HomeMy WebLinkAboutBCOM2024-0127 Title 24BUILDING ENERGY ANALYSIS REPORT
PROJECT:
Washington Park Sub Major 5 Suite #02 TI
46630 Washington Street
La Quinta, CA 92253
Project Designer:
MOA Architects, Inc.
14467 Park Avenue
Victorville, Ca 92392
(760) 241-7858
Report Prepared by:
Rodolfo Torres, P.E.
RKM Consulting Engineers
312 N. 10th Street
Montebello, California 90640-4224
(818) 261-5704
Job Number:
2404-3
Date:
5/20/2024
BCOM2024-0127
CITY OF LA QUINTA
BUILDING DIVISION
REVIEWED FOR
CODE
COMPLIANCE
DATE09/24/2024 Br
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2022 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC — www.energysoft.com.
i
TABLE OF CONTENTS
Cover Page 1
Table of Contents 2
Form NRCC-MCH-E Mechanical Systems 3
Form NRCC-PLB-E Domestic Water Heating System 14
STATE OF CALIFORNIA
Mechanical Systems
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-E
This document is used to demonstrate compliance for mechanical systems that are within the scope of the permit application and are demonstrating compliance using the prescriptive
path outlined in 140.4, or 141.0(b)2 for alterations.
Project Name: Washington Park Sub Major 5 Suite #02 TI
Report Page: (Page 1 of 11)
Project Address: 46630 Washington Street
Date Prepared: 5/20/2024
A. GENERAL INFORMATION
01
Project Location (city)
La Quinta
04
Total Conditioned Floor Area
5818
02
Climate Zone
15
05
Total Unconditioned Floor Area
0
03
Occupancy Types Within Project:
06
# of Stories (Habitable Above Grade)
1
• Gymnasium
B. PROJECT SCOPE
This table Includes mechanical systems or components that are within the scope of the permit application and are demonstrating compliance using the prescriptive path outlined in
140.4, 170.2(b) or 141.0(b)2 and 180.2(b)2 for alterations.
01
02
03
Air System(s)
Wet System Components
Dry System Components
1 Heating Air System
• Water Economizer
0 Air Economizer
A Cooling Air System
• Pumps
• Electric Resistance Heat
Mechanical Controls
• System Piping
0 Fan Systems
Controls (existing to remain, altered
• Cooling Towers
AMechanical
0 Ductwork (existing to remain, altered or new)
or new)
• Chillers
0 Ventilation
• Boilers
• Zonal Systems/ Terminal Boxes
Generated Date/Time:
Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-5889-0524-0174
Report Generated: 2024-05-20 11:15:56
STATE OF CALIFORNIA
Mechanical Systems
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-MCH-E
Project Name: Washington Park Sub Major 5 Suite #02 TI
Report Page:
(Page 2 of 11)
Date Prepared:
5/20/2024
C. COMPLIANCE RESULTS
Table C will indicate if the project data input into the compliance document is compliant with mechanical requirements. This table is not editable by the user. If this table says "DOES
NOT COMPLY" or "COMPLIES with Exceptional Conditions" refer to Table D., or the table indicated as not compliant for guidance.
01
AND
02
AND
03
AND
04
AND
05
AND
06
AND
07
AND
08
09
System
Summary
110.1,
110.2,
140.4,
170.2(c)
Pumps
140.4(k),
170.2(c)41
Fans/
Economizers
140.4(c),
140.4(e),
170.2(c)
System
Controls
110.2, 120.2,
140.4(f),
170.2(c)
Ventilation
120.1, 160.2
Terminal Box
Controls
140.4(d),
170.2(c)4B
Distribution
120.3,
140.4(1),
160.2, 160.3
Cooling Towers
110.2(e)2
Compliance Results
(See Table F)
(See Table G)
(See Table H)
(See Table I)
(See Table J)
(See Table K)
(See Table L)
(See Table M)
Yes
AND
AND
Yes
AND
Yes
AND
Yes
AND
AND
Yes
AND
COMPLIES
Mandatory Measures Compliance (See Table Q for Details)
COMPLIES
D. EXCEPTIONAL CONDITIONS
This table is auto filled with uneditable comments because of selections made or data entered in tables throughout the form.
E. ADDITIONAL REMARKS
This table includes remarks made by the permit applicant to the Authority Having Jurisdiction.
F. HVAC SYSTEM SUMMARY (DRY & WET SYSTEMS)
Space Conditioning System Information
01
02
03
04
05
06
System Name
Quantity
System Serving
System Status
Space Type
Utilizing Recovered Heat
Carrier 10-Ton Package Unit
4
Single zone
New/ Addition
■
Generated Date/Time:
Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-5889-0524-0174
Report Generated: 2024-05-20 11:15:56
STATE OF CALIFORNIA
Mechanical Systems
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-MCH-E
Project Name: Washington Park Sub Major 5 Suite #02 TI
Report Page:
(Page 3 of 11)
Date Prepared:
5/20/2024
F. HVAC SYSTEM SUMMARY (DRY & WET SYSTEMS)
Dry System Equipment Sizing (includes air conditioners, condensers, heat pumps, VRF, furnaces and unit heaters and DOAS systems)
01
02
03
04
05
06
07
08
09
10
11
Name or Item
Tag
Equipment Category per
Tables 110.2, 140.4(a)2 and
170.2(c)3aii
Equipment Type per Tables 110.2 and
Title 20
Smallest Size
Available'Total
140.4(a) and
170.2(c)1
Equipment Sizing per Mechanical Schedule (kBtu/h)
140.4(a&b) 170.2(c)1 & 170.2(c)2
Heating Output2'3
Cooling Output2'3
Load Calculations3,4
Per Design
(kBtu/h)
Rated
(kBtu/h)
Supp.
Heating
Output
(kBtu/h)
Sensible
Per Design
(kBtu/h)
Rated
(kBtu/h)
Total
Heating
Load
(kBtu/h)
Sensible
Cooling
Load
(kBtu/h)
Carrier 10 Ton
Package Unit
Unitary Heat Pumps
Air-cooled, pkg (3 phase)
NA: Load
Controls
287.3
115
0
284.33
76.35
171.63
289.68
1FOOTNOTES: Equipment shall be the smallest size, within the available options of the desired equipment line, necessary to meet the design heating and cooling loads of the building per
140.4(a) and 170.2(c)1. Healthcare facilities are excepted.
