BRES2015-0302 Title 24I ,tttl
BUILDING ENERGY ANALYSIS REPORT
PROJECT:
Ratpack Residence
53-525 Humbolt Blvd.
La Quinta, CA92253
Project Designer:
Gordon Stein
55-053 Sorrel Court
lndio, CA 92201
(760) 773-4488
Report Prepared by:
Tim Scott
Scott Design and Title t o F LA OUINTA74-81 8 Velie Way, Su t6H
& SAFETY DEPT.Palm Desert I CA 92 60rulr- DING VEDb[-*r P R(760) 200-4780
f :)ii COf'ls UCTION
r(
Job Number:
RECEIVED
Date:
1t6t2017
JAN I O ZAfi
^^__clTY o!: tJ\ Quifrj.tacoMMUNtw Dgr'ELopnaeur
The EnergyPro computer program has been used lo perform lhe calculations summarized in this compliance report. This program has approval and is
authorized by the Califomia Energy Commission for use wilh both the Residential and Nonresidential 2013 Building Energy Efficiency Standards.
This program developed by Energysofr, LLC - vvlwv.energysofr.com. A n
ttID:EnergyPro 6.7 by EneryySoft User Number: 6712 , -x!l,
TABLE OF CONTENTS
Cover Page
Table of Contents
Form CF-1 R-PRF-O1 -E Certificate of Compliance
Form RMS-1 Residential Measures Summary
Form MF-1 R Mandatory Measures Summary
HVAC System Heating and Cooling Loads Summary
Room Load Summary
Room Heating Peak Loads
Room Cooling Peak Loads
1
2
3
19
21
25
31
37
44
'!
energvPr*l{y EnergySoft Job Number: lD User Number: 67'12
I?,
.L ,
J
CERTIFICATE OF COiIPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Prclect Name: Ratpack Calculatlon DaterTime: 14:50, Fi, Jan 06, 2017
Calculation D$crlptlon: Title 24 Analysis Input File Nam€: Ratpack-Stein-15.xml
CFl R.PRF-01
RECEIVED
Page 1 of 16
Registration Number: 215-No2o22B5D-ooooooooo-o0oo
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time: 2017-01-06 15:04:04
Report Version - CF 1R-040720L6-7 44
HERS Provider: CaICERTS inc.
Report Generated at: 20L7 -0L-05 14:5L:57
JAI\ I U LUIIGENERAL INFORMATION
Project Name Ratpack ,\r.Fl, AE I A rrl llttTA01
Title 24 Analysis
\rl I I vr
COMMUNITY DEVELOPMENT02Calculation Description
Project Location 53-525 Humbolt Blvd.03
Compliance 2015La Quinta 05 Standards Version04City
--'-BEMCmpMgr 2013-4 (744)07 Compliance Manager Version06Zip Code 92253
Software Version E LJEnergyPro 6.6cz150908Climate Zone
'll>s?-80 n11Front Orientation (deg/Cardinal)10 Building Type Single Family
w)7 LJr3T1 =13 Number of Dwelling Units 1Newly Constructed'12 Project Scope
Number of Zones 7 s qi-ok87771514Total Cond. Floor Area (ft2)
1 \st ,il =1flTr877717Number of Stories16Slab Area (ft2)
19 Natural Gas Available Yes18Addition Cond. Floor Area N/A
C
ooCOMPLIANCE RESULTS
2120 Glazing Percentage (%)37.60/oAddition SIab Area (ft2)N/A
4
I
-o
t01Building Complies with Computer Performance
IF*t provider.02 This bulldlng lncorpoEtes featurss that r€qulre fleld tgstlng and/or vsrificdion by a certltled HERS rater undet the supervision of a CEc-approved
03 This building incorporates one or more Special Features shown below
ENERGY USE SUMMARY
04 05 06 07 08
Energy Use (kTDV/ft2-yr)Standard Design Proposed Design Compliance Margin Percent lmprovement
Space Heating 2.90 3.61 -0.71 -24.5o/o
Space Cooling 106.85 99.57 7.28 6.8%
IAQ Ventilation 0.71 0.71 0.00 0.0%
Water Heating 2.92 3.26 -0.34 -11.60/o
Photovoltaic Offset 0.00 0.00
Compliance Energy Total 113.38 107.15 5.23 s.5%
I
I
CERTIFICATE OF COi'PLIANCE - RESIDENTIAL PERFORi'ANCE COMPLIANCE METHOD
Prcroct Name: Ratpack Calculetion Data/Tlme: 14:50, Fri, Jan 06, 2017
Calculation Descrlptlon: Title 24 Analysis lnput Flle Name: Ratpack-Stein-15.xml
CFlR-PRF.O1
Page 2 ot 16
REQUIRED SPECIAL FEATU RES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
. Cool roof. Window overhangs and/or fins. Exposed slab floor in conditioned zone
HERS FEATURE SUMMARY
provided in the building components tables below.
Bu ilding-level Verifications:. High Quality lnsulation Installation (Qll). lAQ mechanica! ventilation
Coolin g System Verifications:. ilinimum Airflow. Verified EER. Verified SEER. Refrigerant Charge. Fan Efficacy Watts/CFM
HVAC Distribution System Verifications:. Duct Sealing. Ducts located entirely in conditioned space
Domestic Hot Water System Verifications:. -- None --
ENERGY DESIGN RATING
on-site rene\,\rable energy system.
Reference Energy Use Energy Design Rating Margin Percent !mprovement
Total Energy (kTDV/f2-yr).147.12 140.89 6.23 4.2%
* includes calculated Appliances and Miscellaneous Energy Use (AMEU)
Registration Number: 21s-N0202285D-oooooo000-0000
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time: 2017-01-06't5:04:04
Report Version - CF LR-040720L6-7 44
HERS Provider: CaICERTS inc.
Report Generated at: 2017-01-06 L4:51:57
BU!LDING . FEATU RES I NFORII,IATION
01 02 03 04 05 06 07
Project Name Conditioned Floor Area (ft2)
Number of Dwelling
Units Number of Bedrooms Number of Zones
Number of Ventilation
Cooling Systems
Number of Water
Heating Systems
Ratpack 8777 1 6 7 5 1
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE iIIETHOD
Proiect Neme: Ratpack calculation DaterTlme: 14:50, Fri, Jan 06, 20'17
Calculatton D$crlptlon: Title 24 Analysis lnput File Name: Ratpack-Stein-'l5.xml
CF1R.PRF.O1
Page 3 of 16
ZONE INFORMATION
01 02 03 04 05 06 07
Zone Name Zone Type HVAC System Name
Zone Floor Area
(ft2)
Avg. Ceiling
Height Water Heating System 1 Water Heating System 2
Suite 1 Conditioned HVAC 1 mstrl 862 9 DHW Sys 1
great room Conditioned HVAC 2,3&42 4274 I DHW Sys 1
2 Conditioned HVAC 5 & 63 569 9 DHW Sys 1
3 Conditioned HVAC 5 & 63 569 I DHW Sys 1
guest-4 Conditioned HVAC 64 660 9 DHW Sys 1
2 Car Garage Conditioned HVAC 75 1262 I DHW Sys 1
Cart Garage Zone Conditioned HVAC 86 581 9 DHW Sys 1
CITY
BUILDI
AT
Foil
DATE
BY CaICERTS
n L4
)E
EU\)
F a U I N
&A F TY D Ei-l
Y Dr!-')n t,
TJ \-,T,o N
IA
Pr
Registration Number: 21s-N0202285D-000000000-0000
CA Building Energy Efficiency Standards - 2OL3 Residential Compliance
Registration Date/Time: 2017-01-06 1 5:04:04
Report Version - CF 1R-040720L6-7 44 Report Generated at: 20L7
Lf,
q I
OPAQUE SURFACES
01 o2 03 04 05 06 07 08
Name Zone Construction Azimuth Orientation Gross Area (ft2)Window & Door Area (ft2)Tilt (deg)
80d Wall R-21 Wall (W.21.2x6.16)80 Front 150 0 90
170d Wall Suite 1 R-21 Wall (W.21.2x6.16)170 Left 720 125.8 90
260d Wall Suite 1 R-21 Wall (W.21.2x6.16)260 Back 440 133 90
350d Wall Suite 1 R-21 Wall (W.21.2x6.16)350 Right 900 106.2 90
Roof R-38 Suite 1 R-38 Roof Attic 862
80d Wall2 great room R-21 Wall (W.21.2x6.16)80 Front 1 056 575.6 90
17OdV,'lall2 great room R-21 Wall (W.21.2x6. 1 6)170 Left 575 511.055 90
260d Wall2 great room R-21 Wall (W.21.2x6. 1 6)260 Back 952 715.863 90
350d Wall2 great room R-21 Wall (W.21.2x6. 1 6)350 Right 432 272.3 90
Roof R-38 2 great room R-38 Roof Attic 4274
170d Wall 3 2 R-21 Wall (W21.2x6.16)170 Left 230 108.2 90
260d Wall3 2 R-21 Wall (W.21.2x6.16)260 Back 320 108 90
350d Wall3 2 R-21 Wall (W.21.2x6.16)350 Right 230 88 90
Roof R-38 3 2 R-38 Roof Attic 569
80d Wall 3 3 R-21 \ /all (W.21.2x6.16)Front 320 88 90
170d Wall4 3 R-21 Watl (W.21.2x6. 1 6)170 Left 230 108.123 90
350d Wall4 3 R-21 Wall (W.21.2x6.16)350 Right 230 88 90
Roof R-38 4 3 R-38 Roof Attic
80d Wall4 guest-4 R-21 Wall (W.21.2x6. 16)80 Front 200 0 90
170d Wall5 guest-4 R-21 Wall (W.21.2x6.16)170 Left 110.15 90
260d Wall4 guest-4 R-21 Wall (W.21.2x6.16)260 Back 200 88.021 90
350d Wall5 guest-4 R-21 Wall (W.21.2x6.16)350 Right 330 77.988 90
Roof R-38 5 guest-4 R-38 Roof Attic 660
80d Wall5 2 Car Garage R-21 Wall (W.21 .2x6.16)80 Front 476 24 90
170d Wall6 2 Car Garage R-21 Wall (W.21.2x6.16)170 Left 70 0 90
260d Wall 5 2 Car Garage R-21 Wall (W.21.2x6. 1 6)260 Back 406 286.2 90
350d Wall6 2 Car Garage R-21 Wall (W.21.2x6. 16)350 Right 255 0 90
Roof R-38 6 2 Car Garage R-38 Roof Attic 1262
80d Wall6 Cart Garage Zone R-21 Wall (W.21.2x6.16)80 Front 190 0 90
170d WallT Cart Garage Zone R-21 Wall (W.21.2x6.16)170 Left 35 0 90
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: RaFack Calculatlon DaterTime: 14:50, Fd, Jan 06,2017
Calculatlon Descrlptlon: Title 24 Analysis lnput File Name: Ratpack-Stein-'l5.xml
CFlR-PRF-01
Page 4 of 16
Registration Number: 2is-No2o2215D-000000000-0000
CA Building Energy Efficiency Standards - 2Ot3 Residential Compliance
Registration Date/Time: 2017-01-0615:04:04
Report Version - CFlR-04072016-7 44
HERS Provider: CaICERTS inc.
Report Generated at: 20L7 -0L-05 14:51 :57
Suite 1
80
569
330
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COiIPLIANCE METHOD
PrcJect Name: RaFack Calculation DatelTlme: 14:50, Fri, Jan 06, 2017
Calculation Descriptlon: Title 24 Analysis Input File Name: Ratpack-Stein-15.xml
CFlR-PRF.O1
Page 5 of 16
260d Wall6 Cart Garage Zone R-21 Wall (W.21.2x6.16)260 350 110.4 90
350d WallT Cart Garage Zone R-21 Wall (W21.2x6.16)350 Right 278 78.4 90
Roof R-38 7 Cart Garage Zone R-38 Roof Attic 581
ATT!C
01 02 03 04 05 06 07 08
Name Construction Type Roof Reflectance Roof Emittance Radiant Barrier Cool Roof
Attic Suite 1 Attic RoofSuite 1 Ventilated 3 0.62 No Yes
Attic great room Attic Roofgreat room Ventilated 3 0.62 0.83 No Yes
Attic 2 Attic Roof2 Ventilated 3 0.62 0.83 No Yes
Attic 3 Attic Roof3 Ventilated 3 0.62 0.83 No Yes
Attic guest-4 Attic Roofguest4 Ventilated 3 0.62 0.83 No Yes
Attic 2 Car Garage Attic Roof2 Car Garage Ventilated 3 0.62 No Yes
Attic Cart Garage Zone Attic RoofCart Garage Zone Ventilated 3 0.62 0.83 No Yes
CITY OF LA QUINTABUlL.Dirv*G &SAFETY DEPTA:]VEDl- t-
H
FCH Coi\js "I-RUCTION
BY
Registration Number: 21s-No2o2215D-000000000-0000
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time: 2017-01-0o'15:04:04
Report Version - CFlR-040720L6-7 44
a tr
Report Generated at: 2017 -0L-06 14:51
inc.
