BRES2016-0319 Title 24 - Revision 1o o BUILDING ENERGY ANALYSIS REPORT CITY OF LA QUINTA BUILDING & SAFETY DEPT, APPROVED FOR CONSTRUCTION oonq/{Wn PROJECT: Madison Custom Residence Lot 688 - Madison Club La Quinta, C492253 Project Designer: Hayer Architects 445 Marine View Ave., Suite 280 Del Mar, CA 92014 (858) 752-2800 ?eflaor{Report Prepared by: Tim Scott Scott Design and Title 24,lnc, 74-81 8 Velie Way, Suite 8 Palm Desert, CA 92260 (760) 200-4780 Job Number: Date: 8t15t2017 w6Hb- Qal6 --r-RECEIVED AUG 2 1 2r,t7 .orffi,?{SS.itJilENr The EnergyPro compuler program has been used to perlorm the calculations summarized in this compliance reporl. This program has approval and is adhorized by lhe California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Effciency Standards. This program de\€loped by Energysofl, LLC - www.energysofl.com. 6.7 b User Number: 6712E,ID o T-,Jrl TABLE OF GONTENTS Cover Page Table of Contents Form CF-1 R-PRF-01 -E Certificate of Compliance Form RMS-1 Residential Measures Summary Form tvlF-1R Mandatory Measures Summary HVAC System Heating and Cooling Loads Summary Room Load Summary Room Heating Peak Loads Room Cooling Peak Loads 1 2 3 16 18 22 26 30 34 \ EnergyPro 6.7 by EnergySoft Job Number: lD User Number: 6712 .ERTGE oF coMpLrANcE - RE'TDENTIAL 'ERF.RMAN.E coMpLrANcE Project Name: Madison Lot 688 Custom Residence Calculation Description: Title 24 Analysis Dateffime:.08:42, Tue, Aug 15,2017 lnput File Name: Madison Lot 68B-Hayer-16.xml }.oo Calculation cfnr-or Page 1 of 13 GENERAL INFORMATION 01 Project Name Madison Lot 688 Custom Residence 02 Calculation Description Tille 24 Analysis 03 Project Location Lot 688 - Madison Club 04 City La Quinta 05 Standards Version Compliance 2015 06 Zip Code 92253 07 Compliance Manager Version BEMCmpMgr 2013-4 Qaa) 08 Climate Zone cz15 09 Software Version EnergyPro 6.6 10 Building Type Single Family 11 Front Orientation (deg/Cardinal)110 12 Project Scope Newly Constructed 13 Number of Dwelling Units 1 14 Total Cond. Floor Area (ft2)9956 't5 Number of Zones 4 16 Slab Area (fl3)9956 17 Number of Stories 1 18 Addition Cond. FIoor Area N/A 19 Natura! Gas Available Yes 20 Addition Slab Area (fl3)N/A 21 Glazing Percentage (%)35.7Yo COMPLIANCE RESULTS 01 Building Complies with Computer Performance 02 This buildlng incorporates featur.3 that r€qui.e fiold testing and/or verilicatlon by a cortiitod HERS rat r undqr the supervision of e CEc-epprovod HERS provider. 03 This building incorporates one or more Special Features shown below This compliance analysis is valid only for permit applications through December 31, 2015 ENERGY USE SUMMARY 04 05 06 07 08 E nergy U se (kTDV/ ltz -y rl Standard Design Proposed Design Compliance Margin Percent lmprovement Space Heating 3.74 4.28 -0.54 -14.4Yo Space Cooling 84.68 85.30 -0.62 -0.7% IAQ Ventilation 0.65 0.65 0.00 0.lYo Water Heating 2.58 1.41 1.17 45.30 Photovoltaic Offset 0.00 0.00 Compliance Energy Total 91.65 91.64 0.0% Registration Number: 216-N04004048-000000000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2017-08-15 09:15:40 Report Version - CFlR-082520L5-7 44 HERS ProvidEr: CaICERTS inc Report Generated at: 2017-08-15 08:43:L6 0.01 HERS FEATURE SUMMARY provided in the buildinq components tables below. Building-level Verifications:. High Quality lnsulation lnstallation (Qll). lAQ mechanica! ventilation Gooling System Verifications:. Minimum Airflow. Verified EER. Verified SEER. Refrigerant Charge. Fan Efficacy Watts/CFM HVAC Distribution System Verifications:. Duct Sealing. Verified low-leakage ducts entirely in conditioned space Domestic Hot Water System Verifications:. - None -- cERTIE oF coMpLrANcE - RESTDENTTAL nERFoRMANcE coMpLrANcE Project Name: Madison Lot 688 Custom Residence Calculation Description: Title 24 Analysis Registration Number: 216-N04004048-000000000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance !',ooCalculation Date/Time 08:42, Tue, Aug 15,2017 lnput File Name: Madison Lot 688-Hayer-16.xml cQnr-or Page 2 of 13 REQUIRED SPECIAL FEATURES The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis. . Coolroof. CathedralCeiling 'includes calculated Appliances and Miscellaneous Energy Use (AMEU) Registration Date/Time: 2017-08-15 09:15:40 Report Version - CFlR-082520L5-7 44 HERS Provider: CaICERTS inc. Report Generated at: 2017-08-15 08:43:15 ENERGY DESIGN RATING on-sile rcne\ /ade energy system. Reference Energy Use Energy Design Rating Margin Percent lmprovement Total Energy (kTDV/f2-yr).124.90 124.89 0.01 0.0% BUILDING . FEATURES INFORMATION 01 02 03 04 05 06 07 Project Name Conditioned Floor Area (ft2) Number of Dwelling Units Number of Bedrooms Number of Zones Number of Ventilation Cooling Systems Number of Water Heating Systems Madison Lot 688 Custom Residence 99s6 1 5 4 0 1 ZONE !NFORMATION 01 02 03 04 05 06 07 Zone Name Zone Type HVAC System Name Zone Floor Area (ft'?) Avg. Ceiling Height Water Heating System 1 Water Heating System 2 great room Conditioned HVAC1,2&3grt1 4920 11 DHW Sys 1 master Conditioned HVAC 4 mstr2 1',|DHW Sys 1 bedroom Conditioned HVAC 5 bed3 1474 11 DHW Sys 1 guest Conditioned HVAC 6 gst4 1 750 11 DHW Sys 1 cenrJre or coMpLrANcE - REsTDENTTAL eERFoRMANcE coupLrANcefxoo Project Name: Madison Lot 688 Custom Residenc€ Celculation Date/Tlme: 08:42, Tue, Aug '15, 2017 Calculation Description: Title 24 Analysis lnput Flle Name: Madison Lot 688-Hayer-16.xml cQnr -01 Page 3 of 13 Registration Number: 216-N04004048-000000000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2017-oB-15 09:,t5:40 Report Ve rsion - CFlR-082520L5-7 44 HERS Provider: Ca|CERTS inc. Report Generated at: 2017-08-15 08:43:15 1812 GERTOTE oF coMpLrANcE . RESTDENTTAL PERFoRMANCE coMpLrANcEOHoD Project Name: Madison Lot 688 Custom Residence Calculatlon Date/Time: 08:42, Tue, Aug 15, 2017 Calculation Description; Title 24 Analysis lnput File Name: Madison Lot 68B-Hayer-'l6.xml coRF-ol Page 4 of 13 OPAQUE SURFACES 01 o2 03 04 05 06 07 08 Name Zone Construction Azimuth Orientation Gross Area (ft2)Window & Door Area (ft2)Tilt (deg) 9020d Wall great room R-21 Wall (W.21.2x6.16)20 Right 1 360 612.5 110d Wall great room R-21 Wall (W.21.2x6.16)110 Front 980 478.5 90 200d Wall great room R-21 Wall (W.21.2x6.16)200 Left 1 830 545.4 90 90290d Wall great room R-21 Wall (W.21.2x6.16)290 Back 1 360 427.2 Roof 2 great room R-38 Roof Flat 4830 20dWall2 master R-21 Wall(W21.2x6.16)20 Right 1 280 223.6 90 R-21 Wall (W.21.2x6.16)110 Front 120 12 90110d Wall 2 master 200d Wall2 master R-21 Wall (W.21.2x6.1 6)200 Left 780 211.9 90 290d Wall 2 master R-21 Wall (W.21.2x6.1 6)290 Back 1 080 249.6 90 Roof 3 master R-38 Roof Flat 1812 20d Wall3 bedroom R-21 Wall (W.21.2x6.16)20 Right 1044 267.6 90 90110d Wall 3 bedroom 110 Front 100 200d Wall3 bedroom R-21 Wall (W.21.2x6.16)200 Left 380 90 290 Back 90290d Wall 3 bedroom R-21 Wall (W.21.2x6.16)100 Roof 4 bedroom R-38 Roof Flat 1474 N Wall guest R-21 Wall (W.21.2x6.1 6)0 - specify -810 243 90 90E Wall guest 90 - specify -810 25.9 S Wall guest R-21 Wall (W.21.2x6.16)180 - specify -810 60 90 42.9 90200d Wall4 guest R-21 Wall (W.21.2x6.16)200 Left 216 W Wall guest R-21 Wall (W.21.2x6.16)270 - specify -98 29.7 90 90290d Wall4 guest R-21 Wall (W.21.2x6.16)290 Back 216 55 guest R-38 Roof Flat 1 750Roof 5 II OPAQUE SURFACES - Cathedral Ceilings 01 02 03 04 05 06 07 08 09 10 11 Name Zone Type Orientatio n Area (#) Skylight Area (ft2) Roof Rise (x in 12) Roof Pitch Roof Tilt (deg) Roof Reflectance Roof Emittance Framing Factor Roof great room R-38 Roof Flatl - specify -90.1 90 0 0 0 0.62 0.81 0.1 Registration Number: 216-N04004048-000000000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2017-08-15 09:i5:40 Report Version - CFlR-082520L5-7 44 HERS Provider: CaICERTS inc. Report Generated at: 2017-08-15 08:43:15 R-21 Wall (W.21.2x6.16) R-21 Wall(W21.2x6.16) cERrOrE oF coMpLrANcE - RESTDENTAL 'ERF.RMAN.E coMpLrANcElo, Project Name: Madison Lot 688 Custom Residence Calculation Description: Title 24 Analysis Galculation Date/Time: 08:.42, Tue, Aug 15, 2017 lnput File Name: Madison Lot 68B-Hayer-16.xml cQnr-or Registration Number: 216-N04oo4o48-000000000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2oit-ol-1s 09:15:40 Report Version - CFlR-082520L5-7 44 Page 5 of 13 HERS Provider: CaICERTS inc. Report Generated at: 2017-08-15 08:43:15 ATTIC 01 02 03 04 05 06 07 08 Name Construction Type Roof Rise Roof Reflectance Roof Emittance Radiant Barrier Cool Roof Attic great room Attic Roofgreat room Ventilated 0 o.62 0.81 Yes Yes Attic master Attic Roofmaster Ventilated 0 0.62 0.81 Yes Yes Attic bedroom Attic Roofbedroom Ventilated 0 0.62 0.8'l Yes Yes Attic guest Attic Roofguest Ventilated 0 0.62 0.81 Yes Yes W!NDOWS 01 02 03 04 05 06 07 08 09 10 Name Type Surface (Orientation-Azimuth)width (ft)Height (ft) Multipli er Area (d)U-factor SHGC Exterior Shading 12d Window 20d Wall (Right-20)1 159.5 0.39 0.23 lnsect Screen (default) 02w Window 20d Wall(Right-20)1 77.0 0.39 0.23 