Point Happy TR 31348 BCPR2022-0016 - Master Solar Plans - Revision 1SOLAR MASTER PLAN PERMIT PACKAGE WILLIAMS HOMES 21080 CENTRE POINTE PARKWAYSANTA CLARITA, CA 91350 TRACT / PARCEL #: 31348LA QUINTA, CALIFORNIA 92253 POINT HAPPY PLAN 1 (2762), 2 (3213), 2X (3055) 6.48 kW PHOTOVOLTAIC SYSTEM CODE INFORMATION APPLICABLE CODES, LAWS AND REGULATIONS 2022 CALIFORNIA BUILDING CODE (CBC) 2022 CALIFORNIA RESIDENTIAL CODE (CRC) 2022 CALIFORNIA FIRE CODE (CFC) 2022 CALIFORNIA ELECTRICAL CODE (CEC) 2022 CALIFORNIA MECHANICAL CODE (CMC) 2022 CALIFORNIA PLUMBING CODE (CPC) E LECT R I C A L E22659 Exp. 03-31-23R EGISTERE D P R O F ESSIONAL E N G I N EER S T ATE OF CA L I F O R NIA CHI F UNG L E UN G PO I N T H A P P Y TR A C T / P A R C E L # : 3 1 3 4 8 WI L L I A M S H O M E S 21 0 8 0 C E N T R E P O I N T E P A R K W A Y LA Q U I N T A , C A L I F O R N I A 9 2 2 5 3 SA N T A C L A R I T A , C A 9 1 3 5 0 DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID C003130 D-0125405 2023-03-02 GELLIE GREGANDA TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 C A L I C E N S E # 8 9 0 8 9 5 ® VICINITY MAP PROJECT LOCATION SHEET SO L A R M A S T E R P L A N P E R M I T P A C K A G E RE V D E S C R I P T I O N D A T E D B R E V I S I O N S PVA-0 GENERAL NOTES: SHEET INDEX SOLAR ARCHITECTURAL DRAWINGS SOLAR STRUCTURAL DRAWINGS SOLAR ELECTRICAL DRAWINGS PVE-1.1 ELECTRICAL SINGLE LINE DIAGRAM PVE-2 ELECTRICAL DETAILS PVE-3 ELECTRICAL DATA & SPECIFICATIONS PVS-1 MOUNTING DETAILS & STRUCTURAL CALCULATIONS PVA-0 COVER SHEET PVA-1 PLAN 1 (2762) ELEVATION A & B PVA-2 PVA-3 PLAN 2 (3213) ELEVATION A & B PLAN 2X (3055) ELEVATION B 1 TR A N S I T I O N T O 4 0 5 H A N W H A Q - C E L L 3 / 2 / 2 3 G G PVE-1.2 ELECTRICAL SINGLE LINE DIAGRAM REVISION #1 BCPR2022-0016 NEW ROOF LAYOUTS + NEW SYSTEM ATTRIBUTES OF ALL PLAN TYPES: 6.48kW SOLAR ARRAY - (16) 405W HANWHA Q CELLS Q.PEAK DUO BLK ML-G10+ PANELS + W/ (16) ENPHASE IQ7HS-66-M-US MICROINVERTERS [346SF] 03/30/2023 ALL CONSTRUCTION SHALL COMPLY WITH THE 2019 CALIFORNIA RESIDENTIAL, MECHANICAL, ELECTRICAL, PLUMBING, GREEN BUILDING AND ENERGY CODES AND THE LA QUINTA MUNICIPAL CODE ARRAYS MUST BE ORIENTATED BETWEEN 105° - 300° AZIMUTH PER APPROVED ENERGY REPORT E LECT R I C A L E22659 Exp. 03-31-23R EGISTERE D P R O F ESSIONAL E N G I N EER S TATE OF CA L I F O R NIA CHI F UNG L E UN G SO L A R M A S T E R P L A N P E R M I T P A C K A G E PO I N T H A P P Y TR A C T / P A R C E L # : 3 1 3 4 8 WI L L I A M S H O M E S 21 0 8 0 C E N T R E P O I N T E P A R K W A Y LA Q U I N T A , C A L I F O R N I A 9 2 2 5 3 SA N T A C L A R I T A , C A 9 1 3 5 0 DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID C003130 D-0125405 2023-03-02 GELLIE GREGANDA LEGENDS: (3') WIDE ACCESS PATH (PITCHED ROOF) (4') WIDE ACCESS PATH (FLAT ROOF) PLAN TYPE OPTION DESCRIPTION 01 02 03 ----------------------------------- ----------------------------------- ----------------------------------- 04 05 ----------------------------------- ----------------------------------- PLAN 1 (2762) - ELEVATION A - S-TILE NOTE : - ROOFTOP PENETRATIONS AND/OR CONSTRUCTIONS NOT PERTAINING TO SOLAR INSTALLATION SHALL NOT BE LOCATED UNDER ARRAY. - FIRE ACCESS POINTS SHALL NOT BE LOCATED OVER DOORS AND WINDOWS OR BE OTHERWISE OBSTRUCTED BY ATTIC VENT, PLUMBING VENT, MECHANICAL VENT. BASE SQUARE FOOTAGE: 2762 SQ. FT. SLD REFERENCE PVE-1.1 SUNPOWER 