BCOM2022-0025 TAB ReportREPORT DATE:AABC TBE: Eddie Alejandre, P.E. HVAC CONTRACTOR:Modern Air Conditioning Co. 43498REPORT CERTIFICATION#: July 7, 2023 PROJECT: LOS ANGELES AIR BALANCE COMPANY INC. 1848 W. 11TH ST., SUITE #N, UPLAND, CA 91786 HVAC TEST AND BALANCE ANALYSIS REPORT TEL# : 1-800-429-6880 Welbe Health ARCHITECT: LOCATION:La Quinta, California Harriman Kinyon MECHANICAL ENGINEER:Engineering Network Project: WELBE HEALTH, LA QUINTA HVAC TEST AND BALANCE SUMMARY All components of the HVAC system(s) on this project were tested, adjusted and balanced to within the tolerances set forth by AABC and the design documents, with the following exceptions: Setting the Industry Standard No Exceptions "Summary", Page: 1 of 1 Project: WELBE HEALTH, LA QUINTA Design Actual % Design Actual % Design Actual % 5090 NVL #####2650 NVL #####2005 NVL ##### 5370 5389 100%2650 2784 105%2005 2034 101% 3840 3842 100%1730 1838 106%1310 1334 102% 1530 1547 101%920 946 103%695 700 101% Discharge (+)1.12 0.80 0.96 Suction (-)0.40 0.30 0.08 Ext. SP (inches w.g.)1.10 1.52 1.00 1.10 1.00 1.04 TRANE #####TRANE #####TRANE ##### 2.5 BHP 5.0 0.9 BHP 3.0 1.5 BHP 1.0 90% 58% POTENTIOMETER 6.0 208 208-210-210 208 208-210-210 208 206/210/210 3 3 3 3 3 3 11.0 8.6-8.8-8.8 8.8 2.3-2.3-2.4 9.4 5.5/5.6/5.5 E.P. E.P. E.P. DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Remarks / Notes: * ** Fan I.D.#AC Fan Test AC AC Service 100, 140, 103, 104, 102 100, 140, 181, 182 1**2**3* 130, 131, 132 Location ROOF ROOF ROOF Manufacturer TRANE TRANE TRANE Model Number YSJ150 YSJ072 YHC067 Serial Number 232013441L 232013521L 231715467L C F M Air @ Fan Supply Air @ Outlets Return Air @ Inlets S T A T I C Outside Air F A N M O T O R Manufacturer Horsepower RPM Voltage Phase Amperage Service Factor D R I V E Motor Sheave % Closed Fan Sheave Belt Size / Qty Fan RPM Center to Center Adjustment, In / Out PEF is installed, no power 6/22/23 PEF is not installed 6/22/23 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 1 Project: WELBE HEALTH, LA QUINTA Design Actual % Design Actual % 412 433 105%412 429 104% 412 433 105%412 429 104% 412 433 105%412 429 104% Discharge (+)NVL NVL Suction (-)NVL NVL Ext. SP (inches w.g.)0.10 NVL 0.10 NVL MITSUBISHI #####MITSUBISHI 0.04 0.04 4 SPEED MEDIUM LOW 4 SPEED MEDIUM LOW 208 209 208 209 1 1 1 1 0.55 0.30 0.55 0.30 T.P. T.P. DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Remarks / Notes: Fan Test Fan I.D.#FC FC A B Service ELEV. MACH. RM. IT ROOM Location WALL MOUNT WALL MOUNT Manufacturer MITSUBISHI MITSUBISHI Model Number TPLA0A0121LA00A TPLA0A0121LA00A Serial Number 26M0057565TLLR 26M0057565TLLR C F M Air @ Fan Supply Air @ Outlets Return Air @ Inlets S T A T I C F A N M O T O R Manufacturer Horsepower RPM Voltage Phase Amperage Service Factor % Closed Fan Sheave Belt Size / Qty Fan RPM D R I V E Motor Sheave Center to Center Adjustment, In / Out L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 2 Project: WELBE HEALTH, LA QUINTA Design Actual % Design Actual % Design Actual % 800 NVL #####370 NVL #####440 NVL ##### 840 807 96%370 373 101%440 439 100% 460 426 93%230 231 100%305 300 98% 380 381 100%140 142 101%135 144 107% Discharge (+)0.18 0.13 0.15 Suction (-)0.22 0.10 0.13 Ext. SP (inches w.g.)0.90 0.40 0.60 0.23 0.90 0.28 DNL #####DNL DNL DNL DNL DNL 2 SPEED HIGH SPEED 2 SPEED LOW SPEED 2 SPEED LOW SPEED 208 209 208 211 208 211 1 1 1 1 1 1 2.7 1.1 2.1 0.9 1.6 1.0 T.P. T.P. T.P. DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Remarks / Notes: Fan Test Fan I.D.#FC FC FC 1-1 1-2 1-3 Service KITCHEN CONFERENCE 133, 134 CONFERENCE 133, 134 CEILING CEILING CEILINGLocation Manufacturer MITSUBISHI MITSUBISHI MITSUBISHI TPEFYP030MH142A TPEFYP015MH142A TPEFYP018MH142AModel Number Serial Number 12W003047GEHA5 1YWOO2417GEHA1 14W002847GEHAZ C F M Air @ Fan Supply Air @ Outlets Return Air @ Inlets S T A T I C Outside Air F A N M O T O R Manufacturer Horsepower RPM Voltage Phase Amperage Service Factor D R I V E Motor Sheave Fan Sheave % Closed Belt Size / Qty Fan RPM Center to Center Adjustment, In / Out L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 3 Project: WELBE HEALTH, LA QUINTA Design Actual % Design Actual % Design Actual % 1480 NVL #####680 NVL #####1240 NVL ##### 1480 1427 96%680 679 100%1240 1265 102% 1065 1027 96%510 512 100%850 883 104% 415 420 101%170 176 104%390 382 98% Discharge (+)0.19 0.16 0.16 Suction (-)0.20 0.15 0.15 Ext. SP (inches w.g.)0.90 0.39 0.90 0.31 0.90 0.31 DNL #####DNL DNL DNL DNL DNL 4 SPEED HIGH SPEED 2 SPEED HIGHSPEED 2 SPEED HIGH SPEED 208 212 208 210 208 211 1 1 1 1 1 1 4.2 2.6 2.1 1.8 4.2 2.5 T.P. T.P. T.P. DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Remarks / Notes: Fan Test Fan I.D.