lnsect Screen (default) 02d Window 20d Wall (Right-20)1 352.0 0.39 0.23 lnsect Screen (default) 24d Window 110d Wall (Front-110)1 55.0 0.39 0.23 lnsect Screen (default) 15w Window 110d Wall (Front-110)1 1 15.5 0.39 0.23 lnsect Screen (default) 17w Window 110d Wall (Front-110)1 55.0 0.39 0.23 lnsect Screen (default) 01 d Window 1 10d Wall (Front-1 10)1 198.0 0.39 0.23 lnsect Screen (default) 01 w Window 1 10d Wall (Front-1 10)55.0 0.39 0.23 lnsect Screen (default) 25d Window 200d Wall (Left-200)1 352.0 0.39 0.23 lnsect Screen (default) 09d Window 200d Wall (Left-200)1 93.0 0.37 0.23 lnsect Screen (default) 03w Window 200d Wall (Left-200)1 37.2 0.39 0.23 lnsect Screen (default) 04w Window 200d Wall (Left-200)1 63.2 0.39 0.23 lnsect Screen (default) 05d Window 290d Wall (Back-290)1 97.2 0.39 0.23 lnsect Screen (default) 11d Window 290d Wall (Back-290)1 55.0 0.39 0.23 lnsect Screen (default) 13 d Window 290d Wall (Back-290)1 275.0 0.39 0.23 lnsect Screen (default) Skylight Skylight Roof (- specify -95)1 90.0 0.39 0.19 08w Window 20d Wall 2 (Right-2O)1 64.0 0.39 0.23 lnsect Screen (default) 07w Window 20d Wall 2 (Right-2O)1 21.0 0.39 0.23 lnsect Screen (default) '16 d Window 20d Wall 2 (Right20)1 33.3 0.39 0.23 lnsect Screen (default) 08b w Window 20d Wall2 (Right-2O)1 72.0 0.39 0.23 lnsect Screen (default) 17d Window 20d Wall2 (Right-2O)1 33.3 0.39 0.23 lnsect Screen (default) 08c w Window 1 10d Wall 2 (Front-1 10)1 12.O 0.48 0.19 lnsect Screen (default) 14a d Window 200d Wall 2 (Left-200)1 152.0 0.39 0.23 lnsect Screen (default) 15a d Window 200d Wall2 (Left-200)1 59.9 0.39 o.23 lnsect Screen (default) 14b d Window 290d Wall2 (Back-290)1 73.2 0.39 0.23 lnsect Screen (default) 15b d Window 290d Wall2 (Back-290)1 164.4 0.39 0.23 lnsect Screen (default) 08a w Window 290d Wall2 (Back-290)1 12.0 0.48 0.19 lnsect Screen (default) 09w Window 20d Wall 3 (Right-2O)1 13.8 0.48 lnsect Screen (default) 19 d Window 20d Wall3 (Right-2O)1 120.0 0.39 0.23 lnsect Screen (default) cERTIE oF coMpLtANcE - RESTDENTTAL nERFoRMANcE coMpLtANc Project Name: Madison Lot 688 Custom Residence Calculation Description: Titte 24 Analysis =tr,r",c o RF-o1 Date/Time: O8:42, Tue, Aug 15,2017 Page 6 of 13 lnput File Name: Madison Lot 68B-Hayer-16.xml Registration Number: 216-N04004048-000000000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: zO17-oB-15 09:15:40 Report Version - CF 1R-082520L5-7 44 HERS Provider: CaICERTS inc. Report Generated at: 2017-08-15 08:43:L6 1 0.19 GERTOTE oF coMpLrANcE - RESTDENTAL PERFoRMANCE coMpLrANcEOroD Project Name: Madison Lot 688 Custom Residence C-Iculation Date/Tlme: 08:42, Tue, Aug 15, 20'17 Calculation Description: Title 24 Analysis lnput File Name: Madison Lot 688-Ha!€r-16.xml cfnr-or Page 7 ot 13 20d Window 20d Wall3 (Right-2O)1 120.0 0.39 0.23 lnsect Screen (default) 10w Window 20d Wall3 (Right-2O)1 13.8 0.48 0.19 lnsect Screen (default) 21 d Window N Wall (- specify --0)1 143.0 0.39 0.23 lnsect Screen (default) 22d Window N Wall (- specify --0)1 100.0 0.39 0.23 lnsect Screen (default) 11w Window E Wall (- specify -90)1 5.9 0.39 0.23 lnsect Screen (default) 12w Window E Wall (- specify -90)1 20.0 0.39 0.23 lnsect Screen (default) 13w Window S Wall (- specify --180)1 60.0 0.39 o.23 lnsect Screen (default) 14b w Window 200d Walla (Left-200)1 42.9 0.39 0.23 I nsect Screen (default) 14aw Window W Wall (- specify --270)1 29.7 0.39 0.23 lnsect Screen (default) 23d Window 290d Wall4 (Back-290)1 55.0 0.39 0.23 lnsect Screen (default) DOORS 01 02 03 04 Name Side of Building Area (ft2)U-factor Door 57 20d Wall 24.0 0.50 Registration Number: 2'16-N04004048-000000000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2017-08-15 09:15:40 Report Version - CFLR-08252015-7 44 HERS Provider: Ca|CERTS inc. Report Generated at: 20L7-08-15 08:43:16 .ERTIE oF coMpLrANcE - RESTDENTTAL 'ERFoRMAN.E coMpLrANcE Project Name: Madison Lot 688 Custom Residence Calculation Description: Title 24 Analysis OD ation Date/Time: 08:42, Tue, Aug 15,2017 c o RF.O1 Page 8 of 13 lnput File Name: Madison Lot 688-Hayer-16.xml Registration Number: 2'16-N04004048-000000000-oooo CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2017-08-15 09:15:40 Report Version - CF 1R-082520L5-7 44 HERS Provider: CaICERTS inc. Report Generated at: 20L7-08-15 08:43:15 OPAQUE SURFACE CONSTRUCTIONS 01 02 03 04 05 06 07 Construction Name Surface Type Construction Type Framing Total Cavity R-value Winter Design U-value Assembly Layers Attic Roofgreat room Attic Roofs Wood Framed Ceiling 2x4 Top Chord of Roof Truss @ 24 in. O.C.none 0.644 Cavity / Frame: no insul. / 2x4 Top Chrd Roof Deck: Wood Siding/sheathing/decking Roofing: Light Roof (Asphalt Shingle) R-38 Roof Flat Ceilings (below attic)Wood Framed Ceiling 2x4 @ 16 in. O.C R38 0.025 lnside Finish: Gypsum Board Cavity / Frame: R-9.1 / 2x4 Over Floor Joists: R-28.9 insul. R-38 Roof Flatl Cathedral Ceilings Wood Framed Ceiling 2x4 @ 16 in. O.C.R38 0.041 lnside Finish: Gypsum Board Cavity / Frame: R-38 / 2x4 Roof Deck: Wood Siding/sheath ing/decking Roofing: Light Roof (Asphalt Shingle) R-21 Wall (W.21.2x6.16)Exterior Walls Wood Framed Wall 2x6 @ 16 in. O.C.R21 0.066 lnside Finish: Gypsum Board Cavity / Frame: R-21 / 2xG Exterior Finish: Wood S i d i ng/sh e ath i n g/d e cki n g Attic Roofmaster Attic Roofs Wood Framed Ceiling 2x4Top Chord of Roof Truss @ 24 in. O.C.none 0.644 Attic Roofbedroom Attic Roofs Wood Framed Ceiling 2x4Top Chord of Roof Truss @ 24 in. O.C.none 0.644 Cavity / Frame: no insul. / 2x4 Top Chrd Roof Deck: Wood Siding/sheath ing/decking Roofing: Light Roof (Asphalt Shingle) Attic Roofguest Attic Roofs Wood Framed Ceiling 2x4Top Chord of Roof Truss @ 24 in. O.C.none 0.644 Cavity / Frame: no insul. / 2x4 Top Chrd Roof Deck: Wood Siding/sheathing/decking Roofing: Light Roof (Asphalt Shingle) SLAB FLOORS 01 02 03 04 05 06 07 Name Zone Area (ft2)Perimeter (ft)Edge lnsu!. R-value & Depth Carpeted Fraction Heated Slab great room 4920 285 None 0.8 No Slab 2 master 1812 167 None 0.8 No Slab 3 bedroom 1474 75 None 0.8 No Slab 4 guest 1750 153 None 0.8 No . Cavity / Frame: no insul. / 2x4 Top Chrd. Roof Deck: Wood Siding/sheathing/decking. Roofing: Light Roof (Asphalt Shingle) cERnlE oF coMpLrANcE - RESTDENTAL 'ERF.RMAN.E coMpLrA*.=},oo cfnr-or Page 9 of 13Project Name: Madison Lot 688 Custom Residence Calculation Description: Title 24 Analysis Calculation Date/Time: 08:42, Tue, Aug 15, 2017 lnput File Name: Madison Lot 68B-Hayer-16.xml Registration Number: 216-N04004048-000000000-0000 CA Building Energy Efficiency Standards - 20L3 Residential Compliance Registration Date/Time: 2o1t-o}-1509:15:40 Report Version - CFlR-082520L5-7 44 HERS Provider: Ca|CERTS inc. Report Generated at: 2017-08-15 08:43:15 BUILDING ENVELOPE . HERS VERIFICATION 01 02 03 04 Quality Insulation lnstallation (Qll)Quality lnstallation of Spray Foam lnsulation Building Envelope Air Leakage CFM50 Required Not Required Not Required WATER HEATING SYSTEMS 01 02 03 04 05 06 Name System Type Distribution Type Water Heater Number of Heaters Solar Fraction (%) DHWSysl-112 DHW Pipe lnsulation, All Lines DHW Heater 1 2 0% WATER HEATERS 01 02 03 04 05 06 07 08 Name Heater Element Type Tank Type Energy Factor or Efficiency !nput Rating Tank Exterior lnsulation R-value Standby Loss (Fraction) DHW Heater 1 Natural Gas Small lnstantaneous 0 0,96 157000-Btu/hr 0 0 WATER HEATING. HERS VERIFICATION 01 o2 03 o4 05 06 07 Name Pipe !nsulation Parallel Piping Compact Distribution Point-of Use Recirculation Control Central DHW Distribution DHWSysl-112 SPACE CONDITIONING SYSTEMS 01 02 03 04 05 06 SC Sys Name System Type Heating Unit Name Cooling Unit Name Fan Name Distribution Name HVAC1,2&3grt1 Other Heating and Cooling System Heating Component 1 Cooling Component 1 HVAC Fan'l Air Distribution System 1 HVAC 4 mstr2 Other Heating and Cooling System Heating Component 2 Cooling Component 2 HVAC Fan 2 Air Distribution System 2 HVAC 5 bed3 Other Heating and Cooling System Heating Component 3 Cooling Component 3 HVAC Fan 3 Air Distribution System 3 HVAC 6 gst4 Other Heating and Cooling System Heating Component 4 Cooling Component 4 HVAC Fan 4 Air Distribution System 4 Tank Volume (gal) cERrl|,E oF coMpLrANcE - RESTDENTAL 'ERF'RMAN.E coMpLrANcE }.o, Project Name: Madison Lot 688 Custom Residence Calculation Description: Title 24 Analysis Calculation Date/Time:. 