102761 - BARRETT PSU - SILVER ROCK PARK - LA QUINTABARRETT Engineered Pumps SPECIALISTS IN PUMPS AND PUMPING SYSTEMS P.O. Box 13130 San Diego CA 92170 -3130 • 1695 National Ave. San Diego CA 92113 Phone (619) 232-7867 • FAX (619) 232-3029 IRRIBOOST PUMP STARTUP / CERTIFICATION Project Name: SILVER ROCK PARK POND LA QUINTA Contractor Name: URBAN HABITAT Contact: JESSIE Phone #: 860-498-4758 Fax #: Mobile #: Owner Name: Contact: Phone #: Fax #: Mobil #: SYSTEM (rated) MODEL IBPCO-25-2-4 S/N 102761 GPM 220 HP 25 VOLT 208/203/460 VAC PHASE 3 PSI 185 FLOW SWITCH OK 24 VAC 2ND PUMP PUMP (rated) BRAND BALDOR MOTOR MODEL EJMM4107T GPM 220 HP 25 VOLT 460 PHASE 3 FEET HEAD 127 PRESSURE TANK – 200 PSI CONTROL MODEL PHASE/VOLTAGE 3/460 HP 25 DRAWING TIME DELAY FLOW OK 24VAC 2ND PUMP ENCLOSURE CONCRETE GOOD NO RUST NO BAFFLES 2 PLUMBING SIZE 4” LEAKS NONE INCOMING ELECTRICAL CONDUIT INSTALLED YES WIRE AWG Breaker AMP Rating 24 V START SYSTEM (actual/spec) STATIC SUCTION PSI 0 DYNAMIC AMPS A B C DYNAMIC DISCHARGE PSI 90 STATIC VOLTS AB – 460 AG – 275 BG – 460 BG – 276 BC – 460 CG - 276 DYNAMIC VOLTS AB – 460 AG – 275 BG – 460 BG – 276 BC – 460 CG – 276 DYNAMIC SUCTION PSI 0 The Pump Assembly Shown Above: PASS Certification. Notes: Certification Inspection by: RICKY D. Date: 04/28/2021 Completed by: ALEJANDRO R. ✓ 8