Piazza Serena TR 30092 BCPR2023-0016i3
PLAN • -•-
cMrnn<<�
Plan Type:
Building Construction Plan Review Plan No.: BCPR2023-0016
App Date:
08/07/2023
Work Class:
Building Construction Plan Review District: City of La Quinta
Exp Date:
08/06/2024
Status:
Expired Square Feet: 0.00
Completed:
NOT COMPLETED
Valuation:
$0.00 Assigned To:
Approval
Expire Date:
NOT AVAILABLE
Description:
BELLA AT PIAZZA SERENA CODE UPDATE/ TRACT 30092 CONSTRUCTION MASTER PLANS FO
DWELLINGS (SFD x 3) - PLANS 1, 2, AND 3.2022 CALIFORNIA BUILDING CODES.
PLAN 1: 2,446SF
PLAN 2: 2,702SF
PLAN 3: 2,833SF
REVISION #1 - INTERIOR DOOR CHANGES, UPDATED MECHANICAL PLANS + ENERGY DOCUM
TO CORRECT INCONSISTENCIES.
Parcel: 764460046 Main
I Address: Bella At Piazza Serena Main
I Zone:
Applicant Contractor
Larry Liebel Larry Liebel
391 N. Main Street, Suite 205 391 N. Main Street, Suite 205
Corona, CA 92878 Corona, CA 92878
Plan Custom Fields
Tract / Subdivision
BELLA AT PIAZZA
Name
SERENA
Number of Plan Types SFDX3
Is this a revision?
No
City Limits
Within La Quinta City
Limits
Lot Number
M
Lot Size
16778.4
Tract Number 30092
Other Notes
Zoning RL
Acreage 2.74
Legal Description Lot M MB 373/59 TR
30092
Model/Series Name 2022 CODE UPDATE
Code Edition
General Plan
Subdivision Name
Centerlines
2022
LDR, ROW
TR 30092
92527, 92525, 92528,
92522, 92523, 92526,
92520, 92521, 93118,
92524
Attachment File Name
Added On
Added By
Attachment Group
Notes
La Quinta-BCPR2023-0016-PCF-2022
09/21/2023 22:05
Ortega, AJ
Internal Only
1ST REVIEW INTERWEST CORRECTION LIST
Code Update.docx
LaQuinta - LAQ23-0119 -
09/21/2023 22:05
Ortega, AJ
Internal Only
1ST REVIEW INTERWEST FEE SHEET
BCPR2023-0016 - Invoice 90359
$250.00.pdf
BCPR2023-0016 Tract 30097
09/29/2023 14:08
Cox, Chris
Available Online
1ST FIRE REVIEW
corrections 9.29.23.pdf
BCPR2023-0016 - 1 ST REVIEW 10/02/2023 11:43 Clayton, Duane
COMPLETE CORRECTION LIST.pdf
BCPR2023-0016 - 1 ST REVIEW 10/02/2023 11:51 Clayton, Duane Available Online
INTERWEST APPROVAL
TRANSMITTAL.pdf
BCPR2023-0016 - 1ST REVIEW 10/02/2023 11:51 Clayton, Duane
INTERWEST INVOICE.pdf
BCPR2023-0016 Tract 30097 Fire
01/30/2024 11:10
Cox, Chris
Available Online
Conditions of Approval.pdf
BCPR2023-0016 - PLAN 1 - TAKE OFF
02/27/2024 8:31
Clayton, Duane
Internal Only
SHEET.pdf
BCPR2023-0016 - PLAN 2 - TAKE OFF
02/27/2024 8:31
Clayton, Duane
Internal Only
SHEET.pdf
BCPR2023-0016 - PLAN 3 - TAKE OFF
02/27/2024 8:39
Clayton, Duane
Internal Only
1ST REVIEW CORRECTION LIST
u.rraz�r���r���:z•�•c��rz�i.�yi!Ir�r�r
1ST REVIEW INTERWEST INVOICE
PLAN 1 TAKE OFFS
PLAN 2 TAKE OFFS
PLAN 2 TAKE OFFS
June 18, 2025 78-495 Calle Tampico Page 1 of 4
SHEET (2022 CODE UPDATE).pdf
PLAN SET (APPROVED).pdf
02/27/2024
8:47
Mendez, Deisy
TRUSS CALCULATIONS
02/27/2024
8:47
Mendez, Deisy
(APPROVED).pdf
REVISION 1 - PLAN SHEETS
08/20/2024
9:05
Fuson, Jake
(APPROVED).pdf
ARCHITECTUAL LETTER REV1 PC1
08/20/2024
9:11
Villanueva, Celeste
(APPROVE D)_v1.pdf
CF1R REV1 PC1 (APPROVED)_v1.pdf
08/20/2024
9:11
Villanueva, Celeste
Available Online Construction Plan Set
Available Online Truss Calculations
Available Online
Available Online Responses
Available Online Energy Documents
Note Created By Date and Time Created
1. EMAIL SENT TO MR. LARRY LIEBEL (Larry.Liebel@mdch.com) Jack Lima 02/09/2024 8:26
ON 2/8/2024 INFORMING HIM OF THE PLANNING CORRECTIC
CONCERNING GARAGE SIZE.
