BCOM2024-0157BUILDING PERMIT
DESIGN & DEVELOPMENT
DEPARTMENT
78-495 CALLE TAMPICO
LA QUINTA, CALIFORNIA 92253
Permit Type: Building Commercial
Permit Number: BCOM2024-0157
Property Address: 78870 HIGHWAY 111
APN: 643080003
Legal Description Parcel 5 PM 172/21 PM 25865
Property Zoning: CR, 5
Valuation: $35,000.00
PHONE (760) 777-7125
WWW.LAQUINTACA.GOV
APPLIED DATE: 11/07/2024
ISSUED DATE: 02/19/2025
CALIFORNIA
Owner
Applicant: Ellie Alikhani
15 HUBBLE SUITE 200, IRVINE, CA 92618
Contractor: Brian Martinez / 1100427
26760 Black Horse Cir, Corona, CA 92883
PRIOR TO THE ISSUANCE OF THIS PERMIT FOR CONSTRUCTION, ALTERATION, IMPROVEMENT, DEMOLITION, OR REPAIR THE OWNER, APPLICANT AND/OR
CONTRACTOR UNDER PENALTY OF PERJURY HAVE AFFIRMED WHEN APPLICABLE, THROUGH THE SUBMITTAL OF FORMS OR BY OTHER ELECTRONIC MEANS, THE
FOLLOWING:
LICENSED CONTRACTOR OR OWNER -BUILDER DECLARATION (1 or 2)
1) They are licensed under provisions of Chapter 9 (commencing with
Section 7000) of Division 3 of the Business and Professions Code, and the
referenced
License is in full force and effect, or;
2) That they are exempt from the Contractors' State License Law for the
reason(s) indicated by either (2)(a) and/or (2)(b), or (2)(c) where he or
she is exempt from licensure by a valid exemption. [Section 7031.5,
Business and Professions Code: Any city or county that requires a permit
to construct, alter, improve, demolish, or repair any structure, prior to its
issuance, also requires the applicant for the permit to file a signed
statement that he or she is licensed pursuant to the provisions of the
Contractors' State License Law (Chapter (commencing with Section 7000)
of Division 3 of the Business and Professions
Code] Any violation of Section 7031.5 by any applicant for a permit
subjects the
applicant to a civil penalty of not more than five hundred dollars ($500).)
a) As owner of the property, or my employees with wages as their sole
compensation, will do all of or portions of the work, and the structure is
not intended or offered for sale (Section 7044, Business and Professions
Code: The Contractors' State License Law does not apply to an owner of
property who, through employees' or personal effort, builds or improves
the property, provided that the improvements are not intended or offered
for sale. If, however, the building or improvement is sold within one year of
completion, the Owner -Builder will have the burden of proving that it was
not built or improved for the purpose of sale.).
b) As owner of the property, will be exclusively contracting with licensed
c) Are exempt from licensure under the Contractors' State License Law.
As an Owner -Builder, they acknowledge that, except for their personal
residence in which they must have resided in for at least one year prior to
completion of the improvements covered by this permit, they cannot legally
sell a structure built as an owner -builder if it has not been constructed in
its entirety by licensed contractors. It is understood that a copy of the
applicable law, Section 7044 of the Business and Professions Code, is
available upon request when this application was submitted at the
following Web site:
http://www.leginfo.ca.gov/calaw.html.
DECLARATION REGARDING CONSTRUCTION LENDING AGENCY (If
applicable)
A construction lender will be used for completion of the improvements
covered by this permit and the name and information of which is on file for
public inspection during the regular business hours of the public entity.
Failure of the applicant to indicate the construction lender on the
application does not relieve that person of the requirement to give the
construction lender preliminary notice from that duty.
WORKERS' COMPENSATION DECLARATION (1, 2 or 3)
WARNING: FAILURE TO SECURE WORKERS' COMPENSATION COVERAGE IS
UNLAWFUL, AND SHALL SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND
CIVIL FINES UP TO ONE HUNDRED THOUSAND DOLLARS ($100,000), IN ADDITION
TO THE COST OF COMPENSATION, DAMAGES AS PROVIDED FOR IN SECTION
3706 OF THE LABOR CODE, INTEREST, AND ATTORNEY'S FEES.
1) Has and will maintain a certificate of consent to self -insure for workers'
compensation, issued by the Director of Industrial Relations as provided for
by Section 3700 of the Labor Code, for the performance of the work for
which this permit is issued.