132 CELLS AC MODULES MODEL NO.NOMINAL POWER (Pnom) 405W SYSTEM SIZE Q.PEAK DUO BLK ML-G10+ (405) QUANTITY: 16 6.48 kW SLD REFERENCE PVE-1.1 SLD REFERENCE PVE-1.1 LAYOUT 1 LAYOUT 2 LAYOUT 3 PLAN 1 (2762) - ELEVATION B - S-TILE SLD REFERENCE PVE-1.1 SLD REFERENCE PVE-1.1 SLD REFERENCE PVE-1.1 LAYOUT 1 LAYOUT 2 LAYOUT 3 BACK FRONT OF HOUSE : 285° - 120° BACK FRONT OF HOUSE : 285° - 120° LEFT FRONT OF HOUSE : 15° - 210°RIGHT FRONT OF HOUSE : 195° - 30° LEFT FRONT OF HOUSE : 15° - 210°RIGHT FRONT OF HOUSE : 195° - 30° FRONT OF HOUSE (FOH)FRONT OF HOUSE (FOH)FRONT OF HOUSE (FOH) FRONT OF HOUSE (FOH)FRONT OF HOUSE (FOH)FRONT OF HOUSE (FOH) TRANSITION BOX ROOF ACCESS POINT (E) SERVICE POINT AND UTILITY METERING TO ELECTRIC UTILITY GRID UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) (N) LOAD CENTER (INSIDE GARAGE) ROOF ACCESS POINT TRANSITION BOX ROOF ACCESS POINT (E) SERVICE POINT AND UTILITY METERING TO ELECTRIC UTILITY GRID UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) (N) LOAD CENTER (INSIDE GARAGE) ROOF ACCESS POINT ROOF ACCESS POINT (E) SERVICE POINT AND UTILITY METERING TO ELECTRIC UTILITY GRID UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) (N) LOAD CENTER (INSIDE GARAGE) ROOF ACCESS POINT ROOF ACCESS POINT (E) SERVICE POINT AND UTILITY METERING TO ELECTRIC UTILITY GRID UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) (N) LOAD CENTER (INSIDE GARAGE) ROOF ACCESS POINT TRANSITION BOX ROOF ACCESS POINT (E) SERVICE POINT AND UTILITY METERING TO ELECTRIC UTILITY GRID UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) (N) LOAD CENTER (INSIDE GARAGE) ROOF ACCESS POINT ROOF ACCESS POINT (E) SERVICE POINT AND UTILITY METERING TO ELECTRIC UTILITY GRID UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) (N) LOAD CENTER (INSIDE GARAGE) ROOF ACCESS POINT TRANSITION BOX TRANSITION BOX TRANSITION BOX TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 C A L I C E N S E # 8 9 0 8 9 5 ® PVA-1 SHEET RE V D E S C R I P T I O N D A T E D B R E V I S I O N S PL A N 1 ( 2 7 6 2 ) E L E V A T I O N A & B CH A N G E D T H E M O D U L E T Y P E 3 / 2 / 2 3 G G 03/30/2023 ARRAYS MUST BE ORIENTATED BETWEEN 105° - 300° AZIMUTH PER APPROVED ENERGY REPORT LEGENDS: (3') WIDE ACCESS PATH (PITCHED ROOF) (4') WIDE ACCESS PATH (FLAT ROOF) PLAN TYPE OPTION DESCRIPTION 01 02 03 ----------------------------------- ----------------------------------- ----------------------------------- 04 05 ----------------------------------- ----------------------------------- PLAN 1X (2762) - ELEVATION A - S-TILE NOTE : - ROOFTOP PENETRATIONS AND/OR CONSTRUCTIONS NOT PERTAINING TO SOLAR INSTALLATION SHALL NOT BE LOCATED UNDER ARRAY. - FIRE ACCESS POINTS SHALL NOT BE LOCATED OVER DOORS AND WINDOWS OR BE OTHERWISE OBSTRUCTED BY ATTIC VENT, PLUMBING VENT, MECHANICAL VENT. BASE SQUARE FOOTAGE: 2762 SQ. FT. SLD REFERENCE PVE-1.1 SUNPOWER 132 CELLS AC MODULES MODEL NO.NOMINAL POWER (Pnom) 405W SYSTEM SIZE Q.PEAK DUO BLK ML-G10+ (405) QUANTITY: 16 6.48 kW SLD REFERENCE PVE-1.1 LAYOUT 1 LAYOUT 2BACK FRONT OF HOUSE : 285° - 120°RIGHT FRONT OF HOUSE : 195° - 30° FRONT OF HOUSE (FOH)FRONT OF HOUSE (FOH) ROOF ACCESS POINT (E) SERVICE POINT AND UTILITY METERING TO ELECTRIC UTILITY GRID UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) (N) LOAD CENTER (INSIDE GARAGE) ROOF ACCESS POINT TRANSITION BOX ROOF ACCESS POINT (E) SERVICE POINT AND UTILITY