Invoice No. Fee
INV-00004811 Hourly Charge - City Building Staff
Credit Card Convenience Fee
Hourly Charge - Interwest Plans Examiner
Hourly Charge - City Building Staff
INV-00008674 Hourly Charge - City Building Staff
Credit Card Convenience Fee
Fee Amount
Amount Paid
$175.00
$175.00
$27.31
$27.31
$250.00
$250.00
$350.00
$350.00
Total for Invoice INV-00004811 $802.31
$802.31
$218.75
$218.75
$5.47
$5.47
Total for Invoice INV-00008674 $224.22
$224.22
Grand Total for Plan $1,026.53 $1,026.53
Activity Type Activity Number Name Workflow Action Name User Created On
Email ACT-000018-2023 Duane Clayton 10/02/2023
Comments: NOTIFIED LARRY LIEBEL THAT 1ST REVIEW IS COMPLETE AND PLANS REQUIRE REVISIONS.
Submittal Name Status
Building Major Review v.1 Requires Re -submit
Received Date Due Date Complete Date Resubmit Completed
08/07/2023 08/28/2023 10/02/2023 Yes Yes
Item Review Name Department Assigned User Status Assigned Due Completed
Date Date Date
Building Building Clayton, Duane Approved 09/21/2023 08/28/2023 10/02/2023
Comments: 1 HR CODE UPDATE
Item Review Name Department Assigned User Status
Fire Department - Building Cases Office of the Fire Marshal Cox, Chris Revisions Required
Correction Type Category
Fire Review - Correction Fire Review - Correction
Comments Corrective Action
1) Energy Storage Systems
shall comply with CFC
1206.11.
a. Fire Detection - Areas
shall be protected by smoke
alarms. A listed heat detector
shall be installed in locations
within dwelling units and
attached garages where
smoke alarms cannot be
installed based on their listing.
b. Protection from Impact —
ESS installed in a location
subject to vehicle damage
shall be protected by
approved barriers.
C. Operating Temperatures
— ESS system manuals shall
Assigned
Due
Completed
Date
Date
Date
09/21/2023
08/21/2023
09/29/2023
Create
Resolved
Resolved
Date
Date
No
09/29/2023
June 18, 2025 78-495 Calle Tampico Page 2 of 4
be consulted. Compliance with
the maximum operating
ambient temperatures shall be
complied with. Provision of
HVAC climate control may be
necessary.
Assigned
Due
Completed
Item Review Name
Department Assigned User
Status
Date
Date
Date
Complete
Outside Agency Group, Interwest
Approved
09/21/2023
08/22/2023
10/02/2023
Comments: SEE ATTACHED
1ST REVIEW CORRECTION LIST
Assigned
Due
Completed
Item Review Name
Department Assigned User
Status
Date
Date
Date
Planning - Building Cases
Planning/Zoning Fernandez, Siji
Revisions Required
09/21/2023
08/21/2023
08/15/2023
Comments: THE MINIMUM INTERIOR DIMENSIONS OF THE GARAGE SHALL BE TWENTY BY TWENTY
CLEARED OF ANY
PERMANENT
OBSTRUCTIONS. THE PROPOSED WALL MOUNTED BATTERIES IS AN OBSTRUCTION.
