BRES2016-0319 Title 241 BUILDING ENERGY ANALYSIS REPORT PROJECT: Madison Custom Residence Lot 68B - Madison Club La Quinta, CA 92253 Project Designer: Hayer Architects 445 Marine View Ave., Suite 280 Del Mar, CA 92014 (858) 752-2800 Report Prepared by: Jon Scott Scott Design and Title 24, ln 74-81 8 Velie Way, STE I Palm Desert, CA 92260 (760) 702-5406 CI TY OF LA QUINTA BU ILDING & SAFETY DEPT" /\PPR VED F,Oil CONS UCTION Iah> Job Number: 8V==; m*:;; z Od:*j ,.J, Z :^ : o fn -c2 -@ m€-l=-, u2-t Date: 10t26t2016 The EnergyPro compuler program has been used to pe.form the calculations summarized in this compliance report. This program has approval and is authorized by the Califomia Energy Commission tor use with both the Residential and Nonresidenlial 2013 Building Energy Efliciency Standards. This program developed by Energysofr, LLC - r.$r ,rr.energyson.com. EnergyPro 6.7 by EnergySoft User Number: 6712 ID lsh- I TABLE OF CONTENTS Cover Page Table of Contents Form CF-1 R-PRF-O1-E Certificate of Compliance Form RMS-1 Residential Measures Summary Form MF-1 R Mandatory Measures Summary HVAC System Heating and Cooling Loads Summary Room Load Summary Room Heating Peak Loads Room Cooling Peak Loads 1 2 3 16 18 22 26 30 34 EnergyPro 6.7 by EnergySoft .165 1r1urn6sr lD:User Number: 67'l 2 {t CERTIFICATE OF COMPLIANCE . RESIDENTIAL PERFORTIANCE COiIPLIANCE METHOD Project Name: Madison Lot 688 Custom Residence Calculatlon Date/Time: 15:27, \ ed, Oct 26, 2016 Calculatlon D6cription: Title 24 Analysis lnput Flle Name: Madison Lot 688-Hayer-'l6.xml CFlR-PRF-01 Page 1 of 13 Ct*, lf ' r. -, ;],.-fq COiri, ...: : . ..:. i-:,,=.+i,ivlENT Registration Number: 2't6-No4oo4o4A-000000000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2016-10-2615:34:05 Report Version - CFlR-04072016-7 44 HERS Provider: CaICERTS inc. Report Generated at: 2016-10-26 75:28:49 GENERAL INFORMATION Madison Lot 68B Custom Residence01Project Name fille 24 AnalysisCalculation Description Project Location Lot 688 - Madison Club Compliance 2015La Quinta 05 Standards VersionCity BEMCmpMgr 2013-4 (744)Compliance Manager Version92253Zip Code EnergyPro 6.6cz15Software VersionClimate Zone 110Front Orientation (deg/Cardinal)Single FamilyBuilding Type 1Newly Constructed Number of Dwelling UnitsProject Scope 49956Number of ZonesTotat Cond. Floor Area (ft2) 9956Stab Area (ft2) N/AAddition Cond. Floor Area zuH{eEqsAddition Slab Area (ft2)N/A COMPLIANCE RESULTS Building Complies with Computer Performance01 02 This building incorporates features that require field testlng and/or verification by a certified HERSrate6r 03 This building incorporates one or more Special Features shown below rrrrrrgrrrr rrrrrgrg ENERGY USE SUMMARY 04 05 06 07 08 Energy Use (kTDV/ft2-yr)Standard Design Proposed Design Compliance Margin Percent lmprovement Space Heating 3.74 2.78 0.96 25.7o/o Space Cooling 84.68 84.39 o.29 0.3% IAQ Ventilation 0.65 0.65 0.00 \-ttIrt' ]u*{ r L-l \.p 0%-\ Water Heating 2.58 -0.29 I \I-',,.-*o :i*. I V_llr.g|-t Photovoltaic Offset 0.00 0.00 Compliance Energy Total 91.65 90.69 0.96 ,iO\/0&^lgq[w"/" I ff I .l }D III\IT^ Wri.':;l' \/ I tLll\f 7. ."' '\" cf a CEC-approve d HERS provider. < 2.87 CERTIFICATE OF COI'PLIANCE . RESIDENTIAL PERFORi'ANCE COiIPLIANCE METHOD Prciect Namo: Madison Lot 688 Custom Residence Calculatlon Date/Time: 15:27, \ Ed, Oct 26, 2016 Calcutation Descrlptlon: Title 24 Analysis lnput File Name: Madison Lot 688-Hayer-16.xml CF1R.PRF.O1 Page 2 ot 13 REQUIRED SPECIAL FEATURES The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis . Cool roof * includes calculated Appliances and Miscellaneous Energy Use (AMEU) Registration Number: 216-N04oo4o4A-ooooo0000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2016-10-2615:34:05 Report Version - CFlR-040720t6-7 44 HERS Provider: CaICERTS inc. Report Generated at: 2016-10-26 L5',28:49 HERS FEATURE SUMMARY provided in the building components tables below. Building-level Verifications:. High Quality lnsulation lnstallation (Qll). IAQ mechanical ventilation Coolin g System Verifications:. Minimum Airflow. Verified EER. Verified SEER. Refrigerant Charge. Fan Efficacy Watts/CFM HVAC Distribution System Verifications:. Duct Sealing. Verified low-leakage ducts entirely ln conditioned space Domestic Hot Water System Verifications:. -- None -- ENERGY DESIGN RATING on-site renerable energy system. Reference Energy Use Energy Design Rating Margin Percent lmprovement Total Energy (kTDV/f2-yr).124.90 123.94 0.96 0.8% BUILDING . FEATURES INFORMATION 01 02 03 04 05 06 07 Project Name Conditioned Floor Area (ft2) Number of Dwelling Units Number of Bedrooms Number of Zones Number of Ventilation Cooling Systems Number of Water Heating Systems Madison Lot 688 Custom Residence 9956 1 5 4 0 1 ZONE INFORMATION 01 02 03 04 05 06 07 Zone Name Zone Type HVAC System Name Zone Floor Area (ft2) Avg. Ceiling Height Water Heating System I Water Heating System 2 great room Conditioned HVAC1,2&3grt1 4920 11 DHW Sys 1 master Conditioned HVAC 4 mstr2 1812 11 DHW Sys 1 bedroom Conditioned HVAC 5 bed3 1474 11 DHW Sys 1 guest Conditioned HVAC 6 gst4 1750 11 DHW Sys 1 CERTIFICATE OF COi'PLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD PrcJect Name: Madison Lot68B Cuslom Residence Calculation DatorTlme: '15:27, V!bd, Oct26, 2016 Calculatlon Description: Title 24 Analysis lnput Flle Name: Madison Lot 68B-Hayer-16.xml CFlR.PRF-01 Page 3 of 13 cfry o FLA QUIN IACUILDiNG&SA FETYIf'1 ,--J,PR OV DEPI FUR CONS E D]-RU CI,ON BY Registration Number: 216-N04o04o4A-000000000-0000 CA Building Energy Efficiency Standards - 2OL3 Residential Compliance Registration Date/Time: zoi6-10-2615:34:05 Report Version - CFlR-040720t6-7 44 HERS Provider: CaICERTS inc. Report Generated at: 2016-10-26 L5:28:49 D*rr OPAQUE SURFACES 01 02 03 04 05 06 07 08 Name Zone Construction Azimuth Orientation Gross Area (ft2)Window & Door Area (ft2)Tilt (deg) 20d Wall great room R-21 Wall (W.21.2x6. 16)20 Right 1 360 612.5 90 1'l0d Wall great room R-21 Wall (W.21.2x6.16)110 Front 980 478.5 90 200d Wall great room R-21 Wall (W.21.2x6.16)200 Left 1 830 90 290d Wall great room R-21 Wall (W.21.2x6.16)290 Back 1 360 427.2 90 Roof 2 great room R-38 Roof Flat 4830 20dWall2 master R-21 Wall (W.21.2x6.16)20 Right 1280 223.6 90 110d Wall 2 master R-21 Wall (W.21.2x6.1 6)110 Front 120 12 90 200d Wall2 master R-21 Wall (W.21.2x6.16)200 780 211.9 90 290d Wall2 master R-21 Wall (W.21.2x6. 16)290 Back 1 080 249.6 90 Roof 3 master R-38 Roof Flat 1812 20d Wall 3 bedroom R-21 Wall (W.21.2x6.16)20 Right 1044 267.6 90 110d Wall 3 bedroom R-21 Wall (W.21.2x6.16)110 Front 100 0 90 200d Wall3 bedroom R-21 Wall (W.21.2x6.16)200 Left 380 0 90 290d Wall3 bedroom R-21 Wall (W.21.2x6.16)290 100 0 90 Roof 4 bedroom R-38 Roof Flat 1474 N Wall guest R-21 Wall (W.21.2x6.16)0 - specify -810 243 90 E Wall guest R-21 Wall (W.21.2x6.16)90 - specify -810 25.9 90 S Wall guest R-21 Wall (W.21.2x6.16)180 - specify -810 60 90 200d Wall4 guest R-21 Wall (W.21 .2x6. 1 6)200 Left 216 42.9 90 WWall guest R-21 Wall (W.21.2x6.16)270 - specify -9B 29.7 90 290d Wall4 guest R-21 Wall (W.21.2x6. 1 6)290 Back 216 55 90 Roof 5 guest R-38 Roof Flat 1750 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: Madison Lot688 Custom Residence Calculation Date/Time: 15:27, \ /ed, Oct26,20'16 Calculation Descriplion: Title 24 Analysis lnput File Name: Madison Lot 688-Hayer-16.xml Registration Number: 216-N04o04o4A-oooooo000-0000 CA Building Energy Efficiency Standards - 2OL3 Residential Compliance Registration Date/Time: 2oi6-10-2615:34:05 Report Version - CFlR-040720L6-7 44 CF1R.PRF.O1 Page 4 of 13 HERS Provider: CaICERTS inc. Report Generated at: 20L6-10-26 L5:28:49 OPAQU E SURFACES - Cathedral Geilings 01 02 03 04 05 07 08 09 10 11 Name Zone Type Orientatio n Area (ft2) Skylight Area (ft2) Roof Rise (x in 12) Roof Pitch Roof Tilt (deg) Roof Reflectance Roof Emiftance Framing Factor Roof great room R-38 Roof Flatl - specify -90.1 90 0 0 0 0.62 0.81 0.1 545.4 Left Back 06 ATTIC 01 02 03 04 05 06 07 08 Name Construction Type Roof Rise Roof Reflectance Roof Emittance Radiant Barrier Cool Roof Attic great room Attic Roofgreat room Ventilated 0 0.81 Yes Yes Attic master Attic Roofmaster Ventilated 0 0.62 0.81 Yes Yes Attic bedroom Attic Roofbedroom Ventilated 0 0.62 0.81 Yes Yes Attic guest Attic Roofguest Ventilated 0 0.62 0.81 Yes Yes CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORi'ANCE COMPLIANCE i'ETHOD Prclsct Name: Madison Lot 688 Custom Residence Calculation DaterTlme: 15:27, l bd, Oct 26, 2016 Calculation Descriptlon: Title 24 Analysis lnput File Name: Madison Lot 68B-Hayer-16.xml CF1R.PRF.O1 Page 5 of 13 CITY OF LA QUINTAEUILDING &SAFETY D EPT. ,IisP RCV EDf.Cft CO NSTRU CTION BY Registration Number: 216-N04o04o4A-000000000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2016-10-2615:34:05 Report Version - CF 1R-040720L6-7 44 HERS Provider: CaICERTS inc. Report Generated at: 2015-10-26 L5:28:49 0.62 ' l'.,h WINDOWS 01 o2 03 04 05 06 07 08 09 10 Name Type Su rface (Orientation-Azimuth)width (ft)Height (ft) Multipli er Area (ft2)U-factor SHGC Exterior Shading 12d Window 20d Wall (Right20)1 159.5 0.32 o.24 lnsect Screen (default) 02w \Mndow 20d Wall(Right-20)1 77.0 0.31 0.26 lnsect Screen (default) 02d Window 20d Wall (Right-20)1 352.0 