Piazza Serena TR 30092 BCPR2021-0027 - Title 24CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 1 - Pendleton S852 Calculation Date/Time:2022-02-04T15:46:38-08:00 (Page 1 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 1 - Pendleton S852.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 15:50:37
GENERAL INFORMATION
01 Project Name Plan 1 - Pendleton S852
02 Run Title Title 24 Analysis
03 Project Location Bella at Piazza Serena
04 City La Quinta 05 Standards Version 2019
06 Zip code 07 Software Version EnergyPro 8.1
08 Climate Zone 15 09 Front Orientation (deg/ Cardinal)AllOrientations
10 Building Type Single family 11 Number of Dwelling Units 1
12 Project Scope NewConstruction 13 Number of Bedrooms 3
14 Addition Cond. Floor Area (ft
2)0 15 Number of Stories 1
16 Existing Cond. Floor Area (ft
2)n/a 17 Fenestration Average U-factor 0.33
18 Total Cond. Floor Area (ft
2)2328 19 Glazing Percentage (%)14.19%
20 ADU Bedroom Count 0 21 ADU Conditioned Floor Area 0
22 Is Natural Gas Available?Yes
COMPLIANCE RESULTS
01 Building Complies with Computer Performance
02 This building incorporates features that require field testing and/or verification by a certified HERS rater under the supervision of a CEC-approved HERS provider.
03 This building incorporates one or more Special Features shown below
221-P010157782C-000-000-0000000-0000 2022-02-04 16:48:07 CalCERTS inc.
BCPR2021-0027
BELLA AT PIAZZA SERENA / TRACT 30092
CONSTRUCTION MASTER PLANS FOR DWELLINGS
(SFD x 3) - PLANS 1, 2, AND 3. 2019 CALIFORNIA
BUILDING CODES.
PLAN 1: 2,328SF
PLAN 2: 2,392SF
PLAN 3: 2,630SF
04/26/2022
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 1 - Pendleton S852 Calculation Date/Time:2022-02-04T15:46:38-08:00 (Page 2 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 1 - Pendleton S852.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 15:50:37
ENERGY DESIGN RATING
Energy Design Ratings
Efficiency¹ (EDR)Total² (EDR)Efficiency¹ (EDR)Total² (EDR)
Standard Design 50.4 23.1
Proposed Designs
North Facing 45.8 21 4.6 2.1
East Facing 46.9 22.1 3.5 1
South Facing 47.9 23.1 2.5 0
West Facing 47.8 23 2.6 0.1
RESULT:3:COMPLIES
¹ Efficiency EDR includes improvements to the building envelope and more efficient equipment
² Total EDR includes efficiency and demand response measures such as photovoltaic (PV) systems and batteries
³ Building complies when efficiency and total compliance margins are greater than or equal to zero
•Standard Design PV Capacity: 5.21 kWdc
•Proposed PV Capacity Scaling: North (5.22 kWdc) East (5.22 kWdc) South (5.22 kWdc) West (5.22 kWdc)
221-P010157782C-000-000-0000000-0000 2022-02-04 16:48:07 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 1 - Pendleton S852 Calculation Date/Time:2022-02-04T15:46:38-08:00 (Page 3 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 1 - Pendleton S852.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 15:50:37
ENERGY USE SUMMARY
Energy Use (kTDV/ft
2-yr)Standard Design Proposed Design Compliance Margin Percent Improvement
Space Heating 1.66 1.27 0.39 23.5
Space Cooling 86.2 73.69 12.51 14.5
IAQ Ventilation 4.45 4.45 0 0
Water Heating 8.54 7.76 0.78 9.1
Self Utilization Credit n/a 0 0 n/a
North Facing Compliance Total 100.85 87.17 13.68 13.6
Space Heating 1.66 0.91 0.75 45.2
Space Cooling 86.2 77.45 8.75 10.2
IAQ Ventilation 4.45 4.45 0 0
Water Heating 8.54 7.76 0.78 9.1
Self Utilization Credit n/a 0 0 n/a
East Facing Compliance Total 100.85 90.57 10.28 10.2
Space Heating 1.66 1.01 0.65 39.2
Space Cooling 86.2 80.25 5.95 6.9
IAQ Ventilation 4.45 4.45 0 0
Water Heating 8.54 7.76 0.78 9.1
Self Utilization Credit n/a 0 0 n/a
South Facing Compliance Total 100.85 93.47 7.38 7.3
Space Heating 1.66 1.7 -0.04 -2.4
Space Cooling 86.2 79.13 7.07 8.2
IAQ Ventilation 4.45 4.45 0 0
Water Heating 8.54 7.76 0.78 9.1
Self Utilization Credit n/a 0 0 n/a
West Facing Compliance Total 100.85 93.04 7.81 7.7
221-P010157782C-000-000-0000000-0000 2022-02-04 16:48:07 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 1 - Pendleton S852 Calculation Date/Time:2022-02-04T15:46:38-08:00 (Page 4 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 1 - Pendleton S852.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 15:50:37
REQUIRED PV SYSTEMS - SIMPLIFIED
01 02 03 04 05 06 07 08 09 10 11 12
DC System Size
(kWdc)Exception Module Type Array Type Power Electronics CFI Azimuth
(deg)
Tilt
Input
Array Angle
(deg)Tilt: (x in 12)
Inverter Eff.
(%)
Annual
Solar Access
(%)
5.22 NA Premium Fixed (roof
mount)Microinverters true 105-300 n/a n/a <=7:12 96 97
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
•Indoor air quality, balanced fan
•Non-standard roof reflectance
•Insulation below roof deck
•Window overhangs and/or fins
HERS FEATURE SUMMARY
The following is a summary of the features that must be field-verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional
detail is provided in the buildng tables below. Registered CF2Rs and CF3Rs are required to be completed in the HERS Registry
Building-level Verifications:
•Quality insulation installation (QII)
•Building air leakage/reduced infiltration
•Indoor air quality ventilation
•Kitchen range hood
Cooling System Verifications:
•Minimum Airflow
•Verified EER
•Verified SEER
•Verified Refrigerant Charge
•Fan Efficacy Watts/CFM
Heating System Verifications:
•-- None --
HVAC Distribution System Verifications:
•Duct leakage testing
•Low-leakage Air Handling Unit
Domestic Hot Water System Verifications:
•-- None --
221-P010157782C-000-000-0000000-0000 2022-02-04 16:48:07 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 1 - Pendleton S852 Calculation Date/Time:2022-02-04T15:46:38-08:00 (Page 5 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 1 - Pendleton S852.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 15:50:37
BUILDING - FEATURES INFORMATION
01 02 03 04 05 06 07
Project Name Conditioned Floor Area (ft
2)Number of Dwelling
Units Number of Bedrooms Number of Zones
Number of Ventilation
Cooling Systems
Number of Water
Heating Systems
Plan 1 - Pendleton S852 2328 1 3 1 0 1
ZONE INFORMATION
01 02 03 04 05 06 07
Zone Name Zone Type HVAC System Name Zone Floor Area (ft
2)Avg. Ceiling Height Water Heating System 1 Water Heating System 2
Zone 1 Conditioned HVAC1 2328 9.1 DHW Sys 1 N/A
OPAQUE SURFACES
01 02 03 04 05 06 07 08
Name Zone Construction Azimuth Orientation Gross Area (ft
2)Window and Door
Area (ft2)
Tilt (deg)
Front 2X6 Zone 1 Ext. R-19 Wall + R-4.2 0 Front 378.4 26.8 90
Front 2X4 Zone 1 Ext. R-13 Wall + R-4.2 0 Front 337.4 67 90