Submittal Name
Status Received Date
Due Date
Complete Date
Resubmit
Completed
Building Major Review v.2
Requires Re -submit 01/22/2024 01/29/2024
01/30/2024
Yes
Yes
Assigned
Due
Completed
Item Review Name
Department Assigned User
Status
Date
Date
Date
Building
Building Clayton, Duane
Ready for Approval
01/22/2024
01/29/2024
01/29/2024
Comments: PC2
Assigned
Due
Completed
Item Review Name
Department Assigned User
Status
Date
Date
Date
Fire Department - Building Cases Office of the Fire Marshal Cox, Chris
Ready for Approval
01/22/2024
01/29/2024
01/30/2024
Create
Resolved
Correction Type
Category Comments
Corrective Action
Resolved
Date
Date
Fire Review - Correction
Fire Review - Correction 1) Energy Storage Systems
Yes
01/22/2024 01/30/2024
shall comply with CFC
1206.11.
a. Fire Detection - Areas
shall be protected by smoke
alarms. A listed heat detector
shall be installed in locations
within dwelling units and
attached garages where
smoke alarms cannot be
installed based on their listing.
b. Protection from Impact —
ESS installed in a location
subject to vehicle damage
shall be protected by
approved barriers.
C. Operating Temperatures
— ESS system manuals shall
be consulted. Compliance with
the maximum operating
ambient temperatures shall be
complied with. Provision of
HVAC climate control may be
necessary.
June 18, 2025 78-495 Calle Tampico Page 3 of 4
Item Review Name Department
Planning - Building Cases Planning/Zoning
Correction Type Category
Planning Review - Planning Review -
Correction Correction
Submittal Name
Building Major Review v.3
Item Review Name
Building
Item Review Name
Planning - Building Cases
Correction Type
Planning Review -
Correction
Status
Approved
Department
Building
Department
Planning/Zoning
Category
Planning Review -
Correction
Assigned User Status
Fernandez, Siji Revisions Required
Comments Corrective Action
THE MINIMUM INTERIOR
DIMENSIONS OF THE
GARAGE SHALL BE TWENTY
BY TWENTY CLEARED OF
ANY PERMANENT
OBSTRUCTIONS. THE
PROPOSED WALL MOUNTEE
BATTERIES IS AN
OBSTRUCTION.
Received Date
02/15/2024
Assigned
Due
Completed
Date
Date
Date
01/22/2024
01/29/2024
01/24/2024
Create
Resolved
Resolved
Date
Date
No
01/24/2024
Due Date Complete Date Resubmit Completed
02/23/2024 02/27/2024 No Yes
Assigned User Status Assigned Due Completed
Date Date Date
Clayton, Duane Approved 02/15/2024 02/23/2024 02/27/2024
Assigned User Status
Fernandez, Siji Ready for Approval
Comments Corrective Action
THE MINIMUM INTERIOR
DIMENSIONS OF THE
GARAGE SHALL BE TWENTY
BY TWENTY CLEARED OF
ANY PERMANENT
OBSTRUCTIONS. THE
PROPOSED WALL MOUNTEE
BATTERIES IS AN
OBSTRUCTION.
Assigned
Due
Completed
Date
Date
Date
02/15/2024
02/23/2024
02/21/2024
Create
Resolved
Resolved
Date
Date
Yes
02/15/2024 02/21/2024
Submittal Name
Status Received Date Due Date Complete Date
Resubmit
Completed
Building Revision Review v.1
Approved 07/24/2024 07/31/2024 08/20/2024
No
Yes
Item Review Name
Department Assigned User Status Assigned
Due
Completed
Date
Date
Date
Building (1WK)
Building Fuson, Jake Approved 07/24/2024
07/31/2024
08/20/2024
Comments: REVISION #1 - INTERIOR
DOOR CHANGES, UPDATED MECHANICAL PLANS + ENERGY DOCUMENTS TO CORRECT
INCONSISTENC
Workflow Step / Action Name
Plan Check v.1
Building Major Review v.1
Building Major Review v.2
Building Major Review v.3
Revisions v.1
Building Revision Review v.1
Linked Records v.1
Linked Permits v.1
Action Type
Start Date
End Date
02/27/2024 8:47
Receive Submittal
09/21/2023
0:00
10/02/2023 11:53
Receive Submittal
01/22/2024
0:00
01/30/2024 11:30
Receive Submittal
02/15/2024
0:00
02/27/2024 8:47
08/20/2024 9:11
Receive Submittal
07/24/2024
0:00
08/20/2024 9:11
Create Sub Permit
June 18, 2025 78-495 Calle Tampico Page 4 of 4
CAL FIRE — RIVERSIDE UNIT
RIVERSIDE COUNTY FIRE DEPARTMENT �Cci
BILL WEISER -- FIRE CHIEF
OFFICE OF THE FIRE MARSHAL — LA QUINTA-CALIFORNIA
-
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
September 29, 2023
Richmond American Homes
391 N. Main St., Suite 205
Corona, CA 92679
Re: Residential Fire Access & Water / ESS Plan Review —BELLA AT PIAZZA SERENA / SFDx3 /
2022 CBC CODE UPDATE BCPR2023-0016 / TRACT 30097
The plans you submitted for the above referenced project have been reviewed by Riverside County Fire
Department - Office of the Fire Marshal personnel and require the following corrections and additional
details.