2) Has and will maintain workers' compensation insurance, as required by
Section 3700 of the Labor Code, for the performance of the work for which
this permit is issued.
3) Certifies that, in the performance of the work for which this permit is
issued, shall not employ any person in any manner so as to become subject
to the workers' compensation laws of California, and agree that, if should
become subject to the workers' compensation provisions of Section 3700 of
the Labor Code, shall forthwith comply with those provisions.
NOTICE TO APPLICANT (1, 2 and 3)
1) Each person upon whose behalf this application was made, each person
at whose request and for whose benefit work is being performed under or
pursuant to any permit issued as a result of this application, the owner, and
the applicant, each agrees to, and shall defend, indemnify and hold harmless
the City of La Quinta, its officers, agents, and employees for any act or
omission related to the work being performed under or following issuance of
this permit.
2) Any permit issued as a result of this application becomes null and void if
work is not commenced within 360 days from date of issuance of such
permit, or if cessation of work for 180 days will subject permit to
cancellation. On or after January 1, 2019, every permit issued shall become
invalid unless the work on the site authorized by such permit is commenced
within 12 months after its issuance, or if the work authorized on the site by
such permit is suspended or abandoned for a period of 12 months after the
time the work is commenced.
3) Certified that they read the application and state that the information
provided is correct. Agree to comply with all city and county ordinances and
state laws relating to building construction, and hereby authorize
representatives of this city to enter upon the above -mentioned property for
inspection purposes.
IMPORTANT: An Application for Permit was made to the Building Official,
subject to the conditions and restrictions set forth at the time of application,
which is now hereby an Issued Permit. If any part of the information being
supplied on this permit is inaccurate or untrue, please contact the City of La
Quinta at (760) 777-7125 immediately for correction.
Printed: 5/16/25 12:20 pm Page 1 of 5
Permit Type
Building Commercial
BUILDING PERMIT
Permit Number:
Property Address
BCOM2024-0157
78870 HIGHWAY 111
SHELL IMPROVEMENT IN ANTICIPATION OF NEW TENANT, REMOVAL OF INTERIOR PARTITION WALLS, ADDING NEW RESTROOMS.
DOUBLE DOOR AT REAR, ADJUSTMENT TO EXISTING STORE FRONT ENTRY AND MECHANICAL CHANGEOUTS
[VB/M-OCC/124-OL/SPRINKLED] THIS PERMIT DOES NOT INCLUDE T-BAR CEILING OR INSTALLATION OF GENERAL LIGHTING. 2022
CALIFORNIA BUILDING CODES.
,inntructinn Dpt;:.
Commercial Work Type Remodel, Stores/Customer
Building/Unit
M: Stores, Markets, Gas
Gross Square Footage 7560
Service
Occupancy
Station
Classification(s)
Conditioned Square
7560
Fire Sprinkler Square
7560
Number of Floors
1
Footage
Footage
Occupant Load
124
Construction Type
V-B
Code Edition
2022
Original Valuation
35000.00
Number of
1
Number of
1
Door/Window
Door/Window
Retrofit/Repair
New/Alteration
Number of Partition(s)
1
New Electrical Square
145
Number of
15
Footage
Receptacle/Switch/Lig
Electrical Service? No
Number of Ventilation 2
Fan(s)
Number of Water 1
Heater(s)
Sewer Connection? No
Number of Dispensing 1
Units - Gas (TUMF)
Art in Public Places No
Fund Exempt
City Limits Within La Quinta Limits
Lot Size 11232.8
ht(s)
Temporary Power
No
Number of 4
Service?
Condenser(s)
Number of Plumbing
4
Number of Roof Drains 0
Fixtures/Traps
Water System Install
Yes
Back Flow Prevention No
or Alteration?
Device?
Grease Interceptor or
No
Transportation Uniform No
Sand/Oil Separator?
