Bay Mechanical Services
This is to certify that American Air Balance Co., LLC has balanced the systems described herein to theiroptimum performance capabilities, unless otherwise noted in the project summary. The testing and balancinghas been performed in accordance with the standard reTuirements and procedures of the Associated Air Balance Council and the results of these tests are herein recorded.
Certification #246404
DateMay 20, 2024
ApprovedBob Conboy Jr.
AABC National
Performance Guaranty
Pursuant to the agreement between
American Air Balance Co., LLC
AABC Certified Testing & Balancing Agency
and South Bay Mechanical Services
Client
All systems shall be tested and balanced in accordance with the project plans and
specifications and to the optimum performance capabilities of the equipment. Testing and balancing
shall be done in accordance with the standards published by the Associated Air Balance Council.
If the Agency listed above fails to comply with the specifications for any reason other than
termination of business by the AABC agency or equipment malfunction or inadequacy which prevents
proper balancing of the systems, AABC will investigate and, if warranted, will provide supervisory
personnel to assist the member Agency to perform work in accordance with AABC Standards. The
supervision will be provided at no additional cost to building owner.
This Guaranty is valid for one year from the date of submission of a test and balance report,
provided the Agency is a current member of AABC, and may only be invoked in writing by the building
owner, architect, or engineer of record. The Guaranty is limited to the terms and conditions as stated
herein.
Project Name Luna Grill - Pavilion at La Quinta
Address 79124 Highway 111
La Quinta, CA 92253
Name of Engineer N/L
Engineering Firm JAG
Address
Irvine, CA 92618
Email N/L
Date 05/20/24 Associated Air
Balance Council
TBE # 21-01-123 AABC National Headquarters
1518 K Street, N.W.
By Bob Conboy, Jr. Washington, D.C. 20005
AABC Certified TBE
15 Hubble # 200
Corporate Headquarters
American Air Balance Co.., LLC phone: 714-693-3700 fax: 714-693-9509 www. aabctab.com mail@aabctab.com
Test and Balance Analysis
Report Certification
for
Luna Grill - Pavilion at La Quinta
79124 Highway 111
La Quinta, CA 92253
This is to certify that American Air Balance Co., LLC has balanced the
systems described herein to their optimum performance capabilities,
unless otherwise noted in the project summary. The testing and balancing
has been performed in accordance with the standard requirements and
procedures of the Associated Air Balance Council and the results of these
tests are herein recorded.
Certification Number
246404
Date
May 20, 2024
Approved
Bob Conboy Jr., Test and Balance Engineer
Supervisor Managing Technician
Michael Totten Brandon Berry
5obert A. Conboy, -r., TBE
American Air Balance Co., LLC
Ϯϭ-Ϭϭ-ϭϮϯ
Michael -. Totten, TBE
American Air Balance Co., LLC
ϭϴ-Ϭϭ-ϭϭϰ
Brandon L. Berry
American Air Balance Co., LLC
-0-1
Instrument Manufacturer Model Serial #Calib. Date
Air Data Multi Meter Shortridge ADM 870C M17476 12/07/23
Amp Volt Meter Fluke 333 91756564 05/12/24
Drill Dewalt DCD771C2 303836 N/A
Drill Charger Dewalt DW9116 N/A
Flow Hood Shortridge 8405 N/A
Hydrodata Meter Shortridge HDM-250 W20010 03/16/24
Ladder Husky 6'N/A N/A
Laptop Computer Microsoft Surface Pro 6 023774594253 N/A
Mobile Phone Apple iPhone SE3 64gb HVHGJYJ22G N/A
Noncontact Thermometer Ray Tek Mini Temp RAYMT4U RAYL000669536 08/29/23
Pitot Tube Dwyer 48"160-48 N/A
Pitot Tube Dwyer 24"160-24 N/A
Psychrometer Probe Fieldpiece JL3RH 22036149AABH 07/19/23
Sound Meter Lutron SL-4010 Q214198 N/A
Tac Chronometer Shimpo MT-200 167B5020P N/A
TEST AND BALANCE INSTRUMENTATION
The following instruments were used to successfully measure and set each device on this project.
Page 1 of 1
Anaheim
Phone: (714) 693-3700 / Fax: (714) 693-9509
Corporate Headquarters
4721 E. Hunter Ave.
Anaheim, CA 92807
mail@aabctab.com
Las Vegas
Phone: (702) 255-7331 / Fax: (702) 294-1306
Definitions of Abbreviations, Terminology, Symbols & Conversions
#: Symbol for PSI or Pounds per square inch
Δ: Symbol for Delta - difference, net decrease or increase
A:Nameplate Amps
AABC: Associated Air Balance Council
ABS:Absolute
AC or ACU: Air Conditioner or Air Conditioning Unit
ACCU: Air-Cooled Condensing Unit
ACGIH: American Conference of Governmental Hygienists
ACH Air Changes Per Hour
ACT:Actual
ADP: Apparatus Dew Point
AEE: Association of Energy Engineers
AFE: Association of Facility Engineering
AHU: Air Handling Unit
AK: Free Area Factor
ALT:Altitude
AMB:Ambient
AMP:Ampere
ANSI: American National Standards Institute
AP: Access Point
A-Scale or Db(A):A filtering system which roughly matches the response characteristics