1) Energy Storage Systems shall comply with CFC 1206.11.
a. Fire Detection - Areas shall be protected by smoke alarms. A listed heat detector shall be installed
in locations within dwelling units and attached garages where smoke alarms cannot be installed
based on their listing.
b. Protection from Impact — ESS installed in a location subject to vehicle damage shall be protected
by approved barriers.
c. Operating Temperatures — ESS system manuals shall be consulted. Compliance with the
maximum operating ambient temperatures shall be complied with. Provision of HVAC climate
control may be necessary.
All questions regarding the meaning of these requirements should be referred to the Office of the Fire
Marshal staff at (760)777-7078.
Chris Cox — Fire Safety Supervisor
CAL FIRE — RIVERSIDE UNIT
RIVERSIDE COUNTY FIRE DEPARTMENT �Cci
BILL WEISER -- FIRE CHIEF
OFFICE OF THE FIRE MARSHAL — LA QUINTA-CALIFORNIA
-
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
January 30, 2024
Richmond American Homes
391 N. Main St., Suite 205
Corona, CA 92679
Re: Residential Fire Access & Water / ESS Plan Review —BELLA AT PIAZZA SERENA / SFDx3 /
2022 CBC CODE UPDATE BCPR2023-0016 / TRACT 30097
The plans you submitted for the above referenced project have been reviewed by Riverside County Fire
Department - Office of the Fire Marshal personnel and are approved with the following conditions.
1) Property/Unit Addressing shall be provided. Minimum 4-inch tall numbers of contrasting color to
their background shall be displayed on the structure and viewable from the roadway or posted at the
driveway entrance and maintained visible.
2) A Residential Fire Sprinkler system shall be installed in compliance with CRC R313. CA Licensed
Contractor (C-16) shall submit plans and details for review and approval prior to system installation
and Rough Inspections.
3) Energy Storage Systems shall comply with CFC 1206.11.
a. Fire Detection - Areas shall be protected by smoke alarms. A listed heat detector shall be installed
in locations within dwelling units and attached garages where smoke alarms cannot be installed
based on their listing.
b. Protection from Impact — ESS installed in a location subject to vehicle damage shall be protected
by approved barriers.
c. Operating Temperatures — ESS system manuals shall be consulted. Compliance with the
maximum operating ambient temperatures shall be complied with. Provision of HVAC climate
control may be necessary.
All questions regarding the meaning of these requirements should be referred to the Office of the Fire
Marshal staff at (760)777-7078.