21t is common practice to show rated output capacity on the equipment schedule. Sensible cooling output comes from specification sheet tables.
If equipment is heating only, leave cooling output and load blank. If equipment is cooling only, leave heating output and load blank.
4 Authority Having Jurisdiction may ask for load calculations used for compliance per 140.4(b) and 170.2(c).
Dry System Equipment Efficiency (other than Package Terminal Air Conditioners (PTAC) and Package Terminal Heat Pumps (PTHP), DX-DOAS and Dual Fuel Heat Pumps)
01
02
03
04
05
06
07
08
09
Heating Mode
Cooling Mode
Minimum
Minimum
Name or Item
Size Category
Rating
Efficiency
Efficiency
Tag
(Btu/h)
Condition
Efficiency Unit
Required per
Design Efficiency
Efficiency Unit
Required per
Design Efficiency
( °F)
Tables 110.2 /
Tables 110.2 /
Title 20
Title 20
Carrier 10 Ton
Package Unit
>=65,000 and <135,000
COP
3.4
3.4
EER
IEER
11
14.1
11
15
G. PUMPS
This section does not apply to this project.
Generated Date/Time:
Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance
Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-5889-0524-0174
Report Generated: 2024-05-20 11:15:56
STATE OF CALIFORNIA
Mechanical Systems
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-MCH-E
Project Name: Washington Park Sub Major 5 Suite #02 TI
Report Page:
(Page 4 of 11)
Date Prepared:
5/20/2024
H. FAN SYSTEMS & AIR ECONOMIZERS
This table is used to demonstrate compliance with prescriptive requirements found in 140.4(c), 140.4(e), 140.4(m), 170.2(c)3, and 170.2(c)4A for fan systems. Fan systems serving only
process loads are exempt from these requirements and do not need to be included in Table H.
System
Name
Carrier
10-Ton
Package
Unit
Quantit
y
4
Fan System
Status
New
System
Zoning
all other
systems
Serving
Dwelling
Units
Not
Serving
Dwelling
Units
Fan
System
Airflow
(cfm)
16,000
Site
Elevation
400
Economizer
Differential
Enthalpy
01
02
03
04
05
06
07
08
09
10
11
Fan
Name
or Item
Tag
Fan Type
Qty
Component
Airflow through
Component (%)
Water
Gauge
(w.g)
Allowance
Design
Compone
nt
Allowance
Fan
Allowance
(watt/cfm)3
Design Electrical Input Power
Method
Motor
Nameplate
Horsepower
Design
Electrical
Input
Power (kW)
SF
Supply
4
Base Allowance for system serving
spaces <=6 floors away
4,000
928
Manufacturer provided
1.73
MERV 13-16 Filter upstream of
thermal conditioning equipment
4,000
556
Hydronic/DX cooling coil or heat
pump coil
4,000
556
Economizer Return Damper
4,000
184
Supply Fan Base
Allowance (kW)
Exhuast/Return/Relief/Transfer Fan Base
Allowance(kW)
Fan System
Allowance (kW)3
8.9
Fan System Electrical
Output (kW)
6'9
1 FOOTNOTES: Fans serving spaces with design background noise goals below NC35
2 Low -turndown single -zone VAV fan system must be capable of and configured to reduce airflow to 50 percent of
design airflow and use no more than 30 percent of the design wattage at that airflow. No more than 10 percent of the
design load served by the equipment shall have fixed loads.
3 Fan system allowance includes fan system base allowance.
4 Filter pressure loss can only be counted once per fan system.
s Complex Fan System means a fan system that combines a single cabinet fan system with other supply fans, exhaust
fans, or both.
6 Computer room economizers must meet requirements of 140.9(a) and will be documented on the NRCC-PRC-E
document..
Generated Date/Time:
Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-5889-0524-0174
Report Generated: 2024-05-20 11:15:56
STATE OF CALIFORNIA
Mechanical Systems
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-MCH-E
Project Name: Washington Park Sub Major 5 Suite #02 TI
Report Page:
(Page 5 of 11)
Date Prepared:
5/20/2024
H. EXHAUST AIR HEAT RECOVERY 140.4(q), 170.2(c)40
01
02
03
04
05
06
07
08
09
10
11
Fan System
Name
Qty
Hours of
Operation per
Year
Design Supply
Airflow Rate
Outdoor
Airflow
%Outdoor Air
at Full Design
Airflow
Exemptions to
Exhaust Air
Heat Recovery
Requirement
per 140.4(q) &
170.2(c)40
Exhaust Air
Heat Recovery
140.4(q) &
170.2(c)40
Type Of Heat
Recovery Rating
Required
Recovery Ratio
Energy
Recovery
Bypass
Fan Energy Index (FEI)
01
02
03
Name or Item Tag
FEI Exception
FEI
Carrier 10-Ton Package Unit
None Applies
1
I. SYSTEM CONTROLS
This table is used to demonstrate compliance with mandatory controls in 110.2 and 120.2 and prescriptive controls in 140.4(f) and (n), 170.2(c)4D 170.2(c)4L or requirements in
141.0(b)2E 180.2(b)2 for altered space conditioning systems.
01
02
03
04
05
06
07
08
09
System Name
System
Zoning
Conditioned
Floor Area
Being Served
(ft2)
Thermostats
110.2(b) & (c)1, 120.2(a)
160.3(a)2A or 141.0(b)2E &
180.2(b)2
Shut -Off
Controls
120.2(e) &
160.3(a)2D
Isolation
Zone
Controls
120.2(g) &
160.3(a)2F
Demand Response
110.12 120.2(b) &
160.3(a)2B
Supply Air
Temp. Reset
140.4(f) &
170.2(c)4D
Window Interlocks per
140.4(n) & 170.2(c)4D
Carrier 10-Ton Package
Unit
Single zone
<= 25,000 ft2
Setback
Auto Timer
Switch
4 Hour Timer
EMCS
NA: Would
increase
energy use
Provided
'FOOTNOTES: Gravity gas wall heaters, gravity floor heaters, gravity room heaters, non -central electric heaters, fireplaces or decorative gas appliances, wood stoves are not required to
have setback thermostats.