of the human ear
ASHRAE: American Society of Heating, Air Conditioning and Refrigeration
Engineers
ASTM: American Society for Testing and Materials
ATM:Atmosphere
AVG:Average
AZ: Azimuth
B:Boiler
BHP: Brake Horsepower
BP:Boiling Point
BSC: Building Systems Commissioning
BTU: British Thermal Unit
BTUH: British Thermal Units per Hour
C:Celsius
C to C: Center to Center
CAV: Constant Air Volume or Continuous Air Volume
CC:Cooling Coil
CCW:Counter-Clockwise
CD:Ceiling Diffuser
CEG: Ceiling Exhaust Grille
CER: Ceiling Exhaust Register
CFM: Cubic Feet per Minute
CH:Chiller
Anaheim
Phone: (714) 693-3700 / Fax: (714) 693-9509
Corporate Headquarters
4721 E. Hunter Ave.
Anaheim, CA 92807
mail@aabctab.com
Las Vegas
Phone: (702) 255-7331 / Fax: (702) 294-1306
Definitions of Abbreviations, Terminology, Symbols & Conversions
CHW or CHWS: Chilled Water Supply
CHWR: Chilled Water Return
CM² Square Centimeters
CM/SEC Centometers per Second
CMD: Count Mean Diameter
Cp Specific Heat: water = 1.0 BTU / lb per °F air = 0.24 BTU / lb per °F
CP or P: Circulating Pump
CPT: Capacity Performance Testing (Building Commissioning)
CR: Ceiling Register
CRR: Ceiling Return Register
CT: Cooling Tower
CU: Condensing Unit
CUH: Cabinet Unit Heating
CV: Specific Heat at Constant Volume
CV: Valve Constant
CW: Chilled Water
CWR: Condenser Water Return
CW or CWS: Condenser Water Supply
DAT: Discharge Air Temperature
Db: Decibel
DB: Dry Bulb
DC: Direct Current
DD: Direct Drive
Delta (Δ): Difference - net decrease or increase
DIA: Diameter
DNL: Data Not Listed
DOP: Dioctyl Phthalate, an aerosol generated by blowing air through liquid
Dioctyl Phthalate (mean particle diameter is between 0.2 and 0.4
microns)
Δ P: Differential Pressure or Pressure Drop, net change in Pressure
DPT: Dew Point Temperature
DSTD: Standard Air Density, equals 0.075 lb / Cu. Ft. @ 29.92 in, Hg
Δ T: Differential Temperature, net change in temperature
EAT: Entering Air Temperature
EC: Evaporative Cooler
Economizer: Controls and componentry that allow an air handler to logically utilize
outdoor air for cooling as opposed to the use of mechanical cooling
EDC: Electric Duct Coil
EDH: Electric Duct Heater
EER: Energy Efficiency Ratio
EF or E: Exhaust Fan
EFF: Efficiency
EG: Exhaust Grille
EMCS: Energy Management Control System(s)
Anaheim
Phone: (714) 693-3700 / Fax: (714) 693-9509
Corporate Headquarters
4721 E. Hunter Ave.
Anaheim, CA 92807
mail@aabctab.com
Las Vegas
Phone: (702) 255-7331 / Fax: (702) 294-1306
Definitions of Abbreviations, Terminology, Symbols & Conversions
EMF: Electromotive Force
EMS Energy Management System(s)
ENT: Entering
EP: Electro-Pneumatic Switches
ER: Exhaust Register
ESD: Electrostatic Discharge
ESP: External Static Pressure
EWT: Entering Water Temperature
°F: Degrees Fahrenheit
F to F: Face to Face
FAF: Forced Air Fan
FCU: Fan Coil Unit
FDA: Food and Drug Administration
FG: Floor Grille
FH: Fume Hood
FIV: Field Installation Verification (Building Commissioning)
FLA: Full Load Amperage
FLTS: Filters
FP: Freezing Point
FPB: Fan Powered Box
FPM: Feet Per Minute
FPS: Feet Per Second
FPT: Functional Performance Testing (Building Commissioning)
FR: Floor Register
FTU: Fan Terminal Unit
G or g: Gravitational Constant
GA: Gauge
GC: General Contractor
GPH: Gallons Per Hour
GPM: Gallons Per Minute
GR: Grain - measurement of actual moisture in an air sample, 7000 grains
= one pound of water
GSD: Geometric Standard Division
H: Enthalpy
H2O: Water
HC: Heating Coil
HD: Head pressure measured in inches or feet of water
Heater O.L.: Thermal Overload protection for motors located at the motor starter
HEPA: High Efficiency Particulate Arrestance
HEPA Filter: High Efficiency Particulate Air Filter
Hg: Mercury
HOA: Hand/Off/Auto switch
HP: HorsePower
HPS: High Pressure Steam
Anaheim
Phone: (714) 693-3700 / Fax: (714) 693-9509
Corporate Headquarters
4721 E. Hunter Ave.
Anaheim, CA 92807
mail@aabctab.com
Las Vegas
Phone: (702) 255-7331 / Fax: (702) 294-1306
Definitions of Abbreviations, Terminology, Symbols & Conversions
HPU: Heat Pump Unit
HRC: Heat Recovery Coil or Heat Reclaim Coil
HTHW: High Temperature Hot Water
HV: Heating Ventilator
HVAC: Heating, Ventilating & Air Conditioning
HW: Hot Water
HWR: Hot Water Return or Heating Water Return
HWS: Hot Water Supply or Heating Water Supply
HX: Heat exchanger
Hydronic: Indicates the use or conveyance of liquid for thermal transfer
Hz: Hertz
I.D.: Inside Diameter
I/O: Input / Output
ID: Impeller Diameter (pump)
IES: Institute of Environmental Sciences
IV: Inlet Vanes
K: Correction Factor
KW: Kilowatts
KWH: Kilowatt Hour
LAT: Leaving Air Temperature
L/S: Lter per Second
LD: Linear Diffuser
LF: Linear Foot
LPS: Low Pressure Steam
LPS: Liters Per Second
LTD: Least Temperature Difference
LTHW: Low Temperature Hot Water
LV or LVG: Leaving
LWG: Low Wall Grille
LWR: Low Wall Register
LWT: Leaving Water Temperature
MAU or MUA: Make-up Air Unit or Make-Up Air
MAX: Maximum
MB: Mixing Box
MBH: Mega BTU's per Hour
MET: Mean Effective Temperature
Micron: 1.0 x 10-6 meter
Mil.: 2.54 x 10-5 meter
MIN Minimum
MM: Millimeters
MM X MM: Millimeters by Millimeters
MMD: Mass Mean Diameter
MTD: Mean Temperature Difference
MVD: Manual Volume Damper
Anaheim
Phone: (714) 693-3700 / Fax: (714) 693-9509
Corporate Headquarters
4721 E. Hunter Ave.
Anaheim, CA 92807
mail@aabctab.com
Las Vegas
Phone: (702) 255-7331 / Fax: (702) 294-1306
Definitions of Abbreviations, Terminology, Symbols & Conversions
MZ: MultiZone
N/A: Not Applicable or Not Available
NASA: National Aeronautics and Space Administration
NC: Noise Criteria or Normally Closed
NIC: Not in Contract
N/L: Not Listed
NM: Not Measured
NO: Normally Open
NPFC: Naval Publications and Forms Center
NPSHA: Net Positive Suction Head Available
NS: Not Specified
NSF: National Sanitation Foundation
NTIS: National Technical Information Service
NTS: Not To Scale
NVL: No Valid Location for Testing
OB: Octave Band - a range of frequency where the highest frequency of
the band is double the lowest frequency of the band. The band is
usually specified by the center frequency. The preferred octave
bands are designated by the following center frequencies: 31.5, 63,
125, 250, 500, 1000, 2000, 4000, 8000, 16000.