Chris Cox — Fire Safety Supervisor
ADDRESS
81880 AVENUE 58
APPLICATION
BCPR2023-0016
PROJECT DESCRIPTION
VALID UNITL DATE
8/6/2024
BELLA @ PIAZZA SERENA PLAN 1 - PENDELTON
Mechanical
Units
New Construction
FURNACE
2
HEATER
CONDITIONED/AC (SF)
2,446
APPLIANCE (ALT/ADD)
GARAGE/UNCOND (SF)
728
COMPRESSOR
2
PATIO/COVERED (SF)
432
AIR HANDLER
FIRE SPRINKLER (SF)
3174
EVAP COOLER
CASITA (SF)
VENT FAN
5
CODE EDITION
2022
EXHAUST HOOD
1
CONSTRUCTION TYPE
VB
MISC MECHANICAL
GOOD
NO
NUMBER OF FLOORS
1
Electrical
Units
NUMBER OF BEDROOMS
3
NUMBER OF UNITS
1
NEW ELECTRICAL (SF:
3606
OCCUPANT LOAD
and/or
OCCUPANCY
R3/U
RECEP/SWITCH/LIGHT
MSHCP (DU/ACRE)
2.62
plus
(DWELLING UNITS PER ACRE, EX:
43,560SF/7,000SF Lot = 6.22DU/ACRE)
APPLIANCE - RES
APPLIANCE - NONRES
Options
POWER APPARATUS
OPTIONN FIREPLACE
SIGNS
1 GAS OUTLET
SERVICE
1
TEMPORARY SERVICE
OPTION FLEX ROOM
MISC ELECTRICAL
ADD 207 SF
LIGHT POLES
MINUS 207SF
PV SYSTEM - ARRAY
GARAGE SF
PV SYSTEM - MISC EQ
Plumbing
Units
FIXTURE/TRAP
15
SEWER
1
SEPTIC
ROOF DRAIN
Grading
WATER HEATER
1
GREASE INTERCEPTOR
TRACT 1
WATER PIPING
1
CUSTOM HOME <=7KSF
BACKFLOW
REVISED:5/15/2019
CUSTOM HOME >7KSF
GAS OUTLETS
REVISED:5/15/2019
Unit Counts
TOILETS
BIDET/URINAL
SHOWERS
BATHTUBS
SINKS
BAR SINK
BBQ
OVEN
RANGE
COOKTOP
DRINKING FOUNTAIN
WASHER
DRYER
WATER HEATER
ROOF DRAINS
FLOOR DRAINS
KITCHEN SINK
VEGGIE SINK
LAUNDRY SINK
FIREPLACE
Qty
REVISED:5/15/2019
ADDRESS
81880 AVENUE 58
APPLICATION
BCPR2023-0016
PROJECT DESCRIPTION
VALID UNITL DATE
8/6/2024
BELLA @ PIAZZA SERENA PLAN 2 - PINECREST
Mechanical
Units
New Construction
FURNACE
2
HEATER
CONDITIONED/AC (SF)
2,702
APPLIANCE (ALT/ADD)
GARAGE/UNCOND (SF)
729
COMPRESSOR
2
PATIO/COVERED (SF)
424
AIR HANDLER
FIRE SPRINKLER (SF)
3431
EVAP COOLER
CASITA (SF)
VENT FAN
5
CODE EDITION
2022
EXHAUST HOOD
1
CONSTRUCTION TYPE
VB
MISC MECHANICAL
GOOD
NO
NUMBER OF FLOORS
1
Electrical
Units
NUMBER OF BEDROOMS
3
NUMBER OF UNITS
1
NEW ELECTRICAL (SF:
3855
OCCUPANT LOAD
1
and/or
OCCUPANCY
R3/U
RECEP/SWITCH/LIGHT
MSHCP (DU/ACRE)
2.62
plus
(DWELLING UNITS PER ACRE, EX:
43,560SF/7,000SF Lot = 6.22DU/ACRE)
APPLIANCE - RES
APPLIANCE - NONRES
Options
POWER APPARATUS
OPT FIREPLACE
SIGNS
1 GAS OUTLET
SERVICE
1
TEMPORARY SERVICE
OPT FLEX SPACE
MISC ELECTRICAL
ADD 217SF LIVING
LIGHT POLES
MINUS 217SF GARAGE
PV SYSTEM - ARRAY
PV SYSTEM - MISC EQ
OPT SUITE
ADD 1 SINK
Plumbing
Units
MINUS 1 BED
FIXTURE/TRAP
15
SEWER
1
SEPTIC
ROOF DRAIN
Grading
WATER HEATER
1
GREASE INTERCEPTOR
TRACT 1
WATER PIPING
1
CUSTOM HOME <=7KSF
BACKFLOW
REVISED:5/15/2019
