HomeMy WebLinkAboutBCOM2023-1030BUILDING PERMIT
DESIGN & DEVELOPMENT
DEPARTMENT
78-495 CALLE TAMPICO
LA QUINTA, CALIFORNIA 92253
Permit Type:
Building Commercial
Permit Number:
BCOM2023-1030
Property Address:
79295 HIGHWAY 111
APN:
600340027
Legal Description
Parcel 1 PM 202/40 PM 30420
Property Zoning:
CR, 1
Valuation:
$1,000,000.00
PHONE (760) 777-7125
WWW.LAQUINTACA.GOV
APPLIED DATE: 12/29/2023
ISSUED DATE: 06/12/2024
CALIFORNIA
Owner:
Applicant: Teresa Jones
8131 Metcalf Avenue, Suite 300, Overland Park, KS
66204
Contractor: Corey Gibson / 370609
825 N Parkcenter Drive 2nd Floor 2nd Floor, Santa
Ana, CA 92705
PRIOR TO THE ISSUANCE OF THIS PERMIT FOR CONSTRUCTION, ALTERATION, IMPROVEMENT, DEMOLITION, OR REPAIR THE OWNER, APPLICANT AND/OR
CONTRACTOR UNDER PENALTY OF PERJURY HAVE AFFIRMED WHEN APPLICABLE, THROUGH THE SUBMITTAL OF FORMS OR BY OTHER ELECTRONIC MEANS, THE
FOLLOWING:
LICENSED CONTRACTOR OR OWNER -BUILDER DECLARATION (1 or 2)
1) They are licensed under provisions of Chapter 9 (commencing with
Section 7000) of Division 3 of the Business and Professions Code, and the
referenced
License is in full force and effect, or;
2) That they are exempt from the Contractors' State License Law for the
reason(s) indicated by either (2)(a) and/or (2)(b), or (2)(c) where he or
she is exempt from licensure by a valid exemption. [Section 7031.5,
Business and Professions Code: Any city or county that requires a permit
to construct, alter, improve, demolish, or repair any structure, prior to its
issuance, also requires the applicant for the permit to file a signed
statement that he or she is licensed pursuant to the provisions of the
Contractors' State License Law (Chapter (commencing with Section 7000)
of Division 3 of the Business and Professions
Code] Any violation of Section 7031.5 by any applicant for a permit
subjects the
applicant to a civil penalty of not more than five hundred dollars ($500).)
a) As owner of the property, or my employees with wages as their sole
compensation, will do all of or portions of the work, and the structure is
not intended or offered for sale (Section 7044, Business and Professions
Code: The Contractors' State License Law does not apply to an owner of
property who, through employees' or personal effort, builds or improves
the property, provided that the improvements are not intended or offered
for sale. If, however, the building or improvement is sold within one year of
completion, the Owner -Builder will have the burden of proving that it was
not built or improved for the purpose of sale.).
b) As owner of the property, will be exclusively contracting with licensed
c) Are exempt from licensure under the Contractors' State License Law.
As an Owner -Builder, they acknowledge that, except for their personal
residence in which they must have resided in for at least one year prior to
completion of the improvements covered by this permit, they cannot legally
sell a structure built as an owner -builder if it has not been constructed in
its entirety by licensed contractors. It is understood that a copy of the
applicable law, Section 7044 of the Business and Professions Code, is
available upon request when this application was submitted at the
following Web site:
http://www.leginfo.ca.gov/calaw.htm1.
DECLARATION REGARDING CONSTRUCTION LENDING AGENCY (If
applicable)
A construction lender will be used for completion of the improvements
covered by this permit and the name and information of which is on file for
public inspection during the regular business hours of the public entity.
Failure of the applicant to indicate the construction lender on the
application does not relieve that person of the requirement to give the
WORKERS' COMPENSATION DECLARATION (1, 2 or 3)
WARNING: FAILURE TO SECURE WORKERS' COMPENSATION COVERAGE IS
UNLAWFUL, AND SHALL SUBJECT AN EMPLOYER TO CRIMINAL PENALTIES AND
CIVIL FINES UP TO ONE HUNDRED THOUSAND DOLLARS ($100,000), IN ADDITION
TO THE COST OF COMPENSATION, DAMAGES AS PROVIDED FOR IN SECTION
3706 OF THE LABOR CODE, INTEREST, AND ATTORNEY'S FEES.
1) Has and will maintain a certificate of consent to self -insure for workers'
compensation, issued by the Director of Industrial Relations as provided for
by Section 3700 of the Labor Code, for the performance of the work for
which this permit is issued.
2) Has and will maintain workers' compensation insurance, as required by
Section 3700 of the Labor Code, for the performance of the work for which
this permit is issued.
3) Certifies that, in the performance of the work for which this permit is
issued, shall not employ any person in any manner so as to become subject
to the workers' compensation laws of California, and agree that, if should
become subject to the workers' compensation provisions of Section 3700 of
the Labor Code, shall forthwith comply with those provisions.
NOTICE TO APPLICANT (1, 2 and 3)
1) Each person upon whose behalf this application was made, each person
at whose request and for whose benefit work is being performed under or
pursuant to any permit issued as a result of this application, the owner, and
the applicant, each agrees to, and shall defend, indemnify and hold harmless
the City of La Quinta, its officers, agents, and employees for any act or
omission related to the work being performed under or following issuance of
this permit.
2) Any permit issued as a result of this application becomes null and void if
work is not commenced within 360 days from date of issuance of such
permit, or if cessation of work for 180 days will subject permit to
cancellation. On or after January 1, 2019, every permit issued shall become
invalid unless the work on the site authorized by such permit is commenced
within 12 months after its issuance, or if the work authorized on the site by
such permit is suspended or abandoned for a period of 12 months after the
time the work is commenced.
3) Certified that they read the application and state that the information
provided is correct. Agree to comply with all city and county ordinances and
state laws relating to building construction, and hereby authorize
representatives of this city to enter upon the above -mentioned property for
inspection purposes.
IMPORTANT: An Application for Permit was made to the Building Official,
subject to the conditions and restrictions set forth at the time of application,
which is now hereby an Issued Permit. If any part of the information being
supplied on this permit is inaccurate or untrue, please contact the City of La
Quinta at (760) 777-7125 immediately for correction.
Printed: 3/19/26 4:23 pm Page 1 of 6
BUILDING PERMIT
Permit Type: Building Commercial
Permit Number: BCOM2023-1030
Property Address: 79295 HIGHWAY 111
nary notice from
Printed: 3/19/26 4:23 pm Page 2 of 6
Permit Type
Building Commercial
BUILDING PERMIT
Permit Number:
Property Address
BCOM2023-1030
79295 HIGHWAY 111
WALMART / INTERIOR & EXTERIOR REMODEL - ADD MILLWORK AND COUNTERS IN PHARMACY, RESTRIPE AND RESURFACE
PARKING STALLS, REMODEL RESTROOMS AND BREAKROOM, REMODEL CUSTOMERS SERVICE AREA, EXPAND STORAGE AREA,
REPLACE CASES AND RELOCATE EQUIPMENT IN SERVICE DELI, ADD RCU'S ON ROOF, RELOCATE PICKUP STORAGE TO SALES
FLOOR - ADD COOLER/FREEZER, SHELVES AND EXTERIOR SLIDER DOOR, INSTALL NEW EQUIPMENT IN AUTO CENTER, REMODEI
VISION CENTER AND UPDATE CHECKOUT LAYOUT [VB/MIXED OCC/3,473-OL/SPRINKLERED]. NO TUMF OR DIF ASSSESSMENT
APPLICABLE. THIS PERMIT DOES NOT INCLUDE EXTERIOR SIGNAGE. 2022 CALIFORNIA BUILDING CODES.
7)nstruction Deta
Commercial Work Type Remodel Building/Unit A-2: Restaurants, Night Gross Square Footage 221694
Occupancy Clubs, B: Office,
Classification(s) Professional, M: Stores,
Markets, Gas Station, S-1:
Storage, Mod Hazard
Conditioned Square 221694 Covered Square 221694 Fire Sprinkler Square 221694
Footage
Footage
Number of Floors
1
Occupant Load
3473
Code Edition
2022
Original Valuation
1000000.00
Addition Area Square
0
Number of Carport(s)
0
Footage
Reroof Area Square
0
Stucco Application
0
Footage
Square Footage
Number of
0
Number of
0
Door/Window
Fireplace(s)
New/Alteration
New Electrical Square
30000
Number of Residential
0
Footage
Appliances
Temporary Power
No
Number of Forced Air
0
Service?
Furnace(s)
Number of
3
Number of Air
0
Condenser(s)
Handling Unit(s)
Number of Ventilation
0
Number of Exhaust
0
Fan(s)
Hood(s)
Number of Plumbing
12
Number of Roof Drains 0
Fixtures/Traps
Water System Install
Yes
Back Flow Prevention
No
or Alteration?
Device?
Sewer Connection?
No
Grease Interceptor or
No
Sand/Oil Separator?