Generated Date/Time:
Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-5889-0524-0174
Report Generated: 2024-05-20 11:15:56
STATE OF CALIFORNIA
Mechanical Systems
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-MCH-E
Project Name: Washington Park Sub Major 5 Suite #02 TI
Report Page:
(Page 6 of 11)
Date Prepared:
5/20/2024
J. VENTILATION AND INDOOR AIR QUALITY
This table is used to demonstrate compliance with mandatory ventilation requirements in 120.1 120.2(e)36140.4(p) and 140.4(q) for all nonresidential and hotel/motel and
d:t24refnolink/1160.2, 160.3(a)3D, 170.2(a)4N, 170.2(a)40 for high-rise residential occupancies. For alterations, only ventilation systems being altered within the scope of the permit
application need to be documented in this table. In lieu of this table, the required outdoor ventilation rates and airflows may be shown on the plans or the calculations can be presented
in a spreadsheet.
01
■
Check the box if the project is showing ventilation calculations on the plans, or attaching the calculations instead of completing this table.
02
L
Check this box if the project included Nonresidential, Hotel/Motel Spaces or Multifamily Common Use Spaces
■
03
■
Check the box if the project is using natural ventilation in any nonresidential or hotel/motel spaces to meet required ventilation rates per 120.1(c)2.
Nonresidential and Hotel/ Motel Multifamily Common Use Ventilation Systems
04
05
06
07
System Name
Carrier 10-Ton Package Unit
System Design OA CFM
Airflow
600
System Design
Transfer Air CFM
0
Air Filtration per 120.1(c) 141.0(b)2 and
160.2(c)212
Provided
08
09
10
11
12
13
14
15
16
Space Name
or Item Tag
3
Mechanical Ventilation Required per 120.1(c)3 & 160.2(c)3
Exh. Vent per 120.1(c)4 &
c 160.2 4
()
DCV or Sensor Controls per 120.1(d)3,
120.1(d)5, and 120.1(e)36 160.2(c)5D
160.2(c)5E 160.2(c)5D
Occupancy Type4
Conditioned
Floor Area
(ft2)
# of Shower
heads/
toilets
# of
people s
Required
Min OA
CFM
Required
Min CFM
Provided per Design
CFM
Zone 1
Gym/ sports arena (play area)
5818
40
600
0
600
DCV
NA: Not required per
§120.1(d)3
NA: Not required
space type
Occ Sensor
17
Total System Required Min OA CFM
600
18
Ventilation for this System Complies?
Yes
1 FOOTNOTES: System CFM should include both mechanical and natural ventilation for the zone/system
2 Air filtration requirements apply to the following three system types per 120.1(c)1A: space conditioning systems utilizing ducts to supply air to occupiable space; supply -only ventilation
systems providing outside air to occupiable space; supply side of balanced ventilation systems including heat recovery and energy recovery ventilation systems providing outside air to
occupiable space.
3 Uniform Mechanical Code may have more stringent ventilation requirements; the most stringent code requirement takes precedence.
See Standards Tables 120.1-A and 120.1-B.
Generated Date/Time:
Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-5889-0524-0174
Report Generated: 2024-05-20 11:15:56
STATE OF CALIFORNIA
Mechanical Systems
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-MCH-E
Project Name: Washington Park Sub Major 5 Suite #02 TI
Report Page:
(Page 7 of 11)
Date Prepared:
5/20/2024
J. VENTILATION AND INDOOR AIR QUALITY
5 For lecture halls with fixed seating, the expected number of occupants shall be determined in accordance with the California Building Code.
6 120.2(e)3 requires systems serving rooms that are required by 130.1(c) to have lighting occupancy sensing controls to also have occupancy sensing zone controls for ventilation.
Examples of spaces which require lighting occupancy sensors include offices 250ft2 or smaller, multipurpose rooms less than 1,000 ft2, classrooms, conference rooms, restrooms, aisles
and open areas in warehouses, library book stack aisles, corridors, stairwells, parking garages, and loading and unloading zones, unless excepted by 130.1(c).
K. TERMINAL BOX CONTROLS
This section does not apply to this project.
L. DISTRIBUTION (DUCTWORK and PIPING)
This table is used to show compliance with mandatory pipe insulation requirements found in 120.3 and mandatory requirements found in 120.4(g) for duct sealing.
01
Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind. Insulation exposed to
weather shall be installed with a cover suitable for outdoor service. Insulation covering chilled water piping and refrigerant suction piping located
outside the conditioned space shall have a Class I or Class II vapor retarder. All penetrations and joints of which shall be sealed.
■
Duct Leakage Testing
The answers to the questions below apply to the following duct systems:
1
NR/ Common Use: Duct leakage testing shall not exceed 6% per
NA7.5.3 required for these systems?
No
Generated Date/Time:
Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-5889-0524-0174
Report Generated: 2024-05-20 11:15:56
STATE OF CALIFORNIA
Mechanical Systems
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-MCH-E
Project Name: Washington Park Sub Major 5 Suite #02 TI
Report Page:
(Page 8 of 11)
Date Prepared:
5/20/2024
L. DISTRIBUTION (DUCTWORK and PIPING)
Carrier
10-Ton
Package Unit
Dwelling Units: Total duct leakage of duct system shall not exceed 12%
or duct system to outside shall not exceed 6% per RA3.1.4 required for
systems?
No
Duct leakage testing per CMC Section 603.10.1 required for these
systems?
Yes
11
No
The scope of the project includes only duct systems serving healthcare facilities
12
Yes
Duct system provides conditioned air to an occupiable space for a constant volume, single zone, space -conditioning system.
13
No
The space conditioning system serves less than 5,000 ft2 of conditioned floor area.
14
No
The combined surface area of the ducts is more than 25% of the total surface area of the entire duct system:
15
'The
scope of the project includes extending an existing duct system, which is constructed, insulated or sealed with asbestos.
16
No
The scope of the project includes an existing duct system that is documented to have been previously sealed as confirmed through field verification
and diagnostic testing in accordance with procedures in the Reference Nonresidential Appendix NA2.