#FC 1-4 FC FC 1-5 1-6 GYMService NURSE / OFFICES EXAM ROOMS Location CEILING CEILING CEILING MITSUBISHIManufacturer MITSUBISHI MITSUBISHI Model Number TPEFYP054MH142A TPEFY024MH142A TPEFY036MH142A 26W007597GEHA6Serial Number 24W005657GEHA8 1XW004307GEHA3 C F M Air @ Fan Supply Air @ Outlets Return Air @ Inlets S T A T I C Outside Air F A N M O T O R Horsepower RPM Manufacturer Voltage Phase Amperage Service Factor Motor Sheave Fan Sheave D R I V E % Closed Belt Size / Qty Fan RPM Center to Center Adjustment, In / Out L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 4 Project: WELBE HEALTH, LA QUINTA Design Actual % 1340 NVL ##### 1340 1042 78% 580 282 49% 770 760 99% Discharge (+)0.18 Suction (-)0.12 Ext. SP (inches w.g.)0.90 0.30 TRANE ##### 870W 3 SPEED HIGH SPEED 208 212 1 1 7.7 4.9 T.P. DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Remarks / Notes: * Fan Test Fan I.D.#FC 1-7* Service TOILET ROOMS Location CEILING Manufacturer MITSUBISHI Model Number TPEFYP072MH140A Serial Number 12W016707GEHB4 C F M Air @ Fan Supply Air @ Outlets Return Air @ Inlets S T A T I C Outside Air RPM F A N M O T O R Manufacturer Horsepower Voltage Phase Amperage Service Factor D R I V E Motor Sheave % Closed Fan Sheave Belt Size / Qty Fan RPM Center to Center Adjustment, In / Out Unable to obtain design CFM. Unit is a direct-drive fan type in high speed. L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 5 Project: WELBE HEALTH, LA QUINTA Design Actual % Design Actual % Design Actual % 620 NVL #####440 NVL #####1200 NVL ##### 620 600 97%440 468 106%1200 1250 104% 520 515 99%295 313 106%1080 1123 104% 90 85 94%145 155 107%120 127 106% Discharge (+)0.18 0.13 0.15 Suction (-)0.12 0.12 0.15 Ext. SP (inches w.g.)0.90 0.30 0.90 0.25 0.90 0.30 DNL #####DNL DNL DNL DNL DNL 2 SPEED HIGH SPEED 2 SPEED LOW SPEED 2 SPEED LOW SPEED 208 212 208 210 208 212 1 1 1 1 1 1 2.1 1.1 1.63 0.9 4.2 3.0 T.P. T.P. T.P. DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Remarks / Notes: Fan Test Fan I.D.#FC FC FC 2-1 2-2 2-3 Service H.R. /LOBBY CONFERENCE. 221 ADMIN AREA CEILINGLocation CEILING CEILING Manufacturer MITSUBISHI MITSUBISHI MITSUBISHI TPEFYP036Model Number TPEFYP024 TPEFYP015MH142A Serial Number 11W004497GEHA3 1YW002427GEHA1 13W006797GEHA6 Outside Air C F M Supply Air @ Outlets Return Air @ Inlets Air @ Fan S T A T I C RPM F A N M O T O R Manufacturer Horsepower Voltage Phase Amperage Service Factor Fan Sheave D R I V E Motor Sheave % Closed Fan RPM Belt Size / Qty Center to Center Adjustment, In / Out L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 6 Project: WELBE HEALTH, LA QUINTA Design Actual % Design Actual % Design Actual % 340 NVL #####260 NVL #####650 NVL ##### 340 326 96%260 250 96%650 681 105% 290 279 96%165 160 97%555 593 107% 50 47 94%95 90 95%95 88 93% Discharge (+)0.18 0.12 0.20 Suction (-)0.14 0.10 0.15 Ext. SP (inches w.g.)0.60 0.32 0.60 0.22 0.90 0.35 DNL #####DNL DNL 0.114 0.114 DNL 3 SPEED HIGH SPEED 3 SPEED HIGH SPEED 3 SPEED HIGH SPEED 208 210 208 210 208 210 1 1 1 1 1 1 2.1 1.1 1.75 1.2 2.1 1.1 T.P. T.P. T.P. DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Remarks / Notes: Fan Test Fan I.D.#FC FC FC 2-62-4 2-5 OFFICE 227, CORRIDORService OFFICES 223, 224 CONFERENCE 225 Location CEILING CEILING CEILING MITSUBISHIManufacturer MITSUBISHI MITSUBISHI Model Number TPEFYP012 TPEFYP008 TPEFYP024 1XW004317GEHA3Serial Number 24R0161230P90W 19R0010130P90V Outside Air Supply Air @ Outlets Return Air @ Inlets C F M Air @ Fan S T A T I C Manufacturer Horsepower RPM F A N M O T O R Voltage Phase Amperage Service Factor D R I V E Motor Sheave % Closed Fan Sheave Belt Size / Qty Fan RPM Center to Center Adjustment, In / Out L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 7 Project: WELBE HEALTH, LA QUINTA Design Actual % Design Actual % Design Actual % 1370 NVL #####280 NVL #####380 NVL ##### 1320 1348 102%280 255 91%360 338 94% 1055 1076 102%210 189 90%275 258 94% 265 272 103%70 66 94%85 80 94% Discharge (+)0.16 0.11 0.12 Suction (-)0.16 0.14 0.12 Ext. SP (inches w.g.)0.90 0.32 0.60 0.25 0.60 0.24 DNL #####DNL DNL DNL DNL DNL 2 SPEED HIGH SPEED 3 SPEED HIGH SPEED 3 SPEED HIGH SPEED 208 211 208 211 208 211 1 1 1 1 1 1 4.2 2.6 1.75 1.2 2.1 0.9 T.P. T.P. T.P. DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Remarks / Notes: Fan Test Fan I.D.#FC FC FC 2-7 2-8 2-9 Service LOUNGE 230 CONF 228 CONF 229 Location CEILING CEILING CEILING Manufacturer MITSUBISHI MITSUBISHI MITSUBISHI Model Number TPEFYP036 TPEFYP008 TPEFYP012 Serial Number 27W007877GEHA6 19R0010730P90V 24R0161430P90W Outside Air Supply Air @ Outlets Return Air @ Inlets S T A T I C C F M Air @ Fan F A N M O T O R Manufacturer Horsepower RPM Voltage Phase Amperage Service Factor D R I V E Motor Sheave % Closed Belt Size / Qty Fan Sheave Fan RPM Center to Center Adjustment, In / Out L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 8 Project: WELBE HEALTH, LA QUINTA EXHAUST Design Actual % Design Actual % Design Actual % 1150 1151 100%415 450 108%150 231 154% 1150 992 86%415 408 98%510 504 99% Discharge (+)0.40 0.008 0.001 Suction (-)0.48 0.04 0.02 Ext. SP (inches w.g.)0.88 0.048 0.021 TRANE #####TRANE TRANE 0.41 0.41 0.41 4 SPEED HIGH SPEED 4 SPEED MED SPD - HI SPD 4 SPEED MED SPD - HI SPD 208 211 208 212 208 212 1 1 1 1 1 1 1.34 1.1 1.34 1.0 1.34 0.9 T.P. T.P. T.P. DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Remarks / Notes: Fan Test ERV 1-1 1-2 1-3 Fan I.D.