OBD: Opposed Blade Damper
O.D.: Outside Diameter
OAT: Outside Air Temperature
OPT: Operational Performance Testing (Building Commissioning)
O.S.A. or OA: Outside Air
P.E.: Professional Engineer
P: Circulating Pump
Pa: Pascal - 1 Pascal = 6.894 x 10-³ psi
PCT: Percent
PD: Differential Pressure or Pressure Drop
PE: Pneumatic Electric Switch
PF: Power Factor
PH: Phase(s)
PHC: PreHeat Coil
PMP: Circulating Pump
PNC: Preferred Noise Criterion Curves
PPM: Parts Per Million
PSI: Pounds per Square Inch
PSIA: Pounds per Square Inch Absolute
PSIG: Pounds per Square Inch Gauge
PSL: Polystyrene Latex Spheres - used to generate an aerosol challenge
medium where electronic & semi-conductor products are
manufactured
PWR: Power
Anaheim
Phone: (714) 693-3700 / Fax: (714) 693-9509
Corporate Headquarters
4721 E. Hunter Ave.
Anaheim, CA 92807
mail@aabctab.com
Las Vegas
Phone: (702) 255-7331 / Fax: (702) 294-1306
Definitions of Abbreviations, Terminology, Symbols & Conversions
R: Rankine (absolute temperature) - Rankine = 1.8 Kelvin
RA: Return Air
RAT: Return Air Temperature
RCC: Room Criterion Curves
RD: Round (for sizes)
REQ: Required
RF: Return air Fan
RH: Relative Humidity
RHC: ReHeat Coil
RPM: Revolutions Per Minute
RTU: Roof Top Unit
S: Entropy
SA: Supply Air
SAR: Supply Air Register
SAT: Supply Air Temperature
SD: Smoke detector or Smoke Damper
SEER: Season Energy Efficient Ratio
SEF: Smoke Exhaust Fan
SF (AIR): Supply Fan
SF (ELECT): Service Factor
SF (MOTOR): Safety Factor by which actual amps can exceed rated amperage, at
the expense
of expected motor life
SHC: Steam Heating Coil
SMACNA: Sheet Metal and Air Conditioning Contractors National Association
SP: SetPoint
SP: Static Pressure
S.P. "W.C.": Static Pressure resistance measured in inches of Water Column
SP VOLUME: Specific Volume
SPF: Stairwell Pressurization Fan
SQ: Square
STD: Standard
SWG: SideWall Grille
SWR: SideWall Register
SWS: SideWall Supply
T STAT: Thermostat
TAB: Testing, Adjusting and Balancing
TD: Differential Temperature - Net temperature decrease or increase
TDH: Total Dynamic Head or Total Dead Head (pressure differential when
flow equals zero)
T.I. Travel In
T.O. Travel Out
THROW: Distance an air stream travels after leaving an air outlet before the
air stream velocity is reduced to approximately 50 fpm
Anaheim
Phone: (714) 693-3700 / Fax: (714) 693-9509
Corporate Headquarters
4721 E. Hunter Ave.
Anaheim, CA 92807
mail@aabctab.com
Las Vegas
Phone: (702) 255-7331 / Fax: (702) 294-1306
Definitions of Abbreviations, Terminology, Symbols & Conversions
TON (Air Cond.): Equals 12,000 BTU per hour
TP: Traverse Point or Test Point.
TP (Motor): Thermal Protected (opens motor circiutry if rated amps are
exceeded)
TR:Thermal Resistance
TSP: Total Static Pressure
UH:Unit Heater
ULPA Filter: Ultra Low Penetration Air Filter
UV: Unit Ventilator
V: Volt or Voltage
VA:Volt Atmossphere
VAC:Vacuum
VAV: Variable Air Volume
VD:Volume Damper
VEL:Velocity
VFD: Variable Frequency Drive (electric motor speed controller)
VP: Velocity Pressure
W:Watts
WB:Wet Bulb
W.G.:Water Gage
WT:Weight
WTR:Water
Z:Zone
Zoning: The practice of dividing a building into small sections for heating
and cooling control, selected so that one thermostat can be used to
determine each section's heating & cooling requirements
Anaheim
Phone: (714) 693-3700 / Fax: (714) 693-9509
Corporate Headquarters
4721 E. Hunter Ave.
Anaheim, CA 92807
mail@aabctab.com
Las Vegas
Phone: (702) 255-7331 / Fax: (702) 294-1306
Page 1 of 3
Luna Grill - Pavilion at La Quinta
La Quinta, CA 92253
CERT #246404
American Air Balance Co., Inc is a Testing and Balancing Agency that engages in testing,
adjusting and balancing of air and water moving systems. American Air Balance Co., Inc. does
not undertake the construction of HVAC systems, fans, ductwork, terminal boxes, dampers, air
distribution or other components. Additionally, our firm does not undertake construction of other
building systems, such as walls, doors, windows, lights, that may have a direct affect on the
performance of the system(s) being tested.
This report represents the optimal obtainable results given the limits of the installed system and
the existing conditions at the time of certification. The data and information provided herein is
factual, accurate and based upon the information provided in addition to the existing conditions
of the building at the time the tests were conducted.
Each system’s component installation and design dictates limitations and test parameters. System
specific procedures must be followed to duplicate the results listed herein. American Air Balance
Co., Inc. employs the standards and procedures per the latest version of the AABC National
Standards and Test and Balance Procedures, as applicable, unless otherwise dictated by the
project specifications and/or project system specific requirements.
Verification of the report contents must be carried out within 45 days of certification and shall be
accomplished by our Field Technician, using the same instruments, under the same test
conditions used to develop this report; otherwise this project warranty is null and void. Our
office must receive requests for field verification in writing within 30 days of certification.
American Air Balance Co., Inc. makes no representation or warranty that the systems and data
contained herein will remain in the condition recorded beyond the date of certification.
Adjustment(s), change(s) and/or tampering with component of the systems will affect the values
listed herein. Changes, modifications and/or adjustment to the building structure, systems and/or
sub systems, including but not limited to Architectural, Mechanical, Electrical, Plumbing,
Building Automation Controls and Fire/Life Safety Alarm Systems will adversely affect the
integrity of the systems and alter the data listed herein. Any such changes void American Air
Balance Co., Inc.’s warranty and the AABC National Performance Guaranty.
Proper building and HVAC system(s) maintenance must be followed to maintain efficient
conditions. Improper system maintenance directly affects system performance.
Anaheim
Phone: (714) 693-3700 / Fax: (714) 693-9509
Corporate Headquarters
4721 E. Hunter Ave.
Anaheim, CA 92807
mail@aabctab.com
Las Vegas
Phone: (702) 255-7331 / Fax: (702) 294-1306
Page 2 of 3
Explanation of “K” Value and Flow Hood Readings
Air distribution was read with a Shortridge Flow Hood; Air Data Multi-Meter, model ADM-860,
where possible, and where 1.0 is listed as the effective area, “K” in our report, unless otherwise
noted. This flow hood is a direct reading instrument that compensates and corrects for hood
backpressure, altitude, density and temperature when appropriate; therefore a 1.0 is listed as the
effective area. The velocity listed in this report reflects the velocity through the flow hood and
not the diffuser neck or face.
