BOTH2024-0001BUILDING PERMIT
DESIGN & DEVELOPMENT
DEPARTMENT Qa�fra
78-495 CALLE TAMPICO
LA QUINTA, CALIFORNIA 92253 ta
CALIFORNIA
Permit Type: Structure Other Than Building Owner
Permit Number: BOTH2O24-0001
Property Address: 78730 HIGHWAY 111 Applicant:
APN: 643220024
Legal Description Contractor:
Property Zoning:
Valuation: $0.00
PHONE (760) 777-7125
WWW.LAQUINTACA.GOV
APPLIED DATE: 02/02/2024
ISSUED DATE: 06/26/2024
WASHINGTON ADAMS SPE
78720 HIGHWAY 111, LA QUINTA, CA 92253
Alesia Davis
1111 Sartori Ave, Torrance, CA 90501
Kelly Stevens / 775947
421 E CERRITOS AVENUE, ANAHEIM, CA 92805
PRIOR TO THE ISSUANCE OF THIS PERMIT FOR CONSTRUCTION, ALTERATION, IMPROVEMENT, DEMOLITION, OR REPAIR THE OWNER, APPLICANT AND/OR
CONTRACTOR UNDER PENALTY OF PERJURY HAVE AFFIRMED WHEN APPLICABLE, THROUGH THE SUBMITTAL OF FORMS OR BY OTHER ELECTRONIC MEANS, THE
FOLLOWING:
LICENSED CONTRACTOR OR OWNER -BUILDER DECLARATION (1 or 2)
1) They are licensed under provisions of Chapter 9 (commencing with
Section 7000) of Division 3 of the Business and Professions Code, and the
referenced
License is in full force and effect, or;
2) That they are exempt from the Contractors' State License Law for the
reason(s) indicated by either (2)(a) and/or (2)(b), or (2)(c) where he or
she is exempt from licensure by a valid exemption. [Section 7031.5,
Business and Professions Code: Any city or county that requires a permit
to construct, alter, improve, demolish, or repair any structure, prior to its
issuance, also requires the applicant for the permit to file a signed
statement that he or she is licensed pursuant to the provisions of the
Contractors' State License Law (Chapter (commencing with Section 7000)
of Division 3 of the Business and Professions
Code] Any violation of Section 7031.5 by any applicant for a permit
subjects the
applicant to a civil penalty of not more than five hundred dollars ($500).)
a) As owner of the property, or my employees with wages as their sole
compensation, will do all of or portions of the work, and the structure is
not intended or offered for sale (Section 7044, Business and Professions
Code: The Contractors' State License Law does not apply to an owner of
property who, through employees' or personal effort, builds or improves
the property, provided that the improvements are not intended or offered
for sale. If, however, the building or improvement is sold within one year of
completion, the Owner -Builder will have the burden of proving that it was
not built or improved for the purpose of sale.).
b) As owner of the property, will be exclusively contracting with licensed
c) Are exempt from licensure under the Contractors' State License Law.
As an Owner -Builder, they acknowledge that, except for their personal
residence in which they must have resided in for at least one year prior to
completion of the improvements covered by this permit, they cannot legally
sell a structure built as an owner -builder if it has not been constructed in
its entirety by licensed contractors. It is understood that a copy of the
applicable law, Section 7044 of the Business and Professions Code, is
available upon request when this application was submitted at the
following Web site:
http://www.leginfo.ca.gov/calaw.html.
DECLARATION REGARDING CONSTRUCTION LENDING AGENCY (If
applicable)
A construction lender will be used for completion of the improvements
covered by this permit and the name and information of which is on file for
public inspection during the regular business hours of the public entity.
Failure of the applicant to indicate the construction lender on the
application does not relieve that person of the requirement to give the
construction lender preliminary notice from that duty.
WORKERS' COMPENSATION DECLARATION (1, 2 or 3)
WARNING: FAILURE TO SECURE WORKERS' COMPENSATION COVERAGE IS
UNLAWFUL, AND SHALL SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND
CIVIL FINES UP TO ONE HUNDRED THOUSAND DOLLARS ($100,000), IN ADDITION
TO THE COST OF COMPENSATION, DAMAGES AS PROVIDED FOR IN SECTION
3706 OF THE LABOR CODE, INTEREST, AND ATTORNEY'S FEES.
1) Has and will maintain a certificate of consent to self -insure for workers'
compensation, issued by the Director of Industrial Relations as provided for
by Section 3700 of the Labor Code, for the performance of the work for
which this permit is issued.
2) Has and will maintain workers' compensation insurance, as required by
Section 3700 of the Labor Code, for the performance of the work for which
this permit is issued.
3) Certifies that, in the performance of the work for which this permit is
issued, shall not employ any person in any manner so as to become subject
to the workers' compensation laws of California, and agree that, if should
become subject to the workers' compensation provisions of Section 3700 of
the Labor Code, shall forthwith comply with those provisions.
NOTICE TO APPLICANT (1, 2 and 3)
1) Each person upon whose behalf this application was made, each person
at whose request and for whose benefit work is being performed under or
pursuant to any permit issued as a result of this application, the owner, and
the applicant, each agrees to, and shall defend, indemnify and hold harmless
the City of La Quinta, its officers, agents, and employees for any act or
omission related to the work being performed under or following issuance of
this permit.
2) Any permit issued as a result of this application becomes null and void if
work is not commenced within 360 days from date of issuance of such
permit, or if cessation of work for 180 days will subject permit to
cancellation. On or after January 1, 2019, every permit issued shall become
invalid unless the work on the site authorized by such permit is commenced
within 12 months after its issuance, or if the work authorized on the site by
such permit is suspended or abandoned for a period of 12 months after the
time the work is commenced.
3) Certified that they read the application and state that the information
provided is correct. Agree to comply with all city and county ordinances and
state laws relating to building construction, and hereby authorize
representatives of this city to enter upon the above -mentioned property for
inspection purposes.
IMPORTANT: An Application for Permit was made to the Building Official,
subject to the conditions and restrictions set forth at the time of application,
which is now hereby an Issued Permit. If any part of the information being
supplied on this permit is inaccurate or untrue, please contact the City of La
Quinta at (760) 777-7125 immediately for correction.
Printed: 5/16/25 10:07 am Page 1 of 4
BUILDING PERMIT
Permit Type: Structure Other Than Building
Permit Number: BOTH2O24-0001
Property Address: 78730 HIGHWAY 111
FIVE BELOW / 794LF OF STORAGE RACKS & SHELVING [ENGINEERED]. 2022 CALIFORNIA BUILDING CODES.
Storage Racks (LF) 794 Total Wall Length 0 Electrical Service? No
(Linear Footage)
Temporary Power No
Service?
Type Group Sq Ft Value
Invoice No. Fee
INV-00007543 Credit Card Convenience Fee
Technology Enhancement Fee
Storage Racks - First 100 LF PC
Storage Racks
Digital Archiving and Records Management Fee - OTC
Hourly Charge - Interwest Structural Plan Review
Permit Issuance
Fee Amount
$17.57
$8.00
$120.83
$133.67
$12.00
$312.50
$115.94
Total for InvoiceINV-00007543 $720.51
Amount Paid
$17.57
$8.00
$120.83
$133.67
$12.00
$312.50
$115.94
$720.51
Grand Total for Permit $720.51 $720.51
Workflow Step / Action Name Action Type Start Date End Date
Application Completeness Check v.1 02/02/2024 13:31 02/02/2024 13:31
----------------------------------------------------------------------------------------------------------------------------------------
Submittal Document Verification v.1 Generic Action 02/02/2024 13:31
Plan Check v.1
02/02/2024
0:00
03/18/2024 11:19
----------------------------------------------------------------------------------------------------------------------------------------
Building Review (1 Day) v.1
Receive Submittal
02/02/2024
0:00
02/07/2024 9:16
------------------------------------------------
BuildiRg Review (I Day) v.2
Receive Submittal
----
02/07/2024
0:00
02/07/2024 9:17
----------------------------------
Building Review (1 WK) v.1
---- ........
Receive Submittal
----------
02/07/2024
0:00
.....
02/08/2024 14:17
........................................................................................................................................
Building Review (1 WK) v.2
Receive Submittal
03/04/2024
0:00
03/18/2024 11:19
Permit Issuance v.1
03/18/2024
11:26
06/26/2024 14:27
-------------------------------------------------------
Contractor / Owner -Builder Information v.1
Generic Action
03/18/2024 11:26
----------------------------------------------------------------------------------------------------------------------------------------
Verify & Invoice Fees v.1
Generic Action
06/26/2024 14:27
----------------------------------------------------------------------------------------------------------------------------------------
Verify Fee Payment & Issue Permit v.1
Generic Action
06/26/2024 14:27
----------------------------------------------------------------------------------------------------------------------------------------
Print, Attach, and Email Building Permit v.1
Create Report
06/26/2024
14:27
06/26/2024 14:27
Structure Other Than Building Inspections v.1
09/10/2024
0:00
----------------------------------------------------------------------------------------------------------------------------------------
-ona a -
Inspection
------------------------ - --------------------------------------------------------------------------------------------------------------
Bottom Plate Bolting v.1
Inspection
09/10/2024
0:00
09/13/2024 11:10
----------------------------------------------------------------------------------------------------------------------------------------
Bottom Plate Bolting v.2
Inspection
09/13/2024
0:00
----------------------------------------------------------------------------------------------------------------------------------------
Drypack v.1
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
^- 1-1-" "'-° - ^
Inspection
Printed: 5/16/25 10:07 am Page 2 of 4
BUILDING PERMIT
Permit Type: Structure Other Than Building
Permit Number: BOTH2O24-0001
Property Address: 78730 HIGHWAY 111
Footing v.1
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
Framing v.1
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
Gas Test v.1
Inspection
------------------ --
Grade Beam v.1
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
Insulation v.1
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
Exterior Lath v.1
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
Okay to Wrap v.1
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
Piers v.1
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
Roof Drains v.1
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
Roof Nail v.1
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
Rough Electrical v.]