Number of Dispensing
0
City Development
No
Units - Gas (TUMF)
Impact Fee Applicable
CVMSHCP - Project
0
Art in Public Places
No
Acreage (In Acres)
Fund Exempt
General Plan
CG
City Limits
Within La Quinta Limits
Lot Number
1
Lot Size
110488
Legal Description Parcel 1 PM 202/40 PM
30420
Footage
Construction Type V-B
Remodel Area Square 30000
Footage
Number of Balcony 0
Addition(s)
Number of 0
Door/Window
Retrofit/Repair
Number of Partition(s) 0
Electrical Service? No
Number of Wall/Floor 0
Heater(s)
Number of Evaporative 0
Cooler(s)
Miscellaneous
8
Mechanical
Number of Water
0
Heater(s)
Number of Gas
0
Outlet(s)
Transportation Uniform No
Mitigation Fee
Applicable
Number of Hotel
57
Rooms (DIF/TUMF)
Zoning
CR
Subdivision Name PM 30420
Centerlines 86877, 82913, 83863,
86301, 123856, 86087,
82915, 83862, 86300,
82914, 85297, 86878,
82916, 86302, 123848
Printed: 3/19/26 4:23 pm Page 3 of 6
BUILDING PERMIT
Permit Type: Building Commercial
Permit Number: BCOM2023-1030
Property Address: 79295 HIGHWAY 111
Type Group
Sq Ft
Value
Invoice No. Fee
Fee Amount
Amount Paid
INV-00007252 Remodel>100
$1,647.60
$1,647.60
Condenser/Compressor
$137.31
$137.31
Other Mechanical Equipment
$366.16
$366.16
Non -Residential Electrical PC
$276.98
$276.98
Condenser/Compressor PC
$91.53
$91.53
Water System Inst/Alt/Rep PC
$15.26
$15.26
Remodel PC (< 100)
$170.25
$170.25
Art in Public Places - Commercial Remodel
$5,000.00
$5,000.00
Fixture/Trap PC
$183.12
$183.12
Fixture/Trap
$183.12
$183.12
SMI - Commercial
$280.00
$280.00
Digital Archiving and Records Management Fee
$23.00
$23.00
Zoning Clearance - Alt/Add - Non -Residential
$183.00
$183.00
Remodel PC>100
$1,318.20
$1,318.20
Non -Residential Electrical
$778.08
$778.08
Other Mechanical Equipment PC
$366.16
$366.16
Water System Inst/Alt/Rep
$15.26
$15.26
Remodel < 100
$62.24
$62.24
Building Standards Administration
$40.00
$40.00
Technology Enhancement Fee
$8.00
$8.00
Total for Invoice INV-00007252
$11,145.27
$11,145.27
INV-00011109 Fire - Failed or Additional Field Inspections
$183.00
$183.00
Total for Invoice lNV-00011109
$183.00
$183.00
INV-00011737 Building Staff Time
$366.00
$366.00
Total for Invoice lNV-00011737
$366.00
$366.00
Grand Total for Permit
$11,694.27
$11,694.27
Workflow Step / Action Name
Action Type
Start Date
End Date
Application Completeness Check v.1
01/02/2024 9:06
Submittal Document Verification v.1
Generic Action
01/02/2024 9:06
Plan Check v.1
01/02/2024 0:00
-----------------------------------------------------------------------------------------------------------------------------------------
Building Major Review v.1
Receive Submittal
01/02/2024 0:00
01/26/2024 8:22
-----------------------------------------------------------------------------------------------------------------------------------------
Building Major Review v.2
Receive Submittal
03/12/2024 0:00
04/10/2024 9:54
-----------------------------------------------------------------------------------------------------------------------------------------
Building Major Review v.3
Receive Submittal
04/23/2024 0:00
05/15/2024 14:09
Permit Issuance v.1
05/16/2024 12:26
-----------------------------------------------------------------------------------------------------------------------------------------
Contractor / Owner -Builder Information v.1
Generic Action
05/16/2024 12:26
-----------------------------------------------------------------------------------------------------------------------------------------
Verify & Invoice Fees v.1
Generic Action
06/12/2024 13:47
-----------------------------------------------------------------------------------------------------------------------------------------
Ready to Issue v.1
Generic Action
06/12/2024 13:47
-----------------------------------------------------------------------------------------------------------------------------------------
Verify Fee Payment & Issue Permit v.1
Generic Action
06/12/2024 13:50
-----------------------------------------------------------------------------------------------------------------------------------------
Print, Attach, and Email Building Permit v.1
Create Report
06/12/2024 13:50
06/12/2024 13:50
Printed: 3/19/26 4:23 pm Page 4 of 6
BUILDING PERMIT
Permit Type: Building Commercial
Permit Number: BCOM2023-1030
Property Address: 79295 HIGHWAY 111
Inspections - Do Not Pour Concrete Until Approved v.1
07/18/2024 0:00
----------------------------------------------------------- -
Drypack v.1
---------------------------------------------------------
Inspection
08/12/2024 14:28
-------------
08/12/2024 14:29
-----------------------------------------------------------------------------------------------------------------------------------------
Footing v.1
Inspection
08/01/2024 14:30
08/01/2024 14:48
-----------------------------------------------------------------------------------------------------------------------------------------
Footing v.1
Inspection
07/18/2024 0:00
07/22/2024 11:06
-----------------------------------------------------------------------------------------------------------------------------------------
Footing v.2
Inspection
08/06/2024 0:00
08/07/2024 11:21
-----------------------------------------------------------------------------------------------------------------------------------------
Footing v.3
Inspection
08/08/2024 0:00
08/08/2024 12:29
-----------------------------------------------------------------------------------------------------------------------------------------
Footing v.4
Inspection
08/12/2024 0:00
08/13/2024 13:30
-----------------------------------------------------------------------------------------------------------------------------------------
Footing v.5
Inspection
12/20/2024 0:00
12/23/2024 13:22
-----------------------------------------------------------------------------------------------------------------------------------------
Footing v.6
Inspection
12/23/2024 0:00
-----------------------------------------------------------------------------------------------------------------------------------------
Setbacks v.1
Inspection
-----------------------------------------------------------------------------------------------------------------------------------------
Slab v.1
Inspection
07/23/2024 0:00
07/24/2024 10:25
-----------------------------------------------------------------------------------------------------------------------------------------
Slab v.2
Inspection
07/31/2024 0:00
08/01/2024 14:28
-----------------------------------------------------------------------------------------------------------------------------------------
Slab v.3
Inspection
08/12/2024 14:28
08/12/2024 14:30
-----------------------------------------------------------------------------------------------------------------------------------------
Slab v.4
Inspection
08/12/2024 0:00
-----------------------------------------------------------------------------
Underground Electrical v.1
- - - - - - -
Inspection
- - - - - - - - - ----- -
08/08/2024 12:27
- - - - - - - - - -
08/08/2024 12:28
-----------------------------------------------------------------------------
Underground Electrical v.2
- -
Inspection
----------
08/08/2024 0:00
- - - - - - -
- - - - - - - - - - --------------------------------------------------------
Underground Plumbing v.1
- - - - - - -
Inspection
- - - - - - - - - ----- -
07/22/2024 0:00
- - - - - - - - - -
07/23/2024 17:04
- - - - - - - - - - --------------------------------------------------------
Underground Plumbing v.2
- -
Inspection
- - - - - - ----- -
07/23/2024 17:04
- - - - - - - - - -
07/24/2024 10:54
- - - - - - - - - - --------------------------------------------------------
Underground Plumbing v.3
- -
Inspection
-- -
08/16/2024 0:00
- - - - - - - - - -
08/20/2024 16:12
----------------- - --------------------------------------------------------
Water Line v.1
- -
Inspection
--------------------------
- - - - - - -
Inspections - Cover No Work Until Approved v.1
07/23/2024 0:00
--------------------------------------------------- - - - - -
Roof Nail v.1
- - - - - - - - - - - - - ----------------------------------
Inspection
- - - - - - -
----- - - ------------------------------------ - - - - - - -
Okay to Wrap v.1
- - - - - - - - - -
Inspection
----------------------------------------------- - - - - - - -
Framing v.1
- - - - - - - - - - - - - - -
Inspection
- - - - - - - - --------
12/23/2024 0:00
- - - - - - - - - -
12/26/2024 15:12
-----------------------------------------------------------------------------
Framing v.2
- - - - - - -
Inspection
- - - - - - - - - ----- -
12/26/2024 0:00
- - - - - - - - - -
-----------------------------------------------------------------------------
Rough Electrical v.1
- - - - - - -
Inspection
- - - - - - - - --------
08/28/2024 0:00
- - - - - - - - - -
08/29/2024 14:47
-----------------------------------------------------------------------------------------------------------------------------------------
Rough Electrical v.2
Inspection
08/29/2024 0:00
-----------------------------------------------------------------------------------------------------------------------------------------
Rough Mechanical v.1
Inspection
08/28/2024 0:00
08/29/2024 14:39
-----------------------------------------------------------------------------------------------------------------------------------------
Rough Mechanical v.2
Inspection
08/29/2024 0:00
-----------------------------------------------------------------------------------------------------------------------------------------
Rough Plumbing v.1
Inspection
-----------------------------------------------------------------------------------------------------------------------------------------
Rough Fire Clearance Bldg v.1
Inspection
09/03/2024 15:33
09/05/2024 15:23
-----------------------------------------------------------------------------------------------------------------------------------------
Rough Fire Clearance Bldg v.2
Inspection
09/27/2024 9:40
09/27/2024 9:43
-----------------------------------------------------------------------------------------------------------------------------------------
Rough Fire Clearance Bldg v.3
Inspection
11/04/2024 11:19
11/07/2024 13:49
-----------------------------------------------------------------------------------------------------------------------------------------
Shower Pan v.1
Inspection
-----------------------------------------------------------------------------------------------------------------------------------------
Insulation v.1
Inspection
07/23/2024 0:00
07/24/2024 10:24
-----------------------------------------------------------------------------------------------------------------------------------------
Drywall Nail v.1
Inspection
-----------------------------------------------------------------------------------------------------------------------------------------
T-Bar/Overhead v.1
Inspection
-----------------------------------------------------------------------------------------------------------------------------------------
Exterior Lath v.1
Inspection
------------------------------------------------------------------------------
Gas Test v.1
- - - - - -
Inspection
---------------------------------------------
------------------------------------------------------------------------------
Sewer Connection v.1
- - - - -------------------------------------------------
Inspection
Inspections - Final v.1
10/15/2024 13:49 03/17/2025 9:23
- - ---------------- - - - - - - - - - - -
Final Fire v.1
- - - - - - - - - - - - - - - - - - - - - - - -
Inspection
- - - - - - - - - ----- -
10/15/2024 13:49
- - - - - - - - - -
10/24/2024 18:10
- - ---------------- - - - - - - - - - - -
Final Fire v.2
- - - - - - - - - - - - - - - - - - -
Inspection
-- -
11/04/2024 11:22
- - - - - - - - - -
11/07/2024 17:59
- - - ------------ - - - - - - - - - - - -
Final Fire v.3
- - - - - - - - - - - - - - - - - - -
Inspection
- -
11/20/2024 15:29
- - - - - - - - - -
11/21/2024 17:51
Printed: 3/19/26 4:23 pm Page 5 of 6
BUILDING PERMIT
Permit Type: Building Commercial
Permit Number: BCOM2023-1030
Property Address: 79295 HIGHWAY 111
Final Fire v.4
Inspection
12/05/2024 15:25
12/05/2024 15:29
Final Building v.1
Inspection
12/05/2024 0:00
12/06/2024 16:41
-----------------------------------------------------------------------------------------------------------------------------------------
Final Building v.2
Inspection
12/06/2024 16:42
12/10/2024 9:22
-----------------------------------------------------------------------------------------------------------------------------------------
Final Building v.3
Inspection
01/08/2025 16:12
01/09/2025 17:26
-----------------------------------------------------------------------------------------------------------------------------------------
Final Building v.4
Inspection
03/07/2025 0:00
03/11/2025 8:48
-----------------------------------------------------------------------------------------------------------------------------------------
Final Building v.5
Inspection
03/17/2025 9:23
03/17/2025 9:23
Certificate of Occupancy v.1
------ ----------------------------------------------------------------------------------------------------------------------------------
Issue Certificate of Occupancy
Create Report
Construction or work for which a permit is required shall be subject to inspection by the building official and such construction or work
shall remain visible and able to be accessed for inspection purposes until approved. Approval as a result of an inspection shall not be
construed to be an approval of a violation of the provisions of the applicable code and other ordinances of the jurisdiction. Inspections
presuming to give authority to violate or cancel the provisions of the applicable code and other ordinances of the jurisdiction shall not be
valid. It shall be the duty of the owner or the owner's authorized agent to cause the work to remain visible and able to be accessed for
inspection purposes. Neither the building official nor the jurisdiction shall be liable for expense entailed in the removal or replacement of
any material required to allow inspection.
