FSS2023-0032BUILDING PERMIT DESIGN & DEVELOPMENT DEPARTMENT 78-495 CALLE TAMPICO LA QUINTA, CALIFORNIA 92253 PHONE (760) 777-7125 WWW.LAQUINTACA.GOV APPLIED DATE: 01/10/2023 ISSUED DATE: 05/03/2023 Permit Type: Permit Number: Property Address: APN: Legal Description Property Zoning: Valuation: Fire Sprinkler System - Residential - 13D 53325 HUMBOLDT BLVD FSS2023-0032 767700013 $25,000.00 Owner:J D MECHANICAL FIRE INC 82579 FLEMING WAY SUITE D, INDIO, CA 92201 Applicant:J D MECHANICAL FIRE INC 436160 MADISON STREET, INDIO, CA 92201 Contractor:J D MECHANICAL FIRE INC / 1020141 436160 MADISON STREET, INDIO, CA 92201 Declaration / Acknowledgement PRIOR TO THE ISSUANCE OF THIS PERMIT FOR CONSTRUCTION, ALTERATION, IMPROVEMENT, DEMOLITION, OR REPAIR THE OWNER, APPLICANT AND/OR CONTRACTOR UNDER PENALTY OF PERJURY HAVE AFFIRMED WHEN APPLICABLE, THROUGH THE SUBMITTAL OF FORMS OR BY OTHER ELECTRONIC MEANS, THE FOLLOWING: LICENSED CONTRACTOR OR OWNER-BUILDER DECLARATION (1 or 2) 1) They are licensed under provisions of Chapter 9 (commencing with Section 7000) of Division 3 of the Business and Professions Code, and the referenced License is in full force and effect, or; 2) That they are exempt from the Contractors’ State License Law for the reason(s) indicated by either (2)(a) and/or (2)(b), or (2)(c) where he or she is exempt from licensure by a valid exemption. [Section 7031.5, Business and Professions Code: Any city or county that requires a permit to construct, alter, improve, demolish, or repair any structure, prior to its issuance, also requires the applicant for the permit to file a signed statement that he or she is licensed pursuant to the provisions of the Contractors’ State License Law (Chapter (commencing with Section 7000) of Division 3 of the Business and Professions Code] Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($500).) a) As owner of the property, or my employees with wages as their sole compensation, will do all of or portions of the work, and the structure is not intended or offered for sale (Section 7044, Business and Professions Code: The Contractors’ State License Law does not apply to an owner of property who, through employees’ or personal effort, builds or improves the property, provided that the improvements are not intended or offered for sale. If, however, the building or improvement is sold within one year of completion, the Owner-Builder will have the burden of proving that it was not built or improved for the purpose of sale.). b) As owner of the property, will be exclusively contracting with licensed c) Are exempt from licensure under the Contractors’ State License Law. As an Owner-Builder, they acknowledge that, except for their personal residence in which they must have resided in for at least one year prior to completion of the improvements covered by this permit, they cannot legally sell a structure built as an owner-builder if it has not been constructed in its entirety by licensed contractors. It is understood that a copy of the applicable law, Section 7044 of the Business and Professions Code, is available upon request when this application was submitted at the following Web site: http://www.leginfo.ca.gov/calaw.html. DECLARATION REGARDING CONSTRUCTION LENDING AGENCY (If applicable) A construction lender will be used for completion of the improvements covered by this permit and the name and information of which is on file for public inspection during the regular business hours of the public entity. Failure of the applicant to indicate the construction lender on the application does not relieve that person of the requirement to give the construction lender preliminary notice from that duty. WORKERS’ COMPENSATION DECLARATION (1, 2 or 3) WARNING: FAILURE TO SECURE WORKERS’ COMPENSATION COVERAGE IS UNLAWFUL, AND SHALL SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND CIVIL FINES UP TO ONE HUNDRED THOUSAND DOLLARS ($100,000), IN ADDITION TO THE COST OF COMPENSATION, DAMAGES AS PROVIDED FOR IN SECTION 3706 OF THE LABOR CODE, INTEREST, AND ATTORNEY’S FEES. 1) Has and will maintain a certificate of consent to self-insure for workers’ compensation, issued by the Director of Industrial Relations as provided for by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. 2) Has and will maintain workers’ compensation insurance, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. 3) Certifies that, in the performance of the work for which this permit is issued, shall not employ any person in any manner so as to become subject to the workers’ compensation laws of California, and agree that, if should become subject to the workers’ compensation provisions of Section 3700 of the Labor Code, shall forthwith comply with those provisions. NOTICE TO APPLICANT (1, 2 and 3) 1) Each person upon whose behalf this application was made, each person at whose request and for whose benefit work is being performed under or pursuant to any permit issued as a result of this application, the owner, and the applicant, each agrees to, and shall defend, indemnify and hold harmless the City of La Quinta, its officers, agents, and employees for any act or omission related to the work being performed under or following issuance of this permit. 2) Any permit issued as a result of this application becomes null and void if work is not commenced within 360 days from date of issuance of such permit, or if cessation of work for 180 days will subject permit to cancellation. On or after January 1, 2019, every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 12 months after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 12 months after the time the work is commenced. 