Back
Roof Rise
0.83
0.83
WINDOWS
01 02 03 04 05 06 07 08 09 t0
Name Type Surface (Orientation-Azimuth)width (ft)Height (ft)
Multipli
er
Area
(ft2)U-factor SHGC Exterior Shading
D2 Window 170d Wall (Left-170)4.1 10.0 1 41.0 0.37 0.26 lnsect Screen (default)
22 Window 170d Wall (Left-170)5.3 10.0 1 53.0 0.46 0.31 lnsect Screen (default)
D3 Wndow 170d Wall (Left-170)10.6 3.0 1 31.8 0.37 0.26
21 Window 260d Wall (Back-260)13.3 10.0 1 133.0 0.31 lnsect Screen (default)
D1 350d Wall (Right-350)1 30.2 0.37 0.26 lnsect Screen (default)
20 Window 350d Wall (Right-350)1 64.0 0.46 0.31 I nsect Screen (default)
c2 Window 350d Wall (Right-350)1 12.0 0.50 0.20 I nsect Screen (default)
01 80d Wall 2 (Front80)11.0 1 55.0 0.94 0.49
58 Window 80d Wall 2 (Front-80)21.5 10.0 2.2 473.0 0.31 lnsect Screen (default)
G4 80d Wall 2 (Front-8O)1 47.6 0.37 o.26 lnsect Screen (default)
o4 Window 1 178.O 0.31 lnsect Screen (default)
A Window 170d Wall2 (Left-170)5.0 11.0 2.335 128.4 0.37 0.26 lnsect Screen (default)
23 Window 170d Wall2 (Left-170)7.O 11.0 1 77.0 0.76 0.18 lnsect Screen (default)
E2 Window 6.3 15.1 1 95.1 0.37 0.26 lnsect Screen (default)
G2 170d Wall2 (Left-170)1 16.1 0.37 0.26 lnsect Screen (default)
G3 Window 170d Wall2 (Left-170)1 16.4 0.26 lnsect Screen (default)
Window 260d Wall2 (Back-260)473.O 11.O 0.091 473.5 0.46 0.31 lnsect Screen (default)
G1 Window 260d Wall2 (Back-260)1 47.6 0.37 0.26 lnsect Screen (default)
E1 Window 260d Wall2 (Back-260)12.9 15.1 1 194.8 0.37 0.26 lnsect Screen (default)
B Window 350d Wall 2 (Right-350)1 177.0 0.37 0.26 lnsect Screen (default)
G5 Window 350d Wall 2 (Right-350)1 55.0 0.37 I nsect Screen (default)
G6 Window 350d Wall 2 (Right-350)1 23.8 0.37 0.26 lnsect Screen (default)
C1 Window 350d Wall 2 (Righr350)1 16.5 0.50 o.20 lnsect Screen (default)
32 Window 170d Wall 3 (Left-170)1 78.0 0.46 0.31 lnsect Screen (default)
F1 Window 170d Wall 3 (Left-170)1 30.2 0.37 0.26 lnsect Screen (default)
28 Window 260d Wall 3 (Back-260)10.8 10.0 1 108.0 0.46 0.31 lnsect Screen (default)
27 Window 350d Wall 3 (Right-3sO)5.3 10.0 1 53.0 0.46 0.31 lnsect Screen (default)
26 Window 350d Wall 3 (Right-350)3.5 10.0 1 35.0 0.46 0.31 lnsect Screen (default)
37 Window 80d Wall 3 (Front-80)8.8 10.0 1 88.0 0.46 0.31 lnsect Screen (default)
CERTIFICATE OF COMPLIANCE . RESIDENTIAL PERFORMANCE COMPLIANCE I'ETHOD
Project Name: Ratpack Calculation Date/Tlme: 14:50, Fri, Jan 06, 2017
Calculation D$cription: Title 24 Analysis Input Flle Name: Ratpack-Stein-15.xml
CF1R.PRF.O1
Page 6 of 16
Registration Number: 21s-Nozo2za5D-ooooooooo-oooo
CA Building Energy Efficiency Standards - 20L3 Residential Compliance
Registration Date/Time: 2017-01-0615:04:04
Report Version - CF 1R-040720L6-7 44
HERS Provider: CaICERTS inc.
Report Generated at: 2OL7 -0L-06 14:51 :57
lnsect Screen (default)
0.46
Window
Window 5.0 lnsect Screen (default)
0.46
Window
170d Wall2 (Left-170)0.46
170d Wall2 (Left-170)
Window
o.37
24
0.26
CERTIFICATE OF COMPLIANCE . RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Proiect Name: Ratpack Calculation Date/Time: 14:50, Fri, Jan 06, 2017
Calculation D6cription: Title 24 Analysis Input File Name: Ratpack-Stein-'15.xml
CF1R.PRF.O1
Page 7 ot 16
Ci Y CF Lq QUI NIABUS,AFETY DEPIrCVED
au
r
FC;I CC,i.JS TRUCTION
DAT cBy
Registration Number: 215-No2o228sD-000000000-0000
CA Building Energy Efficiency Standards - 20L3 Residential Compliance
Registration Date/Time: 2o'17-01-oo 15:04:04
Report Version - CF 1R-040720L5-7 44
HE
F2 Window 170d Walla (Left-170)15.0 10.0 0.201 30.2 0.37 0.26 lnsect Screen (default)
42 Window 170d Wall4 (Left-170)7.9 10.0 0.987 78.0 0.46 0.31 lnsect Screen (default)
35 Wndow 350d Wall4 (Right-350)3.5 10.0 1 35.0 0.46 0.31 lnsect Screen (default)
36 \Mndow 350d Wall4 (Right-350)5.3 10.0 1 53.0 0.46 0.31 lnsect Screen (default)
50 Window 170d Wall5 (Left-170)8.0 10.0 1 80.0 0.46 0.31 lnsect Screen (default)
F3 Window 170d Wall5 (Left-170)15.0 10.0 o.201 30.2 0.37 lnsect Screen (default)
45 Wndow 260d Wall4 (Back-260)8.9 10.0 0.989 88.0 0.46 0.31 lnsect Screen (default)
44 Window 350d Wall 5 (Right-350)4.4 10.0 o.977 43.0 0.46 0.31 lnsect Screen (default)
43 Window 350d Wall 5 (Right-350)3.5 10.0 1 35.0 0.46 0.31 lnsect Screen (default)
DOORS
01 02 03 04
Name Side of Building Area (ft2)U-factor
Door 54 80d Wall5 24.0 0.50
Door 55 260d Wall 5 178.2 0.08
Door 56 260d Wall 5 108.0 0.08
Door 08 260d Wall6 110.4 0.08
Door 09 350d Wall 7 78.4 0.08
Report Generated at: 2017-01-06 L4:5t:57
c.
r
0.26
OVERHANGS AND FINS
01 o2 03 04 05 06 07 08 09 10 11 12 13 14
Overhang Left Fin Right Fin
Window Depth Dist Up
Left
Extent
Right
Extent Flap Ht.Depth Top Up Distl Bot Up Depth Top Up Dist R Bot Up
D2 4 0.1 4 4 0 0 0 0 0 0 0 0 0
22 4 0.1 4 4 0 0 0 0 0 0 0 0 0
D3 4 0.1 4 4 0 0 0 0 0 0 0 0 0
21 4 0.1 4 4 0 0 0 0 0 0 0 0 0
01 4 0.1 4 4 0 0 0 0 0 0 0 0 0
58 12 0.1 12 12 0 0 0 0 0 0 0 0 0
A 4 0.1 4 4 0 0 0 0 0 0 0 0 0
23 8 0.1 8 8 0 0 0 0 0 0 0 0 0
E2 10 0.1 10 10 0 0 0 0 0 0 0 0
24 12 0.1 12 12 0 0 0 0 0 0 0 0 0
E1 10 0.1 10 10 0 0 0 0 0 0 0 0 0
28 4 0.1 4 4 0 0 0 0 0 0 0 0 0
27 4 0.1 4 4 0 0 0 0 0 0 0 0 0
26 8 0.1 B 8 0 0 0 0 0 0 0 0 0
37 0 0 0 0 0 0 0 0 0 0 0 0 0
F2 0 0 0 0 0 0 0 0 0 0 0 0 0
42 10 0.1 10 10 0 0 0 0 0 0 0 0 0
35 8 0.1 8 I 0 0 0 0 0 0 0 0 0
36 4 0.1 4 4 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0 0 0 0
F3 0 0 0 0 0 0 0 0 0 0 0 0 0
45 4 0.1 4 4 0 0 0 0 0 0 0 0 0
44 4 0.1 4 4 0 0 0 0 0 0 0 0 0
43 4 0.1 4 4 0 0 0 0 0 0 0 0 0
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Ratpack Calculation Date/Time: 14:50, Fri, Jan 06,2017
Calculation Descrlptlon: Title 24 Analysis Input File Name: Ratpack-Stein-15.xml
CFlR-PRF-01
Page 8 of 16
Registration Number: 21s-Nozo2zlsD-ooooooooo-oooo
CA Building Energy Efficiency Standards - 2OL3 Residential Compliance
Registration Date/Time: 2017-01-0615:04:04
Report Version - CF 1R-04072OL6-7 44
HERS Provider: CaICERTS inc.
Report Generated at: 2017 -0L-06 14:51 :57
0
50
CERTIFICATE OF COiIPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE iIETHOD
Prcrect Name: Ratpack calculation Dats/Time: 14:50, Fri, Jan 06, 20'17
Calculstion D$crlptlon: Title 24 Analysis Input File Name: Ratpack-Stein-'l5.xml
OPAQU E SU RFACE CONSTRUCTIONS
01 03 o4 05 06
Construction Name Surface Type Construction Type Framing
TotalCavity
R-value
Winter Design
U-value Assembly Layers
Attic RoofSuite'1 Attic Roofs Wood Framed Ceiling
2x4 fop Chord of Roof Truss @ 24
in. O.C.none 0.644
Cavity / Frame: no insul. / 2x4 Top Chrd
Roof Deck: Wood Siding/sheathing/decking
Roofing: Light Roof (Asphalt Shingle)
R-38 Roof Attic
Ceilings (below
attic)Wood Framed Ceiling 2x4 @ 16 in. O.C R38 0.025
lnside Finish: Gypsum Board
Cavity / Frame: R-9.1 / 2x4
Over Floor Joists: R-28.9 insul.
R-21 Wall (W.21 .2x6. 1 6)Exterior Walls Wood Framed Wall 2x6 @ 16 in. O.C R21 0.066
lnside Finish: Gypsum Board
Cavity / Frame: R-21 / 2xO
Exterior Finish:Wood
S id i n g/sh e ath i n g/de ck i ng
Attic Roofgreat room Attic Roofs Wood Framed Ceiling
2x4 Top Chord of Roof Truss @ 24
in. O.C.none 0.644
Cavity / Frame: no insul. / 2x4 Top Chrd
Roof Deck: Wood Siding/sheathing/decking
Roofing: Light Roof (Asphalt Shingle)
Attic Roof2 Attic Roofs Wood Framed Ceiling
2x4fop Chord of RoofTruss @ 24
in. O.C.none 0.644
Cavity / Frame: no insul. / 2x4 Top Chrd
Roof Deck: Wood Siding/sheathing/decking
Roofing: Light Roof (Asphalt Shingle)
Attic Roof3 Attic Roofs Wood Framed Ceiling
2x4Top Chord of RoofTruss @ 24
in. O.C.none o.644
Cavity / Frame: no insul. / 2x4 Top Chrd
Roof Deck: Wood Siding/sheathing/decking
Roofing: Light Roof (Asphalt Shingle)
Attic Roofguest-4 Attic Roofs Wood Framed Ceiling
2x4 fop Chord of Roof Truss @ 24
in. O.C.none 0.644
Cavity / Frame: no insul. / 2x4 Top Chrd
Roof Deck: Wood Siding/sheathing/decking
Roofing: Light Roof (Asphalt Shingle)
Attic Roof2 Car Garage Attic Roofs Wood Framed Ceiling
2x4fop Chord ofRoofTruss @ 24
in. O.C.none 0.644
Cavity / Frame: no insul. / 2x4 Top Chrd
Roof Deck: Wood Siding/sheathing/decking
Roofing: Light Roof (Asphalt Shingle)
Attic RoofCart Garage Zone Attic Roofs Wood Framed Ceiling
2x4 Top Chord of Roof Truss @ 24
in. O.C.none 0.644
Cavity / Frame: no insul. / 2x4 Top Chrd
Roof Deck: Wood Sidi ng/sheathing/decking
Roofing: Light Roof (Asphalt Shingle)
CITY OF
BU[_Dtr,Jti &
fl .-; : ., r.-F'ti- i- j"
FCR CON
LA QUINTA
SAFEry DEPI
iOVED
SiRUCTION
Registration Number: 2i5-N0202285D-000000000-0000
CA Building Energy Efficiency Standards - 20L3 Residential Compliance
Registration Date/Time: zo't7-01-0615:04:04
Report Version - CF 1R-040720L6-7 44
BY
HERS Provider: CaICERTS inc.
Report Generated at: 20L7 -0L-06 14:51 :57
CF1R.PRF.Ol
Page 9 of 16
02 07
NA-I:
SLAB FLOORS
01 o2 03 o4 05 06 07
Name Zone Area (ft2)Perimeter (ft)Edge lnsul. R-value & Depth Carpeted Fraction Heated
Covered Slab Suite 1 862 100 None 0.8 No
Covered Slab 2 great room 4274 None 0.8 No
Covered Slab 3 2 569 83 None 0.8 No
Covered Slab 4 3 569 83 None 0.8 No
Covered Slab 5 guesl4 660 121 None 0.8 No
Covered Slab 6 2 Car Garage 1262 120 None 0 No
Covered Slab 7 Cart Garage Zone 581 None 0 No
CERTIFICATE OF COMPLIANCE . RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
ProJect Name: Ratpack Calculation Date/Time: 14:50, Fi, Jan 06,20'17
C.lculation Description: Title 24 Analysis Input Flle Name: Ratpack-Stein-'l5.xml
CFlR.PRF-o1
Page 10 of 16
Registration Number: 21s-No2o22a5D-ooooooooo-oooo
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time: 2017-01-0615:04:04
Report Version - CF 1R-040720L6-7 44
HERS Provider: CaICERTS inc.