It shall be the duty of the holder of the building permit or their duly authorized agent to notify the building official when work is ready for
inspection. It shall be the duty of the permit holder to provide access to and means for inspections of such work that are required by this
code.
A building or structure shall not be used or occupied in whole or in part, and a change of occupancy of a building or structure or portion
thereof shall not be made, until the building official has issued a certificate of occupancy therefor as provided herein. Issuance of a
certificate of occupancy shall not be construed as an approval of a violation of the provisions of the applicable code and other ordinances
of the jurisdiction. Certificates presuming to give authority to violate or cancel the provisions of this code or other ordinances of the
iurisdiction shall not be valid.
A person shall not make connections from a utility, a source of energy, fuel, or power, or a water system or sewer system to any building
or system that is regulated by the applicable code and other ordinances of the jurisdiction for which a permit is required, until approved by
the building official.
Printed: 3/19/26 4:23 pm Page 6 of 6
�+ 0"i
W ra
PERMIT #
<:F \1 ,,, :::, 1)1-*.FRI -
PLAN LOCATION:
Project Address: Walmart Store # 18 04
Project Description: Pool, Remodel, Add't, Elect, Plumb, Mech
79295 US Hwy 111
Clean, prep, paint interior and exterior
APN#: 600340027
walls add millwork and counters in
Pharmacy, restripe and resurface parking
stalls, remodel Restrooms and Breakroom,
remodei CustomerService-expand storage
Applicant Name: Teresa Jones
area, replace cases and relocate e ui me
Address:8131 Metcalf Avenue, Suite 300
in Service Deli, add RCU's on roof
relocate Pickup storage to Sales Floor -
City, ST, Zip: Overland Park, KS 66204
add cooler/freezer, shelves, and exterio
slider door, install new equipment in Au
Center, remodei Vision Center and update
Telephone: 913 . 2 3 6 . 3 3 71
checkout layout.
Email: teresa.jones@brrarch.com
Valuation of Project$ 1, 000, 000
Contractor Name:
New SFD Construction:
Address:
Conditioned Space SF
City, St, Zip
Garage SF
Telephone:
Patio/Porch SF
Email:
Fire Sprinklers SF
State Lic: City Bus Lic:
Arch/Eng Name: Mariah B . Meyer, AIA
BRR Architecture Inc.
Construction Type: Occupancy:
Address: 8131 Metcalf Avenue, Suite 300
Grading:
City,St,Zip Overland Park, KS 66204
Telephone: 913 . 236 . 3371
Bedrooms: 0
Stories: 1
# Units: N/A
Email: teresa.jones@brrarch.com
State Lic: C- 3 7 4 4 0 City Bus Lic:
Property Owner's Name: Walmart Real Estate Business Trust
New Commercial / Tenant Improvements:
Address: 2608 SE J Street
Total Building 30, 000 SF
City,ST,Zip Bentonville, AR 72716
Construction Type: V-B Occupancy: M,S1,A2,B
Telephone: 4 7 9. 3 71 . 0 4 2 9
Email:kristen.dinger@walmart.com
78495 CALLE TAMPICO
LA QUINTA, CA 92253
760-777-7000
OFFICE USE ONLY
#
Submittal
Req'd
Ree'd
Plan Sets
Structural Calcs
Truss Calcs
Title 24 Calcs
Soils Report
Grading Plan (PM10)
Landscape Plan
Subcontractor List
Grant Deed
HOA Approval
School Fees
Burrtec Debris Plan
Planning approval
Public Works approval
Fire approval
City Business License
CAL FIRE - RIVERSIDE UNIT
RIVERSIDE COUNTY FIRE DEPARTMENT Qa�&a
BILL WEISER . THIEF
OFFICE OF THE FIRE MARSHAL — LA QUINTA—CALIFORNIA-
78495 Calle Tampico, La Quinta, CA 92253 • Phone (760) 777-7074
• www.rvcfire.org
January 25, 2024
Teresa Jones, BRR Architecture, Inc.
Re: Walmart Remodel
BCOM2023-1030 / 79295 HIGHWAY 111
The building plans you submitted for the above referenced project have been reviewed by Riverside County
Fire Department - Office of the Fire Marshal personnel and are approved with the following conditions.
DEFERRED SUBMITTALS REQUIRED
1) FIRE SPRINKLER SYSTEM - The fire protection plan sheets included in the plan submittal for this
permit were not formally reviewed and approved because these sheets are designated "Not for
Construction" and the sheets don't contain the seal and signature from a California Licensed Fire
Protection Engineer, California Mechanical Engineer, or C-16 California Licensed Contractor for Fire
Protection. Working plans for construction shall be submitted to the La Quinta Office of the Fire
Marshal under a separate fire sprinkler permit number.
2) FIRE ALARM/MONITORING SYSTEM - If the fire alarm system is modified, plans shall be
submitted to the Office of the Fire Marshal under a separate permit for review and approval prior to
installation.
3) HIGH -PILE & RACK STORAGE — If high piled combustible storage and rack systems will be
installed and modified, then plans shall be submitted to the Fire Department under a separate permit
showing the layout, type of racks and shelving as affected by this occupancy. High -Pile Plans shall
include a Technical Report from a licensed Fire Protection Engineer that identifies the planned
commodity storage arrangements.
PRIOR TO FINAL
1) Inspections shall be completed and approved for any of the required separate fire permits.
The Fire Department approved plans and conditions letter must be at the job site.
Applicant/installer shall be responsible to contact the Fire Department to schedule inspections. Requests for
inspections are to be made at least 48 hours in advance and may be arranged by calling (760)777-7131.
All questions regarding the meaning of these conditions should be referred to the Office of the Fire Marshal
staff at (760)777-7078.
Chris Cox - Fire Safety Supervisor
Building Permit Number. BCOM23-1030
Project Description: SFR
Exempt: ❑
(Materials may contain hazardous wastes and
are not subject to recycling provisions)
Construction Debris Management Plan
Plan Submittal
Job SiteAddressl 79295 US HWY 111. La Quinta, CA 92253
Owners Namel Rick Bruns (Wal-Mart Stores )
Number Street or PO Box 805 SE Moberly Lane
City State Postal Code Bentonville, AR 72712-5570
Owners Phone Number 479-212-8075
Owner's E-Marl Address Richard BrunsCck Irrart,00m
Project Manager's Name I Corey Gibson
Project Manager's Phone Number 562-266-8004
Project Manager's E-mail Addressl Core a i gocc
Builder / Contractorl AGI General Contracting
Number Street or PO BoxI 825 N. Parkcenter Drive. 2nd Floor
city State Postal ccclel Santa Ana, CA 92705
Project Square Footage I Site SOFT:221,694 / Remodel SQFT: 30,000
Approval By Burr -tee y `�
Date of City Approval
f Materials
To Be Discarded:
Product
Trash
Asphalt
Brick/Block
Cardboard
Commingled
Concrete
Drywall
Donated / Reuse`
'Describe Items
Tons
270.00 Not recyclable
247.50 Recyclable
165.00 Recyclable
0.00 Recyclable
0.00 Recyclable
247.50 Recyclable
52.50 Recyclable
0.00 Recyclable
Product
Masonry (broken)
Plaster
Scrap Metal
Tile (floor)
Tile (roof)
Wood
Landscape Debris
Tons
0.00 Recyclabie
264.00 Recyclable
0.00 Recyclable
13,80 Recyclable
225.00 Recyclable
30,00 Recyclable
30.00 Recyclable
Totals: Recycle Trash Projected Diversion:
1275.31 1 270 1 1 182.53%
I understand it is the property owner's responsibility to submit copies of weight tickets or receipts to the District
Environmental Coordinator as these hauls occur. I hereby certify that completion, implementation and adherence of the
Debris Management Plan (DMP) for the above named project shall guarantee that at least 65% of the jobsite waste is
diverted from landfilling. The remaining material will be recycled or reused. I will divert, for recycling or re -use, remaining
materials generated from the first day of the project through the completion of the project in accordance with this plan. This
DMP is issued in the name of the property owner(s) and shall remain their property throughout the construction and/or
demolition project. A contractor serving as agent of the owner may obtain a DMP for the owner. However, the DMP is still
issued in the name of the property owner(s) and the owner retains legal responsibility for ensuring that the provisions of the
DMP are adhered to. The pro erty owner(s) and general contractor shall be kept informed of the diversion progress through
bi-monthi41Kris. If self- ng, all refuse material from this project site must be taken to an approved recycer or transfer
X'7�4_ �
/Z - Zy
Deve er / Project Manage / Superintendant Date
POST -INSTALLED ANCHORS REPORT
Report Number: CB241072.0024
Service Date: 02/25/25
Report Date: 02/26/25
Task: General Inspections (ICC)
Client
Walmart Inc
Attn: Andrienne Antonucci
Construction Dept 8702 - Contract Administration
2001 Southeast loth St
Bentonville, AR 72716-0550
a rerracon
1355 E Cooley Dr
Colton, CA 92324-3954
909-824-7311
Project
WM SUP 1805-243 La Quinta, CA RM
79295 US Highway 111
La Quinta, CA 92253
Project Number: CB241072
General Information
Corey Gibson with AGI requested Terracon to be on site to perform load/pull testing of anchor(s) being installed by Axiom Construction. Results of
observation(s) performed today were reported to Robert Libert with AGI. The Terracon representative arrived at the site at 0830 and departed at
1100.