CUSTOM HOME >7KSF
GAS OUTLETS
REVISED:5/15/2019
Unit Counts
TOILETS
BIDET/URINAL
SHOWERS
BATHTUBS
SINKS
BAR SINK
BBQ
OVEN
RANGE
COOKTOP
DRINKING FOUNTAIN
WASHER
DRYER
WATER HEATER
ROOF DRAINS
FLOOR DRAINS
KITCHEN SINK
VEGGIE SINK
LAUNDRY SINK
FIREPLACE
Qty
REVISED:5/15/2019
ADDRESS
81880 AVENUE 58
APPLICATION
BCPR2023-0016
PROJECT DESCRIPTION
VALID UNITL DATE
8/26/2024
BELLA @ PIAZZA SERENA PLAN 3 - POMONA
Mechanical
Units
New Construction
FURNACE
2
HEATER
CONDITIONED/AC (SF)
2,833
APPLIANCE (ALT/ADD)
GARAGE/UNCOND (SF)
680
COMPRESSOR
2
PATIO/COVERED (SF)
424
AIR HANDLER
FIRE SPRINKLER (SF)
3513
EVAP COOLER
CASITA (SF)
VENT FAN
5
CODE EDITION
2022
EXHAUST HOOD
1
CONSTRUCTION TYPE
MISC MECHANICAL
GOOD
NO
NUMBER OF FLOORS
1
Electrical
Units
NUMBER OF BEDROOMS
4
NUMBER OF UNITS
1
NEW ELECTRICAL (SF:
3937
OCCUPANT LOAD
and/or
OCCUPANCY
R3/U
RECEP/SWITCH/LIGHT
MSHCP (DU/ACRE)
2.62
plus
(DWELLING UNITS PER ACRE, EX:
43,560SF/7,000SF Lot = 6.22DU/ACRE)
APPLIANCE - RES
APPLIANCE - NONRES
Options
POWER APPARATUS
OPT FIREPLACE
SIGNS
1 GAS OUTLET
SERVICE
1
TEMPORARY SERVICE
OPT GUEST SUITE
MISC ELECTRICAL
ADD 2 PLB FIX.
LIGHT POLES
MINUS 1 BED
PV SYSTEM - ARRAY
PV SYSTEM - MISC EQ
OPT 2 BD GUEST
ADD 233SF LIVING
Plumbing
Units
MINUS 233SF GARAGE
ADD 2 PLB FIX
FIXTURE/TRAP
15
SEWER
1
SEPTIC
ROOF DRAIN
Grading
WATER HEATER
1
GREASE INTERCEPTOR
TRACT 1
WATER PIPING
1
CUSTOM HOME <=7KSF
BACKFLOW
REVISED:5/15/2019
CUSTOM HOME >7KSF
GAS OUTLETS
REVISED:5/15/2019
Unit Counts
TOILETS
BIDET/URINAL
SHOWERS
BATHTUBS
SINKS
BAR SINK
BBQ
OVEN
RANGE
COOKTOP
DRINKING FOUNTAIN
WASHER
DRYER
WATER HEATER
ROOF DRAINS
FLOOR DRAINS
KITCHEN SINK
VEGGIE SINK
LAUNDRY SINK
FIREPLACE
Qty
REVISED:5/15/2019
SDK
SITE:
Project: BELLA AT PIAZZA SERENA
Location: LA QUINTA, CA
ATELIER
CLIENT:
RICHMOND AMERICAN HOMES
Address 391 N. MAIN STREET, SUITE 205
CORONA, CALIFORNIA 92679
Code Update & Aging in Place Revision List (07.24.2023)
SHEET DESCRIPTION
N852 PENDLETON
ADDED (UPDATED CODE) DESIGNATED AREA FOR NEW WATER HEATER IN GARAGE.
ADDED (UPDATED CODE) E.S.S. ENERGY STORAGE SYSTEM BATTERY EQUIPTMENT AREA IN GARAGE.
UPDATED SQUARE FOOTAGE CALCS. TO REFLECT NEW ADDITION OF WATER HEATER LOCATION.
REVISED MASTER BEDROOM DOOR TO BE 2'-10" WIDE
A111.1 — A111.3 - REVISED MASTER BATHROOM ENTRY TO BE AN OPTIONAL 2'-10" WIDE DOOR.
REVISED WATER CLOSET DOOR TO SWING OUT & BE A 2'-10" WIDE DOOR.
- ADDED A MASTER WALK IN CLOSET DOOR TO BE AN OPTIONAL 2'-10" WIDE DOOR.
ADJUSTED OPTIONAL FLOOR PLANS WITH ADJACENT BATHROOMS WITH 2'-10" WIDE DOORS.