o.32 0.24 lnsect Screen (default) 24d Window 110d Wall (Front-110)1 55.0 0.32 0.24 lnsect Screen (default) 15w Window 1 10d Wall (Frontl 10)1 1 15.5 0.31 0.26 lnsect Screen (default) 17w Window 1 10d Wall (Front-1 10)1 55.0 0.31 0.26 I nsect Screen (derfault) 01 d \l/indow 1 10d Wall (Front-1 10)1 198.0 0.32 0.24 lnsect Screen (default) 01 w Window 1 10d Wall (Front-1 '10)1 55.0 0.31 0.26 lnsect Screen (derfault) Window 200d Wall (Left-200)1 352.0 0.32 0.24 I nsect Screen (de:fault) 09d Window 200d Wall (Left-200)1 93.0 0.32 o.24 lnsect Screen (default) 03w Wndow 200d Wall (Left-200)1 37.2 0.31 o.26 lnsect Screen (default) 04w 200d Wall (Left-200)1 63.2 0.31 0.26 lnsect Screen (delfault) 05d Window 290d Wall (Back-290)1 97.2 4.24 lnsect Screen (delfault) 11d 290d Wall (Back-290)1 55.0 0.32 o.24 lnsect Screen (default) 13 d Window 290d Wall (Back-290)1 275.0 o.32 0.24 lnsect Screen (default) Skylight Skylight Roof (- specify -95)1 90.0 0.39 0.19 08w Wndow 20d Wall2 (Right-20)1 64.0 0.31 0.26 lnsect Screen (default) 07w Window 20d Wall2 (Right-20)1 21.0 0.31 lnsect Screen (default) 16d Window 20d Wall2 (Right-2O)1 33.3 0.32 0.24 lnsect Screen (dc'fault) 08b w Window 20d Wall2 (Right-20)1 72.0 0.31 lnsect Screen (dt-'fault) 17d \Mndow 20d Wall 2 (Right-2O)1 33.3 0.32 0.24 lnsect Screen (default) 08c w Window 110d Wall 2 (Front-110)1 12.0 0.31 lnsect Screen (default) 14a d Window 200d Wall 2 (Left-200)1 152.0 0.32 0.24 lnsect Screen (dr:fault) 15a d Window 200d Wall 2 (Left-200)1 59,9 0.32 0.24 lnsect Screen (default) 14b d Wndow 290d Wall2 (Back-290)1 73.2 0.32 0.24 lnsect Screen (default) 15b d Window 290d Wall2 (Back-290)164.4 0.32 0.24 lnsect Screen (drefault) 08a w \Mndow 290d Wall2 (Back-290)1 12.0 0.31 0.26 lnsect Screen (default) 09w Window 20d Wall 3 (Right-20)1 13.8 0.31 0.26 lnsect Screen (d,efault) 19 d Window 20d Wall 3 (Right-20)1 120.0 0.32 o.24 lnsect Screen (default) CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Projact Name: Madison Lot 688 Custom Residencs Calculation Date/Time: '15:27, I6d, Oct 26, 2016 Calculation Descrlptlon: Title 24 Analysis lnput File Name: Madison Lot 668-Hayer-16.xml CF1R.PRF.O1 Page 6 of 13 Registration Number: 216-N04o04o4A-ooooooooo-0000 CA Building Energy Efficiency Standards - 20L3 Residential Compliance Registration Date/Time: 2016-10-2615:34:05 Report Version - CFlR-040720L6-7 44 HERS Provider: CaICERTS inc Report Generated at: 2015-10-26 LS 28:49 25d Window 0.32 Window 0.26 0.26 0.26 1 CERTIFICATE OF COMPLIANCE . RESIDENTIAL PERFORMANCE COiIPLIANCE METHOD Project Name: Madison Lot 688 Custom Residence Calculation Date/Time: 15:27, t^bd, Oct26,2016 Calculation D$cription: Title 24 Analysis lnput File Nam6: Madison Lot 688-Hayer-16.xml CFlR-PRF-o1 Page 7 ot 13 crry o FLA QUIN IAjuiLDIAJG&SA I- I ETY DpfTCVE EFT F"0j{CONS rR DUCIION BY Registration Number: 216-N04o04o4A-oooooo0oo-0000 CA Building Energy Efficiency Standards - 20L3 Residential Compliance Registration Date/Time: 2016-10-2615:34:05 Report Version - CFlR-040720t6-7 44 HERS Provider: CaICERTS inc. Report Generated at: 2016-10-26 L5:28:49 20d Window 20d Wall 3 (Right-20)1 120.O o.32 0.24 lnsect Screen (default) 10w Window 20d Wall 3 (Right-20)1 13.8 0.31 0.26 lnsect Screen (default) 21 d Window N Wall (- specify --0)1 143.0 0.24 lnsect Screen (default) 22d Window N Wall (- specify --0)1 100.0 0.32 0.24 lnsect Screen (default) 11w Window E Wall (- specify -90)1 5.9 0.31 0.26 lnsect Screen (default) 12w Wndow E Wall (- specify -90)1 20.0 0.31 0.26 lnsect Screen (default) 13w Window S Wall (- specify --180)1 60.0 0.31 0.26 lnsect Screen (default) 14b w Window 200d Wall4 (Left-200)1 42.9 0.31 0.26 lnsect Screen (default) 14aw W Wall (- specify --270)1 29.7 0.31 0.26 lnsect Screen (default) Window 290d Wall4 (Back-290)1 55.0 0.32 0.24 lnsect Screen (default) DOORS 01 02 03 04 Name Side of Building Area (ft2)U-factor Door 57 20d Wall 24.0 0.50 TFi t. 0.32 Window 23d 01 Construction Name Attic Roofgreat room R-38 Roof Flat R-38 Roof Flatl R-21 Wall (W.21 .2x6.1 6) Attic Roofmaster Attic Roofbedroom Attic Roofguest CERTIFICATE OF COiIIPLIANCE - RESIDEI{TIAL PERFORMANCE COMPLIANCE METHOD Project Name: Madison Lot 688 Custom Reriidence Calculatlon Date/Time: 15:27, l Gd, Oct 26, 2016 Calculatlon Description: Title 24 Analysis lnput File Name: Madison Lot 688-Hayer-16.xml OPAQU E SU RFACE CONSTRUCTIONS 02 Surface Type Attic Roofs Ceilings (belovr attic) Cathedral Ceilin 3s Exterior Walls Attic Roofs Attic Roofs Attic Roofs SLAB FLOORS o2 Zone great room master bedroom guest Registration Number: 216-No4o04o4A-ooooo0000- 1000 CA Building Energy Efficiency Standards - 2013 t esidential Compliance Registration Date/Time: 2016-10-26't5:34:05 Report Version - CF 1R-040720L6-7 44 CFlR-PRF.O1 Page I of 13 HERS Provider: CaICERTS inc. Report Generated at: 2016-10-26 L5:28:49 05 06 070304 Winter Design U-value Assembly LayersConstruction Type Framing TotalCavity R-value 0.644 Cavity / Frame: no insul. / 2x4 Top Chrd Roof Deck: Wood Sidi ng/she ath i ng/decking Roofing: Light Roof (Asphalt Shingle)Wood Framed Ceiling 2x4fop Chord ofRoofTruss @ 24 in. O.C.none lnside Finish: Gypsum Board Cavity / Frame: R-9.1 / 2x4 Over Floor Joists: R-28.9 insul.2x4 @ 16 in. O.C.R38 0.025Wood Framed Ceiling lnside Finish: Gypsum Board Cavity / Frame: R-38 / 2x4 Roof De ck : Wood S i d i ng/she ath i ng/dtt cki ng Roofing: Light Roof (Asphalt Shingle)Wood Framed Ceiling 2x4 @ 16 in. O.C.R38 0.041 lnside Finish: Gypsum Board Cavity / Frame: R-21 / 2x6 Exterior Finish: Wood S id i ng/s he ath i ng/d e ck i ngWood Framed Wall 2x6 @ 16 in. O.C.R21 0.066 Cavity / Frcme: no insul. / 2x4 Top Chrd Roof Deck: Wood Siding/sheathing/decking Roofing: Light Roof (Asphalt Shingle)Wood Framed Ceiling 2x4Top Chord ofRoofTruss @ 24 in. O.C.none 0.644 Cavity / Frame: no insul. / 2x4 Top Chrd Roof Deck: Wood Siding/sheathing/decking Roofing: Light Roof (Asphalt Shingle)Wood Framed Ceiling 2x4 Top Chord of Roof Truss @ 24 in. O.C.none 0.644 Cavity / Frame: no insul. / 2x4 Top Chrd Roof Deck: Wood Siding/sheathing/decking Roofing: Light Roof (Asphalt Shingle)Wood Framed Ceiling 2x4 Top Chord of Roof Truss @ 24 in. O.C.none 0.644 01 Name Slab Slab 2 Slab 3 Slab 4 ,07o4050603 Perimeter (ft)Edge lnsul. R-value & Depth Carpeted Fraction HeatedArea (ft2) 0.8 No4920285None 167 None 0.8 lNo1812 None 0.8 No't474 75 No1750153None0.8 BUILDING ENVELOPE . HERS VERIFICATION 01 02 03 04 Quality lnsulation lnstallation (Qll)Quality lnstallation of Spray Foam lnsulation Building Envelope Air Leakage CFM50 Required Not Required Not Required CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORIIIANCE COMPLIANCE iIETHOD Proiect Name: Madison Lot 688 Custom Residence Calculalion DaterTime: 15:27, VGd, Oct26,2O'16 calculatlon Description: Title 24 Analysis lnput File Namc: Madison Lot 68B-Hayer-16.xml CF1R.PRF.O1 Page 9 of 13 Registration Number: 216-No4oo4o4A-ooooooooo-oooo CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2016-10-2615:34:05 Report Version - CFlR-040720L6-7 44 HERS Provider: CaICERTS inc. Report Generated at: 2016-10-26 L5:28:49 WATER HEATING SYSTEMS 01 02 03 04 05 06 Name System Type Distribution Type Water Heater Number of Heaters Solar Fraction (%) DHWSysl-112 DHW Pipe lnsulation, All Lines DHW Heater 1 2 0Yo WATER HEATERS 01 02 03 04 05 05 07 08 Name Heater Element Type Tank Type Tank Volume (gal) Energy Factor or Efficiency Input Rating Tank Exterior lnsulation R-value Standby Loss (Fraction) DHW Heater 1 Natural Gas SmallStorage 50 0.66 40000-Btu/hr 0 0 WATER HEAT!NG . HERS VERIFICATION 01 02 03 04 05 06 07 Name Pipe lnsulation Parallel Piping Compact Distribution Point-of Use Recirculation Control Central DHW Distribution DHWSysl-112 SPACE CONDITIONING SYSTEMS o2 03 04 05 0601 Distribution NameSC Sys Name System Type Heating Unit Name Cooling Unit Name Other Heating and Cooling System Heating Component 1 Cooling Component 1 ] uilHUGF t q rP.l tlt nlr,^ ^ -]-1yffif"''Cooling Component 1:Heating Component 1:Air Distribution System 1:HVAC Fan 1:1 Other Heating and Cooling System Heating Component 2 I I I I Cooling Component 2 ,r!1t4ffi',6frHT flqp'rrs/stemz Cooling Component 2:Heating Component 2:Air Distribution System 2:HVAC Fan2:1 Cooling Component 3:Heating Component 3:Air Distribution System 3:HVAC Fan 3:1 Other Heating and Cooling System Heating Component 3 , I It Cooling Component 3 Fqfrcctusfru 3'/,,", t* LJ Srrfli1q1D'tion Other Heating and Cooling System Heating Component 4 Cooling Component 4 ),tTE HVAC Fan 4 BY-*--- I Air Distribution $ystem , 4Cooling Component 4:Heating Component 4:Air Distribution System 4:HVAC Fan 4:1 ru CERTIFICATE OF COMPLIANCE . RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: Madison Lot688 Custom Residence Calculation Date/Time: 15:27, \ /ed, Oct26,2016 Calculation D$crlption: Title 24 Analysis lnput File Name: Madison Lot 688-Hayer-16.xml Registration Number: 216-N0400404A-000000000-0000 CA Building Energy Efficiency Standards - 20L3 Residential Compliance Registration Date/Time: 2016-10-2615:34:05 Report Version - CFlR-040720L6-7 44 CF1R.PRF.O1 Page 10 of 13 HERS Provider: CaICERTS inc. Report Generated at: 2016-10-26 L5:28:49 HVAC - HEATING UNIT TYPES 01 02 03 Name Type Efficiency Heating Component 1 CntrlFurnace - Fuel-fired central