METERING TO ELECTRIC UTILITY GRID UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) (N) LOAD CENTER (INSIDE GARAGE) ROOF ACCESS POINT TRANSITION BOX E LECT R I C A L E22659 Exp. 03-31-23R EGISTERE D P R O F ESSIONAL E N G I N EER S TATE OF CA L I F O R NIA CHI F UNG L E UN G SO L A R M A S T E R P L A N P E R M I T P A C K A G E PO I N T H A P P Y TR A C T / P A R C E L # : 3 1 3 4 8 WI L L I A M S H O M E S 21 0 8 0 C E N T R E P O I N T E P A R K W A Y LA Q U I N T A , C A L I F O R N I A 9 2 2 5 3 SA N T A C L A R I T A , C A 9 1 3 5 0 DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID C003130 D-0125405 2023-03-02 GELLIE GREGANDA TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 C A L I C E N S E # 8 9 0 8 9 5 ® SHEET RE V D E S C R I P T I O N D A T E D B R E V I S I O N S PVA-2 PL A N 1 X ( 2 7 6 2 ) E L E V A T I O N A CH A N G E D T H E M O D U L E T Y P E 3 / 2 / 2 3 G G 03/30/2023 ARRAYS MUST BE ORIENTATED BETWEEN 105° - 300° AZIMUTH PER APPROVED ENERGY REPORT LEGENDS: (3') WIDE ACCESS PATH (PITCHED ROOF) (4') WIDE ACCESS PATH (FLAT ROOF) PLAN TYPE OPTION DESCRIPTION 01 02 03 ----------------------------------- ----------------------------------- ----------------------------------- 04 05 ----------------------------------- ----------------------------------- PLAN 2 (3213) - ELEVATION A - S-TILE NOTE : - ROOFTOP PENETRATIONS AND/OR CONSTRUCTIONS NOT PERTAINING TO SOLAR INSTALLATION SHALL NOT BE LOCATED UNDER ARRAY. - FIRE ACCESS POINTS SHALL NOT BE LOCATED OVER DOORS AND WINDOWS OR BE OTHERWISE OBSTRUCTED BY ATTIC VENT, PLUMBING VENT, MECHANICAL VENT. BASE SQUARE FOOTAGE: 3213 SQ. FT. SLD REFERENCE PVE-1.1 SUNPOWER 132 CELLS AC MODULES MODEL NO.NOMINAL POWER (Pnom) 405W SYSTEM SIZE Q.PEAK DUO BLK ML-G10+ (405) QUANTITY: 16 6.48 kW SLD REFERENCE PVE-1.1 SLD REFERENCE PVE-1.2 LAYOUT 1 LAYOUT 2 LAYOUT 3 PLAN 2 (3213) - ELEVATION B - S-TILE SLD REFERENCE PVE-1.1 SLD REFERENCE PVE-1.1 LAYOUT 1 LAYOUT 2 LEFT FRONT OF HOUSE : 15° - 210° LEFT FRONT OF HOUSE : 15° - 210° RIGHT FRONT OF HOUSE : 195° - 30°FRONT & BACK RIGHT FRONT OF HOUSE : 195° - 30° FRONT OF HOUSE (FOH)FRONT OF HOUSE (FOH)FRONT OF HOUSE (FOH) FRONT OF HOUSE (FOH)FRONT OF HOUSE (FOH) (E) SERVICE POINT AND UTILITY METERING TO ELECTRIC UTILITY GRID UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) (N) LOAD CENTER (INSIDE GARAGE) (E) SERVICE POINT AND UTILITY METERING TO ELECTRIC UTILITY GRID UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) (N) LOAD CENTER (INSIDE GARAGE) ROOF ACCESS POINT ROOF ACCESS POINT TRANSITION BOX ROOF ACCESS POINT ROOF ACCESS POINT TRANSITION BOX (E) SERVICE POINT AND UTILITY METERING TO ELECTRIC UTILITY GRID UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) (N) LOAD CENTER (INSIDE GARAGE) ROOF ACCESS POINT ROOF ACCESS POINT TRANSITION BOX (E) SERVICE POINT AND UTILITY METERING TO ELECTRIC UTILITY GRID UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) (N) LOAD CENTER (INSIDE GARAGE) ROOF ACCESS POINT ROOF ACCESS POINT TRANSITION BOX (E) SERVICE POINT AND UTILITY METERING TO ELECTRIC UTILITY GRID UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) (N) LOAD CENTER (INSIDE GARAGE) ROOF ACCESS POINT ROOF ACCESS POINT TRANSITION BOX(TYP.) E LECT R I C A L E22659 Exp. 03-31-23R EGISTERE D P R O F ESSIONAL E N G I N EER S TATE OF CA L I F O R NIA CHI F UNG L E UN G SO L A R M A S T E R P L A N P E R