Left 2X4 Zone 1 Ext. R-13 Wall + R-4.2 90 Left 455 181 90
Rear 2X4 Zone 1 Ext. R-13 Wall + R-4.2 180 Back 571 43 90
Right 2X4 Siding Zone 1 Ext. R-13 Wall 270 Right 81.9 36.5 90
Garage 2X4 Zone 1>>__Garage__Garage R-13 Wall n/a n/a 518 17.8 n/a
Roof Zone 1 R-30 Roof Attic + R-13 BD n/a n/a 2298 n/a n/a
Furnace Zone 1 R-30 Roof Attic n/a n/a 30 n/a n/a
Roof 2 __Garage__R-0 Roof Attic n/a n/a 704 n/a n/a
Front 2X4 2 __Garage__Ext R-0 Wall 0 Front 154 0 90
Rear 2X4 2 __Garage__Ext R-0 Wall 180 Back 298.8 56 90
Right 2X4 __Garage__Ext R-0 Wall 270 Right 373.1 112 90
221-P010157782C-000-000-0000000-0000 2022-02-04 16:48:07 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 1 - Pendleton S852 Calculation Date/Time:2022-02-04T15:46:38-08:00 (Page 6 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 1 - Pendleton S852.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 15:50:37
ATTIC
01 02 03 04 05 06 07 08
Name Construction Type Roof Rise (x in 12)Roof Reflectance Roof Emittance Radiant Barrier Cool Roof
Attic __Garage__Attic Garage Roof Cons Ventilated 4 0.12 0.92 No No
Attic Zone 1 Attic RoofZone 1 Ventilated 4 0.12 0.92 No No
FENESTRATION / GLAZING
01 02 03 04 05 06 07 08 09 10 11 12 13 14
Name Type Surface Orientation Azimuth Width
(ft)
Height
(ft)Mult.Area
(ft2)U-factor U-factor
Source SHGC
SHGC
Sourc
e
Exterior
Shading
Window Window Front 2X6 Front 0 1 26.8 0.33 NFRC 0.23 NFRC Bug Screen
Window 2 Window Front 2X4 Front 0 1 67 0.33 NFRC 0.23 NFRC Bug Screen
Window 3 Window Left 2X4 Left 90 1 85 0.33 NFRC 0.23 NFRC Bug Screen
SGD - OH Window Left 2X4 Left 90 12 8 1 96 0.33 NFRC 0.23 NFRC Bug Screen
Window 4 Window Rear 2X4 Back 180 1 43 0.33 NFRC 0.23 NFRC Bug Screen
Window 5 Window Right 2X4 Siding Right 270 1 12.5 0.33 NFRC 0.23 NFRC Bug Screen
OPAQUE DOORS
01 02 03 04
Name Side of Building Area (ft
2)U-factor
Main Door Right 2X4 Siding 24 0.142857
Int Garage Door Garage 2X4 17.8 0.5
Overhead Garage Door Rear 2X4 2 56 0.7
Overhead Garage Door 2 Right 2X4 112 0.7
221-P010157782C-000-000-0000000-0000 2022-02-04 16:48:07 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 1 - Pendleton S852 Calculation Date/Time:2022-02-04T15:46:38-08:00 (Page 7 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 1 - Pendleton S852.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 15:50:37
OVERHANGS AND FINS
01 02 03 04 05 06 07 08 09 10 11 12 13 14
Window
Overhang Left Fin Right Fin
Depth Dist Up Left Extent
Right
Extent Flap Ht.Depth Top Up Dist L Bot Up Depth Top Up Dist R Bot Up
SGD - OH 12 1 10 10 0 0 0 0 0 0 0 0 0
SLAB FLOORS
01 02 03 04 05 06 07
Name Zone Area (ft2)Perimeter (ft)Edge Insul. R-value and Depth Carpeted Fraction Heated
Slab-on-Grade Zone 1 2238 200 None 80%No
Slab-on-Grade 2 __Garage__704 91 None 0%No
OPAQUE SURFACE CONSTRUCTIONS
01 02 03 04 05 06 07 08
Construction Name Surface Type Construction Type Framing Total Cavity
R-value
Interior / Exterior
Continuous
R-value
U-factor Assembly Layers
Ext R-0 Wall Exterior Walls Wood Framed Wall 2x4 @ 16 in. O. C.R-0 None / None 0.361
Inside Finish: Gypsum Board
Cavity / Frame: no insul. / 2x4
Exterior Finish: 3 Coat Stucco
Ext. R-19 Wall + R-4.2 Exterior Walls Wood Framed Wall 2x6 @ 16 in. O. C.R-19 None / R-4.2 0.054
Inside Finish: Gypsum Board
Cavity / Frame: R-19 in 5-1/2 in. (R-18) /
2x6
Sheathing / Insulation: R-4.2 Sheathing
Exterior Finish: Synthetic Stucco
Ext. R-13 Wall + R-4.2 Exterior Walls Wood Framed Wall 2x4 @ 16 in. O. C.R-13 None / R-4.2 0.067
Inside Finish: Gypsum Board
Cavity / Frame: R-13 / 2x4
Sheathing / Insulation: R-4.2 Sheathing
Exterior Finish: Synthetic Stucco
221-P010157782C-000-000-0000000-0000 2022-02-04 16:48:07 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 1 - Pendleton S852 Calculation Date/Time:2022-02-04T15:46:38-08:00 (Page 8 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 1 - Pendleton S852.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 15:50:37
OPAQUE SURFACE CONSTRUCTIONS
01 02 03 04 05 06 07 08
Construction Name Surface Type Construction Type Framing Total Cavity
R-value
Interior / Exterior
Continuous
R-value
U-factor Assembly Layers
Ext. R-13 Wall Exterior Walls Wood Framed Wall 2x4 @ 16 in. O. C.R-13 None / None 0.101
Inside Finish: Gypsum Board
Cavity / Frame: R-13 / 2x4
Exterior Finish: 3 Coat Stucco
Garage R-13 Wall Interior Walls Wood Framed Wall 2x4 @ 16 in. O. C.R-13 None / None 0.092
Inside Finish: Gypsum Board
Cavity / Frame: R-13 / 2x4
Other Side Finish: Gypsum Board
Attic Garage Roof Cons Attic Roofs
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-0 None / None 0.4
Roofing: 10 PSF (RoofTile)
Tile Gap: present
Roof Deck: Wood
Siding/sheathing/decking
Cavity / Frame: no insul. / 2x4
Attic RoofZone 1 Attic Roofs
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-13 None / None 0.072
Roofing: 10 PSF (RoofTile)
Tile Gap: present
Roof Deck: Wood
Siding/sheathing/decking
Cavity / Frame: R-13.0 / 2x4
Around Roof Joists: R-0.0 insul.
R-0 Roof Attic
Ceilings (below
attic)
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-0 None / None 0.481 Cavity / Frame: no insul. / 2x4
Inside Finish: Gypsum Board
R-30 Roof Attic + R-13
BD
Ceilings (below
attic)
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-30 None / None 0.032
Over Ceiling Joists: R-20.9 insul.
Cavity / Frame: R-9.1 / 2x4
Inside Finish: Gypsum Board
R-30 Roof Attic
Ceilings (below
attic)
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-30 None / None 0.032
Over Ceiling Joists: R-20.9 insul.
Cavity / Frame: R-9.1 / 2x4
Inside Finish: Gypsum Board
221-P010157782C-000-000-0000000-0000 2022-02-04 16:48:07 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 1 - Pendleton S852 Calculation Date/Time:2022-02-04T15:46:38-08:00 (Page 9 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 1 - Pendleton S852.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 15:50:37
BUILDING ENVELOPE - HERS VERIFICATION
01 02 03 04
Quality Insulation Installation (QII)Quality Installation of Spray Foam Insulation Building Envelope Air Leakage CFM50
Required Not Required Required 1412.3
WATER HEATING SYSTEMS
01 02 03 04 05 06 07
Name System Type Distribution Type Water Heater Name (#)Solar Heating System Compact Distribution HERS Verification
DHW Sys 1
Domestic Hot Water
(DHW)
Standard Distribution
System DHW Heater 1 (1)n/a None n/a
WATER HEATERS
01 02 03 04 05 06 07 08 09 10 11 12
Name
Heating
Element
Type
Tank Type
#
Units
Tank
Vol.
(gal)
Energy
Factor or
Efficiency
Input Rating
or Pilot
Tank
Insulation
R-value
(Int/Ext)
Standby Loss
or Recovery
Eff.