3) Certified that they read the application and state that the information provided is correct. Agree to comply with all city and county ordinances and state laws relating to building construction, and hereby authorize representatives of this city to enter upon the above-mentioned property for inspection purposes. IMPORTANT: An Application for Permit was made to the Building Official, subject to the conditions and restrictions set forth at the time of application, which is now hereby an Issued Permit. If any part of the information being supplied on this permit is inaccurate or untrue, please contact the City of La Quinta at (760) 777-7125 immediately for correction. Printed: 11/20/25 9:39 am Page 1 of 3 Permit Type: Permit Number: Property Address: Fire Sprinkler System - Residential - 13D FSS2023-0032 53325 HUMBOLDT BLVD BUILDING PERMIT INSTALLATION OF FIRE SPRINKLERS IN CUSTOM HOME *** Use of Permit Construction Details Valuation Details Type Group Sq Ft Value Financial Information Fee AmountFee Amount PaidInvoice No. INV-00002535 $183.00 Fire - Failed or Additional Field Inspections $183.00 $4.58 Credit Card Convenience Fee $4.58 $187.58 $187.58 Total for Invoice INV-00002535 PERMIT-FSS2023-0032 $11.00 RECORDS MANAGEMENT FEE $11.00 $8.00 TECHNOLOGY ENHANCEMENT FEE $8.00 $250.00 FIRE SPRINKLER SYSTEMS - SINGLE FAMILY DETACHED PC $250.00 $250.00 FIRE SPRINKLER SYSTEMS - SINGLE FAMILY DETACHED $250.00 $175.00 FIRE FAILED OR ADDITIONAL FIELD INSPECTIONS (EXCES $175.00 $694.00 $694.00 Total for Invoice PERMIT-FSS2023-0032 Grand Total for Permit $881.58 $881.58 Workflow / Inspections Workflow Step / Action Name Action Type Start Date End Date Inspections v.1 01/10/2023 0:00 OVERHEAD ROUGH PIPING v.2 Inspection OVERHEAD ROUGH PIPING v.1 Inspection OVERHEAD HYRO v.1 Inspection Fire Inspections v.1 11/16/2023 14:37 04/18/2024 13:32 Fire Sprinkler Final 13D v.1 Inspection 11/16/2023 14:37 11/17/2023 15:04 Fire Sprinkler Final 13D v.2 Inspection 04/18/2024 13:31 04/18/2024 13:32 Construction or work for which a permit is required shall be subject to inspection by the building official and such construction or work shall remain visible and able to be accessed for inspection purposes until approved. Approval as a result of an inspection shall not be construed to be an approval of a violation of the provisions of the applicable code and other ordinances of the jurisdiction. Inspections presuming to give authority to violate or cancel the provisions of the applicable code and other ordinances of the jurisdiction shall not be valid. It shall be the duty of the owner or the owner's authorized agent to cause the work to remain visible and able to be accessed for inspection purposes. Neither the building official nor the jurisdiction shall be liable for expense entailed in the removal or replacement of any material required to allow inspection. It shall be the duty of the holder of the building permit or their duly authorized agent to notify the building official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspections of such work that are required by this code. Inspections Printed: 11/20/25 9:39 am Page 2 of 3 Permit Type: Permit Number: Property Address: Fire Sprinkler System - Residential - 13D FSS2023-0032 53325 HUMBOLDT BLVD BUILDING PERMIT A building or structure shall not be used or occupied in whole or in part, and a change of occupancy of a building or structure or portion thereof shall not be made, until the building official has issued a certificate of occupancy therefor as provided herein. Issuance of a certificate of occupancy shall not be construed as an approval of a violation of the provisions of the applicable code and other ordinances of the jurisdiction. Certificates presuming to give authority to violate or cancel the provisions of this code or other ordinances of the jurisdiction shall not be valid. Certificate of Occupancy A person shall not make connections from a utility, a source of energy, fuel, or power, or a water system or sewer system to any building or system that is regulated by the applicable code and other ordinances of the jurisdiction for which a permit is required, until approved by the building official. Service Utilities Printed: 11/20/25 9:39 am Page 3 of 3 DESIGN & DEVELOPMENT DEPARTMENT 78-495 Calle Tampico La Quinta, California 92253 (760) 777-7125 / FAX (760) 777-7011  NEW  TENANT IMPROVEMENT PERMIT NO. PROJECT INFORMATION (Please Print) Project Name: Sign: Site Address: Print: City & Zip: Project Description: • Pursuant to a Cooperative Agreement to Provide Fire Services, the Riverside County Fire Department serves as the City’s fire department, and the County designee serves as the City’s fire chief. Applicant recognizes this contracted arrangement and shall comply with County Fire Department directions. APPLICANT/CONTACT INFORMATION CONTRACTOR INFORMATION:  Same as Applicant info Applicant Name: Contractor #: Contact Person: Contact Person: Mailing Address: Mailing Address: City & Zip: City & Zip: Phone Number: Fax : Phone Number: Fax : Email: Email:  ------------  HOURLY@161/HR  $670  HOURLY@161/HR  $791  $992  $418  $1234  HOURLY@161/HR $418  HOURLY@161/HR ------------  HOURLY@161/HR $418  $498  HOURLY@161/HR  $579  HOURLY@161/HR  $176  $901  $590  HOURLY@161/HR  $659  $418  $579  $1062  $418  $740  HOURLY@161/HR  HOURLY@161/HR  HOURLY@161/HR  HOURLY@161/HR OFFICE OF THE FIRE MARSHAL – LA QUINTA 78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074 • www.rvcfire.org January 26, 2023 JD Mechanical Re: Residential Fire Sprinkler Plan Review – Moonbeam Dreams FSS2023-0032 / 53325 Humboldt Blvd The sprinkler plans you submitted for the above referenced project have been reviewed by Riverside County Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions. Permanently marked identification signs shall be attached to all control valves. The following inspections/tests are required to be witnessed by Office of the Fire Marshal Staff: (a) Overhead Rough and Hydro static test: All piping shall be visible and pumped at normal operating pressure. *No jacketed electrical and data wiring shall be in contact with, nor have the potential to contact CPVC piping once insulation is installed. (b) Final inspection The Fire Department approved plans and conditions letter must be at the job site. Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131. All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal staff at (760)777-7074. Rebecca Winscott - Fire Safety Specialist 78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131 RIVERSIDE COUNTY FIRE PROTECTION PLANNING RECORD OF INSPECTIONS / PERMIT CARD THIS CARD IS TO REMAIN ON SITE AT ALL TIMES. INSTALLING CONTRACTOR MUST BE PRESENT FOR ALL INSPECTIONS. SEE NOTES ON REVERSE SIDE. JOB ADDRESS: 53325 Humboldt BLVD PERMIT#: FSS2023-0032 DATE ISSUED: 1-26-23 DESCRIPTION: Moonbeam Dreams CONTRACTOR: JD Mechanical HYDRANT SYSTEM DATE INITIALS SPECIAL SUPPRESSION DATE INITIALS Thrust block pre-pour Door fan test UG rough piping Abort test UG hydro Mechanical shutdown Flush Detector test Final E F Deluge/pre-action SPRINKLER U.G. Final E F Thrust block pre-pour UST/AST TANK UG rough piping Installation UG hydro Removal Flush Emergency shut off Final E F Primary piping FIRE SPRINKLER Secondary piping Weld inspection Dispensers & shear valves Overhead