Mitigation Fee
Applicable
City Development
No
Number of Hotel 3
Impact Fee Applicable
Rooms (DIF/TUMF)
Zoning
CR
General Plan CG
Subdivision Name PM 25865 Lot Number 5
Legal Description Parcel 5 PM 172/21 PM
25865
Type Group Sq Ft Value
Printed: 5/16/25 12:20 pm Page 2 of 5
Permit Type
Building Commercial
BUILDING PERMIT
Permit Number:
Property Address
BCOM2024-0157
78870 HIGHWAY 111
Invoice No. Fee
INV-00012833 Condenser/Compressor
Ventilation Fan PC
Door/Window, Retro/Repair
Art in Public Places - Commercial
Non -Residential Electrical PC
Partition
Building Standards Administration
Door/Window, Retro/Repair PC
Ventilation Fan
Water System Inst/Alt/Rep
Partition PC
Fixture/Trap PC
Fixture/Trap
Door/Window, New/Alt PC
Digital Archiving and Records Management Fee
Condenser/Compressor PC
Non -Residential Electrical
Door/Window, New/Alt
Receptacle, switch, lighting, or other outlets PC
Water Heater/Vent PC
SMI - Commercial
Water Heater/Vent
Receptacle, switch, lighting, or other outlets
Technology Enhancement Fee
Water System Inst/Alt/Rep PC
Fee Amount
Amount Paid
$190.88
$190.88
$12.72
$12.72
$80.16
$80.16
$175.00
$175.00
$110.70
$110.70
$95.43
$95.43
$2.00
$2.00
$78.26
$78.26
$31.82
$31.82
$15.91
$15.91
$175.60
$175.60
$63.64
$63.64
$63.64
$63.64
$145.06
$145.06
$24.00
$24.00
$127.24
$127.24
$143.15
$143.15
$127.25
$127.25
$31.81
$31.81
$9.54
$9.54
$9.80
$9.80
$15.91
$15.91
$31.81
$31.81
$78.32
$78.32
$15.91
$15.91
Total for InvoiceINV-00012833 $1,555.56 $1,655.56
Grand Total for Permit $1,855.56 $1,855.56
Workflow Step / Action Name Action Type Start Date End Date
Application Completeness Check v.1 11/07/2024 14:38 11/07/2024 14:39
----------------------------------------------------------------------------------------------------------------------------------------
Submittal Document Verification v.1 Generic Action 11/07/2024 14:39
Plan Check v.1
11/07/2024 0:00
12/11/2024 9:14
----------------------------------------------------------------------------------------------------------------------------------------
Building Major Review v.1
Receive Submittal
11/07/2024 0:00
12/11/2024 9:14
Permit Issuance v.1
12/11/2024 11:47
02/19/2025 14:58
----------------------------------------------------------------------------------------------------------------------------------------
Contractor / Owner -Builder Information v.1
Generic Action
12/11/2024 11:47
----------------------------------------------------------------------------------------------------------------------------------------
Verify & Invoice Fees v.1
Generic Action
02/19/2025 11:36
----------------------------------------------------------------------------------------------------------------------------------------
Ready to Issue v.1
Generic Action
02/19/2025 14:58
----------------------------------------------------------------------------------------------------------------------------------------
Verify Fee Payment & Issue Permit v.1
Generic Action
02/19/2025 14:58
----------------------------------------------------------------------------------------------------------------------------------------
Print, Attach, and Email Building Permit v.1
Create Report
02/19/2025 14:58
02/19/2025 14:58
Inspections - Do Not Pour Concrete Until Approved v.1
02/27/2025 0:00
----------------------------------------------------------------------------------------------------------------------------------------
111U V. I
Inspection
----------------------
Setbacks v.1
Inspection
----------------------
-' ' '/.1
..-
Inspection
Printed: 5/16/25 12:20 pm Page 3 of 5
BUILDING PERMIT
Permit Type: Building Commercial
Permit Number: BCOM2024-0157
Property Address: 78870 HIGHWAY 111
Underground Plumbing v.1
Inspection
02/27/2025
0:00
03/03/2025
15:48
----------------------------------------------------------------------------------------------------------------------------------------
Underground Plumbing v.2
Inspection
03/05/2025
0:00
03/06/2025
15:05
----------------------------------------------------------------------------------------------------------------------------------------
Water Line v.1
Inspection
Inspections - Cover No Work Until Approved v.1
02/27/2025
0:00
----------------------------------------------------------------------------------------------------------------------------------------
Roof Nail v.1
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
Okay to Wrap v.1
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
Framing v.1
Inspection
02/27/2025
0:00
03/03/2025
15:56
----------------------------------------------------------------------------------------------------------------------------------------
Framing v.2
Inspection
03/06/2025
0:00
03/07/2025
15:31
----------------------------------------------------------------------------------------------------------------------------------------
Framing v.3
Inspection
03/14/2025
0:00
03/18/2025
14:40