08:42, Tue, Aug 15, 2017 lnput File Name: Madison Lot 68B-Hayer-16.xml cfnr-or Page 10 of 13 HVAC . HEATING UNIT TYPES 01 o2 03 Name Efficiency Heating Component 1 CntrlFurnace - Fuel-fired central furnace BO AFUE Heating Component 2 CntrlFurnace - Fuel-fired central furnace BO AFUE Heating Component 3 CntrlFurnace - Fuel-fired central furnace 80 AFUE Heating Component 4 CntrlFurnace - Fuel-fired central furnace 80 AFUE HVAC . COOLING UNIT TYPES 01 02 04 05 06 07 Name System Type Efficiency EER SEER Zonally Controlled Multi-speed Compressor HERS Verification Cooling Component 1 SplitAirCond 12.7 16 Not Zonal Single Speed Cooling Component 1-hers-cool Cooling Component 2 SplitAirCond 12.7 '16 Not Zonal Single Speed Cooling Component 1-hers-cool Cooling Component 3 SplitAirCond 12.7 16 Not Zonal Single Speed Cooling Component 1-hers-cool Cooling Component 4 SplitAirCond 13 16.5 Not Zonal Single Speed Cooling Component 1-hers-cool HVAC COOLING. HERS VERIFICATION 01 02 03 04 05 06 Name Verified Airflow Airflow Target Verified EER Verified SEER Verified Refrigerant Charge Cooling Component 1-hers-cool Required 350 Required Required Required Cooling Component 2-hers-cool Required 350 Required Required Required Coolin g Component 3-hers-cool Required 350 Required Required Required Cooling Component 4-hers-cool Required 350 Required Required Required Registration Number: 216-N04004048-000000000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2017-ol-ls09:15:40 Report Version - CFlR-08252OL5-7 44 HERS PrOvidcr: CaICERTS inc. Report Generated at: 2017-08-15 08:43:15 Type 03 HVAC . DISTRIBUTION SYSTEMS 01 02 03 04 05 06 07 Name Type Duct Leakage lnsulation R-value Duct Location Bypass Duct HERS Verification Air Distribution System 1 LowLlCod Sealed and tested 8 Conditioned zone (VLL)None Air Distribution System 1-hers-dist Air Distribution System 2 DuctsAttic Sealed and tested 8 Attic None Air Distribution System 2-hers-dist Air Distribution System 3 DuctsAttic Sealed and tested I Attic None Air Distribution System 3-hers-dist Air Distribution System 4 DuctsAttic Sealed and tested 8 Attic None Air Distribution System 4-hers-dist cenrfre or coMpLrANcE - RESTDENTTAL eERFoRMANcE compLrANcefxoo Prcject Name: Madison Lot 688 Custom Residence CElculation Date/Time: 08:42, Tue, Aug 15,2017 Calculation Doscription: Title 24 Analysis lnput File Name: Madison Lot 68B-Hayer-'l6.xml cfnr-or Page 11 of 13 Registration Number: 216-N04004048-oo0oo0000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2017-ol-1s09:15:40 Report Version - CF1R-08252OL5-7 44 HERS Provider: CaICERTS inc Report Generated at: 2017-08-15 08:43:16 HVAC DISTRIBUTION . HERS VERIFICATION 01 02 03 04 05 06 07 08 Name Duct Leakage Verification Duct Leakage Target (%) Verified Duct Location Verified Duct Design Buried Ducts Deeply Buried Ducts Low-leakage Air Handler Air Distribution System'1 -hers-dist Required 6.0 Required Not Required Not Required Not Required Air Distribution System 2-hers-dist Required 6.0 Not Required Not Required Not Required Not Required Air Distribution System 3-hers-dist Required 6.0 Not Required Not Required Not Required Not Required Air Distribution System 4-hers-d ist Required 6.0 Not Required Not Required Not Required Not Required HVAC.FAN SYSTEMS 01 02 03 04 Name Type Fan Power (Watts/CFM)HERS Verification HVAC Fan 1 Single Speed PSC Furnace Fan 0.58 HVAC Fan 1-hers-fan HVAC Fan 2 Single Speed PSC Furnace Fan 0.58 HVAC Fan 2-hers-fan HVAC Fan 3 Single Speed PSC Furnace Fan 0.58 HVAC Fan 3-hers-fan HVAC Fan 4 Single Speed PSC Furnace Fan 0.s8 HVAC Fan 4-hers-fan HVAC FAN SYSTEMS . HERS VERIFICATION 01 02 03 Name Verified Fan Watt Draw Required Fan Efficiency (Watts/CFM) HVAC Fan 1-hers-fan Required 0.s8 HVAC Fan 2-hers-fan Required 0.58 HVAC Fan 3-hers-fan Required 0.58 cERnOE oF coMpLrANcE - RESTDENTTAL ,ERF.RMAN.E coMpLrANcE Project Name: Madison Lot 688 Custom Residence Calculation Description: Title 24 Analysis },o,Calculation Dateffime:08:42, Tue, Aug 15,2017 lnput File Name: Madison Lot 688-Hayer-16.xml cfnr-or Page 12ot13 HVAC Fan 4-hers-hn Required 0.58 IAQ (lndoor Air Quality) FANS 01 02 03 04 05 06 Dwelling Unit IAQ CFM IAQ Watts/CFM IAQ Fan Type IAQ Recovery Effectiveness(%)HERS Verification SFam lAQVentRpt 144.56 0.25 Default 0 Required Registration Number: 216-N04004048-000000000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2017-08-1S 09:15:40 Report Version - CFlR-082 52OL5-7 44 HERS Provider: CaICERTS inc. Report Generated at: 2017-08-15 08:43:16 cERTIE oF coMpLrANcE - RESTDENTTAL eERFoRMANcE coMpLrANcE Project Name: Madison Lot 688 Custom Residence Calculation Description: Title 24 Analysis fxoo CElculation Date/Time: 08:42, Tue, Aug 15,2017 Input File Name: Madison Lot 688-Hayer-16.xml coRF-ol Page 13 of 13 DOC U M E NTATIO N AUTH O R'S D EC LA RATIO N STATE M E NT 1. I certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name Tim Scott Documentation Author Sig nature:7darS* Company: Scott Design and Title 24,lnc. Signature Date: 2017-08-15 09:15:40 Address: 77085 Michigan Drive CEA/HERS Certification ldentification (lf applicable): City/State/Zip: Palm Desert, CA92211 Phone: 760-2004780 RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the follo./ing under penalty ol perjury under the laws of the State of California: 1. I am eligible under Division 3 ofthe Business and Probssions Code lo accept responsibility for the building design identified on this C€rtificate ofCompliance. Regulations. worksheets, calculalions, plans and specmcations submitted lo the enforcement agency fcr approval with this building p€rmit application. Responsible Designer Name Tim Scott Responsible Designer Signature: -l a') 4/(t/;2aoa Company: Scott Design and Title 24,lnc Date Signed: 2017-08-15 09:15:40 Address: 77085 Michigan Drive License: na City/State/Zip: Palm Desert, CA92211 Phone: 760-2004780 Digitally signed by CaICERTS. This digital signature is provided in odet to secwe the content of this rcgisteted document, and h no way implies Registation Provider rcsponsibility fot the accutacy of the information. Registration Number: 216-N04004048-000000000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2017-08-15 09:15:40 Report Version - CFlR-08252OL5-7 44 ! Easy to Verify at CalCERTS.com HERS Provider: CaICERTS inc. Report Generated at: 2017-08-15 08:43:16 o o o RESIDENTIAL MEASURES SUMMARY RMS-1 Project Name M adi son Cu stom Residence Building Type E Single Family tr Addition Alone tr Multi Family tr Existing+ Addition/Alteration Date 8/15/2017 Project Address Lot 688 - Madison Club La Quinta California Energy Climate Zone CA Climate Zone 15 Total Cond. Floor Area 9,956 Addition n/a # of Units 1 Area Cavity (fn Special Features Status Roof Wood Framed Attic R38 9,866 CoolRoof New Wall Wood Framed R21 9,889 New Door Opaque Door - no insulation 24 New S/ab U n he ated Sl ab-o n-G rade - no insulation 9,956 Perim = 680'New Demising Wood Framed - no insulation 2,492 New FENESTRATION Orientation Area(f(l U-Fac SHGC Overhang Sidefins Exterior Shades Status Skylight 90.0 0.390 0.19 none none None New Risht (N)818.1 0.390 0.23 none none Bug Screen New Right (N)234.0 0.390 0.23 none none Bug Screen New Front (E)253.0 0.390 0.23 none none Bug Screen New Front (E)225.5 0.390 0.23 none none Bug Screen New Left (S)563.9 0.390 0.23 none none Bug Screen New Left (S)93.0 0.370 0.23 none none Bug Screen New Left (S)143.3 0.390 0.23 none none Bug Screen New Rear (W)719.8 0.390 0.23 none none Bug Screen New Front (E)12.0 0.480 0.19 none none Bug Screen New Rear (W)12.0 0.480 0.19 none none Bug Screen New Right (N)27.6 0.480 0.19 none none Bug Screen New Risht (N)243.0 0.390 0.23 none none Bug Screen New Front (E)25.9 0.390 0.23 none none Bug Screen New HVAC SYSTEMS Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status 3 Central Furnace 80% AFUE Split Air Conditioner 16.0 SEER Setback New 1 CentralFurnace 80% AFUE Split Air Conditioner 76,0 SEER Setback New 1 Central Furnace 80% AFUE Split Air Conditioner 16.0 SEER Setback New HVAC DISTR!BUTION Location Heating Cooling Duct Location Duct R-Value Status HVAC1,2&3grt Ducted Ducted Conditioned 8.0 New HVAC 4 mstr Ducted Ducted Attic 8.0 New HVAC 5 bed Ducted Ducted Attic 8.0 New WATER HEATING Qty. Type Gallons Min. Eff Distribution Status 2 Smalllnstantaneous Gas 0 0.96 AllPipes lns New EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode:2017-08-15708:55:26 lD:Paqe 16 of 39 INSULATION Construction Type 35.7 %NeWAltered 0.393,551 o o RESIDENTIAL MEASURES SUMMARY RMS.1 Project Name M adi son Cu stom Resrdence Building Type E Single Family tr Addition Alone tr Multi Family tr Existing+ Addition/Alteration Date 8/1 5/2017 Project Address Lot 688 - Madison Club La Quinta California Energy Climate Zone CA Climate Zone 15 Total Cond. Floor Area 9,956 Addition n/a # of Units 1 INSULAT!ON Construction Type Area Cavity tffi Special Features Status FENESTRATION Orientation Area(t(l U-Fac SHGC Overhang Sidefins Exterior Shades Status Left (S)60.0 0.390 0.23 none none Bug Screen New Rear (W)29.7 0.390 0.23 none none Bug Screen New HVAC SYSTEMS Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status 1 CentralFurnace 80% AFUE Split Air Conditioner 76.5 SEER Setback New HVAC DISTRIBUTION Location Heating Cooling Duct Location Duct R-Value Status HVAC 6 gst Ducted Ducted Attic 8.0 New WATER HEATING Qty. Type Gallons Min. Eff Distribution Status EnerqvPro 6.7 bv Enerqv$oft User Number: 6712 RunCode: 2017-08-15T08:55:26 ID:Paqe 17 of 39 o 2013 Low-Rise Residential Mandatory Measures Summary !Q!! Low-rise residektial buildings subject to lhe Standards must corfiply utith all applicable mandatory measures listed, regardless of lhe o used,Review the re,code section more lon. Building Envelope Measures: $l10.6(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage Fenestration products (except field-fabricated windows) have a label listing the certified U-Factor, certified Solar Heat Gain Coefficient (SHGC), and infiltration that meets the requirements of $ l0- l I I (a).