The construction documents referenced for this observation include: Engineer recommendations plans dated 2/25/2025. Permit No: BCOM2023-
1030.
Anchor System Information
The following anchors were tested:
Anchor Type Locations Quantity Anchor Specified
(tested/total) Size (in.) Load
All -Thread (1) Associate canopy south of 6/57 3/4" 2087
garden section
* See below for more information
Testing Equipment
Test Equipment Description
Enerpac RSM100 with gauge #6000
Additional Comments
Test Load Load Type
2087 LBS
Per Corey Gibson of AGI, structural engineer of record (SEOR) requested tests for 10 percent of total anchors.
Compliance
Based on our testing, the post -installed anchors we tested met the SEOR's strength requirements.
Services: Perform pull -testing of post -installed anchors.
Terracon Rep.: Arturo Rodriguez
Reported To: Robert Libert with AGI
Contractor: Axiom Construction
Report Distribution:
(1) AGI General Contractors, Carlos
(1) AGI General Contractors, Corey
Fuentes
Gibson
(1) AGI General Contractors, Frank
(1) AGI General Contractors, Mark
R nrioriniio�
(1) AGI General Contractors, Ramon
Rnnnoll
(1) AGI General Contractors, Steven
Silva
Van
Status*
Complies
Calibration Date
2024-03-18
Arturo Rodriguez
Terracon Field Representative
Start/Stop: 0645-0800,0800-1200, 1200-1315
Reviewed By:
Jason Choi
Assistant Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above
and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at
the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
DM018, 04-29-22, Rev. 5 Page 1 of 1
Photo Log
Report Number:
Service Date:
Report Date:
Task:
C13241072.0024
02/25/25
02/26/25
General Inspections (ICC)
(P1) Area tested
r rerracon
1355 E Cooley Dr
Colton, CA 92324-3954
909-824-7311
CT0001, 10-16-13, Rev.10 Page 1 of 2
Photo Log
Report Number: C13241072.0024
Service Date: 02/25/25
Report Date: 02/26/25
Task: General Inspections (ICC)
(P2) Pull testing
w ierracon
1355 E Cooley Dr
Colton, CA 92324-3954
909-824-7311
CT0001, 10-16-13, Rev.10 Page 2 of 2
POST -INSTALLED ANCHORS REPORT
Report Number: CB241072.0023
Service Date: 02/19/25
Report Date: 02/20/25
Task: General Inspections (ICC)
Client
Walmart Inc
Attn: Andrienne Antonucci
Construction Dept 8702 - Contract Administration
2001 Southeast loth St
Bentonville, AR 72716-0550
a rerracon
1355 E Cooley Dr
Colton, CA 92324-3954
909-824-7311
Project
WM SUP 1805-243 La Quinta, CA RM
79295 US Highway 111
La Quinta, CA 92253
Project Number: CB241072
General Information
Frank W/ AGI requested Terracon to be on site to perform load/pull testing of anchor(s) being installed by AGI. Results of observation(s)
performed today were reported to Frank W/ AGI. The Terracon representative arrived at the site at 2100 and departed at 0200.
The construction documents referenced for this observation include: Construction shop drawings dated 7/8/2024. Permit No: BCOM2023-1030.
Anchor System Information
The following anchors were tested:
Anchor Type Locations Quantity Anchor Specified Test Load Load Type Status*
(tested/total) Size (in.) Load
Expansion (1) Store Gondolas at grocery, 350/350 3/8" 30 30 FT -LB Complies
Anchors toys, pharmacy, home goods
* See below for more information
Testing Equipment
Test Equipment Description Calibration Date
Calibrated torque wrench
Additional Comments
2025-01-02
Performed torque testing on approximately 350 3/8"xY Hilti quick bolt 3 expansion anchors for store Gondolas. 36 legs per gondola , 2
anchors per leg. Locations - grocery, toys, pharmacy, home goods . Verified all anchors for minimum 30 lb torque requirements as per Hilti
manufacturers spec for 3/8" anchors with no failures to report. Reference details 3/FXS2 and 4/FXS1. All WORK IS NOW COMPLETE .
Compliance
Based on our observations and testing, the post -installed anchors referenced above appear to be in general accordance with the project
documents.
Services:
Terracon Rep.: Jeff Burgess, BI
Reported To: Frank W/ AGI
Contractor: AGI
Report Distribution:
(1) AGI General Contractors, Carlos
Fuentes
(1) AGI General Contractors, Frank
R nrio
(1) AGI General Contractors, Ramon
Silva
(1) AGI General Contractors, Corey
Gibson
(1) AGI General Contractors, Mark
Rnn 11
(1) AGI General Contractors, Steven
Van
Start/Stop:
Reviewed By:
Jeff Burgess, BI
Terracon Field Representative
Jason Choi
Assistant Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above
and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at
the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
DM018, 04-29-22, Rev. 5 Page 1 of 1
Photo Log
Report Number: C13241072.0023
Service Date: 02/19/25
Report Date: 02/20/25
Task: General Inspections (ICC)
(P1) Anchor torque testing
(P2) Torque testing
r rerracon
1355 E Cooley Dr
Colton, CA 92324-3954
909-824-7311
(P3) Torque testing
CTOOO1, 10-16-13, Rev.10 Page 1 of 1
Irerracon
SPECIAL INSPECTOR'S DAILY REPORT
TYPE OF
TESTING. REINFORCED CONCRETE
T08 ND. C13241072.0002
- CONCRETE DATE 7-23-24
J REINFORCING STEEL DAY OF WEEK
Tuesday
PROJECT NAME WM SUP 1805-243 La Quinta, CA RM
OSHPD/DSA NO.
JOB ADDRESS
79295 US Highway I 1 I La Quinta, CA 92253
CONTRACTOR AGI
m TIME ARRIVAL 11:30
P
TIME DEPARTURE 3:30 am
ARCHITECT ENGINEER
HOURS CHARGED 4
CONCRETE SUPPLIER
CONCRETE MIX NO
MATERIAL DESCRIPTION
METHOD OF PLACING
WEATHER
AIR TEMPERATURE
PART OF STRUCTURE PLACED
YARDAGE PLACED THIS SHIFT
SUBCONTRACTOR
REINFORCEMENT CHECKED BY
TESTS PERFORMED
SET NO.
N0, OF SAMPLES
TIME
SLUMP
AIR t%)
REMARKS
Description of work inspected: (Detail locations, work progress, etc.)
Arrived on site 9-8-23 for visual rebar inspection.
Observed the install of 44 rebar mat for insulated concrete slab. The mat has been installed at 10" on center each way with 1-1 /2"
clearance at bottom. The work being performed is compliant with the provided drawings and has been checked for dimensions, size
and clearances. Work Complete.
Approved documents were used for inspections. To the best of my knowledge, the above work is in conformance with the approved
documents and specifications.
Remarks: (Work rejected, job problems, etc.)
CERTIFICATE OF COMPLIANCE
I hereby certify that I have inspected to the best of my knowledge all of
the above reported work unless otherwise noted. I have found this work to
comply with the approved plans, specifications, and applicable sections of
the governing building laws unless otherwise noted.
Nathan Lorenz
PRINTED NAME
7-23-24
DATE OF REPORT
SIGNATURE
CWT#12110841 [CC# 8016255
CERTILIC NUMBER
DESIGN & DEVELOPMENT DEPARTMENT
78-495 CALLE TAMPICO
LA QUINTA, CALIFORNIA 92253
(760) 777-7125 FAX (760) 777-7011
NON-RESIDENTIAL PLAN CHECK CORRECTION LIST (CCR)
DATE: 1/18/2024
STATUS: FIRST REVIEW
PLAN CHECKED BY: JAKE FUSON / INTERWEST
TELEPHONE NUMBER: (760) 777-7081
ADDRESS: 79295 HIGHWAY 111
DESCRIPTION: WALMART REMODEL
APPLICANT: TERESA JONES
PLAN CHECK #: BCOM2023-1030
This submittal has been checked for compliance with the 2019 California Building, Electrical, Mechanical, Green Building
and Energy Codes, and the City of La Quinta Municipal Code.
APPLICANT:
The following items are being returned to you for
correction:
THIS CORRECTION LIST
BUILDING DEPARTMENT STAFF:
DO NOT accept any resubmittal unless ALL of the
following items are included:
WRITTEN RESPONSES TO THIS CORRECTION LIST
REVISED PLAN SET
REVISED STRUCTURAL CALCULATIONS
INSTRUCTIONS TO APPLICANT:
1) Provide a written response to each comment on the following pages, noting specifically where the correction can be
found. Responses such as, "Sheet A-3," or, "Handrails shall be per CBC Section 1003," are not acceptable. Show or note
specifically how compliance with a code requirement is achieved. Responses such as, "Added note 16 on sheet A-3"
are appropriate and will help expedite your back check.
2) Corrections may not be made by handwriting on existing drawings. Revise originals and reprint Plans and/or
Calculations as necessary.
3) Return all red -marked Plans and/or Calculations with your resubmittal.
4) Each sheet of resubmitted Plans and/or Calculations shall include the preparer's name and telephone number and shall
be wet -signed by the preparer. If the preparer is a licensed architect or engineer, all documents prepared by that
licensed individual shall also bear his/her stamp as prescribed by California Business and Professions Code Section
5536. Resubmittals will not be accepted with signatures missing.
5) Return this list, your written responses, and all documents listed above with your resubmittal.
Non -Residential Plan Check Correction List Page 1 of 2
SECTION A — GENERAL
1) The City of La Quinta has elected to use Interwest Consulting Group for plan review of your project. In addition to the
comments provided by the City of La Quinta within this correction list please see the attached outside consultant
review comments. For resubmittal please include a separate response sheet for each set of review comments
2) Note on Plans: "All construction shall comply with the La Quinta Municipal Code."
3) Provide Planning Division approval for this Project. Please contact Jack Lima in the Planning Division directly at (760)
777-7195 with questions regarding the following comment(s):
a) A MODIFICATION BY APPLICANT AND SIGN PERMIT SUBMITTALS ARE REQUIRED.
4) Provide Riverside County Office of the Fire Marshal approval of this project. Please note: the Fire review is currently in
progress —please monitor the review's progress through the online permitting portal to determine the result.
5) Provide the Assessor's Parcel Number (APN) and complete legal description of project on the first sheet of plans.
6) Please add the La Quinta Municipal Code to the list of governing codes on the cover sheet of the plans.