Scope of Work
American Air Balance Co., Inc. has been requested to provide a Test and Balance for the above
referenced project. This work is inclusive of:
• Certification of Air Moving System.
• Title 24.
Project Specific Comments
This section of our report is used to describe project special conditions, system observations
and/or operational comments. At times, as applicable, items that remain outstanding and/or
values that are not with the allowable project tolerances are footnoted on each individual test
sheet will also be listed herein.
American Air Balance Co., Inc. has noted the following upon conclusion of the Test and Balance
of this project:
General Notes:
• All air moving equipment and associated air distribution have been measured, balanced,
and recorded under normal operating conditions.
• All final filters were inspected and confirmed to be installed and clean of any debris.
Anaheim
Phone: (714) 693-3700 / Fax: (714) 693-9509
Corporate Headquarters
4721 E. Hunter Ave.
Anaheim, CA 92807
mail@aabctab.com
Las Vegas
Phone: (702) 255-7331 / Fax: (702) 294-1306
Page 3 of 3
Grease Duct Velocity Calculations and Final Measured Numbers:
KEF-1
• Shaft Size: 18” Round
• Area (Sq. Ft.): 1.77
• Velocity (Feet Per Minute): 1876
• Airflow (CFM): 3320
KEF-2
• Shaft Size: 14” Round
• Area (Sq. Ft.): 1.07
• Velocity (Feet Per Minute): 2014
• Airflow (CFM): 2155
Luna Grill - Pavilion at La Quinta
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
TABLE OF CONTENTS
-------------------------------
RTU-1 - Air Moving Equipment Test 1......................................................................
RTU-1 S.P. PROFILE - Static Pressure Profile 2.................................................
RTU-1 OUTSIDE AIR - Air Distribution Schedule 3..............................................
RTU-1 SUPPLY AIR - Air Distribution Schedule 4................................................
RTU-1 RETURN AIR - Air Distribution Schedule 5...............................................
RTU-2 - Air Moving Equipment Test 6......................................................................
RTU-2 S.P. PROFILE - Static Pressure Profile 7.................................................
RTU-2 OUTSIDE AIR - Air Distribution Schedule 8..............................................
RTU-2 SUPPLY AIR - Air Distribution Schedule 9................................................
RTU-2 RETURN AIR - Air Distribution Schedule 10...............................................
RTU-3 - Air Moving Equipment Test 11......................................................................
RTU-3 S.P. PROFILE - Static Pressure Profile 12.................................................
RTU-3 OUTSIDE AIR - Air Distribution Schedule 13..............................................
RTU-3 SUPPLY AIR - Air Distribution Schedule 14................................................
RTU-3 RETURN AIR - Air Distribution Schedule 15...............................................
MUA-1 - Air Moving Equipment Test 16.....................................................................
MUA-1 S.P. PROFILE - Static Pressure Profile 17................................................
MUA-1 SUPPLY AIR - Air Distribution Schedule 18...............................................
TEMPERATURE DATA - Temperature Test 19....................................................
EF-1A - Exhaust Fan Equipment Test 20....................................................................
EF-1A S.P. PROFILE - Static Pressure Profile 21.................................................
EF-1A EXHAUST AIR - Air Distribution Schedule 22..............................................
EF-1B - Exhaust Fan Equipment Test 23....................................................................
EF-1B S.P. PROFILE - Static Pressure Profile 24.................................................
EF-1B EXHAUST AIR - Air Distribution Schedule 25..............................................
KEF-1 - Exhaust Fan Equipment Test 26....................................................................
KEF-1 S.P. PROFILE - Static Pressure Profile 27.................................................
KEF-1 EXHAUST AIR - Air Distribution Schedule 28..............................................
KEF-2 - Exhaust Fan Equipment Test 29....................................................................
KEF-2 S.P. PROFILE - Static Pressure Profile 30.................................................
KEF-2 EXHAUST AIR - Air Distribution Schedule 31..............................................
May 20, 2024
PROJECT
DESCRIPTION
Air Moving Equipment Test
Luna Grill - Pavilion at La Quinta
RTU-1
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Fan Information
FAN NUMBER SERVING
FAN MANUFACTURER MODEL
FAN SERIAL NUMBER MOTOR MANUFACTURER
CFM
Required Actual
Total - Air Dist.
Return
O.S.A
S.P.
Required Actual
Suction
Discharge
Total
EFFICIENCY POWER FACTOR
Conditions
Required Actual
Motor (HP/RPM)
Motor (Volts/Phase)
Motor Amps
Brake HorsePower
Service Factor
Fan RPM
MOTOR SHEAVE % OPEN
FAN SHEAVE DRIVE BELTS
CTR. TO CTR.MOTOR
T.I. T.O.