furnace 80 AFUE Heating Component 2 CntrlFurnace - Fuel-fired central furnace 80 AFUE Heating Component 3 CntrlFurnace - Fuel-fired central furnace 80 AFUE Heating Component 4 CntrlFurnace - Fuel-fired central furnace 80 AFUE HVAC . COOLING UNIT TYPES 01 02 03 04 05 06 07 Name System Type Efficiency EER SEER Zonally Controlled Multi-speed Compressor HERS Verification Cooling Component 1 SplitAirCond 12.7 16 Not Zonal Single Speed Cooling Component 1 -hers-cool Cooling Component 2 SplitAirCond 12.7 16 Not Zonal Single Speed Cooling Component 2-hers-cool Cooling Component 3 SplitAirCond 12.7 16 Not Zonal Single Speed Cooling Component 3-hers-cool Cooling Component 4 SplitAirCond 13 16.5 Not Zonal Single Speed Cooling Component 4-hers-cool HVAC COOLING. HERS VERIFICATION 01 02 03 04 05 05 Name Verified Airflow Airflow Target Verified EER Verified SEER Verified Refrigerant Charge Cooling Component 1 -hers-cool Required 350 Required Required Required Cooling Component 2-hers-cool Required 350 Required Required Required Cooling Component 3-hers-cool 350 Required Required Required Cooling Component 4-hers-cool Required 350 Required Required Required Required CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: Madison Lot 688 Custom Residence Calculation Date/Time: 15:27, \ red, Oct 26, 2016 Calculation Desc ption: Title 24 Analysis lnput File Name: Madison Lot 68B-Hayer-16.xml Registration Number: 216-No4oo4o4A-ooooooooo-oooo CA Building Energy Efficiency Standards - 2OL3 Residential Compliance Registration Date/Time: 2016-10-26'15:34:05 Report Version - CFlR-040720L6-7 44 CFlR.PRF-01 Page 11 of 13 HERS Provider: CaICERTS inc. Report Generated at: 2016-10-26 L5:28:49 HVAC . DISTRIBUTION SYSTEMS 01 02 03 04 05 06 07 Name Type Duct Leakage lnsulation R-value Duct Location Bypass Duct HERS Verification Air Distribution System 1 LowllCod Sealed and tested I Conditioned zone (VLL)None Air Distribution System 1-hers-dist Air Distribution System 2 DuctsAttic Sealed and tested B Attic None Air Distribution System 2-hers-dist Air Distribution System 3 DuctsAttic Sealed and tested 8 Aftic None Air Distribution System 3-hers-dist Air Distribution System 4 DuctsAttic Sealed and tested I Attic None Air Distribution System 4-hers-dist HVAC DISTRIBUTION . HERS VERIFICATION 01 02 03 04 05 06 07 08 Name Duct Leakage Verification Duct Leakage Target (%) Verified Duct Location Verified Duct Design Buried Ducts Deeply Buried Ducts Low-leakage Air Handler Air Distribution System 1-hers-dist Required 6.0 Required Not Required Not Required Not Required Air Distribution System 2-hers-dist Required 6.0 Not Required Not Required Not Required Not Required Air Distribution System 3-hers-dist Required 6.0 Not Required Not Required Not Required Not Required Air Distribution System 4-hers-dist Required 6.0 Not Required Not Required Not Required Not Required HVAC - FAN SYSTEMS 04010203 Name Type Fan Power (Watts/CFM)HERS Verification HVAC Fan 1-hers-fanHVAC Fan 1 Single Speed PSC Furnace Fan 0.58 HVAC Fan 2 Single Speed PSC Furnace Fan 0.58 HVAC Fan 2-hers-fan HVAC Fan 3-hers-fanHVAC Fan 3 Single Speed PSC Furnace Fan 0.58 HVAC Fan 4 Single Speed PSC Furnace Fan 0.s8 W-hers-fan HVAC FAN SYSTEMS. HERS VERIFICATION U Ir- ^ r'\.J , I E0102 Name Verified Fan Watt Draw F Required oHVAC Fan 1-hers-fan HVAC Fan 2-hers-fan Required IE RequiredHVAC Fan 3-hers-fan 0.58 CERTIFICATE OF COi'PLIANCE - RESIDENTIAL PERFORIUIANCE COMPLIANCE METHOD Proiect Nams: Madison Lot 688 Custom Residence Calculation Date/Time: 15:27, l bd, Oct 26, 2016 Calculation Descrlptlon: TiUe 24 Analysis Input Flle Name: Madison Lot 68B-Hayer-16.xml CF1R.PRF.O1 Page 12 of '13 HVAC Fan 4-hers-fan Required 0.58 Registration Number: 216-No4oo4o4A-000000000-0000 CA Building Energy Efficiency Standards - 2OL3 Residential Compliance Registration Date/Time: 2016-10-26 15:34:05 Report Version - CFlR-040720t6-7 44 HERS Provider: CaICERTS inc. Report Generated at: 2015-10-26 L5:28:49 lAQ (lndoor Air Quality) FANS 05 0604030201 HERS VerificationIAQ Fan Type IAQ Recovery Effectiveness(%)lAQ WAttS/CFMIAQ CFMDwelling Unit 0 RequiredDefault0.25't44.56SFam lAQVentRpt DOC UMENTATION AUTHOR'S DECLARATION STATEM E NT 1. I certify that this Certificate of Compliance documentation is accurate and complete Documentation Author Signature 7d"zSmDocumentation Author Name: Tim Scott Signature Date: 2016-10-26 15:34:05 Company: Scott Design and Title 24,lnc. CEA/HERS Certification ldentification (lf applicable)Address: 77085 Michigan Drive Phone: 760-200-4780 City/State/Zip: Palm Desert, CA92211 RESPONSIBLE PERSON'S DEGLARATION STATEM ENT I certiry the bllowing under penalty of perjury underthe laws oI the State of Caliturnia:'1. lam eligible under Division 3 of the Busin$s and ProEssions Code to accepl responsibility furlhe building design identified on this Certificate ofCompliance. Regulations. worksheels, calculations, plans and specifcations submitted to the enforcemenl agency for approval with this building permit application. Responsible Designer Signature:7aa,9*Responsible Designer Name Tim Scott Date Signed: 2016-10-26 15:34:05 Company: Scott Design and Title 24,lnc. License na Address: 77085 Michigan Drive Phone: 760-200-4780 City/State/Zip: Palm Desert, CA92211 DATE BY IA Pr IB TI 0B U IU N,D N G &SA FE l-y D EAPPRoVF,Eo DfiCoNSUCoN CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: Madison Lot68B Custom Residence Calculatlon Date/Time: '15:27, l bd, Oct26,2016 C.lculation D8cription: Title 24 Analysis Input File Name: Madison Lot 688-Hayer-16.xml Digla y s:tgned by CaICEBTS. This digital signeturc is ptovided in otdet to secwe the coltent of this rcgistercd document, and in no way implies Registhtion Providet rcsponsibility fq the accuracy ol the infomation. Registration Number: 216-N04oo4o4A-ooooooooo-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2016-10-2615:34:05 Report Version - CFlR-040720L6-7 44 CF1R.PRF.O1 Page 13 of 13 HERS Provider: catCERTS inc. Report Generated at: 2015-10-26 t5:28:49 2013 Low-Rise Residential Mandato Measures Summa Pipe for cooling system lines shall be insulated as specified in $ I 50.0O2A. Piping insulation for steam and hydronic heating systems or hot water systems with pressure > l5 psig shall meet the requirements in TABLE 120.3-A.$ 1s0.00)2c $ 150.0O3: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind. Insulation exposed to weather shall either be rated for outdoor use or installed with a cover suitable for outdoor service. For example, protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation protected as specified or painted with coating that is rvater retardant and provides shielding from solar radiation that degrades the material. $ 1s0.0(i)3A Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space shall have a Class I or Class II vapor retarding facing, or the insulation shall be installed at the thickness that qualifies as a Class I or Class II vapor retarder. $ 150.0u)38: $ I 50.0(n) I $150.0(n)2: Recirculating loops serving multiple dwelling units shallmeet the requirements of $l10.3(c)5 Solar water-heating systems and collectors shall be certified and rated by the Solar Rating and Certification Corporation (SRCC) or by a testing agency approved by the Executive Director.$ 150.0(n)3 Ducts and Fans Nleasures AII air-distribution system ducts and plenums installed are sealed and insulated to meet the requirements of CMC $601.0, $602.0, $603.0, $604.0, $605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition. Supply-air and return-air ducts and plenums are insulated to a minimum installed level of R-6.0 (or higher if required by CMC $605.0) or enclosed entirely in directly conditioned space as confirmed through field verification and diagnostic testing (RA3.1.4.3.8). Connections of metal ducts and inner core of flexible ducts are mechanically fastened. Openings shall be sealed with mastic, tape, or other duct-closure system that meets the applicable requirements of UL l8l, UL l8 I A, or UL l8l B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than t/a inch, the combination of mastic and either mesh or tape shall be used. Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area of the ducts. $150.0(m)l: Factory-Fabricated Duct Systems shall comply with specified requirements for duct construction, connections, and closures; joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and draw bands. $ 150.0(m)2 Field-Fabricated Duct Systems shall comply with requirements for: pressure-sensitive tapes, mastics, sealants, and other requirements specified for duct construction; duct insulation R-value ratings; duct insulation thickness; and duct labeling$ 150.0(m)3-6: All fan systems that exchange air between the conditioned space and the outside of the building must have backdraft or automatic dampers.$ 150.0(m)7 Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers except combustion inlet and outlet air openings and elevator shaft vents.