rough piping Final E F Overhead hydro MISC. INSPECTIONS UG flush / OK to connect Spray booths Main drain/inspectors’ test Hood/duct extinguishing High pile storage High pile rack storage In-rack sprinklers H.P. vents/access/corridors Hose racks Tract access/hydrant verification Final E F Access & Address verification HOOD EXTINGUISHING OTHER CONST. PERMIT Detection system Function test Gas/electrical shut-off Nozzle model/placement Fire alarm connection Final E F SPRAY BOOTHS FIRE CODE PERMIT(S) Installation Air flow test Mechanical interlock Extinguishing system Fire alarm connection Final E F FIRE ALARM KNOX SYSTEM Rough-wire inspection Building Knox box Function test Gate access Knox box/padlock Duct detectors/velocity BUILDING INSPECTIONS 24 hr. battery test T/I final Sprinkler monitoring Shell final Final E F Final for occupancy FINAL INSPECTION DATE: INSPECTORS SIGNATURE: **WHEN CALLING FOR AN INSPECTION PLEASE HAVE PERMIT NUMBER READY. SEE NOTES ON REVERSE SIDE** 78495 CALLE TAMPICO, LA QUINTA, CA 92253 / 760-777-7000 / INSPECTION HOTLINE: 760-777-7131 INSPECTION NOTES 1. Sway bracing and hangers will be inspected at the time of rough piping inspection. 2. All required hydrostatic pressure tests shall maintain 200 psi for a 2-hour duration. (EX: Residential Fire Sprinkler Systems) 3. Fire sprinkler system remodels: if indicated on plans or this card, a hydrostatic pressure test shall be required. 4. All underground joints and thrusts blocks shall be exposed and readily visible during the hydrostatic test. 5. Contractor shall supply all testing equipment, access and operating instructions at time of test. 6. All systems shall be inspected, tested, and approved by a Fire Inspector before any work is started that may cause the affected system to be covered or hidden. POLICIES ON FIELD INSPECTIONS A. INSPECTION REQUESTS: Inspections are made subject to availability. Please have the permit number available when scheduling inspections. For City of La Quinta inspections call: (760) 777-7131. B. APPROVED PLANS: Shall be kept on the job site at all times that work is in progress. Work shall NOT commence without approved plans. C. INSPECTION REQUESTS: As required by the California Fire Code, the appropriate installing contractor shall be required to schedule the necessary inspections and be present on site for inspections. D. RE-INSPECTIONS: Will be charged against a permit when an inspection has failed, is not ready, the responsible party not on site or where previously noted corrections have not been completed. E. COMMODITIES: Unless otherwise noted on approved plans or letter of conditions, no commodities shall be entered into the structure until clearance has been granted by the Fire Dept and Building Official. F. OCCUPANCY: Buildings shall NOT be occupied by persons other than construction workers until a Final Fire Clearance has been granted by the Fire Dept and a Certificate for Occupancy has been issued by the Building Official. INSPECTION NOTES: THIS CARD IS REQURIED TO BE POSTED AT THE CONSTRUCTION SITE. THIS CARD AND APPROVED PLANS MUST BE AVAILABLE AT THE CONSTRUCTION SITE FOR ALL INSPECTIONS. THIS PERMIT SHALL EXPIRE AND BECOME NULL AND VOID IF THE WORK AUTHORIZED IS NOT COMMENCED WITHIN 180 DAYS OR IF THE WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS OR MORE. THIS PERMIT IS FOR FIRE DEPARTMENT APPROVAL ONLY AND DOES NOT INTEND TO ABROGATE MORE RESTRICTIVE REQUIREMENTS OF OTHER AGENCIES HAVING RESPONSIBILITY. GENERAL DESCRIPTION The Model RC-RES Residential Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder type. They are decorative and fast responding. The Cover Plate Assembly hides the Deflector, Heat Responsive Element etc., which is concealed above the ceiling. The cover plate has a flat profile, and its diameter is extremely small (2-5/8 inch, 68mm). The push-on and/or thread-on, thread-off design of the concealed cover plate assembly allows for easy installation of the cover plate. Therefore, the Model RC-RES should be your first choice when aesthetics is the major consideration for ultimate appeal and unbeatable performance is desired. The Model RC-RES is designed for residential occupancies and is perfect for use in homes, hotels and other living quarters. The Model RC-RES is to be used in wet pipe residential sprinkler systems for One- and Two- Family Dwellings and Manufactured Homes per NFPA 13D; wet pipe residential sprinkler systems for Residential Occupancies up to and Including Four Stories in Height per NFPA 13R; or, wet pipe sprinkler systems for the residential portions of any occupancies per NFPA 13. The Model RC-RES has a 4.9 (70.6 LPM/bar1/2) K-factor that meets the required residential flow rates with minimal residual pressure, which allows for smaller pipe sizes and water supply requirements. For extended installation flexibility, the Model RC-RES provides 1/2 inch (12.8mm) vertical adjustment. This adjustment in installation decreases the need for precise cutting of the pipe that drops to the sprinkler and allows for a perfect fit with a range of pipe lengths. The heat sensitivity and water distribution design of Model RC-RES allows for an increased chance of residents to escape or evacuate in case of a fire. However, residential fire sprinkler systems are not a substitute for fire safety awareness or fire safety construction required by building codes. “Lead Free” is defined in the Reduction of Lead in Drinking Water Act (S.3874) endorsed by AWWA’s Water Utility Council, and California Assembly Bill #1953 as having less than or equal to a weighted average of 0.25% lead in wetted surface of pipes, plumbing fittings and fixtures. Approvals: Sprinkler Identification Number (SIN): Maximum Working Pressure: Discharge Coefficient (Nominal K-Factor): Temperature Rating: Color Code (Sprinkler) Color Code (Cover Plate) Vertical Adjustment: Cover Plate Finishes: Standard Finishes- Custom Finishes- Please see chart on Page 8 for more detail. Physical Characteristics: In case of fire, the solder component that holds together the Cover Plate and the Retainer melts. Then the Cover Plate is released at once. As a result, the Deflector drops down to the intended position. Two Heat Collectors are exposed to fire, and when sufficient heat from the fire is reached, internal components of the sprinkler fall apart. This leads to the water flow to be distributed on the affected fire area. (Ref. Figure 2) DESIGN CRITERIA The herein stated rules for use and installation of Model