1st Hr. Rating
or Flow Rate
NEEA Heat Pump
Brand or Model
Tank Location or
Ambient Condition
DHW Heater 1 Gas Consumer
Instantaneous 1 0 0.93-UEF <= 200
kBtu/hr 0 n/a n/a n/a n/a
WATER HEATING - HERS VERIFICATION
01 02 03 04 05 06 07 08
Name Pipe Insulation Parallel Piping Compact Distribution
Compact Distribution
Type Recirculation Control
Central DHW
Distribution
Shower Drain Water
Heat Recovery
DHW Sys 1 - 1/1 Not Required Not Required Not Required None Not Required Not Required Not Required
221-P010157782C-000-000-0000000-0000 2022-02-04 16:48:07 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 1 - Pendleton S852 Calculation Date/Time:2022-02-04T15:46:38-08:00 (Page 10 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 1 - Pendleton S852.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 15:50:37
SPACE CONDITIONING SYSTEMS
01 02 03 04 05 06 07 08 09 10 11
Name System Type
Heating Unit
Name
Cooling Unit
Name Fan Name
Distribution
Name
Required
Thermostat
Type
Status
Verified
Existing
Condition
Heating
Equipment
Count
Cooling
Equipment
Count
HVAC1 Heating and cooling system
other
Heating
Component
1
Cooling
Component
1
HVAC Fan 1
Air
Distribution
System 1
Setback New NA 2 2
HVAC - HEATING UNIT TYPES
01 02 03 04
Name System Type Number of Units Heating Efficiency
Heating Component 1 Central gas furnace 2 AFUE-96
HVAC - COOLING UNIT TYPES
01 02 03 04 05 06 07 08
Name System Type Number of Units Efficiency EER Efficiency SEER Zonally Controlled
Mulit-speed
Compressor HERS Verification
Cooling Component 1 Central split AC 2 13 16.5 Not Zonal Single Speed
Cooling Component
1-hers-cool
HVAC COOLING - HERS VERIFICATION
01 02 03 04 05 06
Name Verified Airflow Airflow Target Verified EER Verified SEER Verified Refrigerant Charge
Cooling Component
1-hers-cool Required 350 Required Required Required
221-P010157782C-000-000-0000000-0000 2022-02-04 16:48:07 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 1 - Pendleton S852 Calculation Date/Time:2022-02-04T15:46:38-08:00 (Page 11 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 1 - Pendleton S852.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 15:50:37
HVAC - DISTRIBUTION SYSTEMS
01 02 03 04 05 06 07 08 09 10 11 12
Duct Ins. R-value Duct Location Surface Area
Name Type Design Type Supply Return Supply Return Supply Return Bypass
Duct Duct Leakage
HERS
Verification
Air Distribution
System 1
Unconditioned attic Non-Verified R-6 R-6 Attic Attic n/a n/a
No
Bypass
Duct
Air
Distribution
System
1-hers-dist
HVAC DISTRIBUTION - HERS VERIFICATION
01 02 03 04 05 06 07 08 09
Name Duct Leakage
Verification
Duct Leakage
Target (%)
Verified Duct
Location
Verified Duct
Design Buried Ducts
Deeply Buried
Ducts
Low-leakage Air
Handler
Low Leakage
Ducts Entirely in
Conditioned
Space
Air Distribution
System 1-hers-dist
Yes 5.0 Not Required Not Required Not Required Credit not taken Required No
HVAC - FAN SYSTEMS
01 02 03 04
Name Type Fan Power (Watts/CFM)Name
HVAC Fan 1 HVAC Fan 0.45 HVAC Fan 1-hers-fan
HVAC FAN SYSTEMS - HERS VERIFICATION
01 02 03
Name Verified Fan Watt Draw Required Fan Efficacy (Watts/CFM)
HVAC Fan 1-hers-fan Required 0.45
221-P010157782C-000-000-0000000-0000 2022-02-04 16:48:07 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 1 - Pendleton S852 Calculation Date/Time:2022-02-04T15:46:38-08:00 (Page 12 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 1 - Pendleton S852.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 15:50:37
IAQ (INDOOR AIR QUALITY) FANS
01 02 03 04 05 06
Dwelling Unit IAQ CFM IAQ Watts/CFM IAQ Fan Type IAQ Recovery Effectiveness (%)
IAQ Recovery Effectiveness -
SREIAQ Recovery Effectiveness
- SRE
SFam IAQVentRpt 1-1 85 0.517647 Balanced HRV 75 n/a
221-P010157782C-000-000-0000000-0000 2022-02-04 16:48:07 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 1 - Pendleton S852 Calculation Date/Time:2022-02-04T15:46:38-08:00 (Page 13 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 1 - Pendleton S852.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 15:50:37
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:Documentation Author Signature:
Company:Signature Date:
Address:CEA/ HERS Certification Identification (If applicable):
City/State/Zip:Phone:
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1.I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance.
2.I certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations.
3.The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets,
calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
Responsible Designer Name:Responsible Designer Signature:
Company:Date Signed:
Address:License:
City/State/Zip:Phone:
Easy to Verify
at CalCERTS.com
Cristela Lujan
Energy Inspectors
2570 South Miller Lane
Las Vegas, NV 89117
2022-02-04 16:44:05
R19-18-30081
702-365-8080
John Heimann
Richmond American Homes
5171 California Ave. Suite #120
Irvine, CA 92617
2022-02-04 16:48:07
N/A
949-467-2661
Digitally signed by CalCERTS. This digital signature is provided in order to secure the content of this registered document, and in no way implies
Registration Provider responsibility for the accuracy of the information.
221-P010157782C-000-000-0000000-0000 2022-02-04 16:48:07 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 2 - Pinecrest S853 Calculation Date/Time:2022-02-04T16:18:07-08:00 (Page 1 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 2 - Pinecrest S853.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:22:27
GENERAL INFORMATION
01 Project Name Plan 2 - Pinecrest S853
02 Run Title Title 24 Analysis
03 Project Location Bella at Piazza Serena
04 City La Quinta 05 Standards Version 2019
06 Zip code 07 Software Version EnergyPro 8.1
08 Climate Zone 15 09 Front Orientation (deg/ Cardinal)AllOrientations
10 Building Type Single family 11 Number of Dwelling Units 1
12 Project Scope NewConstruction 13 Number of Bedrooms 3
14 Addition Cond. Floor Area (ft
2)0 15 Number of Stories 1
16 Existing Cond. Floor Area (ft
2)n/a 17 Fenestration Average U-factor 0.33
18 Total Cond. Floor Area (ft
2)2392 19 Glazing Percentage (%)13.29%
20 ADU Bedroom Count 0 21 ADU Conditioned Floor Area 0
22 Is Natural Gas Available?Yes
COMPLIANCE RESULTS
01 Building Complies with Computer Performance
02 This building incorporates features that require field testing and/or verification by a certified HERS rater under the supervision of a CEC-approved HERS provider.
03 This building incorporates one or more Special Features shown below
221-P010157785C-000-000-0000000-0000 2022-02-04 16:48:53 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 2 - Pinecrest S853 Calculation Date/Time:2022-02-04T16:18:07-08:00 (Page 2 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 2 - Pinecrest S853.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:22:27
ENERGY DESIGN RATING
Energy Design Ratings
Efficiency¹ (EDR)Total² (EDR)Efficiency¹ (EDR)Total² (EDR)
Standard Design 50.4 23.1
Proposed Designs
North Facing 45.5 21.1 4.9 2
East Facing 47.1 22.6 3.3 0.5
South Facing 47.2 22.8 3.2 0.3
West Facing 47.4 23 3 0.1
RESULT:3:COMPLIES
¹ Efficiency EDR includes improvements to the building envelope and more efficient equipment
² Total EDR includes efficiency and demand response measures such as photovoltaic (PV) systems and batteries
³ Building complies when efficiency and total compliance margins are greater than or equal to zero
•Standard Design PV Capacity: 5.19 kWdc
•Proposed PV Capacity Scaling: North (5.12 kWdc) East (5.12 kWdc) South (5.12 kWdc) West (5.12 kWdc)
221-P010157785C-000-000-0000000-0000 2022-02-04 16:48:53 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 2 - Pinecrest S853 Calculation Date/Time:2022-02-04T16:18:07-08:00 (Page 3 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 2 - Pinecrest S853.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:22:27
ENERGY USE SUMMARY
Energy Use (kTDV/ft
2-yr)Standard Design Proposed Design Compliance Margin Percent Improvement
Space Heating 1.46 1.13 0.33 22.6
Space Cooling 83.21 70.27 12.94 15.6
IAQ Ventilation 4.33 4.33 0 0
Water Heating 8.33 7.57 0.76 9.1
Self Utilization Credit n/a 0 0 n/a
North Facing Compliance Total 97.33 83.3 14.03 14.4
Space Heating 1.46 0.95 0.51 34.9
Space Cooling 83.21 74.89 8.32 10
IAQ Ventilation 4.33 4.33 0 0
Water Heating 8.33 7.57 0.76 9.1
Self Utilization Credit n/a 0 0 n/a
East Facing Compliance Total 97.33 87.74 9.59 9.9
Space Heating 1.46 1.04 0.42 28.8
Space Cooling 83.21 75.25 7.96 9.6
IAQ Ventilation 4.33 4.33 0 0
Water Heating 8.33 7.57 0.76 9.1
Self Utilization Credit n/a 0 0 n/a
South Facing Compliance Total 97.33 88.19 9.14 9.4
Space Heating 1.46 1.44 0.02 1.4
Space Cooling 83.21 75.43 7.78 9.3
IAQ Ventilation 4.33 4.33 0 0
Water Heating 8.33 7.57 0.76 9.1
Self Utilization Credit n/a 0 0 n/a
West Facing Compliance Total 97.33 88.77 8.56 8.8
221-P010157785C-000-000-0000000-0000 2022-02-04 16:48:53 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 2 - Pinecrest S853 Calculation Date/Time:2022-02-04T16:18:07-08:00 (Page 4 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 2 - Pinecrest S853.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:22:27
REQUIRED PV SYSTEMS - SIMPLIFIED
01 02 03 04 05 06 07 08 09 10 11 12
DC System Size
(kWdc)Exception Module Type Array Type Power Electronics CFI Azimuth
(deg)
Tilt
Input
Array Angle
(deg)Tilt: (x in 12)
Inverter Eff.