$ 150.0(m)8 Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind but not limited to the following: insulation exposed to weather shall be suitable for outdoor service. For example, protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation. $ 150.0(m)9: $150.0(m)10: Flexible ducts cannot have porous inner cores. When space conditioning systems use forced air duct systems to supply conditioned air to an occupiable space, the ducts shall be sealed and duct leakage tested, as confirmed through field verification and diagnostic testing, in accordance with Reference Residential Appendix RA3. $ 150.0(m)l I Mechanical systems that supply air to an occupiable space through ductwork exceeding l0 feet in length and through a thermal conditioning component, except evaporative coolers, shall be provided with air filter devices that meet the requirements of $ 150.0(m)12. $ 150.0(m)12 Space conditioning systems that utilize forced air ducts to supply cooling to an occupiable space shall have a hole for the placement of a static pressure probe (HSPP), or a permanently installed static pressure probe (PSPP) in the supply plenum. The space conditioning system must also demonstrate airflow > 350 CFM per ton of nominal cooling capacity through the return grilles, and an air-handling unit fan efficacy < 0.58 WCFM as confirmed by field verification and diagnostic testing, in accordance with Reference Residential Appendix RA3. $1s0.0(m)13 Zonally controlled central forced air cooling systems shall be capable of simultaneously delivering, in every zonal control mode, an airflow from the dwelling, through the air handler fan and delivered to the dlvelling, of > 350 CFM per ton of nominal cooling capacity, and operating at an air-handling unit fan efficacy of < 0.58 W/CFM as confirmed by field verification and diagnostic testing, in accordance with Reference Residential Appendix RA3. $ 150.0(m)15 All dwelling units shall meet the requirements of ASHRAE Standard 62.2. Neither window operation nor continuous operation of central forced air system air handlers used in central fan integrated ventilation systems are permissible methods of providing the Whole Buildine Ventilation. $ 150.0(o) Whole Building Ventilation airflow shall be confirmed through field verification and diagnostic testing, in accordance with Reference Residential Appendix RA3.$ 150.0(o)l A Pool and Spa Heating Systems and Equipment Measures: Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency Regulations; an on-offswitch mounted outside of the heater that allows shutting offthe heater without adjusting the thermostat setting; a perrnanent weatherproof plate or card with operating instructions; and shall not use electric resistance heating. $ I 10.4(a) Systems using gas or propane water heaters to serve individual dwelling units shall include: a l20V electrical receptacle within 3 feet of the water heater; a Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the space rvhere the water heater is installed; a condensate drain that is no more than 2 inches higher than the base of the installed water heater, and allows natural draining without pump assistance; and a gas supply line with a capacity of at least 200,000 Btu/hr. 2013 Low-Rise Residential Mandato Measures Summa Any pool or spa heating equipment shall be installed with at least 36 inches of pipe between filter and heater or dedicated suction and retum lines, or built-up connections for future solar heating.li l 10.4(b)l $ I 10.4(b)2: Outdoor pools or spas that have a heat pump or gas heater shall have a cover Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or pro- grammed to run only during off-peak electric demand periods.$ l 10.4(b)3 $l r0.5:Natural gas pool and spa heaters shall not have a continuous burning pilot light. $150.0(p): Residential pool systems or equipment shall meet specified pump sizing. flow rate, piping. filters, and valve requirements. Lighting Measures: $ r l0.e All lighting control devices and systems, ballasts, and luminaires shall meet the applicable requirements of $l10.9. Installed luminaires shall be classified as high-efficacy or low-efficacy for compliance with $150.0(k) in accordance with TABLE 150.0-A or TABLE 150.0-8. as applicable.$ 150.0(k) l A When a high efficacy and low efficacy lighting system are combined in a single luminaire, each system shall separately comply with the applicable provisions of $150.0(k).$ 150.0(k) l B: The wattage and classification of permanently installed luminaires in residential kitchens shall be determined in accordance with $130.0(c). In residentialkitchens, the wattage of electrical boxes finished with a blank cover or where no electricalequipment has been installed, and where the electrical box can be used for a luminaire or a surface mounted ceiling fan, shall be calculated as I 80 watts of lorv efficacy liehtine per electrical box. $r50.0(k)lc: $ 150.0(k) I D: Ballasts for fluorescent lamps rated 13 watts or greater shall be electronic and shall have an output frequency no less than 20 kHz. Permanently installed night lights and night lights integral to installed luminaires or exhaust fans shall be rated to consume no more than 5 watts of power per luminaire or exhaust fan as determined in accordance with $130.0(c). Night lights do not need to be controlled by vacancy sensors. $ 150.0(k)l E Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust hoods) shall meet the applicable requirements of $ 150.0(k).$ 1s0.0(k)r F () 150.0(k)2A: High efficacy luminaires must be switched separately from low efficacy luminaires. $150.0(k)28: Exhaust fans shall be switched separately from lighting systems. $ 150.0(k)2C: Luminaires shall be switched with readily accessible controls that permit the luminaires to be manually switched ON and OFF $ 150.0(k)2D: Controls and equipment are installed in accordance with manufacturer's instructions $150.0(k)2E: No control shall bypass a dimmer or vacancy sensor function if the control is installed to comply with $150.0(k). $ 150.0(k)2F: Lighting controls comply with applicable requirements of $ I 10.9. An Energy Management Control System (EMCS) may be used to comply with dimmer requirements if, it functions as a dimmer according to $l10.9; meets Installation Certificate requirements of $130.4;the EMCS requirements of $130.5; and allother requirements in $ I 50.0(k)2. $ 1s0.0(k)2G An Energy Management Control System (EMCS) may be used to comply with vacancy sensor requirements of $150.0(k) if: it functions as a vacancy sensor according to $l10.9; meets Installation Certificate requirements of $130.4; the EMCS requirements of $ 130.5; and all other requirements in $ 150.0(k)2. $ 150.0(k)2H: A multiscene programmable controller may be used to comply with dimmer requirements of this section if it provides the functionality of a dimmer according to $l10.9, and complies with allother applicable requirements in $150.0(k)2.$ 150.0(k)2r $ I 50.0(k)3A: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy Kitchen lighting includes all permanently installed lighting in the kitchen except internal lighting in cabinets that illuminate only the inside of the cabinets. Lighting in areas adjacent to the kitchen, including but not limited to dining and nook areas, are considered kitchen lighting if they are not separately switched from kitchen lighting. $ 1s0.0(k)3B Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of illuminated cabinet.$ 1s0.0(k)4 A minimum of one high efficacy luminaire shall be installed in each bathroom; and all other lighting installed in each bathroom shall be high efficacy or controlled by vacancy sensors.$ 150.0(k)5: Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and controlled by vacancy sensors.$ 150.0(k)6: Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be high efficacy. or shall be controlled by either dimmers or vacancy sensors.$ r 50.0(k)7 Luminaires recessed into ceilings shall: be listed for zero clearance insulation contact (lC) by Underwriters Laboratories or other nationally recognized testing/rating laboratory; have a label that certifies that the luminaire is airtight with air leakage less than 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; be sealed with a gasket or caulk between the luminaire housing and ceiling, and shall have all air leak paths between conditioned and unconditioned spaces sealed with a gasket or caulk; and allow ballast maintenance and replacement without requiring cutting holes in the ceiling. For recessed compact fluorescent luminaries with ballasts to qualifu as high efficacy for compliance with $ 150.0(k), the ballasts shall be certified to the Energy Commission to comply with the applicable requirements in $l10.9. $ 1s0.0(k)8 For single-family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on the same lot shall be high efficacy, or may be low efficacy if it meets all of the following requirements: i. Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of Items ii or iii below; and ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor, or controlled by a motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and automatically reactivates the motion sensor within 6 hours; and iii. Controlled by one of the following methods: $ r 50.0(k)eA: 2013 Low-Rise Residential Mandato Measures Summa a. Photocontrol not having an override or bypass switch that disables the photocontrol; or b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and which is programmed to automatically turn the outdoor lighting OFF during daylight hours; or c. Energy management control system which meets all of the following requirements: At a minimum provides the functionality of an astronomicaltime clock in accordance with $l10.9; meets the Installation Certification requirements in $130.4; meets the requirements for an EMCS in $130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and, is programmed to automatically turn the outdoor lighting OFF during daylight hours. For low-rise multifamily residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and outdoor lighting for residentialparking lots and residential carports with less than eight vehicles per site shall comply with one of the following requirements: i. Shall comply with $150.0(k)9A; or ii. Shall comply with the applicable requirements in $110.9, $130.0, $130.2. $130.4, $140.7 and til4l.0. $ r50.0(k)9B: For lorv-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by $150.0(k)98 or 150.0(k)9D shall comply with the applicable requirements in $l10.9, $130.0. {i130.2. $130.4, $140.7 and $141.0.$ 150.0(k)ec: Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site shall comply with the applicable requirements in $l10.9, $130.0, $130.2, $130.4, $140.7 and gl4l.0.$ r 50.0(k)eD: Internally illuminated address signs shall comply with $ 140.8; or shall consume no more than 5 watts of power as determined according to $ 130.0(c).$ l s0.0(k) l0 Lighting for residential parking garages for eight or more vehicles shall comply with the applicable requirements for nonresidential garages in $110.9, $130.0, li130.1, $130.4, $140.6. and $141.0.$ 150.0(k)ll: In a low-dse multifamily residential building where the total interior common area in a single building equals 20 percent or less of $ 150.0(k) l2A: the floor are4 permanently installed lighting for the interior common areas in that building shall be high elTicacy luminaires or controlled by an occupant sensor. In a low-rise multifamily residential building rvhere the total interior common area in a single building equals more than 20 percent of the floor area, permanently installed lighting in that building shall: i. Comply with the applicable requirements in $110.9, $130.0, $130.1, S140.6 and $141.0; and ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each space by at least 50 percent. The occupant sensors shallbe capable of turning the light fully On and Off from all designed paths of ingress and egress. $ls0.0(k)r2B Solar Ready Buildings: Single family residences located in subdivisions with ten or more single family residences and where the application for a tentative subdivision map for the residences has been deemed complete, by the enforcement agency, on or after January l, 2014, shallcomply with the requirements of $l10.10(b) through $l10.10(e). $l 10.10(a)l $l10.10(a)2: Low-rise multi-family buildings shall comply with the requirements of $l10.10(b) through $l10.10(d) The solar zone shall have a minimum total area as described below. The solar zone shall comply with access, pathway. smoke ventilation, and spacing requirements as specified in Title 24,Parl9 or other Parts of Title24 or in any requirements adopted by a localjurisdiction. The solar zone total area shallbe comprised of areas that have no dimension less than 5 feet and are no less than 80 square feet each for buildings with roof areas less than or equalto 10.000 square feet or no less than 160 square feet each for buildings with roof areas greater than 10,000 square feet. For single family residences the solar zone shall be located on the roof or overhang of the building and have a total area no less than 250 square feet. For low-rise multi-family buildings the solar zone shall be located on the roof or overhang of the building or on the roof or overhang of another structure located within 250 feet of the building or on covered parking installed with the building project and have a total area no less than l5 percent of the total roof area of the building excluding any skylight area. $ l 10.10(b) l $l 10.10(b)2: All sections ofthe solar zone located on steep-sloped roofs shall be oriented between I l0 degrees and 270 degrees oftrue north No obstructions, including but not limited to, vents, chimneys, architectural features, and roof mounted equipment, shallbe located in the solar zone.$r 10.10(b)3A Any obstruction, located on the roof or any other part of the building that projects above a solar zone shall be located at least twice the distance, measured in the horizontal plane, of the height difference between the highest point of the obstruction and the horizontal projection of the nearest point of the solar zone, measured in the vertical plane. $l10.10(b)38 For areas of the roof designated as solar zone, the structuraldesign loads for roof dead load and roof live load shall be clearly indicated on the construction documents.$r 10.10(b)4 The construction documents shall indicate: a location for inverters and metering equipment and a pathway for routing of conduit from the solar zone to the point of interconnection with the electrical service (for single family residences the point of interconnection will be the main service panel); a pathway for routing of plumbing from the solar zone to the water-heating system. $l 10.10(c) A copy of the construction documents or a comparable document indicating the information from |)l10.10(b) through $l10.10(c) shall be provided to the occupant.$ll0.l0(d) $l10.10(e)l: The main electrical service panel shallhave a minimum busbar rating of 200 amps. The main electrical service panel shall have a reserved space to allow for the installation of a double pole circuit breaker for a future solar electric installation. The reserved space shall be: positioned at the opposite (load) end from the input feeder location or main circuit location, and permanently marked as "For Future Solar Electric". $l10.10(e)2 HVAC SYSTEM HEATING AND GOOLING LOADS SUMMARY Project Name Madison Custom Residence Date 10t26t2016 System Name HVAC 1,2&3grt Floor Area 4,920 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 3 COIL COOLING PEAK COIL HTG. PEAK CFM Sensible Latent CFM Sensible Tota! Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts 5,889 84,985 6,259 1,718 66,870 0 0 0 0 902 35,517 7,693 902 42,23 8,830 -8,830 0 TOTAL SYSTEM LOAD 129,332 13,952 100,276 Heating System Output per System 89,000 Total Output (Btuh)267,000 Output (Btuh/sqft)54.3 Coolinq System Output per System 57,500 Total Output (Btuh)172,500 Total Output (Tons)14.4 Total Output (Btuh/sqft)35.1 Total Output (sqfUTon)342.3 Air System CFM per System 2,000 HVAC EQUIPMENT SELECTION Airflow (cfm)6,000 Carrier 24ANA760/58PH..1 1 0 130,936 29,432 267,000 Total Adjusted System Output (Adjusted for Peak Design conditions) 130,936 29,432 TIME OF SYSTEM PEAK Aug 3 PM Jan 1 AM Airflow (cfm/sqft)1.22 Airflow (cfmlTon)417.4 Outside Air (%)15.0 o/o Outside Air (cfm/sqft)0.18 Note: values above given at ARI conditions HEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak) 26 0F 63 0F 65 0F 107 0F Outside Air 902 cfm Supply Fan 6,000 cfm Heating Coil 107 0F RooM ffi 70 0F 70 0F EI-I I E COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak) 112 t78'F 81t670F 82l68"F 61 /600F Outside Air 902 cfm E I-t I E + Supply Fan 6,000 cfm Cooling Coil 61 / 60.F RooM tr 75 / 65',F 75/650FEIII E I 59.6 % EneryyPro 6.7 by EnergySoft User Number: 6712 RunCode : 201 6-1 0-2671 5 :29 :23 ID Page 22 of 39 267,000 H Eltth HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name Madison Custom Residence Date 10t26t2016 System Name HVAC 4 mstr Floor Area 1,812 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 COIL COOLING PEAK COIL HTG. PEAK CFM Sensible Latent CFM Sensible Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts 2,41 30,431 2,787 29,024 0 1,757 1,426 0 0 332 12,789 2,267 332 15,319 2,943 -2,943 1,757 1,426 TOTAL SYSTEM LOAD 49,677 4,572 44,252 Heating System Output per System 89,000 Total Output (Btuh)89,000 Output (Btuh/sqft) Cooling System Output per System 57,500 Total Output (Btuh)57,500 Total Output (Tons)4.8 Total Output (Btuh/sqft)31.7 Total Output (sqfUTon)378.2 Air System CFM per System 2,000 HVAC EQUIPMENT SELECTION Airflow (cfm)2,000 Carrier 24ANA760/58PH*.1 1 0 44,499 9,681 89,000 Total Adjusted System Output (Adjusted for Peak Design conditions) 44,499 9,681 89,000 TIME OF SYSTEM PEAK Aug 3 PM Jan 1AM Airflow (cfm/sqft)1.'10 Airflow (cfm/Ton)417.4 Outside Air (%)16.6 % Outside Air (cfm/sqft)0.18 Note: values above given at ARI conditions HEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak) 26 0F 620F 64 0F 105 0F Outside Air 332 cfm H EI-t th 105 0F @ Supply Fan 2,000 cfm Heating Coil 69 0F 70 0F EIII E COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak) 112 I 78 0F 82 I 68oF 83 / 69.F 62 I 61 "F Outside Air 332 cfm IE I Supply Fan 2,000 cfm Cooling Coil 63 / 6'1 0F tr 76/660F 75/660FEIIIE I I ! 