----------------------------------------------------------------------------------------------------------------------------------------
Framing v.4
Inspection
03/26/2025
0:00
03/28/2025
13:05
----------------------------------------------------------------------------------------------------------------------------------------
Rough Electrical v.1
Inspection
02/27/2025
0:00
03/03/2025
15:57
----------------------------------------------------------------------------------------------------------------------------------------
Rough Electrical v.2
Inspection
03/14/2025
0:00
04/03/2025
10:54
----------------------------------------------------------------------------------------------------------------------------------------
Rough Electrical v.3
Inspection
04/09/2025
0:00
04/10/2025
11:32
----------------------------------------------------------------------------------------------------------------------------------------
Rough Mechanical v.1
Inspection
03/26/2025
0:00
03/28/2025
13:08
----------------------------------------------------------------------------------------------------------------------------------------
Rough Plumbing v.1
Inspection
03/14/2025
0:00
03/18/2025
14:31
----- --------------------------------
Rough Plumbing v.2
Inspection
03/26/2025
0:00
03/28/2025
13:06
--------------------------------------------------
Rough Fire Clearance Bldg v.1
Inspection
----------------------------------------------
Shower Pan v.1
Inspection
----------------------------------
Insulation v.1
Inspection
.. .. .. .. .. .. .. .. .............................................................................................................
Drywall Nail v.1
Inspection
--------------------------
T-Bar/Overhead v.1
............................................
Inspection
------------------------------------------------
Exterior Lath v.1
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
Gas Test v.1
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
Sewer Connection v.1
Inspection
Inspections - Masonry v.1
Inspections - Electrical for Meter Release v.1
Temporary Power v.1
Inspection
---------------------------------------------------
Temp Use of Permanent Power v.1
--
Inspection
Inspections - Final v.1
04/09/2025 0:00
----------------------------------------------------------------------------------------------------------------------------------------
rinai rare v.]
Inspection
----------------------------------------------------------------------------------------------------------------------------------------
Final Building v.1
Inspection 04/09/2025 0:00 04/11/2025 13:27
Certificate of Occupancy v.1
----------------------------------------------------------------------------------------------------------------------------------------
Issue Certificate of Occupancy v.1
Create Report
Construction or work for which a permit is required shall be subject to inspection by the building official and such construction or work
shall remain visible and able to be accessed for inspection purposes until approved. Approval as a result of an inspection shall not be
construed to be an approval of a violation of the provisions of the applicable code and other ordinances of the jurisdiction. Inspections
presuming to give authority to violate or cancel the provisions of the applicable code and other ordinances of the jurisdiction shall not be
valid. It shall be the duty of the owner or the owner's authorized agent to cause the work to remain visible and able to be accessed for
inspection purposes. Neither the building official nor the jurisdiction shall be liable for expense entailed in the removal or replacement of
any material required to allow inspection.
It shall be the duty of the holder of the building permit or their duly authorized agent to notify the building official when work is ready for
inspection. It shall be the duty of the permit holder to provide access to and means for inspections of such work that are required by this
code.
Printed: 5/16/25 12:20 pm Page 4 of 5
BUILDING PERMIT
Permit Type: Building Commercial
Permit Number: BCOM2024-0157
Property Address: 78870 HIGHWAY 111
A building or structure shall not be used or occupied in whole or in part, and a change of occupancy of a building or structure or portion
thereof shall not be made, until the building official has issued a certificate of occupancy therefor as provided herein. Issuance of a
certificate of occupancy shall not be construed as an approval of a violation of the provisions of the applicable code and other ordinances
of the jurisdiction. Certificates presuming to give authority to violate or cancel the provisions of this code or other ordinances of the
jurisdiction shall not be valid.
A person shall not make connections from a utility, a source of energy, fuel, or power, or a water system or sewer system to any building
or system that is regulated by the applicable code and other ordinances of the jurisdiction for which a permit is required, until approved by
the building official.