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
Rough Mechanical v.1
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
Rough Plumbing v.1
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
Setbacks v.1
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
Sewer Connection v.1
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
Slab v.1
Inspection
---------------------------------------------
T-Bar/Overhead v.1
Inspection
--------------------------
Template Footing v.1
Inspection
------------------------------
Temporary Power v.1
Inspection
-- -- -- -- -- -- -- -- -- --......................................................................................................
Underground Electrical v.1
Inspection
----------------------------------
Underground Gas v.1
Inspection
------------------------------------------------
Underground Plumbing v.1
Inspection
Final Inspections v.1
09/19/2024 0:00 09/20/2024 15:12
------------------------- — -------------------------------------------------------------------------------------------------------------
Structure Other Than Building Final v.1
Inspection 09/19/2024 0:00 09/20/2024 15:12
Construction or work for which a permit is required shall be subject to inspection by the building official and such construction or work
shall remain visible and able to be accessed for inspection purposes until approved. Approval as a result of an inspection shall not be
construed to be an approval of a violation of the provisions of the applicable code and other ordinances of the jurisdiction. Inspections
presuming to give authority to violate or cancel the provisions of the applicable code and other ordinances of the jurisdiction shall not be
valid. It shall be the duty of the owner or the owner's authorized agent to cause the work to remain visible and able to be accessed for
inspection purposes. Neither the building official nor the jurisdiction shall be liable for expense entailed in the removal or replacement of
any material required to allow inspection.
It shall be the duty of the holder of the building permit or their duly authorized agent to notify the building official when work is ready for
inspection. It shall be the duty of the permit holder to provide access to and means for inspections of such work that are required by this
code.
A building or structure shall not be used or occupied in whole or in part, and a change of occupancy of a building or structure or portion
thereof shall not be made, until the building official has issued a certificate of occupancy therefor as provided herein. Issuance of a
certificate of occupancy shall not be construed as an approval of a violation of the provisions of the applicable code and other ordinances
of the jurisdiction. Certificates presuming to give authority to violate or cancel the provisions of this code or other ordinances of the
iurisdiction shall not be valid.
Printed: 5/16/25 10:07 am Page 3 of 4
BUILDING PERMIT
Permit Type: Structure Other Than Building
Permit Number: BOTH2024-0001
Property Address: 78730 HIGHWAY 111
A person shall not make connections from a utility, a source of energy, fuel, or power, or a water system or sewer system to any building
or system that is regulated by the applicable code and other ordinances of the jurisdiction for which a permit is required, until approved by
the building official.
Printed: 5/16/25 10:07 am Page 4 of 4
rw
INTERWEST
A SAFEbullf COMPANY
Bill to:
City of La Quinta
Attn Danny Castro
Design and Development
Director
78-495 Calle Tampico
La Quinta, CA 92253
Remit to:
Interwest Consulting Group
P.O. Box 301069
Los Angeles, CA 90030-1069
Invoice #279265
February 7, 2024
Direct questions to
Erica Cuevas
ecuevas@interwestgrp.com
Professional services for the period February 6, 2024 through February 6, 2024
Commercial - BOTH2024-0001- 78720 Highway 111 - LAQ24-0025
Employee
Jim Northcu
Title
Invoice Total (Please pay this amount)
Hours Rate
tt
ICC Certified Plans Examiner
2.50
$115.00
Labor
2.50
Jim Northcutt
LAQ24-0025 Commercial - BOTH2024-0001- 78720 Highway 111- LAQ24-0025
Day Description
2/6/2024 LAQ24-0025
$287.50
Total
$287.50
$287.50
Hours
2.50
Total 2.50
Iof1
February 6, 2024
CITY OF LA QUINTA - FINAL REVIEW
Permit No: BOTH2O24-0001
Interwest No.: LAQ24-0025
Non -Structural PC-1: 0.00 Hours
Structural PC-1: 2.5 Hours
City of La Quinta
Building Department
78-495 Calle Tampico
La Quinta, CA 92253
Plan Review: Commercial —Storage Racks -For 513elow
Address: 78720 Highway 111
0
1W
INTERWEST
A SAFEbuilt COMPANY
Interwest Consulting Group has completed a FINAL code compliance review of the following electronic documents
on behalf of the City of La Quinta:
1. Drawings:
a. T1.0 dated 1/26/2024 by Kamus+Keller.
b. S1.1 through S2.1 dated 1/25/2024 by Caruso Turley Scott Structural Engineers.
2. Structural Calculations: One electronic copy dated 1/25/2024 by Caruso Turley Scott Structural Engineers.
The applicable provisions of the 2022 California Building Standards Code were used as the basis of this review.
Enclosed, please find the above noted documents bearing Interwest Consulting Group's plan review stamps indicating
the documents have been reviewed for code compliance. Please do not hesitate to contact us directly with any
questions.
Sincerely,
INTERWEST CONSULTING GROUP
Jim Northcutt
ICC Plans Examiner
1500 S. Haven Ave I Suite 220
Ontario, CA 91761
909.295-3142
iNTEa,,EsreeP.con
DESIGN & DEVELOPMENT DEPARTMENT
78-495 CALLE TAMPICO
LA QUINTA, CALIFORNIA 92253
(760) 777-7125 FAX (760) 777-7011
NON-RESIDENTIAL PLAN CHECK CORRECTION LIST (ccR)
DATE: 2/7/2024
STATUS: FIRST REVIEW
PLAN CHECKED BY: INTERWEST/JAKE FUSON
TELEPHONE NUMBER: (760) 777-7081
ADDRESS: 78-730 HIGHWAY 111
DESCRIPTION: STORAGE RACKS
APPLICANT: ALESIA DAVID
PLAN CHECK #: BOTH2O24-0001
This submittal has been checked for compliance with the 2022 California Building, Electrical, Mechanical, Green Building
and Energy Codes, and the City of La Quinta Municipal Code.
APPLICANT:
The following items are being returned to you for
correction:
THIS CORRECTION LIST
BUILDING DEPARTMENT STAFF:
DO NOT accept any resubmittal unless ALL of the
following items are included:
WRITTEN RESPONSES TO THIS CORRECTION LIST
REVISED PLAN SET
INSTRUCTIONS TO APPLICANT:
1) Provide a written response to each comment on the following pages, noting specifically where the correction can be
found. Responses such as, "Sheet A-3," or, "Handrails shall be per CBC Section 1003," are not acceptable. Show or note
specifically how compliance with a code requirement is achieved. Responses such as, "Added note 16 on sheet A-3"
are appropriate and will help expedite your back check.
2) Corrections may not be made by handwriting on existing drawings. Revise originals and reprint Plans and/or
Calculations as necessary.
3) Return all red -marked Plans and/or Calculations with your resubmittal.
4) Each sheet of resubmitted Plans and/or Calculations shall include the preparer's name and telephone number and shall
be wet -signed by the preparer. If the preparer is a licensed architect or engineer, all documents prepared by that
licensed individual shall also bear his/her stamp as prescribed by California Business and Professions Code Section
5536. Resubmittals will not be accepted with signatures missing.
5) Return this list, your written responses, and all documents listed above with your resubmitta
Non -Residential Plan Check Correction List Page 1 of 2
SECTION A — GENERAL
1) Note on Plans: "All construction shall comply with the 2022 California Building, Mechanical, Electrical, Plumbing, Green
Building and Energy Codes and the La Quinta Municipal Code." Remove notes referencing other codes.
2) Provide the Assessor's Parcel Number (APN) and complete legal description of project on the first sheet of plans.
3) Revise the scope of work statement on the cover sheet to reflect the scope of this permit (storage racks only).
4) Revise the construction type to match the original building designs on file with the city (Type VB).
END CITY REVIEW CORRECTION LIST
CORRECTION LIST CONTINUED BY INTERWEST CONSULTING GROUP ATTACHED
As further information is provided and reviewed, additional corrections may be required.
Non -Residential Plan Check Correction List Page 2 of 2
IMEML, �S* ,.,nz
4�3�n�l LA 0 NTA
- A A CA t2253
pESIN CIfiElA
01
APPLICABLE CODES: EGRE55:
JURISDICTION: CITY OF LA QUINTA, CA OCCUPANT LOAD: (TABLE 1004.1.2)
BUILDING: 2022 CALIFORNIA BUILDING CODE TOTAL SQ.FT.: 10,15350, FT.
MECHANICAL: 2022 CALIFORNIA MECHANICAL CODE SALES: 0,013 S.F. l 60 PER PERSON = 145 PERSONS
ELECTRICAL: 2022 CALIFORNIA ELECTRICAL CODE STOCK: 1,422 S.F. / 300 S.F. PER PERSON = 5 PERSONS
PLUMBING: 2022 CALIFORNIA PLUMBING CODE TOTAL OCCUPANT LOAD = 150 PERSONS
ENERGY: 2022 CALIFORNIA ENERGY CODE
FIRE: INTERNATIONAL FIRE CODE 2022
OCCUPANCY:
USE GROUP: M - MERCANTILE (SECTION 302-312)
CONSTRUCTION TYPE: VB
FULLY SPRINKLERED
ASSESSOR'S PARCEL NUMBER (APN): 643-220-024
LEGAL DESCRIPTION: 1.49 ACRES M/L IN POR PAR 4 PM 202/098 PM 3014�/,
�� � � �� � — ��.�
CONSTRUCTION-
- FIRE RESISTANT RATINGS OF STRUCTURAL ELEMENTS (TABLE 601)
- TENANT SPACE SEPARATIONS
I HR
- COLUMNS 0 HR
- INTERIOR BEARING WALLS ....... 0 HR
- NON -BEARING WALLS WITHIN SPACE
— 0 HR
- BEAMS, GIRDERS, TRUSSES, 4 ARCHES
— 0 HR
- ROOF / CEILING CONSTRUCTION
0 HR
TENANT
FIVE BELOW, INC.