61.5 %ROOM EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode : 201 6-1 0-26T1 5 :29 :23 ID:Page 23 of 39 49.1 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name Madison Custom Residence Date 10t26t2016 System Name HVAC 5 bed Floor Area 1,474 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 COIL COOLING PEAK COIL HTG. PEAK CFM Sensible Latent CFM Sensible Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts 97 15,949 1,875 15,280 0 921 751 0 0 270 10,485 3,493 270 12,527 0 0 921 751 TOTAL SYSTEM LOAD 28,275 5,368 29,309 Heating System Output per System 71,000 Total Output (Btuh)71,000 Output (Btuh/sqft)48.2 Cooling System Output per System 49,000 Total Output (Btuh)49,000 Total Output (Tons)4.1 Total Output (Btuh/sqft)33.2 Total Output (sqfUTon)361.0 Air System CFM per System 1,600 HVAC EQUIPMENT SELECTION Airflow (cfm)1,600 Carrier 24AN 8748-58 PH""090 38,430 6,315 71,000 Total Adjusted System Output (Adjusted for Peak Design conditions) 38,430 6,315 71,000 TIME OF SYSTEM PEAK Aug 3 PM Jan 1 AM Airflow (cfm/sqft)1.09 Airflow (cfm/Ton)391.8 Outside Air (%)16.9 % Outside Air (cfm/sqft)0.18 Note: values above given at ARI conditions HEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak) 260F 62 0F 620F 104 0F Outside Air 270 cfm Supply Fan 1,600 cfm Heating Coil 103 0F @ 70 "F70 0F EIIIE COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak) 112 I 78 0F 82t67"F 82t670F 59/58oF Outside Air 270 cfm EIITE Supply Fan 1,600 cfm Cooling Coil 60/580F tr 76 t640F 75 t640F ETITE I 54.8 o/o ROOM EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode : 201 6-1 0-26T1 5 :29 :23 ID:Page 24 of 39 429 E Ettt- I HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name Madison Custom Residence Date 10t26t2016 System Name HVAC 6 gst Floor Area 1,750 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 COIL COOLING PEAK COIL HTG. PEAK CFM Sensible Latent CFM Sensible Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts 1,640 23,472 2,226 24,806 0 1,355 1,219 0 0 321 12,416 3,025 321 14,828 0 0 1,355 1,219 TOTAL SYSTEM LOAD 38,598 5,251 42,072 Heating System Output per System 1 10,000 Total Output (Btuh)110,000 Output (Btuh/sqft)62.9 Cooling System Output per System 58,000 Total Output (Btuh)58,000 Total Output (Tons)4.8 Total Output (Btuh/sqft)33.1 Total Output (sqfUTon)362.1 Air System CFM per System 2,000 HVAC EQUIPMENT SELECTION Airflow (cfm)2,000 Carrier 24AN 8760-58PH**1 1 0-20 43,752 9,866 1 10,000 Total Adjusted System Output (Adjusted for Peak Design conditions) 43,752 9,866 1 10,000 TIME OF SYSTEM PEAK Aug 3 PM Jan 1 AM Airflow (cfm/sqft)1.14 Airflow (cfm/Ton)413.8 Outside Air (%)16.0 Yo Outside Air (cfm/sqft)0.18 Note: values above qiven at ARI conditions HEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak) 26 0F 620F 620F 114 0F Outside Air 321 cfm Supply Fan 2,000 cfm Heating Coil 114 0F @ 7A oF69 0F EIIIE COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak) 112 t78"F 81 /670F 81t67"F 61/60"F Outside Air 321 cfm EIII E ------l 62/600F,@ 75 / 65.F Supply Fan 2,000 cfm Cooling Coil 58.6 % 76/650F EIIIE I Ru n Code : 201 6-1 0-2671 5 : 29 : 23 tD.EnergyPro 6.7 by EnergySoft User Number: 6712 Page 25 of 39 t ^.l r.G- ^ \L ^- 535 H Et.tth r---' ROOM LOAD SUMMARY Project Name Madison Cu stom Residence Date 10/26/2016 System Name HVAC1,2&3grt Floor Area 4,920 ROOM LOAD SUMMARY ROOIVI COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK Zone Name Room Name fi/ult.CFM Sensible Latent CFIVI Sensible Latent CFM Sensible great room Great Room Living area h 1 5,889 84,985 6,259 5,889 84,985 6,259 1,718 66,870 PAGE TOTAL TOTAL - . Total includes ventilation load for zonal systems. EnerovPro 6.7 bv EnerqvSoft User Number: 6712 Ru n Code : 201 6-1 0-26T1 5 : 29 :23 ID:Paqe 26 of 39 5,889 84,985 1,71 66,870 5,889 84,985 1,71 66,870 ROOM LOAD SUMMARY Project Name Madison Cu stom Residence Date 10/26/2016 System Name HVAC 4 mstr Floor Area 1 ,812 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK Zone Name Room Name Mult.CFM Sensible Latent CFM Sensible Latent CFM Sensible master Master bedroom 1 2,410 30,431 2,305 2,410 30,431 2,305 787 29,024 PAGE TOTAL TOTAL - * Total includes ventilation load for zonal systems. EnergvPro 6.7 by EnergvSoft User Number: 6712 Ru nC ode : 201 6- 1 0-26T1 5 :29 :23 ID:Pase 27 of 39 2,410 30,431 29,024 2,410 30,431 29,024 ROOM LOAD SUMMARY Project Name M adi son C u stom Resrdence Date 10/26/2016 System Name HVAC 5 bed Floor Area 1 ,474 ROOM LOAD SUMMARY ROO[/ COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK Zone Name Mult CFM Sensible Latent CFM Sensible Latent CFTVI Sensible bedroom Bedrooms 2 & 3 1 978 15,949 1,875 978 15,949 1,875 429 15,280 PAGE TOTAL TOTAL - . Total includes ventilation load for zonal systems EneruvPro 6.7 bv EnerqvSoft User Number: 6712 RunCode: 2016-10-26715:29:23 ID:Paqe 28 of 39 Room Name ROOM LOAD SUMMARY Project Name M adi son Cu stom Resldence Date 10/26/2016 System Name HVAC 6 gsf Floor Area 1,750 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK Zone Name Room Name Mult CFM Sensible Latent CFM Sensible Latent CFM Sensible guest Guest Room quarters 1 1,640 23,472 2,226 1,640 23,472 2,226 535 24,806 PAGE TOTAL TOTAL - * Total includes ventilation load for zonal systems EneruvPro 6.7 bv EnerqvSoft User Number: 6712 RunCode: 2016-10-26715:29:23 ID Pase 29 of 39 1,640 23,472 24,806 1,640 23,472 24,806 ROOM HEATING PEAK LOADS Project Name M adison Custom Residence Date 10/26/2016 ROOM INFORMATION DESIGN CONDITIONS Room Name Great Room Living area Kitchen Floor Area 4,920.0 ftz tndoor Dry Bulb Temperature 70 oF Time of Peak Outdoor Dry Bulb Temperature Jan 1 AM 26 0F Conduction Area U-Value AT "F Btu/hr 4,830.0 90.0 3,466.4 1,636.7 402.9 24.0 perim = 285.0 788.0 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x 0.0260 0.3900 0.0690 0.3200 0.3100 0.5000 0.7300 0.3560 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x Items shown with an asterisk (.) denote conduction through an interior surface to another room Page Total tnfittration:I x x /60] x 44 Fraction 44 44 44 44 44 44 44 0 1.00 1.064 4,920 11.00 0.262x ng x AT 66,870TOTAL HOURLY HEAT LOSS FOR ROOM 30 of 39 R-38 Roof Flat 5,526 Skylight 1,544 R-21 Wall (W.21.2x6.1 6)10,524 tint Metal....32/.24 23,045 dual tint Metal....31 /.26 5,496 Wood Door 528 9,154 *R-0 lnteiorWall 0 55,816 11,053 ROOM HEATING PEAK LOADS Project Name Madison Custom Residence Date 10/26/2016 ROOM INFORMATION DESIGN CONDITIONS Room Name Floor Area lndoor Dry Bulb Temperature Master bedroom 1,912.0 ft2 70 0F Time of Peak Outdoor Dry Bulb Temperature Jan 1 AM 26 0F Conduction Area U-Value AT OF Btu/hr 1,812.0 2,562.9 181.0 516.1 perim = 167.0 596.0 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x 0.0260 0.0690 0.3100 0.3200 0.7300 0.3560 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x 44 44 44 44 44 0 Items shown with an asterisk (-) denote conduction through an interior surface to another room Page Total !nfiltration:I x x 1,812 /60] x 44 e H Fraction 1.0641.00 11.00 0.262 Area x ng Height x AT TOTAL HOURLY HEAT LOSS FOR ROOM 29,024 7 ID 31 39 ROOM HEATING PEAK LOADS Date 10/26/2016 Project Name M adison Custom Residence ROOM INFORMATION DESIGN CONDITIONS Room Name Floor Area lndoor Dry Bulb Temperature Bedrooms 2 & 3 1,474.0 ftz 70 0F Time ol Peak Outdoor Dry Bulb Temperature Jan 1 AM 26 0F Conduction Area U-Value AT OF Btu/hr 1,474.0 1,356.4 27.6 240.0 peim = 75.0 410.0 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x 0.0260 0.0690 0.3100 0.3200 0.7300 0.3560 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x Items shown with an asterisk (.) denote conduction through an interior surface to another room Page Total lnfiltration:I 1.00 x 1.064 x 1,474 x 11.00 x 0.262 /60I x 44 Schedule Fraction Air Sensible Area Ceiling Height ACH AT 44 44 44 44 44 0 TOTAL HOURLY HEAT LOSS FOR ROOM 15,280 326.7 User Number: 6712 6-ID: ( Roof Flat 1,686 R-21 Wall (W.21.2x6.16)4,1 18 wndw dual tint Metal....31 /.26 376 dual tint Metal....3Z.24 3,379 Slab-On-Grade 2,409 *R-0 lnteriorWall 0 11,969 3,311 ROOM HEATING PEAK LOADS Project Name Madison Custom Residence Date 10/26/2016 ROOM INFORMATION DESIGN CONDITIONS Room Name Floor Area lndoor Dry Bulb Temperature Guesf Room quafters 1,750.0 ft2 70 0F Time of Peak Outdoor Dry Bulb Temperature Jan 1 AM 26 0F Conduction Area U-Value AT OF Btu/hr 1,750.0 2,503.5 298.0 158.5 perim = 153.0 410.0 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x 0.0260 0.0690 0.3200 0.3100 0.7300 0.3560 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x 44 44 44 44 44 0 Items shown with an asterisk (") denote conduction through an interior surface to another room Page Total !nfiltration:I 1.00 x 1.064 x 1,750 /60] x 44 Schedule Fraction Air Sensible 11.00 0.262 Area x ing Height x H AT TOTAL HOURLY HEAT LOSS FOR ROOM 24,806 1 39 t RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Madison Custom Residence Date 10/26/2016 ROOM INFORMATION DESIGN CONDITIONS Room Name Great Room Living area Kitchen Floor Area 4,920.0 ft'z Indoor Dry Bulb Temperature 75 oF Outdoor Dry Bulb Temperature Outdoor Wet Bulb Temperature Outdoor Daily Range: 1120F 78 0F 34 0F ue Surfaces Orientation Area U-Factor CLTD1 Btu/hr (E) (N) (N) (E) (s) (W 4,830.0 747.5 24.0 501.5 1,284.6 932.8 788.0 x x x x x x x x x 0.0260 0.0690 0.5000 0.0690 0.0690 0.0690 0.3560 x x x x x x x x x 56.0 25.7 25.7 32.1 28.2 31.8 0.0 Page Total Items shown with an asterisk (") denote conduction through an interior surface to another room.1. Cooling Load Temperature Difference (CLTD) Shaded Fenestration Orientation Area GLF Unshaded Area GLF Btu/hr (E) (N) (N) (N) (E) (E) (E) (E) (E) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 x x x x x x x x x 15.1 15.3 15.8 15.3 15.3 15.8 15.8 15.3 15.8 + + + + + + + + + x