Printed: 5/16/25 12:20 pm Page 5 of 5
CAL FIRE — RIVERSIDE UNIT
RIVERSIDE COUNTY FIRE DEPARTMENT �Cci
BILL WEISER -- FIRE CHIEF
OFFICE OF THE FIRE MARSHAL — LA QUINTA-CALIFORNIA
-
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7078
• www.rvcfire.org
November 18, 2024
Ellie Alikhani
Re: Remodel
BCOM2024-0157 / 78870 Highway 111
The building plan for the above referenced project was reviewed and approved by the Fire Department with
the following conditions.
1) Separate permits and submittals to the Office of the Fire Marshal are required for modifications to the
existing fire sprinkler system and fire alarm system, where applicable.
The approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by email:
FireBusines sMailkLaQuintaCA. gov
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7078.
Chris Cox — Supervising Fire Marshal
' Building Permit Number:
Project Description: SFR
S Exempt: ❑
(Materials may contain hazardous wastes and
are not subject to recycling provisions)
oFT Construction Debris Management Plan
Plan Submittal Date
Job Site Address
Owner's Name
Number, Street, or PO Box
City, State, Postal Code
Owner's Phone Number
Owner's E-Mail Address
Project Manager's Name
Project Manager's Phone Number
Project Manager's E-mail Address
Builder / Contractor
Number, Street or PO Box
City, State, Postal Code
Project Square Footage
Approval By Burrtec
Date of City Approval
78870 Highway-111, La Quinta, CA 92253
Milan LQ One XI, LLC & Milan LQ Tuscany, LLC c/o Milan Cal
701 S. Parker St Suite 5200
Orange, CA 92868
949-230-1286
diane0milancap.com
Diane Scioli
949-230-1286
diane .milancap.com
Mart Construction
29192 Ocotillo Dr
Lake Elsinore, CA 92530
7,560
Materials To Be Discarded:
Product
Trash
Asphalt
Brick/Block
Cardboard
Commingled
Concrete
Drywall
Donated / Reuse"
'Describe Items
Tons
Not recyclable Product Tons
Recyclable Masonry (broken) 0.00 Recyclable
Recyclable Plaster 9.45 Recyclable
Recyclable Scrap Metal 0.00 Recyclable
Recyclable Tile (floor) 0.83 Recyclable
Recyclable Tile (roof) 1.06 Recyclable
Recyclable Wood 14.36 Recyclable
Recyclable Landscape Debris 1 0.00 Recyclable
27.97
0.00
0.00
2.04
0.00
37.80
4.01
0.00
Totals: Rec cle Trash Projected Diversion:
69.61 28.0 71.32%
I understand it is the property owner's responsibility to submit copies of weight tickets or receipts to the District
Environmental Coordinator as these hauls occur. I hereby certify that completion, implementation and adherence of the
Debris Management Plan (DMP) for the above named project shall guarantee that at least 65% of the jobsite waste is
diverted from landfilling. The remaining material will be recycled or reused. I will divert, for recycling or re -use, remaining
materials generated from the first day of the project through the completion of the project in accordance with this plan. This
DMP is issued in the name of the property owner(s) and shall remain their property throughout the construction and/or
demolition project. A contractor serving as agent of the owner may obtain a DMP for the owner. However, the DMP is still
issued in the name of the property owner(s) and the owner retains legal responsibility for ensuring that the provisions of the
DMP are adhered to. The property owner(s) and general contractor shall be kept informed of the diversion progress through
bi-monthly reports. If self -hauling, all refuse material from this project site must be taken to an approved recycler or transfer
02/19/2025
Owner / SeTeloper / Project Manager / Superintendant Date
Construction Debris Management Plan
Summary of Requirements
As of January 1, 2017, The Green Building Standards Code (CALGreen) requires that the construction
of most new structures in the State of California comply with sections 4.408 and 5.408 of the code in
accordance with Assembly Bill 939 requiring that no more than 35% of jobsite waste be disposed of as
trash at local land fill sites and transfer stations. Exceptions may be made for certain projects under
certain conditions.
The City of La Quinta is committed to the highest level of environmental respect, to conserving our
precious natural resources and setting an example to provide for a better world for generations to
come. Recycling helps keep reusable resources out of landfills and will also reduce disposal costs.