SECTION B — SITE PLAN / ARCHITECTURAL / ACCESSIBILITY
1) The trash container appears to intrude into the required turning radius on detail 3/A5.1.
2) See separate correction list, attached.
SECTION C —STRUCTURAL
1) See separate structural correction list, attached.
Important note to Engineer of Record:
If these corrections require revisions to structural calculations, in response to these corrections, do NOT simply submit
two copies of a few supplemental calculations. For resubmittal, incorporate any new or supplemental calculations into
the complete set of structural calculations and resubmit as one complete file. Your written responses should direct
the plan reviewer to the appropriate revised page(s).
END CITY REVIEW CORRECTION LIST
CORRECTION LIST CONTINUED BY INTERWEST CONSULTING GROUP ATTACHED
As further information is provided and reviewed, additional corrections may be required.
Non -Residential Plan Check Correction List Page 2 of 2
January 6, 2024
CITY OF LA QUINTA - FIRST REVIEW
Permit No: BCOM2023-1030
Interwest No.: LAQ24-0002
Non -Structural: 7.5-hours
Structural: 2-hours
City of La Quinta
Building Department
78-495 Calle Tampico
La Quinta, CA 92253
Plan Review: Walmart Remodel
Address: 79295 Hwy. 111
0
rtv
INTERWEST
A SAFEbuilt' COMPANY
Interwest Consulting Group has completed a first code compliance review of the following documents on behalf of
the City of La Quinta:
1. Drawings: Two copies of following:
a. C1 through SA1 dated 11/2/23 by brr.
b. SP1 through OPA1.2 datedll/2/23 by brr.
C. S1 through S2 dated 11/2/23 by JBA.
d. FP1 through FP5 dated 11/2/23 by teljian.
e. MP1 through P3 dated 11/2/23 by HARGIS.
f. M1.1 through M3 dated 11/2/23 by HARGIS.
g. BASR1 through R3 dated 11/2/23 by HARGIS.
h. E1 through EPH1 dated 11/2/23 by HARGIS.
i. SSM-1 through CSS-2 dated 11/1/23 by Nasland.
j. OS1 dated 11/2/23 by brr.
2. Structural Calculations: PDF dated 11/2/23 by JBA.
The applicable provisions of the 2022 California Building Standards Code were used as the basis of this review.
Plan review comments follow on the attached list.
Please submit an itemized response letter and complete and revised documents with directly to city of La Quinta
Building and Safety Department.
Sincerely,
INTERWEST CONSULTING GROUP
Steve Kim
Plan Checker
1500 S. Haven Ave I Suite 220
Ontario, CA 91761
Mark Seven
EMP Plans Examiner
909.295-3142 INTERWESTGRP. COM
Walmort Remodel
79295 Hwy. 111
116124
PROJECT DATA:
City of La Quinta - First Review
Interwest Project No. LAQ24-0002
Permit App: BCOM2023-1030
Page 2 of 7
Occupancy Group:
Area (sq. ft.):
M
A2
A3
F1
B
S1
159520+4825+11233
4493
525
4149
6769+5313
34198
Total Area:
231025
Building Height:
Not provided
Building Stories:
Not provided
Type of Construction:
VB
Occupant Load:
3485
Sprinklered:
Y
Valuation:
Wildland Urban Interface N
(WUI) Fire Area?
Flood Zone: I AE
Risk Category:
II
Site Class (seismic):
D-default
Seismic Design Category:
D
Special Wind Region:
N
Snow Loads:
N
GENERAL COMMENTS:
G1. The following plan review documents are based on the City of La Quinta Building Regulations. The following
comments reference the 2022 California Building Standards Code as amended by the authority having
jurisdiction unless otherwise noted.
G2. Please respond in writing to each plan review comment by marking this comment list or creating a response
letter. Indicate which detail, specification, or calculation shows the requested information. At minimum, the
following should be included with each plan review response:
• Page / sheet number(s), detail / specification number(s), etc., and include all applicable code
section(s).
• Briefly explain in writing how the design is intended to comply with the applicable code sections.
• Please provide a narrative of revisions made outside the plan review comments.
Complete and clear responses will expedite the re -check of this project.
INTERWEST
Walmort Remodel City of La Quinta - First Review
79295 Hwy. 111 Interwest Project No. LAQ24-0002
116124 Permit App: BCOM2023-1030
Page 3 of 7
G3. Please be sure to include on the re -submittal the architect's and /or engineer's stamp, signature, date of
signature, and registration number on all sheets of plans depicting structural designed elements and cover
sheets of calculations. CBPC 5536.1 and 6735.
PLAN REVIEW COMMENTS:
BUILDING AND LIFE SAFETY: [Steve Kim; skim@interwestgrp.com; 909.738.0960]
Sheet N1
Al. Sheet N1 is repeated.
SITE ACCESSIBILITY: [Steve Kim; skim@interwestgrp.com; 909.738.0960]
Sheet SP1
SA1. Please provide complete site accessibility plans for review. Identify curbs, zero curbs, curb ramps, blended
transitions, etc. and provide details showing compliance with the current ADA standards. [CBC 1113-202.4]
SA2. Please provide notes and specifications for accessible routes:
a. The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking
surfaces shall not be steeper than 1:48. [CBC 1113-403.3]
b. The clear width for sidewalks and walks shall be 48 inches minimum. [CBC 11B-403.5.1]
C. Floor and ground surfaces shall be stable, firm and slip resistant. [CBC 1113-302.1]
d. Changes in level of 1/4 inch high maximum shall be permitted to be vertical and without edge
treatment. Changes in level between 1/4 inch high minimum and 1/2 inch high maximum shall be
beveled with a slope not steeper than 1:2. [CBC 1113-302.2-3]
e. Objects with leading edges more than 27 inches and not more than 80 inches above the finish floor
or ground shall protrude 4 inches maximum horizontally into the circulation path. [CBC 1113-307.2]
f. Vertical clearance shall be 80 inches high minimum. [CBC 1113-307.4]
SA3. Please provide enlarged plans of the (E) accessible parking and show compliance with the current ADA
standards.
ACCESSIBILITY: [Steve Kim; skim@interwestgrp.com; 909.738.0960]
Sheet A5.1
AC1. On detail 3: A minimum 60 inches wide and 48 inches deep maneuvering space shall be provided in front of
the water closet. [CBC 11B-604.3.1]
Sheet A5.2
AC2. On detail 4: In a wheelchair accessible compartment with a door located in the side wall or partition, either
in -swinging or out -swinging, a minimum 60 inches wide and 60 inches deep maneuvering space shall be
provided in front of the water closet. See Figure 1113-604.8.1.1.2. [CBC 1113-604.8.1.1.2]
INTERWEST
Walmort Remodel
79295 Hwy. 111
116124
City of La Quinta - First Review
Interwest Project No. LAQ24-0002
Permit App: BCOM2023-1030
Page 4 of 7
In a wheelchair accessible compartment with an in -swinging door, a minimum 60 inches wide by 36 inches
deep maneuvering space shall be provided in front of the clearance required in Section 1113-604.8.1.1. See
Figures 1113-604.8.1.1.2 (b) and 11B-604.8.1.1.3 (b). [CBC 11B-604.8.1.1.1]
AC3. On detail 8: Sanitary napkin disposal units, if provided, shall comply with Section 1113-309.4 and shall be wall
mounted and located on the sidewall between the rear wall of the toilet and the toilet paper dispenser,
adjacent to the toilet paper dispenser. The disposal unit shall be located below the grab bar with the
opening of the disposal unit 19 inches minimum above the finish floor. [CBC 11B-604.7.2]
AC4. On detail 8: The space between the grab bar and projecting objects above shall be 12 inches minimum. [CBC
11B-609.3]
Sheet AC1
AC5. On detail 4: The required clearance around the water closet shall be permitted to overlap the water closet,
associated grab bars, dispensers, sanitary napkin disposal units, coat hooks, shelves, accessible routes, clear
floor space and clearances required at other fixtures, and the turning space. No other fixtures or
obstructions shall be located within the required water closet clearance. [CBC 11B-604.3.2]
MECHANICAL: [Mark Seven; mseven@interwestgrp.com; 949.363.3054]
M1. At the time of rough installation and during storage on the construction site until the final startup of the
heating cooling and ventilation equipment, all duct and other related air distribution component openings
shall be covered with tape, plastic, sheet metal, or other methods acceptable to the enforcing agency to
reduce the amount of dust, water or debris which may enter the system (Cal Green 5.504.3). Note to be
added to the plan.
M2. Regularly occupied areas of the building with air filtration media for outside and return air that provides at
least a Minimum Efficiency Reporting Value (MERV) of 13. Existing units shall be inspected, coils cleaned, and
filters replaced. CIVIC 401.2.
M3. Please clarify the CFM for the return grills in the Rear mechanical plan.
M4. Restrooms for Pharmacy shall have door undercut to allow airflow from the room to the exhaust fan.
M5. Please clarify whether the RTU-12 is new or existing. Otherwise please provide the equipment details and SD
to be shown in the plan.
M6. Provide seismic restraints to all ductwork, pipes, and equipment support in accordance with the latest
SMACNA guideline for seismic restraint of mechanical systems.
REFRIGERANT: [Mark Seven; mseven@interwestgrp.com; 949.363.3054]
R1. Where refrigerant from a refrigerant leak may concentrate, please show an alarm system that will actuate
mechanical ventilation in accordance with CIVIC 1106.2.4 at a set point not more than the corresponding
Occupational Exposure Limit (OEL), in accordance with CIVIC Table 1102.3.
INTERWEST
Walmort Remodel City of La Quinta - First Review
79295 Hwy. 111 Interwest Project No. LAQ24-0002
116124 Permit App: BCOM2023-1030
Page 5 of 7
R2. Please provide the design of support and seismic restraint detail for refrigeration piping per occupancy
hazardous facilities on Table 16-K. CIVIC 1105.2.
R3. Provide support for the refrigerant piping within 6 feet following the first bend in such tubing from the
compressor and within 2 feet of each subsequent bend or angle. Piping tubing shall be supported at points
not more than 15 feet apart. CIVIC 1109.6.
R4. Provide note that the refrigerant piping and joints shall be exposed to view for visual inspection and
acceptance by the City prior to being covered or enclosed. CIVIC 1109.8
PLUMBING: [Mark Seven; mseven@interwestgrp.com; 949.363.3054]
P1. New or repaired potable water systems shall be disinfected prior to use where required by the Authority
Having Jurisdiction. The method to be followed shall be that prescribed by the Health Authority or as
prescribed by CPC 609.9(1) through (4). Note to be added to the plan.