#ERV ERV Service 128, 125, 126, 122 173 141 CEILING CEILING CEILINGLocation Manufacturer MITSUBISHI MITSUBISHI MITSUBISHI TLGHF1200RVX02A TLGHF0600RVX02A TLGHF0600RVX02AModel Number Serial Number 22010027546179 22010040546177 22100025546177 C F M Air @ Fan Exhaust Air @ Inlets S T A T I C F A N M O T O R Manufacturer Horsepower RPM Voltage Phase Amperage Service Factor D R I V E Motor Sheave % Closed Fan Sheave Fan RPM Belt Size / Qty Center to Center Adjustment, In / Out L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 9 Project: WELBE HEALTH, LA QUINTA SUPPLY Design Actual % 985 1018 103% 1015 1010 100% 1015 1010 100% Discharge (+)0.48 Suction (-)0.44 Ext. SP (inches w.g.)DNL 0.92 TRANE ##### 0.37 4 SPEED HIGH SPEED 208 212 1 1 1.3 1.10 T.P. DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Remarks / Notes: Fan Test Fan I.D.#ERV 2-1 Service 2ND FLOOR FC'S Location CEILING Manufacturer MITSUBISHI Model Number TLGHF0940RVX02A Serial Number 82030008546178 C F M Air @ Fan Supply Air @ Outlets Outside Air S T A T I C Manufacturer Horsepower F A N M O T O R RPM Voltage Phase Amperage Service Factor D R I V E Motor Sheave % Closed Fan Sheave Fan RPM Belt Size / Qty Center to Center Adjustment, In / Out L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 10 Project: WELBE HEALTH, LA QUINTA EXHAUST Design Actual % 890 844 95% 890 830 93% Discharge (+)0.55 Suction (-)0.60 Ext. SP (inches w.g.)DNL 1.15 TRANE ##### 0.42 HIGH SPEED 208 211 1 1 1.37 1.20 T.P. DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Remarks / Notes: Fan Test Fan I.D.#ERV 2-1 240, 241, CORRIDORService Location CEILING MITSUBISHIManufacturer Model Number TLGHF094ORVX02A 22030008546178Serial Number C F M Air @ Fan Exhaust Air @ Inlets S T A T I C F A N M O T O R Manufacturer Horsepower RPM Voltage Phase Amperage Service Factor % Closed D R I V E Motor Sheave Fan Sheave Fan RPM Belt Size / Qty Center to Center Adjustment, In / Out L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 11 Project: WELBE HEALTH, LA QUINTA Design Actual % 970 NVL ##### 970 984 101% Discharge (+)0.22 Suction (-)0.19 Ext. SP (inches w.g.)0.70 0.41 VARIGREEN ##### 1/4 1/2 350-1750 SPD-CON 6.5 115 118 1 1 6.4 3.0 E.P. DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE Remarks / Notes: Fan Test Fan I.D.#EF 1 Service 121-127, 168-176 CEILINGLocation Manufacturer GREENHECK SQ-120-VG5X-QDModel Number Serial Number 19766474 Air @ Fan Exhaust Air @ Inlets C F M S T A T I C F A N M O T O R Manufacturer Horsepower RPM Voltage Phase Amperage Service Factor D R I V E Motor Sheave % Closed Fan Sheave Fan RPM Belt Size / Qty Center to Center Adjustment, In / Out L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 12 Project: WELBE HEALTH, LA QUINTA System(s): AC-1 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes AC 1 1 SG 24X6 1.0 500 515 103% 2 SG 24X6 1.0 500 513 103% 3 SG 24X6 1.0 500 509 102% 4 SG 24X6 1.0 500 505 101% 5 SG 24X6 1.0 500 492 98% 6 SG 24X6 1.0 500 497 99% 7 SG 24X6 1.0 500 485 97% 8 SG 24X6 1.0 500 506 101% 9 CD 10X10 1.0 50 50 100% 10 CD 10X10 1.0 200 197 99% 11 CD 10X10 1.0 50 52 104% 12 LD 4" 1.0 280 285 102% 13 CD 24X24 1.0 190 193 102% 14 CD 14X14 1.0 300 296 99% 15 CD 14X14 1.0 300 294 98% 5370 5389 100% Remarks / Notes: Air Distribution Test Zone / Room # Terminal Final 100 100 100 100 100 100 100 103 100 104 102 182 104 100 100 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 13 Project: WELBE HEALTH, LA QUINTA System(s): AC-1 CONT. Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes AC 1 1 RG 24X12 1.0 461 448 97% 2 RG 24X12 1.0 461 475 103% 3 RG 24X12 1.0 461 465 101% 4 RG 24X12 1.0 461 462 100% 5 RG 24X12 1.0 461 459 100% 6 RG 24X12 1.0 461 460 100% 7 RG 24X12 1.0 461 463 100% 8 RG 24X12 1.0 461 469 102% 9 CR 24X24 1.0 150 141 94% 3838 3842 100% OSA 1530 1547 101% Remarks / Notes: Air Distribution Test Zone / Terminal Final Room # 100 100 100 100 100 100 100 182 100 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 14 Project: WELBE HEALTH, LA QUINTA System(s): AC-2 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes AC 2 1 LD 4' 1.0 250 272 109% 2 LD 4' 1.0 250 269 108% 3 LD 4' 1.0 250 255 102% 4 LD 4' 1.0 250 263 105% 5 LD 4' 1.0 250 269 108% 6 LD 4' 1.0 250 262 105% 7 LD 4' 1.0 250 254 102% 8 LD 4' 1.0 250 256 102% 9 LD 4' 1.0 250 257 103% 10 LD 4' 1.0 250 266 106% 11 CD 24x24 1.0 150 161 107% 2650 2784 105% 1 LR 4' 1.0 326 349 107% 2 LR 4' 1.0 326 341 105% 3 LR 4' 1.0 326 350 107% 4 LR 4' 1.0 326 343 105% 5 LR 4' 1.0 326 