M I T P A C K A G E PO I N T H A P P Y TR A C T / P A R C E L # : 3 1 3 4 8 WI L L I A M S H O M E S 21 0 8 0 C E N T R E P O I N T E P A R K W A Y LA Q U I N T A , C A L I F O R N I A 9 2 2 5 3 SA N T A C L A R I T A , C A 9 1 3 5 0 DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID C003130 D-0125405 2023-03-02 GELLIE GREGANDA TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 C A L I C E N S E # 8 9 0 8 9 5 ® SHEET RE V D E S C R I P T I O N D A T E D B R E V I S I O N S PVA-3 PL A N 2 ( 3 2 1 3 ) E L E V A T I O N A & B CH A N G E D T H E M O D U L E T Y P E 3 / 2 / 2 3 G G 03/30/2023 ARRAYS MUST BE ORIENTATED BETWEEN 105° - 300° AZIMUTH PER APPROVED ENERGY REPORT LEGENDS: (3') WIDE ACCESS PATH (PITCHED ROOF) (4') WIDE ACCESS PATH (FLAT ROOF) PLAN TYPE OPTION DESCRIPTION 01 02 03 ----------------------------------- ----------------------------------- ----------------------------------- 04 05 ----------------------------------- ----------------------------------- PLAN 2X (3055)- ELEVATION B - S-TILE NOTE : - ROOFTOP PENETRATIONS AND/OR CONSTRUCTIONS NOT PERTAINING TO SOLAR INSTALLATION SHALL NOT BE LOCATED UNDER ARRAY. - FIRE ACCESS POINTS SHALL NOT BE LOCATED OVER DOORS AND WINDOWS OR BE OTHERWISE OBSTRUCTED BY ATTIC VENT, PLUMBING VENT, MECHANICAL VENT. BASE SQUARE FOOTAGE: 3,055 SQ. FT. SLD REFERENCE PVE-1.1 SUNPOWER 132 CELLS AC MODULES MODEL NO.NOMINAL POWER (Pnom) 405W SYSTEM SIZE Q.PEAK DUO BLK ML-G10+ (405) QUANTITY: 16 6.48 kW SLD REFERENCE PVE-1.1 SLD REFERENCE PVE-1.2 LAYOUT 1 LAYOUT 2 LAYOUT 3 LAYOUT 4LEFTFRONT OF HOUSE : 15° - 210°RIGHT FRONT OF HOUSE : 195° - 30°FRONT OF HOUSE : 285° - 30°BACK & RIGHT FRONT OF HOUSE (FOH)FRONT OF HOUSE (FOH)FRONT OF HOUSE (FOH) (E) SERVICE POINT AND UTILITY METERING TO ELECTRIC UTILITY GRID UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) (N) LOAD CENTER (INSIDE GARAGE) ROOF ACCESS POINT ROOF ACCESS POINT (E) SERVICE POINT AND UTILITY METERING TO ELECTRIC UTILITY GRID UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) (N) LOAD CENTER (INSIDE GARAGE) ROOF ACCESS POINT ROOF ACCESS POINT (E) SERVICE POINT AND UTILITY METERING TO ELECTRIC UTILITY GRID UTILITY AC DISCONNECT SWITCH (OUTSIDE GARAGE WITHIN SIGHT FROM THE MAIN SERVICE PANEL) (N) LOAD CENTER (INSIDE GARAGE) TRANSITION BOX(TYP.) ROOF ACCESS POINT ROOF ACCESS POINT TRANSITION BOX TRANSITION BOX E LECT R I C A L E22659 Exp. 03-31-23R EGISTERE D P R O F ESSIONAL E N G I N EER S TATE OF CA L I F O R NIA CHI F UNG L E UN G SO L A R M A S T E R P L A N P E R M I T P A C K A G E PO I N T H A P P Y TR A C T / P A R C E L # : 3 1 3 4 8 WI L L I A M S H O M E S 21 0 8 0 C E N T R E P O I N T E P A R K W A Y LA Q U I N T A , C A L I F O R N I A 9 2 2 5 3 SA N T A C L A R I T A , C A 9 1 3 5 0 DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID C003130 D-0125405 2023-03-02 GELLIE GREGANDA TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 C A L I C E N S E # 8 9 0 8 9 5 ® SHEET RE V D E S C R I P T I O N D A T E D B R E V I S I O N S PVA-4 PL A N 2 X ( 3 0 5 5 ) E L E V A T I O N B CH A N G E D T H E M O D U L E T Y P E 3 / 2 / 2 3 G G 03/30/2023 ARRAYS MUST BE ORIENTATED BETWEEN 105° - 300° AZIMUTH PER APPROVED ENERGY REPORT PO I N T H A P P Y TR A C T / P A R C E L # : 3 1 3 4 8 WI L L I A M S H O M E S 21 0 8 0 C E N T R E P O I N T E P A R K W A Y LA Q U I N T A , C A L I F O R N I A 9 2 2 5 3 SA N T