HomeMy WebLinkAboutBCOM2024-0127 Title 24BUILDING ENERGY ANALYSIS REPORT PROJECT: Washington Park Sub Major 5 Suite #02 TI 46630 Washington Street La Quinta, CA 92253 Project Designer: MOA Architects, Inc. 14467 Park Avenue Victorville, Ca 92392 (760) 241-7858 Report Prepared by: Rodolfo Torres, P.E. RKM Consulting Engineers 312 N. 10th Street Montebello, California 90640-4224 (818) 261-5704 Job Number: 2404-3 Date: 5/20/2024 BCOM2024-0127 CITY OF LA QUINTA BUILDING DIVISION REVIEWED FOR CODE COMPLIANCE DATE09/24/2024 Br The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2022 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC — www.energysoft.com. i TABLE OF CONTENTS Cover Page 1 Table of Contents 2 Form NRCC-MCH-E Mechanical Systems 3 Form NRCC-PLB-E Domestic Water Heating System 14 STATE OF CALIFORNIA Mechanical Systems CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-E This document is used to demonstrate compliance for mechanical systems that are within the scope of the permit application and are demonstrating compliance using the prescriptive path outlined in 140.4, or 141.0(b)2 for alterations. Project Name: Washington Park Sub Major 5 Suite #02 TI Report Page: (Page 1 of 11) Project Address: 46630 Washington Street Date Prepared: 5/20/2024 A. GENERAL INFORMATION 01 Project Location (city) La Quinta 04 Total Conditioned Floor Area 5818 02 Climate Zone 15 05 Total Unconditioned Floor Area 0 03 Occupancy Types Within Project: 06 # of Stories (Habitable Above Grade) 1 • Gymnasium B. PROJECT SCOPE This table Includes mechanical systems or components that are within the scope of the permit application and are demonstrating compliance using the prescriptive path outlined in 140.4, 170.2(b) or 141.0(b)2 and 180.2(b)2 for alterations. 01 02 03 Air System(s) Wet System Components Dry System Components 1 Heating Air System • Water Economizer 0 Air Economizer A Cooling Air System • Pumps • Electric Resistance Heat Mechanical Controls • System Piping 0 Fan Systems Controls (existing to remain, altered • Cooling Towers AMechanical 0 Ductwork (existing to remain, altered or new) or new) • Chillers 0 Ventilation • Boilers • Zonal Systems/ Terminal Boxes Generated Date/Time: Documentation Software: EnergyPro CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: EnergyPro-5889-0524-0174 Report Generated: 2024-05-20 11:15:56 STATE OF CALIFORNIA Mechanical Systems CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-E Project Name: Washington Park Sub Major 5 Suite #02 TI Report Page: (Page 2 of 11) Date Prepared: 5/20/2024 C. COMPLIANCE RESULTS Table C will indicate if the project data input into the compliance document is compliant with mechanical requirements. This table is not editable by the user. If this table says "DOES NOT COMPLY" or "COMPLIES with Exceptional Conditions" refer to Table D., or the table indicated as not compliant for guidance. 01 AND 02 AND 03 AND 04 AND 05 AND 06 AND 07 AND 08 09 System Summary 110.1, 110.2, 140.4, 170.2(c) Pumps 140.4(k), 170.2(c)41 Fans/ Economizers 140.4(c), 140.4(e), 170.2(c) System Controls 110.2, 120.2, 140.4(f), 170.2(c) Ventilation 120.1, 160.2 Terminal Box Controls 140.4(d), 170.2(c)4B Distribution 120.3, 140.4(1), 160.2, 160.3 Cooling Towers 110.2(e)2 Compliance Results (See Table F) (See Table G) (See Table H) (See Table I) (See Table J) (See Table K) (See Table L) (See Table M) Yes AND AND Yes AND Yes AND Yes AND AND Yes AND COMPLIES Mandatory Measures Compliance (See Table Q for Details) COMPLIES D. EXCEPTIONAL CONDITIONS This table is auto filled with uneditable comments because of selections made or data entered in tables throughout the form. E. ADDITIONAL REMARKS This table includes remarks made by the permit applicant to the Authority Having Jurisdiction. F. HVAC SYSTEM SUMMARY (DRY & WET SYSTEMS) Space Conditioning System Information 01 02 03 04 05 06 System Name Quantity System Serving System Status Space Type Utilizing Recovered Heat Carrier 10-Ton Package Unit 4 Single zone New/ Addition ■ Generated Date/Time: Documentation Software: EnergyPro CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: EnergyPro-5889-0524-0174 Report Generated: 2024-05-20 11:15:56 STATE OF CALIFORNIA Mechanical Systems CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-E Project Name: Washington Park Sub Major 5 Suite #02 TI Report Page: (Page 3 of 11) Date Prepared: 5/20/2024 F. HVAC SYSTEM SUMMARY (DRY & WET SYSTEMS) Dry System Equipment Sizing (includes air conditioners, condensers, heat pumps, VRF, furnaces and unit heaters and DOAS systems) 01 02 03 04 05 06 07 08 09 10 11 Name or Item Tag Equipment Category per Tables 110.2, 140.4(a)2 and 170.2(c)3aii Equipment Type per Tables 110.2 and Title 20 Smallest Size Available'Total 140.4(a) and 170.2(c)1 Equipment Sizing per Mechanical Schedule (kBtu/h) 140.4(a&b) 170.2(c)1 & 170.2(c)2 Heating Output2'3 Cooling Output2'3 Load Calculations3,4 Per Design (kBtu/h) Rated (kBtu/h) Supp. Heating Output (kBtu/h) Sensible Per Design (kBtu/h) Rated (kBtu/h) Total Heating Load (kBtu/h) Sensible Cooling Load (kBtu/h) Carrier 10 Ton Package Unit Unitary Heat Pumps Air-cooled, pkg (3 phase) NA: Load Controls 287.3 115 0 284.33 76.35 171.63 289.68 1FOOTNOTES: Equipment shall be the smallest size, within the available options of the desired equipment line, necessary to meet the design heating and cooling loads of the building per 140.4(a) and 170.2(c)1. Healthcare facilities are excepted. 21t is common practice to show rated output capacity on the equipment schedule. Sensible cooling output comes from specification sheet tables. If equipment is heating only, leave cooling output and load blank. If equipment is cooling only, leave heating output and load blank. 