17
All Ductwork and plenums with pressure class ratings shall be constructed to Seal Class A
18
All ductwork is an extension of an existing duct system
19
Ductwork serving individual dwelling unit
20
< 25 ft of new or replacement space conditioning ducts installed
21
R-8
Duct Insulation R-value
22
23
M. COOLING TOWERS
This section does not apply to this project.
Generated Date/Time:
Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-5889-0524-0174
Report Generated: 2024-05-20 11:15:56
STATE OF CALIFORNIA
Mechanical Systems
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-MCH-E
Project Name: Washington Park Sub Major 5 Suite #02 TI
Report Page:
(Page 9 of 11)
Date Prepared:
5/20/2024
N. DECLARATION OF REQUIRED CERTIFICATES OF INSTALLATION
Selections have been made based on information provided in previous tables of this document. If any selection needs to be changed, please explain why in Table E Additional Remarks.
These documents must be provided to the building inspector during construction and can be found online at
https://www.energy.ca.gov/title24/2019standards/2019_compliance_documents/Nonresidential Documents/NRCl/
Form/Title
NRCI-MCH-01-E - Must be submitted for all buildings
O. DECLARATION OF REQUIRED CERTIFICATES OF ACCEPTANCE
Selections have been made based on information provided in previous tables of this document. If any selection needs to be changed, please explain why in Table E Additional Remarks.
These documents must be provided to the building inspector during construction and can be found online at
https://www. energy.ca.gov/title24/2019standards/2019 compliance_documents/Nonresidential Documents/NRCA/
Form/Title
Systems/Spaces To Be Field
Verified
NRCA-MCH-02-A - Outdoor Air must be submitted for all newly installed HVAC units. Note: MCH-02-A can be performed in conjunction with MCH-07-A
Supply Fan VFD Acceptance (if applicable) since testing activities overlap.
Carrier
50FCQM12A2A5-OA6A0;
NRCA-MCH-03-A - Constant Volume Single Zone HVAC NOTE: This form does not automatically move to "Yes'. If Constant Volume Single Zone HVAC
Systems are included in the scope, permit applicant should move this form to "Yes".
Carrier
50FCQM12A2A5-OA6A0;
NRCA-MCH-05-A - Air Economizer Controls
Carrier
50FCQM12A2A5-OA6A0;
NRCA-MCH-11-A Automatic Demand Shed Controls
Carrier
50FCQM12A2A5-OA6A0;
NRCA-MCH-12-A FDD for Packaged Direct Expansion Units
Carrier
50FCQM12A2A5-OA6A0;
NRCA-MCH-16-A Supply Air Temperature Reset Controls
Carrier
50FCQM 12A2A5-OA6A0;
NRCA-MCH-18-A Energy Management Control Systems
Carrier
50FCQM 12A2A5-OA6A0;
Generated Date/Time:
Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-5889-0524-0174
Report Generated: 2024-05-20 11:15:56
STATE OF CALIFORNIA
Mechanical Systems
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-MCH-E
Project Name: Washington Park Sub Major 5 Suite #02 TI
Report Page:
(Page 10 of 11)
Date Prepared:
5/20/2024
P. DECLARATION OF REQUIRED CERTIFICATES OF VERIFICATION
There are no NRCV forms required for this project.
Q. MANDATORY MEASURES DOCUMENTATION LOCATION
This table is used to indicate where mandatory measures are documented in the plan set or construction documentation.
01
02
Compliance with Mandatory Measures documented through MCH
Mandatory Measures Note Block
Yes
Plan sheet or construction document location
M-Sheets
Generated Date/Time:
Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-5889-0524-0174
Report Generated: 2024-05-20 11:15:56
STATE OF CALIFORNIA
Mechanical Systems
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-MCH-E
Project Name:
Washington Park Sub Major 5 Suite #02 TI
Report Page:
(Page 11 of 11)
Project Address:
46630 Washington Street
Date Prepared:
5/20/2024
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Rodolfo Torres, P.E.
Documentation Author Signature: 7-2-' _ _ "^ —
(tea
Company:
RKM Consulting Engineers
Signature Date:
2024-05-20
Address:
312 N. 10th Street
CEA/ HERS Certification Identification (if applicable):
M29983
City/State/Zip:
Montebello California 90640-4224
Phone:
(818) 261-5704
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer)
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements
of Title 24, Part 1 and Part 6 of the California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations,
plans and specifications submitted to the enforcement agency for approval with this building permit application.
5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable
inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy.
Responsible Designer Name:
Rodolfo Torres, P.E.
Responsible Designer Signature: jZ„_
'�`" �(�
Company:
RKM Consulting Engineers, Inc.
Date Signed:
2024-05-20
Address:
312 N. 10 th Street
License:
M29983
City/State/Zip:
Montebello CA 90640
Phone:
(818) 261-5704
Generated Date/Time:
Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-5889-0524-0174
Report Generated: 2024-05-20 11:15:56
STATE OF CALIFORNIA
Domestic Water Heating System
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-PLB-E
This document is used to demonstrate compliance for nonresidential occupancies with requirements in 110.1, 110.3, 120.3, and 140.5, and with requirements in 141.0 for additions and
alterations, for domestic water heating scopes using the prescriptive path. For high-rise residential and hotel/motel occupancies compliance is demonstrated with requirements in
110.1, 110.3, 160.4 and 170.2(d), and with requirements 180.1 for additions and 180.2 for alterations.
Project Name: Washington Park Sub Major 5 Suite #02 TI
Report Page: (Page 1 of 6)
Project Address: 46630 Washington Street
Date Prepared: 5/20/2024
A. GENERAL INFORMATION
01
Project Location (city) La Quinta
02
Climate Zone
15
03
Occupancy Types Within Project (select all that apply):
• Gymnasium
B. PROJECT SCOPE
This table includes domestic water heating systems that are within the scope of the permit application and are demonstrating compliance using the prescriptive paths outlined in 140./
170.2(d) and 141.0(a)/ 180.1, or 141.0(b)2N / 180.2 for additions or alterations. Solar water heating systems are documented on the NRCC-SAB compliance document. Combined
hydronic water heating systems are documented on the NRCC-MCH compliance document.