V.F.D. HERTZ SET POINT OPERATING STATIC PRESSURE SET POINT
RTU-1 DINING
CARRIER XYE08A2B3AA1A111A2
N2G3763953 BALDOR FR: 56HZ
2850 2875 N/A -1.02
2440 2445 N/A 0.49
410 430
External
0.60
Total SP
1.51
2.40 1750 2.40 1761
230 3 213 3
7.20 7.20 7.20 6.29 6.35 6.41
1.91 0.87 0.70
1.15
N/L 773 025
1VL44 X 5/8" 100%
AK74 X 1.0" (1) A-48
16.75 2.50 3.00
60.0 N/A
1
025 REQUIRED INFORMATION IS NOT LISTED.
May 20, 2024
PROJECT
DESCRIPTION
Static Pressure Profile
Luna Grill - Pavilion at La Quinta
RTU-1 S.P. PROFILE
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
SF
OSA
RA
FI
L
T
E
R
CO
O
L
I
N
G
C
O
I
L
SA
A B C
-0.79 -1.02 0.49
ABC
2
May 20, 2024
PROJECT
DESCRIPTION
Air Distribution Schedule
Luna Grill - Pavilion at La Quinta
RTU-1 OUTSIDE AIR
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Data
Req. Req. Actual Actual
Room No. Terminal No. Terminal Size K VEL CFM VEL CFM
RTU-1 OSA-1 32 X 9 2.000 205 410 215 430
Totals:410 430
3
May 20, 2024
PROJECT
DESCRIPTION
Air Distribution Schedule
Luna Grill - Pavilion at La Quinta
RTU-1 SUPPLY AIR
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Data
Req. Req. Actual Actual
Room No. Terminal No. Terminal Size K VEL CFM VEL CFM
DINING 1 18 X 10 1.000 500 500 510 510
DINING 2 18 X 10 1.000 500 500 485 485
DINING 3 18 X 10 1.000 500 500 520 520
RESTROOM 1 4 6 X 6 1.000 75 75 75 75
RESTROOM 2 5 6 X 6 1.000 75 75 75 75
DATA ROOM 6 12 X 12 1.000 200 200 205 205
DINING 7 18 X 10 1.000 500 500 490 490
DINING 8 18 X 10 1.000 500 500 515 515
Totals:2850 2875
4
May 20, 2024
PROJECT
DESCRIPTION
Air Distribution Schedule
Luna Grill - Pavilion at La Quinta
RTU-1 RETURN AIR
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Data
Req. Req. Actual Actual
Room No. Terminal No. Terminal Size K VEL CFM VEL CFM
DINING R-1 20 X 20 1.000 1220 1220 1135 1135
028
DINING R-2 20 X 20 1.000 1220 1220 1115 1115
028
DATA ROOM R-3 12 X 12 1.000 200 200 195 195
Totals:2640 2445
028 THE RETURN AIR QUANTITY WAS PROPORTIONED TO ALLOW FOR DESIGN MINIMUM O.S.A.
5
May 20, 2024
PROJECT
DESCRIPTION
Air Moving Equipment Test
Luna Grill - Pavilion at La Quinta
RTU-2
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Fan Information
FAN NUMBER SERVING
FAN MANUFACTURER MODEL
FAN SERIAL NUMBER MOTOR MANUFACTURER
CFM
Required Actual
Total - Air Dist.
Return
O.S.A
S.P.
Required Actual
Suction
Discharge
Total
EFFICIENCY POWER FACTOR
Conditions
Required Actual
Motor (HP/RPM)
Motor (Volts/Phase)
Motor Amps
Brake HorsePower
Service Factor
Fan RPM
MOTOR SHEAVE % OPEN
FAN SHEAVE DRIVE BELTS
CTR. TO CTR.MOTOR
T.I. T.O.
V.F.D. HERTZ SET POINT OPERATING STATIC PRESSURE SET POINT
RTU-2 DINING
CARRIER XYE08A2B3AA1A111A2
N2G3740407 BALDOR FR: 56HZ
2850 2885 N/A -1.05
2440 2460 N/A 0.48
410 425
External
0.60
Total SP
1.53
2.40 1750 2.40 1764
230 3 214 3
7.20 7.20 7.20 6.26 6.39 6.43
1.92 0.87 0.70
1.15
N/L 778 025
1VL44 X 5/8" 100%
AK74 X 1.0" (1) A-48
16.75 2.50 3.00
60.0 N/A
6
025 REQUIRED INFORMATION IS NOT LISTED.
May 20, 2024
PROJECT
DESCRIPTION
Static Pressure Profile
Luna Grill - Pavilion at La Quinta
RTU-2 S.P. PROFILE
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
SF
OSA
RA
FI
L
T
E
R
CO
O
L
I
N
G
C
O
I
L
SA
A B C
-0.81 -1.05 0.48
ABC
7
May 20, 2024
PROJECT
DESCRIPTION
Air Distribution Schedule
Luna Grill - Pavilion at La Quinta
RTU-2 OUTSIDE AIR
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Data
Req. Req. Actual Actual
Room No. Terminal No. Terminal Size K VEL CFM VEL CFM
RTU-2 OSA-1 32 X 9 2.000 205 410 213 425
Totals:410 425
8
May 20, 2024
PROJECT
DESCRIPTION
Air Distribution Schedule
Luna Grill - Pavilion at La Quinta
RTU-2 SUPPLY AIR
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Data
Req. Req. Actual Actual
Room No. Terminal No. Terminal Size K VEL CFM VEL CFM
DINING 1 18 X 10 1.000 475 475 490 490
DINING 2 18 X 10 1.000 475 475 475 475
DINING 3 18 X 10 1.000 475 475 465 465
DINING 4 18 X 10 1.000 475 475 485 485
DINING 5 18 X 10 1.000 475 475 490 490
DINING 6 18 X 10 1.000 475 475 480 480
Totals:2850 2885
9
May 20, 2024
PROJECT
DESCRIPTION
Air Distribution Schedule
Luna Grill - Pavilion at La Quinta
RTU-2 RETURN AIR
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Data
Req. Req. Actual Actual
Room No. Terminal No. Terminal Size K VEL CFM VEL CFM
DINING R-1 20 X 20 1.000 1220 1220 1210 1210
DINING R-2 20 X 20 1.000 1220 1220 1250 1250
Totals:2440 2460
10
May 20, 2024
PROJECT
DESCRIPTION
Air Moving Equipment Test
Luna Grill - Pavilion at La Quinta
RTU-3
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Fan Information
FAN NUMBER SERVING
FAN MANUFACTURER MODEL
FAN SERIAL NUMBER MOTOR MANUFACTURER
CFM
Required Actual
Total - Air Dist.
Return
O.S.A
S.P.
Required Actual
Suction
Discharge
Total
Conditions
Required Actual
Motor (HP/RPM)
Motor (Volts/Phase)
Motor Amps
Service Factor
Fan RPM
MOTOR SHEAVE % OPEN
FAN SHEAVE DRIVE BELTS
V.F.D. HERTZ SET POINT OPERATING STATIC PRESSURE SET POINT
RTU-3 KITCHEN
CARRIER 50GCQJ06A2A5A
1124C08243 CARRIER
2000 2015 N/A -0.65
1620 1630 N/A 0.39
380 385
External
1.20
Total SP
1.04
2.40 N/A 2.40 N/A
025, 026
208 1 213 1
N/A 9.20 N/A N/A 7.84 N/A
1.00
D.D. D.D. 026
DIRECT DRIVE D.D.