RC-RES are provided by the manufacturer and must be strictly implemented for safe and full results. Locations of sprinklers must follow the obstruction rules of NFPA 13, 13D and 13R for Residential Sprinklers. The Model RC-RES must only be utilized in WET PIPE sprinkler systems. Refer to NFPA 13D, 13R or 13 for the requirements relating to the prevention of possible activation of the Heat Responsive Element of Model RC-RES, due to the exposure of a heat source other than an actual fire. Available Sprinkler Temperature Ratings Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating Maximum Ambient Ceiling Temperature Temperature Rating of the Cover Plate Assembly Ordinary 162°F (72°C) 100°F (38°C) 140°F (60°C) Intermediate 175°F (79°C 150°F (66°C) 140°F (60°C) 1) Intermediate 175°F (79°C) 150°F (66°C) 162°F (72°C) 1) Maximum ambient temperature for the Cover Plate Assembly is 100°F (38°C). Model RC-RES sprinklers should not be installed where they may be subjected to a corrosive environment including the following: Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride. Exposure to this environment may result in sprinklers operating under Non-Fire conditions or Not Operating when exposed to an actual fire. Sprinkler systems should be constructed in compliance with the applicable standards and the requirements for copper piping when copper piping is used in the sprinkler system. (Reference standards NFPA 13, ASTM B813, B828, and CDA (Copper Development Association) – Solder Joint) All residual flux must be removed from the interior and exterior of the copper piping by thoroughly flushing before installation of the Sprinkler Heads. Otherwise, residues of flux may cause corrosion and/or leakage in the sprinkler system. The minimum required sprinkler flow rates for systems designed to NFPA 13D or 13R are given in TABLE A as a function of temperature rating and the maximum allowable coverage area. The sprinkler flow rate is the minimum required discharge from the most hydraulically demanding sprinkler from each of the total number of “design sprinklers” as specified in NFPA 13D or 13R. For systems designed to NFPA 13, the number of designed sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following: The flow rates given in TABLE A for NFPA 13D and 13R as a function of temperature rating and maximum allowable coverage area. A minimum discharge of 0.1GPM/sq.ft. [4.07LPM/sq.m] over the “design area” comprised of the four most hydraulically demanding sprinklers for the actual coverage area being protected by the four sprinklers. For systems with ceiling types smooth flat horizontal, or beamed, or sloped, in accordance with NFPA 13D, 13R or 13 as applicable. Ordinary Temperature Rating 162°F (72°C) Intermediate Temperature Rating 175°F (79°C) Maximum Coverage Area(a) Ft. × Ft. (m ×m) Maximum Spacing Ft. (m) Flow(b) GPM (LPM) Pressure(b) PSI (bar) Flow(b) GPM (LPM) Pressure(b) PSI (bar) Deflector to Ceiling Installation Type Minimum Spacing Ft. (m) 12×12 (3.7×3.7) 12 (3.7) 13 (49.2) 7.0 (0.48) 13 (49.2) 7.0 (0.48) 14×14 (4.3×4.3) 14 (4.3) 13 (49.2) 7.0 (0.48) 13 (49.2) 7.0 (0.48) 15×15 (4.6×4.6) 15 (4.6) 13 (49.2) 7.0 (0.48) 13 (49.2) 7.0 (0.48) 16×16 (4.9×4.9) 16 (4.9) 13 (49.2) 7.0 (0.48) 14 (53.0) 8.2 (0.57) 18×18 (5.5×5.5) 18 (5.5) 17 (64.3) 12.0 (0.83) 18 (68.1) 13.5 (0.93) 20×20 (6.1×6.1) 20 (6.1) 21 (79.5) 18.4 (1.27) Smooth Ceilings 3/8 to 7/8 Inches. Beamed Ceilings per NFPA 13D, 13R or 13 Installed in beam 3/8 to 7/8 inches below bottom of beam. Concealed 8 (2.4) (a) For coverage area dimensions less than the above mentioned, it needs to use the minimum required flow for the Next Higher Coverage Area listed. (b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-Factor. Refer to Hydraulic Design Criteria Section for details. The minimum spacing between sprinklers is 8 feet (2.4m). The maximum spacing between sprinklers cannot go beyond the coverage area calculated by using the specific hydraulic factors. (Ref. TABLE A) The Model RC-RES must be installed in accordance with the following instructions: The installation requirements for the sprinkler are as follows: to be installed only in the pendent position with the waterway perpendicular to the ceiling. Install the sprinkler fitting so that the distance from the face of the fitting to the mounting surface will be nominally 2 inches (50.8mm) as shown in Figure 3. With pipe thread sealant applied to the threads, hand tighten the sprinkler into the sprinkler fitting. Then tighten it with the Socket NR-H or Ratchet (3/8” drive) & Socket NR-H Combination (Ref. Figure 4). The teeth of the Socket must fit perfectly with the grooves on the Sprinkler for proper installation (Ref. Figure 4). If desired, the Protective Cap may also be used to locate the center of the clearance hole by gently pushing the ceiling material against the center point of the Protective Cap. Before the installation of the ceiling, the sprinkler installation can be started with a 2-3/8 inch (60mm) diameter clearance hole (Ref. Figure 3). Use the “Vertical Adjustment” indicator on the Protective Cap to check for proper installation height (Ref. Figure 3). Use the Cap Remover RC to remove the Protective Cap (Ref. Figure 5), and then push or screw a Cover Plate Assembly on the Cup of the Sprinkler by hand until its flange just has contact with the ceiling (Ref. Figure 6 and Figure 7). Stop tightening the Cover Plate Assembly once the flange has contact with the ceiling. If the ceiling has been lifted from its normal position in the process of tightening the Cover Plate Assembly, readjust the cover plate assembly as necessary. If the flange of the Cover Plate Assembly cannot contact the ceiling sufficiently, readjust the sprinkler fitting as necessary. When properly installed, there is a nominal 1/16 inch (1.6mm) air gap between the lip of the Cover Plate and the ceiling, as shown in Figure 6. The following instructions must be implemented for the maintenance and service of the Model RC-RES. When placing an order, please contact a local distributor with the following information (Model Name, Temperature Rating and Finish). Model: RC-RES (SIN: SS8464, Residential Flat Concealed Sprinkler, Pendent, K4.9, Temperature: 162°F (72°C) or 175°F (79°C) ) 2-5/8 inch (68mm) or 3-1/4 inch (83mm) or 2-5/8 inch square (68mm), Order Separately from Sprinkler Please refer to the chart below for available sizes, temperature, and finishes. Standard Finishes Custom Finishes 2-5/8" Round, 140°F - - - - - - 3-1/4" Round, 140°F 2-5/8" Square, 140°F - - - - - - - 2-5/8" Round, 162°F - - - - - - - 3-1/4" Round, 162°F - - - - - - - Socket NR-H For use with a 3/8” drive ratchet (not included) Socket NR-H Plastic For use with a 1/2” drive ratchet (not included) Cap Remover RC Fire Department Notes A. The installation of new fire sprinkler systems or modifications to existing systems shall comply with the following: NFPA 13D 2016 CBC 2019 CFC 2019 Local Municipal Codes Requirements of the AHJ All Manufacture Installation Guidelines Note: When conflict arrises between existing codes and standards, the most stringent shall apply. B. The Fire Department Shall require the following inspections and tests. 