01
02
03
My project consists of (check all that apply):
System Type1'2
System Components
0 New system (DHW system being installed for the first time)
Individual System (serving nonresidential spaces)
A Equipment
L Distribution
0 Controls
• System Alteration (equipment, distribution or controls)
• Equipment
• Distribution
• Controls
'FOOTNOTES: Point of use water heaters, or other non -central systems used to serve nonresidential spaces, are considered individual systems.
2 Dwelling units refers to hotel/motel guest rooms and units in a multifamily residential occupancy.
3 DHW systems serving 2 or more dwelling units are considered "Central Systems" for multifamily occupancies
C. COMPLIANCE RESULTS
Table C will indicate if the project data input into the compliance document is compliant with water heating requirements. If this table says "DOES NOT COMPLY" or "COMPLIES with
Exceptional Conditions" refer to Table D. or the table indicated as not compliant for guidance.
01
02
03
04
Domestic Hot Water Equipment
Distribution Systems
Controls
Compliance Results
Table F
Table G
Table H
Yes
Yes
Yes
COMPLIES
D. EXCEPTIONAL CONDITIONS
This table is auto filled with uneditable comments because of selections made or data entered in tables throughout the form.
Generated Date/Time:
Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance
Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-5889-0524-0173
Report Generated: 2024-05-20 11:15:56
STATE OF CALIFORNIA
Domestic Water Heating System
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-PLB-E
Project Name: Washington Park Sub Major 5 Suite #02 TI
Report Page:
(Page 2 of 6)
Date Prepared:
5/20/2024
E. ADDITIONAL REMARKS
This table includes remarks made by the permit applicant to the Authority Having Jurisdiction.
F. DOMESTIC HOT WATER EQUIPMENT
This table is used to demonstrate compliance with mandatory equipment requirements in 110.1 and 110.3. Compliance with prescriptive requirements in 140.5(c)/170.2(d) must also
be demonstrated and with 141.0 / 180.1/ 180.2 for addition and alteration scopes.
Equipment Schedule: Water Heating Efficiency and Standby Loss
03
04
05
06
System
Name
AO Smith DEL 6S 2
Exception to 140.5(c)/
170.2(d)3
Gas Service
Water Heating
System >=
1MMBtu/h1
Capacity -weighted
Average Efficiency %
•
07
08
09
10
11
12
13
14
15
Name or
Item Tag
Equipment Type
Volume
(gal)
Rated Input
Capacity
(Btu/h)
Max GPM/ First
Hour Rating
(FHR)
Rated
Efficiency
Minimum
Efficiency
Required
Efficiency Unit
Designed Standby Loss
Maximum Standby
Loss
AO Smith
DEL-6S-2
Consumer Rated
Electric Storage
50
20,473
0 <= FHR <18
0.93
0.93
UEF
1FOOTNOTE: In systems >= 1MMBtu/h with multiple units gas water heaters with input capacity > 100,000 Btu/h may meet 90% Et requirements via an input capacity -weighted
average.
Water Heating Equipment All Occupancies
Yes
No
Not
Applicable
Requirement
18
■
■
►1
Unfired storage tank insulation shall have Internal + External >=R-16 OR External >=R-3.5. Label required per 110.3(c)3
19
■
■
1/
New state buildings 60% of energy for service water heating from site solar energy or recovered energy per 110.3(c)5
20
■
■
►1
Isolation valves for instantaneous water heater with input rating >6.8 kBTUH or 2 kW has been specified per 110.3(c)6
21
School buildings < 25,000 ft2 and < 4 stories must install a heat pump water heating system per 140.5(a)1. Water heating
systems serving an individual bathroom space may be an instantaneous electric water heater.
Generated Date/Time:
Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-5889-0524-0173
Report Generated: 2024-05-20 11:15:56
STATE OF CALIFORNIA
Domestic Water Heating System
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-PLB-E
Project Name: Washington Park Sub Major 5 Suite #02 TI
Report Page:
(Page 3 of 6)
Date Prepared:
5/20/2024
G. DOMESTIC HOT WATER DISTRIBUTION SYSTEM
This table is used to demonstrate compliance for nonresidential occupancies with distribution requirements in 120.3 and 140.5. For multifamily and hotel/motel occupancies,
compliance is demonstrated with requirements 110.3(c), 160.4, 170.2(d).
Mandatory Pipe Insulation All Occupancies
13•
For systems serving dwelling units, pipe insulation must meet the minimum insulation requirements in Table 160.4-A (see blow) except:
• Piping that penetrates framing members shall not be required to have pipe insulation for the distance of the framing penetration. Piping that
penetrates metal framing shall use grommets, plugs, wrapping or other insulating material to assure that no contact is made with the metal framing.
Insulation shall abut securely against all framing members
• Piping installed in interior or exterior walls shall not be required to have pipe insulation if all of the requirements are met for compliance with Quality
Insulation Installation (QII) as specified in the Reference Residential Appendix RA3.5.
• Piping surrounded with a minimum of 1 inch of wall insulation, 2 inches of crawlspace insulation, or 4 inches of attic insulation, shall not be required to
have pipe insulation.
14
@
For systems serving nonresidential spaces, pipe insulation for the following applications is specified to comply with Table 120.3-A (see below) per 120.3:
• Recirculating system piping, including supply and return piping of the water heater
• The first 8 ft of hot and cold outlet piping, including between storage tank and heat trap, for a nonrecirculating storage system
• Pipes that are externally heated
15
■
Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind. Insulation exposed to weather shall
be installed with a cover suitable for outdoor service per 120.3(b) / 160.4(f). Pipe insulation buried below grade must be installed in a water proof and
non -crushable casing or sleeve.