4 Authority Having Jurisdiction may ask for load calculations used for compliance per 140.4(b) and 170.2(c). Dry System Equipment Efficiency (other than Package Terminal Air Conditioners (PTAC) and Package Terminal Heat Pumps (PTHP), DX-DOAS and Dual Fuel Heat Pumps) 01 02 03 04 05 06 07 08 09 Heating Mode Cooling Mode Minimum Minimum Name or Item Size Category Rating Efficiency Efficiency Tag (Btu/h) Condition Efficiency Unit Required per Design Efficiency Efficiency Unit Required per Design Efficiency ( °F) Tables 110.2 / Tables 110.2 / Title 20 Title 20 Carrier 10 Ton Package Unit >=65,000 and <135,000 COP 3.4 3.4 EER IEER 11 14.1 11 15 G. PUMPS This section does not apply to this project. Generated Date/Time: Documentation Software: EnergyPro CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: EnergyPro-5889-0524-0174 Report Generated: 2024-05-20 11:15:56 STATE OF CALIFORNIA Mechanical Systems CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-E Project Name: Washington Park Sub Major 5 Suite #02 TI Report Page: (Page 4 of 11) Date Prepared: 5/20/2024 H. FAN SYSTEMS & AIR ECONOMIZERS This table is used to demonstrate compliance with prescriptive requirements found in 140.4(c), 140.4(e), 140.4(m), 170.2(c)3, and 170.2(c)4A for fan systems. Fan systems serving only process loads are exempt from these requirements and do not need to be included in Table H. System Name Carrier 10-Ton Package Unit Quantit y 4 Fan System Status New System Zoning all other systems Serving Dwelling Units Not Serving Dwelling Units Fan System Airflow (cfm) 16,000 Site Elevation 400 Economizer Differential Enthalpy 01 02 03 04 05 06 07 08 09 10 11 Fan Name or Item Tag Fan Type Qty Component Airflow through Component (%) Water Gauge (w.g) Allowance Design Compone nt Allowance Fan Allowance (watt/cfm)3 Design Electrical Input Power Method Motor Nameplate Horsepower Design Electrical Input Power (kW) SF Supply 4 Base Allowance for system serving spaces <=6 floors away 4,000 928 Manufacturer provided 1.73 MERV 13-16 Filter upstream of thermal conditioning equipment 4,000 556 Hydronic/DX cooling coil or heat pump coil 4,000 556 Economizer Return Damper 4,000 184 Supply Fan Base Allowance (kW) Exhuast/Return/Relief/Transfer Fan Base Allowance(kW) Fan System Allowance (kW)3 8.9 Fan System Electrical Output (kW) 6'9 1 FOOTNOTES: Fans serving spaces with design background noise goals below NC35 2 Low -turndown single -zone VAV fan system must be capable of and configured to reduce airflow to 50 percent of design airflow and use no more than 30 percent of the design wattage at that airflow. No more than 10 percent of the design load served by the equipment shall have fixed loads. 3 Fan system allowance includes fan system base allowance. 4 Filter pressure loss can only be counted once per fan system. s Complex Fan System means a fan system that combines a single cabinet fan system with other supply fans, exhaust fans, or both. 6 Computer room economizers must meet requirements of 140.9(a) and will be documented on the NRCC-PRC-E document.. Generated Date/Time: Documentation Software: EnergyPro CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: EnergyPro-5889-0524-0174 Report Generated: 2024-05-20 11:15:56 STATE OF CALIFORNIA Mechanical Systems CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-E Project Name: Washington Park Sub Major 5 Suite #02 TI Report Page: (Page 5 of 11) Date Prepared: 5/20/2024 H. EXHAUST AIR HEAT RECOVERY 140.4(q), 170.2(c)40 01 02 03 04 05 06 07 08 09 10 11 Fan System Name Qty Hours of Operation per Year Design Supply Airflow Rate Outdoor Airflow %Outdoor Air at Full Design Airflow Exemptions to Exhaust Air Heat Recovery Requirement per 140.4(q) & 170.2(c)40 Exhaust Air Heat Recovery 140.4(q) & 170.2(c)40 Type Of Heat Recovery Rating Required Recovery Ratio Energy Recovery Bypass Fan Energy Index (FEI) 01 02 03 Name or Item Tag FEI Exception FEI Carrier 10-Ton Package Unit None Applies 1 I. SYSTEM CONTROLS This table is used to demonstrate compliance with mandatory controls in 110.2 and 120.2 and prescriptive controls in 140.4(f) and (n), 170.2(c)4D 170.2(c)4L or requirements in 141.0(b)2E 180.2(b)2 for altered space conditioning systems. 01 02 03 04 05 06 07 08 09 System Name System Zoning Conditioned Floor Area Being Served (ft2) Thermostats 110.2(b) & (c)1, 120.2(a) 160.3(a)2A or 141.0(b)2E & 180.2(b)2 Shut -Off Controls 120.2(e) & 160.3(a)2D Isolation Zone Controls 120.2(g) & 160.3(a)2F Demand Response 110.12 120.2(b) & 160.3(a)2B Supply Air Temp. Reset 140.4(f) & 170.2(c)4D Window Interlocks per 140.4(n) & 170.2(c)4D Carrier 10-Ton Package Unit Single zone <= 25,000 ft2 Setback Auto Timer Switch 4 Hour Timer EMCS NA: Would increase energy use Provided 'FOOTNOTES: Gravity gas wall heaters, gravity floor heaters, gravity room heaters, non -central electric heaters, fireplaces or decorative gas appliances, wood stoves are not required to have setback thermostats. Generated Date/Time: Documentation Software: EnergyPro CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: EnergyPro-5889-0524-0174 Report Generated: 2024-05-20 11:15:56 STATE OF CALIFORNIA Mechanical Systems CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-E Project Name: Washington Park Sub Major 5 Suite #02 TI Report Page: (Page 6 of 11) Date Prepared: 5/20/2024 J. VENTILATION AND INDOOR AIR QUALITY This table is used to demonstrate compliance with mandatory ventilation requirements in 120.1 120.2(e)36140.4(p) and 140.4(q) for all nonresidential and hotel/motel and d:t24refnolink/1160.2, 160.3(a)3D, 170.2(a)4N, 170.2(a)40 for high-rise residential occupancies. For alterations, only ventilation systems being altered within the scope of the permit application need to be documented in this table. In lieu of this table, the required outdoor ventilation rates and airflows may be shown on the plans or the calculations can be presented in a spreadsheet. 