- ADDED BLOCKING BEHIND E.S.S. BATTERY READY WALL IN THE GARAGE
ADDED (UPDATED CODE) UTILITIES IN LAUNDRY RM. FOR WATER HEATER, READING: "240V READY"
- ADDED (UPDATED CODE) UTILITIES IN LAUNDRY RM. FOR DRYER MARKED: "FOR FUTURE 240V"
ADDED (UPDATED CODE) UTILITY KITCHEN SOCKET FOR STOVE MARKED: "FOR FUTURE 240V"
A155.1 — A155.3 ADJUSTED/SHIFTED ELEC. SWITHES TO ACCOMMODATE WIDER DOOR IN MASTER BATHROOM
ADDED SMOKE & HEATER DETECTOR NEAR E.S.S. BATTERY READY IN THE GARAGE
ADDED NOTE 25B IN THE UTILITY NOTES
- REVISED ELECTRICAL VEHICLE CHARGING SYSTEM (EVCS) #26 IN THE UTILITY NOTES
REVISED MANDATORY (ELECTRICAL READY REQUIREMENT) CODE MEASURES PER (CEC SEC.220)
REVISED FLOOR MATERIALS TO REFLECT NEW WATER HEATER LOCATION.
A158.1 — A158.3
ADJUSTED FLOOR PLANS TO REFLECT WIDER DOORS.
N853 PINECREST
- ADDED (UPDATED CODE) DESIGNATED AREA FOR NEW WATER HEATER IN GARAGE.
- ADDED (UPDATED CODE) E.S.S. ENERGY STORAGE SYSTEM BATTERY EQUIPTMENT AREA IN GARAGE.
- UPDATED SQUARE FOOTAGE CALCS. TO REFLECT NEW ADDITION OF WATER HEATER LOCATION.
- REVISED MASTER BEDROOM DOOR TO BE 2'-10" WIDE
A211.1—A211.3 - REVISED MASTER BATHROOM ENTRY TO BE AN OPTIONAL 2'-10" WIDE DOOR.
- REVISED WATER CLOSET DOOR TO SWING OUT & BE A 2'-10" WIDE DOOR.
- ADDED A MASTER WALK IN CLOSET DOOR TO BE AN OPTIONAL 2'-10" WIDE DOOR.
- ADJUSTED OPTIONAL FLOOR PLANS WITH ADJACENT BATHROOMS WITH 2'-10" WIDE DOORS.
- ADDED BLOCKING BEHIND E.S.S. BATTERY READY WALL IN THE GARAGE
9100 Irvine Center Drive I Irvine, CA 92618 1 tel: 949.585.9167 1 www.sdkatelier.com
S�\J ATELIER
ADDED (UPDATED CODE) UTILITIES IN LAUNDRY RM. FOR WATER HEATER, READING: "240V READY"
- ADDED (UPDATED CODE) UTILITIES IN LAUNDRY RM. FOR DRYER MARKED: "FOR FUTURE 240V"
ADDED (UPDATED CODE) UTILITY KITCHEN SOCKET FOR STOVE MARKED: "FOR FUTURE 240V"
A255.1- A255.3 - ADJUSTED/SHIFTED ELEC. SWITHES TO ACCOMMODATE WIDER DOOR IN MASTER BATHROOM
- ADDED SMOKE & HEATER DETECTOR NEAR E.S.S. BATTERY READY IN THE GARAGE
- ADDED NOTE 25B IN THE UTILITY NOTES
- REVISED ELECTRICAL VEHICLE CHARGING SYSTEM (EVCS) #26 IN THE UTILITY NOTES
- REVISED MANDATORY (ELECTRICAL READY REQUIREMENT) CODE MEASURES PER (CEC SEC.220)
- REVISED FLOOR MATERIALS TO REFLECT NEW WATER HEATER LOCATION.
A258.1- A258.3
- ADJUSTED FLOOR PLANS TO REFLECT WIDER DOORS.
N850 POMONA
ADDED (UPDATED CODE) DESIGNATED AREA FOR NEW WATER HEATER IN GARAGE.
ADDED (UPDATED CODE) E.S.S. ENERGY STORAGE SYSTEM BATTERY EQUIPTMENT AREA IN GARAGE.
UPDATED SQUARE FOOTAGE CALCS. TO REFLECT NEW ADDITION OF WATER HEATER LOCATION.
REVISED MASTER BEDROOM DOOR TO BE 2'-10" WIDE
A311.1 - A311. 4
REVISED MASTER BATHROOM ENTRY TO BE AN OPTIONAL 2'-10" WIDE DOOR.
REVISED WATER CLOSET DOOR TO SWING OUT & BE A 2'-10" WIDE DOOR.