$ I 10.6(a)5: $ l 10.7 Exterior doors and windows are weatherstripped; alljoints and penetrations are caulked and sealed $ I 10.8(a): Insulation specified or installed meets Standards for Insulating Material. Indicate type and include on the CF2R. The thermal emittance and aged solar reflectance values of the cool roofing material meets the requirements of $ I 10.8(i) when the installation of a cool roof is specified on the CFI R.$ r r 0.8(i) $l10.8O: A radiant barrier shall have an emittance of 0.05 or less when the installation of a radiant barrier is specified on the CFIR Minimum R-30 insulation in wood-frame ceiling; or the weighted average U-factor shall not exceed 0.031. Minimum R-19 in a rafter roof alteration. Attic access doors shallhave permanently attached insulation using adhesive or mechanical fasteners. The attic 4ccess shall be gasketed to prevent air leakage. $ 150.0(a) $150.0(b): Loose flll insulation shall confbrm with manufacturer's installed design labeled R-value Minimum R-13 insulation in 2x4 inch wood framing wallor have a U-factor of 0.102 or less (R-19 inZx6 or 0.074 maximum U- factor).$ 1s0.0(c) $ I 50.0(d): M inimum R- l 9 insulation in raised wood-frame floor or 0.037 maximum U-factor In Climate Zones l4 and l6 a Class II vapor retarder shall be installed on the conditioned space side of all insulation in all exterior walls, vented attics and unvented attics with air-permeable insulation.$ 1s0.0(g) I In Climate Zones l -16 with unvented crawl spaces the earth floor of the crawl space shall be covered with a Class I or Class II vapor retarder.$ 150.0(g)2: In a building having a controlled ventilation crawl space, a Class I or Class II vapor retarder shall be placed over the earth floor of the crawl space to reduce moisture entry and protect insulation from condensation, as specified in the exception to Section 1s0.0(d). $ 1s0.0(g)3: Slab edge insulation shall: have a water absorption rate, for the insulation material alone without facings, no greater than 0.3%; have water vapor permeance rate is no greater than 2.0 perm/inch, be protected from physical damage and UV light deterioration: and when installed as part of a heated slab floor meets the requirements of $ I 10.8(g). $ r50.0(r): Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors shall have a maximum U- factor of 0.58; or the weighted average U-factor of all fenestration shall not exceed 0.58.$ 150.0(q): Fireplaces, Decorative Gas Appliances and Gas Log Measures: $ 150.0(e)l A: Masonry or factory-built fireplaces have a closable metal or glass door covering the entire opening of the lirebox Masonry or factory-built fireplaces have a combustion outside air intake, which is at least six square inches in area and is equipped with a readily accessible, operable, and tight-fitting damper or a combustion-air control device.$150.0(e)lB: $ 150.0(e)l C: Masonry or factory-built fireplaces have a flue damper with a readily accessible control. Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside of the building, are prohibited.$ 150.0(e)2: Space Conditioning, Water Heating and Plumbing System Measures $110.0-$l10,3: HVAC equipment, water heaters, showerheads, faucets and allother regulated appliances are certified to the Energy Commission Water heating recirculation loops serving multiple dwelling units meet the air release valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of $l10.3(c)5.$l10.3(c)5 Continuously buming pilot lights are prohibited for natural gas: fan-type central furnaces, household cooking appliances (appli- ances without an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and spa heaters. $ r l0.s Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA using design conditions specified in $150.0(h)2.$ r 50.0(h)l Installed air conditioner and heat pump outdoor condensing units shallhave a clearance of at least five feet from the outlet of any dryer vent.$ 150.0(h)3A: $ I 50.0(i): Heating systems are equipped with thermostats that meet the setback requirements of $ I 10.2(c). Storage gas water heaters with an energy factor equal to or less than the federal minimum standards shall be externally wrapped with insulation having an installed thermal resistance of R-12 or greater.$ 1s0.00)lA Unfired hot water tanks, such as storage tanks and backup storage tanks for solar water-heating systems, have R-12 external insulation or R-16 internal insulation where the internal insulation R-value is indicated on the exterior of the tank.lirs0.0(i)lB For domestic hot water system piping, whether buried or unburied: the first 5 feet of hot and cold water pipes from the storage tank, all piping with a nominal diameter of 314 inch or larger, allpiping associated with a domestic hot water recirculation system regardless of the pipe diameter, piping from the heating source to storage tank or between tanks, piping buried below grade, and allhot water pipes from the heating source to kitchen fixtures must be insulated according to the requirements of TABLE 120.3- A. $ r s0.00)24 All domestic hot water pipes that are buried below grade must be installed in a water proof and non-crushable casing or sleeve that allows for installation, removal, and replacement of the enclosed pipe and insulation.$ r 50.00)28 2013 Low-Rise Residential Mandato Measures Summa o Pipe for cooling system lines shall be insulated as specified in $ 150.0O2A. Piping insulation for steam and hydronic heating systems or hot water systems with pressure > l5 psig shall meet the requirements in TABLE, 120.3-A.$ 150.00)2c $150.0(i)3: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind Insulation exposed to weather shall either be rated for outdoor use or installed with a cover suitable for outdoor service. For example, protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation protected as specified or painted with coating that is water retardant and provides shielding from solar radiation that degrades the material. $r s0.0(i)3A Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space shall have a Class I or Class II vapor retarding facing, or the insulation shall be installed at the thickness that qualifies as a Class I or Class II vapor retarder. $ r 50.0o3B: Systems using gas or propane water heaters to serve individualdwelling units shall include: a l20V electricalreceptacle within 3 feet of the water heater; a Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the space where the water heater is installed; a condensate drain that is no more than2 inches higher than the base of the installed water heater, and allows natural draining without pump assistance; and a gas supply line with a capacity of at least 200,000 Btu/hr. $ 150.0(n)l $ 150.0(n)2: Recirculating loops serving multiple dwelling units shall meet the requirements of $ I 10.3(c)5 Solar water-heating systems and collectors shall be certified and rated by the Solar Rating and Certification Corporation (SRCC) or by a testing agency approved by the Executive Director.$ 150.0(n)3 Ducts and Fans Measures: All air-distribution system ducts and plenums installed are sealed and insulated to meet the requirements of CMC $601.0, $602.0, $603.0, !i604.0, $605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition. Supply-air and return-air ducts and plenums are insulated to a minimum installed level of R'6.0 (or higher if required by CMC $605.0) or enclosed entirely in directly conditioned space as confirmed through field verification and diagnostic testing (RA3.1.4.3.8). Connections of rnetal ducts and inner core of flexible ducts are mechanically fastened. Openings shall be sealed with mastic, tape, or other duct-closure system that meets the applicable requirements of UL l8l, UL l8l A, or UL I 8l B or aerosol sealantthatmeetstherequirementsofULT23. Ifmasticortapeisusedtosealopeningsgreaterthant/qinch,the combination of mastic and either mesh or tape shall be used. Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shallnot be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforrns shallnot be compressed to cause reductions in the cross-sectionalareaof the ducts. $ 150.0(m)l Factory-Fabricated Duct Systems shall comply with specified requirements for duct construction, connections, and closures;joints and seams of duct systems and their components shallnot be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and draw bands. $150.0(m)2: Field-Fabricated Duct Systems shall comply with requirements for: pressure-sensitive tapes, mastics, sealants, and other requirements specified for duct construction; duct insulation R-value ratings; duct insulation thickness; and duct labeling.