A C L A R I T A , C A 9 1 3 5 0 DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID C003130 D-0125405 2023-03-02 GELLIE GREGANDA TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 C A L I C E N S E # 8 9 0 8 9 5 ® SHEET RE V D E S C R I P T I O N D A T E D B R E V I S I O N S PVS-1 03/30/2023 FIGURE A: SINGLE LINE DIAGRAM - 6.48 KWDC UTILITY BIDIRECTIONAL METER (NOT CENTER-FED)INCOMING SOURCE FEED H MCB (E)MAIN SERVICE PANEL 200A, 120/240V, 1PH, 3W GND EXISTING GND TO HOUSE LOADS BREAKERS SHALL BE INSTALLED OPPOSITE END OF THE MAIN BREAKER 200A, 2P 40A,2P GND 3 NOTE: FOR SOLAR PHOTOVOLTAIC ONLY. NO ADDITIONAL LOADS TO BE APPLIED (N)LOAD CENTER 100A OR EQUIVALENT, 120/240V, 1PH 20A, 2P 20A, 2P TAG 1 2 3 4 5 SOURCE CIRCUIT TRANSITION BOX (N) LOAD CENTER PV PRODUCTION METER SEPARATE AC DISCONNECT DESCRIPTION SOLAR AC MODULE / BRANCH 3 4 (N) LOAD CENTER PV PRODUCTION METER ELECTRICAL NOTES 1. ALL SEAL TIGHT FLEXIBLE METAL CONDUIT (OR EQUIVALENT) TO BE BONDED TO GROUND AT COUPLINGS ON BOTH ENDS. 2. CONDUIT ENTRY/CONNECTION TO ELECTRICAL ENCLOSURES SHALL BE SUITABLE FOR GROUNDING AND SHALL BE SEALED AGAINST ENVIRONMENT, SUCH AS WATER, INSECTS AND RODENTS. CONDUIT SHALL NOT ENTER FROM TOP OF ELECTRICAL EQUIPMENT IN OUTDOOR LOCATIONS WITHOUT SITE-SPECIFIC APPROVAL FROM SUNPOWER. IF GRANTED APPROVAL FOR TOP ENTRY, ONLY RIGID CONDUIT WITH MEYERS HUBS TO BE USED. 3. PROPER LISTING EXPECTED FOR CONDITIONS OF USE ON ALL LUGS, FITTINGS, CRIMPS, ETC. 4. ALL CONDUIT BEND RADII TO CONFORM TO THE CEC MINIMUM BEND RADII REQUIREMENTS. 5. MINIMUM CLEARANCE SHALL BE MAINTAINED PER CEC FOR ALL NEW EQUIPMENTS TO BE INSTALLED. 6. EXISTING GROUNDING ELECTRODE SYSTEM MUST MEET CEC AND LOCAL UTILITY REQUIREMENTS. 7. COPPER CONDUCTORS SHALL BE USED UNLESS SPECIFIED. 8. TYPE NM CABLE OR EQUIVALENT CONDUCTORS ARE ALLOWED FOR INTERNAL AND ATTIC RUNS AND SHALL BE INSTALLED MEETING CEC REQUIREMENTS. 9. AC WIRING SHALL UPSIZE IF VOLTAGE DROP EXCEEDS 2%. 10. UN CONDUCTORS IN EXISTING CONDUIT WHEN AVAILABLE PROVIDED IT HAS NO OTHER CONDUCTORS RUNNING THROUGH IT. 11. IF MAIN SERVICE PANEL IS TO BE UPGRADED, IT WILL BE PERMITTED AND INSTALLED BY A THIRD PARTY. 12. CONDUIT SIZE BASED ON 2 BENDS MAXIMUM. ANY ADDITIONAL BENDS MAY REQUIRE UPSIZE. 13. THE DESIGN SPECIFIES THE MINIMUM REQUIRED WIRE SIZE. 14. WIRE GAUGE MAY BE UPSIZE TO ACCOMMODATE ADDITIONAL LENGTH OF THE WIRE DUE TO FIELD OBSERVED CHANGES IN THE LENGTH OF BRANCH WIRE TO LIMIT VOLTAGE DROP 15. PV BREAKER ACTS AS MEANS OF DISCONNECT WHEN AC DISCONNECT IS NOT REQUIRED. NOTE : x SUNPOWER 15A MONITORING BREAKER CAN BE RELOCATED TO OTHER LOAD CENTER OR SUB-PANEL WITHIN THE HOUSE FOR CONSTRUCTION FEASIBILITY. x BELOW ARE OPTIONAL OFFERINGS AND SHALL ONLY BE INSTALLED IF THE HOMEOWNER SIGNS A SPECIFIC CONTRACT WITH SUNPOWER. x SUNPOWER MONITORING SYSTEM x AS DC POWER IS INTERNAL TO THE MODULE, GROUNDING ELECTRODE CONDUCTOR (GEC) FOR THE MODULE OR ARRAY IS NOT REQUIRED. 