345 106% 6 CR 24X24 1.0 100 110 110% 1730 1838 106% OSA 920 946 103% Remarks / Notes: Air Distribution Test Zone / Room # Terminal Final 140 140 140 140 140 140 140 140 140 181 140 140 140 140 140 140 140 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 15 Project: WELBE HEALTH, LA QUINTA System(s): AC-3 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes AC 3 1 LD 4' 1.0 265 267 101% 2 LD 4' 1.0 265 273 103% 3 LD 4' 1.0 265 255 96% 4 LD 4' 1.0 265 269 102% 5 LD 4' 1.0 265 275 104% 6 LD 4' 1.0 265 275 104% 7 LD 4' 1.0 265 278 105% 8 CD 8X8 1.0 50 50 100% 9 CD 24X24 1.0 100 92 92% 2005 2034 101% 1 LR 4' 1.0 218 220 101%* 2 LR 4' 1.0 218 226 104%* 3 LR 4' 1.0 218 222 102%* 4 LR 4' 1.0 218 225 103%* 5 LR 4' 1.0 219 215 98%* 6 LR 4' 1.0 219 226 103%* 1310 1334 102%* OSA 695 700 101% Remarks / Notes: *The required return air quantities were adjusted to allow for the design outside air requirements in the balance condition. Air Distribution Test Room # Zone / Terminal Final 130 130 130 130 130 130 130 132 131 130 130 130 130 130 130 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 16 Project: WELBE HEALTH, LA QUINTA System(s): FC 1-1 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes FC 1-1 1 CD 24X24 1.0 210 201 96% 2 CD 24X24 1.0 210 195 93% 3 CD 24X24 1.0 210 198 94% 4 CD 24X24 1.0 210 213 101% 840 807 96% 1 CR 24X24 1.0 460 426 93% OSA 380 381 100% Remarks / Notes: Air Distribution Test Room # Terminal FinalZone / 141 141 141 141 141 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 17 Project: WELBE HEALTH, LA QUINTA System(s): FC 1-2 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes FC 1-2 1 CD 24X24 1.0 200 205 103% 2 CD 24X24 1.0 70 72 103% 3 CD 24X24 1.0 100 96 96% 370 373 101% 1 CR 24X24 1.0 146 145 99%* 2 CR 24X24 1.0 84 86 102%* 230 231 100% OSA 140 142 101% Remarks / Notes: *The required return air quantities were adjusted to allow for the design outside air requirements in the balance condition. Air Distribution Test Room # Zone / Terminal Final 133 143 134 133 134 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 18 Project: WELBE HEALTH, LA QUINTA System(s): FC 1-3 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes FC 1-3 1 CD 24X24 1.0 260 254 98% 2 CD 24X24 1.0 180 190 106% 440 444 101% 1 CR 24X24 1.0 180 180 100% 2 CR 24X24 1.0 125 120 96% 305 300 98% OSA 135 144 107% Remarks / Notes: Air Distribution Test Terminal Final Room # Zone / 113 105 113 105 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 19 Project: WELBE HEALTH, LA QUINTA System(s): FC 1-4 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes FC 1-4 1 LD 48X2 1.0 350 325 93% 2 CD 24X24 1.0 120 115 96% 3 CD 24X24 1.0 100 102 102% 4 CD 24X24 1.0 50 54 108% 5 CD 24X24 1.0 50 55 110% 6 LD 48X2 1.0 350 330 94% 7 CD 24X24 1.0 50 55 110% 8 CD 24X24 1.0 50 53 106% 9 CD 24X24 1.0 120 115 96% 10 CD 24X24 1.0 240 223 93% 1480 1427 96% 1 CR 24X24 1.0 111 107 96%* 2 LR 48x2 1.0 281 266 95%* 3 LR 48x2 1.0 281 280 100%* 4 LR 48x2 1.0 281 270 96%* 5 LR 48x2 1.0 111 104 94%* 1065 1027 96%* OSA 415 420 101% Remarks / Notes: *The required return air quantities were adjusted to allow for the design outside air requirements in the balance condition. Air Distribution Test Zone / Terminal Final Room # 160 165 107 169 168 160 171 172 178 173 178 160 160 160 165 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 20 Project: WELBE HEALTH, LA QUINTA System(s): FC 1-5 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes FC 1-5 1 CD 24X24 1.0 180 182 101% 2 CD 24X24 1.0 180 168 93% 3 CD 24X24 1.0 100 99 99% 4 CD 24X24 1.0 220 230 105% 680 679 100% 1 CR 24X24 1.0 135 140 104%* 2 CR 24X24 1.0 135 134 99%* 3 CR 24X24 1.0 75 70 93%* 4 CR 24X24 1.0 165 168 102%* 510 512 100%* OSA 170 176 104% Remarks / Notes: *The required return air quantities were adjusted to allow for the design outside air requirements in the balance condition. Air Distribution Test Terminal Final Room # Zone / 164 163 162 161 164 163 162 161 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 21 Project: WELBE HEALTH, LA QUINTA System(s): FC 1-6 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes FC 1-6 1 LD 48X1 1.0 250 265 106% 2 LD 48X1 1.0 250 245 98% 3 LD 48X1 1.0 250 261 104% 4 CD 24X24 1.0 130 120 92% 5 LD 48X1 1.0 250 265 106% 6 CD 24X24 1.0 110 109 99% 1240 1265 102% 1 LD 4 ' 1.0 213 223 105% 2 LD 4 ' 1.0 213 217 102% 3 LD 4 ' 1.0 213 226 106% 4 LD 4 ' 1.0 213 217 102% 852 883 104% OSA 390 382 98% Remarks / Notes: Air Distribution Test Zone / Terminal Final Room # 150 150 150 151 150 129 150 150 150 150 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 22 Project: WELBE HEALTH, LA QUINTA System(s): FC 1-7 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes FC 1-7 1 CD 12X12 1.0 200 109 55%* 2 CD 12X12 1.0 200 210 105% 3 CD 10X10 1.0 80 110 138% 4 CD 10X10 1.0 50 36 72%* 5 CD 12X12 1.0 200 146 73%* 6 CD 10X10 1.0 140 94 