P2. Provide details of typical pipe hangers and supports used for this project. CPC Table 313.3. provide the pipe
schedule to show the pipe type used in the project.
P3. Limitation of Hot Water Temperature for Public Lavatories. Hot water delivered from public -use lavatories
shall be limited to a maximum temperature of 120°F (49°C) by a device that is in accordance with ASSE 1070
or CSA 13125.3. The water heater thermostat shall not be considered a control for meeting this provision. CPC
407.3.
P4. All plumbing fixtures that provide water for human consumption shall comply with the California lead-free
law per section 116875 of the California Health and Safety Code.
P5. hot water and drainpipes under accessible lavatories shall be insulated or otherwise covered. there shall be
no sharp or abrasive surfaces under lavatories. Note to be added to the plan.
P6. Cleanouts are required to be provided on the 'upper terminal' of all sinks and urinals located on the first floor
of a building. Demonstrate cleanout at all sinks (including mop sinks, lavatories, and hand sinks) that are part
of this project. Show all required ceanouts on the plan. CPC 707.4, Exception 1
P7. All horizontal drainage piping shall slope not less than % of an inch per foot (2%). Piping 4 inches or larger may
be sloped not less than 1/8 of an inch (1%) where first approved by the AHJ. CPC 708.1. please show the slope
in the layout.
P8. Domestic water pipe shall be tested per CPC 609.4. Drainage and vent pipe shall be tested per CPC 712.0 and
bleeding sewer per CPC 723.0.
ELECTRICAL: [Mark Seven; mseven@interwestgrp.com; 949.363.3054]
E1. Provide emergency lighting photometry, calculation, and statistic table for verification of egress illumination.
A minimum of 1 foot-candle emergency egress lighting under normal power shall be provided alongthe entire
exit pathway per CBC1008.3.5.
INTERWEST
Walmort Remodel City of La Quinta - First Review
79295 Hwy. 111 Interwest Project No. LAQ24-0002
116124 Permit App: BCOM2023-1030
Page 6 of 7
E2. All installed luminaires shall be high -efficacy in accordance with Table 150.0-A.
E3. All exhaust fans shall be switched separately from the lighting system(s). 2022 California energy code
160.5(a)2g.
E4. All emergency and exit lights shall be provided with a minimum 90-minute rated capacity of emergency
battery under full load. CBC 1008.3.4.
E5. Please Complete the lighting fixture schedule. include wattage consumption. CEC 410.6.
E6. Please provide a disconnecting switch to the equipment JB.
E7. Please show the size of all disconnect switches on the plan; or clarify with a note that all disconnect switches
will match the breaker /switch size of the same branch circuit/feeder in the panel respectively. CEC 240.4;
CEC 220.18(A).
E8. GFCI-protected WP convenience outlet on the same level and within 25' for all locations showing an HVAC
condenser. CEC 210.63.
E9. Provide a note on single -line diagrams that all lugs shall be rated for a minimum 75-degree F.
E10. Show the voltage drop at the end of the site branch circuits and all feeders. For new panels only.
E11. All new circuit breakers should match the existing type and have the highest A.I.C. rating.
E12. Sheet ECC1. Provide tamper -resistant receptacles for all new receptacles, per CEC 406.12. Note on plans.
ENERGY COMPLIANCE:
Electrical Compliance: [Mark Seven; mseven@interwestgrp.com; 949.363.3054]
EE1. Please provide the project address in T-24.
EE2. Wattage should be provided to check T-24.
Mechanical Compliance: [Mark Seven; mseven@interwestgrp.com; 949.363.3054]
EM1. No comments in this section.
Envelope Compliance: [Reviewer; email@interwestgrp.com; phone]
EC1.
CaIGREEN: [Reviewer; email@interwestgrp.com; phone]
CG1.
INTERWEST
Walmort Remodel City of La Quinta - First Review
79295 Hwy. 111 Interwest Project No. LAQ24-0002
116124 Permit App: BCOM2023-1030
Page 7 of 7
STRUCTURAL: [Steve Kim; skim@interwestgrp.com; 909.738.0960]
S1. Provide complete structural plans and calculations for the proposed WIC. [ASCE 7-16 Chapter 15]
Sheet S1
S2. indicate C&C design pressures in accordance with CBC 1603.1.4.
Structural Calculations
S3. Design to comply with the 2022 CBC and adopted reference standards.
S4. For the MWFRS wind design, use the appropriate zones in accordance with ASCE 7-16.
S5. On page 15, seismic design calculations appear to be incomplete.
S6. Provide canopy pad footing design calculations for review.
Sheet AC1
S7. Provide cut sheets for the TIRE CHANGER, WHEEL BALANCER, and CONVEYOR. Discrete mechanical
components weighing more than 400lbs or CG greater than 4ft above adjacent floor, OR suspended
components weighing more than 20lbs must comply with the nonstructural seismic design requirements
of ASCE 7-16 Chapter 13.
Sheet GA1
S8. Provide seismic anchorage details and calculations for the proposed refrigerated cases.
Please contact the listed reviewers between 9:00 A.M. and 4:00 P.M., M-F, with any questions.
[END]
INTERWEST
January 6, 2024
CITY OF LA QUINTA - FIRST REVIEW
Permit No: BCOM2023-1030
Interwest No.: LAQ24-0002
Non -Structural: 7.5-hours
Structural: 2-hours
City of La Quinta
Building Department
78-495 Calle Tampico
La Quinta, CA 92253
Plan Review: Walmart Remodel
Address: 79295 Hwy. 111
0
rtv
INTERWEST
A SAFEbuilt' COMPANY
Interwest Consulting Group has completed a first code compliance review of the following documents on behalf of
the City of La Quinta:
1. Drawings: Two copies of following:
a. C1 through SA1 dated 11/2/23 by brr.
b. SP1 through OPA1.2 datedll/2/23 by brr.
C. S1 through S2 dated 11/2/23 by JBA.
d. FP1 through FP5 dated 11/2/23 by teljian.
e. MP1 through P3 dated 11/2/23 by HARGIS.
f. M1.1 through M3 dated 11/2/23 by HARGIS.
g. BASR1 through R3 dated 11/2/23 by HARGIS.
h. E1 through EPH1 dated 11/2/23 by HARGIS.
i. SSM-1 through CSS-2 dated 11/1/23 by Nasland.
j. OS1 dated 11/2/23 by brr.
2. Structural Calculations: PDF dated 11/2/23 by JBA.
The applicable provisions of the 2022 California Building Standards Code were used as the basis of this review.
Plan review comments follow on the attached list.
Please submit an itemized response letter and complete and revised documents with directly to city of La Quinta
Building and Safety Department.
Sincerely,
INTERWEST CONSULTING GROUP
Steve Kim
Plan Checker
1500 S. Haven Ave I Suite 220
Ontario, CA 91761
Mark Seven
EMP Plans Examiner
909.295-3142 INTERWESTGRP. COM
Walmort Remodel
79295 Hwy. 111
116124
PROJECT DATA:
City of La Quinta - First Review
Interwest Project No. LAQ24-0002
Permit App: BCOM2023-1030
Page 2 of 7
Occupancy Group:
Area (sq. ft.):
M
A2
A3
F1
B
S1
159520+4825+11233
4493
525
4149
6769+5313
34198
Total Area:
231025
Building Height:
Not provided
Building Stories:
Not provided
Type of Construction:
VB
Occupant Load:
3485
Sprinklered:
Y
Valuation:
Wildland Urban Interface N
(WUI) Fire Area?
Flood Zone: I AE
Risk Category:
II
Site Class (seismic):
D-default
Seismic Design Category:
D
Special Wind Region:
N
Snow Loads:
N
GENERAL COMMENTS:
G1. The following plan review documents are based on the City of La Quinta Building Regulations. The following
comments reference the 2022 California Building Standards Code as amended by the authority having
jurisdiction unless otherwise noted.
G2. Please respond in writing to each plan review comment by marking this comment list or creating a response
letter. Indicate which detail, specification, or calculation shows the requested information. At minimum, the
following should be included with each plan review response:
• Page / sheet number(s), detail / specification number(s), etc., and include all applicable code
section(s).
• Briefly explain in writing how the design is intended to comply with the applicable code sections.
• Please provide a narrative of revisions made outside the plan review comments.
Complete and clear responses will expedite the re -check of this project.
INTERWEST
Walmort Remodel City of La Quinta - First Review
79295 Hwy. 111 Interwest Project No. LAQ24-0002
116124 Permit App: BCOM2023-1030
Page 3 of 7
G3. Please be sure to include on the re -submittal the architect's and /or engineer's stamp, signature, date of
signature, and registration number on all sheets of plans depicting structural designed elements and cover
sheets of calculations. CBPC 5536.1 and 6735.
PLAN REVIEW COMMENTS:
BUILDING AND LIFE SAFETY: [Steve Kim; skim@interwestgrp.com; 909.738.0960]
Sheet N1
Al. Sheet N1 is repeated.
SITE ACCESSIBILITY: [Steve Kim; skim@interwestgrp.com; 909.738.0960]
Sheet SP1
SA1. Please provide complete site accessibility plans for review. Identify curbs, zero curbs, curb ramps, blended
transitions, etc. and provide details showing compliance with the current ADA standards. [CBC 1113-202.4]
SA2. Please provide notes and specifications for accessible routes:
a. The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking
surfaces shall not be steeper than 1:48. [CBC 1113-403.3]
b. The clear width for sidewalks and walks shall be 48 inches minimum. [CBC 11B-403.5.1]
C. Floor and ground surfaces shall be stable, firm and slip resistant. [CBC 1113-302.1]
d. Changes in level of 1/4 inch high maximum shall be permitted to be vertical and without edge
treatment. Changes in level between 1/4 inch high minimum and 1/2 inch high maximum shall be
beveled with a slope not steeper than 1:2. [CBC 1113-302.2-3]
e. Objects with leading edges more than 27 inches and not more than 80 inches above the finish floor
or ground shall protrude 4 inches maximum horizontally into the circulation path. [CBC 1113-307.2]
f. Vertical clearance shall be 80 inches high minimum. [CBC 1113-307.4]
SA3. Please provide enlarged plans of the (E) accessible parking and show compliance with the current ADA
standards.