1 2 CONDUCTOR / CONDUIT SCHEDULE DESCRIPTION & CONDUCTOR TYPE CONDUCTOR SIZE(AWG) 2 1 SUNPOWER PROVIDED AC MODULES EXTENSION CABLE, LISTED AS AN ASSEMBLY NUMBER OF CONDUCTORS CONDUIT/ CABLE TYPE CONDUIT SIZE (WHEN NEEDED) #12 TYPE-ER, PER BRANCH CIRCUIT --WITH EGCA B TAG EATON DG221URB OR EQUIVALENT LOCATED OUTSIDE WITH VISIBLE KNIFE BLADES 5 NM CABLE OR EQ INSTALLED IN WALL CAVITY --EGC BARE CU CU-NM-B 3 1 2 GND C C UTILITY-LOCKABLE SAFETY SWITCH 30A, 240VAC #8 #10 OPTIONAL ETHERNET CONNECTION TO DSL/CABLE MODEM CAT5e CURRENT TRANSFORMERS (100A) INSTALLED ON THE CUSTOMER SIDE OF THE PANEL 1#14 NM CABLE OR EQ INSTALLED IN WALL CAVITY #22 NMFC CU-NM-B AWG TWISTED PAIR EGC BARE CU 3 INSTALLED IN WALL CAVITY 1/2" -- PRODUCTION CURRENT TRANSFORMERS (100A) SUNPOWER MONITORING PVS6 E #14 3 D E E D #6 15A, 2P ATTIC ROOFTOP MICROINVERTER 2 A DC AC DC AC 1 SUNPOWER MODULES AC MODULE EXTENSION CABLE NM CABLE OR EQ INSTALLED IN WALL CAVITY --EGC BARE CU CU-NM-B B 8 AC MODULESBRANCH CIRCUIT #2 8 AC MODULESBRANCH CIRCUIT #1 Q.PEAK DUO BLK ML-G10+ (405) #10 #10 IQ7HS-66-M-US (240) E LECT R I C A L E22659 Exp. 03-31-23R EGISTERE D P R O F ESSIONAL E N G I N EER S TATE OF CA L I F O R NIA CHI F UNG L E UN G PO I N T H A P P Y TR A C T / P A R C E L # : 3 1 3 4 8 WI L L I A M S H O M E S 21 0 8 0 C E N T R E P O I N T E P A R K W A Y LA Q U I N T A , C A L I F O R N I A 9 2 2 5 3 SA N T A C L A R I T A , C A 9 1 3 5 0 DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID C003130 D-0125405 2023-03-02 GELLIE GREGANDA TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 C A L I C E N S E # 8 9 0 8 9 5 ® EL E C T R I C A L S I N G L E L I N E D I A G R A M & S P E C I F I C A T I O N SHEET RE V D E S C R I P T I O N D A T E D B R E V I S I O N S PVE-1.1 1 TR A N S I T I O N T O 4 0 5 H A N W H A Q - C E L L 3 / 2 / 2 3 G G 03/30/2023 FIGURE A: SINGLE LINE DIAGRAM - 6.48 KWDC UTILITY BIDIRECTIONAL METER (NOT CENTER-FED)INCOMING SOURCE FEED H MCB (E)MAIN SERVICE PANEL 200A, 120/240V, 1PH, 3W GND EXISTING GND TO HOUSE LOADS BREAKERS SHALL BE INSTALLED OPPOSITE END OF THE MAIN BREAKER 200A, 2P 40A,2P GND 3 NOTE: FOR SOLAR PHOTOVOLTAIC ONLY. NO ADDITIONAL LOADS TO BE APPLIED (N)LOAD CENTER 100A OR EQUIVALENT, 120/240V, 1PH 20A, 2P 20A, 2P TAG 1 2 3 4 5 SOURCE CIRCUIT TRANSITION BOX (N) LOAD CENTER PV PRODUCTION METER SEPARATE AC DISCONNECT DESCRIPTION SOLAR AC MODULE / BRANCH 3 4 (N) LOAD CENTER PV PRODUCTION METER ELECTRICAL NOTES 1. ALL SEAL TIGHT FLEXIBLE METAL CONDUIT (OR EQUIVALENT) TO BE BONDED TO GROUND AT COUPLINGS ON BOTH ENDS. 2. CONDUIT ENTRY/CONNECTION TO ELECTRICAL ENCLOSURES SHALL BE SUITABLE FOR GROUNDING AND SHALL BE SEALED AGAINST ENVIRONMENT, SUCH AS WATER, INSECTS AND RODENTS. CONDUIT SHALL NOT ENTER FROM TOP OF ELECTRICAL EQUIPMENT IN OUTDOOR LOCATIONS WITHOUT SITE-SPECIFIC APPROVAL FROM SUNPOWER. IF GRANTED APPROVAL FOR TOP ENTRY, ONLY RIGID CONDUIT WITH MEYERS HUBS TO BE USED. 3. PROPER LISTING EXPECTED FOR CONDITIONS OF USE ON ALL LUGS, FITTINGS, CRIMPS, ETC. 4. ALL CONDUIT BEND RADII TO CONFORM TO THE CEC MINIMUM BEND RADII REQUIREMENTS. 5. MINIMUM CLEARANCE SHALL BE MAINTAINED PER CEC FOR ALL NEW EQUIPMENTS TO BE INSTALLED. 6. EXISTING GROUNDING ELECTRODE SYSTEM MUST MEET CEC AND LOCAL UTILITY REQUIREMENTS. 7. COPPER CONDUCTORS SHALL BE USED UNLESS SPECIFIED. 8. TYPE NM CABLE OR EQUIVALENT CONDUCTORS ARE ALLOWED FOR INTERNAL AND ATTIC RUNS AND SHALL BE INSTALLED MEETING CEC REQUIREMENTS. 9. AC WIRING SHALL UPSIZE IF VOLTAGE DROP EXCEEDS 2%. 10. UN CONDUCTORS IN EXISTING CONDUIT WHEN AVAILABLE PROVIDED IT HAS NO OTHER CONDUCTORS RUNNING THROUGH IT. 11. IF MAIN SERVICE PANEL IS TO BE UPGRADED, IT WILL BE PERMITTED AND INSTALLED BY A THIRD PARTY. 12. CONDUIT SIZE BASED ON 2 BENDS MAXIMUM. ANY ADDITIONAL BENDS MAY REQUIRE UPSIZE. 