$ 150.0(m)3-6: All fan systems that exchange air between the conditioned space and the outside of the building must have backdraft or automatic dampers.$ 150.0(m)7 Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers except combustion inlet and outlet air openings and elevator shaft vents.$ 1s0.0(m)8 Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind but not limited to the following: insulation exposed to weather shall be suitable for outdoor service. For example, protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shieldine from solar radiation. $ 150.0(m)9: $150.0(m)10: Flexible ducts cannot have porous inner cores. When space conditioning systems use forced air duct systems to supply conditioned air to an occupiable space, the ducts shall be sealed and duct leakage tested, as confirmed through field verification and diagnostic testing, in accordance with Reference Residential Appendix RA3. $150.0(m)l I Mechanical systems that supply air to an occupiable space through ductwork exceeding l0 feet in length and through a thermal conditioning component, except evaporative coolers, shall be provided with air filter devices that meet the requirements of $ 150.0(m)12. $ I 50.0(m) l2 Space conditioning systems that utilize forced air ducts to supply cooling to an occupiable space shall have a hole for the placement of a static pressure probe (HSPP), or a permanently installed static pressure probe (PSPP) in the supply plenum. The space conditioning system must also demonstrate airflow > 350 CFM per ton of nominal cooling capacity through the return grilles, and an air-handling unit f'an efficacy S 0.58 WCFM as confirmed by tield verification and diagnostic testing, in accordance with Reference Residential Appendix RA3. $150.0(m)13: Zonally controlled central forced air cooling systems shall be capable of simultaneously delivering, in every zonal control mode, an airflow from the dwelling, through the air handler tan and delivered to the dwelling, of > 350 CFM per ton of nominal cooling capacity, and operating at an air-handling unit fan efficacy of < 0.58 WCFM as confirmed by field verification and diagnostic testing, in accordance with Reference Residential Appendix RA3. fi I 50.0(m) l5 All dwelling units shall meet the requirements of ASHRAE Standard 62.2. Neither window operation nor continuous operation of central forced air system air handlers used in central fan integrated ventilation systems are permissible methods of providing the Whole Buildine Ventilation. $ 150.0(o): Whole Building Ventilation airflow shall be confirmed through field verification and diagnostic testing, in accordance with Reference Residential Appendix RA3.$ 150.0(o)l A Pool and Spa Heating Systems and Equipment Measures: Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency Regulations; an on-off switch mounted outside of the heater that allows shutting offthe heater without adjusting the thermostat setting; a permanent rveatherproof plate or card with operating instructions; and shall not use electric resistance heating. $l l0.a(a) 2013 Low-Rise Residential Mandato Measures Summa o Any pool or spa heating equipment shall be installed with at least 36 inches of pipe between filter and heater or dedicated suction and return lines, or built-up connections for future solar heating.$l10.4(b)l: $ I 10.4(b)2: Outdoor pools or spas that have a heat pump or gas heater shall have a cover Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or pro- grammed to run only during off-peak electric demand periods.$l r0.a(b)3: $ l l0.s Natural gas pool and spa heaters shall not have a continuous burning pilot light. $150.0(p): Residential pool systems or equipment shall meet specified pump sizing, flow rate, piping, filters, and valve requirements. Lighting Measures: $ l r0.9:All lighting control devices and systems, ballasts, and luminaires shall meet the applicable requirements of $l10.9 Installed luminaires shall be classified as high-efficacy or low-efficacy for compliance with $150.0(k) in accordance with TABLE 0-A or TABLE 150.0-8, as applicable.$ 150.0(k)l A 150 When a high efficacy and low efficacy lighting system are combined in a single luminaire, each system shall separately comply with the applicable provisions of g 150.0(k).$ 150.0(k) l B The wattage and classification of permanently installed luminaires in residential kitchens shall be determined in accordance with $130.0(c). In residentialkitchens, the wattage of electrical boxes finished with a blank cover or where no electrical equipment has been installed, and where the electrical box can be used for a luminaire or a surface mounted ceiling fan, shall be calculated as 180 watts of low efficacy lighting per electrical box. $150.0(k)lc $150.0(k)lD: Ballasts for fluorescent lamps rated 13 watts or greater shallbe electronic and shall have an output frequency no less than 20 kHz. Permanently installed night lights and night lights integral to installed luminaires or exhaust fans shall be rated to consume no more than 5 watts of power per luminaire or exhaust fan as determined in accordance with $130.0(c). Night lights do not need to be controlled by vacancy sensors. $ 150.0(k) l E: Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust hoods) shall meet the applicable requirements of $ I 50.0(k).$ r s0.0(k)l F |i 150.0(k)2A: High efficacy luminaires must be switched separately from low efficacy luminaires. $150.0(k)28: Exhaust fans shall be switched separately frorn lighting systems. $150.0(k)2C: Luminaires shall be switched with readily accessible controls that permil the luminaires to be manually switched ON and OFF $150.0(k)2D: Controls and equipment are installed in accordance with manufacturer's instructions. $150.0(k)2E: No control shall bypass a dimmer or vacancy sensor function if the control is installed to comply with $150.0(k) $ 150.0(k)2F: Lighting controls comply with applicable requirements of g I 10.9 An Energy Management Control System (EMCS) may be used to comply with dimmer requirements if: it functions as a dimmer according to $l10.9; meets Installation Certificate requirements of $130.4; the EMCS requirements of $130.5; and allother requirements in $ I 50.0(k)2. $ 150.0(k)2G: An Energy Management Control System (EMCS) may be used to comply with vacancy sensor requirements of $150.0(k) if: it functions as a vacancy sensor according to $l10.9; meets Installation Certificate requirements of $130.4; the EMCS requirements of $ 130.5; and all other requirements in g 150.0(k)2. $ r s0.0(k)2H: A multiscene programmable controller nray be used to comply with dimmer requirements ofthis section if it provides the functionality of a dimmer according to $l10.9, and complies with allother applicable requirements in $150.0(k)2. $150.0(k)3A: A minimum of 50 percentof the totalrated wattage of permanently installed lighting in kitchens shall be high efficacy Kitchen lighting includes all permanently installed lighting in the kitchen except internal lighting in cabinets that illuminate only the inside of the cabinets. Lighting in areas adjacent to the kitchen, including but not limited to dining and nook areas, are considered kitchen lighting if they are not separately switched from kitchen lighting. $ 150.0(k)3B: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of illuminated cabinet. A minimum of one high efficacy luminaire shall be installed in each bathroom; and all other lighting installed in each bathroom shall be high efficacy or controlled by vacancy sensors.$ 1s0.0(k)5: Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and controlled by vacancy sensors.lil50.0(k)6: Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be high efficacy, or shall be controlled by either dimmers or vacancy sensors.$ r s0.0(k)7: Luminaires recessed into ceilings shall: be listed for zero clearance insulation contact (lC) by Underwriters Laboratories or other nationally recognized testing/rating laboratory; have a label that certifies that the luminaire is airtight with air leakage less than 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; be sealed with a gasket or caulk between the luminaire housing and ceiling, and shall have all air leak paths between conditioned and unconditioned spaces sealed with a gasket or caulk; and allow ballast maintenance and replacement without requiring cutting holes in the ceiling. For recessed compact fluorescent luminaries with ballasts to qualify as high efficacy for compliance with $150.0(k), the ballasts shallbe certified to the Energy Commission to comply with the applicable requirements in $110.9. $ 1s0.0(k)8: For single-family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on the same lot shall be high efficacy, or may be lowefficacy if it meets allof the following requirements: i. Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of Items ii or iii below; and ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor, or controlled by a motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and automatically reactivates the motion sensor within 6 hours; and iii. Controlled by one of the following methods: $ 150.0(k)eAI $ r 50.0(k)2r: $ 1s0.0(k)4: 2013 Low-Rise Residential Mandato Measures Summa o a. Photocontrol not having an override or bypass switch that disables the photocontrol; or b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and which is programmed to automatically turn the outdoor lighting OFF during daylight hours; or c. Energy management controlsystem which meets all of the following requirements: At a minimum provides the functionality of an astronomicaltime clock in accordance with $l10.9;meets the Installation Certification requirements in $130.4; meets the requirements for an EMCS in $130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and. is programmed to automatically turn the outdoor liehtine OFF durine daylieht hours. For low-rise multifamily residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and outdoor lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply with one of the following requirements: i. Shallcomply with $150.0(k)9A; or ii. Shallcomply with the applicable requirements in $l10.9, $130.0, $130.2, t!130.4, $140.7 and $141.0. $ r s0.O(k)eB For low'rise residential buildings with four or more dwelling units, outdoor lighting not regulated by $150.0(k)98 or 150.0(k)9D shallcomply with the applicable requirements in $l10.9, $130.0, $130.2, $130.4, (i140.7 and gl4l.0.lil s0.o(k)ec Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site shall comply with the applicable requirements in gll0.9, $130.0,9130.2, $130.4, $140.7 and gl4l.0.$ r s0.0(k)eD: Internally illuminated address signs shall comply with $ 140.8; or shall consume no more than 5 watts of power as determined according to $ 130.0(c).$ r 50.0(k)10: Lighting for residential parking garages for eight or more vehicles shall comply with the applicable requirements for nonresidential garages in $l10.9, $130.0, $130.1, $130.4, $140.6, and gl4l.0.$150.0(k)r r In a low-rise multifamily residential building where the total interior common area in a single building equals 20 percent or less of the floor area, permanently installed lighting for the interior common areas in that building shall be high efficacy luminaires or controlled by an occupant sensor. $r50.0(k)r2A.: In a low-rise rnultifamily residential building where the total interior common area in a single building equals more than 20 percent of the floor area, permanently installed lighting in that building shall: i. Comply with the applicable requirements in $l10.9, $130.0, $130.1, $140.6 and $141.0; and ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each space by at least 50 percent. The occupant sensors shallbe capable of turning the light fully On and Off from alldesigned paths of $ 150.0(k)r 28 ingress and e8I9SS Solar Ready Buildings: Single family residences located in subdivisions with ten or more single family residences and where the application for a tentative subdivision map for the residences has been deemed complete, by the enforcement agency, on or after January l, 2014, shall comply with the requirements of li I 10. l0(b) through g I 10.10(e). $l 10.10(a)l: $l10.10(a)2: Low-rise multilQnrily buildings shall comply with the requirements of $l10.10(b) through gl10.10(d) The solar zone shall have a minimum total area as described below. The solar zone shall comply with access. pathway, smoke ventilation, and spacing requirements as specified in Title 24,Part 9 or other Parts of Title 24 or in any requirements adopted by a localjurisdiction. The solar zone total area shall be comprised of areas that have no dimension less than 5 feet and are no less than 80 square feet each for buildings with roof areas less than or equalto 10,000 square feet or no less than 160 square feet each fbr buildings with roof areas greater than 10,000 square feet. For single family residences the solar zone shall be located on the roof or overhang of the building and have a total area no less than 250 square feet. For low-rise multi-family buildings the solar zone shall be located on the roof or overhang of the building or on the roof or overhang of another structure located within 250 feet of the building or on covered parking installed with the building project and have a total area no less than l5 percent of the total roof area of the building excluding any skylight area. $l 10.10(b)l: $ I I 0. I 0(b)2: All sections of the solar zone located on steep-sloped roofs shall be oriented between I I 0 degrees and 270 degrees of true north. No obstructions, including but not limited to, vents, chimneys, architectural features, and roof mounted equiprnent, shall be located in the solar zone.$r r0.r0(b)3A: Any obstruction, located on the roof or any other part of the building that projects above a solar zone shall be located at least twice the distance, measured in the horizontal plane, of the height difference between the highest point of the obstruction and the horizontal proiection of the nearest point of the solar zone, measured in the vertical plane. $l r0.10(b)38: For areas of the roof designated as solar zone, the structural design loads for roof dead load and roof live load shall be clearly indicated on the construction documents.$l r0.r0(b)4: The construction documents shall indicate: a location for inverters and metering equipment and a pathway for routing of conduit from the solar zone to the point of interconnection with the electrical service (for single family residences the point of interconnection will be the main service panel); a pathway for routing of plumbing from the solar zone to the water-heating system. $l 10.10(c) A copy of the construction documents or a comparable document indicating the information from $ I 10. l0(b) through $ I 10. l0(c) shall be provided to the occupant.$r r0.10(d): !i I 10.10(e)l: The main electrical service panel shall have a minimum busbar rating of 200 amps The main electrical service panel shall have a reserved space to allow for the installation of a double pole circuit breaker lor a future solar electric installation. The reserved space shall be: positioned at the opposite (load) end from the input feeder location or main circuit location, and permanently marked as "For Future Solar Electric". $ I 10. l0(e)2: o HVAG SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name lttladison Custom Residence Date 8115t2017 System Name HVAC 1,2& 3grt Floor Area 4,920 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 3 Heating System Output per System 89,000 Total Output (Btuh)267,000 Output (Btuh/sqft)54.3 Cooling System Output per System 57,500 Total Output (Btuh)172,s00 Total Output (Tons)14.4 Total Output (Btuh/sqft)35.1 Total Output (sqfUTon)342.3 Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts 13,952 106,653130,279TOTAL SYSTEM LOAD 0 902 CFM Sensible Latent CFM Sensible COIL COOLING PEAK 5 6,85,931 0 0 0 902 35,517 7,693 8,830 0 COIL HTG. PEAK 1,881 73,247 0 0 42,237 -8,830 Air System CFM per System 2,000 HVAC EQUIPMENT SELECTION Airflow (cfm)6,000 Airflow (cfm/sqft)1.22 Airflow (cfm/Ton)417.4 outside Air (%l 15.0 o/o Outside Air (cfm/sqft)0.18 l Note: values above given at ARI conditions Carrier 24ANA760/5BPH.*1 1 0 130,936 29,432 267,000 130,936 29,432 267,000 Aug 3 PM Jan 1 AMTIME OF SYSTEM PEAK Total Adjusted System Output (Adjusted for Peak Design conditions) 'HEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak) H Etttu:26 0F 63 0F 65 0F 107 0F Heating Coil 107 "F ROOM 70 0F 70 0F l- E E Outside Air 902 cfm Supply Fan 6,000 cfm COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak) 112 t78"F 81t670F Cooling Coil 61 /600F 59.6 %ROOM 75165'F75l65"F I tr 82/680F 61/600F EIII E HlII E Outside Air 902 cfm Supply Fan 6,000 cfm EnergyPro 6.7 by EnergySoft User Number: 6712 Ru n Code : 201 7-08-1 5T08 : 5 5 : 26 ID Page 22 of 39 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name Jt/adison Cuslom Residence Date 8t15t2017 'system Name HVAC 4 mstr Floor Area 1,812 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 Heating System Output per System 89,000 Total Output (Btuh)89,000 Output (Btuh/sqft)49.1 Cooling System Output per System 57,500 Total Output (Btuh)57,500 Total Output (Tons)4.8 Total Output (Btuh/sqft)31.7 Total Output (sqft/Ton)378.2 Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts 50,041 4,570 46,783TOTAL SYSTEM LOAD 332 CFM Sensible Latent CFM Sensible COIL COOLING PEAK 2,30,760 0 1,776 0 332 12,786 2,265 2,943 1,776 COIL HTG. PEAK 852 31,346 1,541 1,541 0 -2,943 15,300 Air System CFM per System 2,000 HVAC EQUIPMENT SELECTION Airflow (cfm)2,000 Airflow (cfm/sqft)1 .10 Airflow (cfm/Ton)417.4 Outside Air (%)16.6 % Outside Air (cfm/sqft)0.18 lNote: values above given at ARI