101 MARKET ST., SUITE 300
PHILADELPHIA, PA 19106
TEL: (817) 876-7175
CONTACT: JOHN SUTTON
ARCHITECT
KAMUS + KELLER, INC.
3160 KILROY AIRPOT WAY
SUITE 100
LONG BEACH, CA 9080(o
TEL: (562) 216-5244
CONTACT: ODESSA HARRIS
ENGINEER
DENTON MEP, LLC
300 N. CARROL BLVD
SUITE 200
DALLAS, TX 16201
TEL: (940) 808-0615
CONTACT: MICHELE BURTON
CODE REQUIREMENTS: (CHAPTER 10)
MAXIMUM TRAVEL DISTANCE TO EXIT 250 FT.
M-MERCANTILE 15 FT.
S-STORAGE 100 FT.
(SPRINKLED BUILDING)
MAXIMUM DEAD END CORRIDOR LENGTH — 50 FT.
MINIMUM CORRIDOR / AISLE WIDTH 36 IN.
MINIMUM CLEAR OPENING OF EXIT DOORS - 32 IN.
TOTAL EGRESS WIDTH REQUIRED: 020" PER PERSON X 150
(TOTAL OCCUPANT LOAD) PERSONS = 30 IN.
PLUMBING CODE:
WATER CLOSET REQUIRED: I PER 500
WATER CLOSET PROVIDED: I WOMEN, 1 MEN
LAVATORY REQUIRED: 1 PER 150
LAVATORY PROVIDED: 1 WOMEN, 1 MEN
MOP SINK REQUIRED: I
MOP SINK PROVIDED: I
DRINKING FOUNTAIN REQUIRED: I PER 1000
DRINKING FOUNTAIN PROVIDED: 2
BUILDING DEPARTMENT
ELIZABETH MOLINA - PERMIT TECH
51JI FERNANDEZ - PLANNING
TENANT COORDINATOR
KARLA ARZAGA
KARLAeMILANCAP.COM
SHEET
DESCRIPTION
ISSUE
DATE
REV I
V 2
V. 3
REV. 4
REV. 5
V. 6
REV, i
ARCHITECTURAL
TI.O
COVER SHEET/ KEY PLAN
1/26/24
STRUCTURAL
51.1
GENERAL CONSTRUCTION NOTES
1/26/2024
51.2
TYPICAL DETAILS
1/26/2024
52.1
FIXTURE PLAN
1/26/2024
I N
DETAIL ��__ -��
DETAIL NO.
DU15. NO.
SECTION _
SECTION NO.
DETAIL -
DWG. NO.
ELEVATION
_ ELEVATION NO.
DETAIL
-
DWG. NO.
VERTICAL
ELEVATION
�YHF
INDICATES A CHANGE,
OR CHANGES, TO AN
REVISION
* APPROVED DOCUMENT
SEE REV. SECTION ON
THIS SHEET
NORTH
INDICATES PROJECT'S
ARROW
a D NORTH DIRECTION
.;
EXISTING WALL
WALL DEMO
NEW METAL STUD
W/ GYP. BD.
NEW CONTINUOUS
1-HR FIRE RATED
PARTITION
CONCRETE
Ae-
FIVE 5L0UJ
LOC,4TION
FIVE 5 LOW
LOCATION
sraaeEs _�
,a
�ZJSS PeftO
x �
.e
c
A
ARCO O ,a J9'D
♦c � i � ; _ KOHL'S
16
z� o m m _
o • Z2 p
C'��
0
Z:2�
TRUE NORTH PLAN NORTH
One Eleven La Quinta
ns» - �ww u•+n i wwo - o,w wryw. a
l.Ori•A a msJ
V 76
77
p AkWV v
FGJtClG ® •',cw� WASH � I
u ` atat
MA111Mif AW
"'Irtil'ok
KAMUS KELLER
562.215.5244
kkala. om
CONSULTANTS
ARCHITECTURAL SEAL I
* No. -20397
Ny
07 -31� O�
OF CAL��
DATE ISSUE
1 27/02/24 PLAN CHECK CORR.
Q DATE REVISION
PROJECT NAME / LOCATION
f MiVe g..
LA QUINTA
78-730 CA-111
LA QUINTA, CA 92253
PROJECT INFORMATION
DATE: JANUARY 26, 2024
PROJECT NO. 01480-0001 [23.0371]
DELIVERY TYPE: V-BOX
DRAWN BY: DR
REVIEWED BY: POD
TITLE
COVER SHEET
KEY PLAN
SHEET NUMBER
T1m0
ABBREVIATIONS ABBREV1 I
NOTE: ABBREVIATIONS MAY OR MAY NOT HAVE
PERIODS, BUT SHALL BE READ AS SAME.
A.B. ANCHOR BOLT
A.B.C. AGGREGATE BASE COURSE
ACI AMERICAN CONCRETE INSTITUTE
A/C AIR CONDITIONER
A.F.E. ABOVE FINISHED FLOOR
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
AISI AMERICAN IRON AND STEEL
NSTITUTE
AITC AMERICAN INSTITUTE OF TIMBER
CONSTRUCTION
ALT. ALTERNATE
ANSI AMERICAN NATIONAL STANDARDS
INSTITUTE
APA AMERICAN PLYWOOD ASSOCIATION
ARCH'L ARCHITECTURAL
ASTM AMERICAN SOCIETY FOR TESTING
AND MATERIALS
AWS AMERICAN WELDING SOCIETY
A.W.T.S, AUTOMATIC WELDED THREADED
STUDS
BM BEAM
B.F.F BELOW FINISHED FLOOR
BILK BLOCK
B.O.B. BOTTOM OF BEAM
B.O.D. BOTTOM OF DECK
B.O.F. BOTTOM OF FOOTING
BRG BEARING
C CAMBER
C.C. CENTERLINE TO CENTERLINE
CFS COLD FORMED STEEL
C.G. CENTER OF GRAVITY
C.I.P. CAST IN PLACE
C.L. CENTERLINE
C.L.B. CENTERLINE OF BEAM
C.L.C. CENTERLINE OF COLUMN
C.L.F. CENTERLINE OF FOOTING
C.L.W. CENTERLINE OF WALL
CLR CLEAR
CONC CONCRETE
CONC C.J. CONCRETE CONTROL JOINT
GONG S.J. CONCRETE SAWCUT JOINT
C.M.U. CONCRETE MASONRY UNIT
CONN CONNECTION
CONT CONTINUOUS
CRSI CONCRETE REINFORCING STEEL
INSTITUTE
D.E. (D.F.L.) DOUGLAS FIR LARCH
DL DEAD LOAD
DIA DIAMETER
ON DOWN
DWC(S) DRAWINGS)
E.C. END TO CENTERLINE
E.E. END TO END
E.O.S. EDGE OF SLAB
EQ EQUAL
EQUIP EQUIPMENT
EXP. BOLT (E.B.) EXPANSION BOLT
EXP. JT (E.J.) EXPANSION JOINT
E.W. EACH WAY
(E) EXISTING
F.F. FINISHED FLOOR
F.O.M. FACE OF MEMBER
F.O.S. FACE OF STEEL
F.O.W. FACE OF WALL
GA GAGE (UNIT OF MEASUREMENT)
GALV GALVANIZED
G.S.N. GENERAL STRUCTURAL NOTES
GLB (GLULAM) GLUED -LAMINATED BEAM
H.F. HEM FIR
HORIZ HORIZONTAL REINFORCING
H.S. HEADED STUDS
IBC INTERNATIONAL BUILDING CODE
ICC INTERNATIONAL CODE COUNCIL
ICF INSULATED CONCRETE FORMS
I.F.W. INSIDE FACE OF WALL
I.O.D. INTERPRETATION OF DRAWINGS
JST JOIST
K(KIP) 1000 POUNDS
KLF KIPS PER LINEAR FOOT
LBS (#) POUNDS
LGR LEDGER
LOS LIGHT GAGE STEEL
LGSEA LIGHT GAGE STEEL ENGINEERS
ASSOCIATION
L.O.D. LOCATION OF DETAILS
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
MAS MASONRY
MAS C.J. MASONRY CONTROL JOINT
MAX MAXIMUM
MBMA METAL BUILDING MANUFACTURERS
ASSOCIATION
MECH'L— MECHANICAL
MFR'D MANUFACTURED
MFR('S) MANUFACTURER('S)
MIN MINIMUM
N/A NOT APPLICABLE
N.T.S. NOT TO SCALE
O.C. ON CENTER
O.F.W. OUTSIDE FACE OF WALL
OPP OPPOSITE
OSHA OCCUPATIONAL SAFETY AND
HEALTH ADMINISTRATION
PCI PRECAST/PRESTRESSED CONCRETE
INSTITUTE
P.C. PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PLF POUNDS PER LINEAR FOOT
± PLUS OR MINUS
PREFAB PREFABRICATED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POST -TENSIONED
PT — — — — — — POST -TENSIONING INSTITUTE
REINF REINFORCING
SDI STEEL DECK INSTITUTE
SLH SHORT LEG HORIZONTAL
SLV SHORT LEG VERTICAL
SJI STEEL JOIST INSTITUTE
&M SIMILAR
SQ, SQUARE
SSMA STEEL STUD MANUFACTURERS
ASSOCIATION
STD STANDARD
STL STEEL
TL TOTAL LOAD
T.O.B. TOP OF BEAM
T.0.C.T. TOP OF CONCRETE TOPPING
T.O.D. TOP OF DECK
T.O.F. TOP OF FOOTING
T.O.L. TOP OF LEDGER
T.O.M. TOP OF MASONRY
T.O.P. TOP OF PLATE
T.O.P.C. TOP OF PRECAST CONCRETE
T.O.S. TOP OF STEEL
T.O.W. TOP OF WALL
TPI TRUSS PLATE INSTITUTE
TYP TYPICAL
T&G TONGUE AND GROOVE
U.N.O. UNLESS NOTED OTHERWISE
VERT VERTICAL REINFORCING
WCLA WEST COAST LUMBER ASSOCIATION
WCLIB WEST COAST LUMBER INSPECTION
BUREAU
W.W.F. WELDED WIRE FABRIC
WWPA WESTERN WOOD PRODUCTS
ASSOCIATION
W/C WATER TO CEMENT RATIO
W/0 WITHOUT
GENERAL STRUCTURAL NOTES
BUILDING CODE:
2022 EDITION OF THE CALIFORNIA BUILDING CODE AND STANDARDS REFERENCED THEREIN.
LOADS:
SEISMIC:
RISK CATEGORY,
SEISMIC IMPORTANCE FACTOR, I = 1.5 (STORAGE RACKS OPEN TO THE PUBLIC)
MAPPED SHORT PERIOD SPECTRAL ACCELERATION, Ss = 1,656.
MAPPED ONE SECOND SPECTRAL ACCELERATION, S1 = 0.679.
SOIL SITE CLASS, D — DEFAULT.
DESIGN SHORT PERIOD SPECTRAL ACCELERATION, Sds = 1.325.
DESIGN ONE SECOND SPECTRAL ACCELERATION, Sd1 = 0.770.
SEISMIC DESIGN CATEGORY, D.
RESPONSE MODIFICATION FACTOR (R) = 4 STEEL STORAGE RACKS PER ASCE 7-16 TABLE 15.4-1
OVERSTRENGTH FACTOR (0) = 2.0
ANALYSIS PROCEDURE USED = EQUIVALENT LATERAL FORCE PROCEDURE
FOR DEFLECTION/CAMBER CRITERIA OF STRUCTURAL MEMBERS ENGINEERED BY OTHERS, SEE
SPECIFIC MEMBER'S SECTION BELOW.
POST —INSTALLED ANCHORS:
GENERAL:
ALL POST —INSTALLED ANCHORS SHALL UTILIZE THE EXACT ANCHORAGE SYSTEM SPECIFIED IN
THE STRUCTURAL DETAILS. WHERE ANCHORAGE "PER GSN" IS SPECIFIED, SEE BELOW.
ANCHORAGE PRODUCTS MAY NOT BE SWAPPED BETWEEN MANUFACTURERS WITHOUT APPROVAL
OF THE ENGINEER OF RECORD. ALL REQUESTS FOR EQUIVALENT ANCHORAGE PRODUCTS MUST
BE SUBMITTED TO THE ENGINEER OF RECORD FOR APPROVAL PRIOR TO BEING INSTALLED IN THE
FIELD.
UNLESS NOTED OTHERWISE POST INSTALLED ANCHORS SHALL NOT BE INSTALLED UNTIL
CONCRETE OR MASONRY MATERIAL HAVE REACHED DESIGN STRENGTH AND HAVE BEEN FULLY
CURED FOR A MINIMUM OF 21 DAYS.
MANUFACTURER'S INSTALLATION TRAINING AND CERTIFICATE ARE REQUIRED FOR ALL
INSTALLERS OF POST —INSTALLED ANCHORS. ALL ANCHORS SHALL BE INSTALLED WITH STEEL
WASHERS AT SHORT SLOTTED HOLES IN ACCORDANCE WITH THE MANUFACTURERS PRINTED
INSTALLATION INSTRUCTIONS (MPII). ALL ANCHORS SHALL TIGHTENED/TORQUED AS REQUIRED
PER MANUFACTURERS INSTRUCTIONS AND EVALUATION REPORTS.
POST -INSTALLED ANCHORS IN CONCRETE:
ALL EXPANSION TYPE ANCHORAGE FOR CONCRETE INSTALLATION ONLY SHALL BE PER HILTI
'KWIK BOLT—TZ2' EXPANSION ANCHOR PER ICC ESR-4266 OR APPROVED ICC EQUIVALENT. ALL
SCREW TYPE ANCHORAGE FOR CONCRETE INSTALLATION ONLY SHALL BE PER HILTI 'KWIK HUS—
EZ' SCREW ANCHOR PER ICC ESR-3027 OR APPROVED ICC EQUIVALENT.
POST —INSTALLED ANCHORS IN MASONRY:
ALL EXPANSION TYPE ANCHORAGE FOR MASONRY INSTALLATION ONLY SHALL BE PER HILTI
'KWIK BOLT—TZ2' EXPANSION ANCHOR PER ICC ESR-4266 OR APPROVED ICC EQUIVALENT. ALL
SCREW TYPE ANCHORAGE FOR CONCRETE INSTALLATION ONLY SHALL BE PER HILTI 'KWIK HUS—
EZ' SCREW ANCHOR PER ICC ESR-3027 OR APPROVED ICC EQUIVALENT.
COLD FORMED STRUCTURAL STEEL FRAMING:
lelliallArTAN
ALL COLD FORMED STEEL COMPONENTS INDICATED ON THE STRUCTURAL DRAWINGS SHALL BE
PER SSMA. COMPONENTS SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS AND IN ACCORDANCE WITH THE REFERENCED EDITION OF
"SPECIFICATIONS FOR THE DESIGN OF COLD —FORMED STEEL STRUCTURAL MEMBERS" BY THE AISI
AND ICC ESR-3064P OR APPROVED ICC EQUIVALENT. STEEL FOR COLD FORMED MEMBERS SHALL
HAVE A MINIMUM YIELD STRENGTH OF 33 KSI FOR 43 MIL THICKNESS AND LESS, AND MINIMUM
YIELD STRENGTH OF 50 KSI FOR 54 MIL THICKNESS AND GREATER. STEEL FOR BRIDGING SHALL
HAVE A MINIMUM YIELD STRENGTH OF 33 KSI. STEEL SHALL BE GALVANIZED AT LOCATIONS
EXPOSED TO WEATHER AND WHEREVER NOTED.
ALL COLD FORMED LIGHT GAGE STEEL HORIZONTAL STRUCTURAL ELEMENTS (I.E.: JOISTS, BOXED
BEAMS, HEADERS, ETC) SHALL BE FABRICATED FROM UNPUNCHED COMPONENTS.
WHERE WELDING IS SHOWN ON DRAWINGS IT SHALL BE PERFORMED BY WELDERS CERTIFIED IN
LIGHT GAGE STRUCTURAL STEEL FRAMING WORK. DO NOT NOTCH FLANGES OF MEMBERS
WITHOUT EXPRESSED APPROVAL OF THE ENGINEER OF RECORD.
SCREWED COLD FORMED TO COLD FORMED CONNECTIONS (I.E.: 97 MIL TO 97 MIL MAX) SHALL BE
HILTI SELF —DRILLING AND SELF —PIERCING SCREWS PER ICC ESR-2196, OR APPROVED ICC
EQUIVALENT. SCREW SIZE SHALL BE #10 X 3/4" MINIMUM AND MUST PROTRUDE THROUGH AND
BEYOND THE CONNECTED STEEL MEMBERS A MINIMUM OF THREE FULL THREADS. SCREWS
SHALL BE INSTALLED WITH A MINIMUM EDGE AND END DISTANCE OF THREE SCREW DIAMETERS.
MIL THICKNESS / GAGE NUMBER REFERENCE:
27 MIL — — — — — — 22 GA
33 MIL — — — — — — 20 GA
43 MIL — — — — — — 18 GA
WALLS:
54 MIL — — — — — — 16 GA
68 MIL — — — — — — 14 GA
97 MIL — — — — — — 12 GA
STRUCTURAL STEEL STUD WALLS SHOWN ON PLAN SHALL BE INSTALLED PER STUD/SPACING AS
NOTED BELOW, AND BOTTOM TRACKS SHALL BE INSTALLED WITH 1/2" DIA ANCHOR BOLTS AT 32"
O.C. TYPICAL U.N.O. ATTACHMENT OF STUDS TO TRACKS PER TYPICAL DETAILS U.N.O. ALL
STUDS SHALL BE SECURELY SEATED FOR FULL END BEARING ON TOP AND BOTTOM TRACK.
UNLESS NOTED OTHERWISE, INSTALL DOUBLE STUDS AT ALL JAMBS, CORNERS, INTERSECTIONS
AND ISOLATED BEARING POINTS OF FRAMING MEMBERS ABOVE. BRIDGING SHALL BE INSTALLED
PER MANUFACTURER'S RECOMMENDATION WITH THE FOLLOWING MINIMUM REQUIREMENTS:
AT ALL WALLS, INSTALL BRIDGING PER TYPICAL DETAILS AT 5'-0" O.C. MAXIMUM. SOLID BLOCKING
SHALL BE INSTALLED IN LIEU OF BRIDGING WHERE NOTED ON THE DRAWINGS. FOR NON —BEARING
PARTITIONS AND SOFFITS, SEE ARCHITECTURAL DRAWINGS.