01 ■ Check the box if the project is showing ventilation calculations on the plans, or attaching the calculations instead of completing this table. 02 L Check this box if the project included Nonresidential, Hotel/Motel Spaces or Multifamily Common Use Spaces ■ 03 ■ Check the box if the project is using natural ventilation in any nonresidential or hotel/motel spaces to meet required ventilation rates per 120.1(c)2. Nonresidential and Hotel/ Motel Multifamily Common Use Ventilation Systems 04 05 06 07 System Name Carrier 10-Ton Package Unit System Design OA CFM Airflow 600 System Design Transfer Air CFM 0 Air Filtration per 120.1(c) 141.0(b)2 and 160.2(c)212 Provided 08 09 10 11 12 13 14 15 16 Space Name or Item Tag 3 Mechanical Ventilation Required per 120.1(c)3 & 160.2(c)3 Exh. Vent per 120.1(c)4 & c 160.2 4 () DCV or Sensor Controls per 120.1(d)3, 120.1(d)5, and 120.1(e)36 160.2(c)5D 160.2(c)5E 160.2(c)5D Occupancy Type4 Conditioned Floor Area (ft2) # of Shower heads/ toilets # of people s Required Min OA CFM Required Min CFM Provided per Design CFM Zone 1 Gym/ sports arena (play area) 5818 40 600 0 600 DCV NA: Not required per §120.1(d)3 NA: Not required space type Occ Sensor 17 Total System Required Min OA CFM 600 18 Ventilation for this System Complies? Yes 1 FOOTNOTES: System CFM should include both mechanical and natural ventilation for the zone/system 2 Air filtration requirements apply to the following three system types per 120.1(c)1A: space conditioning systems utilizing ducts to supply air to occupiable space; supply -only ventilation systems providing outside air to occupiable space; supply side of balanced ventilation systems including heat recovery and energy recovery ventilation systems providing outside air to occupiable space. 3 Uniform Mechanical Code may have more stringent ventilation requirements; the most stringent code requirement takes precedence. See Standards Tables 120.1-A and 120.1-B. Generated Date/Time: Documentation Software: EnergyPro CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: EnergyPro-5889-0524-0174 Report Generated: 2024-05-20 11:15:56 STATE OF CALIFORNIA Mechanical Systems CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-E Project Name: Washington Park Sub Major 5 Suite #02 TI Report Page: (Page 7 of 11) Date Prepared: 5/20/2024 J. VENTILATION AND INDOOR AIR QUALITY 5 For lecture halls with fixed seating, the expected number of occupants shall be determined in accordance with the California Building Code. 6 120.2(e)3 requires systems serving rooms that are required by 130.1(c) to have lighting occupancy sensing controls to also have occupancy sensing zone controls for ventilation. Examples of spaces which require lighting occupancy sensors include offices 250ft2 or smaller, multipurpose rooms less than 1,000 ft2, classrooms, conference rooms, restrooms, aisles and open areas in warehouses, library book stack aisles, corridors, stairwells, parking garages, and loading and unloading zones, unless excepted by 130.1(c). K. TERMINAL BOX CONTROLS This section does not apply to this project. L. DISTRIBUTION (DUCTWORK and PIPING) This table is used to show compliance with mandatory pipe insulation requirements found in 120.3 and mandatory requirements found in 120.4(g) for duct sealing. 01 Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind. Insulation exposed to weather shall be installed with a cover suitable for outdoor service. Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space shall have a Class I or Class II vapor retarder. All penetrations and joints of which shall be sealed. ■ Duct Leakage Testing The answers to the questions below apply to the following duct systems: 1 NR/ Common Use: Duct leakage testing shall not exceed 6% per NA7.5.3 required for these systems? No Generated Date/Time: Documentation Software: EnergyPro CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: EnergyPro-5889-0524-0174 Report Generated: 2024-05-20 11:15:56 STATE OF CALIFORNIA Mechanical Systems CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-E Project Name: Washington Park Sub Major 5 Suite #02 TI Report Page: (Page 8 of 11) Date Prepared: 5/20/2024 L. DISTRIBUTION (DUCTWORK and PIPING) Carrier 10-Ton Package Unit Dwelling Units: Total duct leakage of duct system shall not exceed 12% or duct system to outside shall not exceed 6% per RA3.1.4 required for systems? No Duct leakage testing per CMC Section 603.10.1 required for these systems? Yes 11 No The scope of the project includes only duct systems serving healthcare facilities 12 Yes Duct system provides conditioned air to an occupiable space for a constant volume, single zone, space -conditioning system. 13 No The space conditioning system serves less than 5,000 ft2 of conditioned floor area. 14 No The combined surface area of the ducts is more than 25% of the total surface area of the entire duct system: 15 'The scope of the project includes extending an existing duct system, which is constructed, insulated or sealed with asbestos. 16 No The scope of the project includes an existing duct system that is documented to have been previously sealed as confirmed through field verification and diagnostic testing in accordance with procedures in the Reference Nonresidential Appendix NA2. 