(%)
Annual
Solar Access
(%)
5.12 NA Premium Fixed (roof
mount)Microinverters true 105-300 n/a n/a <=7:12 96 97
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
•Indoor air quality, balanced fan
•Non-standard roof reflectance
•Insulation below roof deck
•Window overhangs and/or fins
HERS FEATURE SUMMARY
The following is a summary of the features that must be field-verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional
detail is provided in the buildng tables below. Registered CF2Rs and CF3Rs are required to be completed in the HERS Registry
Building-level Verifications:
•Quality insulation installation (QII)
•Building air leakage/reduced infiltration
•Indoor air quality ventilation
•Kitchen range hood
Cooling System Verifications:
•Minimum Airflow
•Verified EER
•Verified SEER
•Verified Refrigerant Charge
•Fan Efficacy Watts/CFM
Heating System Verifications:
•-- None --
HVAC Distribution System Verifications:
•Duct leakage testing
•Low-leakage Air Handling Unit
Domestic Hot Water System Verifications:
•-- None --
221-P010157785C-000-000-0000000-0000 2022-02-04 16:48:53 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 2 - Pinecrest S853 Calculation Date/Time:2022-02-04T16:18:07-08:00 (Page 5 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 2 - Pinecrest S853.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:22:27
BUILDING - FEATURES INFORMATION
01 02 03 04 05 06 07
Project Name Conditioned Floor Area (ft
2)Number of Dwelling
Units Number of Bedrooms Number of Zones
Number of Ventilation
Cooling Systems
Number of Water
Heating Systems
Plan 2 - Pinecrest S853 2392 1 3 1 0 1
ZONE INFORMATION
01 02 03 04 05 06 07
Zone Name Zone Type HVAC System Name Zone Floor Area (ft
2)Avg. Ceiling Height Water Heating System 1 Water Heating System 2
Zone 1 Conditioned HVAC1 2392 9.1 DHW Sys 1 N/A
OPAQUE SURFACES
01 02 03 04 05 06 07 08
Name Zone Construction Azimuth Orientation Gross Area (ft
2)Window and Door
Area (ft2)
Tilt (deg)
Front 2X4 Zone 1 Ext. R-13 Wall + R-4.2 0 Front 591.5 76.0032 90
Front 2X6 Zone 1 Ext. R-19 Wall + R-4.2 0 Front 97.8 8 90
Left 2X4 Zone 1 Ext. R-13 Wall + R-4.2 90 Left 455 132 90
Rear 2X4 Zone 1 Ext. R-13 Wall + R-4.2 180 Back 283.6 73 90
Rear 2X6 Zone 1 Ext. R-19 Wall + R-4.2 180 Back 200.9 18.8 90
Right 2X4 Siding Zone 1 Ext. R-13 Wall 270 Right 84.7 34 90
Garage 2X4 Zone 1>>__Garage__Garage R-13 Wall n/a n/a 574.9 17.8 n/a
Roof Zone 1 R-30 Roof Attic + R-13 BD n/a n/a 2362 n/a n/a
Furnace Zone 1 R-30 Roof Attic n/a n/a 30 n/a n/a
Roof 2 __Garage__R-0 Roof Attic n/a n/a 753 n/a n/a
Front 2X4 2 __Garage__Ext R-0 Wall 0 Front 171.4 0 90
Rear 2X4 2 __Garage__Ext R-0 Wall 180 Back 376.1 56 90
Right 2X4 __Garage__Ext R-0 Wall 270 Right 370.1 112 90
221-P010157785C-000-000-0000000-0000 2022-02-04 16:48:53 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 2 - Pinecrest S853 Calculation Date/Time:2022-02-04T16:18:07-08:00 (Page 6 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 2 - Pinecrest S853.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:22:27
ATTIC
01 02 03 04 05 06 07 08
Name Construction Type Roof Rise (x in 12)Roof Reflectance Roof Emittance Radiant Barrier Cool Roof
Attic __Garage__Attic Garage Roof Cons Ventilated 4 0.12 0.92 No No
Attic Zone 1 Attic RoofZone 1 Ventilated 4 0.12 0.92 No No
FENESTRATION / GLAZING
01 02 03 04 05 06 07 08 09 10 11 12 13 14
Name Type Surface Orientation Azimuth Width
(ft)
Height
(ft)Mult.Area
(ft2)U-factor U-factor
Source SHGC
SHGC
Sourc
e
Exterior
Shading
Window Window Front 2X4 Front 0 1 56 0.33 NFRC 0.23 NFRC Bug Screen
FRDR - OH Window Front 2X4 Front 0 2.8 8 0 20 0.33 NFRC 0.23 NFRC Bug Screen
Window 2 Window Front 2X6 Front 0 1 8 0.33 NFRC 0.23 NFRC Bug Screen
Window 3 Window Left 2X4 Left 90 1 36 0.33 NFRC 0.23 NFRC Bug Screen
SGD - OH Window Left 2X4 Left 90 12 8 1 96 0.33 NFRC 0.23 NFRC Bug Screen
Window 4 Window Rear 2X4 Back 180 1 25 0.33 NFRC 0.23 NFRC Bug Screen
SGD - OH 2 Window Rear 2X4 Back 180 6 8 1 48 0.33 NFRC 0.23 NFRC Bug Screen
Window 5 Window Rear 2X6 Back 180 1 18.8 0.33 NFRC 0.23 NFRC Bug Screen
Window 6 Window Right 2X4 Siding Right 270 1 10 0.33 NFRC 0.23 NFRC Bug Screen
OPAQUE DOORS
01 02 03 04
Name Side of Building Area (ft
2)U-factor
Main Door Right 2X4 Siding 24 0.142857
Int Garage Door Garage 2X4 17.8 0.5
Overhead Garage Door Rear 2X4 2 56 0.7
Overhead Garage Door 2 Right 2X4 112 0.7
221-P010157785C-000-000-0000000-0000 2022-02-04 16:48:53 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 2 - Pinecrest S853 Calculation Date/Time:2022-02-04T16:18:07-08:00 (Page 7 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 2 - Pinecrest S853.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:22:27
OVERHANGS AND FINS
01 02 03 04 05 06 07 08 09 10 11 12 13 14
Window
Overhang Left Fin Right Fin
Depth Dist Up Left Extent
Right
Extent Flap Ht.Depth Top Up Dist L Bot Up Depth Top Up Dist R Bot Up
FRDR - OH 16.5 1 2 2 0 0 0 0 0 0 0 0 0
SGD - OH 10 1 10 10 0 0 0 0 0 0 0 0 0
SGD - OH 2 16.5 1 2 2 0 0 0 0 0 0 0 0 0
SLAB FLOORS
01 02 03 04 05 06 07
Name Zone Area (ft2)Perimeter (ft)Edge Insul. R-value and Depth Carpeted Fraction Heated
Slab-on-Grade Zone 1 2392 181 None 80%No
Slab-on-Grade 2 __Garage__753 93 None 0%No
OPAQUE SURFACE CONSTRUCTIONS
01 02 03 04 05 06 07 08
Construction Name Surface Type Construction Type Framing Total Cavity
R-value
Interior / Exterior
Continuous
R-value
U-factor Assembly Layers
Ext R-0 Wall Exterior Walls Wood Framed Wall 2x4 @ 16 in. O. C.R-0 None / None 0.361
Inside Finish: Gypsum Board
Cavity / Frame: no insul. / 2x4
Exterior Finish: 3 Coat Stucco
Ext. R-13 Wall + R-4.2 Exterior Walls Wood Framed Wall 2x4 @ 16 in. O. C.R-13 None / R-4.2 0.067
Inside Finish: Gypsum Board
Cavity / Frame: R-13 / 2x4
Sheathing / Insulation: R-4.2 Sheathing
Exterior Finish: Synthetic Stucco
221-P010157785C-000-000-0000000-0000 2022-02-04 16:48:53 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 2 - Pinecrest S853 Calculation Date/Time:2022-02-04T16:18:07-08:00 (Page 8 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 2 - Pinecrest S853.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:22:27
OPAQUE SURFACE CONSTRUCTIONS
01 02 03 04 05 06 07 08
Construction Name Surface Type Construction Type Framing Total Cavity
R-value
Interior / Exterior
Continuous
R-value
U-factor Assembly Layers
Ext. R-19 Wall + R-4.2 Exterior Walls Wood Framed Wall 2x6 @ 16 in. O. C.R-19 None / R-4.2 0.054
Inside Finish: Gypsum Board
Cavity / Frame: R-19 in 5-1/2 in. (R-18) /
2x6
Sheathing / Insulation: R-4.2 Sheathing
Exterior Finish: Synthetic Stucco
Ext. R-13 Wall Exterior Walls Wood Framed Wall 2x4 @ 16 in. O. C.R-13 None / None 0.101
Inside Finish: Gypsum Board
Cavity / Frame: R-13 / 2x4
Exterior Finish: 3 Coat Stucco