WOOD:
GENERAL:
WOOD FRAMING MEMBERS SHALL NOT BE NOTCHED OR DRILLED WITHOUT PRIOR APPROVAL OF
THE STRUCTURAL ENGINEER THROUGH THE ARCHITECT. STRUCTURAL WOOD FRAMING
MEMBERS SHALL HAVE A MAXIMUM MOISTURE CONTENT OF 19% WHEN DELIVERED TO THE JOB
SITE. ALL NAILING NOT NOTED SHALL BE PER TYPICAL DETAIL AND COMMON NAIL DIAMETER
TABLE BELOW. ALL BOLTING SHALL BE PER STRUCTURAL STEEL SECTION. WOOD CONNECTORS
SHALL BE AS MANUFACTURED BY SIMPSON STRONG —TIE COMPANY, INC. OR OTHER
MANUFACTURER WITH CURRENT AND EQUIVALENT ICC APPROVAL. WHERE "TYPE" OF
CONNECTOR IS INDICATED ON THE DRAWINGS, THE CONNECTOR AND ATTACHMENT SHALL BE
PER THE MAXIMUM MODEL NUMBER BASED ON THE SIZE OF THE MEMBERS CONNECTED.
NAIL TYPE REQ'D DIA REQ'D GA LENGTH NAIL TYPE REQ'D DIA REQ'D GA LENGTH
6 d
0.113" 11 1 /2 2"
12d
0.148"
9
3 1 /4"
8d
0.131" 10 1 /4 2 1 /2"
16d
0.162"
8
3 1 /2"
10d
0.148" 9 3"
20d
0.192"
6
4"
PROVIDE
2" SOLID BLOCKING AT SUPPORTS OF
ALL JOISTS.
DOUBLE UP
FLOOR
JOISTS AND
BLOCKING
UNDER PARTITIONS.
SAWN LUMBER:
FRAMING LUMBER SHALL COMPLY WITH THE REFERENCED EDITION OF THE GRADING RULES OF
THE WWPA OR THE WCLIB. ALL SAWN LUMBER SHALL BE STAMPED WITH THE GRADE MARK OF AN
APPROVED LUMBER GRADING AGENCY AND SHALL HAVE MINIMUM PROPERTIES WHICH MEET OR
EXCEED THE FOLLOWING WOOD TYPES:
WOOD TYPE
JOISTS AND STUDS
2 X 4 OR LARGER - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - H.F. #2
GENERAL NOTES:
THE STRUCTURAL CONSTRUCTION DOCUMENTS REPRESENT THE FINISHED STRUCTURE. EXCEPT
WHERE NOTED, THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR
SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING
CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO, BRACING, SHORING
FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC. THE STRUCTURAL ENGINEER OF RECORD
SHALL NOT BE RESPONSIBLE FOR THE CONTRACTOR'S MEANS, METHODS, TECHNIQUES,
SEQUENCES FOR PROCEDURE OF CONSTRUCTION, OR THE SAFETY PRECAUTIONS AND THE
PROGRAMS INCIDENT THERETO (NOR SHALL OBSERVATION VISITS TO THE SITE INCLUDE
INSPECTION OF THESE ITEMS).
WHERE REFERENCE IS MADE TO VARIOUS TEST STANDARDS FOR MATERIALS, SUCH STANDARDS
SHALL BE THE REFERENCED EDITION AND/OR ADDENDA. ANY ENGINEERING DESIGN, PROVIDED
BY OTHERS AND SUBMITTED FOR REVIEW, SHALL BEAR THE SEAL OF A REGISTERED ENGINEER
RECOGNIZED BY THE BUILDING CODE JURISDICTION OF THIS PROJECT.
NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL STRUCTURAL
NOTES AND TYPICAL DETAILS. WHERE NO DETAILS ARE SHOWN, CONSTRUCTION SHALL
CONFORM TO SIMILAR WORK ON THE PROJECT, AND/OR AS PROVIDED FOR IN THE CONTRACT
DOCUMENTS. WHERE DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS, GENERAL
STRUCTURAL NOTES AND SPECIFICATIONS, THE GREATER REQUIREMENTS SHALL GOVERN.
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND ELEVATIONS WITH THE ARCHITECTURAL
DRAWINGS AND FIELD CONDITIONS. BUILDING DIMENSIONS AND ELEVATIONS, WHERE SHOWN,
WERE PROVIDED BY THE ARCHITECT AND IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY
AND COORDINATE ALL DIMENSIONS PRIOR TO PROCEEDING WITH THE WORK. ANY
DISCREPANCIES SHALL BE RESOLVED THROUGH THE ARCHITECT. ESTABLISH AND VERIFY ALL
OPENINGS AND INSERTS FOR ARCHITECTURAL, CIVIL, MECHANICAL, PLUMBING AND ELECTRICAL
ITEMS WITH THE APPROPRIATE TRADE DRAWINGS AND SUBCONTRACTORS PRIOR TO
CONSTRUCTION.
TYPICAL DETAILS MAY NOT NECESSARILY BE CUT ON PLANS, BUT APPLY UNLESS NOTED
OTHERWISE.
CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON FRAMED CONSTRUCTION.
LOAD SHALL NOT EXCEED THE DESIGN LIVE LOAD PER SQUARE FOOT.
OPTIONS AND SUBSTITUTIONS ARE FOR CONTRACTOR'S CONVENIENCE. IF AN OPTION OR
SUBSTITUTION IS CHOSEN, CONTRACTOR SHALL BE RESPONSIBLE FOR ALL NECESSARY
CHANGES, APPROVALS AND THE COORDINATION OF THE WORK WITH ALL RELATED TRADES AND
SUPPLIERS.
Applies unless noted otherwise on drawings
SPECIAL INSPECTION - STRUCTURAL ONLY:
SPECIAL INSPECTIONS SHALL BE PERFORMED UNDER THE DIRECT SUPERVISION OF A STATE
REGISTERED STRUCTURAL ENGINEER WHO IS FAMILIAR WITH THE STRUCTURAL DESIGN OF THIS
PROJECT. THE SUPERVISING STRUCTURAL ENGINEER SHALL SEAL THE SPECIAL INSPECTION
CERTIFICATE.
SPECIAL INSPECTION IS TO BE PROVIDED FOR THE ITEMS LISTED BELOW IN ADDITION TO THE
INSPECTIONS CONDUCTED BY THE BUILDING JURISDICTION. "SPECIAL STRUCTURAL INSPECTION"
SHALL NOT RELIEVE THE OWNER OR THEIR AGENT FROM REQUESTING THE BUILDING
JURISDICTION INSPECTIONS REQUIRED BY SECTION 110 OF THE INTERNATIONAL BUILDING CODE.
SPECIAL INSPECTION IS REQUIRED PER CHAPTER 17 FOR THE FOLLOWING:
SPECIAL CASES:
1. EXPANSION, EPDXY, ADHESIVE, AND SCREW ANCHORS: DURING THE PLACEMENT OF ALL
ANCHORS SHOWN ON STRUCTURAL DRAWINGS. ADDITIONAL INSPECTIONS REQUIRED FOR
REPAIR DETAILS SHALL BE PERFORMED AT THE CONTRACTOR'S EXPENSE.
A. INSPECTION OF HOLE DIAMETER, HOLE DEPTH AND DRILL BIT CONFORMANCE.
B. INSPECTION OF HOLE CLEANING WITH WIRE BRUSH AND COMPRESSED AIR.
C. INSPECTION OF ANCHOR INSTALLATION USING SPECIFIED PRODUCT AND MANUFACTURER'S
RECOMMENDED INSTALLATION PROCEDURES.
D. INSPECTION OF EXPANSION ANCHORS SHALL INCLUDE THE VERIFICATION OF THE TIGHTENING
TORQUE THAT IS SPECIFIED BY THE ANCHOR MANUFACTURER.
DUTIES AND RESPONSIBILITIES OF THE SPECIAL INSPECTOR:
A. THE SPECIAL INSPECTOR SHALL OBSERVE THE WORK ASSIGNED TO BE CERTAIN IT CONFORMS
TO THE APPROVED DESIGN DRAWINGS AND SPECIFICATION.
B. THE SPECIAL INSPECTOR IS NOT AUTHORIZED TO APPROVE DEVIATIONS FROM THE DESIGN
DRAWINGS OR SPECIFICATIONS, AND ALL DEVIATIONS MUST BE APPROVED BY THE STRUCTURAL
ENGINEER OF RECORD PRIOR TO PROCEEDING WITH THE WORK. ALL REQUESTS FOR DEVIATIONS
SHALL BE INITIATED BY THE CONTRACTOR VIA WRITTEN REQUEST FOR INFORMATION (RFI).
C. THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS TO THE BUILDING OFFICIAL,
AND TO THE ENGINEER OR ARCHITECT OF RECORD. ALL DISCREPANCIES SHALL BE BROUGHT TO
THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR CORRECTION, THEN, IF UNCORRECTED, TO
THE DESIGN AUTHORITY AND THE BUILDING OFFICIAL.
D. THE CONTRACTOR SHALL PROVIDE THE SPECIAL INSPECTOR ACCESS TO ALL ITEMS
REQUIRING SPECIAL INSPECTION. ACCESS SHALL BE PROVIDED BY IN —PLACE LADDERS,
SCAFFOLDS, LIFTS AND/OR OTHER EQUIPMENT OPERATED BY THE CONTRACTOR'S PERSONNEL
AS REQUIRED FOR SAFE OBSERVATION. THE SPECIAL INSPECTOR IS NOT RESPONSIBLE OR
AUTHORIZED TO OPERATE CONTRACTOR'S EQUIPMENT.
E. UPON COMPLETION OF THE ASSIGNED WORK THE ENGINEER OR ARCHITECT IN CHARGE OF
SPECIAL INSPECTIONS SHALL COMPLETE AND SIGN THE APPROPRIATE FORMS CERTIFYING THAT
TO THE BEST OF THEIR KNOWLEDGE THE WORK IS IN CONFORMANCE WITH THE APPROVED PLANS
AND SPECIFICATIONS, AND THE APPLICABLE WORKMANSHIP PROVISIONS OF THE CODE.