DIRECT DRIVE DIRECT DRIVE
60.0 N/A
11
025 REQUIRED INFORMATION IS NOT LISTED.
026 D.D. = DIRECT DRIVE FAN
May 20, 2024
PROJECT
DESCRIPTION
Static Pressure Profile
Luna Grill - Pavilion at La Quinta
RTU-3 S.P. PROFILE
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
SF
OSA
RA
FI
L
T
E
R
CO
O
L
I
N
G
C
O
I
L
SA
A B C
-0.43 -0.65 0.39
ABC
12
May 20, 2024
PROJECT
DESCRIPTION
Air Distribution Schedule
Luna Grill - Pavilion at La Quinta
RTU-3 OUTSIDE AIR
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Data
Req. Req. Actual Actual
Room No. Terminal No. Terminal Size K VEL CFM VEL CFM
RTU-3 OSA-1 27 X 13 2.440 156 380 158 385
Totals:380 385
13
May 20, 2024
PROJECT
DESCRIPTION
Air Distribution Schedule
Luna Grill - Pavilion at La Quinta
RTU-3 SUPPLY AIR
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Data
Req. Req. Actual Actual
Room No. Terminal No. Terminal Size K VEL CFM VEL CFM
KITCHEN 1 24 X 24 1.000 400 400 410 410
KITCHEN 2 24 X 24 1.000 400 400 405 405
KITCHEN 3 24 X 24 1.000 400 400 385 385
KITCHEN 4 24 X 24 1.000 400 400 400 400
KITCHEN 5 24 X 24 1.000 400 400 415 415
Totals:2000 2015
14
May 20, 2024
PROJECT
DESCRIPTION
Air Distribution Schedule
Luna Grill - Pavilion at La Quinta
RTU-3 RETURN AIR
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Data
Req. Req. Actual Actual
Room No. Terminal No. Terminal Size K VEL CFM VEL CFM
KITCHEN R-1 24 X 24 1.000 540 540 530 530
KITCHEN R-2 24 X 24 1.000 540 540 555 555
KITCHEN R-3 24 X 24 1.000 540 540 545 545
Totals:1620 1630
15
May 20, 2024
PROJECT
DESCRIPTION
Air Moving Equipment Test
Luna Grill - Pavilion at La Quinta
MUA-1
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Fan Information
FAN NUMBER SERVING
FAN MANUFACTURER MODEL
FAN SERIAL NUMBER MOTOR MANUFACTURER
CFM
Required Actual
Total - Air Dist.
Return
O.S.A
S.P.
Required Actual
Suction
Discharge
Total
EFFICIENCY POWER FACTOR
Conditions
Required Actual
Motor (HP/RPM)
Motor (Volts/Phase)
Motor Amps
Brake HorsePower
Service Factor
Fan RPM
MOTOR SHEAVE % OPEN
FAN SHEAVE DRIVE BELTS
V.F.D. HERTZ SET POINT OPERATING STATIC PRESSURE SET POINT
MUA-1 KITCHEN HOOD
CAPTIVEAIRE SYSTEMS A3-24D
6064933 TECO FR: 213T
4200 4265 N/A -0.35
0 0 N/A 0.33
4200 4265
External
0.50
Total SP
0.68
3.00 1175 3.00 N/A
026
230 3 226 3
9.20 9.20 9.20 5.53 5.61 5.58
2.13 0.89 0.82
1.15
D.D. D.D. 026
DIRECT DRIVE D.D.
DIRECT DRIVE DIRECT DRIVE
35.7 N/A
16
026 D.D. = DIRECT DRIVE FAN
May 20, 2024
PROJECT
DESCRIPTION
Static Pressure Profile
Luna Grill - Pavilion at La Quinta
MUA-1 S.P. PROFILE
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
SF
OSA
CO
O
L
I
N
G
C
O
I
L
FI
L
T
E
R
SA
A B C D
-0.07 -0.18 -0.35 0.33
ABCD
17
May 20, 2024
PROJECT
DESCRIPTION
Air Distribution Schedule
Luna Grill - Pavilion at La Quinta
MUA-1 SUPPLY AIR
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Data
Req. Req. Actual Actual
Room No. Terminal No. Terminal Size K VEL CFM VEL CFM
KITCHEN 1 242 X 18 30.250 139 4200 141 4265
Totals:4200 4265
18
May 20, 2024
PROJECT
DESCRIPTION
Temperature Test
Luna Grill - Pavilion at La Quinta
TEMPERATURE DATA
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Data
Ent. Ent.
EQUIPMENT ID DB WB LV DB LV WB OSA DB OSA WB
RTU-1 COOL 74.1 63.7 54.4 52.6 99.3 87.5
RTU-1 HEAT 74.4 101.3 99.3 87.5
RTU-2 COOL 74.2 63.9 54.8 52.9 99.3 87.5
RTU-2 HEAT 74.4 102.1 99.3 87.5
RTU-3 COOL 73.8 63.2 54.3 52.2 99.3 87.5
RTU-3 HEAT 74.2 100.9 99.3 87.5
MUA-1 COOL 99.3 87.5 76.8 64.5 99.3 87.5
19
May 20, 2024
PROJECT
DESCRIPTION
Exhaust Fan Equipment Test
Luna Grill - Pavilion at La Quinta
EF-1A
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Exhaust Fan Information
FAN NUMBER FAN SIZE
FAN MANUFACTURER MOTOR MANUFACTURER
Exhaust Fan Conditions
Required Actual
CFM-Fan
Fan Static Pressure
Motor HP
Motor RPM
Motor (Volts/Phase)
Motor Amps
Fan RPM
Service Factor
MOTOR SHEAVE % OPEN
FAN SHEAVE DRIVE BELTS
V.F.D. HERTZ SET POINT OPERATING STATIC PRESSURE SET POINT
EF-1A SP-B150-QD
GREENHECK GREENHECK
80 85
0.100 0.120
5.800 N/A
184, 150
625 N/A
026
115 1 119 1
N/A 0.13 N/A N/A 0.11 N/A
D.D D.D 026
1.00
DIRECT DRIVE D.D
DIRECT DRIVE DIRECT DRIVE
N/A N/A
20
026 D.D. = DIRECT DRIVE FAN
150 HORSEPOWER IS NOT LISTED.
184 REQUIRED LISTED IN WATTS.
May 20, 2024
PROJECT
DESCRIPTION
Static Pressure Profile
Luna Grill - Pavilion at La Quinta
EF-1A S.P. PROFILE
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
EF
EA
A B
-0.04 0.08
AB
21
May 20, 2024
PROJECT
DESCRIPTION
Air Distribution Schedule
Luna Grill - Pavilion at La Quinta
EF-1A EXHAUST AIR
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Data
Req. Req. Actual Actual
Room No. Terminal No. Terminal Size K VEL CFM VEL CFM
RESTROOM 1 1 12 X 10 1.000 80 80 85 85
Totals:80 85
22
May 20, 2024
PROJECT
DESCRIPTION
Exhaust Fan Equipment Test
Luna Grill - Pavilion at La Quinta
EF-1B
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Exhaust Fan Information
FAN NUMBER FAN SIZE
FAN MANUFACTURER MOTOR MANUFACTURER
Exhaust Fan Conditions
Required Actual
CFM-Fan
Fan Static Pressure
Motor HP
Motor RPM
Motor (Volts/Phase)