TABLE 120.3-A / 160.4-A PIPE INSULATION THICKNESS
Fluid Temperature Range ( °F)
Conductivity
Range (Btu -in
per hour per ft2
per °F)
Insulation Mean Rating Temp (
°F)
Nominal Pipe Diameter (in)
< 1
1 to < 1.5
1.5 to < 4
1.5 to < 4 Multifamily &
Hotel/Motel
Minimum Insulation Required
105-140
0.22 - 0.28
100
1.0 in or R-7.7
1.5 in or R-12.5
1.5 in or R-11
2.0 in or R-16
Generated Date/Time:
Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-5889-0524-0173
Report Generated: 2024-05-20 11:15:56
STATE OF CALIFORNIA
Domestic Water Heating System
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-PLB-E
Project Name: Washington Park Sub Major 5 Suite #02 TI
Report Page:
(Page 4 of 6)
Date Prepared:
5/20/2024
H. DOMESTIC HOT WATER CONTROLS
This table is used to demonstrate compliance with control requirements in 110.3 for all occupancies. For multifamily residential and hotel/motel occupancies, compliance is also
demonstrated with requirements in 160.4(e)/170.2(d)
Yes
No
Not
Applicable
Requirement
01
Construction documents require manufacturer certification that service water -heating systems are equipped with automatic
temperature controls capable of adjusting temperature settings per 110.3(a).
A
■
■
02
Systems with capacity > 167,000 BTUH equipped with outlet temperature controls per 110.3(c)1 unless covered by California
Plumbing Code 613.0.
■
■
r
03
Controls for circulating pumps or electrical heat trace systems are capable of automatically turning off the system per
§110.3(c)2 unless systems serves healthcare facility.
■
■
L
04
For recirculation systems serving multiple dwelling units, design includes automatic pump controls per 170.2(d) or 180.1(b)3 for
additions.
■
■
@
05
For recirculation systems serving individual dwelling units, design includes manual on/off controls as specified in Reference
Appendix RA4.4.9 per 170.2(d).
■
■
06
Combustion air positive shut-off shall be provided per 160.4(3).on all newly installed commercial boilers as follows:
Boilers with input capacity >= 2.5 MMBtu/h, in which the boiler is designed to operate with a nonpositive vent static
pressure
• Boilers where one stack serves two or more boilers with a total combined input capacity per stack of 2.5 MMBtu/h.
■
■
••
07
Boiler combustion air fans with motor >= 10 hp shall meet one of the following
• The fan motor shall be driven by a variable speed drive OR
• The fan motor shall include controls that limit the fan motor demand to <=30% of the total design wattage at 50% of the
design air volume.
•
•
r
08
Newly installed boilers with an input capacity {d:gte/] 5MMBtu/h and a steady state full -load combustion efficiency < 90% shall
maintain excess (stack -gas) oxygen concentrations <= 5% by volume on a dry basis over firing rates of 20-100%. Combustion air
volume shall be controlled with respect to firing rate or flue gas oxygen concentration. Use of a common gas and combustion air
control linkage or jack shaft is prohibited.
■
■
L
Generated Date/Time:
Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-5889-0524-0173
Report Generated: 2024-05-20 11:15:56
STATE OF CALIFORNIA
Domestic Water Heating System
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-PLB-E
Project Name: Washington Park Sub Major 5 Suite #02 TI
Report Page:
(Page 5 of 6)
Date Prepared:
5/20/2024
I. DECLARATION OF REQUIRED CERTIFICATES OF INSTALLATION
Selections have been made based on information provided in this document. If any selection have been changed by permit applicant, an explanation should be included in Table E.
Additional Remarks. These documents must be provided to the building inspector during construction and can be found online
Form/Title
NRCI-PLB-E - Must be submitted for all buildings
J. DECLARATION OF REQUIRED CERTIFICATES OF ACCEPTANCE
There are no forms required for this project.
K. DECLARATION OF REQUIRED CERTIFICATES OF VERIFICATION
There are no forms required for this project.
Generated Date/Time:
Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-5889-0524-0173
Report Generated: 2024-05-20 11:15:56
STATE OF CALIFORNIA
Domestic Water Heating System
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-PLB-E
Project Name:
Washington Park Sub Major 5 Suite #02 TI
Report Page:
(Page 6 of 6)
Project Address:
46630 Washington Street
Date Prepared:
5/20/2024
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Rodolfo Torres, P.E.
Documentation Author Signature: 72-'1_„ _
(�
Company:
RKM Consulting Engineers
Signature Date:
2024-05-20
Address:
312 N. 10th Street
CEA/ HERS Certification Identification (if applicable):
M29983
City/State/Zip:
Montebello California 90640-4224
Phone:
(818) 261-5704
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer)
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements
of Title 24, Part 1 and Part 6 of the California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations,
plans and specifications submitted to the enforcement agency for approval with this building permit application.
5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable
inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy.
Responsible Designer Name:
Rodolfo Torres, P.E.
Responsible Designer Signature: ZL„ _ _ y —
(l/J'
Company:
RKM Consulting Engineers, Inc.
Date Signed:
2024-05-20
Address:
312 N. 10 th Street
License:
M29983
City/State/Zip:
Montebello CA 90640
Phone:
(818) 261-5704
Generated Date/Time:
Documentation Software: EnergyPro
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: EnergyPro-5889-0524-0173
Report Generated: 2024-05-20 11:15:56
STATE OF CALIFORNIA
Indoor Lighting
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-LTI-E
This document is used to demonstrate compliance with requirements in 110.9, 110.12(c), 130.0, 130.1, 140.6 and 141.0(b)2 for indoor lighting scopes using the prescriptive path for
nonresidential and hotel/motel occupancies. It is also used to document compliance with requirements in 160.5, 170.2(e) and 180.2(b)4 for indoor lighting scopes using the prescriptive
path for multifamily occupancies. Multifamily includes dormitory and senior living facilities.
Project Name: Y23-154.1 La Quinta Gym
Report Page: (Page 1 of 7)
Project Address:
Date Prepared: 2024-05-24T11:21:57-04:00
A. GENERAL INFORMATION
01
Project Location (city)
La Quinta
04
Total Conditioned Floor Area (ft2)
5,716
02
Climate Zone
15
05
Total Unconditioned Floor Area (ft2)
0
03
Occupancy Types Within Project (select all that apply):
06
# of Stories (Habitable Above Grade)
1
• Gymnasium
B. PROJECT SCOPE
This table includes any lighting systems that are within the scope of the permit application and are demonstrating compliance using the prescriptive path outlined in 140.6/170.2(e) or
141.0(b)2 / 180.2(b)4 for alterations.