17 All Ductwork and plenums with pressure class ratings shall be constructed to Seal Class A 18 All ductwork is an extension of an existing duct system 19 Ductwork serving individual dwelling unit 20 < 25 ft of new or replacement space conditioning ducts installed 21 R-8 Duct Insulation R-value 22 23 M. COOLING TOWERS This section does not apply to this project. Generated Date/Time: Documentation Software: EnergyPro CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: EnergyPro-5889-0524-0174 Report Generated: 2024-05-20 11:15:56 STATE OF CALIFORNIA Mechanical Systems CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-E Project Name: Washington Park Sub Major 5 Suite #02 TI Report Page: (Page 9 of 11) Date Prepared: 5/20/2024 N. DECLARATION OF REQUIRED CERTIFICATES OF INSTALLATION Selections have been made based on information provided in previous tables of this document. If any selection needs to be changed, please explain why in Table E Additional Remarks. These documents must be provided to the building inspector during construction and can be found online at https://www.energy.ca.gov/title24/2019standards/2019_compliance_documents/Nonresidential Documents/NRCl/ Form/Title NRCI-MCH-01-E - Must be submitted for all buildings O. DECLARATION OF REQUIRED CERTIFICATES OF ACCEPTANCE Selections have been made based on information provided in previous tables of this document. If any selection needs to be changed, please explain why in Table E Additional Remarks. These documents must be provided to the building inspector during construction and can be found online at https://www. energy.ca.gov/title24/2019standards/2019 compliance_documents/Nonresidential Documents/NRCA/ Form/Title Systems/Spaces To Be Field Verified NRCA-MCH-02-A - Outdoor Air must be submitted for all newly installed HVAC units. Note: MCH-02-A can be performed in conjunction with MCH-07-A Supply Fan VFD Acceptance (if applicable) since testing activities overlap. Carrier 50FCQM12A2A5-OA6A0; NRCA-MCH-03-A - Constant Volume Single Zone HVAC NOTE: This form does not automatically move to "Yes'. If Constant Volume Single Zone HVAC Systems are included in the scope, permit applicant should move this form to "Yes". Carrier 50FCQM12A2A5-OA6A0; NRCA-MCH-05-A - Air Economizer Controls Carrier 50FCQM12A2A5-OA6A0; NRCA-MCH-11-A Automatic Demand Shed Controls Carrier 50FCQM12A2A5-OA6A0; NRCA-MCH-12-A FDD for Packaged Direct Expansion Units Carrier 50FCQM12A2A5-OA6A0; NRCA-MCH-16-A Supply Air Temperature Reset Controls Carrier 50FCQM 12A2A5-OA6A0; NRCA-MCH-18-A Energy Management Control Systems Carrier 50FCQM 12A2A5-OA6A0; Generated Date/Time: Documentation Software: EnergyPro CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: EnergyPro-5889-0524-0174 Report Generated: 2024-05-20 11:15:56 STATE OF CALIFORNIA Mechanical Systems CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-E Project Name: Washington Park Sub Major 5 Suite #02 TI Report Page: (Page 10 of 11) Date Prepared: 5/20/2024 P. DECLARATION OF REQUIRED CERTIFICATES OF VERIFICATION There are no NRCV forms required for this project. Q. MANDATORY MEASURES DOCUMENTATION LOCATION This table is used to indicate where mandatory measures are documented in the plan set or construction documentation. 01 02 Compliance with Mandatory Measures documented through MCH Mandatory Measures Note Block Yes Plan sheet or construction document location M-Sheets Generated Date/Time: Documentation Software: EnergyPro CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: EnergyPro-5889-0524-0174 Report Generated: 2024-05-20 11:15:56 STATE OF CALIFORNIA Mechanical Systems CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-MCH-E Project Name: Washington Park Sub Major 5 Suite #02 TI Report Page: (Page 11 of 11) Project Address: 46630 Washington Street Date Prepared: 5/20/2024 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT I certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Rodolfo Torres, P.E. Documentation Author Signature: 7-2-' _ _ "^ — (tea Company: RKM Consulting Engineers Signature Date: 2024-05-20 Address: 312 N. 10th Street CEA/ HERS Certification Identification (if applicable): M29983 City/State/Zip: Montebello California 90640-4224 Phone: (818) 261-5704 RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. 2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer) 3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Designer Name: Rodolfo Torres, P.E. Responsible Designer Signature: jZ„_ '�`" �(� Company: RKM Consulting Engineers, Inc. Date Signed: 2024-05-20 Address: 312 N. 10 th Street License: M29983 City/State/Zip: Montebello CA 90640 Phone: (818) 261-5704 Generated Date/Time: Documentation Software: EnergyPro CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: EnergyPro-5889-0524-0174 Report Generated: 2024-05-20 11:15:56 STATE OF CALIFORNIA Domestic Water Heating System CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-PLB-E This document is used to demonstrate compliance for nonresidential occupancies with requirements in 110.1, 110.3, 120.3, and 140.5, and with requirements in 141.0 for additions and alterations, for domestic water heating scopes using the prescriptive path. For high-rise residential and hotel/motel occupancies compliance is demonstrated with requirements in 110.1, 110.3, 160.4 and 170.2(d), and with requirements 180.1 for additions and 180.2 for alterations. Project Name: Washington Park Sub Major 5 Suite #02 TI Report Page: (Page 1 of 6) Project Address: 46630 Washington Street Date Prepared: 5/20/2024 A. GENERAL INFORMATION 01 Project Location (city) La Quinta 02 Climate Zone 15 03 Occupancy Types Within Project (select all that apply): • Gymnasium B. PROJECT SCOPE This table includes domestic water heating systems that are within the scope of the permit application and are demonstrating compliance using the prescriptive paths outlined in 140./ 170.2(d) and 141.0(a)/ 180.1, or 141.0(b)2N / 180.2 for additions or alterations. Solar water heating systems are documented on the NRCC-SAB compliance document. Combined hydronic water heating systems are documented on the NRCC-MCH compliance document. 