- ADDED A MASTER WALK IN CLOSET DOOR TO BE AN OPTIONAL 2'-10" WIDE DOOR.
ADDED BLOCKING BEHIND E.S.S. BATTERY READY WALL IN THE GARAGE
- ADDED (UPDATED CODE) UTILITIES IN LAUNDRY RM. FOR WATER HEATER, READING: "240V READY"
ADDED (UPDATED CODE) UTILITIES IN LAUNDRY RM. FOR DRYER MARKED: "FOR FUTURE 240V"
ADDED (UPDATED CODE) UTILITY KITCHEN SOCKET FOR STOVE MARKED: "FOR FUTURE 240V"
A355.1 - A355.4 ADJUSTED/SHIFTED ELEC. SWITHES TO ACCOMMODATE WIDER DOOR IN MASTER BATHROOM
ADDED SMOKE & HEATER DETECTOR NEAR E.S.S. BATTERY READY IN THE GARAGE
- ADDED NOTE 25B IN THE UTILITY NOTES
REVISED ELECTRICAL VEHICLE CHARGING SYSTEM (EVCS) #26 IN THE UTILITY NOTES
- REVISED MANDATORY (ELECTRICAL READY REQUIREMENT) CODE MEASURES PER (CEC SEC.220)
REVISED FLOOR MATERIALS TO REFLECT NEW WATER HEATER LOCATION.
A358.1- A358.3
ADJUSTED FLOOR PLANS TO REFLECT WIDER DOORS.
9100 Irvine Center Drive I Irvine, CA 92618 1 tel: 949.585.9167 1 www.sdkatelier.com
August 19, 2023
CITY OF LA QUINTA - FINAL REVIEW
Permit No: BCPR2O23-0016
Interwest No.: LAQ23-0119
Non -Structural: 2-hours
Structural:.50-hours
City of La Quinta
Building Department
78-495 Calle Tampico
La Quinta, CA 92253
Plan Review: Stock Plan 2022 Code Update
Address: 81880 Avenue 58
0
r"T
INTERWEST
A SAFEbuilt COMPANY
Interwest Consulting Group has completed a FINAL code compliance review of the following documents on behalf of
the City of La Quinta:
1. Drawings: PDF copy of following:
a. Cover through D1O9 dated 7/24/2023 by SDK Atelier.
b. SCS through SD3 dated 7/11/2023 by Performance Plus Engineering.
C. M0.O through MD1.2 dated 7/28/2023 by Ei Engineering.
d. P0.O through PD1.O dated 7/28/2023 by Ei Engineering.
e. E0.O through E1.O dated 7/25/2023 by Ei Engineering.
f. T24-1.0.0 through T24-3.1.1 dated 7/25/2023 by Ei Engineering.
g. PTD through PT-3B dated 7/11/2022 by Specialty Steele.
2. Truss Calculations: PDF copy dated 8/2/2023 by Builders First Source.
Enclosed, please find the above noted documents bearing Interwest Consulting Group's plan review stamps indicating
the documents have been reviewed for code compliance. Please do not hesitate to contact us directly with any
questions.
Sincerely,
INTERWEST CONSULTING GROUP
Eric Corral
Plans Examiner
1500 S. Haven Ave I Suite 220
Ontario, CA 91761
909.295-3142 INTERWESTGRP.COM
8/21/23. 2:43 PM Invoice
1w
INTERWEST
A SAFEbwtt COMPANY
INVOICE #90359
August 21, 2023
Jurisdiction No. BCPR2023-0016
Interwest Job No. LAQ23-0119
Bill to: City of La Quinta Remit to: Interwest Consulting Group Direct questions to:
Attention Danny Castro P.O. Box 301069 € Erica Cuevas
Design & Development Director Los Angeles, CA 90030-1069 (970) 568-5034
78495 Calle Tampico € ecuevas@interwestgrp.com
La Quinta, CA 92253
Professional services for the period August 1 through August 21, 2023
RESIDENTIAL - CODE UPDATE- BCPR2023-0016 - 81880 AVENUE 58 -
LAQ23-0119
81880 Avenue 58
Invoice Total $250.00
Employee Title Day Hours Rate Total
Eric Corral ICC Certified Plans Examiner 1 8/181 2.5 $100.001 $250.00
https://interwest.lucidbilling.com/invoices/print 1/1