Garage R-13 Wall Interior Walls Wood Framed Wall 2x4 @ 16 in. O. C.R-13 None / None 0.092
Inside Finish: Gypsum Board
Cavity / Frame: R-13 / 2x4
Other Side Finish: Gypsum Board
Attic Garage Roof Cons Attic Roofs
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-0 None / None 0.4
Roofing: 10 PSF (RoofTile)
Tile Gap: present
Roof Deck: Wood
Siding/sheathing/decking
Cavity / Frame: no insul. / 2x4
Attic RoofZone 1 Attic Roofs
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-13 None / None 0.072
Roofing: 10 PSF (RoofTile)
Tile Gap: present
Roof Deck: Wood
Siding/sheathing/decking
Cavity / Frame: R-13.0 / 2x4
Around Roof Joists: R-0.0 insul.
R-0 Roof Attic
Ceilings (below
attic)
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-0 None / None 0.481 Cavity / Frame: no insul. / 2x4
Inside Finish: Gypsum Board
R-30 Roof Attic + R-13
BD
Ceilings (below
attic)
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-30 None / None 0.032
Over Ceiling Joists: R-20.9 insul.
Cavity / Frame: R-9.1 / 2x4
Inside Finish: Gypsum Board
221-P010157785C-000-000-0000000-0000 2022-02-04 16:48:53 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 2 - Pinecrest S853 Calculation Date/Time:2022-02-04T16:18:07-08:00 (Page 9 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 2 - Pinecrest S853.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:22:27
OPAQUE SURFACE CONSTRUCTIONS
01 02 03 04 05 06 07 08
Construction Name Surface Type Construction Type Framing Total Cavity
R-value
Interior / Exterior
Continuous
R-value
U-factor Assembly Layers
R-30 Roof Attic
Ceilings (below
attic)
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-30 None / None 0.032
Over Ceiling Joists: R-20.9 insul.
Cavity / Frame: R-9.1 / 2x4
Inside Finish: Gypsum Board
BUILDING ENVELOPE - HERS VERIFICATION
01 02 03 04
Quality Insulation Installation (QII)Quality Installation of Spray Foam Insulation Building Envelope Air Leakage CFM50
Required Not Required Required 1451.1
WATER HEATING SYSTEMS
01 02 03 04 05 06 07
Name System Type Distribution Type Water Heater Name (#)Solar Heating System Compact Distribution HERS Verification
DHW Sys 1
Domestic Hot Water
(DHW)
Standard Distribution
System DHW Heater 1 (1)n/a None n/a
WATER HEATERS
01 02 03 04 05 06 07 08 09 10 11 12
Name
Heating
Element
Type
Tank Type
#
Units
Tank
Vol.
(gal)
Energy
Factor or
Efficiency
Input Rating
or Pilot
Tank
Insulation
R-value
(Int/Ext)
Standby Loss
or Recovery
Eff.
1st Hr. Rating
or Flow Rate
NEEA Heat Pump
Brand or Model
Tank Location or
Ambient Condition
DHW Heater 1 Gas Consumer
Instantaneous 1 0 0.93-UEF <= 200
kBtu/hr 0 n/a n/a n/a n/a
221-P010157785C-000-000-0000000-0000 2022-02-04 16:48:53 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 2 - Pinecrest S853 Calculation Date/Time:2022-02-04T16:18:07-08:00 (Page 10 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 2 - Pinecrest S853.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:22:27
WATER HEATING - HERS VERIFICATION
01 02 03 04 05 06 07 08
Name Pipe Insulation Parallel Piping Compact Distribution
Compact Distribution
Type Recirculation Control
Central DHW
Distribution
Shower Drain Water
Heat Recovery
DHW Sys 1 - 1/1 Not Required Not Required Not Required None Not Required Not Required Not Required
SPACE CONDITIONING SYSTEMS
01 02 03 04 05 06 07 08 09 10 11
Name System Type
Heating Unit
Name
Cooling Unit
Name Fan Name
Distribution
Name
Required
Thermostat
Type
Status
Verified
Existing
Condition
Heating
Equipment
Count
Cooling
Equipment
Count
HVAC1 Heating and cooling system
other
Heating
Component
1
Cooling
Component
1
HVAC Fan 1
Air
Distribution
System 1
Setback New NA 2 2
HVAC - HEATING UNIT TYPES
01 02 03 04
Name System Type Number of Units Heating Efficiency
Heating Component 1 Central gas furnace 2 AFUE-96
HVAC - COOLING UNIT TYPES
01 02 03 04 05 06 07 08
Name System Type Number of Units Efficiency EER Efficiency SEER Zonally Controlled
Mulit-speed
Compressor HERS Verification
Cooling Component 1 Central split AC 2 13 16.5 Not Zonal Single Speed
Cooling Component
1-hers-cool
221-P010157785C-000-000-0000000-0000 2022-02-04 16:48:53 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 2 - Pinecrest S853 Calculation Date/Time:2022-02-04T16:18:07-08:00 (Page 11 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 2 - Pinecrest S853.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:22:27
HVAC COOLING - HERS VERIFICATION
01 02 03 04 05 06
Name Verified Airflow Airflow Target Verified EER Verified SEER Verified Refrigerant Charge
Cooling Component
1-hers-cool Required 350 Required Required Required
HVAC - DISTRIBUTION SYSTEMS
01 02 03 04 05 06 07 08 09 10 11 12
Duct Ins. R-value Duct Location Surface Area
Name Type Design Type Supply Return Supply Return Supply Return Bypass
Duct Duct Leakage
HERS
Verification
Air Distribution
System 1
Unconditioned attic Non-Verified R-6 R-6 Attic Attic n/a n/a
No
Bypass
Duct
Air
Distribution
System
1-hers-dist
HVAC DISTRIBUTION - HERS VERIFICATION
01 02 03 04 05 06 07 08 09
Name Duct Leakage
Verification
Duct Leakage
Target (%)
Verified Duct
Location
Verified Duct
Design Buried Ducts
Deeply Buried
Ducts
Low-leakage Air
Handler
Low Leakage
Ducts Entirely in
Conditioned
Space
Air Distribution
System 1-hers-dist
Yes 5.0 Not Required Not Required Not Required Credit not taken Required No
HVAC - FAN SYSTEMS
01 02 03 04
Name Type Fan Power (Watts/CFM)Name
HVAC Fan 1 HVAC Fan 0.45 HVAC Fan 1-hers-fan
221-P010157785C-000-000-0000000-0000 2022-02-04 16:48:53 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 2 - Pinecrest S853 Calculation Date/Time:2022-02-04T16:18:07-08:00 (Page 12 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 2 - Pinecrest S853.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:22:27
HVAC FAN SYSTEMS - HERS VERIFICATION
01 02 03
Name Verified Fan Watt Draw Required Fan Efficacy (Watts/CFM)
HVAC Fan 1-hers-fan Required 0.45
IAQ (INDOOR AIR QUALITY) FANS
01 02 03 04 05 06
Dwelling Unit IAQ CFM IAQ Watts/CFM IAQ Fan Type IAQ Recovery Effectiveness (%)
IAQ Recovery Effectiveness -
SREIAQ Recovery Effectiveness
- SRE
SFam IAQVentRpt 1-1 85 0.517647 Balanced HRV 75 n/a
221-P010157785C-000-000-0000000-0000 2022-02-04 16:48:53 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 2 - Pinecrest S853 Calculation Date/Time:2022-02-04T16:18:07-08:00 (Page 13 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 2 - Pinecrest S853.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:22:27
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:Documentation Author Signature:
Company:Signature Date:
Address:CEA/ HERS Certification Identification (If applicable):
City/State/Zip:Phone:
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1.I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance.