conditions Carrier 24ANA760/5BPHt*1 1 0 44,505 9,6 89,000 44,505 9,67 89,000 Aug 3 PM Jan'l AMTIME OF SYSTEM PEAK Total Adjusted System Output (Adjusted for Peak Design conditions) ,nrlttttc SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak) H Btttn:26 0F 62 0F 63 0F 105 0F Heating Coil 105 0F noorvr :* __ t_ 69 0F 70 0F lll Outside Air 332 cfm Supply Fan 2,000 cfm HI COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak) ulltH 82l680F112 t780F Cooling Coil 63/61 0F 61.5 % 75/660F76/660F 1 tr H u 83 / 69 0F 62 I 61.F Outside Air 332 cfm Supply Fan 2,000 cfm ROOM EnergyPro 6.7 by EnergySoft User Number: 6712 Ru n Code : 201 7 -08-1 5T08 : 5 5 : 26 ID:Page 23 of 39 HVAG SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name $/adison Custom Residence Date 8t15t2017 System Name HVAC 5 bed Floor Area 1,474 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 Heating System Output per System 71,000 Total Output (Btuh)71,000 Output (Btuh/sqft)48.2 Cooling System Output per System 49,000 Total Output (Btuh)49,000 Total Output (Tons)4.1 Total Output (Btuh/sqft)33.2 Total Output (sqfUTon)361.0 Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts 270 28,504 5,366 30,340TOTAL SYSTEM LOAD 0 933 797 0 2703,491 CFM Sensible Latent CFM Sensible COIL COOLING PEAK 991 1 6,1 56 1,875 COIL HTG. PEAK 456 16,226 10,483 933 0 0 797 12,519 0 Air System CFM per System 1,600 HVAC EQUIPMENT SELECTION Airflow (cfm)1,600 Airflow (cfm/sqft)1.09 Airflow (cfm/Ton)391.8 Outslde Air (%)16.9 % Outside Air (cfm/sqft)0.18 I Note: values above glven at ARI conditions Carrier 24ANB748-58PH..090 38,434 6,314 71,000 6,31 71,000 Jan 1 AMAug 3 PM 38,434 TIME OF SYSTEM PEAK Total Adjusted System Output (Adjusted for Peak Design conditions) HEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak) 104 0F260F620F620F Heating Coil 103 0F noorvr * _L'- 70 0F 70 "F I HEI H EltOutside Air 270 cfm Supply Fan 1,600 cfm COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak) I82t670F112 t78oF EIIIH 60/580FCooling Coil 54.8 o/o ROOM 75t640F76t64"F I 1_- H 82t670F 59/58"F EII Outside Air 270 cfm Supply Fan 1,600 cfm EnergyPro 6.7 by EnergySoft User Number: 6712 Ru n Code : 201 7-08-1 5708 : 5 5 : 26 ID:Page 24 of 39 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name lMadison Custom Residence Date 8t15t2017 System Name HVAC 6 gst Floor Area 1,750 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 Heating System Output per System 1 10,000 Total Output (Btuh)1 10,000 Output (Btuh/sqft)62.9 Cooling System Output per System 58,000 Total Output (Btuh)58,000 Total Output (Tons)4.8 Total Output (Btuh/sqft)33.1 Total Output (sqft/Ton)362.1 Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts 1,292 321 14,81 1,292 5,249 43,68138,869TOTAL SYSTEM LOAD CFM Sensible Latent CFM Sensible COIL COOLING PEAK 2,22623,7171,658 0 1,369 0 321 12,414 3,023 0 1,369 COIL HTG. PEAK 568 26,282 Air System CFM per System 2,000 HVAC EQUIPMENT SELECTION Airflow (cfm)2,000 Airflow (cfm/sqft)1.14 Airflow (cfm/Ton)413.8 Outside Air (%)16.0 % Outside Air (cfm/sqft)0.18 1 Note: values above given at AR! conditions Carrier 24AN 8760-58PH..1 1 0-20 43,757 9,864 110,000 43,757 9,864 1 10,000 Aug 3 PM Jan 1 AMTIME OF SYSTEM PEAK Total Adjusted System Output (Adjusted for Peak Design conditions) ,neattruc SYSTEM PSYCHRoMETRICS (Airstream Temperatures at Time of Heating Peak) 26 0F 620F 620F 114 0F Heating Coil 114 0F ROOM --" t_ 69 0F 70 0F ElI rhl H E EIIIH:Outside Air 321 cfm Supply Fan 2,000 cfm COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak) I81 t67 0F112 t78"F ETI I H Cooling Coil 62/600F 58.6 %ROOM -It--- 75l65"F76/65"F HIIIE + 81 I 67 "F 61 / 60.F Supply Fan 2,000 cfm EnergyPro 6.7 by EnergySoft User Number: 6712 Ru n Code : 201 7-08-1 5T08 : 5 5 : 26 ID Page 25 of 39 Outside Air 321 cfm o o ROOM LOAD SUMMARY Project Name Madison Cu stom Residence Date 8/1 5/2017 System Name UyAC1,2&3grt Floor Area 4,920 HOOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK Zone Name Room Name Mult.CFM Sensible Latent CFM Sensible Latent CFM Sensible great room Great Room Living area k 1 5,954 85,931 6,259 5,954 85,931 6,259 1,881 73,247 PAGE TOTAL TOTAL - " Total includes ventilation load for zonal systems EnergvPro 6.7 by EnergySoft User Number: 6712 RunCode: 2017-08-15708:55:26 ID:Pase 26 of 39 o o o ROOM LOAD SUMMARY Project Name Madi son Cu stom Residence Date 8/1 5/2017 System Name HVAC 4 mstr Floor Area 1,912 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK Zone Name Room Name Mult CFM Sensible Latent CFM Sensible Latent CFM Sensible master Master bedroom 1 2,439 30,760 2,305 2,439 30,760 2,305 852 31,346 PAGE TOTAL TOTAL - * Total includes ventilation load for zonal systems EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode:2017-08-15T08:55:26 ID:Paqe 27 of 39 o o o Project Name Madison Custom Residence 8/1 5/2017 Date System Name HVAC 5 bed Floor Area 1,474 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK Zone Name Room Name Mult CFM Sensible Latent CFM Sensible Latent CFM Sensible bedroom Bedrooms 2 & 3 1 991 16,156 1,875 991 16,156 1,875 456 16,226 . Total includes ventilation load for zonal systems PAGE TOTAL TOTAL * Paqe 28 of 39IDEnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2017-08-15708:55:26 II o ROOM LOAD SUMMARY o o ROOM LOAD SUMMARY Project Name Madison Custom Residence Date 8/1 5/2017 System Name HVAC 6 gsf Floor Area 1,750 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK Zone Name Room Name Mult CFM Sensible Latent CFM Sensible Latent CFM Sensible guesf Guesf Room quafters 1 1,658 23,717 2,226 1,658 23,717 2,226 568 26,282 PAGE TOTAL TOTAL - . Total includes ventilation load for zonal systems, EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2017-08-15T08:55:26 ID:Pase 29 of 39 o o o o ROOM HEATING PEAK LOADS Project Name M adi son C u stom Residence Date 8/1 5/2017 ROOM INFORMATION DESIGN CONDITIONS Room Name Great Room Living area Kitchen Ftoor Area 4,920.0 ft'z lndoor Dry Butb Temperature 70 oF Tlme of Peak Outdoor Dry Bulb Temperature Jan 1 AM 26 0F Conduction Area U-Value AT OF Btu/hr 4,830.0 90.0 3,466.4 1,543.7 402.9 24.0 93.0 perim = 285.0 788.0 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x 0.0260 0.3900 0.0690 0.3900 0.3900 0.5000 0.3700 0.7300 0.3560 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x Items shown with an asterisk (.) denote conduction through an interior surface to another room Page Total lnfiltration:I x x 4,920 x /60] x 44 I Area ing Height H Fraction 44 44 44 44 44 44 44 44 0 1.00 1.064 11.00 0.262x AT TOTAL HOURLY HEAT LOSS FOR ROOM 73,247 EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2017-08-15T08:55:26 ID Page 30 of 39 o o ROOM HEATING PEAK LOADS Project Name M adi son Cu stom Resrdence Date 8/1 5/2017 ROOM INFORMATION DESIGN CONDITIONS Room Name Floor Area lndoor Dry Bulb Temperature Master bedroom 1 ,812.0 ft2 70 0F Time of Peak Outdoor Dry Bulb Temperature Jan 1 AM 26 0F Conduction Area U-Value AT OF Btu/hr 1,812.0 2,562.9 157.0 516.1 24.0 perim = 167.0 596.0 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x 0.0260 0.0690 0.3900 0.3900 0.4800 0.7300 0.3560 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x 44 44 44 44 44 44 0 Items shown with an asterisk (') denote conduction through an interior surface to another room Page Total lnliltration:I 1.00 x 1.064 x 1,812 /60] x 44 Schedule Fraction Air Sensible 11.00 0.262 Area x ng Height x H AT TOTAL HOURLY HEAT LOSS FOR ROOM 31,346 EnergyPro 6.7 by EnergySol o R-38 Roof Flat 2,073 R-21 Watl (W.21.2x6.1 6)7,781 ..39.23 3000f 2,694 .39.23 3000f 8,856 48.19 2000c1 507 Slab-On-Grade 5,364 *R-0 lnteior Wall 0 27,275 4,071 o o ROOM HEATING PEAK LOADS Project Name M adi son Custom Residence Date 8/1 5/2017 ROOM INFORMATION DESIGN CONDITIONS Room Name Floor Area lndoor Dry Bulb Temperature Bedrooms 2 & 3 1,474.0 ft2 70 0F Time ol Peak Outdoor Dry Bulb Temperature Jan 1 AM 26 0F Conduction Area U-Value AT OF Btu/hr 1,474.0 1,356.4 27.6 240.0 perim = 75.0 410.0 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x 0.0260 0.0690 0.4800 0.3900 0.7300 0.3560 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x 44 44 44 44 44 0 Items shown with an asterisk (.) denote conduction through an interior surface to another room Page Total !nliltration:I x 1.064 x 1,474 x 11.00 0.262 /60l xule Air Sensible Area Ceiling Height ACH Fraction 1.00 x A TOTAL HOURLY HEAT LOSS FOR ROOM 16,226 EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2017-08-15T08:55:26 ID:Page 32 of 39 o o o o ROOM HEATING PEAK LOADS Project Name M adi son C u stom Resrdence Date 8/1 5/2017 ROOM INFORMATION DESIGN CONDITIONS Room Name Floor Area lndoor Dry Bulb Temperature Guesf Room quafters 1,750.0 ftz 70 0F Time of Peak Outdoor Dry Bulb Temperature Jan 1 AM 26 0F Conduction Area U-Value AT OF Btu/hr 1,750.0 2,503.5 298.0 158.5 perim = 153.0 410.0 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x 0.0260 0.0690 0.s900 0.s900 0.7300 0.3560 