Report Generated at: 20L7 -0L-06 14:51 :57
BUILDING ENVELOPE . HERS VERIFICATION
01 02 03 o4
Quality lnsulation lnstallation (Qll)Quality lnstallation of Spray Foam lnsulation Building Envelope Air Leakage CFM50
Required Not Required Not Required
WATER HEATING SYSTEMS
01 02 03 04 05 06
Name System Type Distribution Type Water Heater Number of Heaters Solar Fraction (%)
DHWSysl-112 DHW Pipe lnsulation, All Lines DHW Heater 1 2 .0To
WATER HEATERS
01 02 03 04 05 05 07 08
Name Heater Element Type Tank Type
Tank Volume
(ga!)
Energy Factor or
Efficiency lnput Rating
Tank Exterior
lnsulation
R-value
Standby Loss
(Fraction)
DHW Heater 1 NaturalGas Small Storage 50 0.66 40000-Btu/hr 0 0
WATER HEATING. HERS VERIFICATION
01 o2 03 04 05 06 07
Name Pipe lnsulation Parallel Piping Compact Distribution Point-of Use
Recirculation
Control
Central DHW
Distribution
DHWSysl-112
88
85
SPACE CONDITIONING SYSTEMS
01 02 04 05 06
SC Sys Name System Type Heating Unit Name Cooling Unit Name Fan Name Distribution Name
Cooling Component 1:Heating Component 1:Air
Distribution System 1:HVAC Fan 1:1
Other Heating and Cooling
System Heating Component 1 Cooling Component 1 HVAC Fan 1 Air Distribution System 1
Cooling Component 2:Heating Component 2:Air
Distribution System 2:HVAC Fan2:1
Other Heating and Cooling
SYstem Heating Component 2 Cooling Component 2 HVAC Fan 2 Air Distribution System 2
CERTIFICATE OF CO]IIPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Prorect Name: Ratpack Calculation Date/Time: 14:50, Fri, Jan 06, 20'17
Calculation Doscription: Title 24 Analysis Input File Name: Ratpack-Stein-15.xml
CF1R.PRF.O1
Page 11 of 16
CITY OF [A QUINIABUILDIT.JG & SAF ETY DEPIn.iDPHOL;,1 VEDFUii CCNSTR UCTION
DATE BY
Registration Number: 21s-N0202285D-000000000-0000
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time: 2017-01-0615:04:04
Report Version - CFlR-04072016-7 44
HERS Provider:
SPACE CONDITION!NG SYSTEMS
01 03 04 05 06
SC Sys Name System Type Heating Unit Name Cooling Unit Name Fan Name Distribution Name
Heat Pump System 3:Air Distribution System
3:HVAC Fan3:2
Heat Pump Heating and
Cooling System Heat Pump System 3 Heat Pump System 3 HVAC Fan 3 Air Distribution System 3
Heat Pump System 4:Air Distribution System
4:HVAC Fan 4:2
Heat Pump Heating and
Cooling System Heat Pump System 4 Heat Pump System 4 HVAC Fan 4 Air Distribution System 4
Heat Pump System 5:Air Distribution System
S:HVAC Fan 5:2 Heat Pump System 5 Heat Pump System 5 HVAC Fan 5 Air Distribution System 5
Heat Pump System 6:Air Distribution System
6:HVAC Fan62
Heat Pump Heating and
Cooling System Heat Pump System 6 Heat Pump System 6 HVAC Fan 6 Air Distribution System 6
HVAC - HEATING UNIT TYPES
01 02 03
Name Type Efficiency
Heating Component 1 CntrlFurnace - Fuel-fired central furnace 80 AFUE
Heating Component 2 CntrlFurnace - Fuel-fired central furnace 80 AFUE
Report Generated at 20L7 -0t-06 14:51:57
03
02
Heat Pump Heating and
Cooling System
HVAC . HEAT PUMPS
01 o2 03 o4 05 06 07 08 09 10
Name Type
Heating
HSPF/COP Cap 47 Cap 17
Cooling
SEER EER
Zonally
Controlled
Multispeed
Compressor
HERS
Verification
Heat Pump System 3 SplitHeatPump 10 50000 32000 17.7 9.8 Yes No Heat Pump System
3-hers-cool
Heat Pump System 4 SplitHeatPump 10 21600 16500 19.7 12 Yes No Heat Pump System
4-hers-cool
Heat Pump System 5 SplitHeatPump 11.3 21600 16500 18 12.5 Yes No Heat Pump System
5-hers-cool
Heat Pump System 6 SplitHeatPump 11.3 21600 16500 18 12.5 Yes No Heat Pump System
6-hers-cool
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Prcject Name: Ratpack Calculation Date/Tlme: 14:50, Fri, Jan 06,2017
Calculation Description: Title 24 Analysis lnput File Name: Retpack-Stein-15.xml
CF1R.PRF.OI
Page 12of 16
Re gi strati o n N u m be r : 21 s-No2o2zls D-ooooooooo-ooo0
CA Building Energy Efficiency Standards - 20L3 Residential Compliance
Registration Date/Time: 2017-01-06't5:04:04
Report Version - CF 1R-040720L6-7 44
HERS Provider: CaICERTS inc.
Report Generated at: 2017 -0L-05 14:51:57
HVAC . COOLING UNIT TYPES
01 02 03 o4 05 06 07
Name System Type
Efficiency
EER SEER Zonally Controlled
Multi-speed
Compressor HERS Verification
Cooling Component 1 SplitAirCond 13 16 Not Zonal Single Speed Cooling Component
1-hers-cool
Cooling Component 2 SplitAirCond 13 16 Zonally Controlled Single Speed Cooling Component
2-hers-cool
HVAC COOLING . HERS VERIFICATION
01 02 03 04 05 05
Name Verified Airflow Airflow Target Verified EER Verified SEER
Verified Refrigerant
Charge
Cooling Component 1-hers-cool Required 350 Required Required Required
Cooling Component 2-hers-cool Required 150 Required Required Required
Heat Pump System 3-hers-cool Required 350 Not Required Required Required
Heat Pump System 4-hers-cool Required 350 Required Required Required
Heat Pump System S-hers-cool Required 350 Required Required Required
Heat Pump System 6-hers-cool Required 350 Required Required Required
HVAC - DISTRIBUTION SYSTEMS
01 02 03 04 05 06 07
Name Type lnsulation R-value Duct Location Bypass Duct HERS Verification
Air Distribution System 1 DuctslnAll Sealed and tested I Conditioned zone None Air Distribution System
1-hers-dist
Air Distribution System 2 LowLlCod Sealed and tested I Conditioned zone (VLL)None Air Distribution System
2-hers-dist
Air Distribution System 3 DuctslnAll Sealed and tested I Conditioned zone None Air Distribution System
3-hers-dist
Air Distribution System 4 DuctslnAll Sealed and tested 8 Conditioned zone None Air Distribution System
4-hers-dist
Air Distribution System 5 DuctslnAll Sealed and tested I Conditioned zone None Air Distribution System
5-hers-dist
Air Distribution System 6 DuctslnAll Sealed and tested 8 Conditioned zone None Air Distribution System
6-hers-dist
CERTIFICATE OF COMPLIAI{CE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Prcject Name: Ratpack Calculation Date/Time: 14:50, Fri, Jan 06,2017
Calculation Description: Title 24 Analysis Input File Name: Ratpack-Stein-15.xml
CFlR.PRF-01
Page 13 of 16
Registration Number: 21s-N020228sD-000000000-0000
CA Building Energy Efficiency Standards ' 20L3 Residential Compliance
Registration Date/Time: 2017-01-06 15:04:04
Report Version - CF 1R-040720L6-7 44
HERS Provider:
HVAC DISTRIBUTION - HERS VERIFICATION
01 02 03 04 05 06 07 08
Name
Duct Leakage
Verification
Duct Leakage
Target (%)
Verified Duct
Location
Verified Duct
Design
Buried
Ducts
Deeply Buried
Ducts
Low-leakage
Air Handler
Air Distribution System 1-hers-dist Required 6.0 Required Not Required Not Required Not Required
Air Distribution System 2-hers-dist Required 6.0 Required Not Required Not Required Not Required
Air Distribution System 3-hers-dist Required 6.0 Required Not Required Not Required Not Required
Air Distribution System 4-hers-dist Required 6.0 Required Not Required Not Required
Air Distribution System 5-hers-dist Required 6.0 Required Not Required Not Required Not Required
Air Distribution System 6-hers-dist Required 6.0 Required Not Required Not Required
DATE BY
TAI
l1 L]EPT.
o C i\i
C ry o F rx UO I NBULD&S rA E ry D\D,r.,R o V E DFoDInUCTIoN
Report Generated at: 20L7 -0L-06 14:51:57
Duct Leakage
Not Required
Not Required
i1
HVAC - FAN SYSTEMS
01 o2 03 04
Name Type Fan Power (Watts/CFM)HERS Verification
HVAC Fan 1 Single Speed PSC Furnace Fan 0.58 HVAC Fan 1-hers-fan
HVAC Fan 2 Single Speed PSC Furnace Fan 0.58 HVAC Fan 2-hers-fan
HVAC Fan 3 Single Speed PSC Furnace Fan 0.58 HVAC Fan 3-hers-fan
HVAC Fan 4 Single Speed PSC Furnace Fan 0.58 HVAC Fan 4-hers-fan
HVAC Fan 5 Single Speed PSC Furnace Fan 0.58 HVAC Fan S-hers-fan
HVAC Fan 6 Single Speed PSC Furnace Fan 0.58 HVAC Fan 6-hers-fan
CERTIFICATE OF COMPLIANCE . RESIDENTIAL PERFORMANCE COMPLIANCE ETHOD
Project Name: Ratsack Calculatlon Date/Time: 14:50, Fri, Jan 06, 2017
Calculation Doscription: Title 24 Analysis lnput File Name: Ratpack-Stein-15.xml
CFlR-PRF-01
Page 14 of 16
Registration Number: 215-No2o22B5D-ooooooooo-0000
CA Building Energy Efficiency Standards - 20L3 Residential Compliance
Registration Date/Time: 2017-01-0615:04:04
Report Version - CFlR-04072016-7 44
HERS Provider: CaICERTS inc.
Report Generated at: 20L7 -0L-06 14:51:57
HVAC FAN SYSTEMS - HERS VERIFICATION
01 02 03
Name Verified Fan Watt Draw Required Fan Efficiency (Watts/CFM)
HVAC Fan 1-hers-fan Required 0.58
HVAC Fan 2-hers-fan Required
HVAC Fan 3-hers-fan Required 0.58
HVAC Fan 4-hers-fan Required 0.58
HVAC Fan S-hers-fan Required 0.58
HVAC Fan 6-hers-fan Required 0.58
IAQ (lndoor Air Quality) FANS
01 03 04 05 06
Dwelling Unit IAQ CFM IAQ Watts/CFM IAQ Fan Type
IAQ Recovery
Effectiveness(%)HERS Verification
SFam lAQVentRpt 140.27 0.25 Default 0 Required
COOL!NG VENTILATION
0l 02 03 04 05
Name Cooling Vent CFM Cooling Vent Watts/CFM TotalWatts Number of Fans
WH Fan 1 67 0.298507 20 1
WH Fan 2 42 24 1
WH Fan 3 21 0.571429 12 1
WH Fan 4 21 0.571429 12 1
WH Fan 5 21 0.571429 12 1
0.58
02
0.571429
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Ratpack Calculation Date/Time: '14:50' Fri' Jan 06' 2017
Calculation Description: Title 24 Analysis lnput File Name: Ratpack-Stein-15.xml
CFlR-PRF-o1
Page 15 of 16
PROJECT NOTES
The Madison Club
{
CalCfRTS, lnc.
Registration Number: 215-N0202285D-000000000-0000
CA Building Energy Efficiency Standards - 20L3 Residential Compliance
HERS PR()VIDER
Registration Date/Time: 2017-01-0615:04:04
Report Version - CF LR-040720L6-7 44
H CaICERTS inc.
CITY OF LA QUINTA
BUILDING & SAFETY DEPT.
APPFiOVED
FOR CONSTRUCTION
DATE BY
Report Generated al: 20L7 -0L-06 L4:5L:57
DOC U M ENTATION AUTHOR'S DECLARATION STATEM ENT
1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Tim Scott
Documentation Author Signature
t/ur?;7A4&
Company:
Scott Design and Title 24,lnc.
Signature Date:
2017-01-06 15.04:04
Address:
77085 Michigan Drive
CEA/HERS Certification ldentification (lf applicable)
City/State/Zip:
Palm Desert, CA92211
Phone:
760-200-4780
RESPONSIBLE PERSON'S DECLARATION STATEM ENT
I certiry lhe Iollowing under penalty oI perjury, under the laws ofthe Stale of California:
1. I am eligible under Division 3 of the Business and Professions Code to ac4ept responsibility tur the building design idenlified on lhis Certificate of Compliance.
Regulations.
worksheets, calculations, plans and specifcations submitted to the entorcement agency for approval with this building permit application.