Scope of Work
Conditioned Spaces
Unconditioned Spaces
01
02
03
04
05
My Project Consists of (check all that apply):
Calculation Method
Area (ft2)
Calculation Method
Area (ft2)
1 New Lighting System
Area Category Method
5716
N/A
0
• New Lighting System - Parking Garage
N/A
0
N/A
0
Total Area of Work (ft2)
5716
Generated Date/Time:
Documentation Software: Energy Code Ace
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: 201339-0524-0002
Report Generated: 2024-05-24 08:22:00
STATE OF CALIFORNIA
Indoor Lighting
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-LTI-E
Project Name: Y23-154.1 La Quinta Gym
Report Page:
(Page 2 of 7)
Date Prepared:
2024-05-24T11:21:57-04:00
C. COMPLIANCE RESULTS
If any cell on this table says "DOES NOT COMPLY" or "COMPLIES with Exceptional Conditions" refer to Table D. for guidance.
Lighting in
conditioned and
unconditioned
spaces must not be
combined or
f
compliance per
140.6(b)1 /170.2(e)
Allowed Lighting Power per 140.6(b) / 170.2(e (Watts)
>
Adjusted Lighting Power per 140.6(a) / 170.2(e)
(Watts)
Compliance Results
01
02
03
04
_
05
06
07
=
08
09
Complete
Building
140.6(c)1
Area
Category
140.6(c)2 /
170.2(e)4
Area
Category
Additional
140.6(c)2G /
170.2(e)4Av
( +)
Tailored
140.6(c)3 /
170.2(e)4B
(+)
Total
Allowed
(Watts)
Total
Designed
(Watts)*Includes
Adjustments
Total Adjusted
(Watts)
Adjustments
05 must be >= 08
140.6 / 170.2(e)
PAF Lighting
g g
Control Credits
140.6(a)2 /
170.2(e)1B
(-)
(See Table I)
(See Table I)
(See Table J)
(See Table K)
(See Table F)
(See Table P)
Conditioned
2,883.9
=
2,883.9
>_
2,507
=
2507
COMPLIES
Unconditioned
=
>_
=
Controls Compliance (See Table H for Details)
COMPLIES
Rated Power Reduction Compliance (See Table Q for Details)
D. EXCEPTIONAL CONDITIONS
This table is auto filled with uneditable comments because of selections made or data entered in tables throughout the form.
E. ADDITIONAL REMARKS
This table includes remarks made by the permit applicant to the Authority Having Jurisdiction.
Generated Date/Time:
Documentation Software: Energy Code Ace
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: 201339-0524-0002
Report Generated: 2024-05-24 08:22:00
STATE OF CALIFORNIA
Indoor Lighting
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-LTI-E
Project Name: Y23-154.1 La Quinta Gym
Report Page:
(Page 3 of 7)
Date Prepared:
2024-05-24T11:21:57-04:00
F. INDOOR LIGHTING FIXTURE SCHEDULE
This table includes all planned permanent and portable lighting other than dwelling unit/ hotel/ motel room lighting. Multifamily dwelling unit and hotel/motel room lighting is
documented in Table T. If using Table T to document lighting in multifamily common use areas providing shared provisions for living, eating, cooking or sanitation, those luminaires are
not included here.
Designed Wattage: Conditioned Spaces
01
02
03
04
05
06
07
08
09
10
Name or Item
Tag
Complete Luminaire
Description
Modular
(Track) Fixture
Small
Aperture &
Color Changer
Watts per
luminaire2
How is Wattage
determined
Total Number
of Luminaires
Excluded per
140.6(a)3 /
170.2(e)2C
Design Watts
Field Inspector
Pass
Fail
A
8' PENDANT MOUNT LINEAR
No
NA
79
Mfr. Spec
26
No
2,054
■
■
B
6" DOWNLIGHT
No
NA
34
Mfr. Spec
12
No
408
■
■
C
6" DOWNLIGHT
No
NA
15
Mfr. Spec
3
No
45
■
■
Total Designed Watts: CONDITIONED SPACES
2,507
'FOOTNOTE: Design Watts for small aperture and color changing luminaires which qualify per 140.5(a)48 / 170.2(e)2D is adjusted to be 75% /80% of their rated wattage. Table F
automatically makes this adjustment, the permit applicant should enter full rated wattage in column 05.
2Authority Having Jurisdiction may ask for Luminaire cut sheets to confirm wattage used for compliance per 130.0(c) / 160.5(b). Wattage used must be the maximum rated for the
luminaire, not the lamp.
G. MODULAR LIGHTING SYSTEMS
This section does not apply to this project.
H. INDOOR LIGHTING CONTROLS (Not including PAFs)
This table includes lighting controls for conditioned and unconditioned spaces.
Building Level Controls
01
02
03
Mandatory Demand Response 110.12(c)
Shut-off controls 130.1(c) / 160.5(b)4C
Field Inspector
Pass
Fail
NA < 4,000W subject to multilevel
See Area/Space Level Controls
■
■
Generated Date/Time:
Documentation Software: Energy Code Ace
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance
Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: 201339-0524-0002
Report Generated: 2024-05-24 08:22:00
STATE OF CALIFORNIA
Indoor Lighting
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-LTI-E
Project Name: Y23-154.1 La Quinta Gym
Report Page:
(Page 4 of 7)
Date Prepared:
2024-05-24T11:21:57-04:00
H. INDOOR LIGHTING CONTROLS (Not including PAFs)
Area Level Controls
04
05
06
07
08
09
10
11
12
Area Description
Complete Building or Area
Category Primary Function
Area
Manual Area
Controls
130.1(a) /
160.5(b)4A
Multi -Level
Controls
130.1(b) /
160.5(b)4B
Shut Off Controls
130.1(c) //
160.5(b)4C
Primary/Sky
lit
Daylighting
130.1(d) /
160.5(b)4D
Secondary
Daylighting
130.1(d) /
160.5(b)4D
Interlocked
Systems
140.6(a)1/
170.2(e)2A
Field Inspector
Pass
Fail
GYM
Exercise Center Gymnasium
Readily
Accessible
Dimmer
Occupancy Sensor
NA: General
Ltg < 120W
NA: General
Ltg < 120W
No
■
■
RESTROOMS
Restroom
Readily
Accessible
NA: Restrooms
Occupancy Sensor
NA: Not
daylit zone
NA: Not
daylit zone
No
■
■
HALLWAY
Corridor
Readily
Accessible
Dimmer
Occupancy Sensor
NA: Not
daylit zone
NA: Not
daylit zone
No
■
■
13
Plan Sheet Showing Daylit Zones:
I. LIGHTING POWER ALLOWANCE: COMPLETE BUILDING OR AREA CATEGORY METHODS
Each area complying using the Complete Building or Area Category Methods per 140.6(b) are included in this table. Column 06 indicates if additional lighting power allowances per
140.6(c) or adjustments per 140.6(a) are being used .