67%* 7 CD 12X12 1.0 200 140 70%* 8 CD 10X10 1.0 100 78 78%* 9 CD 10X10 1.0 70 65 93% 10 CD 10X10 1.0 100 54 54%* 1340 1042 78%* 1 LR 4' 1.0 470 194 41%* 2 CR 24X24 1.0 110 88 80%* 580 282 49% OSA 770 760 99% Remarks / Notes: *Unable to obtain design CFM. Unit is a direct-drive fan type in high speed. Air Distribution Test Terminal FinalZone / Room # 128 125 128 122 126 122 121 124 123 127 150 129 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 23 Project: WELBE HEALTH, LA QUINTA System(s): FC 2-1 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes FC 2-1 1 CD 24X24 1.0 250 243 97% 2 CD 24X24 1.0 180 175 97% 3 CD 24X24 1.0 190 182 96% 620 600 97% 1 CR 24X24 1.0 180 170 94% 2 CR 24X24 1.0 150 145 97% 190 200 105% 520 515 99% OSA 90 85 94% Remarks / Notes: Air Distribution Test Zone / Terminal Final Room # 220 220 220 220 220 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 24 Project: WELBE HEALTH, LA QUINTA System(s): FC 2-2 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes FC 2-2 1 LD 4' 1.0 220 240 109% 2 LD 4' 1.0 220 228 104% 440 468 106% 1 LR 4' 1.0 147 155 105% 2 LR 4' 1.0 148 158 107% 295 313 106% OSA 145 155 107% Remarks / Notes: Air Distribution Test Terminal FinalZone / Room # 221 221 221 221 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 25 Project: WELBE HEALTH, LA QUINTA System(s): FC 2-3 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes FC 2-3 1 LD 4' 1.0 170 182 107% 2 LD 4' 1.0 170 180 106% 3 LD 4' 1.0 170 175 103% 4 LD 4' 1.0 170 182 107% 5 LD 4' 1.0 170 180 106% 6 LD 4' 1.0 170 176 104% 7 CD 24X24 1.0 180 175 97% 1200 1250 104% 1 LR 4' 1.0 232 242 104%* 2 LR 4' 1.0 232 240 103%* 3 LR 4' 1.0 231 238 103%* 4 LR 4' 1.0 231 235 102%* 5 CR 24X24 1.0 154 168 109%* 1080 1123 104%* OSA 120 127 106% Remarks / Notes: *The required return air quantities were adjusted to allow for the design outside air requirements in the balance condition. Air Distribution Test Zone / Terminal Final Room # 222 222 222 222 222 203 222 222 222 222 222 203 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 26 Project: WELBE HEALTH, LA QUINTA System(s): FC 2-4, FC 2-5 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes FC 2-4 1 CD 24X24 1.0 180 168 93% 2 CD 24X24 1.0 160 158 99% 340 326 96% 1 CR 24X24 1.0 150 142 95% 2 CR 24X24 1.0 140 137 98% 290 279 96% OSA 50 47 94% FC 2-5 1 CD 24X24 1.0 260 250 96% 1 CR 24X24 1.0 165 160 97% OSA 95 90 95% Remarks / Notes: Air Distribution Test FinalZone / Room # Terminal 223 229 223 224 225 225 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 27 Project: WELBE HEALTH, LA QUINTA System(s): System(s): FC 2-6 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes FC 2-6 1 LD 4' 1.0 220 231 105% 2 CD 24X24 1.0 170 180 106% 3 CD 24X24 1.0 260 270 104% 650 681 105% 1 CD 24X24 1.0 160 171 107% 2 CD 24X24 1.0 395 422 107% 555 593 107% OSA 95 88 93% Remarks / Notes: Air Distribution Test Zone / Terminal Final Room # 227 227 CORRIDOR CORRIDOR 227 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 28 Project: WELBE HEALTH, LA QUINTA System(s): FC 2-7 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes FC 2-7 1 CD 24X24 1.0 205 201 98% 2 CD 24X24 1.0 180 195 108% 3 CD 24X24 1.0 180 175 97% 4 CD 24X24 1.0 240 247 103% 5 CD 24X24 1.0 110 109 99% 6 CD 24X24 1.0 100 103 103% 7 CD 24X24 1.0 100 105 105% 8 RG** 24X24 1.0 205 213 104%** 1320 1348 102% 1 CR 24X24 1.0 692 700 101%* 2 CR 24X24 1.0 236 242 103%*/** 3 CR 24X24 1.0 127 134 106%* 1055 1076 102%* OSA 265 272 103% Remarks / Notes: *The required return air quantities were adjusted to allow for the design outside air requirements in the balance condition. **An RG is installed in place of a CD. Air Distribution Test Zone / Terminal Final Room # 230 CORRIDOR 230 230 241 231 CORRIDOR 240 CORRIDOR 230 231 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 29 Project: WELBE HEALTH, LA QUINTA System(s): FC 2-8 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes FC 2-8 1 CD 24X24 1.0 280 255 91% 1 CR 24X24 1.0 210 189 90%* OSA 70 66 94% Remarks / Notes: *The required return air quantities were adjusted to allow for the design outside air requirements in the balance condition. Air Distribution Test Zone / Terminal Final Room # 228 228 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 30 Project: WELBE HEALTH, LA QUINTA System(s): FC 2-9 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes FC 2-9 1 CD 24X24 1.0 280 254 91% 2 CD 24X24 1.0 40 44 110% 3 CD 24X24 1.0 40 40 100% 360 338 94% 1 CR 24X24 1.0 275 258 94% OSA 85 80 94% Remarks / Notes: Air Distribution Test Zone / Terminal Final Room # 229 212 211 228 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 31 Project: WELBE HEALTH, LA QUINTA System(s): ERV 1-1 THRU ERV 1-3 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes ERV 1-1 1 DUCT 10 " Ø 0.55 390 382 98% 2 DUCT 14 " Ø 1.07 770 760 99% 1160 1142 98% ERV 1-2 1 DUCT 10 " Ø 