STRUCTURAL SCOPE OF WORK: COMPONENT AND ANCHORAGE OF SALES FLOOR
FIXTURES AND STOCK ROOM STORAGE SHELVES OVER 5'-9" IN HEIGHT.
SHEET INDEX
DETAILS
SHEET
DESCRIPTION
---
S1.1
GENERAL STRUCTURAL NOTES
01-19
S1.2
DETAILS
- - -
S2.1
FIXTURE PLAN
THESE DRAWINGS/CALCULATIONS ARE CONSIDERED PRELIMINARY —NOT FOR
CONSTRUCTION OR RECORDING UNLESS THE STRUCTURAL ENGINEER OF
RECORD'S SEAL IS AFFIXED WITH WRITTEN SIGNATURE.
PROJECT NUMBER 24-0069
PROJECT MANAGER DST
PROJECT ENGINEER PMP
PROJECT DRAFTER MDF
CARUSO - TURLEY- SCOTT- INC
consulting structural engineers
1215 West Rio Salado Parkway, Suite 200
Tempe, Arizona 85281 (480) 774-1700 (774-1701 FAX)
www.ctsaz.com
KAMUS + KELLER
562=216=5244
kka 1a.wm
CONSULTANTS
01 _25-24
ARCHITECTURAL SEAL
DATE ISSUE
D/MM/YY XXXX
DATE REVISION
PROJECT NAME / LOCATION
fiW BELOW
LA QUINTA
78-730 CA-111
LA QUINTA, CA 92253
PROJECT INFORMATION
DATE: MONTH DAY, YEAR
PROJECT NO. ####-## [##.####]
DELIVERY TYPE: V-BOX
DRAWN BY: MDF
REVIEWED BY: PMP
TITLE
GENERAL STRUCTURAL NOTES
SHEET NUMBER
ILL:
a
x
a
0
00
C�
w
0
z
J
w
cn
NOTES:
1. 2x4 WOOD BLOCK (HEM FIR #2
MIN.) AT 4'-0" O.C. ALONG THE
HEIGHT OF THE SHELF WITH
2 #8 x3" WOOD SCREWS AT
(4) /1) EACH STUD. ATTACH TO 3
\\ WOOD STUDS MIN. FIRE
RETARDANT TREATED WOOD
(2) REQ'D BY BUILDING
CONSTRUCTION TYPE.
2. FIXTURES SHALL BE ANCHORED
TO EXISTING 2x WOOD STUDS
(5) ($ ) (3) AT 16" O.C. MIN. 2x6 STUD
WALL SUPPORTING SHELVES
� SHALL BE SISTERED WITH AN
---- ADDITIONAL 2x6 JOIST PER
DETAIL 13.
(6) 3. GYP BOARD (BOTH SIDES) PER
ARCH'L.
(1) 4. 2 #8 x 1" WOOD SCREWS AT
MFR WALL BRACKET.
I
I
(3) 5. 2'-0" D x 4'-0" W x 8'-O"
_ TALL SHELF OR FIXTURE AS
(7) -� OCCURS (5 MAX).
6. SHELVING UPRIGHT PER MFR
SPACED AT 4'-0' O.C. MAX.
7. EXISTING CONCRETE SLAB ON
=Ju GRADE.
Oo 8. 75# MAX. WEIGHT ON EACH
)000 O°0O 4'-0" LENGTH OF SHELF. 4
%�%�\i\\j/\\ SHELVES MAX AS SHOWN.
NOTE:
MAXIMUM HEIGHT TO TOP OF EXISTING
WOOD STUDS SHALL BE 20'-0".
NOTIFY STRUCTURAL ENGINEER IF THIS
IS NOT THE CASE.
OPTIONAL SHELF/FIXTURE TO EXISTING WOOD STUD WALL
240035 NO SCALE
NOTES:
1.
STUDWALL TOP FRAMING.
2.
NEW 2x6 WOOD STUD.
3.
SIMPSON H2.5 AT TOP AND
(1)
BOTTOM OF STUDWALL
FRAMING.
_ _
4.
5.
EXISTING 2x6 WOOD STUD.
STUDWALL BOTTOM FRAMING.
_
6.
16d NAILS AT 24 O.C.
(2)
STAGGERED AS SHOWN - 2
NAILS AT ENDS.
7.
DOUBLE UP STUDS.
(4)
(s)
SISTER 2x6 WOOD STUDS
(6)
4" 24" (7)
�14-
12" 24"
n
(3)
24-0035 NO SCALE
LL
LL
Q
x
Q
0
CD
w
CD
z
>
J
w
Tn
LL
x
Q
M
0
I
00
w
0
z
>
J
w
NOTES:
1. PLAQUE TO BE NOT LESS THAN
50 SQUARE INCHES IN SIZE.
POST IN ONE OR MORE
CONSPICUOUS LOCATIONS.
NOTICE
MAXIMUM LOADS
SECTION SH ELF x
450 LB. 75 LB.
Including Above/Below Deck O
DO NOT USE FOR A STEP, HAND -HOLD OR LADDERDO
1
REFER TO ASSEMBLY INSTRUCTIONS FOR PROPER INSTALLATION
NO LOAD ON ALLOWED ON TOP SHELF INSTALLATION
PLAQUE AT STOCK ROOM SHELVING
240069 NO SCALE
NOTES:
1. 2x4 WOOD BLOCK (HEM FIR
(7) #2 MIN) TOP AND BOTTOM
(1) WITH 2 #12 SCREW AT EACH
STUD. ATTACH TO 3 STEEL
(3) 7 STUDS MIN. FIRE -RETARDANT
II TREATED WOOD REQ'D BY
BUILDING CONSTRUCTION
0 Q TYPE.
2. FIXTURES SHALL BE
_---- O ANCHORED TO NEW OR
EXISTING 60OS162-43 STEEL
(4) (10 ) ( 2 )
STUDS AT 16" O.C. MIN OR
362S162-97 STEEL STUDS
II II
AT 8" O.C.
---- (8) 3. 2 #8 x1" WOOD SCREWS AT
(6) =----u MFR WALL BRACKET.
4. 2'-0"D x4'-0"W x8'-O" TALL
li (9) SHELF OR FIXTURE AS
(1) D OCCURS.
5. EXISTING CONCRETE SLAB ON
li GRADE.
(3) 1 1 4_2��
6. SHELVING UPRIGHT PER MFR
---- SPACED AT 4'-0' O.C. MAX.
(5)
7. FOR TOP ATTACHMENT OF
NEW/EXISTING STEEL STUD,
II SEE DETAIL 03.
8. GYPSUM BOARD (BOTH SIDES)
�° �° PER ARCH'L.
0 0 9. BASE CONNECTION PER
NOTE:\i�\/// DETAIL 02.
MAXIMUM HEIGHT TO TOP OF EXISTING \ 10. 75# MAX WEIGHT ON EACH
STEEL JOISTS SHALL BE 20'-0". 4'-0" LENGTH OF SHELF. 4
NOTIFY STRUCTURAL ENGINEER IF THIS SHELVES MAX, AS SHOWN.
IS NOT THE CASE.
„� PERIMETER GONDOLA ATTACHMENTS AT STEEL STUD WALL
240069 NO SCALE
NOTES:
(7) 1. 20 WOOD BLOCK (HEM FIR
/ #2 MIN) TOP AND BOTTOM
WITH (2) 3/8" DIA x 2 1/2"
/ EMBED MASONRY SCREW
ANCHOR PER G.S.N. AT
/ EXISTING MASONRY WALL.
/ FIRE -RETARDANT TREATED
n a WOOD IF REQ'D BY THE
(2)
BUILDING CONSTRUCTION
I i
- TYPE.
(3) (6) 2. 2 #8 x1" WOOD SCREWS AT
/ " MFR WALL BRACKET.
3. 2'-0" DEEP x4'-0" WIDE
(1) x8'-0" TALL SHELF OR
---- FIXTURE AS OCCURS.
(5) 4. EXISTING CONCRETE SLAB ON
GRADE.
(1) ,'/ ,� 5. SHELVING UPRIGHT PER MFR
l / SPACED AT 4'-0" O.C. MAX.
(2) 6. 75# MAX WEIGHT ON EACH
/ 4'-0" LENGTH OF SHELF.
(4) / 7. EXISTING MASONRY WALL.
cV Q
-- -- - -- -�O/- 1'OJ[ -T --
----------------- -- - --o
bo 00 NOTE:
° SPECIAL INSPECTION IS
REQUIRED DURING INSTALLATION
OF MASONRY SCREW ANCHORS.
PERIMETER GONDOLA ATTACHMENTS AT EXISTING MASONRY WALL
24-0069 NO SCALE
NOTES:
1. 2x4 WOOD BLOCK (HEM FIR
/1) �r #2 MIN.) AT 4'-0" O.C.
\\ ALONG THE HEIGHT OF THE
(4) n SHELF WITH
I I Iii xQ
1 2 #8 x3" WOOD SCREWS AT
- EACH STUD. ATTACH TO 3
1F WOOD STUDS MIN. FIRE
RETARDANT TREATED WOOD
REQ'D BY BUILDING
CONSTRUCTION TYPE.
Hi Q 2. FIXTURES SHALL BE
(2)----�I �I
ANCHORED TO EXISTING 2x
WOOD STUDS AT 16" O.C. MIN
2x6 STUD WALL SUPPORTING
(5) (8) (2) SHELVES SHALL BE SISTERED
li WITH AN ADDITIONAL 2x6
JOIST PER DETAIL 13.