Conditioned Spaces
01
02
03
04
05
06
Area Description
Complete Building or Area Category Primary
Function Area
Allowed Density
(W/ft2)
Area (ft2)
Allowed Wattage
(Watts)
Additional Allowance / Adjustment
Area Category
PAF
GYM
Exercise Center Gymnasium
0.5
5,430
2,715
No
No
RESTROOMS
Restroom
0.65
218
141.7
No
No
HALLWAY
Corridor
0.4
68
27.2
No
No
TOTALS:
5,716
2,883.9
See Tables J, or P for detail
Generated Date/Time:
Documentation Software: Energy Code Ace
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance
Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: 201339-0524-0002
Report Generated: 2024-05-24 08:22:00
STATE OF CALIFORNIA
Indoor Lighting
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-LTI-E
Project Name: Y23-154.1 La Quinta Gym
Report Page:
(Page 5 of 7)
Date Prepared:
2024-05-24T11:21:57-04:00
J. ADDITIONAL ALLOWANCE: AREA CATEGORY METHOD QUALIFYING LIGHTING SYSTEM
This section does not apply to this project.
K. TAILORED METHOD GENERAL LIGHTING POWER ALLOWANCE
This section does not apply to this project.
L. ADDITIONAL LIGHTING ALLOWANCE: TAILORED WALL DISPLAY
This section does not apply to this project.
M. ADDITIONAL LIGHTING ALLOWANCE: TAILORED FLOOR AND TASK LIGHTING
This section does not apply to this project.
N. ADDITIONAL LIGHTING ALLOWANCE: TAILORED DECORATIVE /SPECIAL EFFECTS
This section does not apply to this project.
O. ADDITIONAL LIGHTING ALLOWANCE: TAILORED VERY VALUABLE MERCHANDISE
This section does not apply to this project.
P. POWER ADJUSTMENT: LIGHTING CONTROL CREDIT (POWER ADJUSTMENT FACTOR (PAF))
This section does not apply to this project.
Q. RATED POWER REDUCTION COMPLIANCE FOR ONE -FOR -ONE ALTERATIONS
This section does not apply to this project.
Generated Date/Time:
Documentation Software: Energy Code Ace
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: 201339-0524-0002
Report Generated: 2024-05-24 08:22:00
STATE OF CALIFORNIA
Indoor Lighting
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-LTI-E
Project Name: Y23-154.1 La Quinta Gym
Report Page:
(Page 6 of 7)
Date Prepared:
2024-05-24T11:21:57-04:00
R. 80% LIGHTING POWER FOR ALL ALTERATIONS - CONTROLS EXCEPTIONS
This section does not apply to this project.
S. DAYLIGHT DESIGN POWER ADJUSTMENT FACTOR (PAF)
This section does not apply to this project.
T. DWELLING UNIT LIGHTING
This section does not apply to this project.
U. DECLARATION OF REQUIRED CERTIFICATES OF INSTALLATION
Selections have been made based on information provided in this document. If any selections have been changed by permit applicant, an explanation should be included in Table E.
Additional Remarks. These documents must be provided to the building inspector during construction and can be found online
Form/Title
NRCI-LTI-E - Must be submitted for all buildings
V. DECLARATION OF REQUIRED CERTIFICATES OF ACCEPTANCE
Selections have been made based on information provided in this document. If any selections have been changed by the permit applicant, an explanation should be included in Table E.
Additional Remarks. These documents must be provided to the building inspector during construction and any with "-A" in the form name must be completed through an Acceptance
Test Technician Certification Provider (ATTCP). For more information visit: http://www.energy.ca.gov/title24/attcp/providers.html
Form/Title
Systems/Spaces To Be Field
Verified
NRCA-LTI-02-A - Must be submitted for occupancy sensors and automatic time switch controls.
GYM; RESTROOMS; HALLWAY
Generated Date/Time:
Documentation Software: Energy Code Ace
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: 201339-0524-0002
Report Generated: 2024-05-24 08:22:00
STATE OF CALIFORNIA
Indoor Lighting
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-LTI-E
Project Name:
Y23-154.1 La Quinta Gym
Report Page:
(Page 7 of 7)
Project Address:
Date Prepared:
2024-05-24T11:21:57-04:00
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Pacific Engineering
Documentation Author Signature:
Company:
Pacific Engineering Group
Signature Date:
2024-05-24
Address: 1106 W. MAGNOLIA BLVD.
CEA/ HERS Certification Identification (if applicable):
City/State/Zip: BURBANK CA 91506
Phone:
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer)
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements
of Title 24, Part 1 and Part 6 of the California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations,
plans and specifications submitted to the enforcement agency for approval with this building permit application.
5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable
inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occu ncy.
Responsible Designer Name: MEL ANTHONY FAJARDO
Responsible Designer Signature: ��
Company: PACIFIC ENGINEERS GROUP
Date Signed: 2024-05-24 /
Address: 1106 W. MAGNOLIA BLVD.
License:
City/State/Zip: BURBANK CA 91506
Phone:
Generated Date/Time:
Documentation Software: Energy Code Ace
CA Building Energy Efficiency Standards - 2022 Nonresidential Compliance Report Version: 2022.0.000
Schema Version: rev 20220101
Compliance ID: 201339-0524-0002
Report Generated: 2024-05-24 08:22:00