1. Overhead installation and hydrostatic test, ( prior to cover ). a. Normal opperating pressure when no FDC is installed. b. 200psi when FDC is required. c. Two hour minimum. 2. Final sprinkler and underground, ( prior to building final ). a. All inspections shall be scheduled by the contractor of record. b. Inspections shall be scheduled 24 hours in advance. GENERAL NOTES 1.General: All materials and devices shall conform to 2016 NFPA 13D standards. Installation shall conform to all applcable State and Local Codes. 2.Scope of Work: Install a new Residential Fire Protection System. 3.Piping: All overhead pipe and fittings shall be CPVC unless otherwise noted. 4.Design: NFPA 13D 2016 Edition and CFC Chapter 80 Standards. 5.System Demand @ Source. Two Sprinklers Flowing (16X16 Spacing): 31 gpm @ ______psi ( AREA ) 6.Water Supply Data: Water is supplied from public water main in street. Static Pressure: Information Source: 7.Sprinkler Head Spacing and Installation Requirements:Sprinklers shall not be located Closer than 8'-0" apart where there is no intervening obstruction. Sprinklers near potential obstruction shall be located per manufactures instructions. 8.Piping Supports: Piping shall be supported and restrained in conformance with local plumbing codes and CPVC manufactures instructions . Eachpipe section that supplies a drop to a sprinkler shall be secured no more than 12" from the drop to prevent laterial and vertical movement. 9.Pipe lenghts are approximate for hydraulic calculation and plan review purposes only. 10.The owner shall furnish sufficant heat in all areas to prevent freezingof pipe. 11.Waterflow Switch and Alarm: By Others a. A dedicated electrical circuit with a circuit breaker lock shall be provided for waterflow horn/strobes. b. An approved audible sprinkler waterflow alarm shall be visible from the street. The device shall be listed for outdoor use. An approved sign shall be placed at or near the device stating, SPRINKLER FIRE ALARM - WHEN ALARM SOUNDS CALL 911 c. An approved audible sprinkler waterflow alarm module shall be conected to the smoke detectors to alert occupants shall be provided. NFPA 13D REFERANCE NOTES 1. NFPA 13D, Section 8.3.2 Sprinklers shall not be required in bathrooms of 55 sq. ft. and less. 2. NFPA 13D, Section 8.3.3 Sprinklers shall not be required in clothes closets, linen closets, and pantries that meet all of the following conditions. (1) The area of the space does not exceed 24 sq. ft. (2) The walls and ceilings are surfaced with noncombustible or limited-combustible material as defined in NFPA 220. 3.NFPA 13D Section 8.3.4 Sprinklers shall not be required in garages, open attached porches, carports, and similar structures. Note that CFC 2016 Chapter 80 Referance Standards requires attached garages, attached porches, carports, and similar structures shall be sprinklered if there is occupied living space above. 4. NFPA 13D Section 8.2.5.6 Shadow Areas Shadow areas shall be permitted in the protection area of a sprinkler as long as the cumulative dry areas do not exceed 15 sq. ft. (1.4 sq. m.) per sprinkler. jd@jdmechanical.co Scale Project number Date Drawn by Checked by 82 5 7 9 F l e m i n g W a y S u i t e D In d i o C a . 9 2 2 0 1 (7 6 0 ) 7 7 5 -62 2 0 C-16 L i c e n s e # 1 0 2 0 1 4 1 ME C H A N I C A L IN C As indicated 11 / 1 5 / 2 0 2 2 8 : 5 4 : 0 1 A M FP-1 Site Plan Project Number LOT 61B 06-30-22 JA JD MO O N B E A M D R E A M S TH E M A D I S O N C L U B LO T 6 1 B La Q u i n t a , C a . 9 2 2 5 3 WH INSPECTOR TEST DETAIL 5' 1" Ball Valve Access Panel (By Others) Exterior Wall of Building Inspector Test to Terminate in a Smooth Bore Corrosion Resistant Orfice With a Flow Equivalent to One Sprinkler NOTE: Access Panel Shall have sign Indicating Inspector Test CPVC HANGERS NO SCALE TOLCO FIG. 24 DOUBLE-FASTENER SIDE-MOUNT HANGER (OR EQUAL) SELF-DRILLING HEX HEAD SCREW TOLCO FIG. 23 DOUBLE-FASTENER STRAP TYPE HANGER (OR EQUAL) TOLCO FIG. 28M OFFSET HANGER (OR EQUAL) TOLCO FIG. 22 SINGLE-FASTENER STRAP-TYPE HANGER (OR EQUAL) TOLCO FIG. 28 DOUBLE-FASTENER STAND-OFF HANGER (OR EQUAL) TOLCO FIG. 29 DOUBLE-FASTENER DOUBLE OFFSET HANGER (OR EQUAL) CPVC HANGER SPACING PIPE SIZE 11/4" 1" MAXIMUM SUPPORT SPACING 6'-6" 6'-0" 2"8'-0" 11/2"7'-0" www.cadmando.co.uk These blocks were brought to you by CADB locksFree.com.For all of your 2D & 3D CA D outsource requirements visit us: C A D M A N D O www.cadblocksfree.com COVER WITH HINGED LID FINISHED GRADE DISC-TYPE WATER METER PLUG VALVE(TYP.)UNION(TYP.) SPRINKLER PIPEINSULATION BOTTOM CORD OF ROOF TRUSS OR CEILING JOIST PIPE INSULATION DETAIL Water Supply Information Static Pressure: Residual Pressure: Residual Flow: Additional Hose Flow: 74.03 psi 68.85 psi 34 GPM 0 GPM IN S P E C T O R S T E S T 1" RISER NOTIFICATION DEVICE BY OTHERS 1 1/2" 4' -1" 1 1 / 2 " 30 ' - 0" 1" 2' -0"1" x 11' -2"1" x 2' -10"1" 2' -8" 1" 2' -8" 1" 11' -10" 1" 5' -2" 1" 4' -4" 1" 7' -5" 1" 10' -3" 1" 11' -5" 1" 6' -9" 1" 5' - 9" 1" 6' -6" 1" 0' -8" 1" 0' -8" 1" 1' -7" 1" 7' -0" 1" 7' -3" 1" 10' -0" 1" 3' -11" 1" 4' -10" 1" 14' -0" 1" 14' -0" 1" 5' -11" 1" 1' -7" 1" 12 ' - 0" 1" 9' - 6" 1" 7' - 9" 1" 10 ' - 9" 1" 12 ' - 0" 1" 1' -8" 1" 8' - 6" 1" 1' -8" 1" 1' -8" 1" 2' -11" 1" 8' - 6" 1" 5' - 10 " 1" 1' -5" 1" 4' - 3" 1" 3' - 0" 1" 11 ' - 0" 1" 1' -6" 1" 12 ' - 6" 1" 16' -0" 1" 16' -0" 1" 16' -0" 1" 4' -6" 1" 2' -8" 1" 6' - 0" 1" 2' - 1" 1" 12' -0" 1" 13' -7" 1" 13' -7" 1" 12' -0" 1" 3' - 11 " 1" 6' - 1" 1" 4' -6" 1" 4' -6" 1" 4' -6" 1" 8' -10" 1" 7' -4" 1" 10' -7" 1" 10' -7" 1" 8' - 9" 1" 1' -5" 1" 3' - 6" 1" 4' -4" 1" 4' -4" 1" 6' -2" 1" 1' -5" 1" 5' -4" 1" 16 ' - 0" 1" 6' -0" 1" 9' -3" 1" 3' - 6" 1" 12 ' - 0" 1" 13 ' - 6" 1" 11 ' - 0" 1" 6' -0" 1" 6' -0" 1" 6' -0" 1" 5' -9" 1" 6' - 0" 1" 9' - 3" 1" 0' -6" 1" 3' -2" 1" 2' -9" 1" 5' -9" 