0.55 415 420 101% 2 DUCT 8" Ø 0.35 170 176 104% 585 596 102% ERV 1-3 1 DUCT 10" Ø 0.55 380 381 100% 2 DUCT 6" Ø 0.2 140 142 101% 520 523 101% Remarks / Notes: Air Distribution Test SUPPLY Zone / Terminal Final Room # FC 1-6 FC 1-7 FC 1-4 FC 1-5 FC 1-1 FC 1-2 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 32 Project: WELBE HEALTH, LA QUINTA System(s): ERV 2-1 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes ERV 2-1 1 DUCT 8 " Ø 0.35 90 85 94% 2 DUCT 8 " Ø 0.35 145 155 107% 3 DUCT 8 " Ø 0.35 120 127 106% 4 DUCT 8 " Ø 0.35 50 47 94% 5 DUCT 8 " Ø 0.35 95 90 95% 6 DUCT 8 " Ø 0.35 95 88 93% 7 DUCT 8 " Ø 0.35 265 272 103% 8 DUCT 8 " Ø 0.35 70 66 94% 9 DUCT 8 " Ø 0.35 85 80 94% 1015 1010 100% Remarks / Notes: Air Distribution Test SUPPLY Zone / Terminal Final Room # FC 2-1 FC 2-2 FC 2-3 FC 2-4 FC 2-5 FC 2-6 FC 2-7 FC 2-8 FC 2-9 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 33 Project: WELBE HEALTH, LA QUINTA System(s): ERV 1-1 THRU ERV 1-3 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes ERV 1-1 1 CE 12X12 1.0 225 185 82%* 2 CE 12X12 1.0 225 198 88%* 3 CE 10X10 1.0 130 110 85%* 4 CE 10X10 1.0 120 104 87%* 5 CE 12X12 1.0 225 205 91%* 6 CE 12X12 1.0 225 190 84%* 1150 992 86%* ERV 1-2 1 CE 24X24 1.0 240 238 99% 2 LE 48X2 1.0 175 170 97% 415 408 98% ERV 1-3 1 CE 24X24 1.0 510 504 99% Remarks / Notes: *Unable to obtain design CFM. Unit is in high speed. Air Distribution Test EXHAUST Zone / Terminal Final Room # 128 128 125 126 122 122 173 173 141 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 34 Project: WELBE HEALTH, LA QUINTA System(s): ERV 2-1 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes ERV 2-1 1 CE 12X12 1.0 280 263 94% 2 CE 12X12 1.0 330 308 93% 3 CE 24X24 1.0 280 259 93% 890 830 93% Remarks / Notes: Air Distribution Test EXHAUST Terminal FinalZone / Room # 240 241 CORRIDOR L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 35 Project: WELBE HEALTH, LA QUINTA System(s): EF-1 THRU EF-4 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes EF 1 1 CE 10X10 1.0 140 142 101% 2 CE 10X10 1.0 110 112 102% 3 CE 10X10 1.0 140 140 100% 4 CE 12X12 1.0 200 211 106% 5 CE 10X10 1.0 100 102 102% 6 CE 10X10 1.0 100 100 100% 7 CE 24X24 1.0 120 113 94% 8 CE 24X24 1.0 60 64 107% 970 984 101% EF 2 1 CE 10X10 1.0 100 92 92%* EF 3 1 CE 10X10 1.0 100 92 92%* EF 4 1 CE 10X10 1.0 100 97 97%* Remarks / Notes: *Drive-drive ceiling fans. Air Distribution Test Zone / Terminal Final Room # 127 124 123 121 168 168 171 176 180 103 104 L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 36 Project: WELBE HEALTH, LA QUINTA System(s): EF-5 & EF-6 Effect Design Prelim. Remarks / I. D. # Type Size Area CFM CFM CFM % Design Notes EF 5 1 CE 10X10 1.0 100 91 91%* EF 6 1 CE 10X10 1.0 100 109 109%* Remarks / Notes: *Drive-drive ceiling fans. Air Distribution Test Zone / Terminal Final Room # 132 DENTAL EQUIP. L.A. Air Balance (909) 931-1114 Section: "AIR BALANCE", Page: 37 CALIBRATION INSTRUMENT MANUFACTURER MODEL SERIAL NO. DATE AIR BORNE PARTICLE COUNTER PARTICLE SYST. ABACUS301-A 5394 10/11/21 AIRDATA MULTIMETER SHORTRIDGE ADM-870C M07071 06/10/21 AIRDATA MULTIMETER SHORTRIDGE ADM-870 M98206 06/17/22 AIRDATA MULTIMETER SHORTRIDGE ADM-870 M97920 09/03/21 AIRDATA MULTIMETER SHORTRIDGE ADM-860 M00000 09/14/21 AIRDATA MULTIMETER SHORTRIDGE ADM-860 M01591 05/10/22 AIRDATA MULTIMETER SHORTRIDGE ADM-860C M07077 09/14/21 AIRDATA MULTIMETER SHORTRIDGE ADM-860C M07552 10/06/21 AIRDATA MULTIMETER SHORTRIDGE ADM-860C M03365 10/06/21 AIRDATA MULTIMETER SHORTRIDGE ADM-860C M06081 06/10/21 AIRDATA MULTIMETER SHORTRIDGE ADM-860C M20548 01/25/22 AIRDATA MULTIMETER SHORTRIDGE ADM-860C M04576 02/22/22 AIRDATA MULTIMETER SHORTRIDGE ADM-860C M05463 07/13/21 AIRDATA MULTIMETER SHORTRIDGE ADM-860C M21049 01/25/22 AIRDATA MULTIMETER SHORTRIDGE ADM-860C M03796 09/14/21 AIRDATA MULTIMETER SHORTRIDGE ADM-860C M07487 06/17/22 AIRDATA MULTIMETER SHORTRIDGE ADM-860C M07501 08/10/21 AIRDATA MULTIMETER SHORTRIDGE ADM-860C M03595 09/03/21 AMP/VOLT METER, CLAMP-ON AMPROBE RS-3 SUPER 1305353 10/11/21 AMP/VOLT METER, CLAMP-ON AMPROBE RS-3 SUPER 1308620 10/11/21 AMP/VOLT METER, CLAMP-ON AMPROBE RS-3 SUPER 820808 10/18/21 AMP/VOLT METER, CLAMP-ON FLUKE 322 96360587 10/18/21 AMP/VOLT METER, CLAMP-ON FLUKE 322 95450543 07/15/21 AMP/VOLT METER, CLAMP-ON FLUKE 323 34930168WS 11/10/21 AMP/VOLT METER, CLAMP-ON FLUKE 323 42060325WS 05/17/21 AMP/VOLT METER, CLAMP-ON FLUKE 323 45680061MW 01/24/22 AMP/VOLT METER, CLAMP-ON FLUKE 323 57690130MV 06/30/22 AMP/VOLT METER, CLAMP-ON FLUKE 322 34930161WS 04/19/22 AMP/VOLT METER, CLAMP-ON FLUKE 323 43101658WS 06/24/21 AMP/VOLT METER, TRUE RMS FLUKE 335 78710548 01/07/22 AMP/VOLT METER, TRUE RMS FLUKE 335 78307378 01/07/22 AMP/VOLT METER, TRUE RMS FLUKE 335 78710545 01/06/22 AMP/VOLT METER, TRUE RMS FLUKE 335 79408155 01/06/22 AMP/VOLT METER, TRUE RMS FLUKE 335 78710542 01/11/22 AMP/VOLT METER, TRUE