Responsible Designer Name:
Tim Scott
Responsible Designer Signature:7t;nSm
Company:
Scott Design and Title 24,lnc
Date Signed:
2017-01-06 15:04:04
Address:
77085 Michigan Drive
License:
na
City/State/Zip:
Palm Desert, CA92211
Phone:
760-200-4780
CERTIFICATE OF COMPLIANCE . RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Prcject Name: Ratpack Calculation Date/Time: 14:50, Fri, Jan 06, 2017
Calculatlon Descrlption: Title 24 Analysis lnput File Name: Ratpack-Stein-15.xml
CF1R.PRF.O1
Page 16 of 16
Digitally signed by CaICEBTS. This digital signature is ptovided in odet to secute the content ol this rcgistercd document, and in no way implies Registration
Ptovidet rcsponsibility fot the accutacy of the ihfonnation-
Registration Number: 21s-NozozzasD-ooooooooo-oooo
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time: 2o1t-oi-0615:04:04
Report Version - CFlR-04072076-7 44
HERS Provider: CaICERTS inc.
Report Generated at: 2017 -0L-06 L4:5L:57
RESIDENTIAL MEASURES SUMMARY RMS.1
Project Name
Ratpack Residence
Building Type E Single Family tr Addition Alone
tr Multi Family tr Existing+ Addition/Alteration
Date
1/6/201 7
Project Address
53-525 Humbolt Blvd. La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
8,777
Addition
n/a
# of Units
1
INSULATION
Construction Type
Area
Cavity (tfi Special Features Status
Roof Wood Framed Attic R38 8,777 CoolRoof New
Wall Wood Framed R21 6,102 New
S/ab U n he ated S lab-on-G rade - no insulation 8,777 Perim = 680'New
Demising Wood Framed - no insulation 1,948 New
Door Opaque Door - no insulation 24 New
Door Opaque Door - no insulation 475 Rigid=R-l2.0 New
FENESTRATION
Orientation Area(f(l U-Fac SHGC Overhang Sidefins Exterior Shades Status
Left (S)201.2 0.370 0.26 4.0 none Bug Screen New
Left (S)53.0 0.460 0.31 4.0 none Bug Scrcen New
Rear (W)329.0 0.460 0.31 4.0 none Bug Screen New
Risht (N)286.0 0.370 0.26 none none Bug Screen New
Risht (N)64.0 0.460 0.31 none none Bug Screen New
Risht (N)28.5 0.500 0.20 none none Bug Screen New
Front (E)55.0 0.940 0.49 4.0 none Bug Screen New
Front (E)473.0 0.460 0.31 12.0 none Bug Screen New
Front (E)47.6 0.370 0.26 none none Bug Screen New
Left (S)336.0 0.460 0.31 none none Bug Scrcen New
Left (S)77.0 0.760 0.18 8.0 none Bug Screen New
Left (S)95.1 0.370 0.26 10.0 none Bug Screen New
Left (S)123.1 0.370 0.26 none none Bug Screen New
Rear (W)473.0 0.460 0.31 12.0 none Bug Screen New
HVAC SYSTEMS
Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status
1 CentralFumace 80% AFUE Split Air Conditioner 16.0 SEER Setback New
3 Central Furnace 80% AFUE Split Air Conditioner 16.0 SEER Sefback New
2 Split Heat Pump 10.00 HSPF Split Heat Pump 17.7 SEER Setback New
HVAC DISTRIBUTION
Location Heating Cooling Duct Location
Duct
R-Value Status
HVAC 1 mstr Ducted Ducted Conditioned 8.0 New
HVAC2,3&4 Ducted Ducted Conditioned 8.0 New
HVACs&6 Ducted Conditioned 8.0 New
WATER HEATING
Qty. Type Gallons Min. Eff Distribution Status
2 SmallSforage Gas 50 0.66 All Pipes lns New
EneryvPro 6.7 bv EnerqySoft User Number: 6712 RunCode:2017-01-06714:53:15 lD:Page 19 of 51
t
TotalArea:3,304 37.6 %U-Factor:0.45
Ducted
RESIDENTIAL MEASURES SUMMARY RMS-1
Project Name
Ratpack Residence
Building Type E Single Family tr Addition Alone
tr Multi Family tr Existing+ Addition/Alteration
Date
1/6/2017
Project Address
53-525 Humbolt Blvd. La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
8,777
Addition
n/a
# of Units
1
INSULATION
Construction Type Cavity
Area
trfi Special Features Status
FENESTRAT!ON
Orientation Areaff(l U-Fac SHGC Overhang Sidefins Exterior Shades Status
Rear (W)47.6 0.370 0.26 none none Bug Screen New
Rear (W)194.8 0.370 0.26 10.0 none Bug Screen New
Risht (N)184.0 0.460 0.31 4.0 none Bug Screen New
Right (N)70.0 0.460 0.31 8.0 none Bug Screen New
Front (E)88.0 0.460 0.31 none none Bug Screen New
Left (S)78.0 0.460 0.31 10.0 none Bug Screen New
HVAC SYSTEMS
Qty. Heatins Min. Eff Cooling Min. Eff Thermostat Status
1 Split Heat Pump 10.00 HSPF Split Heat Pump 19.7 SEER Sefback New
1 Split Heat Pump 11.30 HSPF Split Heat Pump 18.0 SEER Sefback New
1 Split Heat Pump 11.30 HSPF Split Heat Pump 18.0 SEER Sefback New
HVAC DISTRIBUTION
Location Heating Cooling Duct Location
Duct
R-Value Status
HVAC 6 Ducted Ducted Conditioned 8.0 New
HVAC 7 Ducted Ducted Conditioned 8.0 New
HVAC 8 Ducted Ducted Conditioned 8.0 New
WATER HEATING
Qty. Type Gallons Min. Eff Distribution Status
EnemvPro 6.7 bv EnerqvSoft User Number: 6712 RunCode:2017-01-06714:53:15 lD Paqe 20 of 51
J
Area:3,304 37.6 %NeWAltered U-Factor:0.45
'2013 Low-Rise Residential Mandatory Measures Summary
[!f[; Low-rise residential buildings subject lo the Standards must cornply\rith all opplicable mandatory measures listed, regardless of the
used.Review the re ive code section more ton.
Building Envelope Measures:
$l10.6(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
Fenestration products (except field-fabricated windows) have a label listing the certified U-Factor, certified Solar Heat Gain
Coefficient (SHGC), and infiltration that meets the requirements of $ l0- l I I (a).$ I 10.6(a)5
$l r0.7 Exterior doors and windows are weatherstripped; alljoints and penetrations are caulked and sealed.
$ I 10.8(a): Insulation specified or installed meets Standards for Insulating Material. Indicate type and include on the CF2R.
The thermal emittance and aged solar reflectance values of the cool roofing material meets the requirements of $ I 10.8(i) when the
installation of a coolroof is specified on the CFIR.$ l r 0.8(i):
$l10.8(i): A radiant barrier shall have an emittance of 0.05 or less when the installation of a radiant barrier is specified on the CFIR.
Minimum R-30 insulation in wood-frame ceiling; or the weighted average U-factor shall not exceed 0.031. Minimum R-19 in a
rafter roof alteration. Attic access doors shallhave permanently'attached insulation using adhesive or mechanical fasteners. The
attic access shall be gasketed to prevent air leakage.
$ 150.0(a):
$150.0(b): Loose fill insulation shall conform with manufacturer's installed design labeled R-value
Minimum R-13 insulation in 2x4 inch wood framing wallor have a U-factor of 0.102 or less (R-19 in2x6 or 0.074 maximum U-
factor).$ 150.0(c)
$ I 50.0(d): Minimum R- 19 insulation in raised wood-frame floor or 0.037 maximum U-factor
In Climate Zones l4 and l6 a Class II vapor retarder shallbe installed on the conditioned space side of all insulation in allexterior
walls, vented attics and unvented attics with air-permeable insulation.$ I s0.0(e) I
In Climate Zones l - 16 with unvented crawl spaces the earth floor of the crawl space shall be covered with a C lass I or Class II
vapor retarder.$ 1s0.0(g)2
In a building having a controlled ventilation crawl space. a Class I or Class II vapor retarder shall be placed over the earth floor of
the crawl space to reduce moisture entry and protect insulation from condensation, as specified in the exception to Section
150.0(d).
$ 1s0.0(g)3
Slab edge insulation shall: have a water absorption rate, for the insulation material alone without facings, no greater than 0.3%;
have water vapor perrneance rate is no greater than 2.0 perm/inch, be protected from physical damage and UV light deterioration;
and when installed as part of a heated slab floor meets the requirements of $ I 10.8(g).
$ 150.0(r):
Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors shall have a maximum U-
factor of 0.58; or the weighted average U-factor of all fenestration shall not exceed 0.58.$ 150.0(q)
Fireplaces, Decorative Gas Appliances and Gas Log Measures
$ 150.0(e)lA: Masonry or factory-built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
Masonry or factory-built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a readily accessible, operable, and tight-fitting damper or a combustion-air control device.$ 150.0(e) I B
$ 150.0(e)lC: Masonry or factory-built fireplaces have a flue damper with a readily accessible control
Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside
of the building, are prohibited.$ 150.0(e)2
Space Conditioning, Water Heating and Plumbing System Measures:
$l10.0-Sl10.3: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are cenified to the Energy Commission
Water heating recirculation loops serving multiple dwelling units meet the air release valve, backflow prevention, pump isolation
valve, and recirculation loop connection requirements of $l 10.3(c)5.$ I 10.3(c)s
Continuously burning pilot lights are prohibited for natural gas: fan-type central furnaces, household cooking appliances (appli-
ances without an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool
and spa heaters.
$ l l0.s
Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA using design conditions specified
in $150.0(h)2.$ l 50.0(h) l
Installed air conditioner and heat pump outdoor condensing units shall have a clearance of at least five feet from the outlet of any
dryer vent.$ 150.0(h)3A'
$ I 50.0(i): Heating systems are equipped with thermostats that meet the setback requirements of $ I 10.2(c)
Storage gas water heaters with an energy factor equal to or less than the federal minimum standards shall be externally wrapped
with insulation having an installed thermal resistance of R-12 or greater.$ 150.00)l A:
Unfired hot water tanks, such as storage tanks and backup storage tanks for solar water-heating systems, have R-12 external
insulation or R-16 internal insulation where the internal insulation R-value is indicated on the exterior of the tank.$150.0(i)lB
For domestic hot water system piping. whether buried or unburied: the first 5 feet of hot and cold water pipes from the storage
tank, all piping with a nominal diameter of 314 inch or larger, all piping associated with a domestic hot water recirculation system
regardless of the pipe diameter, piping from the heating source to storage tank or between tanks, piping buried below grade, and
all hot water pipes from the heating source to kitchen fixtures must be insulated according to the requirements of TABLE 120.3-
A.
$ 150.0(i)2A
All domestic hot water pipes that are buried below grade must be installed in a water proof and non-crushable casing or sleeve
that allows for installation, removal, and replacement of the enclosed pipe and insulation.$ 1s0.0(i)28
t
I
2013 Low-Rise Residential Mandato Measures Summa
Pipe for cooling system lines shall be insulated as specified in $ I 50.0O2A. Piping insulation for steam and hydronic heating
systems or hot water systems with pressure > l5 psig shall meet the requirements in TABLE 120.3-A.
$150.0()3: Insulation is protected from damage, including that due to sunlight. moisture. equipment maintenance, and wind.
Insulation exposed to weather shall either be rated for outdoor use or installed with a cover suitable for outdoor service. For
example, protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation protected as specified or
painted with coating that is water retardant and provides shielding from solar radiation that degrades the material.
li r 50.00)3A:
Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space shall have a Class I
or Class II vapor retarding facing, or the insulation shall be installed at the thickness that qualifies as a Class I or Class II vapor
retarder.
$ 150.0(i)38:
Systems using gas or propane water heaters to serve individualdwelling units shall include: a l20V electricalreceptacle within 3
feet of the water heater; a Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the
space where the water heater is installed; a condensate drain that is no more than 2 inches higher than the base of the installed
water heater. and allows naturaldraining without pump assistance: and a gas supply line with a capacity of at least 200.000
Btu/hr.
$ I 50.0(n) I
$150.0(n)2: Recirculating loops serving multiple dwelling units shallmeet the requirements of $l10.3(c)5
Solar water-heating systems and collectors shall be certified and rated by the Solar Rating and Certification Corporation (SRCC)
or by a testing agency approved by the Executive Director.$ 150.0(n)3
Ducts and Fans Vleasures:
All air-distribution system ducts and plenums installed are sealed and insulated to meet the requirements of CMC $601 .0, $602.0.
$603.0, $604.0, $605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metaland Flexible 3rd Edition.
Supply-air and return-air ducts and plenums are insulated to a minimum installed levelof R-6.0 (or higher if required by CMC
$605.0) or enclosed entirely in directly conditioned space as confirmed through field verification and diagnostic testing
(RA3.1.4.3.8). Connections of metal ducts and inner core of flexible ducts are mechanically fastened. Openings shallbe sealed
with mastic, tape, or other duct-closure system that meets the applicable requirements of UL l8l, UL l8lA, or UL l8lB or
aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than t/o inch, the
combination of mastic and either mesh or tape shall be used. Building cavities, support platforms for air handlers, and plenums
defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying
conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms
shallnot be compressed to cause reductions in the cross-sectionalareaof the ducts.
$ 150.0(m) I
Factory-Fabricated Duct Systems shall comply with specified requirements for duct construction. connections, and closures; joints
and seams of duct systems and their components shallnot be sealed with cloth back rubber adhesive duct tapes unless such tape is
used in combination with mastic and draw bands.