1" 6' -0"1" 4' -9" 1" 7' -9" 1" 10' -11" 1" 4' -4" 1" 2' -10" 1" 6' -8" 1" 2' -0" 1" 7' - 0" 1" 3' -11" 1" 9' -4" 1" 6' - 9" 1" 1' -2" 1" 3' -2" 1" 3' -0" 1" 7' - 5" 1" 1' -8" 1" 3' -11" 1" 5' - 3" 1" 6' - 6" 1" 10' -10" 1" 10' -4" 1" 10' -10" 1" 2' -7"1" 6' - 4" 1" 4' - 11 " 1" 5' - 2" 1" 13 ' - 1" 1" 1' -0" 1" 1' -6" 1" 1' -0" 1" 13 ' - 1" 1" 1' -0" 1" 1' -6" 1" 1' -0" 1" 13 ' - 2" 1" 1' -0" 1" 1' -5" 1" 1' -0"1" x 3' -0"1" x 3' -0"1" 2' -7" 1" 8' - 2" 1" 0' -10" 1" 6' -6" 1" 0' -9" 1" 0' -9" 1" 6' -6" 1" 1' -9" 1" 5' - 3" 1" 5' - 1" 1" 4' - 7" 1" 11' -3"1" x 3' -0"1" 4' -9" 1" 5' - 1" 1" 4' - 7"1" x 3' -0"1" 5' - 1" 1" 4' - 7" 1" 4' -8"1" x 3' -0"1" 7' -4" 1" 7' -8" 1" 3' -9" 1" 2' -0" 1" 11 ' - 2" 1" 0' -11" 1" 5' - 4" 1" 7' -1" 1" 16 ' - 0" 1" 0' -10" 1" 6' -0" 1" 8' - 5" 1" 6' -0" 1" 6' -0" 1" 6' -0" 1" 17' -10" 1" 9' -2" 1" 12' -0" 1" 16 ' - 0" 1" 5' -5" 1" 6' -0" 1" 8' - 5" 1" 6' -0" 1" 6' -0" 1" 3' -0" BUNK RM 10'-0" REC RM 10'-0" BED 2 10'-0" BATH 10'-0: BED 1 10'-0" BATH 10'-0" GUEST 1 LIVING 10'-0" COURTYARD GUEST 2 LIVING 10'-0" BED 1 10'-0" GARAGE 10'-0" GOLF CART 10'-0" LNDRY 10'-0" BED 3 10'-0" BATH 10'-0" OFFICE 10'-0" GOLF SIMULATOR 10'-0" KITCHEN 13'-0" GREAT ROOM 13'-0" EQ 10'-0" PAN 10'-0" BATH 10'-0" CL 10'-0" BED 2 10'-0"OWNER SUITE 10'-0" BATH 10'-0" HIS HER'sPOWDER STOR VERANDA PATIO STOR CL 1" 1' -5" 1" 6' - 0" 1" 1' -6" 1" 1' -2" Calc-2 Calc-1 Remote area number: Occupancy classification: Density: Area of application: Total water required (including hose streams): @ a required system pressure of: Fire Protection System Demand: No. of sprinklers calculated: Inside Hose Streams: Outside Hose Streams: Calc-2 R-3 2 0.05 Gpm/SqFt 512 Max SqFt 31.0023 GPM 35.8422 Psi 5 GPM 0 GPM BOR TOR DOM 7 6 1 4 2 3 Remote area number: Occupancy classification: Density: Area of application: Total water required (including hose streams): @ a required system pressure of: Fire Protection System Demand: No. of sprinklers calculated: Inside Hose Streams: Outside Hose Streams: Calc-1 R-3 2 0.05 Gpm/SqFt 512 sf 31.0023 GPM 39.5228 Psi 5 GPM 0 GPM 8 12 11 109 Fire Sprinkler Riser Detail TOR BOR Domestic Supply Check Flow Control 1" CPVC Flow Switch Note Wiring by Others 300psi Gage Sprinkler Box with Wrench & two Sprinkler Heads Each Type 1/2" Drain to Outside 1" 1" 1-1/2" PVC UG BY OTHERS Notification Device Wired by Others not to scale Module Must Connect to the Multi Station Smoke Alarm System and the Fire Sprinkler Flow Switch ( all wiring by others ) jd@jdmechanical.co Scale Project number Date Drawn by Checked by 82 5 7 9 F l e m i n g W a y S u i t e D In d i o C a . 9 2 2 0 1 (7 6 0 ) 7 7 5 -62 2 0 C-16 L i c e n s e # 1 0 2 0 1 4 1 ME C H A N I C A L IN C As indicated 11 / 1 5 / 2 0 2 2 8 : 5 4 : 5 7 A M FP-2 Piping Plan Project Number LOT 61B 06-30-22 JA JD MO O N B E A M D R E A M S TH E M A D I S O N C L U B LO T 6 1 B La Q u i n t a , C a . 9 2 2 5 3 1/8" = 1'-0"1 Piping Plan Sprinkler Schedule No. of Sprklrs Description SIN (Hydratec)K-Factor Orifice Size Temp 83 Senju1/2 Light Concealed Temperature -162 Finish - B Quick Response Model - Mirage SIN - SS8464 K Factor - 4.9 SS8464 4.9 1/2" 162 °F 10 Senju 1/2 Light Pendent Temperature -205 Finish - C Special Response Model - Micromatic SIN - SS8464 K Factor - 4.9 SS8464 4.9 1/2" 205 °F : 93 Total No. of Sprinklers: 93 WH BUNK RM 10'-0" REC RM 10'-0" BED 2 10'-0" BATH 10'-0: BED 1 10'-0" BATH 10'-0" GUEST 1 LIVING 10'-0" COURTYARD GUEST 2 LIVING 10'-0" BED 1 10'-0" GARAGE 10'-0" GOLF CART 10'-0" LNDRY 10'-0" BED 3 10'-0" BATH 10'-0" OFFICE 10'-0" GOLF SIMULATOR 10'-0" KITCHEN 13'-0" GREAT ROOM 13'-0" EQ 10'-0" PAN 10'-0" BATH 10'-0" CL 10'-0" BED 2 10'-0"OWNER SUITE 10'-0" BATH 10'-0" HIS HER'sPOWDER STOR VERANDA PATIO STOR CL 3' - 11"12' - 1"3' - 10" 5' - 6"14' - 11"15' - 1"5' - 6" 4' - 6 " 14 ' - 1 1 " 14 ' - 8 " 4' - 9 " 4' - 6 " 5' - 3 " 3' - 1"12' - 0"4' - 9" 3' - 8 " 15 ' - 1 1 " 3' - 0 " 5' - 1 0 " 11 ' - 2 " 5' - 0 " 5' - 1 " 5' - 0 " 3' - 0 " 3' - 0 " 2' - 4 " 11 ' - 1 1 " 2' - 3 " 0' - 1 1 " 5' - 2 " 2' - 7 " 10 ' - 9 " 4' - 6 " 7' - 11"7' - 1" 3' - 5"11' - 9"8' - 8"7' - 2" 14 ' - 0 " 14 ' - 0 " 14 ' - 0 " 6' - 3 " 4' - 5"16' - 0"4' - 2" 8' - 0"8' - 0" 3' - 1 0 " 3' - 1" 5' - 3"11' - 11"5' - 2" 7' - 3 " 7' - 3 " 7' - 9 " 7' - 9 " 4' - 0 " 10 ' - 0 " 6' - 0 " 1' - 6"13' - 8"1' - 11" 3' - 1"11' - 11"2' - 11" 3' - 5 " 13 ' - 9 " 12 ' - 1 " 8' - 3 " 3' - 0 " 4' - 0"12' - 1"3' - 5" 3' - 5 " 16 ' - 0 " 3' - 3 " 4' - 6"8' - 7"12' - 0"4' - 2" 7' - 7"7' - 6" 3' - 0"3' - 1" 2' - 1 0 " 2' - 8 " 6' - 1 " 5' - 0 " 3' - 6 " 3' - 6 " 4' - 0"4' - 0" 7' - 9"7' - 8"2' - 3"14' - 0"2' - 3" 4' - 8 " 12 ' - 1 " 11 ' - 9 " 3' - 0 " 7' - 9"15' - 11"7' - 9" 2' - 3"14' - 0"9' - 3" 6' - 9"4' - 8" 4' - 5 " 6' - 5 " 3' - 5 " 4' - 5 " 6' - 9"6' - 8" 7' - 4 " 14 ' - 5 " 5' - 9 " 3' - 0 " 16 ' - 0 " 3' - 0 " 1-1/2" PVC UNDERGROUND BY OTHERS 1 1/2" 4' -1" 1 1 / 2 " 30 ' - 0" 1 1/2" 70' -0" 1 1 / 2 " 8' - 8" 1" 2' -0"1" x 11' -2"1" x 2' -10"1" 9' - 6" 1" 16' -0" 1" 4' -6" 1" 2' -8" BED 1 10'-0" 1-1/2" WATER METER Supply Point WM 5 BOR TOR DOM jd@jdmechanical.co Scale Project number Date Drawn by Checked by 82 5 7 9 F l e m i n g W a y S u i t e D In d i o C a . 9 2 2 0 1 (7 6 0 ) 7 7 5 -62 2 0 C-16 L i c e n s e # 1 0 2 0 1 4 1 ME C H A N I C A L IN C 1/8" = 1'-0" 11 / 1 5 / 2 0 2 2 8 : 5 5 : 3 5 A M FP-3 RCP Project Number LOT 61B 06-30-22 JA JD MO O N B E A M D R E A M S TH E M A D I S O N C L U B LO T 6 1 B La Q u i n t a , C a . 9 2 2 5 3 1/8" = 1'-0"1 RCP Sprinkler Schedule No. of Sprklrs Description SIN (Hydratec)K-Factor Orifice Size Temp 83 Senju1/2 Light Concealed Temperature -162 Finish - B Quick Response Model - Mirage SIN - SS8464 K Factor - 4.9 SS8464 4.9 1/2" 162 °F 10 Senju 1/2 Light Pendent Temperature -205 Finish - C Special Response Model - Micromatic SIN - SS8464 K Factor - 4.9 SS8464 4.9 1/2" 205 °F : 93 Total No. of Sprinklers: 93 1/8" = 1'-0"2 UG JD Mechanical Fire 82579 Fleming Way Suite D Your Street Address 2 Indio, Ca. 92201 760-775-6220 Job Name : Moonbeam Dreams Drawing : Location : Remote Area : Contract : Data File : Moonbeam Dreams Area Calc-1.WXF Computer Programs by Hydratec Inc. Revision: 50.54.4 JD M e c h a n i c a l F i r e Pa g e 1 Mo o n b e a m D r e a m s Da t e 10203040 E 50 R 60 U 70 S 80 S 90 E 10 0 R 11 0 P 12 0 13 0 14 0 15 0 10 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 0 FL O W ( N ^ 1 . 8 5 ) Ci t y W a t e r S u p p l y : De m a n d : C1 C2 C1 - S t a t i c P r e s s u r e : 7 8 C2 - R e s i d u a l P r e s s u r e : 7 0 C2 - R e s i d u a l F l o w : 3 2 D1 - E l e v a t i o n : 5 . 