RMS FLUKE 335 78709707 01/11/22 ANEMOMETER, DIGITAL VANE ALNOR RV A16287 10/18/21 ANEMOMETER, ROTATING VANE ALNOR RVA801 A05348 02/02/22 ANEMOMETER, ROTATING VANE ALNOR RVA801 A00459 10/18/21 ANEMOMETER, ROTATING VANE ALNOR RVA801 A00472 10/18/21 ANEMOMETER, ROTATING VANE ALNOR RVA801 A00450 11/02/21 ANEMOMETER, ROTATING VANE ALNOR RVA801 A04409 11/02/21 ANEMOMETER, ROTATING VANE ALNOR RVA801 A05343 11/02/21 ANEMOMETER, ROTATING VANE ALNOR RVA801 A05348 09/20/21 ANEMOMETER, ROTATING VANE ALNOR RVA+ 70546159 09/20/21 ANEMOMETER, ROTATING VANE ALNOR RVA801 A05346 02/01/22 ANEMOMETER, ROTATING VANE ALNOR RVA+ 70546160 01/11/22 DISTANCE MEASUREMENT ZIRCON DIM.PRO4.0 EALAAB 10/04/21 DISTANCE MEASUREMENT ZIRCON DIM.PRO4.0 GALAAB 10/04/21 DISTANCE MEASUREMENT ZIRCON DIM.PRO4.0 RHLAAB 10/12/21 DISTANCE MEASUREMENT ZIRCON DIM.PRO4.0 LVLAAB 10/12/21 DUCT LEAKAGE TEST ORIFICE UNITED MCGILL 45-500 CFM 2373-L N/A FLOW HOOD ALNOR LOFLO BALOMETER 208934 FLOW HOOD ALNOR BALOMETER 13835 11/08/21 FLOW HOOD SHORTRIDGE CFM-88-1 M91542 11/08/21 FLOWHOOD ALNOR 634-513-044 BR 2196 10/15/21 FLOWHOOD ALNOR BALOMETER 2196 10/15/21 FLOWHOOD ALNOR BALOMETER 6463 10/15/21 FLOWHOOD ALNOR BALOMETER 6078 10/15/21 FLOWHOOD SHORTRIDGE CFM-83 391 10/15/21 FLOWHOOD, ANALOG SHORTRIDGE SERIES 8400 LAABJM 09/08/21 FLOWHOOD, ANALOG SHORTRIDGE CFM-83 6212 10/07/21 HYGROMETER PACER IND. DH100 100-93-091921 11/08/21 MAGNAHELIC GAUGE DWYER 2000-00AV WB05189434 10/28/21 MAGNAHELIC GAUGE DWYER 2000-0CAV WC0523WW51 10/28/21 MAGNAHELIC GAUGE DWYER 2000-0C R40416MR26 10/19/21 MAGNAHELIC GAUGE DWYER 2010-C R900711CD123 10/19/21 MAGNAHELIC GAUGE DWYER 2002-C 41106NH46 10/19/21 MANOMETER, DIGITAL DWYER 475-0 MARK III 488452 09/22/21 MANOMETER, DIGITAL DWYER 475-0, MARK III IP48303-005 06/22/21 MANOMETER, DIGITAL DWYER 475-0, MARK III IP48303-004 01/21/22 MANOMETER, DIGITAL DWYER 475-0, MARK III RHLAAB 10/04/21 MANOMETER, DIGITAL DWYER 475-0, MARK III 504518 06/23/22 MANOMETER, DIGITAL DWYER 475-0, MARK III LVLAAB 10/04/21 MANOMETER, DIGITAL DWYER 475-0, MARK III IP52292-012 12/06/21 MANOMETER, U-TUBE DWYER 16" DNL N/A PRESS. GAUGE, COMPOUND DIGITAL DWYER 67100B 402974 11/05/21 TEST AND BALANCE INSTRUMENTATION The following checked instruments will be used to successfully test and balance this project. CALIBRATION INSTRUMENT MANUFACTURER MODEL SERIAL NO. DATE TEST AND BALANCE INSTRUMENTATION The following checked instruments will be used to successfully test and balance this project. PRESSURE GAUGE DWYER 63015 402971 10/11/21 PRESSURE GAUGE DWYER 62200 402973 10/11/21 PRESSURE GAUGE DWYER 62100 402972 10/11/21 PRESSURE GAUGE ITT BARTON 247A 102278 10/11/21 PRESSURE GAUGE WEKSLER 30/0/30 2OFFLAAB 10/04/21 PRESSURE GAUGE WEKSLER 0/60 3OFFLAAB 10/04/21 PRESSURE GAUGE WEKSLER 0/30 LAB1001 10/04/21 PRESSURE GAUGE WEKSLER 0/200 LAB1003 10/04/21 PRESSURE GAUGE MARSH 1" N/A 10/04/21 PSYCHROMETER, DIGITAL AMPROBE THWD-2 7070703 02/15/21 PSYCHROMETER, DIGITAL AMPROBE THWD-3 180602076 01/24/22 PSYCHROMETER, SLING BACHARACH 0012-9015 18060152 02/24/21 SMOKE GUN TEL TRU 17-023 DNL N/A SMOKE MACHINE JEMLTD ZR-20 MKII 16283 N/A SMOKE MACHINE JEMLTD ZR-20 MKII 16284 N/A SMOKE MACHINE JEMLTD ZR-33 HI-MASS 113210396 N/A SMOKE MACHINE JEMLTD ZR-33 HI-MASS 113210412 N/A SMOKE MACHINE JEMLTD ZR-33 HI-MASS 113210413 N/A SMOKE MACHINE JEMLTD ZR-33 HI-MASS 113210521 N/A SMOKE MACHINE JEMLTD ZR-33 HI-MASS 113210524 N/A SOUND CALIBRATOR KIT QUEST QC-10 QE6010209 KIT SOUND LEVEL METER GALAXYAUDIO CM-130 050408155 04/27/21 SOUND LEVEL METER GALAXYAUDIO CM-130 050408151 05/10/21 SOUND LEVEL METER GALAXYAUDIO CM-130 050408148 05/10/21 SOUND METER, OCTAVE BAND QUEST 2700 HU6010056 KIT SOUND METER, OCTAVE FILTER QUEST QB-50 JL6020001 KIT TACHOMETER, CONTACT JAQUET 253 751152 09/20/21 TACHOMETER, CONTACT JAQUET 252, TYPE B 384626 06/30/22 TACHOMETER, CONTACT JAQUET 252, TYPE B 736013 09/09/21 TACHOMETER, CONTACT JAQUET 252, TYPE B 734335 09/09/21 TACHOMETER, CONTACT JAQUET 252, TYPE B 736021 01/04/22 TACHOMETER, CONTACT JAQUET 252, TYPE B 736024 01/04/22 TACHOMETER, CONTACT JAQUET 252, TYPE B 736520 01/12/22 TACHOMETER, CONTACT JAQUET 252, TYPE B 736521 01/12/22 TACHOMETER, CONTACT JAQUET 252, TYPE B 368355 01/08/22 TACHOMETER, CONTACT ZERNICKOW 252, TYPE B 730782 10/20/21 TACHOMETER, CONTACT ZERNICKOW 252, TYPE B 732234 01/24/22 TACHOMETER, CONTACT ZERNICKOW 252, TYPE B 736627 02/10/22 TACHOMETER, CONTACT ZERNICKOW 252, TYPE B 736633 02/10/21 TACHOMETER, CONTACT JAQUET 252, TYPE B 756168 06/24/21 TACHOMETER, DIGITAL STICHT 902-A JASLAAB 10/05/21 TACHOMETER, DIGITAL PHOTO EXTECH/DAVIS 461893 L710890 10/05/21 THERMOMETER GUN, NON CONTACT RAYTEK MT EALAAB 11/04/21 THERMOMETER GUN, NON CONTACT RAYTEK MT GALAAB 11/04/21 THERMOMETER GUN, NON CONTACT RAYTEK MT RHLAAB 10/25/21 THERMOMETER GUN, NON CONTACT RAYTEK MT LVLAAB 10/25/21 THERMOMETER GUN, NON CONTACT RAYTEK ST3, H25-814 2682870101-0032 