Motor Amps
Fan RPM
Service Factor
MOTOR SHEAVE % OPEN
FAN SHEAVE DRIVE BELTS
V.F.D. HERTZ SET POINT OPERATING STATIC PRESSURE SET POINT
EF-1B SP-B150-QD
GREENHECK GREENHECK
80 80
0.100 0.110
5.800 N/A
184, 150
625 N/A
026
115 1 119 1
N/A 0.13 N/A N/A 0.11 N/A
D.D D.D 026
1.00
DIRECT DRIVE D.D
DIRECT DRIVE DIRECT DRIVE
N/A N/A
23
026 D.D. = DIRECT DRIVE FAN
150 HORSEPOWER IS NOT LISTED.
184 REQUIRED LISTED IN WATTS.
May 20, 2024
PROJECT
DESCRIPTION
Static Pressure Profile
Luna Grill - Pavilion at La Quinta
EF-1B S.P. PROFILE
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
EF
EA
A B
-0.04 0.07
AB
24
May 20, 2024
PROJECT
DESCRIPTION
Air Distribution Schedule
Luna Grill - Pavilion at La Quinta
EF-1B EXHAUST AIR
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Data
Req. Req. Actual Actual
Room No. Terminal No. Terminal Size K VEL CFM VEL CFM
RESTROOM 2 1 12 X 10 1.000 80 80 80 80
Totals:80 80
25
May 20, 2024
PROJECT
DESCRIPTION
Exhaust Fan Equipment Test
Luna Grill - Pavilion at La Quinta
KEF-1
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Exhaust Fan Information
FAN NUMBER FAN SIZE
FAN MANUFACTURER MOTOR MANUFACTURER
EFFICIENCY POWER FACTOR
Exhaust Fan Conditions
Required Actual
CFM-Fan
Fan Static Pressure
Motor HP
Brake Horsepower
Motor RPM
Motor (Volts/Phase)
Motor Amps
Fan RPM
Service Factor
MOTOR SHEAVE % OPEN
FAN SHEAVE DRIVE BELTS
V.F.D. HERTZ SET POINT OPERATING STATIC PRESSURE SET POINT
KEF-1 DU180HFA
CAPTIVEAIRE SYSTEMS TECO FR: 184T
3300 3320
1.180 0.940
2.000 2.000
2.50 0.88 0.81
1165 N/A
026
230 3 226 3
7.51 7.51 7.51 6.62 6.75 6.71
D.D. D.D. 026
1.15
DIRECT DRIVE D.D.
DIRECT DRIVE DIRECT DRIVE
66.80 N/A
26
026 D.D. = DIRECT DRIVE FAN
May 20, 2024
PROJECT
DESCRIPTION
Static Pressure Profile
Luna Grill - Pavilion at La Quinta
KEF-1 S.P. PROFILE
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
EF
EA
A B
-0.81 0.13
AB
27
May 20, 2024
PROJECT
DESCRIPTION
Air Distribution Schedule
Luna Grill - Pavilion at La Quinta
KEF-1 EXHAUST AIR
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Data
Req. Req. Actual Actual
Room No. Terminal No. Terminal Size K VEL CFM VEL CFM
KITCHEN FLTR-1 20 X 16 1.780 199 355
041
KITCHEN FLTR-2 20 X 16 1.780 208 370
KITCHEN FLTR-3 20 X 16 1.780 205 365
KITCHEN FLTR-4 20 X 16 1.780 225 400
KITCHEN FLTR-5 20 X 16 1.780 233 415
KITCHEN FLTR-6 20 X 16 1.780 222 395
KITCHEN FLTR-7 20 X 16 1.780 200 355
KITCHEN FLTR-8 20 X 16 1.780 186 330
KITCHEN FLTR-9 20 X 16 1.780 188 335
Totals: 3320
041 REQUIRED CFM NOT LISTED FOR AIR DISTRIBUTION
28
May 20, 2024
PROJECT
DESCRIPTION
Exhaust Fan Equipment Test
Luna Grill - Pavilion at La Quinta
KEF-2
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Exhaust Fan Information
FAN NUMBER FAN SIZE
FAN MANUFACTURER MOTOR MANUFACTURER
EFFICIENCY POWER FACTOR
Exhaust Fan Conditions
Required Actual
CFM-Fan
Fan Static Pressure
Motor HP
Brake Horsepower
Motor RPM
Motor (Volts/Phase)
Motor Amps
Fan RPM
Service Factor
MOTOR SHEAVE % OPEN
FAN SHEAVE DRIVE BELTS
V.F.D. HERTZ SET POINT OPERATING STATIC PRESSURE SET POINT
KEF-2 DU180HFA
CAPTIVEAIRE SYSTEMS TECO FR: 182T
2100 2155
1.002 0.790
1.500 1.500
1.68 0.87 0.81
1170 N/A
026
230 3 225 3
6.01 6.01 6.01 4.46 4.63 4.58
D.D. D.D. 026
1.15
DIRECT DRIVE D.D.
DIRECT DRIVE DIRECT DRIVE
52.50 N/A
29
026 D.D. = DIRECT DRIVE FAN
May 20, 2024
PROJECT
DESCRIPTION
Static Pressure Profile
Luna Grill - Pavilion at La Quinta
KEF-2 S.P. PROFILE
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
EF
EA
A B
-0.68 0.11
AB
30
May 20, 2024
PROJECT
DESCRIPTION
Air Distribution Schedule
Luna Grill - Pavilion at La Quinta
KEF-2 EXHAUST AIR
Las Vegas
Corporate Headerquarters
4721 E. Hunter Ave
Anaheim, CA 92807 Anaheim
Phone: (702)255-7331 / Fax: (702)294-1306 mail@americanairbalance.com Phone: (714)693-3700 / Fax: (714)693-9509
Data
Req. Req. Actual Actual
Room No. Terminal No. Terminal Size K VEL CFM VEL CFM
KITCHEN FLTR-1 20 X 16 1.780 199 355
041
KITCHEN FLTR-2 20 X 16 1.780 205 365
KITCHEN FLTR-3 20 X 16 1.780 219 390
KITCHEN FLTR-4 20 X 16 1.780 202 360
KITCHEN FLTR-5 20 X 16 1.780 188 335
KITCHEN FLTR-6 20 X 16 1.780 197 350
Totals: 2155
041 REQUIRED CFM NOT LISTED FOR AIR DISTRIBUTION
31
TH
I
S
D
R
A
W
I
N
G
I
S
A
S
C
H
E
M
A
T
I
C
D
I
A
G
R
A
M
,
F
O
R
R
E
F
E
R
E
N
C
E
O
N
L
Y
,
T
H
A
T
C
O
R
R
E
S
P
O
N
D
S
T
O
T
H
E
T
E
S
T
A
N
D
B
A
L
A
N
C
E
A
N
A
L
Y
S
I
S
R
E
P
O
R
T
P
R
O
V
I
D
E
D
B
Y
A
M
E
R
I
C
A
N
A
I
R
B
A
L
A
N
C
E
C
O
M
P
A
N
Y
A
N
D
S
H
O
U
L
D
O
N
L
Y
B
E
U
S
E
D
F
O
R
C
O
R
R
E
L
A
T
I
O
N
T
O
T
H
E
T
E
S
T
A
N
D
B
A
L
A
N
C
E
A
N
A
L
Y
S
I
S
R
E
P
O
R
T
.