$ 150.0(m)2
Field-Fabricated Duct Systems shall comply with requirements for: pressure-sensitive tapes, mastics, sealants, and other
requirements specified for duct construction: duct insulation R-value ratings; duct insulation thickness: and duct labeling.$ 150.0(m)3-6
All fan systems that exchange air between the conditioned space and the outside of the building must have backdraft or automatic
dampers.$ 150.0(m)7:
Gravity ventilating systems serving conditioned space have either automatic or readily accessible. manually operated dampers
except combustion inlet and outlet air openings and elevator shaft vents.$ 150.0(m)8
Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind but not
limited to the following: insulation exposed to weather shall be suitable for outdoor service. For example, protected by aluminum.
sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is
water retardant and provides shielding from solar radiation.
$ 150.0(m)9
$150.0(m)10: Flexible ducts cannot have porous inner cores.
When space conditioning systems use forced air duct systems to supply conditioned air to an occupiable space, the ducts shall be
sealed and duct leakage tested. as confirmed through field verification and diagnostic testing, in accordance with Reference
Residential Appendix RA3.
$150.0(m)l I
Mechanical systems that supply air to an occupiable space through ductwork exceeding l0 feet in length and through a thermal
conditioning component, except evaporative coolers, shall be provided with air filter devices that meet the requirements of
$ 150.0(m)12.
li I 50.0(m) l2:
Space conditioning systems that utilize forced air ducts to supply cooling to an occupiable space shall have a hole for the
placementof a static pressure probe (HSPP), or apermanently installed static pressure probe (PSPP) in the supply plenum. The
space conditioning system must also demonstrate airflow > 350 CFM per ton of nominal cooling capacity through the retum
grilles, and an air-handling unit fan efficacy S 0.58 WCFM as confirmed by field verification and diagnostic testing. in
accordance with Reference Residential Appendix RA3.
$ 150.0(m) l3
Zonally controlled central forced air cooling systems shall be capable of simultaneously delivering, in every zonal control mode,
an airflow from the dwelling. through the air handler fan and delivered to the dwelling. of > 350 CFM per ton of nominal cooling
capacity, and operating at an air-handling unit fan efficacy of < 0.58 WCFM as confirmed by field verification and diagnostic
testing. in accordance with Reference Residential Appendix RA3.
$ I 50.0(m) l5
All dwelling units shall meet the requirements of ASHRAE Standard 62.2. Neither window operation nor continuous operation of
central forced air system air handlers used in central fan integrated ventilation systems are permissible methods of providing the
Whole Building Ventilation.
$ 150.0(o)
Whole Building Ventilation airflow shall be confirmed through field verification and diagnostic testing, in accordance with
Reference Residential Appendix RA3.$ 150.0(o)l A:
Pool and Spa Heating Systems and Equipment Measures
Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on-offswitch mounted outside of the heater that allows shutting offthe heater without adjusting the thermostat
setting; a permanent weatherproof plate or card with operating instructions; and shall not use electric resistance heating.
li I lO.a(a)
I
I
$ l s0.0o2c:
' 2013 Low-Rise Residential Mandato Measures Summa
Any pool or spa heating equipment shall be installed with at least 36 inches of pipe between filter and heater or dedicated suction
and return lines. or built-up connections for future solar heating.$ l 10.4(b)l
$ I 10.4(b)2: Outdoor pools or spas that have a heat pump or gas heater shall have a cover
Pools shall have directional inlets that adequately mix the pool water. and a time switch that will allorv all pumps to be set or pro-
grammed to run only during off-peak electric demand periods.$ r 10.4(b)3:
$ r r0.s Natural gas pool and spa heaters shall not have a continuous burning pilot light
$150.0(p): Residentialpoolsystems or equipment shall meet specified pump sizing. flow rate, piping. filters, and valve requirements
Lighting Measures:
$ r l0.e All lighting controldevices and systems, ballasts, and luminaires shall meet the applicable requirements of $110.9
Installed luminaires shallbe classified as high-efficacy or low-efficacy for compliance with !i150.0(k) in accordance with TABLE
150.0-4 or TABLE 150.0-8. as applicable.$1s0.0(k)rA:
When a high efficacy and low efficacy lighting system are combined in a single luminaire, each system shall separately comply
with the applicable provisions of $ 150.0(k).$150.0(k)rB
The wattage and classification of permanently installed luminaires in residentialkitchens shall be determined in accordance with
$ 130.0(c). In residential kitchens, the wattage of electrical boxes finished with a blank cover or where no electrical equipment has
been installed, and where the electrical box can be used for a luminaire or a surface mounted ceiling fan, shall be calculated as I 80
watts of low efficacy lighting per electrical box.
$150.0(k)rc
$ 150.0(k) I D: Ballasts fot fluorcscent lamps rated 13 watts or greater shall be electronic and shall have an output frequency no less than 20 kHz.
Permanently installed night lights and night lights integral to installed luminaires or exhaust fans shall be rated to consume no
more than 5 watts of power per luminaire or exhaust fan as determined in accordance with $130.0(c). Night lights do not need to
be controlled by vacancy sensors.
$ 150.0(k) r E:
Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust hoods) shall meet the applicable
requirements of $ 150.0(k).$ 150.0(k) r F:
$150.0(k)2A: High efficacy luminaires must be switched separately from low efficacy luminaires
$150.0(k)28: Exhaust fans shall be switched separately from lighting systems
$150.0(k)2C: Luminaires shall be switched with rcadily accessible controls that permit the luminaires to be manually switched ON and OFF.
$ 150.0(k)2D: Controls and equipment are installed in accordance with manufacturer's instructions.
$ 150.0(k)2E: No control shall bypass a dimmer or vacancy sensor function if the control is installed to comply with $ 150.0(k)
$ 150.0(k)2F: Lighting controls comply with applicable requirements of $ I 10.9
An Energy Management Control System (EMCS) may be used to comply with dimmer requirements if: it functions as a dimmer
according to !il10.9; meets Installation Certificate requirementsof $130.4; the EMCS requirements of $130.5; and allother
requirements in $ I 50.0(k)2.
$ 150.0(k)2G:
An Energy Management ControlSystem (EMCS) may be used to comply with vacancy sensor requirements of $150.0(k) if: it
functions as a vacancy sensor according to $l10.9; meets Installation Certificate requirements of $130.4; the EMCS requirements
of $130.5; and allother requirements in $150.0(k)2.
$ r 50.0(k)2H:
A multiscene programmable controller may be used to comply with dimmer requirements of this section if it provides the
functionality of a dimmer according to $ I 10.9, and complies with all other applicable requirements in (i I 50.0(k)2.$ 150.0(k)2r
$150.0(k)3A: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
Kitchen lighting includes all permanently installed lighting in the kitchen except internal lighting in cabinets that illuminate only
the inside of the cabinets. Lighting in areas adjacent to the kitchen, including but not limited to dining and nook areas, are
considered kitchen lightine if they are not separately switched from kitchen lighting.
{i 1s0.0(k)38
Permanently installed lighting that is internalto cabinets shall use no more than 20 watts of power per linear foot of illuminated
cabinet.$i 1s0.0(k)4
A minimum of one high efficacy luminaire shall be installed in each bathroom; and all other lighting installed in each bathroom
shall be high efficacy or controlled by vacancy sensors.$ 150.0(k)5
Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and
controlled by vacancy sensors.$ r 50.0(k)6
Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be high
efficacy, or shall be controlled by either dimmers or vacancy sensors.$ 1s0.0(k)7
Luminaires recessed into ceilings shall: be listed for zero clearance insulation contact (lC) by Underwriters Laboratories or other
nationally recognized testing/rating laboratory; have a label that certifies that the luminaire is airtight with air leakage less than 2.0
CFM at 75 Pascals when tested in accordance with ASTM E283; be sealed with a gasket or caulk between the luminaire housing
and ceiling. and shall have all air leak paths between conditioned and unconditioned spaces sealed with a gasket or caulk; and
allow ballast maintenance and replacement without requiring cutting holes in the ceiling.
For recessed compact fluorescent luminaries with ballasts to qualify as high efficacy for compliance with $150.0(k), the ballasts
shall be certified to the Energy Commission to comply with the applicable requirements in $ I 10.9.
{i r 50.0(k)8
For single-family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on the
same lot shall be high efficacy, or may be lowefficacy if it meets allof the following requirements:
i. Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of Items iior iii below; and
ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor, or controlled by a
motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and automatically
reactivates the motion sensor within 6 hours; and
iii. Controlled by one of the following methods:
$ 1s0.0(k)eA
2013 Low-Rise Residential Mandato Measures Summa
a. Photocontrol not having an override or bypass switch that disables the photocontrol; or
b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and which is
programmed to automatically turn the outdoor lighting OFF during daylight hours; or
c. Energy management control system which meets all of the following requirements: At a minimum provides the functionaliry of
an astronomicaltime clock in accordance with $l10.9: meets the Installation Certification requirements in $130.41 meets the
requirements for an EMCS in $130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and,
is programmed to automatically turn the outdoor lighting OFF during daylight hours.
For low-rise multifamily residential buildings, outdoor lighting for private patios, entrances, balconies, and porches: and outdoor
lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply rvith one of the
following requirements:
i. Shall comply with $150.0(k)9A;or
ii. Shallcomply with the applicable requirements in $l10.9. $130.0. $130.2. $130.4, $140.7 and $141.0.
$ 150.0(k)eB
For low-rise residential buildings with four or more dwelling units. outdoor lighting not regulated by $ I 50.0(k)98 or 150.0(k)9D
shallcomply with the applicable requirements in $l10.9, |i130.0, (i130.2, $130.4, $140.7 and $141.0.$ r 50.0(k)ec
Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site shalI comply
with the applicable requirements in $l10.9, ti130.0, $130.2. $130.4, $140.7 and $141.0.$ 1s0.0(k)eD
Internally illuminated address signs shallcomply with $140.8;or shallconsume no more than 5 watts of power as determined
according to $ 130.0(c).$ l s0.0(k) l0
Lighting for residential parking garages for eight or more vehicles shall comply with the applicable requirements for
nonresidentialearases in $l10.9. $130.0, li130.1. $130.4, $140.6. and $141.0.$ 150.0(k) l l
In a low-rise multifamily residential building where the total interior common area in a single building equals 20 percent or less of
$ 150.0(k)l2A: the floor are4 permanently installed lighting for the interior common areas in that building shall be high eflicacy luminaires or
controlled by arl occupant sensor.
In a low-rise multifamily residential building where the total interior common area in a single building equals more than 20
percent of the floor area. permanently installed lighting in that building shall:
i. Comply withthe applicable requirements in $110.9, $130.0, $130.1, {l140.6 and $141.0; and
ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each
space by at least 50 percent. The occupant sensors shall be capable of turning the light fully On and Olf from all designed paths of
ingress and egress.
$l50.0(k)r28:
Solar Ready Buildings:
Single family residences located in subdivisions with ten or more single family residences and where the application for a
tentative subdivision map for the residences has been deemed complete, by the enforcement agency. on or after January l, 2014,
shall comply with the requirements of li I 10.10(b) through $ I 10. l0(e).
$l 10.10(a)l
$l10.10(a)2: Low-rise multi-family buildings shallcomply with the requirements of $l10.10(b) through $l10.10(d).
The solar zone shall have a minimum total area as described below. The solar zone shall comply with access, pathway. smoke
ventilation. and spacing requirements as specified in Title 24.Part 9 or other Parts of Title24 or in any requirements adopted by a
localjurisdiction. The solar zone total area shall be comprised of areas that have no dimension less than 5 feet and are no less than
80 square feet each for buildings with roof areas less than or equalto 10,000 square feet or no less than 160 square feet each for
buildings with roof areas greater than 10,000 square feet.
For single family residences the solar zone shall be located on the roof or overhang of the building and have a total area no less
than 250 square feet. For low-rise multi-family buildings the solar zone shall be located on the roof or overhang of the building or
on the roof or overhang of another structure located within 250 feet of the building or on covered parking installed with the
building project and have a total area no less than l5 percent of the totalroof area of the building excluding any skylight area.
$l10.10(b)r
$ I 10.10(b)2: All sections ofthe solar zone located on steep-sloped roofs shall be oriented between I l0 degrees and 270 degrces oflrue north.
No obstructions, including but not limited to, vents, chimneys, architectural features, and roof mounted equipment, shall be
located in the solar zone.(il10.10(b)3A:
Any obstruction, located on the roof or any other part of the building that projects above a solar zone shall be located at least trvice
the distance, measured in the horizontal plane, of the height diflerence between the highest point of the obstruction and the
horizontal proiection of the nearest point of the solar zone, measured in the vertical plane.
$l10.r0(b)38
For areas of the roof designated as solar zone, the structuraldesign loads for roof dead load and roof live load shallbe clearly
indicated on the construction documents.$l10.10(b)4
The construction documents shall indicate: a location for inverters and metering equipment and a pathway for routing of conduit
from the solar zone to the point of interconnection with the electrical service (for single family residences the point of
interconnection will be the main service panel); a pathway for routing of plumbing from the solar zone to the water-heating
system.
$ I 10.10(c):
A copy of the construction documents or a comparable document indicating the information from $ I 10. l0(b) through $ I 10. l0(c)
shall be provided to the occupant.$l10.10(d)
|)l10.10(e)l: The main electricalservice panel shallhave a minimum busbar rating of 200 amps.
The main electrical service panel shall have a reserved space to allow for the installation of a double pole circuit breaker lor a
future solar electric installation. The reserved space shall be: positioned at the opposite (load) end from the input feeder location or
main circuit location. and permanently marked as "For Future Solar Electric".