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x 44 44 44 44 44 0 Items shown with an asterisk (.) denote conduction through an interior surface to another room Page Tota! tnfiltration:I x 1.064 x 1,750 x 11.00 /60I le Air Sensible Area Ceiling Height Fraction 1.00 0.262x x A TOTAL HOURLY HEAT LOSS FOR ROOM 26,282 EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2017-08-15708:55:26 ID:Page 33 of 39 o o o RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name M adi son C u stom Residence Date 8/1 5/2017 ROOM INFORMATION DESIGN CONDITIONS Room Name Great Room Living area Kitchen Ftoor Area 4,920.0 ft2 lnCqor Dry Bulb Temperature 75 oF Outdoor Dry Bulb Temperature Outdoor Wet Bulb Temperature Outdoor Daily Range: 1120F 78 0F 34 0F Surfaces Orientation Area U-Factor CLTDI Btu/hr (E) (N) (N) (E) (s/ (W 4,830.0 747.5 24.0 501.5 1,284.6 932.8 788.0 x x x x x x x x x 0.0260 0.0690 0.5000 0.0690 0.0690 0.0690 0.3560 x x x x x x x x x 56.0 25.7 25.7 32.1 28.2 31.8 0.0 Page Total Items shown with an asterisk (.) denote conduction through an interior surface to another room.1. Cooling Load Temperature Difference (CLTD) Shaded Fenestration Orientation Area GLF Unshaded Area GLF Btu/hr (E) (N) (N) (N) (E) (E) (E) (E) (E) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 x x x x x x x x x 15.1 16.3 16.3 16.3 16.3 16.3 16.3 16.3 16.3 + + + + + + + + + x x x x x x x x x Page Tota! Internal Gain Btu/hr 14.8 4,920 Occupants Floor Area x x 245 0.50 Btuh/occ. w/sqft lnfiltration:x 0.89 x 248.02 x 37 Air ble CFM ELA AT 90.0 159.5 77.0 352.0 55.0 115.5 55.0 198.0 55.0 40.8 19.6 19.6 19.6 29.0 29.0 29.0 29.0 29.0 1.064 TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 85,931 Latent Gain O".u'rn,, -l Btu/hr 14.8 Occupants X 155 lnfiltration:x 0.89 x 248.02 x 0.00376 r ble CFM ELA AW 4,771 Btuh/occ TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 2,288 EnerqvPro 6.7 bv EneruvSoft User Number: 6712 RunCode:2017-08-15708:55:26 lD Paoe 34 of 39 M a'r,or"n, -l t o RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Madison Custom Residence Date 8/1 5/2017 ROOM INFORMATION DESIGN CONDITIONS Room Name Great Room Living area Kitchen Floor Area 4,920.0 ft'z tndoor Dry Bulb Temperature 75 oF Outdoor Dry Bulb Temperature Outdoor Wet Bulb Temperature Outdoor Daily Range: 1120F 78 "F 34 0F ue Surfaces Orientation Area U-Factor CLTD1 Btu/hr x x x x x x x x x x x x x x x x x x Page Total Items shown with an asterisk (*) denote conduction through an interior surface to another room1. Cooling Load Temperature Difference (CLTD) Shaded Fenestration Orientation Area GLF Unshaded Area GLF Btu/hr (s/ (s,) (s,) rs) (W (W (W 0.0 0.0 0.0 0.0 0.0 0.0 0.0 x x x x x x x x x 16.3 15.9 16.3 16.3 16.3 16.3 16.3 + + + + + + + + + x x x x x x x x x Page Total lnternal Gain Btu/hr 14.8 4,920 Occupants Floor Area x x 245 0.50 Btuh/occ. w/sqft lnfiltration:1.064 x 0.89 x 248.02 x 37 Air Sensible CFM ELA AT 352.0 93.0 37.2 63.2 97.2 55.0 275.0 18.7 18.3 18.7 18.7 27.2 27.2 27.2 TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 85,931 14.8 155 0.89 248.02 0.003764,771 Latent Gain Btu/hr Btuh/occ. lnfiltration: CFM AW x x ELA x Occupants X TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 2,288 Paqe 35 of 39EnergvPro 6.7 by EnergySoft User Number: 6712 RunCode: 2017-08-15708:55:26 lD: M =Or,or"n, -l 3,971 o o RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Madi son Custom Residence Date 8/1 5/2017 ROOM INFORMATION DESIGN CONDITIONS Room Name Floor Area Indoor Dry Bulb Temperature Master bedroom 1 ,912.0 ft2 75 0F Outdoor Dry Bulb Temperature Outdoor Wet Bulb Temperature Outdoor Daily Range: 1120F 78 0F 34 0F Surfaces Orientation Area U-Factor CLTD1 Btu/hr (E) (N) (E) (s,) (W 1,812.0 1,056.4 108.0 568.1 830.4 596.0 x x x x x x x x x 0.0260 0.0690 0.0690 0.0690 0.0690 0.3560 x x x x x x x x x 56.0 25.7 32.1 28.2 31.8 0.0 Page Total Items shown with an asterisk (*) denote conduction through an interior surface to another room1. Cooling Load Temperature Difference (CLTD) Shaded Fenestration Orientation Area GLF Unshaded Area GLF Btu/hr (N) (N) (N) (N) (N) (E) rs,) rs,) (W 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 x x x x x x x x x 16.3 16.3 16.3 16.3 16.3 16.7 16.3 16.3 16.3 + + + + + + + + + x x x x x x x x x Page Total lnternal Gain Btu/hr 5.4 1,812 Occupants Floor Area x x 245 0.50 Btuh/occ. w/sqft lnfiltration:x 0.89 x 91.34 x 37 Air Sens CFM ELA AT 64.0 21.0 33.3 72.0 33.3 12.0 152.0 59.9 73.2 19.6 19.6 19.6 19.6 19.6 27.1 18.7 18.7 27.2 1.064 TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 30,760 5.4 155 0.89 91.34 0.003764,771 Latent Gain Btu/hr Btuh/occ. lnfiltration: CFM x x ELA AW x Occupants X TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 843 Paqe 36 of 39EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode:2017-08-15708:55:26 lD M aou,or"n, -l Occuoanls o o RESIDENTIAL ROOM GOOLING LOAD SUMMARY Project Name Madison Custom Residence Date 8/1 5/2017 ROOM INFORMATION DESIGN CONDITIONS Room Name FIoor Area lndoor Dry Bulb Temperature Master bedroom 1,912.0 ft, 75 0F Outdoor Dry Bulb Temperature Outdoor Wet Bulb Temperature Outdoor Daily Range: 1120F 78 0F 34 0F Surfaces Orientation Area U-Factor CLTD1 Btu/hr x x x x x x x x x x x x x x x x x x Page Total Items shown with an asterisk (.) denote conduction through an interior surface to another room1. Cooling Load Temperature Difference (CLTD) Shaded Fenestration Orientation Area GLF Unshaded Area GLF Btu/hr (W (w 0.0 0.0 x x x x x x x x x 16.3 16.7 + + + + + + + + + 164.4 12.0 x x x x x x x x x 27.2 25.6 Page Total lnternal Gain Btu/hr 5.4 1,812 Occupants Floor Area x x 245 0.50 Btuh/occ. w/sqft !nfiltration:x 0.89 x 91.34 x 37 Air e CFM ELA AT 1.064 TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 30,760 Latent Gain O..rO.n,, -l Btu/hr 5.4 Occupants X 155 lnfiltration:x 0.89 x x 0.00376 Air Sensi CFM LA AW 4,771 91.34 Btuh/occ. TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 843 EnergyPro 6.7 by EnersvSoft User Number: 6712 RunCode:2017-08-15T08:55:26 lD:Paqe 37 of 39 o o o RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Madison Custom Residence Date 8/1 5/2017 ROOM INFORMATION DESIGN CONDITIONS Room Name Floor Area lndoor Dry Bulb Temperature Bedrooms 2 & 3 1,474.0 ft2 75 0F Outdoor Dry Bulb Temperature Outdoor Wet Bulb Temperature Outdoor Daily Range: 1120F 7B OF 34 0F o ue Surfaces Orientation Area U-Factor CLTDl Btu/hr (E) (N) (E) (s) (W 1,474.0 776.4 100.0 380.0 100.0 410.0 x x x x x x x x x 0.0260 0.0690 0.0690 0.0690 0.0690 0.3560 x x x x x x x x x 56.0 25.7 32.1 28.2 31.8 0.0 Page Total Items shown with an asterisk (*) denote conduction through an interior surface to another room1. Cooling Load Temperature Difference (CLTD) Shaded Fenestration Orientation Area GLF Unshaded Area GLF Btu/hr (N) (N) (N) (N) 0.0 0.0 0.0 0.0 x x x x x x x x x 16.7 16.3 16.3 16.7 + + + + + + + + + 13.8 120.0 120.0 13.8 x x x x x x x x x 19.4 19.6 19.6 19.4 Page Total lnternal Gain Btu/hr 4.4 1,474 Occupants Floor Area x x 245 0.50 Btuh/occ. w/sqft lnfiltration:x 0.89 x 74.31 x 37 r sible CFM ELA AT 1.064 TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 16,156 Latent Gain Btu/hr 4.4 Occupants X 155 lnfiltration:4,771 x 0.89 x 74.31 x 0.00376 Air Sensible CFM ELA AW Btuh/occ. TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 685 EnerqyPrc 6.7 bv EnerqvSoft User Number: 6712 RunCode:2017-08-15708:55:26 lD:Paqe 38 of 39 o Occupants o t RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name M adi son C u stom Resrdence Date 8/1 5/2017 ROOM INFORMATION DESIGN CONDITIONS Room Name Floor Area lndoor Dry Bulb Temperature Guesf Room quafters 1,750.0 ft2 75 0F Outdoor Dry Bulb Temperature Outdoor Wet Bulb Temperature Outdoor Daily Range: 1120F 7g oF 34 0F ue Surfaces Orientation Area U-Factor CLTDl Btu/hr (E) (N) (E) rs) (s) (W (w 1,750.0 567.0 784.1 750.0 173.1 68.3 161.0 410.0 x x x x x x x x x 0.0260 0.0690 0.0690 0.0690 0.0690 0.0690 0.0690 0.3560 x x x x x x x x x 56.0 23.0 33.0 26.0 28.2 33.0 31.8 0.0 Page Total Items shown with an asterisk (.) denote conduction through an interior surface to another room1. Cooling Load Temperature Difference (CLTD) Shaded Fenestration Orientation Area GLF Unshaded Area GLF Btu/hr (N) (N) (E) (E) rs) rs) (W (W 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 x x x x x x x x x 16.3 16.3 16.3 16.3 16.3 16.3 16.3 16.3 + + + + + + + + + x x x x x x x x x Page Total lnternal Gain Btu/hr 5.2 1,750 Occupants Floor Area x x 245 0.50 Btuh/occ. w/sqft lnfiltration:x 0.89 x 88.22 x 37 Air e CFM ELA AT 143.0 100.0 5.9 20.0 60.0 42.9 29.7 55.0 16.3 16.3 30.0 30.0 16.4 18.7 30.0 27.2 1.064 TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 23,717 Latent Gain Btu/hr Occupants 5.2 Occupants X 155 lnfiltration:x 0.89 x 88.22 x 0.00376 r ble CFM ELA AW 4,771 Btuh/occ TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 814 EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode:2017-08-15708:55:26 lD:Paqe 39 of 39 o