THIS DRAWING AND THE INFORMATION HERE-IN RELATING TO AMERICAN AIR BALANCE COMPANY AND ITS CLIENT HAS BEEN FURNISHED IN CONFIDENCE FOR THE PRIVATE USE OF THE AUTHORIZED PERSONNEL ONLY. NO PART HEREOF SHALL BE COPIED, DUPLICATED, DISTRIBUTED, DISCLOSED, OR MADE AVAILABLE TO OTHERS OR USED TO ANY EXTENT WHATSOEVER EXCEPT AS EXPRESSLY AUTHORIZED IN WRITING BY AMERICAN AIR BALANCE COMPANY AND ITS CLIENT. ANY PERSON, FIRM, OR CORPORATION RECEIVING THIS DOCUMENT SHALL BE DEEMED TO HAVE AGREED TO THE FOREGOING RESTRICTIONS.
THIS DRAWING AND THE INFORMATION HERE-IN RELATING TO AMERICAN AIR BALANCE COMPANY AND ITS CLIENT HAS BEEN FURNISHED IN CONFIDENCE FOR THE PRIVATE USE OF THE AUTHORIZED PERSONNEL ONLY. NO PART HEREOF SHALL BE COPIED, DUPLICATED, DISTRIBUTED, DISCLOSED, OR MADE AVAILABLE TO OTHERS OR USED TO ANY EXTENT WHATSOEVER EXCEPT AS EXPRESSLY AUTHORIZED IN WRITING BY AMERICAN AIR BALANCE COMPANY AND ITS CLIENT. ANY PERSON, FIRM, OR CORPORATION RECEIVING THIS DOCUMENT SHALL BE DEEMED TO HAVE AGREED TO THE FOREGOING RESTRICTIONS.
TH
I
S
D
R
A
W
I
N
G
I
S
A
S
C
H
E
M
A
T
I
C
D
I
A
G
R
A
M
,
F
O
R
R
E
F
E
R
E
N
C
E
O
N
L
Y
,
T
H
A
T
C
O
R
R
E
S
P
O
N
D
S
T
O
T
H
E
T
E
S
T
A
N
D
B
A
L
A
N
C
E
A
N
A
L
Y
S
I
S
R
E
P
O
R
T
P
R
O
V
I
D
E
D
B
Y
A
M
E
R
I
C
A
N
A
I
R
B
A
L
A
N
C
E
C
O
M
P
A
N
Y
A
N
D
S
H
O
U
L
D
O
N
L
Y
B
E
U
S
E
D
F
O
R
C
O
R
R
E
L
A
T
I
O
N
T
O
T
H
E
T
E
S
T
A
N
D
B
A
L
A
N
C
E
A
N
A
L
Y
S
I
S
R
E
P
O
R
T
.
Phone: (714) 693-3700
Las Vegas
Fax: (702) 294-1306
Phone: (702) 255-7331
Fax: (714) 693-9509
Anaheim, CA 92807
4721 E. Hunter Ave.
Headquarters
Anaheim
Online
mail@aabctab.com
www.aabctab.com
Air Balance Co., LLC
American
Schematic Diagram Based On Project Reference Sheet Number
Project Number ScaleDate
Sheet Title
Project Mechanical EngineerProject Architect
Of Sheets
Drawn by
Project Title
LUNA GRILL
PAVILION AT LA QUINTA
79124 HIGHWAY 111
LA QUINTA, CALIFORNIA 92253
JAG
246404 05-20-24 NTS RE
AIR DISTRIBUTION PLAN
M101 01 01
RECTANGULAR SUPPLY AIR RISER
CIRCULAR SUPPLY AIR RISER
RECTANGULAR SUPPLY AIR DIFFUSER
RECTANGULAR SUPPLY AIR DROP
CIRCULAR SUPPLY AIR DIFFUSER
CIRCULAR SUPPLY AIR DROP
DESCRIPTIONS
TEST AND BALANCE ANALYSIS LEGEND
SYMBOL
CIRCULAR RETURN AIR RISER
CIRCULAR RETURN AIR GRILLE
CIRCULAR RETURN AIR DROP
RECTANGULAR RETURN AIR RISER
RECTANGULAR RETURN AIR GRILLE
RECTANGULAR RETURN AIR DROP
RECTANGULAR EXHAUST AIR RISER
RECTANGULAR EXHAUST AIR DROP
CIRCULAR EXHAUST AIR RISER
RECTANGULAR EXHAUST AIR GRILLE
CIRCULAR EXHAUST AIR GRILLE
CIRCULAR EXHAUST AIR DROP
CIRCULAR OUTSIDE AIR RISER
CIRCULAR OUTSIDE AIR DROP
CIRCULAR OUTSIDE AIR GRILLE
RECTANGULAR OUTSIDE AIR RISER
RECTANGULAR OUTSIDE AIR DROP
RECTANGULAR OUTSIDE AIR GRILLE
DUCT DETECTOR REFERENCEDD
1
DUCT DETECTOR
EQUIPMENT REFERENCE
TRAVERSED FAN REFERENCE
DUCT TRAVERSE REFERENCE
EXHAUST AIR GRILLE REFERENCE
EXHAUST FAN REFERENCE
OUTSIDE AIR GRILLE REFERENCE
OUTSIDE AIR FAN REFERENCE
RETURN AIR GRILLE REFERENCE
RETURN FAN REFERENCE
SUPPLY FAN REFERENCE
SUPPLY AIR VAV BOX REFERENCE
SUPPLY AIR DIFFUSER REFERENCE
AH-1
1-1
AH-1
R-1
EF-1
1
AH-1
OSA-1
AH-1
DT-1
U
P
P
L
Y
S
T
U
R
N
E
R
H
A
U
S
X
E
T
S
A
O
I
S
M
C
AH-1
RTU-2
RTU-2
4
RTU-2
1
RTU-2
2
RTU-2
3
RTU-2
5
RTU-2
6
RTU-1
RTU-1
1
RTU-1
2
RTU-1
3
RTU-1
8
RTU-1
7
RTU-1
6
RTU-1
5
RTU-1
4
RTU-2
R-2
RTU-2
R-1
RTU-1
R-1
RTU-1
R-2
RTU-1
R-3
RTU-3
1
RTU-3
2
RTU-3
3
RTU-3
5
RTU-3
4
MUA-1
1
KEF-1
FLT-1-9
KEF-2
FLT-1-6
RTU-3
R-1
RTU-3
R-2
RTU-3
R-3
EF-1B
1
EF-1A
1
EF-1A
EF-1B
HOOD-1 HOOD-2