ACCESSIBILITY: [Steve Kim; skim@interwestgrp.com; 909.738.0960]
Sheet A5.1
AC1. On detail 3: A minimum 60 inches wide and 48 inches deep maneuvering space shall be provided in front of
the water closet. [CBC 11B-604.3.1]
Sheet A5.2
AC2. On detail 4: In a wheelchair accessible compartment with a door located in the side wall or partition, either
in -swinging or out -swinging, a minimum 60 inches wide and 60 inches deep maneuvering space shall be
provided in front of the water closet. See Figure 1113-604.8.1.1.2. [CBC 1113-604.8.1.1.2]
INTERWEST
Walmort Remodel
79295 Hwy. 111
116124
City of La Quinta - First Review
Interwest Project No. LAQ24-0002
Permit App: BCOM2023-1030
Page 4 of 7
In a wheelchair accessible compartment with an in -swinging door, a minimum 60 inches wide by 36 inches
deep maneuvering space shall be provided in front of the clearance required in Section 1113-604.8.1.1. See
Figures 1113-604.8.1.1.2 (b) and 11B-604.8.1.1.3 (b). [CBC 11B-604.8.1.1.1]
AC3. On detail 8: Sanitary napkin disposal units, if provided, shall comply with Section 1113-309.4 and shall be wall
mounted and located on the sidewall between the rear wall of the toilet and the toilet paper dispenser,
adjacent to the toilet paper dispenser. The disposal unit shall be located below the grab bar with the
opening of the disposal unit 19 inches minimum above the finish floor. [CBC 11B-604.7.2]
AC4. On detail 8: The space between the grab bar and projecting objects above shall be 12 inches minimum. [CBC
11B-609.3]
Sheet AC1
AC5. On detail 4: The required clearance around the water closet shall be permitted to overlap the water closet,
associated grab bars, dispensers, sanitary napkin disposal units, coat hooks, shelves, accessible routes, clear
floor space and clearances required at other fixtures, and the turning space. No other fixtures or
obstructions shall be located within the required water closet clearance. [CBC 11B-604.3.2]
MECHANICAL: [Mark Seven; mseven@interwestgrp.com; 949.363.3054]
M1. At the time of rough installation and during storage on the construction site until the final startup of the
heating cooling and ventilation equipment, all duct and other related air distribution component openings
shall be covered with tape, plastic, sheet metal, or other methods acceptable to the enforcing agency to
reduce the amount of dust, water or debris which may enter the system (Cal Green 5.504.3). Note to be
added to the plan.
M2. Regularly occupied areas of the building with air filtration media for outside and return air that provides at
least a Minimum Efficiency Reporting Value (MERV) of 13. Existing units shall be inspected, coils cleaned, and
filters replaced. CIVIC 401.2.
M3. Please clarify the CFM for the return grills in the Rear mechanical plan.
M4. Restrooms for Pharmacy shall have door undercut to allow airflow from the room to the exhaust fan.
M5. Please clarify whether the RTU-12 is new or existing. Otherwise please provide the equipment details and SD
to be shown in the plan.
M6. Provide seismic restraints to all ductwork, pipes, and equipment support in accordance with the latest
SMACNA guideline for seismic restraint of mechanical systems.
REFRIGERANT: [Mark Seven; mseven@interwestgrp.com; 949.363.3054]
R1. Where refrigerant from a refrigerant leak may concentrate, please show an alarm system that will actuate
mechanical ventilation in accordance with CIVIC 1106.2.4 at a set point not more than the corresponding
Occupational Exposure Limit (OEL), in accordance with CIVIC Table 1102.3.
INTERWEST
Walmort Remodel City of La Quinta - First Review
79295 Hwy. 111 Interwest Project No. LAQ24-0002
116124 Permit App: BCOM2023-1030
Page 5 of 7
R2. Please provide the design of support and seismic restraint detail for refrigeration piping per occupancy
hazardous facilities on Table 16-K. CIVIC 1105.2.
R3. Provide support for the refrigerant piping within 6 feet following the first bend in such tubing from the
compressor and within 2 feet of each subsequent bend or angle. Piping tubing shall be supported at points
not more than 15 feet apart. CIVIC 1109.6.
R4. Provide note that the refrigerant piping and joints shall be exposed to view for visual inspection and
acceptance by the City prior to being covered or enclosed. CIVIC 1109.8
PLUMBING: [Mark Seven; mseven@interwestgrp.com; 949.363.3054]
P1. New or repaired potable water systems shall be disinfected prior to use where required by the Authority
Having Jurisdiction. The method to be followed shall be that prescribed by the Health Authority or as
prescribed by CPC 609.9(1) through (4). Note to be added to the plan.
P2. Provide details of typical pipe hangers and supports used for this project. CPC Table 313.3. provide the pipe
schedule to show the pipe type used in the project.
P3. Limitation of Hot Water Temperature for Public Lavatories. Hot water delivered from public -use lavatories
shall be limited to a maximum temperature of 120°F (49°C) by a device that is in accordance with ASSE 1070
or CSA 6125.3. The water heater thermostat shall not be considered a control for meeting this provision. CPC
407.3.
P4. All plumbing fixtures that provide water for human consumption shall comply with the California lead-free
law per section 116875 of the California Health and Safety Code.
P5. hot water and drainpipes under accessible lavatories shall be insulated or otherwise covered. there shall be
no sharp or abrasive surfaces under lavatories. Note to be added to the plan.
P6. Cleanouts are required to be provided on the 'upper terminal' of all sinks and urinals located on the first floor
of a building. Demonstrate cleanout at all sinks (including mop sinks, lavatories, and hand sinks) that are part
of this project. Show all required ceanouts on the plan. CPC 707.4, Exception 1
P7. All horizontal drainage piping shall slope not less than % of an inch per foot (2%). Piping 4 inches or larger may
be sloped not less than 1/8 of an inch (1%) where first approved by the AHJ. CPC 708.1. please show the slope
in the layout.
P8. Domestic water pipe shall be tested per CPC 609.4. Drainage and vent pipe shall be tested per CPC 712.0 and
bleeding sewer per CPC 723.0.
ELECTRICAL: [Mark Seven; mseven@interwestgrp.com; 949.363.3054]
E1. Provide emergency lighting photometry, calculation, and statistic table for verification of egress illumination.
A minimum of 1 foot-candle emergency egress lighting under normal power shall be provided alongthe entire
exit pathway per CBC1008.3.5.
INTERWEST
Walmort Remodel City of La Quinta - First Review
79295 Hwy. 111 Interwest Project No. LAQ24-0002
116124 Permit App: BCOM2023-1030
Page 6 of 7
E2. All installed luminaires shall be high -efficacy in accordance with Table 150.0-A.
E3. All exhaust fans shall be switched separately from the lighting system(s). 2022 California energy code
160.5(a)2g.
E4. All emergency and exit lights shall be provided with a minimum 90-minute rated capacity of emergency
battery under full load. CBC 1008.3.4.
E5. Please Complete the lighting fixture schedule. include wattage consumption. CEC 410.6.
E6. Please provide a disconnecting switch to the equipment JB.
E7. Please show the size of all disconnect switches on the plan; or clarify with a note that all disconnect switches
will match the breaker /switch size of the same branch circuit/feeder in the panel respectively. CEC 240.4;
CEC 220.18(A).
E8. GFCI-protected WP convenience outlet on the same level and within 25' for all locations showing an HVAC
condenser. CEC 210.63.
E9. Provide a note on single -line diagrams that all lugs shall be rated for a minimum 75-degree F.
E10. Show the voltage drop at the end of the site branch circuits and all feeders. For new panels only.
E11. All new circuit breakers should match the existing type and have the highest A.I.C. rating.
E12. Sheet ECC1. Provide tamper -resistant receptacles for all new receptacles, per CEC 406.12. Note on plans.
ENERGY COMPLIANCE:
Electrical Compliance: [Mark Seven; mseven@interwestgrp.com; 949.363.3054]
EE1. Please provide the project address in T-24.
EE2. Wattage should be provided to check T-24.
Mechanical Compliance: [Mark Seven; mseven@interwestgrp.com; 949.363.3054]
EM1. No comments in this section.
Envelope Compliance: [Reviewer; email@interwestgrp.com; phone]
EC1.
CaIGREEN: [Reviewer; email@interwestgrp.com; phone]
CG1.
INTERWEST
Walmort Remodel City of La Quinta - First Review
79295 Hwy. 111 Interwest Project No. LAQ24-0002
116124 Permit App: BCOM2023-1030
Page 7 of 7
STRUCTURAL: [Steve Kim; skim@interwestgrp.com; 909.738.0960]
S1. Provide complete structural plans and calculations for the proposed WIC. [ASCE 7-16 Chapter 15]
Sheet S1
S2. indicate C&C design pressures in accordance with CBC 1603.1.4.
Structural Calculations
S3. Design to comply with the 2022 CBC and adopted reference standards.
S4. For the MWFRS wind design, use the appropriate zones in accordance with ASCE 7-16.
S5. On page 15, seismic design calculations appear to be incomplete.
S6. Provide canopy pad footing design calculations for review.
Sheet AC1
S7. Provide cut sheets for the TIRE CHANGER, WHEEL BALANCER, and CONVEYOR. Discrete mechanical
components weighing more than 400lbs or CG greater than 4ft above adjacent floor, OR suspended
components weighing more than 20lbs must comply with the nonstructural seismic design requirements
of ASCE 7-16 Chapter 13.
Sheet GA1
S8. Provide seismic anchorage details and calculations for the proposed refrigerated cases.
Please contact the listed reviewers between 9:00 A.M. and 4:00 P.M., M-F, with any questions.
[END]
INTERWEST
March 15, 2024
CITY OF LA QUINTA - SECOND REVIEW
Permit No: BCOM2023-1030
Interwest No.: LAQ24-0002
Non -Structural: 0-hours
Structural: 1.5-hours
City of La Quinta
Building Department
78-495 Calle Tampico
La Quinta, CA 92253
Plan Review: Walmart Remodel
Address: 79295 Hwy. 111
0
1W
I N T E R W E S T
A SAFEbuilt COMPANY
Interwest Consulting Group has completed a second code compliance review of the following documents on behalf
of the City of La Quinta:
1. Drawings: Two copies of following:
a. C1 through SA1 dated 2/2/24 by brr.
b. SP1 through OPA1.2 dated 2/2/24 by brr.