x x x x x x x x Page Total Internal Gain Btu/hr 4,920 Occupants Floor Area x x 245 0.50 Btuh/occ. w/sqft lnfiltration:x 0.89 x 248.02 x 37 CFM ELA AT 90.0 159.5 77.0 352.0 55.0 115.5 55.0 198.0 55.0 40.8 18.7 19.6 18.7 28.5 30.1 30.1 28.5 30.1 1.064 TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 84,985 Latent Gain Btu/hr 14.8 Occupants X 155 lnfiltration:4,771 x 0.89 x 248.02 x 0.00376 Air Sensible CFM ELA AW Btuh/occ TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 2,288 EnerqvPro 6.7 bv EnemvSofr User Number: 6712 RunCode: 201 6-1 0-2671 5:29 :23 ID Paqe 34 of 39 M =Or,Or"n, -l 14.8 2, 3,971 ) RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Madison Custom Residence Date 10/26/2016 ROOM INFORMATION DESIGN CONDITIONS Room Name Great Room Living area Kitchen Floor Area 4,920.0 ft2 lndoor Dry Bulb Temperature 75 oF Outdoor Dry Bulb Temperature Outdoor Wet Bulb Temperature Outdoor Daily Range: 1120F 78 0F 34 0F Surfaces Orientation Area U-Factor CLTDl Btu/hr x x x x x x x x x x x x x x x x x x Page Total Items shown with an asterisk (*) denote conduction through an interior surface to another room.1. Cooling Load Temperature Difference (CLTD) Shaded Fenestration Orientation Area GLF Unshaded Area GLF Btu/hr (s) (s) (s) (s) (W (w (w 0.0 0.0 0.0 0.0 0.0 0.0 0.0 x x x x 15.3 15.3 15.8 15.8 15.3 15.3 15.3 + + + + + + + + + x x x x x x x x x Page Total lnternal Gain Btu/hr 14.8 4,920 Occupants Floor Area x x 245 0.50 Btuh/occ. w/sqft lnfiltration:1.064 x 0.89 x x 37 Air Sensible CFM ELA AT 352.0 93.0 37.2 63.2 97.2 55.0 275.0 17.8 17.8 18.5 18.5 26.7 26.7 26.7 TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 84,985 Latent Gain Btu/hr Occupants 14.8 Occupants X 155 !nfiltration:x 0.89 x 248.02 x 0.00s76 Air ble CFM ELA AW 4,771 Btuh/occ. TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 2,288 EnerqvPro 6.7 bv EnemvSoft User Number: 6712 RunCode:2016-10-26715:29:23 lD Paqe 35 of 39 25d 6,263 09d 1, 03w 690 04w 1, 05d 2,591 11d 1,466 13d 21 3,61 248.02 8, 2, 3,971 t RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Madison Custom Residence Date 10/26/2016 ROOM INFORMATION DESIGN CONDITIONS Room Name Floor Area lndoor Dry Bulb Temperature Master bedroom 1,812.0 ft2 75 0F Outdoor Dry Bulb Temperature Outdoor Wet Bulb Temperature Outdoor Daily Range: 1120F 78 0F 34 0F ue Surfaces Orientation Area U-Factor CLTD1 Btu/hr (E) (N) (E) (s) 1,812.0 1,056.4 108.0 568.1 830.4 596.0 x x x x x x x x x 0.0260 0.0690 0.0690 0.0690 0.0690 0.3560 x x x x x x x x x 56.0 25.7 32.1 28.2 31.8 0.0 Page Total Items shown with an asterisk (.) denote conduction through an interior surface to another room 1. Cooling Load Temperature Difference (CLTD) Shaded Fenestration Orientation Area GLF Unshaded Area GLF Btu/hr (N) (N) (N) (N) (N) (E) (s) (s) (w 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 x x x x x x x x x 15.8 15.8 15.3 15.8 15.3 15.8 15.3 15.3 15.3 + + + + + + + + + x x x x x x x x x Page Total I lnternal Gain Btu/hr 5.4 1,812 Occupants Floor Area x x 245 0.50 Btuh/occ w/sqft lnfiltration:x 0.89 x 91.34 x 37 Air CFM ELA AT 64.0 21.0 33.3 72.0 33.3 12.0 152.0 59.9 73.2 19.6 19.6 18.7 19.6 18.7 30.1 17.8 17.8 26.7 1.064 TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 30,431 Latent Gain Btu/hr 5.4 Occupants X 155 lnfiltration:4,771 x 0.89 x 91.34 x 0.00376 Air Sensible CFM ELA AW Btuh/occ TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 843 EneravPro 6.7 bv EneruvSoft User Number: 6712 RunCode : 201 6-1 0-26T1 5:29 :23 ID Paqe 36 of 39 (w Occupants t t RESIDENTIAL ROOM GOOLING LOAD SUMMARY Project Name Madison Custom Residence Date 10/26/2016 ROOM INFORMATION DESIGN CONDITIONS Room Name Floor Area lndoor Dry Bulb Temperature Master bedroom 1,812.0 ft2 75 0F Outdoor Dry Bulb Temperature Outdoor Wet Bulb Temperature Outdoor Daily Range: 1120F 78 0F 34 0F ue Surfaces Orientation Area U-Factor CLTDl Btu/hr x x x x x x x x x x x x x x x x x x Page Total Items shown with an asterisk (.) denote conduction through an interior surface to another room1. Cooling Load Temperature Difference (CLTD) Shaded Fenestration Orientation Area GLF Unshaded Area GLF Btu/hr (W (W 0.0 0.0 x x x x x x x x x 15.3 15.8 + + + + + + + + + 164.4 12.0 x x x x x x x x x 26.7 28.1 Page Total Internal Gain Btu/hr 5.4 1,812 Occupants Floor Area x x 245 0.50 Btuh/occ. w/sqft lnfiltration:x x 91.34 x 37 Air Sensi FM ELA AT 0.891.064 TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 30,431 Latent Gain 5.4 Occupants X 155 lnfiltration:4,771 x 0.89 x 91.34 x 0.00376 Air Sensible CFM ELA AW Btuhiocc. TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 843 EnerqvPro 6.7 bv EneruvSofr User Number: 6712 RunCode:2016-10-26715:29:23 lD:Paqe 37 of 39 15b d 4,382 08a w 338 4, 3, 3,2 Btu/hr 1,462 t RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Madison Custom Residence Date 10/26/2016 ROOM INFORMATION DESIGN CONDITIONS Room Name Floor Area lndoor Dry Bulb Temperature Bedrooms 2 & 3 1,474.0 ftz 75 0F Outdoor Dry Bulb Temperature Outdoor Wet Bulb Temperature Outdoor Daily Range: 1120F 78 0F 34 0F Surfaces Orientation Area U-Factor CLTD1 Btu/hr (E) (N) (E) (s) (W 1,474.0 776.4 100.0 380.0 100.0 410.0 x x x x x x x x x 0.0260 0.0690 0.0690 0.0690 0.0690 0.3560 x x x x x x x x x Page Total Items shown with an asterisk (") denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Shaded Fenestration Orientation Area GLF Unshaded Area GLF Btu/hr (N) (N) (N) (N) 0.0 0.0 0.0 0.0 x x x x x x x x x 1s.8 15.3 15.3 15.8 + + + + + + + + + 13.8 120.0 120.0 13.8 x x x x x x x x x 19.6 18.7 18.7 19.6 Page Total lnternal Gain Btu/hr 4.4 1,474 Occupants Floor Area x x 245 0.50 Btuh/occ. w/sqft lnfiltration:x x 74.31 x 37 M ELA AT 56.0 25.7 32.1 28.2 31.8 0.0 1.064 0.89 TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 15,949 Latent Gain Btu/hr 4.4 Occupants X 155 lnfiltration:4,771 x 0.89 x 74.31 x 0.00376 Air Sensible CFM ELA AW Btuh/occ TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 685 Paqe 38 of 39EnerqvPro 6.7 bv EnerqvSofr User Number:6712 RunCode:2016-10-26T15:29:23 lD: R-38 Roof Flat 2, R-21 Wall (W.21.2x6.16)1 R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) *R-0 lnteriorWall 4, 09w 19d 2,248 20d 2,248 10w 270 2,51 2,61 1 RESIDENTIAL MEASURES SUMMARY RMS.1 Project Name Madison Custom Residence Building Type E Single Family tr Addition Alone tr Multi Family tr Existing+ Addition/Alteration Date 10/26/2016 Project Address Lot 688 - Madison Club La Quinta California Energy Climate Zone CA Climate Zone 15 Total Cond. FloorArea 9,956 Addition n/a # of Units 1 INSULATION Construction Type Cavity Area ff(l Special Features Status Roof Wood Framed Attic R38 9,866 CoolRoof New Wall Wood Framed R21 9,889 New Door Opaque Door - no insulation 24 New S/ab U nheated Slab-on-G rade - no insulation 9,956 Perim = 680'New Demising Wood Framed - no insulation 2,492 New FENESTRATION Orientation Area(t(l U-Fac SHGC Overhang Sidefins Exterior Shades Status Skytight 90.0 0.390 0.19 none none None New Risht (N)818.1 0.320 0.24 none none Bug Screen New Risht (N)261.6 0.310 0.26 none none Bug Screen New Front (E)253.0 0.320 0.24 none none Bug Screen New Front (E)237.5 0.310 0.26 none none Bug Screen New Left (S)656.9 0.320 0.24 none none Bug Screen New Left (S)143.3 0.310 0.26 none none Bug Screen New Rear (W)719.8 0.320 0.24 none none Bug Screen New Rear (W)12.0 0.310 0.26 none none Bug Screen New Right (N)243.0 0.320 0.24 none none Bug Screen New Front (E)25.9 0.310 0.26 none none Bug Screen New Left (S)60.0 0.310 0.26 none none Bug Screen New Rear (W)29.7 0.310 0.26 none none Bug Screen New HVAC SYSTEMS Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status 3 CentralFumace 80% AFUE Split Air Conditioner ,6.0 SEER Sefback New 1 CentralFumace 80% AFUE Split Air Conditioner 76.0 SEER Sefback New 1 CentralFumace 80o/o AFUE Split Air Conditioner 76.0 SEER Setback New HVAC DISTRIBUTION Location Heating Cooling Duct Location Duct R-Value Status HVAC1,2&3grt Ducted Ducted Conditioned 8.0 New HVAC 4 mstr Ducted Ducted Attic 8.0 New HVAC 5 bed Ducted Ducted Attic 8.0 New WATER HEATING Qty. Type Gallons Min. Eff Distribution Status 2 SmallSforage Gas 50 0.66 All Pipes lns New EnemvPro 6.7 bv EnerqvSoft User Number: 6712 RunCode: 201 6-10-2671 5:29:23 ID:Paqe 16 of 39 CERTIFICATE OF COMPLIANCE . RESIDENTIAL PERFORMANCE COMPLIANCE iIETHOD Project Name: Madison Lot 688 Custom Resid€nce caleulatlon DaterTime: 15:27, \ ^9d, oct 26, 20'16 Calculation Description: Title 24 Analysis lnput File Name: Madison Lot 688-Hayer-16.xml CFlR-PRFJO1 Page 13 of 13 DOC U M ENTATION AUTHOR'S DECLARATION STATEM ENT 1. I certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author SignatureDocumentation Author N ame Jon Scott Signature Date: 10t26t2016 Company: Scott Design and Title 24,lnc, CEA/HERS Certification ldentification (lf applicable) 74-818 Velie Way, STE IAddress {e, 7o2 54ooPhonecitv/stateKjt'm Desert, cA 92260 ia:ofState ifornCalfolltheowiunderoftheunderoflawsthecertifongpenaltyperjury, ofCertificate a ce.nonsProfessiodeCbtofobuilddonidentifiedthis1elamibleDunder3ivisiontheofnessBusiandCompliacceptresponsiilityingesignig ofend6ParttheofaCCodlifornia1toconformtheTitleofPart24ianceandSidentifiedcationsthisonCertificaterequirements2thethatfeaturesperformancepecificertiffenergy ons.Regulati comicablereaistentconsthewithinformationotheron documents,of3 pliancebuTheitdifeaturesrofeaturenidentifiedSCertificatethisonprovidedapplngdesigndesigsystem worksheets, calculations, plans and specifications submitted to the enforcement age approval with this building permit application. RESPONSIBLE PERSON'S DECLARATION STATEMENT Responsible Designer Signature:Responsible Designer Name: Hayer Architects Date SignedCompany: Hayer Architects o#j*' License 445 Marine View Ave., Suite 280 $Address: Phone (858) 752-2800 City/State/Zip: Del [\Iar, CA 92014 ^s Registration Number: CA Building Energy Efficiency sJ ,9 ,,.