--A 3. GYP BOARD (BOTH SIDES)
(6) -- PER ARCH'L.
li 4. 2 #8 x 1" WOOD SCREWS AT
(1) III (3) MFR WALL BRACKET.
5. 2'-0" D x 4'-0" W x 8'-0"
(4) ;I
TALL SHELF OR FIXTURE AS
OCCURS (5 MAX).
6. SHELVING UPRIGHT PER MFR
(7) --- SPACED AT 4'-0' O.C. MAX.
N Q 7. EXISTING CONCRETE SLAB ON
----- - -- -�I ---- X-_ GRADE.
8. 75# MAX. WEIGHT ON EACH
�Ju 4'-0" LENGTH OF SHELF. 4
Oo 00 NOTE: SHELVES MAX AS SHOWN.
�\ \\/\\ MAXIMUM HEIGHT TO TOP OF EXISTING
//\ WOOD STUDS SHALL BE 20'-0".
NOTIFY STRUCTURAL ENGINEER IF THIS
IS NOT THE CASE.
��120" PERIMETER GONDOLA ATTACHMENTS AT EXISTING WOOD WALL
24-0069 NO SCALE
/e \
NOTES:
1. SHELVING UNIT PER ARCH'L.
2. 2 SHELVES (MAX).
3. BASE PLATE AND ANCHORAGE
PER DETAIL 05.
4. 100# MAX WEIGHT ON EACH
4'-0" SHELF.
5. EXISTING CONCRETE SLAB ON
GRADE TO REMAIN.
NOTE:
BASED ON MFR.
-7
RECOMMENDATIONS, NET
OVERTURNING FROM
UNBALANCED LOADING NOT
05 TO EXCEED 12,000#-IN.
25" MIN
(5) �� (3)
INTERIOR GONDOLA ANCHORAGE AT BASE SHELVES
240069 NO SCALE
NOTES:
1. SHELF CORNER POST PER SHELF
MFR.
2. 12 GA x 1 1 /2"x6 1/2" STEEL
PLATE WITH (2) 3/8" DIA x
3" LONG CONCRETE EXPANSION
ANCHORS PER G.S.N. WITH
I I
2 1/2" EMBEDMENT OR USE
(1) (2) 3/8" DIA x 3" LONG
CONCRETE SCREW ANCHORS PER
G.S.N. WITH 2 1/2" EMBEDMENT
-� - LOCATE STEEL PLATE AT
EACH SHELF POST.
(3) 3. SHELF POST CONNECTION TO
X z STEEL PLATE PER MFR.
(4) (2) 4. EXISTING CONCRETE SLAB ON
GRADE TO REMAIN.
5. ANCHOR EMBEDMENT DEPTH TO
-- - -- -- III -- -- BE AS NOTED, NOT SHALLOWER,
NOT DEEPER. HOLES ARE TO BE
-- -- -- -- -- -- -- -- -- -- --0 CLEANED FROM ALL DUST, SO
° THE PROPER HOLE DEPTH IS
�� �O
�/�%\
MAINTAINED. DEEPER HOLES
\/ \\�\WITH THE DUST REMAINING IN
EQ THE HOLE ARE NOT ALLOWED.
TI NOTE:
"' SPECIAL INSPECTION IS
-ICV
'n REQUIRED DURING
�I • `f' TIN INSTALLATION OF
1EXPANSION AND SCREW
12 ANCHORS.
• ONLY THE ANCHORS
X PLAN NOTED ABOVE ARE
PERMITTED TO BE USED.
INTERIOR GONDOLA ANCHORAGE AT CONCRETE SLAB ON GRADE
STOCK ROOM SHELVING ELEVATION
240069 NO SCALE
NOTES:
1. PLAQUE PER DETAIL 08.
-0" D x 4'-0" W x 10'-0" 2. 2'
TALL SHELF BY OTHERS (MAX
DIMENSION).
3. EXISTING CONCRETE SLAB ON
GRADE TO REMAIN.
4. 7 SHELVES (MAX).
5. CROSS BRACING PER MFR.
6. SHELF PER MFR.
7. UPRITE PER MFR.
8. DO NOT LOAD TOP SHELF.
THE MAXIMUM TOP -TO -BOTTOM
OUT -OF -PLUMB RATIO FOR A
LOADED RACK COLUMN IS 1/240
(FOR EXAMPLE 1/2 INCHES PER 10
FEET (12.5 MM PER 3 M) OF
HEIGHT). COLUMNS WHOSE
OUT -OF -PLUMB RATIO EXCEEDS
THIS LIMIT SHOULD BE UNLOADED
AND RE -PLUMBED. ANY DAMAGED
PARTS MUST BE REPAIRED OR
REPLACED.
THE MAXIMUM OUT -OF -STRAIGHT
RATIO FOR A LOADED RACK
COLUMN IS 1/240 (0.05 INCHES
PER FOOT OR 1/2 INCHES PER 10
FEET (12.5 MM PER 3 M) OF
HEIGHT). COLUMNS WHOSE
OUT -OF -STRAIGHT RATIO EXCEEDS
THIS LIMIT SHOULD BE UNLOADED
AND RE -PLUMBED. ANY DAMAGED
PARTS MUST BE REPAIRED OR
REPLACED.
24-0069 NO SCALE
(1) NOTES:
1. SHELF CORNER POST PER SHELF
MFR.
I I
2. 12 GA STEEL PLATE WITH
DIMENSIONS AS SHOWN AND
(3) (2) 3/8" DIA x 3" LONG
CONCRETE EXPANSION ANCHORS
X Z PER G.S.N. WITH
(4 ) (2) 2 1/2" EMBEDMENT OR USE (2)
3/8" DIA x 3" LONG CONCRETE
-- -- SCREW ANCHORS PER G.S.N.
�LI; WITH 2 1/2" EMBEDMENT -
-- -- -- -- -- -- -- -- -- -- -- LOCATE STEEL PLATE AT EACH
�co �� S
0 0 HELF POST.
3. SHELF POST CONNECTION TO
Cl `\��/// STEEL PLATE PER MFR.
`\ 4. EXISTING CONCRETE SLAB ON
GRADE TO REMAIN.
11I 5. ANCHOR EMBEDMENT DEPTH TO
If
+ BE AS NOTED, NOT SHALLOWER,
NOT DEEPER. HOLES ARE TO BE
CLEANED FROM ALL DUST, SO
THE PROPER HOLE DEPTH IS
1/2" TYP 2 7/8" MAINTAINED. DEEPER HOLES
(2) WITH THE DUST REMAINING IN
3 3/4" THE HOLE ARE NOT ALLOWED.
1 1/4" TYP 3/16" 2 1/4" NOTE:
• SPECIAL INSPECTION IS
REF REQUIRED DURING
C, 00 INSTALLATION OF
+ \ � EXPANSION AND SCREW
ANCHORS.
• ONLY THE ANCHORS
7/8' NOTED ABOVE ARE
PERMITTED TO BE USED.
(,, 1STOCK ROOM SHELF ANCHORAGE AT CONCRETE SLAB ON GRADE
24-0069 NO SCALE
m N...nzrI
NOTES:
/<� 1. STEEL STUD.
ll9) y a 2. UNPUNCHED STEEL STUD TRACK -
ATTACHMENT REQUIRED 1/2" DIA. Z U IN6,
EXPANSION BOLTS AT 48" O.C. (2
' MINIMUM) OR .148"x3/4" LONG .F
KELLER
POWDER DRIVEN PINS AT 12" O.C. KAMU
FASTENER SHALL HAVE ICC REPORT
FOR SAME INSTALLATION.
. 3. MULTIPLE OR INTERSECTING STUDS_,_
WHERE OCCUR. CONNECT WITH 2
11) 5244
ROWS #10 S.M. SCREWS AT 24" O.C. kkalaxe n
I (3) STAGGERED SPACING. AT
INTERSECTING STUDS 1 ROW OF
SCREWS.
4. #10 S.M. SCREWS EACH SIDE, EACH CONSULTANTS
STUD.
(5) 5. 2 #10 S.M. SCREWS.
()
5 6. 4 #10 S.M. SCREWS.
7. #10 S.M. SCREWS AT 12" O.C. AT
DOUBLE STUDS.
8. STUD BLOCKING.
9. 18 GA CLIP ANGLE BY STUD MFR
' (8) WITH 3 #10 S.M. SCREWS AT EACH
• 7) (2) STUD WHERE SHOWN IN DETAILS.
((4)
01_25_Z4
�� • � NOTE:
6) A. FOR SIZE AND GAGE OF TYPICAL
STEEL STUDS, SEE GENERAL B.INSTALL ALL SCREWS PER
STRUCTURAL NOTES. SPECIAL STEEL STUD MANUFACTURES
SIZES ARE CALLED OUT ASSOC. SPECIFICATIONS.
ON PLAN AND/OR DETAIL. C. S.M. (SHEET METAL) SCREWS
PER G.S.N.
i1 TYPICAL STEEL STUD WALL - SCREW CONNECTION
407-22 NO SCALE
(3)
(4)
L
NOTES:
1. STEEL STUD WALL.
2. CONTINUOUS STEEL TRACK
WITH THICKNESS TO MATCH
STUD GAUGE AND HILTI X-U
(ICC ESR-2269) WITH 1"
(1) PENETRATION AT
16" O.C.
3. #10 SCREW CONNECTION AT
EACH STUD.
4. EXISTING CONCRETE SLAB.
(2)
STEEL STUD WALL BASE CONNECTION
PARALLEL CONDITION
/e\
(4)
r-lzz-=z-=z-r=1-=:s==1=-r-7�-/z�-Zz Z
---------------------
I I
I I
(6) (1)
I I
(2)
I I
I I
240069 NO SCALE
NOTES:
1.