2.I certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations.
3.The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets,
calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
Responsible Designer Name:Responsible Designer Signature:
Company:Date Signed:
Address:License:
City/State/Zip:Phone:
Easy to Verify
at CalCERTS.com
Cristela Lujan
Energy Inspectors
2570 South Miller Lane
Las Vegas, NV 89117
2022-02-04 16:44:46
R19-18-30081
702-365-8080
John Heimann
Richmond American Homes
5171 California Ave. Suite #120
Irvine, CA 92617
2022-02-04 16:48:53
N/A
949-467-2661
Digitally signed by CalCERTS. This digital signature is provided in order to secure the content of this registered document, and in no way implies
Registration Provider responsibility for the accuracy of the information.
221-P010157785C-000-000-0000000-0000 2022-02-04 16:48:53 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 3 - Pomona S850 Calculation Date/Time:2022-02-04T16:37:39-08:00 (Page 1 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 3 - Pomona S850.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:41:58
GENERAL INFORMATION
01 Project Name Plan 3 - Pomona S850
02 Run Title Title 24 Analysis
03 Project Location Bella at Piazza Serena
04 City La Quinta 05 Standards Version 2019
06 Zip code 07 Software Version EnergyPro 8.1
08 Climate Zone 15 09 Front Orientation (deg/ Cardinal)AllOrientations
10 Building Type Single family 11 Number of Dwelling Units 1
12 Project Scope NewConstruction 13 Number of Bedrooms 4
14 Addition Cond. Floor Area (ft
2)0 15 Number of Stories 1
16 Existing Cond. Floor Area (ft
2)n/a 17 Fenestration Average U-factor 0.32
18 Total Cond. Floor Area (ft
2)2630 19 Glazing Percentage (%)17.07%
20 ADU Bedroom Count 0 21 ADU Conditioned Floor Area 0
22 Is Natural Gas Available?Yes
COMPLIANCE RESULTS
01 Building Complies with Computer Performance
02 This building incorporates features that require field testing and/or verification by a certified HERS rater under the supervision of a CEC-approved HERS provider.
03 This building incorporates one or more Special Features shown below
221-P010157786C-000-000-0000000-0000 2022-02-04 16:49:31 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 3 - Pomona S850 Calculation Date/Time:2022-02-04T16:37:39-08:00 (Page 2 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 3 - Pomona S850.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:41:58
ENERGY DESIGN RATING
Energy Design Ratings
Efficiency¹ (EDR)Total² (EDR)Efficiency¹ (EDR)Total² (EDR)
Standard Design 50.8 23.1
Proposed Designs
North Facing 45.6 20.4 5.2 2.7
East Facing 48.2 23.1 2.6 0
South Facing 47 21.9 3.8 1.2
West Facing 47.2 22.1 3.6 1
RESULT:3:COMPLIES
¹ Efficiency EDR includes improvements to the building envelope and more efficient equipment
² Total EDR includes efficiency and demand response measures such as photovoltaic (PV) systems and batteries
³ Building complies when efficiency and total compliance margins are greater than or equal to zero
•Standard Design PV Capacity: 6.06 kWdc
•Proposed PV Capacity Scaling: North (6.05 kWdc) East (6.05 kWdc) South (6.05 kWdc) West (6.05 kWdc)
221-P010157786C-000-000-0000000-0000 2022-02-04 16:49:31 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 3 - Pomona S850 Calculation Date/Time:2022-02-04T16:37:39-08:00 (Page 3 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 3 - Pomona S850.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:41:58
ENERGY USE SUMMARY
Energy Use (kTDV/ft
2-yr)Standard Design Proposed Design Compliance Margin Percent Improvement
Space Heating 1.64 0.85 0.79 48.2
Space Cooling 88.4 74.06 14.34 16.2
IAQ Ventilation 5.46 5.46 0 0
Water Heating 8.11 7.35 0.76 9.4
Self Utilization Credit n/a 0 0 n/a
North Facing Compliance Total 103.61 87.72 15.89 15.3
Space Heating 1.64 1.02 0.62 37.8
Space Cooling 88.4 81.97 6.43 7.3
IAQ Ventilation 5.46 5.46 0 0
Water Heating 8.11 7.35 0.76 9.4
Self Utilization Credit n/a 0 0 n/a
East Facing Compliance Total 103.61 95.8 7.81 7.5
Space Heating 1.64 1.4 0.24 14.6
Space Cooling 88.4 77.9 10.5 11.9
IAQ Ventilation 5.46 5.46 0 0
Water Heating 8.11 7.35 0.76 9.4
Self Utilization Credit n/a 0 0 n/a
South Facing Compliance Total 103.61 92.11 11.5 11.1
Space Heating 1.64 1.45 0.19 11.6
Space Cooling 88.4 78.53 9.87 11.2
IAQ Ventilation 5.46 5.46 0 0
Water Heating 8.11 7.35 0.76 9.4
Self Utilization Credit n/a 0 0 n/a
West Facing Compliance Total 103.61 92.79 10.82 10.4
221-P010157786C-000-000-0000000-0000 2022-02-04 16:49:31 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 3 - Pomona S850 Calculation Date/Time:2022-02-04T16:37:39-08:00 (Page 4 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 3 - Pomona S850.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:41:58
REQUIRED PV SYSTEMS - SIMPLIFIED
01 02 03 04 05 06 07 08 09 10 11 12
DC System Size
(kWdc)Exception Module Type Array Type Power Electronics CFI Azimuth
(deg)
Tilt
Input
Array Angle
(deg)Tilt: (x in 12)
Inverter Eff.