^#r13 Residentiat comptiance Registration Date/Ti me : Report Version - CF 1R-04072016-7 44 HERS Provider: Report Generated at: 2015-10-26 15:28:38 RESIDENTIAL MEASURES SUMMARY RMS.1 Project Name Madison Cu stom Residence Building Type El Single Family tr Addition Alone tr Multi Family tr Existing+ Addition/Alteration Date 10/26/2016 Project Address Lot 688 - Madison Club La Quinta California Energy Climate Zone CA Climate Zone 15 Total Cond. Floor Area 9,956 Addition n/a # of Units 1 INSULATION Construction Type Cavity Area (ffi Special Features Status FENESTRATION Orientation Area(f(l U-Fac SHGC Overhang Sidefins Exterior Shades Status HVAC SYSTEMS Qty. Heating Min. Eff Coolins Min. Eff Thermostat Status 1 CentralFumace 80% AFUE Split Air Conditioner 76.5 SEER Setback New HVAC DISTRIBUTION Location Heating Cooling Duct Location Duct R-Value Status HVAC 6 gst Ducted Ducted Attic 8.0 New WATER HEATING Qty. Type Gallons Min. Eff Distribution Status EnemvPro 6.7 bv EnerqvSoft User Number: 6712 RunCode: 201 6-10-2671 5:29:23 ID,Paqe 17 of 39 2013 Low-Rise Residential Mandatory Measures Summary NqIE; Lov-lise residential buildings subjecl lo the Standatds musl cotlply with all applicable ondatory measures listed, regardless of the used.Review the re,code section r more Building Envelope Measures: $ I 10.6(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage Fenestration products (except field-fabricated windows) have a label listing the certified U-Factor, certified Solar Heat Gain Coefficient (SHGC), and infiltration that meets the requirements of $ I 0- I I I (a).$ I 10.6(a)s $l10.7 Exterior doors and windows are weatherstripped; alljoints and penetrations are caulked and sealed. $l10.8(a): Insulation specified or installed meets Standards for Insulating Material. Indicate type and include on the CF2R. The thermal emittance and aged solar reflectance values of the cool roofing material meets the requirements of {i I 10.8(i) when the installation of a cool roof is specified on the CFIR.$ l r0.8(i): $l10.8(i): A radiant barrier shallhave an emittance of 0.05 or less when the installation of a radiant barrier is specified on the CFIR. Minimum R-30 insulation in wood-frame ceiling; or the weighted average U-factor shall not exceed 0.03 I . Minimum R- l9 in a rafter roof alteration. Attic access doors shallhave permanently attached insulation using adhesive or mechanical fasteners. The attic access shall be gasketed to prevent air leakage. $ 150.0(a) $150.0(b): Loose fill insulation shall conform with manufacturer's installed design labeled R-value. Minimum R-13 insulation in 2x4 inch wood framing wallor have a U-factor of 0.102 or less (R-19 in 2x6 or 0.074 maximum U- factor).$ 150.0(c) $ 150.0(d)Minimum R-19 insulation in raised wood-frame floor or 0.037 maximum U-factor In Climate Zones l4 and l6 a Class II vapor retarder shallbe installed on the conditioned space side of all insulation in all exterior walls, vented attics and unvented attics with air-permeable insulation.$ 1s0.0(g) I In Climate Zones l-16 with unvented crawl spaces the earth floor of the crawl space shall be covered with a Class I or Class II vapor retarder.$ 1s0.0(e)2 In a building having a controlled ventilation crawl space, a Class I or Class ll vapor retarder shall be placed over the earth floor of the crawl space to reduce moisture entry and protect insulation from condensation, as specified in the exception to Section 150.0(d). Slab edge insulation shall: have a water absorption rate, for the insulation material alone without facings, no greater than 0.37o; have water vapor permeance rate is no greater than 2.0 perm/inch, be protected from physical damage and UV light deterioration; and when installed as part of a heated slab floor meets the requirements of $l10.8(g). Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors shall have a maximum U- factor of 0.58; or the weighted average U-factor of all fenestration shall not exceed 0.58.$ 150.0(q) Fireplaces, Decorative Gas Appliances and Gas Log Measures: $ 150.0(e)lA: Masonry or factory-built fireplaces have a closable metal or glass door covering the entire opening of the firebox. Masonry or factory-built fireplaces have a combustion outside air intake, which is at least six square inches in area and is equipped with a readily accessible, operable, and tieht-fitting damper or a combustion-air control device.$ 150.0(e) I B: $150.0(e)lC: Masonry or factory-built fireplaces have a flue damper with a readily accessible control. Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside of the building. are prohibited.$ 150.0(e)2 Space Conditioning, Water Heating and Plumbing System Measures: $l10.0-$l t0.3: fryAC equipment, water heaters, shou€rheads, faucets and all other regulated appliances are certified to the Energy Commission Water heating recirculation loops serving multiple dwelling units meet the air release valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of $ I 10.3(c)5.$ I 10.3(c)5 Continuously burning pilot lights are prohibited for natural gas: fan-type central furnaces, household cooking appliances (appli- ances without an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and spa heaters. $l l0.s Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA using design conditions specified in $150.0(h)2.$ 150.0(h) r : Installed air conditioner and heat pump outdoor condensing units shall have a clearance of at least five feet from the outlet of any dryer vent.$ 150.0(h)3A: $ 150.0(i): Heating systems are equipped with thermostats that meet the setback requirements of $ I 10.2(c) Storage gas water heaters with an energy factor equal to or less than the federal minimum standards shall be externally wrapped with insulation having an installed thermal resistance of R-12 or greater.$150.00lA: Unfired hot water tanks, such as storage tanks and backup storage tanks for solar water-heating systems, have R-12 external insulation or R-16 internal insulation where the internal insulation R-value is indicated on the exterior of the tank.$ r 50.00)l B: For domestic hot water system piping, whether buried or unburied: the first 5 feet of hot and cold water pipes from the storage tank, all piping with a nominal diameter of 314 inch or larger, all piping associated with a domestic hot water recirculation system regardless of the pipe diameter, piping from the heating source to storage tank or between tanks, piping buried below grade, and all hot water pipes from the heating source to kitchen fixtures must be insulated according to the requirements of TABLE 120.3- A. $ l s0.0o2A: All domestic hot water pipes that are buried below grade must be installed in a water proof and non-crushable casing or sleeve that allows for installation, removal, and replacement of the enclosed pipe and insulation.$ 150.0(i)28 $ 150.0(e)3: $ 1s0.0(l): ; !RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Madison Custom Residence Date 10/26/2016 ROOM INFORMATION DESIGN CONDITIONS Room Name Floor Area lndoor Dry Bulb Temperature Guesf Room quarters 1,750.0 ftz 75 0F Outdoor Dry Butb Temperature Outdoor Wet Bulb Temperature Outdoor Daily Range: 1120F 78 0F 34 0F ue Surfaces Orientation Area U-Factor CLTDl Btu/hr (E) (N) (E) (s) (s) (w (W 1,750.0 567.0 784.1 750.0 173.1 68.3 161.0 410.0 x x x x x x x x x 0.0260 0.0690 0.0690 0.0690 0.0690 0.0690 0.0690 0.3560 x x x x x x x x x Page Total Items shown with an asterisk (.) denote conduction through an interior surface to another room1. Cooling Load Temperature Ditference (CLTD) Shaded Fenestration Orientation Area GLF Unshaded Area GLF Btu/hr (N) (N) (E) (E) (s/ (s) (w (W 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 x x x x x x x x x 15.3 15.3 15.8 15.8 15.8 15.8 15.8 15.3 + + + + + + + + + x x x x x x x x x Page Total lnternal Gain Btu/hr 5.2 1,750 Occupants Floor Area x x 245 0.50 Btuh/occ. w/sqft lnfiltration:1.064 x 0.89 x 88.22 x 37 Air Sensible CFM ELA AT 56.0 23.0 33.0 26.0 28.2 33.0 31.8 0.0 143.0 100.0 5.9 20.0 60.0 42.9 29.7 55.0 15.3 15.3 31.3 31.3 15.9 18.5 31.3 26.7 TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 23,472 Latent Gain Btu/hr Occupants 5.2 Occupants X 155 Infiltration:4,771 x 0.89 x 88.22 x 0.00376 Air Sensible CFM ELA AW Btuh/occ TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 814 EnerqvPro 6.7 bv EnerovSofi User Number: 6712 Ru n Code : 201 6-1 0-26T1 5 : 29 :23 ID Paqe 39 of 39 a R-38 Roof Flat 2, R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16)1 R-21 Watl (W.21.2x6.16)1 R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) *R-0 lnterior Wall 21 d 2,189 22d 1,531 11w 185 12w 626 13w 955 14b w 795 14a w 929 23d 1,466 I, 1 3,