10/25/21 THERMOMETER, DIAL TYPE JOHNSTON 40/0/160 LAABT15 11/10/21 THERMOMETER, DIGITAL UEI / DAVIS DT200 1415 11/10/21 THERMOMETER, SUBMERSION VEI PDT300 402286 10/26/21 ULTRASONIC FLOWMETER FUJI FLCS1 LAABUF1 10/19/21 VIBRATION METER SPM, SWEDEN VIB-11 9545013 10/07/21 VOLTMETER, MILLIVOLTS DC/AC MICRONTA 22-171A EALAAB 11/08/21 WATER METER EVERGREEN S-DP-250 1800140 02/15/22 WATER METER SHORTRIDGE HDM250 W17079 03/23/22 WATER METER SHORTRIDGE HDM250 W08029 02/17/22 WATER METER SHORTRIDGE HDM250 W18001 03/24/22 WATER METER SHORTRIDGE HDM300 W03086 03/24/22 WATER METER, B & G ITT BARTON 0-75' N/A 10/05/21 WATER METER, B & G ITT BARTON 0-400" N/A 10/05/21 WATER METER, DIFFERENTIAL ALNOR HM 670 HYD MANOMETER 70711056 03/18/22 WATER METER, DIFFERENTIAL ALNOR HM 670 HYD MANOMETER 70711054 08/12/21 WATER METER, DIFFERENTIAL ALNOR HM 670 HYD MANOMETER 70904116 10/18/21 WATER METER, DIFFERENTIAL ALNOR HM 675 HYD MANOMETER 72102046 02/01/22 WATER METER, GRISWOLD C.A. NORGREN CO. 30/0/100 K41DA00 10/18/21 ABBREVIATIONS, DEFINITIONS, SYMBOLS & CONVERSIONS AABC: Associated Air Balance Council LPS: Liters per Second ACT: Actual LVG: Leaving Air AK: Free Area Factor LWT: Leaving Water Temperature AMB: Ambient MAX: Maximum AMP: Ampere MIN: Minimum ASHRAE: American Society of Heating, Air Conditioning MVD: Manual Volume Damper and Refrigeration Engineers N.A: Not applicable / No Access AVG: Average NC: Noise Criteria or Normally Closed BHP: Brake Horsepower NIC: Not in Contract BTU: British Thermal Unit NM: Not measured BTUH: British Thermal Unit per Hour NPSHA: Net Positive Suction Head Available C to C: Center to Center NS: Not specified C: Celsius NVL: No Valid Location CAV: Constant Air Volume O.B.: Octave Band, a range of frequency where the highest CD: Ceiling Diffisuer frequency of the band. The band is usually specified by CEG: Ceiling Exhaust Grill the center frequency. The preferred octave bands are CER: Ceiling Exhaust Register designated by the following center frequencies: 31.5, 63, CFM: Cubic Feet per Minute 125, 250, 500, 1000, 2000, 4000, 8000, 16000. CHW or CHWS: Chilled Water Supply O.D.: Outside Diameter CHWR: Chiller Water Return OAT: Outside Air Temperature CP: Specific Heat: water = 1.0 BTU / lb per ºF, air = 0.24 ºF: Degrees Fahrentheit BTU / lb per ºF OPT: Operational Performance Testing ( Building Commissioning) CR: Ceiling Register OSA or OA: Outside Air CRR: Ceiling Return Register P.E. Professional Engineer CV: Valve Constant Pa: Pascal, 1 Pascal = 6.894 x 10-3 psi CW or CWS: Condenser Water Supply PD: Pressure Drop CW: Chilled Water PF: Power Factor CWR: Condenser Water Return PH: Phase DB: Dry Bulb PSI: Pounds per Square Inch Db: Decibel RA: Return Air DD: Direct Drive RAT: Return Air Temperature DNL: Data Not Listed R.C: Room Criterion Curves DP:Differential Pressure or Pressure Drop, net change in REQ: Required Pressure RF: Return Air Fan DT:Differential Temperature, net change in temperature RH: Relative Humidity EAT: Entering Air Temperature RPM: Revolutions per Minute Economizer: Allows air handler to utilize cool outside air for cooling SA: Supply Air EF or E: Exhaust Fan S.A.R.: Supply Air Register EG: Exhaust Grill S.A.T.: Supply Air Temperature EMCS: Energy Management Control System SD: Smoke Detector or Smoke Damper ENT: Entering Air SEF: Smoke Exhaust Fan ER: Exhaust Register SF (Motor): Factor by which actual amps can exceed rated amperage ESP: External Static Pressure SF: Supply Fan EWT: Entering Water Temperature SMACNA: Sheet Metal and Air Conditioning Contractors National FG: Floor Grille Association FH: Flow Hood (measures CFM directly so FPM and SP: Set Point or Static Pressure AK Factors are not required) SPF: Stairwell Pressurization Fan FLA: Full Load Amperage STD: Standard FPB: Fan Powered Box SWG: Sidewall Grille FPM: Feet per Minute SWR: Sidewall Register FPS: Feet per Second SWR: Side Wall Return FPT: Functional Performance Testing (Building SWS: Side Wall Supply Commissioning)TDH: Total Dynamic Head or Total Dead Head (pressure FR: Floor Register differential when flow equals zero) GPM Gallons per Minute TP(Motor): Thermally Protected (opens motor circuitry if rated HD: Head Pressure measured in feet of water amps are exceeded) Hg: Mercury TP: Traverse Point, Test Point or Total Pressure HOA Hand/Off/Auto Switch TSP: Total Static Pressure HP: Horse Power or Heat Pump V: Volt or Voltage HW or HTHW Hot Water or High Temperature Hot Water VAV: Variable Air Volume HWR: Hot Water Return or Heating Water Return VD: Volume Damper HWS Hot Water Supply or Heating Water Supply VFD: Variable Frequency Drive (automatic motor speed Hz: Hertz VP: controller) I.D. Inside Diameter W: Velocity Pressure I/O: Input / Output WB: Watts KWH: Kilowatt Hour WG: Wet Bulb L.A.A.B: Los Angeles Air Balance Co., Inc.Water Gauge LAT: Leaving Air Temperature WTR: Water LD: Linear Diffuser Z: Zone