(%)
Annual
Solar Access
(%)
6.05 NA Premium Fixed (roof
mount)Microinverters true 105-300 n/a n/a <=7:12 96 97
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
•Indoor air quality, balanced fan
•Non-standard roof reflectance
•Insulation below roof deck
•Window overhangs and/or fins
HERS FEATURE SUMMARY
The following is a summary of the features that must be field-verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional
detail is provided in the buildng tables below. Registered CF2Rs and CF3Rs are required to be completed in the HERS Registry
Building-level Verifications:
•Quality insulation installation (QII)
•Building air leakage/reduced infiltration
•Indoor air quality ventilation
•Kitchen range hood
Cooling System Verifications:
•Minimum Airflow
•Verified EER
•Verified SEER
•Verified Refrigerant Charge
•Fan Efficacy Watts/CFM
Heating System Verifications:
•-- None --
HVAC Distribution System Verifications:
•Duct leakage testing
•Low-leakage Air Handling Unit
Domestic Hot Water System Verifications:
•-- None --
221-P010157786C-000-000-0000000-0000 2022-02-04 16:49:31 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 3 - Pomona S850 Calculation Date/Time:2022-02-04T16:37:39-08:00 (Page 5 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 3 - Pomona S850.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:41:58
BUILDING - FEATURES INFORMATION
01 02 03 04 05 06 07
Project Name Conditioned Floor Area (ft
2)Number of Dwelling
Units Number of Bedrooms Number of Zones
Number of Ventilation
Cooling Systems
Number of Water
Heating Systems
Plan 3 - Pomona S850 2630 1 4 1 0 1
ZONE INFORMATION
01 02 03 04 05 06 07
Zone Name Zone Type HVAC System Name Zone Floor Area (ft
2)Avg. Ceiling Height Water Heating System 1 Water Heating System 2
Zone 1 Conditioned HVAC1 2630 9.1 DHW Sys 1 N/A
OPAQUE SURFACES
01 02 03 04 05 06 07 08
Name Zone Construction Azimuth Orientation Gross Area (ft
2)Window and Door
Area (ft2)
Tilt (deg)
Front 2X4 Zone 1 Ext. R-13 Wall + R-4.2 0 Front 596.1 55.0024 90
Front 2X6 Zone 1 Ext. R-19 Wall + R-4.2 0 Front 161.5 28 90
Left 2X4 Zone 1 Ext. R-13 Wall + R-4.2 90 Left 455 156 90
Rear 2X4 Zone 1 Ext. R-13 Wall + R-4.2 180 Back 615 121 90
Rear 2X6 Zone 1 Ext. R-19 Wall + R-4.2 180 Back 159.3 63 90
Right 2X4 Siding Zone 1 Ext. R-13 Wall 270 Right 116.8 50 90
Garage 2X4 Zone 1>>__Garage__Garage R-13 Wall n/a n/a 354.9 17.8 n/a
Roof Zone 1 R-30 Roof Attic + R-13 BD n/a n/a 2600 n/a n/a
Furnace Zone 1 R-30 Roof Attic n/a n/a 30 n/a n/a
Roof 2 __Garage__R-0 Roof Attic n/a n/a 659 n/a n/a
Front 2X4 2 __Garage__Ext R-0 Wall 0 Front 302.6 0 90
Left 2X4 2 __Garage__Ext R-0 Wall 90 Left 37.9 0 90
Rear 2X4 2 __Garage__Ext R-0 Wall 180 Back 285.9 56 90
Right 2X4 __Garage__Ext R-0 Wall 270 Right 376.2 112 90
221-P010157786C-000-000-0000000-0000 2022-02-04 16:49:31 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 3 - Pomona S850 Calculation Date/Time:2022-02-04T16:37:39-08:00 (Page 6 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 3 - Pomona S850.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:41:58
ATTIC
01 02 03 04 05 06 07 08
Name Construction Type Roof Rise (x in 12)Roof Reflectance Roof Emittance Radiant Barrier Cool Roof
Attic __Garage__Attic Garage Roof Cons Ventilated 5 0.12 0.92 No No
Attic Zone 1 Attic RoofZone 1 Ventilated 5 0.12 0.92 No No
FENESTRATION / GLAZING
01 02 03 04 05 06 07 08 09 10 11 12 13 14
Name Type Surface Orientation Azimuth Width
(ft)
Height
(ft)Mult.Area
(ft2)U-factor U-factor
Source SHGC
SHGC
Sourc
e
Exterior
Shading
Window Window Front 2X4 Front 0 1 33.7 0.33 NFRC 0.23 NFRC Bug Screen
FRDR - OH Window Front 2X4 Front 0 2.8 8 0 21.3 0.33 NFRC 0.23 NFRC Bug Screen
Window 2 Window Front 2X6 Front 0 1 28 0.33 NFRC 0.23 NFRC Bug Screen
Window 3 Window Left 2X4 Left 90 1 60 0.33 NFRC 0.23 NFRC Bug Screen
SGD - OH Window Left 2X4 Left 90 12 8 1 96 0.33 NFRC 0.23 NFRC Bug Screen
Window 4 Window Rear 2X4 Back 180 1 121 0.3 NFRC 0.23 NFRC Bug Screen
Window 5 Window Rear 2X6 Back 180 1 15 0.33 NFRC 0.23 NFRC Bug Screen
SGD - OH 2 Window Rear 2X6 Back 180 6 8 1 48 0.33 NFRC 0.23 NFRC Bug Screen
Window 6 Window Right 2X4 Siding Right 270 1 26 0.33 NFRC 0.23 NFRC Bug Screen
OPAQUE DOORS
01 02 03 04
Name Side of Building Area (ft
2)U-factor
Main Door Right 2X4 Siding 24 0.142857
Int Garage Door Garage 2X4 17.8 0.5
Overhead Garage Door Rear 2X4 2 56 0.7
Overhead Garage Door 2 Right 2X4 112 0.7
221-P010157786C-000-000-0000000-0000 2022-02-04 16:49:31 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 3 - Pomona S850 Calculation Date/Time:2022-02-04T16:37:39-08:00 (Page 7 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 3 - Pomona S850.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:41:58
OVERHANGS AND FINS
01 02 03 04 05 06 07 08 09 10 11 12 13 14
Window
Overhang Left Fin Right Fin
Depth Dist Up Left Extent
Right
Extent Flap Ht.Depth Top Up Dist L Bot Up Depth Top Up Dist R Bot Up
FRDR - OH 19 1 2 2 0 0 0 0 0 0 0 0 0
SGD - OH 10 1 10 10 0 0 0 0 0 0 0 0 0
SGD - OH 2 19 1 2 2 0 0 0 0 0 0 0 0 0
SLAB FLOORS
01 02 03 04 05 06 07
Name Zone Area (ft2)Perimeter (ft)Edge Insul. R-value and Depth Carpeted Fraction Heated
Slab-on-Grade Zone 1 2630 231 None 80%No
Slab-on-Grade 2 __Garage__659 110 None 0%No
OPAQUE SURFACE CONSTRUCTIONS
01 02 03 04 05 06 07 08
Construction Name Surface Type Construction Type Framing Total Cavity
R-value
Interior / Exterior
Continuous
R-value
U-factor Assembly Layers
Ext R-0 Wall Exterior Walls Wood Framed Wall 2x4 @ 16 in. O. C.R-0 None / None 0.361
Inside Finish: Gypsum Board
Cavity / Frame: no insul. / 2x4
Exterior Finish: 3 Coat Stucco
Ext. R-13 Wall + R-4.2 Exterior Walls Wood Framed Wall 2x4 @ 16 in. O. C.R-13 None / R-4.2 0.067
Inside Finish: Gypsum Board
Cavity / Frame: R-13 / 2x4
Sheathing / Insulation: R-4.2 Sheathing
Exterior Finish: Synthetic Stucco
221-P010157786C-000-000-0000000-0000 2022-02-04 16:49:31 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 3 - Pomona S850 Calculation Date/Time:2022-02-04T16:37:39-08:00 (Page 8 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 3 - Pomona S850.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:41:58
OPAQUE SURFACE CONSTRUCTIONS
01 02 03 04 05 06 07 08
Construction Name Surface Type Construction Type Framing Total Cavity
R-value
Interior / Exterior
Continuous
R-value
U-factor Assembly Layers
Ext. R-19 Wall + R-4.2 Exterior Walls Wood Framed Wall 2x6 @ 16 in. O. C.R-19 None / R-4.2 0.054
Inside Finish: Gypsum Board
Cavity / Frame: R-19 in 5-1/2 in. (R-18) /
2x6
Sheathing / Insulation: R-4.2 Sheathing
Exterior Finish: Synthetic Stucco
Ext. R-13 Wall Exterior Walls Wood Framed Wall 2x4 @ 16 in. O. C.R-13 None / None 0.101
Inside Finish: Gypsum Board
Cavity / Frame: R-13 / 2x4
Exterior Finish: 3 Coat Stucco
Garage R-13 Wall Interior Walls Wood Framed Wall 2x4 @ 16 in. O. C.R-13 None / None 0.092
Inside Finish: Gypsum Board
Cavity / Frame: R-13 / 2x4
Other Side Finish: Gypsum Board
Attic Garage Roof Cons Attic Roofs
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-0 None / None 0.4
Roofing: 10 PSF (RoofTile)
Tile Gap: present
Roof Deck: Wood
Siding/sheathing/decking
Cavity / Frame: no insul. / 2x4
Attic RoofZone 1 Attic Roofs
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-13 None / None 0.072
Roofing: 10 PSF (RoofTile)
Tile Gap: present
Roof Deck: Wood
Siding/sheathing/decking
Cavity / Frame: R-13.0 / 2x4
Around Roof Joists: R-0.0 insul.