7 1 3 D2 - S y s t e m F l o w : 3 1 . 0 0 2 D2 - S y s t e m P r e s s u r e : 3 9 . 5 2 3 Ho s e ( D e m a n d ) : _ _ _ _ _ _ _ D3 - S y s t e m D e m a n d : 3 1 . 0 0 2 Sa f e t y M a r g i n : 3 0 . 9 3 2 D1 D2 W a t e r S u p p l y C u r v e Co m p u t e r P r o g r a m s b y H y d r a t e c I n c . R e v i s i o n : 5 0 .5 4 . 4 JD M e c h a n i c a l F i r e Pa g e 2 Mo o n b e a m D r e a m s Da t e Fi t t i n g L e g e n d Ab b r e v . N a m e ½ ¾ 1 1 ¼ 1 ½ 2 2 ½ 3 3 ½ 4 5 6 8 1 0 1 2 1 4 1 6 1 8 2 0 2 4 N * C P V C 9 0 ' E l l H a r v e l - S p e a r s 7 7 8 9 1 1 1 2 1 3 0 0 0 0 0 0 0 0 0 0 0 0 O * C P V C T e e - B r a n c h 3 3 5 6 8 1 0 1 2 1 5 0 0 0 0 0 0 0 0 0 0 0 0 R * C P V C C o u p l i n g T e e - R u n 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0 Un i t s S u m m a r y Di a m e t e r U n i t s I n c h e s Le n g t h U n i t s F e e t Fl o w U n i t s U S G a l l o n s p e r M i n u t e Pr e s s u r e U n i t s P o u n d s p e r S q u a r e I n c h No t e : F i t t i n g L e g e n d p r o v i d e s e q u i v a l e n t p i p e l e n g t hs f o r f i t t i n g s t y p e s o f v a r i o u s d i a m e t e r s . Eq u i v a l e n t l e n g t h s s h o w n a r e s t a n d a r d f o r a c t u a l d i am e t e r s o f S c h e d 4 0 p i p e a n d C F a c t o r s of 1 2 0 e x c e p t a s n o t e d w i t h * . T h e f i t t i n g s m a r k e d w i t h a * s h o w e q u i v a l e n t l e n g t h s v a l u e s su p p l i e d b y m a n u f a c t u r e r s b a s e d o n s p e c i f i c p i p e d i am e t e r s a n d C F a c t o r s a n d t h e y r e q u i r e n o ad j u s t m e n t . A l l v a l u e s f o r f i t t i n g s n o t m a r k e d w i t h a * w i l l b e a d j u s t e d i n t h e c a l c u l a t i o n fo r C F a c t o r s o f o t h e r t h a n 1 2 0 a n d d i a m e t e r s o t h e r th a n S c h e d 4 0 p e r N F P A . Fi t t i n g s U s e d S u m m a r y Co m p u t e r P r o g r a m s b y H y d r a t e c I n c . R e v i s i o n : 5 0 .5 4 . 4 JD Mechanical Fire Page 3 Moonbeam Dreams Date SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure 5 78.0 70 32.0 70.455 31.0 39.523 NODE ANALYSIS Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes 8 10.19 4.9 7.04 13.0 0.05 256 9 11.0 7.05 10 11.0 7.14 11 11.0 12.05 3 11.0 16.89 4 11.0 21.11 TOR 11.0 27.13 DOM -0.16 33.31 5.0 BOR -3.0 36.04 5 -3.0 39.52 12 10.19 4.9 7.04 13.0 0.05 256 7 11.0 20.76 Flow Summary - NFPA Computer Programs by Hydratec Inc. Revision: 50.54.4 JD Mechanical Fire Page 4 Moonbeam Dreams Date Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe ******* Notes ****** Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf 8 10.19 4.90 13.00 1 N 7.0 3.810 150 7.040 to R 1.0 8.000 -0.351 9 11 13.0 1.101 11.810 0.0307 0.362 Vel = 4.38 9 11 0.0 1 3.000 150 7.051 to 0.0 10 11 13.0 1.101 3.000 0.0307 0.092 Vel = 4.38 10 11 13.00 1 4O 20.0 24.400 150 7.143 to 20.000 0.0 11 11 26.0 1.101 44.400 0.1106 4.910 Vel = 8.76 11 11 -13.73 1 3N 21.0 117.490 150 12.053 to 12R 12.0 58.000 0.0 3 11 12.27 1.101 5O 25.0 175.490 0.0275 4.833 Vel = 4.13 3 11 0.0 1 2O 10.0 124.210 150 16.886 to 12R 12.0 29.000 0.0 4 11 12.27 1.101 N 7.0 153.210 0.0275 4.219 Vel = 4.13 4 11 13.73 1 3R 3.0 39.470 150 21.105 to O 5.0 15.000 0.0 TOR 11 26.0 1.101 N 7.0 54.470 0.1106 6.023 Vel = 8.76 TOR 11 0.0 1 R 1.0 11.160 150 27.128 to 1.000 4.833 DOM -0.16 26.0 1.101 12.160 0.1106 1.345 Vel = 8.76 DOM -0.16 + 5.00 5.00 1 N 7.0 2.840 150 33.306 to 7.000 1.230 BOR -3 31.0 1.101 9.840 0.1530 1.506 Vel = 10.45 BOR -3 0.0 1.5 3N 27.0 112.510 150 36.042 to 27.000 0.0 5 -3 31.0 1.598 139.510 0.0250 3.481 Vel = 4.96 0.0 5 31.00 39.523 K Factor = 4.93 12 10.19 4.90 13.00 1 N 7.0 6.810 150 7.040 to R 1.0 8.000 -0.351 10 11 13.0 1.101 14.810 0.0307 0.454 Vel = 4.38 0.0 10 13.00 7.143 K Factor = 4.86 11 11 13.74 1 5N 35.0 171.440 150 12.053 to 15R 15.0 85.000 0.0 7 11 13.74 1.101 7O 35.0 256.440 0.0340 8.707 Vel = 4.63 7 11 0.0 1 O 5.0 5.170 150 20.760 to 5.000 0.0 4 11 13.74 1.101 10.170 0.0339 0.345 Vel = 4.63 0.0 4 13.74 21.105 K Factor = 2.99 Final Calculations : Hazen-Williams Computer Programs by Hydratec Inc. Revision: 50.54.4 JD Mechanical Fire 82579 Fleming Way Suite D Your Street Address 2 Indio, Ca. 92201 760-775-6220 Job Name : Moonbeam Dreams Drawing : Location : 53325 Humboldt Blvd Remote Area : Calc-2 Contract : Data File : Moonbeam Dreams Area Calc-2.WXF Computer Programs by Hydratec Inc. Revision: 50.54.4 JD Mechanical Fire Page 1 Moonbeam Dreams Date 10 20 30 40 E 50 R 60 U 70 S 80 S 90 E 100 R 110 P 120 130 140 150 10 20 30 40 50 60 70 80 90 FLOW ( N ^ 1.85 ) City Water Supply:Demand: C1 C2 C1 - Static Pressure : 78 C2 - Residual Pressure: 70 C2 - Residual Flow : 32 D1 - Elevation : 5.713 D2 - System Flow : 31.002 D2 - System Pressure : 35.842 Hose ( Demand ) : _______ D3 - System Demand : 31.002 Safety Margin : 34.613 D1 D2 Water Supply Curve Computer Programs by Hydratec Inc. Revision: 50.54.4 JD Mechanical Fire Page 2 Moonbeam Dreams Date Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24 N * CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 O * CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 R * CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used Summary Computer Programs by Hydratec Inc. Revision: 50.54.4 JD Mechanical Fire Page 3 Moonbeam Dreams Date SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure 5 78.0 70 32.0 70.455 31.0 35.842 NODE ANALYSIS Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes 1 10.19 4.9 7.04 13.0 0.05 256 2 11.0 7.14 3 11.0 10.02 4 11.0 17.42 TOR 11.0 23.45 DOM -0.16 29.63 5.0 BOR -3.0 32.36 5 -3.0 35.84 6 10.19 4.9 7.04 13.0 0.05 256 7 11.0 17.25 Flow Summary - NFPA Computer Programs by Hydratec Inc. Revision: 50.54.4 JD Mechanical Fire Page 4 Moonbeam Dreams Date Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe ******* Notes ****** Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf 1 10.19 4.90 13.00 1 R 1.0 6.810 150 7.040 to N 7.0 8.000 -0.351 2 11 13.0 1.101 14.810 0.0307 0.454 Vel = 4.38 2 11 13.00 1 2O 10.0 16.000 150 7.143 to 10.000 0.0 3 11 26.0 1.101 26.000 0.1106 2.875 Vel = 8.76 3 11 -9.37 1 2O 10.0 124.210 150 10.018 to 12R 12.0 29.000 0.0 4 11 16.63 1.101 N 7.0 153.210 0.0483 7.407 Vel = 5.60 4 11 9.37 1 3R 3.0 39.470 150 17.425 to O 5.0 15.000 0.0 TOR 11 26.0 1.101 N 7.0 54.470 0.1106 6.023 Vel = 8.76 TOR 11 0.0 1 R 1.0 11.160 150 23.448 to 1.000 4.833 DOM -0.16 26.0 1.101 