01 02 03 My project consists of (check all that apply): System Type1'2 System Components 0 New system (DHW system being installed for the first time) Individual System (serving nonresidential spaces) A Equipment L Distribution 0 Controls • System Alteration (equipment, distribution or controls) • Equipment • Distribution • Controls 'FOOTNOTES: Point of use water heaters, or other non -central systems used to serve nonresidential spaces, are considered individual systems. 2 Dwelling units refers to hotel/motel guest rooms and units in a multifamily residential occupancy. 3 DHW systems serving 2 or more dwelling units are considered "Central Systems" for multifamily occupancies C. COMPLIANCE RESULTS Table C will indicate if the project data input into the compliance document is compliant with water heating requirements. If this table says "DOES NOT COMPLY" or "COMPLIES with Exceptional Conditions" refer to Table D. or the table indicated as not compliant for guidance. 01 02 03 04 Domestic Hot Water Equipment Distribution Systems Controls Compliance Results Table F Table G Table H Yes Yes Yes COMPLIES D. EXCEPTIONAL CONDITIONS This table is auto filled with uneditable comments because of selections made or data entered in tables throughout the form. Generated Date/Time: Documentation Software: EnergyPro CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: EnergyPro-5889-0524-0173 Report Generated: 2024-05-20 11:15:56 STATE OF CALIFORNIA Domestic Water Heating System CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-PLB-E Project Name: Washington Park Sub Major 5 Suite #02 TI Report Page: (Page 2 of 6) Date Prepared: 5/20/2024 E. ADDITIONAL REMARKS This table includes remarks made by the permit applicant to the Authority Having Jurisdiction. F. DOMESTIC HOT WATER EQUIPMENT This table is used to demonstrate compliance with mandatory equipment requirements in 110.1 and 110.3. Compliance with prescriptive requirements in 140.5(c)/170.2(d) must also be demonstrated and with 141.0 / 180.1/ 180.2 for addition and alteration scopes. Equipment Schedule: Water Heating Efficiency and Standby Loss 03 04 05 06 System Name AO Smith DEL 6S 2 Exception to 140.5(c)/ 170.2(d)3 Gas Service Water Heating System >= 1MMBtu/h1 Capacity -weighted Average Efficiency % • 07 08 09 10 11 12 13 14 15 Name or Item Tag Equipment Type Volume (gal) Rated Input Capacity (Btu/h) Max GPM/ First Hour Rating (FHR) Rated Efficiency Minimum Efficiency Required Efficiency Unit Designed Standby Loss Maximum Standby Loss AO Smith DEL-6S-2 Consumer Rated Electric Storage 50 20,473 0 <= FHR <18 0.93 0.93 UEF 1FOOTNOTE: In systems >= 1MMBtu/h with multiple units gas water heaters with input capacity > 100,000 Btu/h may meet 90% Et requirements via an input capacity -weighted average. Water Heating Equipment All Occupancies Yes No Not Applicable Requirement 18 ■ ■ ►1 Unfired storage tank insulation shall have Internal + External >=R-16 OR External >=R-3.5. Label required per 110.3(c)3 19 ■ ■ 1/ New state buildings 60% of energy for service water heating from site solar energy or recovered energy per 110.3(c)5 20 ■ ■ ►1 Isolation valves for instantaneous water heater with input rating >6.8 kBTUH or 2 kW has been specified per 110.3(c)6 21 School buildings < 25,000 ft2 and < 4 stories must install a heat pump water heating system per 140.5(a)1. Water heating systems serving an individual bathroom space may be an instantaneous electric water heater. Generated Date/Time: Documentation Software: EnergyPro CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: EnergyPro-5889-0524-0173 Report Generated: 2024-05-20 11:15:56 STATE OF CALIFORNIA Domestic Water Heating System CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-PLB-E Project Name: Washington Park Sub Major 5 Suite #02 TI Report Page: (Page 3 of 6) Date Prepared: 5/20/2024 G. DOMESTIC HOT WATER DISTRIBUTION SYSTEM This table is used to demonstrate compliance for nonresidential occupancies with distribution requirements in 120.3 and 140.5. For multifamily and hotel/motel occupancies, compliance is demonstrated with requirements 110.3(c), 160.4, 170.2(d). Mandatory Pipe Insulation All Occupancies 13• For systems serving dwelling units, pipe insulation must meet the minimum insulation requirements in Table 160.4-A (see blow) except: • Piping that penetrates framing members shall not be required to have pipe insulation for the distance of the framing penetration. Piping that penetrates metal framing shall use grommets, plugs, wrapping or other insulating material to assure that no contact is made with the metal framing. Insulation shall abut securely against all framing members • Piping installed in interior or exterior walls shall not be required to have pipe insulation if all of the requirements are met for compliance with Quality Insulation Installation (QII) as specified in the Reference Residential Appendix RA3.5. • Piping surrounded with a minimum of 1 inch of wall insulation, 2 inches of crawlspace insulation, or 4 inches of attic insulation, shall not be required to have pipe insulation. 