R-0 Roof Attic
Ceilings (below
attic)
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-0 None / None 0.481 Cavity / Frame: no insul. / 2x4
Inside Finish: Gypsum Board
R-30 Roof Attic + R-13
BD
Ceilings (below
attic)
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-30 None / None 0.032
Over Ceiling Joists: R-20.9 insul.
Cavity / Frame: R-9.1 / 2x4
Inside Finish: Gypsum Board
221-P010157786C-000-000-0000000-0000 2022-02-04 16:49:31 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 3 - Pomona S850 Calculation Date/Time:2022-02-04T16:37:39-08:00 (Page 9 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 3 - Pomona S850.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:41:58
OPAQUE SURFACE CONSTRUCTIONS
01 02 03 04 05 06 07 08
Construction Name Surface Type Construction Type Framing Total Cavity
R-value
Interior / Exterior
Continuous
R-value
U-factor Assembly Layers
R-30 Roof Attic
Ceilings (below
attic)
Wood Framed
Ceiling 2x4 @ 24 in. O. C.R-30 None / None 0.032
Over Ceiling Joists: R-20.9 insul.
Cavity / Frame: R-9.1 / 2x4
Inside Finish: Gypsum Board
BUILDING ENVELOPE - HERS VERIFICATION
01 02 03 04
Quality Insulation Installation (QII)Quality Installation of Spray Foam Insulation Building Envelope Air Leakage CFM50
Required Not Required Required 1595.5
WATER HEATING SYSTEMS
01 02 03 04 05 06 07
Name System Type Distribution Type Water Heater Name (#)Solar Heating System Compact Distribution HERS Verification
DHW Sys 1
Domestic Hot Water
(DHW)
Standard Distribution
System DHW Heater 1 (1)n/a None n/a
WATER HEATERS
01 02 03 04 05 06 07 08 09 10 11 12
Name
Heating
Element
Type
Tank Type
#
Units
Tank
Vol.
(gal)
Energy
Factor or
Efficiency
Input Rating
or Pilot
Tank
Insulation
R-value
(Int/Ext)
Standby Loss
or Recovery
Eff.
1st Hr. Rating
or Flow Rate
NEEA Heat Pump
Brand or Model
Tank Location or
Ambient Condition
DHW Heater 1 Gas Consumer
Instantaneous 1 0 0.93-UEF <= 200
kBtu/hr 0 n/a n/a n/a n/a
221-P010157786C-000-000-0000000-0000 2022-02-04 16:49:31 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 3 - Pomona S850 Calculation Date/Time:2022-02-04T16:37:39-08:00 (Page 10 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 3 - Pomona S850.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:41:58
WATER HEATING - HERS VERIFICATION
01 02 03 04 05 06 07 08
Name Pipe Insulation Parallel Piping Compact Distribution
Compact Distribution
Type Recirculation Control
Central DHW
Distribution
Shower Drain Water
Heat Recovery
DHW Sys 1 - 1/1 Not Required Not Required Not Required None Not Required Not Required Not Required
SPACE CONDITIONING SYSTEMS
01 02 03 04 05 06 07 08 09 10 11
Name System Type
Heating Unit
Name
Cooling Unit
Name Fan Name
Distribution
Name
Required
Thermostat
Type
Status
Verified
Existing
Condition
Heating
Equipment
Count
Cooling
Equipment
Count
HVAC1 Heating and cooling system
other
Heating
Component
1
Cooling
Component
1
HVAC Fan 1
Air
Distribution
System 1
Setback New NA 2 2
HVAC - HEATING UNIT TYPES
01 02 03 04
Name System Type Number of Units Heating Efficiency
Heating Component 1 Central gas furnace 2 AFUE-96
HVAC - COOLING UNIT TYPES
01 02 03 04 05 06 07 08
Name System Type Number of Units Efficiency EER Efficiency SEER Zonally Controlled
Mulit-speed
Compressor HERS Verification
Cooling Component 1 Central split AC 2 13 16.5 Not Zonal Single Speed
Cooling Component
1-hers-cool
221-P010157786C-000-000-0000000-0000 2022-02-04 16:49:31 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 3 - Pomona S850 Calculation Date/Time:2022-02-04T16:37:39-08:00 (Page 11 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 3 - Pomona S850.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:41:58
HVAC COOLING - HERS VERIFICATION
01 02 03 04 05 06
Name Verified Airflow Airflow Target Verified EER Verified SEER Verified Refrigerant Charge
Cooling Component
1-hers-cool Required 350 Required Required Required
HVAC - DISTRIBUTION SYSTEMS
01 02 03 04 05 06 07 08 09 10 11 12
Duct Ins. R-value Duct Location Surface Area
Name Type Design Type Supply Return Supply Return Supply Return Bypass
Duct Duct Leakage
HERS
Verification
Air Distribution
System 1
Unconditioned attic Non-Verified R-6 R-6 Attic Attic n/a n/a
No
Bypass
Duct
Air
Distribution
System
1-hers-dist
HVAC DISTRIBUTION - HERS VERIFICATION
01 02 03 04 05 06 07 08 09
Name Duct Leakage
Verification
Duct Leakage
Target (%)
Verified Duct
Location
Verified Duct
Design Buried Ducts
Deeply Buried
Ducts
Low-leakage Air
Handler
Low Leakage
Ducts Entirely in
Conditioned
Space
Air Distribution
System 1-hers-dist
Yes 5.0 Not Required Not Required Not Required Credit not taken Required No
HVAC - FAN SYSTEMS
01 02 03 04
Name Type Fan Power (Watts/CFM)Name
HVAC Fan 1 HVAC Fan 0.45 HVAC Fan 1-hers-fan
221-P010157786C-000-000-0000000-0000 2022-02-04 16:49:31 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 3 - Pomona S850 Calculation Date/Time:2022-02-04T16:37:39-08:00 (Page 12 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 3 - Pomona S850.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:41:58
HVAC FAN SYSTEMS - HERS VERIFICATION
01 02 03
Name Verified Fan Watt Draw Required Fan Efficacy (Watts/CFM)
HVAC Fan 1-hers-fan Required 0.45
IAQ (INDOOR AIR QUALITY) FANS
01 02 03 04 05 06
Dwelling Unit IAQ CFM IAQ Watts/CFM IAQ Fan Type IAQ Recovery Effectiveness (%)
IAQ Recovery Effectiveness -
SREIAQ Recovery Effectiveness
- SRE
SFam IAQVentRpt 1-1 100 0.61 Balanced HRV 75 n/a
221-P010157786C-000-000-0000000-0000 2022-02-04 16:49:31 CalCERTS inc.
CERTIFICATE OF COMPLIANCE CF1R-PRF-01E
Project Name:Plan 3 - Pomona S850 Calculation Date/Time:2022-02-04T16:37:39-08:00 (Page 13 of 13)
Calculation Description:Title 24 Analysis Input File Name:Plan 3 - Pomona S850.ribd19x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.108
Schema Version: rev 20200101
Report Generated: 2022-02-04 16:41:58
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:Documentation Author Signature:
Company:Signature Date:
Address:CEA/ HERS Certification Identification (If applicable):
City/State/Zip:Phone:
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1.I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance.
2.I certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations.
3.The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets,
calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
Responsible Designer Name:Responsible Designer Signature:
Company:Date Signed:
Address:License:
City/State/Zip:Phone:
Easy to Verify
at CalCERTS.com
Cristela Lujan
Energy Inspectors
2570 South Miller Lane
Las Vegas, NV 89117
2022-02-04 16:45:27
R19-18-30081
702-365-8080
John Heimann
Richmond American Homes
5171 California Ave. Suite #120
Irvine, CA 92617
2022-02-04 16:49:31
N/A
949-467-2661
Digitally signed by CalCERTS. This digital signature is provided in order to secure the content of this registered document, and in no way implies
Registration Provider responsibility for the accuracy of the information.
221-P010157786C-000-000-0000000-0000 2022-02-04 16:49:31 CalCERTS inc.