$ I 10.l0(e)2:
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Ratpack Residence
Date
1t6t2017
System Name
HVAC 1 mstr
Floor Area
862
ENGINEERING CHECKS SYSTEM LOAD
Number of Systems ,|COIL COOLING PEAK COIL HTG. PEAK
CFM Sensible Latent CFM Sensible
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
17,872 91 452 19,
0
259 229
0 0
129 4,937 2,563 129 6,315
2,943 -2,943
259 229
TOTAL SYSTEM LOAD 26,269 3,479 23,078
Heating System
Output per System 89,000
Total Output (Btuh)89,000
Output (Btuh/sqft)103.2
Cooling System
Output per System 59,000
Total Output (Btuh)59,000
Total Output (Tons)4.9
Total Output (Btuh/sqft)68.4
Total Output (sqfUTon)175.3
Air System
CFM per System 2,000 HVAC EQUIPMENT SELECTION
Airflow (cfm)2,000 Day and Night 5 Ton 51,379 0 89,000
Total Adjusted System Output
(Adjusted for Peak Design conditions)
51,379 0 89,000
TIME OF SYSTEM PEAK Aug 3 PM Jan 1 AM
Airflow (cfm/sqft)2.32
Airflow (cfm/Ton)406.8
Outside Air (%)6.5 Yo
Outside Air (cfm/sqft)0.15
Note: values above qiven at ARI conditions
HEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak)
260F 69 0F 70 0F 112 0F
Outside Air
129 cfm
EIIIh
Supply Fan
2,000 cfm
Heating Coil 112 0F
ROOM tr
72"F 720FEIIIE
:-{
COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak)
112 t780F 78/630F B0/640F 56/540F
Outside Air
129 cfm
il__t IE I
Supply Fan
2,000 cfm
Cooling Coil 56/54"F
RooM tr
76 t620F 76 t620FEIItE
45.7 Yo
EnergyPro 6.7 by EnergySofr User Number: 6712 RunCode : 201 7-01 -06T1 4 :53 : 1 5 ID:Page 25 of 51
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Ratpack Residence
Date
1t6t2017
System Name
HVAC2,3&4
Floor Area
4,274
ENGINEERING CHECKS SYSTEM LOAD
Number of Systems 3 COIL COOLING PEAK COIL HTG. PEAK
CFM Sensible Latent CFM Sensible
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
3 73,819 4,542 1,529 62,286
0
0 0
0 0
641 24,562 11,236 641 31,384
8,830 -8,830
0 0
TOTAL SYSTEM LOAD 107,211 15,778 84,840
Heating System
Output per System 89,000
Tota! Output (Btuh)267,000
Output (Btuh/sqft)62.5
Cooling System
Output per System 59,000
Tota! Output (Btuh)177,000
Total Output (Tons)14.8
Total Output (Btuh/sqft)41.4
Total Output (sqfUTon)289.8
Air System
CFM per System 2,000 HVAC EQUIPMENT SELECTION
Airflow (cfm)6,000 Day and Night 5 Ton 155,344 2,147 267,000
Total Adjusted System Output
(Adjusted for Peak Design conditions)
155,344 2,147 267,000
TIME OF SYSTEM PEAK Aug 3 PM Jan 1 AM
Airflow (cfm/sqft)1.40
Airflow (cfm/Ton)406.8
Outside Air (%)10.7 o/o
Outside Air (cfm/sqft)0.15
Note: values above qiven at ARI conditions
HEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak)
26"F 67 0F 6B F 1 '10 0F
Outside Air
641 cfm
E Elllh
Supply Fan
6,000 cfm
Heating Coil 1100F
ROOM tr
72 0F 720FEIII E
COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak)
112 t780F B0/650F 81/65"F 57l560F
Outside Air
641 cfm
il] IE 1
Supply Fan
6,000 cfm
Cooling Coil 57l560F
48.1 Yo ROOM tr
76/630F 76/630FEIIIE
EnergyPro 6.7 by EnergySoft User Number: 6712 Run Code : 201 7-01 -0671 4 : 53 : 1 5 ID:Page 26 of 51
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Ratpack Residence
Date
1t6t2017
System Name
HVAC5&6
Floor Area
1 ,138
ENGINEERING CHECKS SYSTEM LOAD
Number of Systems 2 COIL COOLING PEAK COIL HTG. PEAK
CFM Sensible Latent CFM Sensible
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
24,620 1,209 502 24,444
0
356 278
0 0
171 6,485 8,774 171 8,313
0 0
356 278
TOTAL SYSTEM LOAD 31,818 9,984 33,312
Heating System
Output per System 50,000
Tota! Output (Btuh)100,000
Output (Btuh/sqft)87.9
Cooling System
Output per System 45,000
Total Output (Btuh)90,000
Total Output (Tons)7.5
Total Output (Btuh/sqft)79.1
Total Output (sqfUTon)151.7
Air System
CFM per System 550 HVAC EQUIPMENT SELECTION
Airflow (cfm)1 ,100 Fujitsu FAOU45 69,606 0 62,457
Total Adjusted System Output
(Adjusted for Peak Design conditions)
69,606 0 62,457
TIME OF SYSTEM PEAK Aug 3 PM Jan 1 AM
Airflow (cfm/sqft)0.97
Airflow (cfm/Ton)146.7
Outside Air (%)15.5 Yo
Outside Air (cfm/sqft)0.15
Note: values above given at AR! conditions
HEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak)
260F 65 0F 65 0F 1180F
Outside Air
171 c'fm Supply Fan
1 ,100 cfm
Heating Coil 11BOF
@
720F720FEIIIE
COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak)
112 t78"F 82/560F 82l560F 22t210F
Outside Air
171 ctm
E_II I E +
231 210F@
76t510F
Supply Fan
1,100 cfm
Cooling Coil
76 I 510F EIIIE
11.6 Yo
EnergyPro 6.7 by EnergySoft User Number: 6712 Run Code : 201 7 -01 -06T1 4 : 53 : 1 5 tD.Page 27 of 51
H Ettth
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Ratpack Residence
Date
1t612017
System Name
HVAC 6
Floor Area
660
ENGINEERING CHECKS SYSTEM LOAD
Number of Systems 1 COIL COOLING PEAK COIL HTG. PEAK
CFM Sensible Latent CFM Sensible
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
581 12,640 701 945 14,350
0
183 163
0 0
99 3,760 1,968 99 4,817
0 0
183 163
TOTAL SYSTEM LOAD 16,766 2,669 19,493
Heating System
Output per System 21,600
Total Output (Btuh)21,600
Output (Btuh/sqft)32.7
Cooling System
Output per System 18,000
Total Output (Btuh)18,000
Total Output (Tons)1.5
Total Output (Btuh/sqft)27.3
Tota! Output (sqfUTon)440.0
Air System
CFM per System 550 HVAC EQUIPMENT SELEGTION
Airflow (cfm)550 Fujitsu l SRLFCD 16,087 0 13,491
Total Adjusted System Output
(Adjusted for Peak Design mnditions)
16,087 13,491
TIME OF SYSTEM PEAK Aug 3 PM Jan 1 AM
Airflow (cfm/sqft)0.83
Airflow (cfm/Ton)366.7
Outside Air (%)18.0 Yo
Outside Air (cfm/sqft)0.15
Note: values above qiven at ARI conditions
HEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak)
26 0F 63 0F 63 0F 87 0F
Outside Air
99 cfm
E Eltlh
Supply Fan
550 cfm
Heating Coil 86 OF
ROOM tr
720F 720FEIIIE
COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak)
112 t78.F 83/650F 83 / 65'F 55 i 54 0F
Outside Air
99 cfm
EIIIE I
Supply Fan
550 cfm
Cooling Coil 56/540F
45.6 o/o ROOM tr
76 t62.F 76 t620FEIII E
I
EnergyPro 6.7 by EnergySoft User Number: 6712 Run Code : 201 7-01 -06T1 4 :53 : 1 5 ID Page 28 of 51
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Ratpack Residence
Date
1t612017
System Name
HVAC 7
Floor Area
1,262
ENGINEERING CHECKS SYSTEM LOAD
Number of Systems 1 COIL COOLING PEAK COIL HTG. PEAK
CFM Sensible Latent CFM Sensible
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
9,421 1 ,181 310 12,441
0
136 141
0 0
189 6,803 4,536 189 9,218
0 0
136 141
TOTAL SYSTEM LOAD '16,497 5,71 21,942
Heating System
Output per System 21,600
Total Output (Btuh)21,600
Output (Btuh/sqft)17.1
Cooling System
Output per System 24,000
Total Output (Btuh)24,000
Total Output (Tons)2.0
Total Output (Btuh/sqft)19.0
Total Output (sqfUTon)631.0
Air System
CFM per System 550 HVAC EQUIPMENT SELECTION
Airflow (cfm)550 Fujitsu FAOU24 21,899 392 13,491
Total Adjusted System Output
(Adjusted for Peak Design conditions)
21,899 392 13,491
TIME OF SYSTEM PEAK Aug 3 PM Jan 1 AM
Airflow (cfm/sqft)0.44
Airflow (cfm/Ton)275.0
Outside Air (%)34.4 0
Outside Air (cfm/sqft)0.15
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak)
26 0F 56 0F 56 0F 110 0F
Outside Air
189 cfm
E EIII
Supply Fan
550 cfm
Heating Coil 1100F
ROOM l
72 0F 720FEIII E
II
COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak)
112 I 78 0F 90/68"F 90/680F 52t510F
Outside Air
189 cfm
I
Supply Fan
550 cfm
Cooling Coil 53/51 0F
386%ROOM tr
781 6',t.F 78l61 0F
EIIIE
EneryyPrc 6.7 by EnergySoft User Number: 6712 Run Code : 201 7-01 -06T1 4 : 53 : 1 5 ID:Page 29 of 51
ETI TE
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Ratpack Residence
Date
1t612017
System Name
HVAC 8
Floor Area
581
ENGINEERING CHECKS SYSTEM LOAD
Number of Systems 1 COIL COOLING PEAK COIL HTG. PEAK
CFM Sensible Latent CFM Sensible
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
201 4,694 544 454 7,477
0
68 85
0
87 3,1 43 1,686 87 4
0
68 85
TOTAL SYSTEM LOAD 7,972 2,230 1 1,900
Heating System
Output per System 21,600
Tota! Output (Btuh)21,600
Output (Btuh/sqft)37.2
Cooling System
Output per System 18,000
Total Output (Btuh)18,000
Total Output (Tons)1.5
Total Output (Btuh/sqft)31.0
Total Output (sqfUTon)387.3
Air System
CFM per System 550 HVAC EQUIPMENT SELECTION
Airflow (cfm)550 Fujitsu FAOU18 16,152 0 13,491
Total Adjusted System Output
(Adjusted for Peak Design conditions)
16,152 0 13,491
TIME OF SYSTEM PEAK Aug 3 PM Jan 1 AM
Airflow (cfm/sqft)0.95
Airflow (cfm/Ton)366.7
Outside Air (%)15.8 %
Outside Air (cfm/sqft)0.15
Note: values above given at ARI conditions
HEATTNG SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak)
26 0F 65 0F
Outside Air
87 cfm Supply Fan
550 cfm
Heating Coil 87 OF
ROOM tr
72"F 720F
IEllIE
COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak)
112 I 78 oF 83/66"F 83/660F 56/540F
Outside Air
87 cfm
H-T-I IE:
Supply Fan
550 cfm
Cooling Coil 56/540F
43.2 Yo ROOM tr
78/630F 78l630F
Ell I E
EnergyPro 6.7 by EnergySoft User Number: 6712 Run Code : 201 7 -01 -0671 4 : 53 : 1 5 ID Page 30 of 51
65 0F BB OFE Eltth
ROOM LOAD SUMMARY
Project Name
Ratpack Residence 1/6/2017
Date
System Name
HVAC 1 mstr
Floor Area
862
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult.CFM Sensible Latent CFM Sensible Latent CFM Sensible
452 19,249Surte 7 Sfe 7 1 832 17,872 916 832 17,872 916
. Total includes ventilation load for zonal syslems
PAGE TOTAL
TOTAL -
Pase 31 of 51IDEnerqvPro 6.7 bv EnerqvSoft User Number: 6712 RunCode: 2017-01-06714:53:15
III
832 17,872 19,249
832 17,872 19,249
ROOM LOAD SUMMARY
Project Name
Ratpack Residence
Date
1/6/2017
System Name
HVAC2,3&4
Floor Area
4,274
ROOM LOAD SUMMARY
ROO[/ COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult CFM Sensible Latent CFM Sensible Latent CFM Sensible
great room Great Dining Kitchen 1 3,632 73,819 4,542 3,632 73,819 4,542 1,529 62,286
PAGE TOTAL
TOTAL -
. Total includes ventilation load for zonal systems
EnerqyPro 6.7 by EnergySoft User Number: 6712 RunCode : 201 7-01 -0671 4: 53 : 1 5 ID Pase 32 of 51
3,632 73,819 1 62,286
3,632 73,819 1 62,286
ROOM LOAD SUMMARY
Project Name
Ratpack Residence
Date
1/6/2017
System Name
HVAC 5 & 6
Floor Area
1,138
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult.CFIM Sensible Latent CFM Sensible Latent CF[/Sensible
2 Suite 2 1 219 12,435 605 219 12,435 605 255 12,402
3 Surte 3 1 215 12,185 605 215 12,185 605 247 12,042
PAGE TOTAL
TOTAL -
" Total includes ventilation load for zonal systems.