14 @ For systems serving nonresidential spaces, pipe insulation for the following applications is specified to comply with Table 120.3-A (see below) per 120.3: • Recirculating system piping, including supply and return piping of the water heater • The first 8 ft of hot and cold outlet piping, including between storage tank and heat trap, for a nonrecirculating storage system • Pipes that are externally heated 15 ■ Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind. Insulation exposed to weather shall be installed with a cover suitable for outdoor service per 120.3(b) / 160.4(f). Pipe insulation buried below grade must be installed in a water proof and non -crushable casing or sleeve. TABLE 120.3-A / 160.4-A PIPE INSULATION THICKNESS Fluid Temperature Range ( °F) Conductivity Range (Btu -in per hour per ft2 per °F) Insulation Mean Rating Temp ( °F) Nominal Pipe Diameter (in) < 1 1 to < 1.5 1.5 to < 4 1.5 to < 4 Multifamily & Hotel/Motel Minimum Insulation Required 105-140 0.22 - 0.28 100 1.0 in or R-7.7 1.5 in or R-12.5 1.5 in or R-11 2.0 in or R-16 Generated Date/Time: Documentation Software: EnergyPro CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: EnergyPro-5889-0524-0173 Report Generated: 2024-05-20 11:15:56 STATE OF CALIFORNIA Domestic Water Heating System CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-PLB-E Project Name: Washington Park Sub Major 5 Suite #02 TI Report Page: (Page 4 of 6) Date Prepared: 5/20/2024 H. DOMESTIC HOT WATER CONTROLS This table is used to demonstrate compliance with control requirements in 110.3 for all occupancies. For multifamily residential and hotel/motel occupancies, compliance is also demonstrated with requirements in 160.4(e)/170.2(d) Yes No Not Applicable Requirement 01 Construction documents require manufacturer certification that service water -heating systems are equipped with automatic temperature controls capable of adjusting temperature settings per 110.3(a). A ■ ■ 02 Systems with capacity > 167,000 BTUH equipped with outlet temperature controls per 110.3(c)1 unless covered by California Plumbing Code 613.0. ■ ■ r 03 Controls for circulating pumps or electrical heat trace systems are capable of automatically turning off the system per §110.3(c)2 unless systems serves healthcare facility. ■ ■ L 04 For recirculation systems serving multiple dwelling units, design includes automatic pump controls per 170.2(d) or 180.1(b)3 for additions. ■ ■ @ 05 For recirculation systems serving individual dwelling units, design includes manual on/off controls as specified in Reference Appendix RA4.4.9 per 170.2(d). ■ ■ 06 Combustion air positive shut-off shall be provided per 160.4(3).on all newly installed commercial boilers as follows: Boilers with input capacity >= 2.5 MMBtu/h, in which the boiler is designed to operate with a nonpositive vent static pressure • Boilers where one stack serves two or more boilers with a total combined input capacity per stack of 2.5 MMBtu/h. ■ ■ •• 07 Boiler combustion air fans with motor >= 10 hp shall meet one of the following • The fan motor shall be driven by a variable speed drive OR • The fan motor shall include controls that limit the fan motor demand to <=30% of the total design wattage at 50% of the design air volume. • • r 08 Newly installed boilers with an input capacity {d:gte/] 5MMBtu/h and a steady state full -load combustion efficiency < 90% shall maintain excess (stack -gas) oxygen concentrations <= 5% by volume on a dry basis over firing rates of 20-100%. Combustion air volume shall be controlled with respect to firing rate or flue gas oxygen concentration. Use of a common gas and combustion air control linkage or jack shaft is prohibited. ■ ■ L Generated Date/Time: Documentation Software: EnergyPro CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: EnergyPro-5889-0524-0173 Report Generated: 2024-05-20 11:15:56 STATE OF CALIFORNIA Domestic Water Heating System CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-PLB-E Project Name: Washington Park Sub Major 5 Suite #02 TI Report Page: (Page 5 of 6) Date Prepared: 5/20/2024 I. DECLARATION OF REQUIRED CERTIFICATES OF INSTALLATION Selections have been made based on information provided in this document. If any selection have been changed by permit applicant, an explanation should be included in Table E. Additional Remarks. These documents must be provided to the building inspector during construction and can be found online Form/Title NRCI-PLB-E - Must be submitted for all buildings J. DECLARATION OF REQUIRED CERTIFICATES OF ACCEPTANCE There are no forms required for this project. K. DECLARATION OF REQUIRED CERTIFICATES OF VERIFICATION There are no forms required for this project. Generated Date/Time: Documentation Software: EnergyPro CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: EnergyPro-5889-0524-0173 Report Generated: 2024-05-20 11:15:56 STATE OF CALIFORNIA Domestic Water Heating System CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-PLB-E Project Name: Washington Park Sub Major 5 Suite #02 TI Report Page: (Page 6 of 6) Project Address: 46630 Washington Street Date Prepared: 5/20/2024 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT I certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Rodolfo Torres, P.E. Documentation Author Signature: 72-'1_„ _ (� Company: RKM Consulting Engineers Signature Date: 2024-05-20 Address: 312 N. 10th Street CEA/ HERS Certification Identification (if applicable): M29983 City/State/Zip: Montebello California 90640-4224 Phone: (818) 261-5704 RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. 