13. THE DESIGN SPECIFIES THE MINIMUM REQUIRED WIRE SIZE. 14. WIRE GAUGE MAY BE UPSIZE TO ACCOMMODATE ADDITIONAL LENGTH OF THE WIRE DUE TO FIELD OBSERVED CHANGES IN THE LENGTH OF BRANCH WIRE TO LIMIT VOLTAGE DROP 15. PV BREAKER ACTS AS MEANS OF DISCONNECT WHEN AC DISCONNECT IS NOT REQUIRED. NOTE : x SUNPOWER 15A MONITORING BREAKER CAN BE RELOCATED TO OTHER LOAD CENTER OR SUB-PANEL WITHIN THE HOUSE FOR CONSTRUCTION FEASIBILITY. x BELOW ARE OPTIONAL OFFERINGS AND SHALL ONLY BE INSTALLED IF THE HOMEOWNER SIGNS A SPECIFIC CONTRACT WITH SUNPOWER. x SUNPOWER MONITORING SYSTEM x AS DC POWER IS INTERNAL TO THE MODULE, GROUNDING ELECTRODE CONDUCTOR (GEC) FOR THE MODULE OR ARRAY IS NOT REQUIRED. 1 2 CONDUCTOR / CONDUIT SCHEDULE DESCRIPTION & CONDUCTOR TYPE CONDUCTOR SIZE(AWG) 2 1 SUNPOWER PROVIDED AC MODULES EXTENSION CABLE, LISTED AS AN ASSEMBLY NUMBER OF CONDUCTORS CONDUIT/ CABLE TYPE CONDUIT SIZE (WHEN NEEDED) #12 TYPE-ER, PER BRANCH CIRCUIT --WITH EGCA B TAG EATON DG221URB OR EQUIVALENT LOCATED OUTSIDE WITH VISIBLE KNIFE BLADES 5 NM CABLE OR EQ INSTALLED IN WALL CAVITY --EGC BARE CU CU-NM-B 3 1 2 GND C C UTILITY-LOCKABLE SAFETY SWITCH 30A, 240VAC #8 #10 OPTIONAL ETHERNET CONNECTION TO DSL/CABLE MODEM CAT5e CURRENT TRANSFORMERS (100A) INSTALLED ON THE CUSTOMER SIDE OF THE PANEL 1#14 NM CABLE OR EQ INSTALLED IN WALL CAVITY #22 NMFC CU-NM-B AWG TWISTED PAIR EGC BARE CU 3 INSTALLED IN WALL CAVITY 1/2" -- PRODUCTION CURRENT TRANSFORMERS (100A) SUNPOWER MONITORING PVS6 E #14 3 D E E D #6 15A, 2P 2 A DC AC DC AC 1 SUNPOWER MODULES AC MODULE EXTENSION CABLE NM CABLE OR EQ INSTALLED IN WALL CAVITY --EGC BARE CU CU-NM-B B 7 AC MODULESBRANCH CIRCUIT #2 9 AC MODULESBRANCH CIRCUIT #1 Q.PEAK DUO BLK ML-G10+ (405) #10 #10 IQ7HS-66-M-US (240) ATTIC ROOFTOP MICROINVERTER E LECT R I C A L E22659 Exp. 03-31-23R EGISTERE D P R O F ESSIONAL E N G I N EER S TATE OF CA L I F O R NIA CHI F UNG L E UN G PO I N T H A P P Y TR A C T / P A R C E L # : 3 1 3 4 8 WI L L I A M S H O M E S 21 0 8 0 C E N T R E P O I N T E P A R K W A Y LA Q U I N T A , C A L I F O R N I A 9 2 2 5 3 SA N T A C L A R I T A , C A 9 1 3 5 0 DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID C003130 D-0125405 2023-03-02 GELLIE GREGANDA TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 C A L I C E N S E # 8 9 0 8 9 5 ® EL E C T R I C A L S I N G L E L I N E D I A G R A M & S P E C I F I C A T I O N SHEET RE V D E S C R I P T I O N D A T E D B R E V I S I O N S PVE-1.2 1 TR A N S I T I O N T O 4 0 5 H A N W H A Q - C E L L 3 / 2 / 2 3 G G 03/30/2023 FIGURE 2: WIRING ROOF PENETRATION CROSS SECTION FIGURE 1: ELECTRICAL SIGNAGES/STICKERS WARNING POWER SOURCE OUTPUT CONNECTION DO NOT RELOCATE THIS OVERCURRENT DEVICE x x x TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUTDOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM x x x E LECT R I C A L E22659 Exp. 03-31-23R EGISTERE D P R O F ESSIONAL E N G I N EER S TATE OF CA L I F O R NIA CHI F UNG L E UN G PO I N T H A P P Y TR A C T / P A R C E L # : 3 1 3 4 8 WI L L I A M S H O M E S 21 0 8 0 C E N T R E P O I N T E P A R K W A Y LA Q U I N T A , C A L I F O R N I A 9 2 2 5 3 SA N T A C L A R I T A , C A 9 1 3 5 0 DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID C003130 D-0125405 2023-03-02 GELLIE GREGANDA TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 C A L I C E N S E # 8 9 0 8 9 5 ® x x x PHOTOVOLTAIC SYSTEM AC DISCONNECT RATED AC OUTPUT