IMPORTANT: Burrtec Waste & Recycling Services is the City's franchise
hauler. If you choose to self -haul any recyclables or trash, you must
provide copies of all weight tickets and/or receipts from the transfer
station, landfill, or recycler as the job progresses. Clean-up companies
and other haulers are not permitted to haul waste or recyclables from the
City of La Quinta. Self -haul weight tickets should be submitted to: Mike
Veto, District Environmental Coordinator - mveto@burrtecdesert.com, or
faxed to (760) 340-0417, or mailed to: 41575 Eclectic Street, Palm
Desert, CA. 92260.
068-
City of La Quinta Permit # BCOM2024-0157
November 22, 2024 BVNA#
Project Description: TI Remodel
Project Address: 78870 CA — 111, La Quinta, CA 92253
Application/ Permit #: BCOM2024-0157
Occupancy: M
Type of Construction: VB
Sprinklers: Yes
Stories: 1
Floor Area (s.f.): 7,560
Fire Hazard Severity Zone/ WUI: No
Flood Zone: No
Fire Alarm: Not Specified
Bureau Veritas has completed the first plan review of the below listed documents on behalf of the
City of La Quinta Building & Safety Department:
GENERAL INSTRUCTIONS
1. This plan review has been made to verify conformance to minimum requirements of codes
and ordinances adopted by the City of La Quinta. Codes in effect for this project include the
2022 editions of the California Building Code (CBC), California Residential Code (CRC),
California Green Building Code (CGBC), California Plumbing Code (CPC), California
Mechanical Code (CIVIC), California Electrical Code (CEC), and California Energy Code
(CEnC). The CBC is based on the 2021 editions of the International Building Code, which
was published by the International Code Council. The CPC and CIVIC are based on the 2021
edition of the Uniform Plumbing and Mechanical Codes, respectively, which were published
by IAPMO. The CEC is based on the 2020 edition of the National Electrical Code published
by the National Fire Protection Association (NFPA). Applicable code sections are referenced
after each item in this list.
2. These plans and documents have been reviewed for compliance with the applicable code
requirements and instructions of the jurisdiction. The stamping of these plans shall not be
held to permit or be an approval of a violation of any applicable codes and/or standards nor
relieve the owner, design professional of record or contractor of compliance with any
applicable codes and/or standards. Plan review of documents does not authorize
construction to proceed in violation of any federal, state, nor local regulation.
3. The review does not necessarily include errors and omissions. Complete compliance is the
responsibility of the designer.
4. All comments shall be resolved on the plans prior to the recommendation to the governing
body for approval.
5. The comments identified in other sections of this review require clarifications/corrections
before this plan check can be completed.
6. For reference for explanations in the examiner's comment sections, italic text refers to the
initial submittals, bold text on second submittals, and underlined text on third submittals.
7. Please annotate your response in the areas on each comment, please see the comment
section,
8. Submit a list showing any changes to the plan or previously submitted documents that are
not the result of the plan check comments. Please "cloud" and/or "delta" all revisions made on
plans due to this comment list as well as any other design changes.
Page 1 of 4
►.0 vF
City of La Quinta Permit # BCOM2024-0157
November 22, 2024 m N BVNA#
1826
IN ORDER TO PROCESS THIS PLAN REVIEW PLEASE PROVIDE THE NAME AND
PHONE NUMBER OF THE INDIVIDUAL WHO PREPARED THESE PLAN REVIEW
RESPONSES
Iill V_1iv, 1=1
PHONE:
Please provide ONE full COMPLETE electronic submittal, with supporting
documentation, and answers to ALL comments listed in the comment section and
submit to:
City of La Quinta, 78495 Calle Tampico, La Quinta, CA 92253
Respectfully Submitted,
Arch/Access/Struc: Dwayne Butz I dwayne.butz@bureauveritas.com 1 714-235-4137
Mech/Elec/Plum: James Waters I james.waters@bureauveritas.com 1 760-497-1392
Please write the sheet number, detail number, and/or location indicating where the comment is located. Please be
specific as to where comment items have been addressed so that recheck may be expedited. To aid in the
plan review process —please indicate in the space adjacent to each comment or on a separate sheet, the sheet and
the exact location on the sheet where corrections have been made (e.g., Detail S of Sheet 3). Please "cloud" and/or
"delta" all revisions made on plans due to this comment list as well as any other design changes.
JURISDICTIONAL COMMENTS
No comments
ARCHITECTURAL COMMENTS
1. Sheet number may be given as a quick reference. Apply comments to all applicable
locations.