2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer) 3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Designer Name: Rodolfo Torres, P.E. Responsible Designer Signature: ZL„ _ _ y — (l/J' Company: RKM Consulting Engineers, Inc. Date Signed: 2024-05-20 Address: 312 N. 10 th Street License: M29983 City/State/Zip: Montebello CA 90640 Phone: (818) 261-5704 Generated Date/Time: Documentation Software: EnergyPro CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: EnergyPro-5889-0524-0173 Report Generated: 2024-05-20 11:15:56 STATE OF CALIFORNIA Indoor Lighting CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-LTI-E This document is used to demonstrate compliance with requirements in 110.9, 110.12(c), 130.0, 130.1, 140.6 and 141.0(b)2 for indoor lighting scopes using the prescriptive path for nonresidential and hotel/motel occupancies. It is also used to document compliance with requirements in 160.5, 170.2(e) and 180.2(b)4 for indoor lighting scopes using the prescriptive path for multifamily occupancies. Multifamily includes dormitory and senior living facilities. Project Name: Y23-154.1 La Quinta Gym Report Page: (Page 1 of 7) Project Address: Date Prepared: 2024-05-24T11:21:57-04:00 A. GENERAL INFORMATION 01 Project Location (city) La Quinta 04 Total Conditioned Floor Area (ft2) 5,716 02 Climate Zone 15 05 Total Unconditioned Floor Area (ft2) 0 03 Occupancy Types Within Project (select all that apply): 06 # of Stories (Habitable Above Grade) 1 • Gymnasium B. PROJECT SCOPE This table includes any lighting systems that are within the scope of the permit application and are demonstrating compliance using the prescriptive path outlined in 140.6/170.2(e) or 141.0(b)2 / 180.2(b)4 for alterations. Scope of Work Conditioned Spaces Unconditioned Spaces 01 02 03 04 05 My Project Consists of (check all that apply): Calculation Method Area (ft2) Calculation Method Area (ft2) 1 New Lighting System Area Category Method 5716 N/A 0 • New Lighting System - Parking Garage N/A 0 N/A 0 Total Area of Work (ft2) 5716 Generated Date/Time: Documentation Software: Energy Code Ace CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: 201339-0524-0002 Report Generated: 2024-05-24 08:22:00 STATE OF CALIFORNIA Indoor Lighting CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-LTI-E Project Name: Y23-154.1 La Quinta Gym Report Page: (Page 2 of 7) Date Prepared: 2024-05-24T11:21:57-04:00 C. COMPLIANCE RESULTS If any cell on this table says "DOES NOT COMPLY" or "COMPLIES with Exceptional Conditions" refer to Table D. for guidance. Lighting in conditioned and unconditioned spaces must not be combined or f compliance per 140.6(b)1 /170.2(e) Allowed Lighting Power per 140.6(b) / 170.2(e (Watts) > Adjusted Lighting Power per 140.6(a) / 170.2(e) (Watts) Compliance Results 01 02 03 04 _ 05 06 07 = 08 09 Complete Building 140.6(c)1 Area Category 140.6(c)2 / 170.2(e)4 Area Category Additional 140.6(c)2G / 170.2(e)4Av ( +) Tailored 140.6(c)3 / 170.2(e)4B (+) Total Allowed (Watts) Total Designed (Watts)*Includes Adjustments Total Adjusted (Watts) Adjustments 05 must be >= 08 140.6 / 170.2(e) PAF Lighting g g Control Credits 140.6(a)2 / 170.2(e)1B (-) (See Table I) (See Table I) (See Table J) (See Table K) (See Table F) (See Table P) Conditioned 2,883.9 = 2,883.9 >_ 2,507 = 2507 COMPLIES Unconditioned = >_ = Controls Compliance (See Table H for Details) COMPLIES Rated Power Reduction Compliance (See Table Q for Details) D. EXCEPTIONAL CONDITIONS This table is auto filled with uneditable comments because of selections made or data entered in tables throughout the form. E. ADDITIONAL REMARKS This table includes remarks made by the permit applicant to the Authority Having Jurisdiction. Generated Date/Time: Documentation Software: Energy Code Ace CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: 201339-0524-0002 Report Generated: 2024-05-24 08:22:00 STATE OF CALIFORNIA Indoor Lighting CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-LTI-E Project Name: Y23-154.1 La Quinta Gym Report Page: (Page 3 of 7) Date Prepared: 2024-05-24T11:21:57-04:00 F. INDOOR LIGHTING FIXTURE SCHEDULE This table includes all planned permanent and portable lighting other than dwelling unit/ hotel/ motel room lighting. Multifamily dwelling unit and hotel/motel room lighting is documented in Table T. If using Table T to document lighting in multifamily common use areas providing shared provisions for living, eating, cooking or sanitation, those luminaires are not included here. Designed Wattage: Conditioned Spaces 01 02 03 04 05 06 07 08 09 10 Name or Item Tag Complete Luminaire Description Modular (Track) Fixture Small Aperture & Color Changer Watts per luminaire2 How is Wattage determined Total Number of Luminaires Excluded per 140.6(a)3 / 170.2(e)2C Design Watts Field Inspector Pass Fail A 8' PENDANT MOUNT LINEAR No NA 79 Mfr. Spec 26 No 2,054 ■ ■ B 6" DOWNLIGHT No NA 34 Mfr. Spec 12 No 408 ■ ■ C 6" DOWNLIGHT No NA 15 Mfr. Spec 3 No 45 ■ ■ Total Designed Watts: CONDITIONED SPACES 2,507 'FOOTNOTE: Design Watts for small aperture and color changing luminaires which qualify per 140.5(a)48 / 170.2(e)2D is adjusted to be 75% /80% of their rated wattage. Table F automatically makes this adjustment, the permit applicant should enter full rated wattage in column 05. 2Authority Having Jurisdiction may ask for Luminaire cut sheets to confirm wattage used for compliance per 130.0(c) / 160.5(b). Wattage used must be the maximum rated for the luminaire, not the lamp. G. MODULAR LIGHTING SYSTEMS This section does not apply to this project. H. INDOOR LIGHTING CONTROLS (Not including PAFs) This table includes lighting controls for conditioned and unconditioned spaces. Building Level Controls 01 02 03 Mandatory Demand Response 110.12(c) Shut-off controls 130.1(c) / 160.5(b)4C Field Inspector Pass Fail NA < 4,000W subject to multilevel See Area/Space Level Controls ■ ■ Generated Date/Time: Documentation Software: Energy Code Ace CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: 201339-0524-0002 Report Generated: 2024-05-24 08:22:00 STATE OF CALIFORNIA Indoor Lighting CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-LTI-E Project Name: Y23-154.1 La Quinta Gym Report Page: (Page 4 of 7) Date Prepared: 2024-05-24T11:21:57-04:00 H. INDOOR LIGHTING CONTROLS (Not including PAFs) Area Level Controls 04 05 06 07 08 09 10 11 12 Area Description Complete Building or Area Category Primary Function Area Manual Area