EnerqvPro 6.7 bv EnerovSoft User Number: 6712 RunCode : 201 7-01 -0671 4: 53 :1 5 ID:Paqe 33 of 51
434 24,620 1 502 24,444
434 1 502 24,44424,620
I
I
)
I
t*
ROOM LOAD SUMMARY
Project Name
Ratpack Residence
Date
1/6/201 7
System Name
HVAC 6
Floor Area
660
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Floom Name It/ult CFt\/Sensible Latent CFM Sensible Latent CFM Sensible
guest-4 Suite 4 1 581 12,640 701 581 12,640 701 945 14,350
PAGE TOTAL
TOTAL "
. Total includes ventilation load for zonal systems.
EnerqvPro 6.7 bv EnerqvSoft User Number: 6712 RunCode: 2017-01-06714:53:15 ID:Pase 34 of 51
ROOM LOAD SUMMARY
Project Name
Ratpack Residence
Date
1/6/2017
System Name
HVAC 7
Floor Area
1,262
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult.CFM Sensible Latent CFM Sensible Latent CFIV Sensible
2 Car Garage Main Garage 1 350 9,421 1,181 350 9,421 1,181 310 12,441
PAGE TOTAL
TOTAL -
" Total includes ventilation load for zonal systems.
EnergyPro 6.7 by EnersySofr User Number: 6712 RunCode: 2017-01-06714:53:15 ID:Page 35 of 51
I
t
(
I
(
350 9,421 1,181 12,441
12,4413509,421 1,181
)
Il
I
,
,
)
ROOM LOAD SUMMARY
Project Name
Ratpack Residence
Date
1/6/2017
System Name
HVAC 8
Floor Area
581
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult CFtU Sensible Latent CFM Sensible Latent CFIVI Sensible
Cart Garage Zone Caft Qarage 1 201 4,694 il4 201 4,694 544 454 7,477
PAGE TOTAL
TOTAL *
" Total includes ventilation load for zonal systems
EnerqvPro 6.7 bv EnersvSoft User Number: 6712 RunCode : 201 7-01 -0671 4: 53 :1 5 ID Pase 36 of 51
ROOM HEATING PEAK LOADS
Project Name
Ratpack Residence
Date
1/6/2017
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Floor Area
lndoor Dry Bulb Temperature
Sfe I
862.0 ft'
72 0F
Time of Peak
Outdoor Dry Bulb Temperature
Jan 1 AM
26 0F
Conduction Area U-Value AT
OF
Btu/hr
862.0
1,845.0
103.0
250.0
12.0
perim = 100.0
424.0
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
0.0260
0.0690
0.3700
0.4600
0.5000
0.7300
0.3560
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
46
46
46
46
46
46
0
Items shown with an asterisk (.) denote conduction through an interior surface to another room Page Total
!nfiltration:I 1.00 x 1.064 x 862 x 9.00 0.266 /60] x 46
Schedule
Fraction
Air Sensible Area Ceiling Height ACH
x
AT
TOTAL HOURLY HEAT LOSS FOR ROOM 19,249
EnergyPro 6.7 by EneryySoft User Number: 6712 RunCode: 2017-01-067i 4:53:1 5 ID Page 37 of 51
I
,{
t
I
(
Roof Attic 1,031
Walt (W.21.2x6.16)5,856
Monumental .37/.26 1,753
Monumental .46/.31 5,290
Monumental .50/.20 276
Slab-On-Grade 3,358
*R-0 lnteiorWall 0
17,564
1,685
)
)
!
)
ROOM HEATING PEAK LOADS
Date
1/6/2017
Project Name
Ratpack Residence
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Floor Area
lndoor Dry Bulb Temperature
Great Dining Kitchen
4,274.0 ftz
72 0F
Time of Peak
Outdoor Dry Bulb Temperature
Jan 1 AM
26 0F
Conduction Area U-Value AT
OF Btu/hr
4,274.0
940.7
55.0
1,124.0
801.8
77.0
16.5
perim = 88.0
424.0
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
0.0260
0.0690
0.9400
0.4600
0.3700
0.7600
0.5000
0.7300
0.3560
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
46
46
46
46
46
46
46
46
0
Items shown with an asterisk (.) denote conduction through an interior surface to another room Page Total
lnfittration:I x 1.064 x 4,274 9.00 0.266 /60] x 46
Schedule
Fraction
Air Sensible ACHArea
x
Ceiling Height
x
AT
TOTAL HOURLY HEAT LOSS FOR ROOM 62,286
6.7 User Number: 6712 5
)
)
1.00
ROOM HEATING PEAK LOADS
Project Name
Ratpack Resrdence
Date
1/6/2017
BOOM INFORMATION DESIGN CONDITIONS
Room Name
Floor Area
lndoor Dry Bulb Temperature
Suite 2
569.0 ft2
72 0F
Time of Peak
Outdoor Dry Bulb Temperature
Jan 1 AM
26 0F
Conduction Area U-Value AT
OF Btu/hr
569.0
475.8
274.0
30.2
peim = 83.0
230.0
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
0.0260
0.0690
0.4600
0.3700
0.7300
0.3560
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
46
46
46
46
46
0
Items shown with an asterisk (.) denote conduction through an interior surface to another room Page Total
lnfiltration:I 1.00 x 1.064 x 569 9.00 /60] x 46
Schedule
Fraction
Air Sensible
0.266
Area
x
Ceiling Height
x
H AT
TOTAL HOURLY HEAT LOSS FOR ROOM 12,402
Roof Aftic 681
Watt (W.21.2x6.16)1,510
.46/.31 5,798
Monumental .37/.26 514
Slab-On-Grade 2,787
*R-0 lnteriorWall 0
11,290
1,112
ROOM HEATING PEAK LOADS
Project Name
Ratpack Residence
Date
1/6/2017
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Floor Area
lndoor Dry Bulb Temperature
Suife 3
569.0 ftz
72 0F
Time of Peak
Outdoor Dry Bulb Temperature
Jan 1 AM
26 0F
Conduction Area U-Value AT
OF Btu/hr
569.0
495.8
254.0
30.2
perim = 83.0
230.0
0.0260
0.0690
0.4600
0.3700
0.7300
0.3560
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
46
46
46
46
46
0
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Items shown with an asterisk (.) denote conduction through an interior surface to another room Page Total
lnfiltration:I x x x /60I 46
Fraction
1.0641.00 9.00 0.266
a
x x
AT
TOTAL HOURLY HEAT LOSS FOR ROOM 12,042
R-38 Roof Attic 681
R-21 Wall (W.21.2x6.16)1,574
Monumental .46/.31 5,375
Monumental .37/.26 514
Slab-On-Grade 2,787
*R-0 lnteiorWall 0
10,930
1,112
aqe 40 of 51
ROOM HEATING PEAK LOADS
Project Name
Ratpack Residence
Date
1/6/2017
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Floor Area
lndoor Dry Bulb Temperature
Suite 4
660.0 ft2
72 0F
Time of Peak
Outdoor Dry Bulb Temperature
Jan 1 AM
26 0F
Conduction Area U-Value AT
OF Btu/hr
660.0
783.8
246.0
30.2
perim = 121.0
124.0
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
0.0260
0.0690
0.4600
0.3700
0.7300
0.3560
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
46
46
46
46
46
0
Items shown with an asterisk (.) denote conduction through an interior surface to another room Page Total
lnfiltration:I x x 660 x x /60I x 46
le Air Area iling Height AT
Fraction
1.0641.00 9.00 0.266
TOTAL HOURLY HEAT LOSS FOR ROOM 14,350
7 6712
Roof Attic 789
Wall (W.21.2x6.16)2,488
.46/31 5,205
.37/.26 514
4,063
*R-0 lnteiorWall 0
13,060
1,290
ROOM HEATING PEAK LOADS
Project Name
Ratpack Residence
Date
1/6/2017
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Floor Area
lndoor Dry Bulb Temperature
Main Garage
1,262.0 ft2
72 0F
Time of Peak
Outdoor Dry Bulb Temperature
Jan 1 AM
26 0F
Conduction Area U-Value AT
OF Btu/hr
1,262.0
896.8
24.0
286.2
perim = 120.0
224.0
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
0.0260
0.0690
0.5000
0.0788
0.7300
0.3560
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
46
46
46
46
46
0
Items shown with an asterisk (.) denote conduction through an interior surface to another room Page Total
lnfiltration:I x x x x /60] x
r g A
Fraction
1.064 1,2621.00 9.00 0.266
TOTAL HOURLY HEAT LOSS FOR ROOM 12,441
51
R-38 Roof Attic 1,509
R-21 Walt (W.21.2x6.16)2,846
Wood Door 552
lnsulated Gange Door 1,037
Slab-On-Grade 4,030
*R-0 lnteriorWall 0
9,975
2,467
ROOM HEATING PEAK LOADS
Project Name
Ratpack Residence
Date
1/6/2017
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Floor Area
lndoor Dry Bulb Temperature
Caft Garage
581.0 ft'
72 0F
Time of Peak
Outdoor Dry Bulb Temperature
Jan 1 AM
26 0F
Conduction Area U-Value AT "F Btu/hr
581.0
664.2
188.8
perim = 85.0
292.0
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
0.0260
0.0690
0.0788
0.7300
0.3560
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
46
46
46
46
0
Items shown with an asterisk (.) denote conduction through an interior surface to another room Page Total
Infiltration:I 1.00 x 1.064 x 581 x x /60I x 46
Schedule
Fraction
Air Sensible Area ng Height AT
9.00 0.266
TOTAL HOURLY HEAT LOSS FOR ROOM 7,477
6.7 User Number: 6712
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Ratpack Residence
Date
1/6/2017
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Floor Area
lndoor Dry Bulb Temperature
Sfe 7
862.0 ft'
76 0F
Outdoor Dry Bulb Temperature
Outdoor Wet Bulb Temperature
Outdoor Daily Range:
1120F
78 0F
34 0F
Surfaces Orientation Area U-Factor CLTDl Btu/hr
(w
(E)
(s)
(W
(N)
862.0
150.0
594.2
307.0
793.8
424.0
x
x
x
x
x
x
x
x
x
0.0260
0.0690
0.0690
0.0690
0.0690
0.3560
x
x
x
x
x
x
x
x
x
56.0
32.1
27.1
32.6
29.0
0.0
Page Total
Items shown with an asterisk (") denote conduction through an interior surface to another room1. Cooling Load Temperature Difference (CLTD)
Shaded
Fenestration Orientation Area GLF
Unshaded
Area GLF Btu/hr
(s)
(s)
rs/
(w
(N)
(N)
(N)
41.0
53.0
31.8
49.6
0.0
0.0
0.0
x
x
x
x
x
x
x
x
x
17.0
20.7
17.0
20.7
17.0
20.7
17.4
+
+
+
+
+
+
+
+
+
x
x
x
x
x
x
x
x
x
Page Total
lnternal Gain Btu/hr
2.6
862
Occupants
Floor Area
x
x
245
0.50
Btuh/occ.
w/sqft
!nfiltration:1.064 x 0.88 x 35.55 x 36
Air Sensible CFM ELA AT
0.0
0.0
0.0
83.4
30.2
64.0
12.0
18.4
22.3
18.4
38.4
25.4
30.7
23.9
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 17,872
Latent Gain Btu/hr
2.6 Occupants X 155 Btuh/occ.
lnfiltration:x 0.88 x 35.55 x 0.00344
Air nsible CFM ELA AW
4,771
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 401
EnerqvPro 6.7 bv EnerqvSofr User Number: 6712 RunCode:2017-01-06T14:53:15 lD Paqe 44 of 51
R-38 Roof Attic 1
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)1 ,11
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)1,
*R-0 lnterior Wall
4,
D2 699
22 1,
D3
21 4,231
D1
20 1,963
c2 286
1,471
1
401
515
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Ratpack Residence
Date
1/6/2017
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Floor Area
lndoor Dry Bulb Temperature
Great Dining Kitchen
4,274.0 ft2
76 0F
Outdoor Dry Bulb Temperature
Outdoor Wet Bulb Temperature
Outdoor Daily Range:
1120F
78 0F
34 0F
o ue Surfaces Orientation Area U-Factor CLTD1 Btu/hr
(W
(E)
(s)
(W
(N)
4,274.4
480.4
64.0
236.6
159.7
424.0
x
x
x
x
x
x
x
x
x
0.0260
0.0690
0.0690
0.0690
0.0690
0.3560
x
x
x
x
x
x
x
x
x
Page Total
Items shown with an asterisk (.) denote conduction through an interior surface to another room1. Cooling Load Temperature Difference (CLTD)
Shaded
Fenestration Orientation Area GLF
Unshaded
Area GLF Btu/hr
(E)
(E)
(E)
(s)
(s/
(s)
(s)
(s)
(s)
11.9
348.4
0.0
0.0
128.4
77.0
95.1
0.0
0.0
x
x
x
x
x
x
x
x
x
37.0
20.7
17.0
20.7
17.0
21.9
17.0
17.0
17.0
+
+
+
+
+
+
+
+
+
x
x
x
x
x
x
x
x
x
Page Tota!
lnternal Gain Btu/hr
12.8
4,274
Occupants
Floor Area
x
x
245
0.50
Btuh/occ.