RESPONSE:
2. (Sheet T-1) Please add the following to Building Analysis.
RESPONSE:
• Building height above grade
• Fire Alarm (Yes or No)
3. (Sheet T-1) Please coordinate Egress Table with Floor Plan.
RESPONSE:
• Egress Table (3) Doors at 72"
• Floor Plans (2) Doors at 72"
4. (Sheet T-1) Please coordinate Sheet Index with provided sheets. Sheets may need to be
added, removed or placed in proper sequence.
RESPONSE:
• M002
• E003
5. Please provide Life Safety Plan. Plan shall include...
RESPONSE:
Page 2 of 4
►.0 vF
City of La Quinta Permit # BCOM2024-0157
November 22, 2024 m N BVNA#
1826
It
• Fire Extinguishers [906 CBC]
• Maximum Travel Distance [1007 CBC] [1017 CBC]
• Emergency Lighting [1008 CBC]
• Exit Signs [1013 CBC]
6. (Sheet A5.0) Architectural and Structural to coordinate. Wood and Steel framing
referenced within plans and calculations. For example...
RESPONSE:
• Detail (1/A5.0) = Steel Framing
• Detail (4/S100) = Wood Framing
• Calculations (Page 7) = New Bearing Studs (2) 2x6 Douglas Fir -Larch
ACCESSIBILITY COMMENTS
No comments
GREEN BUILDING COMMENTS
No comments
ENERGY COMMENTS
No comments
ELECTRICAL COMMENTS
1. A readily accessible electrical disconnecting means within sight of the Water Heater that
will completely de -energize the appliance.
RESPONSE:
2. Show Aqua State pump electrical and Circuit breaker.
RESPONSE:
3. A readily accessible electrical disconnecting means within sight of the Water Heater that
will completely de -energize the appliance.
RESPONSE:
4. Identify #7 Sheet E101.
RESPONSE:
5. For show -window lighting, a load of not less than 660 volt-amperes/linear meter or 200
volt-amperes/linear foot shall be included for a show window, measured horizontally
along its base. [220.43(A) CEC]
RESPONSE:
MECHANICAL COMMENTS
1. Please clarify two conflicting notes say Heat pumps on roof are to be replaced, other say
the Mech contractor is to rehab units on roof.
RESPONSE:
Page 3 of 4
►.0 vF
City of La Quinta Permit # BCOM2024-0157
November 22, 2024 m N BVNA#
1826
It
PLUMBING COMMENTS
1. A water heater installation shall be provided with overpressure protection by means of
an approved, listed device installed in accordance with the terms of its listing and the
manufacturer's installation instructions. [§ 504.4
RESPONSE:
2. Show location of water heater and access.
RESPONSE:
3. If Water Heater is in attic show how it will be seismic restrained (507.2)
RESPONSE:
4. Water heaters shall be anchored or strapped to resist seismic motions. Strapping shall
be at points within the upper 1/3 and lower 1/3 of its vertical dimensions. The straps shall
be a minimum of 4" above the controls. [§507.2 CPC]
RESPONSE:
5. New or repaired potable water systems shall be disinfected prior to use. [§609.9 CPC]
RESPONSE:
6. Materials for drainage piping shall be in accordance with one of the referenced
standards in Table 701.1 except that [§ 701.1 CPC]:
No galvanized wrought -iron or galvanized steel pipe shall be used underground and
shall be kept not less than six inches above ground.
ABS and PVC DWV piping installations shall be installed in accordance with applicable
standards referenced in Table 1401.1. Except for individual single-family dwelling units,
materials exposed within ducts or plenums shall have a flame -spread index of a
maximum of twenty-five and a smoke -developed index of a maximum fifty, where tested
in accordance with ASTM E 84 and UL 723.
No vitrified clay pipe or fittings shall be used above ground or where pressurized by a
pump or ejector. They shall be kept not less than twelve inches below ground.
RESPONSE:
STRUCTURAL COMMENTS
1. (Sheet A5.0) Architectural and Structural to coordinate. Wood and Steel framing
referenced within plans and calculations. For example...
RESPONSE:
Detail (1/A5.0) = Steel Framing
Detail (4/S100) = Wood Framing
Calculations (Page 7) = New Bearing Studs (2) 2x6 Douglas Fir -Larch
FIRE COMMENTS
No comments
END OF COMMENTS