Controls 130.1(a) / 160.5(b)4A Multi -Level Controls 130.1(b) / 160.5(b)4B Shut Off Controls 130.1(c) // 160.5(b)4C Primary/Sky lit Daylighting 130.1(d) / 160.5(b)4D Secondary Daylighting 130.1(d) / 160.5(b)4D Interlocked Systems 140.6(a)1/ 170.2(e)2A Field Inspector Pass Fail GYM Exercise Center Gymnasium Readily Accessible Dimmer Occupancy Sensor NA: General Ltg < 120W NA: General Ltg < 120W No ■ ■ RESTROOMS Restroom Readily Accessible NA: Restrooms Occupancy Sensor NA: Not daylit zone NA: Not daylit zone No ■ ■ HALLWAY Corridor Readily Accessible Dimmer Occupancy Sensor NA: Not daylit zone NA: Not daylit zone No ■ ■ 13 Plan Sheet Showing Daylit Zones: I. LIGHTING POWER ALLOWANCE: COMPLETE BUILDING OR AREA CATEGORY METHODS Each area complying using the Complete Building or Area Category Methods per 140.6(b) are included in this table. Column 06 indicates if additional lighting power allowances per 140.6(c) or adjustments per 140.6(a) are being used . Conditioned Spaces 01 02 03 04 05 06 Area Description Complete Building or Area Category Primary Function Area Allowed Density (W/ft2) Area (ft2) Allowed Wattage (Watts) Additional Allowance / Adjustment Area Category PAF GYM Exercise Center Gymnasium 0.5 5,430 2,715 No No RESTROOMS Restroom 0.65 218 141.7 No No HALLWAY Corridor 0.4 68 27.2 No No TOTALS: 5,716 2,883.9 See Tables J, or P for detail Generated Date/Time: Documentation Software: Energy Code Ace CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: 201339-0524-0002 Report Generated: 2024-05-24 08:22:00 STATE OF CALIFORNIA Indoor Lighting CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-LTI-E Project Name: Y23-154.1 La Quinta Gym Report Page: (Page 5 of 7) Date Prepared: 2024-05-24T11:21:57-04:00 J. ADDITIONAL ALLOWANCE: AREA CATEGORY METHOD QUALIFYING LIGHTING SYSTEM This section does not apply to this project. K. TAILORED METHOD GENERAL LIGHTING POWER ALLOWANCE This section does not apply to this project. L. ADDITIONAL LIGHTING ALLOWANCE: TAILORED WALL DISPLAY This section does not apply to this project. M. ADDITIONAL LIGHTING ALLOWANCE: TAILORED FLOOR AND TASK LIGHTING This section does not apply to this project. N. ADDITIONAL LIGHTING ALLOWANCE: TAILORED DECORATIVE /SPECIAL EFFECTS This section does not apply to this project. O. ADDITIONAL LIGHTING ALLOWANCE: TAILORED VERY VALUABLE MERCHANDISE This section does not apply to this project. P. POWER ADJUSTMENT: LIGHTING CONTROL CREDIT (POWER ADJUSTMENT FACTOR (PAF)) This section does not apply to this project. Q. RATED POWER REDUCTION COMPLIANCE FOR ONE -FOR -ONE ALTERATIONS This section does not apply to this project. Generated Date/Time: Documentation Software: Energy Code Ace CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: 201339-0524-0002 Report Generated: 2024-05-24 08:22:00 STATE OF CALIFORNIA Indoor Lighting CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-LTI-E Project Name: Y23-154.1 La Quinta Gym Report Page: (Page 6 of 7) Date Prepared: 2024-05-24T11:21:57-04:00 R. 80% LIGHTING POWER FOR ALL ALTERATIONS - CONTROLS EXCEPTIONS This section does not apply to this project. S. DAYLIGHT DESIGN POWER ADJUSTMENT FACTOR (PAF) This section does not apply to this project. T. DWELLING UNIT LIGHTING This section does not apply to this project. U. DECLARATION OF REQUIRED CERTIFICATES OF INSTALLATION Selections have been made based on information provided in this document. If any selections have been changed by permit applicant, an explanation should be included in Table E. Additional Remarks. These documents must be provided to the building inspector during construction and can be found online Form/Title NRCI-LTI-E - Must be submitted for all buildings V. DECLARATION OF REQUIRED CERTIFICATES OF ACCEPTANCE Selections have been made based on information provided in this document. If any selections have been changed by the permit applicant, an explanation should be included in Table E. Additional Remarks. These documents must be provided to the building inspector during construction and any with "-A" in the form name must be completed through an Acceptance Test Technician Certification Provider (ATTCP). For more information visit: http://www.energy.ca.gov/title24/attcp/providers.html Form/Title Systems/Spaces To Be Field Verified NRCA-LTI-02-A - Must be submitted for occupancy sensors and automatic time switch controls. GYM; RESTROOMS; HALLWAY Generated Date/Time: Documentation Software: Energy Code Ace CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: 201339-0524-0002 Report Generated: 2024-05-24 08:22:00 STATE OF CALIFORNIA Indoor Lighting CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-LTI-E Project Name: Y23-154.1 La Quinta Gym Report Page: (Page 7 of 7) Project Address: Date Prepared: 2024-05-24T11:21:57-04:00 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT I certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Pacific Engineering Documentation Author Signature: Company: Pacific Engineering Group Signature Date: 2024-05-24 Address: 1106 W. MAGNOLIA BLVD. CEA/ HERS Certification Identification (if applicable): City/State/Zip: BURBANK CA 91506 Phone: RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. 2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer) 3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occu ncy. Responsible Designer Name: MEL ANTHONY FAJARDO Responsible Designer Signature: �� Company: PACIFIC ENGINEERS GROUP Date Signed: 2024-05-24 / Address: 1106 W. MAGNOLIA BLVD. License: City/State/Zip: BURBANK CA 91506 Phone: Generated Date/Time: Documentation Software: Energy Code Ace CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000 Schema Version: rev 20220101 Compliance ID: 201339-0524-0002 Report Generated: 2024-05-24 08:22:00