w/sqft
lnfiltration:1.064 x 0.88 x 176.28 x 36
Air Sensible CFM ELA AT
56.0
32.1
27.1
32.6
29.0
0.0
43.1
124.6
47.6
178.0
0.0
0.0
0.0
16.1
16.4
63.1
37.2
30.9
22.3
18.4
22.8
18.4
18.4
18.4
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 73,819
Latent Gain Btu/hr
12.8 Occupants X 155 Btuh/occ.
lnfiltration:x 0.88 x 176.28 x 0.00344
CFM ELA AW
4,771
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 1,987
EnerovPro 6.7 bv EnemvSoft User Number: 6712 RunCode: 201 7-01 -0671 4: 53 :1 5 ID Paqe 45 of 51
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)1
R-21 Wall (W.21.2x6.16)1
R-21 Wall (W.21.2x6.16)531
R-21 Wall (W.21.2x6.16)
*R-0 lnteriorWall
8,258
01 3,159
58 11,852
G4 1,471
04 3,978
A 2,189
23 1,685
E2 1,621
G2
G3
26,
3,141
5,
1
2,555
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Ratpack Residence
Date
1/6/201 7
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Floor Area
lndoor Dry Bulb Temperature
Great Dining Kitchen
4,274.0 ft2
76 0F
Outdoor Dry Bulb Temperature
Outdoor Wet Bulb Temperature
Outdoor Daily Range:
1120F
78 0F
34 0F
Surfaces Orientation Area U-Factor CLTDl Btu/hr
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Page Total
Items shown with an asterisk (") denote conduction through an interior surface to another room1. Cooling Load Temperature Difference (CLTD)
Shaded
Fenestration Orientation Area GLF
Unshaded
Area GLF Btu/hr
(W
(W
(W
(N)
(N)
(N)
(N)
473.0
0.0
122.3
0.0
0.0
0.0
0.0
x
x
x
x
x
x
x
x
x
20.7
17.0
17.0
17.0
17.0
17.0
17.4
+
+
+
+
+
+
+
+
+
x
x
x
x
x
x
x
x
x
38.4
31.9
31.9
25.4
25.4
25.4
23.9
Page Total
lnternal Gain Btu/hr
12.8
4,274
Occupants
Floor Area
x
x
245
0.50
Btuh/occ.
w/sqft
lnfiltration:x x x 36
r e FM AT
0.0
47.6
72.5
177.0
55.0
23.8
16.5
1.064 0.88 176.28
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 73,819
Latent Gain Btu/hr
12.8 Occupants X 155 Btuh/occ.
lnfiltration:4,771 x 0.88 x 176.28 x 0.00344
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 1,987
EnerqvPro 6.7 bv EnerqvSoft User Number: 6712 RunCode:2017-01-06714:53:15 lD:Paqe 46 of 51
24 9,793
G1 1,519
E1 4,399
B 4,497
G5 1,398
G6 605
c1 394
3,141
5,
1,
2,
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Ratpack Resrdence
Date
1/6/2017
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Floor Area
lndoor Dry Bulb Temperature
Suite 2
569.0 ft'
76 0F
Outdoor Dry Bulb Temperature
Outdoor Wet Bulb Temperature
Outdoor Daily Range:
1120F
78 0F
34 0F
o ue Surfaces Orientation Area U-Factor CLTDl Btu/hr
(W
(s,)
(W
(N)
569.0
121.8
212.0
142.0
230.0
x
x
x
x
x
x
x
x
x
0.0260
0.0690
0.0690
0.0690
0.3560
x
x
x
x
x
x
x
x
x
56.0
27.1
32.6
29.0
0.0
Page Total
Items shown with an asterisk (.) denote conduction through an interior surface to another room1. Cooling Load Temperature Difference (CLTD)
Shaded
Fenestration Orientation Area GLF
Unshaded
Area GLF Btu/hr
(s/
(s/
(w
(N)
(N)
0.0
0.0
40.3
0.0
0.0
x
x
x
x
x
x
x
x
x
20.7
17.0
20.7
20.7
20.7
+
+
+
+
+
+
+
+
+
78.0
30.2
67.7
53.0
35.0
x
x
x
x
x
x
x
x
x
22.3
18.4
38.4
30.7
30.7
Page Total
Internal Gain Btu/hr
M
=Or,Or"n, ---l
1.7
569
Occupants
Floor Area
x
x
245
0.50
Btuh/occ.
w/sqft
lnfiltration:x 0.88 x 23.47 x 36
Air Sensi CFM ELA AT
1.064
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 12,435
Latent Gain Btu/hr
1.7 Occupants X 155 Btuh/occ.
lnfiltration:4,771 x 0.88 x 23.47 x 0.00344
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 265
EnergyPro 6.7 by EnergySofr User Number: 6712 RunCode:2017-01-06714:53:15 lD:Pase 47 of 51
Occupants
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Ratpack Resrdence
Date
1/6/2017
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Floor Area
lndoor Dry Bulb Temperature
Suite 3
569.0 ft2
76 0F
Outdoor Dry Bulb Temperature
Outdoor Wet Bulb Temperature
Outdoor Daily Range:
1120F
78 0F
34 0F
ue Surfaces Orientation Area U-Factor CLTDl Btu/hr
(W
(E)
(s)
(N)
569.0
232.0
121.8
142.0
230.0
x
x
x
x
x
x
x
x
x
0.0260
0.0690
0.0690
0.0690
0.3560
x
x
x
x
x
x
x
x
x
56.0
32.1
27.1
29.0
0.0
Page Total
Items shown with an asterisk (") denote conduction through an interior surface to another room
1. Cooling Load Temperature Difference (CLTD)
Shaded
Fenestration Orientation Area GLF
Unshaded
Area GLF Btu/hr
(E)
(s)
rs)
(N)
(N)
0.0
0.0
78.0
0.0
0.0
x
x
x
x
x
x
x
x
x
20.7
17.0
20.7
20.7
20.7
+
+
+
+
+
+
+
+
+
88.0
30.2
0.0
35.0
53.0
x
x
x
x
x
x
x
x
x
37.2
18.4
22.3
30.7
30.7
Page Total
lnternal Gain Btu/hr
1.7
569
Occupants
Floor Area
x
x
245
0.50
Btuh/occ
w/sqft
lnfiltration:1.064 x 0.88 x 23.47 x 36
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 12,185
Latent Gain Btu/hr
1.7 Occupants X 155
lnfiltration:4,771 x 0.88 x 23.47 x 0.00344
Air Sensible CFM ELA AW
Btuh/occ
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 265
EnerqvPro 6.7 bv EnerqvSoft User Number: 6712 RunCode:2017-01-06T14:53:15 lD Page 48 of 51
tt
R-38 Roof Attic
R-21 Wall (W.21.2x6.1 6)
R-21 Wall (W.21.2x6.1 6)
R-21 Wall (W.21.2x6.1 6)
*R-0 lnteriorWall
1
37 3,277
F2 556
42 1 ,615
35 1,074
36 1,626
8,1
971
RESIDENTIAL ROOM GOOLING LOAD SUMMARY
Project Name
Ratpack Resrdence
Date
1/6/2017
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Floor Area
lndoor Dry Bulb Temperature
Suite 4
660.0 ftz
76 0F
Outdoor Dry Bulb Temperature
Outdoor Wet Bulb Temperature
Outdoor Daily Range:
1120F
78 0F
34 0F
ue Surfaces Orientation Area U-Factor CLTDl Btu/hr
(W
(E)
(s/
(W
(N)
660.0
200.0
219.8
112.0
252.0
124.0
x
x
x
x
x
x
x
x
x
0.0260
0.0690
0.0690
0.0690
0.0690
0.3560
x
x
x
x
x
x
x
x
x
56.0
32.1
27.1
32.6
29.0
0.0
Page Total
Items shown with an asterisk (.) denote conduction through an interior surface to another room1. Cooling Load Temperature Difference (CLTD)
Shaded
Fenestration Orientation Area GLF
Unshaded
Area GLF Btu/hr
(s/
(s)
(w
(N)
(N)
0.0
0.0
32.8
0.0
0.0
x
x
x
x
x
x
x
x
x
20.7
17.0
20.7
20.7
20.7
+
+
+
+
+
+
+
+
+
80.0
30.2
55.2
43.0
35.0
x
x
x
x
x
x
x
x
x
22.3
18.4
38.4
30.7
30.7
Page Total
Internal Gain Btu/hr
2.0
660
Occupants
Floor Area
x
x
245
0.50
Btuh/occ.
w/sqft
lnfiltration:1.064 x 0.88 x 27.22 x 36
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 12,640
Latent Gain Btu/hr
Occupants 2.0 Occupants X 155
lnfiltration:4,771 x 0.88 x 27.22 x 0.00344
Air Sensible CFM ELA AW
Btuh/occ.
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 307
EnerqvPro 6.7 bv EneruvSofr User Number: 6712 RunCode:2017-01-06T14:53:15 lD:Paoe 49 of 51
R-38 Roof Attic 961
R-21 Wall (W.21.2x6.16)443
R-21 Wall (W.21.2x6.16)411
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
*R-0 lnterior Wall
2,571
50 1,788
F3 556
45 2,800
44 1,319
43 1,074
7,
1,1
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Ratpack Residence
Date
1/6/201 7
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Floor Area
Indoor Dry Bulb Temperature
Main Garage
1,262.0 ft2
78 0F
Outdoor Dry Bulb Temperature
Outdoor Wet Bulb Temperature
Outdoor Daily Range:
1120F
78 0F
34 0F
ue Surfaces Orientation Area U-Factor CLTDl Btu/hr
(w
(E)
(E)
(s)
(W
(w
(N)
1,262.0
452.0
24.0
70.0
119.8
286.2
255.0
224.0
x
x
x
x
x
x
x
x
x
0.0260
0.0690
0.5000
0.0690
0.0690
0.0788
0.0690
0.3560
x
x
x
x
x
x
x
x
x
Page Total
Items shown with an asterisk (.) denote conduction through an interior surface to another room.1. Cooling Load Temperature Difference (CLTD)
Shaded
Fenestration Orientation Area GLF
Unshaded
Area GLF Btu/hr
x
x
x
x
x
x
x
x
x
+
+
+
+
+
+
+
+
+
x
x
x
x
x
x
x
x
x
Page Total
lnternal Gain Btu/hr
3.8
1,262
Occupants
Floor Area
x
x
245
0.50
Btuh/occ.
w/sqft
lnfiltration:x 0.87 x 52.05 x 34
Air ble CFM ELA AT
56.0
32.1
32.1
27.1
32.6
32.6
29.0
-2.0
1.064
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 9,421
Latent Gain Btu/hr
3.8 Occupants X 155
lnfiltration:4,771 x 0.87 x 52.05 x 0.00276
Air Sensible CFM ELA AW
Btuh/occ
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 587
EnerqvPro 6.7 bv EneruvSoft User Number: 6712 RunCode:2017-01-06T14:53:15 lD:Paqe 50 of 51
R-38 Roof Attic 1,
R-21 Wall (W.21.2x6.16)1,001
Wood Door
R-21 Wall (W.21.2x6.16)13
R-21 Wall (W.21.2x6.16)269
lnsulated Garage Door 734
R-21 Wall (W.21.2x6.16)
*R-0 lnteriorWall -159
4,709
2,1
1
Occupants
,
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Ratpack Residence
Date
1/6/201 7
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Floor Area
lndoor Dry Bulb Temperature
Cart Garage
581.0 ft'
7g oF
Outdoor Dry Bulb Temperature
Outdoor Wet Bulb Temperature
Outdoor Daily Range:
1120F
7g oF
34 0F
o ue Surfaces Orientation Area U-Factor CLTDl Btu/hr
(W
(E)
(s/
(W
(W
(N)
(N)
581.0
190.0
35.0
239.6
110.4
199.6
78.4
292.0
x
x
x
x
x
x
x
x
x
0.0260
0.0690
0.0690
0.0690
0.0788
0.0690
0.0788
0.3560
x
x
x
x
x
x
x
x
x
Page Total
Items shown with an asterisk (.) denote conduction through an interior surface to another room1. Cooling Load Temperature Difference (CLTD)
Shaded
Fenestration Orientation Area GLF
Unshaded
Area GLF Btu/hr
x
x
x
x
x
x
x
x
x
+
+
+
+
+
+
+
+
+
x
x
x
x
x
x
x
x
x
Page Total
lnternal Gain Btu/hr
1.7
581
Occupants
Floor Area
x
x
245
0.50
Btuh/occ.
w/sqft
lnfiltration:x 0.87 x 23.96 x 34
CFM ELA AT
56.0
32.1
27.1
32.6
32.6
29.0
29.0
-2.0
1.064
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 4,694
Latent Gain Btu/hr
1.7 Occupants X 155
lnfiltration:4,771 x 0.87 x 23.96 x 0.00276
Air Sensible CFM ELA AW
Btuh/occ
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 270
EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode:2017-01-06T14:53:15 lD:Paqe 51 of 51
r
I
Scott
74-818 Velie Way
Palm Deseft, CA 92260
Phone/Fax (760) 200-47 80
Cell: (760) 702-5406
E-Mail ionscott @ title24f oryou.com
www. scottdesignandtitle24.com
Design and Title 24,lnc.
January 6,2017
INVOICE # 3820
Bruce Maize
Discovery Builders
53965 Humbolt Blvd,
La Qunitas, CA 92253
bdmaize @ aol.com
(760) 218-8420
Re: Revised Title 24 Energy Compliance Calculations
Ratpack Residence
La Quinta, CA 92253
WORK PERFORMED.
Revise Title 24 Energy Compliance Calculations
changing windows and AC units $450.00
THANK YOU
TOTAL INVOICE $450.00
We now accept credit cards as a method of payment through PayPal.
Go to www.scottdesi n titl 24.m and click on 'make a payment'.
Please remit to:
Scott Design and Title 24, lnc.
74-81 8 Velie Way, STE 8
Palm Desert, Ca 92260