14 GAGE SLIP TRACK WITH
2 #10 x 1 1/2" WOOD
SCREWS AT EACH MEMBER
ABOVE.
2.
STEEL STUD WALL.
3.
NEW 2x4 AT 24" O.C. WITH
(5)
LU24 HANGER EACH END.
4.
EXISTING PLYWOOD
SHEATHING.
5.
EXISTING 2x OR 4x AT 24"
O.C.
6.
#8 IN SLOTTED HOLES, TYP.
NOTE:
SEE DETAIL 03 FOR CONNECTION
TO EXISTING STEEL JOISTS.
PERPENDICULAR CONDITION
STEEL STUD WALL TO EXISTING WOOD FRAMING - SLIP CONNECTION
24-0069 NO SCALE
THESE DRAWINGS/CALCULATIONS ARE CONSIDERED PRELJMINARY -NOT FOR
CONSTRUCTION OR RECORDING UNLESS THE STRUCTURAL ENGINEER OF
RECORD'S SEAL IS AFFIXED MUH WRITTEN SIGNATURE.
PROJECT NUMBER 24-0069
PROJECT MANAGER DST
PROJECT ENGINEER PIMP
PROJECT DRAFTER MDF
CARUSO - TU RLEY- SCOTT- INC
consulting structural engineers
1215 West Rio Salado Parkway, Suite 200
Tempe, Arizona 85281 (480) 774-1700 (774-1701 FAX)
www.ctsaz.com
ARCHITECTURAL SEAL
DATE ISSUE
D/MM/YY XXXX
Q DATE REVISION
PROJECT NAME / LOCATION
LA QUINTA
78-730 CA-111
LA QUINTA, CA 92253
PROJECT INFORMATION
DATE: MONTH DAY, YEAR
PROJECT NO. ####-## [##,####]
DELIVERY TYPE: V-BOX
DRAWN BY: MDF
REVIEWED BY: PIMP
TITLE
TYPICAL
DETAILS
SHEET NUMBER
S1,2
PER ANSI MH16.1: NOTES — TYP U.N.O.: FLOOR NOTES — TYP U.N.O.:
THE OWNER SHALL MAINTAIN THE STRUCTURAL INTEGRITY OF THE INSTALLED A. CRACKS ARE ALLOWED UP TO 0.012 INCHES WIDE. ANY CRACKS 1. VERIFY ALL DIMENSIONS AND ELEVATIONS WITH THE ARCHITECTURAL DRAWINGS
RACK SYSTEM BY ASSURING PROPER OPERATIONAL, HOUSEKEEPING, AND WIDER THAN THIS WITHIN 4" INCHES OF THE ANCHOR WILL NEED TO AND FIELD CONDITIONS. BUILDING DIMENSIONS AND ELEVATIONS, WHERE SHOWN,
MAINTENANCE PROCEDURES INCLUDING, BUT NOT LIMITED TO, THE BE REPAIRED WITH SIKADUR-55 SLV PER MANUFACTURER'S WERE PROVIDED BY THE ARCHITECT AND IT IS THE CONTRACTOR'S RESPONSIBILITY
FOLLOWING: INSTRUCTIONS. TO VERIFY AND COORDINATE ALL DIMENSIONS PRIOR TO PROCEEDING WITH THE
1. PROHIBIT ANY OVERLOADING OF ANY PALLET POSITIONS AND OF THE B. ANCHORS SHALL BE INSTALLED A MINIMUM OF 4" AWAY FROM ANY WORK. ANY DISCREPANCIES SHALL BE RESOLVED THROUGH THE ARCHITECT.
OVERALL RACK SYSTEM. CONSTRUCTION/EXPANSION JOINT WITHIN THE EXISTING CONCRETE 2 - SLAB ON GRADE. As SHOWN ON PLAN INDICATES EXISTING wooD STUD WALL. ZUN2. REGULARLY INSPECT FOR DAMAGE. IF DAMAGE IS FOUND, IMMEDIATELY C. CONTRACTOR SHALL FIELD VERIFY THAT THE EXISTING CONCRETE SLAB _
FOR
ISOLATE THE AFFECTED AREA. HAVE A STORAGE RACK DESIGN ON GRADE IS A MINIMUM OF 4" IN THICKNESS PRIOR TO 3. SIZES. STEEL STUDS SHALL EAS SHOWN "SP SPACED AT PLANC 6ATES " 0 C. SEE G S.N,STEEL STUD TTYPICALL, SEEPLAN DETAILS, KA M US + K E L L E R
PROFESSIONAL EVALUATE THE DAMAGE, AND UNLOAD, REPLACE OR CONSTRUCTION. PLANS AND OTHER DETAILS FOR ADDITIONAL INFORMATION.
REPAIR IF DIRECTED BY THE PROFESSIONAL, ANY DAMAGED COLUMNS, D. ALL STORAGE RACKS (EXCLUDING WALL FIXTURES) SHALL MAINTAIN A
BEAMS, OR OTHER STRUCTURAL COMPONENTS TO RESTORE THE SYSTEM MINIMUM CLEARANCE OF 6" FROM ANY ADJACENT BUILDING 4. +Z1 ZZZ+— AS SHOWN ON PLAN INDICATES EXISTING 8- MASONRY WALL.
TO AT LEAST ITS ORIGINAL DESIGN CAPACITY. COMPONENTS. 562-216-5244
3. REQUIRE ALL PALLETS TO BE MAINTAINED IN GOOD, SAFE, OPERATING 5. THE EXISTING CONDITIONS DEPICTED ON THESE DRAWINGS ARE BASED ON THE BEST
CONDITION. AVAILABLE INFORMATION AND SHALL BE VERIFIED BY THE CONTRACTOR PRIOR TO kka la.wm
4. ENSURE THAT PALLETS ARE PROPERLY PLACED ONTO PALLET LOAD CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE
SUPPORT MEMBERS IN A PROPERLY STACKED AND STABLE POSITION. STRUCTURAL ENGINEER IMMEDIATELY.
5. REQUIRE THAT ALL GOODS STORED ON EACH PALLET BE PROPERLY
STACKED AND STABLE. CONSULTANTS
6. PROHIBIT DOUBLE -STACKING OF ANY PALLET POSITION, INCLUDING THE
TOP -MOST POSITION, UNLESS THE RACK SYSTEM IS SPECIFICALLY
DESIGNED FOR SUCH LOADING.
7. ENSURE THAT THE RACKS ARE NOT MODIFIED OR REARRANGED IN A
MANNER NOT WITHIN THE ORIGINAL DESIGN CONFIGURATIONS PER 1.4.4
OR AS MIGHT INVALIDATE THE PLAQUE INFORMATION PER 1.4.2.
' 3 2 1 = = o,,ZS,Za
L '+ \ LL__J
���— ��"" ARCHITECTURAL SEAL
�_- - - it
1 +
\ O O
AT ST-01 II II
x120" HEIGHT. I II II
os � IIII
— ------------------
41
i
II
5 4 � r
- - ----- L 1IIII
II II
II II
_ — NEW STEEL
STUD WALL.
III I �I
II
AT PF-03 AT PF-05 AT PF-05
EXISTING x120" HEIGHT. x96" HEIGHT. x96" HEIGHT.
MASONRY WALL. e II II
II II DATE ISSUE
TI
00
FTMI
O ❑
O ,p O
--� AT PF-05 O
x96" /
HEIGHT.OLE=F—
HH
O
I o
I10,
os OAT ST-01 IIII
x120" HEIGHT. pg O
PF-05C x9 O
x96"
O HEIGHT. O
I
EXISTING CONCRETE
I SLAB ON GRADEEl
-
TYP.
EXISTING STEEL EXISTING STEEL D/MM/YY XXXX
COLUMN. COLUMN.
DATE REVISION
II
I I PROJECT NAME /LOCATION
IIII II
I I II II
IIII fiW BELO
og I I
II
06 AT PF-05C
x96" AT ST-01 HEIGHT. 10 / LA Q UINTA
x120" HEIGHT.
78-730 CA-111
AT PF-05
x96" LA QUINTA, CA 92253
- - - - HEIGHT.
O II
III
I
-----------� �-- III
PROJECT INFORMATION
II II
- - � DATE: MONTH DAY, YEAR
PROJECT NO. ####-## [##.####]
� — DELIVERY TYPE. V-BOX
1 �7�O1�-�0 ---1�-i�L1 �1/�1_--711�-������1����011�1l_�-7�lT�-i�li��� _OI/1 -- -- - =Z-�
12 12 11
DRAWN BY: MDF
AT PF-05 AT PF-05 AT PF-05A
x96" HEIGHT. x96" HEIGHT. x120" HEIGHT. SHEET INDEX REVIEWED BY: PMP
FIXTURE PLAN DETAILS SHEET DESCRIPTION
SCALE: 3/16" - V-0" --- S1.1 GENERAL STRUCTURAL NOTES TITLE
01-19 S1.2 DETAILS
FIXTURE PLAN
--- S2.1 FIXTURE PLAN
THESE DRAWINGS/CALCULATIONS ARE CONSIDERED PRELIMINARY -NOT FOR
CONSTRUCTION OR RECORDING UNLESS THE STRUCTURAL ENGINEER OF
RECORD'S SEAL IS AFFIXED WITH WRITTEN SIGNATURE.
PROJECT NUMBER 24-0069 PROJECT MANAGER DST
PROJECT ENGINEER PMP PROJECT DRAFTER MDF SHEET NUMBER
CARUSO - TURLEY- SCOTT- INC
consulting structural engineers
1215 West Rio Salado Parkway, Suite 200
Tempe, Arizona 85281 (480) 774-1700 (774-1701 FAX) S2,1
www.ctsaz.com