C. S1 through S2 dated 2/2/24 by JBA.
d. FP1 through FP5 dated 2/2/24 by teljian.
e. MP1 through P3 dated 2/2/24 by HARGIS.
f. M1.1 through M3 dated 2/2/24 by HARGIS.
g. BASR1 through R3 dated 2/2/24 by HARGIS.
h. E1 through EPH1 dated 2/2/24 by HARGIS.
i. SSM-1 through CSS-2 dated 2/2/24 by Nasland.
j. OS1 dated 2/2/24 by brr.
2. Structural Calculations: PDF dated 2/2/24 by JBA.
The applicable provisions of the 2022 California Building Standards Code were used as the basis of this review.
Plan review comments follow on the attached list.
Please submit an itemized response letter and complete and revised documents with directly to city of La Quinta
Building and Safety Department.
Sincerely,
INTERWEST CONSULTING GROUP
Steve Kim
Plan Checker
1500 S. Haven Ave I Suite 220
Ontario, CA 91761
Mark Seven
EMP Plans Examiner
909.295-3142 INTERWESTGRP.COM
Walmort Remodel
79295 Hwy. 111
3115124
PROJECT DATA:
City of La Quinta - Second Review
Interwest Project No. LAQ24-0002
PermitApp: BCOM2023-1030
Page 2 of 3
Occupancy Group:
Area (sq. ft.):
M
A2
A3
F1
B
S1
159520+4825+11233
4493
525
4149
6769+5313
34198
Total Area:
231025
Building Height:
Not provided
Building Stories:
Not provided
Type of Construction:
VB
Occupant Load:
3485
Sprinklered:
Y
Valuation:
Wildland Urban Interface N
(WUI) Fire Area?
Flood Zone: AE
Risk Category:
II
Site Class (seismic):
D-default
Seismic Design Category:
D
Special Wind Region:
N
Snow Loads:
N
GENERAL COMMENTS:
G1. The following plan review documents are based on the City of La Quinta Building Regulations. The following
comments reference the 2022 California Building Standards Code as amended by the authority having
jurisdiction unless otherwise noted.
G2. Please respond in writing to each plan review comment by marking this comment list or creating a response
letter. Indicate which detail, specification, or calculation shows the requested information. At minimum, the
following should be included with each plan review response:
• Page / sheet number(s), detail / specification number(s), etc., and include all applicable code
section(s).
• Briefly explain in writing how the design is intended to comply with the applicable code sections.
• Please provide a narrative of revisions made outside the plan review comments.
Complete and clear responses will expedite the re -check of this project.
I N T E R W E S T
Walmort Remodel City of La Quinta - Second Review
79295 Hwy. 111 Interwest Project No. LAQ24-0002
3115124 PermitApp: BCOM2023-1030
Page 3 of 3
G3. Please be sure to include on the re -submittal the architect's and /or engineer's stamp, signature, date of
signature, and registration number on all sheets of plans depicting structural designed elements and cover
sheets of calculations. CBPC 5536.1 and 6735.
PLAN REVIEW COMMENTS:
STRUCTURAL: [Steve Kim; skim@interwestgrp.com; 909.738.0960]
S1. Provide complete structural plans and calculations for the proposed WIC. [ASCE 7-16 Chapter 15]
PC2: Comment is not addressed. WIC plans and calculations have not been submitted for review.
Sheet S1
S2. indicate C&C design pressures in accordance with CBC 1603.1.4.
PC2: Comment is partially addressed. C&C pressures vary depending on the tributary area. Please
provide the complete table of design pressures.
Structural Calculations
S6. Provide canopy pad footing design calculations for review.
PC2: Comment is partially addressed. Pending final design of the canopy footings.
Sheet AC1
S7. Provide cut sheets for the TIRE CHANGER, WHEEL BALANCER, and CONVEYOR. Discrete mechanical
components weighing more than 400lbs or CG greater than 4ft above adjacent floor, OR suspended
components weighing more than 20lbs must comply with the nonstructural seismic design requirements
of ASCE 7-16 Chapter 13.
PC2: Comment is partially addressed. Pending final design of nonstructural components.
Please contact the listed reviewers between 9:00 A.M. and 4:00 P.M., M-F, with any questions.
[END]
I N T E R W E S T
April 23, 2024
CITY OF LA QUINTA - FINAL REVIEW
Permit No: BCOM2023-1030
Interwest No.: LAQ24-0002
Non -Structural: 0-hours
Structural: 1.5-hours
City of La Quinta
Building Department
78-495 Calle Tampico
La Quinta, CA 92253
Plan Review: Walmart Remodel
Address: 79295 Hwy. 111
0
1W
I N T E R W E S T
A SAFEbuilt COMPANY
Interwest Consulting Group has completed a FINAL code compliance review of the following documents on behalf of
the City of La Quinta:
1. Drawings: Two copies of following:
a. C1 through SA1 dated 4/17/24 by brr.
b. SP1 through 0PA1.2 dated 4/17/24 by brr.
C. S1 through S2 dated 4/17/24 by JBA.
d. FP1 through FP5 dated 4/17/24 by teljian.
e. MP1 through P3 dated 4/17/24 by HARGIS.
f. M1.1 through M3 dated 4/17/24 by HARGIS.
g. BASR1 through R3 dated 4/17/24 by HARGIS.
h. E1 through EPH1 dated 4/17/24 by HARGIS.
i. SSM-1 through CSS-2 dated 4/17/24 by Nasland.
j. OS1 dated 4/17/24 by brr.
2. Structural Calculations: PDF dated 4/17/24 by JBA.
The applicable provisions of the 2022 California Building Standards Code were used as the basis of this review.
Plan review comments follow on the attached list.
Enclosed, please find the above noted documents bearing Interwest Consulting Group's plan review stamps indicating
the documents have been reviewed for code compliance. Please do not hesitate to contact us directly with any
questions.
Sincerely,
INTERWEST CONSULTING GROUP
Steve Kim
Plan Checker
1500 S. Haven Ave I Suite 220
Ontario, CA 91761
909.295-3142 INTERWESTGRP.COM
Walmort Remodel
79295 Hwy. 111
4123124
City of La Quinta - Second Review
Interwest Project No. LAQ24-0002
PermitApp: BCOM2023-1030
Page 2 of2
INTERWEST
A iAFr Quitz WM!'A Y
Bill to:
City of La Quinta
Attn Danny Castro
Design and Development
Director
78-495 Calle Tampico
La Quinta, CA 92253
Remit to:
Interwest Consulting Group
P.O. Box 301069
Los Angeles, CA 90030-1069
Invoice #384827
April 24, 2024
Direct questions to
Erica Cuevas
ecuevas@interwestgrp.com
Professional services for the period April 23, 2024 through April 23, 2024
Commercial - Walmart Store Remodel - 79295 Highway 111 -
LAQ24-0002 - BCOM2023-1030
Invoice Total (Please pay this amount) $202.50
Employee Title Hours Rate Total
Steve Kim Plan Check Engineer 1.50 $135.00 $202.50
Labor 1.50 $202.50
Steve Kim
LAQ24-0002 Commercial - BCOM2023-1030 - 79295 Highway 111 - LAQ24-0002
Day Description
4/23/2024 LAQ24-0002
Total
Hours
1.50
1.50
Iof1
INTERWEST
A SAFEbu ilt' COMPANY
Bill to:
City of La Quinta
Attn Danny Castro
Design and Development
Director
78-495 Calle Tampico
La Quinta, CA 92253
Remit to:
Interwest Consulting Group
P.O. Box 301069
Los Angeles, CA 90030-1069
Invoice #323498
March 15, 2024
Direct questions to
Erica Cuevas
ecuevas@interwestgrp.com
Professional services for the period March 15, 2024 through March 15, 2024
Commercial - Walmart Store Remodel - 79295 Highway 111 -
LAQ24-0002 - BCOM2023-1030
Invoice Total (Please pay this amount) $202.50
Employee Title Hours Rate Total
Steve Kim Plan Check Engineer 1.50 $135.00 $202.50
Labor 1.50 $202.50
Steve Kim
LAQ24-0002 Commercial - BCOM2023-1030 - 79295 Highway 111 - LAQ24-0002
Day Description
3/15/2024 LAQ24-0002
Total
Hours
1.50
1.50
Iof1
INTERWEST
A SAFEbuilf COMPANY
Bill to:
City of La Quinta
Attn Danny Castro
Design and Development
Director
78-495 Calle Tampico
La Quinta, CA 92253
Remit to:
Interwest Consulting Group
P.O. Box 301069
Los Angeles, CA 90030-1069
Invoice #225254
January 16, 2024
Direct questions to
Erica Cuevas
ecuevas@interwestgrp.com
Professional services for the period January 6, 2024 through January 8, 2024
Commercial - Walmart Store Remodel - 79295 Highway 111 -
LAQ24-0002 - BCOM2023-1030
Invoice Total (Please pay this amount) $1,162.50
Employee Title Hours Rate Total
Mark Seven ICC Certified Plans Examiner 6.00 $115.00 $690.00
Steve Kim Plan Check Engineer 3.50 $135.00 $472.50
Labor 9.50 $1,162.50
Steve Kim
LAQ24-0002 Commercial - Walmart Store Remodel - 79295 Highway 111
Dav Description
Hours
1/6/2024 LAQ24-0002
3.50
Total 3.50
Mark Seven
LAQ24-0002 Commercial - Walmart Store Remodel - 79295 Highway 111
Day Description
Hours
1/6/2024 LAQ24-0002
2.50
1/8/2024 LAQ24-0002
3.50
Total 6.00
IofI
A iAFr Quitz WM!'A Y
Bill to:
City of La Quinta
Attn Danny Castro
Design and Development
Director
78-495 Calle Tampico
La Quinta, CA 92253
Remit to:
Interwest Consulting Group
P.O. Box 301069
Los Angeles, CA 90030-1069
Invoice #384827
April 24, 2024
Direct questions to
Erica Cuevas
ecuevas@interwestgrp.com
Professional services for the period April 23, 2024 through April 23, 2024
Commercial - Walmart Store Remodel - 79295 Highway 111 -
LAQ24-0002 - BCOM2023-1030
Invoice Total (Please pay this amount) $202.50
Employee Title Hours Rate Total
Steve Kim Plan Check Engineer 1.50 $135.00 $202.50
Labor 1.50 $202.50
Steve Kim
LAQ24-0002 Commercial - BCOM2023-1030 - 79295 Highway 111 - LAQ24-0002
Day Description
4/23/2024 LAQ24-0002
Total
Hours
1.50
1.50
Iof1