12.160 0.1105 1.344 Vel = 8.76 DOM -0.16 + 5.00 5.00 1 N 7.0 2.840 150 29.625 to 7.000 1.230 BOR -3 31.0 1.101 9.840 0.1532 1.507 Vel = 10.45 BOR -3 0.0 1.5 3N 27.0 112.510 150 32.362 to 27.000 0.0 5 -3 31.0 1.598 139.510 0.0249 3.480 Vel = 4.96 0.0 5 31.00 35.842 K Factor = 5.18 6 10.19 4.90 13.00 1 N 7.0 6.810 150 7.040 to R 1.0 8.000 -0.351 2 11 13.0 1.101 14.810 0.0307 0.454 Vel = 4.38 0.0 2 13.00 7.143 K Factor = 4.86 3 11 9.38 1 27R 27.0 288.930 150 10.018 to 8N 56.0 143.000 0.0 7 11 9.38 1.101 12O 60.0 431.930 0.0168 7.236 Vel = 3.16 7 11 0.0 1 O 5.0 5.170 150 17.254 to 5.000 0.0 4 11 9.38 1.101 10.170 0.0168 0.171 Vel = 3.16 0.0 4 9.38 17.425 K Factor = 2.25 Final Calculations : Hazen-Williams Computer Programs by Hydratec Inc. Revision: 50.54.4 WH INSPECTOR TEST DETAIL 5' 1" Ball Valve Access Panel (By Others) Exterior Wall of Building Inspector Test to Terminate in a Smooth Bore Corrosion Resistant Orfice With a Flow Equivalent to One Sprinkler NOTE: Access Panel Shall have sign Indicating Inspector Test CPVC HANGERS NO SCALE TOLCO FIG. 24 DOUBLE-FASTENER SIDE-MOUNT HANGER (OR EQUAL) SELF-DRILLING HEX HEAD SCREW TOLCO FIG. 23 DOUBLE-FASTENER STRAP TYPE HANGER (OR EQUAL) TOLCO FIG. 28M OFFSET HANGER (OR EQUAL) TOLCO FIG. 22 SINGLE-FASTENER STRAP-TYPE HANGER (OR EQUAL) TOLCO FIG. 28 DOUBLE-FASTENER STAND-OFF HANGER (OR EQUAL) TOLCO FIG. 29 DOUBLE-FASTENER DOUBLE OFFSET HANGER (OR EQUAL) CPVC HANGER SPACING PIPE SIZE 11/4" 1" MAXIMUM SUPPORT SPACING 6'-6" 6'-0" 2"8'-0" 11/2"7'-0" www.cadmando.co.uk These blocks were brought to you by CADB locksFree.com.For all of your 2D & 3D CA D outsource requirements visit us: C A D M A N D O www.cadblocksfree.com COVER WITH HINGED LID FINISHED GRADE DISC-TYPE WATER METER PLUG VALVE(TYP.)UNION(TYP.) SPRINKLER PIPEINSULATION BOTTOM CORD OF ROOF TRUSS OR CEILING JOIST PIPE INSULATION DETAIL Water Supply Information Static Pressure: Residual Pressure: Residual Flow: Additional Hose Flow: 74.03 psi 68.85 psi 34 GPM 0 GPM IN S P E C T O R S T E S T 1" RISER NOTIFICATION DEVICE BY OTHERS 1 1/2" 4' -1" 1 1 / 2 " 30 ' - 0" 1" 2' -0"1" x 11' -2"1" x 2' -10"1" 2' -8" 1" 2' -8" 1" 11' -10" 1" 5' -2" 1" 4' -4" 1" 7' -5" 1" 10' -3" 1" 11' -5" 1" 6' -9" 1" 5' - 9" 1" 6' -6" 1" 0' -8" 1" 0' -8" 1" 1' -7" 1" 7' -0" 1" 7' -3" 1" 10' -0" 1" 3' -11" 1" 4' -10" 1" 14' -0" 1" 14' -0" 1" 5' -11" 1" 1' -7" 1" 12 ' - 0" 1" 9' - 6" 1" 7' - 9" 1" 10 ' - 9" 1" 12 ' - 0" 1" 1' -8" 1" 8' - 6" 1" 1' -8" 1" 1' -8" 1" 2' -11" 1" 8' - 6" 1" 5' - 10 " 1" 1' -5" 1" 4' - 3" 1" 3' - 0" 1" 11 ' - 0" 1" 1' -6" 1" 12 ' - 6" 1" 16' -0" 1" 16' -0" 1" 16' -0" 1" 4' -6" 1" 2' -8" 1" 6' - 0" 1" 2' - 1" 1" 12' -0" 1" 13' -7" 1" 13' -7" 1" 12' -0" 1" 3' - 11 " 1" 6' - 1" 1" 4' -6" 1" 4' -6" 1" 4' -6" 1" 8' -10" 1" 7' -4" 1" 10' -7" 1" 10' -7" 1" 8' - 9" 1" 1' -5" 1" 3' - 6" 1" 4' -4" 1" 4' -4" 1" 6' -2" 1" 1' -5" 1" 5' -4" 1" 16 ' - 0" 1" 6' -0" 1" 9' -3" 1" 3' - 6" 1" 12 ' - 0" 1" 13 ' - 6" 1" 11 ' - 0" 1" 6' -0" 1" 6' -0" 1" 6' -0" 1" 5' -9" 1" 6' - 0" 1" 9' - 3" 1" 0' -6" 1" 3' -2" 1" 2' -9" 1" 5' -9" 1" 6' -0"1" 4' -9" 1" 7' -9" 1" 10' -11" 1" 4' -4" 1" 2' -10" 1" 6' -8" 1" 2' -0" 1" 7' - 0" 1" 3' -11" 1" 9' -4" 1" 6' - 9" 1" 1' -2" 1" 3' -2" 1" 3' -0" 1" 7' - 5" 1" 1' -8" 1" 3' -11" 1" 5' - 3" 1" 6' - 6" 1" 10' -10" 1" 10' -4" 1" 10' -10" 1" 2' -7"1" 6' - 4" 1" 4' - 11 " 1" 5' - 2" 1" 13 ' - 1" 1" 1' -0" 1" 1' -6" 1" 1' -0" 1" 13 ' - 1" 1" 1' -0" 1" 1' -6" 1" 1' -0" 1" 13 ' - 2" 1" 1' -0" 1" 1' -5" 1" 1' -0"1" x 3' -0"1" x 3' -0"1" 2' -7" 1" 8' - 2" 1" 0' -10" 1" 6' -6" 1" 0' -9" 1" 0' -9" 1" 6' -6" 1" 1' -9" 1" 5' - 3" 1" 5' - 1" 1" 4' - 7" 1" 11' -3"1" x 3' -0"1" 4' -9" 1" 5' - 1" 1" 4' - 7"1" x 3' -0"1" 5' - 1" 1" 4' - 7" 1" 4' -8"1" x 3' -0"1" 7' -4" 1" 7' -8" 1" 3' -9" 1" 2' -0" 1" 11 ' - 2" 1" 0' -11" 1" 5' - 4" 1" 7' -1" 1" 16 ' - 0" 1" 0' -10" 1" 6' -0" 1" 8' - 5" 1" 6' -0" 1" 6' -0" 1" 6' -0" 1" 17' -10" 1" 9' -2" 1" 12' -0" 1" 16 ' - 0" 1" 5' -5" 1" 6' -0" 1" 8' - 5" 1" 6' -0" 1" 6' -0" 1" 3' -0" BUNK RM 10'-0" REC RM 10'-0" BED 2 10'-0" BATH 10'-0: BED 1 10'-0" BATH 10'-0" GUEST 1 LIVING 10'-0" COURTYARD GUEST 2 LIVING 10'-0" BED 1 10'-0" GARAGE 10'-0" GOLF CART 10'-0" LNDRY 10'-0" BED 3 10'-0" BATH 10'-0" OFFICE 10'-0" GOLF SIMULATOR 10'-0" KITCHEN 13'-0" GREAT ROOM 13'-0" EQ 10'-0" PAN 10'-0" BATH 10'-0" CL 10'-0" BED 2 10'-0"OWNER SUITE 10'-0" BATH 10'-0" HIS HER'sPOWDER STOR VERANDA PATIO STOR CL 1" 1' -5" 1" 6' - 0" 1" 1' -6" 1" 1' -2" Calc-2 Calc-1 Remote area number: Occupancy classification: Density: Area of application: Total water required (including hose streams): @ a required system pressure of: Fire Protection System Demand: No. of sprinklers calculated: Inside Hose Streams: Outside Hose Streams: Calc-2 R-3 2 0.05 Gpm/SqFt 512 Max SqFt 31.0023 GPM 35.8422 Psi 5 GPM 0 GPM BOR TOR DOM 7 6 1 4 2 3 Remote area number: Occupancy classification: Density: Area of application: Total water required (including hose streams): @ a required system pressure of: Fire Protection System Demand: No. of sprinklers calculated: Inside Hose Streams: Outside Hose Streams: Calc-1 R-3 2 0.05 Gpm/SqFt 512 sf 31.0023 GPM 39.5228 Psi 5 GPM 0 GPM 8 12 11 109 Fire Sprinkler Riser Detail TOR BOR Domestic Supply Check Flow Control 1" CPVC Flow Switch Note Wiring by Others 300psi Gage Sprinkler Box with Wrench & two Sprinkler Heads Each Type 1/2" Drain to Outside 1" 1" 1-1/2" PVC UG BY OTHERS Notification Device Wired by Others not to scale Module Must Connect to the Multi Station Smoke Alarm System and the Fire Sprinkler Flow Switch ( all wiring by others ) jd@jdmechanical.co Scale Project number Date Drawn by Checked by 82 5 7 9 F l e m i n g W a y S u i t e D In d i o C a . 9 2 2 0 1 (7 6 0 ) 7 7 5 -62 2 0 C-16 L i c e n s e # 1 0 2 0 1 4 1 ME C H A N I C A L IN C As indicated 11 / 1 5 / 2 0 2 2 8 : 5 4 : 5 7 A M FP-2 Piping Plan Project Number LOT 61B 06-30-22 JA JD MO O N B E A M D R E A M S TH E M A D I S O N C L U B LO T 6 1 B La Q u i n t a , C a . 9 2 2 5 3 1/8" = 1'-0"1 Piping Plan Sprinkler Schedule No. of Sprklrs Description SIN (Hydratec)K-Factor Orifice Size Temp 83 Senju1/2 Light Concealed Temperature -162 Finish - B Quick Response Model - Mirage SIN - SS8464 K Factor - 4.9 SS8464 4.9 1/2" 162 °F 10 Senju 1/2 Light Pendent Temperature -205 Finish - C Special Response Model - Micromatic SIN - SS8464 K Factor - 4.9 SS8464 4.9 1/2" 205 °F : 93 Total No. of Sprinklers: 93 12 86 2 Viking 1/2 Light Hazard Concealed Temperature- 165 Finish Quick Response VK 481 K Factor - 5.6 17555A 5.6 1/2”165 *F