CURRENT: NOMINAL OPERATING AC VOLTAGE: AMPS VOLTS AMPS VOLTS PHOTOVOLTAIC POINT OF INTERCONNECTION WARNING: ELECTIC SHOCK HAZARD. DO NOT TOUCH TERMINALS. TERMINALS ON BOTH THE LINE AND LOAD SIDE MAY BE ENERGIZED IN THE OPEN POSITION. FOR SERVICE DE-ENERGIZE BOTH SOURCE AND MAIN BREAKER PV POWER SOURCE MAXIMUM RATED AC OUTPUT CURRENT: MAXIMUM OPERATING AC VOLTAGE: 25.60 240 25.60 240 6.48 kW 6.48 kW PHOTOVOLTAIC SYSTEM COMBINER PANEL: DO NOT ADD LOADS x AC SOLAR DISCONNECT x SHEET RE V D E S C R I P T I O N D A T E D B R E V I S I O N S EL E C T R I C A L D E T A I L S DRIVEWAY PVE-2 TYPICAL DIRECTORY PLACARD NOTE: CUSTOMIZED PLACARD WILL BE PROVIDED FOR EACH LOT(UNIT) N MAIN SERVICEPANEL LOAD CENTER PHOTOVOLTAICAC DISCONNECT PHOTOVOLTAICARRAY ON ROOF POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN: CAUTION: 1 TR A N S I T I O N T O 4 0 5 H A N W H A Q - C E L L 3 / 2 / 2 3 G G 03/30/2023 CURRENT TRANSFORMER SPECIFICATION SHEET PVS6 DATASHEET 1 PVS6 DATASHEET 2 PVS6 INSTALLATION INSTRUCTIONS 2PVS6 INSTALLATION INSTRUCTIONS 1 Q-CABLE DATA SHEET 1/2 Q-CABLE DATA SHEET 2/2ENPHASE DATA SHEET 1/2 ENPHASE DATA SHEET 2/2 INVISIMOUNT DATA SHEET 1/2 INVISIMOUNT DATA SHEET 2/2 CONDUCTOR AND OCP SIZING TABLE PV MODULE SPECIFICATION SHEET 1/2 PV MODULE SPECIFICATION SHEET 2/2CERTIFICATE OF COMPLIANCE CLASS A FIRE RATING LISTING PG 1/3 CLASS A FIRE RATING LISTING PG 2/3 CLASS A FIRE RATING LISTING PG 3/3 PO I N T H A P P Y TR A C T / P A R C E L # : 3 1 3 4 8 WI L L I A M S H O M E S 21 0 8 0 C E N T R E P O I N T E P A R K W A Y LA Q U I N T A , C A L I F O R N I A 9 2 2 5 3 SA N T A C L A R I T A , C A 9 1 3 5 0 DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID C003130 D-0125405 2023-03-02 GELLIE GREGANDA TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 C A L I C E N S E # 8 9 0 8 9 5 ® E LECT R I C A L E22659 Exp. 03-31-23R EGISTERE D P R O F ESSIONAL E N G I N E ER S TATEOF CA L I F O R NIA CHI F UNG L E UN G SHEET RE V D E S C R I P T I O N D A T E D B R E V I S I O N S EL E C T R I C A L D A T A & S P E C I F I C A T I O N S PVE-3 1 TR A N S I T I O N T O 4 0 5 H A N W H A Q - C E L L 3 / 2 / 2 3 G G AC DISCONNECT DATA SHEET TECHNICAL DATA SHEET 6.0" STANCHIONRAIL-MOUNTED JUNCTION BOX 1/2 RAIL-MOUNTED JUNCTION BOX 2/2UNIVERSAL INVISIMOUNT INSTALLATION GUIDE PO I N T H A P P Y TR A C T / P A R C E L # : 3 1 3 4 8 WI L L I A M S H O M E S 21 0 8 0 C E N T R E P O I N T E P A R K W A Y LA Q U I N T A , C A L I F O R N I A 9 2 2 5 3 SA N T A C L A R I T A , C A 9 1 3 5 0 DRAWN BY PROJECT NO. DATE DRAWN COMMUNITY ID C003130 D-0125405 2023-03-02 GELLIE GREGANDA TH I S D O C U M E N T C O N T A I N S P R O P R I E T A R Y I N F O R M A T I O N . R E P R O D U C T I O N , DI S C L O S U R E , O R U S E W I T H O U T S P E C I F I C W R I T T E N A U T H O R I Z A T I O N O F T H E SU N P O W E R C O R P O R A T I O N I S S T R I C T L Y F O R B I D D E N . C O R P O R A T I O N , S Y S T E M S 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 (5 1 0 ) 5 4 0 - 0 5 5 0 C A L I C E N S E # 8 9 0 8 9 5 ® E LECT R I C A L E22659 Exp. 03-31-23R EGISTERE D P R O F ESSIONAL E N G I N E ER S TATEOF CA L I F O R NIA CHI F UNG L E UN G SHEET RE V D E S C R I P T I O N D A T E D B R E V I S I O N S EL E C T R I C A L D A T A & S P E C I F I C A T I O N S PVE-4 1 TR A N S I T I O N T O 4 0 5 H A N W H A Q - C E L L 3 / 2 / 2 3 G G